PCA - Rural Dell Elementary School 1
Property Condition Assessment
Rural Dell Elementary School Site Address:
10500 So. Hwy 211
Molalla, Oregon 97038
Prepared for:
Molalla River SD
PO Box 188
412 S. Sweigle Ave
Molalla OR 97038
Prepared by:
Hill International Bob Collins
March 21, 2014
PCA - Rural Dell Elementary School 2
Rural Dell Elementary School
10500 So. Hwy 211
Molalla, Oregon 97038
RE: Property Condition Assessment
&
Building Condition Evaluation Form
Dear Facilities Committee,
Hill International has completed a Property Condition Assessment (PCA) and Building
Condition Evaluation Form (BCEF) of the above referenced property. The report was conducted
in accordance with generally accepted industry standards. Hill International certifies that to the
best of its knowledge this report is true and accurate.
The PCA provides narrative information about the facility in all of its aspects while the BCEF
evaluates the same items in a numerical format.
We hope you find the report complete and informative. Please do not hesitate to contact
us if you have any questions or if we can be of further service to you.
Sincerely,
Hill International
Bob Collins
Inspector/ Property Condition Assessment Reviewer
PCA - Rural Dell Elementary School 3
TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY ..............................................................................................
1.1 PROPERTY SUMMARY ......................................................................................................
1.2 PROPERTY DESCRIPTION ..................................................................................................
1.3 GENERAL PHYSICAL CONDITION......................................................................................
1.4 RECOMMENDATIONS & DISCUSSION ................................................................................
2.0 PURPOSE, SCOPE AND LIMITATIONS ....................................................................
2.1 PURPOSE ..........................................................................................................................
2.2 SCOPE OF WORK ..............................................................................................................
2.3 LIMITATIONS ....................................................................................................................
2.4 PROPERTY ACCESS AND NON-ACCESS DISCLOSURE ........................................................
2.5 USER RELIANCE .............................................................................................................
3.0 PROPERTY DESCRIPTION ........................................................................................
3.1 PROPERTY DETAILS .......................................................................................................
3.2 UTILITIES AND SERVICE PROVIDERS ..............................................................................
3.3 NEIGHBORING PROPERTIES ............................................................................................
4.0 CODE COMPLIANCE ..................................................................................................
4.1 MUNICIPAL DEPARTMENTS ............................................................................................
5.0 PROPERTY GROUNDS ................................................................................................
5.1 TOPOGRAPHY AND DRAINAGE .......................................................................................
5.2 PAVING AND CURBING ...................................................................................................
5.3 FLATWORK ....................................................................................................................
5.4 LANDSCAPING AND APPURTENANCES ............................................................................
5.5 AMENITIES AND ANCILLARY STRUCTURES ....................................................................
6.0 FRAME AND ENVELOPE ...........................................................................................
6.1 SUBSTRUCTURE .............................................................................................................
6.2 SUPERSTRUCTURE ..........................................................................................................
6.3 ROOFING ........................................................................................................................
6.4 FACADES ........................................................................................................................
7.0 INTERIOR ELEMENTS ...............................................................................................
7.1 FINISHES ........................................................................................................................
7.2 FIXTURES .......................................................................................................................
7.3 APPLIANCES ...................................................................................................................
PCA - Rural Dell Elementary School 4
8.0 PLUMBING, MECHANICAL & ELECTRICAL .......................................................
8.1 PLUMBING ......................................................................................................................
8.2 HEATING, VENTILATION AND AIR CONDITIONING .........................................................
8.3 ELECTRICAL ..................................................................................................................
9.0 LIFE SAFETY-FIRE PROTECTION/ADA/MOLD ..................................................
9.1 LIFE SAFETY SYSTEMS ...................................................................................................
9.2 ADA ISSUES ..................................................................................................................
9.3 MICROBIAL CONTAMINATION (MOLD) ..........................................................................
10.0 INSTRUCTIONAL INFRASTRUCTURE
10.1 CLASSROOMS……………………………………………………………………………………………
APPENDICES
Appendix 1 - Property Photographs
Appendix 2 – Building Condition Evaluation Form
Appendix 3 – Property Maps & Drawings
Appendix 4 - Municipal/Regulatory Information
Appendix 5 Personnel Qualifications
PCA - Rural Dell Elementary School 5
1.0 Executive Summary
1.1 Property Summary
Property Name: Rural Dell Elementary School
Property Address: 10500 So. Hwy 211 Molalla, Oregon 97038
Property Usage: K-5 Educational
1.2 Property Description
The subject property consists of 3 parcels of land totaling 12.89 acres.
They are identified on the Clackamas County Tax Assessor Records as Parcel I.D.’s:
#01072948 which covers .79 acres
#01072920 which covers 6.54 acres
#01072939 which covers 5.56 acres a
and is listed under the address of: 10500 So. Hwy 211 Molalla, Oregon 97038
It is improved with 2 buildings totaling 26,500 square feet (SF) and one original building
designated historical and built circa 1925. This building is currently in violation of
Fire/Life/Safety codes and is not available for District utilization. This building is 2,918 square
feet (SF). See Appendix #4.
The building, which was constructed originally in 1925 with additions is of wood concrete
foundation with predominately wood structure and brick, wood and metal covering exterior
walls.
The roofing system is comprised of BUR (Built up roofing), 3 tab asphalt shingles, standing
seam metal roof and roof panels.
The foundation appeared to consist of concrete slabs with spread footings for load bearing
walls.
There are no basements or crawl spaces associated with the subject property building except for
the unusable original building.
PCA - Rural Dell Elementary School 6
Property amenities include the following:
Gravel onsite parking, some street parking in frontof the building.
The subject property is serviced by electricity, natural gas, well water and septic sewer system.
1.3 General Physical Condition
General Condition: Fair
Level of Maintenance: Good
1.4 Recommendations & Discussion
There are some ongoing issues with roof leaks and a very poor gutter system that
currently is allowing water to penetrate walls and cause damage. The front office has poor
visibility of visitors to the building increasing risk to student safety particularly considering
proximity to major road. The facility does not provide an ADA compliant handicap bathroom
and there is not an easy solution without moving some walls. The parking lot and sidewalk along
the front of the school should undergo a major design and upgrade.
2.0 Purpose, Scope and Limitations
2.1 Purpose Hill International was retained to conduct a Property Condition Assessment of the
subject property. The purpose of the assessment was to provide an objective, independent,
professional opinion of the current state of the subject property or those portions of the property
identified for consideration by the owner.
2.2 Scope of Work The assessment was conducted in accordance with American Society for Testing and
Materials (ASTM) Standard Guide for Property Condition Assessments: Baseline Property
Condition Assessment Process E 2018-08, Building Condition Evaluation Form as has been
utilized in the State of Washington and generally accepted industry standards.
The specific scope of work included the following:
Document Review and Interviews - Efforts were made to review records or documents, if
readily available, to specifically identify, or assist in the identification of, physical
PCA - Rural Dell Elementary School 7
deficiencies, as well as any preceding or ongoing efforts, or a combination thereof including
building certificates of occupancy, outstanding and recorded material building code violations,
and recorded material fire code violations. Only such record information that is reasonably
ascertainable from standard sources was reviewed. Any information not practically reviewable or
not provided to Hill International in a reasonable time to formulate an opinion and
complete the PCA, will be stated in the PCA, and Hill International will have no
further obligation of retrieving such documentation or reviewing it if it is subsequently
provided.
It is understood that information will be provided to Hill International
within ten business days of the source receiving appropriate inquiry, without an in-person
request being required, and at no more than a nominal cost to cover the source’s cost of
retrieving and duplicating the information. The inspection does not include a regulatory or
code compliance audit of the facility.
Hill International provided the owner or owner’s representative, or both, with a
pre-survey questionnaire. In addition, if readily available, Hill International
requested the following documents and information that may be in the possession of or
provided by the owner, owner’s representative, user, or combination thereof, as appropriate and
reviewed each of those made available:
1. Real Property Appraisal,
2. safety inspection records,
3. warranty information (roofs, boilers, chillers, cooling towers, etc.),
4. records indicating the age of material building systems such as roofing, paving,
plumbing, heating, air conditioning, electrical, etc.,
5. historical costs incurred for repairs, improvements, recurring replacements, etc.,
6. descriptions of future work planned,
7. outstanding citations for building,
8. fire and zoning code violations,
9. any ADA survey
10. status of any improvements implemented to effect physical compliance,
11. previously prepared property condition reports or studies pertaining to any aspect of
the subject property’s physical condition,
12. marketing/promotional literature such as photographs, descriptive information,
reduced floor plans, etc.,
13. drawings and specifications (as-built or construction). Very few historical documents
are available.
14. AHERA Survey
Hill International requested that the owner or user identify a person or persons
knowledgeable of the physical characteristics, maintenance, and repair of the property as a
primary point of contact (POC).
Hill International interviewed the POC, property manager or agent of the owner to
PCA - Rural Dell Elementary School 8
inquire about the subject property’s historical repairs and replacements and their costs, level
of preventive maintenance exercised, pending repairs and improvements, frequency of
repairs and replacements, and existence of ongoing or pending litigation related to subject
property’s physical condition.
Walk-Through Survey - The report is based on observations made during the property
“walk-through.” Observations were limited to “representative” property improvements
including exterior surfaces and open spaces, accessible areas of the roof, representative units,
and mechanical, staff, vacant and common areas. Limited or no inspection or investigation
behind walls, inside plenums or in any other generally inaccessible areas was performed. The
investigation of the building facade was performed from street and/or balcony level. The
riding of scaffolding equipment was not part of the scope of Hill International’s
services. No physical tests were made nor were any samples for engineering analysis
collected. As such, Hill International makes no warranties regarding EIFS
systems, curtain walls or other building skin conditions that would not be readily observable
and would, therefore, be considered outside the scope of this assignment. Reliance was
placed on the accuracy and disclosure of property representatives.
A visual survey for mold was conducted. The survey was limited to visual observations in
the areas walked and should not be considered a comprehensive survey of the property. No
sampling was conducted. No inspection or investigation behind walls or in any other
generally inaccessible areas was performed. A conclusion that no mold was observed,
therefore, should not be taken as the property is mold free or concerns do not exist in areas
that were not inspected. Any indication(s) of mold observed during the Property Condition
Assessment will be documented and reported in the Property Condition Report.
The observed condition of building structures and components evaluated were broken down into
one of the following descriptions:
1) Poor - Requiring action immediately or within 12 months;
2) Fair - Serviceable, but showing age and wear, and will require maintenance, repair or
replacement during short term – 3- 5 years;
2) Good - No major signs of age or wear, may need replacement during the medium
term;
4) Excellent - New or like new.
Systems to be Observed:
Property/Site Features - Observations were conducted at the property as to the type,
condition and adequacy of the following items: general topography, storm water drainage,
PCA - Rural Dell Elementary School 9
ingress and egress, paving, curbing and parking, flatwork, landscaping and appurtenances,
recreational facilities, amenities and ancillary structures, and utilities.
Building Frame and Envelope - Observations were conducted at the property as to the type,
condition and adequacy of the following items: substructure, superstructure, facade, and
roofing.
Interior Elements - Observations were conducted at the property as to the type, condition and
adequacy of the following items: interior finishes, fixtures, appliances, and furnishings.
Plumbing, Mechanical and Electrical - Observations were conducted at the property as to the
type, condition and adequacy of the following items: plumbing, heating, ventilation and air
conditioning, electrical, and elevators/escalators.
Life Safety/Fire Protection and ADA Requirements - Observations were conducted at the
property as to the type, condition and adequacy of the life safety and fire protection systems.
Visual Accessibility ADA Survey. The survey included a limited visual assessment of the
subject property to assess if it is accessible and useable by individuals with disabilities in
accordance with the ADA of 1990, Title III, Public Accommodations and Commercial Facilities.
The provisions of Title III provide that persons with disabilities should have accommodations
and access to public accommodation and commercial facilities, which are equal to, or similar to,
those available to the general public.
Public accommodations and commercial facilities constructed or renovated after January 1992
must be brought into compliance with ADA guidelines. Public accommodations constructed
prior to January 1992 must make affirmative attempts to be in compliance. This screening is not
to be considered an in-depth ADA survey or audit. The opinions regarding ADA compliance
should be considered preliminary. The purpose of the limited visual survey is to provide a
general observation of the level of attention paid to keeping the property ADA compliant.
Instructional Adequacy An assessment was made of the characteristics and condition of
instructional facilities including all classrooms, athletics, drama, science, art, storage,
instructional technology and related infrastructure.
Photographs representative of Hill International’s observations are included
in Appendix 1 – Property Photographs. In addition to visual observations, letters to and
responses from municipal and regulatory agencies are included in Appendix 4. Hill International
relied on the sources and contacted the individuals listed within the
report and the appendices.
PCA - Rural Dell Elementary School 10
2.3 Limitations
Hill International has performed the services and prepared this report in
accordance with generally accepted consulting practices, and makes no other warranties, either
expressed or implied, as to the character and nature of such services or product.
Hill International, its officers, and its employees have no present or contemplated
interest in the property. Our employment and compensation for preparing this report are not
contingent upon our observations or conclusions.
Information in this report, concerning equipment operation, condition of spaces and concealed
areas not observed or viewable and for the disclosure of known problems, if any, is from
sources deemed to be reliable, including, but not limited to property managers and
maintenance personnel; however, no representation or warranty is made as to the accuracy
thereof.
No PCA can wholly eliminate the uncertainty regarding the presence of physical deficiencies
and the performance of a subject property’s building systems. Preparation of a PCA in
is intended to reduce, but not eliminate, the uncertainty regarding the potential for component or
system failure and to reduce the potential that such component or system may not be initially
observed. The inherent subjective nature of a consultant’s opinions as to such issues as
workmanship, quality of original installation, and estimating the Remaining Useful Life (RUL)
of any given component or system are not exhaustive and are predictive only. Users of this
Property Condition Assessment recognize that a consultant’s suggested remedy may be
determined under time constraints, formed without the aid of engineering calculations, testing,
exploratory probing, the removal of materials, or design. Furthermore, there may be other
alternate or more appropriate schemes or methods to remedy the physical deficiency.
2.4 Property Access and Non-Access Disclosure
Inspector: Bob Collins
Date of Inspection: March 5, 2014
Weather Conditions: Rainy, 35 degrees
Property Contact: Lauree Nelzen
Property Questionnaire Sent to: Tony Tiano, Lauree Nelzen and Ric Dettwyler.
Questionnaire Results and applicable information are included in the appropriate sections of the
report.
PCA - Rural Dell Elementary School 11
Areas Accessed: Every location and room in the building.
Inaccessible Areas: None
2.5 User Reliance
In consideration of the facts recited in this report, Hill International hereby agrees that Molalla
River School District may rely on the Property Condition Assessment prepared by Hill
International for the purposes intended and agreed upon subject to the limitation herein.
3.0 Property Description
3.1 Property Details
Property Size: 12.89 acres.
Source: Clackamas County Tax Assessor Records
Property Usage: Educational
Number of Buildings: 3
Dates of Construction: The buildings were constructed or renovated per the following:
Historical designated rear white building – circa 1925
Source: Molalla River School District Files
Building Size(s): Two functional buildings – 26,500 square feet
One condemned building – 2,918 square feet
Source: Molalla River School District Files
3.2 Utilities and Service Providers
Electricity: PGE
Gas: NW Natl. Gas
PCA - Rural Dell Elementary School 12
Potable Water: On site Wells
Sanitary Service: Septic System
Storm Water: Dry Wells
Solid Waste: Molalla Sanitary
HVAC Maintenance: District provided/Van Air
Pest Control: District provided
Landscaping: District provided
Fire Extinguishers/Alarm: Western States Fire Protection
Security: NO system on the premises
Roof Maintenance: District provided/Garland Co.
Electrical Maintenance: District provided/Full House Electric
Plumbing Maintenance: District provided
4.0 Code Compliance
4.1 Municipal Departments
Fire Department:
Pertinent Information: Hill International requested information pertaining to any
outstanding fire code violations for the subject property. Hill International
received a phone response from Fire Marshall Mike Penunuri on Janruary 31, 2014. He indicated
that issues found in the July 2012 inspection have all been resolved as of the time of the writing
of this report.
Building Department:
Pertinent Information: Hill International requested information pertaining to Certificates of
Occupancy and any outstanding code violations for the subject property from Clackamas County
Building Department.
PCA - Rural Dell Elementary School 13
Hill International received a response and as of the writing of this report there are no outstanding
violations and no incomplete permits.
Planning and Zoning Authority:
Hill International requested information regarding the current zoning of the property and whether
the property is a legal conforming use or a legal non-conforming use according to density,
parking, and today's codes. Hill International received a response and as of the writing of this
report there are no issues.
5.0 Property Grounds
5.1 Topography and Drainage
Topographic Survey Available: No
Topography: The subject property is located at approximately 265 feet above mean sea level.
The source of elevation and topo data is Clackamas County GIS.
Property Drainage: Runoff from the buildings’ roofs drains and/or interior roof drains that tie-in
underground drain into the storm water collection system which consists of drywells.
Remaining storm water does not have a place to be collected as there are no catch basins on the
grounds or parking lot.
Surface Water Bodies: There are no natural surface water bodies on the subject property.
Flood Plain Designation: The property is not likely in a flood zone.
The Source of Flood Plain data is Clackamas County GIS system.
Seismic Zone: The property is located in Zone 3.
The source of Seismic Zone Data is DOGAMI – GMS 100 – UBC seismic zone factors
General Condition of Topography and Drainage: Poor
PCA - Rural Dell Elementary School 14
Signs of Ponding: There is ponding in parking lots and along Dryland Road adjacent to school
building and in the playground area. See Figure #1&2
Indications of Wetlands: NO wetlands apparent
Recommendations: Have civil design evaluation performed for solutions.
5.2 Paving and Curbing
Parking Areas: The parking area on the north side of the school and along Dryland Road is
gravel based. See Figure #3
Curbs: The curbs in the front of the school are deteriorating but functional.
Number of parking spaces: There are no striped parking stalls. The approximate capacity north
of the buildings and along Dryland Road is 70 vehicles.
General Condition: Poor
Inadequate number of spaces: During school events there is not enough safe parking options.
Recommendations: Have civil design evaluation performed for solutions.
5.3 Flatwork
Sidewalks: The sidewalks along the front of the building are in poor condition See Figure #4
and there are signs of settlement above septic tank and drain line in areas between two buildings.
General Condition: Poor
Trip Hazards: The sidewalk in the front of the school poses some risks that should be
addressed.
5.4 Landscaping and Appurtenances
Landscaping: Shrubs and trees appear to be performing well.
Irrigation sprinkler systems: There is no sprinkler system.
Property Lighting: There is insufficient lighting around some of the perimeter of the building.
Fencing/Walls: Additional fencing would provide greater student safety.
PCA - Rural Dell Elementary School 15
Property Signage: Adequatly placed and functional
Inadequate/broken property lighting: There is no lighting provided in the parking lot.
General Condition: Fair
5.5 Amenities and Ancillary Structures
Main Office: The main office is small but functional. The location is far from any entrance to
the school which provides poor security for unwanted visitors.
Boiler Rooms or Plants:
Water Treatment: New water treatment system installed in pump well house. District
monitoring performance. Well house is missing siding to protect the building. See Figure #5
Courts/Playgrounds and Other Amenities: The playground and covered play area service the
school well. There are drainage issues at times of larger rain events.
Softball Fields: There is one small backstop for use. The field is not particularly developed.
Track surface: There is a rudimentary gravel track around the play field.
Auditorium:
Lighting: There is minimal lighting with little control function. See Figure #6.
Audio: There is a very basic two speaker system.
Storage: There is some storage that is poorly utilized at this time. See Figure #7.
Concerns: The stage curtains do not appear to be fire rated for public assembly area.
Gymnasium(s)
Locker and Shower Rooms: Existing rooms are currently being used for PE storage.
Storage Buildings: The old bus barn is used for storage at this time. There are some issues with
rusted metal siding panels and failing gutter system.
PCA - Rural Dell Elementary School 16
The oldest classroom building is now currently being used only for storage as mandated by the
Molalla and State Fire Marshalls. Excerpt of reports in Appendix #4. There was no further study
done of this building.
General Condition: Fair
6.0 Frame and Envelope
6.1 Substructure
Foundation: No issues noted on property buildings.
General Condition: Good
Flooding/water damage: The current gutter issues that are allowing significant water to pond at
foundation perimeter are a cause for concern.
6.2 Superstructure
Framing System: Wood frame walls and steel posts with 2 x 6 ceiling joists and rafters in main
buildings.
Roof Framing and Decking: NO issues noted
General Condition: Good
6.3 Roofing
Type: There is asphalt shingles and BUR (Built up Roofing) on the main buildings. There is
standing seam metal roofing on the breezeway (see Figure #8), covered play structure and
maintenance building.
Parapets and Coping: Some issues exist that should be addressed. See Figure #9.
Roof penetrations: No issues noted.
General Condition: Fair
Concerns: Failing B.U.R. See Figure #10.
PCA - Rural Dell Elementary School 17
Leaks: There have been leaks in the shingle roof valleys which have been treated with an
emulsion. There are leaks in various locations around the school.
Evidence of repairs: See Figure #11 .
Damaged gutters: There are many issues with gutter nonperformance that must be addressed to
avoid compromising building integrity. See Figures #12-15.
6.4 Facades
Exterior Walls: The majority of the solid exterior wall surface on the two operating buildings
are nonstructural brick.
Fascia, Soffits and Trim: The wooden soffits and fascia are in fair condition but in need of
paint.
Entrances and Doors: Exterior doors are generally in good condition except for the two original
front doors which offer poor security, thermal protection. See Figure #16.
Windows: The window system consists of large areas of glass block over single pane fixed
wood window units. They are in fair condition. See Figure #17
Exterior Wall Damage: See Figure #18.
Inadequate insulation: The current insulation in all parts of the building are far below current
building code standards. No documents exist to determine actual R value in the building nor is
there good access to ascertain.
Vapor/moisture penetration: The only major issue noted was the concern with the failing
gutter system which might be creating issues not fully identified.
General Condition: Fair
7.0 Interior Elements
7.1 Finishes
Walls: The surfaces are generally in fair condition.
Ceilings: Many different types of ceiling tiles with current and past water damage present in
many area.
PCA - Rural Dell Elementary School 18
Flooring: The carpet and older VAT tile should be replaced. The hallway tile is in better
condition.
General Condition: Fair
7.2 Fixtures
Lighting by room, area or building as appropriate: Good
Bathroom Fixtures: The majority of the bathroom fixtures is original and has outlived their
usefulness. They should be replaced.
Kitchen Fixtures: Good
7.3 Appliances
Ranges/Cooktops/Ovens: Ovens are old.
Refrigerators: Older Walk-In.
Freezer: Chest style-good. Poses issues for potential back injuries.
Dishwashers: 1963 model
8.0 Plumbing, Mechanical & Electrical
8.1 Plumbing
Domestic Water Supply Piping: Poor condition
Fire Water Supply Piping: N/A
Gas Supply Piping: N/A
Vaults: N/A
Check valves: Recently inspected - Good
Drainage/Wastewater Piping: Poor
PCA - Rural Dell Elementary School 19
Hot Water Production: Good
Wells: Good
Septic or Wastewater Treatment Systems: Poor
Ejector Pumps/Lift Stations: N/A
Fire Pumps: N/A
Grease Traps: N/A
General Condition: Old underground pipes, all fixtures are old.
Reported or Observed Sewage backup: General drainage issues
8.2 Heating, Ventilation and Air Conditioning
Heating and Cooling Systems: Heat Pumps
General Condition: Good
Boiler(s): N/A
Chiller(s): N/A
Roof Top Units: N/A
Air Handlers: Good
Mechanical Rooms: N/A
HVAC Controls: Thermostats are good
Recommendations: Install automatic controls with Clima-Tech.
8.3 Electrical
Level of Service: Adequate
Type of wiring: Possible use of some aluminum wiring.
PCA - Rural Dell Elementary School 20
Overload Protection: Good
Emergency Generator: None on property
Aluminum wiring: Possible
GFCI: Good
General Condition: Good
9.0 Life Safety-Fire Protection/ADA/Mold
9.1 Life Safety Systems
Smoke Detectors: The building is properly protected.
Sprinkler System: There is no system in place.
Fire Extinguishers: There appear to be a proper amount of units and they have been maintained
and inspected. There are two units that are mounted higher than the code requires.
Cooking Stove Hoods (halon): N/A
Restricted Access Gates: A Schlage keyless entry system with card reader and electric lock is
provided at selected building entries.
Security Cameras/Guard: Interior cameras installed only.
Alarm Systems: There is an entry security system in place.
Fire Inspection/Safety Reports: Refer to Appendix #4
Fire Hydrants – Locations: None noted near the property.
9.2 ADA Issues
All places of public accommodation and commercial facilities constructed for first occupancy
after January 26, 1993 must be constructed to be accessible. Any alteration made to a place of
public accommodation or commercial facility after January 26, 1992, must be made so as to
PCA - Rural Dell Elementary School 21
ensure that, to the maximum extent feasible, the altered portions of the facility are readily
accessible to and useable by individuals with disabilities. Alterations include, but are not
limited to, remodeling, renovations, rehabilitation, reconstruction, historic restoration, changes
or rearrangement in the plan configuration of walls and full-height partitions. Normal
maintenance, reroofing, painting or wallpapering, asbestos removal, or changes to mechanical
and electrical systems are not alterations unless they affect the usability of the building or
facility.
A public accommodation is required to remove architectural barriers in existing facilities,
prior to the making of any alterations, where such removal is readily achievable, i.e., easily
accomplished and able to be carried out without much difficulty or expense. Examples
include, but are not limited to, providing designated handicapped parking spaces, adding small
ramps and curb cuts, widening doorways, rearranging furniture, adding raised markings on
elevators, installing grab bars in toilet stalls and rearranging toilet partitions to increase
maneuvering space. If not readily achievable, alternative methods of providing service, such
as access to the management office, must be offered. Alternative methods include, but are not
limited to, installing an intercom system between the leasing office and an accessible area, or
relocating activities to accessible locations. It is the property owner’s burden to prove that a
modification is not readily achievable, or would pose an undue financial or administrative
burden.
The scope of this limited visual survey is specifically limited to the following five areas: path of-
travel, parking, public toilet restrooms, and elevators. The opinions regarding ADA compliance
should be considered preliminary. The purpose of the limited visual survey is to provide a
general observation of the level of attention paid to keeping the property ADA compliant.
Parking Spaces: There are two marked handicap spaces on the south side of the building.
Accessibility/Path of Travel: There are no apparent issues.
Public Restrooms: There are no ADA compliant restrooms in this facility.
Signage: There are some minor issues noted per ADA guidelines.
General Condition: Poor
Recommendations: Hire an ADA specialist architect to solve the issue.
9.3 Microbial Contamination (Mold)
A visual/olfactory survey for mold was conducted. The survey was limited to observations in
the areas walked and should not be considered a comprehensive survey of the property. No
sampling was conducted. No inspection or investigation behind walls or in any other
PCA - Rural Dell Elementary School 22
generally inaccessible areas was performed. In addition, inquiries were made of the owner
and/or manager of the Property regarding past and current leaks or any known mold issues,
any tenant complaints regarding health problems, musty odors or water leaks. In addition,
when applicable, areas of reported or likely significant leaks or water intrusion/penetration
were inspected.
Observations: No mold noted in site walk.
10.0 Instructional Infrastructure
10.1 Classrooms
Dimensions: The typical classroom is 42’ x 24’ and 28’ x 34’.
Sq. Ft.: The typical classroom is 1008 and 952 square feet respectively.
Lighting Controls: There are no occupancy sensors noted in each classroom.
Marker Boards: There appears to one supplied in each classroom.
Tack Surface: There are sufficient amount of tack surface in each classroom.
Digital Projector: Some rooms are outfitted with a unit.
Digital Marker Boards: Some rooms are outfitted with a unit.
Bookshelves: There appear to be adequate units for the typical classroom.
Storage: There is inadequate space in most classrooms.
File cabinets: Generally, there were none supplied.
Secure storage: There was none noted in the classrooms
Teacher Wardrobe: It appeared classrooms were supplied with these but all noted were
used for additional storage.
Sink/Water: Typically, each classroom has a drinking fountain mounted with a sink
basin.
Recommendations: 1. Add more smart boards and projectors in classrooms.
2. Add security video at entry.
PCA - Rural Dell Elementary School 23
APPENDIX 1
PROPERTY PHOTOGRAPHS
APPENDIX 2
BUILDING CONDITION EVALUATION FORM
APPENDIX 3
PROPERTY MAPS AND DRAWINGS
APPENDIX 4
MUNICIPAL/REGULATORY INFORMATION
APPENDIX 5
PERSONNEL QUALIFICATIONS
PCA - Rural Dell Elementary School 24
APPENDIX 1
PROPERTY PHOTOGRAPHS
Figure 1
Figure 2
PCA - Rural Dell Elementary School 25
Figure 3
Figure 4
PCA - Rural Dell Elementary School 26
Figure 5
Figure 6
PCA - Rural Dell Elementary School 27
Figure 7
Figure 8
PCA - Rural Dell Elementary School 28
Figure 9
PCA - Rural Dell Elementary School 29
Figure 10
Figure 11
PCA - Rural Dell Elementary School 30
Figure 12
Figure 13
PCA - Rural Dell Elementary School 31
Figure 14
Figure 15
PCA - Rural Dell Elementary School 32
Figure 16
Figure 17
PCA - Rural Dell Elementary School 33
Figure 18
Building Condition
Evaluation Manual
Using the State of Washington
Office of the Superintendent of Public Instruction
School Facilities Evaluation Methodology
Appendix 2
Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Mol
alla
Riv
er S
D
Rur
al D
ell E
S
MRSD - Rural Dell Elementary School
16
12
17
12
57
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River SD Rural Dell ES March 12, 2014 Bob Collins
Clackamas County Molalla River SD Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
15 x x
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
MRSD - Rural Dell Elementary School
*
MRSD - Rural Dell Elementary School
21 x51 x x
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
30 x x12 x
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
MRSD - Rural Dell Elementary School
x
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
*
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
1812 24
**
MRSD - Rural Dell Elementary School
* x
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
6 *
MRSD - Rural Dell Elementary School
12 * x
MRSD - Rural Dell Elementary School
Clackamas Molalla River Rural Dell ES March 21, 2014 Rick Detwyler, Tony Tiano, Lauree Nelzen
*
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
MRSD - Rural Dell Elementary School
24 12
**
**
MRSD - Rural Dell Elementary School
6
MRSD - Rural Dell Elementary School
MRSD - Rural Dell Elementary School
Clackamas County Molalla River Rural Dell Bob Collins
APPENDIX 3
PROPERTY MAPS AND DRAWINGS
APPENDIX 4
MUNICIPAL/REGULATORY INFORMATION
APPENDIX 5
PERSONNEL QUALIFICATIONS
Bob Collins has worked in the construction industry for 30 years as a craftsman , supervisor and
Project Manager in many disciplines.. He is a certified Professional Project Manager PMP and
certified Construction Manager CCM with many years building, supervising and managing
educational construction projects.
Stephen Smith is a mechanical engineer with more than 20 years of experience Heh graduated
from Auburn University with a bachelor's degree in mechanical engineering, and he is a
registered Professional Engineer in Oregon, Washington, Montana, and Tennessee. He also has
an MBA from the University of Montana. Stephen is a member of the Big Sky Chapter of
ASHRAE and the Montana Society of Healthcare Engineers, and he is also a LEED Accredited
Professional.
For the past 30 years Jim Krumsick has provided electrical engineering services to the Oregon
community. Between 1984 and 2005 Jim worked as Electrical Department manager and a
principal in the firm of Balzhiser and Hubbard Engineers. In 2005 Jim formally retired but has
continued working for long term clients, including Balzhiser and Hubbard Engineers, through his
firm, Paradigm Engineering.