78
Prepared For: John Benz Property Address: 6948 Gibson Canyon Rd, Vacaville, CA 95688 Inspector: Jason Desmarais Company: Tanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374 [email protected] Services Included in this Report: Extended Full Home & Pool Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JD Tanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374 WINspect v2.2.902 © 2020 WIN Home Inspection Page 1 of 78

Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Prepared For: John Benz

Property

Address:6948 Gibson Canyon Rd, Vacaville, CA 95688

Inspector: Jason Desmarais

Company: Tanryn Business Group, INC

dba WIN Home Inspection Sierra

(916) 256-4374

[email protected]

Services Included in this Report:

Extended Full Home & Pool

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 1 of 78

Page 2: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Table of Contents

Explanation of Terms / Not a Warranty ................................................................................. 3

Extended Full Home & Pool Inspection Cover ...................................................................... 4

Summary Divider .................................................................................................................. 6

Extended Full Home & Pool Summary ................................................................................. 7

Full Report Divider .............................................................................................................. 31

Roof .................................................................................................................................... 32

Structure Perimeter Exterior ............................................................................................... 35

Exterior Structure ................................................................................................................ 38

Site Concrete and Paving ................................................................................................... 41

Patios/Decking/Porches ...................................................................................................... 41

Utility Services .................................................................................................................... 42

Electrical Service ................................................................................................................ 44

Water Heater ...................................................................................................................... 48

Laundry Area ...................................................................................................................... 49

Main Entry Door .................................................................................................................. 50

Other Ext. Entry Doors ........................................................................................................ 51

Kitchen(s) ............................................................................................................................ 52

Fire Place/Wood Stove ....................................................................................................... 54

Other Room(s) .................................................................................................................... 55

Bathroom(s)/Washroom(s) ................................................................................................. 60

Plumbing ............................................................................................................................. 63

Structure ............................................................................................................................. 66

Heating System .................................................................................................................. 69

Air Conditioning .................................................................................................................. 71

Attic ..................................................................................................................................... 73

Slab Foundation .................................................................................................................. 75

Detached Garage ............................................................................................................... 76

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 2 of 78

Page 3: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

NOT A WARRANTY

THE SERVICES PERFORMED, THE AGREEMENT, AND THE REPORT DO NOT CONSTITUTE A WARRANTY, AN INSURANCE POLICY, OR A

GUARANTEE OF ANY KIND, NOR DO THEY SUBSTITUTE FOR ANY DISCLOSURE STATEMENT AS MAY BE REQUIRED BY LAW.

There are no warranties made against roof leaks, wet basements, or mechanical breakdowns The report is NOT a listing of repairs that need to be

made. Therefore, you agree NOT to hold us responsible for future failure and repair, or for the non-discovery of any patent or latent defects in

material, workmanship, or other conditions of the property which may occur or become evident after the date the services were performed; nor for

any alleged non-disclosure of condition that are the express responsibility of the seller of the property. You agree to assume all the risk for

conditions which are concealed from view or inaccessible to us at the time that the services were performed.

THIS REPORT IS INTENDED ONLY FOR THE USE OF THE PERSON PURCHASING THE HOME INSPECTION SERVICES. NO OTHER

PERSON, INCLUDING A PURCHASER OF THE INSPECTED PROPERTY WHO DID NOT PURCHASE THE HOME INSPECTION SERVICES,

MAY RELY UPON ANY REPRESENTATION MADE IN THE REPORT.

THIS REPORT IS FOR THE EXCLUSIVE USE OF OUR CLIENT AS NAMED IN THE INSPECTION AGREEMENT. It may not be used or relied

upon by any other person unless that person is specifically named by us in the Inspection Agreement as a recipient of this report. Distribution of this

report to any third party without the written consent of the inspector and WIN Home Inspection is prohibited. As the client, you agree to maintain the

confidentiality of this report and to reasonably protect the report from distribution to any third party. You agree to indemnify, defend and hold us

harmless if any third party brings a claim against us relating to the inspection or to this report.

EXPLANATION OF TERMS

This report was prepared and written with the age and type of structure taken into consideration. Below is an explanation of the terms used in the

report

FUNCTIONAL: Items marked Functional appear to be in serviceable condition using normal operating controls. There were no visible indication of

failure at the time the services were performed.

SATISFACTORY: Items marked Satisfactory appear to be in serviceable condition using normal operating controls. There were no visible

indications of failure at the time the services were performed. Items that need minor service that do not significantly affect an item's use may be

classified as satisfactory.

ATTENTION: Items marked Attention appear to be in need of preventive maintenance or service. Attention may also indicate an item that the

inspector would recommend gaining further information from a third party immediately in order to provide additional clarification and/or insight into

the item's condition.

MAINTENANCE: Items marked Maintenance are in need of repair or replacement in order to make the item functional and/or prevent further

deterioration.

ACTION REQUIRED: Items marked Action Required appear to be in need of immediate repair or replacement. Delay in repair or replacement may

result in a dramatic shortening of the life expectancy of the item, have immediate effect on the item, system, structure, other related items, or

present a potential health and/or safety hazard.

PRESENT: Items marked Present were visible at the time the services were performed and were not tested or inspected due to either the type of

device or access limitations.

NOT INSPECTED: Items marked Not Inspected may be present at the time the services were performed and were not inspected due to obstruction,

weather condition or the inspection of the item is not within the scope of the services performed.

N/A: Items marked N/A are not included in the report. The item may not be present, not included, not accessible, not available, not addressed, not

applicable, not appropriate, and/or not examined.

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 3 of 78

Page 4: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

WIN Home InspectionExtended Full Home & Pool

This report contains confidential information and is supplied solely for use by the client(s) of:

Tanryn Business Group, INC dba WIN Home Inspection Sierra

2351 Sunset Blvd, Rocklin, California 95765

(916) 256-4374 https://sierra.wini.com

Work Order Number: 040220JD Service Date: 4/2/2020 Time: 12:00 PM

Site Address:

6948 Gibson Canyon Rd, Vacaville, CA 95688

For the purpose of this inspection, the Main Entry Door faces: See MLS

Site Information:

Weather: 65 °F - Partly Cloudy

Approximate Year Built: 1972

Structure: Single Family

Foundation: Concrete Slab

Bedrooms: 3

Bathrooms: 2.5

Floors: 2

Occupied: Yes

Client:

Name: John Benz

Address:

Work Phone:

Home Phone:

Mobile Phone:

Email Address: [email protected]

Client Present at Inspection: Yes

Buyer's Agent:

Name:

Company:

Address:

,

Phone:

Email:

Buyer's Agent Present at Inspection: No

Seller's Agent:

Name:

Company:

Address:

,

Phone:

Email:

Seller's Agent Present at Inspection: No

Inspector: Jason Desmarais

License / Certification:

Email: [email protected]

Tanryn Business Group, INCdba WIN Home Inspection Sierra

Notes:

This is an inspection of the home as built. This is not a compliance inspection, installation inspection, or certification ofcompliance with current or past governmental codes or regulations of any kind. It is not determined as part of thisinspection, weather or not any permits were obtained or required during original construction, or during any updatedconstruction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of theinspector in the use of good building practices. In as much as we strive to collect, detail and describe the conditions

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 4 of 78

Page 5: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

present in this home in accordance with our SOP, conditions change, stored items are moved, systems fail after use. Ourservice as defined in the Inspection Contract which you have signed is not a guarantee or warranty for any portion of thishome. It is very important that you read the entire report thoroughly, review our contract and scope of work, andunderstand that there are limitations to any home inspection. Our inspectors are highly qualified, trained and experienced.They act with equal diligence and care for each and every client. However, we only act in the role of a consultant and thefinal purchase decision is yours. You will have an opportunity to walk through this home prior to signing your escrowclosing and purchase documents. It is incumbent on you "the buyer" to decide if the condition of the property issatisfactory to you. If conditions have changed from the time our inspection was concluded, the time to address thesechanges is prior to signing any closing documents. If you have any questions, or feel you do not have the information thatyou need concerning the condition of this home, or the function of its systems as it falls within our scope of work, pleasecall us anytime prior to closing. Items like out buildings, barns, sheds, parking/garage structures, pools/spas and otherstructures are outside the scope of this inspection and were not inspected unless otherwise specifically mentioned in thisreport. This inspection does NOT look for or report on ANY past/current recalls or class action law suits regarding to anybuilding materials or equipment that may be present in the home unless otherwise noted.

Please noted in light of current issues on mold and fungi contaminations in structure and buildings, any comment is thisreport that indicates evidence of water damage, staining, intrusion, or plumbing leaks should be considered as possibleareas of mold growth whether identified at the time or not. Mold identification and testing is not included in this inspectionscope or process.

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 5 of 78

Page 6: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

SUMMARY

SECTION

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 6 of 78

Page 7: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

We have identified various items on the subject structure that either require maintenance now or require periodicmaintenance in the normal course of ownership. This is only a summary report and is intended as a guide to be used inboth short and long term scheduling of maintenance items. Please read the complete report carefully as additionalinformation and details are contained therein. It is always advisable to use experienced tradespeople or a qualifiedhandyperson when contracting for work that may not be within the scope of your capabilities.

1. Roof - Debris on Roof

Attention - Debris NotedThere is a large amount of debris build up on the roof. There were tree branches overhanging or in contact withthe roof. Leaves, branches, and/or other material that should be removed at some time in the near future. Thedebris can clog gutters, down spouts and/or drains. Debris can hold moisture that can cause damage to the roofsystem if large accumulations develop. Debris should be cleaned off the roof surface on an annual basis as aproper care and maintenance recommendation. Recommend further evaluation and repair by a licensed roofingcontractor.

Roof valleys are a common place for debris build up which can result in roof leaks. Regular inspections for debrisbuild up in the valley areas is recommend.

2. Roof - Valleys

AttentionDebris build up was noted at one or more of the roof valleys, dead valleys, or crickets. Recommend furtherevaluation and repair by a licensed roofing contractor.

3. Roof - Vents/Chimneys/Covers

AttentionThere are one or more cracks in the upper mortar crown of the utility chimney. The cracks may allow rain water toleak down the interior of the chimney and can expedite the deterioration of the bricks and mortar over the years.Consideration should be given to repairing the mortar cap to prevent further deterioration to the chimney system.Recommend further evaluation by a qualified fireplace specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 7 of 78

Page 8: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

4. Roof - Gutters/Down Spouts

AttentionThere are one or more downspouts that are rusty. As an example, the downspout located at the right side of thehome. Recommend further evaluation of the gutter system and repair by a qualified specialist.

5. Roof - Separate Certification Required

Yes - Due to Unknown Remaining LifeThe inspector was unable to determine the number of years of serviceable life left in the roof. Contacting aqualified roofing expert to evaluate the existing condition of the roofing in order to provide an approximate numberof years of serviceable life left is recommended.

This roof inspection should be considered a general inspection of the roof system for obvious faults and defects.

The inspector is not a roofer and this inspection is a non-exhaustive inspection of the roof. The inspector

recommends that interested parties have qualified licensed roofing company do an exhaustive evaluation of the

roof to determine the serviceable life expectancy and obtain a certification.

6. Structure Perimeter Exterior - Vent Screens

AttentionThere are one or more exterior attic vent screens that are damaged and have holes. As an example, the screenlocated at the front of the home. Recommend further evaluation of exterior vents screens and repair by a qualifiedhandyman in order to prevent unwanted pest entrance.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 8 of 78

Page 9: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

7. Structure Perimeter Exterior - Proper Earth-Wood Clearance

NoThe inspection has revealed earth to wood contact around the left side of the structure. There should be nocontact between the earth and the exterior wood to prevent wood deterioration and a conducive condition for pestinfestation. Recommend providing at least four to six inches of clearance between the earth and wood sidingmaterial as a preventive maintenance measure. Recommend checking with the most recent "Pest Report" forfurther evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

8. Structure Perimeter Exterior - Aquatic Safety Devices Installed

Pool or Spa PresentAs of 10-11-17, new laws (SB442) require residential pools/spas containing water over 18 inches deep to havetwo of the seven ASTM approved safety devices specified below. This inspection will try to identify which of thesedevices, if any, are present, however we do not test them, inspect them, or determine if they meet ASTMstandards or code.

(1) An enclosure or fence that isolates the swimming pool or spa from the home. (Min 60" High- Max 2" to Grade-Max 4" fencing voids- Self closing/latching gates that open away from pool): NO

(2) Removable mesh fencing that was installed and up at the time of the inspection, with gate that is self-closing,self-latching and can accommodate a key lockable device. (48"High-Max 1" to grade) NO

(3) An approved safety pool cover: NO

(4) Exit alarms on all of the home’s doors that provide direct access to the swimming pool or spa: NO

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 9 of 78

Page 10: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

(5) A self-closing, self-latching device with a release mechanism placed no lower than 54 inches above the flooron all of the home’s doors providing direct access to the swimming pool or spa: NO

(6) An alarm that, when placed in a swimming pool or spa, will sound upon detection of accidental or unauthorizedentrance into the water: NO

(7) Other means of protection, if the degree of protection afforded is equal to or greater than that afforded by anyof the features set forth above: NO

Were two or more of the above safety items noted: NO. We recommend further evaluation and repair by aqualified ASTM pool technician prior to the close of escrow.

** NOTE **

All gates leading to the rear yard pool area should be equipped with self-closing hinges and should open outward.Recommend inspecting the gates for these requirements prior to the close of escrow.

Pool Safety is very important to WIN Home Inspection. Every effort should be made to learn about your pool andpool safety. Use as many of the above mentioned safety features as possible at all times. Your pool should beassessed for safety and drowning prevention techniques on a regular and yearly basis. Recommend checkingwith the seller to find out which company built the pool/spa, as well as checking on any warranty information andmaintenance records/instructions.

9. Exterior Structure - Siding Condition

AttentionThe exterior siding on the home is in need of attention. There are several areas that are showing signs of wooddeterioration. As an example, the siding noted at the following sides of the structure:

Locations: - Various locations at all sides of home

We note the visually obvious areas of deterioration, however, you must refer to the latest pest inspection reportfor All locations and determinations. Recommend further evaluation and repair by a qualified specialist. Seesample pictures below;

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 10 of 78

Page 11: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The siding material is in need of attention. There are areas that have gaps and no caulking. As an example, thearea located at the front of the home. In addition, there was vent installed at the rear exterior of the home withgaps at the top side. Recommend further evaluation of the siding material and repair by a qualified specialist asneeded.

Brick has been added at one or more locations up against the siding. There appeared to be an improperlyinstalled flashing/moisture barrier installed. The siding material behind the barrier was not visible at the time ofinspection. Recommend further review and evaluation by a qualified specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 11 of 78

Page 12: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The right side exterior closet is mounted through the siding material. Recommend monitoring/sealing this area toprevent moisture intrusion into the wall. In addition, there appeared to be possible deterioration or damage to thefloor boards in this area. Recommend checking with the most recent "Pest Report" for further evaluation anddeterminations. Recommend further evaluation and repair by a qualified specialist.

10. Exterior Structure - Eave/Soffit Areas

AttentionThere appears to be some deterioration of the roof sheathing at the eaves at one or more locations around thehome. As an example, the area located at the front of the home. Recommend checking with the most recent "PestReport" for further evaluation and determinations. Recommend further evaluation and repair by a licensed roofingcontractor.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 12 of 78

Page 13: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There appears to be some deterioration to a few rafter tails around the home. Recommend checking with themost recent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair bya qualified specialist.

11. Exterior Structure - Fascia Boards/Trim

AttentionThere appears to be some deterioration or damage to the window trim , barge board(s) , structure trim(s) at oneor more locations around the home.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 13 of 78

Page 14: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommendfurther evaluation and repair by a qualified specialist.

12. Electrical Service - Over Current Devices

Sylvania/Zinsco Panel

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 14 of 78

Page 15: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The electrical panel appears to be the original panel for the structure and is a Sylvania-Zinsco brand panel. Thisbrand of panel is no longer manufactured and failure of this brand of equipment has been reported. Manyelectricians advise the immediate replacement of Zinsco panels, though this is not the only brand of equipmentthat is prone to failure. Listed replacement breakers for these panels are available but are more expensive thanother brands that are commonly available today. Due to the age and brand of the panel recommend furtherevaluation by a licensed electrician as a preventive safety consideration.

13. Electrical Service - Breaker Configuration

AttentionThere are mixed neutrals and ground wires in the sub panel/hvac disconnect buss bar. These types of wiresshould be isolated in a sub panel for safety reasons. It appears that an additional buss bar should be installed.Recommend further evaluation and repair by a licensed electrician.

14. Electrical Service - Receptacle Ground Verify

AttentionThere are a few outlets located in the living room that indicated an open ground. Recommend further evaluationand repair by a licensed electrician.

15. Electrical Service - G.F.C.I. Protection

AttentionCurrent electrical requirements are such that Ground Fault Circuit Interrupters (GFCI's) be located in areas wherethere is a potential danger of electrical shock, such as kitchens, bathrooms, garages and exterior outlets. Theoutlet or outlets located at the master bathroom and hall bathroom do not appear to be GFCI protected.Recommend further evaluation and repair by a licensed electrician.

16. Electrical Service - Outlets, Switches, Junction Boxes, Lighting

AttentionThe inspector was able to identify and report on the condition of those outlets, switches and junction boxes thatwere visible and accessible at the time of the inspection. We recommend further evaluation and repair of any

items listed in this category by a licensed electrician.

There is exposed Romex in the garage area. Romex should be shielded so that it is not exposed to mechanicaldamage.

There is an outlet located in the kitchen hallway, by the family room, that indicated no power when tested.Recommend checking with the seller in this regard.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 15 of 78

Page 16: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There are several outlets located in the living room that indicated no power at half of the outlet.

There are one or more outlets at the interior/exterior of the home that are loosely mounted in the wall. As anexample, the outlet located in the master bathroom. Recommend re-mounting the outlet(s).

The ceiling fan located in bedroom two appears to be in need of balancing. The unit had more movement thannormal.

The light fixture(s) located in the master bedroom closet appear to have a missing protective cover. Recommendinstalling a new protective cover.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 16 of 78

Page 17: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There are one or more outlets in the home that appear to have loose contacts. As an example, the outlet locatedin the master bedroom. Recommend replacing the outlets.

There are one or more outlets located in the home that have broken safety covers. As an example, the outletcover located at bedroom one. Recommend installation of approved covers.

There is a broken light switch/dial located at the family room. Recommend replacing the light switch/dial.

There are one or more unidentified switches in the home. They were located in the following rooms: - hallway

There may be others. Identifying the use of all switches in the home is often not possible during an inspection.Recommend checking with the seller in this regard.

There are one or more light switch and outlet covers in the home that are missing screws. Recommend replacingthe screws to provide for their intended use.

17. Main Entry Door - Finish

MaintenancePossible wood deterioration was noted at the right main entry door. Deterioration was also noted at the exteriortrim and jamb as well as the interior door trim. Recommend checking with the most recent "Pest Report" forfurther evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 17 of 78

Page 18: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

18. Other Ext. Entry Doors - Finish

MaintenanceThe half bathroom exterior door jamb and trim are showing signs of wear and deterioration. Recommendchecking with the most recent "Pest Report" for further evaluation and determinations. Recommend furtherevaluation and repair by a qualified specialist.

19. Kitchen(s) - Cook top, Burners/Elements

AttentionThe following burner(s) failed to heat up in a timely manner when turned on: left rear

The buyer should check with the seller in regard to this issue. Recommend further evaluation and repair by aqualified appliance specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 18 of 78

Page 19: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

20. Kitchen(s) - Garbage Disposal

AttentionThe disposer's electrical cord is entering the bottom of the unit with out the benefit of a protective bushing. Inorder to prevent accidental mechanical damage to the wires, a bushing should be installed by a qualifiedspecialist.

21. Fire Place/Wood Stove - Flue Dampers

AttentionThe chimney flue damper located at the family room fireplace does not appear to work properly. The inspectorrecommends contacting a chimney service professional to evaluate and make recommendations to repair orreplace the damper as needed.

22. Fire Place/Wood Stove - Firebox

AttentionThe brick/stone located at the front of the living room fireplace is painted. Paint is considered a combustiblematerial. This does not allow for the required 18" of non-combustible clearance around the unit. This constitutes afire hazard. Recommend further evaluation and repair by a qualified fire specialist.

23. Other Room(s) - Ceiling/Walls/Doors

AttentionThere are one or more moisture stains located at the drywall wall located in the following areas:

Locations: - Living Room

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 19 of 78

Page 20: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Recommend further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

There are one or more areas of the interior baseboards that are showing signs of stains. This was noted in thefollowing areas:

Locations: - Master Bedroom

Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommendfurther evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information

24. Bathroom(s)/Washroom(s) - Basin(s)/Fixtures

Attention

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 20 of 78

Page 21: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The right hall bathroom sink appears to have low water flow. Recommend further evaluation and repair by alicensed plumber.

25. Bathroom(s)/Washroom(s) - Shower Fixtures

AttentionThe shower riser located in the master bathroom shower is loose. Recommend further evaluation and repair by alicensed plumber.

26. Bathroom(s)/Washroom(s) - Water Resist Cover Wall Cover

AttentionThere is loose, cracked, or missing grout noted at the shower(s) in the following bathrooms: Master bathroom

Recommend grout touch-up or repair to prevent moisture intrusion. Recommend checking with the most recent"Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by a qualifiedspecialist.

The soap dish in the master bathroom shower is in need of attention. One or more cracks were noted in this area.Damage caused by water seepage into the wall was not determined by this visual inspection. Recommend referto the most recent "Pest Report" for further evaluations and determinations. Recommend further evaluation andrepair by a qualified tile specialist.

There are one or more missing wall tiles located in the master bathroom. Recommend replacing the missingtile(s). Recommend further evaluation and repair by a qualified specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 21 of 78

Page 22: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There appears to be one or more chipped or damaged shower wall tiles located in the master bathroom.Recommend further evaluation and repair by a qualified professional.

27. Bathroom(s)/Washroom(s) - Tub(s)

AttentionThe jetted tub(s) in the master bathroom(s) is/are not functioning properly. Recommend further evaluation andrepair by a licensed plumber.

There is a rust stain in the tub located in the hall bathroom. Recommend further evaluation and repair by aqualified specialist.

28. Bathroom(s)/Washroom(s) - Tub Fixtures

AttentionThe tub diverter spout located in the hall bathroom is not diverting all of the water from the spout to theshowerhead. Recommend further evaluation and repair by a licensed plumber.

29. Bathroom(s)/Washroom(s) - Toilet(s)

AttentionThe toilet or toilets in the following bathrooms were noted as loose: Master bathroom. Unseen damage may existdue to this condition.

Toilets should be kept secure to the floor in order to prevent leaks and mechanical damage. It is often necessaryto pull the toilet, inspect, and replace the wax ring on loose toilets. Recommend further evaluation and repair by alicensed plumber.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 22 of 78

Page 23: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The flush handle for the toilet located in the hall bathroom is not functioning properly. You must hold the handle toget a full flush. Recommend further evaluation and repair by a licensed plumber.

30. Bathroom(s)/Washroom(s) - Medicine Cabinet/Vanity

Attention

There are one or more stains on the wall below the only sink(s) located in the master bathroom. There were NOleaks or moisture noted at the time of the inspection. Recommend checking with the seller in this regard.Recommend further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the nationalstandards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialistfor more detailed information.

31. Bathroom(s)/Washroom(s) - Ceiling/Walls/Doors

AttentionBubbled texture was noted at the ceiling/wall located in the master bathroom. Recommend checking with themost recent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair bya qualified specialist.

32. Plumbing - Interior Water Flow

AttentionThe interior water flow in the house is low when one or more faucets are turned on. Recommend furtherevaluation and repair by a licensed plumber.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 23 of 78

Page 24: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

33. Plumbing - Pressure Readings Interior/Exterior

AttentionThe inspector noted a pressure reading of approx. 25 or less psi at the front yard hose bib. This reading is low astypical water pressure readings are usually between 40-70 psi. High pressure can strain plumbing fittings andfixtures and over time may lead to leaks. Low pressure can cause many issues within the home. Recommendchecking with the seller or the local utility to determine if a pressure regulator is present and can be adjusted asthis falls outside the scope of this inspection. Recommend further evaluation and repair by a licensed plumber.

34. Structure - Smoke Detector(s)

AttentionThere are one or more required areas in the home with no smoke detector. As an example, the upstairs area

Smoke detectors are required in all bedrooms, the hallway or areas outside of the bedrooms, and on each level ofthe home if multiple levels are present. Recommend further evaluation and repair by a qualified handyman.Recommend replacing or installing smoke detector units in all of the required rooms and areas mentioned aboveprior to moving in. There are additional requirements in regards to smoke detectors that fall outside the scope ofthis non invasive inspection. (See NOTE: "Additional Smoke Detector Requirements") Smoke detector unitsgreater than 10 years of age should be replaced as they are considered to be at the end of their service life. Theinspector recommends testing the units and insuring all of the rooms mentioned above still have a unit when firstmoving in, and every month after to identify the functional operation of each detector.

35. Structure - Carbon Monoxide Detector(s)

AttentionThe upstairs of this structure is not equipped with carbon monoxide detectors. Carbon monoxide detectors arerecommended on each level and at seperate sleeping areas in all homes where there is a possible source of COpresent in the home, such as gas burning appliances, water heaters, and heating systems. Some jurisdictionsnow require installation of CO detectors in homes. The inspector recommends that one or more CO detectors withbattery backups be installed in the structure according to jurisdictional and manufacturer recommendations.

36. Heating System - System Type(s)/Info

NotedThe Left Side Furnace is a Gas Fired Unit.

The Manufacture of the unit was Carrier

The Year Built was 1998

The age of the unit is approximately; 22 years old.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 24 of 78

Page 25: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The temperature at the outlets was between 96 and 112

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was faded, please check with the seller to determine if they know the age of the

unit or have it further evaluated by a qualified specialist.

The average life expectancy of a Furnace is 13-20 years although there are exceptions on both sides. If this unitis over 10 years old, this inspection company automatically recommends that a qualified HVAC technicianperform a service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

37. Heating System - Ducts/Returns/Radiators

AttentionThere are a one or more service ducts located in the right hallway, master bedroom, and bedroom one that arenot blowing at the same temperature as the rest of the ducts. The inspector was unable to visually inspect theducting due to the design and build of the heater platform and home. Recommend further evaluation and repairby a qualified HVAC technician.

38. Heating System - Service Notes/Filter Size

None VisibleService Overdue: There does not appear to be any visible posted notes attached to the heater(s). This unit forthe left side of the home is older and may be in the final third of it's usable life. The inspector recommends that aqualified HVAC technician perform a service cleaning, tune up, and review of the entire HVAC system, includingthe heat exchanger, prior to the close of escrow. Heaters need annual service and cleaning as a health andsafety consideration as well as for preventative maintenance reasons. This inspection does not provide anyinformation on recalled equipment that may be in the home or verification of the appropriate units and propersizing of the HVAC system. Please check with the appropriate manufacture for any recalls/recommendations.

39. Air Conditioning - Type of Units

NotedThe First Air Conditioning system is a Split A/C.

The Manufacture of the unit was Carrier

The Year Built was 1998

The age of the unit is approximately; 22 years old.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 25 of 78

Page 26: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was covered with a blanket, please check with the seller to determine if they know

the age of the unit or have it further evaluated by a qualified specialist.

The average life expectancy of a A/C is 13-20 years although there are exceptions on both sides. If this unit is

over 10 years old, this inspection company automatically recommends that a qualified HVAC technician perform a

service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

The Second Air Conditioning system is a Split A/C.

The Manufacture of the unit was Carrier

The Year Built was 1998

The age of the unit is approximately; 22 years old.

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was covered with a blanket, please check with the seller to determine if they know

the age of the unit or have it further evaluated by a qualified specialist.

The average life expectancy of a A/C is 13-20 years although there are exceptions on both sides. If this unit is

over 10 years old, this inspection company automatically recommends that a qualified HVAC technician perform a

service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 26 of 78

Page 27: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

40. Air Conditioning - Systems Operation

Not TestedThe unit was not tested as severe damage can occur to air conditioning compressors if they are turned on whenthe outside temperature is below 60 degrees Fahrenheit or has been below 60 degrees for an extended period oftime in the last 24 hours. Recommend checking with the seller in regard to the operation of the unit. Recommendfurther evaluation and repair by a qualified HVAC technician prior to the close of escrow.

41. Air Conditioning - Service Records/Last Service

Not AvailableService Overdue: There does not appear to be any visible posted notes attached to the A/C system. These unitsare older and may be in the final third of their usable life. The inspector recommends that a qualified HVACtechnician perform a service cleaning, tune up, and review of the entire HVAC system prior to the close of escrow.A/C systems need annual service and cleaning as a heath and safety consideration as well as for preventativemaintenance reasons. This inspection does not provide any information on recalled equipment that may be in thehome or verification of the appropriate units and proper sizing of the HVAC system. Please check with theappropriate manufacture for any recalls.

42. Attic - Roof Inspect from Underside

Attention - Moisture StainsThe attic was entered and the underside of the accessible areas of the roof were inspected. The inspectionidentified moisture stains on the wood joists and sheathing that would indicate the roof system has leaked atsome time in the past. There has been no substantial rain in the recent days prior to this inspection and theinspector was unable to verify that the roof system currently has an active leak condition. The inspector wouldrecommend questioning the home seller to identify if they are aware of the history of any leaks that may haveoccurred during their or prior to their ownership. In addition, re-inspecting the attic during rainy periods isrecommended to ensure that the roof system is providing its intended service. Recommend further evaluation andrepair by a licensed roofing contractor.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the nationalstandards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialistfor more detailed information.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 27 of 78

Page 28: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

43. Detached Garage - Gutters/Down Spouts

AttentionThere is a small amount of debris build up in the gutters at this time. The inspector recommends cleaning thegutters for preventive maintenance considerations. Recommend further evaluation and repair by a qualifiedspecialist.

Any amount of debris can clog the gutters, down spouts, and/or drain system if not cleaned out. Cleaning thegutters on an annual basis is recommended for proper care and maintenance of the gutter system. This can alsohelp reduce the spread of neighborhood and local wild fires. Installing gutter screen over the gutters will reducethe debris build up and the need for frequent cleaning in the fall and winter. Gutter screen can be purchased atyour local hardware or home improvement center.

44. Detached Garage - Exterior Siding

AttentionThe exterior siding, trim and sheathing on the detached garage are in need of attention. There are one or moreareas that are showing signs of wood deterioration. Recommend checking with the most recent "Pest Report" forfurther evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 28 of 78

Page 29: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There appeared to be an improperly installed flashing/moisture barrier installed at the rear exterior of thedetached garage. The siding material behind the barrier was not visible at the time of inspection. Recommendfurther review and evaluation by a qualified specialist.

45. Detached Garage - Garage Door(s)

AttentionThe door leading from the garage to the exterior is showing signs of wear and deterioration. Recommendchecking with the most recent "Pest Report" for further evaluation and determinations. Recommend furtherevaluation and repair by a qualified specialist.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 29 of 78

Page 30: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

46. Detached Garage - Automatic Opener(s)

AttentionThe garage door opener is powered via an extension cord. Extension cords are for temporary power supply only.Recommend installation of a permanent outlet to provide power in this area. Recommend further evaluation by aqualified electrician.

Extended Full Home & Pool Summary

Report

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 30 of 78

Page 31: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

FULL REPORT

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 31 of 78

Page 32: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Roof

1. Roof General Statement(s)

Roof General Statement(s)

Roof systems are known to be a common source of leaking. WIN is not a licensed roofing contractor, we

evaluate every roof conscientiously and look for indications of leaking, but we will not predict its remaining lifeexpectancy, or guarantee that it will not leak. Every roof will wear differently relative to its age, the number of itslayers, the quality of its material, the method of its application, its exposure to direct sunlight or other prevalentweather conditions, and the regularity of its maintenance. Regardless of its design-life, every roof is only as goodas the waterproof membrane beneath it, which is concealed and cannot be examined without removing the roofmaterial. However, what remains true of all roofs is that, whereas their condition can be evaluated, it is virtuallyimpossible for anyone to detect a leak except as it is occurring or by specific water tests, which are beyond thescope of our service. Even water stains on ceilings, or on the framing within attics, could be old and will notnecessarily confirm an active leak without some corroborative evidence, and such evidence can be deliberatelyconcealed. Consequently, only a roofing contractor can credibly guarantee that a roof will not leak, and they do.Naturally, the sellers or the occupants of the residence will generally have the most intimate knowledge of the roofand of its history. Therefore, we recommend that you consult with the sellers. WIN recommends contacting aqualified licensed roofing contractor for further evaluation and **Certification** against leaking prior to the close ofescrow. In addition, you should obtain comprehensive roof coverage in your home insurance policy.

2. Roof Cover Material(s)

TileRoof systems are known to be a common source of leaking. This inspection looks for indications of leaking, butdoes not guarantee a leak free roof. Interested parties should contact a qualified licensed roofing contractor forfurther evaluation and certification against leaking. In addition, the valleys located on tile roofs are known to be acommon source for roof leaks as dirt and debris can get up under the tiles and plug up the valley areas. This ismost often undetectable during a noninvasive overview of the roof cover. Recommend periodic inspections of theroof valleys by a licensed roofing contractor.

3. Roof Type

Pitched

4. Moss/Mildew

NoneThe inspector recommends inspecting the roof system for moss growth on an annual basis. Products that preventgrowth can be purchased at a local hardware store or home improvement center and can be applied by a homeowner.

5. Debris on Roof

Attention - Debris NotedDebris build up on the roof can create leaks and other issues. It is common for debris to build up in the valleysunder the roofing material that may not be visible at the time of the inspection. Debris build up should be cleanedoff the roof surface on an annual basis as a proper care and maintenance recommendation. Recommend furtherevaluation by a licensed roofing contractor on a regular basis.

There is a large amount of debris build up on the roof. There were tree branches overhanging or in contact with

the roof. Leaves, branches, and/or other material that should be removed at some time in the near future. The

debris can clog gutters, down spouts and/or drains. Debris can hold moisture that can cause damage to the roof

system if large accumulations develop. Debris should be cleaned off the roof surface on an annual basis as a

proper care and maintenance recommendation. Recommend further evaluation and repair by a licensed roofing

contractor.

Roof valleys are a common place for debris build up which can result in roof leaks. Regular inspections for debris

build up in the valley areas is recommend.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 32 of 78

Page 33: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

6. Cover

One Or More LayersThis roof has at least one layer of roof covering. Inspection for multiple layers of roofing material falls outside thescope of this inspection and is often not visible during this non invasive inspection. More than two layers of roofingis not allowed. If two layers existed, the next roof installation would require the existing layers to be removed priorto adding the new layer of roofing material. This inspection company always recommends further evaluation by aqualified roofer when more than one layer of roofing has been added over an original layer of roofing.Recommend further evaluation and repair by a licensed roofing contractor.

7. Cover Material Condition

AttentionThis roof inspection should be considered a general inspection of the roof system for obvious faults and defects.(Example; cracked, broken, or missing tiles; torn shingles). The inspector is not a licensed roofer and thisinspection is a non-exhaustive inspection of the roof. The inspector recommends that interested parties havequalified licensed roofing company do an exhaustive evaluation of the roof to determine the serviceable lifeexpectancy and obtain a certification.

There are one or more areas on the roof with tiles that appear to have been replaced or repaired at some point inthe past. Recommend checking with the seller in this regard. Recommend further evaluation and repair by alicensed roofing contractor if needed.

8. Ridges

Functional

9. Valleys

AttentionRoof valleys are known to be a common source for roof leaks as dirt and debris can get up under the tiles andplug up the valley areas. This is most often undetectable during a noninvasive overview of the roof cover.Recommend regular inspections of the roof valleys by a licensed roofing contractor.

Debris build up was noted at one or more of the roof valleys, dead valleys, or crickets. Recommend further

evaluation and repair by a licensed roofing contractor.

10. Flashing/Caulking

FunctionalThere are one or more vent pipes that doe not appear to extend the recommended distance above the the roofflashing. Recommend further evaluation and repair by a licensed plumber.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 33 of 78

Page 34: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

11. Vents/Chimneys/Covers

AttentionThere are one or more cracks in the upper mortar crown of the utility chimney. The cracks may allow rain water to

leak down the interior of the chimney and can expedite the deterioration of the bricks and mortar over the years.

Consideration should be given to repairing the mortar cap to prevent further deterioration to the chimney system.

Recommend further evaluation by a qualified fireplace specialist.

12. Gutters/Down Spouts

AttentionThe inspector recommends inspecting and cleaning the gutter system on an annual basis. If not already present,there is gutter screen material that can be installed over the gutter system to help keep debris out of the guttersand to prevent the clogging of the gutters, down spouts, and drain system. The screen material can be purchasedat a local home improvement center.

There is a small amount of debris build up in the gutters at this time. The inspector recommends cleaning thegutters for preventive maintenance considerations. Recommend further evaluation and repair by a qualifiedspecialist.

Any amount of debris can clog the gutters, down spouts, and/or drain system if not cleaned out. Cleaning thegutters on an annual basis is recommended for proper care and maintenance of the gutter system. This can alsohelp reduce the spread of neighborhood and local wild fires. Installing gutter screen over the gutters will reducethe debris build up and the need for frequent cleaning in the fall and winter. Gutter screen can be purchased atyour local hardware or home improvement center.

There are one or more downspouts that are rusty. As an example, the downspout located at the right side of the

home. Recommend further evaluation of the gutter system and repair by a qualified specialist.

13. Drains/Splash Blocks

Not Tested or InspectedIt is difficult without invasive inspection to determine if the down spout drains are plugged with debris. It isimportant to keep the drains and/or splash blocks clear and functional so that they do not overflow next to thefoundation's perimeter. Recommend inspecting the drains and/or splash blocks after moving in and prior to andafter heavy rains to confirm that they are providing their intended service.

14. Indications of Leaking

No

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 34 of 78

Page 35: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Unless it is currently raining, potential roof leaks are very difficult to identify. WIN is not a licensed roofingcontractor and does not guarantee the roof from leaking. Roof systems are known to be a common source ofleaking. This inspection looks for indications of leaking, but does not guarantee a leak free roof. WIN recommendscontacting a qualified licensed roofing contractor for further evaluation and certification against leaking prior to theclose of this escrow.

15. Soft Spots

NoThe eave areas are not walked for softness. Recommend further evaluation by a licensed roofing contractor ifdesired.

16. Skylight(s)

None

17. Separate Certification Required

Yes - Due to Unknown Remaining LifeThere is no requirement for a "Roof Certification" warranty. The inspector noted that he does NOT provide awarranty against any future roof leaks. If the buyer is interested in obtaining a multi-year roof warranty againstfuture leakage, we recommend that a qualified licensed roofing contractor be contacted to provide this service.

The inspector was unable to determine the number of years of serviceable life left in the roof. Contacting a

qualified roofing expert to evaluate the existing condition of the roofing in order to provide an approximate number

of years of serviceable life left is recommended.

This roof inspection should be considered a general inspection of the roof system for obvious faults and defects.

The inspector is not a roofer and this inspection is a non-exhaustive inspection of the roof. The inspector

recommends that interested parties have qualified licensed roofing company do an exhaustive evaluation of the

roof to determine the serviceable life expectancy and obtain a certification.

18. Roof Evaluated From

NotedDue to weather and accessibility, the roof was evaluated by walking the surface. Conditions may exist that theinspector was not able to see without walking the roof system. WIN Home Inspection recommends contacting aqualified licensed roofing contractor for further evaluations and determinations of the entire roof system.

Structure Perimeter Exterior

1. Structure Perimeter Exterior General Statement(s)

Structure Perimeter Exterior General Statement(s)Many items fall outside the scope of this inspection. As an example; Sprinkler/irrigation systems, fences/gates,electric blinds/awnings, and any decks, pergolas, patio covers or retaining walls not directly attached to the home.For a full list, please refer to the ASHI standards and your inspection agreement. We do not evaluate anydetached structures, such as storage sheds and stables, we do not water test or evaluate subterranean drainagesystems or any mechanical or remotely controlled components, such as driveway gates. We do not evaluatelandscape components, such as trees, shrubs, fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps,and decorative or low-voltage lighting.

Grading and drainage on most sites are rarely ideal and this is most often the case on older properties. The idealsite will have surfaces that slope away from a residence at one half inch per foot for a minimum of six feet, andthe interior floors will be higher than the exterior grade. Our visit to the site is limited, and the sellers or occupantswill have the most intimate knowledge of the property. Please refer to the seller for more information on pastdrainage and moisture intrusion issues.

2. Foundation Material(s)

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 35 of 78

Page 36: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Concrete

3. Vent Screens

AttentionThere are one or more exterior attic vent screens that are damaged and have holes. As an example, the screen

located at the front of the home. Recommend further evaluation of exterior vents screens and repair by a qualified

handyman in order to prevent unwanted pest entrance.

4. Visible Cracks

No

5. Evidence of Separation over 1/4"

No

6. Evidence of Movement

No

7. Site Drainage

AttentionThe grading around the perimeter of the structure is very important. We recommend that you monitor these areaswith future inspections of the grading to make sure that a positive slope away from the foundation is maintained. Aone inch drop in slope away from the home for the first six feet is recommended.

There are low spots next to the foundation at various locations around the home. These may allow the pooling ofwater against the foundation. Recommend further evaluation and repair by a qualified specialist.

8. Evidence of Erosion

No

9. Proper Earth-Wood Clearance

NoInspection around the perimeter of the structure should occur on a regular basis to ensure no contact of earth towood. There should be no contact between the earth and the exterior surface material to prevent wooddeterioration and a conducive condition for pest infestation. The inspector recommends providing at least four tosix inches of clearance between the earth and the siding material as a preventive maintenance measure.

The inspection has revealed earth to wood contact around the left side of the structure. There should be no

contact between the earth and the exterior wood to prevent wood deterioration and a conducive condition for pest

infestation. Recommend providing at least four to six inches of clearance between the earth and wood siding

material as a preventive maintenance measure. Recommend checking with the most recent "Pest Report" for

further evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

10. Vegetation Clear from Structure

NoVegetation growing up against the exterior surface material can create issues. When present, vegetation shouldbe kept trimmed at least 6-12 inches away from the structure to eliminate a common avenue for pest infestationand damage to the exterior structure material.

There is vegetation growing up against the exterior surface material. All vegetation should be trimmed at least6-12 inches away from the structure to eliminate a common avenue for pest infestation and damage to theexterior structure material. Recommend further evaluation and repair by a qualified specialist.

11. Address Identification

VisibleA visible address identification number is important so guest as well as emergency response personnel will beable to find the correct property needed. Maintain address visibility.

12. Mail Box

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 36 of 78

Page 37: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Satisfactory

13. Watering System

YesWatering systems add a positive aspect to properties. If this property has a watering system, testing the system isnot within the scope of the inspection. If present, we would recommend checking with the home seller concerningthe operation of the system and having it further evaluated by a irrigation specialist.

14. Window Wells

None

15. Retaining wall(s)

FunctionalAny retaining walls on the property that are detached from the home (ex: rear, front, or side yard) are outside thescope of this inspection and were not inspected. Recommend checking with the seller in this regard.

16. Aquatic Safety Devices Installed

Pool or Spa PresentAs of 10-11-17, new laws (SB442) require residential pools/spas containing water over 18 inches deep to have

two of the seven ASTM approved safety devices specified below. This inspection will try to identify which of these

devices, if any, are present, however we do not test them, inspect them, or determine if they meet ASTM

standards or code.

(1) An enclosure or fence that isolates the swimming pool or spa from the home. (Min 60" High- Max 2" to Grade-

Max 4" fencing voids- Self closing/latching gates that open away from pool): NO

(2) Removable mesh fencing that was installed and up at the time of the inspection, with gate that is self-closing,

self-latching and can accommodate a key lockable device. (48"High-Max 1" to grade) NO

(3) An approved safety pool cover: NO

(4) Exit alarms on all of the home’s doors that provide direct access to the swimming pool or spa: NO

(5) A self-closing, self-latching device with a release mechanism placed no lower than 54 inches above the floor

on all of the home’s doors providing direct access to the swimming pool or spa: NO

(6) An alarm that, when placed in a swimming pool or spa, will sound upon detection of accidental or unauthorized

entrance into the water: NO

(7) Other means of protection, if the degree of protection afforded is equal to or greater than that afforded by any

of the features set forth above: NO

Were two or more of the above safety items noted: NO. We recommend further evaluation and repair by a

qualified ASTM pool technician prior to the close of escrow.

** NOTE **

All gates leading to the rear yard pool area should be equipped with self-closing hinges and should open outward.

Recommend inspecting the gates for these requirements prior to the close of escrow.

Pool Safety is very important to WIN Home Inspection. Every effort should be made to learn about your pool and

pool safety. Use as many of the above mentioned safety features as possible at all times. Your pool should be

assessed for safety and drowning prevention techniques on a regular and yearly basis. Recommend checking

with the seller to find out which company built the pool/spa, as well as checking on any warranty information and

maintenance records/instructions.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 37 of 78

Page 38: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

17. Evidence of Animal Infestation

Outside Scope of InspectionOUTSIDE SCOPE OF THIS INSPECTION

This inspection does not address any past or present conditions relating to animals, rodents, insects or otherhousehold pests, pest activity or the damage caused thereby inside or outside of the home unless otherwisenoted in this report. This is a state licensed and regulated field of work that requires a Branch 2 license with thestate of California and this inspection company is not licensed in this field. Interested or concerned parties shouldcontact a licensed pest service/exterminator for further evaluation and any needed pest control. This homeinspection company is not responsible for any pest activity or infestation discovered, no matter how severe. It isthe buyers responsibility to contact a separate company and conduct these inspections with a licensed pestcontrol provider prior to the close of escrow.

18. Evidence of Insects

Outside Scope of InspectionOUTSIDE SCOPE OF THIS INPSECTION

This inspection does not address any past or present conditions relating to animals, rodents, insects or other

household pests, pest activity or the damage caused thereby inside or outside of the home unless otherwise

noted in this report. Interested parties should contact a licensed pest service/exterminator for further evaluation

and any needed pest control.

Exterior Structure

1. Exterior Structure General Statement(s)

Exterior Structure General Statement(s)

2. Flat Surface Material(s)

Wood SidingThe siding is T1-11 or other type wood siding.

3. Siding Condition

AttentionAs part of routine maintenance we suggest inspection of the siding material and sealing all open seams, cracks,holes and gaps in the siding material on a regular basis to help prevent water penetration.

The exterior siding on the home is in need of attention. There are several areas that are showing signs of wood

deterioration. As an example, the siding noted at the following sides of the structure:

Locations: - Various locations at all sides of home

We note the visually obvious areas of deterioration, however, you must refer to the latest pest inspection report

for All locations and determinations. Recommend further evaluation and repair by a qualified specialist. See

sample pictures below;

The siding material is in need of attention. There are areas that have gaps and no caulking. As an example, the

area located at the front of the home. In addition, there was vent installed at the rear exterior of the home with

gaps at the top side. Recommend further evaluation of the siding material and repair by a qualified specialist as

needed.

Brick has been added at one or more locations up against the siding. There appeared to be an improperly

installed flashing/moisture barrier installed. The siding material behind the barrier was not visible at the time of

inspection. Recommend further review and evaluation by a qualified specialist.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 38 of 78

Page 39: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The right side exterior closet is mounted through the siding material. Recommend monitoring/sealing this area to

prevent moisture intrusion into the wall. In addition, there appeared to be possible deterioration or damage to the

floor boards in this area. Recommend checking with the most recent "Pest Report" for further evaluation and

determinations. Recommend further evaluation and repair by a qualified specialist.

The satellite dish located at the rear of the home appears to have been screwed through the wall. This may havecompromised the siding material. Recommend further evaluation and repair by a qualified specialist.

There appears to be a few previous repairs to the exterior siding material on the structure. Recommend checkingwith the seller in this regard. Recommend further evaluation and repair by a qualified specialist.

4. Painted Surfaces

AttentionThe paint on the exterior trim/siding/eave material is peeling, bubbled, or showing signs of wear at one or morelocations around the home. Recommend further evaluation and repair by a qualified specialist.

Consideration will need to be given to repainting the structure in the coming years in order to provide long termprotection and a pleasing look to the exterior structure.

5. Glaze/Caulking Window Pane

Satisfactory

6. Caulking Structure

AttentionRecommend touching up the interior and exterior structure caulking around the tops and sides of window/doortrim, splits or cracks in any of the wood/siding and interior drywall materials as well as at the gaps in the siding asthis is often needed in between paintings. The caulking keeps rain water from penetrating behind the sidingmaterial and causing premature deterioration of the material. Caulking/painting the structure on a regular basis aspart of an ongoing maintenance routine will help prolong the life of the siding/trim material. Recommend furtherevaluation and repair by a qualified specialist.

7. Eave/Soffit Areas

AttentionThere appears to be some deterioration of the roof sheathing at the eaves at one or more locations around the

home. As an example, the area located at the front of the home. Recommend checking with the most recent "Pest

Report" for further evaluation and determinations. Recommend further evaluation and repair by a licensed roofing

contractor.

There appears to be some deterioration to a few rafter tails around the home. Recommend checking with the

most recent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by

a qualified specialist.

8. Fascia Boards/Trim

AttentionThere appears to be some deterioration or damage to the window trim , barge board(s) , structure trim(s) at one

or more locations around the home.

Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommend

further evaluation and repair by a qualified specialist.

9. Window Screens

Attention

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 39 of 78

Page 40: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There are one or more windows in the home with missing screens. Screens should be replaced to provide fortheir intended use. Recommend further evaluation of all of the screens and repair by a qualified handyman. Bentscreens, screens with holes or torn screen material are a common occurrence due to plant or animal contact and/or damage when cleaning the windows and are not specifically noted in this report. The screens should berepaired or replaced to provide for their intended use. Repairing screens as needed is recommended as routinemaintenance.

10. Double Pane Seals/Insulating Windows

AttentionThe inspector has noted that there are one or more dual pane insulating windows in the home that appear to havelost their vacuum seal between the panes of glass or have a low-E film failure. They are located in the followingrooms: the family room.

The condition is identified by signs of fogging, condensation build up in between the glass panes, or a coloredmetallic film failure. It is not a failure of the window, per se, since light is allowed in and weather is kept out.However, many clients feel it is not an attractive feature to live with and often choose to have the windowreplaced, resulting in expensive replacement costs. In regards to our service to you, we will note windows whichhave obvious low-E failure or seal failure, that is to say, the metallic sheen or fogging must be clearly obvious tothe inspector in relation to the conditions of light, the cleanliness of the windows, and the accessibility to view thewindow(s) during the short time period we are inspecting the house. When low light levels are present, thewindows are covered in grime, located on tall walls, or concealed by window coverings; a slightly fadedmillimeters thick coating may not be noted or reported. Therefore it is incumbent on the client to closely view thewindows during their pre-closing walk-through to ensure the windows meet their satisfaction. Replacement of thedual pane glass unit is the only way to correct the condition. Recommend further evaluation of all the windows inthe structure and repair as needed by a qualified window specialist.

11. Storm Windows

None

12. Security Lights

Yes - Not TestedThis property is equipped with exterior lighting, adding to the safety and security of the residence. This mayinclude switch controlled light/floods, motion sensor fixtures or regular wall mounted fixtures. Some fixtures arenot tested, due to the fact that it has either a timer or a light sensor and override of the system is not within thescope of this inspection.

13. Security Bar System

Not TestedTesting of the Security Bars or Window Bars fall outside the scope of this inspection and are NOT tested orinspected..

Basements, sleeping rooms, and rooms which are intended for emergency egress should have at least oneoperable emergency escape and rescue opening. Windows that are equipped with bars and must have a quick-release mechanism that complies with the following requirements:

◦ It should be accessible from the inside of the house.◦ It should not require a key or combination.◦ It should not require any special tools, such as a screwdriver.◦ The mechanism should be able to be operated with relatively little force.◦ Operation of the mechanism should not require special knowledge.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 40 of 78

Page 41: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Even if the mechanism appears functional, YOU should test every window prior to occupying the home to ensurethat its ability to operate has not become compromised by rust, paint, or some other factor. Testing these locks ona regular basis is recommend for health and safety reasons.

Site Concrete and Paving

1. Site Concrete and Paving General Statement(s)

Site Concrete and Paving General Statement(s)Cracks in driveways, walkways, porches, and concrete patios are a commonly occurring issue and are typicallyconsidered cosmetic in nature and are not specifically noted unless mentioned elsewhere in the report.Recommend sealing the cracks and monitoring/repair over time to prevent any trip hazards. If cracks are notedand the buyer is concerned, we recommend further evaluation and repair by a qualified licensed concretecontractor.

2. Driveway(s)/Parking

AttentionThe asphalt driveway has one or more cracks located in various areas. There was no visible lifting/bulging noted.Recommend sealing the cracks and monitoring over time. Repair as needed. There were no missing ordeteriorated expansion boards noted. Recommend further evaluation and repair by a qualified licensed concretecontractor.

3. Walkways

AttentionThere are walkways located around the home that are made up of uneven natural style pavers. Caution should beused when walking in these areas as it may present a trip hazard.

The concrete walkways located at the front of the home have one or more cracks located in various areas. Theslabs have lifted or deflected at this time. Recommend sealing the cracks and monitoring over time. Repair asneeded. Recommend further evaluation and repair by a qualified licensed concrete contractor.

4. Steps

AttentionThe steps located at the rear of the home are lower than normal. This may cause an unexpected step up or dropoff. Recommend using caution in this area. Recommend further evaluation and repair by a qualified licensedcontractor.

Patios/Decking/Porches

1. Patios/Decking/Porches General Statement(s)

Patios/Decking/Porches General Statement(s)Unless otherwise mentioned in this report the following items are outside the scope of this inspection and wereNOT inspected whether or not they were free standing, built-in, or attached to the structure: Pools, Spas. Poolhouses, Fire Pits, Barbecues, Barbecue Islands, Grills, Outdoors Kitchens and any and all related components tothese items. We advise inspection of these items by a qualified specialist to ensure proper operation, installation,and code/permit compliance. Recommend checking with the seller in this regard.

Inspection of decks and decking is for obvious defects and deterioration and should be considered noninvasive.Decks and deck systems have many components. This inspection excludes any engineering analysis of any kindincluding structural integrity and system design problems. Concealed cavities within coated deck systems are notinspected. All second and third story decks should be further evaluated for design, engineering, and safetyreasons by a licensed deck contractor.

2. Concrete Slab

Attention

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 41 of 78

Page 42: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The rear patio concrete slab(s) have one or more cracks located in various areas. The slabs have not lifted ordeflected at this time. Recommend sealing the cracks and monitoring over time. Repair as needed. Recommendfurther evaluation and repair by a qualified licensed concrete contractor.

3. Electrical Service

Yes

4. Weather Protected Outlet(s)

YesInstallation of weather dome style covers are now recommended for all exterior outlets especially those that willhave a permanently installed plug. This is to provide around the clock protection to the outlet. This type of covercan be purchased at a home improvement center.

5. Natural Gas Service/Equipment

No

6. Lights

AttentionThere are one or more light fixtures at various locations around the home that are loose. Recommend securing/sealing around the fixtures.

7. Cover/Enclosure

Functional

Utility Services

1. Electrical Services

Underground

2. Overhead Service Lines

N/A

3. Water Source

Water district

4. Water Meter Location

At the pressure tank equipment.There was a water pressure tank located at the right side exterior closet. Recommend checking with the countywater district for more information.

5. Water Shutoff

Right Side YardThere was no pressure regulator noted.

Pressure regulators fall outside the scope of this inspection. Not all homes have pressure regulators. Recommendchecking with your local utility and further evaluation by a licensed plumber if the city or county recommends aregulator.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 42 of 78

Page 43: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

6. Sewer

SepticThis property appears to be equipped with a septic type waste system. This may or may not include othercomponents like a "lift station" type pump that empties the tank into a sewer or other type septic system.Inspection of septic or step septic type systems and "lift station" type pumps and any components relating tothese systems are outside of the scope of this inspection. It is very important that the buyer(s) have a qualifiedlicensed plumber or septic company inspect, operate, and test the system for proper installation and functionalityor any required maintenance prior to the close of escrow.

7. Sewer Line Clean-out

Right ExteriorA sewer scope is always recommended by this company, as the sewer piping that runs from the home all the wayto the city entry point is the responsibility of the homeowner. This includes responsibility for the portion of sewerline that runs under the sidewalk and street if present. Typical sewer line repairs can run between$2,500-$10,000.

Please contact this office if you have questions or would like to schedule a Sewer Scope.

8. Telephone

Underground

9. Cable TV Service

Underground

10. Gas Service

PropaneBy modern standards, drip legs are now recommend on all gas burning appliances such as water heaters andfurnaces. Drip legs are designed to collect debris from inside the piping, and to prevent clogs in the gas line andappliance piping. This company does not specifically comment on the presence or absence of drip legs. Someconsideration may be given to the installation of drip legs when gas burning appliances are replaced, if notalready present. Contact a licensed plumber for further evaluation and a cost estimate.

This inspection does not evaluate the gas supply system or tank for materials, installation or leakage.Recommend further evaluation repair by a qualified plumber if desired.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 43 of 78

Page 44: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

11. Gas Odors

None NotedNote: There are natural gas or propane burning appliances inside this structure. This type of appliance producescarbon monoxide as a byproduct of the combustion process. Carbon monoxide (CO) is a colorless, odorless toxicgas. The inspector did NOT perform any type of CO screening or monitoring during the inspection. This type oftesting is outside the scope of the inspection. The inspector recommends that the buyer consult with the local gasutility in regards to CO monitoring. We also recommend that the buyer install a CO monitor in the home per themanufacturer's guidelines. CO monitors, with battery back up and digital readouts, are available at most homeimprovement centers.

12. Vents/Exhaust

SatisfactoryThe exhaust vent piping for the gas appliances was inspected if readily visible. This type of piping should beinspected on a regular basis to ensure that it is free of defects that would require immediate action. The ventpiping should be inspected annually or anytime when the gas appliances are serviced or replaced.

13. Service Shut Off(s)

Meters and Appliances

14. Carbon Monoxide

Not TestedMonitoring or testing for Carbon Monoxide (CO) was NOT performed during this home inspection. Monitoring ortesting for Carbon Monoxide (CO) is NOT within the scope of a home inspection, according to the nationalstandards of both the American Society of Home Inspectors and the National Association of Home Inspectors. Werecommend that fossil fuel-fired appliances be serviced and evaluated annually per manufacturers instructions.For further information on the causes of CO poisoning and helpful preventive measures please visit these helpfullinks: http://www.epa.gov/air/urbanair/co/index.html http://www.carbon-monoxide-poisoning.com

Electrical Service

1. Electrical Service General Statement(s)

Electrical Service General Statement(s)The inspection of the electrical system is a non invasive general overview of the functionality of the electricalcomponents in the home AT the time of the inspection. Certain electrical conditions may or may not occur or beobvious during this short time frame. There are a wide variety of electrical systems with an even greater variety ofcomponents, and any one particular system may not conform to current standards or provide the same degree ofservice and safety. What is most significant about electrical systems however is that the national electrical codeNEC is not retroactive, and therefore many residential systems do not comply with the latest safety standards.Regardless, we are not electricians and in compliance with our standards of practice we only test a representativenumber of switches and outlets and do not perform load-calculations to determine if the supply meets the

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 44 of 78

Page 45: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

demand. However, in the interests of safety, we regard every electrical deficiency and recommended upgrade asa latent hazard that should be serviced as soon as possible, and that the entire system be evaluated and certifiedas safe by a licensed electrician. Therefore, it is essential that any recommendations that we may make forservice or upgrades should be completed before the close of escrow, because an electrician could revealadditional deficiencies or recommend some upgrades for which we would disclaim any further responsibility.Exterior ceiling fans are on/off tested. Outdoor use rating of the fans is not verified. Any exterior lighting, outlets,or light fixtures (Ex; lamp posts, column lights, path lights) not affixed to the house fall outside the scope of thisinspection and were not tested. Outlets high up on interior or exterior walls are not tested. Recommend checkingwith the seller in this regard.

2. Panel/Sub-Panel Location(s)

NotedThe main electrical panel is located on the right side of the home.

If there was a sub panel present it was located in the attic area.

There does not appear to be a solar electric system installed at this property.

There does not appear to be a back-up generator system installed at this property.

Solar systems, generators and their installation fall outside the scope of this inspection. Inspection of roofmounted systems if they are present is important to ensure the proper sealing of any penetrations through theroofing material is recommended. In addition, recommend monitoring the penetrations over time to preventmoisture intrusion. Recommend further evaluation by a qualified roofer and electrician if solar or a generator ispresent on site. Recommend checking with the seller in this regard.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 45 of 78

Page 46: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

3. Service Size (Amps)/(Volts)

200 Amps - 240 Volts

4. Over Current Devices

Sylvania/Zinsco PanelThe electrical panel appears to be the original panel for the structure and is a Sylvania-Zinsco brand panel. This

brand of panel is no longer manufactured and failure of this brand of equipment has been reported. Many

electricians advise the immediate replacement of Zinsco panels, though this is not the only brand of equipment

that is prone to failure. Listed replacement breakers for these panels are available but are more expensive than

other brands that are commonly available today. Due to the age and brand of the panel recommend further

evaluation by a licensed electrician as a preventive safety consideration.

5. Service to Panel

Copper

6. Panel to Structure

Copper/Aluminum

7. Panel Cover

Functional

8. Panel Cover(s) Removed

Yes

9. Breaker Configuration

AttentionThere are mixed neutrals and ground wires in the sub panel/hvac disconnect buss bar. These types of wires

should be isolated in a sub panel for safety reasons. It appears that an additional buss bar should be installed.

Recommend further evaluation and repair by a licensed electrician.

10. Wire-Over Current Compatibility

SatisfactoryNot all of the wire ends were visible where they connected to the breakers. An over current incompatibilitycondition may exist in the panel. The only way to find out is to turn off the breakers and remove the wires forinspection. This would be well outside the scope of the national home inspection standards of practice and wouldbe considered invasive.

11. Receptacle Ground Verify

Attention

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 46 of 78

Page 47: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The inspector has SPOT CHECKED (at least one per room per ASHI standards) the accessible 110 volt electricaloutlets throughout the structure. NOTE: This is not a warranty and an undiscovered condition may exist. Werecommend all outlets be checked when vacant. Also, all outlets feeding mechanical systems are recommendedto be grounded.

There are a few outlets located in the living room that indicated an open ground. Recommend further evaluation

and repair by a licensed electrician.

12. G.F.C.I. Protection

AttentionCurrent electrical code requires that ground fault interrupters (G.F.I.) be located in areas where there is a potentialdanger of electrical shock. It is recommended that all bathroom, kitchen, exterior and garage area outlets beupgraded with GFI protection if they are not already protected.

Current electrical requirements are such that Ground Fault Circuit Interrupters (GFCI's) be located in areas where

there is a potential danger of electrical shock, such as kitchens, bathrooms, garages and exterior outlets. The

outlet or outlets located at the master bathroom and hall bathroom do not appear to be GFCI protected.

Recommend further evaluation and repair by a licensed electrician.

13. Service Ground Verified

Not visibleNot Visible. Contact a licensed electrician for further evaluation of the electrical system for proper bonding of thepanel for safety considerations.

14. Outlets, Switches, Junction Boxes, Lighting

AttentionThe inspector was able to identify and report on the condition of those outlets, switches and junction boxes that

were visible and accessible at the time of the inspection. We recommend further evaluation and repair of any

items listed in this category by a licensed electrician.

There is exposed Romex in the garage area. Romex should be shielded so that it is not exposed to mechanical

damage.

There is an outlet located in the kitchen hallway, by the family room, that indicated no power when tested.

Recommend checking with the seller in this regard.

There are several outlets located in the living room that indicated no power at half of the outlet.

There are one or more outlets at the interior/exterior of the home that are loosely mounted in the wall. As an

example, the outlet located in the master bathroom. Recommend re-mounting the outlet(s).

The ceiling fan located in bedroom two appears to be in need of balancing. The unit had more movement than

normal.

The light fixture(s) located in the master bedroom closet appear to have a missing protective cover. Recommend

installing a new protective cover.

There are one or more outlets in the home that appear to have loose contacts. As an example, the outlet located

in the master bedroom. Recommend replacing the outlets.

There are one or more outlets located in the home that have broken safety covers. As an example, the outlet

cover located at bedroom one. Recommend installation of approved covers.

There is a broken light switch/dial located at the family room. Recommend replacing the light switch/dial.

There are one or more unidentified switches in the home. They were located in the following rooms: - hallway

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 47 of 78

Page 48: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There may be others. Identifying the use of all switches in the home is often not possible during an inspection.

Recommend checking with the seller in this regard.

There are one or more light switch and outlet covers in the home that are missing screws. Recommend replacing

the screws to provide for their intended use.

15. Wire Method

Grounded 2 Wire

16. Arc Fault Breakers (A.F.C.I.)

Not Present

Water Heater

1. Location(s)

Exterior closet

2. Water Heater General Statement(s)

Water Heater General Statement(s)If your hot water heater is located in your garage or where it can be struck by a vehicle, you should have a bollardinstalled in order to protect it from vehicular damage - or worse yet breaking a gas or water pipe. There aredifferent requirements for individual counties and cities as well as relationship of the age of the home. Thiscompany does not comment on the presence or absence of a bollard. If this property has a water heater locatedin the garage and no bollard (post/pole) to protect it from vehicle damage a plumber should be consulted forfurther evaluation and repair.

If the water heater or water heaters are not original to the home, the person(s) who installed the equipment arerequired to follow municipal regulations; such as pulling installation permits, bringing installation up to recent codechanges, and having the work approved by the local building authorities. Inspecting these systems for theadherence of these regulations is outside the scope of our limited visual inspection. You should inquire with theseller to provide an installation permit and any documents they may have which may transfer a material or workwarranty. We do not endorse any water heaters which have been installed without a permit. In the event the sellercan not produce an installation permit, you should have the local authorities review the system prior to close ofescrow.

3. Type

NotedThe water heater is Electric

The Manufacture of the unit was American

The year built was 2014

If there was a visible specifications label, a photo with the information has been provided below. If no systeminformation was available or it was covered with a blanket, please check with the seller to determine if they knowthe age of the unit or have it further evaluated by a qualified specialist.

The life expectancy of a water heater is typically 8-12 years (tank) and 18-20 years (tankless) from the date ofinstallation, although there are exceptions on both sides. If the year stated above indicates that this unit is over 7years old (tank) and 15 years old (tankless), it may be considered in the final third of its usable life. Recommendmonitoring and repairing or replacing as needed.

Items should not be stored against gas or electric water heater. Providing at least two feet of clearance aroundthe water heater is recommended.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 48 of 78

Page 49: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

4. Solar Auxiliary

None

5. Size Main/Aux (Gal)

Approximately 50 US Gallons

6. Evidence of Leaks

NoAfter the close of escrow on this home, the water heater should be inspected periodically by the owner to ensurethere are no visible leaks at the water heater and related piping. Water heaters can fail without warning especiallywith change in ownership and the difference in usage.

7. Evidence of Encrustation

No

8. Safety Valve

PresentA temperature/pressure relief valve should always be installed on a water heater. These type of valves let waterescape if the temperature or pressure is too high. Water heater safety valves are not tested as valves are proneto leaking

9. Discharge Pipe

SatisfactoryAn approved discharge tube connected to the temperature/pressure relief valve is an important safety feature.

10. Safety Tie Down(s)

SatisfactoryWater heaters need to be equipped with a two strap tie down system. This helps to prevent the tank from tippingover.

11. Insulation Blanket

None

12. Installation

Attention - NO local DisconnectThere is no local service disconnect within sight of the electric water heater unit. Recommend checking with localcounty code. Recommend further evaluation and repair by a licensed electrician.

Laundry Area

1. Location

Adjacent to Hall

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 49 of 78

Page 50: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

2. Washer Hookup(s)

Yes

3. Gas Service

Yes

4. Dryer Electrical Service 240V

YesThere is a 220 volt electrical service outlet in the laundry area. The outlet was tested and appeared to functionproperly.

5. Drain(s)

Not testedFuture periodic inspection of the floors and wall around the laundry area drain is recommend to ensure no leaksor back ups have occurred.

The inspector was unable to test the function of the washer drain due to the presence of the sellers washingmachine. Recommend checking with the seller in regard to the drain system.

6. Laundry Basin

Functional

7. Dryer Ventilation System

SatisfactoryHome maintenance should include periodic evaluation of the air flow at the dryer outlet. One-half inch of lint buildup will reduce venting capabilities by 40%. Recommend dryer vent duct cleaning if low flow is noted. Testing andevaluation of the system was not done during this inspection. Recommend further evaluation and annual cleaningby a qualified specialist.

8. Floor Condition

SatisfactoryNote: The inspector does not move the washer and dryer to inspect behind or under them. A visual inspection ofthe readily accessible portions of the floor was performed. The inspector does NOT warranty the flooring coveringunderneath or behind the appliances for mechanical damage, water related damage including stains, or any otherundiscovered/undisclosed conditions concealed by the appliances or hook-ups. Floors may be damaged byappliance legs or by moving dolly wheels during the moving process. Concerned parties should check with theseller in this regard.

9. Lighting

Satisfactory

10. Area Ventilation

NoneThe laundry room is not equipped with a window to provide passive ventilation or a powered exhaust vent fan.Installation of a fan to reduce moisture build up is recommended. Recommend further evaluation and repair by aqualified specialist.

11. Shelving/Storage

Satisfactory

Main Entry Door

1. Door Fit

AttentionThe main entry door may be in need of adjustment. There is a small amount of light visible between both of thedoor(s). Recommend further evaluation and repair by a qualified specialist.

2. Finish

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 50 of 78

Page 51: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

MaintenancePossible wood deterioration was noted at the right main entry door. Deterioration was also noted at the exterior

trim and jamb as well as the interior door trim. Recommend checking with the most recent "Pest Report" for

further evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

3. Dead Bolts

AttentionThe main entry door fit appears to be off. The dead bolt is not lined up with the strike plate. Recommend furtherevaluation and repair by a qualified handyman.

4. Storm/Screen/Doors

None

5. Door Chime

None

6. Lighting

Functional

Other Ext. Entry Doors

1. Location(s)

NotedThe other exterior doors are located in the following rooms/areas: Master Bedroom - Family Room - 1/2 Bathroom

2. Correct Application

Yes

3. Finish

MaintenanceThe half bathroom exterior door jamb and trim are showing signs of wear and deterioration. Recommend

checking with the most recent "Pest Report" for further evaluation and determinations. Recommend further

evaluation and repair by a qualified specialist.

4. Door Fit

AttentionThe door fit at the half bathroom exterior door is off. Recommend further evaluation and repair by a qualifiedlicensed contractor.

5. Weather Stripping

AttentionThere appears to be some damage to the weather stripping located at the guest bathroom exterior door.Recommend further evaluation and repair by a qualified handyman.

6. Storm/Screen Door(s)

AttentionThe screen door in the the master bedroom may need adjustment. The door is a little rough when opening andclosing. Recommend further evaluation and repair by a qualified handyman.

7. Locks

AttentionThe locking mechanism for the sliding glass door located in the family room does not appear to be functioningproperly. Recommend further evaluation and repair by a qualified specialist.

8. Sliding Door Glass/Safety

Satisfactory

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 51 of 78

Page 52: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Kitchen(s)

1. Kitchen(s) General Statement(s)

Kitchen(s) General Statement(s)Free standing appliances such as refrigerators and freezers are outside the scope of this inspection. Built inappliances such as large high end refrigerators and freezers are outside the scope of this inspection. These itemsare not tested or inspected unless otherwise noted in this report. Non standard or aftermarket appliances such asinstant hot water taps, wine refrigerators, built-in ice makers, and under sink water filters fall outside the scope ofthis inspection and were not tested unless otherwise stated in the report. Several styles of kitchen, bathroom,laundry, and bar faucets are able to fully spin 360 degrees. If this structure has faucets that spin 360 degrees, usecaution as these faucets can swing out over counter tops or out of the sink area. Recommend checking with theseller in this regard.

2. Floor Cover Material

AttentionThere are one or more chipped or cracked floor tiles located in the kitchen area. Recommend further evaluationand repair by a qualified tile specialist.

3. Under Sink Inspection

AttentionThe inspector noticed some stains at the cabinet base and wall under the kitchen sink. There was no moisture orplumbing leaks noted during this visual inspection. The drywall at the wall has been cut out and was not replaced.Previous plumbing repair noted. The deck appears to have been repaired. Recommend checking with the ownerin this regard. Recommend further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

4. Sink/Faucet Leak

No

5. Drains Appear Clear

Yes

6. Stove Exhaust Fan

Attention

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 52 of 78

Page 53: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The cooktop downdraft exhaust fan control switch does not appear to be functional every time it is operated. Thisappears to be an issue with the switch. This unit is older. Recommend further evaluation and repair by a qualifiedappliance specialist.

7. Stove Exhaust Filter

AttentionThe grease filter(s) on the exhaust fan are dirty. Recommend checking with the seller in this regard. Recommendfurther evaluation and repair by a qualified handyman.

8. Water For Refrigerator

YesThere is a water supply connection in the area of the refrigerator. The water service lines and connection fittingswere not checked at this time due to the non-invasive nature of the inspection. Recommend further evaluation ofthe above noted items prior to the close of escrow.

Water was noted on the floor to the right of the refrigerator after testing the water supply to the refrigerator. Thismay be an internal appliance issue when the water line is used. Recommend further evaluation and repair by aqualified specialist.

9. Stove/Cook Top

Electric

10. Cook top, Burners/Elements

AttentionThe following burner(s) failed to heat up in a timely manner when turned on: left rear

The buyer should check with the seller in regard to this issue. Recommend further evaluation and repair by a

qualified appliance specialist.

11. Controls

AttentionThe stove control knobs are functional, however some of the knob markings are faded. Recommend replacingknobs to prevent any safety issues from occurring, if the knobs become completely unreadable.

12. Built-in Microwave Operational

NoneThere did not appear to be a built-in microwave at this property.

13. Built-in Microwave Door Appearance

N/A

14. Oven

Dual ElectricOvens should be cleaned on a regular basis for proper burning.

15. Oven Operational

Yes

16. Oven Appearance/Condition

AttentionLoud fan noted at lower oven. Recommend further evaluation and repair by a qualified appliance specialist.

17. Counter Tops

AttentionThere are one or more cracked or chipped counter top tiles. Some consideration should be given to thereplacement of these tiles. These appear to be cosmetic. Recommend further evaluation and repair by a qualifiedspecialist.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 53 of 78

Page 54: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

18. Garbage Disposal

AttentionThe garbage disposal appears to be functioning, however, the unit is making a louder than normal noise. Rustwas noted at the right sink flange. Recommend further evaluation and repair by a licensed plumber.

The disposer's electrical cord is entering the bottom of the unit with out the benefit of a protective bushing. In

order to prevent accidental mechanical damage to the wires, a bushing should be installed by a qualified

specialist.

19. Lighting

AttentionThere one or more dead or missing bulbs located in the kitchen area. Recommend further evaluation and repairby a qualified specialist.

20. Woodwork Finishes

Satisfactory

21. Drawers/Doors

AttentionThe drawers located in the kitchen area do not have stops to prevent them from coming all the way out.Recommend installing drawer stops to prevent any health and safety issues. Recommend further evaluation andrepair by a qualified handyman.

22. Dishwasher

FunctionalThis inspection does not comment on things like minor rust, broken, bent or missing prongs on the racks. Fullcycle checks are often not possible in the time of this inspection; therefore, we cannot comment on the full extentof its functions or its ability to clean. In addition not all functions or cycles of the unit are tested. The average life ofa dishwasher is 8-12 years from the date of installation.

The dishwasher appears to function, however the unit appears to be older and may be nearing the end of itsuseable life. Recommend monitoring and repair or replacement as needed by a qualified specialist.

23. Trash Compactor

None

Fire Place/Wood Stove

1. Fire Place/Wood Stove General Statement(s)

Fire Place/Wood Stove General Statement(s)This is a non-invasive visual inspection of the fireplace or stove for obvious defects. The inspector is not afireplace or wood stove specialist. Unless mentioned in this report, the fireplace was not tested. This is inspectiondoes not cover code clearances and improper installation of inserts, wood stoves, or wood/gas burning fireplacesor their piping and flue materials. Mantles are not tested unless completely free of stored items. If additionalinformation and certification is desired, contact this inspection service.

2. Solid Fuel/Gas Logs/Gas Appliance

Wood Burning FireplaceThere are two wood-burning fireplaces in this home. This inspection is a general overview for obvious defectsvisible at the time of the inspection. Often times issues are not visible without a more invasive inspection. As anexample, the condition of the interior flue. Recommend a routine of yearly inspections, maintenance, andcleanings by a qualified fireplace specialist.

3. Exterior Chimney(s) Condition

Satisfactory

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 54 of 78

Page 55: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The visible portions of the chimney or stove pipe appeared to be in satisfactory condition. There were areas of thechimney that were not visible at the time of the inspection. This is only a visual non invasive examination. Aprogram of regular inspections by a chimney professional is recommended for the continued safe operation of thesystem. Recommend further evaluation and repair by a qualified specialist.

4. Flue Dampers

AttentionThe chimney flue damper located at the family room fireplace does not appear to work properly. The inspector

recommends contacting a chimney service professional to evaluate and make recommendations to repair or

replace the damper as needed.

5. Flue Condition

Not VisibleNot all areas of the chimney flue were visible. The inspector recommends having the fireplace systemprofessionally evaluated and cleaned as a preventive maintenance measure prior to the close of escrow. This isonly a visual non invasive examination. A program of regular inspections by a chimney professional isrecommended for the continued safe operation of the system. Recommend further evaluation and repair by aqualified specialist.

The inspector was unable to view the condition of the flue due to the design of the insert or damper. Recommendfurther evaluation by a qualified fireplace professional.

6. Rain Cap/Spark Arrestor

SatisfactoryA spark arrestor/rain cap on the top of a chimney should be inspected and cleaned on an annual basis to removethe buildup of soot.

7. Location

NotedThere are fireplaces located in the following rooms/areas: Living Room - Family Room

8. Firebox

AttentionMonitor, inspect, and clean fireplace on a regular basis.

There is a small amount of debris build up or stored items in the fireboxes. Not all areas were visible to inspection.Recommend cleaning and further evaluation by a qualified fireplace specialist.

There is a small amount of cracked or missing grout at the hearth located in the living room. Recommend furtherevaluation and repair by a qualified specialist as needed.

The fireplace opening at the living room fireplace is in need of attention. The following was noted:

There were NO doors or fire screen noted at the fireplace opening Recommend further evaluation and repair by aqualified specialist.

The brick/stone located at the front of the living room fireplace is painted. Paint is considered a combustible

material. This does not allow for the required 18" of non-combustible clearance around the unit. This constitutes a

fire hazard. Recommend further evaluation and repair by a qualified fire specialist.

Other Room(s)

1. Other Room(s) General Statement(s)

Other Room(s) General Statement(s)

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 55 of 78

Page 56: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Our inspection of the interior living space includes the visually accessible areas of walls, floors, cabinets andclosets, and includes the testing of a representative number of windows and doors, switches and outlets. We donot comment on common cosmetic deficiencies. We do not evaluate window treatments, move furniture, liftcarpets or rugs, empty closets or cabinets. We may not comment on previously repaired "spot patch" areas, nailpops, and cracks that appear around windows and doors, or which follow the lines of framing members and theseams of drywall and plasterboard. These cracks are a consequence of movement, such as wood shrinkage orcommon settling, and will often reappear if they are not correctly repaired. Contaminants, such as molds/mildews,as well as other contaminants that form from moisture penetrating carpet, covered cracks in floor slabs, as well asodors from pets or pests and cigarette smoke that can permeate porous surfaces, and which can be difficult toeradicate are outside this scope. However, inasmuch as the sense of smell adjusts rapidly, and the sensitivity tosuch odors is certainly not uniform, we recommend that you make this determination for yourself, and particularlyif you or any member of your family suffers from allergies or asthma, and then schedule whatever remedialservices may be deemed necessary before the close of escrow.

2. Location/Type

Interior RoomsThis section of the report encompasses the following rooms if they were present in this home. Not all homes arethe same. Your home may or may not include one, a few, or several of these rooms.

Living Room - Dining Room - Family Room - All Bedroom Areas - Bonus Rooms - Mud Rooms - Offices/

Dens - Sun Rooms - Loft Areas - Hallways - Kitchen - Laundry

3. Floors

AttentionThere are one or more chipped or cracked floor tiles located in the main entry. Recommend further evaluation andrepair by a qualified specialist is desired.

There are one or more visible gaps at the flooring located in the following areas:

Locations: - Living Room - Dining Room

Recommend sealing these areas to prevent moisture intrusion. Recommend further evaluation and repair by aqualified specialist.

There are one or more sections of damage or missing baseboard located in the following rooms:

Locations: - Family Room - Master Bedroom

Recommend repairing/replacing the baseboards. Recommend further evaluation and repair by a qualifiedhandyman.

Raised seams were noted at the floor covering material in the following areas:

Locations: - Living Room - Dining Room

This may indicate moisture penetration. Recommend further evaluation and repair by a qualified specialist.

There are stains located at the floor covering in the following areas:

Locations: - Dining Room

Recommend further evaluation and repair by a qualified specialist.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 56 of 78

Page 57: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the nationalstandards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialistfor more detailed information.

There are areas noted in the following rooms with uneven floors.

Locations: - Dining Room - Master Bedroom

Recommend further evaluation and repair by a qualified licensed contractor.

There are areas in the home with squeaky flooring. As an example, the floors noted in the following rooms:

Locations: - Loft - Stairway

There may be other areas in the home with squeaky flooring that were not identified. Recommend furtherevaluation and repair by a qualified licensed contractor.

4. Ceiling/Walls/Doors

AttentionThere appears to be one or more previously repaired areas as well as nail pops and drywall cracks on the ceiling/walls in the areas noted below.

Locations: - Living Room - Family Room - Bedroom Areas- Bathroom Areas- Loft

Recommend checking with the seller in this regard. Recommend further evaluation and repair by a qualifiedspecialist.

There are one or more moisture stains located at the drywall wall located in the following areas:

Locations: - Living Room

Recommend further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 57 of 78

Page 58: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Bubbled texture was noted at the wall located in the dining room and loft. Recommend checking with the mostrecent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by aqualified specialist.

Dining room Loft

There are one or more areas of the interior baseboards that are showing signs of stains. This was noted in the

following areas:

Locations: - Master Bedroom

Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommend

further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information

There appears to be uneven drywall located at the wall located in the loft. Recommend checking with the mostrecent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by aqualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 58 of 78

Page 59: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There are one or more areas of missing trim at the ceiling/walls located in the family room. Recommend replacingthe missing trim. Recommend further evaluation and repair by a qualified handyman.

5. Window(s)

AttentionThere are windows in the home that are in need of adjustment. The window(s) are more difficult to open/closethan typical or were stuck and could not be opened. One or more windows were located in the following areas:

Locations: - Living Room - Dining Room - Bedroom Two

Recommend further evaluation and repair by a qualified specialist.

The drywall or wood surrounding the window appears to be damaged. This was noted at one or more windows inthe following areas:

Locations: Loft

Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommendfurther evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 59 of 78

Page 60: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

6. Door(s)/Closet(s)

AttentionThe pocket door located in the family room is in need of attention or adjustment. The door is not functioningproperly. Recommend further evaluation and repair by a qualified handyman.

There are one or more family room bar and stairway area cabinet doors that are not closing properly. The hingesmay be sprung and in need of repair or replacement. Recommend further evaluation and repair by a qualifiedhandyman.

The entry and/or closet door(s) located in the following areas rub on the carpet or jamb.

Locations: - Master Bedroom - Bedroom Two

Recommend further evaluation and repair by a qualified specialist.

The closet door(s) located in the following rooms did not latch properly. The door or strike plate may be in need ofadjustment.

Locations: - Master Bedroom

Recommend further evaluation and repair by a qualified handyman.

There are one or missing door stops located at the bedroom one area. Recommend further evaluation and repairby a qualified handyman to prevent damage to the wall.

Bathroom(s)/Washroom(s)

1. Location(s)

NotedThese sections of the report encompasses the following bathrooms: Master - Hallway(s) - Half

2. Floor Cover

AttentionThere are one or more areas of the baseboards located in the half bathroom that are showing signs of stains andbaseboards located in the hall bathroom that are showing signs of swelling. At the time of the inspection therewas no moisture present. Loose baseboards noted. Recommend checking with the seller in this regard.Recommend checking with the most recent "Pest Report" for further evaluation and determinations. Recommendfurther evaluation and repair by a qualified specialist.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 60 of 78

Page 61: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information

Half bathroom Hall bathroom

There are one or more area with loose, cracked, or missing grout located at the tile floors in the the bathroomareas. Recommend further evaluation and repair by a qualified specialist.

3. Mildew Noted

N/ASome molds are known to produce toxins and toxic responses. Toxic mold detection and testing are NOT withinthe scope of a home inspection. This home inspector is not a qualified professional mold expert. Recommend thatinterested parties consider retaining a qualified professional for testing and evaluation prior to the close of escrow.

4. Basin(s)/Fixtures

AttentionThe sink faucet(s) located in the half bathroom is spraying water out the side of the strainer when turned on.Recommend further evaluation and repair by a qualified handyman.

The right hall bathroom sink appears to have low water flow. Recommend further evaluation and repair by a

licensed plumber.

5. Basin Drain

AttentionSealant putty was noted at half bathroom drain flange. Check with owner in this regard. No leak noted.

One or more of the sink stopper mechanisms located in the following bathrooms did not function properly or aremissing: master bathroom. Recommend further evaluation and repair by a qualified handyman.

6. Shower Fixtures

AttentionThe shower riser located in the master bathroom shower is loose. Recommend further evaluation and repair by a

licensed plumber.

7. Shower Head(s)

Satisfactory

8. Shower/Tub Enclosure(s)

Curtain

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 61 of 78

Page 62: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

9. Water Resist Cover Wall Cover

AttentionThere is loose, cracked, or missing grout noted at the shower(s) in the following bathrooms: Master bathroom

Recommend grout touch-up or repair to prevent moisture intrusion. Recommend checking with the most recent

"Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by a qualified

specialist.

The soap dish in the master bathroom shower is in need of attention. One or more cracks were noted in this area.

Damage caused by water seepage into the wall was not determined by this visual inspection. Recommend refer

to the most recent "Pest Report" for further evaluations and determinations. Recommend further evaluation and

repair by a qualified tile specialist.

There are one or more missing wall tiles located in the master bathroom. Recommend replacing the missing

tile(s). Recommend further evaluation and repair by a qualified specialist.

There appears to be one or more chipped or damaged shower wall tiles located in the master bathroom.

Recommend further evaluation and repair by a qualified professional.

10. Caulking - Water Exposed Area

FunctionalThe caulking along water exposed areas in the bathrooms appears to provide adequate protection. Caulkingaround bathtub, shower fixtures, tubs, floors, and around sinks should be maintained periodically to providecontinued protection.

11. Tub(s)

AttentionThe jetted tub(s) in the master bathroom(s) is/are not functioning properly. Recommend further evaluation and

repair by a licensed plumber.

There is a rust stain in the tub located in the hall bathroom. Recommend further evaluation and repair by a

qualified specialist.

12. Tub Fixtures

AttentionThe tub diverter spout located in the hall bathroom is not diverting all of the water from the spout to the

showerhead. Recommend further evaluation and repair by a licensed plumber.

13. Tub/Shower Drain(s)

FunctionalBathtub and shower drains may need periodic attention to remove clogs or other debris to improve flow. Anyoverflows present at the tubs were not tested as this piping system is not visible and the result of the test maycause damage if not properly connected. This is common area for leakage if the tub is overfilled. Interestedparties should contact a plumber for a more invasive inspection of the overflow connection.

14. Toilet(s)

AttentionCracks are an indication that the toilet has reached the end of its useful life and should be replaced before itleaks. Each toilet should be inspected periodically for indications of cracking in the toilet bowl, tank, and base.

The toilet located in the half bathroom appears to be filling slower than normal. Recommend further evaluationand repair by a licensed plumber.

The toilet or toilets in the following bathrooms were noted as loose: Master bathroom. Unseen damage may exist

due to this condition.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 62 of 78

Page 63: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Toilets should be kept secure to the floor in order to prevent leaks and mechanical damage. It is often necessary

to pull the toilet, inspect, and replace the wax ring on loose toilets. Recommend further evaluation and repair by a

licensed plumber.

The flush handle for the toilet located in the hall bathroom is not functioning properly. You must hold the handle to

get a full flush. Recommend further evaluation and repair by a licensed plumber.

15. Ventilation

FunctionalAll of the bathrooms in this home had a functional exhaust fan or window for passive ventilation.

It is recommend that all bathrooms be equipped with functional fans or windows for proper ventilation.

16. Heat

Functional

17. Window(s)

AttentionThere are one or more windows located in the bathroom area(s) that are in need of adjustment. The window(s)are more difficult to open/close than typical. Recommend further evaluation and repair by a qualified specialist.

18. Medicine Cabinet/Vanity

Attention

There are one or more stains on the wall below the only sink(s) located in the master bathroom. There were NO

leaks or moisture noted at the time of the inspection. Recommend checking with the seller in this regard.

Recommend further evaluation and repair by a qualified specialist.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

The drawers located in the master bathroom and hall bathroom areas do not have stops to prevent them fromcoming all the way out. Recommend installing drawer stops to prevent any health and safety issues. Recommendfurther evaluation and repair by a qualified handyman.

There is loose, cracked, or missing grout located at the bathroom vanity top in the hall bathroom. Recommendfurther evaluation and repair by a qualified specialist.

19. Ceiling/Walls/Doors

AttentionBubbled texture was noted at the ceiling/wall located in the master bathroom. Recommend checking with the

most recent "Pest Report" for further evaluation and determinations. Recommend further evaluation and repair by

a qualified specialist.

Plumbing

1. Plumbing General Statement(s)

Plumbing General Statement(s)This is a non-invasive inspection of the visible supply, waste and vent piping in this structure. The typical lifeexpectancy of metal piping is 50 years. The inspector recommends that homes equipped with galvanized and/orcast iron piping that are 10 years or older, have a licensed plumber perform an invasive inspection for theadequacy, condition and functionality to determine the remaining useful life of the plumbing system prior to theclose of escrow.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 63 of 78

Page 64: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Without being invasive or digging through insulation we try to identify the structure piping. Client should be awarethat if the structure piping was not visible due to the non-invasive nature of this inspection, the client shouldconsult with the seller/property owner. If the seller or property owner is not aware of the structure piping material,it is advised that the buyer contact a licensed plumber for further evaluation. Premature failure of the productsand/or their connection fittings have been reported with the "Kitec" & Zurn brand supply tubing/fittingsmanufactured between the mid 90's through mid 2000's. Older homes that have been remolded may also containthis piping. Recommend ascertaining the brand of structure piping prior to close of escrow.

There are government regulations that require homes in certain counties to be equipped with water-conservingplumbing fixtures based on things such as age, permits pulled, improvements, and/or transfer of property.

Note 1: As of January 1, 2017 all CA single-family residences built prior to January 1, 1994 must comply withthese requirements (permit or no permit) and homeowners are required to install water saving fixtures, if currentfixtures are out of compliance. This law will not affect commercial or multi-family properties until January 1, 2019.

Here are the rules:

*If a toilet is greater than 1.6 gpf, a 1.28 gpf toilet is required.

*If a shower head flows more than 2.5 gpm, a 2.0 gpm shower head is required.

*If a bathroom faucet flows more than 2.2 gpm, a 1.2 gpm faucet is required.

*If a kitchen sink faucet flows more than 2.2 gpm, a 1.8 gpm faucet is required.

These are minimum state requirements and some areas are more stringent. The inspector is not responsible foridentifying or testing the fixtures for flow rate. This inspection company does not look for nor report on the flowrate or conservation rate of any plumbing fixture in the home. Refer to the seller regarding the flow of the currentfixtures. Concerned parties should contact a licensed plumber for a more invasive inspection and determinationprior to close of escrow.

2. Size Service to Structure

3/4 Inch

3. Structure Pipe Material

CopperOther materials may have been used but were not visible at the time of the inspection. Recommend checking withthe seller in this regard. Recommend further evaluation and repair by a licensed plumber.

4. Waste Pipe Material

Plastic/ABSThe interior condition of the main waste lines cannot be determined visually and are outside the scope of thisinspection. This company runs clear water only and for a short period of time. Properties that are vacant or havebeen vacant for any period of time can experience blockage once the home has been occupied and debris andwaste are introduced into the system. We attempt to evaluate drain pipes by flushing every drain that has anactive fixture while observing its draw and watching for blockages or slow drains, but this is not a conclusive testand this method may not provide evidence of a nascent or intermittent problem. You can be sure that blockageswill occur, usually relative in severity to the age of the system, and will range from minor ones in the branch lines,or at the traps beneath sinks, tubs, and showers, to major blockages in the main line. The minor ones are easilycleared, either by chemical means or by removing and cleaning the traps. However, if tree roots grow into themain drain that connects the house to the septic system or public sewer, repairs or replacement could becomeexpensive. For these reasons, we recommend that you check with the sellers in regard to any past drainageproblems, or you may wish to have the main waste line video-scanned before the purchase of the residence.Additionally, you should obtain an insurance policy that covers blockages and damage to the main line.Recommend further evaluation and repair by a licensed plumber.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 64 of 78

Page 65: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There have been cracking problems noted with several brands of ABS pipe that were manufactured around 1984through 1990. This inspection does not look for or note the manufacture of the ABS piping in this structure. Inaddition, this inspection company does not include information on any current or past manufacture recalls of anyproduct or equipment in the home. Not all of the pipe manufactured during this period by these companies isconsidered defective. At some point additional information on the ABS class action law suits was available atwebsites like "www.abspipes.com" and others. These sites have since been shut down. If this house was builtbetween 1984-1990 and you have concerns in regards to ABS waste piping, it is recommended that you contact aqualified licensed plumber for additional information and further evaluation.

5. Pipe Rumble Noise

No

6. Surge Bangs

No

7. Encrustations Evident

No

8. Mineral Deposits

No

9. Water Pipe Insulation

NoHot or cold water pipes that run through unheated or un insulated areas such as attics and sub structure shouldbe insulated to protect against freezing or energy loss. Recommend further evaluation and repair by a qualifiedspecialist.

10. Evidence of Leaks

NoAn inspection of the readily accessible sections of the plumbing water supply, waste pipes, faucets and fixturesshould occur regularly to identify any visible leaks prior to causing any substantial damage. A program of regularinspections by the homeowner should be considered.

11. Interior Water Flow

AttentionThe interior water flow in the house is low when one or more faucets are turned on. Recommend further

evaluation and repair by a licensed plumber.

12. Exterior Water Flow

Functional

13. Pressure Readings Interior/Exterior

AttentionThe inspector noted a pressure reading of approx. 25 or less psi at the front yard hose bib. This reading is low as

typical water pressure readings are usually between 40-70 psi. High pressure can strain plumbing fittings and

fixtures and over time may lead to leaks. Low pressure can cause many issues within the home. Recommend

checking with the seller or the local utility to determine if a pressure regulator is present and can be adjusted as

this falls outside the scope of this inspection. Recommend further evaluation and repair by a licensed plumber.

14. Soft Water System

None

15. Filter System

None

16. Drainage and Sump Pumps

N/A

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 65 of 78

Page 66: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Structure

1. Structure General Statement(s)

Structure General Statement(s)In regards to the interior, exterior, attic and sub structure of this dwelling, this inspection does not address anypast or present conditions relating to animals, rodents or other household pests, pest activity, severity ofinfestation or the damage caused thereby unless otherwise noted in this report. This is a state licensed andregulated field of work that requires a Branch 2 license with the state of California. This inspection company is notlicensed in this field. Interested or concerned parties should contact a licensed pest service/exterminator forfurther evaluation and any needed pest control prior to the close of escrow.

This is not a compliance inspection, installation inspection, or certification of compliance with current or pastgovernmental codes or regulations of any kind. It is not determined as part of this inspection, weather or not anypermits were obtained or required during original construction, or during any updated construction, additions, orremodeling. Items like ceiling height and outlet height fall outside the scope of this inspection. Depending onjurisdiction, ceiling heights will typically run between 7' and 71/2'. If this structure has ceilings that are lower than7' you may wish to consult a contractor or the local building department.

2. Approximate Year Built

Approximate Year Built 1972

3. Bedroom(s)

Bedroom(s) 3

4. Bathroom(s)

Bathroom(s) 2.5

5. Description

NotedThe property inspected appears to be a Wood Framed Home

The following areas of this property were inspected: Interior and Exterior

If this property inspection was marked above as an "Interior Only" inspection, the following sections of the homeand any items related to these sections of the home were not inspected or included in this report unless otherwisementioned. Roof - Structure Perimeter Exterior - Exterior Structure - Site Concrete and Paving - Patios, Decks,Porches, and Covers - Utility Services - Raised Foundation, Basement, or Sub Structure, Detached Garage,Detached Laundry Areas - Attic - Pool - Spa.

NOTE: If you are unclear in ANY way of what was inspected or not inspected in regards to this property, you havean obligation to please contact this inspection company prior to the close of escrow for clarification. Items notmentioned in this report should be considered not inspected or included.

6. Remodel/Modernization Evident

YesIt appears that a number of updates and modifications have been made to the original structure at some timeduring the life of the structure. As an example, one or more rooms appear to have been added to the originalstructure, one or more ceilings in the structure appear to be lower than seven feet, the size of the home appearsto have been increased from the original structure size. The inspector recommends questioning the seller todetermine if any of the updates were performed during their ownership, whether any permits were needed and ifso obtained, as well as who performed the updates. In addition, requesting any warranty information on materialsor workmanship is recommended. It is not determined as part of this inspection, weather or not any permits wereobtained or required during original construction, or during any updated construction, additions, or remodeling.Checking for permits falls outside the scope of this inspection. Recommend consulting with the seller, your RealEstate Agent, or the city prior to the close of escrow.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 66 of 78

Page 67: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

This is not a compliance inspection, installation inspection, or certification of compliance with current or pastgovernmental codes or regulations of any kind. Items like ceiling height, door opening/hallway width, and outletheight fall outside the scope of this inspection. Depending on jurisdiction, ceiling heights will typically run between7' and 71/2'. If this structure has ceilings that are lower than 7' you may wish to consult a contractor or the localbuilding department.

7. Repairs Evident

Yes

The inspector noted repairs one or more items/systems in the home. As an example, repair to the furnacecontrolling the right side of the home.

The inspector recommends questioning the seller to determine if any of the repairs were performed during theirownership and whether any permits were needed and if so obtained. In addition, questioning the seller on whoperformed the repairs, if any warranty on the workmanship or materials have been provided and if so, are theytransferable. Recommend checking with the seller in this regard prior to the close of escrow.

8. Smoke Detector(s)

AttentionNOTE: Additional Smoke Detector Requirements

MUST READ PRIOR TO OCCUPYING HOME

Smoke detector requirements have changed several times since the early seventies. Local codes are constantlychanging. Smoke detectors are now required in all bedrooms, the hallway or areas outside of the bedrooms, andon each level of the home if multiple levels are present.

These additional requirements are noted in California Law SB745 but are not determined as part of thisinspection:

1. Any smoke detector that is solely battery powered must contain a non-removable battery that is

rated to last 10 years.

2. All old smoke detectors that are solely battery powered must be replaced with those that contain

a sealed battery that is rated to last 10 years.

3. All smoke detectors powered by 120VAC or battery must comply with the provisions of having a

label showing the date of installation and manufacturer.

4. All smoke detectors must be approved and listed by the Office of the State Fire Marshal pursuant

to Health and Safety Code Section 13114.

These are a few examples. It is often not possible to determine these requirements without removing the units.This inspection does not report on whether or not smoke detectors are hard wired, battery operated, or both. Thepresent units are ONLY tested with the "test button," if present, to determine if the units alarm/siren is functioning.This is NOT an evaluation to determine if the units are capable of detecting smoke. Smoke detector units greaterthan 10 years of age should be replaced as they are considered to be at the end of their service life.

Since 1980 the number of fire related deaths have been cut roughly in half by the use of proper functioning smokedetectors. It is very important that you the buyers or a handy man for the buyers re-test all of the smokedetectors and insure all of the rooms mentioned above still have a unit when first moving in, and every monthafter to identify the functional operation of each detector. All detectors should have a more invasive examinationfor SB745 compliance.

For more information or other important details please research California Law : SB745 and Health and Safety

Code 13113.8

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 67 of 78

Page 68: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There are one or more required areas in the home with no smoke detector. As an example, the upstairs area

Smoke detectors are required in all bedrooms, the hallway or areas outside of the bedrooms, and on each level of

the home if multiple levels are present. Recommend further evaluation and repair by a qualified handyman.

Recommend replacing or installing smoke detector units in all of the required rooms and areas mentioned above

prior to moving in. There are additional requirements in regards to smoke detectors that fall outside the scope of

this non invasive inspection. (See NOTE: "Additional Smoke Detector Requirements") Smoke detector units

greater than 10 years of age should be replaced as they are considered to be at the end of their service life. The

inspector recommends testing the units and insuring all of the rooms mentioned above still have a unit when first

moving in, and every month after to identify the functional operation of each detector.

9. Alarm/Security System

None

10. Carbon Monoxide Detector(s)

AttentionThe upstairs of this structure is not equipped with carbon monoxide detectors. Carbon monoxide detectors are

recommended on each level and at seperate sleeping areas in all homes where there is a possible source of CO

present in the home, such as gas burning appliances, water heaters, and heating systems. Some jurisdictions

now require installation of CO detectors in homes. The inspector recommends that one or more CO detectors with

battery backups be installed in the structure according to jurisdictional and manufacturer recommendations.

11. Furniture/Storage

AverageFurnishings and storage items in this home are average for an occupied residence. There were furnishings and/orstored items inside the home that limited the inspector's ability to visually inspect all areas of this home. Notationis made that the inspector does not move belongings in order to perform the inspection. Re-inspecting the homeprior to closing escrow is often recommended as issues may become visible once the structure is vacated.

12. Party or Lot Line Wall

No

13. Floor Structure

Concrete slabRadiant flooring systems fall outside the scope of this inspection and were not tested or inspected. Recommendchecking with the seller in this regard. Recommend further evaluation and repair by a qualified specialist.

14. Ceiling Structure

Wood Framing

15. Roof Structure

Roof Trusses

16. Interior Stairway Structure

AttentionThe inspector noted that some of the handrails or railings at the interior stairway and landing are loose. Thehandrails should be tightened down and made secure for safety reasons. Recommend further evaluation by aqualified specialist.

There was lower than normal head clearance noted at one or more areas of the stairway. Use caution in theseareas. Recommend checking with local code. Recommend further evaluation and repair by a qualified specialist.

The only step located at the loft/upstairs area has a shorter than normal drop off. This may be considered a triphazard. Recommend further evaluation and repair by a qualified licensed contractor.

17. Fire Sprinkler System

None Present

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 68 of 78

Page 69: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

18. Insulating Rating Evident

No

19. Insulation

Not Visible in WallsWall insulation not verified. Refer to attic and raised foundation category.

20. Asbestos Noted

N/AThe scope of this inspection does not include an asbestos in materials sampling inspection. Asbestos has beenknown to cause certain health hazards. Additional information on the health hazards of asbestos in a home canbe acquired from the Puget Sound Air Pollution Control Agency (PSAPCA) and/or the Environmental ProtectionAgency (EPA).

21. Lead

N/AThe scope of this inspection does not include a lead in materials sampling inspection.

Heating System

1. Heating System General Statement(s)

Heating System General Statement(s)There are many internal components to an HVAC system that are not visible to this non invasive inspection. AnHVAC system may appear to be functioning properly but may have internal issues that have failed or are failing.The life expectancy of an HVAC system is 13-20 years from the date of installation, although there are exceptionson both sides. HVAC systems may fail unexpectedly and should be monitored on a regular basis for repair orreplacement. This inspection does determine if the system is properly sized for the home, the proper number ofvents in the home, or any air flow testing The inspector recommends that a qualified HVAC technician perform aservice cleaning, tune-up, and a review of the entire HVAC system, including the heat exchanger, prior to theclose of escrow.

If the heating or cooling system(s) are not original to the home, the person(s) who installed the equipment arerequired to follow municipal regulations; such as pulling installation permits and having the work approved by thelocal building authorities. Inspecting these systems for the adherence of these regulations is outside the scope ofour limited visual inspection. You should inquire with the seller to provide an installation permit and anydocuments they may have which may transfer a material or work warranty. We do not endorse any heating orcooling systems which have been installed without a permit. In the event the seller can not produce a installationpermit you should have the local authorities review the system prior to close of escrow.

2. System Type(s)/Info

NotedThe Right Side Furnace is a Gas Fired Unit.

The Manufacture of the unit was Carrier

The Year Built was 2019

The age of the unit is approximately; 1 years old.

The temperature at the outlets was between 118 and 127

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 69 of 78

Page 70: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was faded, please check with the seller to determine if they know the age of the

unit or have it further evaluated by a qualified specialist.

The average life expectancy of a Furnace is 13-20 years although there are exceptions on both sides. If this unitis over 10 years old, this inspection company automatically recommends that a qualified HVAC technicianperform a service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

The Left Side Furnace is a Gas Fired Unit.

The Manufacture of the unit was Carrier

The Year Built was 1998

The age of the unit is approximately; 22 years old.

The temperature at the outlets was between 96 and 112

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was faded, please check with the seller to determine if they know the age of the

unit or have it further evaluated by a qualified specialist.

The average life expectancy of a Furnace is 13-20 years although there are exceptions on both sides. If this unit

is over 10 years old, this inspection company automatically recommends that a qualified HVAC technician

perform a service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

3. Location(s)

Attic

4. Thermostat Type

Electronic Programmable

5. Thermostat Location(s)

NotedThere are thermostats located in the following rooms/areas: Right Hallway - Left Hallway

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 70 of 78

Page 71: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

6. Thermostat Condition

Functional

7. On/Off Check

Satisfactory

8. Operation Noise

Satisfactory

9. Filter Condition

SatisfactoryDisposable filters should be replaced on a routine basis (3 to 4 times per year.) Re-useable and electostatic filtersshould be cleaned periodically to maintain proper air flow.

10. Electronic Filter System

No

11. Vents/Flues

Satisfactory

12. Ducts/Returns/Radiators

Attention

Many areas of the ducting are not visible to inspection during this non invasive inspection. Interested partiesshould contact a qualified HVAC technician for a thorough evaluation.

Ducting types and standards are constantly changing. This inspection does not determine the efficiency of theduct work in this home nor compare the ducting material to current products. Interested parties should contact alicensed HVAC contractor for further inspection and recommendations/upgrades. We recommend having an airduct cleaning company service the heating system (ducts, registers, furnace/air conditioning, etc.) periodically.Routine/annual maintenance is required to the provide a functional and safe environment. Note: In some areas ofthe California, it is now required by the state to have your heating ducts tested for air loss upon a heater or airconditioner being replaced. In cases of excessive loss, replacement of the ducts will be necessary. For moreinformation on this issue, refer to http://www.energy.ca.gov/title24/changeout/2005-08-02_NEW_DUCT_REQUIREMENTS.PDF.

There are a one or more service ducts located in the right hallway, master bedroom, and bedroom one that are

not blowing at the same temperature as the rest of the ducts. The inspector was unable to visually inspect the

ducting due to the design and build of the heater platform and home. Recommend further evaluation and repair

by a qualified HVAC technician.

13. Non-Heated Area(s)

None

14. Service Notes/Filter Size

None VisibleService Overdue: There does not appear to be any visible posted notes attached to the heater(s). This unit for

the left side of the home is older and may be in the final third of it's usable life. The inspector recommends that a

qualified HVAC technician perform a service cleaning, tune up, and review of the entire HVAC system, including

the heat exchanger, prior to the close of escrow. Heaters need annual service and cleaning as a health and

safety consideration as well as for preventative maintenance reasons. This inspection does not provide any

information on recalled equipment that may be in the home or verification of the appropriate units and proper

sizing of the HVAC system. Please check with the appropriate manufacture for any recalls/recommendations.

Air Conditioning

1. Air Conditioning General Statement(s)

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 71 of 78

Page 72: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

Air Conditioning General Statement(s)Verification of the appropriate units and proper sizing of the HVAC system is outside the scope of this inspection.Ducting types and standards are constantly changing. This inspection does not determine the efficiency of theduct work in this home nor compare the ducting material to current products. Interested parties should contact alicensed HVAC contractor for further inspection and recommendations/upgrades. Swamp Coolers fall outside thescope of this inspection and were not tested or inspected unless otherwise mentioned in the report.

Important Note: As per the US Environmental Protection Agency, R22 refrigerant (known as Freon) will becomeillegal in the United States on January 1, 2020. After that date, R22 refrigerant can no longer be manufactured orimported into the US. After R22 becomes illegal on January 1, 2020, older R22 air conditioning systems becomeobsolete and may no longer be repaired when the repair would require adding refrigerant to the system. Exceptfor some simple electrical issues, many types of emergency repairs do require recharging refrigerant. In general,owners of R22 air conditioners may have 3 choices:

1. Do nothing until your system breaks down.

2. Retrofit or convert your old R22 equipment to use an existing refrigerant.

3. Replace your system proactively.

If the heating or cooling system(s) are not original to the home, the person(s) who installed the equipment arerequired to follow municipal regulations; such as pulling installation permits and having the work approved by thelocal building authorities. Inspecting these systems for the adherence of these regulations is outside the scope ofour limited visual inspection. You should inquire with the seller to provide an installation permit and anydocuments they may have which may transfer a material or work warranty. We do not endorse any heating orcooling systems systems which have been installed without a permit. In the event the seller can not produce ainstallation permit you should have the local authorities review it prior to close of escrow.

2. Type of Units

NotedThe First Air Conditioning system is a Split A/C.

The Manufacture of the unit was Carrier

The Year Built was 1998

The age of the unit is approximately; 22 years old.

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was covered with a blanket, please check with the seller to determine if they know

the age of the unit or have it further evaluated by a qualified specialist.

The average life expectancy of a A/C is 13-20 years although there are exceptions on both sides. If this unit is

over 10 years old, this inspection company automatically recommends that a qualified HVAC technician perform a

service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

The Second Air Conditioning system is a Split A/C.

The Manufacture of the unit was Carrier

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 72 of 78

Page 73: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

The Year Built was 1998

The age of the unit is approximately; 22 years old.

If there was a visible specifications label, a photo with the information has been provided below. If no system

information was available or it was covered with a blanket, please check with the seller to determine if they know

the age of the unit or have it further evaluated by a qualified specialist.

The average life expectancy of a A/C is 13-20 years although there are exceptions on both sides. If this unit is

over 10 years old, this inspection company automatically recommends that a qualified HVAC technician perform a

service cleaning, tune-up, and a review of the entire HVAC system, prior to the close of escrow.

3. Location of Units

Right Side of Structure

4. Systems Operation

Not TestedThis is a general visual inspection. This inspection was non exhaustive. Recommend further evaluation by aqualified HVAC technician for a more comprehensive evaluation of the system due to the many internalcomponents that were not inspected at this time.

The unit was not tested as severe damage can occur to air conditioning compressors if they are turned on when

the outside temperature is below 60 degrees Fahrenheit or has been below 60 degrees for an extended period of

time in the last 24 hours. Recommend checking with the seller in regard to the operation of the unit. Recommend

further evaluation and repair by a qualified HVAC technician prior to the close of escrow.

5. Service Records/Last Service

Not AvailableService Overdue: There does not appear to be any visible posted notes attached to the A/C system. These units

are older and may be in the final third of their usable life. The inspector recommends that a qualified HVAC

technician perform a service cleaning, tune up, and review of the entire HVAC system prior to the close of escrow.

A/C systems need annual service and cleaning as a heath and safety consideration as well as for preventative

maintenance reasons. This inspection does not provide any information on recalled equipment that may be in the

home or verification of the appropriate units and proper sizing of the HVAC system. Please check with the

appropriate manufacture for any recalls.

6. Energy Source

Electrical - 240 Volts

7. Condensing Coil Condition

Satisfactory

8. Power Disconnect Location

At or Near the Unit

9. Condensate Drain System

Not Tested - WinterDue to the A/C unit not being run at the time of the inspection, the condensate drain was not tested.

Attic

1. Attic General Statement(s)

Attic General Statement(s)

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 73 of 78

Page 74: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

This inspection does not look for or address any past or present conditions relating to animals, rodents or otherhousehold pests, pest activity, severity of infestation or the damage caused thereby in the attic or any other areaunless otherwise noted in this report. This is a state licensed and regulated field of work that requires a Branch 2license with the state of California and this inspection company is not licensed in this field. We are NOT a licensedpest inspection company. Interested or concerned parties should contact a licensed pest service/exterminator forfurther evaluation and any needed pest control prior to the close of escrow.

In accordance with industry standards, we will not attempt to enter an attic that has less than thirty-six inches ofheadroom, is restricted by ducts, or in which the insulation obscures the joists and thereby makes mobilityhazardous, in which case we will inspect the attic as best we can from the access point. We do not disturb ormove any portion of the attic insulation for inspection, and it may well obscure water pipes, electrical conduits,junction boxes, exhaust fans, pest activity and other components. When access is restricted hidden defects maybe present and we strongly recommend you ask the sellers to disclose all information concerning any previousattic maintenance, repairs or roof leaks that may have occurred.

2. Access Location/Type

Upstairs Hallway Closet

3. Access

Attention

The Access provided to the attic area appears to provide for adequate access to the area.

The inspector noted possible pest/rodent activity in the attic area. This inspection company is not a licensed pestcontrol company and does NOT inspect for pest or household rodent activity. Pest activity falls outside the scopeof this inspection. It is unknown whether or not the pest activity is current and/or how severe the pest activity maybe. Pest activity can range from minor intrusion to major infestation. Interested or concerned parties shouldcontact a licensed pest operator/exterminator for further evaluation and any needed pest control prior to close ofescrow.

4. Attic Evaluated By

Limited Entrance

5. Inaccessible Areas

YesThere are inaccessible structure cavities in the attic, as well as areas of the attic which are inaccessible due toreduced clearance or obstruction by structural members, heavy amounts of insulation, and/or mechanicalapparatus.

6. Ventilation

Whole House Fan

Passive ventilation in the attic area is important. Periodic inspections of the attic area for proper ventilation isrecommended.

If there is a powered gable vent fan in the attic, the fan was not tested or inspected as it falls outside the scope ofthis inspection. Recommend checking with the seller in regard to the use and functionality of the gable vent fan.

There is a "Whole House" fan installed in this home. These units fall outside the scope of the inspection, however,the unit was on/off tested at the time of the inspection. The unit appeared to function properly. The unit appears tobe powered by the living room entry light switch and then controlled from the fan switch located near the unit.Recommend checking with the seller in this regard. In addition, checking to see if any manuals, warranties orother information on operating the unit properly. The inspector recommends routine maintenance inspections.

7. Insulation

Noted

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 74 of 78

Page 75: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

There appears to be approximately 12 or more inches of blown in fiberglass insulation in the attic. 10 or moreinches of fiberglass batts insulation was noted. The insulation is generally evenly spread throughout the visibleportions of the attic; however there are a few areas that have been disturbed by prior trades persons.

Attic insulation standards are constantly changing. This inspection does not determine the insulation rating in thishome nor compare the insulation to current standards. We only note what is present in the attic. Interested partiesshould contact a licensed insulation contractor for further inspection and recommendations/upgrades.

8. Duct Work Piping

SatisfactoryMany areas of the ducting are not visible to this non invasive inspection. Interested parties should contact aqualified HVAC technician for a thorough evaluation.

Ducting types and standards are constantly changing. This inspection does not determine the efficiency of theduct work in this home nor compare the ducting material to current products. Interested parties should contact alicensed HVAC contractor for further inspection and recommendations/upgrades.

9. Framing condition

Functional

10. Exposed Rafters/Sheathing

Yes

11. Roof Inspect from Underside

Attention - Moisture StainsThe attic was entered and the underside of the accessible areas of the roof were inspected. The inspection

identified moisture stains on the wood joists and sheathing that would indicate the roof system has leaked at

some time in the past. There has been no substantial rain in the recent days prior to this inspection and the

inspector was unable to verify that the roof system currently has an active leak condition. The inspector would

recommend questioning the home seller to identify if they are aware of the history of any leaks that may have

occurred during their or prior to their ownership. In addition, re-inspecting the attic during rainy periods is

recommended to ensure that the roof system is providing its intended service. Recommend further evaluation and

repair by a licensed roofing contractor.

Mold/mildew sampling and or testing is not within the scope of the home inspection as outlined by the national

standards. Certain types of mold/mildew may cause a health hazard. Recommend contacting a certified specialist

for more detailed information.

12. Light Thru

No

Slab Foundation

1. Off Sets (Heaving)

Satisfactory

2. Level/Gradation

N/ADue to furnishings and floor coverings, there is limited visual access to determine any abnormal floor grade.

3. Moisture/Dampness

N/ASee "Cracks/Separations" Category below for comment.

4. Cracks/Separations

N/A

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 75 of 78

Page 76: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

5. Footings/Sills

N/ADue to this type of foundation, there is very limited to no visual inspection access. The perimeter is the only areavisually accessible; slab foundation design is such that proper installation of anchor bolts can not be verified.

Detached Garage

1. Size

Multi-car w/shop

2. Roof Material

Tile

3. Roof Condition

Functional

4. Gutters/Down Spouts

AttentionThere is a small amount of debris build up in the gutters at this time. The inspector recommends cleaning the

gutters for preventive maintenance considerations. Recommend further evaluation and repair by a qualified

specialist.

Any amount of debris can clog the gutters, down spouts, and/or drain system if not cleaned out. Cleaning the

gutters on an annual basis is recommended for proper care and maintenance of the gutter system. This can also

help reduce the spread of neighborhood and local wild fires. Installing gutter screen over the gutters will reduce

the debris build up and the need for frequent cleaning in the fall and winter. Gutter screen can be purchased at

your local hardware or home improvement center.

5. Exterior Siding

AttentionThe exterior siding, trim and sheathing on the detached garage are in need of attention. There are one or more

areas that are showing signs of wood deterioration. Recommend checking with the most recent "Pest Report" for

further evaluation and determinations. Recommend further evaluation and repair by a qualified specialist.

There appeared to be an improperly installed flashing/moisture barrier installed at the rear exterior of the

detached garage. The siding material behind the barrier was not visible at the time of inspection. Recommend

further review and evaluation by a qualified specialist.

6. Vegetation Clear From Structure

NoVegetation growing up against the exterior surface material can create issues. When present, vegetation shouldbe kept trimmed at least 6-12 inches away from the structure to eliminate a common avenue for pest infestationand damage to the exterior structure material.

There is vegetation growing up against the exterior surface material. All vegetation should be trimmed at least6-12 inches away from the structure to eliminate a common avenue for pest infestation and damage to theexterior structure material. Recommend further evaluation and repair by a qualified specialist.

7. Electrical Service

See "Electrical" Section

8. Garage Door(s)

AttentionThe door leading from the garage to the exterior is showing signs of wear and deterioration. Recommend

checking with the most recent "Pest Report" for further evaluation and determinations. Recommend further

evaluation and repair by a qualified specialist.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 76 of 78

Page 77: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

9. Door Seal(s)

Functional

10. Automatic Opener(s)

AttentionNOTE: Beginning on July 1,2019 S.B. 969 requires an automatic garage door opener that is manufactured forsale, offered for sale or installed in a residence to have a battery back up function that is designed to operatewhen activated due to an electrical outage. (This law does not require that the existing automatic opener(s)installed in this home have to be replaced at this time.) This company does not inspect for or report on whether ornot the unit(s) in this home are equipped with battery back ups. Recommend checking with the seller or a garagedoor specialist in this regard.

The garage door opener is powered via an extension cord. Extension cords are for temporary power supply only.

Recommend installation of a permanent outlet to provide power in this area. Recommend further evaluation by a

qualified electrician.

11. Springs/Mount

Functional

12. Safety Operation, Opener

Functional

13. Foundation/Framing

Satisfactory

14. Rafter/Beams

Functional

15. Lighting

Functional

16. Insulation

Satisfactory

17. Floor/Foundation

AttentionMost of the garage was inaccessible to inspection due to the amount of items stored there. A condition may existthat was not visible at the time of the inspection. Re-inspecting the garage area after the home is vacated butbefore the close of escrow is recommended as issues may become visible once the structure is vacated.

18. Evidence of Moisture Penetration

AttentionThe are one or more areas located in the garage showing signs of efflorescence. Efflorescence is caused bymoisture/vapor migrating through the concrete/block bringing soluble salts to the surface of the concrete. This isevidence of past moisture. Recommend further evaluation and repair by a qualified specialist especially if theproblem persists or worsens.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 77 of 78

Page 78: Property Address: Inspector: Company: Tanryn Business ... · construction, additions, or remodeling. Though some codes may be referenced, this inspection reflects the opinion of the

19. Cabinets/Shelving

N/AIf present, the garage area work bench(es) and shelve(s) were not inspected as they fall outside the scope of thisinspection. Recommend checking with the seller in this regard.

20. Work Benches

N/AIf present, the garage area work bench(es) and shelve(s) were not inspected as they fall outside the scope of thisinspection. Recommend checking with the seller in this regard.

21. Evidence of Insects

N/AOutside scope of this inspection.

This inspection does not address any past or present conditions relating to animals, rodents, insects or otherhousehold pests, pest activity or the damage caused thereby inside or outside of the home unless otherwisenoted in this report. Interested parties should contact a licensed pest service/exterminator for further evaluationand any needed pest control.

Home Inspection Details(Italicized comments also appear in the summary report)

Client/Site: John Benz 6948 Gibson Canyon Rd, Vacaville, CA 95688 Workorder #: 040220JDTanryn Business Group, INC dba WIN Home Inspection Sierra (916) 256-4374WINspect v2.2.902 © 2020 WIN Home Inspection

Page 78 of 78