SAFETY INTERLOCKS IN CRUDE HEATERS USING PLC BHARAT PETROLEUM CORPORATION LTD., KOCHI REFINERY DEPARTMENT OF INSTRUMENTATION COCHIN UNIVERSITY OF SCIENCE AND TECHNOLOGY KOCHI – 682 022 AZEEM SIDHIQUE KP 90012047 MUHAMMED SALIH P 90012052 SAJNA BEERAN A 90012061 SHAHEEM TM 90012064 SHAMIL AHAMMAD K 90012065 THANSEEM K 90012071

project_presentation-Original - wht_theme

Embed Size (px)

Citation preview

Page 1: project_presentation-Original - wht_theme

SAFETY INTERLOCKS IN CRUDE HEATERS USING PLC

BHARAT PETROLEUM CORPORATION LTD.,KOCHI REFINERY

DEPARTMENT OF INSTRUMENTATION COCHIN UNIVERSITY OF SCIENCE AND TECHNOLOGY

KOCHI – 682 022

AZEEM SIDHIQUE KP90012047

MUHAMMED SALIH P90012052

SAJNA BEERAN A90012061

SHAHEEM TM90012064

SHAMIL AHAMMAD K90012065

THANSEEM K90012071

Page 2: project_presentation-Original - wht_theme

OVERVIEW Introduction Process Involved In Industry Different Units Crude Distillation Unit Programmable Logic Control Intrinsic Safety Barriers Interlocking System Tripping Conditions Parameter Description CH21 Check Record For Shutdown Systems PLC Ladder Diagram Conclusion References

Page 3: project_presentation-Original - wht_theme

INTRODUCTION

Interlock system - vital role in the safe shutdown of the plant during hazard situations or emergencies

Helps prevent a machine from harming its operator or damaging itself. Prevents one element from changing state due to the state of another element. For an example, interlocking system avoids over pressurization of the furnace - ID fan failure,

trip the heater. Immediate action need to be taken for the safe shutdown of the plant during emergencies. Heater operation requires monitoring of many variables. If variables exceeds a certain limit - chance for the heater explosion. Parameters sensed using various sensors. Output of PLC - ON/OFF voltage is given to actuator. This output - close or open the valve – controls fuel flow to the heater - operation is tripped.

Page 4: project_presentation-Original - wht_theme

Process Involved in Refinery₪ Kochi Refinery - crude oil processing capacity 9.5 MMTPA₪ Processes - 30% of Indigenous and 70% Imported crude oils₪ Crude oil transported in ships to Kochi - received through Single Point Mooring (SPM) facility₪ Can handle Very large Crude Carriers (VLCC) - capacities up to 3.0 Lakh Tons₪ First processed in Crude Distillation Unit - heated up to around 360 to 380oC₪ Fractionated in a distillation column - lighter fractions : LPG, Naphtha, Kerosene and Diesel

separated.₪ Products routed to storage locations after cooling to atmospheric temperature.₪ LPG treated using Di-Ethanol Amine (DEA) - remove impurities.₪ Part of the Naphtha - processed in the Aromatics Block - produce Benzene, Toluene and SBPS

(Special Boiling Point Spirit).₪ Part of the Kerosene treated in KHDS - produce Aviation Turbine Fuel (ATF), Mineral

Turpentine Oil (MTO).₪ Diesel from the CDU processed in DHDS unit.₪ Remaining heavier portion - distilled in a Vacuum Distillation Unit (VDU) separate Vacuum Gas

Oil (VGO) and Vacuum Residue (VR) as major fractions.

Page 5: project_presentation-Original - wht_theme

₪ VGO - processed in FCC unit - heavier molecules broken down - produce LPG, Gasoline (also called Motor Spirit or Petrol) and Diesel.

₪ Vacuum Residue (VR) from VDU - routed to Biturox Unit - produce Bitumen or to Vis-Breaker Unit (VBU) - produce Furnace Oil (FO).

₪ VR can be directly routed to LSHS (Low Sulphur Heavy Stock – fuel used in Boilers, Power Plants, etc.) pool if the crude oil - low Sulphur content (less than 0.5 wt.%).

₪ Sulphur Recovery Unit (SRU) recovers Sulphur from the gases produced.₪ Refinery operates Gas Turbine (GT) - capacity of 22.0 MW , Steam Turbine Generator (STG) -

17.8 MW and Turbo Generator (TG) - 2.5 MW.₪ Steam requirement of refinery - 8 boilers and 2 Waste Heat Boilers.₪ A new GT of 34 MW capacity - additional power requirement of CCR and VGO HDS units.₪ Effluent Treatment Plants (ETP) - liquid effluent from the process units and other off site areas₪ Treated effluent - meeting the MINAS (Minimum National Standards) discharged to inland

rivers.₪ Other Utilities and Off-site facilities - tankages flare system , connected pipelines - installed in

refinery – match requirements of processing, storage and products dispatch.

Page 6: project_presentation-Original - wht_theme

Different Units

Crude Distillation Unit (CDU)

Fluidized Catalytic Cracking Unit (FCCU)

Diesel Hydro De-Sulphurization Unit (DHDS)

Continuous Catalyst Regeneration Unit (CCR)

Captive Power Plant (CPP)

Page 7: project_presentation-Original - wht_theme

Crude Distillation Unit (CDU)

₪ Two crude distillation units; CDU-I and CDU-II.₪ Primary distillation of crude oil occurs in crude distillation unit (CDU).₪ Products of CDU : LPG, Naphtha, Diesel, Kerosene, Amine, Light Vacuum Gas Oil and Heavy

Vacuum Gas Oil.₪ First processing of unit in virtually all petroleum refineries.₪ The CDU distills the incoming oil into various fractions of different boiling ranges, each of

which then processed further in the other refinery process units. The CDU is often referred to as atmospheric distillation because it is operated slightly above the atmospheric pressure.

₪ Comprises series distillation columns separates crude into several fractions namely refinery gas, naphtha, kerosene, diesel.

₪ Vacuum residue given to the Feed Preparation Unit (FPU).

Page 8: project_presentation-Original - wht_theme

Overview of CDU-II

Page 9: project_presentation-Original - wht_theme

₪ Preheater₪ Desalter₪ Prefractionator₪ Naphtha Stabilizer₪ Crude Heater CH-21₪ Burner₪ Stack Damper₪ Forced Draft Fan And Induced Fan Draft₪ Fuel Oil, Fuel Gas And Steam Supply₪ Balancing Atmospheric Heater (CH22)₪ Atmospheric Distillation Column (CV21)₪ Vacuum Heater – CH223₪ Vacuum Column (CV27)

Overview of CDU-II

Page 10: project_presentation-Original - wht_theme

Preheater

₪ Crude from storage pumped to CDU II plant at a pressure of 5.0 to 11.0 kg/cm2 and temperature of 300C.

₪ Split into two parallel trains through flow ratio control valves on individual preheat trains 1A and 1B.

₪ Preheat exchangers consists of products.₪ Heat of products used to heat crude.₪ Crude heat exchanger train 1A and 1B are then combined.₪ Crude streams have temperature of 125.60C/127.90C then moves to crude Desalter for removal of

salts and water.₪ Consists of crude charge pumps which pumps the crude to Desalter.

Page 11: project_presentation-Original - wht_theme

Desalter₪ Process unit that removes salt from the crude oil.₪ Salt is dissolved in water in the crude oil, not in the crude oil itself.₪ First process in crude oil refining. ₪ Salt content after desalter measured in PTB - pounds of salt per thousand barrels of crude oil. ₪ Another specification is Basic sediment and water.₪ Most frequent salts - calcium, sodium and magnesium chlorides.₪ If not removed from the oil several problems arise in the refining process. ₪ High temperatures occur downstream in process could cause water hydrolysis which can

corrosive hydrochloric acid.₪ Sand silts and salt cause deposits and foul the heat exchangers.₪ Sodium, arsenic and other metals can poison catalysts.₪ At a preheat temperature 200–250◦F water is injected into crude – dissolve salt.₪ Mixture Desalter drum contains electrostatic precipitator.₪ Separated by means of electrostatic precipitation. ₪ Water from the drum sent to sour-water stripper to be cleaned before disposal to the oily water

sewer.

Page 12: project_presentation-Original - wht_theme

₪ The crude is desalted and leaves at 190 F through set of exchanges, then into crude charge furnace and leaves at 600 F and finally into the crude unit distillation column.

₪ Works by mixing raw crude oil with water in a mix valve with a high differential pressure.

₪ Causes water and oil to form an emulsion with the salt dissolved in the water phase.

₪ Emulsion is broken in Desalter by use of gravity, heat, electrical energy and chemical additives.

₪ After desalter, crude heated to around 198.240C in another preheater and then pumped to Prefractionator.

Page 13: project_presentation-Original - wht_theme

Prefractionator₪ Feed enters the Prefractionator column CV 271, operates at a top pressure of approximately 2.4

– 3.6 Kg/Cm2g.₪ Column overhead pressure is controlled by split range pressure control.₪ With higher pressure, gases from overhead column is released to heater CH-21 or flare to

maintain desired pressure and at low pressure, fuel gas is admitted to overhead column to maintain the desired pressure.

₪ The pre topped crude flow at crude pump discharge is routed to CH-21/CH-22 pass flow control.

₪ The crude pump CP-225 A/B is provided with independent tube oil system.₪ Each pump has : reservoir, two tube oil pumps, one water cooler, one flow transmitter from

which low flow switch is generated.₪ Flow low switch activated – then spare lube oil automatically pump and crude pump CP-225

will trip.₪ Crude is transferred to Naphtha Stabilizer and Crude Heaters (CH-21/CH-22).

Page 14: project_presentation-Original - wht_theme

Naphtha Stabilizer

₪ Unstabilized naphtha from Prefractionator overhead reflux drum (CV-280) pumped to the Naphtha stabilizer CV-26 through Prefractionator overhead product pumps.

₪ Stabilizer column has 36 trays with feed entering on the 18th tray₪ The overhead products condensed in stabilized overhead condenser.₪ Stabilized Naphtha products from stabilizer column bottom are routed on stabilizer column

bottom level control.₪ Stream is then combined with Atmospheric overhead.₪ Unstabilized naphtha from atmospheric distillation column is pumped to naphtha stabilizer

section for separation of stabilized overhead vapors.₪ Condensed to recover LPG which is treated in caustic and amine treating unit.₪ Stabilized naphtha is further separated into light, medium and heavy naphtha.

Page 15: project_presentation-Original - wht_theme

Crude Heater (CH-21)

₪ Crude heaters are of twin cell cabin type (CH21 + CH22).₪ Fed to the heaters through four passes.₪ Furnace casing crude heater lined with refractory materials and ceramic fibers in inside – forms

combustion chamber.₪ Radiant section of the heater houses 152 numbers of 6 inch OD bare tubes - arranged

horizontally in four passes.₪ Convection section - top of radiant section - increase thermal efficiency.₪ Crude from PHT3 split into two, 70% of total to CH21 and 30% goes to the CH22.₪ Heaters have four passes arranged in parallel.₪ Flow through each pass regulated by FC valves (IFV 1401 to 1404).₪ Each pass has 20 tubes.₪ Pressure gauge & temperature gauge provided at convection outlet of each pass.₪ Two rows of (6 each) retraceable soot blowers provided in the convection section.

Page 16: project_presentation-Original - wht_theme

₪ Heating coils come out from bottom of radiation section in 4 parallel passes and join with transfer line where crude from CH22 joins.

₪ Partially vaporized crude is then routed to CV 21.

Page 17: project_presentation-Original - wht_theme
Page 18: project_presentation-Original - wht_theme

Forced Draft Fan and Induced Draft Fan

₪ FD fan suck air from atmosphere and is given to air preheater.₪ ID fan suck flue gas from stack creating negative pressure inside the stack and flue gas is given

to air preheater.₪ In air preheater heat recovered from hot flue gas is used to preheat the from the atmosphere -

increase efficiency of heater.₪ Based on working of ID fan and FD fan, heaters classified into four :

Balanced draft : Both ID and FD fans usedForced draft : Only FD fan usedNatural draft : Both ID and FD fans not usedInduced draft : Only ID fan used

₪ Suction temperature of FD fan 370C and for ID fan 2500C and motor is HITACHI 980 RPM motor.

Page 19: project_presentation-Original - wht_theme

Burner

₪ John Zink gas and oil combination burner.₪ Fire light or heavy fuel oil with steam at a constant

pressure.₪ Each burner have individual wind box to which air from

the APH is routed through inlet damper got vanes.₪ Each burner provided with electrically ignited pilot

burner.

Page 20: project_presentation-Original - wht_theme

Stack damper

₪ Stack damper used to direct flue gas to ID fan.₪ Goes to open condition when ID fan goes out of working.

Fuel oil, Fuel gas and Steam supply

₪ Fuel oil and fuel gas supply are provided to the burner.

₪ Steam provided to vaporize the fuel oil supply for increasing the efficiency.

Page 21: project_presentation-Original - wht_theme

Atmospheric Distillation Column (CV21)

₪ vertical cylindrical vessel with an overall height of 51.45 m.₪ Two sections - bottom stripping section of 6 trays.₪ Upper section of 41 trays.₪ Trays and valves from 1 to 36 are made of stainless steel 410 and from 37

to 47 made of Monel.₪ Has 4 side draws namely heavy naphtha (HN), ATF/MTO, light gas oil

and heavy gas oil all of which are drawn through side strippers.

Page 22: project_presentation-Original - wht_theme

Vacuum Heater – CH223₪ single cell balanced type draft heater.₪ Reduced crude oil from bottom of atmosphere distillation column at 345.5/355.5oC enters four

passes of vacuum furnace CH223.₪ FIC 3401A/ 3402A/ 3403A/ 3404A controls flow of RCO in each pass.₪ Emergency/ decoking steam connections provided to each pass at downstream flow control

valves for purging/ decoking the coils with MP steam.₪ Coil steam also provided to each pass in radiation section to maintain flow velocity in coils if

needed.₪ Pressure indicator PI3522 with PAL alarm is provided.₪ If pressure falls below required minimum pressure PALL-3519 alarm will be generated on DCS

will be actuated on interlock I3505 to close SDV 2201 and open SDV 2201A to cut off hot well off gas flow to heater.

₪ Flame arresters (XX – 3501/ 3502) are provided in hot well off gas flow to heater.

Page 23: project_presentation-Original - wht_theme

₪ Heat carried away by flue gas after convection is utilized for preheating air required for combustion by APH.

₪ Combustion chamber houses radiant section tubes.₪ Convection section provided at top of radiation section serves to increase thermal efficiency of

the furnace by removing further heat from flue gas.₪ RCO enters at top of convection zone in 4 paralleled passes.₪ Flow through each pass controlled by flow control valves FIC 3401A/ 3402A/ 3403A/ 3404A.₪ Tubes are made of 9 Cr, 1 Mo alloy steel materials.₪ Coils come out of bottom of convection zone and return to the radiation zone.₪ Four coils from radiation section of combustion chamber joins 50 inch header that expands to 56

inch and carries partially vaporized feed to vacuum column. TI’s are provided at outlet of each coil (TI3407/ 3408/ 3409/ 3410) with TAH and TAL alarm on DCS.

Page 24: project_presentation-Original - wht_theme

Vacuum Column (CV27)

₪ Vacuum column is packed column for facilitating lower pressure drop across the column.₪ Has 3 different diameters - top section of 600mm diameter, middle 7250mm and bottom section

5000mm diameter.₪ Bottom keg section has diameter of 1800mm, 44640mm tall.₪ Tower is made of carbon steel with 3mm thick lining of SS-410 on inner walls up to height of

32210mm from column bottom, rest of height it is provided with 3mm corrosion allowance.₪ Column is provided with 4 sections.₪ RCO from vacuum heater is fed to vacuum column at flash zone above tray #5. Flash zone

pressure - 39mmHg and temperature of 391/ 403.3oC.₪ Vaporized portion enters flash zone of column along with stripped light ends from bottoms,

rises up column and is fractionated into 4 side stream products in 5 packed sections.

Page 25: project_presentation-Original - wht_theme

INTRINSIC SAFETY BARRIERS

₪ Protection technique for safe operation of electrical equipment in hazardous areas by limiting energy available for ignition.

₪ Done by limiting the energy available for ignition.₪ This approach simplifies circuits and reduces installation cost over other protection methods. ₪ Measuring instruments in hazardous area may be designed without any large capacitors or

inductors that could discharge in a spark.₪ Safety barriers ensure that, no matter what accidental contact occurs between instrument circuit

and outside power sources, no more than approved voltage or current enters hazardous area.

Page 26: project_presentation-Original - wht_theme

Hazardous area designation

Any location in which a combustible material is or may be present in the atmosphere in sufficient condition to produce an ignitable mixture is designated as an hazardous area.

Types of hazardous atmosphere

Class I – Gas or vapor Class II – Dust Class III – Fiber or flying (no group designation)

Page 27: project_presentation-Original - wht_theme

Division / Zones

North America IES Std.

Division Method Zone Method

Ignitable mixture present continuously

Division 1 Zone 0 Zone 0(Zone 20 – Dust)

Ignitable mixture present intermittently

Division 1 Zone 1 Zone 1(Zone 21 – Dust)

Mixture is not normally present

Division 2 Zone 2 Zone 2(Zone 22 – Dust)

Page 28: project_presentation-Original - wht_theme

Hazardous areas are grouped according to their ignition property

Typical Gas IES Gas Group North American Group Minimum Ignition Energy

Acetylene IIC A 20 µJ

Hydron IIB + H2 B 20 µJ

Ethylene IIB C 66 µJ

Propane IIA D 100 µJ

Methane *

Metal dust E

Coal dust F

Grain dust F

Fiber G

Page 29: project_presentation-Original - wht_theme

Enclosure protection IP RatingProtection against solid ingress Protection against water ingress

0 - No protection 0 – No protection1 – Protection against contact by large surface ( i.e. the hand)

1 – Protection against drops of condensed water ( i.e. harmful effect)

2 – Protection against contact by fingers or medium sized solid bodies.

2 – Liquid drops at 15o from vertical

3 – Contact by tools, wires, objects > 2.5 mm or small solid bodies.

3 – Rain up to 60o from vertical

4 – Contact by tools, wires, objects > 1mm or small sized bodies.

4 – Splashing from any direction

5 – Complete protection against contact, ingress of dust not in harmful quantities.

5 – Water from any direction under stated condition.

6 – Complete protection against contact. Protection against ingress of dust.

6 – Protection against heavy sea water under stated conditions.

  7 – Protection against water immersion under stated conditions of pressure and time.

  8 – Protection against indefinite immersion in water under specific pressure.

Page 30: project_presentation-Original - wht_theme

Temperature Classification

T1 4500 C T3A 1800 C

T2 3000 C T3B 1650 C

T2A 2800 C T3C 1600 C

T2B 2600 C T4 1350 C

T2C 2300 C T4A 1200 C

T2D 2150 C T5 1000 C

T3 2000 C T6 850 C

Page 31: project_presentation-Original - wht_theme

Enclosure Ratings

Rating Description1 Indoor, general purpose. Protection against contact.2 Indoor, general purpose. Dust proof and protection against dirt and water.

3 Outdoor, protection against wind, dust and rain.3R Outdoor, protection against rain.3S Outdoor, protection against wind, dust, rain and ice.4 Indoor / outdoor, protection against dust, rain, water and ice.4X Indoor / outdoor, protection against corrosion, dust, rain, water and ice.

6 Indoor / outdoor, protection against water, ice and temporary submersion.

6P Indoor / outdoor, protection against water, ice and prolonged submersion.

7 Indoor use, hazardous class – I, division – I, group A,B,C.9 Indoor use, hazardous class – II, division – I, group E,F,G.12/12K Indoor use, protection against dirt dripping water and non-corrosive liquids.

13 Indoor use, protection against dust, dirt, water, oil and non-corrosive liquids.

Page 32: project_presentation-Original - wht_theme

I to P Converter

₪ Converts an analog signal (4-20mA) to a proportional linear pneumatic output (3-15psi). ₪ Delivers a high performance. ₪ Provides a reliable repeatable, accurate means of converting ₪ At lower end of coil is a flapper valve that operates against a precision ground nozzle to

create a back pressure on servo diaphragm on booster delay. ₪ Input current flows in coil and produces a force between coil and flapper valve, which

controls servo pressure and output pressure. ₪ Zero adjustment of unit is made by turning a screw that regulates distance between flapper

valve and air nozzle. ₪ Span adjustment is made by varying a potentiometer, which shunts input current past coil.

Page 33: project_presentation-Original - wht_theme
Page 34: project_presentation-Original - wht_theme

Solenoid Valve

₪ Electro mechanically operated valve.

₪ Most frequently used control elements in fluidics.

₪ Valve is controlled by an electric current through a solenoid

₪ Tasks are to shut off, release, dose, distribute or mix fluids.

₪ Solenoids offer fast safe switching, high reliability, long service life, good medium compact ability of the materials used, low control power and compact design.

FS = P A = Pπd2/4

Page 35: project_presentation-Original - wht_theme

Pressure Switch

₪ Switch that closes an electrical contact when a certain set pressure has been reached on its input.

₪ Designed to make contact either on pressure rise or on pressure fall.

₪ Adjustable, by moving the contacts or adjusting tension in counter balance spring.

₪ Industrial pressure switches may have a calibrated scale and pointer to show the set point of the switch

₪ Differential range around its set point in which small changes of pressure do not change the state of the contacts.

Page 36: project_presentation-Original - wht_theme

Flow Switch₪ Determines flow rate above or below a certain value. ₪ Setpoint can be fixed or adjustable. ₪ When the setpoint reached, response can be the actuation of an electric or pneumatic circuit. ₪ When the flow switch is actuated, it will stay in that condition until the flow rate moves back

from the setpoint by some amount. ₪ Difference between the setpoint and the reactivation point is - switch differential. ₪ Differential can be fixed or adjustable.

Page 37: project_presentation-Original - wht_theme

Temperature Switch

₪ Temperature switches are on-off devices, ₪ Characteristic is that measurement, set point, and control

functions are all combined into a single instrument. ₪ The switch may actuate at its set point on rising (high) or falling

(low) temperature

Page 38: project_presentation-Original - wht_theme

Combustible Gas Monitor

₪ Designed to detect the presence and measure the concentration of combustible gases and vapors on a continuous basis.

₪ Methods of detecting the presence of combustible gases and vapors can utilize the phenomena of catalytic combustion, electrical resistance, luminosity, thermal conductivity, infrared (IR) absorption, or gas ionization.

₪ Widely used is catalytic combustion method₪ Limits are;

∆ Lower Explosive Limit (LEL)

∆ Upper explosive limit (UEL)

∆ Flash point

Page 39: project_presentation-Original - wht_theme

₪ Suitable for measurements of ppm to % levels of oxygen in a gas or mixture of gases.

₪ Determines oxygen concentration using the conductivity of a zirconia ceramic cell.

₪ Zirconia ceramic cell only allow oxygen ions to pass through at high temperatures.

₪ Within an instrument the zirconium cell is mounted in temperature controlled furnace with necessary electronics to process the signal from the detection cell.

₪ Measurements are displayed directly via a digital display as oxygen concentration over the range 0.01 ppm to 100%.

₪ O2 analyzer is kept at the top portion of the heater to check the efficiency of the heater.

Zirconia Oxygen Analyzer

Page 40: project_presentation-Original - wht_theme

Orifice Plate

₪ An orifice plate is a device used for ∆ Measuring flow rate∆ Reducing pressure ∆ Restricting flow

₪ Either volumetric or mass flow rate may be determined, depending on the calculation associated with the orifice plate.

₪ Uses the same principle as a venture nozzle, namely Bernoulli’s principle.₪ States that there is relationship between the pressure of the fluid and the

velocity of the fluid.₪ When the velocity increases, the pressure decreases ; vice versa.

Page 41: project_presentation-Original - wht_theme

₪ It consists of two dissimilar conductors that contact each other at one or more spots, where a temperature differential is experienced by the different conductors.

₪ It produces a voltage when the temperature of one of the spots differs from the reference temperature at other parts of the circuit.

₪ The principle behind the operation is Seebeck Effect

Thermocouple

Page 42: project_presentation-Original - wht_theme

Thermocouple Types and Comparison

Page 43: project_presentation-Original - wht_theme

Interlocks are provided for safe guarding in abnormal condition

Plays a vital role in the safe shutdown of the plant during emergencies.

Used to prevent undesired states in a finite state machine.

Safety Interlocks

Page 44: project_presentation-Original - wht_theme

₪ Today’s industries have more complex process are larger and are operated closer to their safety limits than in the past.

₪ Plants are more likely to became unsafe, thus having a potential for causing greater damage

₪ This results in costly shutdown.

₪ So design of a plant safety system with their associated alarm is extremely important

Need of Interlocks

Page 45: project_presentation-Original - wht_theme

 SYSTEM TRIPPING CONDITIONS

The PLC trip fuel oil and fuel gas when safety shutdown is neededThe fuel oil and fuel gas supply is controlled by solenoid valve for safety shutdown.

Page 46: project_presentation-Original - wht_theme

Conditions for Fuel Oil Trip

Fuel oil pressure low

Total feed flow

Pass flow in any of four is low

Atmospheric column pressure high

Stack temperature high

Atomizing steam pressure low

FD fan discharge pressure low

ID fan suction pressure low

LEL high

Arch pressure high

Emergencies stop is pressed.

Page 47: project_presentation-Original - wht_theme

Condition for Fuel Gas Trip

Fuel gas pressure low

Total feed flow

Pass flow in any of four is low

Atmospheric column pressure high

Stack temperature high

FD fan discharge pressure low

ID fan suction pressure low

LEL high

Arch pressure high

Emergencies stop is pressed.

Page 48: project_presentation-Original - wht_theme

PROGRAMMABLE LOGIC CONTROLLER

₪ Digital computer for automation of electromechanical processes₪ Designed for multiple inputs and output arrangements₪ PLCs have,

₪ Extended temperature ranges, ₪ Immunity to electrical noise₪ Resistance to vibration and impact

₪ Machine control programs are stored in battery backed up or non volatile memory₪ Hard real time system

Page 49: project_presentation-Original - wht_theme

Ladder Logic

₪ Graphical diagram based on the circuit diagrams of relay logic hardware

₪ Primarily used to develop software for programmable logic controllers 

₪ Programs in this language resemble ladders, with two vertical rails and a series of horizontal

rungs in between

₪ Seen as a set of connections between logical checkers (contacts) and actuators (coils).

₪ If path can be traced between the left side of the rung and the output, through asserted (true or "closed") contacts the rung is true and the output coil storage bit is asserted (1) or true

₪ If no path can be traced, then the output is false (0) and the "coil" by analogy to electro-mechanical relays is considered "de-energized“.

Page 50: project_presentation-Original - wht_theme

₪ Ladder logic has contacts that make or break circuits to control coils₪ Each contact corresponds to the status of a single bit in the PLC's memory₪ Ladder program refer any number of times to the status of a single bit, equivalent to a relay with

an indefinitely large number of contacts.₪ Inputs to the programmable controller from physical devices such as pushbuttons and limit

switches via an integrated or external input module represent the status of internal storage bits which may be generated elsewhere in the program

₪ Typical coil representation—( )— A regular coil, energized whenever its rung is closed.—(\)— A "not" coil, energized whenever its rung is open.—[ ]— A regular contact, closed whenever its corresponding coil or an input which controls it is energized.—[\]— A "not" contact, closed whenever its corresponding coil or an input which controls it is not energized.

Page 51: project_presentation-Original - wht_theme

Basic PLC Components

Processor (CPU)

Rack or mounting

Input assembly

Output assembly

Power supply

Programming Unit

Page 52: project_presentation-Original - wht_theme

Rack Assembly

₪ In smaller PLC systems - components may be contained in a single housing or "brick“.

₪ Smaller systems are sometimes referred to as "bricks" or "shoebox" PLCs.₪ Racks are assembled inside the marshalling room.₪ Most medium to large PLC systems are assembled such that the individual

components

CPU

Input/output Assembly Power Supply

Page 53: project_presentation-Original - wht_theme

Processor (CPU)

₪ Size and type of CPU will determine o Programming functions size of the application logic availableo Amount of memory availableo Processing speed o Flexibility of the PLC

₪ Overall speed is expressed in term of how fast the PLC will scan a given among of memory. ₪ This measure is called as scan rate, typically expressed in milliseconds per thousand words of

memory.

Page 54: project_presentation-Original - wht_theme

Input/output Assembly

₪ Inputs carry signals from the process into the controllero Ex: Input switches, Pressure sensors, Operator inputs, etc.

₪ Outputs are the devices that the PLC uses to send changes out to the field.

₪ These are the actuator of the PLC, can adjust motors, lights, relays, pumps, etc.

₪ Many types of inputs and outputs can be connected to a PLCo Analog and Digital

₪ Digital input/output - Binary change - ON/OFF

₪ Analog input/output change continuously over a variable rangeo Ex: Pressure, Temperature and Potentiometer.

Page 55: project_presentation-Original - wht_theme

Power Supply

₪ Need Internal DC current to operate the processor logic circuitry and input/output assemblies.

₪ Common power levels used are 24V DC or 120 V AC. ₪ Basic function is to convert field power into more

suitable, for electronic devices that comprise the PLCs.

Page 56: project_presentation-Original - wht_theme

₪ PLC is programmed using a specialty programmer or software on a computer that can load and change the logic inside.

₪ Memory of a PLC can be of two types namely: - Volatile Non-Volatile 

₪ Volatile memory loses its contents when power supply is turned OFF, whereas non-volatile does not.

₪ PLC use non-volatile memory from a majority of user’s memory because the program must be retained during the power down cycle.

₪ It is imported that all non-volatile memory in a PLC uses some of the error checking to ensure that the memory has not changed.

₪ The other memories used in PLCs are:  Battery Back up CMOS RAM EPROM Memory EEPROM Memory

Programming Device

Page 57: project_presentation-Original - wht_theme

₪ Some special processes need to work permanently with minimum unwanted down time.

₪ Necessary to design a system which is fault-tolerant and capable of handling the process with faulty modules.

₪ In such cases to increase the system availability in the event of hardware component failure, redundant CPU or I/O modules with the same functionality can be added to hardware configuration for preventing total or partial process shutdown due to hardware failure.

Redundancy

Page 58: project_presentation-Original - wht_theme

PROGRAMMABLE LOGIC CONTROLLER

Page 59: project_presentation-Original - wht_theme

Brand-name of a line of Factory Automation Equipment manufactured by Rockwell Automation The company was founded in 1903 as the Compression Rheostat Company by Dr. Stanton Allen

and Lynde Bradley with an initial investment of $1,000

In 1910 the firm was renamed Allen-Bradley Company

In February 1985,  Rockwell Automation purchased Allen-Bradley for $1.651 billion

Page 60: project_presentation-Original - wht_theme

Software for Allen-Bradley PLC Programming

Page 61: project_presentation-Original - wht_theme

BPCL KR PLC Control Room

Page 62: project_presentation-Original - wht_theme

Sl. No Service Parameters Shutdown Set Value Fuel Oil Solenoid Fuel Gas Solenoid Any Other System Remarks

1 PSHH 1611,1612,1613CV21 O/H PRESSURE HIGH

2.8 Kg/Cm2 + 0.8 Kg/Cm2 (Fill Head) = 3.6 Kg/Cm2

SOV 1401, 1402Tripped

SOV 1403Tripped

CH22, SOV 3301,3102Tripped

2/3 Logic

2 CF21 SUCTION LELGAS MONITOR (CF 21 LEL-1)

60% SOV 1401, 1402Tripped

SOV 1403Tripped

CH22, SOV 3301,3102Tripped

 

3 EMERGENCY TRIP FIELD/CR PB.3011 A/B(CH21 & CH22)

- SOV 1401, 1402Tripped

SOV 1403, 1404Tripped

CH22, SOV 3301,3102Tripped

 

4 FSL-1405,1406,1407,1408CH21 PASS FLOW LOW LOW

45 T/Hr. SOV 1401, 1402Tripped

SOV 1403Tripped

CH22, SOV 3301,3102Tripped

 

5 PSLL 1424 FUEL GASPRESSURE FLOW

0.3 Kg/Cm2 - SOV 1403Tripped

-  

6 PSLL 1427 FUEL OIL PRESSURE LOW

3.5 Kg/Cm2 SOV 1401,1402Tripped

- -  

7 PDALL 1477 FO/STM DP FLOW 0.7 Kg/Cm2 SOV 1401,1402Tripped

- -  

8 PSLL 1428 ATOMISING STM PRESSURE LOW

3.5 Kg/Cm2 SOV 1401,1402Tripped

- -  

9 FSLL 3004, 3005 CF21-A/BFLOW LOW

28 T/Hr. SOV 1401,1402Tripped

SOV 1403Tripped

CH22, SOV 3301,3102Tripped

 

10 FSLL 3003 NEW TOTAL FD FLOW LOW (FT 3001+3002)

28 T/Hr. SOV 1401,1402Tripped

SOV 1403Tripped

CH22, SOV 3301,3102Tripped

 

11 PSHH 3009ID SUCTION PRESSURE HIGH

-50mmWC - - STACK DAMPER OPENED  

12 TSHH 3004 ID SUCTION TEMPERATURE HIGH

2750C - - STACK DAMPER OPENED  

13 TSHH 1436/1436 B CH 21 ARCH TEMPERATURE HIGH

10000C SOV 1401,1402Tripped

SOV 1403, 3201Tripped

CH22, SOV 3301,3102Tripped

 

14 PSHH 3004 CH21 ARCH PRESSURE HIGH

5mH2O - - STACK DAMPER OPENED  

15 COMBUSTION AIR FLOW/PRESSURE LOW

FSLL 3002/PSLL3012,3006

22 T/Hr.5mmH2O

SOV 1401,1402Tripped

SOV 1403, 3201Tripped

STACK DAMPER OPENED 2/3 Logic

CH21 CHECK RECORD FOR SHUTDOWN SYSTEM

Page 63: project_presentation-Original - wht_theme

Fuel oil pressure

Fuel gas pressure

Total feed flow low

Atmospheric column pressure

Stack temperature high

Atomizing steam pressure low

FD fan discharge pressure low

ID fan discharge pressure low

Arch pressure high

Parameter Considered

Page 64: project_presentation-Original - wht_theme

PLC Ladder Programming

Page 65: project_presentation-Original - wht_theme
Page 66: project_presentation-Original - wht_theme
Page 67: project_presentation-Original - wht_theme
Page 68: project_presentation-Original - wht_theme
Page 69: project_presentation-Original - wht_theme
Page 70: project_presentation-Original - wht_theme
Page 71: project_presentation-Original - wht_theme
Page 72: project_presentation-Original - wht_theme

CONCLUSION

₪ Safety interlock is a prerequisite for the safer operation of a heater.₪ Earlier days safety systems made use of relays to implement safety interlocks.₪ We designed a PLC based system for the CH21 crude heater.₪ It is a digital system with redundancy of software.₪ Using PLC based system we can consider more number of interlocks than that we can

consider while using relay logic.₪ Considering the conditions of safety we developed ladder logics; which are then implemented

as software. ₪ This system is more reliable and faster than relay based system.

Page 73: project_presentation-Original - wht_theme

References

[1] BPCL Kochi Refinery workers manual CDU-II[2] https://bharatpetroleum.com/our-business/refinery/kochi-refinery/history.aspx[3] https://bharatpetroleum.com/our-business/refinery/kochi-refinery/process.aspx[4] Instrument engineers’ handbook: Process measurement and analysis _ Bela G Liptak _ Chilton book company[5] Instrument engineers’ handbook: Process control _ Bela G Liptak _ Chilton book company[6] Handbook of Petroleum processing _ David S. J. Jones, Peter R. Pujado _ Springer science and business media[7] Refining process handbook_Surinder Parkash_Gulf professional publishing, 2003[8] Fundamentals of Petroleum Refining _ Mohamed A Fahim ,Taher Al-Sahhaf, Amal Elkilani _ Elsevier