Upload
ahmad-butt
View
9
Download
0
Embed Size (px)
Citation preview
1
Chapter 1
Introduction
1.1: Introduction
Motors are critical components for electrical utilities and process industries. A
motor failure can result in the shutdown of a generating unit or production line.
The operators of motors or electrical drive systems are under continual pressure to
reduce maintenance costs and prevent unscheduled downtimes, which result in lost
production and financial income Early detection of fault within a motor prior to
complete failure provides an opportunity for maintenance to be performed on
scheduled routine without loss of production. This has arises the need for
condition based maintenance strategies i.e. monitoring the condition of motors and
planning the maintenance based on an indication that is a problem about to occur.
Condition monitoring implies monitoring various parameters of a machine in order
to assess the health of the machine. Condition monitoring is equivalent to
cardiogram analysis of the human heart. A cardiogram assesses the state and health
of the human heart. Similarly the various parameters measured during the
condition monitoring of the electrical equipment assess the health of the machine.
Many operators now use online condition based maintenance strategies in parallel
with conventional planned maintenance schemes. This has reduced unexpected
failures, increased the time between planned shutdowns and reduced operational
cost. During past fifteen years there has been substantial amount of research into
the creation of new condition monitoring techniques. New methods have been
developed which are now being used by the operators and research is continuing
2
with the development of new and alternative online diagnostic techniques. This
basic objective of this work is to diagnose the different types of motors faults
online through processing and analysis of motor current. This technique is often
called "current signature analysis"
1.2: CURRENT SIGNATURE ANALYSIS
Signature analysis is the procedure of acquiring the motor current and voltage
signals, performing signal conditioning and analyzing the derived signals to
identify the various faults. Motor current acts as an excellent transducer for
detecting fault in the motor. Spectrum analysis of the motor's current and voltage
signals can hence detect various faults without disturbing its operation. Current
signature analysis involves the measurement of electric current around any one
phase either through clamp on meters or through CT's. This current is then
transformed into its frequency spectra and analyzed for detection of fault.
Information on the application of specific condition monitoring techniques in
industry is not available and evidence of diagnosing problem via reference to
actual on site case histories are also not considered. There is no clear distinction
made between monitoring techniques, which are at the R & D stage in comparison
to those which are being successfully applied in industry. It is a fact that the
operator of induction motor requires evidence of the successful application of
monitoring systems to assist him in their selection of appropriate systems. An
operator must treat each induction motor drive as a unique entity and the potential
failure modes, fundamental causes, mechanical load characteristics and operational
conditions have all to be taken into consideration when a condition monitoring
3
system is being selected. The focus has been on the use of condition monitoring
using Electrical signature analysis technique.
Figure 1.1: Current Signature with No bar Failure
Figure 1.2: Current Signature with bar Failure
1.3: METHOD OF MEASUREMENT
The method of measurement involves measurement of electric current around any
one phase or three phases. Current can be measured with the help of current
transformers. The current signal is conditioned. DAQ (Data acquisition device
USB 6009) digitizes the signal to permit the time and frequency spectra for
4
analysis. The time varying current signal is then transformed into frequency
domain through FFT algorithm.
1.4: FAULTS IN INDUCTION MOTOR
The most prevalent faults in Induction Motor are briefly categorized as:
Rotor Faults (10%)
Bearing Faults (41%)
Eccentricity Faults (12%)
Stator Faults (37%)
The surveys indicate that in general, failures in electrical machines are dominated
by bearing and stator faults with rotor winding problems being less frequent.
1.4.1: ROTOR FAULT
Each individual rotor bar can be considered to form a short pitched single turn,
single-phase winding. The air gap field produced by a slip frequency current
flowing in a rotor bar will have a fundamental component rotating at a slip speed in
the forward direction with respect to rotor and one of equal magnitude that rotates
at the same speed in the backward direction. With symmetrical rotor, the backward
component sums to zero. For a broken bar rotor, however the resultant is non-zero.
The field, which rotates at slip frequency backward with respect to the rotor, will
induce EMF on stator side that modulates the main frequency component at twice
slip frequency.
5
The measurements on totally enclosed IHP motor with cast rotor was undertaken to
verify the presence of broken bar signals predicted by the above analysis. The
motor was fed with 3ph-balanced supply through measurement panel. The line
current was recorded through the non-inductive shunt. The signal was then given to
Oscilloscope for the processing. Initially the no load current and no load losses
were also calculated and then the motor was operated at rated output. The slip and
efficiency of the motor were calculated. The same experiments were repeated first
for motor with one broken bar, two broken bar and three broken bars. With one
broken bar, there is increase in the magnitude of LSB 1.The ratio also drops down
to 31 indicating the fault within rotor. The constant losses and no load current of
the motor also increase. There is also decrease in the efficiency of the motor. With
increase in the bar failure there is increase in magnitude of LSB1 and ratio and
efficiency goes on decreasing. The slip, constant losses and no load current go on
increasing.
1.4.2: BEARING FAULTS
The relationship of the bearing vibration to the stator current spectrum can be
determined by remembering that any air gap eccentricity produces anomalies in the
air gap flux density. As with the air gap eccentricities, these variations generate
stator current at predictable frequencies. Where m = 1, 2, 3 ... and f is one of the
characteristics vibration frequencies calculated based on bearing dimensions. The
characteristic frequencies for ball bearings are based upon dimensions.
6
where n(b) is the number of balls, f(r) the mechanical rotor speed in Hz, PD the
bearing pitch diameter, BD the ball diameter. The Bearing fault was simulated by
replacing the driving end bearing with the degraded bearing of same size and
number. The fault frequencies were predicted as these frequencies were visible in
the frequency spectrum.
1.4.3: ECCENTRICITY FAULTS
The use of current monitoring for detection of air gap eccentricity to identify the
frequency component in the current spectrum .The eccentricity fault was simulated
by inserting the 0.1mm copper strip in the end shield of driving end. This will
create the static eccentricity in the motor. The motor will be allowed to run at rated
speed to create the dynamic eccentricity. These frequencies were visible in the
frequency spectrum.
1.4.4: STATOR FAULTS
Stator winding failures are also a major problem in low and medium voltage
induction motors. It should be noted that volume of low voltage motors is much
greater than high voltage machines. In motors it is normally the case that insulation
degradation cannot be initially diagnosed via on line measurements and the first
indication of a problem will be that a fault actual develops. It is important to
appreciate that there is clear distinction between insulation degradation prior to a
fault and an actual fault. Stator winding faults can be classified as follows:
7
1. Turn to turn short within coil
2. Short Circuit between coils of the single phase motor
3. Phase to phase short circuit
4. Phase to earth short
5. Open circuit in a single phase (Single Phasing)
Pre warning of serious problem (3 and 4 above) can only be achieved if shorted
turns within coil (one or two shorted turns) can be initially diagnosed via online
diagnostic techniques. This requires continuous online monitoring to diagnose the
faults state in 1 and 2 above. There is also the question of how long does it take for
shorted turns within coil to develop into phase to phase or phase to earth fault and
motor failure? This question has not been resolved and will be function of many
variables and will be unique to each motor. Some operators and manufacturers
have previously considered that it is not worth diagnosing shorted turns or coils in
stator windings since the lead time to failure is too short to merit a continuous
online diagnostic system. The concept that the motor has already developed a fault
and will need to be repaired has prevailed. This philosophy is generally now
considered to be somewhat out dated and defeatist. In modern production process
any lead time can be extremely advantageous since unexpected failure of a drive
can be very costly and in some industries it can also be a serious safety hazard. If
shorted turns in a stator coil can be diagnosed a preplanned shut down can be
arranged for the motor to be replaced by healthy one and the faulty one sent for
repair With respect to the problem of single phasing it is relatively easy to
diagnose the problem provided the correct protection equipment is used to cater for
all load conditions. It is also possible to monitor and analyze signals such as
current to diagnose single phasing under any load operating condition. The stator
winding itself is used as the sensor for the detection of abnormalities in the
8
windings. The harmonics which are expected to vary and which have their origin
in the stator currents.
The stator fault i.e. inter-turn short circuit in the winding was simulated by the
rewinding the 1 (h. p), 4 pole motor. The winding of the motor was re-winded and
the tapings at the end of the coils and the tapings at 1, 3, 5, 20 and 25turns were
taken out on the terminal box. The inter-turn short circuit was created by shorting
the turns through rheostat to limit the short circuit current to rated current of the
winding. Fig. 7 shows the arrangement for simulating the stator fault. The fault
frequencies related to stator fault were predicted and obtained in the spectrum It
was found that for the 2 turn inter-turn short circuit, frequency component 398 was
most sensitive to fault. From no fault to maximum fault current variations in the
range of 49% was recorded. Components 498 Hz were found to be less sensitive.
The component 198 and 298Hz was decreasing in all the phases. But decrease is
more pronounced in the faulty phase. For 4 turn inter-turn short circuit, frequency
component398 Hz also increased from no fault conditions. The variations of more
than 100% were observed from no fault to maximum fault current. For 20 turn
inter-turn short circuit, frequency component398Hz also increased. The variation
of more than 400%was observed from no fault to maximum fault current.
From the experiments it was apparent that some of the specified frequency
components were redundant, but whether or not this would be the case for other
machines.
9
Chapter 2
Induction Motor
2.1: Introduction
An electric motor is an electrical machine that converts electrical energy into
mechanical energy. The reverse of this would be the conversion of mechanical
energy into electrical energy and is done by an electric generator.
In normal motoring mode, most electric motors operate through the interaction
between an electric motor's magnetic field and winding currents to generate force
within the motor. In certain applications, such as in the transportation industry with
traction motors, electric motors can operate in both motoring and generating or
braking modes to also produce electrical energy from mechanical energy.
Figure 2.1: Energy Conversion
10
AC induction motors are commonly used in industrial applications. This type
of motor has three main parts rotor, stator and enclosure. The stator and rotor do
the work and the enclosure protects the stator and rotor.
Figure 2.2: Induction Motor
2.2: Stator Core
The stator is the stationary part of the motor’s electromagnetic Circuit. The stator
core is made up of many thin metal sheets called laminations. Laminations are
used to reduce energy loses that would result if a solid core were used.
11
2.3: Stator Windings
Stator laminations are stacked together forming a hollow cylinder. Coils of
insulated wire are inserted into slots of the stator core.
Figure 2.3: Stator Core and Winding
When the assembled motor is in operation the stator windings are connected
directly to the power source. Each grouping of Coils together with the steel core it
surrounds becomes an electromagnet when current is applied. Electromagnetism is
the basic principle behind motor operation.
2.4: Rotor Construction
The rotor is the rotating part of the motor’s electromagnetic circuit. The most
common type of rotor used in an induction motor is a squirrel cage rotor. Another
type is wound rotor.
12
Figure 2.4: Rotor
2.4.1: Wound Rotor Motor
A major difference between the wound rotor motor and the squirrel cage rotor is
that the conductors of the wound rotor consist of wound coils instead of bars.
These coils are connected through slip rings and brushes to external variable
resistors. The rotating magnetic field induces a voltage in the rotor winding.
Increasing the resistance of the rotor windings causes less current to flow in the
rotor windings decreasing rotor speed. Decreasing the resistance causes more
current to flow increasing rotor speed.
2.5: Synchronous Speed
The speed of the rotating magnetic field is referred to as the synchronous speed of
the motor. Synchronous speed is equal to 120 times the frequency (F) divided by
the number of motor poles (P).
The synchronous speed for a two-pole motor operated at 60Hz is 3600 RPM.
13
Synchronous speed decreases as the number of poles increases. The following
table shows the synchronous speed at 60 Hz for several different pole numbers.
Table 1: Synchronous Speeds
2.6: Slip
For an induction motor the rotating magnetic field of stator must rotate faster than
the rotor to induce current in the rotor. When power is first applied to the motor
with the rotor stopped this difference in speed is at its maximum and a large
amount of current is induced in the rotor.
After the motor has been running long enough to get up to operating speed the
difference between the synchronous speed of the rotating magnetic field and the
rotor speed is much smaller. This speed difference is called slip. Slip is necessary
to produce torque. Slip is also dependent on load. An. Increase in load causes the
rotor to slow down increasing slip. A decrease in load causes the rotor to speed up
decreasing slip. Slip is expressed as a percentage and can be calculated using the
following formula.
14
For example a four-pole motor operated at 60 Hz has a synchronous speed of 1800 RPM. If its
rotor speed at full load is 1775 RPM then its full load slip is 1.4%
2.7: Types of Torque
There are different types of torque associated with induction motor. They are
briefly described below.
2.7.1: Starting Torque
Starting torque also referred to as locked rotor torque is the torque that the motor
develops each time it is started at rated voltage and frequency. When voltage is
initially applied to the motor’s stator there is an instant before the rotor turns.
2.7.2: Pull-out Torque
As the motor picks up speed, torque decreases slightly until a point is reached. The
torque available at this point is called pull-up torque.
15
2.7.3: Breakdown Torque
As torque increases up to a maximum value at approximately 200% of full-load
torque. This maximum value of torque is referred to as breakdown torque.
2.7.4: Full-Load Torque
Torque decreases rapidly as speed increases beyond breakdown torque until it
reaches full-load torque at a speed slightly less than 100% of synchronous speed.
Full- load torque is developed with the motor operating at rated voltage, frequency,
and load.
Figure 2.5: Torque Speed Characteristics of Induction Motor
16
Speed-torque curves are useful for understanding motor performance under load.
The following speed-torque curve shows four load examples. This motor is
appropriately sized for constant torque load 1 and variable torque load 1. In each
case, the motor will accelerate to its rated speed. With constant torque load 2, the
motor does not have sufficient starting torque to turn the rotor. With variable
torque load 2, the motor cannot reach rated speed. In this example, the motor will
most likely overheat until its overload relay trips.
Figure 2.6: Torque Speed Characteristics w.r.t Loads
17
2.8: Types of Induction Motors
There are two types of induction motor with respect to supply voltages.
Single phase induction motor
Three Phase induction motor
2.8.1: Single Phase Induction Motor Types
There are four types of single phase induction motor.
1. Split Phase induction motor.
2. Capacitor Starts induction motor.
3. Capacitor Start-Capacitor Run induction motor.
4. Shaded Poles induction motor.
2.8.1.1: Split Phase Induction Motor
In addition to the main winding or running winding, the stator of single phase
induction motor carries another winding called auxiliary winding or starting
winding. A centrifugal switch is connected in series with auxiliary winding. The
purpose of this switch is to disconnect the auxiliary winding from the main circuit
when the motor attains a speed up to 75 to 80% of the synchronous speed. We
know that the running winding is inductive in nature. Our aim is to create the phase
difference between the two winding and this is possible if the starting winding
carries high resistance. Let us say Irun is the current flowing through the main or
running winding, Istart is the current flowing in starting winding, and VT is the
supply voltage.
18
Figure2.7: Circuit Diagram of Split Phase Induction Motor
We know that for highly resistive winding the current is almost in phase with the
voltage and for highly inductive winding the current lag behind the voltage by
large angle. The starting winding is highly resistive so, the current flowing in the
starting winding lags behind the applied voltage by very small angle and the
running winding is highly inductive in nature so, the current flowing in running
winding lags behind applied voltage by large angle. The resultant of these two
current is IT. The resultant of these two current produce rotating magnetic field
which rotates in one direction. In split phase induction motor the starting and main
current get spitted from each other by some angle so this motor got its name as
split phase induction motor.
2.8.1.1.1: Applications of Split Phase Induction Motor
Split phase induction motors have low starting current and moderate starting
torque. So these motors are used in fans, blowers, centrifugal pumps, washing
19
machine, grinder, lathes, air conditioning fans, etc. These motors are available in
the size ranging from 1 / 20 to 1 / 2 KW.
2.8.1.2: Capacitor Start Induction Motor
The working principle and construction of Capacitor start inductor motors and
capacitor start capacitor run induction motors are almost the same. We already
know that single phase induction motor is not self-starting because the magnetic
field produced is not rotating type. In order to produce rotating magnetic field there
must be some phase difference. In case of split phase induction motor we use
resistance for creating phase difference but here we use capacitor for this purpose.
We are familiar with this fact that the current flowing through the capacitor leads
the voltage. So, in capacitor start inductor motor and capacitor start capacitor run
induction motor we are using two winding, the main winding and the starting
winding. With starting winding we connect a capacitor so the current flowing in
the capacitor i.e. Ist leads the applied voltage by some angle.
Figure 2.8: Capacitor Start Induction Motor
20
The working principle and construction of Capacitor start inductor motors and
capacitor start capacitor run induction motors are almost the same. We already
know that single phase induction motor is not self-starting because the magnetic
field produced is not rotating type. In order to produce rotating magnetic field there
must be some phase difference. In case of split phase induction motor we use
resistance for creating phase difference but here we use capacitor for this purpose.
We are familiar with this fact that the current flowing through the capacitor leads
the voltage. So, in capacitor start inductor motor and capacitor start capacitor run
induction motor we are using two winding, the main winding and the starting
winding. With starting winding we connect a capacitor so the current flowing in
the capacitor i.e. Ist leads the applied voltage by some angle.
The running winding is inductive in nature so, the current flowing in running
winding lags behind applied voltage by an angle, φm. Now there occur large phase
angle differences between these two currents which produces a resultant current, I
and this will produce a rotating magnetic field. Since the torque produced by these
motors depends upon the phase angle difference, which is almost 90°. So, these
motors produce very high starting torque. In case of capacitor start induction
motor, the centrifugal switch is provided so as to disconnect the starting winding
when the motor attains a speed up to 75 to 80% of the synchronous speed but in
case of capacitor start capacitors run induction motor there is no centrifugal switch
so, the capacitor remains in the circuit and helps to improve the power factor and
the running conditions of single phase induction motor.
21
2.8.1.3: Capacitor Start-Capacitor Run Induction Motor (Two Value
Capacitor Method)
The working principle and construction of Capacitor start inductor motors and
capacitor start capacitor run induction motors are almost the same. We already
know that single phase induction motor is not self-starting because the magnetic
field produced is not rotating type. In order to produce rotating magnetic field there
must be some phase difference. In case of split phase induction motor we use
resistance for creating phase difference but here we use capacitor for this purpose.
We are familiar with this fact that the current flowing through the capacitor leads
the voltage. So, in capacitor start inductor motor and capacitor start capacitor run
induction motor we are using two winding, the main winding and the starting
winding. With starting winding we connect a capacitor so the current flowing in
the capacitor i.e. Ist leads the applied voltage by some angle. In capacitor start-
capacitor run induction motor capacitor is no excluded with the use of centrifugal
switch. Capacitor remains in the circuit during motor running.
2.8.1.3.1: Application of Capacitor Start IM and Capacitor Start
Capacitor Run IM
These motors have high starting torque hence they are used in conveyors, grinder
and air Conditioners, compressor, etc. They are available up to 6 KW.
22
2.8.1.4: Shaded Pole Single Phase Induction Motors
The stator of the shaded pole single phase induction motors has salient or projected
poles. These poles are shaded by copper band or ring which is inductive in nature.
The poles are divided into two unequal halves. The smaller portion carries the
copper band and is called as shaded portion of the pole.
Figure 2.9: Shaded Pole Induction Motor
When a single phase supply is given to the stator of shaded pole induction motor
an alternating flux is produced. This change of flux induces emf in the shaded coil.
Since this shaded portion is short circuited, the current is produced in it in such a
direction to oppose the main flux. The flux in shaded pole lags behind the flux in
the un shaded pole. The phase difference between these two fluxes produces
resultant rotating flux.
23
We know that the stator winding current is alternating in nature and so is the flux
produced by the stator current. In order to clearly understand the working of
shaded pole induction motor consider three regions.
24
Chapter 3
Faults In Induction Motor
3.1: Introduction
The SQUIRREL-GAGE induction motors are most widely used electrical
machines for industrial commercial and domestic applications. They are more
widespread than any other electric machine in industry due to their intrinsic
ruggedness and reduced cost. Surveys have found that these machines demand
around 40- 50% of the total energy generated in a developed country. These
machines have created a revolution in world economy as most of the production
processes in a developed country is carried out by utilizing an induction machine.
Recently, the use of adjustable speed drives has also spread in many applications.
Hence, sudden failures in these machines can be catastrophic for the processes in
which they are involved. These machines are therefore seeking more attention
from researchers to diagnose the various faults occurring in these machines and to
develop various monitoring and signal processing techniques that can be applied
for prognosis.
Electrical machines and drive systems are subject to many different types of faults.
These faults include:
1. Stator faults which are defined by stator winding open or short-circuited.
2. Rotor faults which include rotor winding open or short circuited and broken
bar(s) or cracked end-ring for squirrel cage machines.
25
3. Mechanical faults such as bearing damage, eccentricity, bent shaft, and
misalignment.
4. Failure of one or more power electronic components of the drive system.
Induction machines are highly symmetrical machines, so any kind of fault modifies
their symmetrical properties.
Characteristics fault frequencies therefore appear in the measured sensor signals,
depending on the type of fault. The factors responsible for failure of three-phase
induction motor are highlighted in Fig.3.1. It is evident from the below given chart
that the highest contributor for failure in a three-phase induction motor is the
bearing fault. This fault is categorized as a mechanical fault.
Figure 3.1: Distribution of Faults In Induction Motor
26
3.2: Classification of Induction Motor Faults
The induction motor faults can be classified in given manner:
Figure 3.2: Faults Classification
3.3: MECHANICAL FAULTS
About 40-50% of induction motor faults are related to mechanical defects.
Classification of these faults includes the following:
27
1. Damage in rolling element bearing.
2. Eccentricity fault.
3.3.1: Bearing Faults
Most electrical machines use either ball or rolling element bearings which consists
of outer and inner rings. Balls or rolling elements rotate in tracks inside the rings.
Bearing faults may be reflected in defects of outer race, inner race, ball or track.
Vibrations, internal stresses, inherent eccentricity, and bearing currents have
effective influence on the development of such faults.
Taking a step back and looking at the big picture, it is found that motors which
were controlled using variable frequency drives tend to show more premature
failures. Variable frequency drives (VFDs, ADSs, or inverters) regulate the speed
of motor by converting sinusoidal line AC voltage to DC voltage, and then back to
pulse width modulated (PWM) AC voltage of variable frequency. The switching
frequency of these pulses ranges from 1 kHz up to 20 kHz and is referred as the
“Carrier frequency”. The ratio of change of the ΔV/ΔT creates a parasitic
capacitance between the motor stator and the rotor, which induces a voltage on the
rotor shaft. If this voltage referred as “Shaft voltage”, builds up to a sufficient
level, it can discharge to ground through the bearings. This current is called as
“bearing current”.
The bearing current results from voltage pulse overshoot created by the fast-
switching IGBT in the VFD. Other reasons of shaft voltage include non-symmetry
of motor’s magnetic circuit, supply unbalances, transient conditions and others.
Any of these conditions can create bearing currents. Shaft voltage accumulates on
28
the rotor until it exceeds the dielectric capacity of the motor bearing lubricant, then
the voltage discharges in a short pulse to ground through the bearing. After
discharge, the voltage again accumulates on the shaft and the cycle repeats itself.
This random and frequent discharging has an electric discharge machining (EDM)
effect, causing pitting of bearings rolling elements and raceways. The first effect of
bearing current damage is the audible noise created by rolling elements riding over
these pits in the bearing race. This deterioration causes a groove pattern in the
bearing race, which indicates that the bearing has sustained severe damage. This
can lead to complete bearing failure.
Figure 3.3 Time Vs Amplitude
The bearing current results from voltage pulse overshoot created by the fast-
switching IGBT in the VFD. Other reasons of shaft voltage include non-symmetry
29
of motor’s magnetic circuit, supply unbalances, transient conditions and others.
Any of these conditions can create bearing currents. Shaft voltage accumulates on
the rotor until it exceeds the dielectric capacity of the motor bearing lubricant, then
the voltage discharges in a short pulse to ground through the bearing. After
discharge, the voltage again accumulates on the shaft and the cycle repeats itself.
This random and frequent discharging has an electric discharge machining (EDM)
effect, causing pitting of bearings rolling elements and raceways. The first effect of
bearing current damage is the audible noise created by rolling elements riding over
these pits in the bearing race. This deterioration causes a groove pattern in the
bearing race, which indicates that the bearing has sustained severe damage. This
can lead to complete bearing failure.
Bearing faults may be reflected in defects of outer race, inner race, ball or track.
Fault in the load part of the drive system, load imbalance, shaft misalignment,
gearbox faults, or bearing faults, gives rise to a periodic variation of the induction
machine load torque. Torque oscillations already exist in a healthy motor owing to
space and harmonics of the air-gap field but fault-related torque oscillations are
present at particular frequencies often related to the shaft speed.
Shaft vibration frequencies associated with different ball-bearing faults were given
in. Different fault gives rise to different harmonic frequencies which are listed
below:
FC = 1/2 FR (1-Dbcosβ/Dc)
FO = NB/2 FR (1-Dbcosβ/Dc)
30
FI = NB/2 FR (1+Dbcosβ/Dc)
FB = DC/DB FR [1-(Dbcosβ/Dc)]
They define cage fault frequency, outer raceway fault frequency, inner raceway
fault frequency, ball fault frequency.
Typically bearing faults are detected through vibration signals. Internal vibrations
are caused by asymmetries and construction details. Vibration and current have
different natures. Vibration is acceleration, and is bound to the square of the
frequency, while current is a displacement. Hence current is mainly sensitive to
low-frequency phenomena. Link between vibration and current component was
presented using two different approaches and vibration was seen as a torque
component that generates two frequency components Fbe in the stator current.
Fbe=|f±kfcar|
Industrial systems are however, still based on vibration signals as they are the only
reliable media. However, use of electrical signals is, preferable in many
applications. Extensive research activity focuses on bearing fault detection based
on current Signals. Current signals can be used for bearing fault detection only in
the case of large failures where it is desirable to detect incipient faults that quickly
degenerate into other defects.
It was shown that mechanically induced speed oscillations give rise to sidebands
components of the fundamental stator current frequency. It was also demonstrated
31
that shaft misalignment causes modulation of current by the shaft rotational
frequency.
The use of dedicated signal processing techniques is essential in order to extract
the fault signature from current efficiently.
3.3.2: Eccentricity Faults
The eccentricity of a cylinder rotating around an air gap can be classified as static,
dynamic, or mixed eccentricity (Fig.3.). Air gap eccentricity is one of the common
failure conditions in an induction motor. For static eccentricity the center of
rotation is displaced from the original center, for dynamic eccentricity, the center
of rotation is at origin while the cylinder is displaced. Finally, for mixed
eccentricity, both the cylinder and center of rotation are displaced from their
respective origin.
An eccentricity may be caused by many problems such as bad bearing positioning
during the motor assembly, worn bearings, bent rotor shaft or operation under a
critical speed creating rotor whirl. The eccentricity causes extensive stressing on
the machine and greatly increases the bearing wear. Also, the radial magnetic field
owing to the eccentricity can act on the stator core exposing the stator windings to
potentially harmful vibrations. More recently, the rotor eccentricity was evaluated
through different signal analysis such as vibration, flux and current.
Under mixed eccentricity conditions, the stator currents contain the following
frequencies:
32
𝐹𝑒𝑐𝑐 =f ± k 1 − s
𝑝 𝑓
Where, “s” is the machine slip. Since the frequencies related to the eccentricity and
to the load torque overlap on the current sidebands, the frequencies provided by
above equation are no longer enough for the diagnosis. The model of eccentricity
using both analytical and finite element (FE) approach is still investigated so that it
can be improved.
Figure 3.4: Eccentricity Faults(a) Without eccentricity(b) Static eccentricity(c) Dynamic
eccentricity(d) Mixed eccentricity
33
3.4: ELECTRICAL FAULTS
In electrical faults there are two types of faults.
1. Rotor Faults
2. Stator Faults
3.4.1: Rotor Faults:
In rotor, there can be some faults which are given below.
3.4.1.1: Unbalanced Currents
Unsymmetrical faults may produce more severe heating in machines than
symmetrical faults or balanced three-phase operation. The negative sequence
currents which flow during these unbalanced faults induce 120 Hz rotor currents
which tend to flow on the surface of the rotor forging and in the nonmagnetic rotor
wedges and retaining rings. The resulting I 2R loss quickly raises the temperature.
If the fault persists, the metal will melt, damaging the rotor structure.
A basic question concerns the cause of the system unbalance. For generators, such
operation is very often the failure of the protection or equipment external to the
machine. For large motors, the unbalance can be caused by the supply equipment,
34
e.g. fused disconnects. Typical conditions that can give rise to the unbalanced
generator currents are:
1. Accidental single-phasing of the generator due to open leads or bushing.
2. Unbalanced generator step-up transformers.
3. Unbalanced system fault conditions and a failure of the relays or breakers.
4. Planned single-phase tripping without rapid reclosing.
3.4.1.2: Rotor Mass Unbalance
From the knowledge of construction of motor it is known that rotor is placed inside
the stator bore and it rotates coaxially with the stator. In a healthy motor, rotor is
centrally aligned with the stator and the axis of rotation of the rotor is the same as
the geometrical axis of the stator. This results in identical air gap between the outer
surface of the rotor and the inner surface of the stator. However, if the rotor is not
centrally aligned or its axis of rotation is not the same as the geometrical axis of
the stator, then the air gap will not be identical and the situation is referred as air-
gap eccentricity. In fact air-gap eccentricity is common to rotor fault in an
induction motor. Air-gap eccentricity may occur due to any of the rotor faults like
rotor mass unbalance fault, bowed rotor fault, etc. Due to this air-gap eccentricity
fault, in an induction motor electromagnetic pull will be unbalanced. The rotor side
where the air gap is minimum that will experience greater pull and the opposite
side will experience lower pull and as a result rotor will tend to move in the greater
pull direction across that gap. The chance of rotor pullover is normally greatest
during the starting period when motor current is also the greatest. In severe case
35
rotor may rub the stator which may result in damage to the rotor and/or stator. Air-
gap eccentricity can also cause noise and/or vibration.
This rotor mass unbalance occur mainly due to manufacturing defect, if not may
occur even after an extended period of operation, for nonsymmetrical addition or
subtraction of mass around the center of rotation of rotor or due to internal
misalignment or shaft bending due to which the center of gravity of the rotor does
not coincide with the center of rotation. In severe case of rotor eccentricity, due to
unbalanced electromagnetic pull if rotor rubs the stator then a small part of
material of rotor body may wear out which is being described here as subtraction
of mass, resulting in rotor mass unbalance fault.
3.4.1.3: Classification of Mass Unbalance
There are three types of mass unbalanced rotor:
1. Static mass unbalanced rotor.
2. Couple unbalance rotor.
3. Dynamic unbalance rotor.
36
3.4.1.3.1: Static Mass Unbalanced Rotor
For this fault shaft rotational axis and weight distribution axis of rotor are parallel
but offset, as shown in below Figure. Without special equipment this type of
eccentricity is difficult to detect.
Figure 3.5: Static Mass Unbalance Rotor
3.4.1.3.2: Couple Unbalance Rotor:
It is shown in below given Figure that if this fault occurs then the shaft rotational
axis and weight distribution axis of rotor intersect at the center of the rotor.
Figure 3.6: Couple Unbalanced Rotor
37
3.4.1.3.3: Dynamic Unbalance Rotor
It is shown in below given figure that if this fault occurs then shaft rotational axis
and weight distribution axis of rotor do not coincide. It is the combination of
coupling unbalance and static unbalance.
Figure 3.7: Dynamic Unbalanced Rotor
3.4.1.4: Causes of Rotor Unbalance
The main causes of rotor mass unbalance in an induction motor can be mentioned,
point wise, as follows:
1. Manufacturing defect.
2. Internal misalignment or shaft bending.
3. It may occur after an extended period of operation, for nonsymmetrical
addition or subtraction of mass around the center of rotation of rotor.
38
3.4.2: Stator Faults
This fault is due to failure of insulation of the stator winding. It is mainly termed as
inter-turn short-circuit fault. Different types of stator winding faults are (i) short
circuit between two turns of same phase—called turn-to-turn fault, (ii) short circuit
between two coils of same phase—called coil to coil fault, (iii) short circuit
between turns of two phases—called phase to phase fault, (iv) short circuit
between turns of all three phases, (v) short circuit between winding conductors and
the stator core— called coil to ground fault, and (vi) open-circuit fault when
winding gets break.
Different types of stator winding faults are shown in below figure. Short-circuit
winding fault shows up when total or a partial of the stator windings get shorted.
Open-circuit fault shows up when total or a partial of the stator windings get
disconnected and no current flows in that phase/line.
Figure 3.8: Star-Connected Stator Showing Different Types of Stator winding Fault
39
Figure 3.9: Photograph of Damage Stator Winding
40
Chapter 4
Electrical Signature Analysis (ESA)
4.1: Introduction
Electric Signature Analysis (ESA) is a technique used for condition, monitoring
and incipient fault detection in motors, generators and transformers. By using ESA
we can identify electrical and mechanical faults in electrical equipment when are in
operation. As a preventive-maintenance tool, Electrical Signature Analysis can be
used for analyzing the performance of many different types of equipment while in
operation.
We can also identify several mechanical and electrical problems; rotor-stator
eccentricity, bearing failures, stator winding short circuits and misalignments. It is
a more preventive and predictive approach towards the incipient fault detection and
gives us a level of redundancy.
As already mentioned, the Electric Signature Analysis (ESA) and condition
monitoring techniques both are used for studying faults in electrical equipment’s so
in electrical motor’s the ESA provides the ability to identify connection problems
and rotor-stator eccentricity (air gap) characteristics. If the rotor-stator eccentricity
misaligns then it will cause the vibrations in motor. As these vibrations will
possess a certain pattern which will repeat itself due to the periodic nature of motor
operation. These vibrations will affect the electrical signature of INDUCTION
motor and will cause the periodic noise in the signal. As mentioned earlier,
41
frequency domain possesses strong immunity to time-domain signal processing.
These vibrations which seem to be a noise in time domain will possess a certain
frequency domain signature. By just eliminating the healthy signature out of this
faulty signature we can get the required results.
Figure 4.1: ESA
ESA is a portable, remote and non-invasive technique. Its whole assembly is
invisible to the monitored equipment. Data acquisition is very simple and it takes
less than three minutes to get all the required signatures of voltage or currents out
of the INDUCTION motor. The biggest advantage of this technique is that it works
while the equipment is in operation. So we don’t need to stop the operation to
perform electrical signature analysis. This compiled data can help us determine the
problems in rotor demagnetization, phase imbalance, motor load, power factor,
power harmonics and the impact of the driven equipment on the motor. ESA also
assesses rotor as well as stator health and rotor-stator eccentricity (air gap)
characteristics. In addition, the bearings condition can also be observed by the data
42
obtained. ESA is particularly helpful in accessing mechanical conditions when it is
not possible or convenient to make vibration measurements.
4.2: Importance of Electrical Signature Analysis (ESA)
ESA is an uprising and beneficial technique. The development of ESA has spanned
over fifteen years and has benefited from the testing of a wide variety of devices. It
is used in given devices.
1. Air Compressors.
2. Textile Plant Motors.
3. Navy P-3C Generator.
4. Multi-Axis Milling Machines.
5. Helicopter Tachometer Generators.
6. Air Force C-141 Fuel Pumps and Pitch Trim Actuators.
7. Large Chillers, Blowers and Fans.
8. Electric Fuel Injectors.
Figure 4.2: Air Compressor
43
Figure 4.3: Textile Plant Motor
Figure 4.4: Electric Fuel Injector
Figure 4.5: Air Force C-141
44
4.3: Condition Monitoring
On-load condition monitoring and incipient fault detection is the topic that has
recently acquired a lot of attention. As the monitored already that the equipment is
invisible to the measuring unit we don’t have to shut down the machine operation
to get the status of their health and on-load condition monitoring can use either
vibration analysis or electrical signature analysis technique. By real time analysis
we could identify the faults before they escalate into something critical. Hence,
machine down time could be minimized reflecting in less cost of the complete
operation cycle.
Trending in the field of health diagnosis of electrical machines is the introduction
of new digital signal processing techniques to extract the faulty signatures of the
machine. In case of time domain the added noise in the signatures could mislead to
wrong results. While in frequency domain, every signal possesses a particular
pattern. So we could easily identify and separate the faulty signature out of healthy
signature and we could benchmark these signatures for the future comparison.
Condition based monitoring services improves the availability and reliability of the
equipment under consideration. Dynamic forces have a direct impact on the
internal working of the electrical machines. These have to withstand many strains
over thousands of operating hours during their life time. Any breakdown would
substantially diminish the profitability of the machine unit. To prevent the
occurrence of any damage their condition monitoring is very important. The
system monitors the condition of the rotating parts inside the electrical machine. It
requires sensors to be attached to the equipment under test. Sensors measure
45
vibrations caused by the enormous forces. The information gathered by the sensors
is digitalized and recorded. After that the data get analyzed. Bearings and other
components oscillates at a certain frequency. The frequency could be calculated
based on the geometry of the bearing. If any fault occurs in the machine it would
indicate a specific signature in the analysis. Condition monitoring allows us to
reduce the down time of the electrical machines by half and gear repairs can be
quickly planned. By cutting down time by half, increases efficiency bare by
boosting the economic viability of the electrical machine. Condition monitoring
can be applied to more than just mechanical components so that no damage is
overlooked during the maintenance to reduce the down time.
By condition monitoring we minimize the risk through early fault detection. As we
are aware of the fact that rotating machine and the static electrical equipment give
us different indications that the problem is developing then if catch those signs in
enough time we can in react to them. There are lot of ways we can in react to them
e.g.
1. Vibration analysis.
2. Ultrasound.
3. Thermography.
4. Partial discharge.
5. Electrical signature analysis.
The inspection and observation both are an important part of condition monitoring.
The basic principal behind condition monitoring is that we run the test for a certain
46
period of time when the equipment is running in its normal healthy state so that we
could say it is running defect free. Then at a certain point we can say that there is
the ability to detect that the condition is degrading and the fault has developed. In
some cases ultrasound is the first technique that is employed to detect any defect in
the rotating electrical equipment. As it has the ability to locate any lubrication
problems. But generally speaking, during initial stages bearing does not make any
sound. The earlier we pick it up the lower risks associated with the failure of the
equipment and lower the cost of dealing with the problem.
The basic application of the condition monitoring is the fault detection,
maintenance, planning, and avoidance of secondary damage or collateral damage
and reduced spares inventory. After consideration of these point there are fewer
safety incidents both in terms of the equipment failing and environmental point of
view. In that case we can plan the maintenance in a better way and that would
reflect the improved safety higher likelihood of having less down time and greater
availability of spare equipment. We either let the equipment fail via getting the
advanced warning of the failure, or fix it before it fails. It avoids catastrophic
failures and reduces the likelihood that a machine will fail catastrophically. The
aim of reliability improvement is to run a plant with the lowest costs, at the highest
availability. After detection of the root cause of the fault and conditions that will
result in failure and reduced reliability, proactive measures can be taken. The
failure can be a cause of unbalance, poor installation, misalignment, soft foot,
lubrication, turbulence and cavitations. Poor lubrication increase friction in the
rotating parts, operating it incorrectly puts all kinds of load on the bearings, shields
and shafts. They all result in bearing failure, reduced efficiency, and seal failure,
coupling failure, shaft failure, leaks and contamination. From a condition
47
monitoring point of view we need to detect the occurrence of these conditions. If
we detect those issues and correct them then we are less likely to get bearing faults.
4.3.1: Advantages of Condition Monitoring
In our system, maintenance is a major problem. There are some types of
maintenance which are given.
4.3.2: Maintenance:
Maintenance, repair and operations (MRO) or maintenance, repair, and overhaul
involves fixing any sort of mechanical, plumbing or electrical device should it
become out of order or broken known as repair, unscheduled, or
casualty maintenance.
4.4: Classification of the Maintenance Activities
“Maintenance” can be understood as the action to repair or to execute
services in equipment and systems.
It can have its activities classified in five main groups:
48
4.4.1: Corrective Maintenance:
This is the most primary form of maintenance. It occurs after a failure carried out.
Usually, it becomes the unavailable equipment for use. Many disadvantages of this
type of maintenance are clear. As examples, the systematic occurrence of not
programmed stops, lesser time of useful life for the machine, bigger consumption
of energy (since with the presence of the failure the motor needs more current
keeping the constant torque) can be cited.
4.4.2: Preventive Maintenance:
This is the name that receives a set of actions developed with the intention of
preventing the occurrence of unsatisfactory conditions, and consequently, reducing
the number of corrective actions. When preventive maintenance plan is elaborated,
a set of technical measurements must be created in order to increase the machine
reliability and decrease the total cost of the maintenance.
A preventive maintenance program can still choose for one of the three types
of activities:
Continuous monitoring.
Periodic measurements.
Predictive techniques.
49
4.4.3: Predictive Maintenance
The predictive maintenance can be a sub-area of the preventive maintenance.
However, the predictive maintenance presents some proper characteristics as:
Support in not invasive techniques, that is, it is not necessary to stop the
operation of the machine for its application.
Elimination of corrective maintenance.
Not consideration of information as the durability of components.
On-line or off-line can be effected through techniques.
4.4.4: Systematic Maintenance
Systematic characterized for the substitution of components of the equipment or
for the substitution of the equipment as a whole.
4.4.5: Zero Hours Maintenance (Overhaul)
The set of tasks whose goal is to review the equipment at scheduled intervals
before appearing any failure either when the reliability of the equipment has
decreased considerably so it is risky to make forecasts of production capacity. This
review is based on leaving the equipment to zero hours of operation, that is, as if
the equipment were new. These reviews will replace or repair all items subject to
50
wear. The aim is to ensure, with high probability, a good working time fixed in
advance.
4.4.6: Periodic Maintenance (TBM)
The basic maintenance of equipment is the analysis of equipment with respect to
the passage of time. It consists of a series of elementary tasks i.e. data collections,
visual inspections, cleaning, lubrication, retightening screws e.g. for which no
extensive training is necessary, but perhaps only a brief training. TBM stands for
time based maintenance.
ESA is used as a special technique in Condition monitoring. So ESA is very
helpful and user friendly technique for our system maintenance.
51
Chapter 5
Procedure Observations And Calculations
5.1: Project Flow Chart
The flow diagram of our FYP is as follows:
Figure 5.1: Flow Chart
52
5.2: Hall Effect Sensor
The Hall Effect was discovered by Edwin Hall while he was a attempting to verify
the theory of electron flow proposed by Kelvin. Hall found when a magnet was
placed so that its field was perpendicular to one face of a thin rectangle of gold
through which current was flowing, a difference in potential appeared at the
opposite edges. He found that this voltage was proportional to the current flowing
through the conductor, and the flux density or magnetic induction perpendicular to
the conductor.
5.2.1: Principle
When a current-carrying conductor is placed into a magnetic field, a voltage will
be generated perpendicular to both the current and the field. This principle is
known as the Hall Effect. Below given figure illustrates the basic principle of the
Hall Effect. It shows a thin sheet of semiconducting material (Hall element)
through which a current is passed. The output connections are perpendicular to the
direction of current. When no magnetic field is present, current distribution is
uniform and no potential difference is seen across the output.
When a perpendicular magnetic field is present, a Lorentz force is exerted on the
current. This force disturbs the current distribution, resulting in a potential
difference (voltage) across the output. This voltage is the Hall voltage (VH).
53
Figure 5.2: Hall Effect Sensor
5.2.2: Advantage of Hall Effect Sensor
The reasons for using a particular technology or sensor vary according to the
application. Cost, performance and availability are always considerations. In this
project we used Hall Effect sensor as current sensing device as it was cheaper and
easily available. It helped a great deal in making our final cost small. And it also
generated the required results.
General features of Hall Effect based sensing devices are:
True solid state
Long life (30 billion operations in a continuing keyboard module test
program)
High speed operation - over 100 kHz possible
Operates with stationary input (zero speed)
No moving parts
Logic compatible input and output
54
Broad temperature range (-40 to +150°C)
Highly repeatable operation
5.2.3: Output vs. power supply characteristics
Analog output sensors are available in voltage ranges of 4.5 to 10.5, 4.5 to 12, or
6.6 to 12.6 VDC. They typically require a regulated supply voltage to operate
accurately. Their output is usually of the push-pull type and is ratio metric to the
supply voltage with respect to offset and gain. Figure on the next page illustrates a
ratio metric analog sensor that accepts a 4.5 to 10.5 V supply. This sensor has a
sensitivity (mV/Gauss) and offset (V) proportional (ratio metric) to the supply
voltage. This device has “rail-to-rail” operation. That is, its output varies from
almost zero (0.2 V typical) to almost the supply voltage (Vs - 0.2 V typical).
Figure 5.3: Input Output Circuitry of Hall Sensor
Utilization of Hall Effect sensors
There are 4 Hall Effect sensors are used in this project. Three of them are for
measurement of three phase current individually and one is for neutral current
55
measurement. On PCB, they are arranged in such a way that current flows to the
bottom copper and then by using small piece of cables ,each phase current is
allowed to pass through that cable which is wound around Hall Effect sensor
tightly. The other end of the cable is fed directly to the output terminal of data
acquisition module from which external connections to the induction motor are
provided.
5.2.4: Hall Effect Sensor Specifications
The data sheet of sensors used in this project is given in the following figure. It
shows that it has wide range of current sensing ability. The dimensions of this
sensor is just bigger than thumbnail. In comparison to CTs there is no issue of
saturation and burden resistance. So for accurate measurement of current for power
quality analysis these sensors provide the best solution. The output of the device is
fed to NI USB 6009.
Figure 5.4: Data Sheet For Hall Effect Sensor
56
5.3: Introduction to NI USB-6009
NI USB-6009 is a low cost device that provides connections to 8 analog inputs
channels, 2 analog output channels, ADC, 12 digital input output channels and 32
bit counter with full USB speed. The maximum sampling rate is 20 kS/s and USB
(2.0) bus speed is 12 Mb/s.
Figure 5.5: NI USB 6009
57
5.3.1: Block Diagram of Internal Structure
Figure 5.6: Internal Structure of NI USB 6009
58
5.3.2: Hardware Connections
To use NI USB 6009 installation of combicon screw terminal blocks are used by
inserting them into combicon jack, terminals orientation are checked and then
wires are connected to appropriate terminals. A 16 pin bus is used instead of wire
connection to keep distinction between voltage and current signals.
Figure 5.7: Connections to NI USB 6009
The Analog terminal assignments are given as follow:
59
Figure 5.8: Analog Input Terminal Assignment
The digital terminals assignments are as follow:
Figure 5.9: Digital Input Terminal Assignment
60
5.3.3: Signal Description
GND: The reference point for single ended Analog Inputs(AI),bias current return
point for differential mode measurement, AO voltages,+5V DC supply and +2.5V
DC supply.
AI (0 to 7): For single ended measurements, each signal is an analog input voltage
channel. For differential measurement positive and negative inputs are applied at
following terminals.
AI 0: AI 4, AI 1: AI 5, AI 2:AI6, AI 3: AI 7
AO (0 & 1): Supply voltage output of Analog output.
P1 (0 to 3) & P0 (0 to 7): Each signal can be individually configured as digital
input or output.
2.5V & 5V DC: Provide DC power either 2.5V or 5V according to requirements.
PFI 0: This pin is configurable as either digital trigger or event counter input.
MUX: USB 6009 has one ADC. The multiplexer route is one AI channel at a time
to PGA.
PGA: Programmable gain amplifier provides input gains of 1, 2, 4, 5, 8, 10, 16 or
20 when configured for differential measurements and gain of 1 when configured
for single ended measurements. PGA gain is automatically calculated based on
voltage range selected in measurement application.
ADC: It converts AI to digital format by converting analog voltage to digital code.
AI FIFO: It holds data during AI acquisition to ensure that no data is lost.
61
5.3.4: Analog input Modes
5.3.4.1: Differential Mode
The positive terminal is connected to AI+ and negative terminal to AI-.In this
mode +20 to -20 V can be measured but voltage on one pin must not exceed 10V
(either positive or negative) with respect to GND.
5.3.4.2. Single Ended Mode
To connect single ended input, positive terminal is connected to AI terminal and
ground signal to GND.PFI 0 is configured as digital trigger input when AI task is
defined. When digital trigger is enabled, AI waits for a rising edge on PFI 0 before
starting acquisition. To use Start trigger with digital source, PFI 0 is specified as
source and rising edge is selected.
5.3.5: Specification of Analog Inputs
1. Input range….. .....…………………………….. -10 to +10 V (single ended)
.… ..……… ……….……… …. ……… ……. -20 to +20V (Differential)
2. Input impedance………………………………………………..…….144kΩ
3. Trigger source……………………………………….…..Software or external
digital source
62
4. AI FIFO ……………………………… …………………………512 bytes
5. Max sampling rate…………………… …………………………….48kS/s
6. Overvoltage protection……… … … …… …… ………………….+-35V
7. System noise………………………..…………0.73mV (rms) (Single ended)
8. System noise …………………...… ………..0.37mV (rms) (Differential)
5.3.6: Analog Output
USB 6009 has two AO channels which can generate 0-5 V. All updates of AO are
software timed. There is DAC which converts digital signal to analog voltage. To
connect load at AO, positive terminal is connected to one of the AO port and
ground to GND.
5.3.7: Digital IO
There are 12 digital lines which comprise DIO ports. GND is ground reference
point for these ports. Individually assignments of ports as DI or DO are possible.
5.3.8: Reference and Power Sources
+2.5V external reference: It creates high purity voltage supply for ADC using
multi state regulator, amplifier and filters. This reference is used as signal for self-
test.
+5 V power source: It supplies 5V, 200mA output. It can be used to power external
components.
63
5.4: MATLAB Simulation
The block diagram of MATLAB simulation is as follows:
Figure 5.10: Block Diagram
After performing analysis on different faults, we got different results for every
fault which are given in their corresponding sections.
5.5: Healthy Signature
To work on our research, we first took healthy signatures of our
healthy motor. The equipment was shown in diagram given below.
64
Figure 5.11: Hardware
After taking signatures, the results was as follows:
Figure 5.12: Healthy Signature
65
5.5.1: MATLAB Simulation for Healthy Motor
After taking simulation on MATLAB, the results of healthy motor was
as follows
Figure 5.13: Healthy Signature
In this figure, we can see that for healthy motor DC Offset is very low.
5.6: Fault of Broken Bars of Rotor
For broken bars of rotor, we opened motor and broke some bars of rotor
by grinding the rotor. The procedure is in given figures.
66
Figure 5.14 Opened motor for application of faults
Figure 5.15: Applying Rotor Fault
67
After that, we connect our faulty motor in circuit and take signatures which are as
follows:
Figure 5.16: ESA for Broken Rotor
5.7: Main Winding Fault
For this fault, we added a resistance of 7.5 ohm in main winding then took
signatures. The block diagram is as follows:
Figure 5.17: Circuit Diagram
68
After performing experiment, the results were as follows:
Figure 5.18: ESA of Main Winding Fault
5.7.1: MATLAB Simulation
In MATLAB when we add these faults, the results were as follows:
Figure 5.19: Main Winding Harmonics Waveform
69
From this figure, we can see that by adding resistance in main winding, DC offset
increases as compared to healthy winding.
5.8: Starter Winding Fault
For this fault, we added a resistance of 7.5 ohm in starter winding then took
signatures. The block diagram is as follows:
Figure 5.20: Circuit Diagram
After performing experiment, the results were as follows.
70
Figure 5.21: ESA of Starter Winding Fault
5.8.1: MATLAB Simulation
In MATLAB simulation, after adding resistance, the results was as
follows:
Figure 5.22: Starter Winding Faults
71
From this figure, we can see that by adding resistance in main winding, DC offset
increase as compared to healthy and main winding.
5.9: Supply Cable Resistance Fault
For this fault, we added a resistance of 7.5 ohm in supply cable then took
signatures. The block diagram is as follows
Figure 5.23: Resistance Added At Supply Cable
72
Figure 5.24: ESA of Supply Cable Resistance Fault
5.9.1: MATLAB Simulation
In MATLAB simulation, after adding resistance, the results was as follows:
Figure 5.25: Supply Cable Resistance Harmonics Waveform
73
Chapter 6
Conclusion
It has been theoretically verified and experimentally confirmed that Induction
motor faults can be identified at initial stages by spectrum of the stator currents.
Electrical signature analysis (ESA) technique is invisible to monitored device in
comparison to vibration analysis based technique that needs accelerometers and
other associated equipment.
It has been empirically verified that all Induction stator faults produces an
imbalance scenario which results in an increase in total harmonic distortion on the
spectrum of stator currents.
Electrical signature analysis of healthy Induction motor confirms the absence of
3rd and 9th harmonic from the spectrum of the stator current. When stator winding
is subjected to fault, triplet harmonics escalates into the signatures of stator current,
which could be used as a warning to incipient fault condition.
Moreover, an increase in total harmonic distortion is observed during varying
mechanical stresses on the Induction motor. While, vibration analysis based
monitoring technique is considered to be more reliable, but it does not give any
information on electrical characteristics of Induction motor.
74
Chapter 7
References
[1] Benbouzid, M.H. (2000). A Review of Induction Motors Signature Analysis
as a medium for Faults Detection, IEEE Transactions on Industrial
Electronics, Vol.47, No.5, (October 2000), pp. 984-993, ISSN 0278-0046.
[2] R.R. Schoen, T.G. Habetler, F. Kamran, and R.G. Bartfield,” Motor bearing damage detection using stator current monitoring”, IEEE transaction. Ind. Appl. Vol 31, Dec 1995.
[3] Mohd El Hachemi B, “A review of induction motor signature analysis as a medium for fault detection”, IEEE transaction on Ind.Elect, vol47, Oct2000.
[4] H.A. Toliyat, M.S. Arefeen and A.G. Parlos, “A method for dynamic simulation of air-gap eccentricity in induction motors”, IEEE transaction Ind.Elect, vol32, Aug 1996.
[5] Bin Lu; Yaoyu Li; Xin Wu; Zhongzhou Yang; , "A review of recent
advances in wind turbine condition monitoring and fault diagnosis," Power
Electronics and Machines in Wind Applications, 2009. PEMWA 2009.
IEEE, vol., no., pp.I-7, 24-26 June 2009.
[6] Mohanty, A.R.; Kar, c.; , "Fault Detection in a Multistage Gearbox by
Demodulation of Motor Current Waveform," Industrial El ectronics, IEEE
Transactions on, vo1.53, no.4, pp.1285-1297, June 2006.
[7] Thomson, W.T., & Fenger, M. (2001). Current Signature Analysis to Detect
Induction Motor Faults, IEEE Industry Applications Magazine, Vol.7, No.4,
(July 2001), pp. 26-34, ISS 1077-2618. [8] Legowski, S.F., Sadrul Ula, A.H.M., & Trzynadlowski, A.M. (1996).
Instantaneous Power as a Medium for the Signature Analysis of Induction
Motors. IEEE Transactions on Industry Applications, Vol.32, No.4, (July/August 1996), pp. 904-909, ISSN 0093-9994.
[9] Cardoso, A.J.M. & Saraiva, E.S. (1993). Computer-Aided Detection of
Airgap Eccentricity in Operating Three-Phase Induction Motors by Park’s
Vectors Approach, IEEETransactions on Industry Applications, Vol.29,
No.5, (Sept/Oct 1993), ISSN 0093-9994.
[10] R. M. Tallam, T. G. Habetler, and R. G. Harley, “Stator winding turn fault detection for closed-loop induction motor drives,” IEEE Trans. Ind. Appl., vol. 39, no. 3, pp. 720–724, May/Jun. 2003.
75
[11] W.T.Thomson, M.Fenger, “Current signature analysis to detect induction motor faults” IEEE.Ind.Appl.Mag, Aug 2001.