NAVFAC MIDLANT, Utilities and Energy Management Rev. 10.06.10 Page 1 of 1 Scope of Work Building: SC-401 Project Title: Replacement of a 112.5 KVA PMT for Bldg. SC-401 Customer: Christopher J. Eyler, PE Scope By: Christopher J. Eyler, PE Date: 7/7/2015 Project Description: The scope of this project is to provide the replacement of the failed 15kV 112.5kVA, 11500 delta primary, 208Y/120 secondary Pad Mounted Transformer (PMT), in the SC Area at Naval Support Activity, Hampton Roads, Main Site, Norfolk, Virginia. 1. The contractor is responsible for the demolition and disposal of all projects' residual materials like wires and transformers, etc.... 2. The contractor is responsible for submitting outage requests associated with the tasks described in this SOW15 days in advance. 3. The contractor should provide all requirements in accordance with the specifications of this SOW. The following lists are the tasks to perform in this scope of work: Electrical: 1. Demolish the failed 112.5kVA transformer. Retain the primary and secondary connection for connection to the secondary of the new. 2. Verify and mark the phase and rotation for all secondary cabling connection, prior to de- energize the temporary trailer mounted transformer. The contractor is required to check for proper phase and rotation upon completion of the transformer installation. 3. Remove existing transformer currently serving building SC-401 and properly dispose of the transformer. 4. Provide a new three-phase 112.5KVA Pad Mount Transformer (PMT), as specified, on the same foundation where the old transformer was located in order to reuse the existing primary and secondary cabling. The concrete pad may need modification to accommodate any differences between the failed building transformer and the new transformer. Remove and relocate the existing metering equipment for the building according to the location of the new PMT. 5. Connect the new 112.5 KVA PMT, using existing cabling. If existing cabling is not sufficient to provide proper termination to the new transformer, contact Chris Eyler at 757-341-1217 for government furnished cable. 6. Verify phase and rotation for all secondary cabling connection once the new 112.5 KVA PMT is energized. SPECIFICATIONS:

PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

NAVFAC MIDLANT, Utilities and Energy Management Rev. 10.06.10 Page 1 of 1

Scope of Work Building: SC-401 Project Title: Replacement of a 112.5 KVA PMT for Bldg. SC-401 Customer: Christopher J. Eyler, PE Scope By: Christopher J. Eyler, PE Date: 7/7/2015 Project Description: The scope of this project is to provide the replacement of the failed 15kV 112.5kVA, 11500 delta primary, 208Y/120 secondary Pad Mounted Transformer (PMT), in the SC Area at Naval Support Activity, Hampton Roads, Main Site, Norfolk, Virginia.

1. The contractor is responsible for the demolition and disposal of all projects' residual

materials like wires and transformers, etc.... 2. The contractor is responsible for submitting outage requests associated with the tasks

described in this SOW15 days in advance. 3. The contractor should provide all requirements in accordance with the specifications of

this SOW. The following lists are the tasks to perform in this scope of work: Electrical:

1. Demolish the failed 112.5kVA transformer. Retain the primary and secondary connection for connection to the secondary of the new.

2. Verify and mark the phase and rotation for all secondary cabling connection, prior to de-energize the temporary trailer mounted transformer. The contractor is required to check for proper phase and rotation upon completion of the transformer installation.

3. Remove existing transformer currently serving building SC-401 and properly dispose of the transformer.

4. Provide a new three-phase 112.5KVA Pad Mount Transformer (PMT), as specified, on the same foundation where the old transformer was located in order to reuse the existing primary and secondary cabling. The concrete pad may need modification to accommodate any differences between the failed building transformer and the new transformer. Remove and relocate the existing metering equipment for the building according to the location of the new PMT.

5. Connect the new 112.5 KVA PMT, using existing cabling. If existing cabling is not sufficient to provide proper termination to the new transformer, contact Chris Eyler at 757-341-1217 for government furnished cable.

6. Verify phase and rotation for all secondary cabling connection once the new 112.5 KVA PMT is energized.

SPECIFICATIONS:

Page 2: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

PROJECT TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS26 08 00 APPARATUS INSPECTION AND TESTING26 12 19.10 THREE-PHASE PAD-MOUNTED TRANSFORMERS

DIVISION 33 - UTILITIES

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

-- End of Project Table of Contents --

PROJECT TABLE OF CONTENTS Page 1

Page 3: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

SECTION 26 00 00.00 20

BASIC ELECTRICAL MATERIALS AND METHODS

07/06

PART 1 GENERAL

1.1 REFERENCES 1.2 RELATED REQUIREMENTS 1.3 DEFINITIONS 1.4 ELECTRICAL CHARACTERISTICS 1.5 ADDITIONAL SUBMITTALS INFORMATION 1.5.1 Shop Drawings (SD-02) 1.5.2 Product Data (SD-03) 1.6 QUALITY ASSURANCE 1.6.1 Regulatory Requirements 1.6.2 Standard Products 1.6.2.1 Alternative Qualifications 1.6.2.2 Material and Equipment Manufacturing Date 1.7 WARRANTY 1.8 POSTED OPERATING INSTRUCTIONS 1.9 MANUFACTURER'S NAMEPLATE 1.10 FIELD FABRICATED NAMEPLATES 1.11 WARNING SIGNS 1.12 ELECTRICAL REQUIREMENTS 1.13 INSTRUCTION TO GOVERNMENT PERSONNEL

PART 2 PRODUCTS

2.1 FACTORY APPLIED FINISH

PART 3 EXECUTION

3.1 FIELD APPLIED PAINTING 3.2 FIELD FABRICATED NAMEPLATE MOUNTING 3.3 WARNING SIGN MOUNTING

-- End of Section Table of Contents --

SECTION 26 00 00.00 20 Page 1 July 07, 2015

Page 4: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION 26 00 00.00 20

BASIC ELECTRICAL MATERIALS AND METHODS07/06

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM D709 (2013) Laminated Thermosetting Materials

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms

IEEE C2 (2012; Errata 2012; INT 1-4 2012; INT 5-7 2013) National Electrical Safety Code

IEEE C57.12.28 (2005; INT 3 2011) Standard for Pad-Mounted Equipment - Enclosure Integrity

IEEE C57.12.29 (2005) Standard for Pad-Mounted Equipment - Enclosure Integrity for Coastal Environments

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA 250 (2008) Enclosures for Electrical Equipment (1000 Volts Maximum)

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013) National Electrical Code

1.2 RELATED REQUIREMENTS

This section applies to all sections of Division 26 and 33, ELECTRICAL and UTILITIES, of this project specification unless specified otherwise in the individual sections. This section has been incorporated into, and thus, does not apply to, and is not referenced in the following sections.

Section 26 12 19.10 THREE-PHASE PAD MOUNTED TRANSFORMERSSection 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

1.3 DEFINITIONS

a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, shall be as

SECTION 26 00 00.00 20 Page 2 July 07, 2015

Page 5: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

defined in IEEE 100.

b. The technical sections referred to herein are those specificationsections that describe products, installation procedures, and equipmentoperations and that refer to this section for detailed description ofsubmittal types.

c. The technical paragraphs referred to herein are those paragraphs inPART 2 - PRODUCTS and PART 3 - EXECUTION of the technical sections thatdescribe products, systems, installation procedures, equipment, andtest methods.

1.4 ELECTRICAL CHARACTERISTICS

Electrical characteristics for this project shall be 11.5 kV primary, three phase, three wire, 60 Hz, and 208Y/120 volts secondary, three phase, our wire. Final connections to the power distribution system at the existing pole shall be made by the Contractor as directed by the Contracting Officer.

1.5 ADDITIONAL SUBMITTALS INFORMATION

Submittals required in other sections that refer to this section must conform to the following additional requirements as applicable.

1.5.1 Shop Drawings (SD-02)

Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings shall indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices.

1.5.2 Product Data (SD-03)

Submittal shall include performance and characteristic curves.

1.6 QUALITY ASSURANCE

1.6.1 Regulatory Requirements

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.

1.6.2 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar

SECTION 26 00 00.00 20 Page 3 July 07, 2015

Page 6: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in the technical section.

1.6.2.1 Alternative Qualifications

Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

1.6.2.2 Material and Equipment Manufacturing Date

Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified otherwise.

1.7 WARRANTY

The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.

1.8 POSTED OPERATING INSTRUCTIONS

Provide for each system and principal item of equipment as specified in the technical sections for use by operation and maintenance personnel. The operating instructions shall include the following:

a. Wiring diagrams, control diagrams, and control sequence for eachprincipal system and item of equipment.

b. Start up, proper adjustment, operating, lubrication, and shutdownprocedures.

c. Safety precautions.

d. The procedure in the event of equipment failure.

e. Other items of instruction as recommended by the manufacturer of eachsystem or item of equipment.

Print or engrave operating instructions and frame under glass or in approved laminated plastic. Post instructions where directed. For operating instructions exposed to the weather, provide weather-resistant materials or weatherproof enclosures. Operating instructions shall not fade when exposed to sunlight and shall be secured to prevent easy removal or peeling.

1.9 MANUFACTURER'S NAMEPLATE

Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.

SECTION 26 00 00.00 20 Page 4 July 07, 2015

Page 7: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

1.10 FIELD FABRICATED NAMEPLATES

ASTM D709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified in the technical sections or as indicated on the drawings. Each nameplate inscription shall identify the function and, when applicable, the position. Nameplates shall be melamine plastic, 0.125 inch thick, white with black center core. Surface shall be matte finish. Corners shall be square. Accurately align lettering and engrave into the core. Minimum size of nameplates shall be one by 2.5 inches. Lettering shall be a minimum of 0.25 inch high normal block style.

1.11 WARNING SIGNS

Provide warning signs for the enclosures of electrical equipment including substations, pad-mounted transformers, pad-mounted switches, generators, and switchgear having a nominal rating exceeding 600 volts.

a. When the enclosure integrity of such equipment is specified to be inaccordance with IEEE C57.12.28 or IEEE C57.12.29, such as forpad-mounted transformers, provide self-adhesive warning signs on theoutside of the high voltage compartment door(s). Sign shall be a decaland shall have nominal dimensions of 7 by 10 inches with the legend"DANGER HIGH VOLTAGE" printed in two lines of nominal 2 inch highletters. The word "DANGER" shall be in white letters on a redbackground and the words "HIGH VOLTAGE" shall be in black letters on awhite background. Decal shall be Panduit No. PPSO710D72 or approvedequal.

1.12 ELECTRICAL REQUIREMENTS

Electrical installations shall conform to IEEE C2, NFPA 70, and requirements specified herein.

1.13 INSTRUCTION TO GOVERNMENT PERSONNEL

Where specified in the technical sections, furnish the services of competent instructors to give full instruction to designated Government personnel in the adjustment, operation, and maintenance of the specified systems and equipment, including pertinent safety requirements as required. Instructors shall be thoroughly familiar with all parts of the installation and shall be trained in operating theory as well as practical operation and maintenance work. Instruction shall be given during the first regular work week after the equipment or system has been accepted and turned over to the Government for regular operation. The number of man-days (8 hours per day) of instruction furnished shall be as specified in the individual section.

PART 2 PRODUCTS

2.1 FACTORY APPLIED FINISH

Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance test and the additional requirements specified in the technical sections.

SECTION 26 00 00.00 20 Page 5 July 07, 2015

Page 8: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

PART 3 EXECUTION

3.1 FIELD APPLIED PAINTING

Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria. Painting shall be as specified in the section specifying the associated electrical equipment.

3.2 FIELD FABRICATED NAMEPLATE MOUNTING

Provide number, location, and letter designation of nameplates as indicated. Fasten nameplates to the device with a minimum of two sheet-metal screws or two rivets.

3.3 WARNING SIGN MOUNTING

Provide the number of signs required to be readable from each accessible side, but space the signs a maximum of 30 feet apart.

-- End of Section --

SECTION 26 00 00.00 20 Page 6 July 07, 2015

Page 9: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

SECTION 26 08 00

APPARATUS INSPECTION AND TESTING

08/08

PART 1 GENERAL

1.1 REFERENCES 1.2 RELATED REQUIREMENTS 1.3 SUBMITTALS 1.4 QUALITY ASSURANCE 1.4.1 Qualifications 1.4.2 Acceptance Tests and Inspections Reports 1.4.3 Acceptance Test and Inspections Procedure

PART 2 PRODUCTS

PART 3 EXECUTION

3.1 ACCEPTANCE TESTS AND INSPECTIONS 3.2 SYSTEM ACCEPTANCE 3.3 PLACING EQUIPMENT IN SERVICE

-- End of Section Table of Contents --

SECTION 26 08 00 Page 1 July 07, 2015

Page 10: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION 26 08 00

APPARATUS INSPECTION AND TESTING08/08

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems

1.2 RELATED REQUIREMENTS

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to this section with additions and modifications specified herein.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-06 Test Reports

Acceptance tests and inspections; G

SD-07 Certificates

Qualifications of organization, and lead engineering technician; G

Acceptance test and inspections procedure; G

1.4 QUALITY ASSURANCE

1.4.1 Qualifications

Contractor shall engage the services of a qualified testing organization to provide inspection, testing, calibration, and adjustment of the electrical distribution system and generation equipment listed in paragraph entitled "Acceptance Tests and Inspections" herein. Organization shall be independent of the supplier, manufacturer, and installer of the equipment. The organization shall be a first tier subcontractor. No work required by this section of the specification shall be performed by a second tier subcontractor.

a. Submit name and qualifications of organization. Organization shallhave been regularly engaged in the testing of electrical materials,devices, installations, and systems for a minimum of 5 years. The

SECTION 26 08 00 Page 2 July 07, 2015

Page 11: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

organization shall have a calibration program, and test instruments used shall be calibrated in accordance with NETA ATS.

b. Submit name and qualifications of the lead engineering technicianperforming the required testing services. Include a list of threecomparable jobs performed by the technician with specific names andtelephone numbers for reference. Testing, inspection, calibration, andadjustments shall be performed by an engineering technician, certifiedby NETA or the National Institute for Certification in EngineeringTechnologies (NICET) with a minimum of 5 years' experience inspecting,testing, and calibrating electrical distribution and generationequipment, systems, and devices.

1.4.2 Acceptance Tests and Inspections Reports

Submit certified copies of inspection reports and test reports. Reports shall include certification of compliance with specified requirements, identify deficiencies, and recommend corrective action when appropriate. Type and neatly bind test reports to form a part of the final record. Submit test reports documenting the results of each test not more than 10 days after test is completed.

1.4.3 Acceptance Test and Inspections Procedure

Submit test procedure reports for each item of equipment to be field tested at least 45 days prior to planned testing date. Do not perform testing until after test procedure has been approved.

PART 2 PRODUCTS

Not used.

PART 3 EXECUTION

3.1 ACCEPTANCE TESTS AND INSPECTIONS

Testing organization shall perform acceptance tests and inspections. Test methods, procedures, and test values shall be performed and evaluated in accordance with NETA ATS, the manufacturer's recommendations, and paragraph entitled "Field Quality Control" of each applicable specification section. Tests identified as optional in NETA ATS are not required unless otherwise specified. Equipment shall be placed in service only after completion of required tests and evaluation of the test results have been completed. Contractor shall supply to the testing organization complete sets of shop drawings, settings of adjustable devices, and other information necessary for an accurate test and inspection of the system prior to the performance of any final testing. Contracting Officer shall be notified at least 14 days in advance of when tests will be conducted by the testing organization. Perform acceptance tests and inspections on applicable equipment and systems specified in the following sections:

b. Section 26 12 19.10 THREE-PHASE PAD-MOUNTED TRANSFORMERS

e. Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

SECTION 26 08 00 Page 3 July 07, 2015

Page 12: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.2 SYSTEM ACCEPTANCE

Final acceptance of the system is contingent upon satisfactory completion of acceptance tests and inspections.

3.3 PLACING EQUIPMENT IN SERVICE

A representative of the approved testing organization shall be present when equipment tested by the organization is initially energized and placed in service.

-- End of Section --

SECTION 26 08 00 Page 4 July 07, 2015

Page 13: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

SECTION 26 12 19.10

THREE-PHASE PAD-MOUNTED TRANSFORMERS

02/12

PART 1 GENERAL

1.1 REFERENCES 1.2 RELATED REQUIREMENTS 1.3 DEFINITIONS 1.4 SUBMITTALS 1.4.1 Government Submittal Review 1.4.2 Reduced Submittal Requirements 1.5 QUALITY ASSURANCE 1.5.1 Pad-Mounted Transformer Drawings 1.5.2 Regulatory Requirements 1.5.3 Standard Products

1.5.3.1 Alternative Qualifications1.5.3.2 Material and Equipment Manufacturing Date

1.6 MAINTENANCE 1.6.1 Additions to Operation and Maintenance Data 1.7 WARRANTY

PART 2 PRODUCTS

2.1 PRODUCT COORDINATION 2.2 THREE-PHASE PAD-MOUNTED TRANSFORMERS 2.2.1 Compartments

2.2.1.1 High Voltage, Dead-Front2.2.1.2 Low Voltage

2.2.2 Transformer2.2.2.1 Specified Transformer Efficiencies

2.2.3 Insulating Liquid2.2.3.1 Liquid-Filled Transformer Nameplates

2.2.4 Corrosion Protection 2.3 WARNING SIGNS 2.4 Arc Flash Warning Label 2.5 GROUNDING AND BONDING 2.6 PADLOCKS 2.7 CAST-IN-PLACE CONCRETE 2.8 SOURCE QUALITY CONTROL 2.8.1 Transformer Test Schedule 2.8.2 Design Tests 2.8.3 Routine and Other Tests

PART 3 EXECUTION

3.1 INSTALLATION 3.2 GROUNDING 3.2.1 Grounding Electrodes 3.2.2 Pad-Mounted Transformer Grounding

SECTION 26 12 19.10 Page 1 July 07, 2015

Page 14: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.2.3 Connections 3.2.4 Grounding and Bonding Equipment 3.3 INSTALLATION OF EQUIPMENT AND ASSEMBLIES 3.3.1 Meters and Current Transformers 3.4 FIELD APPLIED PAINTING 3.5 FOUNDATION FOR EQUIPMENT AND ASSEMBLIES 3.5.1 Cast-In-Place Concrete 3.5.2 Sealing 3.6 FIELD QUALITY CONTROL 3.6.1 Performance of Acceptance Checks and Tests

3.6.1.1 Pad-Mounted Transformers3.6.1.2 Current Transformers3.6.1.3 Grounding System3.6.1.4 Surge Arresters, Medium- and High-Voltage

3.6.2 Follow-Up Verification

-- End of Section Table of Contents --

SECTION 26 12 19.10 Page 2 July 07, 2015

Page 15: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION 26 12 19.10

THREE-PHASE PAD-MOUNTED TRANSFORMERS02/12

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)

ACI 318M (2011; Errata 2013) Building Code Requirements for Structural Concrete & Commentary

ASTM INTERNATIONAL (ASTM)

ASTM A240/A240M (2013c) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications

ASTM C260/C260M (2010a) Standard Specification for Air-Entraining Admixtures for Concrete

ASTM D1535 (2013) Specifying Color by the Munsell System

ASTM D877/D877M (2013) Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes

ASTM D92 (2012b) Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester

ASTM D97 (2012) Pour Point of Petroleum Products

FM GLOBAL (FM)

FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms

IEEE 386 (2006; INT 1 2011) Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600V

IEEE C2 (2012; Errata 2012; INT 1-4 2012; INT 5-7 2013) National Electrical Safety Code

SECTION 26 12 19.10 Page 3 July 07, 2015

Page 16: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

IEEE C57.12.00 (2010) Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEEE C57.12.28 (2005; INT 3 2011) Standard for Pad-Mounted Equipment - Enclosure Integrity

IEEE C57.12.29 (2005) Standard for Pad-Mounted Equipment - Enclosure Integrity for Coastal Environments

IEEE C57.12.34 (2009) Standard for Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase Distribution Transformers, 5 MVA and Smaller; High Voltage, 34.5 kV Nominal System Voltage and Below; Low Voltage, 15 kV Nominal System Voltage and Below

IEEE C57.12.90 (2010) Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEEE C57.13 (2008; INT 2009) Standard Requirements for Instrument Transformers

IEEE C57.98 (2011) Guide for Transformer Impulse Tests

IEEE C62.11 (2012) Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuits (>1kV)

INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

ANSI C12.1 (2008) Electric Meters Code for Electricity Metering

ANSI C12.7 (2005) Requirements for Watthour Meter Sockets

NEMA/ANSI C12.10 (2011) Physical Aspects of Watthour Meters - Safety Standards

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013) National Electrical Code

ORGANISATION FOR ECONOMIC CO-OPERATION AND DEVELOPMENT (OECD)

OECD Test 203 (1992) Fish Acute Toxicity Test

SECTION 26 12 19.10 Page 4 July 07, 2015

Page 17: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)

EPA 712-C-98-075 (1998) Fate, Transport and Transformation Test Guidelines - OPPTS 835.3100- "Aerobic Aquatic Biodegradation"

EPA 821-R-02-012 (2002) Methods for Measuring the Acute Toxicity of Effluents and Receiving Waters to Freshwater and Marine Organisms

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

10 CFR 431 Energy Efficiency Program for Certain Commercial and Industrial Equipment

UNDERWRITERS LABORATORIES (UL)

UL 467 (2007) Grounding and Bonding Equipment

1.2 RELATED REQUIREMENTS

Section 26 08 00 APPARATUS INSPECTION AND TESTING applies to this section, with the additions and modifications specified herein.

1.3 DEFINITIONS

Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, shall be as defined in IEEE 100.

1.4 SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Pad-mounted transformer drawings; G

SD-03 Product Data

Pad-mounted transformers; G

Submittal shall include manufacturer's information for each component, device, insulating fluid, and accessory provided with the transformer.

SD-06 Test Reports

Acceptance checks and tests; G

Submittal shall include acceptance criteria and limits for each test in accordance with NETA ATS "Test Values".

SD-07 Certificates

SECTION 26 12 19.10 Page 5 July 07, 2015

Page 18: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

Transformer Efficiencies; G

Submit certification, including supporting calculations, from the manufacturer indicating conformance with the paragraph entitled "Specified Transformer Efficiencies."

SD-09 Manufacturer's Field Reports

Pad-mounted transformer design tests; G

Pad-mounted transformerroutine and other tests; G

SD-10 Operation and Maintenance Data

Transformer(s), Data Package 5; G

Submit operation and maintenance data in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA and as specified herein.

SD-11 Closeout Submittals

Transformer test schedule; G

Submit report of test results as specified by paragraph entitled "Field Quality Control."

1.4.1 Government Submittal Review

Code BMPW64, NAVFAC MIDLANT, Naval Facilities Engineering Command will review and approve all submittals in this section requiring Government approval.

1.4.2 Reduced Submittal Requirements

Transformers designed and manufactured by ABB in Jefferson City, MO; by Cooper Power Systems in Waukesha, WI; by ERMCO in Dyersburg, TN; or by Howard Industries in Laurel, MS need not submit the entire submittal package requirements of this contract. Instead, the following items shall be submitted:

a. A certification, signed by the manufacturer, stating that the technicalrequirements of this specification shall be met.

b. An outline drawing of the transformer with devices identified(paragraph entitled "Pad-Mounted Transformer Drawings", item a).

c. ANSI nameplate data of the transformer (paragraph entitled "Pad-MountedTransformer Drawings", item b).

d. Manufacturer's published time-current curves (properly overlaid on onefull size logarithmic paper) of the transformer high side fuses(paragraph entitled "Pad-Mounted Transformer Drawings", item e) withtransformer damage curve, inrush curve, and thru fault currentindicated.

e. Routine and other tests (in PART 2, see paragraph entitled "SourceQuality Control", subparagraph entitled "Routine and Other Tests"),shall be conducted by the manufacturer and may be witnessed by thegovernment. Provide transformer test schedule required by submittal

SECTION 26 12 19.10 Page 6 July 07, 2015

Page 19: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

item "SD-11 Closeout Submittals". Provide certified copies of the tests.

f. Provide acceptance test reports required by submittal item "SD-06 TestReports".

g. Provide operation and maintenance manuals required by submittal item"SD-10 Operation and Maintenance Data".

1.5 QUALITY ASSURANCE

1.5.1 Pad-Mounted Transformer Drawings

Drawings shall indicate, but not be limited to the following:

a. An outline drawing, with front, top, and side views.

b. ANSI nameplate data.

c. Elementary diagrams and wiring diagrams with terminals identified ofwatthour meter and current transformers.

d. One-line diagram, including switch(es), current transformers, meters,and fuses.

e. Manufacturer's published time-current curves (on full size logarithmicpaper) of the transformer high side fuses.

1.5.2 Regulatory Requirements

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.

1.5.3 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.

1.5.3.1 Alternative Qualifications

Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

SECTION 26 12 19.10 Page 7 July 07, 2015

Page 20: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

1.5.3.2 Material and Equipment Manufacturing Date

Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified otherwise.

1.6 MAINTENANCE

1.6.1 Additions to Operation and Maintenance Data

In addition to requirements of Data Package 5, include the following on the actual transformer(s) provided:

a. An instruction manual with pertinent items and information highlighted

b. An outline drawing, front, top, and side views

c. Prices for spare parts and supply list

d. Routine and field acceptance test reports

e. Fuse curves for primary fuses

f. Information on watthour demand meter, CT's, and fuse block

g. Actual nameplate diagram

h. Date of purchase

1.7 WARRANTY

The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.

PART 2 PRODUCTS

2.1 PRODUCT COORDINATION

Products and materials not considered to be pad-mounted transformers and related accessories are specified in.

2.2 THREE-PHASE PAD-MOUNTED TRANSFORMERS

IEEE C57.12.34, IEEE C57.12.29 and as specified herein.

2.2.1 Compartments

The high- and low-voltage compartments shall be separated by steel isolating barriers extending the full height and depth of the compartments. Compartment doors: hinged lift-off type with stop in open position and three-point latching.

2.2.1.1 High Voltage, Dead-Front

High-voltage compartment shall contain the incoming line, insulated high-voltage load-break connectors, bushing well inserts, six high-voltage bushing wells configured for loop feed application, load-break switch

SECTION 26 12 19.10 Page 8 July 07, 2015

Page 21: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

handle(s), access to oil-immersed bayonet fuses, dead-front surge arresters, tap changer handle, connector parking stands with insulated standoff bushings, protective caps, and ground pad.

b. Insulated high-voltage dead-break connectors: IEEE 386, rated 15 kV,95 kV BIL. Current rating: 600 amperes rms continuous. Short timerating: 25,000 amperes rms symmetrical for a time duration of 0.17seconds. Connector shall have a 200 ampere bushing interface for surgearresters, steel reinforced hook-stick eye, grounding eye, test point,and arc-quenching contact material.

e. Load-break switch

Radial-feed oil-immersed type rated at 15 kV, 95 kV BIL, with acontinuous current rating and load-break rating of 200 amperes, and amake-and-latch rating of 12,000 rms amperes symmetrical. Locate theswitch handle in the high-voltage compartment.

h. Surge arresters: IEEE C62.11, rated 12 kV, fully shielded, dead-front,metal-oxide-varistor, elbow type with resistance-graded gap. Providethree arresters for loop feed circuits.

i. Parking stands: Provide a parking stand near each bushing. Provideinsulated standoff bushings for parking of energized high-voltageconnectors on parking stands.

j. Protective caps: IEEE 386, 200 amperes, 15 kV Class. Provideinsulated protective caps (not shipping caps) for insulating andsealing out moisture from unused bushings.

2.2.1.2 Low Voltage

Low-voltage compartment shall contain low-voltage bushings with NEMA spade terminals, accessories, metering, stainless steel or laser-etched anodized aluminum diagrammatic transformer nameplate, and ground pad.

a. Accessories shall include drain valve with sampler device, fill plug,pressure relief device, liquid level gage, pressure-vacuum gage, anddial type thermometer with maximum temperature indicator. c.Metering: NEMA/ANSI C12.10. Provide a socket surface mounted flushagainst the side of the low-voltage compartment as indicated. Existingmeter shall be reinstalled to new socket.

1. Class: 20; Form: 9S; Accuracy: plus or minus 1.0 percent;Finish: Class II

2. Meter reading multiplier: Indicate multiplier on the meter face.

3. Meter fusing: Provide a fuse block mounted in the secondarycompartment containing one fuse per phase to protect the voltageinput to the watthour meter. Size fuses as recommended by themeter manufacturer.

4. Socket: ANSI C12.7. Provide NEMA Type 3R stainless steelenclosure, box-mounted socket having automatic circuit-closingbypass and having jaws compatible with requirements of the meter.Cover unused hub openings with blank hub plates. Paint boxMunsell 7GY3.29/1.5 green to match the pad-mounted transformer towhich the box-mounted socket is attached. The Munsell colornotation is specified in ASTM D1535.

SECTION 26 12 19.10 Page 9 July 07, 2015

Page 22: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

a. Surge withstand capability shall conform to IEEE C37.90.1.

b. Use #12 SIS (XHHW, or equivalent) wiring with ring lugs forall meter connections. Color code and mark the conductors as follows:

(1) Red - Phase A CT - C1(2) Orange - Phase B CT - C2(3) Brown - Phase C CT - C3(4) Gray with white stripe - neutral current return - C0(5) Black - Phase A voltage - V1(6) Yellow - Phase B voltage - V2(7) Blue - Phase C voltage - V3(8) White - Neutral voltage

c. Disconnect Method

1. Provide a 10-pole safety disconnect complete with isolationdevices for the voltage and current transformer inputs, including a shorting means for the current transformers.

2. Disconnecting wiring blocks shall be provided between thecurrent transformer and the meter. A shorting mechanism shall be built into the wiring block to allow the current transformer wiring to be changed without removing power to the transformer. The wiring blocks shall be located where they are accessible without the necessity of disconnecting power to the transformer.

3. Voltage monitoring circuits shall be equipped withdisconnect switches to isolate the meter base or socket from the voltage source.

5. Current transformers: IEEE C57.13. Provide butyl-molded windowtype current transformers with 600-volt insulation, 10 kV BIL andmount on the low-voltage bushings. Provide shorting type terminalblocks and route current transformer leads from the shorting typeterminal blocks in a location as remote as possible from the powertransformer secondary cables to permit current measurements to betaken with hook-on-ammeters. Provide three current transformersper power transformer with characteristics listed in the followingtable.

kVA Sec. Volt CT Ratio RF Meter Acc. Class

112.5 208Y/120 300/5 3.0 0.3 thru B-0.2

2.2.2 Transformer

a. Less-flammable liquid-insulated, two winding, 60 hertz, 65 degrees Crise above a 30 degrees C average ambient, self-cooled type.

b. Transformer shall be rated 112.5 kVA.

c. Transformer voltage ratings: 11500 V Delta - 208Y/120 V GrdY.

SECTION 26 12 19.10 Page 10 July 07, 2015

Page 23: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

d. Tap changer shall be externally operated, manual type for changing tapsetting when the transformer is de-energized. Provide four 2.5 percentfull capacity taps, two above and two below rated primary voltage. Tapchangers shall clearly indicate which tap setting is in use.

e. Minimum tested percent impedance at 85 degrees C shall not be less thanthe following values:

2.50 for units rated 75kVA and below2.87 for units rated 112.5kVA to 300kVA4.03 for 500kVA rated units5.32 for units rated 750kVA and above

f. Audible sound levels shall comply with the following:

kVA DECIBELS(MAX

75 51

112.5 55

150 55

225 55

300 55

500 56

750 57

1000 58

1500 60

2000 61

2500 62

g. Transformer shall include lifting lugs and provisions for jacking underbase. The transformer base construction shall be suitable for usingrollers or skidding in any direction. Provide transformer top with anaccess handhole. Transformer shall have its kVA rating conspicuouslydisplayed on its enclosure. The transformer shall have an insulatedlow-voltage neutral bushing with NEMA spade terminal, and withremovable ground strap.

2.2.2.1 Specified Transformer Efficiencies

Provide transformer efficiency calculations utilizing the actual no-load and load loss values obtained during the routine tests performed on the actual transformer(s) prepared for this project. No-load losses (NLL) shall be referenced at 20 degrees C. Load losses (LL) shall be referenced at 55 degrees C and at 50 percent of the nameplate load. The transformer is not acceptable if the calculated transformer efficiency is less than the efficiency indicated in the "KVA / Efficiency" table below. That table is based on requirements contained within 10 CFR 431, Subpart K.

SECTION 26 12 19.10 Page 11 July 07, 2015

Page 24: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

kVA EFFICIENCY (percent)

15 98.36

30 98.62

45 98.76

75 98.91

112.5 99.01

150 99.08

225 99.17

300 99.23

500 99.25

750 99.32

1000 99.36

1500 99.42

2000 99.46

2500 99.49

above 2500 99.50

2.2.3 Insulating Liquid

a. Less-flammable transformer liquids: NFPA 70 and FM APP GUIDE forless-flammable liquids having a fire point not less than 300 degrees Ctested per ASTM D92 and a dielectric strength not less than 33 kVtested per ASTM D877/D877M. Provide identification of transformer as"non-PCB" and "manufacturer's name and type of fluid" on the nameplate.

The fluid shall be a biodegradable electrical insulating and coolingliquid classified by UL and approved by FM as "less flammable" fluids.The fluid shall meet the following fluid properties:

1. Pour point: ASTM D97, less than -15 degree C

2. Aquatic biodegradation: EPA 712-C-98-075, 100 percent

3. Trout toxicity: OECD Test 203, zero mortality of EPA 821-R-02-012,pass

2.2.3.1 Liquid-Filled Transformer Nameplates

Distribution transformers shall be provided with nameplate information in accordance with IEEE C57.12.00 and as modified or supplemented by this section.

SECTION 26 12 19.10 Page 12 July 07, 2015

Page 25: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

2.2.4 Corrosion Protection

Entire transformer assembly, including tank and radiator, base, enclosure, and metering enclosure shall be fabricated of stainless steel conforming to ASTM A240/A240M, Type 304 or 304L. Form enclosure of stainless steel sheets. The optional use of aluminum is permitted for the metering enclosure.

Paint entire transformer assembly Munsell 7GY3.29/1.5 green. Paint coating system shall comply with IEEE C57.12.28 and IEEE C57.12.29 regardless of base, cabinet, and tank material. The Munsell color notation is specified in ASTM D1535.

2.3 WARNING SIGNS

Provide warning signs for the enclosures of pad-mounted transformers having a nominal rating exceeding 600 volts.

a. When the enclosure integrity of such equipment is specified to be inaccordance with IEEE C57.12.28, such as for pad-mounted transformers,provide self-adhesive warning signs on the outside of the high voltagecompartment door(s). Sign shall be a decal and shall have nominaldimensions of 7 by 10 inches with the legend "DANGER HIGH VOLTAGE"printed in two lines of nominal 2 inch high letters. The word "DANGER"shall be in white letters on a red background and the words "HIGHVOLTAGE" shall be in black letters on a white background. Decal shallbe Panduit No. PPSO710D72 or approved equal.

2.4 Arc Flash Warning Label

Provide warning label for the enclosure of pad-mounted transformers. Locate this self-adhesive warning label on the outside of the high voltage compartment door warning of potential electrical arc flash hazards and appropriate PPE required. The label format shall be as indicated.

2.5 GROUNDING AND BONDING

UL 467. Provide grounding and bonding as specified in Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION.

2.6 PADLOCKS

Padlocks shall be provided for pad-mounted equipment. Padlocks shall be keyed as directed and provided by the Contracting Officer.

2.7 CAST-IN-PLACE CONCRETE

Shall be composed of fine aggregate, coarse aggregate, portland cement, and water so proportioned and mixed as to produce a plastic, workable mixture. Fine aggregate shall be of hard, dense, durable, clean, and uncoated sand. The coarse aggregate shall be reasonably well graded from 3/16 inch to 1 inch. The fine and coarse aggregates shall be free from injurious amounts of dirt, vegetable matter, soft fragments or other deleterious substances. Water shall be fresh, clean, and free from salts, alkali, organic matter, and other impurities. Concrete associated with electrical work for other than encasement of underground ducts shall be 4000 psi minimum 28-day compressive strength unless specified otherwise. Slump shall not exceed 4 inches. Retempering of concrete will not be permitted. Exposed, unformed

SECTION 26 12 19.10 Page 13 July 07, 2015

Page 26: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

concrete surfaces shall be given a smooth, wood float finish. Concrete shall be cured for a period of not less than 7 days, and concrete made with high early strength portland cement shall be repaired by patching honeycombed or otherwise defective areas with cement mortar as directed by the Contracting Officer. Air entrain concrete exposed to weather using an air-entraining admixture conforming to ASTM C260/C260M. Air content shall be between 4 and 6 percent.

2.8 SOURCE QUALITY CONTROL

2.8.1 Transformer Test Schedule

The Government reserves the right to witness tests. Provide transformer test schedule for tests to be performed at the manufacturer's test facility. Submit required test schedule and location, and notify the Contracting Officer 30 calendar days before scheduled test date. Notify Contracting Officer 15 calendar days in advance of changes to scheduled date.

a. Test Instrument Calibration

1. The manufacturer shall have a calibration program which assuresthat all applicable test instruments are maintained within ratedaccuracy.

2. The accuracy shall be directly traceable to the National Instituteof Standards and Technology.

3. Instrument calibration frequency schedule shall not exceed 12months for both test floor instruments and leased specialtyequipment.

4. Dated calibration labels shall be visible on all test equipment.

5. Calibrating standard shall be of higher accuracy than that of theinstrument tested.

6. Keep up-to-date records that indicate dates and test results ofinstruments calibrated or tested. For instruments calibrated bythe manufacturer on a routine basis, in lieu of third partycalibration, include the following:

(a) Maintain up-to-date instrument calibration instructions andprocedures for each test instrument.

(b) Identify the third party/laboratory calibrated instrument toverify that calibrating standard is met.

2.8.2 Design Tests

IEEE C57.12.00 states that "design tests are made only on representative apparatus to substantiate the ratings assigned to all other apparatus of basically the same design." Submit design test reports (complete with test data, explanations, formulas, and results), in the same submittal package as the catalog data and drawings for the specified transformer(s). Design tests shall have been performed in accordance with IEEE C57.12.90 prior to the award of this contract.

a. Tests shall be certified and signed by a registered professional

SECTION 26 12 19.10 Page 14 July 07, 2015

Page 27: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

engineer.

b. Temperature rise: "Basically the same design" for the temperature risetest means a pad-mounted transformer with the same coil construction(such as wire wound primary and sheet wound secondary), the same kVA,the same cooling type (ONAN), the same temperature rise rating, and thesame insulating liquid as the transformer specified.

c. Lightning impulse: "Basically the same design" for the lightningimpulse dielectric test means a pad-mounted transformer with the sameBIL, the same coil construction (such as wire wound primary and sheetwound secondary), and a tap changer, if specified. Design lightningimpulse tests shall include the primary windings only of thattransformer.

1. IEEE C57.12.90, paragraph 10.3 entitled "Lightning Impulse TestProcedures," and IEEE C57.98.

2. State test voltage levels.

3. Provide photographs of oscilloscope display waveforms or plots ofdigitized waveforms with test report.

d. Lifting and moving devices: "Basically the same design" requirementfor the lifting and moving devices test means a test report confirmingthat the lifting device being used is capable of handling the weight ofthe specified transformer in accordance with IEEE C57.12.34.

e. Pressure: "Basically the same design" for the pressure test means apad-mounted transformer with a tank volume within 30 percent of thetank volume of the transformer specified.

f. Short circuit: "Basically the same design" for the short circuit testmeans a pad-mounted transformer with the same kVA as the transformerspecified.

2.8.3 Routine and Other Tests

IEEE C57.12.00. Routine and other tests shall be performed in accordance with IEEE C57.12.90 by the manufacturer on the actual transformer(s) prepared for this project to ensure that the design performance is maintained in production. Submit test reports, by serial number and receive approval before delivery of equipment to the project site. Required tests and testing sequence shall be as follows:

a. Phase relation

b. Ratio

c. No-load losses (NLL) and excitation current

d. Load losses (LL) and impedance voltage

e. Dielectric

1. Impulse

2. Applied voltage

SECTION 26 12 19.10 Page 15 July 07, 2015

Page 28: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3. Induced voltage

f. Leak

PART 3 EXECUTION

3.1 INSTALLATION

Electrical installations shall conform to IEEE C2, NFPA 70, and to the requirements specified herein. Provide new equipment and materials unless indicated or specified otherwise.

3.2 GROUNDING

NFPA 70 and IEEE C2, except that grounding systems shall have a resistance to solid earth ground not exceeding 5 ohms.

3.2.1 Grounding Electrodes

Provide driven ground rods as specified in Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Connect ground conductors to the upper end of ground rods by exothermic weld or compression connector. Provide compression connectors at equipment end of ground conductors.

3.2.2 Pad-Mounted Transformer Grounding

Provide separate copper grounding conductors and connect them to the ground loop as indicated. When work in addition to that indicated or specified is required to obtain the specified ground resistance, the provision of the contract covering "Changes" shall apply.

3.2.3 Connections

Make joints in grounding conductors and loops by exothermic weld or compression connector. Exothermic welds and compression connectors shall be installed as specified in Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION.

3.2.4 Grounding and Bonding Equipment

UL 467, except as indicated or specified otherwise.

3.3 INSTALLATION OF EQUIPMENT AND ASSEMBLIES

Install and connect pad-mounted transformers furnished under this section as indicated on project drawings, the approved shop drawings, and as specified herein.

3.3.1 Meters and Current Transformers

ANSI C12.1.

3.4 FIELD APPLIED PAINTING

Where field painting of enclosures is required to correct damage to the manufacturer's factory applied coatings, provide manufacturer's recommended coatings and apply in accordance with manufacturer's instructions.

SECTION 26 12 19.10 Page 16 July 07, 2015

Page 29: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.5 FOUNDATION FOR EQUIPMENT AND ASSEMBLIES

Mount transformer on concrete slab. Unless otherwise indicated, the slab shall be at least 8 inches thick, reinforced with a 6 by 6 - W2.9 by W2.9 mesh, placed uniformly 4 inches from the top of the slab. Slab shall be placed on a 6 inch thick, well-compacted gravel base. Top of concrete slab shall be approximately 4 inches above finished grade with gradual slope for drainage. Edges above grade shall have 1/2 inch chamfer. Slab shall be of adequate size to project at least 8 inches beyond the equipment.

Stub up conduits, with bushings, 2 inches into cable wells in the concrete pad. Coordinate dimensions of cable wells with transformer cable training areas.

3.5.1 Cast-In-Place Concrete

Cast-in-place concrete work shall conform to the requirements of ACI 318M.

3.5.2 Sealing

When the installation is complete, the Contractor shall seal all entries into the equipment enclosure with an approved sealing method. Seals shall be of sufficient strength and durability to protect all energized live parts of the equipment from rodents, insects, or other foreign matter.

3.6 FIELD QUALITY CONTROL

3.6.1 Performance of Acceptance Checks and Tests

Perform in accordance with the manufacturer's recommendations and include the following visual and mechanical inspections and electrical tests, performed in accordance with NETA ATS.

3.6.1.1 Pad-Mounted Transformers

a. Visual and mechanical inspection

1. Compare equipment nameplate data with specifications and approvedshop drawings.

2. Inspect physical and mechanical condition. Check for damaged orcracked insulators and leaks.

3. Inspect anchorage, alignment, and grounding.

4. Verify the presence of PCB content labeling.

5. Verify the bushings and transformer interiors are clean.

6. Inspect all bolted electrical connections for high resistanceusing low-resistance ohmmeter, verifying tightness of accessiblebolted electrical connections by calibrated torque-wrench method,or performing thermographic survey.

7. Verify correct liquid level in tanks and bushings.

8. Verify that positive pressure is maintained on gas-blanketedtransformers.

SECTION 26 12 19.10 Page 17 July 07, 2015

Page 30: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

9. Perform specific inspections and mechanical tests as recommendedby manufacturer.

10. Verify de-energized tap changer position is left as specified.

11. Verify the presence of transformer surge arresters.

b. Electrical tests

1. Perform resistance measurements through all bolted connectionswith low-resistance ohmmeter.

2. Verify proper secondary voltage phase-to-phase andphase-to-neutral after energization and prior to loading.

3.6.1.2 Current Transformers

a. Visual and mechanical inspection

1. Compare equipment nameplate data with specifications and approvedshop drawings.

2. Inspect physical and mechanical condition.

3. Verify correct connection.

4. Verify that adequate clearances exist between primary andsecondary circuit wiring.

5. Verify the unit is clean.

6. Inspect all bolted electrical connections for high resistanceusing low-resistance ohmmeter, verifying tightness of accessiblebolted electrical connections by calibrated torque-wrench method,or performing thermographic survey.

7. Verify that all required grounding and shorting connectionsprovide good contact.

8. Verify correct operation of transformer withdrawal mechanism andgrounding operation.

9. Verify appropriate lubrication on moving current-carrying partsand on moving and sliding surfaces.

b. Electrical tests

1. Perform resistance measurements through all bolted connectionswith low-resistance ohmmeter, if applicable.

2. Perform insulation-resistance test of each current transformer andits secondary wiring.

3. Perform a polarity test of each current transformer.

4. Perform a ratio-verification test.

SECTION 26 12 19.10 Page 18 July 07, 2015

Page 31: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.6.1.3 Grounding System

a. Visual and mechanical inspection

1. Inspect ground system for compliance with contract plans andspecifications.

b. Electrical tests

1. Perform ground-impedance measurements utilizing thefall-of-potential method. On systems consisting of interconnectedground rods, perform tests after interconnections are complete.On systems consisting of a single ground rod perform tests beforeany wire is connected. Take measurements in normally dry weather,not less than 48 hours after rainfall. Use a portable groundtesting megger in accordance with manufacturer's instructions totest each ground or group of grounds. The instrument shall beequipped with a meter reading directly in ohms or fractionsthereof to indicate the ground value of the ground rod orgrounding systems under test.

2. Submit the measured ground resistance of each ground rod andgrounding system, indicating the location of the rod and groundingsystem. Include the test method and test setup (i.e., pinlocation) used to determine ground resistance and soil conditionsat the time the measurements were made.

3.6.1.4 Surge Arresters, Medium- and High-Voltage

a. Visual and mechanical inspection

1. Compare equipment nameplate data with specifications and approvedshop drawings.

2. Inspect physical and mechanical condition.

3. Inspect anchorage, alignment, grounding, and clearances.

4. Verify the arresters are clean.

5. Inspect all bolted electrical connections for high resistanceusing low-resistance ohmmeter, verifying tightness of accessiblebolted electrical connections by calibrated torque-wrench method,or performing thermographic survey.

6. Verify that the ground lead on each device is individuallyattached to a ground bus or ground electrode.

b. Electrical tests

1. Perform resistance measurements through all bolted connectionswith low-resistance ohmmeter, if applicable.

2. Perform an insulation-resistance test on each arrester, phaseterminal-to-ground.

3. Test grounding connection.

SECTION 26 12 19.10 Page 19 July 07, 2015

Page 32: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.6.2 Follow-Up Verification

Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that circuits and devices are in good operating condition and properly performing the intended function. As an exception to requirements stated elsewhere in the contract, the Contracting Officer shall be given 5 working days advance notice of the dates and times of checking and testing.

-- End of Section --

SECTION 26 12 19.10 Page 20 July 07, 2015

Page 33: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION TABLE OF CONTENTS

DIVISION 33 - UTILITIES

SECTION 33 71 02

UNDERGROUND ELECTRICAL DISTRIBUTION

02/14

PART 1 GENERAL

1.1 REFERENCES 1.2 DEFINITIONS 1.3 SUBMITTALS 1.4 QUALITY ASSURANCE 1.4.1 Certificate of Competency for Cable Splicer/Terminator 1.4.2 Cable Installer Qualifications 1.4.3 Regulatory Requirements 1.4.4 Standard Products

1.4.4.1 Alternative Qualifications1.4.4.2 Material and Equipment Manufacturing Date

PART 2 PRODUCTS

2.1 CONDUIT, DUCTS, AND FITTINGS 2.1.1 Rigid Metal Conduit

2.1.1.1 Rigid Metallic Conduit, PVC Coated 2.1.2 Plastic Duct for Concrete Encasement 2.1.3 Conduit Sealing Compound 2.1.4 Fittings

2.1.4.1 Metal Fittings2.1.4.2 PVC Conduit Fittings2.1.4.3 PVC Duct Fittings2.1.4.4 Outlet Boxes for Steel Conduit

2.2 LOW VOLTAGE INSULATED CONDUCTORS AND CABLES 2.2.1 Conductor Types 2.2.2 Conductor Material 2.2.3 Jackets 2.2.4 Cable Marking 2.3 LOW VOLTAGE WIRE CONNECTORS AND TERMINALS 2.4 LOW VOLTAGE SPLICES 2.4.1 Heat Shrinkable Splice 2.4.2 Cold Shrink Rubber Splice 2.5 MEDIUM VOLTAGE CABLE 2.5.1 Cable Configuration 2.5.2 Conductor Material 2.5.3 Insulation 2.5.4 Shielding 2.5.5 Jackets 2.6 MEDIUM VOLTAGE CABLE TERMINATIONS 2.6.1 Cold-Shrink Type 2.6.2 Heat Shrinkable Type 2.6.3 Separable Insulated Connector Type 2.7 MEDIUM VOLTAGE CABLE JOINTS 2.7.1 Heat-Shrinkable Joint

SECTION 33 71 02 Page 1 July 07, 2015

Page 34: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

2.7.2 Cold-Shrink Rubber-Type Joint 2.8 LIVE END CAPS 2.9 TAPE 2.9.1 Insulating Tape 2.9.2 2.4 BURIED WARNING AND IDENTIFICATION TAPE 2.9.2.1 2.4.1 Detectable Warning Tape for Non-Metallic Piping 2.9.3 Fireproofing Tape 2.10 PULL ROPE 2.11 GROUNDING AND BONDING 2.11.1 Driven Ground Rods 2.11.2 Grounding Conductors 2.12 CAST-IN-PLACE CONCRETE 2.13 UNDERGROUND STRUCTURES 2.13.1 Cast-In-Place Concrete Structures 2.14 CABLE TAGS IN MANHOLES 2.14.1 Polyethylene Cable Tags 2.15 SOURCE QUALITY CONTROL 2.15.1 Arc-Proofing Test for Cable Fireproofing Tape 2.15.2 Medium Voltage Cable Qualification and Production Tests

PART 3 EXECUTION

3.1 INSTALLATION 3.2 CABLE INSPECTION 3.3 UNDERGROUND FEEDERS SUPPLYING BUILDINGS 3.4 UNDERGROUND STRUCTURE CONSTRUCTION 3.4.1 Cast-In-Place Concrete Structures 3.5 UNDERGROUND CONDUIT AND DUCT SYSTEMS 3.5.1 Requirements 3.5.2 Treatment 3.5.3 Conduit Cleaning 3.5.4 Multiple Conduits 3.5.5 Conduit Plugs and Pull Rope 3.5.6 Conduit and Duct Without Concrete Encasement 3.5.6.1 Encasement Under Roads and Structures 3.5.7 Duct Encased in Concrete 3.5.7.1 Connections to Manholes 3.5.7.2 Connections to Existing Underground Structures 3.5.7.3 Connections to Existing Concrete Pads 3.5.7.4 Connections to Existing Ducts 3.5.7.5 Partially Completed Duct Banks 3.5.7.6 Removal of Ducts 3.6 CABLE PULLING 3.6.1 Cable Lubricants 3.7 CABLES IN UNDERGROUND STRUCTURES 3.7.1 Cable Tag Installation 3.8 CONDUCTORS INSTALLED IN PARALLEL 3.9 LOW VOLTAGE CABLE SPLICING AND TERMINATING 3.10 MEDIUM VOLTAGE CABLE TERMINATIONS 3.11 MEDIUM VOLTAGE CABLE JOINTS 3.11.1 Joints in Shielded Cables 3.12 CABLE END CAPS 3.13 LIVE END CAPS 3.14 FIREPROOFING OF CABLES IN UNDERGROUND STRUCTURES 3.14.1 Fireproofing Tape 3.14.2 Tape-Wrap 3.15 GROUNDING SYSTEMS 3.15.1 Grounding Electrodes 3.15.2 Grounding Connections

SECTION 33 71 02 Page 2 July 07, 2015

Page 35: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.15.3 Grounding Conductors 3.15.4 Ground Cable Crossing Expansion Joints 3.15.5 Manhole Grounding 3.15.6 Fence Grounding 3.16 EXCAVATING, BACKFILLING, AND COMPACTING 3.16.1 Reconditioning of Surfaces

3.16.1.1 Unpaved Surfaces3.16.1.2 Paving Repairs

3.17 CAST-IN-PLACE CONCRETE 3.17.1 Concrete Slabs for Equipment 3.17.2 Sealing 3.18 FIELD QUALITY CONTROL 3.18.1 Performance of Field Acceptance Checks and Tests

3.18.1.1 Medium Voltage Cables3.18.1.2 Low Voltage Cables, 600-Volt3.18.1.3 Grounding System

3.18.2 Follow-Up Verification

-- End of Section Table of Contents --

SECTION 33 71 02 Page 3 July 07, 2015

Page 36: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

SECTION 33 71 02

UNDERGROUND ELECTRICAL DISTRIBUTION02/14

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASSOCIATION OF EDISON ILLUMINATING COMPANIES (AEIC)

AEIC CS8 (2007) specification for Extruded Dielectric Shielded Power Cables Rated 5 Through 46 kV

ASTM INTERNATIONAL (ASTM)

ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire

ASTM B3 (2013) Standard Specification for Soft or Annealed Copper Wire

ASTM B496 (2013a) Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors

ASTM B8 (2011) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft

ASTM C309 (2011) Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete

ASTM C478 (2013) Standard Specification for Precast Reinforced Concrete Manhole Sections

ASTM C857 (2013) Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures

ASTM F512 (2012) Smooth-Wall Poly (Vinyl Chloride) (PVC) Conduit and Fittings for Underground Installation

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 386 (2006; INT 1 2011) Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600V

SECTION 33 71 02 Page 4 July 07, 2015

Page 37: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

IEEE 404 (2012) Standard for Extruded and Laminated Dielectric Shielded Cable Joints Rated 2500 V to 500,000 V

IEEE 48 (2009) Standard for Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5 kV through 500 kV

IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System

IEEE C2 (2012; Errata 2012; INT 1-4 2012; INT 5-7 2013) National Electrical Safety Code

IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of Terms & Definitions

INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

ICEA S-94-649 (2013) Standard for Concentric Neutral Cables Rated 5 Through 46 KV

INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

ANSI C119.1 (2011) Electric Connectors - Sealed Insulated Underground Connector Systems Rated 600 Volts

ANSI/NEMA WC 71/ICEA S-96-659 (1999) Standard for Nonshielded Cables Rated 2001-5000 Volts for use in the Distribution of Electric Energy

NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit

NEMA TC 2 (2013) Standard for Electrical Polyvinyl Chloride (PVC) Conduit

NEMA TC 9 (2004) Standard for Fittings for Polyvinyl Chloride (PVC) Plastic Utilities Duct for Underground Installation

NEMA WC 74/ICEA S-93-639 (2012) 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy

SECTION 33 71 02 Page 5 July 07, 2015

Page 38: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013) National Electrical Code

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

TIA-758 (2012b) Customer-Owned Outside Plant Telecommunications Infrastructure Standard

U.S. DEPARTMENT OF AGRICULTURE (USDA)

RUS Bull 1751F-644 (2002) Underground Plant Construction

UNDERWRITERS LABORATORIES (UL)

UL 1072 (2006; Reprint Jun 2013) Medium-Voltage Power Cables

UL 44 (2010) Thermoset-Insulated Wires and Cables

UL 467 (2007) Grounding and Bonding Equipment

UL 486A-486B (2013; Reprint Dec 2013) Wire Connectors

UL 510 (2005; Reprint Jul 2013) Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape

UL 514A (2013) Metallic Outlet Boxes

UL 514B (2012) Conduit, Tubing and Cable Fittings

UL 6 (2007; reprint Nov 2010) Electrical Rigid Metal Conduit-Steel

UL 651 (2011; Reprint Mar 2012) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings

UL 854 (2004; Reprint Sep 2011) Standard for Service-Entrance Cables

1.2 DEFINITIONS

a. Unless otherwise specified or indicated, electrical and electronicsterms used in these specifications, and on the drawings, are as definedin IEEE Stds Dictionary.

b. In the text of this section, the words conduit and duct are usedinterchangeably and have the same meaning.

c. In the text of this section, "medium voltage cable splices," and"medium voltage cable joints" are used interchangeably and have thesame meaning.

SECTION 33 71 02 Page 6 July 07, 2015

Page 39: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Medium voltage cable; G

Medium voltage cable joints; G

Medium voltage cable terminations; G

Live end caps; G

SD-06 Test Reports

Medium voltage cable qualification and production tests; G

Field Acceptance Checks and Tests; G

Arc-proofing test for cable fireproofing tape; G

SD-07 Certificates

Cable splicer/terminator; G

Cable Installer Qualifications; G

1.4 QUALITY ASSURANCE

1.4.1 Certificate of Competency for Cable Splicer/Terminator

The cable splicer/terminator must have a certification from the National Cable Splicing Certification Board (NCSCB) in the field of splicing and terminating shielded medium voltage (5 kV to 35 kV) power cable using pre-manufactured kits (pre-molded, heat-shrink, cold shrink). Submit "Proof of Certification" for approval, for the individuals that will be performing cable splicer and termination work, 30 days before splices or terminations are to be made.

]1.4.2 Cable Installer Qualifications

Provide at least one onsite person in a supervisory position with a documentable level of competency and experience to supervise all cable pulling operations. Provide a resume showing the cable installers' experience in the last three years, including a list of references complete with points of contact, addresses and telephone numbers. Cable installer must demonstrate experience with a minimum of three medium voltage cable installations. The Contracting Officer reserves the right to require additional proof of competency or to reject the individual and call for an alternate qualified cable installer.

1.4.3 Regulatory Requirements

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted

SECTION 33 71 02 Page 7 July 07, 2015

Page 40: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of IEEE C2 and NFPA 70 unless more stringent requirements are specified or indicated.

1.4.4 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products must have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been for sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.

1.4.4.1 Alternative Qualifications

Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

1.4.4.2 Material and Equipment Manufacturing Date

Products manufactured more than 3 years prior to date of delivery to site are not acceptable, unless specified otherwise.

PART 2 PRODUCTS

2.1 CONDUIT, DUCTS, AND FITTINGS

2.1.1 Rigid Metal Conduit

UL 6.

2.1.1.1 Rigid Metallic Conduit, PVC Coated

NEMA RN 1, Type A40, except that hardness must be nominal 85 Shore A durometer, dielectric strength must be minimum 400 volts per mil at 60 Hz, and tensile strength must be minimum 3500 psi.

2.1.2 Plastic Duct for Concrete Encasement

UL 651 and ASTM F512, NEMA TC 2, Type EPC-40-PVC.

2.1.3 Conduit Sealing Compound

Compounds for sealing ducts and conduit must have a putty-like consistency workable with the hands at temperatures as low as 35 degrees F, must neither slump at a temperature of 300 degrees F, nor harden materially when exposed to the air. Compounds must adhere to clean surfaces of fiber or plastic ducts; metallic conduits or conduit coatings; concrete, masonry, or lead; any cable sheaths, jackets, covers, or insulation materials; and the

SECTION 33 71 02 Page 8 July 07, 2015

Page 41: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

common metals. Compounds must form a seal without dissolving, noticeably changing characteristics, or removing any of the ingredients. Compounds must have no injurious effect upon the hands of workmen or upon materials.

2.1.4 Fittings

2.1.4.1 Metal Fittings

UL 514B.

2.1.4.2 PVC Conduit Fittings

UL 514B, UL 651.

2.1.4.3 PVC Duct Fittings

NEMA TC 9.

2.1.4.4 Outlet Boxes for Steel Conduit

Outlet boxes for use with rigid or flexible steel conduit must be cast-metal cadmium or zinc-coated if of ferrous metal with gasketed closures and must conform to UL 514A.

2.2 LOW VOLTAGE INSULATED CONDUCTORS AND CABLES

Insulated conductors must be rated 600 volts and conform to the requirements of NFPA 70, including listing requirements. Wires and cables manufactured more than 24 months prior to date of delivery to the site are not acceptable. Service entrance conductors must conform to UL 854, type USE.

2.2.1 Conductor Types

Cable and duct sizes indicated are for copper conductors and THHN/THWN unless otherwise noted. Conductors No. 10 AWG and smaller must be solid. Conductors No. 8 AWG and larger must be stranded. All conductors must be copper.

2.2.2 Conductor Material

Unless specified or indicated otherwise or required by NFPA 70, wires in conduit, other than service entrance, must be 600-volt, Type XHHW or RHW conforming to UL 44. Copper conductors must be annealed copper complying with ASTM B3 and ASTM B8.

2.2.3 Jackets

Multiconductor cables must have an overall PVC outer jacket.

]2.2.4 Cable Marking

Insulated conductors must have the date of manufacture and other identification imprinted on the outer surface of each cable at regular intervals throughout the cable length.

Identify each cable by means of a fiber, laminated plastic, or non-ferrous metal tags, or approved equal, in each manhole, handhole, junction box, and each terminal. Each tag must contain the following information; cable

SECTION 33 71 02 Page 9 July 07, 2015

Page 42: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

type, conductor size, circuit number, circuit voltage, cable destination and phase identification.

Conductors must be color coded. Provide conductor identification within each enclosure where a tap, splice, or termination is made. Conductor identification must be by color-coded insulated conductors, plastic-coated self-sticking printed markers, colored nylon cable ties and plates, heat shrink type sleeves,or colored electrical tape. Control circuit terminations must be properly identified. Color must be green for grounding conductors and white for neutrals; except where neutrals of more than one system are installed in same raceway or box, other neutrals must be white with a different colored (not green) stripe for each. Color of ungrounded conductors in different voltage systems must be as follows:

a. 208/120 volt, three-phase

(1) Phase A - black

(2) Phase B - red

(3) Phase C - blue

2.3 LOW VOLTAGE WIRE CONNECTORS AND TERMINALS

Must provide a uniform compression over the entire conductor contact surface. Use solderless terminal lugs on stranded conductors.

a. For use with copper conductors: UL 486A-486B.

2.4 LOW VOLTAGE SPLICES

Provide splices in conductors with a compression connector on the conductor and by insulating and waterproofing using one of the following methods which are suitable for continuous submersion in water and comply with ANSI C119.1.

2.4.1 Heat Shrinkable Splice

Provide heat shrinkable splice insulation by means of a thermoplastic adhesive sealant material applied in accordance with the manufacturer's written instructions.

2.4.2 Cold Shrink Rubber Splice

Provide a cold-shrink rubber splice which consists of EPDM rubber tube which has been factory stretched onto a spiraled core which is removed during splice installation. The installation must not require heat or flame, or any additional materials such as covering or adhesive. It must be designed for use with inline compression type connectors, or indoor, outdoor, direct-burial or submerged locations.

2.5 MEDIUM VOLTAGE CABLE

Cable (conductor) sizes are designated by American Wire Gauge (AWG) and Thousand Circular Mils (Kcmil). Conductor and conduit sizes indicated are for copper conductors unless otherwise noted. Insulated conductors must have the date of manufacture and other identification imprinted on the outer surface of each cable at regular intervals throughout cable length. Wires and cables manufactured more than 24 months prior to date of delivery

SECTION 33 71 02 Page 10 July 07, 2015

Page 43: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

to the site are not acceptable. Provide single conductor type cables unless otherwise indicated.

2.5.1 Cable Configuration

Provide Type MV cable, conforming to NEMA WC 74/ICEA S-93-639 and UL 1072 . Provide cables manufactured for use in duct applications. Cable must be rated 15 kV with 133 percent insulation level.

2.5.2 Conductor Material

Provide concentric-lay-stranded, Class B conductors. Provide soft drawn copper cables complying with ASTM B3 and ASTM B8 for regular concentric and compressed stranding or ASTM B496 for compact stranding.

2.5.3 Insulation

Provide ethylene-propylene-rubber (EPR) insulation conforming to the requirements of ANSI/NEMA WC 71/ICEA S-96-659 and ICEA S-94-649.

2.5.4 Shielding

Cables rated for 2 kV and above must have a semiconducting conductor shield, a semiconducting insulation shield, and an overall copper tape shield for each phase.

2.5.5 Jackets

Provide cables with a PVC jacket. Provide PVC jackets with a separator that prevents contact with underlying semiconducting insulating shield.

2.6 MEDIUM VOLTAGE CABLE TERMINATIONS

IEEE 48 Class 1; of the molded elastomer, prestretched elastomer, or heat-shrinkable elastomer. Acceptable elastomers are track-resistant silicone rubber or track-resistant ethylene propylene compounds, such as ethylene propylene rubber or ethylene propylene diene monomer. Separable insulated connectors may be used for apparatus terminations, when such apparatus is provided with suitable bushings. Terminations, where required, must be provided with mounting brackets suitable for the intended installation and with grounding provisions for the cable shielding, metallic sheath, or armor. Terminations must be provided in a kit, including: skirts, stress control terminator, ground clamp, connectors, lugs, and complete instructions for assembly and installation. Terminations must be the product of one manufacturer, suitable for the type, diameter, insulation class and level, and materials of the cable terminated. Do not use separate parts of copper or copper alloy in contact with aluminum alloy parts in the construction or installation of the terminator.

2.6.1 Cold-Shrink Type

Terminator must be a one-piece design, utilizing the manufacturer's latest technology, where high-dielectric constant (capacitive) stress control is integrated within a skirted insulator made of silicone rubber. Termination must not require heat or flame for installation. Termination kit must contain all necessary materials (except for the lugs). Termination must be designed for installation in low or highly contaminated indoor and outdoor locations and must resist ultraviolet rays and oxidative decomposition.

SECTION 33 71 02 Page 11 July 07, 2015

Page 44: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

2.6.2 Heat Shrinkable Type

Terminator must consist of a uniform cross section heat shrinkable polymeric construction stress relief tubing and environmentally sealed outer covering that is nontracking, resists heavy atmospheric contaminants, ultra violet rays and oxidative decomposition. Provide heat shrinkable sheds or skirts of the same material. Termination must be designed for installation in low or highly contaminated indoor or outdoor locations.

2.6.3 Separable Insulated Connector Type

IEEE 386. Provide connector with steel reinforced hook-stick eye, grounding eye, test point, and arc-quenching contact material. Provide connectors of the loadbreak or deadbreak type as indicated, of suitable construction for the application and the type of cable connected, and that include cable shield adaptors. Provide external clamping points and test points. Separable connectors must not be used in manholes/handholes.

b. 600 Ampere deadbreak connector ratings: Voltage: 15 kV, 95 kV BIL.Short time rating: 25,000 rms symmetrical amperes. Connectors musthave 200 ampere bushing interface as indicated.

2.7 MEDIUM VOLTAGE CABLE JOINTS

Provide joints (splices) in accordance with IEEE 404 suitable for the rated voltage, insulation level, insulation type, and construction of the cable. Joints must be certified by the manufacturer for waterproof, submersible applications. Upon request, supply manufacturer's design qualification test report in accordance with IEEE 404. Connectors for joint must be tin-plated electrolytic copper, having ends tapered and having center stops to equalize cable insertion.

2.7.1 Heat-Shrinkable Joint

Consists of a uniform cross-section heat-shrinkable polymeric construction with a linear stress relief system, a high dielectric strength insulating material, and an integrally bonded outer conductor layer for shielding. Replace original cable jacket with a heavy-wall heat-shrinkable sleeve with hot-melt adhesive coating.

2.7.2 Cold-Shrink Rubber-Type Joint

Joint must be of a cold shrink design that does not require any heat source for its installation. Splice insulation and jacket must be of a one-piece factory formed cold shrink sleeve made of black EPDM rubber. Splice must be packaged three splices per kit, including complete installation instructions.

2.8 LIVE END CAPS

Provide live end caps using a "kit" including a heat-shrinkable tube and a high dielectric strength, polymeric plug overlapping the conductor. End cap must conform to applicable portions of IEEE 48.

SECTION 33 71 02 Page 12 July 07, 2015

Page 45: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

2.9 TAPE

2.9.1 Insulating Tape

UL 510, plastic insulating tape, capable of performing in a continuous temperature environment of 80 degrees C.

2.9.2 2.4 BURIED WARNING AND IDENTIFICATION TAPE

Polyethylene plastic and metallic core or metallic-faced, acid- and alkali-resistant, polyethylene plastic warning tape manufactured specifically for warning and identification of buried utility lines. Provide tape on rolls, 3 inch minimum width, color coded as specified below for the intended utility with warning and identification imprinted in bold black letters continuously over the entire tape length. Warning and identification to read, "CAUTION, BURIED (intended service) LINE BELOW" or similar wording. Color and printing shall be permanent, unaffected by moisture or soil.

Warning Tape Color CodesYellow: Electric

2.9.2.1 2.4.1 Detectable Warning Tape for Non-Metallic Piping

Polyethylene plastic tape conforming to the width, color, and printing requirements specified above. Minimum thickness of the tape shall be 0.004 inch. Tape shall have a minimum strength of 1500 psi lengthwise and 1250 psi crosswise. Tape shall be manufactured with integral wires, foil backing, or other means of enabling detection by a metal detector when tape is buried up to 3 feet deep. Encase metallic element of the tape in a protective jacket or provide with other means of corrosion protection.

2.9.3 Fireproofing Tape

Provide tape composed of a flexible conformable unsupported intumescent elastomer. Tape must be not less than .030 inch thick, noncorrosive to cable sheath, self-extinguishing, noncombustible, and must not deteriorate when subjected to oil, water, gases, salt water, sewage, and fungus.

2.10 PULL ROPE

Plastic or flat pull line (bull line) having a minimum tensile strength of 200 pounds.

2.11 GROUNDING AND BONDING

2.11.1 Driven Ground Rods

Provide copper-clad steel ground rods conforming to UL 467 not less than 3/4 inch in diameter by 10 feet in length. Sectional type rods may be used for rods 20 feet or longer.

2.11.2 Grounding Conductors

Stranded-bare copper conductors must conform to ASTM B8, Class B, soft-drawn unless otherwise indicated. Solid-bare copper conductors must conform to ASTM B1 for sizes No. 8 and smaller. Insulated conductors must be of the same material as phase conductors and green color-coded, except

SECTION 33 71 02 Page 13 July 07, 2015

Page 46: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

that conductors must be rated no more than 600 volts. Aluminum is not acceptable.

2.12 CAST-IN-PLACE CONCRETE

Provide concrete for encasement of underground ducts with 3000 psi minimum 28-day compressive strength. Concrete associated with electrical work for other than encasement of underground ducts must be 4000 psi minimum 28-day compressive strength unless specified otherwise.

2.13 UNDERGROUND STRUCTURES

Provide precast concrete underground structures or standard type cast-in-place manhole types as indicated, conforming to ASTM C857 and ASTM C478. Top, walls, and bottom must consist of reinforced concrete. Walls and bottom must be of monolithic concrete construction. Locate duct entrances and windows near the corners of structures to facilitate cable racking. Covers must fit the frames without undue play. Form steel and iron to shape and size with sharp lines and angles. Castings must be free from warp and blow holes that may impair strength or appearance. Exposed metal must have a smooth finish and sharp lines and arises. Provide necessary lugs, rabbets, and brackets. Set pulling-in irons and other built-in items in place before depositing concrete. Install a pulling-in iron in the wall opposite each duct line entrance. Cable racks, including rack arms and insulators, must be adequate to accommodate the cable.

2.13.1 Cast-In-Place Concrete Structures

Construct walls on a footing of cast-in-place concrete except that precast concrete base sections may be used for precast concrete manhole risers.

2.14 CABLE TAGS IN MANHOLES

Provide tags for each power cable located in manholes. The tags must be polyethylene. Do not provide handwritten letters. The first position on the power cable tag must denote the voltage. The second through sixth positions on the tag must identify the circuit. The next to last position must denote the phase of the circuit and include the Greek "phi" symbol. The last position must denote the cable size. As an example, a tag could have the following designation: "11.5 NAS 1-8(Phase A)500," denoting that the tagged cable is on the 11.5kV system circuit number NAS 1-8, underground, Phase A, sized at 500 kcmil.

2.14.1 Polyethylene Cable Tags

Provide tags of polyethylene that have an average tensile strength of 3250 pounds per square inch; and that are 0.08 inch thick (minimum), non-corrosive non-conductive; resistive to acids, alkalis, organic solvents, and salt water; and distortion resistant to 170 degrees F. Provide 0.05 inch (minimum) thick black polyethylene tag holder. Provide a one-piece nylon, self-locking tie at each end of the cable tag. Ties must have a minimum loop tensile strength of 175 pounds. The cable tags must have black block letters, numbers, and symbols one inch high on a yellow background. Letters, numbers, and symbols must not fall off or change positions regardless of the cable tags' orientation.

SECTION 33 71 02 Page 14 July 07, 2015

Page 47: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

2.15 SOURCE QUALITY CONTROL

2.15.1 Arc-Proofing Test for Cable Fireproofing Tape

Manufacturer must test one sample assembly consisting of a straight lead tube 12 inches long with a 2 1/2 inch outside diameter, and a 1/8 inch thick wall, and covered with one-half lap layer of arc and fireproofing tape per manufacturer's instructions. The arc and fireproofing tape must withstand extreme temperature of a high-current fault arc 13,000 degrees K for 70 cycles as determined by using an argon directed plasma jet capable of constantly producing and maintaining an arc temperature of 13,000 degrees K. Temperature (13,000 degrees K) of the ignited arc between the cathode and anode must be obtained from a dc power source of 305 (plus or minus 5) amperes and 20 (plus or minus 1) volts. The arc must be directed toward the sample assembly accurately positioned 5 (plus or minus 1) millimeters downstream in the plasma from the anode orifice by fixed flow rate of argon gas (0.18 g per second). Each sample assembly must be tested at three unrelated points. Start time for tests must be taken from recorded peak current when the specimen is exposed to the full test temperature. Surface heat on the specimen prior to that time must be minimal. The end point is established when the plasma or conductive arc penetrates the protective tape and strikes the lead tube. Submittals for arc-proofing tape must indicate that the test has been performed and passed by the manufacturer.

2.15.2 Medium Voltage Cable Qualification and Production Tests

Results of AEIC CS8 qualification and production tests as applicable for each type of medium voltage cable.

PART 3 EXECUTION

3.1 INSTALLATION

Install equipment and devices in accordance with the manufacturer's published instructions and with the requirements and recommendations of NFPA 70 and IEEE C2 as applicable. In addition to these requirements, install telecommunications in accordance with TIA-758 and RUS Bull 1751F-644.

3.2 CABLE INSPECTION

Inspect each cable reel for correct storage positions, signs of physical damage, and broken end seals prior to installation. If end seal is broken, remove moisture from cable prior to installation in accordance with the cable manufacturer's recommendations.

3.3 UNDERGROUND FEEDERS SUPPLYING BUILDINGS

Connect existing secondary feeders from the existing secondary junction box to the new transformer. Modify conduits feeding the junction box from the existing transformer secodnary to interface with the secondary of the new transformer.

Encase the underground portion of the conduit in a concrete envelope and bury as specified for underground duct with concrete encasement.

3.4 UNDERGROUND STRUCTURE CONSTRUCTION

Provide standard type cast-in-place construction as specified herein and as

SECTION 33 71 02 Page 15 July 07, 2015

Page 48: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

indicated, or precast construction as specified herein. Horizontal concrete surfaces of floors must have a smooth trowel finish. Cure concrete by applying two coats of white pigmented membrane forming-curing compound in strict accordance with the manufacturer's printed instructions, except that precast concrete may be steam cured. Curing compound must conform to ASTM C309. Locate duct entrances and windows in the center of end walls (shorter) and near the corners of sidewalls (longer) to facilitate cable racking and splicing. Covers for underground structures must fit the frames without undue play. Steel and iron must be formed to shape and size with sharp lines and angles. Castings must be free from warp and blow holes that may impair strength or appearance. Exposed metal must have a smooth finish and sharp lines and arises. Provide necessary lugs, rabbets, and brackets. Set pulling-in irons and other built-in items in place before depositing concrete. Manhole locations, as indicated, are approximate. Coordinate exact manhole locations with other utilities and finished grading and paving.

3.4.1 Cast-In-Place Concrete Structures

Construct walls on a footing of cast-in-place concrete except that precast concrete base sections may be used for precast concrete manhole risers.

3.5 UNDERGROUND CONDUIT AND DUCT SYSTEMS

3.5.1 Requirements

Run conduit in straight lines except where a change of direction is necessary. Provide numbers and sizes of ducts as indicated. Ducts must have a continuous slope downward toward underground structures and away from buildings, laid with a minimum slope of 3 inches per 100 feet. Depending on the contour of the finished grade, the high-point may be at a terminal, a manhole, a handhole, or between manholes or handholes. Short-radius manufactured 90-degree duct bends may be used only for pole or equipment risers, unless specifically indicated as acceptable. The minimum manufactured bend radius must be 18 inches for ducts of less than 3 inch diameter, and 36 inches for ducts 3 inches or greater in diameter. Otherwise, long sweep bends having a minimum radius of 25 feet must be used for a change of direction of more than 5 degrees, either horizontally or vertically. Both curved and straight sections may be used to form long sweep bends, but the maximum curve used must be 30 degrees and manufactured bends must be used. Provide ducts with end bells whenever duct lines terminate in structures.

3.5.2 Treatment

Ducts must be kept clean of concrete, dirt, or foreign substances during construction. Field cuts requiring tapers must be made with proper tools and match factory tapers. A coupling recommended by the duct manufacturer must be used whenever an existing duct is connected to a duct of different material or shape. Ducts must be stored to avoid warping and deterioration with ends sufficiently plugged to prevent entry of any water or solid substances. Ducts must be thoroughly cleaned before being laid. Plastic ducts must be stored on a flat surface and protected from the direct rays of the sun.

3.5.3 Conduit Cleaning

As each conduit run is completed, for conduit sizes 3 inches and larger, draw a flexible testing mandrel approximately 12 inches long with a

SECTION 33 71 02 Page 16 July 07, 2015

Page 49: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

diameter less than the inside diameter of the conduit through the conduit. After which, draw a stiff bristle brush through until conduit is clear of particles of earth, sand and gravel; then immediately install conduit plugs. For conduit sizes less than 3 inches, draw a stiff bristle brush through until conduit is clear of particles of earth, sand and gravel; then immediately install conduit plugs.

3.5.4 Multiple Conduits

Separate multiple conduits by a minimum distance of 3 inches, except that light and power conduits must be separated from control, signal, and telephone conduits by a minimum distance of 12 inches. Stagger the joints of the conduits by rows (horizontally) and layers (vertically) to strengthen the conduit assembly. Provide plastic duct spacers that interlock vertically and horizontally. Spacer assembly must consist of base spacers, intermediate spacers, ties, and locking device on top to provide a completely enclosed and locked-in conduit assembly. Install spacers per manufacturer's instructions, but provide a minimum of two spacer assemblies per 10 feet of conduit assembly.

3.5.5 Conduit Plugs and Pull Rope

New conduit indicated as being unused or empty must be provided with plugs on each end. Plugs must contain a weephole or screen to allow water drainage. Provide a plastic pull rope having 3 feet of slack at each end of unused or empty conduits.

3.5.6 Conduit and Duct Without Concrete Encasement

Depths to top of the conduit must be not less than 24 inches below finished grade. Provide not less than 3 inches clearance from the conduit to each side of the trench. Grade bottom of trench smooth; where rock, soft spots, or sharp-edged materials are encountered, excavate the bottom for an additional 3 inches, fill and tamp level with original bottom with sand or earth free from particles, that would be retained on a 1/4 inch sieve. The first 6 inch layer of backfill cover must be sand compacted as previously specified. The rest of the excavation must be backfilled and compacted in 3 to 6 inch layers. Provide color, type and depth of warning tape as specified in this section.

3.5.6.1 Encasement Under Roads and Structures

Under roads, paved areas, and railroad tracks, install conduits in concrete encasement of rectangular cross-section providing a minimum of 3 inch concrete cover around ducts. Concrete encasement must extend at least 5 feet beyond the edges of paved areas and roads, and 12 feet beyond the rails on each side of railroad tracks. Depths to top of the concrete envelope must be not less than 24 inches below finished grade.

3.5.7 Duct Encased in Concrete

Construct underground duct lines of individual conduits encased in concrete. Depths to top of the concrete envelope must be not less than 18 inches below finished grade. Do not mix different kinds of conduit in any one duct bank. Concrete encasement surrounding the bank must be rectangular in cross-section and must provide at least 3 inches of concrete cover for ducts. Separate conduits by a minimum concrete thickness of 3 inches. Before pouring concrete, anchor duct bank assemblies to prevent the assemblies from floating during concrete pouring. Anchoring must be

SECTION 33 71 02 Page 17 July 07, 2015

Page 50: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

done by driving reinforcing rods adjacent to duct spacer assemblies and attaching the rods to the spacer assembly.

3.5.7.1 Connections to Manholes

Duct bank envelopes connecting to underground structures must be flared to have enlarged cross-section at the manhole entrance to provide additional shear strength. Dimensions of the flared cross-section must be larger than the corresponding manhole opening dimensions by no less than 12 inches in each direction. Perimeter of the duct bank opening in the underground structure must be flared toward the inside or keyed to provide a positive interlock between the duct bank and the wall of the structure. Use vibrators when this portion of the encasement is poured to assure a seal between the envelope and the wall of the structure.

3.5.7.2 Connections to Existing Underground Structures

For duct bank connections to existing structures, break the structure wall out to the dimensions required and preserve steel in the structure wall. Cut steel and extend into the duct bank envelope. Chip the perimeter surface of the duct bank opening to form a key or flared surface, providing a positive connection with the duct bank envelope.

3.5.7.3 Connections to Existing Concrete Pads

For duct bank connections to concrete pads, break an opening in the pad out to the dimensions required and preserve steel in pad. Cut the steel and extend into the duct bank envelope. Chip out the opening in the pad to form a key for the duct bank envelope.

3.5.7.4 Connections to Existing Ducts

Where connections to existing duct banks are indicated, excavate the banks to the maximum depth necessary. Cut off the banks and remove loose concrete from the conduits before new concrete-encased ducts are installed. Provide a reinforced concrete collar, poured monolithically with the new duct bank, to take the shear at the joint of the duct banks. Remove existing cables which constitute interference with the work.

3.5.7.5 Partially Completed Duct Banks

During construction wherever a construction joint is necessary in a duct bank, prevent debris such as mud, and, and dirt from entering ducts by providing suitable conduit plugs. Fit concrete envelope of a partially completed duct bank with reinforcing steel extending a minimum of 2 feet back into the envelope and a minimum of 2 feet beyond the end of the envelope. Provide one No. 4 bar in each corner, 3 inches from the edge of the envelope. Secure corner bars with two No. 3 ties, spaced approximately one footapart. Restrain reinforcing assembly from moving during concrete pouring.

3.5.7.6 Removal of Ducts

Where duct lines are removed from existing underground structures, close the openings to waterproof the structure. Chip out the wall opening to provide a key for the new section of wall.

SECTION 33 71 02 Page 18 July 07, 2015

Page 51: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.6 CABLE PULLING

Test existing duct lines with a mandrel and thoroughly swab out to remove foreign material before pulling cables. Pull cables down grade with the feed-in point at the manhole or buildings of the highest elevation. Use flexible cable feeds to convey cables through manhole opening and into duct runs. Do not exceed the specified cable bending radii when installing cable under any conditions, including turnups into switches, transformers, switchgear, switchboards, and other enclosures. Cable with tape shield must have a bending radius not less than 12 times the overall diameter of the completed cable. If basket-grip type cable-pulling devices are used to pull cable in place, cut off the section of cable under the grip before splicing and terminating.

3.6.1 Cable Lubricants

Use lubricants that are specifically recommended by the cable manufacturer for assisting in pulling jacketed cables.

3.7 CABLES IN UNDERGROUND STRUCTURES

Do not install cables utilizing the shortest path between penetrations, but route along those walls providing the longest route and the maximum spare cable lengths. Form cables to closely parallel walls, not to interfere with duct entrances, and support on brackets and cable insulators. Support cable splices in underground structures by racks on each side of the splice. Locate splices to prevent cyclic bending in the spliced sheath. Install cables at middle and bottom of cable racks, leaving top space open for future cables, except as otherwise indicated for existing installations. Provide one spare three-insulator rack arm for each cable rack in each underground structure.

3.7.1 Cable Tag Installation

Install cable tags in each manhole as specified, including each splice. Tag wire and cable provided by this contract. Install cable tags over the fireproofing, if any, and locate the tags so that they are clearly visible without disturbing any cabling or wiring in the manholes.

3.8 CONDUCTORS INSTALLED IN PARALLEL

Conductors must be grouped such that each conduit of a parallel run contains 1 Phase A conductor, 1 Phase B conductor, 1 Phase C conductor, and 1 neutral conductor.

3.9 LOW VOLTAGE CABLE SPLICING AND TERMINATING

Make terminations and splices with materials and methods as indicated or specified herein and as designated by the written instructions of the manufacturer. Do not allow the cables to be moved until after the splicing material has completely set.3.10 MEDIUM VOLTAGE CABLE TERMINATIONS

Make terminations in accordance with the written instruction of the termination kit manufacturer.

3.11 MEDIUM VOLTAGE CABLE JOINTS

Provide power cable joints (splices) suitable for continuous immersion in water. Make joints only in accessible locations in manholes or handholes

SECTION 33 71 02 Page 19 July 07, 2015

Page 52: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

by using materials and methods in accordance with the written instructions of the joint kit manufacturer.

3.11.1 Joints in Shielded Cables

Cover the joined area with metallic tape, or material like the original cable shield and connect it to the cable shield on each side of the splice. Provide a bare copper ground connection brought out in a watertight manner and grounded to the manhole grounding loop as part of the splice installation. Ground conductors, connections, and rods must be as specified elsewhere in this section. Wire must be trained to the sides of the enclosure to prevent interference with the working area.

3.12 CABLE END CAPS

Cable ends must be sealed at all times with coated heat shrinkable end caps. Cables ends must be sealed when the cable is delivered to the job site, while the cable is stored and during installation of the cable. The caps must remain in place until the cable is spliced or terminated. Sealing compounds and tape are not acceptable substitutes for heat shrinkable end caps. Cable which is not sealed in the specified manner at all times will be rejected.

3.13 LIVE END CAPS

Provide live end caps for single conductor medium voltage cables where indicated.

3.14 FIREPROOFING OF CABLES IN UNDERGROUND STRUCTURES

Fireproof (arc proof) wire and cables which will carry current at 2200 volts or more in underground structures.

3.14.1 Fireproofing Tape

Tightly wrap strips of fireproofing tape around each cable spirally in half-lapped wrapping. Install tape in accordance with manufacturer's instructions.

3.14.2 Tape-Wrap

Tape-wrap metallic-sheathed or metallic armored cables without a nonmetallic protective covering over the sheath or armor prior to application of fireproofing. Wrap must be in the form of two tightly applied half-lapped layers of a pressure-sensitive 10 mil thick plastic tape, and must extend not less than one inch into the duct. Even out irregularities of the cable, such as at splices, with insulation putty before applying tape.

3.15 GROUNDING SYSTEMS

NFPA 70 and IEEE C2, except provide grounding systems with a resistance to solid earth ground not exceeding 5 ohms.

3.15.1 Grounding Electrodes

Provide cone pointed driven ground rods driven full depth plus 6 inches, installed to provide an earth ground of the appropriate value for the particular equipment being grounded.

SECTION 33 71 02 Page 20 July 07, 2015

Page 53: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

If the specified ground resistance is not met, an additional ground rod must be provided in accordance with the requirements of NFPA 70 (placed not less than 6 feet from the first rod). Should the resultant (combined) resistance exceed the specified resistance, measured not less than 48 hours after rainfall, notify the Contracting Officer immediately.

3.15.2 Grounding Connections

Make grounding connections which are buried or otherwise normally inaccessible, by exothermic weld or compression connector.

a. Make exothermic welds strictly in accordance with the weld manufacturer's written recommendations. Welds which are "puffed up" or which show convex surfaces indicating improper cleaning are not acceptable. Mechanical connectors are not required at exothermic welds.

b. Make compression connections using a hydraulic compression tool to provide the correct circumferential pressure. Tools and dies must be as recommended by the manufacturer. An embossing die code or other standard method must provide visible indication that a connector has been adequately compressed on the ground wire.

3.15.3 Grounding Conductors

Provide bare grounding conductors, except where installed in conduit with associated phase conductors. Ground cable sheaths, cable shields, conduit, and equipment with No. 6 AWG. Ground other noncurrent-carrying metal parts and equipment frames of metal-enclosed equipment. Ground metallic frames and covers of handholes and pull boxes with a braided, copper ground strap with equivalent ampacity of No. 6 AWG.

3.15.4 Ground Cable Crossing Expansion Joints

Protect ground cables crossing expansion joints or similar separations in structures and pavements by use of approved devices or methods of installation which provide the necessary slack in the cable across the joint to permit movement. Use stranded or other approved flexible copper cable across such separations.

3.15.5 Manhole Grounding

Loop a 4/0 AWG grounding conductor around the interior perimeter, approximately 12 inches above finished floor. Secure the conductor to the manhole walls at intervals not exceeding 36 inches. Connect the conductor to the manhole grounding electrode with 4/0 AWG conductor. Connect all incoming 4/0 grounding conductors to the ground loop adjacent to the point of entry into the manhole. Bond the ground loop to all cable shields, metal cable racks, and other metal equipment with a minimum 6 AWG conductor.

3.15.6 Fence Grounding

Provide grounding for fences as indicated. Drive ground rods until the top is 12 inches below grade. Attach a No. 4 AWG copper conductor, by exothermic weld to the ground rods and extend underground to the immediate vicinity of fence post. Lace the conductor vertically into 12 inches of fence mesh and fasten by two approved bronze compression fittings, one to bond wire to post and the other to bond wire to fence. Each gate section must be bonded to its gatepost by a 1/8 by one inch flexible braided copper strap and ground post clamps. Clamps must be of the anti-electrolysis type.

SECTION 33 71 02 Page 21 July 07, 2015

Page 54: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.16 EXCAVATING, BACKFILLING, AND COMPACTING

Provide in accordance with NFPA 70.

3.16.1 Reconditioning of Surfaces

3.16.1.1 Unpaved Surfaces

Restore to their original elevation and condition unpaved surfaces disturbed during installation of duct . Preserve sod and topsoil removed during excavation and reinstall after backfilling is completed. Replace sod that is damaged by sod of quality equal to that removed. When the surface is disturbed in a newly seeded area, re-seed the restored surface with the same quantity and formula of seed as that used in the original seeding, and provide topsoiling, fertilizing, liming, seeding, sodding, sprigging, or mulching.

3.16.1.2 Paving Repairs

Where trenches, pits, or other excavations are made in existing roadways and other areas of pavement where surface treatment of any kind exists , restore such surface treatment or pavement the same thickness and in the same kind as previously existed, except as otherwise specified, and to match and tie into the adjacent and surrounding existing surfaces.

3.17 CAST-IN-PLACE CONCRETE

Provide concrete in accordance with this section .

3.17.1 Concrete Slabs for Equipment

Unless otherwise indicated, the slab must be at least 8 inches thick, reinforced with a 6 by 6 - W2.9 by W2.9 mesh, placed uniformly 4 inches from the top of the slab. Slab must be placed on a 6 inch thick, well-compacted gravel base. Top of concrete slab must be approximately 4 inches above finished grade with gradual slope for drainage. Edges above grade must have 1/2 inch chamfer. Slab must be of adequate size to project at least 8 inches beyond the equipment.

Stub up conduits, with bushings, 2 inches into cable wells in the concrete pad. Coordinate dimensions of cable wells with transformer cable training areas.

3.17.2 Sealing

When the installation is complete, seal all conduit and other entries into the equipment enclosure with an approved sealing compound. Seals must be of sufficient strength and durability to protect all energized live parts of the equipment from rodents, insects, or other foreign matter.

3.18 FIELD QUALITY CONTROL

3.18.1 Performance of Field Acceptance Checks and Tests

Perform in accordance with the manufacturer's recommendations, and include the following visual and mechanical inspections and electrical tests, performed in accordance with NETA ATS.

SECTION 33 71 02 Page 22 July 07, 2015

Page 55: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.18.1.1 Medium Voltage Cables

Perform tests after installation of cable, splices, and terminators and before terminating to equipment or splicing to existing circuits.

a. Visual and Mechanical Inspection

(1) Inspect exposed cable sections for physical damage.

(2) Verify that cable is supplied and connected in accordance withcontract plans and specifications.

(3) Inspect for proper shield grounding, cable support, and cable termination.

(4) Verify that cable bends are not less than ICEA or manufacturer's minimum allowable bending radius.

(5) Inspect for proper fireproofing.

(6) Visually inspect jacket and insulation condition.

(7) Inspect for proper phase identification and arrangement.

b. Electrical Tests

(1) Perform a shield continuity test on each power cable by ohmmetermethod. Record ohmic value, resistance values in excess of 10 ohms per 1000 feet of cable must be investigated and justified.

(2) Perform acceptance test on new cables before the new cables are connected to existing cables and placed into service, including terminations and joints. Provide Insulation resitance testing of existing cable or where new cable assemblies connect to existing cable. Test the completed circuits with a 5000 volt megaohm tester. The reading should be 15 megaohms and climbing. If there is a problem reaching this level contact Chris Eyler at 341-1712. Test voltages must be as follows:

CABLE RATING AC TEST VOLTAGEfor ACCEPTANCE TESTING

5 kV 10kV rms(peak)

8 kV 13kV rms(peak)

15 kV 20kV rms(peak)

25 kV 31kV rms(peak)

35 kV 44kV rms(peak)

CABLE RATING AC TEST VOLTAGEfor MAINTENANCE TESTING

5 kV 7kV rms(peak)

SECTION 33 71 02 Page 23 July 07, 2015

Page 56: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

CABLE RATING AC TEST VOLTAGEfor MAINTENANCE TESTING

8 kV 10kV rms(peak)

15 kV 16kV rms(peak)

25 kV 23kV rms(peak)

35 kV 33kV rms(peak)

3.18.1.2 Low Voltage Cables, 600-Volt

Perform tests after installation of cable, splices and terminations and before terminating to equipment or splicing to existing circuits.

a. Visual and Mechanical Inspection

(1) Inspect exposed cable sections for physical damage.

(2) Verify that cable is supplied and connected in accordance withcontract plans and specifications.

(3) Verify tightness of accessible bolted electrical connections.

(4) Inspect compression-applied connectors for correct cable match and indentation.

(5) Visually inspect jacket and insulation condition.

(6) Inspect for proper phase identification and arrangement.

b. Electrical Tests

(1) Perform insulation resistance tests on wiring No. 6 AWG and largerdiameter using instrument which applies voltage of approximately 1000 volts dc for one minute.

(2) Perform continuity tests to insure correct cable connection.

3.18.1.3 Grounding System

a. Visual and mechanical inspection

Inspect ground system for compliance with contract plans and specifications

b. Electrical tests

Perform ground-impedance measurements utilizing the fall-of-potential method in accordance with IEEE 81. On systems consisting of interconnected ground rods, perform tests after interconnections are complete. On systems consisting of a single ground rod perform tests before any wire is connected. Take measurements in normally dry weather, not less than 48 hours after rainfall. Use a portable megohmmeter tester in accordance with manufacturer's instructions to test each ground or group of grounds. The instrument must be equipped with a meter reading directly in ohms or fractions thereof to indicate the ground value of the ground rod or grounding systems under test.

SECTION 33 71 02 Page 24 July 07, 2015

Page 57: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SPECIFICATIONS REPLACE BUILDING SC-401 TRANSFORMERNAVAL SUPPORT ACTIVITY, HAMPTON ROADS, NORFOLK, NORFOLK, VA

3.18.2 Follow-Up Verification

Upon completion of acceptance checks and tests, show by demonstration in service that circuits and devices are in good operating condition and properly performing the intended function. As an exception to requirements stated elsewhere in the contract, the Contracting Officer must be given 5 working days advance notice of the dates and times of checking and testing.

-- End of Section --

SECTION 33 71 02 Page 25 July 07, 2015

Page 58: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 1 OF 2 PAGES

REPLACE BUILDING SC-401 TRANSFORMER

26 08 00 SD-06 Test Reports3.1 GAcceptance tests and inspections

SD-07 Certificates1.4.1 GQualifications1.4.3 GAcceptance test and inspections

procedure26 12 19.10 SD-02 Shop Drawings

1.5.1 GPad-mounted transformerdrawings

SD-03 Product Data2.2 GPad-mounted transformers

SD-06 Test Reports3.6.1 GAcceptance checks and tests

SD-07 Certificates2.2.2.1 GTransformer Efficiencies

SD-09 Manufacturer’s FieldReports

2.8.2 Gdesign tests2.8.3 Groutine and other tests

SD-10 Operation and MaintenanceData

1.6.1 GTransformer(s)SD-11 Closeout Submittals

2.8.1 GTransformer test schedule33 71 02 SD-03 Product Data

2.5 GMedium voltage cable

SUBMITTAL REGISTERCONTRACT NO.

TITLE AND LOCATION CONTRACTOR

CONTRACTOR:SCHEDULE DATES

CONTRACTORACTION

APPROVING AUTHORITY

ACTIVITY NO

TRANSMITTAL NO

SPEC SECT

DESCRIPTION

ITEM SUBMITTED

PARAGRAPH

#

CLASSIFICATION

GOVT OR A/E REVWR SUBMIT

APPROVALNEEDED

BY

MATERIALNEEDED

BY

ACTION CODE

DATEOF

ACTION

DATE FWDTO APPR

AUTH/

DATE RCDFROM

CONTR

DATE FWDTO OTHERREVIEWER

DATE RCDFROM OTHREVIEWER

ACTION CODE

DATEOF

ACTION

MAILEDTO

CONTR/

DATE RCDFRM APPR

AUTH REMARKS

(a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) (o) (p) (q) (r)

Page 59: PROJECT TABLE OF CONTENTSops.noahent.com/BIDDING/9828/Building SC-401... · specifications replace building sc-401 transformer naval support activity, hampton roads, norfolk, norfolk,

SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 2 OF 2 PAGES

REPLACE BUILDING SC-401 TRANSFORMER

33 71 02 2.7 GMedium voltage cable joints2.6 GMedium voltage cable

terminations2.8 GLive end caps

SD-06 Test Reports2.15.2 GMedium voltage cable

qualification and production tests3.18.1 GField Acceptance Checks and

Tests2.15.1 GArc-proofing test

SD-07 Certificates1.4.1 GCable splicer/terminator1.4.2 GCable Installer Qualifications

SUBMITTAL REGISTERCONTRACT NO.

TITLE AND LOCATION CONTRACTOR

CONTRACTOR:SCHEDULE DATES

CONTRACTORACTION

APPROVING AUTHORITY

ACTIVITY NO

TRANSMITTAL NO

SPEC SECT

DESCRIPTION

ITEM SUBMITTED

PARAGRAPH

#

CLASSIFICATION

GOVT OR A/E REVWR SUBMIT

APPROVALNEEDED

BY

MATERIALNEEDED

BY

ACTION CODE

DATEOF

ACTION

DATE FWDTO APPR

AUTH/

DATE RCDFROM

CONTR

DATE FWDTO OTHERREVIEWER

DATE RCDFROM OTHREVIEWER

ACTION CODE

DATEOF

ACTION

MAILEDTO

CONTR/

DATE RCDFRM APPR

AUTH REMARKS

(a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) (o) (p) (q) (r)