Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft
Page 2: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-30 16:58:27Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:Living/Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

1 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh8409 Structure Btuh4865Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh8409 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh5059

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh244Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0469469Area (ft²) Equipment latent load Btuh244

42214221Volume (ft³)Air changes/hour 0.220.62 Equipment total load Btuh5303Equiv. AVF (cfm) 1544 Req. total capacity at 0.70 SHR ton0.6

Heating Equipment Summary Cooling Equipment Summary

Make 12000 btuh Ductless Mini Split Make 12000 btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm253 Actual air flow cfm253Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 0.95

Page 3: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-30 16:58:27Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1

...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

BR Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information1 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

20

40

60

80

100

120

140

160

180

200

220

240

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 4: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-30 16:58:27Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

Living/Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information1 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

50

100

150

200

250

300

350

400

450

500

550

600

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 5: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 16:58:27

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:BR Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name BR Zone Bedroom2 Exposed wall 24.0 ft 24.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft10.0x14.05 Room area 140.0 f t² 140.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 126 114 539 270 126 114 539 270. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 12 0 193 168 12 0 193 168. DD 11N011N0 0.3500.350 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 90 90 426 213 90 90 426 213

11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0WW 12C-0sw12C-0sw 0.0910.091 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 140 140 371 218 140 140 371 218FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 140 24 361 0 140 24 361 0

6 c) AED excursion 0 0

Envelope loss/gain 1891 869 1891 869

12 a) Infiltration 690 111 690 111b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 2581 980 2581 980

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 2581 980 2581 98015 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 2581 980 2581 980Air required (cfm)Air required (cfm) 51 51 51 51

Page 6: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 16:58:27

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living/Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Living/Kitch Zon Living/Kitchen2 Exposed wall 76.0 ft 56.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft370.0x1.05 Room area 469.0 f t² 370.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 135 86 407 203 135 86 407 203. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 28 0 451 392 28 0 451 392. DD 11N011N0 0.3500.350 nn 18.2018.20 10.8510.85 21 21 382 228 21 21 382 228. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 99 99 468 234 0 0 0 0

11 WW 12C-0sw12C-0sw 0.0910.091 ss 4.734.73 2.372.37 261 261 1235 618 180 180 852 426WW 12C-0sw12C-0sw 0.0910.091 ww 4.734.73 2.372.37 189 189 894 447 189 189 894 447CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 469 469 1244 730 370 370 981 576FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 469 76 1142 0 370 56 842 0

6 c) AED excursion 0 0

Envelope loss/gain 6224 2852 4809 2272

12 a) Infiltration 2185 353 1610 260b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 2 460 2 460Appliances/other 1200 1200

Subtotal (lines 6 to 13) 8409 4865 6419 4192

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 1990 673

14 Subtotal 8409 4865 8409 486515 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 8409 4865 8409 4865Air required (cfm)Air required (cfm) 253 253 253 253

Page 7: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 16:58:27

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3...ings\User\My Documents\Dropbox\Project Files\AEA-1 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living/Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Bath2 Exposed wall 20.0 ft3 Ceiling height 9.0 heat/coolft4 Room dimensions ft11.0x9.05 Room area 99.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area Loadnumber (Bt uh/f t²- °F) (Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 W 12C-0sw 0.091 n 4.73 2.37 0 0 0 0. G 2 glazing, clr outr, 0.310 n 16.12 14.01 0 0 0 0. D 11N0 0.350 n 18.20 10.85 0 0 0 0. W 12C-0sw 0.091 e 4.73 2.37 99 99 468 234

11 W 12C-0sw 0.091 s 4.73 2.37 81 81 383 192W 12C-0sw 0.091 w 4.73 2.37 0 0 0 0C 18A-19xd 0.051 - 2.65 1.56 99 99 263 154F 22B-5tpl 0.289 - 15.03 0.00 99 20 301 0

6 c) AED excursion 0

Envelope loss/gain 1415 580

12 a) Infiltration 575 93b) Room ventilation 0 0

13 Internal gains: Occupants @ 230 0 0Appliances/other 0

Subtotal (lines 6 to 13) 1990 673

Less external load 0 0Less transfer 0 0Redistribution -1990 -673

14 Subtotal 0 015 Duct loads -0% 0% 0 0

Total room load 0 0Air required (cfm) 0 0

Page 8: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Job #:Performed for:1 Bedroom Apartment

NM

Salome Arciniega, PE, LEED AP, MS...

Architectural Engineering AssociatesAlbuquerque, NM

Scale: 1 : 48

Page 1

Right -Suite® Uni versal

8.0.20 RSU15338

2012-Aug-30 17:02:58

...\Project Files\AEA-1 Bedroom.rup

N

Level 1

Living/Kitchen

Bedroom

Bath

Page 9: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft
Page 10: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft
Page 11: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-30 17:23:09Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:BR Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

2 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh1270 Structure Btuh559Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh1270 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh581

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh-22Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0100100Area (ft²) Equipment latent load Btuh0900900Volume (ft³)

Air changes/hour 0.150.39 Equipment total load Btuh581Equiv. AVF (cfm) 26 Req. total capacity at 0.70 SHR ton0.1

Heating Equipment Summary Cooling Equipment Summary

Make 9000 btuh Ductless Mini Split Make 9000 btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm29 Actual air flow cfm29Air flow factor cfm/Btuh0.023 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 1.00

Page 12: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-30 17:23:09Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3

...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:Living/Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

2 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh8922 Structure Btuh5079Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh8922 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh5283

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh221Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0519519Area (ft²) Equipment latent load Btuh221

46714671Volume (ft³)Air changes/hour 0.220.60 Equipment total load Btuh5503Equiv. AVF (cfm) 1847 Req. total capacity at 0.70 SHR ton0.6

Heating Equipment Summary Cooling Equipment Summary

Make 12000 btuh Ductless Mini Split Make 12000 btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm264 Actual air flow cfm264Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 0.96

Page 13: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-30 17:23:09Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1

...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

BR 2 Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information2 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

20

40

60

80

100

120

140

160

180

200

220

240

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 14: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-30 17:23:09Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

BR Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information2 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

20

40

60

80

100

120

140

160

180

200

220

240

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 15: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-30 17:23:09Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3

...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

Living/Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information2 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

50

100

150

200

250

300

350

400

450

500

550

600

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 16: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 17:23:09

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:BR 2 Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name BR 2 Zone BR 22 Exposed wall 24.0 ft 24.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft137.0x1.05 Room area 137.0 f t² 137.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 99 87 412 206 99 87 412 206. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 12 0 193 168 12 0 193 168. DD 11N011N0 0.3500.350 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 117 117 554 277 117 117 554 277

11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0WW 12C-0sw12C-0sw 0.0910.091 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 137 137 363 213 137 137 363 213FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 137 24 361 0 137 24 361 0

6 c) AED excursion 0 0

Envelope loss/gain 1883 864 1883 864

12 a) Infiltration 700 121 700 121b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 2583 985 2583 985

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 2583 985 2583 98515 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 2583 985 2583 985Air required (cfm)Air required (cfm) 51 51 51 51

Page 17: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 17:23:09

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:BR Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name BR Zone Bedroom2 Exposed wall 10.0 ft 10.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft10.0x10.05 Room area 100.0 f t² 100.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 90 78 369 185 90 78 369 185. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 12 0 193 168 12 0 193 168. DD 11N011N0 0.3500.350 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0

11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0WW 12C-0sw12C-0sw 0.0910.091 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 100 100 265 156 100 100 265 156FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 100 10 150 0 100 10 150 0

6 c) AED excursion 0 0

Envelope loss/gain 978 508 978 508

12 a) Infiltration 292 51 292 51b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 1270 559 1270 559

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 1270 559 1270 55915 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 1270 559 1270 559Air required (cfm)Air required (cfm) 29 29 29 29

Page 18: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 17:23:09

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living/Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Living/Kitch Zon Living/Kitchen2 Exposed wall 80.0 ft 63.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft447.0x1.05 Room area 519.0 f t² 447.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 135 86 407 203 135 86 407 203. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 28 0 451 392 28 0 451 392. DD 11N011N0 0.3500.350 nn 18.2018.20 10.8510.85 21 21 382 228 21 21 382 228. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 72 72 341 170 0 0 0 0

11 WW 12C-0sw12C-0sw 0.0910.091 ss 4.734.73 2.372.37 324 324 1533 767 243 243 1150 575WW 12C-0sw12C-0sw 0.0910.091 ww 4.734.73 2.372.37 189 189 894 447 189 189 894 447CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 519 519 1376 807 447 447 1185 695FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 519 80 1202 0 447 63 947 0

6 c) AED excursion 0 0

Envelope loss/gain 6587 3015 5417 2541

12 a) Infiltration 2335 404 1839 318b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 2 460 2 460Appliances/other 1200 1200

Subtotal (lines 6 to 13) 8922 5079 7256 4519

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 1667 560

14 Subtotal 8922 5079 8922 507915 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 8922 5079 8922 5079Air required (cfm)Air required (cfm) 264 264 264 264

Page 19: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-30 17:23:09

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 4...ings\User\My Documents\Dropbox\Project Files\AEA-2 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living/Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Bath2 Exposed wall 17.0 ft3 Ceiling height 9.0 heat/coolft4 Room dimensions ft8.0x9.05 Room area 72.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area Loadnumber (Bt uh/f t²- °F) (Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 W 12C-0sw 0.091 n 4.73 2.37 0 0 0 0. G 2 glazing, clr outr, 0.310 n 16.12 14.01 0 0 0 0. D 11N0 0.350 n 18.20 10.85 0 0 0 0. W 12C-0sw 0.091 e 4.73 2.37 72 72 341 170

11 W 12C-0sw 0.091 s 4.73 2.37 81 81 383 192W 12C-0sw 0.091 w 4.73 2.37 0 0 0 0C 18A-19xd 0.051 - 2.65 1.56 72 72 191 112F 22B-5tpl 0.289 - 15.03 0.00 72 17 255 0

6 c) AED excursion 0

Envelope loss/gain 1170 474

12 a) Infiltration 496 86b) Room ventilation 0 0

13 Internal gains: Occupants @ 230 0 0Appliances/other 0

Subtotal (lines 6 to 13) 1667 560

Less external load 0 0Less transfer 0 0Redistribution -1667 -560

14 Subtotal 0 015 Duct loads -0% 0% 0 0

Total room load 0 0Air required (cfm) 0 0

Page 20: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Job #:Performed for:2 Bedroom Apartment

NM

Salome Arciniega, PE, LEED AP, M...

Architectural Engineering AssociatesAlbuquerque, NM

Scale: 1 : 60Page 1

Right-Sui te® Univ ersal8.0.20 RSU15338

2012-Aug-30 17:23:40...\Project Files\AEA-2 Bedroom.rup

N

Level 1

Living/Kitchen

Bedroom

Bath

BR 2

Page 21: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft
Page 22: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft
Page 23: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:BR 2 Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

3 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh1922 Structure Btuh790Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh1922 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh822

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh-30Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0128128Area (ft²) Equipment latent load Btuh0

11521152Volume (ft³)Air changes/hour 0.150.43 Equipment total load Btuh822Equiv. AVF (cfm) 38 Req. total capacity at 0.70 SHR ton0.1

Heating Equipment Summary Cooling Equipment Summary

Make 9000 btuh Ductless Mini Split Make 9000 btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm41 Actual air flow cfm41Air flow factor cfm/Btuh0.021 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 1.00

Page 24: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:Living Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

3 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh7913 Structure Btuh3104Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh7913 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh3229

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh-127Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0561561Area (ft²) Equipment latent load Btuh0

50495049Volume (ft³)Air changes/hour 0.150.41 Equipment total load Btuh3229Equiv. AVF (cfm) 1235 Req. total capacity at 0.70 SHR ton0.4

Heating Equipment Summary Cooling Equipment Summary

Make 12000 btuh Ductless Mini Split Make 12000 btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm161 Actual air flow cfm161Air flow factor cfm/Btuh0.020 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 1.00

Page 25: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 4

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Project Summary Aug 30, 2012Date:M-Bedroom Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information

3 Bedroom ApartmentFor:NM

Notes:

Design Information

Hobbs AP, NM, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F18 Outside db °F99Inside db °F70 Inside db °F75Design TD °F52 Design TD °F24

Daily range HRelative humidity %50Moisture difference gr/lb-17

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh3005 Structure Btuh1878Ducts Btuh0 Ducts Btuh0Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh3005 Use manufacturer's data n

Rate/swing multiplier 1.04Infiltration Equipment sensible load Btuh1953

Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight

1 (Average)Fireplaces Structure Btuh-49Ducts Btuh0

CoolingHeating Central vent (0 cfm) Btuh0186186Area (ft²) Equipment latent load Btuh0

16741674Volume (ft³)Air changes/hour 0.170.47 Equipment total load Btuh1953Equiv. AVF (cfm) 513 Req. total capacity at 0.70 SHR ton0.2

Heating Equipment Summary Cooling Equipment Summary

Make 9000 Btuh Ductless Mini Split Make 9000 Btuh Ductless Mini SplitTrade TradeModel CondAHRI ref no. Coil

AHRI ref no.Efficiency 0 HSPF Efficiency 0 SEERHeating input Sensible cooling Btuh0Heating output Btuh @ 47°F0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm98 Actual air flow cfm98Air flow factor cfm/Btuh0.032 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0Space thermostat Load sensible heat ratio 1.00

Page 26: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

BR 1 Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information3 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

20

40

60

80

100

120

140

160

180

200

220

240

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 27: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

BR 2 Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information3 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

20

40

60

80

100

120

140

160

180

200

220

240

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 28: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

Living Kitch Zon By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information3 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

50

100

150

200

250

300

350

400

450

500

550

600

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 21.4%.

Zone has adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 0 Btuh

Page 29: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

2012-Aug-31 08:38:33Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 4

...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:AED Assessment Aug 30, 2012Date:

M-Bedroom Zone By:

Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

Project Information3 Bedroom ApartmentFor:NM

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Hobbs AP, NM, US2452Design TD (°F)ft3655Elevation:5050Relative humidity (%)°N33Latitude:

Outdoor: -17.250.2Moisture difference (gr/lb)CoolingHeatingInfiltration:9918Dry bulb (°F)

)H(29-Daily range (°F)66-Wet bulb (°F)7.515.0Wind speed (mph)

Test for Adequate Exposure Diversity

Hourly Glazing Load

Hourly Average AED limit

Gla

zing

load

(B

tuh)

Hour of Day

0

100

200

300

400

500

600

700

800

900

1,000

8 9 10 11 12 13 14 15 16 17 18 19 20

Maximum hourly glazing load exceeds average by 88.6%.

Zone does not have adequate exposure diversity (AED), based on AED limit of 30%.

AED excursion: 290 Btuh (PFG - 1.3*AFG)

Page 30: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-31 08:38:34

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 1...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:BR 1 Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name BR 1 Zone BR 12 Exposed wall 23.0 ft 23.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft121.0x1.05 Room area 121.0 f t² 121.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 90 78 369 185 90 78 369 185. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 12 0 193 168 12 0 193 168. WW 12C-0sw12C-0sw 0.0910.091 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0

11 WW 12C-0sw12C-0sw 0.0910.091 ww 4.734.73 2.372.37 117 117 554 277 117 117 554 277GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0

CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 121 121 321 188 121 121 321 188FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 121 23 346 0 121 23 346 0

6 c) AED excursion 0 0

Envelope loss/gain 1783 818 1783 818

12 a) Infiltration 523 87 523 87b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 2305 905 2305 905

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 2305 905 2305 90515 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 2305 905 2305 905Air required (cfm)Air required (cfm) 0 47 0 47

Page 31: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-31 08:38:34

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 2...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:BR 2 Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name BR 2 Zone BR 22 Exposed wall 18.0 ft 18.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft128.0x1.05 Room area 128.0 f t² 128.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 108 96 454 227 108 96 454 227. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 12 0 193 168 12 0 193 168. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 54 54 256 128 54 54 256 128. WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0

11 WW 12C-0sw12C-0sw 0.0910.091 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0

CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 128 128 339 199 128 128 339 199FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 128 18 271 0 128 18 271 0

6 c) AED excursion 0 0

Envelope loss/gain 1513 722 1513 722

12 a) Infiltration 409 68 409 68b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 1922 790 1922 790

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 1922 790 1922 79015 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 1922 790 1922 790Air required (cfm)Air required (cfm) 41 41 41 41

Page 32: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-31 08:38:34

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 3...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Living Kitch Zon Bath2 Exposed wall 76.0 ft 7.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft9.0x7.05 Room area 561.0 f t² 63.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 4.734.73 2.372.37 162 134 634 317 0 0 0 0. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 16.1216.12 14.0114.01 28 0 451 392 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ee 4.734.73 2.372.37 243 243 1150 575 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ss 4.734.73 2.372.37 225 225 1065 532 63 63 298 149

11 WW 12C-0sw12C-0sw 0.0910.091 ww 4.734.73 2.372.37 54 54 256 128 0 0 0 0GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0

CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 561 561 1488 873 63 63 167 98FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 561 76 1142 0 63 7 105 0

6 c) AED excursion 0 0

Envelope loss/gain 6185 2817 570 247

12 a) Infiltration 1727 287 159 26b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 7913 3104 729 274

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 -729 -274

14 Subtotal 7913 3104 0 015 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 7913 3104 0 0Air required (cfm)Air required (cfm) 161 161 0 0

Page 33: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-31 08:38:34

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 4...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:Living Kitch Zon

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name Living/Kitchen2 Exposed wall 69.0 ft3 Ceiling height 9.0 heat/coolft4 Room dimensions ft498.0x1.05 Room area 498.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area Loadnumber (Bt uh/f t²- °F) (Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 W 12C-0sw 0.091 n 4.73 2.37 162 134 634 317. G 2 glazing, clr outr, 0.310 n 16.12 14.01 28 0 451 392. W 12C-0sw 0.091 e 4.73 2.37 243 243 1150 575. W 12C-0sw 0.091 s 4.73 2.37 162 162 767 383

11 W 12C-0sw 0.091 w 4.73 2.37 54 54 256 128G 2 glazing, clr outr, 0.310 w 0.00 0.00 0 0 0 0

C 18A-19xd 0.051 - 2.65 1.56 498 498 1321 775F 22B-5tpl 0.289 - 15.03 0.00 498 69 1037 0

6 c) AED excursion 0

Envelope loss/gain 5615 2570

12 a) Infiltration 1568 261b) Room ventilation 0 0

13 Internal gains: Occupants @ 230 0 0Appliances/other 0

Subtotal (lines 6 to 13) 7183 2831

Less external load 0 0Less transfer 0 0Redistribution 729 274

14 Subtotal 7913 310415 Duct loads -0% 0% 0 0

Total room load 7913 3104Air required (cfm) 161 161

Page 34: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2012-Aug-31 08:38:34

Right-Suite® U niv ersal 8.0 .20 R SU15338 Page 5...ings\User\My Documents\Dropbox\Project Files\AEA-3 Bedroom.rup Calc = MJ8 Front Door faces:

Job:Right-J® WorksheetAug 30, 2012Date:M-Bedroom Zone

By:Salome Arciniega, PE, LEED AP, MSME

Architectural Engineering Associates, Albuquerque, NM

1 Room name M-Bedroom Zone M-Bedroom2 Exposed wall 29.0 ft 29.0 ft3 Ceiling height 9.0 ft 9.0 heat/coolft4 Room dimensions ft186.0x1.05 Room area 186.0 f t² 186.0 f t²

Ty Construction U-value Or HTM Area (f t² ) Load Area (f t² ) Loadnumber (Bt uh/f t²- °F)(Bt uh/f t²- °F) (Bt uh/f t²)(Bt uh/f t²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0. GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0. WW 12C-0sw12C-0sw 0.0910.091 ss 4.734.73 2.372.37 135 135 639 319 135 135 639 319

11 WW 12C-0sw12C-0sw 0.0910.091 ww 4.734.73 2.372.37 126 110 521 260 126 110 521 260GG 2 glazing, clr outr, 0.3102 glazing, clr outr, 0.310 ww 16.1216.12 38.0838.08 16 0 258 609 16 0 258 609

CC 18A-19xd18A-19xd 0.0510.051 -- 2.652.65 1.561.56 186 186 493 289 186 186 493 289FF 22B-5tpl22B-5tpl 0.2890.289 -- 15.0315.03 0.000.00 186 29 436 0 186 29 436 0

6 c) AED excursion 290 290

Envelope loss/gain 2346 1769 2346 1769

12 a) Infiltration 659 110 659 110b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 3005 1878 3005 1878

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 3005 1878 3005 187815 Duct loads 0% 0% 0 0 -0% 0% 0 0

Total room load 3005 1878 3005 1878Air required (cfm)Air required (cfm) 98 98 98 98

Page 35: Project Summary - Pavilion Construction Hermosa...Salome Arciniega, PE, LEED AP, MSME Architectural Engineering Associates, Albuquerque, NM 1 Room name Bath 2 Exposed wall 20.0 ft

Job #:Performed for:3 Bedroom Apartment

NM

Salome Arciniega, PE, LEED AP, MS...

Architectural Engineering AssociatesAlbuquerque, NM

Scale: 1 : 67

Page 1Right-Sui te® Universal

8.0.20 RSU153382012-Aug-31 08:38:45

...\Project Files\AEA-3 Bedroom.rup

N

Level 1

BR 1

M-Bedroom

Bath

BR 2

Living/Kitchen