Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856) 629-6545 TO: Imad Haq PROJECT NAME: Philadelphia International Airport – Concourse B HVAC Renovation & Replacement - Mechanical CONTRACT: Mechanical PHL-1520.16 SPECIFICATION SECTION: 232123 ITEM DESCRIPTION: Hydronic Pumps MANUFACTURER: Armstrong APPROVED DOLAN MECHANICAL, INC. SUBMITTAL # 16-232123-001 BY DAT E 11/01/16 Stephen L. Agozzino, Vice President SHOP DRAWING REVIEW REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN INTENT. SEE SUBMITTALS SECTION IN SPECIFICATIONS FOR SPECIFIC CONDITIONS THAT APPLY TO THIS REVIEW. BURNS ENGINEERING, INC. SHOP DWG. JOB BY DATE NO EXCEPTION TAKEN MAKE CORRECTIONS NOTED SUBMIT SPECIFIED ITEM REVISE AND RESUBMIT REJECTED ACCEPTED – INFO ONLY 232123- SUBM. 1 X 2015-127 EL 2016-11-3 PUMPS MEET REQUIREMENTS AND ARE ACCEPTED. HOWEVER, RESUBMIT FOR RECORD P-1 AND P-2 PUMP CURVES SINCE IT INDICATES WATER NOT 30% ETHYLYNE GLYCOL. APPROVED APPROVED AS NOTED REVISE AND RESUBMIT DISAPPROVED Failure to comply exactly with the notations on the attached submittal will constitute in non-approval of same. Contractor is required to comply with all Contract Documents. DIVISION OF AVIATION ENGINEERING REVIEWED BY: DATE: 11/16/2016

PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Embed Size (px)

Citation preview

Page 1: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326

Sicklerville, NJ 08081 (856) 629-9331 FAX (856) 629-6545

TO: Imad Haq

PROJECT NAME: Philadelphia International Airport – Concourse B HVAC Renovation & Replacement - Mechanical

CONTRACT: Mechanical PHL-1520.16

SPECIFICATION SECTION: 232123

ITEM DESCRIPTION: Hydronic Pumps

MANUFACTURER: Armstrong

APPROVED DOLAN MECHANICAL, INC.

SUBMITTAL # 16-232123-001

BY DAT E 11/01/16 Stephen L. Agozzino, Vice President

SHOP DRAWING REVIEWREVIEW IS FOR GENERAL CONFORMANCE WITHDESIGN INTENT. SEE SUBMITTALS SECTION IN

SPECIFICATIONS FOR SPECIFIC CONDITIONS THATAPPLY TO THIS REVIEW.

BURNS ENGINEERING, INC.

SHOP DWG.

JOB

BY

DATE

NO EXCEPTION TAKEN

MAKE CORRECTIONS NOTED

SUBMIT SPECIFIED ITEM

REVISE AND RESUBMIT

REJECTED

ACCEPTED – INFO ONLY

232123- SUBM. 1

X 2015-127

EL

2016-11-3

PUMPS MEET REQUIREMENTS AND ARE ACCEPTED. HOWEVER, RESUBMIT FOR RECORDP-1 AND P-2 PUMP CURVES SINCE IT INDICATES WATER NOT 30% ETHYLYNE GLYCOL.

APPROVED

APPROVED AS NOTED

REVISE AND RESUBMIT

DISAPPROVED

Failure to comply exactly with the notations on the attached submittal will constitute in non-approval of same. Contractor is required to

comply with all Contract Documents.

DIVISION O

F AVIATION ENGINEERING

REVIEWED BY: DATE: 11/16/2016

Page 2: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Submittal

BLANKIN EQUIPMENT

489 Shoemaker Road King of Prussia PA 19406

215-229-7400 Fax 215-228-2560 .

Prepared For: Dolan Mechanical Date: 10-26-2016 Job Name: PHL – Concourse B Prepared By: Brandon Zee Lang

Products Included in this Submittal Package: Qty Description

(2) Armstrong 4600 8x6x10L pumps (P-1,2) (2) Armstrong 4030 4x3x10 pumps (P-3,4)

Blankin Equipment 489 Shoemaker Road King of Prussia PA 19406

215-229-7400 Fax 215-228-2560

The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.

Page 3: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

To: Dolan MechanicalAttn: Steve638 Johnson RoadSicklerville, NJ 08081

Date: 10/26/2016

Job Name: Philadelphia International Airport - Concourse B HVAC RenovationJob Engineer: Burns Engineering

We are pleased to submit on the following equipment.

Armstrong Centrifugal Pump(s)

Specification Section

[P-1,2] Quantity (2) Armstrong Centrifugal Pump(s), Model 4600 - 8x6x10L

Base Mounted, Horizontal Split-Case, Double Suction Pumps. Coupled to 200 HP, 3600 RPM, 480/3/60,TEFC motors. Based on 2,150 GPM @ 250' TDH each

Base Price Includes- Bronze-Fitted Construction (Bronze Impeller)- Cast Iron Casing with Fabricated Steel Baseplate- Flexible Coupling, with OSHA Guard- Carbon Steel Shaft w/ 304 Stainless Steel Shaft Sleeve- Mechanical Seal w/ Carbon Rotating Face and Silicon Carbide Seat (Free Upgrade From StandardCarbon Seal - EXTRA LONG LIFE)- Bronze Casing Wear Rings

— ROTATION ORIENTATION - Must Be Confirmed Prior To Ordering

— NEMA Premium Efficiency Inverter Ready Rated Pump Motor

— VFD Rated Pump Coupling

— Field Alignment P-1,2,3,4

— Spare Mechanical Seals 9975000-997

[P-3,4] Quantity (2) Armstrong Centrifugal Pump(s), Model 4030 - 4x3x10

489 Shoemaker RoadKing of Prussia, PA 19406Phone: 2152297400 Fax: 2152282560Web Address: www.blankinequipment.com

SUBMITTALS FOR APPROVALReference No. 16-00000058

Date: 10/26/2016 Reference No. 16-00000058Page 1 of 2

Page 4: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Submitted By:

BlankinBrandon Lang

Base Mounted, End Suction Pumps. Coupled to 75 HP, 3600 RPM, 208/3/60, TEFC motors. Based on695 GPM @ 260' TDH each

Base Price Includes- Bronze-Fitted Construction (Bronze Impeller)- Cast Iron Casing with Fabricated Steel Baseplate- Flexible Coupling, with OSHA Guard- Carbon Steel Shaft w/ 304 Stainless Steel Shaft Sleeve- Mechanical Seal w/ Carbon Rotating Face and Silicon Carbide Seat (Free Upgrade From StandardCarbon Seal - EXTRA LONG LIFE)

— VFD Rated Pump Coupling

— Spare Mechanical Seals 975000-984

— NEMA Premium Efficiency Inverter Duty Rated Pump Motor

Date: 10/26/2016 Reference No. 16-00000058Page 2 of 2

Page 5: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Submittal Ref. #: 503840.1 rev6

Horizontal split case pump

Model: Series 4600-8x6x10L-200 hp Pump (Motor supplier: Armstrong choice)

Project name: 16-0058 - Philadelphia Airport - Concourse B

Location: Representative: Blankin Equipment Corporation

Date submitted: 10/20/2016 12:19:36 PM Phone number:

Engineer: e-mail: [email protected]

Contractor: Submitted by: Brandon Lang

Application design data

Tag number: P-1,2 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: Water:

Quantity: 2 Operating temperature: 60 F

Viscosity: 31 SSUDuty flow per pump: 2150 USgpm

Specific gravity: 1.0000Duty head: 250 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: Carbon Steel (C1045-100)

Connections: Inlet: 8 in, Outlet: 6 in Shaft sleeve: Bronze (B584-932)

Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel

Bearings: Anti-Friction Grease Lubricated Casing gasket: Velotherm (Non-Asbestos fiber)

Pump suction: Right-hand when viewed from Drive End

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon

Manufacturer code: 21A Stationary seat: Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 200 hp Inverter motor type: Inverter Duty

Frame number: 447TSC Efficiency: NEMA Prem (12.12)

Enclosure: TEFC Speed: 3580 rpm

Motor Electrics: 480/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 225 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 4 of 20

Page 6: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Performance curve

--- Admin Data --- Tag Num: P-1,2 Service: Location:

--- Motor Data --- Motor Size: 200 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 2150 usgpm Head: 250 ft Impeller: 8.84 in

--- Performance Data ---• NPSHR: 31.8 ft• Eff. @ Design: 76.48 % • BHP @ Design: 177.48 hp• Mtr Capability @ Rated Spd: 200.00 hp• %Mtr Safety: 12.69%

• BEP @ Design Imp.:76.49 % @ 2143.4 usgpm

• Impeller Max BHP @ Flow:185.54 hp @ 2636.4 usgpm

• %max imp. range: 51.16 %• Outlet Velocity: 23.88 ft/s• VFD Setting: 60.0 Hz

Series 4600

8x6x10L @ 3580 rpm

0 0.8 1.6 2.4 3.2 4 4.8

0

80

160

240

320

400

480

Flow ( 1,000 usgpm)

Head

(ft)

10.00 in

7.63 in

System

8.84 in

125 hp150 hp

200 hp

250 hp300 hp

100 hp

81

81

78

78

72

72

64

64

52

52%

38

Water:, spgr= 1.0000

PT154-2-0 (3.23.0.1)ANSI/HI 14.6.3.4 1B

82

--- Admin Data ---Tag Num: P-1,2Service:Location:

--- Motor Data ---Motor Size: 200 hpMotor Speed: 3600 rpm

--- Design Duty Point ---Flow: 2150 usgpmHead: 250 ftImpeller: 8.84 in

--- System Intersect Data ---1. System @ 60.0 Hz:• 2150 @ 250, 177.48 hp2. System @ 51.6 Hz:• 1850.1 @ 185.1, 113.08 hp3. System @ 43.2 Hz:• 1549.7 @ 129.9, 66.46 hp4. System @ 34.9 Hz:• 1249.3 @ 84.4, 34.82 hp5. System @ 26.5 Hz:• 949.2 @ 48.7, 15.27 hp6. System @ 18.0 Hz:• 645.2 @ 22.5, 4.8 hp

Series 4600

8x6x10L @ 8.84 in

0 0.8 1.6 2.4 3.2 4

0

80

160

240

320

400

Flow ( 1,000 usgpm)

Head

(ft)

3580 rpm

1074 rpm

System

3580 rpm

60 hp75 hp

100 hp125 hp

150 hp

200 hp

77

76

76

73

73

68

68

60

60

50

3080 rpm

2580 rpm

2080 rpm

1580 rpm

Water:, spgr= 1.0000

PT154-2-0 (3.23.0.1)ANSI/HI 14.6.3.4 1B

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 5 of 20

Page 7: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Dimensional data (not for construction)

Top viewSide view

Weight: 2728 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 8 13.5ANSI-125 8 0.7511.75

Outlet 6 11ANSI-125 8 0.759.5

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options

Casing Wear Ring - Not included Motor Nameplate Voltages (200, 416, 480, 600 volts) Couplings-Rotex Casing Wear Rings - Bronze (B584-936)

Additional equipment Flotrex: FTV-10FA (570200-482) Suction Guide: SG-108 (516860-029)

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 6 of 20

Page 8: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Submittal Ref. #: 503840.1 rev6

Horizontal base mounted end suction pump

Model: Series 4030-4x3x10-75 hp Pump (Motor supplier: Armstrong choice)

Project name: 16-0058 - Philadelphia Airport - Concourse B

Location: Representative: Blankin Equipment Corporation

Date submitted: 10/20/2016 12:19:36 PM Phone number:

Engineer: e-mail: [email protected]

Contractor: Submitted by: Brandon Lang

Application design data

Tag number: P-3,4 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: PropyleneGlycol:30

Quantity: 2 Operating temperature: 60 F

Viscosity: 37.213 SSUDuty flow per pump: 695 USgpm

Specific gravity: 1.0248Duty head: 260 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: Carbon Steel

Connections: Inlet: 4 in, Outlet: 3 in Shaft sleeve: 304 SS

Casing (volute): Cast Iron (A48-30) Flexible coupling: Rotex

Bearings: Anti-Friction Grease Lubricated Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon

Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 75 hp Inverter motor type: Inverter Duty

Frame number: 365TSC Efficiency: NEMA Prem (12.12)

Enclosure: TEFC Speed: 3580 rpm

Motor Electrics: 208/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 1 of 20

Page 9: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Performance curve

--- Admin Data --- Tag Num: P-3,4 Service: Location:

--- Motor Data --- Motor Size: 75 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 695 usgpm Head: 260 ft Impeller: 8.73 in

--- Performance Data --- • NPSHR: 18.3 ft • Eff. @ Design: 76.44 % • BHP @ Design: 61.17 hp • Mtr Capability @ Rated Spd: 75.00 hp • %Mtr Safety: 22.60% • BEP @ Design Imp.: 76.57 % @ 667.0 usgpm • Impeller Max BHP @ Flow: 72.32 hp @ 964.9 usgpm • %max imp. range: 33.37 % • Outlet Velocity: 30.16 ft/s • VFD Setting: 60.0 Hz

Series 4030

4x3x10 @ 3580 rpm

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

0

80

160

240

320

400

480

Flow ( 1,000 usgpm)

Head

(ft)

10.19 in

8.00 in

System

8.73 in

40

50

60

75

100

125

30 hp

76

76

74

74

70

70

63

63

5339

PropyleneGlycol:30, spgr= 1.0248

PT75-1-0 (3.23.0.1)ANSI/HI 14.6.3.4 2B

77

--- Admin Data --- Tag Num: P-3,4 Service: Location:

--- Motor Data --- Motor Size: 75 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 695 usgpm Head: 260 ft Impeller: 8.73 in

--- System Intersect Data --- 1. System @ 60.0 Hz: • 695 @ 260, 61.17 hp 2. System @ 51.6 Hz: • 598 @ 192.5, 38.97 hp 3. System @ 43.2 Hz: • 500.9 @ 135, 22.9 hp 4. System @ 34.9 Hz: • 403.8 @ 87.8, 12 hp 5. System @ 26.5 Hz: • 306.8 @ 50.7, 5.26 hp 6. System @ 18.0 Hz: • 208.5 @ 23.4, 1.65 hp

Series 4030

4x3x10 @ 8.73 in

0 0.2 0.4 0.6 0.8 1 1.2

0

80

160

240

320

400

Flow ( 1,000 usgpm)

Head

(ft)

3580 rpm

1074 rpm

System

3580 rpm

7.5 hp10 hp 15 hp20 hp

25 hp30 hp

40 hp

50 hp

60 hp

75 hp

7777

77

74

74

70

70

63

63

53

3080 rpm

2580 rpm

2080 rpm

1580 rpm

PropyleneGlycol:30, spgr= 1.0248

PT75-1-0 (3.23.0.1)ANSI/HI 14.6.3.4 2B

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 2 of 20

Page 10: PROJECT NAME: Additions and Renovations to Kingsway ... In Progress/Phila... · Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326 Sicklerville, NJ 08081 (856) 629-9331 FAX (856)

Dimensional data (not for construction)

Top viewSide view

Weight: 1061 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 4 9ANSI-125 8 0.6257.5

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Casing Wear Ring - Not included Couplings-Rotex

Additional equipment Flotrex: FTV-6FS (570200-380) Suction Guide: SG-64 (516860-023)

www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 3 of 20