Dolan Mechanical, Inc. 638 Johnson Road, PO Box 326
Sicklerville, NJ 08081 (856) 629-9331 FAX (856) 629-6545
TO: Imad Haq
PROJECT NAME: Philadelphia International Airport – Concourse B HVAC Renovation & Replacement - Mechanical
CONTRACT: Mechanical PHL-1520.16
SPECIFICATION SECTION: 232123
ITEM DESCRIPTION: Hydronic Pumps
MANUFACTURER: Armstrong
APPROVED DOLAN MECHANICAL, INC.
SUBMITTAL # 16-232123-001
BY DAT E 11/01/16 Stephen L. Agozzino, Vice President
SHOP DRAWING REVIEWREVIEW IS FOR GENERAL CONFORMANCE WITHDESIGN INTENT. SEE SUBMITTALS SECTION IN
SPECIFICATIONS FOR SPECIFIC CONDITIONS THATAPPLY TO THIS REVIEW.
BURNS ENGINEERING, INC.
SHOP DWG.
JOB
BY
DATE
NO EXCEPTION TAKEN
MAKE CORRECTIONS NOTED
SUBMIT SPECIFIED ITEM
REVISE AND RESUBMIT
REJECTED
ACCEPTED – INFO ONLY
232123- SUBM. 1
X 2015-127
EL
2016-11-3
PUMPS MEET REQUIREMENTS AND ARE ACCEPTED. HOWEVER, RESUBMIT FOR RECORDP-1 AND P-2 PUMP CURVES SINCE IT INDICATES WATER NOT 30% ETHYLYNE GLYCOL.
APPROVED
APPROVED AS NOTED
REVISE AND RESUBMIT
DISAPPROVED
Failure to comply exactly with the notations on the attached submittal will constitute in non-approval of same. Contractor is required to
comply with all Contract Documents.
DIVISION O
F AVIATION ENGINEERING
REVIEWED BY: DATE: 11/16/2016
Submittal
BLANKIN EQUIPMENT
489 Shoemaker Road King of Prussia PA 19406
215-229-7400 Fax 215-228-2560 .
Prepared For: Dolan Mechanical Date: 10-26-2016 Job Name: PHL – Concourse B Prepared By: Brandon Zee Lang
Products Included in this Submittal Package: Qty Description
(2) Armstrong 4600 8x6x10L pumps (P-1,2) (2) Armstrong 4030 4x3x10 pumps (P-3,4)
Blankin Equipment 489 Shoemaker Road King of Prussia PA 19406
215-229-7400 Fax 215-228-2560
The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.
To: Dolan MechanicalAttn: Steve638 Johnson RoadSicklerville, NJ 08081
Date: 10/26/2016
Job Name: Philadelphia International Airport - Concourse B HVAC RenovationJob Engineer: Burns Engineering
We are pleased to submit on the following equipment.
Armstrong Centrifugal Pump(s)
Specification Section
[P-1,2] Quantity (2) Armstrong Centrifugal Pump(s), Model 4600 - 8x6x10L
Base Mounted, Horizontal Split-Case, Double Suction Pumps. Coupled to 200 HP, 3600 RPM, 480/3/60,TEFC motors. Based on 2,150 GPM @ 250' TDH each
Base Price Includes- Bronze-Fitted Construction (Bronze Impeller)- Cast Iron Casing with Fabricated Steel Baseplate- Flexible Coupling, with OSHA Guard- Carbon Steel Shaft w/ 304 Stainless Steel Shaft Sleeve- Mechanical Seal w/ Carbon Rotating Face and Silicon Carbide Seat (Free Upgrade From StandardCarbon Seal - EXTRA LONG LIFE)- Bronze Casing Wear Rings
— ROTATION ORIENTATION - Must Be Confirmed Prior To Ordering
— NEMA Premium Efficiency Inverter Ready Rated Pump Motor
— VFD Rated Pump Coupling
— Field Alignment P-1,2,3,4
— Spare Mechanical Seals 9975000-997
[P-3,4] Quantity (2) Armstrong Centrifugal Pump(s), Model 4030 - 4x3x10
489 Shoemaker RoadKing of Prussia, PA 19406Phone: 2152297400 Fax: 2152282560Web Address: www.blankinequipment.com
SUBMITTALS FOR APPROVALReference No. 16-00000058
Date: 10/26/2016 Reference No. 16-00000058Page 1 of 2
Submitted By:
BlankinBrandon Lang
Base Mounted, End Suction Pumps. Coupled to 75 HP, 3600 RPM, 208/3/60, TEFC motors. Based on695 GPM @ 260' TDH each
Base Price Includes- Bronze-Fitted Construction (Bronze Impeller)- Cast Iron Casing with Fabricated Steel Baseplate- Flexible Coupling, with OSHA Guard- Carbon Steel Shaft w/ 304 Stainless Steel Shaft Sleeve- Mechanical Seal w/ Carbon Rotating Face and Silicon Carbide Seat (Free Upgrade From StandardCarbon Seal - EXTRA LONG LIFE)
— VFD Rated Pump Coupling
— Spare Mechanical Seals 975000-984
— NEMA Premium Efficiency Inverter Duty Rated Pump Motor
Date: 10/26/2016 Reference No. 16-00000058Page 2 of 2
Submittal Ref. #: 503840.1 rev6
Horizontal split case pump
Model: Series 4600-8x6x10L-200 hp Pump (Motor supplier: Armstrong choice)
Project name: 16-0058 - Philadelphia Airport - Concourse B
Location: Representative: Blankin Equipment Corporation
Date submitted: 10/20/2016 12:19:36 PM Phone number:
Engineer: e-mail: [email protected]
Contractor: Submitted by: Brandon Lang
Application design data
Tag number: P-1,2 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: Water:
Quantity: 2 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 2150 USgpm
Specific gravity: 1.0000Duty head: 250 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: Carbon Steel (C1045-100)
Connections: Inlet: 8 in, Outlet: 6 in Shaft sleeve: Bronze (B584-932)
Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel
Bearings: Anti-Friction Grease Lubricated Casing gasket: Velotherm (Non-Asbestos fiber)
Pump suction: Right-hand when viewed from Drive End
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon
Manufacturer code: 21A Stationary seat: Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 200 hp Inverter motor type: Inverter Duty
Frame number: 447TSC Efficiency: NEMA Prem (12.12)
Enclosure: TEFC Speed: 3580 rpm
Motor Electrics: 480/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 225 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 4 of 20
Performance curve
--- Admin Data --- Tag Num: P-1,2 Service: Location:
--- Motor Data --- Motor Size: 200 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 2150 usgpm Head: 250 ft Impeller: 8.84 in
--- Performance Data ---• NPSHR: 31.8 ft• Eff. @ Design: 76.48 % • BHP @ Design: 177.48 hp• Mtr Capability @ Rated Spd: 200.00 hp• %Mtr Safety: 12.69%
• BEP @ Design Imp.:76.49 % @ 2143.4 usgpm
• Impeller Max BHP @ Flow:185.54 hp @ 2636.4 usgpm
• %max imp. range: 51.16 %• Outlet Velocity: 23.88 ft/s• VFD Setting: 60.0 Hz
Series 4600
8x6x10L @ 3580 rpm
0 0.8 1.6 2.4 3.2 4 4.8
0
80
160
240
320
400
480
Flow ( 1,000 usgpm)
Head
(ft)
10.00 in
7.63 in
System
8.84 in
125 hp150 hp
200 hp
250 hp300 hp
100 hp
81
81
78
78
72
72
64
64
52
52%
38
Water:, spgr= 1.0000
PT154-2-0 (3.23.0.1)ANSI/HI 14.6.3.4 1B
82
--- Admin Data ---Tag Num: P-1,2Service:Location:
--- Motor Data ---Motor Size: 200 hpMotor Speed: 3600 rpm
--- Design Duty Point ---Flow: 2150 usgpmHead: 250 ftImpeller: 8.84 in
--- System Intersect Data ---1. System @ 60.0 Hz:• 2150 @ 250, 177.48 hp2. System @ 51.6 Hz:• 1850.1 @ 185.1, 113.08 hp3. System @ 43.2 Hz:• 1549.7 @ 129.9, 66.46 hp4. System @ 34.9 Hz:• 1249.3 @ 84.4, 34.82 hp5. System @ 26.5 Hz:• 949.2 @ 48.7, 15.27 hp6. System @ 18.0 Hz:• 645.2 @ 22.5, 4.8 hp
Series 4600
8x6x10L @ 8.84 in
0 0.8 1.6 2.4 3.2 4
0
80
160
240
320
400
Flow ( 1,000 usgpm)
Head
(ft)
3580 rpm
1074 rpm
System
3580 rpm
60 hp75 hp
100 hp125 hp
150 hp
200 hp
77
76
76
73
73
68
68
60
60
50
3080 rpm
2580 rpm
2080 rpm
1580 rpm
Water:, spgr= 1.0000
PT154-2-0 (3.23.0.1)ANSI/HI 14.6.3.4 1B
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 5 of 20
Dimensional data (not for construction)
Top viewSide view
Weight: 2728 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 8 13.5ANSI-125 8 0.7511.75
Outlet 6 11ANSI-125 8 0.759.5
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options
Casing Wear Ring - Not included Motor Nameplate Voltages (200, 416, 480, 600 volts) Couplings-Rotex Casing Wear Rings - Bronze (B584-936)
Additional equipment Flotrex: FTV-10FA (570200-482) Suction Guide: SG-108 (516860-029)
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 6 of 20
Submittal Ref. #: 503840.1 rev6
Horizontal base mounted end suction pump
Model: Series 4030-4x3x10-75 hp Pump (Motor supplier: Armstrong choice)
Project name: 16-0058 - Philadelphia Airport - Concourse B
Location: Representative: Blankin Equipment Corporation
Date submitted: 10/20/2016 12:19:36 PM Phone number:
Engineer: e-mail: [email protected]
Contractor: Submitted by: Brandon Lang
Application design data
Tag number: P-3,4 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: PropyleneGlycol:30
Quantity: 2 Operating temperature: 60 F
Viscosity: 37.213 SSUDuty flow per pump: 695 USgpm
Specific gravity: 1.0248Duty head: 260 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: Carbon Steel
Connections: Inlet: 4 in, Outlet: 3 in Shaft sleeve: 304 SS
Casing (volute): Cast Iron (A48-30) Flexible coupling: Rotex
Bearings: Anti-Friction Grease Lubricated Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon
Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 75 hp Inverter motor type: Inverter Duty
Frame number: 365TSC Efficiency: NEMA Prem (12.12)
Enclosure: TEFC Speed: 3580 rpm
Motor Electrics: 208/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 1 of 20
Performance curve
--- Admin Data --- Tag Num: P-3,4 Service: Location:
--- Motor Data --- Motor Size: 75 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 695 usgpm Head: 260 ft Impeller: 8.73 in
--- Performance Data --- • NPSHR: 18.3 ft • Eff. @ Design: 76.44 % • BHP @ Design: 61.17 hp • Mtr Capability @ Rated Spd: 75.00 hp • %Mtr Safety: 22.60% • BEP @ Design Imp.: 76.57 % @ 667.0 usgpm • Impeller Max BHP @ Flow: 72.32 hp @ 964.9 usgpm • %max imp. range: 33.37 % • Outlet Velocity: 30.16 ft/s • VFD Setting: 60.0 Hz
Series 4030
4x3x10 @ 3580 rpm
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
0
80
160
240
320
400
480
Flow ( 1,000 usgpm)
Head
(ft)
10.19 in
8.00 in
System
8.73 in
40
50
60
75
100
125
30 hp
76
76
74
74
70
70
63
63
5339
PropyleneGlycol:30, spgr= 1.0248
PT75-1-0 (3.23.0.1)ANSI/HI 14.6.3.4 2B
77
--- Admin Data --- Tag Num: P-3,4 Service: Location:
--- Motor Data --- Motor Size: 75 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 695 usgpm Head: 260 ft Impeller: 8.73 in
--- System Intersect Data --- 1. System @ 60.0 Hz: • 695 @ 260, 61.17 hp 2. System @ 51.6 Hz: • 598 @ 192.5, 38.97 hp 3. System @ 43.2 Hz: • 500.9 @ 135, 22.9 hp 4. System @ 34.9 Hz: • 403.8 @ 87.8, 12 hp 5. System @ 26.5 Hz: • 306.8 @ 50.7, 5.26 hp 6. System @ 18.0 Hz: • 208.5 @ 23.4, 1.65 hp
Series 4030
4x3x10 @ 8.73 in
0 0.2 0.4 0.6 0.8 1 1.2
0
80
160
240
320
400
Flow ( 1,000 usgpm)
Head
(ft)
3580 rpm
1074 rpm
System
3580 rpm
7.5 hp10 hp 15 hp20 hp
25 hp30 hp
40 hp
50 hp
60 hp
75 hp
7777
77
74
74
70
70
63
63
53
3080 rpm
2580 rpm
2080 rpm
1580 rpm
PropyleneGlycol:30, spgr= 1.0248
PT75-1-0 (3.23.0.1)ANSI/HI 14.6.3.4 2B
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 2 of 20
Dimensional data (not for construction)
Top viewSide view
Weight: 1061 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 9ANSI-125 8 0.6257.5
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Casing Wear Ring - Not included Couplings-Rotex
Additional equipment Flotrex: FTV-6FS (570200-380) Suction Guide: SG-64 (516860-023)
www.armstrongfluidtechnology.com 10/26/2016, Ref. # 503840.1 rev6 Page 3 of 20