Progress Report No 1t-b

Embed Size (px)

Citation preview

  • 7/30/2019 Progress Report No 1t-b

    1/16

    PROGRESS REPORT No 1T-B

    Results of the autotransformer AODCTN-167000/500/220 No.64458 (1T phase B)

    testing

    Head of diagnostic department_______________ .. Popov

    _____ ______________2007

    Diagnostician_______________V.V. Makolkin_____ ______________2007

    2007

    SCIENTIFIC AND ENGINEERING NTERZTZ-Service Co.

    11, Dnepropetrovskoye sh., Zaporozhye, 69069, Ukrainetel.: (380 61) 280-2801, fax: (380 61) 280-2800

    E-mail: [email protected]://www.ztz-service.com.ua

    SEC ZTZ-SERVICE Co.

  • 7/30/2019 Progress Report No 1t-b

    2/16

    1. Main technical data of the autotransformer No.64458 (1T phase B)Type DCN-167000/500/220

    No., manuf. date 64458 (1T ph. B), 1967

    Calculation sheet 215 740Capacity HV / MV / LV, kVA 167000 / 167000 / 50000

    Voltage HV / MV / LV, kV 500 / 230 6 2.06 / 11.0

    Current HV / MV / LV, A 578 / 1256 / 4545

    Connection diagram 1auto/1-0-0

    Frequency, Hz 50

    OLTC SAV-220/1600-3/12/1

    Cooling system OFAF (6 coolers + 1 spare)

    Weight of oil, t 44

    Table 1.1 No-load losses and currents

    Energized U, V I, P, W"b - y" 380 0.90 188.0

    No-load losses 0 = 123 kW No-load current I0 = 0.34 %

    Table 1.2. Windings resistance at t= 21C

    WindingOLTC

    positionR, Ohms

    B - 0 - 0.400

    Bm-0

    1 0.174

    2 0.168

    3 0.1624 0.158

    5 0.150

    6 0.146

    7 0.138

    8 0.134

    9 0.128

    10 0.122

    11 0.116

    12 0.110

    13 0.106

    b y - 0.00122

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 2Sheets 16

  • 7/30/2019 Progress Report No 1t-b

    3/16

    Table 1.3. Short circuit losses and impedances (Zk) at 75C.Windings

    pair*Voltage

    Full losses

    Related tocapacity

    Uk (Related to167 MVA)

    Calculatedimpedance

    (Zk)MW MV % Ohms

    HV MV7 500/3/230/3 329 167 9.40 46.949

    HV-LV 500/3/11.0 98.1 50 30.0 149.836

    MV7 - LV 230/3/11.0 84.9 50 18.0 19.031

    * Note: MV7 middle voltage winding at 7 tap position (230 kV).

    Table 1.4. Insulation characteristics R15/R60 & tan

    Scheme

    t= 37C t= 56CU

    R15 R60 tan R15 R60 tanMOhm MOhm % MOhm MOhm % kV

    HV-(LV+G) 470 850 0.3 260 400 0.5 10

    LV-(HV+G) 350 900 0.3 220 420 0.6 10

    (HV+LV)-G 240 500 0.3 150 240 0.6 10

    Image 1. General view of autotransformer

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 3

    500 kVbushing OLTC

    bushing

    220 kVbushing

    OLTC

    Maincore leg(HV)

    Tappingcore leg

    Freecore leg

    11 kVbushings

  • 7/30/2019 Progress Report No 1t-b

    4/16

  • 7/30/2019 Progress Report No 1t-b

    5/16

    2.3 Results of leakage reactance measurement (impedances).

    Leakage reactance (Zk) measurements were carried out for HV-MV, HV-LV and MV-

    LV windings pairs at the maximum (1 tap), rated (7 tap) and minimum (13 tap) taps of theMV winding.

    Table 2.3

    Windings pair Zk calc., Ohm Zk meas., OhmZk, %

    (Zk meas/ Zk calc)

    HV MV1 - 53.75 -

    HV MV 7 46.95 46.25 - 1.49

    HV MV13 - 52.50 -

    HV LV 149.84 149.9 0.04

    MV1 LV - 24.98 -

    MV7 LV 19.03 19.63 3.15MV13 LV - 18.19 -

    Conclusion: Low difference between calculated impedances and measured duringcondition assessment testifies the absence of the windings displacement (deformation).Deviation of the measured values from calculated not exceed 5%.

    2.4 Insulation electrical characteristics

    Table 2.4.

    No Scheme

    04.03.2007

    tw.=+60, tair=25

    06.03.2007

    tw.=+33, tair=18

    tan,%

    C,pF

    R15,MOhm

    R60,MOhm

    tan,%

    C,pF

    R15,MOhm

    R60,MOhm

    1 HV (LV+G) 0.90 9991 85.4 89.5 0.33 10031 405 562

    2 LV - (HV +G) 1.18 18886 51.00 55.00 0.38 18864 266.1 487

    3 (HV +LV) G 1.08 23473 39.94 43.00 0.37 23487 218.5 345.2

    4 HV LV 1.10 2697.4 295 311.5 0.33 2700.6 1147 1953

    5 HV G 0.82 7293 124.2 129.1 0.32 7329 616 803

    6 LV HV 1.10 2698 - - 0.33 2700.3 - -

    7 LV - G 1.2 16186 62.3 67.9 0.38 16162 336.7 660

    Remark: tw windings temperature calculated from measured DC current resistance of HV-winding.

    Table 2.5 Comparison of the measured values and certified

    No Scheme

    R60, MOhm

    Certified at

    t=56C

    Measured at

    t=60C

    Reduced to

    t=56C1 HV (LV+G) 400 89.5 105.32 LV - (HV +G) 420 55.00 64.73 (HV +LV) G 240 43.00 50.6

    Conclusion: Main insulation of the autotransformer is in bad condition. Insulationcontamination by polar aging products presumed.

    During repair insulation shall be washed with special oil by oil-spray method.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 5

  • 7/30/2019 Progress Report No 1t-b

    6/16

    2.5 Insulation electrical characteristics of the bushings

    Table 2.6

    No Scheme

    04.03.2007

    tw.=+60, tair=25, tbush=43

    06.03.2007

    tw.=+ 33, tair=18 , tbush=26tan,

    %

    C,pF

    R15,MOhm

    R60,MOhm

    tan,%

    C,pF

    R15,MOhm

    R60,MOhm

    500 kV bushing

    1 1 0.20 619.3 11170 16020 0.31 615.6 31570 58600

    2 1inv. 0.18 618.7 - - 0.31 616.3 - -

    3 3 0.39 3055.2 10710 15590 0.26 3071.5 42500 69100

    4 1+3 0.36 3674.6 - - 0.26 3688.0 - -

    220 kV bushing

    5 1 0.23 570.7 10640 15180 0.35 567.2 29090 45500

    6 1inv. 0.21 565.1 - - 0.30 556.5 - -

    7 3 0.88 880.4 9050 15110 0.53 867.5 28380 45400

    8 1+3 0.62 1445.5 - - 0.44 1424.1 - -

    220 kV OLTC bushing

    9 1 0.26 430.2 1891 5700 0.35 427.9 2855 10090

    10 1inv. 0.24 426.9 - - 0.31 419.8 - -

    11 3 1.60 1036.8 1909 5560 0.76 954.9 2387 9840

    12 1+3 1.20 1463.7 - - 0.61 1374.7 - -Remark: tw windings temperature calculated from measured DC current resistance of HV-winding.

    tbush bushings temperature, calculated from tw & tair.

    Conclusion: Results of the insulation characteristics measurements testifies that allbushings are in normal condition.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 6

  • 7/30/2019 Progress Report No 1t-b

    7/16

    3. OLTC checking.OLTC type SAV-220/1600-3/12/1

    3.1 OLTC oscillograms

    Image 2. OLTC switching from 7 tap position to 8 tap position

    Image 3. OLTC switching from 8 tap position to 7 tap position

    Table 3.1Tapping Certified time (seconds) Measured time (seconds)

    From odd toeven (from 7 to8)

    t1 0.010 - 0.030 0.020

    t2 0.020 - 0.042 0.030

    t3 0.010 - 0.020 0.019

    ttotal 0.048 0.085 0.069

    From even toodd (from 8 to 7)

    t1 0.010 - 0.030 0.021

    t2 0.020 - 0.042 0.024

    t3 0.010 - 0.020 0.028

    ttotal 0.048 0.085 0.073

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 7

    t1 t2 t3

    t, seconds

    I, amperes

    t1 t2 t3

    t, seconds

    I, amperes

  • 7/30/2019 Progress Report No 1t-b

    8/16

    3.2 Diverter switch circle diagram (degrees)

    No OLTC tapping Certified Testing result

    1 From 7 tap position to 8 tap position

    1560-1800

    1730

    2 From 8 tap position to 9 tap position 1700

    3 From 9 tap position to 8 tap position 1600

    4 From 8 tap position to 7 tap position 1620

    Conclusion: OLTC is in normal condition.

    4. Results of partial discharges (PD) location by acoustic method

    Date: 25.02.2007

    Conditions:- oil temperature 52;- load 44%.

    PD location was done at 3 levels around the autotransformer tank (see Image 5):- 1 level 500 millimeters above the tank joint- 2 level 1600 millimeters above the tank joint (middle of the tank height)- 3 level - 2800 millimeters above the tank joint

    Before the measurements performance the basic level of acoustic signal was

    measured.At all points around the tank (at all levels) the measured signals not exceed the basiclevel of acoustic signal and amount 0 1.94 dB (allowed level of acoustic signal is 20 dB).

    Conclusion:Partial discharges activity inside the tank not presumed.

    5. Results of the oil pumps & fans vibrations and currents measurements

    Date: 27.02.2007The points of the oil pumps vibration measurements are shown on the image 4.Vibrations of the oil pumps were assessed on the ISO 2372 recommendations and

    ZTZ-Service Co experience basis:

    - vibration velocity 2.8 millimeters per second normal condition;

    - vibration velocity > 2.8 millimeters per second bad condition

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 8

    Z1 1

    1

    2

    2 Z1 1,2

    1,2

  • 7/30/2019 Progress Report No 1t-b

    9/16

    vertical axis; horizontal axis; Z rotation axis.

    Image 4. Points of the oil pumps vibration measurements.

    Table 5.1. Oil pumps vibrations, millimeter per second

    Cooler (pump) No. X1 Y1 X2 Y2 Z Condition1 1.2 0.8 1.3 0.7 0.5 Normal

    2 0.9 1.0 0.9 1.1 0.3 Normal

    3 1.2 1.1 1.1 1.1 1.0 Normal

    4 0.6 0.6 0.6 0.6 0.5 Normal

    5 0.9 1.0 0.6 0.7 0.4 Normal

    6 1.5 1.3 1.3 1.1 1.3 Normal

    7 2.5 4.3 1.2 2.0 2.9 Bad

    Table 5.2. Oil pumps currents, Amperes.

    Cooler (pump) No. Phase * Phase * Phase * Max. difference betweenphases, %

    1 5.58 5.27 5.46 5.88

    2 5.65 5.61 5.52 2.36

    3 5.86 5.87 5.85 0.34

    4 6.08 5.98 6.03 1.67

    5 5.32 5.36 5.20 3.08

    6 6.75 6.75 6.60 2.27

    7 5.76 5.87 5.75 2.09* Note: phases marking - from left to right

    Conclusion: Oil pump No. 7 shall be repaired. All other oil pumps are in normalcondition. Pressure-gauge at the oil pump No. 6 shall be replaced.

    The points of the fans vibration measurements are the follow:- X1 horizontal axis of a lower fan;- Y1 - vertical axis of a lower fan;- X2 horizontal axis of an upper fan;- Y2 - vertical axis of an upper fan.Vibrations of the fans were assessed on the ISO 2372 recommendations and ZTZ-

    Service Co experience basis:

    - vibration velocity 4.5 millimeters per second normal condition;

    - vibration velocity > 4.5 millimeters per second bad condition

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 9

  • 7/30/2019 Progress Report No 1t-b

    10/16

    Table 5.3. Fans vibrations, millimeter per second

    Cooler No.Lower fan Upper fan

    ConditionX1 Y1 X2 Y2

    1 1.0 1.3 1.0 1.3 Normal2 1.5 1.4 1.0 1.2 Normal

    3 1.7 1.1 1.2 1.6 Normal

    4 1.2 1.2 1.3 1.6 Normal

    5 1.0 1.0 1.4 1.0 Normal

    6 2.6 1.6 2.5 2.0 Normal

    7 2.3 2.3 4.7 1.6 Bad shall be repaired

    Table 5.4. Fans currents, Amperes.Cooler

    No.Fan No. Phase * Phase * Phase *

    Max. difference between

    phases, %

    11 (lower) 5.68 5.55 5.73 3.24

    2 (upper) 6.25 6.25 6.41 2.56

    21 (lower) 5.78 5.65 5.86 3.72

    2 (upper) 5.49 5.50 5.51 0.36

    31 (upper) 5.27 5.18 5.16 2.13

    2 (lower) 5.45 5.38 5.42 1.30

    41 (upper) 6.02 5.80 5.97 3.79

    2 (lower) 5.69 5.47 5.80 6.03

    51 (lower) 5.60 5.64 5.46 3.30

    2 (upper) 5.08 5.20 5.00 4.00

    6 1 (lower) 5.65 5.68 5.56 2.162 (upper) 5.25 5.26 5.20 1.15

    71 (upper) 5.85 5.92 5.75 2.96

    2 (lower) 4.97 5.05 4.78 5.65* Note: phases marking - from left to right

    Conclusion: At the cooler No. 7 bearings of the upper fans shall be replaced.All other fans are in normal condition.

    6. Results of the magnetic field intensity measurements

    Measurements of the magnetic field intensity (MFI) were done around theautotransformer tank at load 44% and at no-load.

    Date: 25.02.2007

    Conditions: oil temperature 52; load 44%.Date: 02.03.2007

    Conditions: oil temperature 63; no-load.

    Points of the MFI measurements are shown at the image 5.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 10

  • 7/30/2019 Progress Report No 1t-b

    11/16

    - points for partial discharges location- points for measurement of magnetic flux intensity

    Image 5. Points of the PD location and MFI measurements.

    0

    1

    2

    3

    4

    5

    6

    7

    1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73

    Point No.

    Relative units

    Load 44%

    No-load

    Image 6. MFI distribution around the tank joint at 44% load and no-load.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 11

    500 kVbushing

    220 kVbushing

    OLTC

    11 kVbushings

    1

    2

    3

    4

    56

    7812 11

    109

    16

    15

    1413

    17

    18

    19

    2021

    22 23

    24 25

    2627

    28 29

    30

    31

    32

    1

    1020

    30

    40

    50

    56

    63

    60

    70

    1

    1

  • 7/30/2019 Progress Report No 1t-b

    12/16

    Table 6.1. Results of the MFI measurements at 44% load and no-load.

    PointNo

    Magnetic field intensity,relative units

    PointNo

    Magnetic field intensity,relative units

    PointNo

    Magnetic field intensity,relative units

    Load 44% No-load Load 44% No-load Load 44% No-load

    1 0.80 0.02 26 1.34 0.20 51 3.22 0.24

    2 0.47 0.01 27 4.10 0.46 52 3.43 0.39

    3 0.45 0.01 28 5.12 0.84 53 6.45 0.91

    4 0.51 0.01 29 1.26 0.85 54 3.16 0.16

    5 0.72 0.02 30 4.01 0.27 55 3.65 0.54

    6 0.99 0.04 31 4.32 1.33 56 4.27 0.73

    7 1.06 0.05 32 2.26 0.28 57 0.50 0.12

    8 0.86 0.05 33 1.72 0.12 58 0.28 0.08

    9 0.25 0.05 34 1.33 0.32 59 1.07 0.04

    10 0.34 0.03 35 1.46 0.15 60 0.54 0.02

    11 0.90 0.06 36 0.74 0.17 61 1.86 0.14

    12 1.10 0.07 37 0.66 0.09 62 3.94 0.3013 0.92 0.15 38 0.70 0.08 63 0.60 0.07

    14 0.78 0.16 39 3.47 0.03 64 0.74 0.05

    15 0.84 0.01 40 2.90 0.13 65 2.70 0.12

    16 0.42 0.09 41 5.27 0.18 66 2.16 0.09

    17 0.14 0.12 42 4.63 0.30 67 1.65 0.03

    18 0.63 0.19 43 2.02 0.02 68 1.96 0.03

    19 0.47 0.17 44 1.87 0.01 69 0.65 0.03

    20 4.08 0.63 45 0.66 0.06 70 0.59 0.02

    21 4.38 0.90 46 0.93 0.11 71 0.38 0.01

    22 2.59 0.25 47 2.15 0.16 72 1.11 0.02

    23 4.60 0.53 48 2.53 0.18 73 0.73 0.02

    24 4.30 0.50 49 1.72 0.19 74 0.15 0.0225 1.43 0.12 50 0.80 0.17

    Conclusion: Any deviation from normal condition not exposed. Peaks at some pointsare related to autotransformer design (magnetic shunts and leads arrangement).

    7. Results of the autotransformer vibration measurements

    Date: 27.02.2007

    Conditions: oil temperature 60; load 37%.Date: 02.03.2007

    Conditions: oil temperature 63; no-load.

    Vibration measurements were done at 3 levels around the autotransformer tank (seeImage 7):

    - 1 level 500 millimeters above the tank joint- 2 level 1600 millimeters above the tank joint (middle of the tank height)- 3 level - 2800 millimeters above the tank joint

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 12

  • 7/30/2019 Progress Report No 1t-b

    13/16

    - points for the vibration assessment by the special software Vesta- points for the analytical estimation

    Image 7. Points for the vibration measurements.

    Table 7.1. Vibro-acceleration at 37% load and no-load (m/s2).PointNo

    Level 1 PointNo

    Level 2 PointNo

    Level 3

    Load 37% No-load Load 37% No-load Load 37% No-load

    1 2.256 1.816 1 1.198 1.266 1 1.000 1.235

    2 1.521 2.358 2 1.620 1.570 2 1.000 1.718

    3 1.116 1.517 3 2.640 2.760 3 2.701 2.054

    4 2.608 3.497 4 1.250 2.221 4 1.000 1.367

    5 3.073 3.020 5 2.300 3.507 5 3.551 4.245

    6 1.335 1.391 6 2.788 3.307 6 3.417 4.700

    7 2.11 2.938 7 1.917 2.988 7 1.180 1.158

    8 1.874 3.150 8 1.594 2.836 8 1.571 2.234

    9 1.454 1.636 9 1.355 2.283 9 1.881 2.693

    10 1.000 1.166 10 1.000 1.000 10 1.000 1.000

    All measured values not exceed allowed vibro-acceleration value (9.81 m/s2).

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 13

    500 kVbushing

    220 kVbushing

    OLTC

    Maincore leg(HV)

    Tappingcore leg

    Freecore leg

    1

    2

    3

    5

    4

    7

    6

    10

    98

  • 7/30/2019 Progress Report No 1t-b

    14/16

    Table 7.2. Vibro-velocity at 37% load and no-load (millimeter per second).PointNo

    Level 1 PointNo

    Level 2 PointNo

    Level 3

    Load 37% No-load Load 37% No-load Load 37% No-load

    1 3.753 2.837 1 1.845 1.980 1 1.519 1.6942 2.474 3.513 2 2.611 1.236 2 1.135 1.466

    3 1.814 2.477 3 2.194 2.960 3 2.245 2.525

    4 4.349 4.690 4 1.157 2.266 4 1.005 2.224

    5 5.108 4.935 5 1.520 3.066 5 2.928 4.547

    6 1.562 2.145 6 2.033 5.484 6 2.875 4.760

    7 2.062 3.183 7 2.141 3.241 7 1.359 1.518

    8 3.084 4.193 8 2.619 2.804 8 2.445 2.990

    9 2.355 1.415 9 1.166 1.917 9 2.548 2.707

    10 1.373 1.239 10 1.015 1.000 10 1.581 1.476

    Table 7.3. Vibro-displacement at 37% load and no-load (micrometer).

    PointNo

    Level 1 PointNo

    Level 2 PointNo

    Level 3Load 37% No-load Load 37% No-load Load 37% No-load

    1 16.81 12.69 1 13.31 13.93 1 15.81 13.21

    2 15.96 16.56 2 11.50 13.23 2 10.86 14.26

    3 26.90 14.96 3 12.20 13.82 3 17.28 15.75

    4 19.07 18.70 4 17.79 12.48 4 15.06 16.46

    5 16.81 19.16 5 11.24 17.10 5 13.37 17.77

    6 16.42 22.67 6 11.94 22.70 6 17.28 21.00

    7 13.98 20.27 7 15.06 15.26 7 16.15 15.28

    8 15.95 21.80 8 13.85 18.67 8 20.88 17.00

    9 27.97 12.48 9 18.20 10.00 9 20.14 14.75

    10 15.26 10.64 10 16.36 11.71 10 11.73 12.67

    All measured values not exceed allowed vibro-displacement value (100micrometers).

    Also, vibration assessment with special software Vesta using was done.

    Readings of the images 8 and 9 colors:Green normal condition;Yellow lightly loosening of pressure;Red high loosening of pressure.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 14

  • 7/30/2019 Progress Report No 1t-b

    15/16

    Image 8. Results of vibration diagnosis at no-load

    Image 9. Results of vibration diagnosis at load 45%.

    Conclusion: It is possible a lightly loosening of pressure of the windings and tappingcore leg. Windings shall be pressed during repair.

    SEC ZTZ-Service Co.

    Progress report No. 1T-B Sheet 15

    HV

    side

    LV

    side

    Main

    core leg

    Main

    core leg

    Tapping

    core leg

    Freecore leg

    Freecore leg

    HVside

    LVside

    Maincore leg

    Maincore leg

    Tappingcore leg

    Freecore leg

    Freecore leg

  • 7/30/2019 Progress Report No 1t-b

    16/16