Upload
haydar
View
214
Download
1
Embed Size (px)
Citation preview
Thermal Comfort Analysis of Novel Low Exergy Radiant HeatingCooling System and Energy Saving Potential Comparingto Conventional Systems
38
Aliihsan Koca, Zafer Gemici, Koray Bedir, Erhan Boke,Barıs Burak Kanbur, and Yalcın Topacoglu
Abstract
In this study characteristics of a model room with dimensions 6 m � 4 m � 3 m has been investigated using
Computational Fluid Dynamics method with regard to thermal comfort, in case of that the room is heated and cooled
by the means of radiant panels. Both general thermal comfort parameters [PMV (percentage mean vote), PPD (predicted
percentage of dissatisfied)] and local thermal comfort parameters (radiant temperature asymmetry, draught, vertical air
temperature difference, warm and cool floors) which are described by the standards ISO 7730 and ASHRAE 55 have been
taken into consideration. Radiant panels have been placed to exterior walls for heating system, and they have been put on
both exte\rior walls and ceiling for cooling system. According to the TS 2164 standards, different regions are identified
with regard to outdoor climate conditions for heating and cooling seasons in Turkey, and analysis of heating/cooling is
done for each region. Heat fluxes from radiant panels and corresponding values of room mean temperature required in
order for the conditions of thermal comfort described by the standards ISO 7730 to be met have been determined for these
regions and heating/cooling system configurations. Energy saving potential of radiant system has been evaluated for these
regions and heating/cooling mode.
Keywords
Energy saving � Thermal comfort � Low exergy � Heating � Cooling
Introduction
Energy saving and emission reduction are both affected by the energy efficiency of the built environment and the quality of
the energy carrier in relation to the required quality of the energy. Low exergy heating and cooling systems allow to use low
valued energy, which is delivered by sustainable energy sources (e.g., by using heat pumps, solar collectors, either separate
or linked to waste heat, energy storage, etc.) and improve their performances.
It is vitally important to have a clear image of the exergy balance of the human body in order to understand what the low
exergy systems for heating and cooling in buildings are. It is interesting that the thermal comfortable condition is provided
A. Koca (*) � Z. Gemici � K. Bedir � B.B. Kanbur � Y. TopacogluMir Arastirma ve Gelistirme Inc., Y.T.U. Technopark A1 Building, 34220 Istanbul, Turkey
e-mail: [email protected]; [email protected]; [email protected]; [email protected];
E. Boke
I.T.U. Mechanical Engineering Faculty, Istanbul Technical University, 34437 Istanbul, Turkey
e-mail: [email protected]
I. Dincer et al. (eds.), Progress in Exergy, Energy, and the Environment,DOI 10.1007/978-3-319-04681-5_38, # Springer International Publishing Switzerland 2014
435
with lowest exergy consumption rate with the human body. This suggests that rational heating and cooling systems in
building would go well with low exergy consumption under a condition in which we humans consume as low amount of
exergy as possible. That is we may be able to establish both thermal comfort and low exergy consuming systems at the
same time.
Human body doesn’t sense just the temperature of the air, but also feels the operative temperature that is combination of
air temperature, air humidity, air velocity, and radiant temperature. According to this relationship lowest exergy consump-
tion rate emerges at the point where the room air temperature equals 18 �C and mean radiant temperature 25 �C [1].
This suggest that use of warm radiant energy is more effective than use of convective warm energy for a heating purpose to
realise both thermal comfort and as low exergy consumption within human body as possible.
The work concerning low exergy systems (LowEx) by Virtane and Ala-Juusela [2, 3] encourages the use of low
temperature heating systems for buildings. Low exergy heating systems allow the use of low valued energy sources. Such
heating system operates at low temperature levels that are close to room temperature. These systems can provide the
occupants with comfortable, clean, and healthy environment. In addition, low temperature systems lead to efficient use of
energy and provide flexibility in the choice of the energy source. To the knowledge of the authors, there are only a few
papers available about low temperature heating systems.
Low temperature heating with heat pump or other low temperature devices has several advantages. When using, for
example, a heat pump in low temperature systems, energy may be saved because the thermal efficiency of the pump (COP)
increases and energy loses in the distribution net decrease. Energy efficiency aside, studies show that low temperature
heating may improve indoor air quality as well as the thermal comfort conditions [4–7].
Scientist and engineers are concerned about new heating and cooling systems in buildings due to conventional air
conditioning systems consuming large amount of energy. As a result of their studies, radiant heating and cooling systems
which can produce more comfortable conditions in occupied zone and energy saving are developed. Working principle of
radiant system is based upon at least 50 % of heat transfer occurring via radiation from radiant panel placed on floor, wall, or
ceiling. By the radiant panel heat transfer occurs in two ways, primarily via radiation between panel surface and occupants
which constitutes 60–80 % of heat transfer and secondarily, heat transfer to indoor air by means of natural convection [8].
The intent of radiant systems is to lower thermostat set point temperature in winter and to increase it in summer, resulting
in substantial energy savings for heating and cooling as compared with conventional systems [9]. A forced convection
air-conditioning system creates uncomfortable environment caused by draught and air temperature differences between the
human head and foot, whereas radiant air-conditioning systems can provide lower vertical air temperature differences
and air velocity. At a given volume flow rate, water is about 4,000 times more efficient for heat transport than air.
Therefore, water heating systems are very common in Europe, and hydronic cooling systems progressively replace
air conditioning [10].
Thermal Comfort
As defined by ASHRAE Standard 55, thermal comfort is that condition of the mind that expresses satisfaction with
the thermal environment. Thermal comfort is investigated considering both general and local thermal sensation of the
human body.
General Thermal Comfort
General thermal comfort that is mainly related to PMV–PPD index can be expressed as mathematically and occupant’s
thermal sensation temperature by the whole body called as operative temperature. PMV consists of six comfort variables
(metabolic rate, clothing insulation, ambient air temperature, mean radiant temperature relative humidity, and air velocity)
and is expressed Eq. (38.1) [11] as
436 A. Koca et al.
PMV ¼ 0:303 � e�0,036�M þ 0:028� �
M �Wð Þ � 3:05 � 10�3 � 5733� 6:99 � M �Wð Þ � paf g�0:42 � M �Wð Þ � 58:15f g � 1:7 � 10�5 �M � 5867� pað Þ�0:0014M 34� Tað Þ � 3:96 � 10�8f cl Tcl þ 273ð Þ4 � Tr þ 273ð Þ4
n o
�f cl � h � Tcl � Tað Þ
2666664
3777775
ð38:1Þ
PPD is expressed via Eq. (38.2) using PMV index value [11]:
PPD ¼ 100� 95 � exp �0:03353 � PMV4 � 0:2179 � PMV2� � ð38:2Þ
Operative temperature is not equal to the ambient air temperature and is affected by surface and object temperatures of
indoor environment. When mean air speed is less than 0.2 m/s, operative temperature is calculated by Eq. (38.3):
T0 ¼ Tr þ Ta
2ð38:3Þ
General thermal comfort criteria which are described by the standards ISO 7730 are shown in Table 38.1.
Local Thermal Comfort
In the earlier years of thermal comfort studies, comfort was usually described as affected by the occupant’s thermal sensation
by the whole body. But aside from the overall thermal state of the body, an occupant may also find the thermal environment
unacceptable if local influences on the body from radiant temperature asymmetry, draught, vertical air temperature
differences, and cold or warm floors.
Radiant temperature asymmetry is the difference between the maximum and the minimum radiant temperature on the
surfaces of a cube element located at a point in the space being conditioned [3].
Draught is the unwanted local cooling of the body caused by air movement.
Vertical air temperature difference is a high vertical air temperature difference between the ankle and the head (0.1 and
1.1 m above the floor) which usually causes discomfort. This air temperature difference should be less than 3 �C.Floor surface temperature is especially important for thermal comfort assessment of spaces with occupants wearing light
indoor shoes or in cases where occupants sit/lie on the floor or walk indoors with bare feet as common in Asia.
Room Modeling
A CFD model with dimensions 6 m � 4 m � 3 m is designed. Two single-glazed windows which are included in the CFD
model have 1.4 m height and 1.2 m weight. Four different room models are obtained to be placed on wall surfaces of panels
with dimensions 0.6 m � 1.2 m as shown in Fig. 38.1; panels are installed all around of the window in the first model
(Fig. 38.1a), windowless exterior wall in the second model (Fig. 38.2a), either walls in the third model (Fig. 38.3a), and
ceiling in the fourth model (Fig. 38.4a). The TS 2164 standards identify four different regions in Turkey with regard to
outdoor climate conditions in winter used in heating systems design. Each region has been represented in numerical analysis
by setting these climatological parameters as boundary conditions in heating mode (Table 38.2), where in the case of
cooling, summer conditions as well as incident radiation through window are taken into account.
Table 38.1 General thermal
comfort criteriaParameter Limit value
PMV �0.5 < PMV < 0.5
PPD (%) PPD < 10
Operative temperature (�C) Winter (1 clo/1.2 met) 20–24Summer (0.5 clo/1.2 met) 23–26
38 Thermal Comfort Analysis of Novel Low Exergy Radiant Heating Cooling System. . . 437
Fig. 38.1 (a) Model 1;
(b) Model 2; (c) Model 3;
(d) Model 4
a bVelocity
0.130
0.098
0.065
0.033
0.000[m s∧−1]
Temperature
295.987
297.614
294.361
292.734
291.108
289.481
287.855[K]
Fig. 38.2 (a) Streamline distribution in model 2; (b) Model 2 surfaces temperature distribution
0
20
40
60
80
100
-3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 3
PP
D (
%)
PMV
Fig. 38.3 The relationship
between PMV and PPD
for model 2
438 A. Koca et al.
Numerical Solution Method
In fluid mechanics and heat transfer, basis of conservation equations stated as mathematical treatment of fluid depends on
conservation of mass, momentum, and energy. In this study, flow is steady state and three dimensional, and physical
properties of the fluid such as density, viscosity, and thermal conductivity are constant. Consequently, conservation
equations are obtained as below [12]:
Continuity equation,
∂u∂x
þ ∂v∂y
þ ∂w∂z
¼ 0 ð38:4Þ
Momentum equations of x, y, z direction can be stated, respectively:
u∂u∂x
þ v∂u∂y
þ w∂u∂z
¼ � 1
ρ
∂p∂x
þ ν∂2u
∂x2þ ∂2u
∂y2þ ∂2u
∂z2
� �ð38:5Þ
u∂v∂x
þ v∂v∂y
þ w∂v∂z
¼ � 1
ρ
∂p∂y
þ ν∂2v
∂x2þ ∂2v
∂y2þ ∂2v
∂z2
� �� g ð38:6Þ
u∂w∂x
þ v∂w∂y
þ w∂w∂z
¼ � 1
ρ
∂p∂z
þ ν∂2w
∂x2þ ∂2w
∂y2þ ∂2w
∂z2
� �ð38:7Þ
Energy equation can be stated as below:
u∂T∂x
þ v∂T∂y
þ w∂T∂z
¼ α∂2T
∂x2þ ∂2T
∂y2þ ∂2T
∂z2
� �ð38:8Þ
Fig. 38.4 Reference line 1, 2, 3
Table 38.2 Outside air temperature in different region for cooling and heating season
Region City
Heating season outside
air temperature (�C)Cooling season outside
air temperature (�C)1 Antalya 3 39
2 Istanbul �3 33
3 Ankara �12 35
4 Erzurum �21 31
38 Thermal Comfort Analysis of Novel Low Exergy Radiant Heating Cooling System. . . 439
Between radiant panels and indoor air, heat transfer occurs via natural convection which has been modeled by employing
Boussinesq method that yields good results provided with small difference in extremum values of temperature within the
space in question. Turbulence is simulated by the standard k-ε model which is reported to be a good approximation
especially for near-wall flows. Radiation heat transfer has been represented by employing the Discrete Ordinates method
which takes account scattering, semi-transparent media, reflecting surface, and wavelength-dependent transmission [13].
Results and Discussion
Heating Cases of Study
Room has two exterior and interior walls, a ceiling, and floor. This room heating analysis is done when room situate in
self-contained flat. In this case, ceiling, floor, and interior walls of the room are neighbor to cockloft, ground, and unheated
space, respectively. Heating analysis was made for room model 1, 2, 3.
Results of Heating CasesAnalysis results will be expressed with regard to model 2. These results were obtained when panel heating performance
was 35 W/m2, considering second region’s outside air condition. Figure 38.2a shows velocity streamline in room.
Natural circulation of air flow in contact with warm panel surface is obviously shown in Fig. 38.2a. On the panel, surface
had air speed 0.13 m/s which is the highest air velocity in the room. Figure 38.2b represents temperature distribution on
walls, window, and panels. Warmed panel, cold window, and whole wall surface mean temperatures were found to be
296.4, 288, and 292 K, respectively, in the room.
Investigation of General Thermal Conditions Comfort for Room Model 2
General thermal comfort is based on PMV and PPD indices and operative temperature. Therefore, these parameters must be
calculated. The PMV value is calculated from Eq. (38.1). For the purpose of solving this equation, mean radiant temperature
that must be calculated is expressed in Eq. (38.9) [14].
Tr ¼ Tp þ Taust
2ð38:9Þ
Panel surface temperature (Tp) was found to be 296.4 K as a result of numerical analysis. Area-weighted unheated surface
temperature (Taust) was calculated as 292 K with Eq. (38.10) [14].
Taust ¼ Ts1 � As1 � εs1 þ Ts2 � As2 � εs2 þ . . .þ Tsn � Asn � εsnð ÞAs1 � εs1 þ As2 � εs2 þ . . .þ Asn � εsnð Þ ð38:10Þ
Depending on these values, mean radiant temperature (Tr) was estimated to be 294.1 K using Eq. (38.9). As a result
of numerical analysis, mean air temperature and air velocity were found to be 292.5 K and 0.013 m/s, respectively. Clothing
in winter, metabolic rate of occupants, and relative humidity were admitted 1 clo, 1.2 met, and 50 %, respectively [11].
Values of these six comfort variables are shown in Table 38.3.
Operative temperature was computed 293.3 K with Eq. (38.3). PMV and PPD values were estimated by computer
program which is written based on ASHRAE 55 and ISO 7730 standards. Values of the these parameters are shown in
Table 38.4.
Table 38.3 General thermal
comfort input values for model 2Parameter Input values
Clothing insulation (clo) 1
Mean air temperature (�C) 19.5
Mean radiant temperature (�C) 21.1
Metabolic rate (met) 1.2
Air velocity (m/s) 0.013
Relative humidity (%) 50
440 A. Koca et al.
The relationship between PMV and PPD is shown in Fig. 38.3. Intersection of PMV and PPD values is within the region
defined by thermal comfort
Investigation of Local Thermal Comfort Conditions for Room Model 2
The occupied zone is defined as a space 0.6 m distant from all walls and up to 1.8 m above floor level [9]. Most critical plane
in the occupied zone is farthest from panels. Reference lines were all in the critical plane and the reference lines 1, 2, and 3
were 0.6, 3, and 5.4 m distant from exterior wall which has a window, respectively (Fig. 38.4).
Temperature differences between 0.1 and 1.1 m above the floor on reference line 1, 2, and 3 were found to be 0.4, 0.3, and
0.5 �C, respectively. None of the values exceed recommended limit that is given by ISO 7730 (Table 38.5).
Maximum air velocities on reference line 1, 2, and 3 were obtained as 0.013, 0.01, 0.017 m/s, respectively. These air
velocities are less than 0.18 m/s described by ISO 7730 (Table 38.6).
Figure 38.5 represents temperature distribution in the middle plane of the room. The difference between highest and
lowest temperature is 0.34 K, which is under the standard limitation of 23 K (radiant temperature asymmetry caused by
warm vertical wall) set by ISO 7730.
Room floor surface temperature was found to be 19.2 �C which is the range of floor surface temperatures (19–29 �C)described by ISO 7730.
Table 38.4 General thermal
comfort output values for model 2Parameter Output values
Operative temperature (�C) 20.3
PMV �0.28
PPD (%) 6.63
Table 38.5 Vertical air
temperature differences
0.1–1.1 m on reference line
Reference line T0.1 (K) T1.1 (K) T1.1–T0.1 (K) ISO 7730 (K)
1 292 292.4 0.4 <3
2 292.1 292.4 0.3 <3
3 291.8 292.3 0.5 <3
Table 38.6 Maximum air
velocities on reference lineReference line Maximum speed (m/s) ISO 7730 (m/s)
1 0.013 <0.18
2 0.01 <0.18
3 0.017 <0.18
Fig. 38.5 Temperature
distribution in the middle
plane of the room
38 Thermal Comfort Analysis of Novel Low Exergy Radiant Heating Cooling System. . . 441
Investigation of Thermal Comfort as Regards Clothing Insulation and Metabolic Rate
The relationship between PPD and clothing insulation is shown in Fig. 38.6. Thermal comfort requirement is provided in the
range of 1–1.6 clo. Clothing insulation and PPD values of the optimal thermal comfort are 1.2 clo and 5 %, respectively.
Figure 38.7 presents the relationship between PPD and metabolic rate. Thermal comfort is satisfied from 1.2 to 1.6 clo, so
occupants feel comfortable themselves in this metabolic rate range in room. Clothing insulation and PPD values of the
optimum thermal comfort are 1.3 met and 5.13 %, respectively.
Cooling Cases of Study
Room cooling analysis is done when room situate in mezzanine, so heat loss takes place from exterior walls and window
only. Cooling analysis was made for all room models.
Results of Cooling CasesAnalysis results will be explained considering model 4. These results were obtained when panel cooling performance
was 18 W/m2, considering second region’s outside air condition. Figure 38.8a represents velocity streamline in model 4,
and maximum air speed was 0.111 m/s. Figure 38.8b demonstrates temperature distribution on whole room surfaces.
Warm window, cooled panel, and other wall surface temperatures were found to be 302.2, 299, and 296.8 K, respectively.
Investigation of General Thermal Comfort Conditions for Room Model 4
Parameters of calculating PMV were given as follows: clothing, 0.5 clo in summer; metabolic rate of occupant, 1.2 met;
relative humidity, 50 % [11]. As a result of numerical analysis, mean air temperature and air velocity were found to be
298.5 K and 0.018 m/s, respectively, and mean radiant temperature was found to be 297.9 K using with Eq. (38.9).
Consequently, the values of these six comfort variables are shown in Table 38.7.
PMV, PPD, and operative temperature values are shown in Table 38.8. These values show that thermal comfort is provided.
0
5
10
15
20
25
30
35
0.5 1 1.5 2 2.5
PP
D (
%)
Icl (clo)
Fig. 38.6 The relationship
between PPD and clothing
insulation
0
5
10
15
20
25
30
35
40
45
0.5 1 1.5 2 2.5
PP
D (
%)
Metabolic rate (met)
Fig. 38.7 The relationship
between PPD and metabolic rate
442 A. Koca et al.
Minimum Heat Flux Requirements from Radiant Panels in the Case of Heating and Cooling
Minimum heat fluxes from radiant panels and corresponding values of PMV, PPD, and room mean temperature are shown
for different region and heating/cooling in Tables 38.9 and 38.10. Mean air temperature of model 1 became lower in cooling
and higher in heating than other models for different regions.
Comparison of Radiant and Conventional Systems Under Similar Thermal Conditions
Having compared radiant and conventional heating systems under similar thermal conditions, indoor air temperature was
found to be 1.1 �C less in case of radiant heating than that of conventional heating because mean radiant temperature in
radiant heating was 1.1 �C higher than in convective heating (Table 38.11).
baVelocity
0.111
0.083
0.055
0.028
0.000[m s∧−1]
Temperature
302.352
301.473
300.594
299.715
298.837
297.958
297.079
296.200
295.322[K]
Fig. 38.8 (a) Streamline distribution in model 4; (b) Model 4 surfaces temperature distribution
Table 38.7 General thermal
comfort input values for model 4Parameter Input values
Clothing insulation (clo) 0.5
Mean air temperature (�C) 25.5
Mean radiant temperature (�C) 24.9
Metabolic rate (met) 1.2
Air velocity (m/s) 0.018
Relative humidity (%) 50
Table 38.8 General thermal
comfort output values for model 4Parameter Output values
Operative temperature (�C) 25.2
PMV 0.21
PPD (%) 5.91
Table 38.9 Minimum heat flux requirements from radiant panels for different regions in heating
Region
Model 1 Model 2 Model 3
1 2 3 4 1 2 3 4 1 2 3 4
Heat flux (W/m2) 60 70 90 110 30 35 45 55 15 20 25 30
PMV �0.47 �0.29 �0.32 �0.39 �0.35 �0.28 �0.29 �0.32 �0.48 �0.28 �0.37 �0.44
PPD (%) 9.61 6.75 7.13 8.17 7.55 6.63 6.75 7.1 9.81 6.63 7.85 9.04
Operative temperature (�C) 20 20.4 20.4 20.2 20 20.3 20.3 20.2 20 20.2 20 20
Mean air temperature (�C) 17.2 18.4 17.8 17 19.2 19.5 19.2 18.9 18.9 19.7 19.2 18.8
38 Thermal Comfort Analysis of Novel Low Exergy Radiant Heating Cooling System. . . 443
Annual Energy Saving in the Case of Radiant Heating and Cooling
Table 38.12 demonstrates annual energy savings using radiant heating system for different regions. There is remarkable
energy saving using radiant system for heating. Energy saving was larger at regions where heating load was higher and could
reach maximum level in the coldest region. The more energy saving could be achieved using model 3.
Annual energy savings are shown for radiant cooling system in Table 38.13. Model 3 has maximum energy saving,
whereas model 4 has minimum energy saving. Energy saving is larger at regions where cooling load is higher.
Conclusion
Thermal comfort and energy efficiency performance of the novel radiant heating and cooling systems were investigated with
CFD method according to different building and heating/cooling system configurations in this study. The following
conclusions have been reached:
• The use of radiant heating and cooling systems in a model room fulfills general and local thermal comfort requirements
with lower air temperature for heating and higher air temperature for cooling than conventional system
Table 38.13 Annual energy saving use of radiant cooling systems
Region
Energy saving (Turkish currency)
Model 1 Model 2 Model 3 Model 4
1 25.7 30.0 36.4 15.1
2 15.0 15.0 16.7 10.1
3 11.9 12.5 14.5 7.6
4 1.3 1.5 1.6 1.1
Table 38.10 Minimum heat fluxes requirements from radiant panels for different regions in cooling
Region
Model 1 Model 2 Model 3 Model 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Heat flux (W/m2) 54 47 49 44 25.5 23.5 24 21 15.5 15 15 13.5 20.5 17.5 18.5 15.5
PMV 0.25 0.35 0.35 0.37 0.32 0.33 0.44 0.43 0.31 0.29 0.4 0.4 0.36 0.38 0.39 0.37
PPD (%) 6.3 7.55 7.55 7.85 7.13 7.26 9.04 8.86 7 6.75 8.33 8.33 7.7 8.01 8.17 7.85
Operative temperature (�C) 25.2 25.6 25.6 25.7 25.6 25.6 25.9 25.9 25.5 25.5 25.8 25.8 25.7 25.8 25.8 25.5
Mean air temperature (�C) 27 27 27 26.9 26.1 26.2 26.6 26.4 26 25.8 26.2 26.1 26 26.1 26.1 26
Table 38.11 Comparison of radiant and conventional systems
Parameter Radiant heating Conventional heating
Input Clothing insulation (clo) 1 1Mean air temperature (�C) 20.9 22Mean radiant temperature (�C) 22.3 21.2Metabolic rate (met) 1.2 1.2Air velocity (m/s) 0.028 0.028Relative humidity (%) 50 50
Output Operative temperature (�C) 21.6 21.6PMV 0 0PPD (%) 5 5
Table 38.12 Annual energy saving use of radiant heating systems
Region
Energy saving (Turkish currency)
Model 1 Model 2 Model 3
1 79.0 79.0 100.7
2 143.2 143.2 179.4
3 178.5 178.5 233.8
4 268.2 268.2 333.7
444 A. Koca et al.
• All investigated radiant heating and cooling systems gave an acceptable indoor environment, which has smaller vertical
temperature differences and almost no air movement field
• In order to meet the conditions of thermal comfort required heat flux from radiant panels are obtained numerically for
different regions
• There is remarkable energy saving using radiant system for heating, even much more in colder areas in Turkey. In cooling
season energy saving associated with radiant system is lower than it is in heating season, since there is a smaller
difference between values of indoor and outdoor temperature, and furthermore, cooling period is shorter than its heating
counterpart.
• Both in heating and cooling cases, energy savings increase when panels are placed and heat loss occurred in either
exterior walls
Nomenclature
As Surface area
M Metabolic rate, W/m2
W Effective mechanical power, W/m2
pa Water vapour partial, Pa
Ta Air temperature, �Cfcl Clothing surface area factor
Taust Area-weighted unheated surface temperature, �CTcl Clothing surface temperature, �CTo Operative temperature
Tp Panel surface temperature, �CTr Mean radiant temperature, �C
Ts Surface temperature
T0.1 Air temperature at 0.1 m above floor level, �CT1.1 Air temperature at 1.1 m above floor level, �Ch Convective heat transfer coefficient, W/m2�Cu Velocity component in x direction, m/s
v Velocity component in y direction, m/s
w Velocity component in z direction, m/s
x,y,z Cartesian coordinates
p Pressure, Pa
g Acceleration of gravity
Greek Letters
ρ Density, kg/m3
α Thermal diffusivity coefficient
ε Emissivity
References
1. Isawa K, Komizo T, Shukuya M (2002) Low exergy systems will provide us with the lowest human-body exergy consumption and thermal comfort. Lowex News,
publication of IEA Annex 37, No 5, July 2002, pp 8–11
2. Virtanen M, Ala-Juusela M (2007) Increased energy efficiency and improved comfort. Paper No. 1494. 9th REHVA world congress, Clima 2007, 10–14 June,
Helsinki, Finland
3. Ala-Juusela M (2003) Heating and cooling with focus on increased energy efficiency and improved comfort. Guidebook to IEA ECBCS, Annex 37, Low Exergy
Systems for Heating and Cooling of Buildings, VTT Technical Research Centre of Finland. http://www.vtt.fi/inf/pdf/tiedotteet/2004/T2256.pdf
4. Olesen BW, Mortensen E, Thorshauge J (1980) Thermal comfort in a room heated by different methods. Technical Paper no. 2256, Los Angeles Meeting,
ASHRAE Transactions 86
5. Nilsson PE (ed) (2003) Achieving the desired indoor climate, IMI indoor climate and studentlitteratur. ISBN 91-44-03235-8
6. Hutter E (1991) Comparison of different heat emitters in respect of thermal comfort and energy consumption. In: Proceedings of the international centre for heat
and mass transfer, heat and mass transfer in building materials and structures, pp 753–769
7. Eijdems HHEW, Boerstra AC (2000) Low temperature heating systems: impact on IAQ. Thermal comfort and energy consumption, Annex 37, Newsletter 1
8. Laouadi A (2004) Development of a radiant heating and cooling model for building energy simulation software. Build Environ 39:421–431
9. Myhren JA, Holmberg S (2008) Flow patterns and thermal comfort in a room with panel, floor and wall heating. Energy Build 40:524–536
10. Okamoto S, Kitora H, Yamaguchi H, Oka T (2010) A simplified calculation method for estimating heat flux from ceiling radiant panels. Energy Build 42:29–33
11. EN ISO 7730 (2005) Ergonomics of thermal environment-analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD
indices and local thermal comfort criteria. International Organization for Standardization, Geneva
12. White FM (2003) Fluid mechanics. Hemisphere–McGraw-Hill, New York, NY
13. Fluent User’s Guide (1998) Fluent incorporated. Centerra Resource Park, Lebanon
14. ASHRAE Standard 55 (2003) Thermal environment conditions for human occupancy. ASHRAE
38 Thermal Comfort Analysis of Novel Low Exergy Radiant Heating Cooling System. . . 445