Upload
vuongnhu
View
213
Download
0
Embed Size (px)
Citation preview
1 Program Summary
XC series PLC as the controllers, accept the signal and execute the program in the
controller, to fulfill the requirements from the users. In this chapter, we start with the
program forms, introduce the main features, the supported two program languages etc.
1-1.Programmer Controller’s Features
1-2.Program Language
1-3.Program Format
1-1.Program Controller’s Features
XC series PLC support two kinds of program languages, instruction list and ladder,
the two languages can convert to the other;
To avoid the stolen or wrong modifying of user program, we encrypt the program.
When uploading the encrypted program, it will check in the form of password. This
can maintain the user’s copyright; meantime, it limits the download, to avoid the
modification with the program spitefully.
When the user program is too long, adding comments to the program and its soft
components is necessary.
Add offset appendix (like X3[D100]、M10[D100]、D0[D100]) behind coils, data
registers can realize indirect addressing. For example, when D100=9, X3[D100]=X14;
M10[D100]=M19, D0[D100]=D9
l XC series PLC offers enough basic instructions, can fulfill basic sequential
control, data moving and comparing, arithmetic operation, logic control, data
loop and shift etc.
l XC series PLC also support special compare, high speed pulse, frequency testing,
precise time, PID control, position control etc for interruption, high speed counter
(HSC).
XC series PLC support C language function block, users can call the edited function
block freely. This function reduces the program quantity greatly.
Program Language
Security of the Program
Program’s comments
Rich Basic Functions
C Language Function Block
Stop when power ON Function
Offset Function
XC series PLC support “Stop when power on PLC” function. With this function,
when there is a serious problem during PLC running, use this method to stop all
output immediately. Besides, with this method, connect PLC when parameters are set
wrongly.
XC series PLC support many communication formats, like basic Modbus
communication, CABBUS communication, free format communication. Besides, via
special network module, connect to Ether net, GPRS net.
1-2.Program Language
1-2-1.Type
XC series PLC support two types of program language:
Instruction list inputs in the form of “LD”, “AND”, “OUT” etc. This is the basic input
form of the programs, but it’s hard to read and understand;
E.g.: Step Instruction Soft Components
With sequential control signal and soft components, draw the sequential control graph
on program interface, this method is called “Ladder”. This method use coil signs etc.
to represent sequential circuit, so it’s easier to understand the program. Meantime,
monitor PLC with the circuit’s status.
E.g.:
X0 X2
Y5
Y5
0 LD X000
1 OR Y005
2 ANI X002
3 OUT Y005
Instruction List
Ladder
Communication Function
1-2-2.Alternation
Convert the above two methods freely:
1-3.Program Format
The above two program methods can input in the correspond interface separately, especially in the
ladder window, there is a instruction hint function, which improves the program efficiency greatly;
As in XC series PLC, there are many instructions which has complicate usage and
many using methods, like pulse output instruction, main unit PID etc. XCPPro also
support the configure interface for these special instructions. In the correcpond
configure interface, input the parameters and ID according to the requirements will be
ok;
Instruction Ladder
Direct Input
Panel Configuration
For the details of panel configuration, please refer《XC series PLC user manual【software part】》
2 Soft Component’s Function
In chapter 1, we briefly tell the program language of XC series PLC. However, the most important
element to a program is the operands. These elements relate to the relays and registers inside the
controller. In this chapter, we will describe the functions and using methods of these relays and
registers.
2-1.Summary of the Soft Components
2-2.Structure of the Soft Components
2-3.List of the Soft Components
2-4.Input/output Relays (X、Y)
2-5.Auxiliary Relays (M)
2-6.Status Relays (S)
2-7.Timers (T)
2-8.Counters (C)
2-9.Data Registers (D)
2-10.Constant (K、H)
2-11.Pointer (P、I)
2-12.Program Principle
2-1.Summary of the Soft Components
There are many relays, timers and counters inside PLC. They all have countless NO (Normally
ON) and NC (Normally Closed) contactors. Connect these contactors with the coils will make a
sequential control circuit. Below, we will introduce these soft components briefly;
l Usage of the input relays
The input relays are used to accept the external ON/OFF signal, we use X to state.
l Address Specify Principle
Ø In each basic unit, specify the ID of input relay, output relay in the form of
X000~X007,X010~X017…,Y000~Y007,Y010~Y017… (octal form)
Ø The expansion module’s ID obeys the principle of channel 1 starts from X100/Y100,
channel 2 starts from X200/Y200… 7 expansions can be connected in total.
l Points to pay attention when using
Ø For the input relay’s input filter, we use digital filter. Users can change the filter
parameters via relate settings.
Ø We equip enough output relays inside PLC; for the output relays beyond the
input/output points, use them as auxiliary relays, program as normal contactors/coils.
l Usage of the output relays
Output relays are the interface of drive external loads, represent with sign Y;
l Address Assignment Principle
Ø In each basic unit,assign the ID of output relays in the form of Y000~Y007,
Y010~Y017… this octal format.
Ø The ID of expansion obeys the principle of: channel 1 starts from Y100, channel 2 starts
from Y200… 7 expansions could be connected totally.
l Usage of Auxiliary Relays
Auxiliary relays are equipped inside PLC, represent with the sign of M;
l Address assignment principle
In basic units, assign the auxiliary address in the form of decimal
l Points to note
Ø This type of relays are different with the input/output relays, they can’t get external load,
can only use in program;
Ø Retentive relays can keep its ON/OFF status in case of PLC power OFF;
Output Relay(Y)
Auxiliary Relays(M)
Input Relay (X)
l Usage of status relays
Used as relays in Ladder, represent with “S”
l Address assignment principle
In basic units, assign the ID in the form of decimal
l Points to note
If not used as operation number, they can be used as auxiliary relays, program as
normal contactors/coils. Besides, they can be used as signal alarms, for external
diagnose.
l Usage of the timers
Timers are used to calculate the time pulse like 1ms, 10ms, 100ms etc. when reach the
set value, the output contactors acts, represent with “T”
l Address assignment principle
In basic units, assign the timer’s ID in the form of decimal. But divide ID into several parts
according to the clock pulse, accumulate or not. Please refer to chapter 2-2 for details.
l Time pulse
There are three specifications for the timer’s clock pulse: 1ms、10ms、100ms. If choose 10ms timer,
carry on addition operation with 10ms time pulse;
l Accumulation/not accumulation
The times are divided into two modes: accumulation time means even the timer coil’s driver is
OFF, the timer will still keep the current value; while the not accumulation time means when the
count value reaches the set value, the output contact acts, the count value clears to be 0;
According to different application and purpose, we can divide the counters to different types as
below:
l For internal count (for general using/power off retentive usage)
Ø 16 bits counter: for increment count, the count range is 1~32,767
Ø 32 bits counter: for increment count, the count range is 1~2,147,483,647
Ø These counters can be used by PLC’s internal signal. The response speed is one scan
cycle or longer.
l For High Speed Count (Power off retentive)
Ø 32 bits counter: for increment/decrement count, the count range is -2,147,483,648~
+2,147,483,647
(single phase increment count, single phase increment/decrement count, AB phase cont)
specify to special input points (
Status Relays(S)
Timer(T)
Counter(C)
Ø The high speed counter can count 80KHz frequency, it separates with the PLC’s scan
cycle;
l Usage of Data Registers
Data Registers are used to store data, represent with “D”
l Addressing Form
The data registers in XC series PLC are all 16 bits (the highest bit is the sign bit), combine
two data registers together can operate 32 bits (the highest bit is the sign bit) data process.
l Points to note
Same with other soft components, data registers also have common usage type and power off
retentive type.
l Usage of FlashROM registers
FlashROM registers are used to store data soft components, represent with “FD”
l Addressing Form
In basic units, FlashROM registers are addressed in form of decimal;
l Points to note
Even the battery powered off, this area can keep the data. So this area is used to store
important parameters. FlashROM can write in about 1,000,000 times, and it takes time at
every write. Frequently write can cause permanent damage of FD.
l In every type of data in PLC, B represents Binary, K represents Decimal, H represents
Hexadecimal. They are used to set timers and counters value, or operands of application
instructions.
Data Register(D)
FlashROM Register(FD)
Constant(B)(K)(H)
2-2.Structure of Soft Components
2-2-1.Structure of Memory
In XC series PLC, there are many registers. Besides the common data registers D, FlashROM
registers, we can also make registers by combining bit soft components.
Data Register D
l For common use, 16 bits
l For common use, 32 bits (via combine two sequential 16 bits registers)
l For power off retentive usage, can modify the retentive zone
l For special usage, occupied by the system, can’t be used as common instruction’s parameters
l For offset usage (indirect specifies)
Ø Form: Dn[Dm]、Xn[Dm] 、Yn[Dm] 、Mn[Dm] etc.
MOV D10[D0] D100M8000
M2
Y0[D0]
MOV K5 D0
M8002MOV K0 D0
In the above sample, if D0=0, then D100=D10, Y0 is ON.
If M2 turns from OFF to be ON, D0=5, then D100=D15, Y5 is ON.
Therein, D10[D0]=D[10+D0],Y0[D0]=Y[0+D0]。
Ø The word offset combined by bit soft components: DXn[Dm] represents DX[n+Dm]。
Ø The soft components with offset, the offset can be represent by soft component D.
Timer T/Counter C
l For common usage, 16 bits, represent the current value of timer/counter;
l For common usage, 32 bits, (via combine two sequential 16 bits registers)
l To represent them, just use the letter+ID method, such as T10, C11.
E.g.
MOV D0T11M0
T11Y1
X0T11 K99
In the above example, MOV T11 D0, T11 represents word register;
LD T11, T11 represents bit register.
Bit soft components combined to be register
l For common usage, 16 bits, (via combine two sequential 16 bits registers)
l The soft components which can be combined to be words are: X、Y、M、S、
T、C
l Format: add “D” in front of soft components, like DM10, represents a 16
bits data from M10~M25
l Get 16 points from DXn, but not beyond the soft components range;
l The word combined by bit soft components can’t realize bit addressing;
E.g.:
MOV K21 DY0M0
MOV K3 D0M1
MOV DX2[D0] D10M8000
Ø When M0 changes from OFF to be ON, the value in the word which is
combined by Y0~Y17 equals 21, i.e. Y0、Y2、Y4 becomes to be ON
Ø Before M1 activates, if D0=0, DX2[D0] represents a word combined by
X2~X21
Ø If M1 changes from OFF→ON, D0=3,then DX2[D0] represents a
Expansion’s internal register ED
l For common usage, 16 bits,
l For common usage, 32 bits, (via combine two sequential 16 bits registers)
FlashROM Register FD
l For power off retentive usage, 16 bits
l For power off retentive usage, 16 bits, (via combine two sequential 16 bits registers)
l For special usage, occupied by the system, can’t be used as common instruction’s
parameters
2-2-2.Structure of Bit Soft Components
Bit soft components structure is simple, the common ones are X、Y、M、S、T、C, besides, a bit
of a register can also represents:
Relay
l Input Relay X, octal type
l Output Relay Y, octal type
l Auxiliary Relay M、S, decimal type
l Auxiliary Relay T、C, decimal type, as the represent method is same with
registers, so we need to judge if it’s word register or bit register according to
the register.
Register’s Bit
l Composed by register’s bit, support register D
l Represent method: Dn.m (0≤m≤15): the Nr.m bit of Dn register
l The represent method of word with offset: Dn[Dm].x
l Bit of Word can’t compose to be word again;
E.g.:
D0.4Y0
D5[D1].4Y1
Ø D0.4 means when the Nr.4 bit of D0 is 1, set Y0 ON .
Ø D5[D1].4 means bit addressing with offset, if D1=5, then D5[D1]
means the Nr.4 bit of D10
2-3.Soft Components List
2-3-1.Soft Components List
Range points Mnemonic Name
10I/O 16 I/O 24 I/O 32 I/O 10 I/O 16 I/O 24 I/O 32 I/O
Input Points X0~X4 X0~X7 X0~X13 X0~X17 5 8 12 16 I/O points
※1 Output Points Y0~Y4 Y0~Y7 Y0~Y13 Y0~Y17 5 8 12 16
X※2 Internal Relay X0~X77 64
Y※3 Internal Relay Y0~Y77 64
M0~M199【M200~M319】※4 320
For Special Usage ※5M8000~M8079
For Special Usage ※5M8120~M8139
For Special Usage ※5M8170~M8172
For Special Usage ※5M8238~M8242
M Internal Relay
For Special Usage ※5M8350~M8370
128
S Flow S0~S31 32
T0~T23: 100ms not accumulation
T100~T115: 100ms accumulation
T200~T223: 10ms not accumulation
T300~T307: 10ms accumulation
T400~T403: 1ms not accumulation
T Timer
T500~T503: 1ms accumulation
80
C0~C23: 16 bits forward counter
C300~C315: 32 bits forward/backward
counter
C600~C603: single-phase HSC
C620~C621
C Counter
C630~C631
48
D0~D99【D100~D149】※4 150
For Special Usage ※5D8000~D8029
For Special Usage ※5D8060~D8079
For Special Usage ※5D8120~D8179
For Special Usage ※5D8240~D8249
For Special Usage ※5D8306~D8313
D Data Register
For Special Usage ※5D8460~D8469
138
FD FlashROM FD0~FD411 412
XC1 Series
For Special Usage ※5FD8000~FD8011
For Special Usage ※5FD8202~FD8229
For Special Usage ※5FD8306~FD8315
For Special Usage ※5FD8323~FD8335
Register※6
For Special Usage ※5FD8350~FD8384
98
Range Points
Mnemonic Name 14 I/O 16 I/O 24/32 I/O 48/60 I/O
14
I/O
16
I/O
24/32
I/O
48/60
I/O
Input
Points X0~X7 X0~X7
X0~X15
X0~X21
X0~X33
X0~X43 8 8 14/18 28/36
I/O Points※1 Output
Points Y0~Y5 Y0~Y7
Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 6 8 10/14 20/24
X※2
Internal
Relay X0~X1037 544
Y※3
Internal
Relay Y0~Y1037 544
M0~M2999
【M3000~M7999】※4
8000 M
Internal
Relay For Special Usage
※5M8000~M8767 768
S Flow S0~S511
【S512~S1023】※4
1024
T0~T99: 100ms not accumulation
T100~T199: 100ms accumulation
T200~T299: 10ms not accumulation
T300~T399: 10ms accumulation
T400~T499: 1ms not accumulation
T500~T599: 1ms accumulation
T Timer
T600~T639: 1ms precise time
640
C0~C299: 16 bits forward counter
C300~C599: 32 bits forward/backward
counter
C600~C619: single-phase HSC
C620~C629: double-phase HSC
C Counter
C630~C639: AB phase HSC
640
D0~D999
【D4000~D4999】※4
2000 D Data
Register
For Special Usage※5D8000~D8511 612
XC2 Series
For Special Usage※5D8630~D8729
FD0~FD127 128 FD
FLASH
Register For Special Usage※5FD8000~FD8383 384
Range Points
Mnemonic Name 14 I/O 24/32 I/O 48/60 I/O
14
I/O
24/32
I/O
48/60
I/O
Input Points X0~X7 X0~X15
X0~X21
X0~X33
X0~X43 8 14/18 28/36
I/O Points※1
Output Points Y0~Y5 Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 6 10/14 20/24
X※2 Internal Relay X0~X1037 544
Y※3 Internal Relay Y0~Y1037 544
M0~M2999
【M3000~M7999】※4
8000 M Internal Relay
For Special Usage※5M8000~M8767 768
S Flow S0~S511
【S512~S1023】※4
1024
T0~T99: 100ms not accumulation
T100~T199: 100ms accumulation
T200~T299: 10ms not accumulation
T300~T399: 10ms accumulation
T400~T499: 1ms not accumulation
T500~T599: 1ms accumulation
T TIMER
T600~T639: 1ms precise time
640
C0~C299: 16 bits forward counter
C300~C599: 32 bits forward/backward counter
C600~C619: single-phase HSC
C620~C629: double-phase HSC
C COUNTER
C630~C639: AB phase HSC
640
D0~D3999
【D4000~D7999】※4
8000 D
DATA
REGISTER For Special Usage
※5D8000~D9023 1024
XC3 Series
FD0~FD1535 1536 FD
FlashROM
REGISTER※6 For Special Usage
※5FD8000~FD8511 512
ED※7
EXPANSION’S
INTERNAL
REGISTER
ED0~ED16383 16384
I/O RANGE POINTS Mnemonic Name
24/32 I/O 48/60 I/O 24/32 I/O 48/60 I/O
Input Points X0~X15
X0~X21
X0~X33
X0~X43 14/18 28/36
I/O Points※1
Output Points Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 10/14 20/24
X※2 Internal Relay X0~X1037 544
Y※3 Internal Relay Y0~Y1037 544
M0~M3999
【M4000~M7999】※4
8000 M Internal Relay
For Special Usage※5M8000~M8767 768
S Flow S0~S511
【S512~S1023】※4
1024
T0~T99: 100ms not accumulation
T100~T199: 100ms accumulation
T200~T299: 10ms not accumulation
T300~T399: 10ms accumulation
T400~T499: 1ms not accumulation
T500~T599: 1ms accumulation
T TIMER
T600~T639: 1ms precise time
640
C0~C299: 16 bits forward counter
C300~C599: 32 bits forward/backward counter
C600~C619: single-phase HSC
C620~C629: double-phase HSC
C COUNTER
C630~C639: AB phase HSC
640
D0~D3999
【D4000~D7999】※4
8000 D
DATA
REGISTER For Special Usage
※5D8000~D9023 1024
FD FlashROM FD0~FD5119 5120
XC5 Series
REGISTER※6 For Special Usage
※5FD8000~FD9023 1024
ED※7
EXPANSION’S
INTERNAL
REGISTER
ED0~ED36863 36864
I/O range Points Mnemonic Name
24/32 I/O 48 I/O 24/32 I/O 48 I/O
Input Points X0~X15
X0~X21 X0~X33 14/18 28
I/O Points※1
Output Points Y0~Y11
Y0~Y15 Y0~Y23 10/14 20
X※2 Internal Relay X0~X1037 544
Y※3 Internal Relay Y0~Y1037 544
M0~M2999
【M3000~M7999】※4
8000 M Internal Relay
For Special Usage※5M8000~M8767 768
S Flow S0~S511
【S512~S1023】※4
1024
T0~T99: 100ms not accumulation
T100~T199: 100ms accumulation
T200~T299: 10ms not accumulation
T300~T399: 10ms accumulation
T400~T499: 1ms not accumulation
T500~T599: 1ms accumulation
T TIMER
T600~T639: 1ms precise time
640
C0~C299: 16 bits forward counter
C300~C599: 32 bits forward/backward
counter
C600~C619: single-phase HSC
C620~C629: double-phase HSC
C COUNTER
C630~C639: AB phase HSC
640
D0~D2999
【D4000~D4999】※4
4000 D
DATA
REGISTER For Special Usage
※5D8000~D9023 1024
FD FlashROM FD0~FD63 64
XCM Series
For Special Usage※5FD8000~FD8349 REGISTER
※6
For Special Usage※5FD8890~FD8999
460
ED※7
EXPANSION’S
INTERNAL
REGISTER
ED0~ED36863 36864
※1: I/O points, means the terminal number that users can use to wire the input, output
※2: X, means the internal input relay, the X beyond Input points can be used as middle relay;
※3: Y, means the internal output relay, the Y beyond Output points can be used as middle relay;
※4: The memory zone in【 】 is power off retentive zone, soft components D、M、S、T、C can change the
retentive area via setting. Please refer to 2-3-2 for details;
※5: for special use, means the special registers occupied by the system, can’t be used for other purpose. Please
refer to Appendix 1.
※6: FlashROM registers needn’t set the power off retentive zone, when power is off (no battery), the data will not
lose
※7: Expansion’s internal register ED, require PLC hardware V3.0 or above
※8: Input coils、output relays are in octal form, the other registers are in decimal form;
※9: The I/O that are not wired with external device can be used as fast internal relays;
※10: for the soft components of expansion devices, please refer to relate manuals;
2-3-2.Power Off Retentive Zone
The power off retentive area of XC series PLC are set as below, this area can be set by user again;
Soft
components
SET
AREA FUNCTION
System’s
default
value
Retentive
Zone
D FD8202 Start tag of D power off retentive zone 100 D100~D149
M FD8203 Start tag of M power off retentive
zone 200 M200~M319
T FD8204 Start tag of T power off retentive zone 640 Not set
C FD8205 Start tag of C power off retentive zone 320 C320~C631
XC1
Series
S FD8206 Start tag of S power off retentive zone 512 S0~S31
D FD8202 Start tag of D power off retentive zone 4000 D4000~D4999
M FD8203 Start tag of M power off retentive
zone 3000 M3000~M7999
T FD8204 Start tag of T power off retentive zone 640 Not set
C FD8205 Start tag of C power off retentive zone 320 C320~C639
XC2
Series
S FD8206 Start tag of S power off retentive zone 512 S512~S1023
D FD8202 Start tag of D power off retentive zone 4000 D4000~D7999
M FD8203 Start tag of M power off retentive
zone 3000 M3000~M7999
T FD8204 Start tag of T power off retentive zone 640 Not set
C FD8205 Start tag of C power off retentive zone 320 C320~C639
S FD8206 Start tag of S power off retentive zone 512 S512~S1023
XC3
Series
ED FD8207 Start tag of ED power off retentive
zone 0 ED0~ED16383
D FD8202 Start tag of D power off retentive zone 4000 D4000~D7999
M FD8203 Start tag of M power off retentive
zone 4000 M4000~M7999
T FD8204 Start tag of T power off retentive zone 640 Not set
C FD8205 Start tag of C power off retentive zone 320 C320~C639
S FD8206 Start tag of S power off retentive zone 512 S512~S1023
XC5
Series
ED FD8207 Start tag of ED power off retentive
zone 0 ED0~ED36863
D FD8202 Start tag of D power off retentive zone 4000 D4000~D4999
M FD8203 Start tag of M power off retentive
zone 3000 M3000~M7999
T FD8204 Start tag of T power off retentive zone 640 Not set
XCM
Series
C FD8205 Start tag of C power off retentive zone 320 C320~C639
S FD8206 Start tag of S power off retentive zone 512 S512~S1023
ED FD8207 Start tag of ED power off retentive
zone 0 ED0~ED36863
For timer T, we can set not only retentive zone, but also set certain timer’s retentive zone
Soft
Components
Set area Function Retentive Zone
FD8323 Set the start tag of 100ms not accumulation timer’s
retentive zone
The set value ~T99
FD8324 Set the start tag of 100ms accumulation timer’s retentive
zone
The set value~T199
FD8325 Set the start tag of 10ms not accumulation timer’s
retentive zone
The set value~T299
FD8326 Set the start tag of 10ms accumulation timer’s retentive
zone
The set value~T399
FD8327 Set the start tag of 1ms not accumulation timer’s
retentive zone
The set value~T499
FD8328 Set the start tag of 1ms accumulation timer’s retentive
zone
The set value~T599
T
FD8329 Set the start tag of 1ms precise timer’s retentive zone The set value~T639
For counter C, we can set not only retentive zone, but also set certain counter’s retentive
zone
Soft
Components
Set area Function Retentive Zone
FD8330 Set the start tag of 16 bits positive counter’s retentive
zone
The set value~C299
FD8331 Set the start tag of 32 bits positive/negative counter’s
retentive zone
The set value~C599
FD8332 Set the start tag of single phase HSC’s retentive zone The set value~C619
FD8333 Set the start tag of dual direction HSC’s retentive zone The set value~C629
C
FD8334 Set the start tag of AB phase HSC’s retentive zone The set value~C639
※1:if the whole power off retentive zone is smaller than the segment’s retentive area, then the segment’s area is
invalid. If the total counter’s set range is T200~T640, FD8324 value is 150, then the 100ms accumulate timer’s
retentive area T150~T199 is invalid.
2-4.Input/output relays(X、Y)
XC series PLC’s input/output are all in octal form, each series numbers are listed below:
Range Points
Series Name 10I/O 16 I/O 24 I/O 32 I/O 10 I/O
16
I/O 24 I/O 32 I/O
X X0~X4 X0~X7 X0~X13 X0~X17 5 8 12 16 XC1
Y Y0~Y4 Y0~Y7 Y0~Y13 Y0~Y17 5 8 12 16
Range Points
Series Name 14 I/O 16 I/O 24/32 I/O 48/60 I/O
14
I/O
16
I/O 24/32 I/O
48/60
I/O
X X0~X7 X0~X7 X0~X15
X0~X21
X0~X33
X0~X43 8 8 14/18 28/36
XC2
Y Y0~Y5 Y0~Y7 Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 6 8 10/14 20/24
Range Points
Series Name 14 I/O 24/32 I/O 48/60 I/O 14 I/O 24/32 I/O
48/60
I/O
X X0~X7 X0~X15
X0~X21
X0~X33
X0~X43 8 14/18 28/36
XC3
Y Y0~Y5 Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 6 10/14 20/24
Range Points Series Name
24/32 I/O 48/60 I/O 24/32 I/O 48/60 I/O
X X0~X15
X0~X21
X0~X33
X0~X43 14/18 28/36
XC5
Y Y0~Y11
Y0~Y15
Y0~Y23
Y0~Y27 10/14 20/24
Range Points Series Name
24 I/O 32 I/O 48 I/O 24 I/O 32 I/O 48 I/O
X X0~X15 X0~X21 X0~X33 14 18 28 XCM
Y Y0~Y11 Y0~Y15 Y0~Y23 10 14 20
Number List
Input Relay X
l PLC’s input terminals are used to accept the external signal input, while the input relays are a
type of optical relays to connect PLC inside and input terminals;
l The input relays have countless normally ON/OFF contactors, they can be used freely;
l The input relays which are not connected with external devices can be used as fast internal
relays;
Output Relay Y
l PLC’s output terminals can be used to send signals to external loads. Inside PLC, output
relay’s external output contactors (including relay contactors, transistor’s contactors) connect
with output terminals.
l The output relays have countless normally ON/OFF contactors, they can be used freely;
l The output relays which are not connected with external devices can be used as fast internal
relays;
Function
Execution Order
XC series PLC
CPU unit
Ex
ternal Sig
nal In
pu
t
Inp
ut T
ermin
al X
Ou
tpu
t Term
inal Y
Ex
ternal Sig
nal O
utp
ut
XC series PLC
CPU unit
Program
Dispose Area
External S
ignal Input
Input Term
inal X
Input Image A
rea
Output Im
age Area
Output T
erminal Y
External S
ignal Output
l Input Disposal
Ø Before PLC executing the program, read every input terminal’s ON/OFF status of PLC
to the image area.
Ø In the process of executing the program, even the input changed, the content in the input
image area will not change. However, in the input disposal of next scan cycle, read out
the change.
l Output Disposal
Ø Once finish executing all the instructions, transfer the ON/OFF status of output Y image
area to the output lock memory area. This will be the actual output of the PLC.
Ø The contacts used for the PLC’s external output will act according to the device’s
response delay time.
2-5.Auxiliary Relay (M)
The auxiliary relays M in XC series PLC are all in decimal form, please refer the details from
tables below:
RANGE
SERIES NAME FOR COMMON
USE
FOR POWER-OFF
RETENTIVE USE FOR SPECIAL USE
M8000~M8079
M8120~M8139
M8170~M8172
M8238~M8242
XC1 M M000~M199 M200~M319
M8350~M8370
RANGE
SERIES NAME FOR COMMON
USE
FOR POWER-OFF
RETENTIVE USE FOR SPECIAL USE
XC2 M M000~M2999 M3000~M7999 M8000~M8767
RANGE
SERIES NAME FOR COMMON
USE
FOR POWER-OFF
RETENTIVE USE FOR SPECIAL USE
XC3 M M000~M2999 M3000~M7999 M8000~M8767
SERIES NAME RANGE
Number List
FOR COMMON
USE
FOR POWER-OFF
RETENTIVE USE FOR SPECIAL USE
XC5 M M000~M3999 M4000~M7999 M8000~M8767
RANGE
SERIES NAME FOR COMMON
USE
FOR POWER-OFF
RETENTIVE USE FOR SPECIAL USE
XCM M M000~M2999 M3000~M7999 M8000~M8767
In PLC, auxiliary relays M are used frequently. This type of relay’s coil is same with the output
relay. They are driven by soft components in PLC;
auxiliary relays M have countless normally ON/OFF contactors. They can be used freely, but this
type of contactors can’t drive the external loads.
l For common use
Ø This type of auxiliary relays can be used only as normal auxiliary relays. I.e. if power
supply suddenly stop during the running, the relays will disconnect.
Ø Common usage relays can’t be used for power off retentive, but the zone can be
modified;
l For Power Off Retentive Use
Ø The auxiliary relays for power off retentive usage, even the PLC is OFF, they can keep
the ON/OFF status before power OFF.
Ø Power off retentive zone can be modified by the user;
Ø Power off retentive relays are usually used to memory the status before stop the power,
then when power the PLC on again, the status can run again;
l For Special Usage
Ø Special relays refer some relays which are defined with special meanings or functions,
start from M8000.
Ø There are two types of usages for special relays, one type is used to drive the coil, the
other type is used to the specified execution;
E.g.: M8002 is the initial pulse, activates only at the moment of start
M8033 is “all output disabled”
Ø Special auxiliary relays can’t be used as normal relay M;
Function
2-6.Status Relay (S)
RANGE SERIES NAME
FOR COMMON USE FOR POWER-OFF RETENTIVE USE
XC1 S S000~S031 -
RANGE SERIES NAME
FOR COMMON USE FOR POWER-OFF RETENTIVE USE
XC2 S S000~S511 S512~S1023
RANGE SERIES NAME
FOR COMMON USE FOR POWER-OFF RETENTIVE USE
XC3 S S000~S511 S512~S1023
RANGE SERIES NAME
FOR COMMON USE FOR POWER-OFF RETENTIVE USE
XC5 S S000~S511 S512~S1023
RANGE SERIES NAME
FOR COMMON USE FOR POWER-OFF RETENTIVE USE
XCM S S000~S511 S512~S1023
l For common use
After shut off the PLC power, this type of relays will be OFF status;
l For Power Off Retentive Use
Ø The status relays for power off retentive usage, even the PLC is OFF, they can keep the
ON/OFF status before power OFF.
Ø Power off retentive zone can be modified by the user;
l The status relays also have countless “normally ON/OFF” contactors. So users can use them
freely in the program;
Address List
Function
XC series PLC’s status relays S are addressed in form of decimal; each
subfamily’s ID are listed below:
Status relays are very import in ladder program; usually use them with
instruction “STL”. In the form on flow, this can make the program’s structure
much clear and easy to modify;
2-7.Timer (T)
RANGE SERIES NAME
FOR COMMON USE POINTS
T0~T23: 100ms not accumulation
T100~T115: 100ms accumulation
T200~T223: 10ms not accumulation
T300~T307: 10ms accumulation
T400~T403: 1ms not accumulation
XC1 T
T500~T503: 1ms accumulation
80
T0~T99: 100ms not accumulation
T100~T199: 100ms accumulation
T200~T299: 10ms not accumulation
T300~T399: 10ms accumulation
T400~T499: 1ms not accumulation
T500~T599: 1ms accumulation
XC2
XC3
XC5
XCM
T
T600~T639: 1ms with precise time
640
We use OUT or TMR instruction to time for the normal timers. We use constant (K) to set the
value, or use data register (D) to indirect point the set value;
Address List
Function
Norm
al Typ
e
l If X0 is ON, then T200 accumulate
10ms clock pulse based on the current
value; when the accumulation value
reaches the set value K200, the timer’s
output contact activates. I.e. the output
contact activates 2s later. If X0 breaks,
the timer resets, the output contact
resets;
XC series PLC’s timers T are addressed in form of decimal; each
subfamily’s ID are listed below:
The timers accumulate the 1ms, 10ms, 10ms clock pulse, the output contactor
activates when the accumulation reaches the set value;
l Both OUT and TMR can realize the
time function. But if use OUT, the start
time is 0; if use TMR, the start time is 1
scan cycle
T10 K100X0
MOV K200 D5
T10 D5
X0
X1
Y0
T2
X0
Y0 X0
X0
Y0 T2K200
T2
Accu
mu
lation T
yp
e
If X001 is ON, then T300 accumulate
10ms clock pulse based on the current
value; when the accumulation value
reaches the set value K2000, the timer’s
output contact activates. I.e. the output
contact activates 2s later.
Even if X0 breaks, the timer will
continue to accumulation on re-starting.
The accumulation time is 20ms;
If X002 is ON, the timer will be reset,
the output contacts reset;
T10 is the timer with 100ms as the
unit. Specify 100 as the constant, then
0.1s*100=10s timer works;
Write the value of indirect
data register in the
program or input by value
switch.
If set as the retentive
register, make sure the
battery voltage is enough,
or the value will be
unstable.
《output delay OFF timer》
《Constant (K)》
《Register (D)》
When X000 is ON, output Y000;
When X000 from ON to OFF, delay T2(20s), then output Y000 is OFF.
Timer T0~T599 is 16 bits linear increment mode (0~K32767), when the timer’s
value reaches the max value K32767, it stops timing. The timer’s status keeps
still;
Specify the set
value
Timer Value
Action
Example
T1
T2
Y0
X0
T1
T2
X0
Y0
T1 T2 T1K10
K20
2-8.Counter ( C )
RANGE SERIES NAME
FOR COMMON USE POINTS
C0~C23: 16 bits forward counter
C300~C315: 32 bits forward/backward counter
C600~C603: single-phase HSC
C620~C621
XC1 C
C630~C631
48
C0~C299: 16 bits forward counter
C300~C599: 32 bits forward/backward counter
C600~C619: single-phase HSC
C620~C629: double-phase HSC
XC2
XC3
XC5
XCM
C
C630~C639: AB phase HSC
640
All the counters number meaning:
※1: Please see chapter 5 for high speed counter.
《glitter》
When X000 is ON, Y000 starts to glitter.
T1 controls the OFF time of Y000, T2 controls the ON time of Y000.
Number list
TYPE DESCRIPTION
16 bits forward counter C0~C299
32 bits forward/backward
counter
C300~C599 (C300,C302...C598)(each occupies 2 counters
number) the number should be even
HSC (High Speed
Counter)
C600~C634(C600,C602...C634)( (each occupies 2 counters
number) the number should be even
Counter
characteristics
XC series PLC counters’ number are all decimal, please see the following
table for all the counter numbers.
The characteristics of 16 bits and 32 bits counters:
Items 16 bits counter 32 bits counter
Count direction Positive Positive/negative
The set value 1~32,767 -2,147,483,648~+2,147,483,647
The assigned set
value Constant K or data register
Same as the left, but data register must be in a
couple
Changing of the
current value Change after positive count Change after positive count (Loop counter)
Output contact Hold the action after
positive count
Hold the action after positive count, reset if
negative count
Reset activates When executing RST command, counter’s current value is 0, output contacts
recover
The current value
register 16 bits 32 bits
RST C0X0
C0 K10
Y0
X1
C0
Function
16 bits binary increment counters, the valid value is K1~K32,767 (decimal type
constant). The set value K0 and K1 has the same meaning. i.e. the output contact
works on the first count starts
If cut the PLC power supply, the normal
counter value become zero, the retentive
counter can store the value, it can
accumulate the value of last time.
l When X001 is ON once, the counter increases 1. When the counter value is 10,
its output is activated. After, when the X001 is ON again, the counter continues
increasing 1.
l If X000 is ON, reset counter, the counter value becomes zero.
l It also can set the counter value in D register. For example, D10=123 is the same
as K123.
16 bits counter normal/retentive type
The assignment of common use counters and power off retentive counters,
can me changed via FD parameters from peripheral devices;
RST C300X3
C300 K10
Y1
X4
C300
M8238X2
C0X001
K100
C300X001
K43,100
32 bits increase/decrease count range is +2147483648 ~ - 2147483647. Set the
increase or decrease count mode in M8238.
l If M8238=1, it is decrease mode;
M8238=0, it is increase mode.
l Set the count value in K or D, if set in D0
register, D0 and D1 will be seemed as one
32bits value.
l X004 is ON, C300 starts to count.
32
bits co
un
ter norm
al/retentiv
e type
l If X003 is ON, reset the counter and C300 output.
l If use retentive counter, the count value will be stored in PLC.
l 32 bits counter can be used as 32 bits register.
u 16 bits counter
《set as constant K》 《set in D register》
u 32 bits counter
《set as constant K》 《set in D register》
Set the count
value
MOV K100 D5
C0 D5
X000
X001
DMOV K43100 D0
C300 D0(D1)
X000
X001
It includes 16 bits and 32 bits count value.
C0~C299 are 16 bits linear increase counter (0~32767), when the counter value reaches
32767, it will stop count and keep the state.
C300~C599 are 32 bits linear increase/decrease counter (-2147483648~+2147483647), when
the counter value reaches 2147483647, it will become -2147483648, when the counter value
reaches -2147483648, it will become 2147483647, the counter state will change as the count
value.
2-9.Data register ( D)
RANGE
SERIES NAME FOR COMMON
USE
FOR POWER OFF
RETENTIVE USE FOR SPECIAL USE
D8000~D8029
D8060~D8079
D8120~D8179
D8240~D8249
D8306~D8313
XC1 D D0~D99 D100~D149
D8460~D8469
138
D8000~D8511 XC2 D D0~D999 D4000~D4999
D8630~D8729 612
XC3
XC5 D D0~D3999 D4000~D7999 D8000~D9023 1024
XCM D D0~D2999 D3000~D4999 D8000~D9023 1024
Count value
Address list
Structure
XC series PLC data register D address is shown as below:
Data register is soft element which used to store data, it includes 16 bits and
32 bits. ( 32 bits contains two registers, the highest bit is sign bit )
l Normal type
Ø When write a new value in the register, the former value will be covered.
Ø When PLC from RUN to STOP or STOP to RUN, the value in the register will be
cleared.
l Retentive type
Sign bit
b 0
D 0 ( 16 bits )
0 0 0 0 1 0 1 0 0 1 1 0 0 0 0 0 b 15
0 : positive 1 : negative
Sign bit
b 0
D 1 ( 16 bits )
0 0 0 0 1 01 00 1 1 0 0 0 0 0
b 31
0 : positive 1 : negative
0 0 0 0 1 0 1 0 0 1 1 0 0 0 0 0
D 0 (16 bits ) Low
bit
High
bit
16
bits
16 bits register range is -32,768 ~ +32,767
Use the applied instruction to read and write the register data. Or use other
devices such as HMI.
32 bits
32 bits value is consisted of two registers. The range is -2147483648 ~ 2147483647.
When appoint the 32bits register, if set D0, the PLC will connect the next register D1 as
the high bits. Generally, we often appoint even address register.
Function
Ø When PLC from RUN to STOP or power off, the value in the register will be retained.
Ø The retentive register range can be set by user.
l Special type
Ø Special register is used to set special data, or occupied by the system.
Ø Some special registers are initialized when PLC is power on.
Ø Please refer to the appendix for the special register address and function.
l Used as offset (indirect appoint)
Ø Data register can be used as offset of soft element.
Ø Format : Dn[Dm]、Xn[Dm]、Yn[Dm]、Mn[Dm].
Ø Word offset: DXn[Dm] means DX[n+Dm].
Ø The offset value only can be set as D register.
MOV D10[D0] D100M8000
M2
Y0[D0]
MOV K5 D0
M8002MOV K0 D0
When D0=0, D100=D10, Y0 is ON;
When M2 is from OFF→ON, D0=5, D100=D15, Y5 is ON.
D10[D0]=D[10+D0], Y0[D0]=Y[0+D0].
l Data storage
MOV K100 D0M0
M1DMOV K41100 D10
l Data transfer
MOV D0 D10M0
l Read the timer and counter
MOV C10 D0M0
Example
When M0 is ON, write 100 into D0.(16 bits value)
When M1 is ON, write 41100 into D11,D10 (32bits value)
When M0 is ON, transfer the value of D10 to D0
When M0 is ON, move the value of C10 to D0.
Data register D can deal with many kinds of data and realize various controls.
l As the set value of timer and counter
C300 D1
X0
X1
T10 D0
↑
2-10.Constant
l DEC: DECIMAL NUMBER
Ø The preset number of counter and timer ( constant K)
Ø The number of Auxiliary relay M, timer T, counter C, state S.
Ø Set as the operand value and action of applied instruction (constant K)
l HEX: HEXADECIMAL NUMBER
Ø Set as the operand value and action of applied instruction (constant K)
l BIN: BINARY NUMBER
Ø Inside the PLC, all the numbers will be processed by binary. But when monitoring on
the device, all the binary will be transformed into HEX or DEC.
l OCT: OCTAL NUMBER
Ø XC series PLC I/O relays are addressed in OCT. Such as [0-7, 10-17,….70-77,100-107].
When X0 is ON, T10 starts to work, the time is set in D0.
When X1 is ON once, C300 increase 1, when C300 value=D1,
C300 coil outputs.
Data process XC series PLC use the following 5 number systems.
l BCD: BINARY CODE DECIMAL
Ø BCD uses 4 bits binary number to display decimal number 0-9. BCD can be used in 7
segments LED and BCD output digital switch
l Other numbers ( float number)
XC series PLC can calculate high precision float numbers. It is calculated by binary
numbers, and display by decimal numbers.
l Constant K
K is used to display decimal numbers. K10 means decimal number 10. It is used to set timer and
counter value, operand value of applied instruction.
l Constant H
H is used to display hex numbers. H10 means hex number 10. It is used to set operand value of
applied instruction.
2-11.PROGRAM PRINCIPLE
l Tag P、I
Tag P、I are used in branch division and interruption.
Tag for branch (P) is used in condition jump or subroutine’s jump target;
Tag for interruption (I) is used to specify the e input interruption, time interruption;
The tags P、I are both in decimal form, each coding principle is listed below:
SERIES NAME RANGE
XC1、XC2、XC3、XC5、XCM P P0~P9999
RANGE
FOR EXTERNAL
INTERRUPTION SERIES NAME
Input
terminals
Rising edge
interruption
Falling
edge
interruption
For time interruption
X2 I0000 I0001
X5 I0100 I0101 XC2 I
X10 I0200 I0201
There are 10 channels time interruption,
the represent method is: I40**~I49**.
(“**” represents interruption time, the unit
is mm)
Display PLC program should use K, H to process values. K means decimal
numbers, H means hex numbers. Please note the PLC input/output relay use
octal address.
RANGE
FOR EXTERNAL
INTERRUPTION SERIES NAME I/O
Input
terminals
Rising
edge
interruption
Falling
edge
interruption
For time interruption
14 X7 I0000 I0001
X2 I0000 I0001
X5 I0100 I0101 24
32 X10 I0200 I0201
X10 I0000 I0001
X7 I0100 I0101
XC3 I
19
48
60 X6 I0200 I0201
There are 10 channels time interruption,
the represent method is: I40**~I49**.
(“**” represents interruption time, the
unit is mm)
RANGE
FOR EXTERNAL
INTERRUPTION SERIES NAME I/O
Input
terminals
Rising
edge
interruption
Falling
edge
interruption
For time interruption
X2 I0000 I0001
X5 I0100 I0101
X10 I0200 I0201
X11 I0300 I0301
24
32
X12 I0400 I0401
X2 I0000 I0001
X5 I0100 I0101
XC5 I
48
60 X10 I0200 I0201
There are 10 channels time interruption,
the represent method is: I40**~I49**.
(“**” represents interruption time, the
unit is mm)
RANGE
FOR EXTERNAL
INTERRUPTION SERIES NAME I/O
Input
terminals
Rising
edge
interruption
Falling
edge
interruption
For time interruption
X2 I0000 I0001 XCM I 24
32 X5 I0100 I0101
There are 10 channels time interruption,
the represent method is: I40**~I49**.
X10 I0200 I0201
X11 I0300 I0301
X12 I0400 I0401
(“**” represents interruption time, the
unit is mm)
Tag P is usually used in flow, it is used with CJ (condition jump)、CALL (subroutine
call)etc.
l Condition Jump CJ
X0
CJ
X1
X2
P1
T0RST
Y0
P1
l Call the subroutine (CALL)
CALLX0
FEND
SRET
P10
P10
Tag I is usually used in interruption, including external interruption, time interruption etc.
use with IRET (interruption return)、EI (enable interruption)、DI (disable interruption);
l External interruption
Ø Accept the input signal from the special input terminals, not effected by the scan
cycle. Activate the input signal, execute the interruption subroutine.
Ø With external interruption, PLC can dispose the signal shorter than scan cycle;
So it can be used as essential priority disposal in sequence control, or used in
short time pulse control.
l Time interruption
Ø Execute the interruption subroutine at each specified interruption loop tine. Use
Tag P
If coil X0 gets ON, jump to the step behind
tag P1;
If the coil X0 is not ON, do not execute
jump action, but run with the original
program;
If X0 gets ON, jump to the
subroutine from the main program;
If the coil is not ON, run with the
original program;
After executing the subroutine,
return to the main program; T
ag I
Main program
Subroutine
this interruption in the control which requires it to be different with PLC’s
operation cycle;
l Action order of input/output relays and response delay
Ø Input disposal
Before PLC executing the program, read all the input terminal’s ON/OFF status of PLC
to the image area. In the process of executing the program, even the input changed, the
content in the input image area will not change. However, in the input disposal of next
scan cycle, read out the change.
Ø Output disposal
Once finish executing all the instructions, transfer the ON/OFF status of output Y image
area to the output lock memory area. This will be the actual output of the PLC. The
contacts used for the PLC’s exterior output will act according to the device’s response
delay time.
When use this input/output format in a batch, the drive time and operation cycle of input filter
and output device will also appear response delay.
l Not accept narrow input pulse signal
PLC’s input ON/OFF time should be longer than its loop time. If consider input filter’s response
delay 10ms, loop time is 10ms,then ON/OFF time needs 20 ms separately. So, up to 1,
000/(20+20)=25Hz input pulse can’t be disposed. But, this condition could be improved when use
PLC’s special function and applied instructions.
l Dual output(Dual coils)action
Y3
Y4
Y3
X1
Y3
X2
As shown in the left map, please consider
the things of using the same coil Y003 at
many positions:
E.g. X001=ON,X002=OFF
At first, X001 is ON, its image area is ON,
output Y004 is also ON.
But, as input X002 is OFF, the image area
of Y003 is OFF.
So, the actual output is: Y003=OFF,
Y004= ON.
When executing dual output (use dual coil),
the back side act in prior.
3 Basic Program Instructions
In this chapter, we tell the basic instructions and their functions.
3-1.Basic Instructions List
3-2.[LD], [LDI], [OUT]
3-3.[AND], [ANI]
3-4.[OR], [ORI]
3-5.[LDP], [LDF], [ANDP], [ANDF], [ORP], [ORF]
3-6.[LDD], [LDDI]
3-7.[ORB]
3-8.[ANB]
3-9.[MCS], [MCR]
3-10.[ALT]
3-11.[PLS], [PLF]
3-12.[SET], [RST]
3-13.[OUT], [RST] (Aim at counter device)
3-14.[NOP], [END]
3-15.[GROUP], [GROUPE]
3-16.Items to be attended when programming
3-1.Basic Instructions List
All XC1、XC2、XC3、XC5、XCM series support the below instructions:
Mnemonic Function Format and Device Chapter
LD
(LoaD)
Initial logical operation
contact type NO (normally
open)
X、Y、M、S、T、C、Dn.m、FDn.m
3-2
LDD
(LoaD
Directly)
Read the status from the
contact directly
X0
D
X
3-6
LDI
(LoaD
Inverse)
Initial logical operation
contact type NC (normally
closed)
X、Y、M、S、T、C、Dn.m、FDn.m
3-2
LDDI Read the normally closed
contact directly
X0
D
X
3-6
LDP
(LoaD
Pulse)
Initial logical
operation-Rising edge
pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
LDF
(LoaD
Falling
Pulse)
Initial logical
operation-Falling /trailing
edge pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
AND
(AND)
Serial connection of NO
(normally open) contacts
M0
X、Y、M、S、T、C、Dn.m、FDn.m
3-3
ANDD Read the status from the
contact directly
X0
D
X
3-6
ANI
(AND
Inverse)
Serial connection of NC
(normally closed) contacts
M0
X、Y、M、S、T、C、Dn.m、FDn.m
3-3
ANDDI Read the normally closed
contact directly
X0
D
X
3-6
ANDP
(AND
Pulse)
Serial connection of rising
edge pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
ANDF
(AND
Falling
pulse)
Serial connection of
falling/trailing edge pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
OR
(OR)
Parallel connection of NO
(normally open) contacts
X、Y、M、S、T、C、Dn.m、FDn.m
3-4
ORD Read the status from the
contact directly X0
D
X
3-6
ORI
(OR
Inverse)
Parallel connection of NC
(normally closed) contacts
X、Y、M、S、T、C、Dn.m、FDn.m
3-4
ORDI Read the normally closed
contact directly X0
D
X
3-6
ORP
(OR
Pulse)
Parallel connection of
rising edge pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
ORF
(OR
Falling
pulse)
Parallel connection of
falling/trailing edge pulse
X、Y、M、S、T、C、Dn.m、FDn.m
3-5
ANB
(ANd
Block)
Serial connection of
multiply parallel circuits
None
3-8
ORB
(OR
Block)
Parallel connection of
multiply parallel circuits
None
3-7
OUT
(OUT)
Final logic operation type
coil drive Y、M、S、T、C、Dn.m
3-2
OUTD Output to the contact
directly
Y0
D
Y
3-6
SET
(SET)
Set a bit device
permanently ON
Y、M、S、T、C、Dn.m
3-12
RST
(ReSeT)
Reset a bit device
permanently OFF
Y、M、S、T、C、Dn.m
3-12
PLS
(PuLSe)
Rising edge pulse
X、Y、M、S、T、C、Dn.m
3-11
PLF
(PuLse
Falling)
Falling/trailing edge pulse
X、Y、M、S、T、C、Dn.m
3-11
MCS
(New bus
line start)
Connect the public serial
contacts
Y0
None
3-9
MCR
(Bus line
return)
Clear the public serial
contacts
Y0
None
3-9
ALT
(Alternate
state)
The status of the assigned
device is inverted on every
operation of the instruction
M0ALT
X、Y、M、S、T、C、Dn.m
3-10
END
(END)
Force the current program
scan to end None
3-14
GROUP Group
None
3-15
GROUPE Group End
None
3-15
TMR Time
2-7
3-2.[LD] , [LDI] , [OUT]
Mnemonic Function Format and Operands
LD
(LoaD)
Initial logic operation
contact type NO
(Normally Open)
Operands: X、Y、M、S、T、C、
Dn.m、FDn.m
LDI
(LoaD Inverse)
Initial logic operation
contact type NC
(Normally Closed)
Devices:X、Y、M、S、T、C、Dn.m、
FDn.m
OUT
(OUT)
Final logic operation
type drive coil Operands: X、Y、M、S、T、C、
Dn.m
Timer, Counter Setting Range of constant K The actual setting value
1ms Timer 0.001~32.767 sec
10ms Timer 0.01~327.67 sec
100ms Timer
1~32,767
0.1~3276.7 sec
16 bits counter 1~32,767 Same as the left
l Connect the LD and LDI instructions directly to the left bus bar. Or use them
to define a new block of program when using ANB instruction.
l OUT instruction is the coil drive instruction for the output relays、auxiliary
relays、status、timers、counters. But this instruction can’t be used for the
input relays
l Can not sequentially use parallel OUT command for many times.
l For the timer’s time coil or counter’s count coil, after using OUT instruction,
set constant K is necessary.
l For the constant K’s setting range、actual timer constant、program’s step
relative to OUT instruction (include the setting value), See table below:
Mnemonic and Function
Statement
Y100
M1203
T 0
X0
Y 1
X1
T0
K19
3-3.[AND] , [ANI]
32 bits counter 1~2,147,483,647 Same as the left
Mnemonic Function Format and Operands
AND
(AND)
Serial connection of
NO (Normally
Open) contacts
M0
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ANI
(ANd
Inverse)
Serial connection of
NC (Normally
Closed) contacts
M0
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
LD X0
OUT Y100
LDI X1
OUT M1203
OUT T0 K19
LD T0
OUT Y1
Program
Statements
l Use the AND and the ANI instruction for serial connection of contacts. As
many contacts as required can be connected in series. They can be used for
many times.
l The output processing to a coil, through writing the initial OUT instruction is
called a “follow-on” output (For an example see the program below: OUT M2
and OUT Y003). Follow-on outputs are permitted repeatedly as long as the
output order is correct. There’s no limit for the serial connected contacts’ Nr.
and follow-on outputs’ number.
Mnemonic and Function
Y2
M2
Y3
X2 M1
X3Y2
T1
3-4.[OR] , [ORI]
Y6
M100
X5
X6
M11
Y6 M4 X7
M12
M13
Mnemonic Function Format and Operands
OR
(OR)
Parallel connection
of NO (Normally
Open) contacts
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ORI
(OR
Inverse)
Parallel connection
of NC (Normally
Closed) contacts
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
Program
LD X2
AND M1
OUT Y2
LD Y2
ANI X3
OUT M2
AND T1
OUT Y3
Mnemonic and Function
Statements
Program
LD X5
OR X6
OR M11
OUT Y6
LDI Y6
AND M4
OR M12
ANI X7
OR M13
OUT M100
l Use the OR and ORI instructions for parallel connection of contacts. To connect a block
that contains more than one contact connected in series to another circuit block in parallel,
use an ORB instruction, which will be described later;
l OR and ORI start from the instruction’s step, parallel connect with the LD and LDI
instruction’s step said before. There is no limit for the parallel connect times.
3-5.[LDP] , [LDF] , [ANDP] , [ANDF] , [ORP] , [ORF]
Mnemonic Function Format and Operands
LDP
(LoaD
Pulse)
Initial logical
operation-Rising edge
pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
LDF
(LoaD
Falling
pulse)
Initial logical operation
Falling/trailing edge pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ANDP
(AND
Pulse)
Serial connection of
Rising edge pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ANDF
(AND
Falling
pulse)
Serial connection of
Falling/trailing edge pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ORP
(OR
Pulse)
Parallel connection of
Rising edge pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
ORF
(OR
Falling
pulse)
Parallel connection of
Falling/trailing edge pulse
Operands: X、Y、M、S、T、C、Dn.m、FDn.m
The parallel connection with OR, ORI
instructions should connect with LD, LDI
instructions in principle. But behind the
ANB instruction, it’s still ok to add a LD
or LDI instruction.
Relationship with ANB
Mnemonic and Function
3-6.[LDD] , [LDDI] , [ANDD] , [ANDDI] , [ORD] , [ORDI],[OUTD]
Mnemonic Function Format and Operands
LDD Read the status from the
contact directly
X0
D
Devices: X
LDDI Read the normally closed
contact directly
X0
D
Devices: X
ANDD Read the status from the
contact directly
X0
D
Devices: X
ANDDI Read the normally
closed contact directly
X0
D
Devices: X
ORD Read the status from the
contact directly X0
D
l LDP、ANDP、ORP are active for one program scan after the associated devices switch from
OFF to ON.
l LDF、ANDF、ORF are active for one program scan after the associated devices switch from
ON to OFF.
M13
M15
X5
X6
M8000 X7
LDP X5
ORP X6
OUT M13
LD M8000
ANDP X7
OUT M15
Statements
Program
Mnemonic and Function
l The function of LDD、ANDD、ORD instructions are similar with LD、AND、OR; LDDI、
ANDDI、ORDI instructions are similar with LDI、ANDI、ORI; but if the operand is X, the
LDD、ANDD、ORD commands read the signal from the terminals directly, this is the only
difference.
l OUTD and OUT are output instructions. But if use OUTD, output immediately if the
condition comes true, needn't wait the next scan cycle.
M13X0
X1
X2D
D
DY0D
3-7.[ORB]
Mnemonic Function Format and Devices
ORB
(OR Block)
Parallel connection
of multiply parallel
circuits
Devices: none
Devices: X
ORDI Read the normally
closed contact directly X0
D
Devices: X
OUTD Output to the contact
directly
Y0
D
Devices: Y
LDD X0
LDDI X2
ORD X2
ANB
OUTD Y0
Program
Statements
Mnemonic and Function
l The serial connection with two or more contacts is called "serial block". If parallel connect
the serial block, use LD, LDI at the branch start place, use ORB at the stop place;
l As the ANB instruction,an ORB instruction is an independent instruction and is not
associated with any device number.
l There are no limitations to the number of parallel circuits when using an ORB instruction in
the sequential processing configuration.
Recommended good
programming method:
LD X0
AND X1
LD X2
AND X3
ORB
LD X4
AND X5
ORB
Non-preferred batch
programming
method:
LD X0
AND X1
LD X2
AND X3
LD X4
AND X5
ORB
ORB
Statements
Program
3-8.[ANB]
Mnemonic Function Format and Devices
ANB
(And
Block)
Serial
connection of
multiply
parallel circuits
Devices: none
Start of a branch
End of a parallel circuit block
Serial connect with the preceding circuit
l To declare the starting point of the circuit block, use a LD or LDI
instruction. After completing the parallel circuit block, connect it to the
preceding block in series using the ANB instruction.
l It is possible to use as many ANB instructions as necessary to connect a
number of parallel circuit blocks to the preceding block in series.
LD X0
OR X1
LD X2
AND X3
LDI X4
AND X5
ORB
OR X6
ANB
OR X7
OUT Y20
Statements
Program
Mnemonic and Function
3-9.[MCS] , [MCR]
Mnemonic Function Format and Devices
MCS
(Master
control)
Denotes the
start of a
master control
block
Y0
Devices:None
MCR
(Master
control
Reset)
Denotes the
end of a master
control block
Y0
Devices:None
X1 X2
M2
M3M1
Y0
Y1
Y2
l After the execution of an MCS instruction, the bus line(LD、LDI)shifts
to a point after the MCS instruction. An MCR instruction returns this to
the original bus line.
l MCS、MCR instructions should use in pair.
l The bus line could be used nesting. Between the matched MCS、MCR
instructions use matched MCS、MCR instructions. The nest level
increase with the using of MCS instruction. The max nest level is 10.
When executing MCR instruction, go back to the upper bus line.
l When use flow program, bus line management could only be used in the
same flow. When end some flow, it must go back to the main bus line.
LD X1
MCS
LD X2
OUT Y0
LD M1
MCS
LD M3
OUT Y1
LD M2
OUT Y2
MCR
MCR
Bus line starts
Bus line nest
Bus line back
Statements
Program
Mnemonic and Function
3-10.[ALT]
Mnemonic Function Format and Devices
ALT
(Alternate
status)
The status of the
assigned devices
inverted on every
operation of the
instruction
M0ALT
Devices: Y、M、S、T、C、Dn.m
M0ALT
M0Y0
M100
Y1M0
3-11.[PLS] , [PLF]
Mnemonic Function Format and Devices
PLS
(Pulse)
Rising edge
pulse
Devices: Y、M、S、T、C、Dn.m
PLF
(Pulse
Falling)
Falling/trailing
edge pulse
Devices: Y、M、S、T、C、Dn.m
The status of the destination device is alternated on every operation of the
ALT instruction.
LDP M100
ALT M0
LD M0
OUT Y0
LDI M0
OUT Y1
Statements
Program
Mnemonic and Function
Mnemonic and Function
X0PLS M0
M0SET Y0
X1PLF M1
M1RST Y0
3-12.[SET] , [RST]
Mnemonic Function Format and Devices
SET(Set) Set a bit device
permanently
ON
Devices: Y、M、S、T、C、Dn.m
RST(Reset) Reset a bit
device
permanently
OFF
Devices: Y、M、S、T、C、Dn.m
l When a PLS instruction is executed, object devices Y and M operate
for one operation cycle after the drive input signal has turned ON.
l When a PLF instruction is executed, object devices Y and M operate
for one operation cycle after the drive input signal has turned OFF.
LD X0
PLS M0
LD M0
SET Y0
----------------------
LD X1
PLF M1
LD M1
RST Y0
Statements
Program
Mnemonic and Function
X10SET Y0
X11RST Y0
X12SET M50
X13RST M50
X14SET S0
X15RST S0
X10T250
K10
X17RST T250
X10
X11
Y0
LD X10
SET Y0
LD X11
RST Y0
LD X12
SET M50
LD X13
RST M50
LD X14
SET S0
LD X15
RST S0
LD X10
OUT T250 K10
LD X17
RST T250
l Turning ON X010 causes Y000 to turn ON. Y000 remains ON even after
X010 turns OFF. Turning ON X011 causes Y000 to turn OFF. Y000
remains OFF even after X011 turns OFF. It’s the same with M、S.
l SET and RST instructions can be used for the same device as many times
as necessary. However, the last instruction activated determines the
current status.
l Besides, it’s also possible to use RST instruction to reset the current
contents of timer, counter and contacts.
l When use SET, RST commands, avoid to use the same ID with OUT
command;
Statements
Program
3-13.【OUT】,【RST】for the counters
Mnemonic Function Format and Devices
OUT Final logic
operation type
coil drive
Device:K、D
RST Reset a bit device
permanently OFF
Device:C
C0 carries on increase count for the
OFF→ON of X011. When reach the
set value K10, output contact C0
activates. Afterwards, even X011 turns
from OFF to ON, counter’s current
value will not change, output contact
keep on activating.
To clear this, let X010 be the activate
status and reset the output contact. It’s
necessary to assign constant K or
indirect data register’s ID behind OUT
instruction.
l In the preceding example, when M0 is ON, carry on positive count with OFF→ON
of X0.
l Counter’s current value increase, when reach the set value (K or D), the output
contact is reset.
l When M1 is ON, counter’s C600 output contact is reset, counter’s current value turns
to be 0.
Programming of
interior counter
Programmi
ng of high
speed
Mnemonic and Function
Counter used for power cut retentive.
Even when power is cut, hold the current
value and output contact’s action status
and reset status.
3-14. [END]
Mnemonic Function Format and Devices:None
END
(END)
Force the
current
program scan
to end
Devices: None
When executing END instruction, refresh monitor timer. (Check if scan cycle is a long timer.)
PLC repeatedly carry on input disposal, program
executing and output disposal. If write END
instruction at the end of the program, then the
instructions behind END instruction won’t be
executed. If there’s no END instruction in the
program, the PLC executes the end step and then
repeat executing the program from step 0.
When debug, insert END in each program
segment to check out each program’s action.
Then, after confirm the correction of preceding
block’s action, delete END instruction.
Besides, the first execution of RUN begins with
END instruction.
Statements
Mnemonic and Function
3-15.[GROUP] , [GROUPE]
Mnemonic Function Format and Device
GROUP GROUP
Devices: None
GROUPE GROUP END
Devices: None
l GROUP and GROUPE should used in pairs.
l GROUP and GROUPE don't have practical meaning, they are used to optimize the program
structure. So, add or delete these instructions doesn't effect the program's running;
l The using method of GROUP and GROUPE is similar with flow instructions; enter GROUP
instruction at the beginning of group part; enter GROUPE instruction at the end of group
part.
Generally, GROUP and GROUPE
instruction can be programmed according to
the group's function. Meantime, the
programmed instructions can be FOLDED or
UNFOLDED. To a redundant project, these
two instructions are quite useful.
Statements
Mnemonic and Function
3-16.Items To Note When Programming
1、Contacts’ structure and step number
Even in the sequencial control circuit with the same action, it’s also available to
simple the program and save program’s steps according to the contacts’ structure.
General program principle is:a)write the circuit with many serial contacts on the top;
b)write the circuit with many parallel contacts in the left.
2、Program’s executing sequence
Handle the sequencial control program by【From top to bottom】and【From left to
right】
Sequencial control instructions also encode following this flow.
3、Dual output dual coil’s activation and the solution
l If carry on coil’s dual output (dual coil) in the sequencial control program, then
the backward action is prior.
l Dual output (dual coil) doesn’t go against the input rule at the program side. But
as the preceding action is very complicate, please modify the program as in the
following example.
Y0
Y0
X0 X2
X3 X4
Y0X0 X2
X3 X4
M0
M1
X0 X2
X3 X4
Y0M0
M1
There are other methods. E.g. jump instructions or step ladder. However, when use
step ladder, if the main program’s output coil is programmed, then the disposal
method is the same with dual coil, please note this.
4 applied instructions
4 Applied Instructions In this chapter, we describe applied instruction’s function of XC series PLC.
4-1.Table of Applied Instructions
4-2.Reading Method of Applied Instructions
4-3.Flow Instructions
4-4.Contactors Compare Instructions
4-5.Move Instructions
4-6.Arithmetic and Logic Operation Instructions
4-7.Loop and Shift Instructions
4-8.Data Convert
4-9.Floating Operation
4-10.Clock Operation
4 applied instructions
4 applied instructions
4-1.Applied Instruction List
Mnemonic Function Ladder chart Chapter
Program Flow
CJ Condition jump CJ Pn
4-3-1
CALL Call subroutine CALL Pn
4-3-2
SRET Subroutine return SRET
4-3-2
STL Flow start STL Sn
4-3-3
STLE Flow end S 1 ·
4-3-3
SET Open the assigned flow, close
the current flow S ·
4-3-3
ST Open the assigned flow, not
close the current flow D ·
4-3-3
FOR Start a FOR-NEXT loop D ·
4-3-4
NEXT End of a FOR-NEXT loop D ·
4-3-4
FEND Main program END D ·
4-3-5
END Program END
4-3-5
Data Compare
LD= LD activates if (S1) = (S2) S ·
4-4-1
LD> LD activates if (S1) > (S2) D ·
4-4-1
LD< LD activates if (S1) =< (S2) D ·
4-4-1
LD<> LD activates if(S1)≠(S2) D ·
4-4-1
LD<= LD activates if(S1)≤(S2) D ·
4-4-1
LD>= LD activates if(S1)≥(S2) LD>= S1 S2
4-4-1
AND= AND activates if(S1)=(S2) AND= S1 S2
4-4-2
4 applied instructions
AND> AND activates if(S1)>(S2) AND> S1 S2
4-4-2
AND< AND activates if(S1)<(S2) AND< S1 S2
4-4-2
AND<> AND activates if(S1)≠(S2) AND<> S1 S2
4-4-2
AND<= AND activates if(S1)≤(S2) AND<= S1 S2
4-4-2
AND>= AND activates if(S1)≥(S2) B M O V D 1 0 D 1 1 K 3
B M O V D 1 0 D 9 K 3X 1
X 2
4-4-2
OR= OR activates if(S1)=(S2) OR= S1 S2
4-4-3
OR> OR activates if(S1)>(S2) PMOV D5 D10 K3
X0nS· D·
4-4-3
OR< OR activates if(S1)<(S2) OR< S1 S2
4-4-3
OR<> OR activates if(S1)≠(S2) OR<> S1 S2
4-4-3
OR<= OR activates if(S1)≤(S2) DFMOV D0 D10 K3
X0nS· D·
4-4-3
OR>= OR activates if(S1)≥(S2) OR>= S1 S2
4-4-3
Data Move
CMP Compare the data CMP S1 S D
4-5-1
ZCP Compare the data in certain area D 0F W R T F D 0X 2
K 3
S · D 1 · D 2 ·
4-5-2
MOV Move MOV S D
4-5-3
BMOV Block move M S E T M 1 0 M 1 2 0
D 1 · D 2 ·X 0
4-5-4
PMOV Transfer the Data block D 2 ·
4-5-5
FMOV Multi-points repeat move D 1 ·
4-5-6
FWRT Flash ROM written D 2 ·
4-5-7
MSET Zone set D 1 ·
4-5-8
ZRST Zone reset D 2 ·
4-5-9
SWAP Swap the high and low byte D 1 ·
4-5-10
4 applied instructions
XCH Exchange two values Z R S T M 5 0 0 M 5 5 9
D 0 D 1 0 0
D 1 · D 2 ·
D 1 · D 2 ·
X 0
Z R S T 4-5-11
EMOV Float move
4-5-12
Data Operation
ADD Addition D 2 ·
4-6-1
SUB Subtraction D 1 ·
4-6-2
MUL Multiplication D 2 ·
4-6-3
DIV Division D 1 ·
4-6-4
INC Increment D 1 ·
4-6-5
DEC Decrement D 2 ·
4-6-5
MEAN Mean D 1 ·
4-6-6
WAND Word And WAND S1 S2 D
4-6-7
WOR Word OR WOR S1 S2 D
4-6-7
WXOR Word exclusive OR WXOR S1 S2 D
4-6-7
CML Compliment CML S D
4-6-8
NEG Negative
4-6-9
Data Shift
SHL Arithmetic Shift Left SHL D n
4-7-1
SHR Arithmetic Shift Right SHR D n
4-7-1
LSL Logic shift left
4-7-2
LSR Logic shift right
4-7-2
ROL Rotation shift left
4-7-3
ROR Rotation shift right
4-7-3
4 applied instructions
SFTL Bit shift left SFTL S D n1 n2
4-7-4
SFTR Bit shift right SFTR S D n1 n2
4-7-5
WSFL Word shift left
4-7-6
WSFR Word shift right
4-7-7
Data Convert
WTD Single word integer converts
to double word integer WTD S D
4-8-1
FLT 16 bits integer converts to
float point 4-8-2
DFLT 32 bits integer converts to float point
4-8-2
FLTD 64 bits integer converts to
float point 4-8-2
INT Float point converts to integer
4-8-3
BIN BCD converts to binary
4-8-4
BCD Binary converts to BCD
4-8-5
ASCI Hex. converts to ASCII ASCI S D n
4-8-6
HEX ASCII converts to Hex.
4-8-7
DECO Coding
4-8-8
ENCO High bit coding
4-8-9
ENCOL Low bit coding
4-8-10
Float Point Operation
ECMP Float compare ECMP S1 S2 D
4-9-1
EZCP Float Zone compare EZCP S1 S2 D1 D2
4-9-2
4 applied instructions
EADD Float Add
4-9-3
ESUB Float Subtract
4-9-4
EMUL Float Multiplication
4-9-5
EDIV Float division
4-9-6
ESQR Float Square Root
4-9-7
SIN Sine
4-9-8
COS Cosine
4-9-9
TAN Tangent
4-9-10
ASIN Floating Sine
4-9-11
ACOS Floating Cosine
4-9-12
ATAN Floating Tangent
4-9-13
Clock Operation
TRD Read RTC data
4-10-1
TWR Write RTC data
4-10-2
4 applied instructions
4-2.Reading Method of Applied Instructions In this manual, the applied instructions are described in the following manner. 1.Summary
ADDITION [ADD]
16 bits ADD 32 bits DADD
Execution
condition
Normally ON/OFF, Rising/Falling
edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
S1 Specify the augend data or register 16 bits/32 bits, BIN
S2 Specify the summand data or register 16 bits/32 bits, BIN
D Specify the register to store the sum 16 bits/32 bits, BIN
3.Suitable Soft Components
<16 bits instruction>
ADD D10 D12 D14X0
S1· S2· D·
<32 bits instruction>
DADD D10 D12 D14X0
S1· S2· D·
Word operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ● ●
Bit Operands System
X Y M S T C Dn.m
Description
(D10)+(D12)→(D14)
(D11D10)+(D13D12)→(D15D14)
4 applied instructions
The data contained within the two source devices are combined and total is stored in the specified
destination device. Each data’s highest bit is the sign bit, 0 stands for positive, 1 stand for negative. All
calculations are algebraic processed. (5+(-8)= -3).
If the result of a calculations is “0”, the “0’ flag acts. If the result exceeds 323,767(16 bits limit) or
2,147,483,648 ( 32 bits limit), the carry flag acts. ( refer to the next page). If the result exceeds -323,768 (16
bits limit) or -2,147,483,648 (32 bits limit ) , the borrow flag acts (Refer to the next page)
When carry on 32 bits operation, word device’s 16 bits are assigned, the device follow closely the preceding
device’s ID will be the high bits. To avoid ID repetition, we recommend you assign device’s ID to be even
ID.
The same device may be used a source and a destination. If this is the case then the result changes after
every scan cycle. Please note this point.
Flag Name Function
M8020 Zero ON:the calculate result is zero
OFF:the calculate result is not zero
M8021 Borrow
ON:the calculate result is over 32767(16bits) or 2147483647(32bits)
OFF:the calculate result is not over 32767(16bits) or 2147483647(32bits)
M8022 Carry
ON:the calculate result is over 32767(16bits) or 2147483647(32bits)
OFF:the calculate result is not over 32767(16bits) or 2147483647(32bits)
Instruction D(NUM) Object data
Related flag
The assignment of the data The data register of XC series PLC is a single word (16 bit) data register, single word data only engross one data register which is assigned by single word object instruction. The disposal bound is: Dec. –327,68~327,67, Hex. 0000~FFFF.
The related
description
D(NUM) Single word object instruction
→
Double word(32 bit)engrosses two data register, it’s composed by two consecutive data registers, the first one is assigned by double word object instruction. The dispose bound is: Dec. -214,748,364,8~214,748,364,7, Hex. 00000000~FFFFFFFF.
4 applied instructions
Instruction D(NUM) Object data Object data
※1:Flag after executing the instruction. Instructions without the direct flag will not display. ※2: Source operand, its content won’t change after executing the instruction
※3: Destinate operand, its content changes with the execution of the instruction ※4:Tell the instruction’s basic action, using way, applied example, extend function, note items etc. 4-3.Program Flow Instructions
Mnemonic Instruction’s name Chapter CJ Condition Jump 4-3-1 CALL Call subroutine 4-3-2 SRET Subroutine return 4-3-2 STL Flow start 4-3-3 STLE Flow end 4-3-3 SET Open the assigned flow, close the current flow (flow
jump) 4-3-3
ST Open the assigned flow, not close the current flow (Open the new flow)
4-3-3
FOR Start of a FOR-NEXT loop 4-3-4 NEXT End of a FOR-NEXT loop 4-3-4 FEND First End 4-3-5 END Program End 4-3-5
D(NUM+1) D(NUM) Double word object instruction
→
The denote way of 32 bits instruction If an instruction can not only be 16 bits but also be 32 bits, then the denote method for 32 bits instruction is to add a “D” before 16 bits instruction. E.g:ADD D0 D2 D4 denotes two 16 bits data adds;
DADD D10 D12 D14 denotes two 32 bits data adds
S·
D·
4 applied instructions
4-3-1.Condition Jump [CJ] 1.Summary
As used to run a part of program, CJ shorten the operation cycle and using the dual coil Condition Jump [CJ] 16 bits CJ 32 bits - Execution
condition
Normally ON/OFF coil Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
Pn Jump to the target (with pointer Nr.) P (P0~P9999) Pointer's Nr. 3.Suitable Soft Components
In the below graph, if X000 is “ON”, jump from the first step to the next step behind P6 tag. If X000 “OFF”, do not execute the jump construction;
Pointer
P I
●
Other
Description
4 applied instructions
CJ
Y0
X0
X1
X3
X4
X0
RST
T246 K1000
MOV
CJ
X2
X5
X6
P6
T246
K3 D0
P7
T246RST
Y0
P6
P7
4-3-2.Call subroutine [CALL] and Subroutine return [SRET]
1.Summary Call the programs which need to be executed together, decrease the program's steps;
Subroutine Call [CALL] 16 bits CALL 32 bits - Execution
condition
Normally ON/OFF, Rising/Falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Subroutine Return [SRET] 16 bits SRET 32 bits - Execution
condition
- Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
Pn Jump to the target (with pointer Nr.) P (P0~P9999) Pointer's Nr. 3.Suitable Soft Components
In the left graph, Y000 becomes to be dual coil output, but when X000=OFF, X001 activates; when X000=ON, X005 activates
CJ can’t jump from one STL to another STL;
After driving time T0~T640 and HSC C600~C640, if execute CJ, continue to work, the output activates.
4 applied instructions
CALLX0
FEND
SRET
END
P10
P10
4-3-3.Flow [SET].[ST] .[STL]. [STLE]
1、Summary Instructions to specify the start, end, open, close of a flow;
Open the specified flow, close the local flow [SET] 16 bits SET 32 bits - Execution
condition
Normally ON/OFF, Rising/Falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Open the specified flow, not close the local flow [ST] 16 bits ST 32 bits - Execution
condition
Normally ON/OFF, Rising/Falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Flow starts [STL] 16 bits STL 32 bits -
Others Pointer
P I
●
Main Program
Subroutine
If X000= “ON”, execute the call instruction and jump to the step tagged by P10. after executing the subroutine, return the original step via SRET instruction.Program the tag with FEND instruction (will describe this instruction later)
In the subroutine 9 times call is allowed, so totally there can be 10 nestings.
Description
4 applied instructions
Execution
condition
- Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Flow ends [STLE] 16 bits STLE 32 bits - Execution
condition
- Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.operands
Operands Function Data Type
Sn Jump to the target flow S Flow ID 3.Suitable Soft Components
Operands System
X Y M S T C Dn.m
Sn ●
Bit
Description
STL and STLE should be used in pairs. STL represents the start of a flow, STLE represents the end of a flow.
After executing of SET Sxxx instruction, the flow specified by these instructions is ON. After executing RST Sxxx instruction, the specified flow is OFF. In flow S0, SET S1 close the current flow S0, open flow S1. In flow S0, ST S2 open the flow S2, but don’t close flow S0. When flow turns from ON to be OFF, reset OUT、PLS、PLF、not accumulate timer etc.
which belongs to the flow. ST instruction is usually used when a program needs to run more flows at the same time. After executing of SET Sxxx instruction, the pulse instructions will be closed (including
one-segment, multi-segment, relative or absolute, return to the origin)
4 applied instructions
SET S0
STL S0
SET S1
ST S2
STL S1
STLE
STLE
STL S2
STLE
4 applied instructions
4-3-4. [FOR] and [NEXT] 1.Summary Loop execute the program between FOR and NEXT with the specified times;
Loop starts [FOR] 16 bits FOR 32 bits - Execution
condition
Rising/Falling edge Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Loop ends [NEXT] 16 bits NEXTs 32 bits - Execution
condition
Normally ON/OFF, Rising/Falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
S Program’s loop times between FOR~NEXT 16 bits, BIN 3.Suitable Soft Components
FOR.NEXT instructions must be programmed as a pair. Nesting is allowed, and the nesting
level is 8. Between FOR/NEXT, LDP.LDF instructions are effective for one time. Every time when M0
turns from OFF to ON, and M1 turns from OFF to ON, [A] loop is executed 6 times. Every time if M0 turns from OFF to ON and M3 is ON, [B] loop is executed 5×7=35 times. If there are many loop times, the scan cycle will be prolonged. Monitor timer error may
occur, please note this. If NEXT is before FOR, or no NEXT, or NEXT is behind FENG,END, or FOR and NEXT
number is not equal, an error will occur. Between FOR~NEXT, CJ nesting is not allowed, also in one STL, FOR~NEXT must be
programmed as a pair.
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ●
Word
Description
4 applied instructions
F O R K 6
IN C D 0
N E X T
F O R K 7
IN C D 1
N E X T
N E X T
F O R K 5M 0
M 3
M 1
[A ]
[B ]
[C ]
S ·
4-3-5. [FEND] and [END] 1.Summary FEND means the main program ends, while END means program ends;
main program ends [FEND] Execution condition - Suitable Models XC1.XC2.XC3.XC5.XCM Hardware requirement - Software requirement - program ends [END] Execution condition - Suitable Models XC1.XC2.XC3.XC5.XCM Hardware requirement - Software requirement -
2.Operands
Operands Function Data Type
None - - 3.Suitable Soft Components
Even though [FEND] instruction represents the end of the main program, if execute this instruction, the function is same with END. Execute the output/input disposal, monitor the refresh of the timer, return to the 0th step.
None
Description
4 applied instructions
If program the tag of CALL instruction behind FEND instruction, there must be SRET instruction. If the interrupt pointer program behind FEND instruction, there must be IRET instruction.
After executing CALL instruction and before executing SRET instruction, if execute FEND instruction; or execute FEND instruction after executing FOR instruction and before executing NEXT, then an error will occur.
In the condition of using many FEND instruction, please compile routine or subroutine between the last FEND instruction and END instruction.
4-4. Data compare function
Mnemonic Function Chapter LD= LD activates when(S1)=(S2) 4-4-1 LD> LD activates when(S1)>(S2) 4-4-1 LD< LD activates when(S1)<(S2) 4-4-1 LD<> LD activates when(S1)≠(S2) 4-4-1 LD<= LD activates when(S1)≤(S2) 4-4-1 LD>= LD activates when(S1)≥(S2) 4-4-1 AND= AND activates when(S1)=(S2) 4-4-2 AND> AND activates when(S1)>(S2) 4-4-2 AND< AND activates when(S1)<(S2) 4-4-2 AND<> AND activates when(S1)≠(S2) 4-4-2 AND<= AND activates when(S1)≤(S2) 4-4-2 AND>= AND activates when(S1)≥(S2) 4-4-2
4 applied instructions
OR= OR activates when(S1)=(S2) 4-4-3 OR> OR activates when(S1)>(S2) 4-4-3 OR< OR activates when(S1)<(S2) 4-4-3 OR<> OR activates when(S1)≠(S2) 4-4-3 OR<= OR activates when(S1)≤(S2) 4-4-3 OR>= OR activates when(S1)≥(S2) 4-4-3
4-4-1.LD Compare [LD□]
1. Summary
LD□ is the point compare instruction connected with the generatrix. LD Compare [LD□] 16 bits As below 32 bits As below Execution
condition
- Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
S1 Specify the Data ( to be compared) or soft component’s address code
16/32bits, BIN
S2 Specify the comparand’s value or soft component’s address code
16/32 bits, BIN
3.Suitable soft components 16 bits instruction 32 bits instruction Activate Condition Not Activate Condition LD= DLD= (S1)=(S2) (S1)≠(S2) LD> DLD> (S1)>(S2) (S1)≤(S2)
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
Word
Description
4 applied instructions
LD< DLD< (S1)<(S2) (S1)≥(S2) LD<> DLD<> (S1)≠(S2) (S1)=(S2) LD<= DLD<= (S1)≤(S2) (S1)>(S2) LD>= DLD>= (S1)≥(S2) (S1)<(S2)
LD> D200 K-30 SET Y1
DLD> K68899 C300 M50
X1
M4
S1· S2·
LD= K100 C0 Y0X0
4-4-2.AND Compare [AND□] 1.Summary
AND□: The compare instruction to serial connect with the other contactors. AND Compare [AND□] 16 bits As Below 32 bits As Below Execution
condition
Normally ON/OFF coil Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
S1 Specify the Data ( to be compared) or soft component’s address code
16/32bit,BIN
S2 Specify the comparand’s value or soft component’s address code
16/32bit,BIN
3.suitable soft components
When the source data’s highest bit (16 bits:b15,32 bits:b31) is 1,use the data as a negative.
The comparison of 32 bits counter (C300~) must be 32 bits instruction. If assigned as a 16 bits instruction, it will lead the program error or operation error.
。
Note Items
Operands System Konstant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
Word
4 applied instructions
16 bits instruction 32 bits instruction Activate Condition Not Activate Condition AND= DAND= (S1)=(S2) (S1)≠(S2) AND> DAND> (S1)>(S2) (S1)≤(S2) AND< DAND< (S1)<(S2) (S1)≥(S2) AND<> DAND<> (S1)≠(S2) (S1)=(S2) AND<= DAND<= (S1)≤(S2) (S1)>(S2) AND>= DAND>= (S1)≥(S2) (S1)<(S2)
AND= K100 C0 Y0
AND> D0K-30 SET Y1
DAND> K68899 D10 M50
X1
M4
X0
X2
S1· S2·
4-4-3.Parallel Compare [OR□] 1. Summary
OR□ The compare instruction to parallel connect with the other contactors Parallel Compare [OR□] 16 bits As below 32 bits As below Execution - Suitable XC1.XC2.XC3.XC5.XCM
Description
When the source data’s highest bit (16 bits:b15,32 bits:b31) is 1,use the data as a negative.
The comparison of 32 bits counter (C300~) must be 32 bits instruction. If assigned as a 16 bits instruction, it will lead the program error or operation error.
Note Items
4 applied instructions
condition Models
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Specify the Data ( to be compared) or soft component’s address code
16/32 bit,BIN
S2 Specify the comparand’s value or soft component’s address code
16/32 bit,BIN
3. suitable soft components 16 bits instruction 32 bits instruction Activate Condition Not Activate Condition OR= DOR= (S1)=(S2) (S1)≠(S2) OR> DOR> (S1)>(S2) (S1)≤(S2) OR< DOR< (S1)<(S2) (S1)≥(S2) OR<> DOR<> (S1)≠(S2) (S1)=(S2) OR<= DOR<= (S1)≤(S2) (S1)>(S2) OR>= DOR>= (S1)≥(S2) (S1)<(S2)
OR= K100 C0
Y0
DOR> K68899D10
M50M4
X0
X2
S1· S2·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
Word
Description
4 applied instructions
4-5.Data Move
Mnemonic Function Chapter CMP Data compare 4-5-1 ZCP Data zone compare 4-5-2 MOV Move 4-5-3 BMOV Data block move 4-5-4 PMOV Data block move (with faster speed) 4-5-5 FMOV Fill move 4-5-6 FWRT FlashROM written 4-5-7 MSET Zone set 4-5-8 ZRST Zone reset 4-5-9 SWAP The high and low byte of the destinated
devices are exchanged 4-5-10
XCH Exchange 4-5-11
When the source data’s highest bit (16 bits:b15,32 bits:b31) is 1,use the data as a negative.
The comparison of 32 bits counter (C300~) must be 32 bits instruction. If assigned as a 16 bits instruction, it will lead the program error or operation error.
Note Items
4 applied instructions
4-5-1.Data Compare [CMP] 1. Summary
Compare the two specified Data, output the result. Data compare [CMP] 16 bits CMP 32 bits DCMP Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Specify the data (to be compared) or soft component’s address code
16 bit,BIN
S Specify the comparand’s value or soft component’s address code
16 bit,BIN
D Specify the compare result’s address code bit 3. Suitable soft component
CMP D10 D20 M0
S1·
X0
M0
M1
M2
D10 > D20
S·
D10 = D20
D10 < D20
ON
ON
ON
D
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S ● ● ● ● ● ● ● ● ●
Oper
ands
System
X Y M S T C Dn..m
D ● ● ●
Bit
Description
Even X000=OFF to stop ZCP instruction, M0~M2 will
keep the original status Compare data and , output the three points’ ON/OFF status (start with ) according to the value
S1· S·
D·
4 applied instructions
4-5-2.Data zone compare [ZCP] 1. Summary
Compare the two specify Data with the current data, output the result. Data Zone compare [ZCP] 16 bits ZCP 32 bits DZCP Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Specify the down-limit Data (of the compare stand) or soft component’s address code
16 bit, BIN
S2 Specify the Up-limit Data (of the compare stand) or soft component’s address code
16 bit, BIN
S Specify the current data or soft component’s address code
16 bit, BIN
D Specify the compare result’s data or soft component’s address code
bit
3.Suitable soft components
, +1, +2 :the three point’s on/off output according to the valve D· D· D·
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
S ● ● ● ● ● ● ● ● ●
Bit Oper
ands
System
X Y M S T C Dn..m
D ● ● ●
4 applied instructions
4-5-3.MOV [MOV]
ZCP D20 D30 D0 M0
S1· S2· S· D·
X0
M0
M1
M2
D0 M0 ON
M1 ON
M2 ON
D0
D0
D20
D20 D31(分)
D31(分)
>
≤ ≤
>
1. Summary
Move the specified data to the other soft components MOV [MOV] 16 bits MOV 32 bits DMOV Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Specify the source data or register’s address code 16 bit/32 bit, BIN D Specify the target soft component’s address code 16 bit/32 bit, BIN
3. Suitable soft component
Even X000=OFF stop ZCP instruction,M0~M2 will keep
the original status
Description
Compare data with and , output the three point’s ON/OFF status according to the zone size.
, +1, +2 : the three point’s ON/OFF output according to the result
S· D·
D·D·D·
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ● ●
S1 S2
4 applied instructions
MOV K10 D10X0
S· D·
<read the counter’s or time’s current value> <indirectly specify the counter’s ,time’s set value>
MOV T0 D20X1
MOV K10 D20X2
M0T20 D20
< Move the 32bits data >
DMOV D0 D10
DMOV C235 D20
Description Move the source data to the target When X000 is off, the data keeps
same Convert constant K10 to be BIN
code automatically
(K10)(D10)
D20=K10 ( The current value of T0)→(D20)
The same as counter
Please use DMOV when the value is 32 bits, such as MUL instruction, high speed counter…
(D1,D0)→(D11,D10)
(the current value of C235)→(D21,D20)
4 applied instructions
4-5-4.Data block Move [BMOV] 1. Summary
Move the specified data block to Data block move [BMOV] 16 bits BMOV 32 bits - Execution
condition
Normally ON/OFF coil Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Specify the source data block or soft component address code
16 bits, BIN; bit
D Specify the target soft components address code 16 bits, BIN; bit n Specify the move data’s number 16 bits, BIN;
3. Suitable soft components
Move the specified “n” data to the specified “n” soft components in the form block.
BMOV D5 D10 K3X0
nS· D·
D5
D6
D7
D10
D11
D12
n=3
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ● ●
n ● ● ● ● ● ● ●
Word
Bit Operands System
X Y M S T C Dn.m
S ● ● ●
D ● ● ●
Description
4 applied instructions
As the following picture, when the data address overlapped, the instruction will do from 1 to 3.
BMOV D10 D11 K3
BMOV D10 D9 K3X1
X2
D10
D11
D12
D9
D10
D11
D10
D11
D12
D11
D12
D13
①
②
③
③
②
①
4 applied instructions
4-5-5.Data block Move [PMOV] 1. Summary
Move the specified data block to the other soft components Data block mov[PMOV] 16 bits PMOV 32 bits - Execution
condition
Normally ON/OFF coil Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Specify the source data block or soft component address code
16 bits, BIN; bit
D Specify the target soft components address code 16 bits, BIN; bit n Specify the move data’s number 16 bits, BIN;
3. Suitable soft components
Move the specifed “n” data to the specified “n” soft components in form of block
PMOV D5 D10 K3X0
nS· D·
D5
D6
D7
D10
D11
D12
n=3
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ● ●
n ● ● ● ● ● ● ●
Word
Oper
ands
system
X Y M S T C Dn.m
S ● ● ●
D ● ● ●
Bit
Description
4 applied instructions
4-5-6.Fill Move [FMOV] 1. Summary
Move the specified data block to the other soft components Fill Move [FMOV] 16 bits FMOV 32 bits DFMOV Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
DFMOV need above V3.0 Software
requirement
-
2. Operands
Operands Function Data Type
S Specify the source data block or soft component address code
16 bits, BIN; bit
D Specify the target soft components address code 16 bits, BIN; bit n Specify the move data’s number 16 bits, BIN;
3. Suitable soft component
<16 bits instruction>
FMOV K0 D0 K10X0
nS· D·
The function of PMOV and BMOV is mostly the same, but the PMOV has the faster speed
PMOV finish in one scan cycle, when executing PMOV , close all the interruptions
Mistake many happen, if there is a repeat with source address and target address
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ● ●
n ● ● ● ● ● ● ●
Description
4 applied instructions
Move K0 to D0~D9, copy a single data device to a range of destination
device The data stored in the source device (S) is copied to every device within
the destination range, The range is specified by a device head address (D) and a quantity of consecutive elements (n).
If the specified number of destination devices (n) exceeds the available space at the destination location, then only the available destination devices will be written to.
<32 bits instruction >
DFMOV D0 D10 K3X0
nS· D·
Move D0.D1 to D10.D11:D12.D13:D14.D15.
<16 bits Fill Move > <32 bits Fill move>
K0 D0K0
n
D1K0
D2K0
D3K0
D4K0
D5K0
D6K0
D7K0
D8K0
D9K0
4 applied instructions
4 applied instructions
4-5-7.FlashROM Write [FWRT] 1. Summary
Write the specified data to other soft components FlashROM Write [FWRT] 16 bits FWRT 32 bits DFWRT Execution
condition
rising/falling edge Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S The data write in the source or save in the soft element
16 bits/32 bits, BIN
D Write in target soft element 16 bits/32 bits, BIN D1 Write in target soft element start address 16 bits/32 bits, BIN D2 Write in data quantity bit
3. Suitable soft components
< Written of a word >
D0FWRT FD0X0
S· D·
<Written of double word> <Written of multi-word>
D0DFWRT FD0X1
S· D·
※1:FWRT instruction only allow to write data into FlashRom register. In this storage, even battery drop, data
could be used to store important technical parameters
※2:Written of FWRT needs a long time, about 150ms, so frequently operate this operate this operate operation is
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ● ●
D ●
D1 ●
D2 ● ● ● ● ● ● ● ●
Word
Description
Write value in D0 into FD0
D0FWRT FD0X2
K3
S· D1· D2·
Write value in D0,D1 into FD0,FD1 Write value in D0,D1,D2 into FD0,FD1,FD2
4 applied instructions
recommended
※3:The written time of Flshrom is about 1,000,000 times. So we suggest using edge signal (LDP, LDF etc.) to
trigger.
※4:Frequently written of FlashROM
4-5-8.Zone set [MSET]
1. Summary Set or reset the soft element in certain range
Multi-set [MSET] 16 bits MSET.ZRST 32 bits - Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D1 Start soft element address bit D2 End soft element address bit
3. Suitable soft components
MSET M10 M120
D1· D2·X0
Operands System
X Y M S T C Dn.m
D1 ● ● ● ● ● ●
D2 ● ● ● ● ● ●
Bit
Zone set unit M10~M120 Description
Are specified as the same type of soft units, and < When > ,will not run Zone set, set M8004.M8067,and
D8067=2。
D2·D1·D2·D1·
D2·D1·
4 applied instructions
4-5-9.Zone reset [ZRST] 1. Summary Reset the soft element in the certain range
Multi-reset [ZRST] 16 bits ZRST 32 bits - Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D1 Start address of soft element Bit:16 bits,BIN D2 End address of soft element Bit:16 bits,BIN
3. Suitable soft components
ZRST M500 M559
D0 D100
D1· D2·
D1· D2·
X0
ZRST
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ●
D2 ● ● ● ● ●
Word
Operands System
X Y M S T C Dn.m
D1 ● ● ● ● ● ●
D2 ● ● ● ● ● ●
Bit
Zone reset bits M5 00~M559。
Zone reset words D0~D100
Description
Are specified as the same type of soft units, and < When > , only reset the soft unit specified in ,and set
M8004.M8067,D8067=2。
D2·D1·D2·D1·
D1·D2·D1·
Other Reset Instruction
As soft unit’s separate reset instruction, RST instruction can be used to bit unit Y, M, S and word unit T, C, D
As fill move for constant K0, 0 can be written into DX, DY, DM, DS, T, C, D.
4 applied instructions
4-5-10.Swap the high and low byte [SWAP] 1. Summary
Swap the high and low byte High and low byte swap [SWAP] 16 bits SWAP 32 bits - Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S The address of the soft element 16 bits: BIN 3. Suitable soft components
SWAP D10
高8位
D10
低8位
S·X0
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ●
Description
Low 8 bits and high 8 bits change when it is 16 bits instruction. If the instruction is a consecutive executing instruction, each operation
cycle should change.
4 applied instructions
4-5-11.Exchange [XCH] 1. Summary
Exchange the data in two soft element Exchange [XCH] 16 bits XCH 32 bits DXCH Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D1 The soft element address 16 bits, BIN D2 The soft element address 16 bits, BIN
3. Suitable soft component <16 bits instruction>
XCH D10 D11X0
D1· D2·
<32 bits instruction >
DXCH D10 D20X0
D1· D2·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ● ● ●
D2 ● ● ● ● ● ●
Word
Description
Before(D10)=100 →After (D10)=101
(D11)=101 (D11)=100
The contents of the two destination devices D1 and D2 are swapped, When drive input X0 is ON, each scan cycle should carry on data
exchange, please note.
32 bits instruction [DXCH] swaps value composed by D10、D11 and the value composed by D20、D21.
4 applied instructions
4-5-12.Floating move [EMOV]
1. Summary Send the floating number from one soft element to another
Floating move [EMOV] 16 bits - 32 bits EMOV Execution condition
Normally on/off, edge trigger Suitable models
XC2、XC3、XC5、XCM、XCC
Hardware V3.3 and higher Software V3.3 and higher
2. Operands Operand Function Type S Source soft element address 32 bits, BIN D Destination soft element address 32 bits, BIN
3. Suitable soft element
<32 bits instruction>
Binary floating → binary floating
(D1,D0)→(D11,D10)
X0 is ON, send the floating number from (D1, D0) to (D11, D10). X0 is OFF, the instruction doesn’t work
EMOV K500 D10X0
S· D·
(K500)→(D11,D10)
If constant value K, H is source soft element, they will be converted to floating number.
K500 will be converted to floating value.
Operand System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
4 applied instructions
4-6.Data Operation Instructions
Mnemonic Function Chapter ADD Addition 4-6-1 SUB Subtraction 4-6-2 MUL Multiplication 4-6-3 DIV Division 4-6-4 INC Increment 4-6-5 DEC Decrement 4-6-5 MEAN Mean 4-6-6 WAND Logic Word And 4-6-7 WOR Logic Word Or 4-6-7 WXOR Logic Exclusive Or 4-6-7 CML Compliment 4-6-8 NEG Negation 4-6-9
4 applied instructions
4-6-1 Addition [ADD] 1. Summary
Add two numbers and store the result Add [ADD] 16 bits ADD 32 bits DADD Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 The number address 16 bit/32 bit, BIN S2 The number address 16 bit/32bit, BIN D The result address 16 bit/32bit, BIN
3. Suitable soft components
ADD D10 D12 D14X0
S1· S2· D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description
(D10)+(D12)→(D14)
The data contained within the two source devices are combined and the total is stored in the specified destination device. Each data’s highest bit is the sign bit, 0 stands for positive、1 stands for negative. All calculations are algebraic processed.(5+(-8)=-3)
If the result of a calculation is “0”, the “0” flag acts. If the result exceeds 323,767(16 bits limit)or 2,147,483,647(32 bits limit), the carry flag acts.(refer to the next page). If the result exceeds –323,768(16 bits limit)or –2,147,483,648(32 bits limit), the borrow flag acts(Refer to the next page。
When carry on 32 bits operation, word device’s low 16 bits are assigned, the device following closely the preceding device’s ID will be the high bits. To avoid ID repetition, we recommend you assign device’s ID to be even ID.
The same device may be used as a source and a destination. If this is the case then the result changes after every scan cycle. Please note this point.
4 applied instructions
Flag meaning
Flag Name Function
M8020 Zero ON:the calculate result is zero OFF:the calculate result is not zero
M8021 Borrow ON:the calculate result is less than -32768(16 bit) or -2147483648(32bit) OFF:the calculate result is over -32768(16 bit) or -2147483648(32bit)
M8022 Carry ON:the calculate result is over 32768(16 bit) or 2147483648(32bit) OFF:the calculate result is less than 32768(16 bit) or 2147483648(32bit)
4-6-2.Subtraction [SUB] 1. Summary
Sub two numbers, store the result Subtraction [SUB] 16 bits SUB 32 bits DSUB Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2.Operands
Operands Function Data Type
S1 The number address 16 bits /32 bits,BIN S2 The number address 16 bits /32 bits,BIN D The result address 16 bits /32 bits,BIN
3.Suitable soft component
Related flag
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
4 applied instructions
SUB D10 D12 D14
X0S1· S2· D·
The relationship of the flag’s action and vale’s positive/negative is shown below:
4-6-3.Multiplication [MUL]
1. Summary
Multiply two numbers, store the result Multiplication [MUL] 16 bits MUL 32 bits DMUL Execution
condition
Normally ON/OFF Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 The number address 16 bits/32bits,BIN S2 The number address 16 bits/32bits,BIN D The result address 16 bits/32bits,BIN
3. Suitable soft component
(D10)—(D12)→(D14) Description
appoint the soft unit’s content, subtract the soft unit’s content appointed by in the format of algebra. The result will be stored in the soft unit appointed by . (5-(-8)=13)
The action of each flag, the appointment method of 32 bits operation’s soft units are both the same with the preceding ADD instruction.
The importance is: in the preceding program, if X0 is ON, SUB operation will be executed every scan cycle
S1· S2·
D·
4 applied instructions
<16 bits Operation>
MUL D0 D2 D4X0
S1· S2· D·
<32 bits Operation >
X1DMUL D0 D2 D4
S1· S2· D·
4-6-4.Division [DIV] 1. Summary
Divide two numbers and store the result Division [DIV] 16 bits DIV 32 bits DDIV Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 The number address 16 bits / 32 bits, BIN S2 The number address 16 bits /32 bits, BIN
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description BIN BIN BIN
(D0) × (D2) → (D5,D4)
16 bits 16 bits → 32 bits
The contents of the two source devices are multiplied together and the result is stored at the destination device in the format of 32 bits. As in the upward chart: when (D0)=8、(D2)=9, (D5, D4) =72.
The result’s highest bit is the symbol bit: positive (0)、negative (1). When be bit unit, it can carry on the bit appointment of K1~K8. When appoint K4, only
the result’s low 16 bits can be obtained.
BIN BIN BIN
(D1,D0)× (D3,D2) → (D7,D6,D5,D4)
32 bits 32 bits → 64 bits
When use 2 bits Operation ,the result is stored at the destination device in the format of 64 bits.
Even use word device, 64 bits results can’t be monitored at once.
4 applied instructions
D The result address 16 bits /32 bits, BIN 3.Suitable soft components
<16 bits operation >
DIV D0 D2 D4X0
S1· S2· D·
<32 bits operation >
DDIV D0 D2 D4X1
S1· S2· D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Dividend Divisor Result Remainder
BIN BIN BIN BIN
(D0) ÷ (D2) → D4) ┅ (D5)
16 bits 16 bits 16 bits 16 bits
Description
appoints the device’s content be the dividend, appoints the device’s content be the divisor, appoints the device and the next one to store the result and the remainder.
In the above example, if input X0 is ON, devision operation is executed every scan cycle.
D·
S2·S1·
Dividend Divisor Result Remainder
BIN BIN BIN BIN
(D1,D0) ÷ (D3,D2) (D5,D4)┅ (D7,D6)
32 bits 32 bits 32 bits 32 bits
The dividend is composed by the device appointed by and the next one. The divisor is composed by the device appointed by and the next one. The result and the remainder are stored in the four sequential devices, the first one is appointed by
If the value of the divisor is 0, then an operation error is executed and the operation of the DIV instruction is cancelled
S1·
S2·
D·
The highest bit of the result and remainder is the symbol bit (positive:0, negative: 1). When any of the dividend or the divisor is negative, then the result will be negative. When the dividend is negative, then the remainder will be negative.
4 applied instructions
4-6-5.Increment [INC] & Decrement [DEC] 1. Summary
Increase or decrease the number Increment 1[INC] 16 bits INC 32 bits DINC Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Increment 1[DEC] 16 bits DEC 32 bits DDEC Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D The number address 16 bits / 32bits,BIN 3. Suitable soft components
< Increment [INC]>
INC D0X0
D·
<Decrement [DEC]>
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ● ● ● ●
Description
(D0)+1→(D0)
On every execution of the instruction the device specified as the destination has its current value incremented (increased) by a value of 1.
In 16 bits operation, when +32,767 is reached, the next increment will write -32,767 to the destination device. In this case, there’s no additional flag to identify this change in the counted value.
D·
4 applied instructions
DEC D0X1
D·
4-6-6.Mean [MEAN] 1. Summary
Get the mean value of numbers Mean [MEAN] 16 bits MEAN 32 bits DMEAN Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S The head address of the numbers 16 bits, BIN D The mean result address 16 bits, BIN n The number quantity 16 bits, BIN
3. Suitable soft components
(D0) + +
3(D10)
(D1) (D2)
(D0)-1 →(D0)
On every execution of the instruction the device specified as the destination has its current value decremented (decreased) by a value of 1.
When -32,768 or -2,147,483,648 is reached, the next decrement will write +32,767 or +2,147,483,647 to the destination device.
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n ●
Word
Description MEAN D0 D10 K3
S· D·X0
n
4 applied instructions
4-6-7.Logic AND [WAND] , Logic OR[WOR], Logic Exclusive OR [WXOR] 1. Summary
Do logic AND, OR, XOR for numbers Logic AND [WAND] 16 bits WAND 32 bits DWAND Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Logic OR[WOR] 16 bits WOR 32 bits DWOR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Logic Exclusive OR [WXOR] 16 bits WXOR 32 bits DWXOR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 The soft element address 16bit/32bit,BIN S2 The soft element address 16bit/32bit,BIN D The result address 16bit/32bit,BIN
The value of all the devices within the source range is summed and then divided by the number of devices summed, i.e. n.. This generates an integer mean value which is stored in the destination device (D) The remainder of the calculated mean is ignored.
If the value of n is specified outside the stated range (1 to 64) an error is generated.
4 applied instructions
3. Suitable soft components
< Execute logic AND operation with each bit>
WAND D10 D12 D14
D·X0
S1· S2·
< Execute logic OR operation with each bit >
WOR D10 D12 D14
D·X0
S1· S2·
< Execute logic Exclusive OR operation with each bit >
WXOR D10 D12 D14
D·X0
S1· S2·
If use this instruction along with CML instruction, XOR NOT operation could also be executed.
WXOR D10 D12 D14
D·X0
S1· S2·
CML D14 D14
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description 0&0=0 0&1=0 1&0=0 1&1=1
0 or 0=0 0 or 1=1 1 or 0=1 1 or 1=1
0 xor 0=0 0 xor 1=1 1 xor 0=1 1 xor 1=0
4 applied instructions
4-6-8.Converse [CML] 1. Summary
Converse the phase of the numbers Converse [CML] 16 bits CML 32 bits DCML Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source number address 16 bits/32 bits, BIN D Result address 16 bits/32 bits, BIN
3. Suitable soft components
CML D0 DY0
S· D·M0↑
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
D0
Y17 Y7 Y6 Y5 Y4
Sign bit
(0=positive,1=negative)
< Reading of inverted input >
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Each data bit in the source device is inverted (1→0,0→1) and sent to the destination device. If use constant K in the source device, it can be auto convert to be binary.
It’s available when you want to inverted output the PLC’s output
Description
4 applied instructions
M0
M1
M2
M3
M17
CML DX0 DM0M8000
X0
X1
X2
X3
X17
4-6-9.Negative [NEG]
1. Summary
Get the negative number Negative [NEG] 16 bits NEG 32 bits DNEG Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC1.XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D The source number address 16 bits/ bits, BIN 3. Suitable soft components
NEG D10 (D10) +1 (D10)M0
D·
The sequential control instruction in the left could be denoted by the following CML instruction.
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ● ● ● ●
Word
Description
The bit format of the selected device is inverted, I.e. any occurrence of a “1’ becomes a “0” and any occurrence of “0” becomes “1”, when this is complete, a further binary 1 is added to the bit format. The result is the total logic sigh change of the selected devices contents.
4 applied instructions
4-7.Shift Instructions
Mnemonic Function Chapter SHL Arithmetic shift left 4-7-1 SHR Arithmetic shift right 4-7-1 LSL Logic shift left 4-7-2 LSR Logic shift right 4-7-2 ROL Rotation left 4-7-3 ROR Rotation right 4-7-3 SFTL Bit shift left 4-7-4 SFTR Bit shift right 4-7-5 WSFL Word shift left 4-7-6 WSFR Word shift right 4-7-7
4 applied instructions
4-7-1.Arithmetic shift left [SHL], Arithmetic shift right [SHR] 1. Summary
Do arithmetic shift left/right for the numbers Arithmetic shift left [SHL] 16 bits SHL 32 bits DSHL Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Arithmetic shift right [SHR] 16 bits SHR 32 bits DSHR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D The source data address 16bit/32bit,BIN n Shift left or right times 16bit/32bit,BIN
3. Suitable soft components
< Arithmetic shift left > < Arithmetic shift right >
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ● ● ● ●
n ●
Word
After once execution, the low bit is filled in 0, the final bit is stored in carry flag.
After once execution, the high bit is same with the bit before shifting, the final bit is stored in carry flag.
Description
4 applied instructions
、
4-7-2.Logic shift left [LSL] , Logic shift right [LSR] 1. Summary
Do logic shift right/left for the numbers Logic shift left [LSL] 16 bits LSL 32 bits DLSL Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Logic shift right [LSR] 16 bits LSR 32 bits DLSR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
D Source data address 16 bits/32 bits, BIN n Arithmetic shift left/right times 16 bits/32bits, BIN
3. Suitable soft components
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ● ● ● ●
n ●
Word
4 applied instructions
LSR and SHR is different, LSR add 0 in high bit when moving, SHR all bits are moved.
< Logic shift left > < Logic shift right >
4-7-3.Rotation shift left [ROL] , Rotation shift right [ROR] 1. Summary
Continue and cycle shift left or right Rotation shift left [ROL] 16 bits ROL 32 bits DROL Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
Rotation shift right [ROR] 16 bits ROR 32 bits DROR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands Operands Function Data Type
After once execution, the low bit is filled in 0, the final bit is stored in carry flag.
LSL meaning and operation are the same as SHL. After once execution, the high bit is same with the bit before shifting,
the final bit is stored in carry flag。
Description
4 applied instructions
D Source data address 16 bits/32 bits, BIN n Shift right or left times 16 bits/32 bits, BIN
3. Suitable soft components
< Rotation shift left > < Rotation shift right >
4-7-4.Bit shift left [SFTL]
1. Summary
Bit shift left Bit shift left [SFTL] 16 bits SFTL 32 bits DSFTL Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Types S Source soft element head address bit D Target soft element head address bit
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ● ● ● ●
n ●
Word
The bit format of the destination device is rotated n bit places to the left on every operation of the instruction.
Description
4 applied instructions
n1 Source data quantity 16 bits /32 bits, BIN n2 Shift left times 16 bits/32 bits, BIN
3. Suitable soft components
4-7-5.Bit shift right [SFTR] 1. Summary
Bit shift right Bit shift right [SFTR] 16 bits SFTR 32 bits DSFTR Execution rising/falling edge Suitable XC2.XC3.XC5.XCM
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
n1 ● ● ● ● ● ● ● ●
n2 ● ● ● ● ● ● ● ●
Operands System
X Y M S T C Dn..m
S ● ● ● ● ● ●
D ● ● ● ● ●
Bit
The instruction copies n2 source devices to a bit stack of length n1. For every new addition of n2 bits, the existing data within the bit stack is shifted n2 bits to the left/right. Any bit data moving to the position exceeding the n1 limit is diverted to an overflow area.
In every scan cycle, loop shift left action will be executed
Description
① M15~M12→Overflow
② M11~M 8→M15~M 12
③ M 7~M 4→M11~M8
④ M 3~M 0→M7~M4
⑤ X 3~X 0→M3~M0
4 applied instructions
condition Models
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element head address bit D Target soft element head address bit n1 Source data quantity 16 bits/32 bits, BIN n2 Shift right times 16 bits/32 bits, BIN
3. Suitable soft components
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
n1 ● ● ● ● ● ● ● ●
n2 ● ● ● ● ● ● ● ●
Word
Bit
The instruction copies n2 source devices to a bit stack of length n1. For every new addition of n2 bits, the existing data within the bit stack is shifted n2 bits to the left/right. Any bit data moving to the position exceeding the n1 limit is diverted to an overflow area.
In every scan cycle, loop shift right action will be executed
Description
① M 3~M 0→Overflow
② M 7~M 4→M3~M0
③ M11~M 8→M7~M4
④ M15~M12→M11~M8
⑤ X 3~X 0→M15~M12
Operands System
X Y M S T C Dn..m
S ● ● ● ● ● ●
D ● ● ● ● ●
4 applied instructions
n2 word shift left
4-7-6.Word shift left [WSFL]
1. Summary
Word shift left Word shift left [ [WSFL] 16 bits WSFL 32 bits - Execution
condition
rising/falling edge Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element head address 16 bits/32 bits, BIN D Target soft element head address 16 bits /32 bits, BIN n1 Source data quantity 16 bits /32 bits, BIN n2 Word shift left times 16 bits /32 bits, BIN
3. Suitable soft components
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n1 ● ● ● ● ● ● ●
n2 ● ● ● ● ● ● ●
Word
Description The instruction copies n2 source devices to a word stack of length n1. For each addition of n2 words, the existing data within the word stack is shifted n2 words to the left. Any word data moving to a position exceeding the n1 limit is diverted to an overflow area.
In every scan cycle, loop shift left action will be executed.
① D25~D22→Overflow
② D21~D18→D25~D22
③ D17~D14→D21~D18
④ D13~D10→D17~D14
⑤ D 3~D 0→D13~D10
4 applied instructions
4-7-7.Word shift right[WSFR] 1. Summary
Word shift right Word shift right [WSFR] 16 bits WSFR 32 bits - Execution
condition
rising/falling edge Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element head address 16 bits/32 bits, BIN D Target soft element head address 16 bits/32 bits, BIN n1 Source data quantity 16 bits/32 bits, BIN n2 Shift right times 16 bits/32 bits, BIN
3. Suitable soft components
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n1 ● ● ● ● ● ● ●
n2 ● ● ● ● ● ● ●
Word
Description The instruction copies n2 source devices to a word stack of length n1.
For each addition of n2 words, the existing data within the word stack is shifted n2 words to the right. Any word data moving to a position exceeding the n1 limit is diverted to an overflow area.
4 applied instructions
n2 字右移
4-8.Data Convert
Mnemonic Function Chapter WTD Single word integer converts to
double word integer 4-8-1
FLT 16 bits integer converts to float point
4-8-2
DFLT 32 bits integer converts to float point
4-8-2
FLTD 64 bits integer converts to float point
4-8-2
INT Float point converts to integer 4-8-3 BIN BCD convert to binary 4-8-4 BCD Binary converts to BCD 4-8-5 ASCI Hex. converts to ASCII 4-8-6 HEX ASCII converts to Hex. 4-8-7 DECO Coding 4-8-8 ENCO High bit coding 4-8-9 ENCOL Low bit coding 4-8-10
① D13~D10→Overflow
② D17~D14→D13~D10
③ D21~D18→D17~D14
④ D25~D22→D21~D18
⑤ D 3~D 0→D25~D22
In every scan cycle, loop shift right action will be executed
4 applied instructions
4-8-1.Single word integer converts to double word integer [WTD] 1. Summary
Single word integer converts to double word integer [WTD] 16 bits WTD 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address 16 bits, BIN D Target soft element address 32 bits, BIN
3.Suitable soft components
WTD D0 D10X0
S· D·
High bits Low bits
D11 D10
0 or 1 D0
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description (D0) → (D11,D10) Single Word Double
When single word D0 is positive integer, after executing this instruction, the high bit of double word D10 is 0.
When single word D0 is negative integer, after executing this instruction, the high bit of double word D10 is 1.
4 applied instructions
4-8-2.16 bits integer converts to float point [FLT] 1. Summary
16 bits integer converts to float point [FLT] 16 bits FLT 32 bits DFLT 64 bits FLTD Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement -
2. Operands
Operands Function Data Type
S Source soft element address 16 bits/32 bits/64 bits,BIN D Target soft element address 32 bits/64 bits,BIN
3. Suitable soft components <16 bits>
<32 bits >
DFLT D10 D12
S· D·X0
<64 bits>
FLTD D10 D14
S· D·X0
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ●
D ●
Word
Description (D10) → (D13,D12)
BIN integer Binary float point FLT D10 D12
S· D·X0
(D11,D10)→ (D13,D12)
BIN integer Binary float point
(D13,D12,D11,D10)→ (D17,D16,D15,D14)
BIN integer Binary float point
Convert BIN integer to binary float point. As the constant K ,H will auto convert by the float operation instruction, so this FLT instruction can’t be used.
The instruction is contrary to INT instruction
4 applied instructions
4-8-3.Float point converts to integer [INT] 1. Summary
Float point converts to integer [INT] 16 bits INT 32 bits DINT Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address 16 bits/32 bits, BIN D Target soft element address 16 bits/32 bits, BIN
3. Suitable soft components <16 bits>
INT D10 D20
S· D·X0
<32 bits>
DINT D10 D20
S· D·X0
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ●
D ●
Word
Description (D11,D10) → (D20)
Binary Float BIN integer
Give up the data after the decimal dot
(D11,D10) → (D20,D21)
Binary Float BIN integer
Give up the data after the decimal dot
The binary source number is converted into a BIN integer and stored at the destination device. Abandon the value behind the decimal point.
This instruction is contrary to FLT instruction. When the result is 0, the flag bit is ON
When converting, less than 1 and abandon it, zero flag is ON. The result is over below data, the carry flag is ON. 16 bits operation: -32,768~32,767 32 bits operation: -2,147,483,648~2,147,483,647
4 applied instructions
4-8-4.BCD convert to binary [BIN] 1. Summary
BCD convert to binary [BIN] 16 bits BIN 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address BCD D Target soft element address 16 bits/32 bits, BIN
3. Suitable soft components
BIN D10 D0
S· D·X0
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description Convert and move instruction of Source (BCD) → destination (BIN)
When source data is not BCD code, M8067(Operation error), M8004 (error occurs) As constant K automatically converts to binary, so it’s not suitable for this instruction.
4 applied instructions
4-8-5.Binary convert to BCD [BCD] 1. Summary
Binary convert to BCD [BCD] 16 bits BCD 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address 16 bits/32 bits, BIN D Target soft element address BCD code
3. Suitable soft components
BCD D10 D0
S· D·X0
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
Word
Description Convert and move instruction of source (BIN)→destination (BCD)
This instruction can be used to output data directly to a seven-segment display.
4 applied instructions
4-8-6.Hex. converts to ASCII [ASCI] 1. Summary
Hex. convert to ASCII [ASCI] 16 bits ASCI 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address 2 bits, HEX D Target soft element address ASCII code n Transform character quantity 16 bits, BIN
3. Suitable soft components
ASCI D100 D200 K4
S· D· nX0
The convert result is this
n D
K1 K2 K3 K4 K5 K6 K7 K8 K9
D200 down [C] [B] [A] [0] [4] [3] [2] [1] [8] D200 up [C] [B] [A] [0] [4] [3] [2] [1] D201 down [C] [B] [A] [0] [4] [3] [2] D201 up [C] [B] [A] [0] [4] [3] D202 down [C] [B] [A] [0] [4] D202 up [C] [B] [A] [0] D203 down [C] [B] [A]
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n ● ● ● ● ● ● ●
Word
Description
D·S· Convert each bit of source’s (S) Hex. format data to be ASCII code, move separately to the high 8 bits and low 8 bits of destination (D). The convert alphanumeric number is assigned with n.
is low 8 bits, high 8 bits, store ASCII data. D·
4 applied instructions
4-8-7.ASCII convert to Hex.[HEX]
1. Summary
ASCII converts to Hex. [HEX] 16 bits HEX 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands
Function Date type
S Source soft element address ASCII D Target soft element address 2 bits, HEX n Character quantity 16 bits, BIN
3. Suitable soft components
HEX D200 D100 K4
S· D· nX0
D203 up [C] [B] D204 down [C]
Assign start device: (D100)=0ABCH (D101)=1234H (D102)=5678H
[0]=30H [1]=31H [5]=35H [A]=41H [2]=32H [6]=36H [B]=42H [3]=33H [7]=37H [C]=43H [4]=34H [8]=38H
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n ●
Word
Description
Convert the high and low 8 bits in source to HEX data. Move 4 bits every time to destination . The convert alphanumeric number is assigned by n.
S·
D·
4 applied instructions
The convert of the upward program is the following: 时
n=k4 0 1 0 0 0 0 0 1 0 0 1 1 0 0 0 0D200
41H? [A] 30H? [0]
0 1 0 0 0 0 1 1 0 1 0 1 0 0 1 0D201
43H? [C] 42H? [B]
0 0 0 0 1 0 1 0 1 0 1 1 1 1 0 0D100
0 A B C
4-8-8.Coding [DECO] 1. Summary Transform the ASCII code to Hex numbers.
Coding [DECO] 16 bits DECO s - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Source soft element address ASCII D Target soft element address 2 bits HEX n The coding soft element quantity 16bits, BIN
2. Suitable soft components
(S·)
ASCII Code
HEX Convert
D200 down 30H 0 D200 up 41H A D201 down 42H B D201 up 43H C D202 down 31H 1 D202 up 32H 2 D203 down 33H 3 D203 up 34H 4 D204 down 35H 5
n (D·) D102 D101 D100
1 Not change to
be 0
···0H 2 ··0AH 3 ·0ABH 4 0ABCH 5 ···0H ABC1H 6 ··0AH BC12H 7 ·0ABH C123H 8 0ABCH 1234H 9 ···0H ABC1H 2345H
4 applied instructions
③
② ①
全部转化为 0 ③
① ②
< When is bit unit > n≤16
DX0DECO M10 K3X10
nS· D·
0 1 1
0 0 0 1 0 0 0
X002 X001 X000
M17 M16 M15 M14 M13 M12 M11 M10
7 6 5 4 2 1 0
4
0
< When is word device > n≤4
D0DECO D1 K3X0
nS· D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
n ●
Word
Operands System
X Y M S T C Dn.m
D ● ● ● ● ● ●
Bit
Description D·
The source address is 1+2=3,so starts from M10, the number 3 bit (M13) is 1. If the source are all 0, M10 is 1.
When n=0, no operation, beyond n=0~16, don’t execute the instruction. When n=16, if coding command is soft unit, it’s point is
2^16=65536。 When drive input is OFF, instructions are not executed, the activate
coding output keep on activate.
D·
Low n bits(n≤4) of source address is decoded to target address. n≤3, the high bit of target address all become 0.
When n=0, no operation, beyond n=0~14, don’t execute the instruction.
4 applied instructions
All be 0
② ①
③
4-8-9.High bit coding [ENCO]
1. Summary
Transform the ASCII code to hex numbers High bit coding [ENCO] 16 bits ENCO 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S data address need coding 16 bits, BIN; bit D Coding result address 16 bits, BIN n soft element quantity to save result 16 bits, BIN
3. Suitable soft components < When is bit device > n≤16
M10ENCO D10 K3X0
nS· D·
0 0 0 1 0 1 0M17 M16 M15 M14 M13 M12 M11 M10
7 6 5 4 2 1 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1D10b15
b0
4
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n ●
Word
Operands System
X Y M S T C Dn..m
S ● ● ● ● ● ●
Bit
Description S·
4 applied instructions
被忽视
All be 0
① ②
③
< When is word device > n≤4
D0ENCO D1 K3X1
nS· D·
0 1 0 1 0 1 0 1 0 0 0 0 1 0 1 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1
7 6 5 4 2 1 0
D0
D1b15
b15 b0
b0
4
If many bits in the source ID are 1, ignore the low bits. If source ID are all 0, don’t execute
the instructions. When drive input is OFF, the instruction is not executed, encode output don’t change. When n=8, if encode instruction’s “S” is bit unit, it’s point number is 2^8=256
4-8-10.Low bit coding [ENCOL] 1. Summary
Transform the ASCII to hex numbers. Low bit coding [ENCOL] 16 bits ENCOL 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need coding 16bit,BIN;bit D Soft element address to save coding result 16bit,BIN n The soft element quantity to save result 16bit,BIN
3. Suitable soft components
S·
4 applied instructions
All be 0
② ①
③
被忽视
All be 0
① ②
③
<if is bit device > n≤16
M10ENCOL D10 K3X0
nS· D·
0 1 0 1 0 0 0M17 M16 M15 M14 M13 M12 M11 M10
7 6 5 4 2 1 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1D10b15
b0
4
< if is word device> n≤4
D0ENCOL D1 K3X1
nS· D·
0 1 0 1 0 1 0 1 0 0 1 0 1 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1
7 6 5 4 2 1 0
D0
D1b15
b15 b0
b0
4
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
D ● ● ● ● ● ●
n ●
Word
Operands System
X Y M S T C Dn.m
S ● ● ● ● ● ●
Bit
Description S·
S·
If many bits in the source ID are 1, ignore the high bits. If source ID are all 0, don’t execute the instructions。
When drive input is OFF, the instruction is not executed, encode output don’t change
When n=8, if encode instruction’s is bit unit, it’s point number is 2^8=256 S·
4 applied instructions
4-9.Floating Operation
Mnemonic Function Chapter ECMP Float Compare 4-9-1 EZCP Float Zone Compare 4-9-2 EADD Float Add 4-9-3 ESUB Float Subtract 4-9-4 EMUL Float Multiplication 4-9-5 EDIV Float Division 4-9-6 ESQR Float Square Root 4-9-7 SIN Sine 4-9-8 COS Cosine 4-9-9 TAN Tangent 4-9-10 ASIN ASIN 4-9-11 ACOS ACOS 4-9-12 ATAN ATAN 4-9-13
4 applied instructions
4-9-1.Float Compare [ECMP] 1. Summary
Float Compare [ECMP] 16 bits - 32 bits ECMP Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need compare 32 bits, BIN S2 Soft element address need compare 32 bits, BIN D Compare result bit
3. Suitable soft components
ECMP D10 D20 M0
M0
M1
M2
X0D·S1· S2·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
Word
Operands System
X Y M S T C Dn.m
D ● ● ●
Bit
(D11,D10) : (D21,D20)→ M0,M1,M2 Binary Floating Binary Floating
Description
(D11,D10) > (D21<D20)
Binary Floating Binary Floating
(D11,D10) = (D21<D20)
Binary Floating Binary Floating
(D11,D10) < (D21<D20)
Binary Floating Binary Floating
The status of the destination device will be kept even if the ECMP instruction is
deactivated.
4 applied instructions
ECMP K500 D100 M10X0
4-9-2.Float Zone Compare [EZCP] 1. Summary
Float Zone Compare [EZCP] 16 bits - 32 bits EZCP Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need compare 32 bits, BIN S2 Upper limit of compare data 32 bits, BIN S3 Lower limit of compare data 32 bits, BIN D The compare result soft element address bit
3.Suitable soft components
The binary float data of S1 is compared to S2. The result is indicated by 3 bit devices specified with the head address entered as D
If a constant K or H used as source data, the value is converted to floating point before the addition operation.
(K500)∶ (D101,D100)→M10,M11,M12
Binary converts Binary floating
to floating
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
S3 ● ● ● ● ● ● ●
Word
Operands System
X Y M S T C Dn..m
D ● ● ●
Bit
4 applied instructions
Compare a float range with a float value..
EZCP D10 D20 D0
M3
M4
M5
X0S1· S2·
M3
S3· D·
EZCP K10 K2800 D5 M0X0
Description
(D1,D0) < (D11,D10) ON
Binary Floating Binary Floating
(D11,D10) ≤ (D1,D0 ) ≤(D21,D20) ON
Binary Floating Binary Floating Binary Floating
(D1,D0) > (D21,D20) ON
Binary Floating Binary Floating
The status of the destination device will be kept even if the EZCP instruction
is deactivated.
The data of S1 is compared to the data of S2. The result is indicated by 3 bit devices specified with the head address entered as D.
If a constant K or H used as source data, the value is converted to floating point before the addition operation.
(K10)∶ [D6,D5]∶ (K2800)→ M0,M1,M2
Binary converts Binary Floating Binary converts
to Floating to Floating
Please set S1<S2, when S2>S1, see S2 as the same with S1 and compare them
4 applied instructions
4-9-3.Float Add[EADD] 1. Summary
Float Add [EADD] 16 bits - 32 bits EADD Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need to add 32 bits, BIN S2 Soft element address need to add 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
EADD D10 D20 D50
S1· S2· D·X0
EADD D100 K1234 D110X1
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D11,D10) + (D21,D20) → (D51,D50)
Binary Floating Binary Floating Binary Floating
The floating point values stored in the source devices S1 and S2 are algebraically added and the result stored in the destination device D.
If a constant K or H used as source data, the value is converted to floating point before the addition operation.
(K1234) + ( D101,D100) → (D111,D110)
Binary converts to Floating Binary Floating Binary Floating
The same device may be used as a source and as the destination. If this is the case then, on continuous operation of the EADD instruction, the result of the previous operation will be used as a new source value and a new result calculated. This will happen every program scan unless the pulse modifier or an interlock program is used.
4 applied instructions
4-9-4.Float Sub[ESUB] 1. Summary
Float Sub [ESUB] 16 bits - 32 bits ESUB Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need to subtract 32 bits, BIN S2 Soft element address need to subtract 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
ESUB D10 D20 D50
S1· S2· D·X0
ESUB D100K1234 D110X1
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D11,D10) - (D21,D20) → (D51,D50)
Binary Floating Binary Floating Binary Floating
The floating point value of S2 is subtracted from the floating point value of S1 and the result stored in destination device D.
If a constant K or H used as source data, the value is converted to floating point before the addition operation。
(K1234) - (D101,D100) → (D111,D110)
Binary converts to Floating Binary Floating Binary Floating
The same device may be used as a source and as the destination. If this is the case then, on continuous operation of the EADD instruction, the result of the previous operation will be used as a new source value and a new result calculated. This will happen every program scan unless the pulse modifier or an interlock program is used.
4 applied instructions
4-9-5.Float Mul[EMUL] 1. Summary
Float Multiply [EMUL] 16 bits - 32 bits EMUL Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need to multiply 32 bits, BIN S2 Soft element address need to multiply 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
EMUL D10 D20 D50
S1· S2· D·X0
EMUL D100K100 D110X1
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D11,D10) × (D21,D20)→ (D51,D50)
Binary Floating Binary Floating Binary Floating
The floating value of S1 is multiplied with the floating value point value of S2. The result of the multiplication is stored at D as a floating value
If a constant K or H used as source data, the value is converted to floating point before the addition operation.
(K100) × (D101,D100) → (D111,D110)
Binary converts to Floating Binary Floating Binary Floating
4 applied instructions
4-9-6.Float Div[EDIV] 1. Summary
Float Divide [EDIV] 16 bits - 32 bits EDIV Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S1 Soft element address need to divide 32 bits, BIN S2 Soft element address need to divide 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
EDIV D10 D20 D50
S1· S2· D·X0
EDIV D100 K100 D110X1
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ● ● ●
S2 ● ● ● ● ● ● ●
D ● ● ● ●
word
Description
(D11,D10) ÷ (D21,D20)→ (D51,D50)
Binary Floating Binary Floating Binary Floating
The floating point value of S1 is divided by the floating point value of S2. The result of the division is stored in D as a floating point value. No remainder is calculated.
If a constant K or H used as source data, the value is converted to floating point before the addition operation
(D101,D100) ÷ (K100) →(D111,D110)
Binary converts to Floating Binary Floating Binary Floating
If S2 is 0, the calculate is error, the instruction can not work
4 applied instructions
4-9-7.Float Square Root [ESQR] 1. Summary
Float Square Root [ESQR] 16 bits - 32 bits ESQR Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S The soft element address need to do square root 32 bits, BIN D The result address 32 bits, BIN
3. Suitable soft components
ESQR D10 D20X0
S· D·
ESQR K1024 D110X1
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
(D11,D10) →(D21,D20)
Binary Floating Binary Floating Description
A square root is performed on the floating point value in S the result is stored in D If a constant K or H used as source data, the value is converted to floating point before
the addition operation.
(K1024) → (D111,D110)
Binary converts to Floating Binary Floating
When the result is zero, zero flag activates. Only when the source data is positive will the operation be effective. If S is negative
then an error occurs and error flag M8067 is set ON, the instruction can’t be executed.
4 applied instructions
4-9-8.Sine[SIN] 1. Summary
Float Sine[SIN] 16 bits - 32 bits SIN Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S The soft element address need to do sine 32 bits, BIN D The result address 32 bits, BIN
3. Suitable soft components
SIN D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D51,D50) → (D61,D60)SIN
Binary Floating Binary Floating
This instruction performs the mathematical SIN operation on the floating point value in S (angle RAD). The result is stored in D.
RAD value (angle×π/180)
Assign the binary floating value
SIN value
Binary Floating
4 applied instructions
4-9-9.Cosine[SIN] 1. Summary
Float Cosine[COS] 16 bits - 32 bits COS Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need to do cos 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
COS D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D51,D50)RAD → (D61,D60)COS
Binary Floating Binary Floating
This instruction performs the mathematical COS operation on the floating point value in S (angle RAD). The result is stored in D。
RAD value (angle×π/180)
Assign the binary floating value
COS value
Binary Floating
4 applied instructions
4-9-10.TAN [TAN] 1. Summary
TAN [TAN] 16 bits - 32 bits TAN Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
- Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need to do tan 32bit,BIN D Result address 32bit,BIN
3. Suitable soft components
TAN D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Description
(D51,D50)RAD → (D61,D60)TAN
Binary Floating Binary Floating
This instruction performs the mathematical TAN operation on the floating point value in S. The result is stored in D.
RAD value (angle×π/180)
Assign the binary floating value
TAN value
Binary Floating
4 applied instructions
4-9-11.ASIN [ASIN] 1. Summary
ASIN [ASIN] 16 bits - 32 bits ASIN Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
V3.0 and above version Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need to do arcsin 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
ASIN D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D51,D50)ASIN → (D61,D60)RAD
Binary Floating Binary Floating
This instruction performs the mathematical ASIN operation on the floating point value in S. The result is stored in D.
ASIN value
Binary Floating
RAD value (angle×π/180)
Assign the binary floating value
4 applied instructions
4-9-12.ACOS [ACOS] 1. Summary
ACOS [ACOS] 16 bits - 32 bits ACOS Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
V3.0 and above Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need to do arccos 32 bits, BIN D Result address 32 bits, BIN
3. Suitable soft components
ACOS D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D51,D50)ACOS → (D61,D60)RAD
Binary Floating Binary Floating
Calculate the arcos value(radian), save the result in the target address
TCOS value
Binary Floating
RAD value (angle×π/180)
Assign the binary floating value
4 applied instructions
4-9-13.ATAN [ATAN] 1. Summary
ATAN [ATAN] 16 bits - 32 bits ACOS Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
V3.0 and above Software
requirement
-
2. Operands
Operands Function Data Type
S Soft element address need to do arctan 32 bit, BIN D Result address 32 bit, BIN
3.Suitable soft components
ATAN D50 D60X0
S· D·
D51 D50
D61 D60
S·
D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ●
D ● ● ● ●
Word
Description
(D51,D50)ATAN → (D61,D60)RAD
Binary Floating Binary Floating
Calculate the arctan value ( radian), save the result in the target address
ATAN value
Binary Floating
RAD value (angle×π/180)
Assign the binary floating value
4 applied instructions
4-10.RTC Instructions
Mnemonic Function Chapter TRD Clock data read 4-10-1 TWR Clock data write 4-10-2
※1: To use the instructions, The Model should be equipped with RTC function;
4 applied instructions
4-10-1.Read the clock data [TRD] 1. Instruction Summary
Read the clock data: Read the clock data: [TRD] 16 bits TRD 32 bits - Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
V2.51 and above Software
requirement
-
2. Operands
Operands Function Data Type
D Register to save clock data 16 bits, BIN 3. Suitable Soft Components
TRD D0X0
D·
Read PLC’s real time clock according to the following format.
The reading source is the special data register (D8013~D8019) which save clock data.
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
D ● ● ●
Functions And Actions
The current time and date of the real time clock are read and stored in the 7 data devices specified by the head address D.
Unit Item
D0 Year
D1 Month
D2 Date
D3 Hour
D4 Minute
D5 Second
D Week
Unit Item Clock data
Special data register for real tim
e clock t
D8018 Year 0-99
D8017 Month 1-12
D8016 Date 1-31
D8015 Hour 0-23
D8014 Minute 0-59
D8013 Second 0-59
D8019 Week 0 (Sun.)-6 (Sat.)
4 applied instructions
4-10-2.Write Clock Data [TWR] 1. Instruction Summary
Write the clock data: Write clock data [TRD] 16 bits - 32 bits TRD Execution
condition
Normally ON/OFF, rising/falling edge
Suitable
Models
XC2.XC3.XC5.XCM
Hardware
requirement
V2.51 and above Software
requirement
-
2. Operands
Operands Function Data Type
S Write the clock data to the register 16 bits, BIN 3. Suitable Soft Components
TWR D0X0
S·
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ● ● ● ●
The 7 data devices specified with the head
address S are used to set a new current value of
the real time clock.
Functions And Actions
Write the set clock data into PLC’s real time clock. In order to write real time clock, the 7 data devices specified with the head address should be pre-set.
S·
Unit Item Clock data
Data for clock setting
D10 Year 0-99
D11 Month 1-12
D12 Date 1-31
D13 Hour 0-23
D14 Minute 0-59
D15 Second 0-59
D16 Week 0 (Sun.)-6 (Sat.)
Unit Item
D8018 Year Special data register for real tim
e clock t
D8017 Month
D8016 Date
D8015 Hour
D8014 Minute
D8013 Second
D8019 Week
4 applied instructions
After executing TWR instruction, the time in real time clock will immediately change to be the new set time. So, when setting the time it is a good idea to set the source data to a time a number of minutes ahead and then drive the instruction when the real time reaches this value.
4 applied instructions
5 HIGH SPEED COUNTER (HSC)
In this chapter we tell high speed counter’s functions, including high speed count
model, wiring method, read/write HSC value, reset etc.
5-1.FUNCTIONS SUMMARY
5-2.HIGH SPEED COUNTER’S MODE
5-3.HIGH SPEED COUNTER’S RANGE
5-4.INPUT WIRING OF HIGH SPEED COUNTER
5-5.INPUT TERMINALS ASSIGNMENT FOR HSC
5-6.READ AND WRITE THE HSC VALUE
5-7.RESET MODE OF HSC
5-8.FREQUENCY MULTIPLICATION OF AB PHASE HSC
5-9.HSC EXAMPLES
5-10.HSC INTERRUPTION
Instructions List for HSC
MNEMONIC FUNCTION CIRCUIT AND SOFT COMPONENTS CHAPTER
READ/WRITE HIGH SPEED COUNTER
HSCR Read HSC
5-6-1
HSCW Write HSC
5-6-2
OUT HSC (High Speed Counter)
3-13
OUT 24 segments HSC Interruption
5-10
RST HSC Reset
3-13
5-1.Functions Summary
XC series PLC has HSC (High Speed Counter) function which is independent
with the scan cycle. Via choosing different counter, test the high speed input signals
with detect sensors and rotary encoders. The highest testing frequency can reach
80KHz.
5-2.HSC Mode
XC series high speed counter’s function has three count modes: Increment Mode,
Pulse+Direction Mode and AB phase Mode;
Under this mode, count and input the pulse signal, the count value increase at each
pulse’s rising edge;
Under this mode, the pulse signal and direction signal are all inputted, the count value
increase or decrease with the direction signal’s status. When the count signal is OFF,
Increment Mode
Pulse+Direction Mode
the count input’s rising edge carry on plus count; When the count signal is ON, the
count input’s rising edge carry on minus count;
Under this mode, the HSC value increase or decrease according to two differential
signal (A phase and B phase). According to the multiplication, we have 1-time
frequency and 4-time frequency two modes, but the default count mode is 4-time
mode.
1-time frequency and 4-time frequency modes are shown below:
l 1-time Frequency
l 4-time Frequency
AB Phase Mode
5-3.HSC Range
HSC’s count range is: K-2,147,483,648 ~ K+2,147,483,647. If the count value
overflows this range, then up flow or down flow appears;
For “up flow”, it means the count value jumps from K+2,147,483,647 to be
K-2,147,483,648, then continue to count; For “down flow”, it means the count value
jumps from K-2,147,483,648 to be K+2,147,483,647 then continue to count.
5-4.HSC Input Wiring
For the counter’s pulse input wiring, things differ with different PLC model and
counter model; several typical input wiring are shown below: (take XC3-48 as the
example):
5-5.HSC ports assignment
Each letter’s Meaning:
U Dir A B
Pulse input Count Direction Judgment
(OFF=increment, ON=decrement)
A phase input B phase input
Normally, X0 and X1 can accept 80KHz frequency under single phase mode and AB phase
mode. Other terminals can accept only 10KHz under single phase mode, 5KHz under AB phase
mode. X can use as normal input terminals when they are not used as high speed input. The
detailed assignment is shown as below:
XC2 series PLC
Increment Pulse+Dir Input AB Phase Mode
C600 C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Max.F 80K 80K 10K 10K 10K 80K 10K 80K 5K
4-times F √
Count
Interrupt √ √ √ √ √ √ √
X000 U U A
X001 U Dir B
X002
* C600、C620、C630 can support 80KHz with special requirement
X003 U U A
X004 Dir B
X005
X006 U
X007 U
X010
X011
X012
XC3-14 PLC
Increment Pulse+Dir Input AB Phase Mode
C600C602C604 C606 C608 C610 C612 C614 C616 C618C620C622 C624 C626 C628 C630C632 C634
*Max.F 10K 10K 10K 10K 10K 10K 5K
4-times F
Count
Interrupt √ √ √ √ √
X000 U U A
X001 Dir B
X002 U
X003 U
X004
X005 U
XC3-19AR-E
Increment Pulse+Dir Input AB Phase Mode
C600C602 C604 C606 C608 C610 C612C614 C616 C618 C620C622 C624 C626 C628 C630C632 C634
Max.F 10K 10K 10K 10K 10K 10K 5K 5K
4-times F √
Count
Interrupt √ √ √ √ √ √
X000 U U A
X001 Dir B
X002 U U A
X003 Dir B
X004 U
X005 U
XC3-24、32 PLC and XC5-48、60 PLC
Increment Pulse+Dir Input AB Phase Mode
C600 C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Max.F 80K 80K 10K 10K 10K 10K 80K 10K 10K 80K 5K 5K
4-times F √ √
Count
Interrupt √ √ √ √ √ √ √ √
X000 U U A
X001 U Dir B
X002
X003 U U A
X004 Dir B
X005
X006 U U A
X007 Dir B
X010
X011 U
X012 U
XC3-48、60 PLC
Increment Pulse+Dir Input AB Phase Mode
C600 C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Max.F 80K 80K 10K 10K 80K 80K 80K 80K
4-times F √
Count
Interrupt √ √ √ √ √ √
X000 U U A
X001 Dir B
X002 U U A
X003 Dir B
X004 U
X005 U
XC5-24/32 PLC、XCM-24/32 PLC
Increment Pulse+Dir Input AB Phase Mode
C600 C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Max.F 80K 10K 80K 80K
4-times F √
Count
Interrupt √ √ √ √
X000 U U A
X001 Dir B
X002
X003 U
5-6.Read/Write HSC value
All high speed counters support read instruction [HSCR] and write instruction
[HSCW], but users need to use hardware V3.1c and above.
5-6-1.Read HSC value [HSCR]
1、Instruction Summary
Read HSC value to the specified register;
Read from HSC [HSCR]/ write to HSC [HSCW]
16 bits
Instruction
- 32 bits
Instruction
HSCR
Execution
condition
Normally ON/OFF,
rising/falling edge
Suitable
models
XC2、XC3、XC5、XCM
Hardware
requirement
V3.1c and above Software
requirement
-
2、Operands
Operands Function Type
S Specify HSC code 32 bits, BIN
D Specify the read/written register 32 bits, BIN
3、Suitable Soft Components
HSCR C630 D10M0
S· D·
X004
X005
X006
system constant module operands
D FD ED TD CD DX DY DM DS K /H ID QD
S ●
D ●
word
FUNCTIONS AND ACTIONS
Sample Program:
5-6-2.Write HSC value [HSCW]
1、Instruction Summary
Write the specified register value into HSC;
Write HSC value [HSCW]
16 bits
Instruction
- 32 bits
Instruction
HSCW
Execution
condition
Normally ON/OFF,
rising/falling edge
Suitable
models
XC2、XC3、XC5、XCM
Hardware
requirement
V3.1c and above Software
requirement
-
2、operands
Operands Function Type
S Specify HSC code 32 bits, BIN
D Specify the read/written register 32 bits, BIN
3、suitable soft components
l When the activate condition is true, read the HSC value in C630 (DWORD) into
D10 (DWORD)
l Instruction HSCR read the HSC value into the specified register, improve HSC
value’s precision.
system constant module operands
D FD ED TD CD DX DY DM DS K /H ID QD
S ●
D ●
word
FUNCTIONS AND ACTIONS
HSCW C630 D20M0
S· D·
l When the activate condition is true, write the value in D20 (DWORD) into C630 (DWORD),
the original value is replaced;
l We suggest the users to apply high speed counter only with HSCR and HSCW, not with other
instructions like DMOV, LD>, DMUL etc. and users must run after converting HSC to be
other registers.
5-7.HSC Reset Mode
Reset HSC via software:
M0
M1
( )C600 K2000
( )C600
R↑
5-8.AB Phase counter multiplication setting
About AB phase counter, modify the frequency multiplication value via setting
FLASH data register FD8241, FD8242, FD8243. If the value is 1, it is 1-time
frequency, if it is 4, it is 4-time frequency.
In the above graph, when M0 is ON, C600 starts to count the input pulse on X0;
when M1 changes from OFF to be ON, reset C600, clear the count value
Register Function Set Value Meaning
1 1-time frequency FD8241 Frequency multiplication of C630
4 4-time frequency
1 1-time frequency FD8242 Frequency multiplication of C632
4 4-time frequency
1 1-time frequency FD8243 Frequency multiplication of C634
4 4-time frequency
5-9.HSC Example
Below, we take XC3-60 PLC as the example, to introduce HSC’s program form;
l When M0 is ON, C600 starts the HSC with the OFF→ON of X000;
l When comes the rising edge of M1, reset HSC C600
l When normally ON coil M8000 is ON, set the value of C600, the set value is
K888888888, read the HSC value (DWORD) into data register D0 (DWORD).
l If the value in C600 is smaller than value in D2, set the output coil Y0 ON; If the
value in C600 equals or be larger than value in D2, and smaller than value in D4,
set the output coil Y1 ON; If the value in C600 equals or be larger than value in
D4, set the output coil Y2 ON;
l When comes the rising edge of M1, reset HSC C600 and stop counting.
l When M4 is ON, C620 starts the HSC with the OFF→ON of X000; judge the
count direction according to the input X001 status (OFF or ON). If X001 is OFF,
it’s increment count; if X001 is ON, it’s decrement count;
l When comes the rising edge of M5, reset HSC C620 and stop counting.
Increment M
ode P
ulse+D
ir Mode
l When M8 is ON, C630 starts to count immediately. Count input via X000 (B
Phase)、X001 (A Phase)
l When the count value exceeds K3000, output coil Y2 is ON;
l When comes the rising edge of M9, reset HSC C630
l When therising edge of initial positive pulse coil M8002 comes, i.e. Each scan
cycle starts, HSC C630 reset and clear the count value.
l When set coil M8000 ON, C630 starts to count, the count value is set to be
K8888888。
l If the count value is greater than K0 but smaller than K100, the output coil Y0 set
ON; If the count value is greater thanK100 but smaller than K200时,the output
coil Y1 set ON; If the count value is greater thanK200, the output coilY2 set ON;
AB
phase mode
Counter Interruption tag
C630 I2501~I2524
C632 I2601~I2624
C634 I2701~I2724
C636 I2801~I2824
C638 I2901~I2924
5-10.高速计数中断
To XC series PLC, each HSC channels has 24 segments 32-bit pre-set value. When the HSC
difference value equals the correspond 24-segment pre-set value, then interruption occures
according to the interruption tag;
To use this function, please use hardware V3.1c or above;
5-10.高速计数中断
(for the program about interruption, please refer chapter 5-10-4)
LD M0 //HSC activate condition M0 (interruption count condition)
OUT C600 K20000 D4000 //HSC value and set the start ID of 24-segment
LDP M1 //activate condition reset
RST C600 //HSC and 24-segment reset (interruption reset)
As shown in the above graph, data register D4000 is the start ID of 24-segment pre-set value
area. Behind it, save each pre-set value in DWORD form. Please pay attention when using HSC:
l If certain pre-set value is 0, it means count interruption stops at this segment;
l Set the interruption pre-set value but not write the correspond interruption program is not
allowed;
l 24-segment interruption of HSC occurs in order. I.e. If the first segment interruption
doesn't happen, then the second segment interruption will not happen;
l 24-segment pre-set value can be specified to be relative value or absolute value. Meantime,
users can specify the et value to be loop or not. But the oop mode can't be used together
with absolute value.
5-10.高速计数中断
In the below table, we list each counter's 24-segment pre-set value to its interruption tag. E.e.:
24-segment pre-set value of counter C600 correspond with the interruption pointer: I1001、I1002、
I1003、⋯I1024.
Increment mode pulse+direction mode AB phase mode
5-10. HSC Interruption
Counter Interruption tag
C600 I1001~I1024
C602 I1101~I1124
C604 I1201~I1224
C606 I1301~I1324
C608 I1401~I1424
Counter Interruption tag
C620 I2001~I2024
C622 I2101~I2124
C624 I2201~I2224
C626 I2301~I2324
C628 I2401~I2424
5-10-1. Instruction Description
5-10-2. Interruption tags to HSC
C610 I1501~I1524
C612 I1601~I1624
C614 I1701~I1724
C616 I1801~I1824
C618 I1901~I1924
E.g. 1, the current value is C630 is 0, the first preset value is 10000, the preset value in
segment 2 is -5000, the preset value in segment 3 is 20000. When start to count, the counter's
current value is 10000, generate first interruption I2501; When start to count, the counter's current
value is 5000, generate first interruption I2502;When start to count, the counter's current value is
25000, generate first interruption I2503.
See graph below:
E.g. 2, the current value is C630 is 10000, the first preset value is 10000, the preset value in
segment 2 is 5000, the preset value in segment 3 is 20000. When start to count, the counter's
current value is 20000, generate first interruption I2501; When start to count, the counter's current
value is 25000, generate first interruption I2502;When start to count, the counter's current value is
45000, generate first interruption I2503.
See graph below:
HSC 24-segment pre-set value is the difference value, the count value
equals the counter's current value plus the preset value, generate the
interruption. N interruption tags correspond with N interruptionpreset
values. The (N+1) preset value is 0;
Define the presetvalue
C600= K5000+K20000=K25000
C600= K10000+(K-5000)=K5000
C600= K0+K10000=K10000
C630 D4000 D4001 D4002 D4003 D4004 D4005
K0 K10000 K-5000 K20000
I2501
I2502
I2503
5-10.高速计数中断
Mode 1: Unicycle (normal mode)
Not happen after HSC interruption ends. The conditions below can re-start the interruption:
(1) reset the HSC
(2) Reboot the HSC activate condition
Mode 2: Continuous loop
Restart after HSC interruption ends. This mode is especially suitable for the following
application:
(1) continous back-forth movement
(2) Generate cycle interruption according to the defined pulse
Via setting he special auxiliary relays, users can set the HSC interruption to be unicycle mode
or continous loop mode. The loop mode is only suitable with the relative count. The detailed
assignment is show below:
ID HSC ID Setting
M8270 24 segments HSC interruption loop (C600)
M8271 24 segments HSC interruption loop (C602)
M8272 24 segments HSC interruption loop (C604)
M8273 24 segments HSC interruption loop (C606)
M8274 24 segments HSC interruption loop (C608)
M8275 24 segments HSC interruption loop (C610)
M8276 24 segments HSC interruption loop (C612)
M8277 24 segments HSC interruption loop (C614)
M8278 24 segments HSC interruption loop (C616)
M8279 24 segments HSC interruption loop (C618)
M8280 24 segments HSC interruption loop (C620)
OFF: unicycle mode
ON: continous loop mode
C600= K25000+K20000=K45000
C600= K20000+K5000=K25000
C600= K10000+K10000=K20000
C630 D4000 D4001 D4002 D4003 D4004 D4005
K10000 K10000 K5000 K20000
I2501
I2502
I2503
5-10-3. Loop mode of HSC Interruption
M8281 24 segments HSC interruption loop (C622)
M8282 24 segments HSC interruption loop (C624)
M8283 24 segments HSC interruption loop (C626)
M8284 24 segments HSC interruption loop (C628)
M8285 24 segments HSC interruption loop (C630)
M8286 24 segments HSC interruption loop (C632)
M8287 24 segments HSC interruption loop (C634)
5-10.高速计数中断
E.g.2:Application on knit-weaving machine (continous loop mode)
The system theory is shown as below: Control the inverter via PLC, thereby control the motor.
Meantime, via the feedback signal from encoder, control the knit-weaving machine and realize the
precise position.
5-10-4. Example of HSC Interruption
Below is PLC program: Y2 represents forward output signal; Y3 represents backward output
signal; Y4 represents output signal of speed 1; C340: Back-forth times accumulation counter;
C630: AB phase HSC;
FEND
I2501
M8000 Y4S
IRET
IRET
M8000( )
M8285S
Y2S( )
Y2
OUT C340 K1000000
DMOV K75000 D4000
M8000
DMOV K15000 D4002
DMOV K-75000 D4004
DMOV K-15000 D4006
M8000
OUT C630 D4000K30000000
M8000HSCR C630 D200
( )
I2502
M8000 Y4R( )
Y2R( )
Y3S( )
I2503
M8000 Y4S( )
IRET
I2504
IRET
M8000 Y3R( )
Y4R( )
Y2S( )
Instruction List Form:
LD M8002 //M8002 is initial positive pulse coil
SET M8285 //special auxiliary relay set ON, to enable C630 continuous loop
SET Y2 //set output coil Y2 (i.e. Start run forth)
LDP Y2 //knit-weaving machine back-forth times counter's activate condition Y2 (forth rising edge activate)
OUT C340 K1000000 //counter C340 starts to count
LD M8000 //M8000 is normally ON coil
DMOV K75000 D4000 //set segment-1 ID D4000 to be K75000,
DMOV K15000 D4002 //set segment-2 D4002 to be K15000,
DMOV K-75000 D4004 //set segment-3 D4004 to be K-75000,
DMOV K-15000 D4006 //set segment-4 D4004 to be K-15000,
LD M8000 //M8000 is normally ON coil
OUT C630 K30000000 D4000 //HSC and start ID of 24-segment
LD M8000 //M8000 is normally ON coil
HSCR C630 D200 //read the HSC value of C630 to D200
FEND //main program end
I2501 //interruption tag of segment 1
LD M8000 //M8000 is normally ON coil
SET Y4 //output coil Y4 set (low-speed run with speed 1)
IRET //interruption return tag
I2502 ///interruption tag of segment 2
LD M8000 //M8000 is normally ON coil
RST Y4 //output coil Y4 reset (low-speed run stop)
RST Y2 //output coil Y2 reset (run forward stops)
SET Y3 //output coil Y3 set (back running)
IRET //interruption return tag
I2503 ///interruption tag of segment 3
LD M8000 //M8000 is normally ON coil
SET Y4 //output coil Y4 set (low-speed run with speed 1)
IRET //interruption return tag
I2504 ///interruption tag of segment 4
LD M8000 //M8000 is normally ON coil
RST Y3 //output coil Y3 reset (back running stop)
RST Y4 //output coil Y4 reset (low-speed run stop)
SET Y2 //output coil Y2 set (run forward)
IRET //interruption return tag
6 PULSE OUTPUT
In this chapter we tell the pulse function of XC series PLC. The content includes pulse output instructions, input/output wiring, notes and relate coils and registers etc.
6-1.Functions Summary
6-2.Pulse Output Types and Instructions
6-3.Output Wiring
6-4.Notes
6-5.Sample Programs
6-6.Coils and Registers Relate To Pulse Output
Pulse Output Instructions List
Mnemonic Function Circuit And Soft Device Chapter
PULSE OUTPUT
PLSY
Unidirectional ration pulse output without ACC/DEC time change
PLSY S1 S2 D 6-2-1
PLSF Variable frequency pulse output
PLSF S D 6-2-2
PLSR
Ration pulse output with ACC/DEC speed
PLSR S1 S2 S3 D 6-2-3
PLSNEXT/ PLSNT
Pulse Section Switch
PLSNT S 6-2-4
STOP Pulse Stop STOP S 6-2-5
PLSMV Refresh Pulse Nr. immediately
PLSMV S D 6-2-6
ZRN Original Return
ZRN S1 S2 S3 D 6-2-7
DRVI Relative Position Control
DRVI S1 S2 S3 D1 D2 6-2-8
DRVA Absolute Position Control
DRVA S1 S2 S3 D1 D2 6-2-9
PLSA
Absolute Position multi-section pulse control
PLSA S1 S2 D 6-2-10
PTO
Relative position multi-section pulse control
6-2-11
PTOA Absolute position 6-2-12
PTO D0 Y0M0 S1· D1·
Y1
D2·
PTOA D0 Y0M0 S1· D1·
Y1
D2·
multi-section pulse control
PSTOP Pulse stop
6-2-13
PTF
Variable frequency single-section pulse output
6-2-14
6-1.Functions Summary Generally, XC3 and XC5 series PLC are equipped with 2CH pulse output function. Via different instructions, users can realize unidirectional pulse output without ACC/DEC speed; unidirectional pulse output with ACC/DEC speed; multi-segments, positive/negative output etc., the output frequency can reach 200K Hz.
※1: To use pulse output, please choose PLC with transistor output, like XC3-14T-E
or XC3-60RT-E etc. ※2: XC5 series 32I/O PLC has 4CH (Y0, Y1, Y2, Y3) pulse output function. ※3: XCM series 32/24 have 4 CH pulse output; XCC series has 5 CH pulse output; XCM-60 has 10 CH pulse output. ※4: Pulse output terminal Y1 cannot be used together with expansion BD.
PSTOP Y0 K1M0
S1· S2·
PTF D0 Y0M0
S1· D1·
Y1
D2·
6-2.Pulse Output Types and Instructions
6-2-1.Unidirectional ration pulse output without ACC/DEC time change [PLSY]
1、Instruction Summary Instruction to generate ration pulse with the specified frequency;
Unidirectional ration pulse output without ACC/DEC time change [PLSY] 16 bits instruction
PLSY 32 bits instruction
DPLSY
Execution condition
Normally ON/OFF coil Suitable models
XC2, XC3, XC5, XCM, XCC
Hardwarere quirement
- Software requirements
-
2、Operands
Operands Function Type S1 Specify the frequency’s value or register ID 16 bits/32 bits, BIN S2 Specify the pulse number or register’s ID 16 bits /32 bits, BIN D Specify the pulse output port bit
3、Suitable soft components 《16 bits instruction》
PLSY K30 D1 Y0M0
S1· S2· D·
M8170RST M0
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D ●
Bit
Functions And Actions
Frequency Range: 0~32767Hz; Pulse Quantity Range: 0~K32767; Pulse output from Y000 or Y001 only; When M0 is ON, PLSY instruction output 30Hz pulse at Y0, the pulse
number is decided by D1, M8170 is set ON only when sending the pulse.
《32 bits instruction》
DPLSY K30 D1 Y0M0
S1· S2· D·
M8170RST M0
《continuous or limited pulse number》
When finish sending the set pulse number, stop outputting automatically
Note: T1 is pulse start time, T2 is pulse end time.
Frequency Range: 0~200KHz; Pulse Quantity Range: 0~K2147483647; Pulse output from Y000 or Y001 only; When M0 is ON, DPLSY instruction output 30Hz pulse at Y0, the pulse
number is decided by D2D1, M8170 is set ON only when sending the pulse. When the output pulse number reaches the set value, stop sending the pulse, M8170 is set to be OFF, reset M0;
Output Mode
Limited pulse output
Set pulse number
Example
Pulse frequency=1000Hz, pulse quantity 20K, no acceleration/deceleration and single direction pulse output:
Note: D0 is pulse frequency, D2 is pulse quantity. D0=1000, D2=20000. If the control object is stepping/servo motor, we recommend users not use this instruction, to avoid the motor losing synchronism. PLSR is available.
6-2-2.Variable Pulse Output [PLSF] PLSF has 4 control modes. Mode 1: changeable frequency continuous pulse output PLSF 1、Instruction Summary
Instruction to generate continuous pulse in the form of variable frequency Variable Pulse Output [PLSF] 16 bits Instruction
PLSF 32 bits Instruction
DPLSF
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type
Items to Note
S Specify the frequency or register ID 16 bits/32 bits, BIN D Specify pulse output port bit
3、suitable soft components 《16 bit instruction form》
PLSF D0 Y0M0
S· D·
《32 bit instruction form》
DPLSF D0 Y0M0
S· D·
Frequency range: 5Hz~200KHz (when the set frequency is lower than 5Hz, output 5Hz) Pulse can only be output at Y0 or Y1. With the changing of setting frequency in D0, the output pulse frequency changes at Y0 Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency continuous pulse output.
Frequency range: 5Hz~32767Hz (when the set frequency is lower than 5Hz, output 5Hz) Pulse can only be output at Y0 or Y1. With the changing of setting frequency in D0, the output pulse frequency changes at Y0 Accumulate pulse number in register D8170 (DWord) When pulse frequency is 0, the pulse output end There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the
condition is off. It is fit for changeable frequency continuous pulse output.
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D ●
Bit
Functions And Actions
Output Mode
Continuous output pulse with the set frequency until stop output via the instruction
Note: T1 is pulse start time, T2 is pulse end time. Mode2: changeable frequency continuous pulse output (with direction) PLSF 1、Instruction Summary
Instruction to generate continuous pulse in the form of variable frequency (with direction) Variable Pulse Output (with direction) [PLSF] 16 bits Instruction
PLSF 32 bits Instruction
DPLSF
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
V3.3 and above Software requirement
V3.3 and above
2、Operands
Operands Function Type S Specify the frequency or register ID 16 bits/32 bits, BIN D1 Specify pulse output port bit D2 Specify pulse direction output port bit
3、suitable soft components
Continuous pulse output
《16 bit instruction form》
PLSF D0 Y0M0
S· D1·
Y2
D2·
Frequency range: 5Hz~32767Hz (when the set frequency is lower than 5Hz, output 5Hz) Pulse can only be output at Y0 or Y1. The negative/positive of pulse frequency decides the pulse direction ( direction port output
when the frequency is positive) The direction output can control the rotation direction of motor (CW/CCW) With the changing of setting frequency in D0, the output pulse frequency changes at Y0 Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency continuous pulse output. 《32 bit instruction form》
Frequency range: 5Hz~200KHz (when the set frequency is lower than 5Hz, output 5Hz) Pulse can only be output at Y0 or Y1. The negative/positive of pulse frequency decides the pulse direction ( direction port output
when the frequency is positive) The direction output can control the rotation direction of motor (CW/CCW) With the changing of setting frequency in D0, the output pulse frequency changes at Y0 Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency continuous pulse output.
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Bit
Functions And Actions
Continuous output pulse with the set frequency until stop output via the instruction
Note: T1 and T3 is pulse start time, T2 and T4 is pulse end time. Mode3: changeable frequency limited quantity pulse output PLSF 1、Instruction Summary
Instruction to generate changeable frequency limited quantity pulse Variable frequency limited quantity pulse output [PLSF] 16 bits Instruction
PLSF 32 bits Instruction
DPLSF
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
V3.3 and above Software requirement
V3.3 and above
2、Operands
Operands Function Type S1 Specify the frequency or register ID 16 bits/32 bits, BIN S2 Specify pulse quantity or register ID 16 bits/32 bits, BIN D Specify pulse output port bit
3、suitable soft components
Continuous pulse output
Output Mode
《16 bit instruction form》
PLSF D0 D2M0
S1· S2·
Y0
D·
M8170RST M0
Frequency range: 5Hz~32767Hz (when the set frequency is lower than 5Hz, output 5Hz) Pulse quantity range: K0~K32767 Pulse can only be output at Y0 or Y1 With the changing of setting frequency in D0, the output pulse frequency changes at Y0 When the pulse frequency is 0Hz, the pulse output end Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency limited quantity pulse output. When M0 is ON, PLSF output the pulse at Y0 with frequency D0 (word), pulse quantity D2
(word). M8170 is ON when the pulse is outputting. The pulse stops output when the pulse quantity reaches the limit value. And the M8170 is off, M0 is off.
《32 bit instruction form》
DPLSF D0 D2M0
S1· S2·
Y0
D·
M8170RST M0
Frequency range: 5Hz~200KHz (when the set frequency is lower than 5Hz, output 5Hz) Pulse quantity range: K0~K2147483647 Pulse can only be output at Y0 or Y1 With the changing of setting frequency in D0, the output pulse frequency changes at Y0
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D1 ●
Bit
Functions And Actions
When the pulse frequency is 0Hz, the pulse output end Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency limited quantity pulse output. When M0 is ON, PLSF output the pulse at Y0 with frequency D0 (Dword), pulse quantity D2
(Dword). M8170 is ON when the pulse is outputting. The pulse stops output when the pulse quantity reaches the limit value. And the M8170 is off, M0 is off.
Continuous output pulse with the set frequency and limited pulse quantity
Note: T1 is pulse start time, T2 is pulse end time. Mode4: changeable frequency limited quantity pulse output PLSF (with direction) 1、Instruction Summary
Instruction to generate changeable frequency limited quantity pulse (with direction) Variable frequency limited quantity pulse output (with direction) [PLSF] 16 bits Instruction
PLSF 32 bits Instruction
DPLSF
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
V3.3 and above Software requirement
V3.3 and above
2、Operands
Operands Function Type S1 Specify the frequency or register ID 16 bits/32 bits, BIN S2 Specify pulse quantity or register ID 16 bits/32 bits, BIN
Continuous pulse output
Output Mode
When the pulse quantity
reaches the limited value,
the pulse stop output
D1 Specify pulse output port bit D2 Specify pulse direction output port bit
3、suitable soft components 《16 bit instruction form》
PLSF D0 D2M0
S1· S2·
Y0
D1·
M8170RST M0
Y2
D2·
Frequency range: 5Hz~32767Hz (when the set frequency is lower than 5Hz, output 5Hz) Pulse quantity range: K0~K32767 Pulse can only be output at Y0 or Y1 The negative/positive of pulse frequency decides the pulse direction ( direction port output
when the frequency is positive) The direction output can control the rotation direction of motor (CW/CCW) With the changing of setting frequency in D0, the output pulse frequency changes at Y0 When the pulse frequency is 0Hz, the pulse output end Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency limited quantity pulse output. When M0 is ON, PLSF output the pulse at Y0 with frequency D0 (word), pulse quantity D2
(word). M8170 is ON when the pulse is outputting. The pulse stops output when the pulse quantity reaches the limit value. And the M8170 is off, M0 is off.
《32 bit instruction form》
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Bit
Functions And Actions
DPLSF D0 D2M0
S1· S2·
Y0
D1·
M8170RST M0
Y2
D2·
Frequency range: 5Hz~200KHz (when the set frequency is lower than 5Hz, output 5Hz) Pulse quantity range: K0~K2147483647 Pulse can only be output at Y0 or Y1 With the changing of setting frequency in D0, the output pulse frequency changes at Y0 When the pulse frequency is 0Hz, the pulse output end Accumulate pulse number in register D8170 (DWord) There is no acceleration/deceleration time when the frequency changed When the condition is on, it output the pulse with changeable frequency until the condition is
off. It is fit for changeable frequency limited quantity pulse output. When M0 is ON, PLSF output the pulse at Y0 with frequency D0 (Dword), pulse quantity D2
(Dword). M8170 is ON when the pulse is outputting. The pulse stops output when the pulse quantity reaches the limit value. And the M8170 is off, M0 is off.
Continuous output pulse with the set frequency and limited pulse quantity
Continuous pulse output
Output Mode
When the pulse quantity
reaches the limited value,
the pulse stop output
When the pulse quantity reaches the limited
value, the pulse stop output
6-2-3.Multi-segment pulse control at relative position [PLSR] PLSR/DPLSR instruction has two control modes. Below we will introduce one by one; Mode 1: segment single direction pulse output PLSR 1、Instruction Summary
Generate certain pulse quantity (segmented) with the specified frequency and acceleration/deceleration time Segmented single direction pulse output [PLSR] 16 bits Instruction
PLSR 32 bits Instruction
DPLSR
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands Operands Function Type S1 Specify the soft component’s start ID of the segmented
pulse parameters 16 bit/ 32 bit, BIN
S2 Specify acceleration/deceleration time or soft component’s ID
16 bit/ 32 bit, BIN
D Specify the pulse output port Bit
3、suitable soft components
《16 bit instruction form》
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● ●
Word
operands system
X Y M S T C Dn.m
D ●
Bit
Functions And A
PLSR D0 D100 Y0
RST M0
M0
M8170
S1· S2· D·
《32 bit instruction form》
DPLSR D0 D100 Y0
RST M0
M0
M8170
S1· S2· D·
Note: the address of pulse segment must be continuous and the pulse frequency and quantity of segment N+1 must be 0. Acceleration/deceleration time address cannot behind segment N.
M8170
M0
Segment 1D0, D1
Segment 2D2, D3
Segment 3D4, D5
The parameters’ address is a section starts from Dn or FDn. In the above example (16bit instruction form): D0 set the first segment pulse’s highest frequency, D1 set the first segment’s pulse number, D2 set the second segment pulse’s highest frequency, D3 set the second segment’s pulse number, …… if the set value in Dn, Dn+1 is 0, this represents the end of segment, the segment number is not limited.
For 32 bit instruction DPLSR, D0, D1 set the first segment pulse’s highest frequency, D2, D3 set the first segment’s pulse number, D4, D5 set the second segment pulse’s highest frequency, D6, D7 set the second segment’s pulse number……
Acceleration/deceleration time is the time from the start to the first segment’s highest frequency. Meantime, it defines the slope of all segment’s frequency to time. In this way the following acceleration/deceleration will perform according to this slope.
Pulse can be output at only Y000 or Y001 Frequency range: 0~32767Hz (16 bits instruction), 0~200KHz (32 bits instruction) Acceleration/deceleration time : 0~65535 ms
Name Pulse frequency (Hz) Pulse quantity Segment 1 1000 2000 Segment 2 200 1000 Segment 3 3000 6000 Segment 4 800 1600 Segment 5 100 800 Segment 6 1200 3000 Acceleration/deceleration time 100ms
Use 32-bit instruction DPLSR, the address is shown as the following table: Name Pulse
frequency(Hz) Frequency address (Dword)
Pulse quantity pulse quantity address (Dword)
Segment 1 1000 D1, D0 2000 D3, D2 Segment 2 200 D5, D4 1000 D7, D6 Segment 3 3000 D9, D8 6000 D11, D10 Segment 4 800 D13, D12 1600 D15, D14 Segment 5 100 D17, D16 800 D19, D18 Segment 6 1200 D21, D20 3000 D23, D22 Acceleration/deceleration time
100ms D51, D0
Note: the 4 registers behind segment 6 must be 0 (D27, D26, D25, D24), which means the pulse
output end; for 16 bits instruction, D25, D24 must be 0.
Example Send 6 segments of pulse, the pulse frequency and quantity please see below table:
Mode 2: segmented dual-direction pulse output PLSR 1、Instruction Summary Generate certain pulse quantity with the specified frequency、acceleration/deceleration time and pulse direction;
Segmented dual-directional pulse output [PLSR] 16 bits Instruction
PLSR 32 bits Instruction
DPLSR
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands Operands Function Type S1 Specify the soft component’s start ID of the segmented pulse
parameters 16 bit/ 32 bit, BIN
S2 Specify acceleration/deceleration time or soft component’s ID 16 bit/ 32 bit, BIN
D1 Specify the pulse output port Bit D2 Specify the pulse output direction’s port Bit
3、suitable soft components 《16 bit instruction form》
PLSR D0 D100 Y0
RST M0
M0
M8170
S1· S2·
Y3
D1· D2·
The parameters’ address is a section starts from Dn or FDn. In the above example: D0 set the
first segment pulse’s highest frequency, D1 set the first segment’s pulse number,D2 set the second segment pulse’s highest frequency, D3 set the second segment’s pulse number, …… if the set value in Dn, Dn+1 is 0, this represents the end of segment, the segment number is not limited.
For 32 bit instruction DPLSR, D0, D1 set the first segment pulse’s highest frequency, D2, D3 set the first segment’s pulse number, D4, D5 set the second segment pulse’s highest frequency, D6, D7 set the second segment’s pulse number……
Acceleration/deceleration time is the time from the start to the first segment’s highest frequency. Meantime, it defines the slope of all segment’s frequency to time. In this way the following acceleration/deceleration will perform according to this slope.
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● K
Word
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Bit
Functions And Actions
Pulse can be output at only Y0 or Y1 Pulse direction output terminal Y can be specified freely. E.g.: if in S1 (the first segment) the
pulse number is positive, Y output is ON; if the pulse number is negative, Y output is OFF; Note: the pulse direction is decided by the pulse number’s nature (positive or negative) of the first segment.
Frequency range: 0~32767Hz (16 bits), 0~200KHz (32 bits) Pulse number range: 0~K32,767 (16 bits instruction), 0~K2,147,483,647 (32 bits instruction) Acceleration/deceleration time : below 65535 ms
M8170
M0
Segment 1D0, D1
Segment 2D2, D3
Segment 3D4, D5
Name Pulse frequency (Hz) Pulse quantity Segment 1 1000 2000 Segment 2 200 1000 Segment 3 3000 6000 Segment 4 800 1600 Segment 5 100 800 Segment 6 1200 3000 Acceleration/deceleration time 100ms
Use 32bits instruction DPLSR, the address is shown as the following table: Name Pulse frequency
(Hz) Frequency address (Dword)
Pulse quantity Pulse quantity address (Dword)
Segment 1 1000 D1, D0 2000 D3, D2 Segment 2 200 D5, D4 1000 D7, D6 Segment 3 3000 D9, D8 6000 D11, D10 Segment 4 800 D13, D12 1600 D15, D14 Segment 5 100 D17, D16 800 D19, D18 Segment 6 1200 D21, D20 3000 D23, D22 Acceleration/ 100ms D51, D0
例 6 segments pulse output. The pulse frequency and quantity are shown in the following table:
deceleration time Note: the 4 registers behind segment 6 must be 0 (D27, D26, D25, D24), which means the pulse
output end; for 16 bits instruction, D25, D24 must be 0.
6-2-4.Pulse Segment Switch [PLSNEXT]/[PLSNT] 1、Instruction Summary
Enter the next segment of pulse output;
Pulse segment switch [PLSNEXT]/[PLSNT] 16 bits Instruction
PLSNEXT/PLSNT 32 bits Instruction
-
Execution condition
Rising/falling edge Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type D Specify the pulse output port Bit
3、suitable soft components 《16 bit instruction form》
Y0PLSNEXTM1
PLSR D0 D100 Y0M0
D
If the pulse output reaches the highest frequency at the current segment, and output steadily at this frequency; when M1 changes from OFF to ON, then enter the next pulse output with the acceleration/deceleration time; (this instruction is suitable for multi-segment pulse output)
Run the instruction within the acceleration/deceleration time is invalid Instruction PLSNT is the same to PLSNEXT
operands system
X Y M S T C Dn.m
D ●
Bit
Functions And Actions
The object needs to move from A to B to C. The speed of the three segments is different. The position of A, B and C is uncertain. We can use DPLSR and PLSNEXT to make this program. We can use proximity switch in position A, B, C. Connect the proximity to PLC terminal X1, X2, X3. Pulse frequency terminal is Y0, pulse direction terminal is Y2.
Name Pulse frequency (Hz)
Frequency address (Dword)
Pulse quantity Pulse quantity address (Dword)
Segment origin-A 1000 D1, D0 999999999 D3, D2 Segment A-B 3000 D5, D4 999999999 D7, D6 Segment B-C 2000 D9, D8 999999999 D11, D10 Acceleration/ deceleration time
30ms D31, D30
Note: the pulse quantity should be set to a large value to ensure it can reach the proximity switch. Please clear the 4 registers behind segment 3. (D15, D14, D13, D12).
-------- the dashed line represents the original pulse output
Example
Diagram:
6-2-5.Pulse Stop [STOP] 1、Instruction Summary
Stop pulse output immediately; Pulse stop [STOP] 16 bits Instruction
STOP 32 bits Instruction
-
Execution condition
Rising/falling edge Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type D Specify the port to stop pulse output Bit
3、suitable soft components 《16 bit instruction form》
D0PLSR D100 Y0M0
M1
M8170
STOP Y0
RST M0
D
When M0 changes from OFF to be ON, PLSR output pulse at Y0. D0 specify the frequency,
D1 specify the pulse number, D100 specify the acceleration/deceleration time; when the output pulse number reaches the set value, stop outputting the pulse; on the rising edge of M1, STOP instruction stops outputting the pulse at Y0;
When STOP works, the pulse will stop at once even the M0 is not off.
operands system
X Y M S T C Dn.m
D ●
Bit
Functions And Actions
6-2-6.Refresh the pulse number at the port [PLSMV] 1、Instruction Summary
Refresh the pulse number at the port; Refresh the pulse number at the port [PLSMV] 16 bits Instruction
- 32 bits Instruction
PLSMV
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type S Specify the pulse number or soft components’ ID 32bit, BIN D Specify the port to refresh the pulse Bit
3、suitable soft components
operands system
X Y M S T C Dn.m
D ●
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S ● ● ● ● ●
Word
《32 bit instruction form》
When the working table is moving backward, it gets the origin signal X2, execute the
external interruption, PLSMV command run immediately, not effected by the scan cycle. Refresh the pulse number from Y0 and send to D8170;
This instruction is used to clear the accumulation difference caused in pulse control; PLSMV instruction is only for PLSR and DPLSR.
6-2-7.Back to the Origin [ZRN] Method 1: Simple ZRN
1、Instruction Summary
Back to the Origin Back to the Origin [ZRN] 16 bits Instruction
ZRN 32 bits Instruction
DZRN
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
Functions And Actions
2、Operands Operands Function Type S1 Specify the backward speed or soft components’ ID 16/32bit, BIN S2 Specify the creeping speed or soft components’ ID 16/32 bit, BIN S3 Specify the soft components’ ID of the close point’s signal Bit D Specify the pulse output port Bit
3、suitable soft components 《16 bit instruction form》
《32 bit instruction form》
operands system
X Y M S T C Dn.m
S3 ● ●
D ●
Word
Functions And Actions
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Pulse output address: Y0 or Y1 only; XC5 series is Y0~Y3, 3 axis is Y0~Y2, 10 axis is Y0~Y11.
S1 and S2 direction is same and the absolute value of S1 is greater than S2; After driving the instruction, move to signal X3 with origin returning speed S1; When the closed point signal turns from OFF to be ON, decrease the speed to be S2; When the closed point signal X3 turns from OFF to ON, accelerate from origin returning
speed to creeping speed S2. When the closed point signal X3 turns from ON to be OFF, after one scanning period, write
to registers (Y0:[D8171,D8170]=0,Y1:[D8174,D8173]=0) when stopping pulse output; No acceleration/deceleration time when the instruction works at the beginning, the pulse
frequency changes from 0Hz to S1 suddenly The decrease time can be specified by D8230~D8239; please refer to chapter 6-6 for details; Method 2: High precision ZRN
1、Summary
High precision back to the origin Back to the origin [ZRN] 16 bits - 32 bits ZRN Execution condition
Normally ON/OFF coil Suitable models
XC2, XC3, XC5, XCM, XCC
Hardware V3.3 and higher Software V3.3 and higher
2、Operand
Operand Function Type S0 Soft element head address of origin back data block 32 bits, BIN S1 Soft element address of limit signal bit S2 Soft element address of origin auxiliary signal bit S3 Soft element address of origin signal (external
interruption) bit
S4 Soft element address of Z phase signal (external interruption)
bit
D1 Address of pulse output terminal bit D2 Address of pulse output direction terminal bit
3、Suitable soft element
Operand System
X Y M S T C Dn.m
S1、S2 ● ● ● ● ●
S3、S4 ●
D1、D2 ●
Word
Bit
operand System constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S0 ● ● ● ●
《Mode1: no Z phase signal》
《Mode2: with Z phase signal》
Parameter address distribution: (32 bits, 2 bytes) S0 :back to origin speed VH S0+2 :back to origin speed VL S0+4 :creep speed S0+6 :slope of pulse rising and falling S0+8 :initial pulses after back to origin (D8170) S0+10:Z phase count value (for mode2) (A)back start point is behind the origin Mode1: Description: Move towards the origin with speed VH. If it encounters origin auxiliary signal S2, it will decelerate to speed VL with the slope K
(note: if it encounters the origin when decelerating from VH to VL, please modify the pulse slope or origin position to avoid it).
Keep forward with the current speed VL. Decelerate to 0 with the slope K after touching the origin. Start to delay (delay time is FD8209, unit is ms). It accelerates to creep speed with the slope
Description ZRN D0 X0 X1
M0S2·
X2
S3S0·
Y0 Y1
D1 D2S1·
ZRN D0 X0 X1M0
S2·
X2
S3S0·
X3 Y0
D1 D2S1·
Y1
S4·
VL
Slope
VH
Speed=0
Limit Origin Origin auxiliary
Creep speed
K after delaying. Move in reverse direction with creep speed. Stop origin returning when it leaves the origin with creep speed.
Change the pulses (D8170) to setting value.
Note: in this mode, please keep the origin limit switch ON during the process (from touching the origin limit switch at speed VL to stop origin returning)
Mode2:
VL
Slope VH
Speed=0
Limit Origin Origin auxiliary
Creep speed
Count for Z phase signal
Description: Move towards origin with speed VH. If it encounters origin auxiliary signal S2, decelerate to speed VL with slope K. Move forward at speed VL. Decelerate to 0 with slope K when encountering the origin. Start to delay (the delay time is FD8209, unit is ms). Accelerate to creep speed with the slope
K. Move in reverse direction at creep speed. Stop Z phase counting when leaving the origin at creep speed. Stop origin returning when Z phase cumulative value is equal to setting value.
Change the pulses (D8170) to setting value.
Note: in this mode, please keep the origin limit switch ON during the process (from touching the origin limit switch at speed VL to stop origin returning)
(B)the start point is ahead the origin, with limit signal Mode1:
VLSlope
VH
Speed=0
Limit Origin Origin auxiliary
Creep speed
VH
Slope
Description: Move towards origin at speed VH, when touching the limit switch, it decelerate to 0 with
slope K. Start to delay (delay time is FD8209, the unit is ms). Accelerate to speed VH with slope K
after delaying. Run at speed VH. Decelerate to 0 with slope K when encountering origin. Accelerate to speed VL with slope K and move towards origin. Decelerate to 0 with slope K when touching the origin. Start to delay (delay time is FD8209, the unit is ms). Accelerate to creep speed with slope K. Stop after leaving the origin at creep speed.
Change the pulses (D8170) to setting value.
Note: in this mode, please keep the origin limit switch ON during the process (from touching the origin limit switch at speed VL to stop origin returning)
Mode2:
VLSlope
VH
Speed=0
Limit Origin Origin auxiliary
Creep speed
VH
Slope
Count for Z phase signal
Description: Move towards origin at speed VH, decelerate to 0 with slope K when touching the limit
signal. Start to delay (delay time is FD8209, the unit is ms). Accelerate to speed VH with slope K
after delaying. Run at speed VH. Decelerate to 0 with slope K when encountering the origin. Accelerate to speed VL with slope K and move toward origin. Decelerate to 0 with slope K when touching the origin. Start to delay (delay time is FD8209, the unit is ms). Accelerate to creep speed with slope K
after delaying. Start to count Z phase signal after leaving origin at creep speed. Stop origin returning when cumulative value of Z phase signal is equal to setting value. Change the pulses to setting value. (D8170)
Note: in this mode, please keep the origin limit switch ON during the process (from touching the origin limit switch at speed VL to stop origin returning)
6-2-8.Relative position single-segment pulse control [DRVI] 1、Instruction Summary
Relative position single-segment pulse control;
Relative position single-segment pulse control [DRVI] 16 bits Instruction
DRVI 32 bits Instruction
DDRVI
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands Operands Function Type S1 Specify the output pulse value or soft components ID 16/32bit, BIN S2 Specify the output pulse frequency or soft components ID 16/32 bit, BIN D1 Specify the pulse output port Bit D2 Specify the pulse output direction port Bit
3、suitable soft components 《16 bit instruction form》
《32 bit instruction form》
Pulse output ID: only Y0 or Y1; XC5 series is Y0~Y3, 3 axis is Y0~Y2, 10 axis is Y0~Y11 Pulse output direction can specify any Y; Acceleration/deceleration time is specified by D8230 (single word) The relative drive form means: move from the current position (the distance from current
position to target position);
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Word
Functions And Actions
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Confirm the value of current position registers before executing the instruction (D8171, D8170[Y0]/ D8174, D8173[Y1] ……)
The current position of X axis is (100, 0), it will move to target position (3000, 0) at the speed of 1000Hz, pulse output terminal is Y0, direction terminal is Y4. The distance between current position and target position is 2900=3000-100. The DRVI executing diagram is shown as below:
Program:
Example
6-2-9.Absolute position single-segment pulse control [DRVA] 1、Instruction Summary
Absolute position single-segment pulse control Absolute position single-segment pulse control [DRVA] 16 bits Instruction
DRVA 32 bits Instruction
DDRVA
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands Operands Function Type S1 Specify the output pulse value or soft components ID 16/32bit, BIN S2 Specify the output pulse frequency or soft components ID 16/32 bit, BIN D1 Specify the pulse output port Bit D2 Specify the pulse output direction port Bit
3、suitable soft components 《16 bit instruction form》
《32 bit instruction form》
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Word
Functions And Actions
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
(Y0:[D8171,D8170],Y1:[D8174,D8173])
Pulse output ID: only Y0 or Y1; XC5 series is Y0~Y3, 3 axis is Y0~Y2, 10 axis is Y0~Y11 Pulse output direction can specify any Y; Acceleration/deceleration time is specified by D8230 (single word) The relative drive form means: move from the origin position (the position from origin to
target position); Confirm the value of current position registers (D8171, D8170[Y0]/ D8174,
D8173[Y1] ……)
The current position of X axis is (100, 0), it will move to target position (3000, 0) at the speed of 1000Hz, pulse output terminal is Y0, direction terminal is Y4. The distance between origin and target position is 3000. The DRVA executing diagram is shown as below:
Program:
Example
6-2-10.Absolute position multi-segment pulse control [PLSA] PLSA/DPLSA has two control modes, below we will introduce one by one; Mode 1: uni-directional pulse output PLSA 1、Instruction Summary Generate absolute position segmented pulse with the specified frequency, acceleration/deceleration time and pulse direction;
Absolute position multi-segment pulse control [PLSA] 16 bits Instruction
PLSA 32 bits Instruction
DPLSA
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type S1 Specify the soft component’s number to output the pulse
parameters 16/32bit, BIN
S2 Specify the acceleration/deceleration time or soft component’s number
16/32 bit, BIN
D Specify the pulse output port Bit
3、suitable soft components
operands system
X Y M S T C Dn.m
D1 ●
Word
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● K
《16 bit instruction form》
《32 bit instruction form》
The parameters’ address is a section starts from Dn or FDn. In the above example: D0 set the
first segment pulse’s highest frequency、D1 set the first segment’s absolute position,D2 set the second segment pulse’s highest frequency、D3 set the second segment’s absolute position,…… if the set value in Dn、Dn+1 is 0, this represents the end of segment, we can set 24 segments in total;
For 32 bits instruction DPLSA, D0, D1 set the first segment pulse highest frequency, D2,D3 set the first segment pulse quantity, D4, D5 set the second segment pulse highest frequency, D6,D7 set the second segment pulse quantity……. If the setting value of Dn, Dn+1, Dn+2, Dn+3 are 0, it means the end of the segment. It can set 24 segments in total.
Acceleration/deceleration time is the time from the start to the first segment’s highest frequency. Meantime, it defines the slope of all segment’s frequency to time. In this way the following acceleration/deceleration will perform according to this slope.
Pulse can be output at only Y0 or Y1; XC5 series is Y0~Y3, 3 axis is Y0~Y2, 10 axis is Y0~Y11;
Frequency range: 0~32767Hz (16 bits instruction), 0~200KHz (32 bits instruction) Pulse number range: K0~K32,767 (16 bits instruction), K0~K2,147,483,647 (32 bits
instruction) Confirm the value in current position registers (D8171, D8170[Y0]/ D8174,
D8173[Y1] ……) Note: if the segment quantity is n, the address of the segments must be continuous, and the pulse frequency and quantity of n+1 segment must be 0. It means the pulse output end. The address of acceleration/deceleration time cannot follow the segment n.
Functions And Actions
Output 6 segments of pulse through instruction DPLSA. Y0 is pulse output terminal.
Name Frequency (Hz) Absolution position Segment 1 1000 2000 Segment 2 200 3000 Segment 3 3000 9000 Segment 4 800 10600 Segment 5 100 11400 Segment 6 1200 14400 Acceleration/deceleration time 100ms
Use 32 bits instruction DPLSA: Name Frequency
(Hz) Frequency address (Dword)
Absolution position
Absolution position address (Dword)
Segment 1 1000 D1、D0 2000 D3、D2 Segment 2 200 D5、D4 3000 D7、D6 Segment 3 3000 D9、D8 9000 D11、D10 Segment 4 800 D13、D12 10600 D15、D14 Segment 5 100 D17、D16 11400 D19、D18 Segment 6 1200 D21、D20 14400 D23、D22 Acceleration/deceleration time
100ms D51、D0
Note: the 4 registers after segment 6 must be 0. (D27, D26, D25, D24).It means the pulse output
end. For 16 bits instruction PLSA, 2 registers after segment 6 must be 0.
F Hz
3000
1200
1000
800
200100
0 2000 3000 9000 10600 11400 14400
Example
Program:
Mode2: dual-directional pulse output PLSA 1、Instruction Summary Generate absolute position pulse with the specified frequency, acceleration/deceleration time and pulse direction;
Absolute position multi-segment pulse control [PLSA] 16 bits Instruction
PLSA 32 bits Instruction
DPLSA
Execution condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware requirement
- Software requirement
-
2、Operands
Operands Function Type S1 Specify the soft component’s number to output the pulse
parameters 16/32bit, BIN
S2 Specify the acceleration/deceleration time or soft component’s number
16/32 bit, BIN
D1 Specify the pulse output port Bit D2 Specify the pulse direction port Bit
3、suitable soft components 《16 bit instruction form》
《32 bit instruction form》
The parameters’ address is a section starts from Dn or FDn. In the above example: D0 set the
first segment pulse’s highest frequency、D1 set the first segment’s absolute position,D2 set the second segment pulse’s highest frequency、D3 set the second segment’s absolute position,…… if the set value in Dn、Dn+1 is 0, this represents the end of segment, we can set 24 segments in total;
For 32 bits instruction DPLSA. The parameters’ address is a section starts from Dn or FDn.
operands system
X Y M S T C Dn.m
D1 ●
D2 ●
Word
Functions And Actions
Bit
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● K
In the above example: D0,D1 set the first segment pulse’s highest frequency、D2,D3 set the first segment’s absolute position,D4,D5 set the second segment pulse’s highest frequency、D6,D7 set the second segment’s absolute position , … … if the set value in Dn,Dn+1,Dn+2,Dn+3 is 0, this represents the end of segment, we can set 24 segments in total;
Acceleration/deceleration time is the time from the start to the first segment’s highest frequency. Meantime, it defines the slope of all segment’s frequency to time. In this way the following acceleration/deceleration will perform according to this slope.
Pulse can be output at only Y0 or Y1, XC5 series is Y0~Y3, 3 axis is Y0~Y2, 10 axis is Y0~Y11.
Frequency range: 0~32767Hz (16 bits instruction), 0~200KHz (32 bits instruction) Pulse number range: K0~K32,767 (16 bits instruction), K0~K2,147,483,647 (32 bits
instruction) Confirm the value in current position registers (D8171, D8170[Y0]/ D8174,
D8173[Y1] ……) The Y port to output the pulse direction can be set freely;
Note: when PLSA and DPLSA has several segments, the direction of these segments must be the same.
Output 6 segments of pulse through instruction DPLSA. The pulse terminal is Y0, direction terminal is Y2.
Example
Name Frequency (Hz) Absolution position
Segment 1 1000 2000 Segment 2 200 3000 Segment 3 3000 9000 Segment 4 800 10600 Segment 5 100 11400 Segment 6 1200 14400 Acceleration/deceleration time 100ms
Use 32 bits instruction DPLSA: Name Frequency
(Hz) Frequency address (Dword)
Absolution position
Absolution position (Dword)
Segment 1 1000 D1、D0 2000 D3、D2 Segment 2 200 D5、D4 3000 D7、D6 Segment 3 3000 D9、D8 9000 D11、D10 Segment 4 800 D13、D12 10600 D15、D14 Segment 5 100 D17、D16 11400 D19、D18 Segment 6 1200 D21、D20 14400 D23、D22 Acceleration/deceleration time
100ms D51、D0
Note: the 4 registers after segment 6 must be 0. (D27、D26、D25、D24). It means the pulse output
end. For 16 bits instruction PLSA, the 2 registers after segment 6 must be 0.
F Hz
3000
1200
1000
800
200100
0 2000 3000 9000 10600 11400 14400
Program:
6-2-11.Relative position multi-section pulse control [PTO] 1、Summary
Produce relative position multi-section pulse as setting parameters. Relative position multi-section pulse control [PTO] 16 bits - 32 bits PTO Execution condition
Edge triggering Suitable models
XC3、XC5、XCM、XCC
Hardware V3.3 and higher Software V3.3 and higher 2、Operand
Operands Function Type S1 Soft element head address of output pulse
parameters 32 bits, BIN
S2 External interruption input port no. Bit
D1 Pulse output port no. Bit D2 Pulse output direction port no. Bit
3、Suitable soft element PTO instruction has two control modes. Mode1: PTO without external interruption
《32 bits instruction》
《no direction》 《with direction》
Parameters distribution: (the parameters are 32 bits 2 bytes): S1 :section quantity N, range 1~255 S1+2 :reserved S1+4 :pulse direction, 0 is positive direction; 1 is negative direction Among each section, only one section pulse quantity can be 0. S1+6 :pulse falling slope, which is decreasing frequency per second. 0 means urgent stop.
S1+8 :start frequency of section 1 S1+10:end frequency of section 1 S1+12:pulse quantity of section 1
S1+14:start frequency of section 2
Oper-
and
System
X Y M S T C Dn.m
S2 ●
D1 ●
D2 ●
Word
Description
Bit
Oper-
and
System Const
-ant
Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ●
PTO D0 Y0M0 S1· D1·
PTO D0 Y0M0 S1· D1·
Y1
D2·
S1+16:end frequency of section 2 S1+18:pulse quantity of section 2
S1+20:start frequency of section 3 S1+22:end frequency of section 3 S1+24:pulse quantity of section 3
…… and so on, user can set section N parameters
The parameters address starts from Dn or FDn
In the above example:(D1,D0) is pulse section quantity;(D5,D4)is pulse direction; (D7,D6)is pulse falling frequency;(D9,D8)is start frequency of section 1;(D11,D10)is end frequency of section 1; (D13,D12) is the pulse quantity of section 1. The max section quantity can be 255.
Pulse output: Y0, Y1; the pulse output terminal is different for each model. If pulse quantity of section m is 0, this means the pulse quantity is unlimited. If pulse quantity of section m is 0, the start frequency must be equal to the end frequency;
otherwise this section will not be executed. If pulse quantity is not 0, the pulse direction is decided by the positive/negative of pulse. If
the pulse quantity is 0, the pulse direction is set through S1+4. S1+6 is the slow stop slope when executing PSTOP (refer to PSTOP instruction). Pulse parameters occupy the register size: [(N*3+4)+(N*3+4)+(N*4+5)]*2. The instruction is executed at the rising edge; if the signal is normally close, the instruction
will be executed repeatedly.
Section Start frequency (Hz)
End frequency (Hz)
Relative pulse quantity
1 1000 1500 3000 2 1500 3200 3200
1 2 3 4 5 6 7 8 9
Example Continuous output 9 sections of pulses, the pulse output terminal is Y0, pulse direction terminal is Y2, the start frequency and end frequency please see the following table:
3 3200 6000 2000 4 6000 8000 10000 5 8000 8000 18000 6 8000 6000 10000 7 6000 3200 2000 8 3200 1500 3200 9 1500 1000 3000
�
Ladder chart:
Set the parameters:
Set the parameters through PTO config . Please find it in XCPpro software.
Note:
(1) PTO parameters will occupy the registers of D4000~D4205, please don’t use these registers for other purpose.
(2) Click “Write to PLC” / OK. Then click stop , run .
Mode2: PTO with external interruption
《32 bits instruction》
Parameter distribution (the parameter is 32 bits, 2 bytes): S1 :section quantity N, range 1~255 S1+2 :reserved S1+4 :pulse direction (the section of 0 pulses), 0 is positive direction, 1 is negative direction S1+6 :pulse falling slope, decreasing frequency per second, 0 is urgent stop
S1+8 :start frequency of section 1 S1+10:end frequency of section 1 S1+12:pulse quantity of section 1
S1+14:start frequency of section 2 S1+16:end frequency of section 2 S1+18:pulse quantity of section 2
S1+20:start frequency of section 3 S1+22:end frequency of section 3 S1+24:pulse quantity of section 3
…… And so on, user can set the parameters of section N
If user has not set the 0 pulse section, the instruction will not be executed. If the external signal is produced in zero pulse section, it will switch to the next section (if
there is no next section, stop the pulse output). If the external signal is produced in non-zero pulse section, it will run the rest pulses with the
set slope (S1+6 parameter); if the rest pulses is larger than the pulse quantity of frequency falling section, it will run a smooth section and then the falling section.
S1+6 is the urgent stop slope when running PSTOP instruction. Cannot support absolute position instruction, cannot support instruction with direction.
Description
PTO D0 X1M0 S1· D1·
Y0
S2·
1 2 6 7 8
Extenal signal
The instruction will be executed at the rising edge; if it is normally close signal, the instruction will be executed repeatedly.
The instruction execution in different conditions:
The external interruption signal is produced in zero pulse section.
The instruction will switch to the next section when encountering the external interruption signal, Ss=S3+S4+S5. S3 is section 3 pulse quantity. S4 is section 4 pulse quantity. S5 is section 5 pulse quantity.
External interruption signal is produced in non-zero pulse section, rest pulses Ss is larger than
falling pulses Sn.
When encountering the external interruption signal, it runs the smooth section with the current frequency Sm=Ss-Sn, then the falling section Sn.
Ss is pulses of rest section. Sn is pulses of frequency falling section when encountering external interruption signal. Sm is pulses of smooth section when encountering the external interruption signal. S6 is the pulses of section 6 S7 is the pulses of section 7 S8 is the pulses of section 8
The external interruption signal is produced in the non-zero pulse section. The rest pulses Ss
is smaller than falling section pulses Sn.
1 4 5
External signal
S3
4 6 7 8
External signal
Slope KS
nm
When encountering the external interruption signal, it runs the falling section with the slope K. When Ss= S6+S7, it stops outputting the pulses. Ss is the pulses of rest section. S6 is the pulses of section 6. S7 is the pulses of section 7. Sn is the pulses of falling section when encountering the external interruption signal.
S1+6=0, the pulse will stop after running the smooth section. Sm=S6+S7+S8 The external interruption signal is produced in non-zero pulse section, rest pulses Ss is
smaller than falling section pulses Sn. If encountering the external interruption signal, it runs the falling pulses with slope K, when
Ss= S6+S7, it stop outputting the pulses. Ss is the rest section pulses. S6 is the pulses of section 6. S7 is the pulses of section 7. Sn is the falling section pulses when encountering the external interruption signal.
3
6 7
External signal
Slope K
S
n
6-2-12.Absolute position multi-section pulse control [PTOA]
1、Summary
Section to produce pulse instructions of absolute position according to specified parameters Absolute position multi-section pulse control [PTOA] 16 bits Instruction
- 32 bits Instruction
PTOA
Execution condition
Edge triggering Suitable Models
XC3、XC5、XCM、XCC
Hardware requirement
V3.3 and higher version Software requirement
V3.3 and higher version
2、Operands
Operands Function Type S1 Specify the soft component’s start ID of the output
pulse parameters 32bits,BIN
D1 Specify the pulse output port Bit D2 Specify the pulse output direction port Bit
3、Suitable soft components
3
6 7
External signal
Slope K
S
n
Mode: PTOA (Fixed pulse quantity)
《32 bits instruction form》 《Without direction》
《With direction》
The parameters address and functions are shown as below (the parameter is 32 bits, two bytes): S1 :Total section N, range is 1~255 S1+2 :reserved S1+4 :The direction(0 is positive,1 is negative) of unlimited pulse section (zero pulse
section) S1+6 : Pulse descending slope, decreasing frequency per second, 0 means urgent stop
S1+8 : Start pulse frequency of section 1 S1+10: End pulse frequency of section 1 S1+12:Absolute pulse position of section 1
S1+14:Start pulse frequency of section 2 S1+16:End pulse frequency of section 2 S1+18:Absolute pulse position of section 2
S1+20:Start pulse frequency of section 3 S1+22:End pulse frequency of section 3 S1+24:Absolute pulse position of section 3
……
operands System
X Y M S T C Dn.m
D1 ●
D2 ●
Word
Bit
operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
PTOA D0 Y0M0
S1· D1·
PTOA D0 Y0M0 S1· D1·
Y1
D2·
Description
The pulse parameters address of section N can be known by this discipline
The pulse direction of section 1 is decided by current pulse quantity and cumulative pulse quantity, other section directions are decided by current pulse quantity and last section pulse quantity;
Occupied registers size: [(N*3+4)+(N*3+4)+(N*4+5)]*2; The toggle condition to execute the pulse is rising edge, if the signal is closed signal the pulse
will execute repeatedly.
Name Start Frequency(Hz) End Frequency(Hz) Absolute pulse quantity of each section Section 1 1000 1500 3000 Section 2 1500 3200 6200 Section 3 3200 6000 8200 Section 4 6000 8000 18200 Section 5 8000 8000 36200 Section 6 8000 6000 46200 Section 7 6000 3200 48200 Section 8 3200 1500 51400 Section 9 1500 1000 54400
1 2 3 4 5 6 7 8 9
Example The pulse output terminal is Y0, direction terminal is Y2; The start, end frequency, pulse absolute position is shown in below table:
Ladder chart:
Set the parameters:
Fast configure the parameters through the PTO config function in XCPpro software:
Caution: because the pulse instruction occupy the register address D4000~D5205, these register addresses can’t be used for other purpose.
6-2-13.Pulse Stop [PSTOP] 1、Summary
Pulse stop instruction, execute with PTO instruction. Pulse Stop [PSTOP] 16 bits Instruction
- 32 bits Instruction
PSTOP
Execution condition
Normally ON/OFF coil Suitable Models
XC3、XC5、XCM、XCC
Hardware requireme
V3.3 and higher version Software requirement
V3.3 and higher version
nt 2、Operands
Operands Function Type S1 Specify pulse stop output port bit S2 Specify pulse stop mode data decimal,K
3、suitable soft components
This instruction is used to stop PTO pulse instruction. S2:Stop mode (urgent stop; slow stop).
S2=K1, M0 is ON, pulses urgent stop. S2=K0, M0 is ON, pulses slow stop with the slope of PTO instruction parameter S1+6 (If S1+6=0, it is urgent stop mode).
Frequency
0
M0
K
T
When M0 is ON, the solid line is urgent stop (K1), dotted line is slow stop.
operands System
X Y M S T C Dn.m
S1 ●
Word
Description
Bit
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S2 ●
PSTOP Y0 K1M0
S1· S2·
6-2-14. Variable frequency single-section pulse [PTF]
1、Summary To produce the variable frequency pulses as set parameters:
Variable frequency single section pulse output [PTF] 16 bits Instruction
- 32 bits Instruction
PTF
Execution condition
Normally ON/OFF coil Suitable Models
XC3、XC5、XCM、XCC
Hardware requirement
V3.3 and higher vision Software requirement
V3.3 and higher vision
2、Operands
Operands Function Type S1 Specify the soft component start ID of the pulse
parameters 32 bits,BIN
D1 Specify the pulse output port Bit D2 Specify the pulse output direction port Bit
3、Suitable soft components
《32 bits instruction》
《Without directions》 《With directions》
operands System
X Y M S T C Dn.m
D1 ●
D2 ●
Word
Description
Bit
operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
PTF D0 Y0M0
S1· D1·
PTF D0 Y0M0
S1· D1·
Y1
D2·
The parameters are shown as below (the parameters is 32 bits, two bytes): S1 :Pulse frequency S1+2 : Rising and falling frequency of pulse, which is increasing/decreasing frequency per
second Pulse quantity in current section and cumulative pulses are not refreshed. Current pulse frequency is a target for every scanning period
(A)The increasing pulses are 0 in unit time(S1+2 = 0)
Pulse frequency will change as the slope K:
(B) The increase frequency quantity in unit time is not 0(he parameter of S1+2 is not 0)
1)The pulse is in a smooth section when user set a new frequency, then the frequency will change to setting frequency through with the setting slope, please see the following diagram:
2)The pulse is in non-smooth section when user set a new frequency, then the frequency
will change to setting frequency with setting slope (current setting frequency>last setting frequency, current setting frequency will be the target), please see the following diagram:
V0
V1
V2
V3
Slope K
V0Slope K
V1
Slope K
Target frequency V0
V0
V1
Target frequency V1 Target frequency 0
Before the frequency reaches V0, user set the new target frequency V1(V1>V0), then the
frequency will turn to V1 according to the slope.
3)The pulse is in non-smooth section, when user set the new frequency, then change to setting frequency with the setting slope (Current setting frequency<last setting frequency, current setting frequency<current frequency), please see the following diagram:
Before the frequency reaches V0, user set the new target frequency V1(V1<V0,V1<current frequency), it will go to the decreasing section until V1, the slope is the same to the increasing section.
Target frequency V0
V2Target frequency V1 Target frequency 0
V0
V1
Target frequency V2
Target frequency V0
V2
Target frequency V1 Target frequency 0
V0
V1
Target frequency V2
6-3.Output Wiring
Y0COM0
Y1COM1
Y2COM2
Below is the graph to show the output terminals and stepping driver wiring:
Y0PU
PUY1
6-4.Notes
1、Concept of Step Frequency
PLC side Stepping driver side
Output port Y0: Pulse output port 0 (single phase) Output port Y1: Pulse output port 1 (single phase)
频率的跳变
2、frequency jump in segment pulse output
When outputting the segmented pulse, if the current segment’s pulse has been set out, while meantime it doesn’t reach the highest frequency, then from the current segment to the next pulse output segment, pulse jump appears, see graph above;
To avoid frequency jump, please set suitable acceleration/deceleration time. 3、dual pulse output is invalid
D0PLSR D100 Y0M0
D200PLSR D1000 Y0M1
In the following cases, dual pulse output is invalid:
(1)in main program
In one main program, users can’t write two or more pulse output instructions with one output port Y;
The below sample is wrong;
During ACC/DEC, each step time is 5ms, this time is fixed and not changeable. The minimum step frequency (each step’s rising/falling time) is 10Hz. If the frequency is
lower than 10Hz, calculate as 10Hz; the maximum step frequency is 15Hz. If the frequency is larger than 15Hz, calculate as 15Hz;
In case of frequency larger than 200Hz, please make sure each segment’s pulse number no less than 10, if the set value is less than 10, send as 200Hz;
(2)in STL
(3)in subprogram
(4)one in main program, another in STL
(5)one in main program, another in subprogram
The correct programming method when it needs to write more than one pulse output instructions:
Method 1: use STL, each STL only write one pulse output instruction
Example:
Note: the two STL cannot work at the same time! (M2 and M3 cannot be ON at the same time)
Method2: if the same instruction needs to work in many places of the program, user can write one instruction in the main program, and put its parameter registers in STL.
M0
( S )S0
STL S0
DMOV K1000 D4000S0
M8170 M1
( R )
S1( S )
STLE
STL S1
0
4
6
27
31
39
42
65
68
DMOV K3000 D4002
FMOV K0 D4004 K8
DMOV K100 D4030
( )TO K1
T0
( S )M1
M1
DMOV K1000 D4000S1
DMOV K-3000 D4002
FMOV K0 D4004 K8
DMOV K100 D4030
TO K1( )
M8170 M1( R )
S1( R )
STLE
63
67
( S )M1
M1
T0
DPLSR D4000 D4030 Y0 Y2M1
Method3: use sequence block. BLOCK can support multi-instruction sequential working. Please refer to chapter 10.
6-5.Sample Programs
Program:
Note: register D0, D1, D2, D3 set the frequency and pulse quantity of segment 1 and 2. D30 set the acceleration/deceleration time, reset register D4, D5.
FRQM K20 D0 K1 X003X000
PLSF D0 Y0
E.g.2: follow function In this sample, the pulse frequency from Y0 equals with the frequency tested from X003. If the frequency tested from X003 changes, the pulse frequency from Y0 changes;
E.g.1: Stop at certain length With instruction [PLSR] and [PLSNEXT], make “stop at certain length” function;
M0
M1
M8170
Take the sample program as the example, set two segments pulse output in D0、D1 and D2,D3, with the same frequency value; In second segment pulse output, set pulse number D3 as the output pulse number after receive M1 signal. This will realize “stop at certain length” function. See graph by the left side;
6-6.Relative coils and registers of pulse output Some flags of pulse output are listed below:
ID Pulse ID Function specification M8170 PULSE_1 “sending pulse” flag Being ON when sending the pulse,
M8171 overflow flag of “32 bits pulse sending”
When overflow, Flag is on
M8172 Direction flag 1 is positive direction, the correspond direction port is on
M8173 PULSE_2 “sending pulse” flag Being ON when sending the pulse,
M8174 overflow flag of “32 bits pulse sending”
When overflow, Flag is on
M8175 Direction flag 1 is positive direction, the correspond direction port is on
M8176 PULSE_3 “sending pulse” flag Being ON when sending the pulse,
M8177 overflow flag of “32 bits pulse sending”
When overflow, Flag is on
M8178 Direction flag 1 is positive direction, the correspond direction port is on
M8179 PULSE_4 “sending pulse” flag Being ON when sending the pulse,
M8180 overflow flag of “32 bits pulse sending”
When overflow, Flag is on
M8181 Direction flag 1 is positive direction, the correspond direction port is on
M8210 PULSE_1 Pulse alarm flag (frequency change suddenly) 1 is alarm, 0 is correct
M8211 Neglect the alarm or not When flag is 1, stop sending alarm
M8212 PULSE_2 Pulse alarm flag (frequency change suddenly) 1 is alarm, 0 is correct
M8213 Neglect the alarm or not When flag is 1, stop sending alarm
M8214 PULSE_3 Pulse alarm flag (frequency change suddenly) 1 is alarm, 0 is correct
M8215 Neglect the alarm or not When flag is 1, stop sending alarm
M8216 PULSE_4 Pulse alarm flag (frequency change suddenly) 1 is alarm, 0 is correct
M8217 Neglect the alarm or not When flag is 1, stop sending alarm
M8218 PULSE_5 Pulse alarm flag (frequency change suddenly) 1 is alarm, 0 is correct
M8219 Neglect the alarm or not When flag is 1, stop sending alarm
Some special registers of pulse output are listed below:
ID Pulse ID Function Specification
D8170 PULSE_1 The low 16 bits of accumulated pulse number
D8171 The high 16 bits of accumulated pulse number
D8172 The current segment (means segment n)
D8173 PULSE_2 The low 16 bits of accumulated pulse number
D8174 The high 16 bits of accumulated pulse number
D8175 The current segment ( means segment n )
D8176 PULSE_3 The low 16 bits of accumulated pulse number
D8177 The high 16 bits of accumulated pulse number
D8178 The current segment ( means segment n )
D8179 PULSE_4 The low 16 bits of accumulated pulse number
D8180 The high 16 bits of accumulated pulse number
D8181 The current segment ( means segment n )
D8190 PULSE_1 The low 16 bits of the current accumulated current pulse number
D8191 The high 16 bits of the current accumulated current pulse number
D8192 PULSE_2 The low 16 bits of the current accumulated current pulse number
D8193 The high 16 bits of the current accumulated current pulse number
D8194 PULSE_3 The low 16 bits of the current accumulated current pulse number
Only XC5-32RT-E (4PLS) model has
D8195 The high 16 bits of the current accumulated current pulse number
D8196 PULSE_4 The low 16 bits of the current accumulated current pulse number
D8197 The high 16 bits of the current accumulated current pulse number
D8210 PULSE_1 The error pulse segment’s position D8212 PULSE_2 The error pulse segment’s position D8214 PULSE_3 The error pulse segment’s position D8216 PULSE_4 The error pulse segment’s position
Absolute position/relative position/back to origin;
Note: for frequency rising time of absolution/relative positioning instruction, the register setting value should meet the following formula:
For example: instruction DRVA K300080 K3000 Y0 Y4, rising time is 100ms. Then register D8230 (Dword) = 3=[100(ms)×3000(Hz)] ÷100K(Hz).
D8218 PULSE_5 The error pulse segment’s position
ID Pulse Function Description
D8230 PULSE_1
Rising time of the absolute/relation position instruction (Y0)
D8231 Falling time of the origin return instruction (Y0)
D8232
PULSE_2
Rising time of the absolute/relation position instruction (Y1)
D8233 Falling time of the origin return instruction (Y1)
D8234 PULSE_3
Rising time of the absolute/relation position instruction (Y2)
D8235 Falling time of the origin return instruction (Y2)
D8236 PULSE_4
Rising time of the absolute/relation position instruction (Y3)
D8237 Falling time of the origin return instruction (Y3)
D8238 PULSE_5
Rising time of the absolute/relation position instruction
D8239 Falling time of the origin return instruction
Register (D8230, D8232……) = Rising time(ms)×max frequency
100K
7 Communication Function
This chapter mainly includes: basic concept of communication, Modbus communication, free communication and CAN-bus communication;
7-1.Summary
7-2.Modbus Communication
7-3.Free Communication
7-4.CAN Communication
Relative Instructions:
Mnemonic Function Circuit and Soft Components Chapter
MODBUS Communication
COLR Coil Read
7-2-3
INPR Input coil read INPR S1 S2 S3 D1 D2
7-2-3
COLW Single coil write COLW D1 D2 S1 S2
7-2-3
MCLW Multi-coil write MCLW D1 D2 D3 S1 S2
7-2-3
REGR Register read REGR S1 S2 S3 D1 D2
7-2-3
INRR Input register read INRR S1 S2 S3 D1 D2
7-2-3
REGW Single register write REGW D1 D2 S1 S2
7-2-3
MRGW Multi-register write MRGW D1 D2 D3 S1 S2
7-2-3
Free Communication
SEND Send data SEND S1 S2 n
7-3-2
RCV Receive data RCV S1 S2 n
7-3-2
CAN-bus Communication
CCOLR Read coil
7-4-4
CCOLW Write coil
7-4-4
CREGR Read register CREGR S1 S2 S3 D
7-4-4
CREGW Write register CREGW D1 D2 D3 S
7-4-4
7-1.Summary
XC2-PLC, XC3-PLC, XC5-PLC main units can fulfill your requirement on communication and network. They not only support simple network (Modbus protocol、free communication protocol), but also support those complicate network. XC2-PLC, XC3-PLC, XC5-PLC offer communication access, with which you can communicate with the devices (such as printer, instruments etc.) that have their own communication protocol.
XC2-PLC, XC3-PLC, XC5-PLC all support Modbus protocol 、 free protocol these communication function, XC5-PLC also have CANbus function.
7-1-1.COM port There are 2 COM ports (Port1、Port2) on XC3 series PLC basic units, while there are 3 COM ports on XC5 series PLC main units. Besides the same COM ports (COM1、COM2), they have also CAN COM port. COM 1 (Port1) is the programming port, it can be used to download the program and connect with the other devices. The parameters (baud rate, data bit etc.) of this COM port are fixed, can’t be re-set. Note: PLC hardware version less than v3.1: port 1 parameters cannot be changed, otherwise port 1 cannot connect to PC PLC hardware version higher than v3.2: port 1 parameters cannot be changed. But user can stop the PLC when start, then initialize the PLC. COM 2 (Port2) is communication port, it can be used to download program and connect with other devices. The parameters (baud rate, data bit etc.) of this COM port can be changed via software. Via BD cards, XC series PLC can expand port 3. These COM ports can be RS232 and RS485.
COM9COM8
Y
X
X0X1COM
COM X2X3
X4X5
X6X7
X10X11
X12X13
X14X15
X16X17
X20X21
X22X23
X24X25
X26X27
X30X37
X40X36X35
X34X33
X32X31 X41
X42X43
Y27Y26
Y25Y24
Y15 Y17COM6 Y21
Y20COM7Y23
Y22Y16Y13 Y14
COM5Y11
Y12Y7 Y10Y6COM4
Y4Y5COM3
Y3Y2Y1COM2
Y0COM1COM0
CAN+ CAN-A B
0V24V
PORT2PORT1XC3-60R-E
ERR
RUNPWR
0 1 32 6 754
4 5 762 310
COM Port
Port 1
Port 2 (232)
Port 3
Port 2 (485)
1. RS232 Port Note: 1. Port 1 support RS232. 2. Port 2 support RS232, RS485. But RS232 and RS485 cannot be used at the same time. 3. Port 3 support RS232, RS485. But RS232 and RS485 cannot be used at the same time. (need to expand XC-COM-BD).
2. RS485 port: About RS485 port, A is “+” signal、B is “-“ signal. The A, B terminals (RS485) on XC series PLC is the same port to Port 2. This two ports cannot be used at the same time. (the same to Port 3). Please use twisted pair cable for RS485. (see below diagram). But shielded twisted pair cable is better and the single-ended connect to the ground.
3. CAN port: CAN port can be applied to CANBUS communication. The pin terminals are “CAN+”, “CAN-“ For the detailed CAN communication functions, please refer to chapter 7-4 CAN bus function.
COM1 Pin Definition:
3 4 5
1 2
6 87
Mini Din 8 pin female
2:PRG 4:RxD 5:TxD 6:VCC 8:GND
COM2 Pin Definition:
3 4 5
1 2
6 87
Mini Din 8 pin female
4:RxD 5:TxD 8:GND
Send Receive
Receive Send
Interference signal
7-1-2.Communication Parameters Station Modbus Station number: 1~254、255 (FF) is free format communication Baud Rate 300bps~115.2Kbps Data Bit 8 bits data、7 bits data Stop Bit 2 stop bits、1 stop bit Parity Even、Odd、No check
The default parameters of COM 1: Station number is 1、baud rate is 19200bps、8 data bit、1 stop bit、Even parity
COM 1
Number Function Description
FD8210 Communication mode 255 is free format, 1~254 bit is Modbus station number
FD8211 Communication format Baud rate, data bit, stop bit, parity
FD8212 ASC timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8213 Reply timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8214 Start symbol High 8 bits invalid FD8215 End symbol High 8 bits invalid
FD8216 Free format setting 8/16 bits cushion, with/without start bit, with/without stop bit
COM 2
FD8220 Communication mode 255 is free format, 1~254 bit is Modbus station number
FD8221 Communication format Baud rate, data bit, stop bit, parity
FD8222 ASC timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8223 Reply timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8224 Start symbol High 8 bits invalid FD8225 End symbol High 8 bits invalid
Parameters Setting
Set the parameters with the COM ports on XC series PLC;
Communication Parameters
Baud rate: Please see below table
0:8bits data 1:7bits data
0:2 stop bits 2:1stop bit
0:No parity 1:Odd parity 2:Even parity
FD8226 Free format setting 8/16 bits cushion, with/without start bit, with/without stop bit
COM 3
FD8230 Communication mode 255 is free format, 1~254 bit is Modbus station number
FD8231 Communication format Baud rate, data bit, stop bit, parity
FD8232 ASC timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8233 Reply timeout judgment time Unit: ms,if set to be 0, it means no timeout waiting
FD8234 Start symbol High 8 bits invalid FD8235 End symbol High 8 bits invalid
FD8236 Free format setting 8/16 bits cushion, with/without start bit, with/without stop bit
※1: The PLC will be Off line after changing the communication parameters, use “stop when reboot” function to
keep PLC online; ※2: After modifying the data with special FLASH data registers, the new data will get into effect after reboot;
FD8211 (COM1)/FD8221 (COM2)/FD8231 (COM3)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Set the communication parameters:
0: 8 bits communication 1: 16 bits communication
0: without start symbol 1: with start symbol
0: without end symbol 1: with end symbol
Reserved
bit0~bit3 baud rate: Baud rate Suitable type Baud rate Suitable type 0:300bps XC1 0:768Kbps - XC2、XCM、XCC 1:600bps XC1 1:600bps XC3、XC5 XC2、XCM、XCC 2:1200 bps XC1 2:1200 bps XC3、XC5 XC2、XCM、XCC 3:2400 bps XC1 3:2400 bps XC3、XC5 XC2、XCM、XCC 4:4800 bps XC1 4:4800 bps XC3、XC5 XC2、XCM、XCC 5:9600 bps XC1 5:9600 bps XC3、XC5 XC2、XCM、XCC 6:19.2K bps XC1 6:19.2Kbps XC3、XC5 XC2、XCM、XCC 7:38.4K bps XC1 7:38.4Kbps XC3、XC5 XC2、XCM、XCC 8:57.6K bps XC1 8:57.6Kbps XC3、XC5 - 9:115.2K bps XC1 9:115.2Kbps XC3、XC5 - - - A:192Kbps XC3、XC5 XC2、XCM、XCC - - B:256Kbps - XC2、XCM、XCC - - C:288Kbps XC3、XC5 - - - D:384Kbps XC3、XC5 XC2、XCM、XCC - - E:512Kbps - XC2、XCM、XCC - - F:576Kbps XC3、XC5 - FD8216 (COM1)/FD8226 (COM2)/FD8236 (COM3)
Note: user doesn’t have to calculate the FD value to set the communication parameter. Please set the parameters in XCPpro software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
After changing the parameters, please restart the PLC to make it effective.
7-2.MODBUS Communication
7-2-1.Function XC series PLC support both Modbus master and Modbus slave. Master mode: When PLC is set to be master, PLC sends request to other slave devices via Modbus
instructions, other devices response the master. For example, Xinje PLC can control the inverter through Modbus.
Slave mode: when PLC is set to be slave, it can only response with other master devices. Master and slave: in RS485 network, there are one maser and several slaves at one time (see
below diagram). The master station can read and write any slave stations. Two slave stations cannot communicate with each other. Master station communicates with slave station through Modbus instructions. Slave station has no program but only response the master station. (wiring: connect all the RS485 +, connect all the RS485-)
In RS232 network, there is only one master and one slave.
There is dotted line in the diagram. It means any PLC can be master station when all the PLC in the network don’t send data. But more than one PLC will send data at one time, the communication will fail. It is not recommended to use. Note: For XC series PLC, RS232 only support half-duplex.
Slave Master
Master
Slave 1
Slave 2
Slave 3
7-2-2.Address For the soft component’s number in PLC which corresponds with Modbus address number, please see the following table:
Coil address: (Modbus ID prefix is “0x”) Bit ID ModbusID
( decimal K)
Modbus ID
(Hex. H)
M0~M7999 0~7999 0~1F3F X0~X1037 16384~16927 4000~421F Y0~Y1037 18432~18975 4800~4A1F S0~S1023 20480~21503 5000~53FF M8000~M8511 24576~25087 6000~61FF T0~T618 25600~26218 6400~666A C0~C634 27648~28282 6C00~6E7A
Register address: (Modbus ID prefix is “4x”)
Word ID ModbusID
( decimal K)
Modbus ID
(Hex. H)
D0~D7999 0~7999 0~1F3F TD0~TD618 12288~12906 3000~326A CD0~CD634 14336~14970 3800~3A7A D8000~D8511 16384~16895 4000~41FF FD0~FD5000 18432~23432 4800~5B88 FD8000~FD8511 26624~27135 6800~69FF
The address is used when PLC uses Modbus-RTU protocol. The host machine is PLC,
HMI or SCADA. If the host machine is PLC, please write the program as Modbus-RTU protocol. If the
host machine is HMI or SCADA, there are two conditions. Condition one: with Xinje driver such as Xinje HMI. Please write the program with PLC soft components (Y0, M0, D0…). Condition two: without Xinje driver. Please choose Modbus-RTU protocol, the address is as the above table.
※1: Bit soft components X, Y are in Octal form, others are in decimal form. For example: X10 modbus address is not K16394 but K16392. Y100 modbus address is K18496. Note: octal has no Y8/Y9 and Y80/Y90.
7-2-3 Modbus communication format Modbus communication data format 1. RTU mode:
START No signal input ≧ 10ms Address Communication address: 8-bit binary Function Function code: 8-bit binary
DATA(n - 1) Data contents:
N*8-bit data, N<=8, max 8 bytes ……………
DATA 0 CRC CHK Low CRC check code
CRC CHK High 16-bit CRC check code is built up by 2 8-bit
binary END No signal input ≧ 10ms
2. Modbus address
00H: all the Xinje XC series PLC broadcast ---- slave stations don’t response. 01H: communicate with address 01H PLC 0FH: communicate with address 0FH PLC 10H: communicate with address 10H PLC……….the max address is FEH (254)
3. Function and DATA:
Function code Function Modbus instruction 01H Read coil COLR 02H Read input coil INRR 03H Read register REGR 04H Read input register INRR 05H Write coil COLW 06H Write register REGW 10H Write multi-register MRGW 0FH Write multi-coil MCLW
Now we use function code 06H to introduce the data format. For example: write data to register D2 (address H0002) RTU mode:
Asking format Response format Address 01H Address 01H Function code 06H Function code 06H Register address 00H Register address 00H
02H 02H Data contents 13H Data contents 13H
88H 88H CRC CHECK Low 25H CRC CHECK Low 25H
CRC CHECK High 5CH CRC CHECK High 5CH Explanation: 1. Address is PLC station no. 2. Function code is Modbus-RTU protocol read/write code. 3. Register address is the PLC modbus address, please see chapter 7-2-2. 4. Data contents is the value in D2. 5. CRC CHECK Low / CRC CHECK High is low bit and high bit of CRC check value If 2 piece of XINJE XC series PLC communicate with each other, write K5000 to D2.
M0 is trigger condition. If the communication is failure, the instruction will try twice again. If the third time communication is failure, the communication ends. The relationship between REGW and Modbus RTU protocol (other instructions are the same)
REGW Function code 06H K1 Station no. H0002 Modbus address K5000 Data contents 1388H K2 PLC serial port
The complete communication data are : 01H 06H 00H 02H 13H 88H (system take
the CRC checking automatically)
If monitor the serial port data by serial port debugging tool, the data are: 01 06 00 02 13 88 25 5C Note: the instruction doesn’t distinguish decimal, hex, binary, hex, octal, etc. For example,
B10000, K16 and H10 are the same value, so the following instructions are the same. REGW K1 B111110100 D1 K2
REGW K1 K500 D1 K2 REGW K1 H1F4 D1 K2
7-2-4.Communication Instructions Modbus instructions include coil read/write, register read/write; below, we describe these instructions in details: The operand definition in the instruction:
1. Remote communication station and serial port number
For example, one PLC connects 3 inverters. PLC needs to write and read the parameters of inverter. The inverter station no. is 1, 2, 3. So the remote communication station no. is 1, 2, 3.
2. Remote register/coil quantity
For example, PLC read inverter frequency (H2103), output current (H2104) and bus voltage (H2105). So the remote register first address is H2103, quantity is K3 (3 registers).
3. Local coil/register address
For example, local coil is M0, write the M0 state to remote coil.
Local register is D0, write the D0 value to remote register.
Coil Read [COLR] 1、Instruction Summary
Read the specified station’s specified coil status to the local PLC; Coil read [COLR] 16 bits instruction
COLR 32 bits instruction
-
Execution Condition
Normally ON/OFF coil Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the remote communication station 16bits, BIN S2 Specify the remote coil first address 16bits, BIN S3 Specify the coil quantity 16bits, BIN D1 Specify the local coil first address bit D2 Specify the serial port no. 16bits, BIN
3、suitable soft components
COLR K1 K500 K3 M1X0
K2
S1· S2· S3· D1· D2·
Read coil instruction, Modbus function code is 01H Serial Port: K1~K3 Operand S3: K1~K984, the max coil quantity is 984 Input Coil Read [INPR] 1、Instruction
Read the specified station’s specified input coils into local coils: Input coil read [INPR] 16 bits instruction
INPR 32 bits instruction -
Execution Condition
Normally ON/OFF、rising edge Suitable Models XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the remote communication station 16bits, BIN S2 Specify the remote coil first address 16bits, BIN S3 Specify the coil quantity 16bits, BIN D1 Specify the local coil first address bit D2 Specify the serial port no. 16bits, BIN
Operands Operands
X Y M S T C Dn.m
D1 ● ● ● ● ● ●
Word
Function
Bit
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D2 K
3、Suitable Soft Components
INPR K1 K500 K3 M1X0
K2
S1· S2· S3· D1· D2·
Instruction to read the input coil, Modbus function code is 02H Serial port: K1~K3 Operand S3: K1~K984, the max coil quantity is 984 When X0 is ON, execute COLR or INPR instruction, set communication flag after execution
the instruction; when X0 is OFF, no operation. If error happens during communication, resend automatically. If the errors reach 3 times, set the communication error flag. The user can check the relative registers to judge the error
single coil write [COLW] 1、summary
Write the local coil status to the specified station’s specified coil; Single coil write [COLW] 16 bits instruction
COLW 32 bits instruction
-
Execution Condition
Normally ON/OFF、rising edge Suitable Models XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
Operands System
X Y M S T C Dn.m
D1 ● ● ● ● ● ●
Word
Function
Bit
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D2 K
2、Operands Operands Function Type D1 Specify the remote communication station 16bits, BIN D2 Specify the remote coil first address 16bits, BIN S1 Specify the local coil first address bit S2 Specify the serial port no. 16bits, BIN
3、suitable soft components
COLW K1 K500 M1X0
K2
D1· D2· S1· S2·
Write the single coil, Modbus function code is 05H Serial port: K1~K3 multi-coil write [MCLW] 1、Summary
Write the local multi-coil status into the specified station’s specified coil; Multi-coil write [MCLW] 16 bits instruction
MCLW 32 bits instruction -
Execution Condition
Normally ON/OFF、rising edge Suitable Models XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
Operands System
X Y M S T C Dn.m
S1 ● ● ● ● ● ●
Word
Function
Bit
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ● ●
D2 ● ● ● ● ●
S2 K
2、Operands Operands Function Type D1 Specify the remote communication station 16bits, BIN D2 Specify the remote coil first address 16bits, BIN D3 Specify the coil quantity 16bits, BIN S1 Specify the local coil first address bit S2 Specify the serial port no. 16bits, BIN
3、Suitable soft components
MCLW K1 K500 K3 M1X0
K2
D1· S1· S2·D2· D3·
Instruction to write the multiply coils, Modbus function code is 0FH Serial port: K1~K3 Operand D3: the max coil quantity is 952 When X0 is ON, execute COLW or MCLW instruction, set communication flag after
execution the instruction; when X0 is OFF, no operation. If error happens during communication, resend automatically. If the errors reach 3 times, set the communication error flag. The user can check the relative registers to judge the error;
Register Read [REGR] 1、Summary
Read the specified station’s specified register to the local register; Register read [REGR] 16 bits instruction
REGR 32 bits instruction
-
Execution Condition
Normally ON/OFF、rising edge Suitable Models
XC2, XC3, XC5, XCM, XCC
Operands System
X Y M S T C Dn.m
S1 ● ● ● ● ● ●
Word
Function
Bit
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ● ●
D2 ● ● ● ● ●
D3 ● ● ● ● ●
S2 K
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the remote communication station 16bits, BIN S2 Specify the remote register first address 16bits, BIN S3 Specify the register quantity 16bits, BIN D1 Specify the local register first address bit D2 Specify the serial port no. 16bits, BIN
3、Suitable soft components
REGR K1 K500 K3 D1X0
K2
S1· S2· S3· D1· D2·
Instruction to read the REGISTERS, Modbus function code is 03H Serial port: K1~K3 Operand S3: the max register quantity is 61 Read Input Register [INRR] 1、Summary
Read the specified station’s specified input register to the local register Read Input Register [INRR] 16 bits instruction
INRR 32 bits instruction
-
Execution Condition
Normally ON/OFF、rising edge Suitable Models
XC2, XC3, XC5, XCM, XCC
Word
Function
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D1 ●
D2 K
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the remote communication station 16bits, BIN S2 Specify the remote register first address 16bits, BIN S3 Specify the register quantity 16bits, BIN D1 Specify the local register first address 16bits, BIN D2 Specify the serial port no. 16bits, BIN
3、Suitable soft components
INRR K1 K500 K3 D1X0
K2
S1· S2· S3· D1· D2·
Instruction to read the input registers, Modbus function code is 04H Serial port: K1~K3 Operand S3: the max input register quantity is 61 When X0 is ON, execute REGR or INRR instruction, set communication flag after execution
the instruction; when X0 is OFF, no operation. If error happens during communication, resend automatically. If the errors reach 4 times, set the communication error flag. The user can check the relative registers to judge the error;
Word
Function
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D1 ●
D2 K
Single register write [REGW] 1、summary
Instruction to write the local specified register into the specified station’s specified register; Single register write [REGW] 16 bits instruction
REGW 32 bits instruction
-
Execution Condition
Normally ON/OFF、rising edge Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type D1 Specify the remote communication station 16bits, BIN D2 Specify the remote register first address 16bits, BIN S1 Specify the local register first address 16bits, BIN S2 Specify the serial port no. 16bits, BIN
3、Suitable soft components
REGW K1 K500 D1X0
K2
D1· S1· S2·D2·
Write the single register, Modbus function code is 06H Serial port: K1~K3
Word
Function
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ● ●
D2 ● ● ● ● ●
S1 ●
S2 K
Multi-register write [MRGW] 1、Summary
Instruction to write the local specified register to the specified station’s specified register; Multi-register write [MRGW] 16 bits instruction
MRGW 32 bits instruction
-
Execution Condition
Normally ON/OFF 、 rising edge
Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type D1 Specify the remote communication station 16bits, BIN D2 Specify the remote register first address 16bits, BIN D3 Specify the register quantity 16bits, BIN S1 Specify the local register first address 16bits, BIN S2 Specify the serial port no. 16bits, BIN
3、Suitable soft components
MRGW K1 K500 K3 D1X0
K2
D1· D2· D3· S1· S2·
Instruction to write the multiply registers, Modbus function code is 10H Serial port: K1~K3 Operand D3: the max register quantity is 59 When X0 is ON, execute REGW or MRGW instruction, set communication flag after
execution the instruction; when X0 is OFF, no operation. If error happens during communication, resend automatically. If the errors reach 4 times, set the communication error flag. The user can check the relative registers to judge the error;
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
D1 ● ● ● ● ●
D2 ● ● ● ● ●
S1 ●
S2 K
Function
7-2-5.Application Wiring method There are two wiring methods: A、RS232 wiring method
Note:
(1) COM2 with *1 only show the RS232 pins. The RS485 pins are external terminal, which is not listed.
(2) XC series PLC RS232 cannot support full-duplex; it only can communicate in single direction.
(3) The communication distance of RS232 is not far (about 13m). RS485 can be further. B、485 wiring method
Connect all the terminal A, connect all the terminal B. A is RS485+, B is RS485-. Application: One XC series PLC connects 3 XC series PLCs. 3 slave PLCs follow the master’s action. Master PLC Y0 ON, slave Y0 ON. Master PLC Y0 OFF, slave PLC Y0 OFF. But the action of 3 slave PLCs cannot be very synchronous.
Method 1 program
( )SY0
Y0
S0PLC1
STL S0
M8138
M8137
S0COLW K1 H4800 Y0 K2
ZRST M8137 M8138
STLE
S1( )S
STL S1
M8138
M8137
S1COLW K2 H4800 Y0 K2
ZRST M8137 M8138
STLE
S2( )S
STL S2
M8138
M8137
S2COLW K3 H4800 Y0 K2
ZRST M8137 M8138
STLE
S2( )R
There are 3 STL in the program. Every STL is communication program of one slave. If one STL communication is successful, it jumps to the next STL. If not, it tries twice. If three times all fail, M8137 is ON and jump to the next STL. (This program uses serial port 2, if it is other serial port, please see appendix 1 for communication flag bit)
Method 2: use BLOCK to make the program
M8000 is always ON coil, the master will keep on writing the Y0 state to slave Y0. (Please refer to chapter 10 for BLOCK function). Method 3: use broadcast function
When master Y0 state changes, it broadcasts the state to all the slave. The synchronization is better than method 1 and 2.
7-3.FREE FORMAT COMMUNICATION
7-3-1.Communication mode Free format communication transfer data in the form of data block, each block can transfer 128 bytes at most. Free format communication mode Free format is free protocol communication. Now many devices support RS232 or RS485, but the communication protocol is different. For example, XINJE PLC is Modbus protocol, some temperature controllers use special protocol. If PLC needs to read temperature, it can send data according to the temperature controller protocol. Note: Port1, Port2 or Port3 can support free format communication, but free format usually needs
to change the serial port parameters. Port 1 parameter cannot be changed, so it is not recommended to use port 1.
In free format mode, FD8220 (port 2) or FD8230 (port 3) should set to be 255 (FF) Baud Rate: 300bps~115.2Kbps Data Format
Data Bit: 7bits, 8bits Parity: Odd, Even, No Check Stop bit: 1 bit, 2 bits
Start bit: 1 bit Stop bit: 1 bit User can set a start/stop bit, then PLC will automatically add this start/stop bit when sending data; remove this start/stop bit when receiving data. Start bit and stop bit can be seemed as header and frame end. If slave station has start and stop bit, they can be set in software or protocol.
Communication Format: 8 bits, 16 bits If choose 8 bits buffer format to communicate, in the communication process, the high bytes are invalid, PLC only use the low bytes to send and receive data. If choose 16 bits buffer format to communicate, when PLC is sending data, PLC will send low bytes before sending higher bytes
7-3-2.Suitable condition When can we use free format communication? In the last chapter, XINJE PLC communicates with temperature controller, the controller use own protocol. The protocol said that 4 characters should be sent when temperature read/write.
Character Meaning : Data start R Read function T Temperature CR Enter, data end
PLC needs to send the ASCII code of above character to the controller.
The ASCII code of characters:
Character ASCII code : 3A R 52 T 54 CR 0D
PLC cannot use Modbus protocol to communicate with the controller. The free format communication should be used. Please see the details in the following chapter.
7-3-3.Instruction form Send data [SEND] 1、Summary
Write the local specified data to the specified station’s specified ID; Send data [SEND] 16 bits instruction
SEND 32 bits instruction
-
Execution Condition
Normally ON/OFF 、 rising edge
Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the start address of local sending data 16bits, BIN S2 Specify the send character quantity or soft component
address 16bits, BIN
n Specify the serial port no. 16bits, BIN
3、Suitable soft components
SEND D10 D100 K2
S1· S2· nM0
Data send instruction, send data on the rising edge of M0; Serial port: K2~K3 When sending data, set “sending” flag M8132 (COM2) ON
Receive Date [RCV] 1、Summary
Write the specified station’s data to the local specified ID; Receive data [RCV] 16 bits instruction
RCV 32 bits instruction
-
Execution Condition
Normally ON/OFF 、 rising edge
Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify the start address of local receiving data 16bits, BIN
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● ●
n ● K
Function
S2 Specify the receive characters quantity or soft component address
16bits, BIN
n Specify the serial port no. 16bits, BIN
3、Suitable soft components
RCV D20 D200 K2
S1· S2· nM1
Data receive instruction, receive data on the rising edge of M0; Serial port: K2~K3 When receiving data, set “receiving” flag M8134(COM2) ON
※1: If you require PLC to receive but not send, or receive before send, you need to set the communication timeout
to 0ms
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ● ●
n ●
Function
Release serial port [RCVST] 1、Summary Release the serial port Receive data [RCVST] 16 bits instruction
RCVST 32 bits instruction
-
Execution Condition
Normally ON/OFF 、 rising edge
Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type n Specify the serial port no. 16bits, BIN
3、Suitable soft components
RCVST K2
nM0
RCVST instruction, it executes once at the rising edge of M0 Serial port: K2, K3 When releasing the serial port, set OFF M8134 (port 2 receiving sign bit), set ON M8135
(port 2 receive uncompleted sign bit) In free format communication mode, if there is no timeout or the timeout time is too long,
please use RCVST to release the serial port.
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
n K
Function
start
M0
M8135Receive
data
M8134
data
7-3-4.Free format communication application Here we use the example in chapter 7-3-2 (XINJE PLC and temperature controller) to explain the application. Operation:
1. Connect all the hardware wires. 2. Set the PLC serial port parameters as the controller communication parameters. (PLC
station no. is 255 in free format communication). Please restart the PLC after setting the parameters.
3. Make the program as the protocol in chapter 7-3-2. Read temperature send data: : R T CR : ---- start R ---- read T ---- temperature CR ---- enter, end
Two methods to making the program:
A. Normal method
M0
M0
MOV H3A D0
MOV H52 D1
MOV H54 D2
MOV H0D D3
SEND D0 K4 K2
RCV D10 K4 K2
D0:“:”asciicode
D1:“R”asciicode
D2:“T”asciicode
D1:“CR”asciicode
D0:“:”asciicode
M8132
D10:receive start0
0
0
0
0
0
If it needs to use STL, please refer to Modbus example program. Switch the STL by serial port communication sign bit.
B. use BLOCK to make the program Send data:
Receive data
Program:
M8000 is always ON coil; PLC will keep on reading the temperature.
When the PLC communicate with other device, please use serial port debug tool to monitor the data. Then make the free format protocol as the data format in the tool. This method can save time and easy to do. 7-4.CAN Bus Functions
7-4-1.Brief Introduction of CAN-bus XC5 series PLC support CANbus bus function. Below we will give some basic concept on CANbus;
CAN (Controller Area Network) belongs to industrial area bus category. Compared with common communication bus, CAN bus data communication has performance of outstanding dependability、real time ability and flexibility. CAN controller works under multi-master format. In the network, each node can send data to bus according to the bus visit priority. These characters enable each node in CAN bus network to have stronger data communication real time performance, and easy to construct redundant structure, improve the system’s dependability and flexibility.
In CANBUS network, any node can initiatively send message at any time to any other node, no master and no slave. Flexibility communication, it’s easy to compose multi-device backup system, distributing format monitor, control system. To fulfill different real time requirement, the
CAN-bus node Sub address 01
CAN-bus node Sub address 02
CAN-bus node Sub address 03
CAN-bus node Sub address 04
Sub address 00
120R 120R
nodes can be divided to be different priority level. With non-destroy bus adjudication technology, when two nodes send message to the network at the same time, the low level priority node initiatively stop data sending, while high level priority node can continue transferring data without any influence. So there is function of node to node, node to multi-node, bureau broadcasting sending/receiving data. Each frame’s valid byte number is 8, so the transfer time is short, the probability ratio is low.
7-4-2.External Wiring CAN-Bus Communication Port: CAN+, CAN- The wiring among each node of CAN bus is shown in the following graph; at the two ends, add 120 ohm middle-terminal resistors.
7-4-3.CAN Bus Network Form
There are two forms of CAN bus network: one is instructions communication format; the other is internal protocol communication format. These two forms can work at the same time Instructions communication format This format means, in the local PLC program, via CAN-bus instructions, execute bit or word reading/writing with the specified remote PLC. Internal protocol communication format This format means, via setting of special register, via configure table format, realize allude with each other among PLC’s certain soft component’s space. In this way, PLC can share the source in CAN-bus network.
7-4-4.CAN-bus Instructions
Read Coil [CCOLR] 1、Instruction Description
Function: Read the specified station’s specified coil status into the local specified coil. Read Coil [CCOLR] 16 bits instruction
CCOLR 32 bits instruction
-
120R 120R
00 01 02
CAN+ CAN- CAN+ CAN- CAN+ CAN-
Execution Condition
Normally ON/OFF, rising edge activates
Suitable Models
XC5, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 Specify remote communication station no. or soft component’s
address; 16bits, BIN
S2 Specify the remote coil’s start address or soft component’s address; 16bits, BIN S3 Specify the coil quantity or soft component’s address; 16bits, BIN D Specify the local receive coil’s start address bit
3、Suitable Soft Components
CCOLR K2 M20K20 K4
S1· S2· S3· D·X0
Execute CCOLR instruction when X0 changes from OFF to ON; read the four coils data of remote station 2, coil’s start address K20 to local coils M20~M23.
Write the Coil [CCOLW] 1、Summary
Write the local specified multi-coils status into the specified station’s specified coils; Write the coil [CCOLW] 16 bits instruction
CCOLW 32 bits instruction
-
Execution Normally ON/OFF 、 rising Suitable XC5, XCC
Word Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
Function
Operands System
X Y M S T C Dn.m
D ● ● ● ● ● ●
Bit
Condition edge Models Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type D1 Specify remote communication station no. or soft
component’s number; 16 bit, BIN
D2 Specify the remote coil’s start address or soft component’s number;
16 bit, BIN
D3 Specify the coil quantity or soft component’s number;
16 bit, BIN
S Specify the local receive coil’s start address bit
3、Suitable soft components
CCOLW K2 M20K20 K4X0
S·D1· D2· D3·
Execute CCOLW instruction when X0 changes from OFF to ON; write the local M20~M23
to the remote station no.2, coil’s start address K20, coil quantity is 4.
Read Register [CREGR] 1、Summary
Read the specified station’s specified register to the local specified register; Read register [CREGR] 16 bits instruction
CREGR 32 bits instruction -
Execution Condition
Normally ON/OFF、rising edge Suitable Models XC5, XCC
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
Operands System
X Y M S T C Dn.m
D ● ● ● ● ● ●
Bit
Function
Hardware Requirement
- Software Requirement -
2、Operands Operands Function Type D1 Specify remote communication station no. or soft component’s
number; 16bits, BIN
D2 Specify the remote register’s start address or soft component’s number;
16bits, BIN
D3 Specify the register quantity or soft component’s number; 16bits, BIN S Specify the local receive coil’s start address 16bits, BIN
3、Suitable soft components
CREGR K2 D20K20 K4
S1· S2· S3· D·X0
Execute CREGR instruction when X0 changes from OFF to ON; read the remote station no.2, coil’s start address K20 (4 coils) to the local D20~D23
Write the Register [CREGW] 1、Summary
Write the specified local input register to the specified station’s specified register;
Write the register [CREGW] 16 bits instruction
CREGW 32 bits instruction
-
Execution Condition
Normally ON/OFF、rising edge Suitable Models
XC5, XCC
Hardware Requirement
- Software Requirement
-
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D ● ● ●
Function
2、Operands Operands Function Type D1 Specify remote communication station no. or soft
component’s number; 16bits, BIN
D2 Specify the remote register’s start address or soft component’s number;
16bits, BIN
D3 Specify the register quantity or soft component’s number;
16bits, BIN
S Specify the local receive coil’s start address 16bits, BIN 3、Suitable soft components
CREGW K2 D20K20 K4X0
S·D1· D2· D3·
Execute CREGW instruction when X0 changes from OFF to ON; write the local D20~D23 to
the remote station no.2, coil’s start address K20.
7-4-5.Communication Form of Internal Protocol Open/close the internal protocol communication function
Set the value in register FD8350: 0: do not use CAN internal protocol communication; 1: use CAN internal protocol communication CAN internal protocol communication is default to open;
Set the communication parameters Method 1: direct setting
Step1. Add four configure items quantity separately: FD8360—read the bit items, FD8361—read the word items, FD8362—write the bit items, FD8363—write the word items
Word Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
S3 ● ● ● ● ●
D ● ● ●
Function
Function
Step2. Set each configure item’s communication object, each item includes four parameter: remote station, remote object address, local object address, local quantity. The correspond registers are: FD8370~FD8373 represents item 1, FD8374~FD8377 represents item2 … …
FD9390~FD9393 represents item256; totally we can set 256 configure items; see the following table (communication setting).
Item Function Description FD8350 CAN communication mode 0 represents not use; 1 represents internal protocol FD8351 CAN baud rate See CAN baud rate setting table FD8352 Self CAN station no. For CAN protocol using (the default value is 1)
FD8354 Configured sending frequency
The set value’s unit is ms, represents “send every ms” if set to be 0, it means send every cycle, the default value is
5ms FD8360 Read bit number
- FD8361 Read word number FD8362 write bit number FD8363 write word number FD8370 Remote station address
The item 1 configuration FD8371 Remote object address FD8372 Local object address FD8373 Quantity …… …… …… FD9390 Remote node’s ID
The item 256 configuration FD9391 Remote node’s object ID FD9392 Local object’s ID FD9393 Number
M8240 CAN self check error flag
Set 1 if error; set 0 if correct
M8241 Error flag of CAN configure
Set 1 if error; set 0 if correct
Communication Setting
Status Flag
M8242 Automatically recover the control after CAN bus error
If set to be 1, then recover after error happens; If set to be 1, then CAN stops working after error happens; The default value is 1, this flag is not power-off retentive
FD8351 value
Baud Rate (BPS)
0 1K 1 2K 2 5K 3 10K 4 20K 5 40K 6 50K 7 80K 8 100K 9 150K
10 200K 11 250K 12 300K 13 400K 14 500K 15 600K 16 800K 17 1000K
Baud Rate Setting
D8240 CAN error information
0: no error 2: initialize error 30: bus error 31: error alarm 32: data overflow
D8241 The configure item no. which has error Show the first number of error configure item
D8242 Data package quantity sent every second -
D8243 Data package quantity received every second
-
D8244 CAN communication error count -
7-4-6.CAN Free Format Communication Please set FD8350 to 2 for CAN free format communication CAN Sending [CSEND] 1、Instructions Summary
Write the specified data from the unit to a specified address (data transfer in one unit) CAN Sending [CSEND] 16bits instruction
CSEND 32bits instruction
-
Executing Condition
Normally ON/OFF、Rising edge Suitable Models
XC5, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 specify the ID of sending data package 16bits, BIN S2 specify the local sending data or soft component
locally 16bits, BIN
Register Status
S3 specify the byte number of sent data 16bits, BIN 3、Suitable soft components
CSEND K100 D0 K4
S1· S2·M0
S3·
Instruction for data sending, send data at every rising edge of M0 ID number of sending data package is 100, 4 bytes data, the first ID is in D0 8 bits data transfer: the transferred data is: D0L、D1L、D2L、D3L (D0L means the low byte
of D0) 16 bits data transfer: the transferred data is: D0L、D0H、D1L、D1H (D0H means the high byte
of D0)
CSEND D10 D0 D20M0
The ID of sending data package is specified by D10, the data number is specified by D20, the first ID is in D0;
8 bits data transfer: the transferred data is: D0L、D1L、D2L、D3L(D0L means the low byte of D0)
16 bits data transfer: the transferred data is: D0L、D0H、D1L、D1H (D0H means the high byte of D0)
Standard Frame: the valid bits of the data package ID number that is specified by D10 is the low 11 bits, the left bits are invalid;
The expansion frame: the valid bits of the data package ID number that is specified by D10 is the low 29 bits, the left bits are invalid;
The maximum data bits specified by D20 is 8, if exceeds 8, the instruction will send only 8 bits;
Word type
Operands System constant module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ●
S3 ● ● ● ● ●
Functions and Actions
CAN Receive [CRECV] 1、Instructions Summary Write the specified data in one unit to a specified address in another unit (data transfers between different units) CAN Receive [CRECV] 16 bits instruction
CRECV 32 bits instruction
-
Executing Condition
Normally ON/OFF 、 Rising edge
Suitable Models
XC5, XCC
Hardware Requirement
- Software Requirement
-
2、Operands Operands Function Type S1 specify the ID number to receive the data package 16bits, BIN S2 specify the local receiving soft component start ID 16bits, BIN S3 specify the byte quantity of received data 16bits, BIN S4 specify the soft component’s start ID number of ID
filter code 16bits, BIN
3、Suitable soft components
CRECV D0 D10 D20
S1· S2·M0
S3·
D30
S4·
The 32 bits memory combined by [D1, D0] (D0 is low byte, D1 is high byte) is used to stock ID number of the received data package. The received data length is stored in D20. The data content is stored in registers start from D10. D30 specifies the received ID filter code; if the received data doesn’t fit the filter codes, then it will keep the RECV status;
ID filter code: D30 specifies the start address of ID filter codes; the instruction specifies two groups of filter codes, occupy D30~D37;
Word Type
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ● ● ● ●
S3 ● ● ● ●
S4 ●
Functions and Actions
Filter Code
Memory Description Example
The first group
D31, D30 D30 low bytes, D31 high bytes, they compose a 32 bits mask code
D30=0xFFFF, D31=0x0000, then the mask code is 0x0000FFFF D30=0x1234, D31=0x0000, then filter value is 0x00001234 If ID and 0x0000FFFF equals 0x00001234, the pass the first group of filter. If the ID pass any of two groups, the allow the reception
D33, D32 D32 low bytes, D33 high bytes, they compose a 32 bits filter value
The first group
D35, D34 D34 low bytes, D35 high bytes, they compose a 32 bits mask code
D37, D36 D36 low bytes, D37 high bytes, they compose a 32 bits filter value
Standard/ expansion frame: the setting of FD8358 has no effect to reception. If the data frame fulfills ID mask codes, the standard frame and the expansion frames can be all received. When receive the standard frame, the ID bits is 11, but will still occupy the 32 bits memory combined by [D1,D0]
8 bits data transfer: the transfer data is: D0L、D1L、D2L、D3L……(D0L means the low byte of D0)
16 bits data transfer: the transfer data is: D0L、D0H、D1L、D1H……(D0H means the high byte of D0)
Relate Special Soft Components List
1. System FD8000 Setting ID Function Description
FD8350 CAN Mode 0: not usable 1: XC-CAN network 2: Free format FREE
FD8351 CAN baud rate
0, 1KBPS initial value, actual is 5KBPS. 1, 2KBPS initial value, actual is 5KBPS. 2, 5KBPS initial value 3, 10KBPS initial value 4, 20KBPS initial value 5, 40KBPS initial value 6, 50KBPS initial value 7, 80KBPS initial value 8, 100KBPS initial value 9, 150KBPS initial value 10, 200KBPS initial value 11, 250KBPS initial value 12, 300KBPS initial value
13, 400KBPS initial value 14, 500KBPS initial value 15, 600KBPS initial value 16, 800KBPS initial value 17, 1000KBPS initial value
FD8358 CAN free format mode
low 8 bits: 0-standard frame . low 8 bits: 1-expansion frame high 8 bits: 0-8 bits data store high 8 bits: 1-16 bits data store
FD8359 CAN accept timeout time
for free format using, unit: ms
CAN send timeout time
fixed to be 5ms
2. System M8000 flag
ID Function Description
M8240 CAN error flag
ON: error happens OFF: normal if set M8242 as ON, and manually set M8240 as ON, this will enable CAN reset
M8241 CAN node dropped off flag
XC-CAN mode valid ON: certain node/nodes are dropped off OFF: Normal
M8242 do reset or not if CAN error happens
ON: CAN reset automatically when error happens OFF: take no operation when error happens
M8243 CAN send/accept finished flag
FREE mode valid ON: receive/accept finish reset ON automatically when starting to send/accept
M8244 CAN send/accept timeout flag
FREE mode valid ON: send/accept timeout Set OFF automatically when starting to send/accept
3. System D8000
ID Function Description
D8240 CAN error information
0: no error 2: initializing error 30: CAN bus error 31: error alarm 32: data overflow
D8241 configure item number when XC-CAN valid
error happens
D8242 data package number sent every second
both XC-CAN and FREE modes are valid
D8243 data package number accepted every second
both XC-CAN and FREE modes are valid
D8244 CAN communication error counter
correspond with M8240 at every CAN error, M8240 will be set ON one time, D8244 increase 1
Note: when D8240 is not zero, please try the follow operations:
1. Check the wiring 2. Decrease baud rate or increase sending frequency
Applications Example 1: instruction communication PLC station 1 and PLC station 2 communicate with each other through CAN instructions. Program: (1) M0 is ON, send D100 of PLC station 1 to D20 of PLC station 2 (Y0 and Y2 is ON) (2) M4 is ON, send D4000 of PLC station 2 to D0 of PLC station 1. Ladder chart: PLC station 1:
Set CAN baud rate = 1000K, sending frequency=5, CAN station no.1, master station no. 1022
Write these parameters in PLC, cut off and power on the power again
MOV K5 D100M8002
M0 M8013
CREGW K2 K20 K1 D100
CREGR K2 K4000 K1 D0
M4
PLC station 2:
Example 2: Internal protocol PLC station 1 and station 2 communicate with each other through CAN internal communication mode. Program: (1) send (D4000, D4001) of station 2 to (D0, D1) of station 1 (2) send M0 state of station 1 to M0 of station 2, show the M0 state in Y0 of station 2 (3) set on M0 when station 1 power on Programming and ladder chart:
(1) Open XCPpro software, click , configure station 1.
send M0 state of station 1 to M0 of station 2
set on M0 when station 1 power on
(1) Open XCPpro software, click , configure station 2.
send (D4000, D4001) of station 2 to (D0, D1) of station 1
send M0 state of station 1 to M0 of station 2, show the M0 state in Y0 of station 2
Example 3: Free format (please set FD8350 to 2 first) Two Xinje PLCs communicate with each other through CAN free format mode Program: (1) PLC station 1 sends the data package ID100 (4 bytes starts from D4000) every 1s
(2) When M0 is ON, PLC station 2 receives data package ID100 (4 bytes, ID filter code is defaulted), then save the data in register starts from D4000.
Ladder chart: PLC station 1:
PLC station 2:
8 PID Control Function In this chapter, we mainly introduce the applications of PID instructions for XC series PLC basic units, including: call the instructions, set the parameters, items to notice, sample programs etc.
8-1. Brief Introduction of The Functions
8-2. Instruction Formats
8-7. Sample Programs
8-5. Advanced Mode
8-6.Application Outlines
8-4. Auto Tune Mode
8-3. Parameter Setting
8-1.Brief Introductions of The Functions PID instruction and auto tune function are added into XC series PLC basic units (Version 3.0 and above). Via auto tune method, users can get the best sampling time and PID parameters and improve the control precision.
The previous versions can not support PID function on basic units unless they extend analog module or BD cards. PID instruction has brought many facilities to the users. 1. The output can be data form D and on-off quantity Y, user can choose them freely when program. 2. Via auto tune, users can get the best sampling time and PID parameters and improve the control precision. 3. User can choose positive or negative action via software setting. The former is used to heating control; the later is used to cooling control. 4. PID control separates the basic units with the expansions; this improves the flexibility of this function. 5. A new PID algorithm-critical oscillation is added in v3.3 and higher version of PLC. For temperature control object: Step response method: the PID auto tune will start when current temperature of object is equal to ambient temperature. Critical oscillation method: the PID auto tune will start at any temperature. 8-2.Instruction Forms 1、Brief Introductions of the Instructions
Execute PID control instructions with the data in specified registers. PID control [PID] 16 bits instruction
PID 32 bits instruction
-
Executing Condition
Normally ON/normally closed coil activates
Suitable Models
XC2, XC3, XC5, XCM, XCC
Hardware Condition
V3.0 or above Software Condition
V3.0 or above V3.3a and above (critical oscillation)
V3.3f and above (critical oscillation)
2、Operands
Operands Usage Type S1 set the address of the target value (SV) 16bits, BIN S2 set the address of the tested value (PV) 16 bits, BIN S3 set the start address of the control parameters 16 bits, BIN D the address of the operation result (MV) or output port 16 bits, BIN; bit
3、Suitable soft components
PID D0 D10 D4000 D100
X0D·S1· S2· S3·
PID D0 D10 D4000 Y0
X0D·S1· S2· S3·
S3~ S3+ 43 will be occupied by this instruction, so please don’t use them as the
common data registers.
This instruction executes when each sampling time interval comes.
To the operation result D, the data registers are used to store PID output values; the output points are used to output the occupy space ratio in the form of ON/OFF.
PID control rules are shown as below:
Operands System
X Y M S T C Dn.m
D ● ● ● ● ●
Word
Type
Functions and Actions
Bit
Type
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ●
S2 ● ●
S3 ●
D ● ●
u(t) c(t) r(t) + e(t)
Proportion
Integral
Differential
Be controlled object
+
+
+
-
e(t) = r (t ) –c ( t ) (1-1) u(t) = Kp [ e ( t ) + 1/Ti∫e(t)dt + TD de(t)/dt] (1-2)
Here, e(t) is warp, r(t) is the given value, c(t) is the actual output value, u(t) is the control value;
In function (1-2), Kp is the proportion coefficient, Ti is the integration time coefficient, and TD is the differential time coefficient. The result of the operation: 1. Analog output: MV= digital form of u (t), the default range is 0 ~ 4095. 2. Digital output: Y=T*[MV/PID output upper limit]. Y is the output’s activate time within the
control cycle. T is the control cycle, equals to the sampling time. PID output upper limit default value is 4095.
8-3.Parameters Setting Users can call PID instruction in XCP Pro software directly and set the parameters in the window (see graph below), for the details please refer to XCPPro user manual. Users can also write the parameters into the specified registers by MOV instructions before PID operation.
Auto tune mode:
V3.3f and higher version software can choose auto tune mode: step response or critical oscillation.
8-3-1.Registers and their functions For PID control instruction’s relative parameters ID, please refer to the below table:
ID Function Description Memo S3 sampling time 32 bits without sign Unit: ms S3+1 sampling time 32 bits without sign Unit: ms S3+2 mode setting bit0:
0: Negative action; 1 positive action; bit1~bit6 not usable bit7: 0: Manual PID; 1: auto tune PID bit8: 1: auto tune successful flag bit9~bit10 auto tune method
00: step response 01: critical oscillation Bit11~bit12: not use Bit13~bit14: auto tune PID mode(valid in critical oscillation mode) 00: PID control 01: PI control 10: P control bit15: 0: regular mode; 1: advanced mode
S3+3 Proportion Gain (Kp) Range: 1~32767[%] S3+4 Integration time (TI) 0~32767[*100ms] 0 is taken as no integral. S3+5 Differential time (TD) 0~32767[*10ms] 0 is taken as no differential. S3+6 PID operation zone 0~32767 PID adjustment band width
value. S3+7 control death zone 0~32767 PID value keeps constant in
death zone S3+8 PID auto tune cycle
varied value full scale AD value * (0.3~1%)
S3+9 PID auto tune overshoot permission
0: enable overshoot 1:not overshoot
(valid when using step response method)
S3+10 current target value adjustment percent in auto tune finishing transition stage
S3+11 current target value resident count in auto tune finishing transition stage
S3+12~ S3+39
occupied by PID operation’s internal process
Below is the ID of advanced PID mode setting S3+40 Input filter constant (a) 0~99[%] 0: no input filter S3+41 Differential gain (KD) 0~100[%] 0: no differential gain S3+42 Output upper limit value -32767~32767 S3+43 Output lower limit value -32767~32767
8-3-2.Parameters Description
Movement Direction:
Positive movement: the output value MV will increase with the increasing of the detected value PV, usually used for cooling control.
Negative movement: the output value MV will decrease with the increasing of the detected value PV, usually used for heating control.
Mode Setting
Common Mode: The parameter’s register zone is from S3 to S3+43, S3 to S3+11 needs to be set by users. S3+12 to S3+43+12 are occupied by the system, users can’t use them.
Advanced Mode The parameter’s register zone is from S3 to S3+43, S3 to (S3+11) and (S3+40) to (S3+43) need to be set by users. (S3+12) to (S3+39) are occupied by the system, users can’t use them.
Sample Time [S3]
The system samples the current value according to certain time interval and compare them with the output value. This time interval is the sample time T. There is no requirement for T during AD output. T should be larger than one PLC scan period during port output. T value should be chosen among 100~1000 times of PLC scan periods.
PID Operation Zone [S3+6]
PID control is entirely opened at the beginning and close to the target value with the highest speed (the defaulted value is 4095), when it entered into the PID computation range, parameters Kp, Ti, TD will be effective. See graph below:
If the target value is 100, PID operation zone is 10, then the real PID’s operation zone is from 90 to 110.
Death Region [S3+7]
If the detected value changed slightly for a long time, and PID control is still in working mode, then it belongs to meanless control. Via setting the control death region, we can overcome this condition. See graph below:
Suppose: we set the death region value to be 10. Then in the above graph, the difference is only 2 comparing the current value with the last value. It will not do PID control. The difference is 13 (more than death region 10) comparing the current value with the next value, this difference value is larger than control death region value, it will do the PID control with 135. 8-4.Auto Tune Mode If users do not know how to set the PID parameters, they can choose auto tune mode which can find the best control parameters (sampling time, proportion gain Kp, integral time Ti, differential time TD) automatically. Auto tune mode is suitable for these objects: temperature, pressure; not suitable for liquid level and flow. For step response method: Users can set the sampling cycle to be 0 at the beginning of the auto tune process then modify the value manually in terms of practical needs after the auto tune process is completed. For step response method: Before doing auto tune, the system should be under the non-control steady state. Take the temperature for example; the detected temperature should be the same to the environment temperature. For critical oscillation method: user needs to set the sampling time at the beginning of the auto tune process. Reference value: for slow response system, 1000ms. For high response system, 10-100ms. For critical oscillation method: the system can start the auto tune at any state. For temperature object, the current temperature doesn’t need to be same to ambient temperature. Two different method and PID control diagram:
(1) Step response method Make sure current temperature is equal to ambient temperature
(2) Critical oscillation method The auto tune start temperature can be any value
To enter the auto tune mode, please set bit7 of (S3+ 2) to be 1 and turn on PID working condition.
If bit8 of (S3+ 2) turn to 1, it means the auto tune is successful.
PID auto tune period value [S3+ 8]
Set this value in [S3+ 8] during auto tune. This value decides the auto tune performance, in a general way, set this value to be the AD result corresponding to one standard detected unit. The default value is 10. The suggested setting range: full-scale AD result × 0.3 ~ 1%. User doesn’t need to change this value. However, if the system is interfered greatly by outside, this value should be increased modestly to avoid wrong judgment for positive or negative movement. If this value is too large, the PID control period (sampling time) got from the auto tune process will be too long. As the result do not set this value too large. ※1: if users have no experience, please use the defaulted value 10, set PID sampling time (control period) to be 0ms then start the auto tune.
PID auto tune overshooting permission setting [S3+ 9] If set 0, overshooting is permitted, the system can study the optimal PID parameters all the time. But in auto tune process, detected value may be lower or higher than the target value, safety factor
should be considered here.
If set 1, overshooting is not permitted. For these objectives which have strict safety demand such
as pressure vessel, set [S3+ 9] to be 1 to prevent from detected value seriously over the target
value. In this process, if [S3+ 2] bit8 changes from 0 to 1, it means the auto tune is successful and
the optimal parameters are got; if [S3+ 2] is always 0 until [S3+ 2] bit7 changes from 1 to 0, it
means the auto tune is completed but the parameters are not the best and need to be modified by
users.
Every adjustment percent of current target value at auto tune process finishing transition
stage [S3+10]
This parameter is effective only when [S3+ 9] is 1.
If doing PID control after auto tune, small range of overshooting may be occurred. It is better to
decrease this parameter to control the overshooting. But response delay may occur if this value is
too small. The defaulted value is 100% which means the parameter is not effective. The
recommended range is 50~80%.
Cutline Explanation: Current target value adjustment percent is 2/3 (S3 + 10 = 67%), the original temperature of the system is 0 ºC, target temperature is 100 ºC, the current target temperature adjustment situation is shown as below:
Next current target value = current target value + (final target value – current target value ) × 2/3;
So the changing sequence of current target is 66 ºC, 88 ºC, 96 ºC, 98 ºC, 99 ºC, 100 ºC.
℃
t
100 96 88
66
Current system value
Current target 3 Current target 2
Current target 1
Target value
The stay times of the current target value in auto tune process finishing transition stage [S3+11]
This parameter is valid only when [S3+9] is 1; If entering into PID control directly after auto tune, small range of overshoot may occur. It is good for preventing the overshoot if increasing this parameter properly. But it will cause response lag if this value is too large. The default value is 15 times. The recommended range is from 5 to 20. 8-5.Advanced Mode Users can set some parameters in advanced mode in order to get the better effect of PID control. Enter into the advanced mode, please set [S3+2] bit 15 to be 1, or set it in the XCP Pro software. Input Filter constant
It will smooth the sampling value. The default value is 0% which means no filter. Differential Gain The low pass filtering process will relax the sharp change of the output value. The default value is 50%, the relaxing effect will be more obviously if increasing this value. Users do not need to change it. Upper-limit and lower-limit value Users can choose the analog output range via setting this value. Default value: lower- limit output= 0 Upper -limit= 4095 8-6.Application Outlines Under the circumstances of continuous output, the system whose effect ability will die down
with the change of the feedback value can do self-study, such as temperature or pressure. It is not suitable for flux or liquid level.
Under the condition of overshoot permission, the system will get the optimal PID parameters from self-study.
Under the condition of overshoot not allowed, the PID parameters got from self-study is up to the target value, it means that different target value will produce different PID parameters which are not the optimal parameters of the system and for reference only.
If the self-study is not available, users can set the PID parameters according to practical experience. Users need to modify the parameters when debugging. Below are some experience values of the control system for your reference:
8-7.Application PID Control Program is shown below:
Soft component function comments: D4000.7: auto tune bit D4002.8: auto tune successful sign M0: normal PID control M1: auto tune control M2: enter into PID control after auto tune
// Move ID100 content into D10
// convert PID mode to be auto tune at
the beginning of auto tune control
starts or auto tune finish
// start PID, D0 is target value, D10 is
detected value, from D4000 the zone
is PID parameters area; output PID
result via Y0
// PID control finish, close auto tune PID
mode
// if auto tune is successful, and
overshoot is permitted, close auto
tune control bit, auto tune finish;
If auto tune turns to be manual mode,
and auto tune is not permitted, close
auto tune control bit
Temperature system: P (%) 2000 ~ 6000, I (minutes) 3 ~ 10, D (minutes) 0.5 ~ 3 Flux system: P (%) 4000 ~ 10000, I (minutes) 0.1 ~ 1 Pressure system: P (%) 3000 ~ 7000, I (minutes) 0.4 ~ 3 Liquid level system: P (%) 2000 ~ 8000, I (minutes) 1 ~ 5
9 C Language Function Block In this chapter, we focus on C language function block’s specifications, edition, instruction calling, application points etc. we also attach the common Function list.
9-1.Functions Summary
9-2.Instrument Form
9-3.Operation Steps
9-4.Import and Export of the Functions
9-5.Edit the Function Block
9-6.Example Program
9-7.Application Points
9-8.Function List
9-1.Summary This is the new added function in XCPPro software. This function enables the customers to write program via C language in XCPPo; and call the C program at any necessary place. This function supports most of C language functions, strength the program’s security. As users can call the function at many places and call different functions, this function increase the programmer’s efficiency greatly.
9-2.Instruction Format 1、Instruction Summary
Call the C language Func Block at the specified place Call the C language Func Block [NAME_C] 16 bits Instruction
NAME_C 32 bits Instruction
-
Execution Condition
Normally ON/OFF, Rising/Falling Edge activation
Suitable Models
XC1, XC2, XC3, XC5, XCM, XCC
Hardware Requirement
V3.0C and above Software Requirement
V3.0C and above
2、Operands Operands Function Type S1 name of C Func Block, defined by the user String S2 Correspond with the start ID of word W in C language
Function 16 bits, BIN
S3 Correspond with the start ID of word B in C language Function
16 bits, BIN
3、Suitable Soft Components
Operands System
X Y M S T C Dn.m
S3 ●
Word
Bit
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S2 ●
NAME_C D0 M0X0
S1· S2· S3·
The name is composed by numbers, letters and underlines, the first character
can’t be numbers, the name’s length shouldn’t longer than 8 ASC. The name can’t be same with PLC’s self instructions like LD,ADD,SUB,PLSR
etc. The name can’t be same with the func blocks exist in current PLC; 9-3.Operation Steps 1、Open PLC edit tool, in the left “Project” toolbar, choose “Func Block”, right click it
and choose”Add New Func Block”
2、See graph below, fill in the information of your function;
Functions and Actions
3、After new create the Func Block, you can see the edit interface as shown below:
Parameters’ transfer format: if call the Func Block in ladder, the transferred D
and M is the start ID of W and B. Take the above graph as the example, start with D0 and M0, then W[0] is D0, W[10] is D10, B[0 is M0, B[10]is M10. If in the ladder the used parameters are D100, M100, then W[0] is D100, B[0]is M100. So, word and bit component’s start address is defined in PLC program by the user.
Parameter W: represent Word soft component, use in the form of data group. E.g. W[0]=1;W[1]=W[2]+W[3]; in the program, use according to standard C language
Edit your C language program between “{}”
Main function’s name (it’s function block’s name, this name can’t be changed freely, and users should modify in the edit window.
WORD W: correspond with soft component D BIT B: correspond with soft component M
rules. Parameter B: represent Bit soft component, use in the form of data group.
Support SET and RESET. E.g: B[0]=1;B[1]=0; And assignment, for example B[0]=B[1]。
Double-word operation: add D in front of W, e.g. DW[10]=100000, it means assignment to the double-word W[10]W[11]
Floating Operation: Support the definition of floating variable in the function, and execute floating operation;
Function Library: In Func Block, users can use the Functions and Variables in function library directly. For the Functions and Variables in function library, see the list in Appendix.
The other data type supported: BOOL; //BOOL Quantity
INT8U; //8 bits unsigned integral INT8S; //8 bits signed integral
INT16U //16 bits unsigned integral INT16S //8 bits signed integral
INT32U //32 bits unsigned integral INT32S //32 bits signed integral
FP32; //Single precision Floating FP64; // Doubleprecision Floating
Predefined Marco #define true 1 #define false 0 #define TRUE 1 #define FALSE 0
9-4.Import and Export the Functions 1、Export (1) Function: export the function as the file, then other PLC program can import to use;
(2) Export Format
a) Editable; export the source codes out and save as a file. If import again, the file is editable; b) Not editable: don’t export the source code, if import the file, it’s not editable;
2、Import
Function; Import the exist Func Block file, to use in the PLC program;
Choose the Func Block, right click “Import Func Block From Disk”, choose the correct file, then click OK.
9-5.Edit the Func Blocks Example: Add D0 and D1 in PLC’s registers, then assign the value to D2; (1) In “Project” toolbar, new create a Func Block, here we name the Func Block as
ADD_2, then edit C language program; (2) Click compile after edition
According to the information shown in the output blank, we can search and modify the grammar error in C language program. Here we can see that in the program there is no “;” sign behind W[2]=W[0]+W[1];
Compile the program again after modify the program. In the information list, we can corfirm that there is no grammar error in the program;
The information list
(3) Write PLC program, assign value 10 and 20 into registers D0, D1 separately, then call Func Block ADD_2, see graph below:
(4) Download program into PLC, run PLC and set M0.
(5) From Free Monitor in he toolbar, we can see that D2 changes to be 30, it means the assignment is successful;
Free Monitor
9-6.Program Example If PLC needs to do complicated calculation (including plus and minus calculation), the calculation will be used for many times, C language function is easy to use. Example 1: Calculation a=b/c+b*c+(c-3)*d. Method 1: use ladder chart: Get the result of c-3 Get the result of three multiplication equations Get the sum Ladder chart only support two original operands, it needs many steps to get the result.
Note:
1. The result of MUL is Dword, the result is stored in D14~D15. 2. The result of DIV has quotient D16 and remainder D17. If D17 has value, the
calculation precision will decrease. Please use float format to ensure the precision.
3. D16 quotient is word value, in plus calculation all the data should be changed to Dword. The final result is stored in D22~D23.
Method 2: use C language Ladder chart:
目 标 值
P I D 运 算 范 围
P I D 全 开 区
时 间 t
输 出 值
C program:
RESULT Function name D0 In the function, W[0]=D0, W[1]=D1….
If S2=D32, then W[0]=D32, W[1]=D33…. M0 In the function, B[0]=M0, B[1]=M1…..
If S2=M32, then B[0]=M32, B[1]=M33…. Method 2 can simplify the program. The C function is the same to ladder chart of method 1. The precision is not high. If it needs to get the high precision, please use float calculation. Example 2: calculate CRC parity value via Func Block CRC calculation rules: (1) Set 16 bits register (CRC register) = FFFF H (2) XOR (Exclusive OR) 8 bits information with the low byte of the 16 bits CRC register. (3) Right shift 1 bit of CRC register, fill 0 in the highest bit. (4) Check the right shifted value, if it is 0, save the new value from step3 into CRC register; if it is not 0, XOR the CRC register value with A001 H and save the result into the CRC register. (5) Repeat step3&4 until all the 8 bits have been calculated. (6) Repeat step2~5, then calculate the next 8 bits information. Until all the information has been calculated, the result will be the CRC parity code in CRC register.
Edit C language Function Block program, see graph below:
Edit PLC ladder program, D0: Parity data byte number; D1~D5: Parity data’s content, see graph below:
MOV H5 D0M8002
MOV H12 D1
MOV H34 D2
MOV H56 D3
MOV H78 D4
MOV H90 D5
CRC_CHECK D0 M0M8002
Download to PLC, then RUN PLC, set M0, via Free Monitor, we can find that values in D6
and D7 are the highest and lowest bit of CRC parity value;
9-7.Application Points When upload the PLC program in which there are some Func Blocks, the Func
Blocks can’t be uploaded, there will be an error say: There is an unknown instruction;
In one Func Block file, you can write many functions, they can be call each other; Each Func Block files is independent, they can’t call each other; Func Block files can call C language library functions in form of floating,
arithmetic like sin, cos, tan etc.
XCPpro software v3.3 and later version add C function library:
In this function block, user can call the C function directly:
For example: click TEL10, the function name will show on the project bar:
User can call it in the ladder chart editing window.
9-8.Function Table
The default function library
Constant Data Description _LOG2 (double)0.693147180559945309417232121458 Logarithm of 2
_LOG10 (double)2.3025850929940459010936137929093 Logarithm of 10
_SQRT2 (double)1.41421356237309504880168872421 Radical of 2
_PI (double)3.1415926535897932384626433832795 PI
_PIP2 (double)1.57079632679489661923132169163975 PI/2
_PIP2x3 (double)4.71238898038468985769396507491925 PI*3/2
String Function Description
void * memchr(const void *s, int c, size_t n); Return the first c position among n words before s position
int memcmp(const void *s1, const void *s2, size_t n); Compare the first n words of position s1 and s2
void * memcpy(void *s1, const void *s2, size_t n); Copy n words from position s2 to s1and return s1
void * memset(void *s, int c, size_t n); Replace the n words start from s position with word c, and return position s
char * strcat(char *s1, const char *s2); Connect string ct behind string s
char * strchr(const char *s, int c); Return the first word c position in string s
int strcmp(const char *s1, const char *s2); Compare string s1 and s2 char * strcpy(char *s1, const char *s2); Copy string s1 to string s2
Double-precision math
function Single-precision math
function Description
double acos(double x); float acosf(float x); Inverse cosine function. double asin(double x); float asinf(float x); Inverse sine function double atan(double x); float atanf(float x); Inverse tangent function double atan2(double y, double x);
float atan2f(float y, float x); Inverse tangent value of parameter (y/x)
double ceil(double x); float ceilf(float x); Return the smallest double integral which is greater or equal with parameter x
double cos(double x); float cosf(float x); Cosine function
double cosh(double x); float coshf(float x); Hyperbolic cosine function cosh(x)=(e^x+e^(-x))/2.
double exp(double x); float expf(float x); Exponent (e^x) of a nature data double fabs(double x); float fabsf(float x); Absolute value of parameter x double floor(double x); float floorf(float x); Return the largets dounble
integral which is smaller or equals with x
double fmod(double x, double y);
float fmodf(float x, float y); If y is not zero, return the reminder of floating x/y
double frexp(double val, int _far *exp);
float frexpf(float val, int _far *exp);
Break floating data x to be mantissa and exponent x = m*2^exp, return the mantissa of m, save the logarithm into exp.
double ldexp(double x, int exp);
float ldexpf(float x, int exp);
X multipy the (two to the power of n) is x*2^n.
double log(double x); float logf(float x); Nature logarithm logx double log10(double x); float log10f(float x); logarithm (log10x)
double modf(double val, double *pd);
float modff(float val, float *pd);
Break floating data X to be integral part and decimal part, return the decimal part, save the integral part into parameter ip.
double pow(double x, double y);
float powf(float x, float y); Power value of parameter y (x^y)
double sin(double x); float sinf(float x); sine function
double sinh(double x); float sinhf(float x); Hyperbolic sine function, sinh(x)=(e^x-e^(-x))/2.
double sqrt(double x); float sqrtf(float x); Square root of parameter X
double tan(double x); float tanf(float x); tangent function.
double tanh(double x); float tanhf(float x); Hyperbolic tangent function, tanh(x)=(e^x-e^(-x))/(e^2+e^(-x)).
The using method of the functions in the table:
Take function arcsin as an example. float asinf (float x); float asinf: float means the return value is float format; float x: float means the function formal parameter is float format. In actual using, it no needs to write the float. See line14 in the following example:
10 SEQUENCE BLOCK
This chapter will introduce the sequence block instruction and the application.
10-1. Concept of the BLOCK
10-2. Call the BLOCK
10-3. Edit the instruction inside the BLOCK
10-4. Running form of the BLOCK
10-5. BLOCK instruction editing rules
10-6. BLOCK related instructions
10-7. BLOCK flag bit and register
10-8. Program example
Block instruction:
Instruction Function Ladder chart Chapter
Block
SBSTOP Stop the BLOCK SBSTOP S1 S2
10-6-1
SBGOON Continue running the
BLOCK SBGOON S1 S2
10-6-1
10-1.Concept of the BLOCK
10-1-1.BLOCK summarization
Sequence block, which is also called block, is a program block can realize certain function. Block is a special flow, all the instructions run in order; this is the difference from other flows. BLOCK starts from SBLOCK and ends by SBLOCKE, you can write program between them. If there are many pulse output instructions (or other instructions), they will run one after one according to the condition. After one pulse outputting over then the next pulse will output.
The construction of the block is as the following:
※1: The BLOCK quantity can up to 100 for XC series PLC, XC3-14 BLOCK quantity is 30.
User’s program
Pulse output Communication Frequency inverter Wait instruction Instruction list
SBLOCK n
SBLOCKE
BLOCK start
The instructions in the BLOCK run one after one
BLOCK end
10-1-2.The reason to use BLOCK
To optimize the editing method of pulse and communication instruction in the process In former program, XC series PLC can not support many pulse or communication
instructions in one process, but BLOCK can support this and the instructions will run in sequence.
Unavailable (×) Available (√)
Former
After using block
DPLSR D0 D2 D4 Y0
M0
DPLSR D6 D8 D10 Y0
SBLOCK Sequence block1
SBLOCKE
Former
After using block
M0
SBLOCK communication
COLR K1 K500 K3 M1 K2
COLR K2 K500 K3 M1 K2
SBLOCKE
Note: when the trigger condition of BLOCK is normal ON coil, the BLOCK will execute one by one from up to down circular until the condition is OFF. When the trigger condition of BLOCK is rising edge, the BLOCK will execute once from up to down. 10-2.Call the BLOCK
In one program file, it can call many BLOCK; the following is the method to add BLOCK in the program.
10-2-1.Add the BLOCK
Open XCPpro software, right click the sequence block in the project bar:
Click “add sequence block” will show below window:
You can edit the program in this window. Upwards and downwards are used to change the
position of the instruction in the block. There is a “Insert” choice on the bottom left of the window, when selecting it, the add button
will become insert:
The difference between insert and add: Add is to add instructions in the end of the block; insert can add instruction in any place in
the block. Click add button, you will see the instructions can be added in the block.
For example, add a pulse item in the program:
Click ok, the pulse item is added in the list:
Click ok, the BLOCK will show in the program:
10-2-2.Move the BLOCK
If you want to move the block to other position, you have to select the former block and delete it.
Then put the cursor in the place you want to move:
Right click the “add to lad” in the project bar:
Now the block is moved to the new place:
10-2-3.Delete the BLOCK
You can select the whole block and delete it. If you want to delete the block forever, please right click the block you want to delete in the project bar and select “delete sequence block”. After this operation, you can not call this block anymore.
10-2-4.Modify the BLOCK
There are two methods to modify the block. (A)double click the start or end instruction to modify all the instructions in the block.
(B)double click one instruction in the block to modify it:
10-3.Edit the instruction inside the BLOCK
10-3-1.Common item
Use command to edit the program. Open the block editing window, click add/common item:
It will show the editing window:
User can add instructions in this window.
SKIP condition: can control the stop and running of the instructions. When select skip and enter coil in it, if the coil is ON, the instructions will stop.
Comment: can modify the note for this instruction.
After setting, the block will be changed as the following:
10-3-2.Pulse item
Open the pulse item window:
Set the pulse output frequency, numbers, output terminals, accelerate/decelerate time and so
on. Then add the pulse instruction in the block:
※1:The pulse output instructions are all 32bits.
10-3-3.Modbus item
Open the modbus item window:
Select the modbus instructions, set the address and com port, then software will build an
instruction.
10-3-4.Wait item
There are two modes to wait. (A) flag bit
(B) timer wait
The ladder chart is as the following:
10-3-5.Frequency inverter item
Users only have to set the parameters in below window, the PLC will communicate with the frequency inverter.
There are four areas in the window, the following will introduce one by one: (A) Inverter station number and serial number
Set the station number of the frequency inverter and the PLC serial port:
(B) Control inverter action There are two modes to set parameters. First one is write constant value:
Second one is to set the parameters in register:
(C) Inverter status read into To read the status from the frequency inverter to the PLC register.
(D) User define To write or read the frequency inverter address flexible.
For example, add a writing inverter instruction:
Add a reading inverter instruction:
The result after adding:
※1:Frequency inverter instructions will not expand in the block.
10-3-6.Free format communication item Add free format communication instructions in the block. For example, select “send” instruction, first address set to D0, serial port is 2, 16 bits.
There are two methods to set the data. Const data is to set the value directly. Reg is to set the
value via register.
Change to check out tab, select the checking mode.
Besides, it needs to set the communication parameters. Click “serial port config”:
10-4.Running form of the BLOCK 1. If there are many blocks, they run as the normal program. The block is running when the condition is ON. (A) The condition is normal ON, normal OFF coil
M1SBLOCK Sequence block 1
SBLOCK Sequence block 2
SBLOCK Sequence block 3
M2
M3
(B) the condition is rising or falling edge of pulse
When M1, M2, M3 is from OFF to ON, all these blocks will run once.
2. The instructions in the block run in sequence according to the scanning time. They run one after
another when the condition is ON. (A) Without SKIP condition
Scanning period 1 Scanning period 2 Scanning period 3
Block1 Block1, Block2 Block1, Block2, Block3
M1
M2
M3
M1
SBLOCK Sequence block 1
SBLOCK Sequence block 2
SBLOCK Sequence block 3
M2
M3
↑
↑
↑
The instructions running sequence in block 1 is shown as below:
(B) With SKIP condition
Scanning period 1 Scanning period 2 Scanning period 3 Scanning period 4 Scanning period 5
PLS Y0 PLS Y1 Inverter config
BLOCK running
BLOCK condition is
OFF and all the
sequence instructions
are finished running.
M2
M2
SBLOCK Sequence block1
Inverter Config
SBLOCKE
↑
M0( )
Y0
M1( )
Y1
DPLSR D 0 D2 D4 Y0
DPLSR D 0 D2 D4 Y1
Explanation: A) When M2 is ON, block 1 is running. B) All the instructions run in sequence in the block. C) M3, M4, M5 are the sign of SKIP, when they are ON, this instruction will not run. D) When M3 is OFF, if no other instructions use this Y0 pulse , DPLSR D0 D2 D4 Y0 will
run; if not, the DPLSR D0 D2 D4 Y0 will run after it is released by other instructions. E) After “DPLSR D0 D2 D4 Y0” is over, check M4. If M4 is OFF, check “DPLSR D0 D2
D4 Y1”, if M4 is ON, check M5. If M5 is OFF, “inverter config” will run. 10-5.BLOCK instruction editing rules
In the BLOCK, the instruction editing should accord with some standards.
1. Do not use the same pulse output terminal in different BLOCK.
NO(×) YES(√)
M2SBLOCK Sequence block1
Inverter config
SBLOCKE
M0( )
Y0
M1( )
Y1
DPLSR D0 D2 D4 Y0
DPLSR D0 D2 D4 Y1
M3
M4
M5
DPLSR D0 D2 D4 Y0
M 0 SBLOCK Sequence block1
SBLOCKE
M1
M2
DPLSR D10 D12 D14 Y0
SBLOCK Sequence block2
SBLOCKE
DPLSR D0 D2 D4 Y 0
M 0 SBLOCK Sequence block1
SBLOCKE
M1
M 2
DPLSR D10 D12 D14 Y1
SBLOCK Sequence block2
SBLOCKE
2. Do not use the same pulse output terminal in BLOCK and main program.
NO(×) YES(√)
3. There only can be one SKIP condition for one BLOCK instruction.
NO(×) YES(√)
4. The SKIP condition only can use M, X, can not use other coil or register.
NO(×) YES(√)
DPLSR D0 D2 D4 Y0 M0
M2
DPLSR D10 D12 D14 Y0
SBLOCK Sequence block1
SBLOCKE
DPLSR D0 D2 D4 Y1 M 0
M 2
DPLSR D10 D12 D14 Y0
SBLOCK Sequence block1
SBLOCKE
DPLSR D 0 D2 D4 Y 0
M0 SBLOCK Sequence block1
SBLOCKE
M 1 M2
DPLSR D 0 D2 D4 Y 0
M 0 SBLOCK Sequence block1
SBLOCKE
M 1
DPLSR D0 D2 D 4 Y0
M0
SBLOCK Sequence block1
SBLOCKE
T 0
M2 [D10]
DPLSR D0 D2 D4 Y1
DPLSR D0 D2 D 4 Y0
M0
SBLOCK Sequence block1
SBLOCKE
X0
M2
DPLSR D0 D2 D4 Y1
5. The output instructions can not be HSC, PLSF, PWM, FRQM.
NO(×) YES(√)
6. LabelKind type can not be used in the block
Sign P, I can not be used in block. Even they can be added in block, but they do not work in fact.
7. BLOCK is not recommended to put in the STL. Because if one STL ends, but the BLOCK doesn’t end, big problem will happen.
NO(×) YES(√)
HSCR C600 D0
M0
SBLOCK Sequence block1
SBLOCKE
M1
M2 PLSF D 0 Y0
PWM K100 D 0 Y1
M3
DPLSY K30 D1 Y 0
M0
SBLOCK Sequence block1
SBLOCKE
M 1
M 2 DPLSR D0 D2 D4 Y1
10-6.BLOCK related instructions
10-6-1.Instruction explanation
stop running the BLOCK [SBSTOP] 1、Summarization
Stop the instructions running in the block
[SBSTOP] 16 bits SBSTOP 32 bits - Condition NO,NC coil and pulse edge Suitable types XC1, XC2, XC3, XC5, XCM,
XCC Hardware Software -
2、Operand Operand Function Type S1 The number of the BLOCK 16 bits, BIN S2 The mode to stop the BLOCK 16 bits, BIN
3、Suitable component
S2 is the mode to stop BLOCK, operand K0, K1 K0: stop the BLOCK slowly, if the pulse is outputting, the BLOCK will stop after the pulse outputting is finished.
K1: stop the BLOCK immediately; stop all the instructions running in the BLOCK.
Word
Function
Operand Register Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ●
S2 K
SBSTOP K1 K0M1
S1· S2·
↑
Continue running the BLOCK[SBGOON] 1、Summarization
This instruction is opposite to BSTOP. To continue running the BLOCK. [SBGOON] 16 bits SBGOON 32 bits - Condition Pulse edge Suitable types XC1, XC2, XC3, XC5, XCM,
XCC Hardware - Software -
2、Operand Operand Function Type S1 The number of the BLOCK 16 bits, BIN S2 The mode to continue running the BLOCK 16 bits, BIN
3、Suitable component
Word Comp onent
Function
Operand Register Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ●
S2 K
SBGOON K1 K0M3
S1· S2·
↑
S2 is the mode to continue running the BLOCK. Operand: K0, K1. K0: continue running the instructions in the BLOCK. For example, if pulse outputting stopped last time, SBGOON will continue outputting the rest pulse. K1: continue running the BLOCK, but abandon the instructions have not finished last time. Such as the pulse output instruction, if the pulse has not finished last time, SBGOON will not continue outputting this pulse but go to the next instruction in the BLOCK.
10-6-2.The timing sequence of the instructions 1. SBSTOP (K1 K1) + SBGOON (K1 K1)
When M0 is from OFF→ON, run “DSPLSR D0 D2 D4 Y0” in the BLOCK to output the pulse; when M2 is from OFF→ON, the BLOCK stops running, pulse outputting stops at once; when M4 is from OFF→ON, abandon the rest pulse.
Scanning period1 Scanning period 2 Scanning period 3
Condition M0
Scanning period 4 Scanning period 5
Condition M2
Condition M4
PLS Y0
2. SBSTOP (K1 K1) + SBGOON (K1 K0)
When M0 is from OFF→ON, run “DSPLSR D0 D2 D4 Y0” in the BLOCK to output the
pulse; when M2 is from OFF→ON, the BLOCK stops running, the pulse outputting stops at once; when M4 is from OFF→ON, output the rest pulses.
Scanning period 1 Scanning period 2 Scanning period 3
Condition M0
Scanning period 4 Scanning period 5
Condition M2
Condition M4
PLS Y0
PLS Y0
3. SBSTOP (K1 K0) + SBGOON (K1 K1)
When M0 is from OFF→ON, run “DSPLSR D0 D2 D4 Y0” in the BLOCK to output the
pulse; when M1 is from OFF→ON, stop the BLOCK, the pulse will stop slowly with slope, when M4 is from OFF→ON, abandon the rest pulses.
Scanning period 1 Scanning period 2 Scanning period 3
Condition M0
Scanning period 4 Scanning period 5
Condition M1
Condition M4
PLS Y0
4. SBSTOP (K1 K0)+ SBGOON (K1 K0)
When M0 is from OFF→ON, run “DSPLSR D0 D2 D4 Y0” in the BLOCK to output the
pulse; when M1 is from OFF→ON, stop running the BLOCK, the pulse will stop slowly with slope; when M3 is from OFF→ON, output the rest pulses. Please note that though the SBSTOP stops the pulse with slope, there maybe still some pulses; in this case, if run SBGOON K1 K1 again, it will output the rest of the pulses.
Scanning period 1 Scanning period 2 Scanning period 3
Condition M0
Scanning period 4 Scanning period 5
Condition M1
Condition M3
PLS Y0
PLS Y0
10-7.BLOCK flag bit and register
1、BLOCK flag bit:
2、BLOCK flag register
Address Function Explanation
M8630
1: running 0: not running
M8631 BLOCK1 running flag
M8632 BLOCK2 running flag
……. …….
…….. …….
M8729 BLOCK99 running flag
Address Function Explanation
D8630
BLOCK use this value when monitoring
D 8631 BLOCK1 current running instruction
D8632 BLOCK2 current running instruction
……. …….
…….. …….
D8729 BLOCK99 current running instruction
10-8.Program example Example 1: This example is used in the tracking system. The process is like this: Output some pulses and prohibit the exterior interruption. Continue outputting the pulse but at low speed, and open the exterior interruption. When checked the exterior cursor signal, stop the pulse outputting and machine running.
Ladder chart:
The instruction list content: RST M8050 Notes: M8050: prohibit the exterior interruption
MOV K100 D100
SBLOCKE
MOV K1000 D0
MOV K20000 D2
MOV K0 D4
I0000
IRET
M8000 STOP Y0
M8002 ( )S
M8050
X0↑ SBLOCK Sequence block1
DPLSR D0 D2 D4 Y0
Instruction list
DPLSR D100 D102 D104 Y0
M8000
MOV K300 D102
MOV K20 D104
( )SM8050
Output the pulses at low speed
PLC power on, prohibit the exterior interruption
BLOCK starts
Output the pulses and move some distance
Reset M8050, open the exterior interruption
BLOCK ends
The first pulse frequency
The first pulse numbers
Accelerate/decelerate time for the first pulse
The second pulse frequency
The second pulse numbers
Accelerate/decelerate time for the second pulse
Stop outputting the pulse
Close the interruption
The interruption ends
The interruption starts
Example 2: One PLC (master station no.1) communicates with 3 PLCs (slave station no. 2, 3, 4) via serial port 2 RS485. Master PLC needs to read the D0 value of 3 PLCs. Then store the value in master PLC D100~D102.
M8000 is normal ON coil, the master PLC can real-time communicate with slave PLCs.
Communicate with slave station 2 Communicate with slave station 3 Communicate with slave station 4
11 Special Function Instructions
In this chapter, we mainly introduce PWM pulse width modulation, frequency detect, precise time, interruption etc;
11-1.PWM Pulse Width Modulation
11-2.Frequency Detect
11-3.Precise Time
11-4.Interruption
Instructions List
Mnemonic Function Circuit and soft components Chapter
Pulse Width Modulation, Frequency Detection
PWM Output pulse with the specified occupied ratio and frequency
PWM S1 S2 D 11-1
FRQM Frequency Detection FRQM S1 D S2 S3
11-2
Time
STR Precise Time STR D1 D2
11-3
STRR Read Precise Time Register
STRR S
11-3
STRS Stop Precise Time STRS S
11-3
Interruption
EI Enable Interruption EI
11-4-1
DI Disable Interruption DI
11-4-1
IRET Interruption Return IRET
11-4-1
11-1.PWM Pulse Width Modulation 1、Instruction’s Summary
Instruction to realize PWM pulse width modulation PWM pulse width modulation [PWM] 16 bits instruction
PWM 32 bits instruction
-
execution condition
normally ON/OFF coil suitable models
XC2、XC3、XC5、XCM、XCC
hardware requirement
- software requirement
-
2、Operands Operands Function Type S1 specify the occupy ratio value or soft component’s ID
number 16 bits, BIN
S2 specify the output frequency or soft component’s ID number
16 bits, BIN
D specify the pulse output port bit 3、Suitable Soft Components
PWM K100 D10 Y0X0
S1· S2· D·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ● ●
S2 ● ● ● ● ●
Word
Bit
Operands System
X Y M S T C Dn.m
D ●
Function and
Action
T0
t
11-2.Frequency Testing 1、Instruction’s Summary Instruction to realize frequency testing frequency testing [FRQM] 16 bits instruction
FRQM 32 bits instruction
-
execution condition
normally ON/OFF coil suitable models
XC2、XC3、XC5、XCM
hardware requirement
- software requirement
-
2、Operands
Operands Function Type S1 Specify the sampling pulse quantity or soft component’s
ID number 32 bits, BIN
S2 Specify the frequency division value 32 bits, BIN S3 Specify the pulse input port bit D specify the tested result’s soft component’s number 32 bits, BIN
The occupy ratio n: 1~255 Output pulse f: 0~72KHz Pulse is output at Y0 or Y1 (Please use transistor output)
The output occupy empty ratio of PMW =n /256×100%
PWM output use the unit of 0.1Hz, so when set (S2) frequency, the set value is 10 times of
the actual frequency (i.e. 10f). E.g.:to set the frequency as 72KHz, then set value in (S2) is
720000.
When X000 is ON, output PWM wave;when X000 is OFF, stop output. PMW output
doesn’t have pulse accumulation.
In the left graph: T0=1/f T/T0=n/256
3、Suitable Soft Components
FRQM K20 D100 K1 X003X000
D·S1· S2· S3·
Operands System Constant Module
D FD ED TD CD DX DY DM DS K /H ID QD
S1 ● ● ● ●
S2 ●
D ● ● ●
Word
Bit Operands System
X Y M S T C Dn.m
S3 ●
FUNCTIONS AND ACTIONS
S1: sampling pulse quantity: the number to calculate the pulse frequency, this parameter can be changed as the frequency (generally, the higher the frequency the larger the pulse quantity)
D: tested result, the unit is Hz. S2: Frequency division choice. Range: K1 or K2; Whatever K1 or K2, the effect is the same. Testing frequency range is 1~200KHz. The testing precision will change when the frequency increasing. 1~80KHz,
precision is 100%; 80~200KHz, precision is 99.5%.
When X0 is ON, FRQM will test 20 pulse from X3 every scan cycle. Calculate the
frequency’s value and save into D100. Test repeat. If the tested frequency’s value is
smaller than the test range, then return the test value is 0.
The pulse output to X number:
Type X terminal XC2 14/16/24/32/48/60 X1 XC3 24/32/42 X1 XC5 48/60 X1 XCM 60 X1
11-3.Precise Time
1、Instruction List Read and stop precise time when execute precise time;
precise time [STR] 16 bits instruction
- 32 bits instruction
STR
execution condition
edge activation suitable models
XC2、XC3、XC5、XCM、XCC
hardware requirement
- software requirements
-
read precise time [STRR] 16 bits instruction
- 32 bits instruction
STRR
execution condition
edge activation suitable models
XC2、XC3、XC5、XCM、XCC
hardware requirement
V3.0e and above software requirements
-
stop precise time [STRS] 16 bits instruction
- 32 bits instruction
STRS
execution condition
edge activation suitable models
XC2、XC3、XC5、XCM、XCC
hardware requirement
V3.0e and above software requirements
-
2、Operands Operands Function Type D Timer Number bit D1 Timer Number bit D2 specify timer’s value or soft component’s ID
number 16 bits, BIN
3、Suitable Soft Components
operands system constant module
D FD ED TD CD DX DY DM DS K /H ID QD
D2 ● ● ● ● ●
Word
Bit operands system
X Y M S T C Dn.m
D ●
D1 ●
《Precise Time》
STR T600 K100X0
D1· D2·
Y0T600
RST T600M0
X0
T600
100ms 100ms
M0
《read the precise time》、《stop precise time》
STRR T600X0
STRS T600M0
D·
D·
FUNCTIONS AND ACTIONS
D1: Timer’s number. Range: T600~T618 (T600、T602、T604…T618, the number should be even) D2: Time Value The precise timer works in form of 1ms The precise timer is 32 bits, the count range is 0~+2,147,483,647. When executing STR, the timer will be reset before start timing. When X0 turns from OFF to ON, timer T600 starts to time, when time
accumulation reaches 100ms, set T600; if X0 again turns from OFF to ON, timer T600 turns from ON to OFF,restart to time, when time accumulation reaches 100ms, T600 reset again. See graph below:
When X0 changes from OFF to ON, move the current precise time value into TD600 immediately, it will not be affected by the scan cycle;
When M0 changes from OFF to ON, execute STRS
instruction immediately, stop precise time and refresh the count value in TD600. It will not be affected by the scan cycle;
STR T600 K100X0
RST T600M0
I3001
IRET
FEND
Interruption Tag correspond to the Timer
Timer’s Nr. Interruption Tag T600 I3001 T602 I3002 T604 I3003 T606 I3004 T608 I3005 T610 I3006 T612 I3007 T614 I3008 T616 I3009 T618 I3010
When the precise time reaches the count value, it will generate an interruption tag, interruption subprogram will be executed.
Start the precise time in precise time interruption; Every precise timer has its own interruption tag, see table below:
Precise Time Interruption
When X0 changes from OFF to ON, T600 starts timing. When time accumulates to 100ms, set ON T600; meantime, generate an interruption, the program jumps to interruption tag I3001 and execute the subprogram.
11-4.Interruption
XC series PLC are equipped with interruption function. The interruption function includes external interruption and time interruption. Via interruption function we can dispose some special programs. This function is not affected by the scan cycle.
11-4-1.External Interruption The input terminals X can be used to input external interruption. Each input terminal corresponds with one external interruption. The input’s rising/falling edge can activate the interruption. The interruption subroutine is written behind the main program (behind FEND). After interruption generates, the main program stops running immediately, turn to run the correspond subroutine. After subroutine running ends, continue to execute the main program.
XC3-14
Input Terminal
Pointer No. Disable the interruption instruction
Rising Interruption
Falling Interruption
X7 I0000 I0001 M8050
XC2-14/16
Input terminal
Pointer No. Disable the interruption instruction
Rising interruption
Falling interruption
X2 I0000 I0001 M8050 X5 I0100 I0101 M8051
XC2-24/32/48/60、XC3-24/32/42、XC5-24/32/48/60
Input Terminal
Pointer No. Disable the interruption instruction
Rising Interruption
Falling Interruption
X2 I0000 I0001 M8050 X5 I0100 I0101 M8051 X10 I0200 I0201 M8052
Main Program Main Program
subprogram
Input interrupt
External Interruption’s Port Definition
XC3-48/60、XC3-19AR-E
Input Terminal
Pointer No. Disable the interruption instruction
Rising Interruption
Falling Interruption
X10 I0000 I0001 M8050 X7 I0100 I0101 M8051 X6 I0200 I0201 M8052
XCM-24/32 (3 or 4 axis output)
Input Terminal
Pointer No. Disable the interruption
instruction Rising
Interruption Falling
Interruption X2 I0000 I0001 M8050 X5 I0100 I0101 M8051 X10 I0200 I0201 M8052 X11 I0300 I0301 M8053 X12 I0400 I0401 M8054 X13 I0500 I0501 M8055
XCM-60
Input Terminal
Pointer No. Disable the interruption
instruction Rising
Interruption Falling
Interruption X2 I0000 I0001 M8050 X3 I0100 I0101 M8051 X4 I0200 I0201 M8052 X5 I0300 I0301 M8053
XCC-24
Input Terminal
Pointer No. Disable the interruption
instruction Rising
Interruption Falling
Interruption X14 I0000 I0001 M8050 X15 I0100 I0101 M8051
XCC-32
Input Terminal
Pointer No. Disable the interruption
instruction Rising
Interruption Falling
Interruption X14 I0000 I0001 M8050 X15 I0100 I0101 M8051 X16 I0200 I0201 M8052 X17 I0300 I0301 M8053
Enable Interruption [EI]、Disable Interruption [DI]、Interruption Return [IRET]
If use EI instruction to allow interruption, then when scanning the program, if interruption input changes from OFF to be ON, then execute subroutine①、②, return to the original main program;
Interruption pointer (I****) should be
behind FEND instruction; PLC is default to allow interruption
Via program with DI instruction, set interruption forbidden area;
Allow interruption input between EI~DI
If interruption forbidden is not required, please program only with EI, program with DI is not required.
Interruption Instruction
Interruption’s Range Limitation
11-4-2.Time Interruption
Every input interruption is equipped with special relay (M8050~M8052) to disable interruption;
In the left program, if use M0 to set
M8050 “ON”, then disable the interruption input at channel 0.
FUNCTIONS AND ACTIONS
In the condition of main program’s execution cycle long, if you need to handle a special program; or during the sequential scanning, a special program needs to be executed at every certain time, time interruption function is required. This function is not affected by PLC’s scan cycle, every Nm, execute time interruption subroutine.
Disable the Interruption
Y0
FEND
I4010
INC D0
IRET
X0
M8000
Interruption No.
Interruption Forbidden Instruction
Description
I40** M8056
“**” represents time interruption’s time, range from 1 to 99, unit is ms.
I41** M8057
I42** M8058
I43** - I44** - I45** - I46** - I47** - I48** - I49** -
Time interruption is default in open status, time interruption subroutine is similar with other interruption subroutine, it should be written behind the main program, starts with I40xx, ends with IRET.
There are 10CH time interruptions. The represent method is I40**~I49** (“**” means time interruption’s time, unit is ms. For example, I4010 means run one channel time interruption every 10ms.
Interruption No.
FEND
I4010
IRET
DI
EI
EI
M8056
FEND
I4020
IRET
END
M0
Normally time interruption is in “allow” status With EI、DI can set interruption’s allow or forbidden area. As in the above
graph, all time interruptions are forbidden between DI~EI, and allowed beyond DI~EI.
Interruption Allowed
Interruption Allowed
Interruption Forbidden
Interruption Program
The first 3CH interruptions are equipped with special relays (M8056~M8059) to forbid interrupt
In the left example program, if use M0 to
enable M8056 “ON”, the forbid 0CH’s time interruption.
Interruption range’s limitation
Interruption Forbidden
Interruption Allowed
Interruption Program
12 Application Program Samples
In this chapter, we make some samples about pulse output instruction, Modbus communication instructions and free format communication instructions etc.
12-1.Pulse Output Sample
12-2.Modbus Communication Sample
12-3.Free Format Communication Sample
12-1.Pulse Output Application Example: send high frequency and low frequency of pulse Parameters: Stepping motor parameters: step angle= 1.8 degrees/step, scale=40, pulse number per rotate is 8000 High frequency pulse: maximum frequency is 100KHz, total pulse number is 24000 (3 rotates) Low frequency pulse: maximum frequency is 10KHz, total pulse number is 8000 (1 rotates) Ladder Program:
Explanation: When PLC changes from STOP to RUN, set ON M0, set the high frequency parameter D0, D2, low frequency parameter D4, D6, speed up/down time D20, clear D8~D11, set ON M1, set OFF M0. The motor rotates at high frequency for 3 turns, set ON M8170; then the motor rotates at low frequency for 1 turn, set OFF M8170, set OFF M1.
100000
10000
0 High frequency 3 turns Low frequency 1 turn
frequency
t
12-2.MODBUS COMMUNICATION SAMPLES Example 1: one master station communicates with 3 slave stations.
Operation: (1) write content in D10~D14 to D10~D14 of slave station 2; (2) read D15~D19 of the slave station 2 to D15~D19 of the mater station; anyhow, write the first five registers’ content to the slaves, the left five registers are used to store the content from the slaves; (3) slave station 3 and 4 are similar; Soft component’s comments: D0: communication station number D1: offset M2: station 2 communication error M3: station 3 communication error M4: station 4 communication error M8137: COM2 communication error end signal M8138: COM2 communication correct end signal
Ladder chart
S0: write the target station S1: read the target station S2: judge the communication status S3: offset the communication address T200: communication interval 1 T201: communication interval 2 D20: plus one for write error times D21: plus one for read error times
Program Explanation: When PLC turns from STOP to RUN, M8002 gets a scan cycle. S0 flow open, write the master’s D10~D14 to slave 2 D10~D14. If the communication is successful, it goes to the next flow; if not, it will try three times then go to the S1 flow. It delays for a while then read D15~D19 of station 2. The method is similar to S0 flow. Then go to S2 flow. If the communication is failed, set ON M23. Then it goes to S3 flow. S3 flow will judge the station no, if the no. is less than 4, the station no. will plus 1, offset value plus 10; if not, the station no. will start again from 2.
Example 2: XINJE PLC writes frequency to two inverters via Modbus.
Set the first inverter’s station no. to 1; set the second inverter’s station no. to 2; store the frequency in D1000 and D2000. Communicate with inverter via serial port.
Program Description: Use BLOCK to make the program. The two Modbus instructions will be executed from up to down. 12-3.Free Format Communication Example In this example, we use DH107/DH108 series instruments; 1、Interface Specifications DH107/DH108 series instruments use asynchronous serial communication interface, the interface level fits RS232C or RS485 standard. The data format is: 1 start bit, 8 data bits, no parity, one/two stop bit. The baud rate can be 1200~19200bit/s . 2、Communication Instruction Format DH107/108 instruments use Hex data form to represent each instruction code and data; Read/write instructions: Read: address code +52H (82) +the para.(to read) code +0+0+CRC parity code Write: address code +43H(67)+ the para.(to write) code +low bytes of the wrote data + high bytes of the wrote data +CRC parity code The read instruction’s CRC parity code is: the para. (to read) code *256+82+ADDR ADDR is instrument’s address para., the range is 0~100 (pay attention not to add 80H). CRC is the remainder from the addition of the above data (binary 16bits integral). The reminder is 2 bytes, the high byte is behind the low byte; The write instruction’s CRC parity code is: the para. (to write) code *256+67+ the para. value (to write) +ADDR The parameter. to write represents with 16 bits binary integral; No matter to write or read, the instrument should return data as shown below: The test value PV+ given value SV+ output value MV and alarm status +read/write parameters value +CRC parity code Among in, PV、SV and the read parameters are all in integral form, each occupies two bytes, MV occupies one byte, the value range is 0~220, alarm status occupies one byte, CRC parity code
occupies two bytes, totally 10 byes. CRC parity code is the reminder from the result of PV+SV+ (alarm status *256+MV)+ para. value +ADDR; (for details, please refer to AIBUS communication description)
3、Write the program After power on the PLC, the PLC read the current temperature every 40ms. During this period, the user can write the set temperature. Data zone definition: buffer area of sending data D10~D19
buffer area of accepting data D20~D29 instruction’s station number: D30 read command’s value: D31=52 H write command’s value: D32=43 H parameter’s code: D33 temperature setting: D34 CRC parity code: D36 Temperature display: D200,D201
The send data form: 81H 81H 43H 00H c8H 00H 0cH 01H (current temperature display) Communication parameters setting: baud rate: 9600, 8 data bits, 2 stop bits, no parity Set FD8220=255; FD8221=5 ( the hardware and software must be V2.4 or above)
Ladder:
Write instrument’s station Nr. K1 in to D30
Time 40ms
Output M10
Write the read code 52H into D31
Clear registers D40-D56
D30 add H80 to get value 81H
move D40 (81H) to D10
move D40 (81H) to D11
move D31 (read code 52H) to D12
move D33 (para. code) to D13
write zero to D14
write zero to D15
below is to calculate CRC parity;
D33 multiply K256, the result is saved in D42
D42 add K82, the result is stored in D44
D44 add D30 (instrument’s station), the result
is saved in D52
Move D52 into D54 Logic AND D54 with HFF, save the result in D16
Move D52 into D56
Right shift 8 bits with D56 (convert the high
8bits to the low 8 bits)
Logic AND D56 with HFF, save the result in
D17
↓
M11↑
M10H43 D32MOV
K0 D40FMOV D56
D30 H80ADD D40
D40 D10MOV
D40 D11MOV
D32 D12MOV
D33 D13MOV
D34 D42MOV
D34 D44MOV
D33 K256MUL D46
D46 K67ADD D48
D48 D34ADD D50
D52 D54MOV
D44 HFFWAND D15
D52 D56MOV
D44 K8ROR
D54 HFFWAND D16
D42 HFFWAND D14
D50 D30ADD D52
D56 K8ROR
D56 HFFWAND D17M10↑ D10 K8SEND K2
M11↑
M8132D20 K10RCV K2
D101 K8ROL
D101 D100WOR D200
D103 K8ROL
D102 D103WOR D201
M8134D100 K10D20BMOV↓
Write code H43 into D32
Clear registers D40-D56
D30 (station Nr.) add H80, save the result in
D40
Move D40 to D10
Move D40 to D11
Move D32 (write code H43) to D12
Move D33 (para .code) to D13 Move D34 (temp. set) to D42
Logic and D42 with HFF, save data in D14
Move D34 (temp. set) to D44 D44 right shift 8 bits
Logic and D44 with HFF, save data in D15
Below is to calculate CRC parity:
D33 (para. code) multiply K256, save result
in D46
D46 add K67, save data in D48
D48 add D34, save data in D50
D50 add D30, save data in D52
Move D52 to D54
Logic and D54 with HFF, save result in D16
Move D52 to D56
Right shift 8 bits with D56
Logic and D56 with HFF, save result in D17
Send data D10-D17 out
Read the returned data and save in D20-D29
Move the returned data to D100~109
Left shift 8 bits with D101
Logic OR D101 with D100, save result in
D200
Left shift 8 bits with D103
Logic OR D102 with D103, save result in D201
Program Description: The above program is written according to DH instrument’s communication protocol, the soft component’s functions are listed below: Relationship of sent (SEND) data string and registers: D10 D11 D12 D13 D14 D15 D16 D17 Read Address
code Address code
Read code 52H
Parameters code
0 0 CRC low bytes
CRC high bytes
Write Address code
Address code
Write code 42H
Parameters code
low bytes of the written data
high bytes of the written data
CRC low bytes
CRC high bytes
Relationship of received (RCV) data (data returned by the instrument) and the registers: D20 D21 D22 D23 D24 D25 D26 D27 D28 D29 PV low bytes
PV high bytes
SV low bytes
SV high bytes
Output value
Alarm status
Read/write low bytes
Read/write high bytes
CRC low bytes
CRC high bytes
So, if write data string according to the communication objects’ protocol, use SEND and RCV commands from free format communication, user will get the communication with the objects.