1
The 24 VDC proflo uses 2 “AA” lithium batteries for Back-up Power to the micro processor when the control panel power is turned off or if the power fails. These batteries are for back-up power only and cannot be used to power the 24 VDC proflo. The life of these batteries are approximately 24 months when the proflo is not powered by the control panel. When it becomes necessary to replace the back-up batteries use the L91 Energizer Lithium “AA” ONLY. (SEE FIG. A.) DO NOT Overtighten Screws on the cover plate! If the batteries are drained to ZERO and are not replaced before the compressor is started the trending information will not be accurate. If the Battery voltage drops it does not affect the proflo’s ability to protect the compressor for no-flow shut down. Wiring Schematic and Battery Instructions for 24 VDC proflo PF-1 to PLC, Murphy or Altronic control panel on the divider block or mounted in control panel. wiring diagram CPI Worldwide Headquarters - 4410 Greenbriar Drive, Stafford, TX 77477, USA tel: 281 207 4600 or 800 675 6646 fax: 281 207 4612 email: [email protected] www.c-p-i.com Battery Cover Screws Inside Battery Compartment Back-up Battery L91 Lithium “AA” FIG. A (2) WHITE WIRES ..............to Proximity Switch on Divider Block (2) RED WIRES...................to Control Panel Alarm Circuit (2) GREEN WIRES .............to Ground (2) BLUE WIRES.................Pulse Output to PLC or new Murphy control panel (2) PURPLE WIRES ...........18 to 24 VDC .5 amp Max Power Input Set Button Mode Button prO flO 203633 CL I, DIV 2 Grps A, B, C, D T4A Max 85 o C Amb. C US IrDA PORT Model-PF1 R US Copyright Registered 2001 Patent Pending REFER TO MANUAL FOR PROPER OPERATION & BATTERY TYPE WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS BATTERIES MUST ONLY BE CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS ! BLUE BLUE PULSE OUTPUT TO PLC TO MONITOR DIVIDER BLOCK CYCLE (Use Edge Trigger) RED RED WHITE WHITE N E E R G GROUND PROXIMITY SWITCH REFER TO MANUAL FOR PROPER OPERATION. WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS GREEN Control Panel or PLC INPUT MODULE PURPLE PURPLE 18 TO 24 VDC POWER Non-Polarity Sensitive N E E R G ALARM CIRCUIT - LUBE NO FLOW TO CONTROL PANEL See proflo operation brochure for N/O - N/C wiring instructions CAUTION: DO NOT CONNECT PULSE OUTPUT, ( BLUE WIRES ) AND ALARM CIRCUIT ( RED WIRES ) AT THE SAME TIME ! ! Guaranteed to work flawlessly with All Manufacturers Divider Blocks Ariel - SB - Graco/Trabon - Lincoln - DropsA US Patent # 6,823,270 B1 DO NOT connect BLUE WIRES and RED WIRES to control panel at the same time. All unused wires must be isolated from contact with each other and isolated from ground. NEVER WELD ON THE COMPRESSOR SKID OR FRAME WITH ANY WIRING CONNECTED! Welding will cause premature or immediate failure of the proflo alarm circuits. ! CAUTION: The wiring schematic is universal and will work with most control panels. To avoid destroying the proflo by incorrect wiring or if you have a proprietary control device please contact CPI. NOTE: The 24 VDC proflo Pf1 can be mounted in the control panel or directly on the divider block. proflo 24 VDC POWER

proflo 24 VDC POWER wiring diagram - CPI - … diagram CPI Worldwide Headquarters - 4410 Greenbriar Drive, Stafford, TX 77477, USA ... GREEN DISCONNECT WHILE CIRCUIT IS LIVE UNLESS

Embed Size (px)

Citation preview

The 24 VDC proflo uses 2 “AA” lithium batteries for Back-up Power to the micro processor when the control panel power is turned off or if the power fails. These batteries are for back-up power only and cannot be used to power the 24 VDC proflo. The life of these batteries are approximately 24 months when the proflo is not powered by the control panel. When it becomes necessary to replace the back-up batteries use the L91 Energizer Lithium “AA” ONLY. (SEE FIG. A.)

DO NOT Overtighten Screws on the cover plate!

If the batteries are drained to ZERO and are not replaced before the compressor is started the trending information will not be accurate. If the Battery voltage drops it does not affect the proflo’s ability to protect the compressor for no-flow shut down.

Wiring Schematic and Battery Instructions for 24 VDC proflo PF-1 to PLC, Murphy or Altronic control panel on the divider block or mounted in control panel.

wiring diagram

CPI Worldwide Headquarters - 4410 Greenbriar Drive, Stafford, TX 77477, USA

tel: 281 207 4600 or 800 675 6646 fax: 281 207 4612

email: [email protected] www.c-p-i.com

BatteryCover ScrewsInside BatteryCompartment

Back-up BatteryL91 Lithium “AA”

FIG. A

(2) WHITE WIRES ..............to Proximity Switch on Divider Block(2) RED WIRES ...................to Control Panel Alarm Circuit (2) GREEN WIRES .............to Ground (2) BLUE WIRES .................Pulse Output to PLC or new Murphy control panel (2) PURPLE WIRES ...........18 to 24 VDC .5 amp Max Power Input

SetButton

ModeButton

prOflO203633

CL I, DIV 2 Grps A, B, C, DT4A Max 85 o C Amb.

C US

IrDA PORT

M o d e l - P F 1

R

US Copyright Registered 2001Patent Pending

REFER TO MANUAL FOR PROPER OPERATION & BATTERY TYPEWARNING - EXPLOSION HAZARD - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS

BATTERIES MUST ONLY BE CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS!

BLUEBLUE PULSE OUTPUT TO PLC TO MONITOR DIVIDER BLOCK CYCLE (Use Edge Trigger)

REDRED

WHITE

WHITE

NE

ER

G

GROUND

PROXIMITY SWITCH

REFER TO MANUAL FOR PROPER OPERATION. WARNING - EXPLOSION HAZARD - DO NOTDISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUSGREEN

Control Panel orPLC INPUT

MODULE

PURPLEPURPLE 18 TO 24 VDC POWER

Non-Polarity Sensitive

NE

ER

G

ALARM CIRCUIT - LUBE NO FLOW TO CONTROL PANEL

See pro�o operation brochure for N/O - N/C wiring instructions

CAUTION: DO NOT CONNECTPULSE OUTPUT, ( BLUE WIRES )

AND ALARM CIRCUIT ( RED WIRES )AT THE SAME TIME

!

!Guaranteed to work flawlessly

with All Manufacturers Divider BlocksAriel - SB - Graco/Trabon - Lincoln - DropsA

US Patent # 6,823,270 B1

• DO NOT connect blue wireS and reD wireS to control panel at the same time.• All unused wires must be isolated from contact with each other and isolated from ground. • NeVer welD ON THe COMPreSSOr SKiD Or FrAMe wiTH ANY wiriNG CONNeCTeD!

welding will cause premature or immediate failure of the proflo alarm circuits.!CAUTION:

The wiring schematic is universal and will work with most control panels. To avoid destroying the proflo by incorrect wiring or if you have a proprietary control device please contact CPi.

NOTE: The 24 VDC proflo Pf1 can be mounted in the control panel or directly on the divider block.

proflo 24 VDC POWER