Prof. Edwin Chi Yan TSO Research Assistant Professor of Mechanical and Aerospace Engineering The Hong Kong University of Science and Technology Prof. Christopher Y.H. CHAO Head and Chair Professor of Mechanical and Aerospace Engineering The Hong Kong University of Science and Technology 22 Nov 2016 Smart Cities - A Convergence of People, Technologies and Big Data 2016 IERE CLP-RI Hong Kong Workshop 21-24 November 2016

Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Prof. Edwin Chi Yan TSO Research Assistant Professor of Mechanical and Aerospace Engineering

The Hong Kong University of Science and Technology

Prof. Christopher Y.H. CHAO Head and Chair Professor of Mechanical and Aerospace Engineering

The Hong Kong University of Science and Technology

22 Nov 2016

Smart Cities - A Convergence of People, Technologies and Big Data

2016 IERE – CLP-RI Hong Kong Workshop

21-24 November 2016

Page 2: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Energy Usage in Hong Kong Buildings

Source: EMSD Data 2015

45%

35%

Current Status of Global Energy Usage

• High Energy Consumption Worldwide Problem

• Total Worldwide primary energy consumption

• 355EJ in 1990

• 406EJ in 2000

• 590EJ in 2020

• 687EJ in 2030

Introduction

2 Source: EIA, 2012

Page 3: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

By analyzing the spectral characteristics, electromagnetic (EM) waves with different wavelengths have different transmittance in the atmosphere. There is a high transmittance band called "atmospheric window", for example: 0.3 - 2.5 μm, 3.2 - 4.8 μm, 8 – 13 μm, etc. The 8-13 μm band is the one people most are interested in, because blackbody radiation is concentrated in this range at room temperature.

Working Principle of Photonic Passive Radiative Coolers

Page 4: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Working Principle of Photonic Passive Radiative Coolers

Page 5: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Working Principle of Photonic Passive Radiative Coolers

5500°C 0.38-0.78 μm (visible light)

Passive Radiative Cooler

Object to be cooled ~30°C 8-13 μm (longwave infrared) Temp

Most common radiative cooling phenomenon: Frost

5

Environmentally Friendly Electricity Free

-270 oC

Outer Space

Page 6: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

• To experimentally investigate the passive

radiative cooler with different thermal

designs (i.e. vacuum and non-vacuum

configurations);

• To test its cooling performance in the hot

and humid environment of Hong Kong.

Page 7: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Raman, A. P., Anoma, M. A., Zhu, L., Rephaeli, E., & Fan, S. (2014). Nature, 515(7528), 540-4.

Multi-layer Passive Radiative Cooler

cool wafer sun conv cond radP P P P P P

Page 8: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

200 mm

Page 9: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global
Page 10: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Cooling effect of both radiative coolers (vacuum & non-vacuum) are hardly to be achieved during the

day time operation!

Day Time (Clear sky + Sunny)

Very cloudy at night the overall cooling performance is

poor no matter which coolers are.

~ 6 - 7 oC

~ 1 - 2 oC

Page 11: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Night Time (Clear + Cloudy)

~ 5 - 6 oC ~ 1 - 2 oC

Clear Cloudy

Cooling effect can be achieved during the night!

Page 12: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Clear sky for a few hours

Maximum temperature difference ≈ 5 - 6 oC

Mostly cloudy at Night & Partly Sunny at Day

Night Day

Similar results are obtained comparing to the previous 2 slides!

Page 13: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Very cloudy at night (cooling performance is limited)

Just about 1.5 oC temperature difference!

Very Cloudy at Night & Partly Sunny at Day

Weather plays a major role on the cooling performance of the passive radiative cooler!

Night Day

Page 14: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

≈ 6 oC (constantly)

Very Clear Sky at Night & Mostly Sunny at Day

Night Day

≈ 6 - 7 oC

≈ 1 - 2 oC

Non-vacuum

Vacuum

Black Body

Polished Copper Plate

Ambient Air Temp

Solar Intensity

Page 15: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Cooling Power of the Radiative Cooler (non-vacuum)

≈ 1.2 W (≈ 38 W/m2)

Cloudy during this period The temperature is increased.

Most of the time, the temperature difference ≈ 6 oC (radiative cooler non-vacuum Vs ambient air temperature)!

Cooling Capacity

Night

Day Mostly Clear Sky at Night & Sunny at Day

Page 16: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global

Conclusions • Both passive radiative coolers with vacuum and non-vacuum design

were unable to provide a cooling effect under direct sunlight.

• Although vacuum design cannot provide the cooling effect during the daytime operation, its outcome is much better than that of the non-vacuum design.

• Local weather plays a major role on the cooling performance of the passive radiative cooler.

• The passive radiative cooler with non-vacuum design can cool the ambient air temperature during night time (i.e. reducing the ambient air temperature by about 7 oC), producing a cooling power of 1.2 W (i.e. 38 W/m2) under a clear night sky in Hong Kong.

• Cooling by using night radiation technique seemed to be feasible in Hong Kong, but there remains much work to successfully produce the cooling effect under direct sunlight in Hong Kong’s climate.

Page 17: Prof. Edwin Chi Yan TSO - IERE...2016 IERE – CLP-RI Hong Kong Workshop 21-24 November 2016 Energy Usage in Hong Kong Buildings Source: EMSD Data 2015 45% 35% Current Status of Global