Doc. Name: PRODUCT REQUIREMENT SPECIFICATION
forCONTROL SYSTEM CONFIGURATOR
PROJECT: ASTeC – Systems - CONTROL SYSTEM CONFIGURATOR
PRODUCT: Systems – Flexible Open SCADADoc No.: DRS CI 162 4301Control Status: Controlled Mastercopy if read from cvs Copy No:
Approved by Issuing AuthorityName: Designation: Project LeaderDesignation Group Head
(If the approving authority is not Group Head, then the designated approving authority shall be specified in the quality plan for the project.)
Address:(Section and Group)
Date: 15/02/08For any clarifications/ corrections/ amendments in this document please contact Issuing Authority
Issue History
Issue No Effective From Reason for Re-issue
Total Doc.
Pages
Date of Review / Change Report
Approved by
1 15/02/08 NA 78 NA
Copyright : No part of this document may be reproduced in an y form without the prior permission in writing of issuing authority
CENTRE FOR DEVELOPMENT OF ADVANCED COMPUTINGThiruvananthapuram
Table of contents
SL. No Contents Page No.
1. Introduction 11.1 Name of the Product 11.2 Product Mnemonic 11.3 Abbreviations 1
1.4 Reference 12. General Description 2
2.1 Product Perspective 3 2.2 Product Functions 3 2.3 Product Specification 3 3. Specific Requirements 4 3.1 Configuration 4 3.1.1 Configuration of Control System / Hardware 4 3.1.1.1 Configuration of General Purpose Controllers 5 3.1.1.1.1 Configuration of I/O cards 5 3.1.1.2 Configuration of Single Board Controller 6 3.1.1.3 Configuration of Low Power Controller 7 3.1.1.4 Configuration of Multiple Controller 8 3.1.2 Configuration of Control Schemes 8 3.1.2.1 Control Strategy using Functional Block Logic 8 3.1.3 Configuration of network and communication protocol 11 3.2 Download configuration 12 3.3 Upload configuration 12 3.5 Import/Export Utility 12 4. List of Annexure 13
Annexure A - IEC 61131-3: A Standard Programming Resource 14Annexure B - List of blocks with details 24Annexure C - Modbus TCP and DNP3 75
Doc. Name : Product Requirement Specification for Control System Configurator
Doc. No. DRS CI 162 4301 Doc Issue No:01
1. Introduction
1.1. Name of the Product: CONTROL SYSTEM CONFIGURATOR
1.2. Product Mnemonic : CSCONFIG 1.3. Abbreviations
TCP - Transmission Control Protocol or Transport Control Protocol,
IP - Internet Protocol
RTU - Remote Terminal Unit
PLC - Programmable Logic Controllers
I/O - Input/Output
IEC - International Electrotechnical Commission
ST - Structured Text
FBD - Functional Blocks Diagrams
SFC - Sequential Function Chart
IL - Instruction List
FB - Functional Blocks
DNP3 - Distributed Network Protocol
1.4. Reference
Programming Industrial Control Systems using 1131-3 (Revised edition) -
R.W. Lewis, Published by : The Institution of electrical Engineers, London,
United kingdom
International Standard CEI IEC 1131-3(first edition) - Programmable Controllers –
Part-3 : Programming languages - IEC Publication
Prepared by Technical Committee No. 65
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 1
2. General Description
The opening of the control system to interface with general-purpose platforms and software
has made a major change in the way control systems will be engineered in the future.
Control System Configurator is used to configure the hardware and control strategy
required for the control system. The number of Controllers, the type of I/O cards used, the
I/O channel description along with the TAG name can be configured. Configuration of
control strategy is to be done according to the Functional Block Logic of IEC 61131-3
standard.
The IEC (International Electrotechnical Commission) 61131-3 standard is for the
improvement of programming techniques and control strategy for process industries.
This standard was setup to look at the complete design, installation, testing,
documentation, programming and communication. IEC 61131-3 standard provides flexible
language selection for expressing different parts of a control application. They are
Structured Text – ST, Functional Blocks Diagrams – FBD, Sequential Function
Chart – SFC, Instruction List –IL.
Structured Text – ST - a very powerful high level language with its root in Ada,
Pascal and C
Functional Block Diagram – FBD – A graphical language for depicting signal and
data flows through function blocks – reusable software elements
Functional Blocks – FB – A function block is a part of a control program that is
packaged so that it can be reused in different parts of the same program. It should be
regarded as basic building blocks of a control system.
Sequential Function Chart – SFC - A graphical language for depicting
sequential behavior of control system. It is used for defining control sequences that are
time –and event- driven.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 2
Instruction List - IL - textual language resembles assembler. Instruction
List is a low level language that can be used to express the behavior of
functions, function blocks and programs, and also actions and transitions in sequential
function charts.
It consists of a series of instructions where each instruction is on a new line.
2.1. Product Perspective
Development of CONTROL SYTEM CONFIGURATOR
2.2. Product Functions
Control System Configurator is an IEC 61131-3 compliant software utility to configure
Control system components.
2.3. Product Specification
The SCADA system shall include data acquisition servers for establishing the I/O
interface between field devices such as Controllers, RTUs etc. The software shall
have the flexibility to permit easy configuration of the system in accordance with the
specific end user requirements as well as quick and easy modification by the end user in
the field.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 3
3. Specific Requirements
Functional Requirements
3.1 Configuration
It should be possible to create a new configuration
It should be possible to edit an existing configuration
It should be possible to save a configuration
It should be possible to download a configuration
It should be possible to view tag values in a separate browser or on the control
logic diagram of configuration
Configuration shall provide a user validation for allowing only privileged users
Data Entry validation with respect to default data limits
Configuration can be classified into three categories :
1. Configuration of Control System/hardware
2. Configuration of control schemes
3. Configuration of network/communication
3.1.1 Configuration of Control System / Hardware
This includes the configuration of various subsystems used in the main control
system.
The module should be capable of adding areas depending on the control
functions.
Under each area it should be possible to add controllers developed as part of
the project ‘Embedded Controllers’.
It should be possible to remove controllers.
It should be possible to select the following types of controllers
a) General Purpose Controller
b) Single Board Controller
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 4
c) Low Power Controller
It should be possible to configure each controller
3.1.1.4 Configuration of General Purpose Controllers
The following properties of the controller should be configured.
o Selection of protocols for communication with PC –Modbus/DNP3
o Name of Controller
o Mac Address and IP Address of the controller
o Redundancy – Default / Redundant / Critical
(It defines how important the device for the SCADA system, and effects
what action should be taken upon failure of the device.)
o Slot address
o I/O slots - No of slots can be configured as
8 slots
16 slots
24 slots
o Sampling time – Scanning rate of Controller (default 10 ms)
It shall be possible to add and configure I/O cards
3.1.1.1. 1 Configuration of I/O cards
It shall be possible to configure the following properties of the I/O board:
Types of I/O cards (analog /digital) – slot configuration
Analog Output 8 channel
Analog Input 16 channel
Digital I/O – 5VDC, 24VDC,48VDC
Digital Input – 230VAC/DC
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 5
Should have facility to add new card types
Scan rate ( Scanning rate of I/O card) – should be selectable (Analog, Digital)
Update interval - should be selectable for digital and analog signals
(Update rate of signals)
Jumper address
Channel Configuration
o Hart I/O or Conventional I/O- (Channel Should be selectable)o It should be possible to select whether the channel is input or
output for DI/O board o Tags - Physical tags that are connected to the I/O card
o Tag properties
Tag name – Editable stereotypes for tagnames should be provided
Tag type – shall specify the type of the tag. i.e. Analog/Digital
Tag description – Description of the tag
Maximum value - the maximum value associated with the
particular analog tag. For Analog Tags the default value is 100
and for digital tags the default value is 1.
Minimum value - the minimum value that can be associated with
the particular tag.
3.1.1.4 Configuration of Single Board Controller
The following properties of the controller should be configured.
o Selection of protocols for communication with PC –Modbus/DNP3
o Name of Controller
o Mac Address and IP Address of the controller
o Sampling time – Scanning rate of Controller (default 10 ms)
Jumper address
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 6
Channel Configuration
It should be possible to configure analog channels and digital channels
Tags - Physical tags
Tag properties
Tag name – Editable stereotypes for tagnames should be provided
Tag type – shall specify the type of the tag. i.e. Analog/Digital
Tag description – Description of the tag
Maximum value - the maximum value associated with the
particular analog tag. For Analog Tags the default value is 100
and for digital tags the default value is 1.
Minimum value - the minimum value that can be associated with
the particular tag.
3.1.1.3Configuration of Low Power Controller
The following properties of the controller should be configured.
o Selection of protocols for communication with PC –Modbus/DNP3
o Name of Controller
o Mac Address and IP Address of the controller
o Sampling time – Scanning rate of Controller (default 10 ms)
Jumper address Channel Configuration
It should be possible to configure analog channels and digital channels
Tags - Physical tags, Virtual Tags ( for display)
Tag properties
Tag name – Editable stereotypes for tagnames should be provided
Tag type – shall specify the type of the tag. i.e. Analog/Digital
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 7
Tag description – Description of the tag
Maximum value - the maximum value associated with the
particular analog tag. For Analog Tags the default value is 100
and for digital tags the default value is 1.
Minimum value - the minimum value that can be associated with
the particular tag.
3.1.2 Configuration of Control Schemes
The configurator shall follow IEC 61131-3 standard for configuring control
schemes.
It should be possible to configure the control schemes to be run in each
controller.
The configurator shall provide facility to configure the control strategy usin
Functional Block Logic of the standard. (See Annexure A for more details)
Predefined control schemes should be made available in a library for the
users to select.
It should be possible to view tag values on the control scheme diagram
3.1.2.1 Control Strategy using Functional Block Logic
The configurator shall provide a GUI to create control schemes using
functional block logic. A library of function blocks will be
provided which contain the following blocks:
1. CINP - Analog Input Processor
2. LOGI - Digital Logic Operator
3. DINT - DIGITAL INTEGRATION BLOCK
4. ASW - Analog Signal Switch
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 8
5. AINT - Analog Integrator Block
6. SQRT - Square Root
7. FUNC - Function Generator Block
8. CPID - PID Block
9. ADSB - ADDITION SUBTRACTION BLOCK
10. MULD - MULTIPLIER/DIVIDER BLOCK
11. SELH - LOW/HIGH SELECTOR BLOCK
12. MPCG - Multi Point Constant Generator
13. HLMT - High/Low block
14. TLDT - Time Lag + Dead Time
15. DBOG - Dead Band Operator with Gain
16. LDLG - Lead Lag Block
17. OUTP - Output Processor Block
18. MLOG - Multiple Operator Logical Operator Block
19. PPID - Pulse PID
20. PEU - Percentage To Engineering Unit
21. EUP - Engineering Unit to Percentage
22. PTC - Pressure Temperature Compensator
23. PPC -PID To Pulse Converter
24. CNTR – Counter
25. MAVG - Moving/Fixed Average
26. PARA - Parameter Setter
27. CMP – Comparator
(Refer Annexure B for details)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 9
It should be possible to add new function blocks to the library. For each
function block, it should be possible to configure the following :
o No. of Inputs
o No. of outputs
o Maximum inputs and outputs to a function block
Placing and movement of function blocks on the screen should be possible
Resizing of function blocks should be done the extent possible
It should be possible to check the validity of blocks
The control strategy is to be created by interconnecting the function blocks and
setting the parameters.
Interconnection should be possible between blocks in the same frame and also
between blocks in different frames.
Maximum No. of blocks in a frame -12
Max No. of loops for each controller - 50 ( H/w dependent)
Tags can be attached to parameters and function block outputs for
debugging purposes.
Library of commonly used control schemes shall be provided.
It should be possible to create composite function blocks by combining basic
function blocks.
It should be possible to add newly created composite function blocks to the
library.
Connectivity should be checked for compatibility
Each signal is connected to exactly one source.
This source can be the output of a function block or a plant signal.
The type of the output pin, the type of the input pin and the signal type must be identical.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 10
3.1.3 Configuration of network and communication protocol
The network configuration includes:
Type of network (Serial, Ethernet)
Parameter assignments
Serial interface
COM port (RS 232, RS485, RS422)
Baud rate
Data Bits
Parity
Stop bit
Ethernet interface
IP address
MacAddress
Port No.
Type of network protocol
Modbus TCP - Modbus Protocol is a messaging structure used to establish
master-slave /client - server communication between intelligent devices
DNP3 - Distributed Network Protocol is a set of communications protocols
used between components in process automation systems
It should be possible to configure the types of protocol
(i.e. Modbus TCP or DNP3)
It should be possible to configure either master or slave
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 11
In case of Modbus TCP
Settings
Host address
Port
Mapping of Register and Coil addresses
Discrete Inputs- Start and End address
Coils-Start and End Address
Input Registers- Start and End Address
Holding Registers- start and End Address
In case of DNP 3
Settings
Host address
Port No.
Link Addresses
3.2 Download configuration
Before downloading, check the configuration for errors and see whether downloadable
system data can be created from the present configuration. Any errors found during
consistency checking are to be displayed in a window.
3.3 Upload configuration
It shall be possible to Upload into a New configuration
It shall be possible to Upload into an Existing configuration
3.5 Import/Export Utility
The Development Environment shall include a utility to support import or
export from external editors. (to be decided)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 12
4 List of Annexure
Annexure A - IEC 61131-3 : a standard programming resource
Annexure B - List of blocks with details
Annexure C - Modbus TCP, DNP3
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 13
Annexure A
IEC 61131-3: a standard programming resource
IEC 61131-3 is the third part of the open international standard IEC 61131, and was first published
in December 1993 by the IEC. The current (second) edition was published in 2003.
IEC 61131-3 is the first real endeavor to standardize programming languages for industrial
automation. With its worldwide support, it is independent of any single company.
IEC 61131-3 is the third part of the IEC 61131 family. This consists of:
Part 1: General Overview
Part 2 Hardware
Part 3 Programming Languages
Part 4 User Guidelines
Part 5 Communication
Another elegant view is by splitting the standard in two parts:
1. Common Elements
2. Programming Languages
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 14
Common Elements
Data Typing
Within the common elements, the data types are defined. Data typing prevents errors in an early
stage. It is used to define the type of any parameter used. This avoids for instance dividing a Date
by an Integer. Common datatypes are Boolean, Integer, Real and Byte and Word, but also Date,
Time_of_Day and String. Based on these, one can define own personal data types, known as
derived data types. In this way one can define an analog input channel as data type, and re-use this
over and over again.
Variables
Variables are only assigned to explicit hardware addresses (e.g. input and outputs) in
configurations, resources or programs. In this way a high level of hardware independency is
created, supporting the reusability of the software. The scopes of the variables are normally limited
to the organization unit in which they are declared, e.g. local. This means that their names can be
reused in other parts without any conflict, eliminating another source of errors, e.g. the scratchpad.
If the variables should have global scope, they have to be declared as such (VAR_GLOBAL).
Parameters can be assigned an initial value at start up and cold restart, in order to have the right
setting.
Configuration, Resources and Tasks
To understand these better, let us look at the software model, as defined in the standard in the
figure.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 15
At the highest level, the entire software required to solve a particular control problem can be
formulated as a Configuration. A configuration is specific to a particular type of control system,
including the arrangement of the hardware, i.e. processing resources, memory addresses for I/O
channels and system capabilities.
Within a configuration one can define one or more Resources. One can look at a resource as a
processing facility that is able to execute IEC programs. Within a resource, one or more Tasks can
be defined. Tasks control the execution of a set of programs and/or function blocks. These can
either be executed periodically or upon the occurrence of a specified trigger, such as the change of
a variable. Programs are built from a number of different software elements written in any of the
IEC defined languages. Typically, a program consists of a network of Functions and Function
Blocks, which are able to exchange data. Function and Function Blocks are the basic building
blocks, containing a datastructure and an algorithm.
Let’s compare this to a conventional PLC: this contains one resource, running one task, controlling
one program, running in a closed loop. IEC 61131-3 adds much to this, making it open to the
future. A future that includes multi-processing and event driven programs. And this future is not so
far: just look at distributed systems or real-time control systems. IEC 61131-3 is suitable for a
broad range of applications, without having to learn additional programming languages.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 16
Program Organization Units (POU)
Within IEC 61131-3, the Programs, Function Blocks and Functions are called Program
Organization Units, POUs.
Functions
IEC has defined standard functions and user defined functions. Standard functions are for instance
ADD(ition), ABS (absolute), SQRT, SINus and COSinus. User defined functions, once defined,
can be used over and over again.
Function Blocks, FBs
Function Blocks are the equivalent to Integrated Circuits, ICs, representing a specialized control
function. They contain data as well as the algorithm, so they can keep track of the past (which is
one of the differences w.r.t. Functions). They have a well-defined interface and hidden internals,
like an IC or black box. In this way they give a clear separation between different levels of
programmers, or maintenance people.
A temperature control loop, or PID, is an excellent example of a Function Block. Once defined, it
can be used over and over again, in the same program, different programs, or even different
projects. This makes them highly re-usable. Function Blocks can be written in any of the IEC
languages, and in most cases even in “C”. In this way they can be defined by the user. Derived
Function Blocks are based on the standard defined FBs, but also completely new, customized FBs
are possible within the standard: it just provides the framework.
The interfaces of functions and function blocks are described in the same way:
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 17
The declarations above describe the interface to a function block with two Boolean input
parameters and one Boolean output parameter.
Programs
With the above-mentioned basic building blocks, one can say that a program is a network of
Functions and Function Blocks. A program can be written in any of the defined programming
languages.
Sequential Function Chart, SFC - has elements to organize programs for sequential and
parallel control processing.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 18
SFC describes graphically the sequential behavior of a control program. It is derived from
Petri Nets and IEC 848 Grafcet, with the changes necessary to convert the representation
from a documentation standard to a set of execution control elements. SFC structures the
internal organization of a program, and helps to decompose a control problem into
manageable parts, while maintaining the overview. SFC consists of Steps, linked with
Action Blocks and Transitions. Each step represents a particular state of the systems being
controlled. A transition is associated with a condition, which, when true, causes the step
before the transition to be deactivated, and the next step to be activated. Steps are linked to
action blocks, performing a certain control action. Each element can be programmed in any
of the IEC languages, including SFC itself.
One can use alternative sequences and even parallel sequences, such as commonly
required in batch applications. For instance, one sequence is used for the primary
process, and the second for monitoring the overall operating constraints. Because of
this general structure, SFC provides also a communication tool, combining people of
different backgrounds, departments or countries.
Programming Languages
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 19
Within the standard four programming languages are defined. This means that their syntax and
semantics have been defined, leaving no room for dialects. Once you have learned them, you can
use a wide variety of systems based on this standard. The languages consist of two textual and two
graphical versions:
Textual: Instruction List, IL
Structured Text, ST
Graphical:
Ladder Diagram, LD
Function Block Diagram, FBD
In the above figure, all four languages describe the same simple program part.
The choice of programming language is dependent on:
the programmers’ background
the problem at hand
the level of describing the problem
the structure of the control system
the interface to other people / departments
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 20
All four languages are interlinked: they provide a common suite, with a link to existing experience.
In this way they also provide a communication tool, combining people of different backgrounds.
Ladder Diagram has its roots in the USA. It is based on the graphical presentation of
Relay Ladder Logic.
Instruction List is its European counterpart. As textual language, it resembles
assembler.
Function Block Diagram is very common to the process industry. It expresses the
behavior of functions, function blocks and programs as a set of interconnected graphical
blocks, like in electronic circuit diagrams. It looks at a system in terms of the flow of
signals between processing elements.
Structured Text is a very powerful high-level language with its roots in Ada, Pascal
and “C”. It contains all the essential elements of a modern programming language,
including selection branches (IF-THEN-ELSE and CASE OF) and iteration loops (FOR,
WHILE and REPEAT). These elements can also be nested. It can be used excellently for
the definition of complex function blocks, which can be used within any of the other
languages.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 21
Also, the standard allows two ways of developing your program: top down and bottom
up. Either you specify your whole application and divide it into sub parts, declare your
variables, and so on. Or you start programming your application at the bottom, for
instance via derived functions and function blocks. Whichever you choose, the
development environment will help you through the whole process.
Implementations
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 22
The overall requirements of IEC 61131-3 are not easy to fulfill. For that reason, the standard
allows partial implementations in various aspects. This covers the number of supported
languages, functions and function blocks. This leaves freedom at the supplier side, but a user
should be well aware of it during his selection process. Also, a new release can have a dramatically
higher level of implementation. Many current IEC programming environments offer everything
you expect form modern environments: mouse operation, pull down menus, graphical
programming screens, support for multiple windows, built in hypertext functions, verification
during design. Please be aware that this is not specified within the standard itself: it is one of
the parts where suppliers can differentiate.
The technical implications of the IEC 61131-3 standard are high, leaving enough room for
growth and differentiation. This makes this standard suitable to evolve well into the next
century. IEC 61131-3 will have a great impact on the whole industrial control industry. It
certainly will not restrict itself to the conventional PLC market. Nowadays, one sees it
adopted in the motion control market, distributed systems and softlogic / PC based control
systems, including SCADA packages. And the areas are still growing. Having a standard over
such a broad application area, brings numerous benefits for users / programmers. The benefits for
adopting this standard are various, depending on the application areas. Just to name a few for the
mindsetting:
reduced waste of human resources, in training, debugging, maintenance and
consultancy
creating a focus to problem solving via a high level of software reusability
reduced misunderstanding and errors
programming techniques usable in a broad environment: general industrial control
combining different components from different programs, projects, locations,
companies and/or countries
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 23
Annexure B
List of blocks with details
1. CINP - Analog Input Processor
2. LOGI - Digital Logic Operator
3. DINT - DIGITAL INTEGRATION BLOCK
4. ASW - Analog Signal Switch
5. AINT - Analog Integrator Block
6. SQRT - Square Root
7. FUNC - Function Generator Block
8. CPID - PID Block
9. ADSB - ADDITION SUBTRACTION BLOCK
10. MULD - MULTIPLIER/DIVIDER BLOCK
11. SELH - LOW/HIGH SELECTOR BLOCK
12. MPCG-Multi Point Constant Generator
13. HLMT - High/Low block
14. GSFG - Gradient Setting Function Generator
15. MSFG - Multi Stage Function Generator
16. TLDT -Time Lag + Dead Time
17. DBOG -Dead Band Operator with Gain
18. LDLG - Lead Lag Block
19. OUTP - Output Processor Block
20. PLSR - Pulser Block For Batching Operation
21. BTCH - Batching Operation
22. SEQ - Sequencer Block
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 24
23. MLOG - Multiple Operator Logical Operator Block
24. SINT - Sintering Block
25. AINP - Alarm Checking Input Block
26. MMDET - Maximum/Minimum Detector
27. NNET - Neutral Net Block
28. LCON - Loop Execution Controller
29. FOP - First Order Process
30. PPID - Pulse PID
31. RLS - Recursive Least Square Estimator
32. RND - Random Signal Generator
33. PEU - Percentage To Engineering Unit
34. EUP - Engineering Unit to Percentage
35. PRDT - Predictor Block
36. PTC - Pressure Temperature Compensator
37. PPC -PID To Pulse Converter
38. CNTR – Counter
39. RTT - Real Time Trigger
40. MAVG - Moving/Fixed Average
41. PARA - Parameter Setter
42. ABS - Absolute Value Finder
43. STL - Statistical Function
44. LGM - Logarithm
45. RCL - Rate of Change Limitter
46. PLN - Polynomial Line Table For Linearisation
47. CMP – Comparator
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 25
1. CINP - Analog Input Processor
This block is used to read analog input from physical channel and to process it after
reading the input the block executes the following functions on the input signal as per the
relevant parameter specification
Inputs
Input 1,is an analog signal, which is to be read and processed.
Outputs
Output 1 is an analog signal, which is the processed output signal.
Output 2 is the instrument alarm
Output 3 is the High-High alarm
Output 4 is the High alarm
Output 5 is the Low alarm
Output 6 is the LowLow
Output 7 is the Rate alarm
Parameters
P01: Instrument error checking. High limit in percentage.
P02: Instrument error checking. Low limit in percentage.
P03: Rate of change limit. Maximum change (in %) permitted per execution cycle.
P04: Process Maximum Value
P05: Process Minimum Value
P06: Engineering Units(Max 7 Chars)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 26
P07: Process HIHI limit in percentage
P08: Process HI limit in percentage
P09: Process LO limit in percentage
P10: Process LOLO limit in percentage
P11: Filter time constants in seconds.
P12: Instrument error alarm enable(0-disable,1-enable)
P13: Process HIHI alarm enable(0-disable,1-enable)
P14: Process HI alarm enable(0-disable,1-enable)
P15: Process LO alarm enable(0-disable,1-enable)
P16: Process LOLO alarm enable(0-disable,1-enable)
P17: Process RATE alarm enable(0-disable,1-enable)
P18:Alarm hysterisis constant in percentage(common for all alarms)
P19:Square root extraction (0-NO,1-YES)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 27
2. LOGI - Digital Logic Operator
This block reads or writes digital signals from/to physical channels.One LOGI block can
take two inputs and it can execute any of the following logical function on the input
signals. The function selection is done by the parameter no 4.Apart from the logical
function,this block can detect alarm(status change) of both the inputs and output.If A and B
are the two inputs to block,then the output for diffrent function codes are as follows.
Inputs
D1: Digital input 1
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 28
D2: Digital Input 2
Outputs
Y: Digital output
D11: Input1 (d1) alarm status
D12: Input2 (d2) alarm status
D13: Output alarm status
Parameters
P01: In #1 Normal State (1/0)
P02: In #2 Normal State (1/0)
P03: Output Normal State (1/0)
P04: Function Code
P05: ON Time (seconds)
P06: OFF Time (seconds)
P07: Input #1 Alarm (1=Y, 0=N)
P08: Input #2 Alarm (1=Y, 0=N)
P09: Output Alarm (1=Y, 0=N)
P10: In #1 Normal State (Max 7 char)
P11: In #1 Alarm State (Max 7 char)
P12: In #2 Normal State (Max 7 char)
P13: In #2 Alarm State (Max 7 char)
P14: Output Normal State (Max 7 char)
P15: Output Alarm State (Max 7 char)
P16:Set trigger.
P17:Counter reload value
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 29
3. DINT - DIGITAL INTEGRATION BLOCK
This block can be used to increment/decrement its output(Y) by a user defined step
size(delta Y) during each cycle of block execution. The step size is defined using the
block parameter P03.Increment/decrement action is decided by the value of digital inputs
D! and D2.When D1 is ON, the step size is added to the previous value of the output(Y 0).
When D2 is ON, the step size is subtracted from the previous value of the output. The
output will be reset to the value K1(as defined by the block parameter P04) when the
digital input D3 is ON. The output can be preset to the value K2(as defined by the block
parameter P05) by making the digital input D4 ON.
Inputs
D1 = Digital Input.
D2 = Digital Input.
D3 = Digital Input.
D4 = Digital Input.
Output
Y = Integrated analog output Parameters
P01: Output Low Limit (%)
P02: Output High Limit (%)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 30
P03: StepSize Per Cycle : delta Y (%)
P04: Reset Value : K1 (%)
P05: Preset Value : K2 (%)
4. ASW - Analog Signal Switch
This block works as a digitally controlled switch for analog signals. So depending upon
some process conditions you can select the analog signal for computation, processing or
for outputing. There are two constants(Parameters 3 and 4)also provided as parameters
and selection will be between parameters if specified so.
Inputs
D1 : Digital input: Switching Control signal (acts as a control for the switch)
A1 : Analog input : Analog Input 1 (signal to be switched)
A2 : Analog input : Analog Input 2 (signal to be switched)
Output
Y : Switched analog output
Parameters
P01 : Select Analog #1/Const #1(1/0)
P02 : Select Analog #2/Const #2(1/0)
P03 : Const #1 (%)
P04 : Const #2 (%)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 31
P05 : Ramp Rate(%)
5. AINT - Analog Integrator
The AINT block provides an analog output which is the integral of the input signal over a
period of time. It is basically used for computing the cumulative quantity of the material
used over a period of time by totalising the flow rate.
The analog signal corresponding to the flow rate is to be connected to the input A of the
block. Output represents the integrated value. Care should be taken to specify the high
and low range of the input flow rate to be totalised(P04 & P05)and the time base of the
input flow rate(P03) to get the integrated output correctly. The output of this block cannot
be connected to any other block. The tag fixed at the block output can be used for the
display purpose.
The analog output Y will be reset to the value K1(as defined by the parameter P01)when
the digital input D1 is ON. The output Y will be held at the previous value when the
digital input D2 is ON.
Inputs:
A Analog input signal to be integrated.
D1 When this input ON, the integrated output will be reset to a value K1.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 32
D3 When this input ON, the integrated output will be held at the previous value.
Outputs:
Y Analog input signal to be integrated.
d11 This output will be set when the integrated output Y overflows or when it is reset
by the digital input D1.
Parameters:
P01 Reset Value of O/P:K1(engg.unit)
P02 O/P Overflow Limit:K2(engg.unit)
P03 Time Base(1=per Hour,2=per Minute)
P04 I/P(flow rate) High range(engg unit)
P05 I/P(flow rate) Low range(engg unit)
P06 Reset at 6 AM(N=No,else Yes)
P07 Process Maximum Value
P08 Process Minimum Value
6. SQRT-Square Root
Parameters
P01 C BIAS CONSTANT
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 33
7. FUNC - Function Generator Block
The FUNC block generates an output which is a function of the input(Y=f(A1)).The
input/output relationship is defined with the help of block parameters in terms of a look-
up table. The output values for intermediate input points are computed by interpolation.
This block can be used to configure look-up tables for split ranging of signals or
linearisation. Linearization of temperature input is one typical application of this block.
The output pf thermocouple or RTD can be linearised with the help of this block. The
percentage temperature for the incoming millivolt signal at 0 tp 100% with an interval of
10% can be calculated and configured as the parameters of the FUNC block. this can
be used to find out the percentage temperature for a given percentage millivolt input.
Another typical application is the ranging of the signal going to the control valves. For
example, if we have two valves, to be operated for different range of flow by the output
of one controller, ie.first valve to operate in the range of 0% to 50% and second valve to
operate in the range of 50% to 100% of the controller output. This can be implemented by
using FUNC blocks.
Input
A1: Analog input
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 34
Output
Y: Analog output
Parameters:
P01: OUTPUT AT 0%. Output when input is 0%.
P02: OUTPUT AT 10%. Output when input is 10%.
P03: OUTPUT AT 20%. Output when input is 20%.
P04: OUTPUT AT 30%. Output when input is 30%.
P05: OUTPUT AT 40%. Output when input is 40%.
P06: OUTPUT AT 50%. Output when input is 50%.
P07: OUTPUT AT 60%. Output when input is 60%.
P08: OUTPUT AT 70%. Output when input is 70%.
P09: OUTPUT AT 80%. Output when input is 80%.
P10: OUTPUT AT 90%. Output when input is 90%.
P11: OUTPUT AT 100%. Output when input is 100%
CPID - PID BLOCK
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 35
This block performs PID control action depending on the controller mode (P03) and the
values of the PID parameters set by the user. The CPID block is used for the regulation
control of the process variables. This block is normally used in the CINP-CPID-OUTP
combination. The block takes the incoming signal (Process Variable) PV and compares it
with the Set Value (SV) and executes the PID control algorithm and outputs the
Manipulated variable (MV).
Inputs
PV : Process Variable
SV : Remote (Cascade) Setpoint
D1 : Enable / Disable PID operation (0 = enable, 1 = disable)
D2 : Enable / Disable Setpoint tracking
Outputs
Y : PID output
D11 : Cascade mode opearation
D12 : Output High Alarm
D13 : Output Low Alarm
D14 : Deviation alarm
Parameters
P01: Direct/Reverse Acting (1/0)
P02: Set Point Value (%)
P03: Mode (0=A, 1=M, 2=C)
P04: Hysterisis Constant (%)
P05: Setpoint Ramp Rate (%)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 36
P06: Proportional Gain Kp
P07: Integral Time Ti
P08: Derivative Time Td
P09: Output Hi Limit (%)
P10: Output Lo Limit (%)
P11: Deviation Limit (%)
P12: Master PID (1=Y, 0=N)
P13: Deviation Alarm (1=Y, 0=N)
P14: Output Limit Alarm (1=Y, 0=N)
P15: Valve Direction (1=DIR, 0=REV)
P16: Output Ramp Rate (%)
ADSB - ADDITION SUBTRACTION BLOCK
This block computes the arithmetic sum or difference of two or more analog signals. The
maximum number of inputs is limited to 4. Zero value(0) will be assumed for the
unconnected analog inputs in the computation.
Inputs
A1 = Analog input1
A2 = Analog input2
A3 = Analog input3
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 37
A4 = Analog input4
Output
Y = Processed analog output signal.
Parameters
P01: constant #1 (k1)
P02: constant #1 (k2)
P03: constant #1 (k3)
P04: constant #1 (k4)
P05: Bias Constant, C (%)
P06: -ve Output Value (0=N, 1=Y)
MULD - MULTIPLIER/DIVIDER BLOCK
This block can be used to carry out multiplication or division operation on two analog
signals. The required arithmetic operation can be selected using the block parameter P01.
Unity value (1) will be assumed for the unconnected analog inputs in the computation.
Inputs
A1 = Analog input1
A2 = Analog input2
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 38
Output
Y = Processed Analog output
Parameters
P01: Computation Code (0 = MUL, 1= DIV)
P02: Gain Constant: K
P03: Bias Constant: C (%)
SELH - LOW/HIGH SELECTOR BLOCK
Inputs
A1 = Analog Input 1
A2 = Analog Input 2
A3 = Analog Input 3
A4 = Analog Input 4
Output
Y = Processed analog output signal
Parameters
P01: Function Code: CD (0 = LO, 1 = HI)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 39
MPCG - Multi Point Constant Generator
P01 C1 CONSTANT WHEN D1 IS ONP02 C2 CONSTANT WHEN D2 IS ONP03 C3 CONSTANT WHEN D3 IS ONP04 C4 CONSTANT WHEN D4 IS ONP05 C5 CONSTANT WHEN D1,D2,D3,D4 IS OFF
This block is a constant generator equipped with constants at four points. Any of the
constants can be selected by proper combination of the digital signals D1..D4. If select
commands D1..D4 are not connected ,it functions as a single point constant generator and
outputs C5.D1 has highest priority and D4 lowest.
d11=1 if C1!=C2d12=1 if C3!=C4d13=1 if D1,D2,D3 & D4 are not connected
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 40
13. HLMT - High/Low block
This block is used to limit the value of an analog signal within the high limit and low limit set by the user. The limits can be set using the block parameters P01 and P02.
Output Y=A if C2 < A< C1 Where A= Input signal =C1 if A>C1 C1 = High limit
=C2 if A< limit C2="Low">
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 41
14. GSFG - Gradient Setting Function Generator
P01 CD 0 FOR TIME TO BE TAKEN IN SECS 1 FOR TIME TO BE TAKEN IN MINS 2 FOR TIME TO BE TAKEN IN HRP02 C1 START POINT A1P03 C2 TARGET POINT A2P04 Ti TIME TO BE TAKENP05 ALPHA GRADIENT CONSTANT IF CD/Ti IS CHOSEN, ALPHA IS AUTOMATICALLY FIXED.P06 C2A ALARM OUTPUT ENABLE WHEN SET POINT IS REACHED.
When D1 is ON, output ramps to target point in time Ti specified.(D2 should be OFF)
When D1 is OFF then ramping is stopped. When D2 is ON output is reset to C1.
This is a computing block for generating a function having gradient specified by the
parameters CD and ALPHA. The start point and target point are given by inputs A1 and
A2. If A1&A2 are not connected parameters C1&C2 are taken as start point and target
point respectively.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 42
15. MSFG-Multi Stage Function Generator
P01 CD CODE 0 FOR SEC 1 FOR MINP02 C CONSTANT TAKEN TO BE START POINT IF A1 IS NOT CONNECTEDP03 T1 TIME SETTINGP04 T2 TIME SETTINGP05 T3 TIME SETTINGP06 T4 TIME SETTINGP07 T5 TIME SETTINGP08 T6 TIME SETTINGP09 T7 TIME SETTINGP10 Y1 OUTPUT SETTINGP11 Y2 OUTPUT SETTINGP12 Y3 OUTPUT SETTINGP13 Y4 OUTPUT SETTINGP14 Y5 OUTPUT SETTINGP15 Y6 OUTPUT SETTINGP16 Y7 OUTPUT SETTING
This computing block generates functions with specified parameters when input D1 is '1'.Input A1 is the start point. For time=t1 the output ramps to Y1 and for the next time Y1 to Y2 and so on. If at any time D2 is on, output holds to the previous value.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 43
16. TLDT-Time Lag + Dead Time
P01 T TIME CONSTANT IN SECP02 K GAIN CONSTANTP03 L DEAD TIME
This block computes first order LAG+DEAD time while receiving analog signals A1.
17. DBOG-Dead Band Operator with Gain
P01 C1 DEAD BAND ON +VE SIDEP01 C2 DEAD BAND ON -VE SIDEP03 K1 GAIN WITHIN DEADBANDP04 K2 GAIN OUTSIDE DEADBAND
WHEN INPUT IS WITHIN DEADBAND OUTPUT Y:K1*A1WHEN INPUT IS OUTSIDE DEADBAND OUTPUT Y: K2*(A1-C1)+K1*C1 .....(+VE) K2*(A1+C2)+K1*C2 .....(-VE)
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 44
This computing block performs dead band processing while receiving analog signal. It judges
whether input data is inside or outside deadband and provides output with gain specified by a
parameter.
18. LDLG - Lead Lag Block
This block provides lead/lag compensated input.
OutputY=K.1+T1s/1+T2s.A Where A=Input signal'T1=LEAD Time Constant T2= LAG Time Constant and T1/T2< 100
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 45
19. OUTP - Output Processsor Block
This block outputs the processed analog value to a physical tag (tag representing a
signal physically connected to the Analog Output module of RTU). It converts the
digitised value of the input signal (0-4000 counts) into the range used by the Analog
Output module (0-4096 counts).
Output Y=A.4096/4000 Where A=Input signal
This block can also be used to interconnect two or more loops using Loop-back Tag
(LPB Tag). The LPB tag fixed at the output of an OUTP block may be connected as
input to a block in another loop.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 46
20. PLSR - Pulser Block For Batching Operation
P01 WS WEIGHING SCALE IN KGSP02 SP SETPOINT IN KGSP03 HTL HIGH TOLERANCE LIMIT %P04 LTL LOW TOLERANCE LIMIT %P05 SL1 SLOWING PRESET(00-20) IN KGSP06 SL2 SLOWING PRESET(20-40) IN KGSP07 SL3 SLOWING PRESET(40-60) IN KGSP08 SL4 SLOWING PRESET(60-80) IN KGSP09 SL5 SLOWING PRESET(80-100) IN KGSP10 ESL EMPTY SCALE LIMIT IN KGSP11 FC1 FLIGHT CORRECTION (00-20) IN KGSP12 FC2 FLIGHT CORRECTION (20-40) IN KGS
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 47
P13 FC3 FLIGHT CORRECTION (40-60) IN KGSP14 FC4 FLIGHT CORRECTION (60-80) IN KGSP15 FC5 FLIGHT CORRECTION (80-100) IN KGSP16 PON PULSE ON TIME IN SECSP17 POFF PULSE OFF TIME IN SECSP18 BTM BATCHING TIME IN SECS
This block is used for batching and weighing operations.It accepts one analog and
an enable command(D3) to manipulate the digital output Y and the four alarms which
indicate the various states of the batching cycle. The second input to the pulser is the
setpoint in percentage and the fourth ouput is the HALT signal. If the second input is
not connected the parameter specified as the setpoint will be taken for the batching
operation. When the HALT signal is on the pulser will stop the batching operations,
and the halted time will not be counted as batch time. Batching resumes when the signal
goes OFF.
21. BTCH-Batching Operation
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 48
This block is used for batching and weighing operations. It accepts one analog input and
an enable command(D3) to manipulate the digital outputs Y1,Y2 and the four alarms
which indicate the various states of the Batching cycle. This block is same as the pulser
block except that it has two control outputs namely FAST(Y1) and SLOW (Y2).
The second input to the batcher is the setpoint in percentage and the fourth input is the
HALT signal. If the second input is not connected the parameter specified will be taken for
the batching operation. When the HALT signal is ON the batcher will stop the batching
operations, and the halted time will not be counted as batch time. Batching resumes when
the HALT signal goes OFF.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 49
A batching cycle starts on the high going edge of the enable input.A bin is considered to
be empty if the bin is less than the Empty Scale Limit(ESL).An empty bin is indicated by a
high signal on 'd13' output irrespective of whether the block is enabled or not.
The following functions are performed only when the enable input is high.
If 'A1' goes higher than the HighLimit(HL),Alarm 'd12' is set.
If A1 could not attain the set value(Low limit in this case)during the Maximun Batching
Time(BTM),alarm 'd14' is set.
Successful completion of the Batching operation is indicated by a high state of Alarm
'd15' (Batch Over).
If any of the above mentioned alarms namely d12,d14 or d15 is high,the block output is
permanently disabled for the current batching operation.
In the absence of any alarm condition ,the FAST outputs are activated until the Slowing
Limit(SL) is attained. At this point the FAST output goes OFF and SLOW output
continues till the Flight Corrected Value(FCV) is reached. FCV should be carefully
chosen so that the input reaches the lower tolerance limit after settling. However no
further action is taken if the limits are not attained.
22. SEQ-Sequencer Block
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 50
P01 A/M AUTO/MANUAL mode selector P1=1-AUTO;P1=0-MANUALP02 TE Transition edge selector P2=1-Low to High;P2=0-High to LowP03 OP1 P3=1,d11 enabled;P3=0 d11 disabledP04 OP2 P4=1,d12 enabled;P4=0 d12 disabledP05 OP3 P5=1,d13 enabled;P5=0 d13 disabledP06 OP4 P6=1,d14 enabled;P6=0 d14 disabledP07 OP5 P7=1,d15 enabled;P7=0 d15 disabledP08 OP6 P8=1,d16 enabled;P8=0 d16 disabled
D1 - Input for sequencing.Depending on P2 the sequencing will be done +ve edge -ve edge d11 - Sequence output 1d12 - Sequence output 2d13 - Sequence output 3d14 - Sequence output 4d15 - Sequence output 5d16 - Sequence output 6
This block does the function of sequencing the outputs as per the function of sequencing
the outputs as per the required pattern. The block has one input and six outputs. The
outputs can be sequenced(ie.made '1')one by one according to the parameter entered, on the
+ve/-ve edge of the input. Parameter 02 specifies the required edge for sequencing.
Parameters 03 to 08 are used to specify the outputs to be enabled during sequencing.
Parameter 03 corresponds to output 1 and parameter 08 corresponds to output 6.If the value
of the parameter value is '0' then the output will be skipped during sequencing. When the
mode is manual as set by parameter 01,all he outputs will be set to their respective
parameter value.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 51
23. MLOG-Multiple Operator Logical Operator Block
The MLOG block is similar to the LOGI block, which can be used to perform any
one of the logic functions namely AND, OR NAND and NOR. Depending on the
requirement, the function code can be four digital signal can be connected to the input of
this block.
Inputs:
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 52
24. SINT-Sintering Block
P01 MAXIMUM VALUE OF SINT OUTPUTP02 MINIMUM VALUE OF SINT OUTPUTP03 TOTAL NUMBER OF WIND BOXESP04 MINIMUM DIFFERENCE BETWEEN TWO TEMPERATURES
Inputs:A1 - INPUT TEMPERATURE FROM LAST WIND BOXA2 - INPUT TEMPERATURE FROM (N-1)th WIND BOXA3 - INPUT TEMPERATURE FROM (N-2)th WIND BOX
OUTPUTS:Y - ACTIVE LENGTH OF SINTERING MACHINE
This block determine the active length of machine within which sintering process is
distribution curve of the last three wind boxes.Let Xm be the active length of the sintering
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 53
process.Suppose tn-2,tn-1,tn are the last three wind boxes,then active machine length Xm=tn-2-tn/2 *
(tn-2 * tn-1+tn)+15
25. AINP-Alarm Checking Input Block
26. MMDET-Maximum/Minimum Detector
P01 CD Control Code
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 54
P01 = 0 - Detect Maximum = 1 - Detect Minimum = 2 - Sample & Hold
This block is used to detect the maximum or minimum of an input signal. The block
has 3 inputs and one output.These inputs have the following definition.
D1 - Reset - If D1=1 the block is held in reset condition
and the internal variable are initialised.
ie. Y=0 if CD=0 or CD=2
Y=1 if CD=1D2 - Hold - If D2=1 the output of Y is held to its previous value.For normal working D2=0A1 - Analog inputY - Block Output
Y=0 if (D1=1) & CD=0 Y=100 if (D1=1) & CD=1 Y=0 if (D1=1) & CD=2 If D1=0 & D2=0 and CD=0 Y=A1 if A1>Y If D1=0 & D2=0 and CD=1 Y=A1 if A1< pre Y="A1" CD="2" and D2="0" & D1="0" If>
27. NNET-Neutral Net Block
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 55
28. LCON-Loop Execution Controller
P01 CD Logic Control ParameterP02 to P20 Loop No.whose execution is to be nabled/disabled
This is a general purpose loop control block which takes two digital inputs and gives a
digital output. The digital output is used to selectively enable or disable the execution of
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 56
a set of control loops. Depending on the inputs can be used for controlling the loop
execution. If the logical output Y=1 then all the loops as specified in parameter P02 to P20
will be enabled for execution. If the logical output Y=0,then all the loop specified by
the parameter P02 to P20 will be disabled.
The logic is defined as follows
IfCD=0 Y=0CD=1 Y=1CD=2 Y=D1&D2CD=3 Y=!D1&D2CD=4 Y=D1&!D2CD=5 Y=!D1&!D2CD=6 Y=D1+D2CD=7 Y=!D1+D2CD=8 Y=D1+!D2CD=9 Y=!D1+!D2CD=8 Y=(D1+Y) & !D2
If Y=0 all the loops specified in P02 to P20 are disabled. If Y=1 all the loops specified
in P02 to P20 are enabled.
29. FOP-First Order Process
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 57
Parameters:P01:T,Time constant in no of samples.P02:K,Gain Constant.P03:L,Dead Time in no of samples.
Inputs:A1:Input Signal
Outputs:Y:Block output
This block is used for simulation of a first order process using a time lag and dead time.
30. PPID - Pulse PID
Parameters:
P01:DR:CONTROLLER ACTION DIRECT/REVERSE.
P02:MD:MODE 0-AUTO 1-MANUAL 2-CASCADE.
P03:SV:SET VALUE.
P04:HS:HYSTERISIS CONSTANT FOR ALARM.
P05:DH:DEVIATION HIGH LIMIT.
P06:DL:DEVIATION LOW LIMIT.
P07:KP:GAIN CONSTANT.
P08:TD:DERIVATIVE TIME CONSTANT.
P09:TI:INTEGRAL TIME CONSTANT.
P10:DHA:DEVIATION HIGH ALARM ENABLE.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 58
P11:DLA:DEVIATION LOW ALARM ENABLE.
P12:D/M:DEVIATION?MEASURED VALUE INPUT.
P13:MO:MANUAL OUTPUT.
P14:CONTROLLER CONSTANTS INT/EXT.
P15:NUMBER OF LEARNING CYCLES.
P16:CHANGE IN PID O/P.
P17:INCREMENT(forcing in manual mode).
P18:DECREMENT(forcing in manual mode).
P19:VALUE POSITION HIGH LIMIT(%).
P20:VALUE POSITION LOW LIMIT(%).
Inputs:
A1:Measured Variables A2..A4:External Constants P1,P2,P3
Outputs:
Y:Controller output d11:Deviation High Alarm d12:Deviation Low Alarmt d13:Mode
Indication d14:Learning Mode
31. RLS - Recursive Least Square Estimator
Inputs:A1:PLANT INPUT A2:PLANT OUTPUT D1:START ESTIMATION D2:LEARNING MODE
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 59
Outputs:
P1,P2,P3 tuning constants for velocity mode PID controller
The RLS block computes the optimum value of the controller constants for a PID controller
based on an estimate of the plant parameters through Recursive Least Squares
(RLS)technique. The outputs P1 ,P2 and P3 can be connected to PID controller which
controls the plant .The plant input and output are connected to the inputs A1 and A2
respectively. When the D1 input goes from LOW to HIGH a fresh estimation cycle starts.
When input D2 is high ,the internal proceeds but the outputs P1,P2 and P3 are held
constants.
32. RND:Random Signal Generator
Parameters:P01:NL,max noise level peak to peak in %P02:C,Bias Constant in %
Inputs:None Outputs:Y : Block Output
This block is used for generating a Random Noise Signal whose amplitude and bias can be set using the block parameters.
33. PEU - Percentage To Engineering Unit
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 60
Parameters:
P01:EURH:ENGINEERING UNIT RANGE HIGH
P02:EURL:ENGINEERING UNIT RANGE LOW
P03:PHH:PROCESS HIGH HIGH LIMIT
P04:PH:PROCESS HIGH LIMIT
P05:PL:PROCESS LOW LIMIT
P06:PLL:PROCESS LOW LOW LIMIT
P07:PHHA:PROCESS HIGH HIGH ALARM OUTPUT ENABLE
P08:PHA:PROCESS HIGH ALARM OUTPUT ENABLE
P09:PLA:PROCESS LOW ALARM OUTPUT ENABLE
P10PLLA:PROCESS LOW LOW ALARM OUTPUT ENABLE
P11:HYST:HYSTERESIS CONSTANT
The function performed in this block is percentage to engineering conversion.
When an abnormality is detected in any of the limit checks ,the corresponding alarm is
activated.The alarms may be connected to a physical tag,input of another blck or it can be
left unconnected.
d11-process high high alarm
d12-process high alarm
d13-process low alarm
d14-process low low alarm
Y=(EURH-EURL) * A1 / 100 + EURL
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 61
34. EUP:Engineering Unit to Percentage
Parameters:
P01:EURH:ENGINEERING UNIT RANGE HIGH
P02:EURL:ENGINEERING UNIT RANGE LOW
The function performed in this block is engineering unit to percentage conversion.
Y=(A1-EURL)/( EURH-EURL) * 100
35. PRDT-Predictor Block
Parameters:
P01:Tp,Prediction Period in secs
Inputs:
A1:Input Signal
Outputs:
Y:Block output,ie predicted value of the input signal
This block predicts the value of the input signal after a time Tp using the method of
least estimation.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 62
36. PTC - Pressure Temperature Compensator
Parameters:
P01:TRH:TEMPERATURE RANGE HIGH
P02:TRL:TEMPERATURE RANGE LOW
P03:PRH:PRESSURE RANGE HIGH
P04:PRL:PRESSURE RANGE LOW
P05:C1:CONST FOR ABS PRESS CONV
P06:C2:CONST FOR ABS TEMP CONV
P07:DP:DESIGN PRESSURE
P08:EURL:DESIGN TEMPERATURE
Inputs:
A1:FLOW(%)
A2:TEMPERATURE(%)
A3:PRESSURE(%)
These input terminals should be used only for the designated signals.
This block provides presure and temperature compensation.The pressure compensation
factor is calculated using the relation
PCF=(EU(PRESS)+C1)+(DP+C1).
The temperature compensation factor is calculated using the relation
TCF=(DT+C2)/(EU(TEMP)+C2).
The corrected flow is calculated using the relation
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 63
Y=SQRT(A1 * PCF * TCF) * 10.
If the pressure or temperature input is left unconnected,then the corresponding
compensation factor is set equal to 1.If the flow input is left unconnected,then A1 is set
equal to 0.
In the equation for calculating the corrected flow,the resulting value is multiplied by
10.This is done to correct the scaling error.
37. PPC-PID To Pulse Converter
Parameters
P01:Sampling rate the at which the PPC algorithm is to be executed.Normally set to 1 for
exceeding the algorithm every cycle.
P02:Percentage PID output change corresponding to one cycle ON pulse. P03:Settling
time,to be used with process having large response time.
Inputs
A1:Analog input,which is normally the output of a controller.
A2:Analog input giving position of the final control element.
Outputs
Y:Digital signal normally used as the pulse to increase the final control element position
d11:Digital signal normally used as the pulse to decrease the final control element
position.
This block is provided for converting the output of a PID controller to digital signal
to operate final control elements which need pulses to increase and decrease the
controlled variable. For example there are valves with actuators which responds to
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 64
increase or decrease pulses instead of continuous 4-20ma signal. This block generates
two different signals or output pulses, with the number of pulses and width being
proportional to the PID output. A second input is provided to read the final control
element position, and the PPC block always tries to match both the inputs by adjusting
the output pulses. In case the valve position input is not available from the field, PPC
will generate pulses as per parameter 02,making the final control element position
match with the PID output.
38. CNTR-Counter
Parameters:P01 Maximum Value of the Counter OutputP02 Minimum Value of the Counter OutputP03 Counter Output ValueP04 Counter up for rising(0)/Falling(1) edgeP05 Counter down for rising(0)/Falling(1) edgeP06 Reset ValueP07 Preset ValueP08 Alarm Enable(I/O)P09 High Alarm LimitP10 Low Alarm LimitInputs:D1 Count Up InputD2 Count Down InputD3 Reset Input
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 65
D4 Preset InputOutputs:Y Count Outputd11 High Alarm Outputd12 Low Alarm Output
This block can be used as general purpose counter. This block counts up or down
depending upon the incoming signals at D1 and D2.It counts up for the rising edge or for
falling edge of D1 as per the specification in the parameter P04 and it counts down for the
rising edge or falling edge of D2 as per the specification in parameter P05.D3 and D4 are
used for resetting and presetting the counter output. The high alarm and low alarm limit is
also provided for high/low alarm checking and high alarm(d1) and alarm(d12) outputs are
also provided.
39. RTT-Real Time Trigger
Parameters:
P01 Seconds Trigger Time(00-59)P02 Minutes Trigger Time(00-59)P03 Hours Trigger Time(00-23)P04 Trigger on Time in No of Cycles
Inputs:A1 Seconds Trigger InputA2 Minutes Trigger InputA3 Hours Trigger Input
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 66
Outputs:d11 Seconds Trigger Outputd12 Minutes Trigger Outputd13 Hours Trigger Outputd14 HH:MM:SS TriggerThis block is used to co-relate the logic configured in the loop with real time clock.It can
be used to reset/restart the logic/counters/ integrators configured.
A pulse with the width(for no of cycles)specified at P04 will be generated at d11 when the
'seconds' (SS) in the real time(HH:MM:SS) becomes equal to A1 or P01(if A1 is
unconnected).d12 will be ON for no of cycles specified at P04 when the 'minutes'(MM) in
the real time (HH:MM:SS) becomes equal to A2 or P02(if A2 is not connected).Similarly
d13 will ON for no of cycles specified at P04 when the 'hours'(HH) in the real time
(HH:MM:SS) becomes equal to A3 or P03(if A3 is not connected).
The fourth output,d14,will be ON for no of cyckes specified at P04 when all the three ,ie
seconds(SS),minutes(MM) and hours(HH) matches with A1/P01.A2/P02 and A3/P03
respectively.One typical application for this output is the initialization of the counters and
integrators at the beginning of the shift or day
40. MAVG-Moving/Fixed Average
This block computes the average of the incoming signal continuously or for a fixed
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 67
number of latest samples. f the parameter 1(P01) is zero, hen the block continuously
updates the average computed with every new samples read. n this case, input 1 can be
used to initialise or reset the output to the specified
In parameter 3(P03).If the parameter 1(P01) is specified as 1, then the block computes the
average of the last few (Parameter 2) inputs. When a new value is read into this queue of
few last samples, the oldest will be ignored.
Input 1 is a digital signal ,which initialise/reset signal for the block.
Input 2 is an analog signal, for which the averaging computation has to be done.
Output, is an analog signal, which is the average or moving of the input signal.
Parameter 1(P01):Set to '0' for continuous averaging and '1' to moving average.
Parameter 1(P02):No of samples to be used for moving average computation.
Parameter 1(P03):Reset/Initialise value.
Parameter 1(P04):Enable/Disable flag.
41. PARA-Parameter Setter
This block is used automatically set the parameters of other blocks to any desired
value. This block gets actuated with a rising edge in the first signal. For example, this
block can be used to automatically change the mode of the controller(which is a
parameter of the PID block) or alarm limit of an incoming signal etc. conditionally. Once
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 68
when this block gets actuated, it can be set a maximum of three parameter in other blocks
which may be in different loops. The value to which the parameters has to be set be
decided by parameters P10,P11, and P12 or the input signals 2,3 and 4.
Input 1,is a digital signal ,which is the 'condition' by which the block is getting actuated.
i.e.a rising edge of this input will set the three parameter specified by the parameters P01
to P09 to the values specified in P10 to P12.
Input 2,Input 3 and Input4 are the three incoming values, if connected, to which the
parameters has to be set when the block gets actuated.
There is no Output signal for this block.It only executes the parameter setting job during
the execution cycle in which it detects a rising edge in the input1.
Parameter 1(P01):Loop no of the first parameter to be modified.
Parameter 2(P02):Block no of the first parameter to be modified.
Parameter 3(P03):Parameter no of the first parameter to be modified.
Parameter 4(P04):Loop no of the second parameter to be modified.
Parameter 5(P05):Block no of the secon parameter to be modified.
Parameter 6(P06):Parameter no of the second parameter to be modified.
Parameter 7(P07):Loop no of the third parameter to be modified.
Parameter 8(P08):Block no of the third parameter to be modified.
Parameter 9(P09):Parameter no of the third parameter to be modified.
Parameter 10(P10):Constant 1(To which the first parameter to be changed) .
Parameter 11(P11):Constant 2(To which the second parameter to be changed).
Parameter 12(P12):Constant 3(To which the third parameter to be changed).
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 69
42. ABS - Absolute Value Finder
This block gives the absolute value of the input signal, i.e.the output will be equal to the
magnitude of the input signal irrespective of the input signal.
Input1 is an analog signal for which the absolute value has to be found.
Output1 is an analog value equal to the magnitude of the input.
There is no parameters for this block.
43. STL:Statistical Function
This block gives the mean or median of incoming signals. There are four inputs
(maximum) can be connected to this block and it gives the mean or median of the inputs at
the output.
Input1 is an analog signal,one among the signals for which the mean or median of the
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 70
inputs has to be found.
Input2 is an analog signal,one among the signals for which the mean or median of the
inputs has to be found.
Input3 is an analog signal,one among the signals for which the mean or median of the
inputs has to be foundd.
Input4 is an analog signal,one among the signals for which the mean or median of the
inputs has to be found.
Output1 is an analog signal,which is the mean or median of the connected inputs.
Parameter 1(P01):Selection between mean(0) or median(1)..
44. LGM - Logarithm
ParametersP01:LOG/ANTI LOG selector P01=0-Log;P01=1-Anti Log
InputsA1:Analog inputs whose log og antilog is to be calculated.
OutputsY:Analog value equal to the log or antilog of the input.
This block computes the log or antilog of the input signal
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 71
45. RCL-Rate of Change Limitter
This block limits the rate of change of output irrespective of the fast variations in the input.
The maximum variation permitted in an execution cycle is limited by the parameter P01
specified. There are three inputs provided for this block.
Input 1,is a digital one, which is the enable/disable flag for the rate of change limiting
function. When the first input is 1,the output of the block will same as the second
input,which is the analog signal on which the limiting function is applied.
Input 2,is an analog one, which is the input signal on which the rate of change limiting
function is to be applied.
Input 3,is an analog one, which is an alternative to the parameter P01.ie.if this signal is
connected ,the rate of change limit will be equal to this input instead of the parameter P01.
Output, is an analog signal, which is the second input itself limited to the specified rate of
change limit.
Parameter (P01) limits for rate of change.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 72
46. PLN - Polynomial Line Table For Linearisation
This block provides a look-up table which is mainly used for linearisation of signals from
non-linear transducers such as thermocouple , RTD etc. This provides 9 segment, piece
wise linearisation with ten co-ordinates. Compared to the FUNC block, the flexibility
available with the input co-ordinates makes the linearisation computation very easy. This
block can be used for split ranging of input and output signals, scaling of signals, low
cutting of flow signals, clipping etc.
Input 1, is an analog one, which is the input to be linearised or split.
Output 1 ,is an analog signal, which is the linearised signal.
Parameters:
P01 Input Value(X1)P02 Input Value(X2)P03 Input Value(X3)P04 Input Value(X4)P05 Input Value(X5)P06 Input Value(X6)P07 Input Value(X7)P08 Input Value(X8)P09 Input Value(X9)P10 Input Value(X10)P11 Output corresponding to X1P12 Output corresponding to X2P13 Output corresponding to X3P14 Output corresponding to X4P15 Output corresponding to X5P16 Output corresponding to X6
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 73
P17 Output corresponding to X7P18 Output corresponding to X8P19 Output corresponding to X9P20 Output corresponding to X10
47. CMP - Comparator
This block is an analog value comparator.It compares the analog inputs for 'greater
than,,'greater than or equalto','equalto','less than','less than or equal to' and 'not equal to'.
Input 1,is an analog input,which is compared with the second analog input or the second
parameter(P02).
Input 2,is an analog one,which is compared with the first input if connected.
Output 1,is a digital one,will be TRUE(1) or FALSE(0) depending upon the result
comparison.
Parameters:
P01
Logic code which decides the type of comparison.0-greater than1-greater than or equalto2-less than3-less than or equal to4-equal to5-not equal to
P02 Alternative for second input.ie if second input is not connected this parameter will be used for comparison
P03 Hysterisis constant for comparison
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 74
Annexure C
Modbus TCP
MODBUS® TCP/IP IS an Internet protocol. The fact that TCP/IP is the transport protocol of the
Internet automatically means that MODBUS® TCP/IP can be used over the Internet! Among other
things it was designed to reach this goal, and as part of this goal the MODBUS® protocol
specification has been submitted to the Internet Engineering Task Force (IETF). In practical terms,
this means that a MODBUS® TCP/IP device installed in Europe can be addressed over the
Internet from the USA from anywhere else in the world.
The implications for a vendor of equipment or an end-user are endless. Performing maintenance and repair on remote devices from the office using a PC and
browser reduce support costs and improve customer service.
Logging onto a plant's control system from home allows the maintenance engineer to
maximize his plant's uptime and reduce the number of times that he is called out from
home.
Managing geographically distributed systems becomes easy using commercially available
internet/intranet technologies.
MODBUS® TCP/IP has became an industry de facto standard because of its openness, simplicity,
low cost development, and minimum hardware required to support it.
At this moment there are more than 200 MODBUS® TCP/IP devices available in the market. It is
used to exchange information between devices, monitor and program them. It is also used to
manage distributed I/Os, being the preferred protocol by the manufacturers of this type of devices.
Combining a versatile, scaleable, and ubiquitous physical network (Ethernet) with a universal
networking standard (TCP/IP) and a vendor-neutral data representation (MODBUS® ) gives a
truly open, accessible network for exchange of process data.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 75
The protocol - Modbus TCPModbus/TCP basically embeds a Modbus frame into a TCP frame in a simple manner. This is a
connection-oriented transaction which means every query expects a response.
This query/response technique fits well with the master/slave nature of Modbus, adding to the
deterministic advantage that Switched Ethernet offers industrial users. The use of OPEN Modbus
within the TCP frame provides a totally scaleable solution from ten nodes to ten thousand nodes
without the risk of compromise that other multicast techniques would give.
Performance from a MODBUS TCP/IP system
The performance basically depends on the network and the hardware. If you are running
MODBUS® TCP/IP over the Internet, you won't get better than typical Internet response times.
However, for communicating for debug and maintenance purposes, this may be perfectly adequate
and save you from having to catch a plane or go to site on a Sunday morning!
For a high-performance Intranet with high-speed Ethernet switches to guarantee performance, the
situation is completely different.
In theory MODBUS® TCP/IP carries data at up to 250/(250+70+70) or about 60% efficiency
when transferring registers in bulk, and since 10 Base T Ethernet carries about 1.25 Mbytes/sec
raw, the theoretical throughput is:
1.25M / 2 * 60% = 360000 registers per second and the 100 Base T speed is 10 x greater.
This assumes that you are using devices that can service Ethernet as fast as bandwidth is available.
Practical tests carried out by Schneider Automation using a MOMENTUMTM Ethernet PLC with
Ethernet I/O demonstrated that up to 4000 I/O bases could be scanned per second, each I/O base
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 76
having up to 16 12-bit analog I/O or 32 discrete I/O. Four bases could be updated in one
millisecond. While this is below the theoretical limit calculated above, it must be remembered that
the tested device was running with a lowly 80186 CPU running at 50Mhertz with an effective
computing power of 3 MIPS (compared to the 700 MIPS of a 500MHz Pentium). Also, these
results are nevertheless faster than the proprietary I/O scan methods used to date.
As low-end CPU's get cheaper, Momentum-type devices will chase the theoretical limit, although
they'll never reach it because the limit will be continually pushed further away with 1 Gigabit
Ethernet, 10 Gigabit Ethernet, etc. This is in contrast to other field-buses which are inherently
stuck at one speed.
How can existing MODBUS devices communicate over MODBUS TCP/IP?
MODBUS® TCP/IP is simply MODBUS® protocol with a TCP wrapper. It is therefore extremely
simple for existing MODBUS® devices to communicate over MODBUS® TCP/IP. To do this a
gateway device is required to convert MODBUS protocol to MODBUS TCP/IP.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 77
DNP3
DNP3 (Distributed Network Protocol) is a set of communications protocols used between
components in process automation systems. Its main use is in utilities such as electric and water
companies. Usage in other industries is not common, although technically possible. Specifically, it
was developed to facilitate communications between various types of data acquisition and control
equipment. It plays a crucial role in SCADA systems, where it is used by SCADA Master Stations
(aka Control Centers), Remote Terminal Units (RTUs), and Intelligent Electronic Devices (IEDs).
It is used only for communications between a master station and RTUs or IEDs. ICCP(Inter-
Control Center Communications Protocol) the Inter-Control Centre Protocol, is used for inter-
master station communications.
Doc. Name: Product Requirement Specification for Control System Configurator1Doc. No. DRS CI 162 4301 Doc Issue No: 01 Page No: 78