PRODUCT FAILURES
Product Complaint – Bankstown (NSW)
Issue: Incorrect Product Installed.
• Incorrect product installed – drawings were not provided to
evaluate.
• Galintel T-Bar installed when product not engineered/specified.
• Uneven load not considered.
• Opening impacted by concrete slab on internal leg.
• Control joints impacting load.
• Refer to enginer & remove & replace with engineered solution -
fabricated beam.
Product Complaint – Bankstown (NSW
Product Complaint – Bowral (NSW)
Product Complaint – Bowral (NSW)
Issue: Installation.
• No evidence of props being used.
• Props removed before mortar fully cured, this sometimes occurs
due to other trades pulling props out to gain access & not
reinstating them at all or incorrectly.
Product Complaint – Mansfield (VIC)
Product Complaint – Mansfield (VIC)
Issue: Incorrect Product Installed.
• Incorrect product installed – drawings were not provided to
evaluate.
• Galintel T-Bar installed when product not engineered/specified.
• Uneven load not considered.
• Racked ceiling being supported with uneven load of brickwork.
• Control joints impacting load.
• Refer to enginer & remove & replace with engineered solution -
fabricated beam.
Product Complaint – The Oaks (NSW)
Product Complaint – The Oaks (NSW)
Issue: Incorrect Product Installed
• Galintel MR T-Bar 200x200x9 specified on project
• Incorrect T-Bar installed.
• Required demolishing of brickwork over opening & installing
correct product specified.
Product Complaint – Harrington Park (NSW)
Product Complaint – Harrington Park (NSW)
Issue: Incorrect Installation
• Galintel MR T-Bar 200x200x9 installed with no mortar bond as
required for composite design.
• Inspection highlighted no mortar on base & back of brickwork in
contact with steel as per Galintel load tables.
• No evidence of propping &/or removal of props before curing
exacerbated the problem.
Product Complaint – Albany (WA)
Product Complaint – Albany (WA)
Issue: Coating & Design
• Project used prime painted product only.
• Entire project exposed to aggressive environment including salt
laden air.
• Product should have been supplied in HDG finish minimum or
with approved top coat system – 2 part epoxy applied off site.
Product Complaint – Anna Bay (NSW)
Product Complaint – Anna Bay (NSW)
Issue: Coating & Design
• Project in aggressive environment including south facing with
constant wetting from salt spray.
• Product required to be HDG product with 2 part epoxy coating at
minimum R4 durability.
• Pictures indicate that rendering trapped salt deposites on
surface that when wet rapidly & aggressively attacked the
surface coating causing rust staining & damage.
Product Complaint – Helensburgh (NSW)
Product Complaint – Helensburgh (NSW)
Issue: Rusting
Product Complaint
Issue: Incorrect Labelling
Product Complaint – Labelling
Issue: Labelling
• Incorrect labelling not in accordance with AS/NZS2699.3
AS/NZS 2699.3 Built-in components for masonry construction.
Part 3: Lintels and shelf angles (durability requirements)
• Label identification must have the following three mandatory
details DurabilityManufactures designation
• Durabiltiy Rating
• Australian/New Zealand Standard clearly stated