Tracer™ MP580/581
Programmable Controller
November 2010 BAS-PRC056-EN
Product Data Sheet
The Tracer™MP580/581 programmable controller is a factory-installed unit on Trane™ air handlers such as M-series and T-series Climate Changers and custom AireSystems. In addition, this controller can be field-installed on a variety of HVAC applications such as:
• Air handler control
• Support of Space Comfort Control (SCC) and Discharge Air Control (DAC) LonMark™ profiles
• Control of mechanical equipment in commercial buildings
Features and Benefits
Features Benefits
Product model availability:
• Factory installed.
• NEMA-1 enclosure (with or without touch screen).
• Frame-mounted.
• Touch screen operator displays: door mounted, portable, or stand-alone.
Total of 25 I/O points and expandable to 55 points: Meets most terminal needs with the flexibility to add up to 4 EX2 expansion modules.
Graphical programming:
• Programming ease.
• Built-in PID functionality.
• Pictorial representation and simulation.
• Offline programming.
LonTalk™ interoperability: Can be programmed as a DAC or SCC LonMark profile.
Optional operator display:Monitor, change, identify, troubleshoot, view, and manually override building control functions and schedules.
Smoke control protection: UUKL versions of the MP581 and Tracer BCU controllers are available to create a UUKL rated system.
Specifications
Category Specification/Description
Input power:• With NEMA-1 Enclosure: (Nominal rating) 120/230 Vac, 50 Hz/60 Hz, 1 Phase
• Frame-mounted: (Nominal rating) 24 Vac, 50 Hz/60 Hz, 1 Phase• EX2 expansion Module: (Nominal rating) 24 Vac, 50 Hz/60 Hz, 1 Phase
Microprocessor/memory:
• Motorola MC68332, 20 MHz
• RAM; 512K
• ROM; 2Mb flash
• EEPROM; 256K
Operating temperature:
• With NEMA-1 Enclosure: 32°F to 122°F (0°F to 50°C)
• Frame-mounted: -40°F to 158°F (-40°F to 70°C)
• EX2 Expansion Module: -40°F to 158°F (-40°F to 70°C)
Storage temperature:• With NEMA-1 Enclosure: -58°F to 203°F (-50°C to 95°C) [without display]; -13°F to 149°F (-25°C to 65°C) [with display]
• EX2 expansion Module: -40°F to 185°F (-40°F to 85°C)
Storage/operating humidity range:
• With NEMA-1 Enclosure and Frame-mounted: 10% to 90% non-condensing
• EX2 Expansion Module 10% to 90% non-condensing
Input/output points:
• Tracer MP580/581:
•12 universal inputs; dry contact binary (including pulse accumulation), 0–20 mA, 0–10 Vdc, linear resistance, or thermistor
•6 binary outputs; 3 VA per ordered binary output isolation relay (MP580) and 12 VA at 24 Vac powered relay contacts (MP581)
•6 analog outputs; 0–10 Vdc or 0–20 mA
•1 static pressure input; 5 Vdc, 0–5 in. wc (used with a Trane differential pressure sensor)
• EX2 expansion module:
•6 universal inputs
•4 binary outputs
•4 analog outputs
Mounting weight:• With NEMA-1 Enclosure: 15 lb. (7 kg) and mounted with #10 (5 mm) screws.
• Frame-mounted: 2 lb. (1 kg) and mounted with #8 (4 mm) screws.
Agency Compliance
• U.L. and C.U.L 916 Energy Management
• CE Immunity (directive 89/336/EEC) EN 50090-2-2:1996
• CE Emissions (directive 89/336/EEC) EN 50090-2-2:1996, EN 61000-3-2: 1995, EN 61000-3-3:1995
• FCC Part 15, Subpart B, Class A
• U.L. 864 UUKL Engineered Smoke Control
2 BAS-PRC056-EN Nov 2010
Dimensions
Tracer MP580/581
EX2 Expansion Module
5.625 in.(143 mm)
6.313 in.(160 mm)
6.875 in.(175 mm)
5.375 in.(137 mm) 2 in.
(51 mm)
Portable and Stand-alone Enclosure Dimensions:
10.25 in. (260 mm) x 8.75 in. (222 mm) x 2.25 in. (58 mm)
BAS-PRC056-EN Nov 2010 3
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2010 Trane All rights reserved
BAS-PRC056-EN 05 Nov 2010
NEW
Produced with paper that uses fewer trees and
chemicals, less energy, and environmentally friendly
print practices that reduce waste.
Typical Wiring Diagrams
Powered Output
0–20 mA Sensor
0–10 Vdc OutputLoad > 500 Ω
Temperature Sensor
I/O Bus to Expansion Module
3-Wire, 0–20 mA Sensor or3-Wire, 0–10 Vdc Sensor(With Distance Limitation)
2-Wire, 0–20 mA Sensor
Temperature Sensor
24 Vac Transformer
Powered Output
AC Powered Actuator
I/O Bus to MP580 and Expansion Module
Tracer MP580/581
EX2 Expansion Module