76
Packaged Rooftop Air Conditioners Voyager™ with eFlex™ Technology Cooling & Gas/Electric 12.5 to 17.5 Tons, 60 Hz October 2020 RT-PRC056G-EN Product Catalog

Product Catalog Packaged Rooftop Air Conditioners Voyager™ … · 2021. 2. 3. · Table 2. Voyager™ Light Commercial features - standard and optional Standard Features Options(a)

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • Packaged Rooftop Air ConditionersVoyager™ with eFlex™ TechnologyCooling & Gas/Electric12.5 to 17.5 Tons, 60 Hz

    October 2020 RT-PRC056G-EN

    Product Catalog

  • ©2020 Trane RT-PRC056G-EN

    Introduction

    Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionize this design concept.

    The ReliaTel™control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.

    Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.

    Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and provide a payback based on life cycle costs. Trane delivers with Voyager with eFlex™ technology.

    Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner, you can be certain Voyager products are built to meet your needs.

    CopyrightThis document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

    TrademarksTrane and the Trane logo, CompleteCoat, Frostat, Integrated Comfort Systems, Voyager, ReliaTel, Tracer, Tracker, eFlex are trademarks of Trane in the United States and other countries. BACnet is a registered trademark. All trademarks referenced in this document are the trademarks of their respective owners.

    Revision SummaryAdded AHRI CFRN logo in the Back Cover.

  • Table of Contents

    RT-PRC056G-EN 3

    Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Standard Features and Available Options . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Outstanding Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Single Zone Variable Air Volume (Single Zone VAV) Control . . . . . . . . . 23Variable Air Volume Applications (Traditional VAV) . . . . . . . . . . . . . . . . 27

    Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Air Delivery Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Model Number Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Zone Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

  • Features and BenefitsNote: Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified

    within scope of AHRI Standard 340/360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces (gas heating units).

    Standard Features and Available Options

    Table 1. Voyager™ Light Commercial control options — standard and optional

    Standard Features

    Options(a)

    Factory Installed

    Factory or Field

    InstalledField

    Installed

    BACnet® Communications Interface (BCI) X

    Discharge Line Thermostat X

    Humidity Sensor X

    LonTalk® Communications Interface (LCI) X

    ReliaTel™ Microprocessor Controls X

    ReliaTel™ Options Module X

    Trane® Air-Fi™ Wireless Communication Interface X

    Trane® Communications Interface (TCI) X

    Wireless Zone Sensor X

    Zone Sensors and Remote Zone Sensors X

    Table 2. Voyager™ Light Commercial features - standard and optional

    Standard Features

    Options(a)

    Factory Installed

    Factory or Field

    InstalledField

    Installed

    1-year Limited Parts Warranty X

    5-year Limited Compressor Warranty X

    5-year Limited Heat Exchanger Warranty X

    2” MERV 8 Filters or 2” MERV 13 Filters with Filter Removal Tool X

    2” throwaway filters X

    Anti-Short Cycle Timer X

    Barometric Relief X

    Belt Drive Motors X

    Clogged Filter/Fan Failure Switch X

    CO2 Sensor X

    CO2 Sensor Wiring (Wiring Only) X

    Colored and Numbered Wiring X

    Complete Coat™ Microchannel Condenser Coil X

    Condensate Overflow Switch X

    Crankcase Heaters X

    Dedicated Airflow X

    Digital Display Zone Sensor X

    Discharge Air Temperature Sensor X

    Easy Access Low Voltage Terminal Board (LTB) X

    Economizer - Standard, Downflow X

    (a) Refer to model number description for option availability

    4 RT-PRC056G-EN

  • Features and Benefits

    Economizer - Standard, Horizontal X

    eFlex™ Variable Speed Technology X

    Electric Heaters X

    Enhanced Dehumidification X

    Fault Detection & Diagnostics (FDD) X

    Foil-Faced and Edge Captured Insulation X

    Frostat™ X

    High Altitude Kit X

    High and Low Static Drive Kits X

    High Efficiency Drum and Tube Heat Exchanger X

    High Efficiency Gas Heat with Hot Surface Ignition X

    High Pressure Cutout X

    High Short Circuit Current Rated (SCCR) Electrical Subsystem X

    Hinged Access Doors X

    Human Interface - 5 inch Color Touchscreen X

    IAQ Sloped Condensate Drain Pan X

    Indoor Fan Motor Shaft Grounding Ring X

    Liquid Line Refrigerant Drier X

    Low Ambient Cooling to 0°F X

    Low Leak Economizer - Downflow X

    Low Leak Economizer - Downflow and Horizontal X

    LP Conversion Kit X

    Microchannel Type Condenser Coils X

    Modulating Gas Heat Furnace with a 2.5:1 Turndown Ratio X

    Multiple Zone Variable Air Volume (MZVAV) X

    Operating Charge of R-410A X

    Oversized Motors X

    Phase Monitor X

    Powered Exhaust X

    Powered or Unpowered Convenience Outlet X

    Provisions for Through-the-Base Gas Connections X

    Quick Access Panels X

    Quick Adjust Idler Arm Pulley X

    Reference or Comparative Enthalpy X

    Remote Potentiometer X

    Roof Curb (Downflow Only) X

    Single Point Power X

    Single Side Service X

    Single Zone Variable Air Volume (SZ VAV) X

    Stainless Steel Drain Pan X

    Stainless Steel Heat Exchanger with 10 Year Warranty X

    Standardized Components X

    Table 2. Voyager™ Light Commercial features - standard and optional

    Standard Features

    Options(a)

    Factory Installed

    Factory or Field

    InstalledField

    Installed

    RT-PRC056G-EN 5

  • Features and Benefits

    6 RT-PRC056G-EN

    Note: Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.

    Outstanding Standard FeaturesAnti-Short Cycle TimerProvides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.

    Barometric ReliefDesigned to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.

    Colored and Numbered WiringSave time and money tracing wires and diagnosing the unit.

    Supply and/or Return Air Smoke Detector X

    Thermal Expansion Valve X

    Through the Base Electrical Access X

    Through the Base Electrical with Circuit Breaker X

    Through the Base Electrical with Disconnect Switch X

    Through the Base Gas Piping X

    Tool-less Hail Guards X

    U-shaped Airflow Pattern X

    Variable Frequency Drive X

    Ventilation Override Accessory X

    (a) Refer to model number description for option availability.

    Table 2. Voyager™ Light Commercial features - standard and optional

    Standard Features

    Options(a)

    Factory Installed

    Factory or Field

    InstalledField

    Installed

    CompressorsTrane eFlex™ variable speed scroll compressors are matched with a specially designed variable frequency drive that allows a modulating ratio of up to 4:1. Our eFlex™ compressors are paired with fixed speed compressors such that the units are capable of continuous capacity modulation from 10% to 100%. By design, unit combined airflow and compressor capacities overlap to minimize the frequent cycling between stages typical of competing designs. This allows for unmatched control of leaving air temperatures to meet space loads.

    The eFlex™ compressors also include brushless permanent magnet motors designed to operate at higher efficiency along with reducing the compressor motor speed and cycling results in significant part load energy savings. This makes units with eFlex™ compressors the most efficient products in their class at part load.

  • Features and Benefits

    Controls—ReliaTelReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to “Other Benefits,” p. 16.

    Conversionless UnitsThe dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.

    Crankcase HeatersThese band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

    Discharge Air Temperature SensorProvides true discharge air sensing in heating models.

    Discharge Line ThermostatA bi-metal element discharge line thermostats installed as a standard feature on the discharge line of each system. This standard feature provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.

    Enhanced Dehumidification with eFlex™Every Ultra High Efficiency unit is equipped with Enhanced Dehumidification, which operates when connected to a humidity sensor. With Enhanced Dehumidification, the ReliaTel control reduces the minimum indoor airflow and modulates the eFlex compressor operation to allow for additional moisture removal of the return air. When dehumidification is required without cooling, the ReliaTel control brings the compressors to an appropriate capacity to remove moisture without overcooling the space providing efficient humidity control.

    Easy Access Low Voltage Terminal Board Foil Faced Insulation

    Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.

    All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.

    RT-PRC056G-EN 7

  • 8 RT-PRC056G-EN

    Features and Benefits

    Frostat™This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and/or high latent load applications.

    Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve is used in the standard furnaces. This is one of our unique safety features. Modulating heaters use a pressure switch to ensure that the blower motor is operating before the gas valve is allowed to open.

    The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. Modulating furnaces contain a metal fiber material to ensure proper flame distribution at low fire. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NOx emission requirements.

    Low Ambient CoolingAll Voyager microprocessor units have cooling capabilities down to 0°F as standard.

    Heat Exchanger—Drum and TubeThe cabinet features a drum and tube heat exchanger (pictured right) that is manufactured using aluminized steel with stainless steel components for maximum durability.

    The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements.

    Low Voltage ConnectionsThe wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.

    Hot Surface Ignitor

    Negative Pressure Gas Valve

    Forced Combustion Blower

  • Features and Benefits

    MotorsAll indoor fan motors are belt drive as standard.

    Pressure CutoutsLow and high pressure cutouts are standard on all Voyager models.

    Phase MonitorVoyager features a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

    Single Point PowerA single electrical connection powers the unit.

    Single Side ServiceSingle side service is standard on all units.

    Single Zone VAV - One Zone Variable Air Volume ModeNote: Single Zone VAV is designed to be used with a zone sensor. If a unit is configured for Single

    Zone VAV operation but is connected to a thermostat, the control will revert to multi-speed

    Microchannel CoilsMicrochannel coils are all-aluminum coils with fully-brazed construction. This design reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer. Microchannel all-aluminum construction provides several additional benefits:

    • Light weight (simplifies coil handling)

    • Easy to recycle

    • Minimize galvanic corrosion

    Quick-Access PanelsRemove three or more screws for access to the standardized internal components and wiring.

    Quick-Adjust Slider PlateWith the Quick-Adjust Slider Plate (pictured right), the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.

    ReliaTel Options Module (RTOM)The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, dehumidification setpoint, supply air tempering, frostat™ and smoke detector.

    Slit Fins and Braze Contactfor Improved Heat Transfer and Strength

    Air Inlet

    Air OutletMicrochannelsfor Refrigerant

    RT-PRC056G-EN 9

  • Features and Benefits

    (2-Speed) indoor fan control and staged compressor control. This drastically reduces the energy savings available with this design.

    Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to "yesterday's" constant volume (CV) systems, by reducing operating costs while improving occupant comfort. SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20%.

    Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application.

    SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider - Trane.

    Sloped Drain PansEvery Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.

    Standardized ComponentsComponents are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager. Due to standardized components throughout the Voyager line, contractors/owners can stock fewer parts.

    Thermal Expansion ValveThermal expansion valves are standard on ultra high efficiency units to allow superior control over full modulating operating range.

    U-Shaped Airflow PatternThe U-shaped airflow allows for improved static capabilities.

    Variable Frequency Drives Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation, as well as modulating gas heat. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. Bypass control will simply provide full nominal airflow in the event of drive failure. Modulating gas heat models with VFDs allow tighter space temperature control with less temperature swing.

    10 RT-PRC056G-EN

  • Features and Benefits

    Variety of Options1

    Factory Installed Options

    Air-Fi™ Wireless CommunicationTrane® Air-Fi™ wireless communication is a reliable, flexible solution that frees you from the hassles associated with wired components for your building controls system. With Air-Fi wireless, you get easy problem solving, efficient performance, and cost savings over the life of the equipment.

    CO2 Sensor WiringThis is the unit wiring for field installed C02 sensors. Factory-installed C02 sensor wiring saves time and ensures proper unit connections for the field installed C02 sensor kits.

    Complete Coat™ Condenser CoilThe cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating is available for microchannel coils only.

    Circuit Breaker (Requires Through-the-Base Electrical)This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.

    Condensate Overflow SwitchA condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the units.

    Fault Detection & Diagnostics (FDD)This offering meets the mandatory requirement of CA Title 24 of fully configurable diagnostics allowing fault history and reading fault codes at the unit.This option provides detection of the following faults: Air temperature sensor failure/fault and notification of acceptable economizer mode.The FDD system shall be certified by the Energy Commission as meeting the requirements.

    1 Refer to “Model Number Description,” p. 33 for option availability.

    Disconnect Switch (Requires Through-the-Base Electrical)

    Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. Available on all models.Codes require a method of assured unit shutdown for servicing. Field-installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.

    RT-PRC056G-EN 11

  • Features and Benefits

    High Efficiency FiltrationVoyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.

    High Short Circuit Current Rating (SCCR)Voyager rooftop units now have an optional high short circuit current rated electrical subsystem for units with an MOP above 60A. This option is a perfect fit for applications that need protection against high potential fault currents. This option also includes individual over current protection for each compressor and the indoor fan, as well as a dedicated over current protection to the condenser fan motor(s). When the high SCCR is ordered, the control box will have components separated into two sections - high and low voltage components.

    Modulating Gas Heat with a 2.5:1 Turndown RatioUpon receiving a call for heat, modulating gas heat units with a 2.5:1 turndown ratio light their burner at full fire (100%). After the burner is lit, the unit controls will monitor the discharge air temperature and modulate the input rate down to match the load.

    Note: Modulating gas heat units are equipped with a stainless steel heat exchanger as standard.

    Multiple-Zone Variable Air Volume ControlA multiple-zone VAV (MZVAV) system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a VAV terminal unit that varies the quantity of air delivered to maintain the desired temperature in that zone. The rooftop unit controller varies the speed of the indoor fan to maintain the static pressure in the supply ductwork

    Hinged Access DoorsThese doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.

    Human InterfaceThe Trane 5 Inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features such as:

    • Data trending capabilities by means of time series graphs

    • Historical alarm messages

    • Real-time sensor measurements

    • On board system setpoints

    • USB port that enables the downloading of component runtime information as well as trended historical sensor data

    • Customized reports

    Note: For more information, refer to RT-SVX49*-EN.

    12 RT-PRC056G-EN

  • Features and Benefits

    at a setpoint, ensuring that all zones receive the necessary quantity of air. In addition, cooling capacity is cycled to maintain the supply air temperature at the desired setpoint.

    For decades, Trane has been an industry leader in rooftop VAV systems. Now, multiple-zone VAV control is available in Trane’s light commercial rooftop platform (3-25 tons).

    Powered or Unpowered Convenience Outlet This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered. This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered. This option is available on all models.

    Stainless Steel Drain PanFor excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8 or 13), and demand control ventilation (CO2).

    Stainless Steel Heat ExchangerThe optional stainless steel heat exchanger is constructed of 439 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units and comes standard with a modulating gas heat option. With this option, a 10-year stainless steel heat exchanger warranty is standard.

    Through-the-Base Electrical Utility AccessAn electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

    Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

    Factory or Field Installed Options

    BACnet™ Communications InterfaceThe BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.

    Supply and Return Air Smoke DetectorWith this option (pictured right) installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.

    Through-the-Base Gas Piping (Gas/Electric Only)This option (pictured right) shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. This assembly will require minor field labor to install.

    RT-PRC056G-EN 13

  • Features and Benefits

    Clogged Filter/Fan Failure SwitchA dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.

    Economizer - Standard, DownflowEconomizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.

    Note: Factory-installed economizers require some field set-up.

    Economizer - Low Leak, DownflowThis accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements. Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).

    Electric HeatersElectric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.

    Indoor Fan Motor Shaft Grounding RingShaft grounding rings are available on VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Rings shall be maintenance free circumferential rings of conductive micro fibers that discharge voltages to ground.

    LonTalk® Communications InterfaceThe LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.

    Oversized MotorsFactory or field installed oversized motors are available for high static applications.

    Reference or Comparative EnthalpyMeasures and communicates humidity while maximizing comfort control.

    Tool-less Hail GuardsTool-less, hail protection quality coil guards (pictured right) shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.

    14 RT-PRC056G-EN

  • Features and Benefits

    Field Installed Options

    CO2 Sensor - Demand Control Ventilation (DCV)Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (Carbon Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed accessory. Two field installed kits are offered; C02 sensor and wiring or C02 sensor only. The C02 sensor only kit should be ordered with factory installed C02 sensor wiring. Factory installed C02 sensor wiring saves set-up time and ensures proper unit connections for the C02 sensor.

    Digital Display Zone SensorThe Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.

    Economizer - Standard, HorizontalEconomizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings.

    Economizer - Low Leak, Downflow & HorizontalThis accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.

    High Altitude KitRequirement for units applies above 2000 feet. Derate gas orifices by 10%.

    LP Conversion KitProvided for field conversion of gas/electric units from natural gas to propane.

    Powered ExhaustThis option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.

    Remote PotentiometerWhen properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.

    Roof CurbsAvailable for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.

    Static Drive AccessoriesAvailable on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

    Trane Communication Interface (TCI)Available field installed. This module - when applied with the ReliaTel™- easily interfaces with Trane’s Integrated Comfort™ System.

    RT-PRC056G-EN 15

  • Features and Benefits

    Ventilation Override AccessoryWith the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.

    Wireless Zone SensorLCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.

    Zone SensorsAvailable in programmable, automatic and manual styles.

    Note: Zone sensors are required for units configured for Single Zone VAV indoor fan and eFlex compressor system control to enable Single Zone VAV and eFlex modulation functionality.

    Other BenefitsCabinet IntegrityFor added water integrity, Voyager has a raised 1-1/8” lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.

    Easy to Install, Service and MaintainBecause today’s owners are very cost-conscious when it comes to service and maintenance, Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.

    Outstanding Airflow DistributionAirflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.

    Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.

    ReliaTel Makes Installing and Servicing Easy

    ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays.

    ReliaTel™ Controls BenefitsReliaTel controls provide unit control for heating, cooling and ventilating by utilizing input from sensors that measure outdoor and indoor temperature.

    Quality and Reliability are enhanced through ReliaTel control and logic:

    – Prevents the unit from short cycling, considerably improving compressor life.

    – Ensures the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.

    16 RT-PRC056G-EN

  • Features and Benefits

    ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.

    ReliaTel Makes Testing Easy

    ReliaTel requires no special tools to run Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.

    The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.

    As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.

    ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.

    Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).

    Other ReliaTel Benefits

    The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.

    Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.

    The same ReliaTel Board fits all Packaged Gas/Electric, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.

    Rigorous TestingAll of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Voyager units incorporate the Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.

    Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. For the microchannel coils, the supplier will perform the leak check at 450 psig. The completely assembled refrigerant system is leak tested at a minimum of 225 psig with a refrigerant and nitrogen mixture.

    All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.

    Unmatched SupportTrane Sales Representatives are a Support Group that can assist you with:

    • Product • Service • Special Applications • Computer Programs and much more• Application • Training • Specifications

    RT-PRC056G-EN 17

  • Application ConsiderationsApplication of this product should be within the cataloged airflow and cooling considerations.

    Air-Fi® WirelessPlease refer to Air-Fi Network Design Installation, Operation, and Maintenance manual BAS-SVX55*-EN for additional details on applications with factory installed wireless.

    Barometric ReliefThis product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.

    Notes:

    • The effectiveness of barometric relief damper during economizing operation is system related.

    • Pressure drop of the return air system should be considered to control building pressurization.

    Clearance RequirementsThe recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with local Trane sales personnel.

    Complete Coat™ Microchannel Condenser CoilThe cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating shall be available on microchannel condenser coils.

    Condensate TrapThe evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the cooling cycle.

    Heating OperationThe heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum mixed air temperature of 40°F.

    Optional Stainless Steel Heat ExchangerThe optional stainless steel heat exchanger is manufactured with 439 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20°F. The stainless steel heat exchanger option is an excellent option that compliments the dehumidification package and is used in conjunction with the modulating heat option. Whenever high outside air or outside applications exist, these options should be utilized.

    Low Ambient CoolingThe Voyager line features, with ReliaTel™ microprocessor controls, low ambient cooling down to 0°F. A Frostat™ needs to be included in the selection when Low Ambient Cooling is required. Contact your local Trane Representative for more assistance with low ambient cooling applications.

    Unit PitchThese units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.

    18 RT-PRC056G-EN

  • Application Considerations

    Low AirflowUnit applications designed for airflow below 320cfm/ton are not available on units with eFlex™ and Single Zone VAV. Voyager units will operate below 320 cfm/ton during normal operation. Units should not be set below 320 cfm/ton.

    Sequence of Operation

    ReliaTel Controls• The master module is the ReliaTel Refrigeration Module (RTRM).

    • The RTRM provides compressor anti-short cycle timing functions through minimum "Off" and "On" timing to increase reliability, performance and to maximize unit efficiency.

    • Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functioning. It checks the configuration parameters against the components connected to the system.

    • The LED located on the RTRM module is turned "On" within one second after power-up if all internal operations are okay.

    • The RTRM in conjunction with the Variable Speed Module (VSM) will provide capability to control of a modulating eFlex™ compressor, and two multispeed outdoor motors (ODM).

    • The ReliaTel Options Module (RTOM) is utilized in conjunction with the RTRM for control of a variable speed indoor motor (IDM) and optional accessories.

    • All units employ a Phase Monitor to ensure proper power supply connection of phases for compressor operation. If the monitor senses incorrect phase connection (phase reversal), a loss of phase, or large voltage imbalance between phases, all unit operation will be prevented until the condition is corrected. The Phase Monitor has green (Ok) and red (Phase Fault) status LEDs on the face of the monitor. All units are functional tested to ensure correct factory wiring. A red status LED is an indication of a serious problem that can only be resolved by isolating and repairing the Supply Power fault.

    ReliaTel Control Cooling without an EconomizerWhen the system switch is set to the "Cool" position and the zone temperature rises above the cooling setpoint controlband, the RTRM energizes the modulating eFlex compressor starting with the minimum compressor motor speed and runs through a start-up sequence for that compressor, provided the low pressure control (LPC4), high pressure control (HPC3), and the discharge line thermostat (DLT3) are closed. When the eFlex compressor and the outdoor fan motor are energized, they adjust motor speeds in order to maintain the zone temperature (Single Zone VAV) to within +/-0.5°F or Supply Air Temperature (Multi Zone VAV) to within ±1°F of the sensor setpoint at the sensed location. If the modulating compressor at its maximum capacity cannot satisfy the cooling requirement, the RTRM energizes the first fixed speed compressor, provided the low pressure control (LPC1), the high pressure control (HPC1), and the discharge line thermostat (DLT1) are closed, while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system capacity. When the fixed speed compressor is energized, the ReliaTel control starts to maintain the zone temperature (Single Zone VAV) to within +/-0.5°F or Supply Air Temperature (Multi Zone VAV) to within ±1°F of the sensor setpoint at the sensed location by modulating the eFlex compressor speed and both ODM. If the first two compressors cannot satisfy the load, the second fixed speed compressor is energized in addition to the first fixed speed compressor, provided the low pressure control (LPC1), the high pressure control (HPC2), and the discharge line thermostat (DLT2) are closed. Simultaneously, the modulating compressor speed is reduced for a smooth transition to the higher system capacity. When the third compressor is energized, the ReliaTel control starts to maintain the zone temperature (Single Zone VAV) to within +/-0.5°F or Supply Air Temperature (Multi Zone VAV) to within +/-1°F of the sensor setpoint at the sensed location by modulating the eFlex compressor motor speed and both ODM.

    RT-PRC056G-EN 19

  • Application Considerations

    ReliaTel Control Evaporator Fan OperationWith the indoor fan in "Auto" mode, the RTRM energizes the indoor fan motor for approximately 1 second after energizing the modulating compressor in the cooling mode. In the heating mode, the RTRM energizes the indoor fan motor approximately 45 seconds after gas ignition (gas heat unit) or 1 second before energizing electric heat (electric heat unit). With the indoor fan in "On" mode, the RTRM keeps the indoor fan energized for continuous fan motor operation. When the unit is equipped with the optional clogged filter switch, wired to the ReliaTel Options Module (RTOM), the RTRM produces an analog signal output if the clogged filter switch closes for two minutes after a request for fan operation. When the system is connected to a remote panel, the "SERVICE" LED will be turned on when this failure occurs.

    Drain Pan Condensate Overflow Switch (Optional)This input incorporates the Condensate Overflow Switch (COF) mounted on the drain pan and the ReliaTel Options Module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit function until the overflow condition has cleared. The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes the unit to shutdown more than 2 times in a 3 day period, the unit will be locked-out of operation. A manual reset of the diagnostic system through the Zone Sensor or Building Automation System will be required. Cycling unit power will also clear the fault.

    Low Ambient OperationDuring low ambient operation, outside air temperature below 40°F, the RTRM will cycle the compressors and outdoor fan motors "Off" for approximately 3 minutes after every 10 minutes of accumulated compressor run time. The indoor fan motor will continue to operate during this evaporator defrost cycle and the compressors and outdoor fans will return to normal operation once the defrost cycle has terminated and the compressor "Off" time delay has been satisfied.

    ReliaTel Control Cooling with an EconomizerThe economizer is utilized to control the zone temperature providing the outside air conditions are suitable. Outside air is drawn into the unit through modulating dampers. When cooling is required and economizing is possible, the RTRM sends the cooling request to the unit economizer actuator to open the economizer damper.

    The RTRM tries to cool the zone utilizing the economizer to slightly below the zone temperature setpoint. If the mixed air sensor (MAS) senses that the mixed air temperature is below 53°F, the damper modulates toward the closed position.

    If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM energizes the modulating eFlex compressor. If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM instructs the compressor inverter drive to increase the compressor speed to allow more compressor capacity.

    If the eFlex compressor is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM energizes the first fixed speed compressor, while simultaneously instructing the compressor inverter drive to decrease the eFlex compressor capacity to allow a smooth system capacity transition. If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM instructs the compressor inverter drive to increase the eFlex compressor speed to allow more compressor capacity.

    If the eFlex compressor is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM energizes the second fixed speed compressor, while simultaneously decreasing the eFlex compressor speed to allow a smooth transition of system cooling capacity.

    20 RT-PRC056G-EN

  • Application Considerations

    All compressor capacity transitions are accompanied by corresponding IDM and ODM speed adjustments to allow optimal unit cooling performance. The ECA continues to modulate the economizer damper open/closed to keep the mixed air temperature that is calculated by the RTRM.

    If economizing is not possible, the ECA drives the damper to the minimum position setpoint when the indoor fan relay is energized and allows mechanical cooling operation. When the unit is equipped with the optional fan failure switch, wired to the RTOM, the RTRM will stop all cooling functions and produce an analog output if the fan failure switch does not open within 40 seconds after a request for fan operation. When the system is connected to a remote panel, the "SERVICE" LED will flash when this failure occurs.

    Economizer Set-UpAdjusting the minimum position potentiometer located on the unit economizer actuator (ECA) sets the required amount of ventilation air.

    Two of the three methods for determining the suitability of the outside air can be selected utilizing the enthalpy potentiometer on the ECA, as described below:

    1. Ambient Temperature-Controlling the economizing cycle by sensing the outside air dry bulb temperature. Table 3 lists the selectable dry bulb values by potentiometer setting.

    2. Reference Enthalpy-Controlling the economizer cycle by sensing the outdoor air humidity. Table 3 lists the selectable enthalpy values by potentiometer setting. If the outside air enthalpy value is less than the selected value, the economizer is allowed to operate.

    3. Comparative Enthalpy-By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the unit control processor (RTRM) will be able to establish which conditions are best suited for maintaining the zone temperature, i.e. indoor conditions or outdoor conditions.

    The potentiometer located on the ECA is non-functional when both the temperature and humidity sensors are installed.

    ReliaTel Control Heating Operation for Cooling Only UnitsWhen the system switch is set to the "Heat" position and the zone temperature falls below the heating setpoint controlband, the RTRM energizes the first stage of electric heat. If the first stage of electric heat cannot satisfy the heating requirement, the RTRM energizes the second stage electric heat if applicable. The RTRM cycles both the first and second stages of heat "On" and "Off" as required to maintain the zone temperature setpoint.

    ReliaTel Control Heating Operation for Gas UnitsWhen the system switch is set to the "Heat" position and the zone temperature falls below the heating setpoint controlband, a heat cycle is initiated when the RTRM communicates ignition information to the Ignition module.

    Table 3. Potentiometer settings

    Potentiometer Setting Enthalpy Dry Bulb

    A 27 Btu/lb (63 kJ/kg) 73°F(22.8°C)

    B 25 Btu/lb (58 kJ/kg) 70°F (21.1°C)

    C(a)

    (a) Factory setting

    23 Btu/lb (53 kJ/kg) 67°F (19.4°C)

    D 22 Btu/lb (51 kJ/kg) 63°F (17.2°C)

    E 19 Btu/lb (44 kJ/kg) 55°F (12.8°C)

    RT-PRC056G-EN 21

  • Application Considerations

    Modulating Gas Heat 2.5:1 TurndownIn a modulating heat unit, when a call for heat is received, the burner will light at full fire (100%). After the burner is lit, the unit controls will monitor the discharge air temperature and modulate the input rate down to match the load.

    Ignition Control ModuleTwo-Stage (IGN) runs self-check (including verification that the gas valve is de-energized). IGN checks the high-limit switches (TC01 and TC02) for normally closed contacts. With power supplied to the ignition module, the hot surface ignition probe is preheated. The gas valve is energized for a few seconds for trial for ignition, to ignite the burner. Once the burner is ignited, the hot surface ignition probe is de-energized by the ignition module and functions as the flame sensing device. If the burner fails to ignite, the ignition module will attempt two retries before locking out. The green LED will indicate a lockout by two fast flashes. An ignition lockout can be reset by:

    1. Opening for 3 seconds and closing the main power disconnect switch.

    2. By switching the "Mode" switch on the zone sensor to "OFF" and then to the desired position.

    3. Allowing the ignition control module to reset automatically after one hour. Refer to Table 4 for the LED diagnostic definitions.

    When the fan selection switch is set to the "Auto" position, the RTRM energizes the indoor fan relay coil approximately 30 seconds after initiating the heating cycle to start the indoor fan motor. The automatic reset high limit, located in the bottom right corner of the burner compartment, protects against abnormally high leaving air temperatures. The automatic reset fan fail limit, located in the upper middle section of the indoor fan board, protects against abnormally high heat buildup which could occur because of extended cycling of the high limit or if the indoor fan motor fails to operate. Should TCO2 open, the RTRM will energize the indoor fan relay in an attempt to start the fan motor. The RTRM signals that a heat failure has occurred by flashing the "Heat" LED on the zone sensor. There is a green LED located in the Ignition Control Module. Table 4 lists the diagnostics and the status of the LED during the various operating states.

    Ignition Control Module Diagnostics

    At any time the control is powered, a green LED indicator light shall be lit using the following signal:

    Table 4. Ignition module diagnostics

    Steady OFF: No Power/Failure/Internal Failure

    Steady ON: Normal

    Slow Flash Rate: Normal, call for heat (¾ second on, ¼ second off).

    Fast Flash Rate: Used for error indication only (¼ second off, ¾ second on).

    Error Code Fast Flash Rate:

    1 Flash Communication Issue between Refrigeration Module and 3SH control.

    2 Flashes System Lockout: Failed to detect or sustain flame.

    3 Flashes Not implemented.

    4 Flashes High Limit switch protection device open.

    5 Flashes Flame sensed and gas valve not energized or flame sensed and no call for heat.

    6 Flashes Not implemented.

    Note: The pause between groups of fast flashes is approximately two seconds. Additionally, the LED indicator light shall flash for one second at power-up.

    22 RT-PRC056G-EN

  • Application Considerations

    Enhanced DehumidificationEnhanced Dehumidification will be available on all units equipped with a Space Humidity sensor. Once the Space Humidity value exceeds the Dehumidification Setpoint and dehumidification is enabled the unit will transition to the Enhanced Dehumidification mode. If the unit is actively cooling, the ReliaTel control will latch the current compressor operation and reduce the current indoor airflow. If the unit is not actively cooling when the Enhanced Dehumidification mode is activated, the unit will energize a single fixed speed compressor and the modulating eFlex compressor will ramp to a fixed speed while engaging the IDM and both ODM at the appropriate airflow for that condition. If during active enhanced dehumidification the Space Humidity falls below the Dehumidification Setpoint – 2%, Dehumidification will be terminated and the unit will transition back to normal Cooling or Heating control.

    Single Zone Variable Air Volume (Single Zone VAV) ControlFor normal Cooling operation, available cooling capacity will be modulated in order to meet the calculated discharge air setpoint between the user selected upper and lower limits. If the current active cooling capacity is controlling the discharge air within the deadband no additional Cooling capacity change will be requested. As the Discharge Air Temperature rises above the deadband the control will request additional capacity as required (additional compressor operation or economizer). As the Discharge Air Temperature falls below the deadband the algorithm will request a reduction in active capacity.

    Cooling OperationIf the control determines that there is a need for compressor operation in order to meet the discharge air requirements, once supply fan proving has been made, the unit will begin to modulate compressors. As the zone cooling demand continues to increase, if additional capacity is required, the supply fan output will be modulated above minimum speed in order to meet the zone requirements.

    Note: The supply fan speed will remain at the activated compressors’ associated minimum value until the control requires additional capacity to meet the zone demand.

    As the cooling load in the zone decreases the control will reduce the speed of the fan down to minimum per compressor operation and control the compressor outputs accordingly. As the compressors begin to de-energize, the Supply Fan speed will fall back to the Cooling Capacity's associated minimum fan speed but not below. As the load in the zone continues to drop, cooling capacity will be reduced in order to maintain the calculated discharge air setpoint.

    Economizer CoolingDuring normal Economizer Cooling, the fan speed will operate at its minimum. However, if the economizer is able to meet the demand alone, due to desirable ambient conditions, the supply fan speed will be allowed to increase above the minimum prior to utilizing mechanical cooling. Note that Economizer Enable/Disable decisions will be made based on the previous sections; however, the economizer control point will now be variable based on the zone cooling demand.

    Demand Controlled VentilationUnits configured for SZVAV and Demand Controlled Ventilation (CO2 sensor value available) require a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive; DCV and OA CFM Compensation. Units configured with DCV will invoke the new Demand Controlled Ventilation scheme which allows variable Bldg. Design and DCV Minimum Positions and OA Damper Position Target setpoints based on the supply fan speed and space CO2 requirements.

    Economizer Damper Position Set-Up with DCV This new scheme will require the setting of 5 OA Damper position setpoints; 3 more than on non-SZ VAV. These new setpoints are located on the RTVM module:

    RT-PRC056G-EN 23

  • Application Considerations

    1. Design Min Position @ Minimum Fan Speed Command (RTVM R130)

    2. Design Min Position @ Middle Fan Speed Command (RTVM R136)

    3. Design Min Position @ Full Fan Speed Command (RTEM Design Min Position)

    4. DCV Min Position @ Minimum Fan Speed Command (RTVM R41)

    5. DCV Min position @ Full Fan Speed Command (RTEM DCV Min Position)

    As the supply fan speed command varies between minimum and maximum, the Building Design and DCV Minimum Position Targets will be calculated between the user selected setpoints based on the instantaneous supply fan speed. The Bldg. Design and DCV Minimum Position Targets will be used to calculate the Active OA Damper Minimum Position Target, as on traditional units, based on the Space CO2 relative to the active Design and DCV CO2 setpoints.

    By default, the Design Minimum Position schedule will be a linear line through all user selectable Design Minimum Position setpoints. The user will have the ability to set the Design Minimum Position at Middle fan speed command to a point that would be lower than the calculated linear line between the Design Minimum Position setpoints at 0% and 100% fan speed command in order to compensate for the non-linear outside airflow through the fan and damper modulation range. However, if the Design Minimum Position at Middle fan speed command is set to a point that would be higher than the calculated linear line between the Design Minimum Position setpoints at Minimum and Full fan speed command, the minimum position will be limited to the point that would make the Design Minimum Position schedule linear.

    Provisions have been made in Service Test Mode to allow for proper damper minimum position setup:

    1. To set the Design and DCV Minimum Position setpoints at Minimum Fan Speed, set the unit to operate at Step 1 (Fan ON) or Step 2 (Economizer Open) and make the proper adjustments.

    2. To set the Design Minimum Position setpoint at Middle Fan Speed, set the unit to operate at Step 3 (Cool 1) and make the proper adjustment.

    3. To set the Design and DCV Minimum Position setpoints at Full Fan Speed, set the unit to operate at Step 4 (Cool 2) and make the proper adjustments.

    Economizer Damper Position Set-Up without DCVFor units not configured with DCV (no CO2 sensor value available), additional minimum position setpoints to increase outdoor airflow accuracy will be supported. The operation will be similar to OA CFM Compensation on Traditional VAV units with the addition of a Design Minimum Position setpoint at Middle Fan Speed Command. The following setpoint potentiometers will be used on the RTEM:

    1. Design Min at Minimum Fan Speed Command (RTEM DCV Min)

    2. Design Min at Middle Fan Speed Command (RTEM DCV Setpoint LL)

    3. Design Min at Full Fan Speed Command (RTEM Design Min)

    The controller will calculate the active OA Damper Minimum position between the user-selected setpoints based on the supply fan speed command. By Default, the Design Minimum Position schedule will be a linear line through all user selectable Design Minimum Position setpoints. As with Demand Controlled Ventilation, if the Design Minimum Position at Middle fan speed command is set to a point that would be higher than the calculated linear line between the Design Minimum Position setpoints at Minimum and Maximum fan speed command, the minimum position will be limited to the point that would make the Design Minimum Position schedule linear.

    Provisions have been made in Service Test Mode to allow for proper damper minimum position setup:

    1. To set the Design Minimum Position setpoint at Minimum Fan Speed, set the unit to operate at Step 1 (Fan ON) or Step 2 (Economizer Open) and make the proper adjustment.

    24 RT-PRC056G-EN

  • Application Considerations

    2. To set the Design Minimum Position setpoint at Middle Fan Speed, set the unit to operate at Step 3 (Cool 1) and make the proper adjustment.

    3. To set the Design Minimum Position setpoint at Full Fan Speed, set the unit to operate at Step 4 (Cool 2) and make the proper adjustment.

    Heating OperationHeating operation on units configured with Single Zone VAV control will utilize two separate control methodologies based on heating configurations. For all "Staged" Heating types (Electric and Gas), the unit will utilize 100% full airflow during all active heating periods like traditional Constant Volume units. For Modulating Gas heat units, the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpoint.

    Staged Heating OperationFor units configured with Staged Heat once the control determines that there is an active heating capacity request, the unit will energize the Supply Fan and ramp up to full speed. The control methodology during Active Heating on units configured with Staged Heat types will be identical to traditional Constant Volume units; heating stages will be energized/de-energized to meet the Zone Heating demand.

    Note: All Electric and Gas Heat staging sequences will be identical to Constant Volume unit staging sequences.

    Modulating Heat Operation with SZVAV HeatingUnits configured with Modulating Gas Heat will utilize true Single Zone VAV control in the same manner as during Active Cooling.

    Heating Sequence

    Once the unit control determines that there is a space heating demand, the unit will transition into zone heating. Once the Discharge Air Temperature falls below the calculated discharge air temperature setpoint, the unit will initiate the Modulating Heat output request and control the supply fan at minimum speed. At this point, the Modulating Heat output will be controlled to maintain the discharge air temperature requirements and the supply fan speed will be controlled between 63%-100% to meet the zone heating requirements.

    As the heating load in the zone decreases the fan speed will decrease down to minimum (63%) and control the modulating heat output as necessary to meet the discharge air heating requirements. As the load in the zone continues to drop the fan speed will be maintained at this minimum airflow and the modulating heat output will be controlled accordingly.

    Low Ambient OperationThe indoor fan motor (IDM) will operate at 100% fan speed during this evaporator defrost cycle (EDC) and the compressor and outdoor fan will return to normal operation once the defrost cycle has terminated and the compressor "Off" time delay has been satisfied.

    Clogged Filter OptionThe unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the indoor section and is connected to the RTOM. The clogged filter switch is normally open and will automatically close when the pressure differential across the filters falls below the clogged filter setpoint. The RTOM will generate a SERVICE diagnostic that will be sent to the zone sensor or remote panel when the clogged filter switch has been closed for at least 2 minutes during supply fan operation. The system will continue to operate regardless of the status of the clogged filter switch.

    RT-PRC056G-EN 25

  • Application Considerations

    Ventilation OverrideNote: Applying 24 volts to one of the three Ventilation Override inputs manually activates

    ventilation override. One input is provided to request the Pressurize Mode, the second input the Purge Mode, and the third input the Exhaust Mode.

    When the Pressurize Mode is selected, activating Ventilation Override will cause the supply fan to run, the economizer to open to 100%, the exhaust fan to turn (remain) off, or the VFD to run at full speed, and the VAV boxes to fully open.

    When Purge is selected, activating Ventilation Override will cause the supply fan to run, the economizer to open to 100%, the exhaust fan to run, or the VFD to run at full speed, and the VAV boxes to fully open.

    When Exhaust is selected, activating Ventilation Override will cause the supply fan to turn off, the economizer to close to 0%, the exhaust fan to run (exhaust damper at 100% if configured for Statitrac), or the VFD to stop, and the VAV boxes to operate normally.

    If more than one mode is requested at the same time, the Pressurize request will have priority followed by Purge. When any Ventilation Override Mode is active, all heating and cooling is turned off. For the case where the unit is required to turn off, the Emergency Stop input is used. The ICS can also initiate any ventilation override mode. Table 5 lists the sequence of events within the system for each ventilation mode. Refer to the unit wiring diagram for contact switching and wiring.

    Note: Fresh air tracking will not work with VOM.

    Emergency StopWhen this binary input is opened, all outputs are immediately turned off and the system will not be allowed to restart until the binary input is closed for approximately 5 seconds minimum. The shutdown is communicated to Tracer™ if applicable and the Heat and Cool LED outputs (RTRM J6-7 and J6-8) will blink at a nominal rate of 1 blink per second.

    Phase MonitorThe Phase Monitor is a 3 phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 VAC, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

    Low Pressure ControlThis input incorporates the low pressure cutout of each refrigeration circuit and can be activated by opening a field supplied contact.

    Table 5. Ventilation override sequence

    Mode and Priority

    Affected Function Pressurize Purge Exhaust(a)

    (a) Exhaust mode 3 is not available with the tracking power exhaust option.

    1 2 3

    Heat/Cool off off off

    VFD full speed full speed full speed

    Supply Fan on on off

    Exhaust Fan off on(b)

    (b) For units configured with the Statitrac option, the Exhaust Damper will open during Ventilation Override modes that request the exhaust fan to operate.

    on

    Economizer open open closed

    VAV Boxes forced open forced open normal operation

    26 RT-PRC056G-EN

  • Application Considerations

    If this circuit is open before a compressor(s) is started, the compressor(s) in that circuit will not be allowed to operate.

    Anytime this circuit is opened for 5 continuous seconds, the compressor(s) in that circuit are turned off immediately. The compressor(s) will not be allowed to restart for a minimum of 3 minutes.

    If four consecutive open conditions occur during the first three minutes of operation, the compressor(s) in that circuit will be locked out, a diagnostic communicated to Tracer, and a manual reset will be required to restart the compressor(s).

    High Pressure Cutout and Temperature Discharge Limit The high pressure controls and temperature discharge limit are wired in series between the compressor outputs on the RTRM and the compressor contactors. If the high pressure safety or temperature discharge limit opens, the compressor(s) on the affected circuit is locked out. If the compressor output circuit is opened four consecutive times during compressor operation, the RTRM will generate a manual reset lockout.

    Coil Frost ProtectionThe Frostat™ control monitors the evaporator coil temperature to prevent the evaporator from freezing due to low operating temperatures whenever there is a demand for cooling. When a closed circuit has occurred for 5 seconds minimum, the RTRM turns off all of the cooling outputs. The Supply Fan will be held “On” until the Frostat has been opened for 5 continuous seconds or for 60 seconds after the last compressor was shut “Off”, whichever is the longest. The compressor shutdown is communicated to Tracer, if applicable. There is no local diagnostic for this condition.

    Failure and Override ModesCertain failure and overriding conditions require special handling of the Supply Fan Speed on units configured with Single Zone VAV. See below for a list of these conditions:

    • Supply Fan Proving Failure - If a Supply Fan Proving failure is detected, the Supply Fan will be de-energized after 40s of run time and the Fan Speed output will go to 0 Vdc (0%).

    • Ventilation Override Mode - If a VOM goes active in which the Supply Fan is commanded ON (Purge, Pressurize, etc.), the Supply Fan will be energized and the Fan Speed output will ramp to 100%.

    • Zone Temperature Sensor Failure - If the Active Zone Temperature input goes out of range, the unit will discontinue all Heating, Cooling, and Dehumidification operation.

    • Supply Air Temperature Sensor Failure - If the Supply Air Temperature input goes out of range, the unit will revert back to Full Airflow, Traditional CV control. The unit will call out a Supply Air Temperature Sensor Failure Alarm, the RTRM System LED will flash the 2-blink error code, and the Zone Sensor Heat (Modulating Heat Only) and Cool LEDs will flash.

    • Frostat Failure - If a Frostat failure occurs, all active Heating, Cooling, and Dehumidification will be de-energized immediately and the Supply Fan will ramp up to 100%.

    • Heat Failure (High Temp. Limit Trip) - If a unit configured with Gas Heat has a High Temp. Limit trip, the Supply Fan will be requested to remain ON and the Fan Speed output will ramp to full speed.

    Variable Air Volume Applications (Traditional VAV)

    Supply Air Temperature Control - Occupied Cooling and HeatingThe RTRM is designed to maintain a selectable supply air temperature of 40°F to 90°F with a +/- 3.5°F deadband.

    Note: To reduce the risk of coil freezing, it is not recommended to set the supply air temperature below 50°F.

    In cooling, if supply air temperature is more than 3.5 degrees warmer than the selected temperature, a stage of cooling will be turned “On” (if available). Then if the supply air temperature

    RT-PRC056G-EN 27

  • Application Considerations

    is more than 3.5 degrees cooler than the selected temperature, a stage of cooling will be turned “Off”. At very low airflows the unit may cycle stages “On” and “Off” to maintain an average discharge air temperature outside the 7 degree deadband.If the unit has modulating heat, the unit can be made to do discharge heating with VAV control. This is done by placing a contact closure across the “Changeover Input” on the RTAM. During this mode, the unit will heat to the Supply Air Heating Setpoint +/- 3.5°F. During low load or low airflow conditions the actual temperature swing of the discharge air will likely be greater. The RTRM utilizes a proportional and integral control scheme with the integration occurring when the supply air temperature is outside the deadband. As long as the supply air temperature is within the setpoint deadband, the system is considered to be satisfied and no staging up or down will occur.

    Supply Air Temperature Control with an EconomizerThe economizer is utilized to control the supply air cooling at +1.5°F around the supply air temperature setpoint range of 40°F and 90°F providing the outside air conditions are suitable. While economizing, the mechanical cooling is disabled until the economizer dampers have been fully open for three minutes. If the economizer is disabled due to unsuitable conditions, the mechanical cooling will cycle as though the unit had no economizer.

    VHR Relay OutputDuring unoccupied mode, daytime warm-up (DWU) and morning warm-up (MWU) the VFD will open to 100%. All VAV boxes must be opened through an ICS program or by the VHR wired to the VAV boxes. The RTRM will delay 100% fan operation approximately 6.5 minutes when switching from occupied cooling mode to a heating mode.

    Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied CoolingWhen a field supplied occupied/unoccupied switching device is connected between RTRM J6-11 and RTRM J6-12, both the economizer and the mechanical cooling will be disabled.

    Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied HeatingWhen a field supplied occupied/unoccupied switching device is connected between RTRM J6-11 and J6-12 and DWU is enabled, the zone temperature will be controlled at 10°F below the Morning Warm-up setpoint, but not less than 50°F, by cycling one or two stages of either gas or electric heat, whichever is applicable.

    Morning Warm-up (MWU) ControlMorning Warm-up is activated if the zone temperature is at least 1.5°F below the MWU setpoint whenever the system switches from Unoccupied to Occupied status. The MWU setpoint may be set from the unit mounted potentiometer or a remotely mounted potentiometer. The setpoint ranges are from 50°F to 90°F. When the zone temperature meets or exceeds the MWU setpoint, the unit will switch to the “Cooling” mode. The economizer will be held closed during the morning warm-up cycle.

    Daytime Warm-up (DWU) ControlDaytime Warm-up is applicable during occupied status and when the zone temperature is below the initiation temperature. It can be activated or deactivated through ICS or a night setback zone sensor. If ICS or a night setback zone sensor is not utilized, DWU can be activated by setting the DWU enable DIP switch (RTAM) to ON and supplying a valid morning warm-up setpoint. The unit is shipped with a Morning Warm-up setpoint configured and the Daytime Warm-up function is activated (switch on). Opening the DWU enable switch will disable this function. If the system control is local, the DWU initiation setpoint is 3°F below the Morning Warm-up setpoint. The termination setpoint is equal to the Morning Warm-up setpoint. If the system control is remote (Tracer™), the DWU setpoint is equal to the Tracer Occupied heating setpoint. The initiation and

    28 RT-PRC056G-EN

  • Application Considerations

    termination setpoints are selectable setpoints designated by Tracer. When the zone temperature meets or exceeds the termination setpoint while the unit is in an Occupied, “Auto” Mode or switched to the “Cooling” Mode, the unit will revert to the cooling operation. If an Occupied “Heating” Mode is selected, the unit will only function within the DWU perimeters until the system is switched from the “Heat” Mode or enters an Unoccupied status.

    Note: When a LCI is installed on a VAV unit, the MWU setpoint located on the RTAM board is ignored. The MWU and DWU setpoints come from the higher priority LCI-R DAC.

    Supply Duct Static Pressure ControlThe supply duct static pressure is measured by a transducer with a 0.25 to 2.125 Vdc proportional output which corresponds to an adjustable supply duct static pressure of 0.3" w.c. to 2.5" w.c. respectively with a deadband adjustment range from 0.2" w.c. to 1.0" w.c. The setpoint is adjustable on the RTAM Static Pressure Setpoint potentiometer or through ICS.

    Example:Supply Duct Static setpoint = 2.0" w.c. (RTAM)Deadband = 0.2" w.c. (RTAM)Duct Static Control Range = 1.9" w.c. to 2.1" w.c.

    Mechanical Cooling with an EconomizerThe economizer is utilized to control the zone temperature when the outside air conditions are suitable. The method used to determine economizer effectiveness, depending on the available data, is described below in descending order of complexity.

    The most sophisticated method available is always used. Two of the three methods for determining the suitability of the outside air can be selected utilizing the potentiometer on the Economizer Actuator, as described below:

    1. Ambient Temperature - controlling the economizing cycle by sensing the outside air dry bulb temperature. Table 8 lists the selectable dry bulb values by potentiometer setting.

    2. Reference Enthalpy - controlling the economizer cycle by sensing the outdoor air humidity. Table 8 lists the selectable enthalpy values by potentiometer setting. If the outside air enthalpy value is less than the selected value, the economizer is allowed to operate.

    Table 6. Variable air volume mode operation

    System Mode Fan “Auto” Fan “On”

    HeatDWU ActiveDWU Off

    DWU2Off4

    DWU2 VAV Heating4

    Cool VAV Cooling1 VAV Cooling1

    AutoDWU ActiveDWU Off

    DWU or Cooling1,2,3,4VAV Cooling1

    DWU or Cooling1,2,3,4VAV Cooling or Heating1

    Off Off4 Off4

    Notes: 1. If Cooling is selected the supply fan will run continuously. If VAV Heating is activated the supply fan

    will run continuously. 2. If Daytime Warmup is Activated, the supply fan will run continuously. 3. Auto changeover between Cooling and Daytime Warmup depends upon the DWU initiate setpoint. 4. The fan will be Off any time the system selection switch is “Off”.

    Table 7. Economizer effectiveness

    Method used to determine economizer effectiveness Required

    Comparative Enthalpy OAT, OAH, RAT, RAH

    Reference Enthalpy OAT, OAH

    Reference Dry Bulb OAT

    Unable to determine effectiveness OAT data is invalid or unavailable

    RT-PRC056G-EN 29

  • Application Considerations

    3. Comparative Enthalpy - By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the economizer will be able to establish which conditions are best suited for maintaining the zone temperature, i.e., indoor conditions or outdoor conditions.

    Off ModeThis mode is set at the zone sensor or by ICS. During this status, no heating, ventilation, or mechanical cooling is being performed. When switching the “System” selector to the “Off” mode from any other mode, any diagnostic data and diagnostic indication signal will be retained as long as the system remains in the “Off” status. Switching the “System” selector from the “Off” mode back to any other mode of operation will reset all diagnostics.

    Heating OperationHeating operation on units configured with Traditional Multi-Zone VAV control will utilize two separate control methodologies based on heating configurations. For all “Staged” Heating types (Electric and Gas), the unit will utilize 100% full airflow during all active heating periods like traditional Constant Volume units. If the unit has modulating heat, the unit can be made to do discharge heating with VAV control. This is done by placing by placing a contact closure across the “Changeover Input” on the RTAM. During this mode, the unit will heat to the Supply Air Heating Setpoint ± 3.5°F. During low load or low airflow conditions the actual temperature swing of the discharge air will likely be greater.

    Zone Temperature - Unoccupied HeatingWhile a building is in an unoccupied period as designated by a remote panel with night setback or ICS, the necessary heating capacity will be controlled to maintain the zone temperature to within the unoccupied setpoint deadband. For traditional VAV systems, the VFD will operate at 100% during this mode. It will be necessary to drive VAV boxes to their maximum position through ICS programming or the factory provided VHR relay. For Modulating Gas Heat units, Full Airflow is not required but can be enabled by connecting the changeover mode input J5-1 and J5-2 on the RTAM module. For all Staged Heating types, the Supply Fan will be controlled at maximum fan speed during active heating operation as during Occupied periods.

    Gas Heat ControlThe ignition sequence and timing are provided by a separate heat control module. The RTRM only provides the heating outputs to initiate 1st and 2nd stages and control the combustion blower relay. Both stages of the furnace will start and operate for one minute and then cycle back if only one stage is required. Units with modulating heat capabilities will light on high fire for one minute and then modulate to the appropriate heating rate for the building load present.

    Electric Heat ControlThe RTRM provides two heating outputs for 1st and 2nd stages that will be controlled with at least a 10 seconds delay between each stage. When the fan selection switch is in the “AUTO” mode, the fan will start approximately 1 second before the 1st heater stage is activated. The fan and heater will cycle off after the heating setpoint has been satisfied. Once the Zone Heating requirements have been satisfied, the fan and heat outputs will be controlled off.

    Table 8. Economizer configuration

    Selection Dry Bulb Enthalpy Value

    A 73°F 27 BTU/LB Air

    B 70°F 25 BTU/LB Air

    C 67°F 23 BTU/LB Air

    D 63°F 22 BTU/LB Air

    E 55°F 19 BTU/LB Air

    30 RT-PRC056G-EN

  • Selection Procedure

    Cooling Capacity Note: Cooling Capacity Procedure is the same for cooling (TZ) and gas/electric (YZ).

    Step 1.

    Calculate the building’s total and sensible cooling loads at design conditions. Use the following calculation methods or any other standard accepted method. Factors used in unit selection:

    Total Cooling Load: 180 MBh Sensible Cooling Load: 126 MBh Airflow: 6000 cfm Electrical Characteristics: 460/60/3Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB External Static Pressure: 0.39 i