Pride in WorkmanshipWorldwide

Pride in Workmanship Worldwide

Page 2: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MASTER Fire Pump Controllers MASTER Fire Pump Controllers Are Engineered to the Highest Are Engineered to the Highest

Standards in the IndustryStandards in the Industry Instant-On circuitry Restart time delay Modular Mother board All printed circuits are

enclosed in a steel card cage Diagnostic Plug and LEDs Triple redundant control

transformers 35% voltage drop

Page 3: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Features That Make MC Series Fire Features That Make MC Series Fire Pump Controllers a Smart ChoicePump Controllers a Smart Choice

No field Programming LED’s and SPDT contacts for visual

and remote monitoring of alarms Vertically mounted ISO SW and CB Digital display readout Single phase protection Independent pressure and alarm

recorder DC Shunt trip

Page 4: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued Restart Time Delay

Controllers utilize a re-start timer to delay the

instantaneous re-start of the controller. This allows

electromagnetic fields in the motor to decay.

Page 5: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued Control Chassis

Control chassis has Diagnostic LEDs, latched connectors and a steel card cage for mechanical protection of printed circuit boards

Page 6: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued Triple Redundant Control Transformers

Triple Redundant control transformers privide full control power even if a phase is lost

Page 7: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued 35% Voltage Drop

Model MCP

Controllers will continue to operate if

the voltage drops by as much as 35% of rated voltage. This can be critical when starting

the fire pump on emergency power.

Page 8: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued Isolation Switch and Circuit Breaker

Vertically mounted Isolation Switch and Circuit Breaker with

Separate operating

handles and interlock.

Page 9: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued Door Display

Through the door digital display reads out voltages, phase currents and pressure

Page 10: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features ContinuedDR2500 Paperless Pressure and Alarm Recorder

Independent digital recorder saves the latest

2500 pressure points and 350 alarm points into a

separate permanent memory buffers

Page 11: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features ContinuedDR2500 Paperless Pressure and Alarm Recorder

The DR2500 is specifically designed to communicate through an RS-232 serial port directly to a lap‑top computer or a network server

Page 12: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features ContinuedDR2500 Paperless Pressure and Alarm Recorder

Data may be downloaded by using any terminal emulator program such as Terminal, Hyperterm, etc.

Page 13: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features ContinuedDR2500 Paperless Pressure and Alarm Recorder

DR2500 control menu

Page 14: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features ContinuedDR2500 Paperless Pressure and Alarm Recorder

Retrieved data

Page 15: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

MC Features ContinuedMC Features Continued DC Shunt Trip

Controllers use a DC shunt trip coil

powered from all 3 phases. The locked rotor protector will

still operate under a single phase

condition.

Page 16: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Motor Starting TypesMotor Starting Types

Across-the-linePart-windingPrimary reactorWye-delta (open)Wye-delta (closed)Soft StartAutotransormer

Page 17: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Motor Starting Types ContinuedMotor Starting Types Continued

Reactor ComparisonReactor ComparisonReactor uses a standard electric motorReduces complexity of field wiring - wired

same as across the lineLow Power Factor makes the reactor ideal

for gen-set applications

Page 18: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Motor Starting Types ContinuedMotor Starting Types Continued

Fire Pump Starting Type Characteristics

Page 19: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Motor Starting Types ContinuedMotor Starting Types Continued

Leading Phase Monitor™Used on Wye-Delta (open) controllersUsed on Wye-Delta (open) controllersReduces open circuit transient to closed Reduces open circuit transient to closed

circuit levelscircuit levelsAllows you to use Wye-Delta (open) as an Allows you to use Wye-Delta (open) as an

option to Wye-Delta (closed)option to Wye-Delta (closed)

Page 20: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Motor Starting Types ContinuedMotor Starting Types Continued

Leading Phase Monitor™

Closing the Delta contactor Closing the Delta contactor (run) with closing voltage (run) with closing voltage leading the Wye contactor leading the Wye contactor

(start) gives you closing (start) gives you closing currents about the same as currents about the same as

closed transition controllers closed transition controllers

Wye-Delta Transition Transients (typical)

Page 21: Pride in Workmanship Worldwide Pride in Workmanship Worldwide

Pride in WorkmanshipWorldwide

Thank You!Thank You!