Upload
trinhdiep
View
215
Download
0
Embed Size (px)
Citation preview
Product Description
Product Description
ERG-MAN-EMM-STE-P04-XXX-015-003-REV.0
EGS Business Park B2 Kat: 11 No: 348 34149 Bakırköy, Istanbul/TURKEY E-Mail: [email protected]: +90 212 485 40 07 (Pbx) Fax: +90 212 485 40 42
Flame Arresters & Storage Tank Valves
ERGIL Storagetech™ Model 102 Pressure-Vacuum Relief Valve with Integrated End-of-line Flame Arrester provides total security of mind to operators of storage tanks. The Model 102 ensures protection against damage through over-pressurisation, implosion due to vacuum conditions, and prevents any external �ame entering the tank.
In the closed position the pressure relief pallet and diaphragm assembly is held tightly against a seal to prevent the loss of vapour to atmosphere. As the internal pressure in the tank increases, due to product �lling and vapour development, the pressure in tank increases and in the event that the set pressure of the unit is reached, the diaphragm will open and discharge the gas to atmosphere. The opening set-point is selectable from a range between 1 and 28.1 W.C. (2.5 and 70 mbar), and the valve will reseal when the tank returns to a safe pressure.
The vacuum pallet and diaphragm assembly is similarly maintained in the closed position. As the internal pres-sure in the tank reduces, due to emptying, the balance between the tank pressure and the external atmospheric pressure changes, and when the set pressure of the unit is reached, the diaphragm opens to admit air and rebal-ance the internal pressure. The vacuum set-point is selectable from a range between 1 and 28.1 W.C. (2.5 and 70 mbar). The valve will reseal when the tank returns to a safe pressure.
Unlike the conventional PVRV, the Model 102 discharges vapour and takes in air through the same vent, conse-quently a single end-of-line �ame arrester provides protection from the potential ingress of �ames emanating from an external �re.
Model Number 102
(End of Line, weight loaded, integrated, atmospheric
de�agration proof)
Pressure Vacuum Relief Valve With
Flame Arrester
ergilR
ergilR
ERG-MAN-EMM-STE-P04-XXX-015-003-REV.0
EGS Business Park B2 Kat: 11 No: 348 34149 Bakırköy, Istanbul/TURKEY E-Mail: [email protected]: +90 212 485 40 07 (Pbx) Fax: +90 212 485 40 42
Product Description
Flame Arresters & Storage Tank Valves
o o
The integral de�agration �ame arrestor is designed to minimise pressure loss and with an element constructed with a <0.65mm Maximum Experimental Safe Gap is suitable for gas groups IIB and IIA.
Several features are inherent in the valve design to ensure a smooth, positive and e�ective operation. The body is self-draining and drip design prevents condensate from settling on seating surfaces. A diaphragm and seal manufactured from Te�on reduce the possibility of ice formation and sticky residues hindering the valve open-ing, while the pallet assembly moves freely on its guide post.
Pressure
Ambient temp. : -20 C to +60 C
: Weight-loaded 2.5 mbar to 70 mbar
ConstructionSizes : 2” to 12” 50 to 300mm
Flanges : API Class 150 RF, DIN PN16
Body : Carbon steel, stainless steel, or aluminium
Cap : Carbon steel, stainless steel, or aluminium
Cover : Carbon steel, stainless steel, or aluminium
Seals : Viton, Te�on, and Klingrit
Pallet : Stainless steel AISI 304
Paint �nish : 1- Powder Coating, Colour RAL 9006
2- Epoxy Paint, Colour RAL 9006
3- Customer Speci�cation
Setting Range
ISO 16852:2008 - Flame Arresters, Performance requirements, test methods and limits of use.
API RP 2210 -Flame Arrestors for Vents of Tanks Storing Petroleum Product.
The size of the vent should be calculated in accordance with API Standard 2000 (ISO 28300) - Venting Atmos-pheric and Low-Pressure Storage Tanks or other international standards.
The integrity of the seal is tested for leakage in accordance with API Standard 2521 - Use of Pressure-Vacuum Vent Valves for Atmospheric Loss.
Design & Manufacturing Speci�cations
Technical Draw
ing and Dim
ensions
ERG-MAN-EMM-STE-P04-XXX-015-003-REV.0
EGS Business Park B2 Kat: 11 No: 348 34149 Bakırköy, Istanbul/TURKEY E-Mail: [email protected]: +90 212 485 40 07 (Pbx) Fax: +90 212 485 40 42
Technical Drawing
Dimensions
Flame Arresters & Storage Tank Valves
ergilR
18
18
18
22
22
26
26
4
4
4
8
12
12
8
310
360
380
450
505
565
645
195
240
265
285
320
380
450
168
205
230
275
320
350
435
120,5
152,5
241,5
298,5
362
432
190,5
92
127
157,5
216
270
324
381
ØD Ød ØC ØL n ØD1 H H1
2"
3"
4"
6"
8"
10"
12"