Project : GOLA HILLI FLNG Subject : Pressure Loss Calculation Date : 13/05/2015 Sr. No., Description Fitting Type Fitting loss Cofficient Remark 1 A- 1 1000 x 350 mm 7.50 m 9100 CMH 8.22 m/s 1.11 Pa/m 11.82 Pa 2 SR3-1-1 8.22 m/s 90 Elbow 40.68 Pa 0.26 10.58 Pa 3 SR3-1-6 8.22 m/s 90 Elbow 40.68 Pa 0.26 10.58 Pa 32.97 35.00 4 A -2 1000 x 300 mm 10.00 m 7250 CMH 7.79 m/s 1.11 Pa/m 15.54 Pa 15.54 18.20 5 A -3 1000 x 250 mm 11.00 m 5500 CMH 7.28 m/s 1.11 Pa/m 17.22 Pa 6 SR3-1-1 7.28 m/s 90 Elbow 31.91 Pa 0.27 8.61 Pa 7 SR3-1-5 7.28 m/s 90 Elbow 31.91 Pa 0.70 22.33 Pa 48.16 51.11 28.50 m 44.58 Pa 52.10 Pa 96.68 Pa 104.31 Pa 1 7th Poop Deck 1000 x 350 mm 2.50 m 9100 CMH 8.22 m/s 1.11 Pa/m 3.97 Pa 2 SR5-5-4 8.22 m/s Tee 40.68 Pa 0.02 0.61 Pa 4.58 Pa 5.26 Pa 3 6th Poop Deck 6 -7 1000 x 400 mm 3.50 m 10520 CMH 8.19 m/s 1.00 Pa/m 4.94 Pa 4 SR5-5-3 8.19 m/s Tee 40.38 Pa 0.03 1.21 Pa 6.15 Pa 7.63 Pa 5 5th Poop Deck 5 -6 1000 x 450 mm 3.50 m 14200 CMH 9.71 m/s 1.29 Pa/m 6.46 Pa 6 SR5-5-2 9.71 m/s Tee 56.76 Pa 0.10 5.68 Pa 12.13 Pa 12.18 Pa 7 4th Poop Deck 4 -5 1000 x 500 mm 3.50 m 16830 CMH 10.13 m/s 1.29 Pa/m 6.50 Pa 8 SR5-5-1 1.13 m/s Tee 0.77 Pa 0.03 0.02 Pa 6.52 Pa 6.57 Pa 9 3rd Poop Deck 3 -4 1000 x 600 mm 3.50 m 20740 CMH 10.40 m/s 1.22 Pa/m 6.11 Pa 10 SR5-5-1 10.40 m/s Tee 65.11 Pa 0.03 1.82 Pa 7.93 Pa 8.33 Pa 11 12 2nd Poop Deck 3 -2 1000 x 550 mm 3.50 m 17150 CMH 9.43 m/s 1.07 Pa/m 5.30 Pa 13 SR5-5-1 9.43 m/s Tee 53.56 Pa 0.03 1.50 Pa 6.80 Pa 7.96 Pa 14 1st Poop Deck 2 - 1P 1000 x 400 mm 5.50 m 11380 CMH 8.86 m/s 1.17 Pa/m 9.24 Pa 15 SR5-5-1 8.86 m/s Tee 47.22 Pa 0.03 1.32 Pa 10.56 Pa 11.62 Pa 16 1st Deck 1P - 1D 600 x 400 mm 3.50 m 6260 CMH 7.80 m/s 1.22 Pa/m 6.05 Pa 6.46 Pa 7 Top Velocity Velocity Pressure Fitting Pressure Loss Total Pressure Loss D, Total Pressure Loss Duct Section Duct Size Duct Length Air Flow Rate Velocity Pressure Losses/m Duct Pressure Loss Page 1 of 2

Pressure Loss Calculation_Damper Losses (Version 1)

  • Upload
    zwe1991

  • View
    215

  • Download
    2

Embed Size (px)

DESCRIPTION

Sample

Citation preview

  • Project : GOLA HILLI FLNG

    Subject : Pressure Loss Calculation

    Date : 13/05/2015

    Sr. No., DescriptionFitting

    Type

    Fitting loss

    CofficientRemark

    1 A - 1 1000 x 350 mm 7.50 m 9100 CMH 8.22 m/s 1.11 Pa/m 11.82 Pa

    2 SR3-1-1 8.22 m/s 90 Elbow 40.68 Pa 0.26 10.58 Pa

    3 SR3-1-6 8.22 m/s 90 Elbow 40.68 Pa 0.26 10.58 Pa 32.97 35.00

    4 A - 2 1000 x 300 mm 10.00 m 7250 CMH 7.79 m/s 1.11 Pa/m 15.54 Pa 15.54 18.20

    5 A - 3 1000 x 250 mm 11.00 m 5500 CMH 7.28 m/s 1.11 Pa/m 17.22 Pa

    6 SR3-1-1 7.28 m/s 90 Elbow 31.91 Pa 0.27 8.61 Pa

    7 SR3-1-5 7.28 m/s 90 Elbow 31.91 Pa 0.70 22.33 Pa 48.16 51.11

    28.50 m 44.58 Pa 52.10 Pa 96.68 Pa 104.31 Pa

    1 7th Poop Deck 1000 x 350 mm 2.50 m 9100 CMH 8.22 m/s 1.11 Pa/m 3.97 Pa

    2 SR5-5-4 8.22 m/s Tee 40.68 Pa 0.02 0.61 Pa 4.58 Pa 5.26 Pa

    3 6th Poop Deck 6 - 7 1000 x 400 mm 3.50 m 10520 CMH 8.19 m/s 1.00 Pa/m 4.94 Pa

    4 SR5-5-3 8.19 m/s Tee 40.38 Pa 0.03 1.21 Pa 6.15 Pa 7.63 Pa

    5 5th Poop Deck 5 - 6 1000 x 450 mm 3.50 m 14200 CMH 9.71 m/s 1.29 Pa/m 6.46 Pa

    6 SR5-5-2 9.71 m/s Tee 56.76 Pa 0.10 5.68 Pa 12.13 Pa 12.18 Pa

    7 4th Poop Deck 4 - 5 1000 x 500 mm 3.50 m 16830 CMH 10.13 m/s 1.29 Pa/m 6.50 Pa

    8 SR5-5-1 1.13 m/s Tee 0.77 Pa 0.03 0.02 Pa 6.52 Pa 6.57 Pa

    9 3rd Poop Deck 3 - 4 1000 x 600 mm 3.50 m 20740 CMH 10.40 m/s 1.22 Pa/m 6.11 Pa

    10 SR5-5-1 10.40 m/s Tee 65.11 Pa 0.03 1.82 Pa 7.93 Pa 8.33 Pa

    11

    12 2nd Poop Deck 3 - 2 1000 x 550 mm 3.50 m 17150 CMH 9.43 m/s 1.07 Pa/m 5.30 Pa

    13 SR5-5-1 9.43 m/s Tee 53.56 Pa 0.03 1.50 Pa 6.80 Pa 7.96 Pa

    14 1st Poop Deck 2 - 1P 1000 x 400 mm 5.50 m 11380 CMH 8.86 m/s 1.17 Pa/m 9.24 Pa

    15 SR5-5-1 8.86 m/s Tee 47.22 Pa 0.03 1.32 Pa 10.56 Pa 11.62 Pa

    16 1st Deck 1P - 1D 600 x 400 mm 3.50 m 6260 CMH 7.80 m/s 1.22 Pa/m 6.05 Pa 6.46 Pa

    7

    Top

    VelocityVelocity

    Pressure

    Fitting

    Pressure

    Loss

    Total Pressure

    Loss

    D, Total Pressure

    LossDuct Section Duct Size Duct Length Air Flow Rate Velocity

    Pressure

    Losses/m

    Duct

    Pressure

    Loss

    Page 1 of 2