Configured to Order Automatic Transfer Switch Applications

Presented by: Ryan Surmik – Southeast Area Sales Manager

Page 2: Presented by: Ryan Surmik Southeast Area Sales Manager

• A device which transfers electrical loads between two

sources using either manual or automatic controls.

Transfer Switch Definition – A Quick Recap

UTILITY LOAD GENERATOR

TRANSFER SWITCH

What is a transfer switch?

An ATS is powered by the source that it’s transferring to…

Page 2Confidential Property of Schneider Electric |

Page 3: Presented by: Ryan Surmik Southeast Area Sales Manager

Seven Major Functions of An Automatic Transfer Switch

• Carry Current Continuously

• Detect Power Failures

• Initiate Alternate Source

• Transfer Load

• Sense Restoration of Normal

• Retransfer Load To Normal

• Withstand And Close On Fault Currents

Purpose Of An Automatic Transfer Switch – A Quick Recap

UTILITY LOAD GENERATOR

TRANSFER SWITCH

Page 3Confidential Property of Schneider Electric |

Page 4: Presented by: Ryan Surmik Southeast Area Sales Manager

ATS Physical Elements

Page 4Confidential Property of Schneider Electric |

Page 5: Presented by: Ryan Surmik Southeast Area Sales Manager

Automatic Transfer Switch Product Overview

Residential Mission Critical

ASCO SERIES 185 Power

Transfer Switches

ASCO SERIES 300 Power

Transfer Switches

ASCO SERIES 7000 Power

Transfer Switches

Light Commercial & Industrial

Page 5Confidential Property of Schneider Electric |

Page 6: Presented by: Ryan Surmik Southeast Area Sales Manager

Balancing Need Based on the Application

Residential, Commercial, Industrial

• “I need a switch…”

• Notion of Pre-Configuration:• Decrease time from concept to customer

delivery

• Reduce engineering time through predefined accessory availability

• Can serve an immediate need

• Stock or Configured-to-Order

Mission Critical

• “I need a switch, AND it has to have a,b,c and do x,y,z”

• Highly Specified by Owner or Consulting Engineer• Fully customizable

• Feature Rich

• Typically Engineered-to-Order

Page 6Confidential Property of Schneider Electric |

Page 7: Presented by: Ryan Surmik Southeast Area Sales Manager

Balancing Need Based on the Application

Residential

ASCO SERIES 185 Power

Transfer Switches

ASCO SERIES 300 Power

Transfer Switches

Light Commercial & Industrial

Page 7Confidential Property of Schneider Electric |

Page 8: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 185 - Residential■ 100-400A

■ 240V/120V Single Phase

■ Type 1 or 3R enclosure

■ Auto or Manual

■ Service Entrance Breaker (optional)

Page 8Confidential Property of Schneider Electric |

Page 9: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 185 - Residential■ Equipped with In Phase Monitor

■ Adjustable Dip Switch Settings for Pre-Defined Settings● Engine Exerciser – On/Off

● Exercise with or without load – On/Off

● Limited Time Delay Adjustments

● Limited Pickup and Dropout Voltage Adjustments

■ Optional Features● Strip Heater (for Outdoor Installations)

● Connectivity for use with Remote Annunciator

● Position Indication Contact

● Fusing and Controls for Air-Cooled Generators

Page 9Confidential Property of Schneider Electric |

Page 10: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 185 - Residential■ Manual Configurations

● Deletes the Control Panel

● True Double Throw, Manual Operation Between Sources via External Handle

■ Service Entrance Configurations● Adds Manually Operated Circuit Breaker on Utility Source and

Bonding Jumper on Neutral and Ground

● Meets all NEC Requirements for Service Entrance Equipment

Page 10Confidential Property of Schneider Electric |

Page 11: Presented by: Ryan Surmik Southeast Area Sales Manager

Residential Applications

MTS/ATS Application

`

■ ATS feeds a standby circuit breaker panel for specific branches during a power outage

● HVAC

● Refrigeration

● Sump Pump

Service Entrance ATS Application

■ Service Entrance Rated ATS feeds the whole house through the load center

Page 11Confidential Property of Schneider Electric |

Page 12: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 Automatic Transfer Switch■ 30A - 3000A

■ 120V - 600V

■ 2, 3 or 4 Pole Configuration

■ Single & Three Phase

■ Automatic, Non-Automatic, or Manual

■ Open Transition or Delayed Transition

■ Enclosure Options – Type 1, 3R, 12, 4X

■ Service Entrance Breaker Option

Page 12Confidential Property of Schneider Electric |

Page 13: Presented by: Ryan Surmik Southeast Area Sales Manager

Auto vs Non-Auto vs ManualAutomatic

■ Detect Power Failures

■ Initiates Alternate Source

■ Transfer Load One Emergency is Acceptable

■ Sense Restoration of Normal

■ Retransfers Load To Normal

Non-Automatic

■ ATS Detect Power Failures

■ User Initiates Alternate Source (at the Generator)

■ Emergency Source becomes Acceptable

■ User Transfers Load via Push Button on ATS

■ ATS Senses Restoration of Normal

■ User Retransfers Load To Normal via Push Button on ATS

Page 13Confidential Property of Schneider Electric |

Page 14: Presented by: Ryan Surmik Southeast Area Sales Manager

Auto vs Non-Auto vs ManualNon-Automatic

■ ATS Detect Power Failures (Control Panel & Indicating Lights Go Out)

■ User Initiates Alternate Source (at the Generator)

■ Emergency Source becomes Acceptable

■ User Transfers Load via Push Button on ATS

■ ATS Senses Restoration of Normal

■ User Retransfers Load To Normal via Push Button on ATS

Manual

■ User Detect Power Failures

■ User Initiates Alternate Source (at the Generator)

■ Emergency Source becomes Acceptable

■ User Transfers Load via Manual Operating Handle

■ User Senses Restoration of Normal

■ User Retransfers Load To Normal via Manual Operating HandlePage 14Confidential Property of Schneider Electric |

Page 15: Presented by: Ryan Surmik Southeast Area Sales Manager

“Open” Transition– Conventional 2-position ATS

– True double throw (no intermediate position)

– Single operator:

• Solenoids, charge & close mechanism, linear

motor, or solenoid (mfr. / switch type

dependent)

• Most reliable & cost effective method of

transfer

N E

L

Load on

Normal

N E

L

Load Not

Connected

N E

L

Load on

Emergency

Transfer Switch Transition Types

Page 15Confidential Property of Schneider Electric |

Page 16: Presented by: Ryan Surmik Southeast Area Sales Manager

“Delayed” Transition– Other Aliases - Center-Off, Neutral position

– Dual Operators & Switching Mechanisms

• Intermediate position for hot-to-hot transfers

• 0-5 minutes (user selectable based on

applicable motor inertia)

• Commonly used as an alternate to in-phase

transfer

• NOT recommended for life safety/critical

branches; good option for equipment loads

requiring load shed (with paralleling)

Transfer Switch Transition Types

Load on

Normal

Load Not

Connected

Load on

Emergency

N

L

E

N

L

E

N

L

E

Page 16Confidential Property of Schneider Electric |

Page 17: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 – Group G Controls

Page 17Confidential Property of Schneider Electric |

Page 18: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 – Standard Features■ In Phase Monitor

■ Engine Exerciser● Provides Weekly Automatic Testing Of An Engine Generator

Set With Or Without Load For 20 Minutes Fixed

■ Commit To Transfer● If Commit To Transfer Is Active, And 1C Timer Has Expired

Controller Will Continue Transfer Sequence To Emergency Even If Normal Returns Before Emergency Becomes Acceptable, Provided Controller Does Not Loss Power In The Middle Of The Sequence

■ Real Time Clock● Real Time Keeps Track Of Date Time

● Used To Enable Engine Exerciser To Operate At The Proper Day And Time And To Reference Entries Into Event Log

● Maintains The Following Parameters: Year, Month, Day Of Month, Day Of Week, Hours (Military), Minutes, Seconds And Tenths Of Seconds

● Parameters Are Initialized From User Interface Or Via Serial Communications Port

● Provides Automatic Update Of Time Per United States Daylight Savings Time

● With Battery Backup

■ Statistics And Diagnostics● Controller Monitors Several Values And Displays Them In

Statistics And Diagnostics Menu

● Total Transfer

● Total Transfers Due To Source Failures

● Days Energized

● Total Time N Available

● Total Time E Available

● Input And Output Status

■ About● Controller Displays Controller Part Number And Software

Part Number

■ Common Alarm● A Common Alarm Lights Up The Alert Indicator, And De-

energizes The Configured Common Alarm Output Relay For External Mounting

Page 19: Presented by: Ryan Surmik Southeast Area Sales Manager

Over 5000 students rely on ASCO Power for dependable backup power to keep systems

and school facilities working 24/7.

Challenges

• Prevent power outages from impacting data center, class room, and other facilities.

• Meet compliance demands imposed by NEC, NFPA, and other codes and standards.

Solution

• ASCO – SERIES 300 Automatic Transfer Switches• Square D - Low Voltage Distribution Switchgear

Benefits

• Fast turnaround time• Engineer-Specified standardized package• Cost efficient solution• Reliable back-up power

“We’ve always received great support from ASCO … I’ll continue to use you and anyone you partner with on my projects.”

John TanRW Sullivan

Holyoke Community College, USA Reliable power for higher education facilities.

Page 19Confidential Property of Schneider Electric |

Page 20: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 – Configurable Accessories■ Accessory 1UP – UPS Control Panel Back Up

● Allows controller to run for 3 minutes without AC Power

■ Accessory 11BE – Exerciser Bundle● Upgrades to a fully programmable engine exercisers with up

to 7 different exercise routines

● Adds Event Log Display to show a minimum of 300 events included a date and time stamp and reason (if applicable)

● Enables RS-485 Communication Port

● Includes a programmable Common Alarm output contact

■ Accessory 18RX – Relay Expansion Module● Configurable to include addition output contacts:

■ Source Availability Contacts

■ Signal Before Transfer Contacts (Elevator Contacts)

■ Non-in-Automatic Contact

● Can be daisy-chained to another 18RX for additional contacts

■ Accessory 23G – Load Current Card● Displays current reading on the load side of the ATS

■ Accessory 30 - Load Shed Contacts● Contact to initiate disconnecting load from Emergency

Source

■ Accessory 62W – Transfer Alarm Contact● Audible Alarm With Silencing Feature To Signal Each Time

Transfer To Emergency Occurs:

● Includes Keyed Switch/Retransfer Delay Bypass, Momentary In Both Directions. Keyed Test Switch Maintained Transfer To Emergency

● In Lieu Of User Interface A Mounting Plate Is Provided For Discrete Components

REMEMBER - All of these accessories can be ordered as field installable kits!

Page 20Confidential Property of Schneider Electric |

Page 21: Presented by: Ryan Surmik Southeast Area Sales Manager

• Accessory 1UP Backup Power (UPS)

• This Feature Allows Controller To Run For 3 Minutes Minimum Without AC Power

• Includes Ribbon Cable

• Shown With Cover Removed

• Available As Kit For Field Installation P/N 935149

21

Capacitor Bank

Ribbon Connection

Cover On

ASCO SERIES 300 – Configurable Accessories

Page 21Confidential Property of Schneider Electric |

Page 22: Presented by: Ryan Surmik Southeast Area Sales Manager

• Accessory 11BE Feature Bundle

Consists Of The Following:

• A Fully Programmable Engine Exerciser With

Seven Independent Routines To Exercise The

Engine Generator, With Or Without Loads, On A

Daily Weekly, Bi – Weekly, Or Monthly Basis

• Event Log Display Which Shows The Event

Number, Time And Date Of Events, Event Type

And Reason (If Applicable). A Minimum Of 300

Events Can Be Stored

• RS - 485 Communications Port Enabled

• Common Alarm Output Contact (OP1)

• Field Installation Kit Available

22

ASCO SERIES 300 – Configurable Accessories

Page 22Confidential Property of Schneider Electric |

Page 23: Presented by: Ryan Surmik Southeast Area Sales Manager

■ Accessory 18RX REX Module (Relay Expansion Module) ● Primary Function Of REX Module is to interface to the Dual

Operator Switching Device (DTTS)

● The REX Module provides the following relays

■ OP2 And OP3 Relays And Terminal Block Connections

● The default function of OP2 is to provide a common alarm output with the Common Alarm feature triggers

● Can Be Configured For:

− Common Alarm

− Accessory 31

− Not In Auto

■ 18B,18G Relay And Terminal Block Connections

● 18B Relay Is Energized When Emergency Source Is Accepted.

● 18G Relay Is Energized When Normal Source Is Accepted.

■ REX Module Can Be Daisy Chained To Allow Multiple Sets Of Contacts Via 2nd REX Module – Accessory 18RX2

ASCO SERIES 300 – Configurable Accessories

High Voltage Plug Connection

OP2 Contacts

OP3 Contacts

Additional Relays for Delayed Transition

Page 24: Presented by: Ryan Surmik Southeast Area Sales Manager

• Accessory 23G*Load Current Card

• Load Current Metering Card, Measures Either Single (23GA) Or Three (23GB) Phase Load Current

• Includes Current Transformers (CT’s), And Shorting Block

• Parameters Can Be Viewed Via The User Interface

• Available As Kit For Field Installation, Either Current Card Only (P/N 935150) Or Current Card, Spilt Core CT’s, And Mounting Hardware

24

Current Metering

Card

Typical Ring Type

Current Transformer

Typical Split Core

CT For Field Retrofit

ASCO SERIES 300 – Configurable Accessories

Page 24Confidential Property of Schneider Electric |

Page 25: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 – Configurable Accessories■ Accessory 72EE – Ethernet Connectivity Module

● (2) CAN Ports And (4) RJ-45 Ethernet Ports

● Improved SMNP Capabilities, Increased List Of Parameters Available

● Improved SMTP Capabilities For Communication With Customer’s E Mail Server

● Remote Transfer Capability Via Embedded Web Page

● Provides a 10/100 Mbit Ethernet Interface To Transfer Switch

● Includes Embedded Web Pages And Access To Modbus Registers For Monitoring And Control With Encryption

● Includes 11BE Feature Bundle

■ Accessory 135L – Power Meter on Load Side● Measures, displays and provide single- or 3-phase Energy

and Power Information

Page 25Confidential Property of Schneider Electric |

Page 26: Presented by: Ryan Surmik Southeast Area Sales Manager

■ Project Requirements

● (1) 400A ATS, Life Safety

● (1) 400A ATS, Critical Loads

● (2) 400A ATS, Equipment Loads

● Provisions for a Roll Up Generator

● Needs to communicate:

■ Show NFPA 110 Alarms

■ Display power information from ATS

■ Display generator information

■ Needs to provide email notifications

■ Leadtime Requirement < 7 days

Emergency Switchboard (By Others)

ATS-LS ATS-CR ATS-EQ1 ATS-EQ2

EthernetCable

ATS’s include 1UP (control panel back UPS power), 72EE (ethernet comm module) and 135L (power manager)

Roll Up Generator

Rapid Deployment Healthcare with Communication

Page 26Confidential Property of Schneider Electric |

Page 27: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO SERIES 300 – Additional Configurations■ Service Entrance Rated – 3AUS

● Addition of circuit breaker on the Normal source

● Includes Neutral & Ground Disconnect Link

■ Breaker on Generator Source – 3AGS

■ Breaker on both Utility and Generator Source – 3APS

■ Power Transfer Load Center Configuration – 300L● Breaker on Normal & Emergency Source

● Internal Surge Protection

● Load Side Panelboard

■ Additional Accessories –● Shunt Trip on Circuit Breaker

● ERMS Switch

Page 27Confidential Property of Schneider Electric |

Page 28: Presented by: Ryan Surmik Southeast Area Sales Manager

Over 14,000 residents feel more secure with ASCO’s reliable back-up power for critical

flood control.

Challenges

• Assurance of power supply during utility outage• Compliance with government regulation

Solution

• ASCO – SERIES 300 Service Entrance Transfer Switch

Benefits

• Provided reliable power products within budgetary constraints

• Expedited solution to meet a critical construction schedule

“ASCO is a well-known brand and we have a great working relationship.”

Pete GantzModern Group Power

Systems

Bloomsburg Flood Risk ManagementFlood management for a Pennsylvania community.

Page 28Confidential Property of Schneider Electric |

Page 29: Presented by: Ryan Surmik Southeast Area Sales Manager

Normal

SourceEmergency

Generator

Utility

Breaker

Generator

Breaker In Type

3R Enclosure

SPD On

Normal

SPD On

Emergency

Branch Circuit Panelboard

200/400 Amp

SERIES 300

Automatic Transfer

Switch

Typical Cell Tower Installation

Page 29Confidential Property of Schneider Electric |

Page 30: Presented by: Ryan Surmik Southeast Area Sales Manager

SERIES 300 PTLC (Power Transfer Load Center Switch)

Square D

Panelboard

200A

ATS

Surge

Devices

Group G

Controller

Square D

Utility and

Generator

Breakers

Integrated Solution Application

Page 30Confidential Property of Schneider Electric |

Page 31: Presented by: Ryan Surmik Southeast Area Sales Manager

SERIES 300 PTLC (Power Transfer Load Center Switch)

Square D

Panelboard

200A

ATS

Surge

Devices

Group G

Controller

Square D

Utility and

Generator

Breakers

• Complete integrated solution

• Lower installation costs

• Components mounted, wired and tested at the factory

• Product of single manufacturer

• One Warranty for all Components

• Interconnect Wiring Diagrams And Operator’s Manual Provided With Each Switch

• Supplied In A Common Enclosure Indoor (Type 1) Or Outdoor (Type 3R)

• Integrated PTLC Listed To UL 67 And Includes UL 1008 Listed Transfer Switch

Integrated Solution

Page 31Confidential Property of Schneider Electric |

Page 32: Presented by: Ryan Surmik Southeast Area Sales Manager

2017 NEC 700.3

32

700.3 (F) “ ….If the emergency system relies on a single alternate source of power which will be disabled for maintenance or repair, the emergency system shall include permanent switching means to connect a portable or temporary alternate source of power …. The permanent switching means to connect a portable or temporary alternate source of power shall comply with the following:

(1) Connection to the portable or temporary alternate source of power shall not require modification of the permanent system wiring.”

Be sure to join us again on April 30th for an in-depth look at the new NEC code!!

Page 32Confidential Property of Schneider Electric |

Page 33: Presented by: Ryan Surmik Southeast Area Sales Manager

A Solution for NEC 700.3(F) Requirements

Page 33Confidential Property of Schneider Electric |

Page 34: Presented by: Ryan Surmik Southeast Area Sales Manager

ASCO 3MTS & 3MTQ

34

Page 34Confidential Property of Schneider Electric |

Page 35: Presented by: Ryan Surmik Southeast Area Sales Manager

180 residents plus skilled healthcare workers feel safe and secure with ASCO’s

reliable back-up power.

Challenges

• Securing well-being of patients during extended power outages

• Compliance with Florida mandate for 96 hours of backup power

Solution

• ASCO Value Added Automatic Transfer Switches• ASCO SERIES 300 Manual Transfer Switch with Quick

Connect Docking Station• ASCO Surge Protective Devices• SquareD - Low Voltage Distribution

Benefits

• Provided reliable power products within budget• Custom power system integration• Pre-packaged solution

“"ASCO provides a variety superior products to meet the back-up power needs from the largest hospital to the smallest nursing facility.“

Randall Power

Greystone Health Providing our clients with peace of mind, safety and improved quality of life.

Page 35Confidential Property of Schneider Electric |

Page 36: Presented by: Ryan Surmik Southeast Area Sales Manager

What design considerations push us out of pre-configuration?■ Any accessory outside ones listed previously

■ Bypass Isolation

■ Custom Lugs Configurations

■ Closed Transition (Active or Passive) & Utility Requirements

Page 36Confidential Property of Schneider Electric |

Page 37: Presented by: Ryan Surmik Southeast Area Sales Manager

How do I get something quickly?

■ Contact your local field sales office.

■ Subscribe to the ASCO Stock List● Provided daily/weekly updates on items in stock and available for quick

shipment.

● Email: [email protected]

● Subject: “Please ADD me to the Automated Inventory Stocking List Enter the following information”■ Company Name:

■ Contact Name:

■ Address:

■ City:

■ State:

■ Zip:

■ Email:

■ Phone #

■ Territory:

■ Type of business

An email with how to join will be sent out after the presentation.

Page 37Confidential Property of Schneider Electric |

Page 38: Presented by: Ryan Surmik Southeast Area Sales Manager