Confidential Property of Schneider Electric
Configured to Order Automatic Transfer Switch Applications
Presented by: Ryan Surmik – Southeast Area Sales Manager
• A device which transfers electrical loads between two
sources using either manual or automatic controls.
Transfer Switch Definition – A Quick Recap
UTILITY LOAD GENERATOR
TRANSFER SWITCH
What is a transfer switch?
An ATS is powered by the source that it’s transferring to…
Page 2Confidential Property of Schneider Electric |
Seven Major Functions of An Automatic Transfer Switch
• Carry Current Continuously
• Detect Power Failures
• Initiate Alternate Source
• Transfer Load
• Sense Restoration of Normal
• Retransfer Load To Normal
• Withstand And Close On Fault Currents
Purpose Of An Automatic Transfer Switch – A Quick Recap
UTILITY LOAD GENERATOR
TRANSFER SWITCH
Page 3Confidential Property of Schneider Electric |
ATS Physical Elements
Page 4Confidential Property of Schneider Electric |
Automatic Transfer Switch Product Overview
Residential Mission Critical
ASCO SERIES 185 Power
Transfer Switches
ASCO SERIES 300 Power
Transfer Switches
ASCO SERIES 7000 Power
Transfer Switches
Light Commercial & Industrial
Page 5Confidential Property of Schneider Electric |
Balancing Need Based on the Application
Residential, Commercial, Industrial
• “I need a switch…”
• Notion of Pre-Configuration:• Decrease time from concept to customer
delivery
• Reduce engineering time through predefined accessory availability
• Can serve an immediate need
• Stock or Configured-to-Order
Mission Critical
• “I need a switch, AND it has to have a,b,c and do x,y,z”
• Highly Specified by Owner or Consulting Engineer• Fully customizable
• Feature Rich
• Typically Engineered-to-Order
Page 6Confidential Property of Schneider Electric |
Balancing Need Based on the Application
Residential
ASCO SERIES 185 Power
Transfer Switches
ASCO SERIES 300 Power
Transfer Switches
Light Commercial & Industrial
Page 7Confidential Property of Schneider Electric |
ASCO SERIES 185 - Residential■ 100-400A
■ 240V/120V Single Phase
■ Type 1 or 3R enclosure
■ Auto or Manual
■ Service Entrance Breaker (optional)
Page 8Confidential Property of Schneider Electric |
ASCO SERIES 185 - Residential■ Equipped with In Phase Monitor
■ Adjustable Dip Switch Settings for Pre-Defined Settings● Engine Exerciser – On/Off
● Exercise with or without load – On/Off
● Limited Time Delay Adjustments
● Limited Pickup and Dropout Voltage Adjustments
■ Optional Features● Strip Heater (for Outdoor Installations)
● Connectivity for use with Remote Annunciator
● Position Indication Contact
● Fusing and Controls for Air-Cooled Generators
Page 9Confidential Property of Schneider Electric |
ASCO SERIES 185 - Residential■ Manual Configurations
● Deletes the Control Panel
● True Double Throw, Manual Operation Between Sources via External Handle
■ Service Entrance Configurations● Adds Manually Operated Circuit Breaker on Utility Source and
Bonding Jumper on Neutral and Ground
● Meets all NEC Requirements for Service Entrance Equipment
Page 10Confidential Property of Schneider Electric |
Residential Applications
MTS/ATS Application
`
■ ATS feeds a standby circuit breaker panel for specific branches during a power outage
● HVAC
● Refrigeration
● Sump Pump
Service Entrance ATS Application
■ Service Entrance Rated ATS feeds the whole house through the load center
Page 11Confidential Property of Schneider Electric |
ASCO SERIES 300 Automatic Transfer Switch■ 30A - 3000A
■ 120V - 600V
■ 2, 3 or 4 Pole Configuration
■ Single & Three Phase
■ Automatic, Non-Automatic, or Manual
■ Open Transition or Delayed Transition
■ Enclosure Options – Type 1, 3R, 12, 4X
■ Service Entrance Breaker Option
Page 12Confidential Property of Schneider Electric |
Auto vs Non-Auto vs ManualAutomatic
■ Detect Power Failures
■ Initiates Alternate Source
■ Transfer Load One Emergency is Acceptable
■ Sense Restoration of Normal
■ Retransfers Load To Normal
Non-Automatic
■ ATS Detect Power Failures
■ User Initiates Alternate Source (at the Generator)
■ Emergency Source becomes Acceptable
■ User Transfers Load via Push Button on ATS
■ ATS Senses Restoration of Normal
■ User Retransfers Load To Normal via Push Button on ATS
Page 13Confidential Property of Schneider Electric |
Auto vs Non-Auto vs ManualNon-Automatic
■ ATS Detect Power Failures (Control Panel & Indicating Lights Go Out)
■ User Initiates Alternate Source (at the Generator)
■ Emergency Source becomes Acceptable
■ User Transfers Load via Push Button on ATS
■ ATS Senses Restoration of Normal
■ User Retransfers Load To Normal via Push Button on ATS
Manual
■ User Detect Power Failures
■ User Initiates Alternate Source (at the Generator)
■ Emergency Source becomes Acceptable
■ User Transfers Load via Manual Operating Handle
■ User Senses Restoration of Normal
■ User Retransfers Load To Normal via Manual Operating HandlePage 14Confidential Property of Schneider Electric |
“Open” Transition– Conventional 2-position ATS
– True double throw (no intermediate position)
– Single operator:
• Solenoids, charge & close mechanism, linear
motor, or solenoid (mfr. / switch type
dependent)
• Most reliable & cost effective method of
transfer
N E
L
Load on
Normal
N E
L
Load Not
Connected
N E
L
Load on
Emergency
Transfer Switch Transition Types
Page 15Confidential Property of Schneider Electric |
“Delayed” Transition– Other Aliases - Center-Off, Neutral position
– Dual Operators & Switching Mechanisms
• Intermediate position for hot-to-hot transfers
• 0-5 minutes (user selectable based on
applicable motor inertia)
• Commonly used as an alternate to in-phase
transfer
• NOT recommended for life safety/critical
branches; good option for equipment loads
requiring load shed (with paralleling)
Transfer Switch Transition Types
Load on
Normal
Load Not
Connected
Load on
Emergency
N
L
E
N
L
E
N
L
E
Page 16Confidential Property of Schneider Electric |
ASCO SERIES 300 – Group G Controls
Page 17Confidential Property of Schneider Electric |
ASCO SERIES 300 – Standard Features■ In Phase Monitor
■ Engine Exerciser● Provides Weekly Automatic Testing Of An Engine Generator
Set With Or Without Load For 20 Minutes Fixed
■ Commit To Transfer● If Commit To Transfer Is Active, And 1C Timer Has Expired
Controller Will Continue Transfer Sequence To Emergency Even If Normal Returns Before Emergency Becomes Acceptable, Provided Controller Does Not Loss Power In The Middle Of The Sequence
■ Real Time Clock● Real Time Keeps Track Of Date Time
● Used To Enable Engine Exerciser To Operate At The Proper Day And Time And To Reference Entries Into Event Log
● Maintains The Following Parameters: Year, Month, Day Of Month, Day Of Week, Hours (Military), Minutes, Seconds And Tenths Of Seconds
● Parameters Are Initialized From User Interface Or Via Serial Communications Port
● Provides Automatic Update Of Time Per United States Daylight Savings Time
● With Battery Backup
■ Statistics And Diagnostics● Controller Monitors Several Values And Displays Them In
Statistics And Diagnostics Menu
● Total Transfer
● Total Transfers Due To Source Failures
● Days Energized
● Total Time N Available
● Total Time E Available
● Input And Output Status
■ About● Controller Displays Controller Part Number And Software
Part Number
■ Common Alarm● A Common Alarm Lights Up The Alert Indicator, And De-
energizes The Configured Common Alarm Output Relay For External Mounting
Over 5000 students rely on ASCO Power for dependable backup power to keep systems
and school facilities working 24/7.
Challenges
• Prevent power outages from impacting data center, class room, and other facilities.
• Meet compliance demands imposed by NEC, NFPA, and other codes and standards.
Solution
• ASCO – SERIES 300 Automatic Transfer Switches• Square D - Low Voltage Distribution Switchgear
Benefits
• Fast turnaround time• Engineer-Specified standardized package• Cost efficient solution• Reliable back-up power
“We’ve always received great support from ASCO … I’ll continue to use you and anyone you partner with on my projects.”
John TanRW Sullivan
“
Holyoke Community College, USA Reliable power for higher education facilities.
Page 19Confidential Property of Schneider Electric |
ASCO SERIES 300 – Configurable Accessories■ Accessory 1UP – UPS Control Panel Back Up
● Allows controller to run for 3 minutes without AC Power
■ Accessory 11BE – Exerciser Bundle● Upgrades to a fully programmable engine exercisers with up
to 7 different exercise routines
● Adds Event Log Display to show a minimum of 300 events included a date and time stamp and reason (if applicable)
● Enables RS-485 Communication Port
● Includes a programmable Common Alarm output contact
■ Accessory 18RX – Relay Expansion Module● Configurable to include addition output contacts:
■ Source Availability Contacts
■ Signal Before Transfer Contacts (Elevator Contacts)
■ Non-in-Automatic Contact
● Can be daisy-chained to another 18RX for additional contacts
■ Accessory 23G – Load Current Card● Displays current reading on the load side of the ATS
■ Accessory 30 - Load Shed Contacts● Contact to initiate disconnecting load from Emergency
Source
■ Accessory 62W – Transfer Alarm Contact● Audible Alarm With Silencing Feature To Signal Each Time
Transfer To Emergency Occurs:
● Includes Keyed Switch/Retransfer Delay Bypass, Momentary In Both Directions. Keyed Test Switch Maintained Transfer To Emergency
● In Lieu Of User Interface A Mounting Plate Is Provided For Discrete Components
REMEMBER - All of these accessories can be ordered as field installable kits!
Page 20Confidential Property of Schneider Electric |
• Accessory 1UP Backup Power (UPS)
• This Feature Allows Controller To Run For 3 Minutes Minimum Without AC Power
• Includes Ribbon Cable
• Shown With Cover Removed
• Available As Kit For Field Installation P/N 935149
21
Capacitor Bank
Ribbon Connection
Cover On
ASCO SERIES 300 – Configurable Accessories
Page 21Confidential Property of Schneider Electric |
• Accessory 11BE Feature Bundle
Consists Of The Following:
• A Fully Programmable Engine Exerciser With
Seven Independent Routines To Exercise The
Engine Generator, With Or Without Loads, On A
Daily Weekly, Bi – Weekly, Or Monthly Basis
• Event Log Display Which Shows The Event
Number, Time And Date Of Events, Event Type
And Reason (If Applicable). A Minimum Of 300
Events Can Be Stored
• RS - 485 Communications Port Enabled
• Common Alarm Output Contact (OP1)
• Field Installation Kit Available
22
ASCO SERIES 300 – Configurable Accessories
Page 22Confidential Property of Schneider Electric |
■ Accessory 18RX REX Module (Relay Expansion Module) ● Primary Function Of REX Module is to interface to the Dual
Operator Switching Device (DTTS)
● The REX Module provides the following relays
■ OP2 And OP3 Relays And Terminal Block Connections
● The default function of OP2 is to provide a common alarm output with the Common Alarm feature triggers
● Can Be Configured For:
− Common Alarm
− Accessory 31
− Not In Auto
■ 18B,18G Relay And Terminal Block Connections
● 18B Relay Is Energized When Emergency Source Is Accepted.
● 18G Relay Is Energized When Normal Source Is Accepted.
■ REX Module Can Be Daisy Chained To Allow Multiple Sets Of Contacts Via 2nd REX Module – Accessory 18RX2
ASCO SERIES 300 – Configurable Accessories
High Voltage Plug Connection
OP2 Contacts
OP3 Contacts
Additional Relays for Delayed Transition
• Accessory 23G*Load Current Card
• Load Current Metering Card, Measures Either Single (23GA) Or Three (23GB) Phase Load Current
• Includes Current Transformers (CT’s), And Shorting Block
• Parameters Can Be Viewed Via The User Interface
• Available As Kit For Field Installation, Either Current Card Only (P/N 935150) Or Current Card, Spilt Core CT’s, And Mounting Hardware
24
Current Metering
Card
Typical Ring Type
Current Transformer
Typical Split Core
CT For Field Retrofit
ASCO SERIES 300 – Configurable Accessories
Page 24Confidential Property of Schneider Electric |
ASCO SERIES 300 – Configurable Accessories■ Accessory 72EE – Ethernet Connectivity Module
● (2) CAN Ports And (4) RJ-45 Ethernet Ports
● Improved SMNP Capabilities, Increased List Of Parameters Available
● Improved SMTP Capabilities For Communication With Customer’s E Mail Server
● Remote Transfer Capability Via Embedded Web Page
● Provides a 10/100 Mbit Ethernet Interface To Transfer Switch
● Includes Embedded Web Pages And Access To Modbus Registers For Monitoring And Control With Encryption
● Includes 11BE Feature Bundle
■ Accessory 135L – Power Meter on Load Side● Measures, displays and provide single- or 3-phase Energy
and Power Information
Page 25Confidential Property of Schneider Electric |
■ Project Requirements
● (1) 400A ATS, Life Safety
● (1) 400A ATS, Critical Loads
● (2) 400A ATS, Equipment Loads
● Provisions for a Roll Up Generator
● Needs to communicate:
■ Show NFPA 110 Alarms
■ Display power information from ATS
■ Display generator information
■ Needs to provide email notifications
■ Leadtime Requirement < 7 days
Emergency Switchboard (By Others)
ATS-LS ATS-CR ATS-EQ1 ATS-EQ2
EthernetCable
ATS’s include 1UP (control panel back UPS power), 72EE (ethernet comm module) and 135L (power manager)
Roll Up Generator
Rapid Deployment Healthcare with Communication
Page 26Confidential Property of Schneider Electric |
ASCO SERIES 300 – Additional Configurations■ Service Entrance Rated – 3AUS
● Addition of circuit breaker on the Normal source
● Includes Neutral & Ground Disconnect Link
■ Breaker on Generator Source – 3AGS
■ Breaker on both Utility and Generator Source – 3APS
■ Power Transfer Load Center Configuration – 300L● Breaker on Normal & Emergency Source
● Internal Surge Protection
● Load Side Panelboard
■ Additional Accessories –● Shunt Trip on Circuit Breaker
● ERMS Switch
Page 27Confidential Property of Schneider Electric |
Over 14,000 residents feel more secure with ASCO’s reliable back-up power for critical
flood control.
Challenges
• Assurance of power supply during utility outage• Compliance with government regulation
Solution
• ASCO – SERIES 300 Service Entrance Transfer Switch
Benefits
• Provided reliable power products within budgetary constraints
• Expedited solution to meet a critical construction schedule
“ASCO is a well-known brand and we have a great working relationship.”
Pete GantzModern Group Power
Systems
“
Bloomsburg Flood Risk ManagementFlood management for a Pennsylvania community.
Page 28Confidential Property of Schneider Electric |
Normal
SourceEmergency
Generator
Utility
Breaker
Generator
Breaker In Type
3R Enclosure
SPD On
Normal
SPD On
Emergency
Branch Circuit Panelboard
200/400 Amp
SERIES 300
Automatic Transfer
Switch
Typical Cell Tower Installation
Page 29Confidential Property of Schneider Electric |
SERIES 300 PTLC (Power Transfer Load Center Switch)
Square D
Panelboard
200A
ATS
Surge
Devices
Group G
Controller
Square D
Utility and
Generator
Breakers
Integrated Solution Application
Page 30Confidential Property of Schneider Electric |
SERIES 300 PTLC (Power Transfer Load Center Switch)
Square D
Panelboard
200A
ATS
Surge
Devices
Group G
Controller
Square D
Utility and
Generator
Breakers
• Complete integrated solution
• Lower installation costs
• Components mounted, wired and tested at the factory
• Product of single manufacturer
• One Warranty for all Components
• Interconnect Wiring Diagrams And Operator’s Manual Provided With Each Switch
• Supplied In A Common Enclosure Indoor (Type 1) Or Outdoor (Type 3R)
• Integrated PTLC Listed To UL 67 And Includes UL 1008 Listed Transfer Switch
Integrated Solution
Page 31Confidential Property of Schneider Electric |
2017 NEC 700.3
32
700.3 (F) “ ….If the emergency system relies on a single alternate source of power which will be disabled for maintenance or repair, the emergency system shall include permanent switching means to connect a portable or temporary alternate source of power …. The permanent switching means to connect a portable or temporary alternate source of power shall comply with the following:
(1) Connection to the portable or temporary alternate source of power shall not require modification of the permanent system wiring.”
Be sure to join us again on April 30th for an in-depth look at the new NEC code!!
Page 32Confidential Property of Schneider Electric |
A Solution for NEC 700.3(F) Requirements
Page 33Confidential Property of Schneider Electric |
ASCO 3MTS & 3MTQ
34
Page 34Confidential Property of Schneider Electric |
180 residents plus skilled healthcare workers feel safe and secure with ASCO’s
reliable back-up power.
Challenges
• Securing well-being of patients during extended power outages
• Compliance with Florida mandate for 96 hours of backup power
Solution
• ASCO Value Added Automatic Transfer Switches• ASCO SERIES 300 Manual Transfer Switch with Quick
Connect Docking Station• ASCO Surge Protective Devices• SquareD - Low Voltage Distribution
Benefits
• Provided reliable power products within budget• Custom power system integration• Pre-packaged solution
“"ASCO provides a variety superior products to meet the back-up power needs from the largest hospital to the smallest nursing facility.“
Randall Power
“
Greystone Health Providing our clients with peace of mind, safety and improved quality of life.
Page 35Confidential Property of Schneider Electric |
What design considerations push us out of pre-configuration?■ Any accessory outside ones listed previously
■ Bypass Isolation
■ Custom Lugs Configurations
■ Closed Transition (Active or Passive) & Utility Requirements
Page 36Confidential Property of Schneider Electric |
How do I get something quickly?
■ Contact your local field sales office.
■ Subscribe to the ASCO Stock List● Provided daily/weekly updates on items in stock and available for quick
shipment.
● Email: [email protected]
● Subject: “Please ADD me to the Automated Inventory Stocking List Enter the following information”■ Company Name:
■ Contact Name:
■ Address:
■ City:
■ State:
■ Zip:
■ Email:
■ Phone #
■ Territory:
■ Type of business
An email with how to join will be sent out after the presentation.
Page 37Confidential Property of Schneider Electric |