Presentation on Power Transformer & Distribution Transformer Protection

  • Upload
    nisargo

  • View
    314

  • Download
    10

Embed Size (px)

Citation preview

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    1/47

    1

    Presentation on Power Transformer &

    Distribution Transformer Protection

    Presented by-

    Ch. Alamgir Hossain

    Deputy General Manager

    System Protection & Metering CirclePGCB,Dhaka

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    2/47

    2

    Protection of Transformer

    Requirements of Transformer Protection-

    -To protect the equipment form external and internal faults

    Type of Transformer Faults:A: Internal Faults

    1.Earth Fault

    2.Phase to Phase Fault

    3.Inter-turn Fault

    4.Core Fault5.Tank Fault- ex. Loss of Oil

    6.Slug Formation

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    3/47

    3

    External Faults:

    1. Over Loading Causes I2

    R losses2. System Faults- Causes Mechanical stress to transformer

    3. Over Voltage-

    - Transient Over Voltage- LAs are provided

    - System O/V- Causes Over Flexing which increases Iran

    losses and damage insulation.

    Protection of Transformer: cont.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    4/47

    4

    Protection of Transformer: cont.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    5/47

    5

    Protection of Transformer: cont.

    Inrush Current A transformer steel core's retains a static magnetic field when power is removed.

    When power is then reapplied, the residual field will cause a high inrush

    current until the effect of the remnant magnetism is reduced, usually after a

    few cycles of the applied alternating current. Transformer protection devices must be selected to allow this harmless inrush to

    pass.

    When a transformer is energized, the magnetizing inrush currents are estimated as

    multiples up to 08 to 10 times of the transformer's rated current.

    Factors that affect the Inrush Current

    The source impedance

    The size of the transformer

    The point of wave when the switch closes

    The magnetic properties of the core

    The remanence magnetism of the core

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    6/47

    6

    Protection of Transformer: cont. Protections provided by external protective relays:

    Transformer Differential Protection (87T)

    Restricted Earth Fault (REF) Protection (87N)Time Delayed Over Current & Earth Fault Protection (51/51N)

    Instantaneous Over Current & Earth Fault Protection (50/50N)

    Thermal Overload Protection (49)

    Over Fluxing Protection (24)

    Mechanical/Self Protection (Provided within the transformer ):

    Main Tank Buchholz Protection

    OLTC Buchholz Protection

    Pressure Relief Device (PRD) Protection

    Winding Temperature ProtectionOil Temperature Protection

    Oil Level Alarm

    Main Tank Buchholz Alarm

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    7/47

    7

    Protection of Transformer: cont.

    Conventional Protection Scheme of a Two WindingTransformer

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    8/47

    8

    Protection of Transformer: cont.

    Conventional Protection Scheme of a Two Winding TransformerIncluding REF

    87N

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    9/47

    9

    Protection of Transformer: cont.

    Conventional Protection Scheme of a Three Winding Transformer

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    10/47

    10

    Protection of Transformer: cont.

    Conventional Protection Scheme of an Auto-Transformer

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    11/47

    11

    Protection of Transformer: cont.

    Grouping of protection:

    As transformer protections are not duplicated. So that

    protection functions are divided in two groups to obtain some

    redundancy.

    1. Group A Protection

    2. Group B protection

    The group A and group B protection are connected to separateDC source.

    All the Group-A and Group-B protection functions energize

    separate lockout relays (86-1 & 86-2) respectively to trip the

    circuit breaker during fault.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    12/47

    12

    Protection of Transformer: cont.

    Generally Group-A protection consists of-

    Differential Protection (87T)

    Time Delayed Over Current & Earth Fault Protection (51/51N)_HV

    Instantaneous Over Current & Earth Fault Protection (50/50N)_HV

    Thermal Over Load Protection (49)

    Main Tank Buchholz Relay Protection

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    13/47

    13

    Protection of Transformer: cont.

    Generally Group-B protection consists of-

    Restricted Earth Fault Protection (87N)

    Time Delayed Over Current & Earth Fault Protection (51/51N)_LV

    Instantaneous Over Current & Earth Fault Protection (50/50N)_LV

    OLTC Buchholz Relay Protection

    Pressure Relief Device (PRD) Protection

    Winding Temperature Protection

    Oil Temperature Protection

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    14/47

    14

    Protection of Transformer: cont.

    Transformer Differential Protection (87T)Basics:

    Transformer differential protection is a unit

    scheme that compares the current on the primary

    side of a transformer with that of the secondary

    side.

    If any difference in HV & LV currents exists

    (beyond the setting value) it is assumed that the

    transformer has developed a fault and the relayinstantaneously trips the relevant circuit

    breakers.

    The principle of operation is made possible by

    virtue of the fact that large transformers are very

    efficient and hence under normal operation

    power-in equals power-out.

    Transformer differential protection detects faults

    within the differential protected zone, including

    inter-turn short circuits. Fig: Zone of Differential Protection

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    15/47

    15

    Protection of Transformer: cont.

    Transformer Differential Protection (87T)

    Principle of Operation:

    The operating principle employed by transformer differential protection is the Merz-

    Price circulating current system as shown in the figure.Under normal conditions I1and I2 are made equal and opposite such that the resultant

    current through the relay is zero.

    An internal fault produces an unbalance or 'spill' current that is detected by the relay,

    leading to operation to isolate the fault.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    16/47

    16

    Protection of Transformer: cont.

    Transformer Differential Protection (87T)

    Transformer Differential

    Protection (87T) Relay

    Types:

    High Impedance Type

    Low Impedance Type

    In a low impedance

    protection scheme, thedifferential protection can

    have the protection

    characteristic set typically

    with a two slope restraint

    characteristic. 87T relays are generally of

    low impedance type. Id min

    1 5 10

    1

    5

    10

    I

    High

    Trips

    Blocks

    Differential current |I1+I2|

    Unrestrained

    < 25

    Irestrain(|I1|+ |I2|)/2

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    17/47

    17

    Protection of Transformer: cont.

    Transformer Differential Protection (87T)

    Transformer Differential Protection With Matching CT

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    18/47

    18

    Protection of Transformer: cont.

    Transformer Differential Protection (87T)

    Factors to be considered in selecting 87T relay:

    Extremely stable under through fault conditions andmagnetic inrush.

    Very fast to operate for an internal fault

    Able to restrain second harmonics and block fifthharmonics.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    19/47

    19

    Protection of Transformer: cont.

    Restricted Earth Fault Protection (87N)

    Basics:

    Conventional earth fault protection using over-current

    elements fails to provide adequate protection fortransformer.

    Restricted earth fault, or zero-sequence differential

    protection is implemented in transformer star winding. Its a unit protection and operation of relay is

    instantaneous.

    It offers a significant improvement in sensitivity overtraditional differential protection

    It does not respond to load current.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    20/47

    20

    Protection of Transformer: cont.

    Restricted Earth Fault Protection (87N)

    Basics:

    Ground current in the transformer neutral is used as areference and is compared to zero-sequence current at theterminals to determine if a fault is internal to the transformer.

    The relay is operative for faults within the region between

    current transformers, that is, for faults on the star winding inquestion.

    The relay will remain stable for all faults outside this zone.

    87N relays are also available high impedance and low

    impedance type. Generally 87N relays are of High Impedance type.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    21/47

    21

    Protection of Transformer: cont.

    Restricted Earth Fault Protection (87N)

    Basic 87N Scheme:

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    22/47

    22

    Protection of Transformer: cont.

    Restricted Earth Fault Protection (87N)

    Fig. Restricted earth fault protection : (a) neutral earthed within the

    protected zone (b) neutral not earthed within the protected zone

    (a)

    (b)

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    23/47

    23

    Protection of Transformer: cont.

    Time Delayed/Instantaneous Over Current & Earth FaultProtection (50/50N & 51/51N)

    Used on all feeding circuits of transformer

    Provide back up for internal faults

    Also provide back up for system faults

    Instantaneous high element51/51N can be definite time or inverse time to

    achieve proper relay co-ordination from

    upstream to downstream

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    24/47

    24

    The transformer winding hot-spot temperature is

    another quantity that should be used for protection of

    transformers.

    Protection based on winding hot-spot temperature can

    potentially prevent short circuits and catastrophic

    transformer failure, as excessive winding hot-spot

    temperatures cause degradation and eventual failure of

    the winding insulation.

    During over load conditions excessive load current

    through the transformer causes over heating of the

    winding and insulating oil.

    Protection of Transformer: cont.

    Thermal Overload Protection (49)

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    25/47

    25

    Protection of Transformer: cont.

    Thermal Overload Protection (49)

    To prevent damage of the winding insulation thermal

    overload protection is used.

    It is basically a over current protection implemented

    in both windings of the transformer

    Tripping is time delayed. First alarm is generated then

    finally tripping occurs.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    26/47

    26

    Time

    Rise of temperature

    Trip

    Alarm

    Protection of Transformer: cont.

    Thermal Overload Protection (49)

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    27/47

    27

    Protection of Transformer: cont.

    Over Fluxing Protection (24)

    Transformer over-fluxing can be a result of

    Overvoltage

    Low system frequencyA transformer is designed to operate at or below a

    maximum magnetic flux density in the transformer core.

    Above that design limit the eddy currents in the core andnearby conductive components cause overheating which

    within a very short time may cause severe damage.

    The magnetic flux in the core is proportional to thevoltage applied to the winding divided by the impedance of

    the winding.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    28/47

    28

    Protection of Transformer: cont.

    Over Fluxing Protection (24)

    The flux in the core increases with either increasing voltage ordecreasing frequency-

    EMF = E = 4.44fmN =>E/f = 4.44 mN

    During startup or shutdown of generator-connectedtransformers, or following a load rejection, the transformer mayexperience an excessive ratio of volts to hertz, that is, becomeoverexcited.

    Overexcited transformers become overheated and damaged

    Over fluxing protection is specially required for GeneratorTransformers

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    29/47

    29

    Protection of Transformer: cont.

    Mechanical Protection

    There are several mechanical protection relays installed

    on transformers .

    Transformer mechanical protection relays operate by sensing

    operational parameters like oil pressure, oil level, gas evolved,

    oil & winding temperature.Generally these relays are built in features of power and

    distribution transformers having capacity more than 10MVA.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    30/47

    30

    Protection of Transformer: cont.

    Mechanical Protection: cont.Buchholz Relays (63):

    Buchholz relay is a mechanical protection device for monitoring

    the gas and oil movements in oil immersed transformers.

    It is used on practically all power transformers with the

    exception of small distribution transformers.

    In addition with the main tank Buchholz relay another Buchholz

    relay is mounted on OLTC (On Load Tap Changer).

    Location of main tank Buchholz relay is given as follows:

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    31/47

    31

    Fig. Buchholz Relay

    Protection of Transformer: cont.

    Buchholz Relay: contd.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    32/47

    32

    The internal mechanism of a Buchholz relay mainly comprises two

    floats.

    During normal operation, the relay is completely filled with oil

    keeping the floats in their top limit or reset position.

    The contact mechanisms in the relays respond to:

    Slight faults causing a slow evolution of gas in the transformer (e.g.

    overheating).

    Serious faults creating an immediate surge of oil (e.g. short-

    circuits etc.).

    Unattended Oil leakage may lead to operation of the Buchholz relay.

    Protection of Transformer: cont.

    Buchholz Relay: contd.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    33/47

    33

    Schematic Diagram of a conventional Buchholz Relay Arrangement

    Protection of Transformer: cont.

    Buchholz Relay: contd.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    34/47

    34

    Schematic Diagram of a modern Buchholz Relay (Oil Surge) Arrangement

    Protection of Transformer: cont. Buchholz Relay: contd.

    An oil-surge detection feature of the Buchholz relay will trip the upstream

    circuit-breaker instantaneously if a surge of oil occurs in the pipe connecting

    the main tank with the conservator tank.

    Such a surge can only occur due to the displacement of oil caused by a rapidly

    formed bubble of gas, generated by an arc of short-circuit current in the oil.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    35/47

    35

    Schematic Diagram of a Buchholz Relay Mounting Arrangement

    Protection of Transformer: cont.

    Buchholz Relay: contd.

    = 3-5

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    36/47

    36

    Buchholz Relay Operation:

    When a slight fault occurs in the transformer, the small bubbles of gas which

    pass upwards towards the oil conservator tank are trapped in the relay housingthis causing its oil level to fall.

    As a result, the upper float drops and activates the external alarm switch.

    If gas continues to be generated then the second float operates the second

    switch that is normally used to isolate (trip) the transformer.

    If an arc forms, gas accumulation is rapid, and oil flows rapidly into the

    conservator which is called oil surge.

    This flow of oil operates a switch attached to a vane located in the path of the

    moving oil.

    This switch normally will operate a circuit breaker to isolate the apparatus

    before the fault causes additional damage

    Protection of Transformer: cont.

    Buchholz Relay: contd.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    37/47

    37

    Protection of Transformer: cont.

    Pressure Relief Device (PRD)

    Basics:

    Pressure Relief Device is a safety element of the transformer employs to prevent

    heavy damages of the tank in the case of sudden rise of the internal pressure.

    These device has been designed in order to remove the excess pressure in a very

    short time as soon as the pressure in the tank rises above predetermined safe limit

    PRD operates and allows the pressure to drip instantaneously and avoids damage

    to transformer body.

    During internal faults of a power transformer, there will be an increase of

    temperature associated with formation of gases, impurities in oil and thus

    increase in pressure.

    This pressure is sufficient to damage the transformer.

    The pressure relief device is applied to prevent the transformer from this

    danger

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    38/47

    38

    Protection of Transformer: cont.

    Pressure Relief Device (PRD): cont.

    Fig. Pressure Relief Device

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    39/47

    39

    Protection of Transformer: cont.

    Pressure Relief Device (PRD): cont.The pressure relief device consists of a spring which normally is uncompressed

    and when the pressure increased in the transformer, the spring get compressed and

    give a path of gases to go out of the transformer.

    Compressing the spring will close an electrical contact, and this contact will give trip to

    circuit breakers associated with alarm.Following Figure (shows the pressure relief device in the normal condition (before the

    fault occurrence):

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    40/47

    40

    Protection of Transformer: cont.

    Pressure Relief Device (PRD): cont.

    Following figure shows the fault condition at which the

    compressed gases get passage to let the gases out from the

    transformer.

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    41/47

    41

    Protection of Transformer: cont.

    Winding & Oil Temperature Protection

    By making a "Thermal Image" of the

    winding the Winding Temperature Indicator,

    simulates the winding temperature.The temperature of the winding depends on

    the transformer load (i.e. the current through

    the winding) and the temperature of the cooling

    medium (the oil).

    Temperature is measured with a bulb in apocket.

    It has a specially designed heating element,

    to measure the transformer load.

    This heating element is a thermal model of

    the winding.The heating element is connected to the

    current transformer (CT) via a Matching

    Resistance or a Matching Unit, to allow setting

    the correct winding temperature gradient.

    Winding Temperature Indicator

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    42/47

    42

    Protection of Transformer: cont.

    Winding Temperature Protection: cont.

    Generally winding temperature indicator consists of four contacts

    which are normally open and closes in series according to pre set

    closing value (temperature).

    These contacts can be assigned as follows:-1.The first contact is used for automatic operation of first fan

    group.

    2.The second contact is used for automatic operation of second fangroup, this value is higher than the first contact setting.

    3.If the cooling fans are not sufficient to retain the transformer

    temperature to its normal value, the third contact is applied to feed

    alarm circuit.

    4.As a last step, the fourth contact is applied for tripping to prevent

    the transformer from high temperatures. Normally it trips the load side

    breaker, (i.e. the secondary side CB)

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    43/47

    43

    Protection of Transformer: cont.

    Oil Temperature Protection

    Oil Temperature Indicator:

    Oil temperature indicator is

    similar to winding temperatureindicator except that it depends only

    on the temperature transferred by the

    bulb (no current transformer is used).

    This consists only of two contacts.

    These contacts are similar to the

    third and the fourth contacts of the

    winding temperature indicator butwith preset values less than

    winding temperature indicator by

    approximately 5-10 degrees.

    Protection of Transformer: cont

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    44/47

    44

    Transformer Dehydrating Breather:

    A transformer breather is an

    accessory of an oil filled typetransformer which is attached to the

    oil conservator tank.

    When the insulating oil of the

    transformer gets heated up, itexpands and goes back to the

    conservator tank and subsequently

    pushes the dry air out of the

    conservator tank through the

    breather

    Protection of Transformer: cont.

    Transformer Dehydrating Breather

    P t ti f T f t T f D h d ti B th

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    45/47

    45

    Protection of Transformer: cont. Transformer Dehydrating Breather

    It is filled with some desiccating agent,e.g. silica gel.

    When the oil cools down, it retracts andsucks fresh air from the atmospherethrough the breather

    the silica gel dries up the moisture

    content of the air that goes back in tothe conservator tank.

    If the silica gel looses its moistureabsorbing capability then the oil in theconservator gets contaminated andeventually losses the insulatingproperty.

    Protection of Transformer: cont.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    46/47

    46

    Protection of Transformer: cont.

    Oil Level Indicator

    Oil level indicators with magnetic joint are usually used on

    transformers' conservators.

    It is mounted on the body of the conservator.

    Its function is to give a visual alarm of the oil level contained in

    the conservator.

    Furthermore they are provided with micro switches to signal the

    alarm in case the oil level reaches its minimum and/or maximum.

  • 7/23/2019 Presentation on Power Transformer & Distribution Transformer Protection

    47/47

    47

    Thanks to All