Presentation May 2012

Embed Size (px)

DESCRIPTION

Presentation May 2012

Citation preview

  • 5/20/2018 Presentation May 2012

    1/47

    IEEE Baton Rouge

    Grounding for Electrical Power Systems

    (Low Resistance and High ResistanceDesign)

  • 5/20/2018 Presentation May 2012

    2/47

    Low Resistance Grounding Advantages/Disadvantages Design Considerations

    High Resistance Grounding Advantages/Disadvantages Design Considerations

    Generator Grounding

    Single/Multiple arrangements

  • 5/20/2018 Presentation May 2012

    3/47

  • 5/20/2018 Presentation May 2012

    4/47

    Impedance selected to limit line-to-ground fault current (normallybetween 100A and 1000A asdefined by IEEE std. 142-2007section 1.4.3.2)

  • 5/20/2018 Presentation May 2012

    5/47

    Advantages Eliminates high transient overvoltages

    Limits damage to faulted equipment

    Reduces shock hazard to personnel

    Disadvantages Some equipment damage can still occur

    Faulted circuit must be de-energized

    Line-to-neutral loads cannot be used.

    ccc IabIIcIr

    A B

    C

    3 Load

    or Network

    Source

    N

    NeutralGroundingResistor

  • 5/20/2018 Presentation May 2012

    6/47

    Most utilized on Medium Voltage Some 5kV systems

    Mainly 15kV systems

    Has been utilized on up to 132kV systems (rare)

    Used where system charging current may beto high for High Resistance Grounding

    ccc IabIIcIr

    A B

    C

    3 Load

    or Network

    Source

    N

    NeutralGroundingResistor

  • 5/20/2018 Presentation May 2012

    7/47

    Resistor Amperage (ground fault let through current) System Capacitance

    System Bracing

    System Insulation

    Relay Trip points (Time current curve)

    Selective tripping Resistance increase with temperature

    Resistor time on (how long the fault is on the system)

    Single Phase Loads

  • 5/20/2018 Presentation May 2012

    8/47

    Conductor

    Cableinsulation

    Cable tray

    Every electrical system has some natural capacitance. The capacitivereactance of the system determines the charging current.

    Zero-sequence Capacitance: 0 =106

    2F/phase

    Charging Current: 30 =2

    106 A

  • 5/20/2018 Presentation May 2012

    9/47

  • 5/20/2018 Presentation May 2012

    10/47

    During an arcing or intermittentfault, a voltage is held on the systemcapacitance after the arc isextinguished. This can lead to asignificant voltage build-up whichcan stress system insulation andlead to further faults.

    In a resistance grounded system, theresistance must be low enough toallow the system capacitance to

    discharge relatively quickly.

    Only discharges if Ro< Xco, so Ir> Ixcoper IEEE142-2007 1.2.7)

    That is, resistor current must be greater than capacitive charging current.

  • 5/20/2018 Presentation May 2012

    11/47

    Total Fault current is the vector sum of capacitive charging currentand resistor current

    = 2 + 0

    2

    So, if IR= IC0, then IF= 1.414 IR

    Total fault current must not exceed the value for which the system isbraced.

    In many cases, the system is already braced for the three-phase faultcurrent which is much higher than the single line-ground fault

    current of a resistance grounded system.

  • 5/20/2018 Presentation May 2012

    12/47

    Resistance grounded systems must be insulated for full line-linevoltage with respect to ground.

    Surge Arrestor Selection: NEC 280.4 (2) Impedance or UngroundedSystem. The maximum continuous operating voltage shall be thephase-to-phase voltage of the system.

    Cables: NEC Table 310.13E allows for use of 100% Insulation level,but 173% is recommended for orderly shutdown.

    VAG

    VBGVCG

    VAG

    VBG

    Un-faulted Voltages to ground Faulted Voltages to ground (VCG= 0)

  • 5/20/2018 Presentation May 2012

    13/47

    Properly rated equipment prevents Hazards.

    A B

    C

    3 Load

    HRG

    480V Wye Source

    N

    0V

    2400V

    Ground A

    Cables, TVSSs, VFDs, etc. and otherequipment must be rated forelevated voltages.

    0V

    4160V

    4160VGR

  • 5/20/2018 Presentation May 2012

    14/47

    N

    G

    R

    CTs and relays must bedesigned such that systemwill trip on a fault of themagnitude of the groundfault current, but not ontransient events such aslarge motor startup.

    Network protection schemeshould try to trip faultlocation first, then goupstream.

  • 5/20/2018 Presentation May 2012

    15/47

    Residual connected CTs Zero Sequence CT

  • 5/20/2018 Presentation May 2012

    16/47

    Widely varying use of resistance material in the industry. Different coefficients of resistivity for these materials.

    Coefficient of resistivity typically increases with temperature of the material, thusresistance of the NGR increases while the unit runs.

    As resistance increases, current decreases.

    Relay current trip curve must fall below the current line in the graph below.

    5.5

    6

    6.5

    7

    7.5

    300

    320

    340

    360

    380

    400

    1 2 3 4 5 6 7 8 9 10

    NGR Resistance vs Current

    Current

    Resistance

  • 5/20/2018 Presentation May 2012

    17/47

    Normally, protective relaying will tripwithin a few cycles.

    IEEE 32 defines standard resistor ontimes. Lowest rate is 10 seconds, butcould potentially go less to savematerial/space.

    Can go as high as 30 or 60 secondsas required (rare).

    Extended or Continuous ratings arealmost never used in this applicationdue to the relatively high fault

    currents.

    IEEE Std 32Time Rating and Permissible

    Temperature Rise for Neutral

    Grounding Resistors

    Time Rating

    (On Time)

    Temp Rise (deg

    C)

    Ten Seconds

    (Short Time)760oC

    One Minute

    (Short Time)760oC

    Ten Minutes(Short Time)

    610oC

    Extended Time 610oC

    Continuous 385oC

  • 5/20/2018 Presentation May 2012

    18/47

    A B

    C

    3 Load

    HRG

    480V Wye Source

    N

    Phase and Neutral wires in same conduit.If faulted, bypass HRG, thus, -G fault.

    No line-to-neutral loads allowed, preventsHazards.

    NGR

  • 5/20/2018 Presentation May 2012

    19/47

    Add small 1:1

    transformer and solidlyground secondary for 1loads (i.e. lighting).

  • 5/20/2018 Presentation May 2012

    20/47

  • 5/20/2018 Presentation May 2012

    21/47

    Impedance selected to limit line-to-ground fault current (normally< 10A as defined by IEEE std.142-2007 section 1.4.3.1)

    Ground detection system required

    System is alarm and locate insteadof trip.

    Source

    (Wye)

    HRG C

    BA

    N

  • 5/20/2018 Presentation May 2012

    22/47

    Advantages

    Eliminates high transient overvoltages Limits damage to faulted equipment

    Reduces shock hazard to personnel

    Faulted circuit allowed to continueoperating

    Disadvantages

    Nuisance alarms are possible. Line-to-neutral loads cannot be used.

    ccc IabIIcIr

    A B

    C

    3 Loador Network

    Source

    N

    NeutralGrounding

    Resistor

  • 5/20/2018 Presentation May 2012

    23/47

    Most utilized on Low Voltage Many 600V systems Some 5kV systems

    Has been utilized on up to 15kV systems (rare)

    ccc IabIIcIr

    A B

    C

    3 Loador Network

    Source

    N

    NeutralGrounding

    Resistor

  • 5/20/2018 Presentation May 2012

    24/47

    Resistor Amperage (ground fault let through current) System Capacitance

    Alarm notification

    Fault Location Pulsing

    Data Logging

    Relay Coordination (What to do if there is a second fault)

    System Insulation

    Personnel training

  • 5/20/2018 Presentation May 2012

    25/47

    Conductor

    Cableinsulation

    Cable tray

    Every electrical system has some natural capacitance. The capacitivereactance of the system determines the charging current.

    Zero-sequence Capacitance: 0 =106

    2F/phase

    Charging Current: 30 =2

    106A

  • 5/20/2018 Presentation May 2012

    26/47

    During an arcing or intermittentfault, a voltage is held on the systemcapacitance after the arc isextinguished. This can lead to asignificant voltage build-up whichcan stress system insulation andlead to further faults.

    In a resistance grounded system, theresistance must be low enough toallow the system capacitance todischarge relatively quickly.

    Only discharges if Ro< Xco, so Ir> Ixcoper IEEE142-2007 1.2.7)

    That is, resistor current must be greater than capacitive charging current.

  • 5/20/2018 Presentation May 2012

    27/47

    Major Contributors to system capacitance: Line-ground filters on UPS systems

    Line-ground smoothing capacitors

    Multiple sets of line-ground surge arrestors

    All of these can make implementation ofHRG difficult

  • 5/20/2018 Presentation May 2012

    28/47

    HRG systems are alarm andlocate systems

    Alarm methods: Audible horn Red fault light

    Dry contact toPLC/DCS/SCADA opens

    DCS/SCADA polling ofunit via Modbus RS-485

    Ethernet

  • 5/20/2018 Presentation May 2012

    29/47

    HRG

    480V Wye Source

    C

    B A

    55.4ohms

    Operator controlledcontactor shorts outpart of the resistor

    Ideally, the increasein current is twice

    that of the normalfault current, unlessthat level is unsafe.

  • 5/20/2018 Presentation May 2012

    30/47

    NOTE:Tracking a ground fault can only be done on anenergized system. Due to the inherent risk of

    electrocution this should only be performed by trainedand competent personnel.

  • 5/20/2018 Presentation May 2012

    31/47

    ZSCT

    Meter

    ZSCT

    MeterMeter

    ZSCT

    0A

    55A

    50A

    50A80A

    80A

    50A 50A 50A

    50A50A55A30A 30A 30A

    30A30A30A

    MotorMotor

    5A

    5A0A

    5A

    HRG

    5A

    480V Wye Source85A

    C

    BA

    55.4

    ohms

    Meter reading will alternatefrom 5A to 10A every 2

    seconds.

    Alternatives to Manual location: Add zero sequence CTs & ammeters to each feeder Use metering inherent to each breaker (newer equipment only)

  • 5/20/2018 Presentation May 2012

    32/47

    HRG systems with data logging can be used to locateintermittent ground faults

    Example: Heater with ground fault comes on at 11:00am and then

    turns off at 11:01am

    Normal Pulsing will not locate since the fault will be gone. HRG Data logging can help locate faulted equipment in

    conjunction with DCS/SCADA data records

    Fault time

    frame

    Equipment

    On

  • 5/20/2018 Presentation May 2012

    33/47

    If there is a second groundfault on another phase, itis essentially a phase-phase fault and at leastone feeder needs to trip

    Network protectionscheme should bedesigned to trip the lowestpriority feeder first, thenthe next, and then moveupstream.

  • 5/20/2018 Presentation May 2012

    34/47

    Check MCC GF pickup ratings to be sure the small ground fault currentvalues do not trip off the motor on the first ground fault.

    Also, fusing on small motors can open during a ground fault. ConsultNEC Table 430.52 for Percentage of full load current fuse ratings. Mostare 300% FLC.

  • 5/20/2018 Presentation May 2012

    35/47

    Resistance grounded systems must be insulated for full line-linevoltage with respect to ground.

    NEC 285.3: An SPD (surge arrestor or TVSS) device shall not beinstalled in the following: (2) On ungrounded systems, impedancegrounded systems, or corner grounded systems unless listedspecifically for use on these systems.

    VAG

    VBGVCG

    VAG

    VBG

    Un-faulted Voltages to ground Faulted Voltages to ground (VCG= 0)

  • 5/20/2018 Presentation May 2012

    36/47

    Properly rated equipment prevents Hazards.

    A B

    C

    3 Load

    HRG

    480V Wye Source

    N

    0V

    277V

    Ground A

    Cables, TVSSs, VFDs, etc. and otherequipment must be rated forelevated voltages.

    0V

    480V

    480V

  • 5/20/2018 Presentation May 2012

    37/47

    Common Mode Capacitors provide pathfor Common-mode currents in outputmotor leads

    MOVs protect against Transients

  • 5/20/2018 Presentation May 2012

    38/47

    Ground fault in Drive #1caused Drive 2 to fault on

    over-voltage

    Drive 3 was not affected

  • 5/20/2018 Presentation May 2012

    39/47

    Factory optioncodes exist to

    remove the internaljumpers

  • 5/20/2018 Presentation May 2012

    40/47

    Per NEC 250.36, personnel must be trained onImpedance Grounded systems. Training should:

    Establish seriousness of a fault Discuss location methods Familiarize personnel with equipment

  • 5/20/2018 Presentation May 2012

    41/47

  • 5/20/2018 Presentation May 2012

    42/47

    Fault current Paralleled generators Common Ground Point

    Separate Ground Point

  • 5/20/2018 Presentation May 2012

    43/47

    In most generators, the zero-sequenceimpedance is much less than the positive ornegative sequence impedances.

    Due to this, resistance grounding must be

    used unless the generator is specificallydesigned for solid grounding service.

    = =

  • 5/20/2018 Presentation May 2012

    44/47

    Generators Grounded through a single impedance must be the sameVA rating and pitch to avoid circulating currents in the neutrals

    Each Neutral must have a disconnecting means for maintenance asgenerator line terminals can be elevated during a ground fault.

    Not recommended for sources that are not in close proximity

  • 5/20/2018 Presentation May 2012

    45/47

    Separately grounding prevents circulating currents

    Multiple NGRs have a cumulative effect on ground fault current i.e.the total fault current is the sum of all resistor currents plus

    charging current. Can be difficult to coordinate tripping or fault location

    If total current exceeds about 1000A, single ground point should beconsidered.

  • 5/20/2018 Presentation May 2012

    46/47

    IEEE 242-2001 IEEE 142-2007

    NEC

    IEEE 32

  • 5/20/2018 Presentation May 2012

    47/47