Upload
ahmed-seddik
View
13
Download
0
Tags:
Embed Size (px)
DESCRIPTION
Presentation May 2012
Citation preview
5/20/2018 Presentation May 2012
1/47
IEEE Baton Rouge
Grounding for Electrical Power Systems
(Low Resistance and High ResistanceDesign)
5/20/2018 Presentation May 2012
2/47
Low Resistance Grounding Advantages/Disadvantages Design Considerations
High Resistance Grounding Advantages/Disadvantages Design Considerations
Generator Grounding
Single/Multiple arrangements
5/20/2018 Presentation May 2012
3/47
5/20/2018 Presentation May 2012
4/47
Impedance selected to limit line-to-ground fault current (normallybetween 100A and 1000A asdefined by IEEE std. 142-2007section 1.4.3.2)
5/20/2018 Presentation May 2012
5/47
Advantages Eliminates high transient overvoltages
Limits damage to faulted equipment
Reduces shock hazard to personnel
Disadvantages Some equipment damage can still occur
Faulted circuit must be de-energized
Line-to-neutral loads cannot be used.
ccc IabIIcIr
A B
C
3 Load
or Network
Source
N
NeutralGroundingResistor
5/20/2018 Presentation May 2012
6/47
Most utilized on Medium Voltage Some 5kV systems
Mainly 15kV systems
Has been utilized on up to 132kV systems (rare)
Used where system charging current may beto high for High Resistance Grounding
ccc IabIIcIr
A B
C
3 Load
or Network
Source
N
NeutralGroundingResistor
5/20/2018 Presentation May 2012
7/47
Resistor Amperage (ground fault let through current) System Capacitance
System Bracing
System Insulation
Relay Trip points (Time current curve)
Selective tripping Resistance increase with temperature
Resistor time on (how long the fault is on the system)
Single Phase Loads
5/20/2018 Presentation May 2012
8/47
Conductor
Cableinsulation
Cable tray
Every electrical system has some natural capacitance. The capacitivereactance of the system determines the charging current.
Zero-sequence Capacitance: 0 =106
2F/phase
Charging Current: 30 =2
106 A
5/20/2018 Presentation May 2012
9/47
5/20/2018 Presentation May 2012
10/47
During an arcing or intermittentfault, a voltage is held on the systemcapacitance after the arc isextinguished. This can lead to asignificant voltage build-up whichcan stress system insulation andlead to further faults.
In a resistance grounded system, theresistance must be low enough toallow the system capacitance to
discharge relatively quickly.
Only discharges if Ro< Xco, so Ir> Ixcoper IEEE142-2007 1.2.7)
That is, resistor current must be greater than capacitive charging current.
5/20/2018 Presentation May 2012
11/47
Total Fault current is the vector sum of capacitive charging currentand resistor current
= 2 + 0
2
So, if IR= IC0, then IF= 1.414 IR
Total fault current must not exceed the value for which the system isbraced.
In many cases, the system is already braced for the three-phase faultcurrent which is much higher than the single line-ground fault
current of a resistance grounded system.
5/20/2018 Presentation May 2012
12/47
Resistance grounded systems must be insulated for full line-linevoltage with respect to ground.
Surge Arrestor Selection: NEC 280.4 (2) Impedance or UngroundedSystem. The maximum continuous operating voltage shall be thephase-to-phase voltage of the system.
Cables: NEC Table 310.13E allows for use of 100% Insulation level,but 173% is recommended for orderly shutdown.
VAG
VBGVCG
VAG
VBG
Un-faulted Voltages to ground Faulted Voltages to ground (VCG= 0)
5/20/2018 Presentation May 2012
13/47
Properly rated equipment prevents Hazards.
A B
C
3 Load
HRG
480V Wye Source
N
0V
2400V
Ground A
Cables, TVSSs, VFDs, etc. and otherequipment must be rated forelevated voltages.
0V
4160V
4160VGR
5/20/2018 Presentation May 2012
14/47
N
G
R
CTs and relays must bedesigned such that systemwill trip on a fault of themagnitude of the groundfault current, but not ontransient events such aslarge motor startup.
Network protection schemeshould try to trip faultlocation first, then goupstream.
5/20/2018 Presentation May 2012
15/47
Residual connected CTs Zero Sequence CT
5/20/2018 Presentation May 2012
16/47
Widely varying use of resistance material in the industry. Different coefficients of resistivity for these materials.
Coefficient of resistivity typically increases with temperature of the material, thusresistance of the NGR increases while the unit runs.
As resistance increases, current decreases.
Relay current trip curve must fall below the current line in the graph below.
5.5
6
6.5
7
7.5
300
320
340
360
380
400
1 2 3 4 5 6 7 8 9 10
NGR Resistance vs Current
Current
Resistance
5/20/2018 Presentation May 2012
17/47
Normally, protective relaying will tripwithin a few cycles.
IEEE 32 defines standard resistor ontimes. Lowest rate is 10 seconds, butcould potentially go less to savematerial/space.
Can go as high as 30 or 60 secondsas required (rare).
Extended or Continuous ratings arealmost never used in this applicationdue to the relatively high fault
currents.
IEEE Std 32Time Rating and Permissible
Temperature Rise for Neutral
Grounding Resistors
Time Rating
(On Time)
Temp Rise (deg
C)
Ten Seconds
(Short Time)760oC
One Minute
(Short Time)760oC
Ten Minutes(Short Time)
610oC
Extended Time 610oC
Continuous 385oC
5/20/2018 Presentation May 2012
18/47
A B
C
3 Load
HRG
480V Wye Source
N
Phase and Neutral wires in same conduit.If faulted, bypass HRG, thus, -G fault.
No line-to-neutral loads allowed, preventsHazards.
NGR
5/20/2018 Presentation May 2012
19/47
Add small 1:1
transformer and solidlyground secondary for 1loads (i.e. lighting).
5/20/2018 Presentation May 2012
20/47
5/20/2018 Presentation May 2012
21/47
Impedance selected to limit line-to-ground fault current (normally< 10A as defined by IEEE std.142-2007 section 1.4.3.1)
Ground detection system required
System is alarm and locate insteadof trip.
Source
(Wye)
HRG C
BA
N
5/20/2018 Presentation May 2012
22/47
Advantages
Eliminates high transient overvoltages Limits damage to faulted equipment
Reduces shock hazard to personnel
Faulted circuit allowed to continueoperating
Disadvantages
Nuisance alarms are possible. Line-to-neutral loads cannot be used.
ccc IabIIcIr
A B
C
3 Loador Network
Source
N
NeutralGrounding
Resistor
5/20/2018 Presentation May 2012
23/47
Most utilized on Low Voltage Many 600V systems Some 5kV systems
Has been utilized on up to 15kV systems (rare)
ccc IabIIcIr
A B
C
3 Loador Network
Source
N
NeutralGrounding
Resistor
5/20/2018 Presentation May 2012
24/47
Resistor Amperage (ground fault let through current) System Capacitance
Alarm notification
Fault Location Pulsing
Data Logging
Relay Coordination (What to do if there is a second fault)
System Insulation
Personnel training
5/20/2018 Presentation May 2012
25/47
Conductor
Cableinsulation
Cable tray
Every electrical system has some natural capacitance. The capacitivereactance of the system determines the charging current.
Zero-sequence Capacitance: 0 =106
2F/phase
Charging Current: 30 =2
106A
5/20/2018 Presentation May 2012
26/47
During an arcing or intermittentfault, a voltage is held on the systemcapacitance after the arc isextinguished. This can lead to asignificant voltage build-up whichcan stress system insulation andlead to further faults.
In a resistance grounded system, theresistance must be low enough toallow the system capacitance todischarge relatively quickly.
Only discharges if Ro< Xco, so Ir> Ixcoper IEEE142-2007 1.2.7)
That is, resistor current must be greater than capacitive charging current.
5/20/2018 Presentation May 2012
27/47
Major Contributors to system capacitance: Line-ground filters on UPS systems
Line-ground smoothing capacitors
Multiple sets of line-ground surge arrestors
All of these can make implementation ofHRG difficult
5/20/2018 Presentation May 2012
28/47
HRG systems are alarm andlocate systems
Alarm methods: Audible horn Red fault light
Dry contact toPLC/DCS/SCADA opens
DCS/SCADA polling ofunit via Modbus RS-485
Ethernet
5/20/2018 Presentation May 2012
29/47
HRG
480V Wye Source
C
B A
55.4ohms
Operator controlledcontactor shorts outpart of the resistor
Ideally, the increasein current is twice
that of the normalfault current, unlessthat level is unsafe.
5/20/2018 Presentation May 2012
30/47
NOTE:Tracking a ground fault can only be done on anenergized system. Due to the inherent risk of
electrocution this should only be performed by trainedand competent personnel.
5/20/2018 Presentation May 2012
31/47
ZSCT
Meter
ZSCT
MeterMeter
ZSCT
0A
55A
50A
50A80A
80A
50A 50A 50A
50A50A55A30A 30A 30A
30A30A30A
MotorMotor
5A
5A0A
5A
HRG
5A
480V Wye Source85A
C
BA
55.4
ohms
Meter reading will alternatefrom 5A to 10A every 2
seconds.
Alternatives to Manual location: Add zero sequence CTs & ammeters to each feeder Use metering inherent to each breaker (newer equipment only)
5/20/2018 Presentation May 2012
32/47
HRG systems with data logging can be used to locateintermittent ground faults
Example: Heater with ground fault comes on at 11:00am and then
turns off at 11:01am
Normal Pulsing will not locate since the fault will be gone. HRG Data logging can help locate faulted equipment in
conjunction with DCS/SCADA data records
Fault time
frame
Equipment
On
5/20/2018 Presentation May 2012
33/47
If there is a second groundfault on another phase, itis essentially a phase-phase fault and at leastone feeder needs to trip
Network protectionscheme should bedesigned to trip the lowestpriority feeder first, thenthe next, and then moveupstream.
5/20/2018 Presentation May 2012
34/47
Check MCC GF pickup ratings to be sure the small ground fault currentvalues do not trip off the motor on the first ground fault.
Also, fusing on small motors can open during a ground fault. ConsultNEC Table 430.52 for Percentage of full load current fuse ratings. Mostare 300% FLC.
5/20/2018 Presentation May 2012
35/47
Resistance grounded systems must be insulated for full line-linevoltage with respect to ground.
NEC 285.3: An SPD (surge arrestor or TVSS) device shall not beinstalled in the following: (2) On ungrounded systems, impedancegrounded systems, or corner grounded systems unless listedspecifically for use on these systems.
VAG
VBGVCG
VAG
VBG
Un-faulted Voltages to ground Faulted Voltages to ground (VCG= 0)
5/20/2018 Presentation May 2012
36/47
Properly rated equipment prevents Hazards.
A B
C
3 Load
HRG
480V Wye Source
N
0V
277V
Ground A
Cables, TVSSs, VFDs, etc. and otherequipment must be rated forelevated voltages.
0V
480V
480V
5/20/2018 Presentation May 2012
37/47
Common Mode Capacitors provide pathfor Common-mode currents in outputmotor leads
MOVs protect against Transients
5/20/2018 Presentation May 2012
38/47
Ground fault in Drive #1caused Drive 2 to fault on
over-voltage
Drive 3 was not affected
5/20/2018 Presentation May 2012
39/47
Factory optioncodes exist to
remove the internaljumpers
5/20/2018 Presentation May 2012
40/47
Per NEC 250.36, personnel must be trained onImpedance Grounded systems. Training should:
Establish seriousness of a fault Discuss location methods Familiarize personnel with equipment
5/20/2018 Presentation May 2012
41/47
5/20/2018 Presentation May 2012
42/47
Fault current Paralleled generators Common Ground Point
Separate Ground Point
5/20/2018 Presentation May 2012
43/47
In most generators, the zero-sequenceimpedance is much less than the positive ornegative sequence impedances.
Due to this, resistance grounding must be
used unless the generator is specificallydesigned for solid grounding service.
= =
5/20/2018 Presentation May 2012
44/47
Generators Grounded through a single impedance must be the sameVA rating and pitch to avoid circulating currents in the neutrals
Each Neutral must have a disconnecting means for maintenance asgenerator line terminals can be elevated during a ground fault.
Not recommended for sources that are not in close proximity
5/20/2018 Presentation May 2012
45/47
Separately grounding prevents circulating currents
Multiple NGRs have a cumulative effect on ground fault current i.e.the total fault current is the sum of all resistor currents plus
charging current. Can be difficult to coordinate tripping or fault location
If total current exceeds about 1000A, single ground point should beconsidered.
5/20/2018 Presentation May 2012
46/47
IEEE 242-2001 IEEE 142-2007
NEC
IEEE 32
5/20/2018 Presentation May 2012
47/47