Prepared for: Niccholas Azzolini
March 19, 2018
404 Telfair Street
Augusta, Ga.
WILLIS HOME INSPECTIONS P. O. Box 204927
MARTINEZ, GEORGIA 30917
(706) 863-9667
AIKEN (803) 645-7327
Page 2 of 24
While conducting the inspection described herein Don Willis Inspections, Inc., has diligently attempted to present an honest and unbiased evaluation of the property in question. This inspection constitutes a visual examination of the premises for the purpose of determining the condition, at the time of the inspection only, of the accessible portions of the building and related components, systems, and appliances considered to be real property. Excluded from this inspection are those items considered inaccessible, not visible, optional, and/or considered not to be essential to the occupancy of the building, including, but not limited to:
Washing machines (including hook-ups and drains) Dryers and portable dishwashers
Window air conditioners, dehumidifiers and humidifiers Solar heating systems and portable heating equipment
Water softeners, conditioners, purifiers, and filters Timers , automatic timing devices and sprinkler systems
Intercom systems and related equipment Fire and burglar alarm systems and related equipment
Property boundaries, surveys, and easements Municipal zoning laws, restrictions, and ordinances
Drainage, water tables, and flood plains Ecological conditions of lakes, ponds, rivers, brooks, and streams
Geological conditions, mineral deposits, radiation, and molds Public services and utilities
THIS IS NOT AN OFFICIAL WOOD INFESTATION REPORT. We are neither qualified, authorized, nor licensed to inspect for health related molds, mildew, or fungi. Water, plumbing, and sub-surface sewerage disposal system evaluations do not include underground and/or inaccessible components. This inspection and report are not intended, or to be considered, as a guarantee or warranty regarding the condition of the property. This inspection has been conducted with the “STANDARDS OF PRACTICE” of the AMERICAN SOCIETY OF HOME INSPECTORS as a guide and is not intended to be interpreted as technically exhaustive. This inspection and report is valid for a period of 90 days from the date of the report. The report is confidential and is the exclusive property of the party or parties for whom it was prepared and is not intended to be used by any third party for any purpose whatsoever.
PURPOSE AND SCOPE OF INSPECTION
Page 3 of 24
House Elevation: Multi-level
Water Supply: Public
Sewerage: Public
Wall Finish: Siding
Roofing: Asphalt Shingles
OUTSIDE
COMMENTS
Grade/Slopes X
Hose Bibbs X
Driveway X
Chimney X
Roofing X ROOF SHINGLES ARE WORN AND NEED REPLACING
OVER REAR LOWER PORTIONS OF ROOF
AND LEFT SIDE OF UPSTAIRS
GROUNDS / EXTERIOR
Page 4 of 24
OUTSIDE
COMMENTS
; ACTIVE LEAK AROUND CHIMNEY ON RIGHT SIDE
OF UPSTAIRS; RECOMMEND LICENSED ROOFING
COMPANY EVALUATE ALL OF ROOF SHINGLES
AND REPAIR
Flashing X SEE CHIMNEY
Roof Vents X
Cornice/Fascia X WOOD ROT TO CORNICE/FASCIA AT LEFT REAR
CORNER OF HOUSE
Page 5 of 24
OUTSIDE
COMMENTS
Screens/Shutters
Gutters/Downspouts X RECOMMEND ALL GUTTERS BE CLEANED; WOOD
ROT TO CORNICE AND SECTION OF DOWNSPOUT IS
MISSING ON RIGHT SIDE OF HOUSE
Electrical
Exterior Doors X WOOD ROT TO REAR UPSTAIRS EXTERIOR DOOR
(INTERIOR DOOR)
Storm Doors
Windows X WOOD ROT TO BOTH FRONT UPSTAIRS DINING
ROOM WINDOWS
Page 6 of 24
OUTSIDE
COMMENTS
Storm Windows
Caulking
Garage Door/ Casing
Garage Door Opener
Siding X WOOD ROT TO SIDING IN PLACES AT REAR OF
UPSTAIRS
AND AT FRONT BAY WINDOW
Page 7 of 24
OUTSIDE
COMMENTS
Steps
Decks
Porch Support X WOOD ROT TO COLUMNS ALONG FRONT OF
BALCONY
Page 8 of 24
OUTSIDE
COMMENTS
Porch X
Brick veneer
Concrete slab
Page 9 of 24
CRAWL SPACE
COMMENTS
Foundation
X MORTAR AND BRICKS ARE BRITTLE AT SEVERAL
PIERS IN CRAWLSPACE-RECOMMEND LICENSED
STRUCTURAL REPAIR COMPANY EVALUATE AND
REPAIR
Page 10 of 24
CRAWL SPACE
COMMENTS
Moisture / Vapor Barrier
X
Rotting X TERMITE DAMAGE TO GIRDER ALONG RIGHT SIDE
OF CRAWLSPACE UNDER BAR
Piers X SEE FOUNDATION
Electrical X EXPOSED SPLICES IN ELECTRICAL WIRING AT
REAR OF CRAWLSPACE-JUNCTION BOX IS MISSING
A COVER
Page 11 of 24
CRAWL SPACE
COMMENTS
Floors X
Insulation
Joist/Sills X SEE ROTTING
Plumbing X LEAK AROUND WASTE LINE UNDER FRONT RIGHT
CORNER OF CRAWLSPACE-CAST IRON APPEARS TO
BE CRACKED AND NEEDS REPLACING
; LEAK AROUND WATER LINE UNDER REAR
WOMENS BATHRROM
Page 12 of 24
CRAWL SPACE
COMMENTS
; WOOD ROT TO SUBFLOOR, JOIST, AND ACTIVE
LEAK AROUND DRAIN LINE UNDER KITCHEN
UTILITY SINK
Page 13 of 24
DOWNSTAIRS INTERIOR
COMMENTS
Walls X
Doors X
Ceilings X WATER STAINS ON CEILING IN FRONT LEFT DINING
AREA-DRY (APPEARS TO BE OLD LEAK)
Switches X
Receptacles X
Double Hung Windows
X
Ceiling Fans
Hardwood
Carpet X
Floors X
Lighting X
Electrical X EXPOSED WIRES ABOVE FRONT BAY WINDOW IN
FRONT LEFT DINING AREA
UPSTAIRS INTERIOR
COMMENTS
Walls X
Doors X
Ceilings X WATER STAINS ON CEILING IN DINING ROOM
AREA-APPEARS TO BE ACTIVE LEAKS
Switches X
Receptacles X RECEPTACLE IS BROKEN IN FRONT LEFT DINING
AREA
Double Hung X THERMAL PANE WINDOW IN REAR DINING ROOM
AREA (PICTURE WINDOW)
INTERIOR
Page 14 of 24
UPSTAIRS INTERIOR
COMMENTS
Windows
AND FRONT RIGHT DINING ROOM AREA HAVE
LOST THEIR SEAL
; WINDOWS ARE CRACKED AT UPSTAIRS MEN’S
BATHROOM AND PRIVATE BATHROOM
Railing X RAILING IS LOOSE ON STAIRS AT SECOND AND
THIRD LEVEL
Hardwood X
Carpet X
Floors X
Lighting X
Electrical X
Page 15 of 24
DOWNSTAIRS MEN’S BATHROOM
COMMENTS
Electrical X
GFCI
Plumbing/Drains X
Ceiling/Walls/Flooring X
Sink(s) X
Tub/Shower
Tile/Vinyl Flooring X
DOWNSTAIRS WOMEN’S BATHROOM
COMMENTS
Electrical X
GFCI X
Plumbing/Drains X
Ceiling/Walls/Flooring X
Sink(s) X
Tub/Shower
Tile/Vinyl Flooring X
UPSTAIRS MEN’S BATHROOM
COMMENTS
Electrical X
GFCI
Plumbing/Drains X FLUSH VALVE IS NOT WORKING (BROKEN) AND
THE TOILET IS CONTINUOUSLY RUNNING
Ceiling/Walls/Flooring X
Sink(s) X
Tub/Shower
Tile/Vinyl Flooring X
BATHROOMS
Page 16 of 24
UPSTAIRS PRIVATE BATHROOM
COMMENTS
Electrical X
GFCI
Plumbing/Drains X LEFT TOILET FLUSH VALVE IS NOT WORKING
(BROKEN)
Ceiling/Walls/Flooring X
Sink(s) X
Tub/Shower
Tile/Vinyl Flooring X
UPSTAIRS WOMEN’S BATHROOM
COMMENTS
Electrical X
GFCI
Plumbing/Drains X LEFT TOILET FLUSH VALVE IS NOT WORKING
(BROKEN)
Ceiling/Walls/Flooring X
Sink(s) X
Tub/Shower
Tile/Vinyl Flooring X
Page 17 of 24
UPSTAIRS FRONT BATHROOM
COMMENTS
Electrical X
GFCI
Plumbing/Drains X LEAK AT THE DRAINLINE UNDERNEATH SINK;
SHOWER HEAD IS LEAKING
; TOILET IS NOT FLUSHING (FLUSH VALVE IS
BROKEN)
Ceiling/Walls/Flooring X
Sink(s) X
Shower X
Tile/Vinyl Flooring X
Page 18 of 24
MASONARY
FIREPLACE
COMMENTS
Cleanout
Damper X NO DAMPER IN REAR DINING ROOM FIREPLACE-DO
NOT RECOMMEND WOOD BURNING FIRES IN
FIREPLACES
Chimney Needs Cleaning
Grates
Firebrick
Gas Start
Gas Logs
Cracks
Insert
Other
Page 19 of 24
Heating: Manufacturer: (4) Goodmans/Trane
Type: Heat Pump/
Gas furnace
Cooling: Manufacturer: Same Type: Electric
Location of Unit(s): Exterior/Attic
HEATING / COOLING
COMMENTS
Operation X UNABLE TO CHECK GAS FURNACES-GAS IS OFF;
G.E. FURNACE AT 2ND FLOOR IS TURNING OFF
WHEN HEAT OR AC ARE TURNED ON FOR A FEW
MINUTES -RECOMMEND LICENSED HVAC
CONTRACTOR REPAIR UNIT AND SERVICE ALL
UNITS
Filters X FILTERS ARE MISSING AT MOST REGISTERS
Returns X
Vents/Registers X
Venting X
Duct Work X DUCTWORK IS DICONNECTED IN TWO PLACES IN
CRAWLSPACE UNDER REAR DINING AREA
MASTER / UTILITIES
Page 20 of 24
HEATING / COOLING
COMMENTS
Temp. Readings: Level1: Heat Cool 54 Return 69 Temp. Readings: Level2: Heat Cool 56 Return 7
0
Page 21 of 24
Water Heater: Manufacturer: Rheem Ext. Capacity 80
Type: Gas
WATER HEATER AGE: 2009
COMMENTS
Rust X
Vent Pipe X
Protect Pan
Electric Service
Leaks X
Temp/Press Release X
Operation X UNABLE TO CHECK WATER HEATER-GAS IS OFF
Electrical: U n d e r g r o u n d Location of Box: Basement/Hallway Ma in D is c o n n e c t : 600/(2)200Amps Service Line: A l u m i n u m
2 4 0 V o l t L i n e s : Aluminum Copper 120 Volt Line: C o p p e r
ELECTRICAL
COMMENTS
Breakers X NOTE: 600 AMP PANEL BOX LOCATED
UNDERNEATH THE HOUSE-RECOMMEND LICENSED
ELECTRICIAN EVALUATE
Fuses
Ground X
Sub Panel(s) X (2) 200 AND (1) 100 AMP SUB PANEL BOXES
LOCATED AT 1ST FLOOR HALLWAY, AT KITCHEN
STAIRS, AND UNDERNEATH THE HOUSE
GFCI
Page 22 of 24
Roof Construction: 2 X 6 16 oc
Sheathing: Boards
ATTIC
COMMENTS
Access X
Plumbing Vents X
Exhaust Vents X
Moisture X WATER STAINS AND WOOD ROT TO ROOF DECKING
IN PLACES OVER REAR KITCHEN
; WATER STAIN AND WOOD ROT TO ROOF DECKING
AT CHIMNEY ON RIGHT SIDE OF ATTIC
Power Vents
Chimney X
ATTIC
Page 23 of 24
ATTIC
COMMENTS
Wiring X WIRE FOR POWER VENTILATOR IS FRAYED
Electrical Junctions
Ventilation
Insulation X INSULATION IS LOW AND MISSING IN AREAS OVER
UPSTAIRS FRONT DINING AREA
AND IN REAR OVER
KITCHEN
Page 24 of 24
ATTIC
COMMENTS
Framing X
It is understood and agreed that should company and/or employees be found liable for any loss or damages resulting from a failure to perform any of its obligations, including but not limited to negligence, breach of contract, or otherwise, then the liability of company and/or its agents or employees shall be limited to a sum equal to the amount of the fee paid by the customer for the inspection and report.