ECBC Karnataka

Workshop I

Page 2: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• It is estimated that the implementation of ECBC for commercialbuildings with connected load above 100kW, will lead to energysavings to the tune 65 Million units which can supply electricity to40000 rural families for a year without additional installation ofpower plant, at current rate of commercial growth in cities.

Why ECBC

The objective of ECBC is to provide minimum requirements for energy efficient design of buildings and their systems.

Page 3: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Why ECBC

Projection

It is projected that a nationwide mandatory

enforcement of ECBC will yield annual energy

savings to the tune of 1.7 billion kwh

Estimation

Estimates based on simulation models

indicates ECBC compliant buildings can use 40%-60% less energy than

conventional buildings

Saving

At the lowest estimate, this implies an annual saving of nearly Rs. 6

billion; with new rates for commercial

establishments, this amount would be far

higher.

Page 4: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Karnataka Climatic Zones

Demographic shifts transformon Facebookcommunity

High temperature – Low humidity and rainfall – Intense solar radiation and a generally clear sky – Hot winds during the day

and cool winds at night

Temperature is moderately high during day and night – Very high humidity and rainfall – Diffused solar radiation if cloud

cover is high and intense if sky is clear – Calm to very high winds from prevailing wind directions.

This applies when 6 month or more do not fall within any of the other categories -High temperature in summer and cold in winter – low humidity in summer and high in monsoons – High

direct solar radiation in all seasons except monsoons high diffused radiation – occasional hazy sky hot winds in summer,

cold winds in winter and strong wind in monsoons

Moderate temperature – Moderate humidity and rainfall – Solar radiation same throughout the year and sky is generally clear –

High winds during summer depending on topography.

Moderate summer temperature and very low in winter – Low humidity in cold/ sunny and high humidity in cold/cloudy – Low precipitation in cold/sunny and high in cold/cloudy – High

solar radiation in cold/sunny and low in cold/cloudy – Cold winds in winter

Page 5: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Solar-passive building design

Thermal comfort

Reduce energy demand of space-conditioning

Visual comfort

Reduce energy demand of artificial lighting

Solar-passive building design

Addresses indoor thermal comfort as well as visual comfort.

Reduction in energy

consumption and GHG emission

Page 6: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Climate-responsive design strategies

DESIGN STRATEGIES

two

Internal space arrangement (thermal buffer zone)

three

Allocation of building openings

one

Optimum orientation

four

Sizing of openings (limitation of window-wall-ratio and skylight-roof-ratio)

five

Appropriate shading design (façade shading and fenestration shading) and

six

Adequate day lighting (optimum day lighted area and daylight factor)

Page 7: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Significance of ECBC

• Regulates building thermal performance and energy use according

to climate zone.

• Encourages climate responsive building design

• Encourages use of day lighting , shading , natural ventilation ,solar

energy etc.

• Energy efficiency strategies appropriate in India.

• Focuses on energy performance of buildings rather than green

building design

• Material properties ,water use, building site etc. not regulated

• Green Building design standards will refer to ECBC for energy

performance

Page 8: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Scope

Applicable building systems

• Building Envelope

• Mechanical systems and equipment, including HVAC

• Service hot water and pumping

• Interior and exterior lighting

• Electrical power and motors

The code is applicable to all buildings or building complexes that have a connected

load of 100 kW or greater or a contract demand of 120 kVA or greater or having

conditioned area of 500 m2 or more and used for commercial purposes.

Ref: Page no.1, Karnataka Energy Conservation Building Code (ECBC) 2014

Exceptions

• Buildings that do not use either electricity or fossil fuels

• Equipment and portions of building systems that use energy primarily for manufacturing processes

• Safety, Health and Environmental codes take precedence

Page 9: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Compliance Process

Envelope

HVAC

Lighting

Electrical Power

Service Hot Water and Pumping

Mandatory Requirements

Ap

plic

able

Bu

ildin

g Sy

stem

s

Co

mp

lian

ce A

pp

roac

hes

Prescriptive

Whole Building Performance

Trade-off option (for envelope

only)

Page 10: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Compliance Approaches

PRESCRIPTIVE

• Each building/system component should have specific performance value

• Requires little energy expertise; provides minimum performance requirements; no flexibility.

TRADE-OFF

• Applies to Building Envelope ONLY

• Component performance value can be less BUT Overall performance of the envelope complies with ECBC

• Allows some flexibility through the balance of some high efficiency components with other lower efficiency components.

WHOLE BUILDING PERFORMANCE

• Allows flexibility in meeting or exceeding energy efficiency requirements by optimizing system interactions

» Component and Systems Modeling: Envelope, Lighting, HVAC

» Physical Processes: Day lighting, Heat-flow, Airflow

Page 11: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

BUILDING ENVELOPE

Page 12: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Building Envelope: Outline

Building Envelope

Opaque Construction

Cool Roof

Fenestration

Moisture and Infiltration

ECBC Compliance Forms

• Heat Transfer• ECBC Requirements• Exercises

• Solar Radiation• Significance of Cool roofs• ECBC Prescriptive Requirements• Selection Guidelines

• Fenestration components• Heat Transfer.• Optimization of fenestration for

energy performance• ECBC requirements

• Air leakage• Moisture Penetration• Air infiltration V.S. Vapor diffusion • ECBC Mandatory Requirements

Page 13: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Building Envelope

• Surface that separates external

environment from the interior

(occupied) space

• Opaque Construction: Roof,

Walls and Floors

• Fenestration : Windows,

Doors and Skylights

Unconditioned Space

The building envelop depicted here by the

colored line

NOTE: Floors are not regulated through the ECBC

Page 14: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Building Envelope Design Considerations

• Building Envelope Component Design– Area, orientation and tilt of

the building envelope components

– Roof form design, choice of shading devices, fenestration size, placement of windows, construction specifications etc.

• Building Material Specification– Insulating Properties (U-

values, SHGC), emissivity & color/texture

ECBC requirements impact heat transfer throughbuildings by regulating building insulation, area ECBCrequirements impact heat transfer through buildingsby regulating building insulation, area of fenestrationand air leakage through buildings

ECBC requirements affect envelope component design & material selection

Page 15: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Opaque Construction: Outline

• Heat Transfer

– R-value {Insulation)

– U-value

• ECBC Requirements

– Mandatory Requirements

– Prescriptive Requirements

• Exercises

Page 16: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Heat Transfer

Mode of Heat Transfer Affected By ECBCs role in regulating Heat

TransferCONDUCTION Thermal Properties of Materials

& Effectiveness of Insulation

U-factors/ R-values of roofs & walls

CONVECTION Air movement at the surface Building Envelope Sealing

Requirements

RADIATION Indirect and direct solar

radiation

• R-values of roofs & walls

• Cool Roofs

Thermal Property Units Effect of Thickness Relationship

CONDUCTIVITY [k] W/m-K For unit thickness (m)

RESISTIVITY [r] m-K/W For unit thickness (m) 1/k

RESISTANCE [R value] m2-K/W For thickness of construction (d) d/k

CONDUCTANCE (Single Layer) [U-

value]W/im2-K For thickness of construction (d) 1/R-value

CONDUCTANCE (Multiple Layers]

[U-factor]W/im2-K For thickness of construction (d)

l/R-value (Total)

Page 17: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

R-value

• Thermal resistance: R-value

R = Thickness of the material (d)

-------------------------------------------------

Thermal conductivity of the material (k)

• Thermal resistances of multi-layered components

• Effectiveness of thermal insulation to retard the heatflow

• Higher R-value indicates higher insulating properties(Units = m2K/W)

Page 18: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Building Insulation

• One of the ways to improve energy

efficiency, especially in air

conditioned buildings

• Has high R-value

• Increases thermal comfort in

cooling & heating mode

• Helps in reducing heating and

cooling costs

Page 19: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Common Insulation Materials

Page 20: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

U-value

• Thermal Conductance (Heat Transfer Coefficient): U-value

U=1/R

• Measures heat transfer through the envelope due to a

temperature difference between the indoors and outdoors

(Unit = W/m2-K)

• U-factor of composite wall/roof assembly as 1/RT

• Rate of the heat flow, therefore, lower numbers are better.

Page 21: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Sample Thermal Conductivity Values

• Effect of Thickness on Resistance & Conductance of Glass Fiber

Insulation Board.

Page 22: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Mandatory

• U-factors shall be determined from the default tables in Appendix

C §11 or determined from data or procedures contained in the

ASHRAE Fundamentals, 2005.

Page 23: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive

• For opaque construction, individual building envelope components must comply with:

– Maximum U-factor or Minimum R-value (Exterior roofs , ceilings and opaque walls)

– Solar Reflectance & Emittance (Cool Roofs)

• Compliance requirements vary according to:– The climate zone of the building location– Occupancy of the building (24 hour use or daytime use)

Page 24: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Opaque Walls)

• Maximum U-factor is prescribed for the complete wall assembly

• Minimum R-value is prescribed for insulation alone (excluding air films)

Climate Zone

Hospitals, Hotels, Call Centers etc.

(24 - Hour)

Other Buildings Types

(Daytime)

Maximum U-factor of

the overall assembly

(W/m2_0C)

Minimum R-value of

insulation alone

(m2_0C/W)

Maximum U-factor

of the overall

assembly2_0

(W/ m C)

Minimum R-value of insulation alone

2_0

(m C/W)

Composite U-0.440 R-2.10 U-0.440 R-2.10

Hot and Dry U-0.440 R-2.10 U-0.440 R-2.10

Warm and Humid U-0.440 R-2.10 U-0.440 R-2.10

Moderate U-0.440 R-2.10 U-0.440 R-2.10

Cold U-0.369 R-2.20 U-0.352 R-2.35

Table 3.2: Opaque Wall Assembly U-factor and Insulation R-value Requirements

Ref: Table 3.2, Karnataka ECBC report

Page 25: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Roofs)

• Maximum U-factor is prescribed for the complete roof assembly

• Minimum R-value is prescribed for insulation alone (excluding air films)

Recommendations made for proper placement, installation and protection of insulation

Climate Zone 24-Houruse buildings Hospital*, Hotels, Call Centers etc. Daytime use buildings Other Building Types

Maximum: U-factor of the overall assembly (W/m1-

°C)

Minimum R-value of insulation alone (m2-DC/W)

Maximum U-factor of the overall assembly (CW/m2-DC)

Minimum R-value of insulation alone (rn2-aC/W)

Composite U-0.261 R-3.5 U-0.409 R-2.1

Hot and Dry U-0.261 R-3.5 U-0.409 R-2.1

Warm and Humid U-0.261 R-3.5 U-0.409 R-2.1

Moderate U-0.409 R-2.1 U-0.409 R-2.1

Cold U-0.261 R-3.5 U-0.409 R-2.1

Page 26: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Table 10.4:Typical Thermal Properties of Common Building and Insulating Materials- Design Values

(Source: ASHRAE Fundamentals Handbook, 2001)

Page 27: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exercise: R-value calculation

Question

• What is the thermal resistance (R-Value) for a 5.0 mm Asbestos cement board?

Answer0.086 K-m2/WCalculated From: Thermal resistivity (1.73 * 0.05 ) OR Thermal Conductivity (0.05 / 0.058)

Page 28: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exercise: U-factor Calculation

R1: Resistance for Layer 1 (13mm Gypsum Plaster) = 0.056 Km²/W (from KECBC Table 10.4)

R2: resistance of Layer 2 (230mm Brick wall, density = 1920kg/m³

=𝑑2

𝑘2=

0.230

0.81= 0.284 𝑘𝑚2/𝑊 (from KECBC Table

10.4)

R3: Resistance of Layer 3 ( 115 mm air gap) =1.8 Km²/W

R4: Resistance of Layer 4 (115mm Brick wall, density = 1920kg/m³)

=𝑑4

𝑘4=

0.115

0.81= 0.1426

𝐾𝑚2

𝑊(from KECBC Table 10.4)

𝑅𝑡: Minimum R-value for the composite wall = R1+ R2+ R3+ R4= 0.056+ 0.2840+ 0.18+ 0.1426= 0.6626𝐾𝑀2/𝑊

𝑅𝑇: 𝑅𝑠𝑖 + 𝑅𝑡 + 𝑅𝑠𝑒 =0.1 + 0.6626 + 0.04 =0.8026

Maximum U-factor for the composite wall : 𝑈𝑚𝑖𝑛 1

𝑅𝑇=

1

0.8026= 1.246

𝑊

𝑀2. 𝐾

STEP1: Estimate R-values for individual

building material layers KECBC Table

10.4

STEP3: Obtain U-factor by getting the reciprocal

value for R-total

STEP2: Add individual R-values to obtain R-total

Page 29: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exercise: U-factor Calculation

Question• Calculate the U-factor for a roof assembly made up of a RCC roof slab insulated

with 5.00 cm thick expanded polystyrene (density of 24 kg/m3), and finished with 4.00 cm thick brick tiles (density of 1760 kg/m3) on the top, and 1.00 cm thick cement plaster on the bottom.

NOTE: Refer to ECBC Appendix C for thermal properties of materials

Page 30: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exercise: U-factor Calculation

From ECBC Appendix C Layer 1:

L1= 0.04 m of brick tilek1= 0.79 W/m-K (Range 0.71-0.85)

𝑅1 =𝐿1

𝑘1=

0.04

0.79= 0 051 𝐾.𝑚2/𝑊

Page 31: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Layer 2: L2=0.05 m of insulation

k2= 0.035 W/(m K)

R2 = L2/k2= 0,05/ 0.035 = 0.7 K.m2/W

Layer 3: L3=0.15 m RCC slab (Cement/lime, mortar, and stucco)

k3= 1.40 W/(m.K)

R3 = L3/k3 = 0.15/ 1.4 = 0.11 K.m2/W

Layer 4: L4= 0.01 m plaster

k4=0.72W/(m.K)

R4 = L4/k4= 0.01/ 0.72 = 0.014 K.m2/W

Rroof = Rlayer1 + Rlayer2 + Rlayer3 + Rlayer4

= 0.051 + 0.7 + 0.11 + 0.014 = 0.875 W/m2 K

Uroof = 1/ Rroof = 1.14 W/m2 K

Exercise: U-factor Calculation

NOTE; This calculation doesnot take into considerationthermal resistance of airfilms for reasons ofsimplicity. Resistance of airfilm is critical for accurateU-value calculation. Pleaserefer to ECBC User Guide,Building Envelope section,for sample calculations.SAME STEPS CAN BE USEDFOR CALCULATING U VALUEOF A WALL.

Page 32: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Building Envelope Requirements: Cool Roofs

Components of Solar Radiation

• Solar Reflectance : Energyreflected back to theatmosphere.

• Solar Absorptance :Energy absorbed by theroof and transferred tothe building’s interior

• Solar Emittance:Absorbed solar energyradiated back to theatmosphere

Solar Radiation

Significance of Cool Roofs

ECBC Prescriptive Requirements

Selection Guidelines

Cool Roofs: Outline

Page 33: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Significance of Cool Roofs

• "Cool roofs" are roofs covered with a reflective coating with a

high emissivity property that is very effective in reflecting the

sun's energy away from the roof surface.

– Known to stay 10°C to 16°C cooler than a normal roof under a

hot summer sun

– Reduced Urban Heat Island Effect

• Ideal Exterior Surface in hot climates

– Reflectance near 1 & Absorptance near zero to minimize solar

gain

– Emissivity near 1 to radiate absorbed heat back to the sky.

Page 34: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Significance of Cool Roofs

Effect of Solar Reflective Roofs

Case study: Satyam Technology Center, Hyderabad, India

By International Institute of Information Technology (HIT), Hyderabad, withLawrence Berkeley Notional Lab, California

• Measured daily electricity savings = 30 kWh (Building operation: 25 days/month,12 month = 300 days}

• Estimated annual electricity savings = 9,000 kWh

• Annual savings per square meter = 13 kWh/m2

• Monitory savings at Rs. 5 /kWh = Rs. 65 /m2/year

• Incremental cost of cool roof = Rs, 700 /m2

• Total discounted savings over the expected life of the roof = Rs. 430,000

Gray IRoof Cool Roof

Average daily maximum roof-surface temperature 52°C 32°C

Page 35: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Significance of Cool Roofs

1 White Roof will be "diluted' by cool colored roofs of lower reflectivity, and roofs that can not be changed because they are long-lived tile, or perhaps they are already white. 2 Compare 10 tans with a family car, which emits -4tones /year.

A Solar Reflectivity C02 Offset by 100 mz C02 Offset Globally

White Roof 0.40 10 tonsAverage Roof 0,25 6.3 tons 24 Gt

Cool Pavement1 0.15 4 tons² 20 GtTotal Potential 44 Gt

Value of 44 Gt C02 at $15A $660 Billion

Effect of Solar Reflective Roofs and Pavements in Cooling the Globe

C02 Equivalency of Cool Roofs World-wide (Tropics + Temperate)

• Cool Roofs alone offset 24 Gt C02

• Worth > $600 Billion

• To Convert 24 Gt C02 one time Into a rate

• Assume 20 Year Program, thus

• 1.2 Gt C02/year

Average World Car Emits 41 C02/year, equivalent to 300 Million Cars off the Road for 20 years.

100 m2 of a white roof, replacing a dark roof, offset the emission of 10 tons of C02

Page 36: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive

For roofs with slope less than 20 degree

» Initial solar reflectance of no less than 0.70

» Initial emitance no less than 0.75

Initial reflectance/ emitance rice may _ decrease over time of depending on the product, due to aging, dirt, and microbial accumulation.

Efficiency Recommendation for Cool Roofing Products (U.S. DOE)

Efficiency Recommendation

Roof slopeRecommended Solar Reflectance Best Available Solar Reflectanceb

Initial 3 Years after Installation Initial3 Years after Installation

Low-slope {<2:12) 65% or greater 50% or greater 87% 85%

High-slope L (<2:12) 25% or greater 15% of greater 77% 60%

a) Following this recommendation will provide the greatest benefit where cooling energy costs exceed heating castsb) Roof products must be tested when new and after three years of exposure, according to ASTM E-903 c) For products that can be instated on both low- and high-slope roofs, "Law-slope* guidelines should be followed.

Page 37: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Selection Guidelines

Low Slope Roofs

• White colored roofing materials

• Coatings

• Applied using rollers, sprays, or brushes

• Single Ply Materials

• Mechanically fastened over the existing roof and sealed at the seams

High Slope Roofs or roofs visible from ground

• Non-White, high reflectance materials (Glare control)

• Concrete Tile

• Clay Tiles

Common Indian Cool Roofing Products

• Lime coats

• White tiles grouted with white cement

• Special paints

Page 38: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Building Envelope Requirements: Fenestration

Fenestration: Outline

Fenestration Components

Heat/Light Transfer

• Solar Heat Gain Coefficient (SHGC)

• Shading Coefficient (SC) and SHGC

• Visual Light Transmittance (VLT)

Optimization of Fenestration for Energy Performance

ECBC Requirements

• ECBC Mandatory Requirements

* ECBC Prescriptive Requirements

Page 39: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Fenestration Components

Glazing Area80-90% of the total area and therefore the most important part to address for achieving energy efficiency

FramesImportant to optimize the overall energy efficiency of the window

Page 40: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Heat Transfer

Mode of HeatTransfer

Affected By ECBC's role in regulating HeatTransfer

CONDUCTION Thermal properties offenestration assembly

• U-factor & Solar Heat GainCoefficient (SHGC) of glazing

• Wall-Window Ratio (WWR)• Skylight Roof Ratio (SSR)

CONVECTION Air movement at thesurface

• Maximum Air Leakage

RADIATION Indirect and direct solarradiation

• Solar Heat Gain Coefficient ofGlazing and Skylights

• Wall Window Ratio (WWR)• Skylight Roof Ratio (SSR)

Page 41: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Solar Heat Gain Coefficient (SHGC)

• Ratio of solar heat gain that passes through

fenestration to the total incident solar

radiation that falls on the fenestration.

• Indicates how well fenestration insulates

heat caused by direct solar rays

• Lower SHGC means lesser heat transfers

into the building through the window

• Depends on properties of glazing material

& Window Operation (Fixed or Operable)

• In hot climates, SHGC is more significant

than U-factor.

Page 42: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Shading Coefficient (SC) & SHGC

• The solar heat gain coefficient (SHGC) has replaced the shading

coefficient (SC) as the standard indicator of a window's shading ability.

• Relationship between SC and SHGC

– SHGC is expressed as a number between 0 and 0.87

– SC as a number between 0 and 1

– SHGC = SC x 0.87

• SHGC may be expressed in terms of the glass alone or may refer to the

entire window assembly

– SC is typically indicated for the glass alone, and does not take into

consideration the effects of the frame

Page 43: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Visual Light Transmittance (VLT)

• VLT is concerned with the visible portion ofthe solar spectrum as opposed to SHGC,which takes into account the entire solarradiation

• Typically, lower the SHGC, lower the VLT

– Higher insulating property glass will reducedaylight

• Higher the VLT, more light is transmitted

– Balance is needed between daylightrequirements & heat gain through windows

• Fraction of visible light transmitted through the glazing

– Affects daylight and visibility

– Varies between 0 & 1

Page 44: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Optimization of Fenestration for EnergyPerformance

• Balance between window size and glazing selection– Use insulating glazing materials for larger windows. Dual

pane or higher insulating glass instead of single pane glazing

– Larger window area requires lower visible light transmittance; smaller windows requires high visible light transmittance

SOURCE: ECBC User Guide. USAC ECCMII Project. New Delhi

• Appropriate design of shading devices• to reduce SHGC; vary according to orientation, climate (radiation)

• Vary glazing selection by facade, if possible• A lower SHGC & U-value on the south, east, and especially west windows

reduces the cooling load.

• For optimum energy performance balance, Wall window ratio(WWR), SHGC (glazing and shading), U- Value and VLT need to be balanced

Page 45: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Overview

ECBC regulates heat gain through fenestration through

• Size and Orientation– ECBC regulates maximum glazing area (Window-to-Wall

Ratio)

• Shading Devices– ECBC takes into account reduction in heat gain through

use of shading devices

• Glazing Properties– ECBC regulates Solar Heat Gain Factor (SHGC), U-value and

Visual Light Transmittance (VLT)

Page 46: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Mandatory

• U-factors AND SHGC (Appendix C of the ECBC)

• In accordance with ISO-15099 AND labeled and certified by the manufacturer

• U-Factors and SHGC must be certified by an accredited independent testing laboratory

Table 10.1: Defaults for Unrated Vertical Fenestration (Overall Assembly including the Sash and Frame)

Page 47: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Vertical Fenestration)

• Fenestration area is limited to a maximum of 60% of the gross wall area for the prescriptive requirement.

• Maximum area weighted U-factor and maximum area weighted SHGC requirements

WWR<40% 40% WWR<60%

Climate Maximum U-factor

Maximum SHGC Maximum SHGC

Composite 3.30 0.25 0.20

Hot and Dry 3.30 0.25 0.20

Warm and Humid 3.30 0.25 0.20

Moderate 6.90 0.40 0.30

Cold 3.30 0.51 0.51

[ see ECBC guild Appendix C §11.2.1 (or Defaults values of Unrated Fenestration ]

Table 3.3: Vertical Fenestration U-factor and SHGC Requirements (U-factor in W/m2-°C)

Reduced SHGC tocompensate forincrease in heatgain through alarger window towall (WWR) ratio

Less stringentrequirements formoderate Climates.Higher U-factor andSHGC

Page 48: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Vertical Fenestration)

• Minimum VLT defined as function of Window Wall Ratio (WWR), where Effective Aperture > 0.1, equal to or greater than the Minimum VLT requirements of Table 4.5.

Table 3.5: MinimumVL T Requirements

Effective ApertureLight admitting potential of vertical fenestration Depends on glazing property and size of openingEffective Aperture = Visual Light Transmittance (VLT) * Window to Wall Ratio (WWR)

Lower VLT requirementsto offset the increasedheat transfer throughhigher WWR

Page 49: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Vertical Fenestration)

ECBC Exception To Vertical Fenestration Requirements• Applies to fenestration with shading devices (Overhangs/Fins)

• Adjustment to window SHGC through a multiplication (M) factor to account for reduced solarheat gain from windows that are well shaded

• "M Factor" shall be determined for each orientation, latitude of the building site and uniqueshading condition

ECBC Exception To SHGC Requirements• Vertical Fenestration areas located more than 2.2 m (7 ft.) above the floor level are exempt

from the SHGC requirement in Table 4.3 if

– The total Effective Aperture for the elevation is less than 0.25, including all fenestrationareas greater than 1.0 m (3 ft.) above the floor level

• An interior light shelf is provided at the bottom of this fenestration area, with an interiorprojection factor not less than:

– 1.0 for E-W, SE, SW, NE, and NW orientations

– 0.5 for S orientation, and

– 0.35 for N orientation when latitude is < 23 degrees.

Page 50: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

M-factor (ECBC Table 4.4)

• M-factor captures the effectiveness of shading devices to provide solar protection Varies according to latitude of site, choice of shading option and projection factor

Overhang “M” Factors for

4 Projection

Factors

Vertical Fin “M” Factors for4 Projection Factors

Overhang +Fin “M” Factors for 4

Projection Factors

Project Location

Orientation

0.25-

0.49

0.50-

0.74

0.75-

0.99

1.0

0

+

0.25-

0.49

0.50-

0.74

0.75

-

0.99

1.00

+

0.25-

0.49

0.50-

0.74

0.75-

0.99

1.00

+

North latitude15º or

greater

N .88 .80 .76 .73 .74 .67 .58 .52 .64 .51 .39 .31

E/W .79 .65 .56 .50 .80 .72 .65 .60 .60 .39 .24 .16

S .79 .64 .52 .43 .79 .69 .60 .56 .60 .33 .10 .02

Less than150

North latitude

N .83 .74 .69 .66 .73 .65 .57 .50 .59 .44 .32 .23

E/W .80 .67 .59 .53 .80 .72 .63 .58 .61 .41 .26 .16

S .78 .62 .55 .50 .74 .65 .57 .50 .53 .30 .12 .04

Projection Factors (PF) need to be calculated

For Example:Combination of overhang +Fins

provides maximum solar

protection. Thus, M-factor are the lowest

Page 51: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Projection Factor (PF) Calculation

PF is needed to determine M-factor

PF = H (Horizontal) / V (vertical)

• PF = Ratio of overhang projectiondivided by height from window sill tobottom of overhang (must bepermanent)

Solar heat gain Coefficient Requirements dependent on:

Overhang projection factor M- Factor from Table 4.3.3-2• Orientation• And Climate ZoneWithout Overhang: SHGC range 0.25-0.51 based on climate zone.

Page 52: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Skylights)

• ECBC regulates all fenestration (skylights) with slope of less than 60 Deg.

• U-Factor and SHGC requirements according to

– Installation of skylight (Flush mounted/curb mounted)

– Skylight Roof Ratio (SSR)

Source: ECBC User Guide. USAID ECO-III Project, New Delhi

Page 53: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Prescriptive (Skylights)

• Maximum U-factor and SHGC requirements of Table 3.6

• Lower U-factors limit for flush mounted installation

• Skylight area is limited to a maximum of 5% of the grossroof area or Skylight Roof Ratio (SRR) =< 5%

– Higher the SRR; lower the maximum SHGC required

Maximum U – factor Maximum SHGC

Climate With Curb w/o Curb 0-2% SRR 2.1-5% SRR

Composite 11.24 7.71 0.40 0.25

Hot and Dry 11.24 7.71 0.40 0.25

Warm and Humid 11.24 7.71 0.40 0.25

Moderate 11.24 7.71 0.61 0.4

Cold 11.24 7.71 0.61 0.4

Higher SHGC limits for moderate and cold climate zones

where heat gain through windows

»s less of a concern

Page 54: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Building Envelope RequirementsMoisture and Infiltration

• Air Leakage

• Moisture Penetration

• Air infiltration Vs. Vapor diffusion

• ECBC Requirements

Page 55: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Air Leakage

Amount of air leakage through a building depends on:

• Air Leakage through gaps in the building envelope

– Between different building materials, fenestrations, and openings for piping, wiring ducts etc.

• Air leakage due to pressure difference between a building'sinterior and exterior

– Caused by wind, indoor and outdoor temperature differences, ventilation fans, exhaust fans etc.

NOTE: ECBC regulates air leakage through the building envelope only

Page 56: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Passage of air through the building envelope

• Infiltration: Leakage to the interior

• Ex-filtration: Leakage to the exterior

Measured as the volumetric flow rate of outside air into a building - Cubic Feet per Minute (CFM) or Liters per second (LPS)

Air Exchange Rate = Air Changes per hour (ACH= CFM* 60/Volume)

Common places of air leakage

• Windows and Doors

• Openings of roofs, walls, and floors

• Ducts or plenums

• Other joints and seams

Air Leakage

Page 57: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Consequences

• Infiltrating air may contain pollutants, allergens, bacteria etc., as it is untreated

• Accompanying changes in air pressure may disrupt delicate pressure relationships between HVAC zones, esp. in critical facilities such as hospitals and labs, leading to IAQ. problems

• Condensation of moisture from ex-filtrating air in cold climates and from infiltrating air in hot-humid climates may cause health problems and deterioration of building components

• Unnecessary energy consumption due to added heating and cooling loads and additional humidification/dehumidification needed

Air Leakage

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/airbarriers.php#

Page 58: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Air Barrier System

Combination of interconnected materials, flexible sealed joints and components of the building envelope

• Air-tightness of the building enclosure

• Separation between conditioned and unconditioned spaces

Features of an Air barrier system

• Continuity

• Structural support

• Air permeability

• Durability

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/airbarriers.php#

Page 59: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Air Barrier System

Location• Can be located anywhere in the envelope assembly (unlike the

vapor retarder)

– If placed on the predominantly warm, humid side (high vapor pressure side), can work as an 'air and vapor barrier'

– If placed on the predominantly cool, drier side (low vapor pressure side) of the wall, it should be vapor permeable

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/airbarriers.php#

Page 60: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Air Sealing Advantages

Improved thermal integrity of envelope & improved thermal comfort

• Improved performance of insulation

• Minimized temperature differences between rooms

• Reduction in unconditioned air, drafts, noise, and moisture

Reduction of unwanted condensation

• Reduction of insulation R-value, degradation of building materials

Improved indoor air quality

• Reduced pollution, dust, mold and moisture

Reduced energy loss and heating/cooling costs

• Infiltration loads can add up to 20-40% heating/cooling loads

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/airbarriers.php#

Page 61: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Moisture Penetration

Causes

• Rainwater intrusion

• Infiltration of outside moisture-laden air (a primary problem in hot, humid climates)

• Internally generated moisture (from occupant activities and routine housekeeping)

• Vapor diffusion through the building envelope

To avoid moisture related problems, building envelope should do the following:

• Adequately retard moisture or air movement into the building

• Allow accumulated moisture to either drain to the exterior or evaporate

SOURCE: Whole Building Design Guide, ttp://www.wbdg.org/resources/moisturemanagement.php#

Page 62: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Vapor retarder

• May not be required in all situations; envelope (without vapor retarder) may perform as an adequate barrier to vapor diffusion

• Under many conditions using an air barrier is more important than using a vapor retarder (as moisture contributed by air leakage is much more than through vapor diffusion)

• Properties of Vapor retarders:– Permeance (measure of resistance to vapor flow)– Location– Use of multiple retarders

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/moisturemanagement.php#

Page 63: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Air infiltration Vs. Vapor diffusion

• In hot, humid climates, air barrier or vapor retarder must have proper air resistance

or moisture permeability and must be installed at the correct location within the

walls.

• The point where cool surfaces meet warm, moist air is where condensation and

excess moisture can occur. If moisture-laden outside air is retarded before it meets

the first cool surface inside the building envelope then few problems will result. If

this moisture is allowed to further enter a wall system, it will condense.

• Thus, the building envelope plays a vital role in minimizing uncontrolled moisture

and air movement into a building and in preventing moisture entrapment within the

wall system.

• Confusion still exists related to the integrity requirements of air, weather barriers

and vapor retarders; the way they can be incorporated into one membrane; the

location of these features within the building envelope; the effects of using multiple

vapor retarders; and even the need for air barriers and vapor retarders in every

facility.

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/moisturemanagement.php#

Page 64: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Envelope must be designed to prevent the entry of liquid water into the envelope assembly

• Building envelope components should be designed for air tightness -provision of air barrier (on both the inside and outside of the insulated portion of the wall)

• Building envelope assemblies will tend to dry out if water vapor transmission toward the cool dry side of the envelope is not impeded with a vapor retarder; water vapor will migrate from the assembly towards that environment.– In cold climates the envelope will dry toward the outside.

– In hot humid climates the envelope will dry to the air conditioned interior.

– In mixed climates the envelope will dry to the outside during the heating season and to the inside during the cooling season.

• The dynamics of water vapor movement through envelope assemblies is complex, especially in parts of the country that have both a heating and cooling season.

Air infiltration Vs. Vapor diffusion

SOURCE: Whole Building Design Guide, http://www.wbdg.org/resources/env_iaq.php#

Page 65: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements: Mandatory

Air Leakage through doors and fenestration

• for glazed swinging entrance doors and revolving doors shall not exceed 5.0 l/s-m2.

• Other fenestration and doors shall not exceed 2.0 l/s-m2.

Building Envelope Sealing

The following areas of the enclosed building envelope shall be sealed, caulked, gasketed, or weather-stripped to minimize air leakage:

• Joints around fenestration and door frames

• Openings between walls and foundations and between walls and roof and wall panels

• Openings at penetrations of utility services through, roofs, walls, and floors

• Site-built fenestration and doors

• Building assemblies used as ducts or plenums

• All other openings in the building envelope

Page 66: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Building Envelope Requirements: Overview

Building Component Mandatory Requirements Prescriptive Requirement

OPAQUE CONSTRUCTION (Roofs

and Walls)

Building Envelope Sealing

Requirements [ECBC 4.2.3]

Maximum U-factors & Minimum R-

values of roofs & walls [ ECBC 4.3.1 &

4.3.2)

Cool Roof Specifications [ECBC 4.3.1.1]

FENESTRATION (Doors, Windows

and Skylights)

Calculation of U-factors & Solar

Heat Gain Coefficient (SHGC) of

glazing [ECBC 4.2.1 & 4.2.1.2]

Air Leakage Maximum Limits

[ECBC 4.2.1.3]

Maximum U-factors & SHGC, Wall-

Window Ratio (WWR), & Visible

Transmission (VLT) of Glazing

[ECBC4.3.3 ]

Skylight Roof Ratio (SSR); Maximum

U-factors & SHGC of glazing [ECBC

4.3.4]

Page 67: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Compliance form

Page 68: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Heating Ventilation and Air Conditioning

Energy Conservation Building Code

Page 69: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

HVAC Design

Mechanical HVAC System

High efficiency Refrigerative

systems

Natural Ventilation

Controlling unwanted heat

gains

Solar-passive building design

Addresses indoor thermal comfort as well as energy efficiency

Reduction in energy consumption and GHG emission

Page 70: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

HVAC

• Introduction

• Whole Building Performance approach

• Non – Refrigerative Cooling

• Refrigerative Cooling

• Building Commissioning and System Balancing

• ECBC Requirements:

– Mandatory

– Prescriptive

• ECBC Compliance forms

Page 71: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

V (Ventilation)H

(Heating)

AC (Air-

Conditioning)

Natural VentilationMechanical Ventilation

CoolingDehumidification

Humidification

Cabin design –cooling and

heating requirements

Temperature and Humidity

range

Placement of Vents and

Ducts

Space considerations

Energy Efficiency

Environmental Impact

Activities

Introduction

Page 72: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Thermal Comfort

External Loads

Internal Loads

Temperature

HumidityIndoor Air

Quality (IAQ)

Solar Gain

Outside Air

Conduction

People

Equipment

Lighting

Thermal Comfort

Page 73: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes
Page 74: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

7

4

Air Conditioning Processes

• Heating: transfer of energy to the air in a space

• Cooling: transfer of energy from the air in a space

• Humidifying: transfer of water vapor to the air in a space

• Dehumidifying: removal of water vapor from the air in thespace

• Cleaning: removal of particulate and biologicalcontaminants from the air in a space

• Air Motion (Circulation): movement of air through thespaces in a building to achieve the proper ventilation andfacilitate the energy transfer, humidification (ordehumidification), and cleaning processes described above

Page 75: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

HVAC System Components

• Furnace/Heating Unit

• Filters

• Compressors

• Condensing Units

• Evaporator (Cooling coil)

• Control System (Thermostats, Economizers, VAV’s,etc.)

• Distribution System (Supply/Return Ducts, Piping,Plenums, etc.)

Page 76: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

AC System Types

• Room Air Conditioners

– Split Systems (Separate Indoor

(evaporator) and Outdoor

(Condenser)

– Window Systems (All functions in one outdoor package)

• Centralized Air conditioners

Page 77: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Chillers

Page 78: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

78

Factors that Determine Building HVAC Energy Use

• Building configuration and orientation

• Building envelope construction

• Interior space arrangement

• Design temperature and humidity, indoor and outdoor

• Zoning criteria

• Equipment application and sizing

• Control methodologies

Page 79: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

7

9

Design Conditions

Indoor Design Conditions:

• The primary purpose of the heating and air-conditioning system is to

maintain the space in a comfortable and healthy condition

• This is generally accomplished by maintaining the dry-bulb temperature

and the relative humidity within an acceptable range

• The HVAC Applications Volume of the ASHRAE Handbook gives

recommendations for indoor design conditions for specific comfort as well

as industrial applications

Outdoor Design Conditions:

• Climatic Data of the Karnataka state, provided by Indian Meteorological

Department was taken into consideration for the calculations.

Page 80: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

0

Example: Typical Brick Veneer Wall Section

Page 81: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

1

Calculation of Overall Heat Transfer Coefficient - U

• U = overall heat transfer coefficient, BTU/ hr· sf· ºF

• R = thermal resistance, hr· sf· ºF /BTU

R = (0.10)(12.08)+(0.90)(18.70) = 18.04

U = 1 / R = 1 / 18.04 = 0.055

Wall Component Thermal Resistance

Stud Path (~10%) Cavity Path (~90%)

Outside air film (15 mph) 0.17 0.17

Face brick (4”) 0.44 0.44

Air space (1”) 0.85 0.85

Styrofoam insulation (1”, 90ºF) 5.00 5.00

Batt insulation 0 11.00

Wood studs 4.38 0

Foil-back gypsum board 0.56 0.56

Inside air film (still air) 0.68 0.68

Total R (R+) 12.08 18.70

Page 82: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

2

Transmission Heat Loss Through Walls, Roofs, and GlassH = A x U x TD

H = heat loss, BTU/hr

A = surface area of element, sf

U = overall heat transfer coefficient, BTU/ hr· sf· ºF

TD = design dry bulb temperature difference between indoors and outdoors, ºF

Transmission Heat Gain Through Walls and Roofs

H = A x U x CLTD

H = heat gain, BTU/hr

A = surface area of element, sf

U = overall heat transfer coefficient, BTU/ hr· sf· ºF

CLTD = cooling load temperature difference, ºF

Page 83: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

3

Conduction Heat Gains Through Glass

H = A x U x CLTD

H = heat gain, BTU/hr

A = surface area of element, sf

U = overall heat transfer coefficient, BTU/ hr· sf· ºF

CLTD = cooling load temperature difference, ºF

Solar Heat Gain Through Glass

• H = A x SC x SCL

H = heat gain, BTU/hr

SC = shading coefficient

SCL = solar cooling load factor

Page 84: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Infiltration Heat Gain and HeatLoss• The uncontrolled leakage of

outdoor air into a buildingthrough window and doorcracks, floors, walls, etc., as wellas the flow of outdoor air into abuilding through the normal useof exterior doors

Exfiltration Heat Gain andHeat Loss

• Exfiltration is the leakage ofindoor air out of the building.The amount of exfiltrationequals the amount ofinfiltration]

Heat Gain from Occupants

8

4

Page 85: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

5

Heat Gains from Lights

• Each watt of lighting load (including both lamp and ballast) releases 3.413 BTU/hr

Heat Gain from Motors

• Each brake or net horsepower of motor load divided by the efficiency (including both motor and drive) releases 2545 BTU/hr

H = 2545 BTU/hr x Bhp / EffM x EffD

H = heat gain, BTU/hr

Bhp = brake horsepower

EffM = motor efficiency, decimal fraction, 0 – 1.0

EffD = drive efficiency, decimal fraction, 0 – 1.0

Page 86: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

6

Heat Gains from Appliances and Equipment

• Appliances and equipment (including food prep., hospital, lab, office,

etc.) normally produce significant sensible heat, and may also

produce significant latent heat.

• To estimate the cooling load, specific heat gain data obtained from

the manufacturer is preferred. However, if it is not available,

recommended heat gains are published by ASHRAE and other

sources.

• Evaluation of the operating schedule and the load factor for each

piece of equipment is essential.

Page 87: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

8

7

Energy Saving Opportunities

• Change indoor temperature and/or humidityset-points

• Improve building thermal envelope

– Apply additional thermal insulation

– Improve fenestration

– Reduce infiltration

• Improve lighting system efficiency

Page 88: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Role of ECBC in Thermal comfort of Buildings

• As the climate map of India (ECBC 2007) shows that most of India falls mainly under three Climatic zones, i.e., Hot & Dry, Warm & Humid and Composite, the buildings need cooling for at least 6 to 8 months per year to provide thermal comfort to the occupants of the building.

• All of this comes with significant energy consumption and the costs. Both needs to be addressed while designing the building.

• Reducing electricity consumption through a high quality and high efficiency design could enhance the value of the building and its rent.

• Hence the strategic measures in HVAC design were prescribed by ECBC, in order to reduce the operating costs and saving energy.

Page 89: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Whole Building Design Approach

1) Reducing the cooling loads by controlling unwanted heat gains

• Reduced latent heat load, air movement-ceiling fans, less insulated furniture, more casual dress codes

2) System Interactions for Reduced Loads

3) Expand the comfort envelope

• Reducing velocity, pressure and friction in ducts and piping4) Optimization of Delivery systems

5) Apply Non-Refrigerative cooling techniques

6) Serve the remaining load with high-efficiency Refrigerative cooling

• Sensors, Signal Delivery, User Interface, Simulators, etc.7) Improve controls

Page 90: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

1) Cooling Load Reduction Measures

Ref: Tip Sheet on HVAC System-2.0 March 2011

Page 91: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

2) System Interactions for Reduced Loads

• Cooling load reduction should be

approached in concert with whole-

building load reduction measures for

both cooling and heating systems.

• The objectives of saving cooling and

heating energy may be in conflict or

may support each other.

• For example, better insulation and

efficient windows reduce both loads

while lighting load reductions may

increase heating loads.

• High-performance windows may be the last

step needed in eliminating part or all of the

perimeter HVAC equipment, while providing

superior radiant comfort in both summer and

winter.

• To take advantage of load variations, it is

critical that building HVAC systems be

capable of reacting to the reduced loads.

• This requires variable capacity pumps and

fans (or variable capacity compressor and

condenser units in case of packaged or split-

systems) and reliable sensors and controls to

allow the equipment to power down when

loads drop.

Page 92: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

3) Expansion of Comfort Envelope

• Expand the comfort envelope with reduced Latent Heat load, Increased

air flow, less insulated furniture, more casual dress where appropriate:

• These opportunities are less understood and deployed but have the

potential to save cooling loads. In an indoor environment with fixed air

temperature, relative humidity, air speed and activity , an office worker

in cotton trousers and half shirt (with an insulating value of 0.5 clo)

will be comfortable at almost 3°C warmer than the same person in a

heavy two piece business suit and accessories (with an insulating value

of 1.0 clo).

• A 3°C increase in inside temperature can save significant amount of

energy.

Page 93: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

3) Expansion of Comfort Envelope

Ref: Tip Sheet on HVAC System-2.0 March 2011

Page 94: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

4) Optimization of Delivery Systems

• Huge savings are available from reducing the velocity, pressure, and friction losses in ducts and piping.

• These improvements can be captured with high-efficiency fans, diffusers, and other components.

• A properly operating diffuser spreads the supply air out along the ceiling nearly as far as the wall before the air begins to drop into the space.

Page 95: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

5) Application of Non-Refrigerative Cooling Techniques

• Ground coupled cooling

• Night-sky Radiation cooling

• Cooling with outdoor air

• Evaporative cooling

• Desiccant dehumidification and cooling

• Heat pipe cooling cycle enhancements

• Hydronic Cooling

Page 96: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

6) Serving remaining load with efficient Refrigerative system

Page 97: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

7) Improvement of Controls

• Sensors

• Signal Delivery

• User Interface

• Simulators

Page 98: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Non-Refrigerative Cooling methods

• Ground Coupled Cooling

– Ground-source closed loop Heat Pump system

– Ground-coupled water loop heat pump system

• Night Sky Radiation Cooling

• Cooling with outdoor air

– Natural Ventilation

– Air Side Economizer

– Night Ventilation Cooling

Page 99: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Energy Efficient Measures

• Non Refrigerative Cooling methods

• Evaporative Cooling

• Desiccant Dehumidification and cooling

Page 100: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Types of Natural Ventilation Openings

• Windows

– Windows sliding vertically, sliding horizontally, tilting,

swinging.

• Doors, monitor openings and skylights.

• Roof Ventilators (weather proof air outlet).

• Stacks connecting to registers.

• Specially designed inlet or outlet openings.

Page 101: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Natural Ventilation Rules

1. Buildings and ventilating equipment should not usually be oriented for

a particular wind direction.

2. Inlet openings should not be obstructed by buildings , trees,

signboards, or indoor partitions.

3. Greatest flow per unit area of total opening is equal to inlet and outlet

openings of nearly equal areas.

4. For temperature difference to produce a motive force, there must be

vertical distance between openings; vertical distance should be as great

as possible.

5. Openings in the vicinity of the neutral pressure level are least effective

for ventilation.

Page 102: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Evaporative Cooling

• Evaporative cooling is an ancient air conditioning technique that is

growing in popularity due to increased interest in energy efficiency,

reduced peak demand, improved indoor air quality, and non-CFC

cooling.

• Evaporative cooling typically uses less than one-fourth the energy of

vapor-compression air-conditioning systems, while using no more

water than a power plant uses to produce the electricity needed for

the same amount of vapor-compression cooling.

• The cost of an evaporative cooling system may be higher than a vapor

compression chiller system, but payback is typically 1-5 years

depending on climate.

Page 103: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Indirect Evaporative Cooler

Page 104: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Desiccant dehumidification and Cooling

Page 105: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Desiccant Dehumidification

Page 106: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Heat Pipe Cooling

Page 107: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Refrigerative Cooling System

Page 108: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Room Air Conditioners

• Energy Efficiency Ratio

(EER) = Rate of Cooling (or) Cooling Output/Cooling Input (atfull load Conditions)

Page 109: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Chillers

Chiller Size and Efficiency

• Tons: Measure of the rate of cooling supplied (Chiller Size)

• 1 Ton = 12000 BTU/hr or 3.516 thermal kW

Efficiency Ratings

• kW/ton rating = Power Input to Compressor motor/Tons of coolingProduced

• COP Rating – (Coefficient of Performance) = BTU Output (Cooling)/BTUInput (Electric Power)

• EER Rating = Energy Efficiency Ratio

Integrated Part Load Value (IPLV)

kW/ton = 12/EER;

kW/ton= 3.516/COP

Page 110: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Building Commissioning & System Balancing

Building Commissioning

• Quality Oriented process of achieving, verifying and documenting the

performance of the facilities, systems and assemblies meets defined

objectives and criteria (ASHRAE Guideline 0, The Commissioning Process)

Testing, Adjusting and Balancing (TAB)

• TAB of all HVAC Systems and equipment is needed to complete the

installation and to make the system perform as the designer intended.

• TAB is not commissioning, although Commissioning includes TAB

verification.

• Commissioning is required for green building rating programs (LEED and

GRIHA).

Page 111: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Commissioning assists in the delivery and overall quality assurance of

a project, including:

– Planning delivery team member roles and responsibilities

– Planning tasks for all project phases and activities including:

• Review and Acceptance procedures

• Documentation Requirements

• Development and approval of Commissioning Plans,

Commissioning Schedules and Testing and Inspection Plans

• Cost of Correcting deficiencies and contractor call-backs during

warranty period often make up for the cost of commissioning

Page 112: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements for HVAC: Overview

ECBC Mandatory Requirements– Natural Ventilation

– Equipment Efficiency

– Controls

– Piping and Ductwork

– System Balancing

– Condensers

ECBC Prescriptive Requirements• Economizers

– Reduce energy consumption by using cooler outdoor air to cool the building whenever possible

• Hydronic Systems

– Variable fluid flow saves water and reduces energy use in water based systems

Page 113: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Natural Ventilation

Natural ventilation shall comply with the design guidelines provided for

natural ventilation in the National Building Code of India 2005 Part 8

Section 1, 5.4.3 and 5.7.1

Page 114: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Minimum Equipment Efficiencies

• Cooling equipment shall meet or

exceed the minimum efficiency

requirements presented in Table

4.1 (ECBC Karnataka). Heating &

cooling equipment not listed here

shall comply with ASHRAE 90.1 -

2004 § 6.4.1.

• Unitary Air Conditioner shall meet

IS 1391 (Part 1), Split air

conditioner shall meet IS 1391 (Part

2), Packaged air conditioner shall

meet IS 8148 and Boilers shall meet

IS 13980 with above 75% thermal

efficiency.

Equipment Class Minimu

m

C

O

P

Minimum

IPL

V

Test Standard

Air Cooled Chiller <530 kW (<150tons) 2.90 3.16 ARI 550/590 - 1998

Air Cooled Chiller>530 kW (>150tons) 3.05 3.32 ARI 550/590 - 1998

Centrifugal Water Cooled Chiller

<530kW (<150 tons)

5

.

0

5.25 ARI 550/590 - 1998

Centrifugal Water Cooled Chiller >530

and <1050 kW(>150 and < 300 tons )

5.55 5.9 ARI 550/590 - 1998

Centrifugal Water Cooled Chiller

>1050 kW ( >300tons)

6

.

1

6.4 ARI 550/590 - 1998

Reciprocating Compressor, Water

Cooled Chiller all sizes

4.20 5.05 ARI 550/590 - 1998

Rotary Screw and Scroll Compressor, Water Cooled Chiller <530kW(<150tons)

4.70 5.49 ARI 550/590 - 1998

Rotary Screw and Scroll Compressor,

Water Cooled Chiller >530 and

<1050 kW (>150and <300 tons)

5.40 6.17 ARI 550/590 - 1998

Rotary Screw and Scroll Compressor

Water Cooled Chiller >1050kW (>300tons)

5.75 6.43 ARI 550/590 - 1998

Page 115: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes
Page 116: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Controls

All mechanical cooling and heating systems shall be controlled by a

time-clock that:

• Can start and stop the system under different schedules for three

different day- types per week

• Is capable of retaining programming and time setting during loss of

power for a period of at least 10 hours, and

• Includes an accessible manual override that allows temporary

operation of the system for up to 2 hours

Page 117: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Controls

Exceptions to §4.2.3.1:

• a) Cooling systems < 28kW (8tons)

• b) Heating systems < 7 kW (2tons).

• All heating and cooling equipment shall be temperature controlled. Where a unit provides both

heating and cooling, controls shall be capable of providing a temperature dead band of 30C (50 0F)

within which the supply of heating and cooling energy to the zone is shut off or reduced to a

minimum.

• Where separate heating and cooling equipment serve the same temperature zone, thermostats

shall be interlocked to prevent simultaneous heating and cooling.

• All cooling towers and closed circuit fluid coolers shall have either two speed motors, pony motors,

or variable speed drives controlling the fans.

• The automatic door closure and door gaps sealing arrangement shall be provided in all air

conditioned rooms.

Page 118: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Piping and Ductwork

• To minimize energy losses, ECBC requires that piping of heating and cooling systems,

(including storage tanks) must be installed. ECBC specifies required R-values of insulation

based on the operating temperature of the system.

• Piping for heating systems with a design operating temperature of 60oC (140oF) or

greater shall have at least R-0.70(R-4) insulation.

• Piping for heating systems with a design operating temperature less than 60 oC (140oF)

but greater than 40oC (104 oF), piping for cooling systems with a desiccant operating

temperature less than 15oC (59 oF), and refrigerant suction piping on split systems shall

have at least R-0.35 (R-2) insulation.

• Insulation exposed to weather shall be protected by aluminium sheet metal, painted

canvas, or plastic cover.

• Cellular foam insulation shall be protected as above, or be painted with water

retardant paint.

Page 119: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Piping and Ductwork

• Note:(a ) Insulation R-value is measured on a horizontal plane in accordance with ASTM C518 at a

mean temperature of 24oC (75oF) at the installed thickness;

(b) Includes crawlspaces, both ventilated and non-ventilated;

(c) Include return air plenums with or without exposed roofs above.

Page 120: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

System Balancing

• Construction documents shall requirethat all HVAC systems be balanced inaccordance with generally acceptedengineering standards.

• Construction documents shall requirethat a written balance report beprovided to the owner or thedesignated representative of thebuilding owner for HVAC systemsserving zones with a total conditionedarea exceeding 250 m2 (2,500ft2).

Air System Balancing

• Air systems shall be balanced in amanner to first minimize throttlinglosses.

• Then, for fans with fan system powergreater than 0.75 kW (1.0 hp), fanspeed shall be adjusted to meetdesign flow conditions.

Hydronic system Balancing

• Hydronic systems shall beproportionately balanced in amanner to first minimize throttlinglosses; then the pump impellershall be trimmed or pump speedshall be adjusted to meet designflow conditions.

Exceptions to Hydronic SystemBalancing

• Impellers need not be trimmed norpump speed adjusted for pumpswith pump motors of 7.5 kW (10HP) or less,

• Impellers need not be trimmedwhen throttling results is nogreater than 5% of the nameplatehorsepower draw, or 2.2 kW ( 3HP),whichever is greater.

Page 121: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Condensers

ECBC regulates the Condenser locations to ensure:

• There is no restriction to the air flow around condenser coils

• No short circuiting of discharge air to the intake side

• Heat discharge of other adjacent equipment is not near the air intake of

the condenser

• Care shall be exercised in locating the condensers in such a manner that

heat sink is free of interference from heat discharge by devices located

in adjoining spaces and also does not interfere with such other systems

installed nearby.

• The condensers (outdoor units) especially of single unit room split air

conditioners shall be located in shaded and well ventilated area closest

to the evaporator (indoor unit).

Page 122: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Condensers

• In case of unavailability of shaded area, and the condensers shall

be provided with artificial shading to prevent direct heating of the

unit during day time by the sun light.

• The unitary air conditioners shall also be installed at suitable

locations to avoid direct sunlight and shading may be provided for

improved performance. The piping system connecting the outdoor

and indoor units shall be insulated and the length of such pipes

shall not exceed the length as specified by the manufacturer.

Treated Water for condensers

• All high - rise buildings using centralized cooling water system shall

use soft water for the condenser and chilled water system.

Page 123: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Prescriptive Requirements

• Compliance shall be demonstrated with the requirements in § 4.3.1 through §

4.3.2 for each HVAC system that meets the following criteria:

– Serves a single zone

– Cooling (if any) is provided by a unitary packaged or split-system air

conditioner or heat pump

– Heating (if any) is provided by a unitary packaged or split-system heat

pump, fuel- fired furnace, electric resistance heater or baseboards

connected to a boiler

– Outside air quantity is less than 1,400 l/s (3000 cfm) and less than 70% of

supply air at design conditions

• Other HVAC systems shall comply with ASHRAE 90.1-2004 § 6.5.

Page 124: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Economizers

Air side Economizers

• Each individual cooling fan system that has a design supply capacity over 1,200 l/s (2,500 cfm) and a total mechanical cooling capacity over 22kW (6.3 tons) shall include either :

(a) An air economizer capable of modulating outside -air and return – airdampers to supply 100 percent of the design supply air quantity as outside –air;

(or)

(b) A water economizer capable of providing 100% of the expected system

cooling load at outside air temperatures of 10 oC (50 oF ) dry- bulb/7.2oC (450F)

wet -bulb and below

Page 125: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exceptions for Economizers

(a) Projects in the Hot-Dry and Warm - Humid climate zones are exempt

(b) Individual ceiling mounted fan systems < 3,200 l/s (6,500cfm) are

exempt-

• Wherever required, economizers shall be capable of providing partial

cooling even when additional mechanical cooling is required to meet

the cooling load.

• Air –side economizers shall be tested in the field following the

requirements in Appendix F to ensure proper operation.

• Air economizers installed by the HVAC system equipment

manufacturer and certified to the building department as being

factory calibrated and tested per the procedures in Appendix F,

Karnataka ECBC.

Page 126: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Variable Flow Hydronic Systems

• Chilled or hot-water systems shall be designed for variable fluid flow and shall becapable of reducing pump flow rates to no more than the larger of:

(a) 50% of the design flow rate, or

(b) The minimum flow required by the equipment manufacturer for proper operation ofthe chillers or boilers.

• Water cooled air -conditioning or heat pump units with a circulation pump motorgreater than or equal to 3.7 kW (5 hp) shall have two – way automatic isolationvalves on each water cooled air- conditioning or heat pump unit that areinterlocked with the compressor to shut off condenser water flow when thecompressor is not operating.

• Chilled water or condenser water systems that must comply with either of theabove, and that have pump motors greater than or equal to 3.7 kW (5 hp) shall becontrolled by variable speed drives.

Page 127: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC KARNATAKA

Service Water Heating and Pumping

Page 128: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Service Hot Water and Pumping

• Introduction

• Types of water heaters

• ECBC Requirements• Mandatory

• ECBC Compliance Forms

Page 129: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Introduction

Water heating is a thermodynamic process using an energy source to heat waterabove its initial temperature.

Hot water Use

Domestic• Cooking• Cleaning• Bathing• Space Heating

• ECBC Compliance Forms

Industrial

• Hospitals• Cleaning• Disinfection• Bathing

Commercial• Hotels

• Cooking• Laundry• Bathing

Page 130: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Introduction

Source Type

System Type

Conventional• Electricity• Natural Gas/ LPG• Oil• Solid Fuels

Alternative• Solar Energy• Heat Pumps• Hot Water Recycling• Geothermal Heating

• Storage• Instantaneous

Energy Loss

• Inefficiency of heating equipment

• Heat loss from hot water storage tanks

• Heat loss from the distribution network

(piping)

Opportunities for improvement

• Use hot water heating system, that has a

Thermostat.

• Reduce water heating Temperature .For each

5.5 degree C (10 degree F) reduction in water

temperature , can lead to 3-5% savings in

energy costs

• Insulate the storage tanks, pipes and heat

traps.

For some building types such as large hotels and

hospitals service heating can be major energy

consumer. Inefficiency in water heating is caused

primarily by inefficiency of the heating

equipment and by heat loss from hot water

storage tanks and distribution piping network.

Page 131: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Types Of Water Heaters

Storage Heat pump

• An electric water heater that uses a compressor to transfer thermal energy from one

temperature level to higher temperature level for the purpose of heating water .

• It includes all necessary auxiliary equipment such as fans , storage tanks , pumps or controls.

Storage Heaters (Gas or Electric)

• Designed to heat and store water at less than 80°C.

• Water temperature is controlled with a thermostat

• Storage electric water heaters have a manufacturer's specified capacity of at least two

gallons

Instantaneous (Gas or Electric)

• Instantaneous water heaters provide hot water only as it is needed.

• Controlled manually or automatically by water flow activated control and /or

thermostatic controls.

• Water heaters heat water directly without the use of a storage tank.

Page 132: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Types Of Water Heaters

Solar (Passive or Active)

• Systems which collect and store solar thermal energy for water heating

applications

• Passive systems do not require electricity to recirculate water, whereas active

systems require electricity to operate pumps or other components.

• Passive systems are not readily available in the market and generally need to be

designed for a particular usage.

Indirect gas

• A water heater consisting of a storage tank with no heating elements or

combustion devices .

• Connected via piping and recirculating pump to a heat source consisting of a gas

or oil fired boiler , or instantaneous gas water heater.

Page 133: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements : Mandatory

1. Utilizing Solar water heating

2. Specifying heating Equipment Efficiency

3. Supplementary water heating system

4. Insulating hot water storage tanks and pipelines

5. Heat Traps

6. Swimming pool(covers)

ECBC through mandatory requirements seeks to minimize energy usage in waterheating systems by:

1.Solar Water Heating

Residential facilities , hotels and hospitals with a centralized system shall have solar

water heating for at least 1/5 of the design capacity.

Exception: Systems that use heat recovery for at least 1/5 (20 percent) of the

design capacity are exempted.

Page 134: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Compliance : Mandatory

Service water heating equipment shall

meet or exceed the performance and

minimum efficiency requirements

presented in the available Indian

standards.

• Solar water heater shall meet the

performance /minimum

efficiency level mentioned in IS

13129 part (1&2).

• Gas Instantaneous Water heaters

shall meet the performance

/minimum efficiency level

mentioned n IS 15558 with

above 80% thermal efficiency.

2.Equipment Efficiency • Electric water heater shall meet the

performance /minimum efficiency level

mentioned in IS 2082.

SOURCE: Bureau of Indian Standards(1991),IS 2082 (Part1):1993(Reaffirmed 2004) Edition 5.4(2002-05) Stationary Storage TypeElectric Water Heaters –Specification (Fourth Revision)

Page 135: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Supplemental water heating system shall be designed to

maximize energy efficiency and shall incorporate and prioritize

the following design features as shown:

• Maximum heat recovery from hot discharge system like

condensers of air conditioning units.

• Use of gas-fired heaters wherever gas is available.

• Electric heater as last resort.

3.Supplemental Water Heating

4.Piping Insulation

The entire hot water system including the storage tanks,

pipelines shall be insulated conforming to the relevant IS

standards on the materials and applications.

5.Heat Traps As per code-

Vertical pipe risers serving storage

water heaters and storage tanks

not having integral heat traps and

serving a non-recirculating system

shall have heat traps on both the

inlet and outlet as close as

practical to the storage tank.

ECBC Requirements : Mandatory

Page 136: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements : Mandatory

Heating pools shall be provided with a vapor retardant pool

cover on or at the water surface Pools heated to more than

32°C(90°F) shall have a pool cover with a minimum insulation

of R-2.1(R-12).

Exception : Pools deriving over 60% of their energy from

site recovered energy or solar energy source.

6.Swimming Pools

Compliance Documentation

As per code:

The application for approval shall furnish calculation showing the

design to ensure that at least 20% of the heating requirement shall

be met from solar heat/heat recovery and not more than 80% of

the heat shall be met from electrical heating. Wherever gas is

available ,not more than 20% of he heat shall be met from

electrical heating.

ECBC Compliance

Forms

At least 20% of the heating

requirement shall be met

from solar heat/heat

recovery.

Not more than 80% of the

heat shall be met from

electrical heating.

Wherever gas is available ,not

more than 20 % of the heat

shall be met from electrical

heating.

Page 137: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Lighting

ECBC Karnataka

Page 138: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

INTRODUCTION: LIGHTINGECBC prescribes the amount of power for lighting, specifies types oflighting controls, and defines situations where day lighting must be used.

Lighting is a major energy consumer in commercial buildings. Heat generated from

electrical lighting also contributes significantly to the energy needed for cooling of

buildings.

• Lighting accounts for 15% of total energy consumption in India. Lighting is an

area that offers many energy efficiency opportunities in almost any building

facility, existing or new.

• While energy efficiency is an attractive goal for many reasons, lighting designers

also need to consider a host of other factors, including the effect of quality of light

on the visual comfort and productivity of the occupants. In practice, the right

quality and quantity of light can be provided efficiently (with less energy) by using

the right technology and its effective integration with daylight.

Page 139: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

INTRODUCTION: LIGHTING

The right quality and quantity of light can be provided efficiently (with less energy)

by using the right technology and its effective integration with day light.

Lighting

Day lightingHeating effects

of lighting

Lighting technology

Lighting distribution

Lighting controls

Efficient lighting design

Lighting design tools

Lamp technologies

Incandescent lamps

Linear and compact fluorescent lamps

High density discharge lamps

Light emitting diodes

Fixture and reflector

Ref: ECBC Karnataka

Page 140: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements

• ECBC Lighting Requirements apply to

– Interior spaces of buildings

– Exterior building features, including facades, illuminated roofs, architecturalfeatures, entrances, exits, loading docks, and illuminated canopies

– Exterior buildings grounds lighting that is provided through the building’s electricalservice

– The mandatory requirements for lighting mostly relate to interior and exteriorlighting controls

– The prescriptive requirements limit the installed electric wattage for interiorbuilding lighting

– Interior lighting systems in buildings larger than 500 m² (5000 ft²) shall be equippedwith an automatic control device.

– Each space shall have at least one control device to independently control thegeneral lighting

– Each control device shall be activated either manually by an occupant orautomatically by sensing an occupant.

– Luminaire in day lighted areas greater than 25m² shall be equipped with either amanual or automatic control device.

Lighting Control

Space Control

Control in Day Light

Exterior Lighting Control

Exterior building Ground Light

Additional Control

Page 141: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Compliant Lighting Design Strategy

• Specifying the amount of light for general usage without considering the needs of

specific tasks (supplying light for general office work but not addressing the effect

of glare on computer screen).

• Designing a day lighting strategy but not enabling the lighting system to dim or

turn off when there is sufficient daylight in the interior space.

• Supplying inadequate control of lighting by not allowing lights to be adjusted to

specific needs and not providing easily accessible control switches

• Adding a large window area to the facade for day lighting but ignoring the

problems of solar heat gain and the need for shading

• Designing/sizing the building’s HVAC system on rules of thumb and not accounting

for the reduction in cooling loads created through efficient lighting system.

Page 142: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Compliant Lighting Design Strategy

1. Prescriptive Requirements (in accordance with the ECBC table)

– Step 1: depending upon the type of the proposed building, select thecorresponding permissible LPD

– Step 2: determine the gross lighted floor area of the building

– Step 3: calculate the interior lighting power allowance (LPA) which is theproduct of the gross lighted floor area and the selected LPD for the building.

– Step 4: calculate the total installed lighting power (ILP) of the all proposedluminaires in the building.

– Step 5: compare ILP values with LPA values. If ILP is less than or equal to LPA,the lighting system of the building complies with ECBC. Otherwise, it is not.

Page 143: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

2. Space function MethodDetermination of interior lighting power allowance (watts) by the space function methodshall be in accordance with the following:

– Step 1: Determine the appropriate building type from Table 6.2 and the allowed lightingpower density

– Step 2: For each space enclosed by partitions 80% or greater than ceiling height,

determine the gross interior floor area by measuring to the center of the partition wall.Include the floor area of balconies or other projections. Retail spaces do not have tocomply with the80%partition height requirements

– Step 3: The interior lighting power allowance is the sum of the lighting power allowancesfor all spaces. The lighting power allowance for a space is the product of the gross lightedfloor area of the space times the allowed lighting power density for that space.

ECBC Compliant Lighting Design Strategy

Page 144: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Tips for Energy Efficient Lighting

• Day lighting Tips

– Plan the layout of interior spaces- use the layout to allow daylight to penetrate far into

the building.

– Orient the building to minimise building exposure to the east and west and maximise

glazing on the south and north exposures.

– Follow ECBC Visible Light transmittance (VLT) requirements for windows – to maximise

light and visual quality.

• Effective day lighting strategy should include a combination of thefollowing– Address interior colour schemes

– Avoid glare

– Control

– Design Tips

– Lighting Retrofit tips Ref: ECBC Karnataka

Page 145: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Tips for Energy Efficient Lighting

• Capture Daylight

– Building form: U-shaped, stepped-back

– Skylights, atria

– Elements: light shelves, reflectors, louvers,

blinds

– Reducing need for electrical lighting

– Reducing cooling load

– Glazing selection

• Tinted

• Reflective

• Low-e

• Spectrally selective

– Redirecting day light (and light transport

systems)

Page 146: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Tips for Energy Efficient Lighting

• Use of lighting controls

– On-off controls

• Manual switches

• Elapsed time switches

• Clock switches

• EMS controls

• Photocell controls

• Occupancy controls

• Switched power strips

– Dimming controls

• Power reducers

• Stepped dimming controls

• Continuous- dimming controls

Page 147: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exit Signs

Electrically powered exit signs normally use incandescent bulbs.

Most LED and some CFL exit signs can meet ECBC requirement.

Due to their low power consumption, LED exit signs can be

purchased with built-in-back-up power supplies.

With an estimate life of 10 years or more, LEDs require significantly

fewer lamp replacements than exit signs equipped with either

incandescent lamps or CFLs.

Page 148: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Exterior Building Grounds Lighting

• Lighting for exterior building grounds luminaires which operate at greater than 100W shall

contain lamps having a minimum efficacy of 60lm/W unless the luminaire is controlled by

a motion sensor or exempt under fig. 6.1 of ECBC

• High-efficacy lighting components, such as T-8 fluorescent lamps and electronic high-

frequency ballasts, make a significant impact on lighting energy and its associated costs by

reducing the kW required to illuminate buildings. Lighting controls, on the other hand,

affect lighting energy by directly reducing lighting’s time of use.

Ref: ASHRAE/IESNA Standard 90.1-1999

Page 149: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

The installed interior lighting power calculated for compliance with table

6.3 of the code shall include all power used by the luminaires, including

lamps, ballasts, current regulators, and control devices except as

specifically exempted in table 6.1 of the ECBC Karnataka code.

Installed Interior Lighting Power

Page 150: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Installed Exterior Lighting Power

• Lighting power limits are specified for building exterior lighting applications in table6.3 of the code. The connected lighting power for these applications must notexceed these allowed limits. In addition, trade-offs between applications are notpermitted.

• Exemptions are allowed for the following lighting applications, only if they areequipped by an independent control device:

– Specialized signal, directional, and marker lighting associated withtransportation

– Lighting used to highlight features of public monuments and registered historiclandmark structures or buildings.

– Lighting that is integrated to advertise signage

– Lighting that is specifically designated as required by a health or life safetystatue, ordinance, or regulation.

Page 151: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electrical Power

ECBC Karnataka

Page 152: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Introduction

Electrical Power comprises of all physical components that make up the electric

equipment and systems installed in a facility.

Power PlantTransmission Sub Station

High Voltage transmission

lines

Power Sub-station

Power poles Transformer Facility

Page 153: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Introduction

Page 154: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Transformer

Device to either increase (Set-up) or decrease (Step-down) the input supplyvoltage

Page 155: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Transformers

Efficiency

– Varies anywhere between 96 to 99%

– Depends on the design and operating load

– Transformer losses consist of two parts:

• No load-loss: occurs whenever the transformer is energized

and it does not vary with load

• Load loss (copper loss): associated with full-load current

flow in the transformer windings and varies with the square of

the load current (P=I²R)

Page 156: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motors

Device to convert energy into mechanical energy

– Drives equipment such as pumps, blowers and fans, compressors,conveyors and production lines

Page 157: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Types of Electric Motors

Page 158: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motor

Page 159: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motors

More variables-

– Physical construction characteristics

• Enclosure type

• Winding pattern

• Insulation system

• Voltage

• Physical dimension and frame type

– Performance characteristics

• Single-speed, two-speed, and variable speed

• Startup and operating torque characteristics

• Slip

• Power factor

• efficiency

Page 160: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

– Environmental characteristics

• Hazardous location

• Temperature limit

• Caustic and containment tolerance

• Noise level

Electric Motors

Page 161: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motors

• Winding: number of turns of insulated wire, usually copper, wrapped around the

core of steel laminations.

• Rewinding: a repair technique for induction motors where the old windings are

removed and new windings are installed, either in the stator, rotor, or both.

• Power factor: the ratio between the real power (in watts or kW) and apparent

power (the product of the voltage times the current measured in volt-amperes or

kVA)

• Power Factor Correction: the application of capacitors to compensate the lagging

power factor caused by induction motors.

• Power factor correction (PFC) may be applied either by an electrical power

transmission utility to improve the stability and efficiency of the transmission

network or, correction may be installed by individual electrical customers.

Page 162: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motors

Motor input consumption

• Motor efficiency: ratio of the useful mechanical power output to the total

electric power input to the motor.

– Nameplate efficiency: efficiency provided by a motor manufacturer and

the nominal efficiency for that motor design. Actual motor efficiency can

be above or below this value.

• Electrical energy input is measured in watts (W), while output is given in

horsepower (hp)

• 1 hp = 746 W

Page 163: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Electric Motors

• Oversizing: process of system design and hardware selection that results in the

selection of a motor (or other component) that is larger than necessary to perform the

job.

• Oversized motors that operate at part load are disadvantageous:

– Reduced efficiency

– Reduced slip (important if the load is a cube-law type)

– Reduced power factor

• Efficiency drops precipitously below 50% load

– Average 100-hp energy efficient motor losing over two points between 50 and

25% load

– The average 100-hp standard efficiency induction motor dropping some 5.5 points

over the same range.

Page 164: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

ECBC Requirements

• ECBC has only Mandatory requirements for electric power systems installed in

buildings

• The mandatory requirements of the Code, cover the following electrical equipment

and systems of the building:

– Transformers

– Energy-efficient Motors

– Power Factor Correction

– Electrical Metering and Monitoring

– Power Distribution Systems

Page 165: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Transformers (Maximum Allowable PowerTransformer Losses)

– Power transformers of the power ratings and design

must be selected to satisfy the minimum acceptable

efficiency at 50% and full load rating.

– The transformers must be selected such that it minimizes

the total of its initial cost in addition to the present value

of the cost of its total lost energy while serving its

estimated loads during its respective life span.

ECBC Requirements

ECBC lists various transformer sizes of dry-type and oil-filled transformers

and their associated losses at 50% and full load rating.

Page 166: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Dry Type Transformers

Ref: ECBC Karnataka

Page 167: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Oil Filled Transformers

Ref: ECBC Karnataka

Page 168: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

Transformers (Measurement and Reporting of Transformer Losses)

– All measurement of losses shall be carried out by using calibrated

digital meters of 0.5 or better accuracy and certified by the

manufacturer.

– All transformers of capacity of 500 kVA and above would be

equipped with additional metering class current transformers (CTs)

and potential transformers (PTs) additional to requirements of

Utilities so that periodic loss monitoring study may be carried out.

ECBC Requirements

Page 169: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Energy Efficient Motors

– Minimum acceptable nominal full load motor efficiency not less than IS 12615

standard for energy-efficiency motors.

– Motors horsepower ratings shall not exceed 20% of the calculated maximum load

being served.

– Motor nameplates shall list the nominal full-load motor efficiencies and the full-

load power factor.

– Motor users should insist on proper rewinding practices for any rewound motors,

or, the damage motor should be replaced with a new, efficient one

– Certificates shall be obtained and kept on record indicating the motor efficiency.

During rewinding of motors, the core characteristics of the motor should not be

lost during removal of damaged parts. After rewinding, a new efficiency test shall

be performed and a similar record shall be maintained.

ECBC Requirements

Page 170: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Power Factor Correction

– All electricity supplies exceeding 100 A, 3 phases shall maintain their power factor

between 0.95 lag and unity at the point of connection.

– Benefits of Power Factor Correction

• Reduced power consumption and electricity bills

• Improved electrical energy efficiency

• Extra kVA availability from the existing supply

• Reduced 12R losses from transformer and distribution equipment

• Minimized voltage drop in long cables

– Ways to correct the power factor

• Minimize operation of idling or lightly loaded motors

• Avoid operation of equipment above its rated voltage

• Replace standard motors as they burn out with energy-efficient motors

• Install capacitors in your AC circuit to decrease the magnitude of reactive power.

ECBC Requirements

Page 171: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Check-Metering and Monitoring

– To improve a building’s performance over its operating life, and optimize the energy-

efficient requirements, the Code requires that the building’s performance be measured.

– Metering is about having information that allows buildings energy managers to analyze

and track changes in energy demand and, therefore, to manage their energy

consumption more effectively.

• Services exceeding 1000 kVA shall have permanently installed electrical metering to

record demand (kVA), energy (kWh), and total power factor. The metering shall also

display current (in each phase and the neutral), voltage (between phases and

between each phase and neutral), and Total Harmonic Distortion (THD) as a

percentage of total current.

• Services not exceeding 1000 kVA but over 65 kVA shall have permanently installed

electric metering to record demand (kW), energy (kWh), and total power factor (or

kVARh)

• Services not exceeding 65 kVA shall have permanently installed electric metering to

record energy (kWh)

ECBC Requirements

Page 172: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes

• Power Distribution Losses

– The power cabling shall be adequately sized as to maintain

the distribution losses not to exceed 1% of the total power

usage

– Record of design calculation for the losses shall be

maintained.

– Advantages of optimally sized distribution system:

• Lower heat generation

• Increased flexibility of installation

• Reduced energy consumption and cost

ECBC Requirements

Ref: ECBC Karnataka

Page 173: Premium Abstract Blue - kredlinfo.inkredlinfo.in/EC/ECBC/Master presentation on ECBC basics and Compliance.pdf · conditioned area of 500 m2 or more and used for commercial purposes