PRC / PRCLC
REGENCORE
The RegenCore is a high effectiveness energy recovery unit. The RegenCore recovers sensible energy during
both heating and cooling seasons, and under select conditions, RegenCore also recovers latent energy. The
new regenerating core product sets itself apart from other recovery devices with its fully tested design, industry
leading effectiveness of up to 90% and no pre-heat requirement down to outdoor temperatures of -40°C/F.
PRC and PRCLC units are available in a wide range of sizes to accommodate each unique project’s airflow
requirements. The PRC’s wide range of available airflows combined with its indoor and outdoor designs make
it suitable for a multitude of applications. The PRCLC is a lighter duty unit for indoor use is an ideal option for
use in compact spaces.
2 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
TYPICAL APPLICATIONSThe RegenCore has excellent
owner payback when used in most
applications: education facilities,
sportsplex facilities, commercial office
buildings, multi-story residential
buildings, banks, warehouses,
car dealerships and casinos.
MODELS + Standard (PRC)
+ Light Duty (PRCLC)
CONSTRUCTION FEATURES + Indoor and outdoor designs
+ Thermally broken aluminum post & corner cabinet (PRC)
+ Double wall 2 inch foam panel
+ Formed or structural base frame (PRC)
+ AMCA listed, low leakage, high cycle dampers
+ Gear drive motors
+ 1100 Alloy aluminum cores
+ Carel controls
+ 1500 hour salt spray rated finish
INDUSTRY LEADING TEST FACILITIESRegenCore units are tested to the highest industry standards
via the Price Environmental Chamber. The chamber maintains
temperatures ranging from -40°C/F to +40°C (104°F) and is paired
with a Price Mechanical custom air handling unit to simulate building
return air by heating or cooling and introducing humidity. The
chamber, air handling unit, and instrumentation allow for precise
energy balances and accurate efficiency measurement making
RegenCore the industry’s only product with fully tested indoor
and outdoor performance data.
3v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
Carel controller
THERMAL BREAK + The thermal break system provides high thermal insulation
+ Gasket system ensures smooth internal surfaces and
airtightness inside the unit
+ The design allows for the panels to be removed from the
exterior of the unit
+ Optional thermally broken panels
MATERIAL OPTIONS + Double wall panels with foam insulation and 1,500 hour salt spray paint
+ 16 to 22 gauge painted galvanneal steel and unpainted galvanized steel outer panel
+ 16 to 20 gauge galvanized steel inner panel
+ 14 gauge aluminum inner and outer panels
CAREL CONTROLS + Integrating HVAC equipment into the building automation
system can allow remote control, quick recognition of
issues and improved control for performance and savings
+ Optional BACnet MSTP, BACnet IP, MODBUS
FILTERS + Standard 2 inch filter rack with MERV 8 filters for improved
indoor air quality
+ Highly customizable options to meet filtration, available as 2
inch, 4 inch, and 12 inch cartridge types
BASES + 4 inch and 6 inch formed base
+ 4 inch and 6 inch structural baseFilter Rack
4 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
HYDRONIC COILS + Hydronic coils constructed from high quality materials
+ Certified in accordance with AHRI standards
Gas heating
Electric heating
Hydronic coil
DX COOLING DEHUMIDIFICATION
+ Price offers fully tested packaged and split DX cooling
options
+ Electronic expansion valves for highly accurate, modulating
refrigerant control
GAS HEAT + Stainless steel 3 pass and 4 pass drum and tube style heat
exchanger
+ Convoluted tube style heat exchanger
+ Up to 20 to 1 turndown
+ Up to 90% efficient furnaces
ELECTRIC HEAT + Optional galvanized or stainless steel heater frames
+ Integrated and pre-wired controls in NEMA-1 control panel
+ Thermal safety switches and fan interlocked heating
elements are supplied for safe operation
5v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
Core 1
Core 1
Supply
Supply
Return
Return
Core 2
Core 2
PRC OPERATING MODESEnergy RecoveryThere are two stages to the energy recovery process. Below is an explanation of typical operation during winter
conditions:
Cycle A: shows core 1 storing heat from return air being
exhausted from the building. Core 2 is releasing the
heat previously stored to condition the colder outdoor
air to supply air.
Cycle B: During the cycle, dampers are re-positioned
so the inverse occurs. Now core 1 is releasing heat it
captured and stored during the cycle A. Core 2 is now
recovering heat from the exhaust air.
Energy Recovery Cycle A
Energy Recovery Cycle B
6 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
StandbyThe standby mode positions the dampers
to isolate the building from outdoor
conditions.
EconomizerThe economizer mode suspends the
re-positioning of the dampers & energy
recovery to use outdoor air for cooling.
During this mode the dampers will
reposition every 3 hours to self-clean the
cores.
Recirculation (Optional)The recirculation mode positions the
dampers to recirculate building air when
the space is not occupied. Additional
dampers are required for this mode.
Core 1 Return
Return
Return
Core 2Supply
Supply
Supply
Core 1
Core 2
Core 1
Core 2
7v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRCLC OPERATING MODESEnergy RecoveryThere are two stages to the energy recovery process. Below is an explanation of typical operation during winter
conditions:
Cycle A
Core 1 storing heat from return air being exhausted
from the building. Core 2 is releasing the heat previously
stored to condition the colder outdoor air to supply air.
Cycle B
During this cycle, dampers are re-positioned so the
inverse occurs. Now Core 1 is releasing heat is captured
and stored during Cycle A. Core 2 is recovering heat
from the exhaust air.
Economizer
The economizer mode suspends re-positioning of the dampers and
energy recovery to use outdoor air for cooling. During this mode,
the dampers will reposition every 3 hours to self-clean the cores.
Core 2 Core 2
Core 2
Core 1 Core 1
Core 1
8 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
PRC DIMENSIONAL DATA
MODEL # CFMWinter
EffectivenessSummer
EffectivenessA B C D E F G H
PRC 1000 1000 90.2 82.2 122 31 48 25.5 21 10.6 9.4 10.8
PRC 1500 1500 90.2 82.2 122 42 50 36.5 22 10.6 9.4 16.3
PRC 2000 2000 90.2 82.3 122 44 52 38.5 23 10.6 9.4 17.3
PRC 2500 2500 90.3 82.3 126 53 52 47.5 23 11.6 13.3 19.9
PRC 3000 3000 90.3 82.4 130 53 60 47.5 27 13.7 15.8 18.6
PRC 3500 3500 90.3 83.3 130 61 60 55.5 27 13.7 15.8 22.6
PRC 4000 4000 90.3 82.4 130 55 76 49.5 35 16.2 18.8 18.1
PRC 4500 4500 90.4 82.5 136 60 76 54.5 35 16.2 18.8 20.6
PRC 5000 5000 90.3 82.4 136 63 76 57.5 35 16.2 18.8 22.1
PRC 5500 5500 90.3 82.4 136 69 76 63.5 35 16.2 18.8 25.1
PRC 6000 6000 90.4 82.5 154 67 84 61.5 39 13.7 44.1 11.4
PRC 6500 6500 90.3 82.4 154 72 84 66.5 39 13.7 44.1 13.9
PRC 7500 7500 90.3 82.3 160 74 92 68.5 43 13.7 44.1 14.9
PRC 8500 8500 90.3 82.4 164 83 92 77.5 43 13.7 44.1 19.4
PRC 9500 9500 90.4 82.5 164 78 107 72.5 50.5 16.2 52.4 12.8
PRC 10500 10500 90.3 82.4 174 85 107 79.5 50.5 16.2 52.4 16.3
PRC 11500 11500 90.3 82.4 174 93 107 87.5 50.5 16.2 52.4 20.3
PRC 12500 12500 90.3 82.5 182 100 107 94.5 50.5 19.1 62.1 18.9
RA AIRFLOW
SA AIRFLOW
A
C
4"
2"
EA / OA
EA / OA
RETURN FAN/FILTERSECTION
SUPPLY FAN /FILTERSECTION
HEAT EXCHANGERSECTION
HEAT EXCHANGERSECTION DAMPER
SECTION D
E
LOUVER*BASE FRAMEOPTIONAL
LOUVER*
STANDING SEAMROOF*
B
4" DRAIN DRAIN
CONTROL BOX
* NOT REQUIRED ON INDOOR UNITS
MODEL # CFM WINTER EFFECTIVENESS
SUMMER EFFECTIVENESS A B C D E
PRC 1000 1000 90.2 82.2 122 31 48 25.5 21
PRC 1500 1500 90.2 82.2 122 42 50 36.5 22
PRC 2000 2000 90.2 82.3 122 44 52 38.5 23
PRC 2500 2500 90.3 82.3 122 53 52 47.5 23
PRC 3000 3000 90.3 82.4 126 53 60 47.5 27
PRC 3500 3500 90.3 83.3 124 61 60 55.5 27
PRC 4000 4000 90.3 82.4 130 55 76 49.5 35
PRC 4500 4500 90.4 82.5 130 60 76 54.5 35
PRC 5000 5000 90.3 82.4 132 63 76 57.5 35
PRC 5500 5500 90.3 82.4 132 69 76 63.5 35
PRC 6000 6000 90.4 82.5 136 67 84 61.5 39
PRC 6500 6500 90.3 82.4 136 72 84 66.5 39
PRC 7500 7500 90.3 82.3 138 74 92 68.5 43
PRC 8500 8500 90.3 82.4 138 83 92 77.5 43
PRC 9500 9500 90.4 82.5 146 78 107 72.5 50.5
PRC 10500 10500 90.3 82.4 146 85 107 79.5 50.5
PRC 11500 11500 90.3 82.4 144 93 107 87.5 50.5
PRC 12500 12500 90.3 82.5 144 100 107 94.5 50.5
RA AIRFLOW
SA AIRFLOW
A
C
4"
2"
EA / OA
EA / OA
RETURN FAN/FILTERSECTION
SUPPLY FAN /FILTERSECTION
HEAT EXCHANGERSECTION
HEAT EXCHANGERSECTION DAMPER
SECTION D
E
LOUVER*BASE FRAMEOPTIONAL
LOUVER*
STANDING SEAMROOF*
B
4" DRAIN DRAIN
CONTROL BOX
* NOT REQUIRED ON INDOOR UNITS
MODEL # CFM WINTER EFFECTIVENESS
SUMMER EFFECTIVENESS A B C D E
PRC 1000 1000 90.2 82.2 122 31 48 25.5 21
PRC 1500 1500 90.2 82.2 122 42 50 36.5 22
PRC 2000 2000 90.2 82.3 122 44 52 38.5 23
PRC 2500 2500 90.3 82.3 122 53 52 47.5 23
PRC 3000 3000 90.3 82.4 126 53 60 47.5 27
PRC 3500 3500 90.3 83.3 124 61 60 55.5 27
PRC 4000 4000 90.3 82.4 130 55 76 49.5 35
PRC 4500 4500 90.4 82.5 130 60 76 54.5 35
PRC 5000 5000 90.3 82.4 132 63 76 57.5 35
PRC 5500 5500 90.3 82.4 132 69 76 63.5 35
PRC 6000 6000 90.4 82.5 136 67 84 61.5 39
PRC 6500 6500 90.3 82.4 136 72 84 66.5 39
PRC 7500 7500 90.3 82.3 138 74 92 68.5 43
PRC 8500 8500 90.3 82.4 138 83 92 77.5 43
PRC 9500 9500 90.4 82.5 146 78 107 72.5 50.5
PRC 10500 10500 90.3 82.4 146 85 107 79.5 50.5
PRC 11500 11500 90.3 82.4 144 93 107 87.5 50.5
PRC 12500 12500 90.3 82.5 144 100 107 94.5 50.5
9v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRC 15000 TO 40000 DIMENSIONAL DATA
MODEL # CFMWINTER
EFFECTIVENESSSUMMER
EFFECTIVENESSA B C D E
PRC 15000 15000 90.4 82.5 168 119 107 114.5 50.5
PRC 17500 17500 90.3 82.4 168 137 107 132.5 50.5
PRC 20000 20000 90.3 82.4 204 126 131 121.5 62.5
PRC 22500 22500 90.2 82.3 204 141 131 136.5 62.5
PRC 25000 25000 90.0 81.9 212 156 131 151.5 62.5
PRC 30000 30000 90.3 82.3 212 178 154 173.5 74
PRC 35000 35000 90.2 82.2 190 180 154 175.5 74
PRC 40000 40000 90.1 82.1 200 178 178 173.5 86
SA AIRFLOW
RA AIRFLOW
EA / OA
EA / OA
MODEL # CFM WINTER EFFECTIVENESS
SUMMER EFFECTIVENESS A B C D E
PRC 15000 15000 90.4 82.5 150 119 107 114.5 50.5
PRC 17500 17500 90.3 82.4 150 137 107 132.5 50.5
PRC 20000 20000 90.3 82.4 158 126 131 121.5 62.5
PRC 22500 22500 90.2 82.3 158 141 131 136.5 62.5
PRC 25000 25000 90.0 81.9 158 156 131 151.5 62.5
PRC 30000 30000 90.3 82.3 160 178 154 173.5 74
PRC 35000 35000 90.2 82.2 168 180 154 175.5 74
PRC 40000 40000 90.1 82.1 176 178 178 173.5 86
* NOT REQUIRED ON INDOOR UNITS
EQUALS SPLIT FOR SHIPMENTS
DRAIN DRAIN
CONTROL BOX
B
4"
BASE FRAME
ROOF*STANDING SEAM
LOUVER*RETURN FAN
SECTIONHEAT EXCHANGER
S
SECTION
SUPPLY FAN /FILTERSECTION
HEAT EXCHANGERSECTION
DAMPERSECTION
S
C
2"
A
6" LOUVER*
B
D
E
10 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.0750 1000 1250 1500 1750
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
2000 2250 2500 2750 3000
PRC1000 - Winter
PRC1000 - Summer
PRC1500 - Winter
PRC1500 - Summer
PRC2000 - Winter
PRC2000 - Summer
PRC2500 - Winter
PRC2500 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
11v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.02000 2500 3000 3500 4000
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
4500 5000 5500
PRC3000 - Winter
PRC3000 - Summer
PRC3500 - Winter
PRC3500 - Summer
PRC4000 - Winter
PRC4000 - Summer
PRC4500 - Winter
PRC4500 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
12 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.04000 4500 5000 5500 6000
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
6500 7000 7500 8000 8500 9000
PRC5000 - Winter PRC5500 - Winter PRC6000 - Winter PRC6500 - Winter
PRC6500 - Summer
PRC7500 - Winter
PRC7500 - SummerPRC5500 - Summer PRC6000 - SummerPRC5000 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
13v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.06500 7500 8500 9500 10500
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
11500 12500 13500 14500 15500
PRC8500 - Winter PRC9500 - Winter PRC10500 - Winter PRC11500 - Winter
PRC11500 - Summer
PRC12500 - Winter
PRC12500 - SummerPRC9500 - Summer PRC10500 - SummerPRC8500 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
14 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.011000 13000 15000 17000 19000
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
21000 23000 25000 27000
PRC22500 - Winter
PRC22500 - Summer
PRC17500 - Winter
PRC17500 - Summer
PRC20000 - Winter
PRC20000 - Summer
PRC15000 - Winter
PRC15000 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
15v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRC PERFORMANCE DATA
95.0
90.0
85.0
80.0
75.020000 25000 30000 35000 40000
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
45000 50000
PRC40000 - Winter
PRC40000 - Summer
PRC30000 - Winter
PRC30000 - Summer
PRC35000 - Winter
PRC35000 - Summer
PRC25000 - Winter
PRC25000 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
16 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
PRCLC DIMENSIONAL DATA
EA / FA EA / FASA AIRFLOW
RA AIRFLOW
MODEL # CFM WINTER EFFECTIVENESS
SUMMER EFFECTIVENESS A B C D E F G
PRCLC 250 250 90.4 82.5 76 40 24.5 18.3 6.5 17 17
PRCLC 375 375 90.4 82.5 76 40 24.5 18.3 6.5 17 17
PRCLC 500 500 90.3 82.4 78 44 24.5 18.3 6.5 17 17
PRCLC 700 700 90.3 82.3 80 54 24.5 18.3 10.5 20 17
PRCLC 1000 1000 90.2 82.2 84 60 26.5 26.3 10.5 24 24
PRCLC 1500 1500 90.3 82.3 92 64 48.5 42.3 10.5 25 40
PRCLC 2000 2000 90.2 82.3 94 64 63 56.8 10.5 24 48
G
F
DAMPER MOTORFILTER
FILTER
EXCHANGEREXCHANGER
RETURN BLOWER
HEATHEAT
CONTROLSDAMPERS
A
1.5
1.5
DRAIN DRAIN
E
D
B
C
E
D
17v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
PRCLC PERFOMANCE DATA
95.0
90.0
85.0
80.0
75.0175 275 375 475 575
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
675 775 875
PRCLC250 - Winter
PRCLC250 - Summer
PRCLC375 - Winter
PRCLC375 - Summer
PRCLC500 - Winter
PRCLC500 - Summer
PRCLC700- Winter
PRCLC700 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
18 For more information visit www.priceindustries.com | v001
PRC / PRCLC Regencore
95.0
90.0
85.0
80.0
75.0750 950 1150 1350 1550
Airflow, cfm
Sens
ible
Effe
ctiv
enes
s, %
1750 1950 2150 2350 2550
PRCLC1000 - Winter
PRCLC1000 - Summer
PRCLC1500 - Winter
PRCLC1500 - Summer
PRCLC2000 - Winter
PRCLC2000 - Summer
Effectiveness calculations include the following assumptions: + Ducted indoor units with 1 in. w.c. ESP + Winter outdoor air at 35°F, and return air at 70°F, inclusive of fan and motor loads + Summer outdoor air at 95°F, and return air at 75°F + Effectiveness will vary based on air conditions
PRCLC PERFOMANCE DATA
19v001 | For more information visit www.priceindustries.com
PRC / PRCLC Regencore
Product Improvement is a continuing endeavour at Price. Therefore, specifications are subject to change without notice.Consult your Price Sales Representative for current specifications or more detailed information. Not all products may be
available in all geographic areas. All goods described in this document are warranted as described in the Limited Warrantyshown at priceindustries.com. The complete Price product catalog can be viewed online at priceindustries.com.
® Price is a registered trademark of Price Industries Limited. © 2018. Printed in Canada. v001