72
Powerware 9125 Two-in-One UPS 700–2000 VA User’s Guide ®

Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

Embed Size (px)

Citation preview

Page 1: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

Powerware 9125 Two-in-One UPS700–2000 VAUser’s Guide

®

Page 2: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

US Patent 6,160,722

Requesting a Declaration of ConformityUnits that are labeled with a CE mark comply with the following harmonized standards and EU directives:

S Harmonized Standards: EN 62040-1-1 and EN 50091-2; IEC 60950-1

S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits93/68/EEC, Amending Directive 73/23/EEC89/336/EEC, Council Directive relating to electromagnetic compatibility92/31/EEC, Amending Directive 89/336/EEC relating to EMC

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the ECDeclaration of Conformity, contact:

Eaton Power Quality OyKoskelontie 13FIN-02920 EspooFinlandPhone: +358-9-452 661Fax: +358-9-452 665 68

Powerware, ABM, X-Slot, LanSafe, and FERRUPS are registered trademarks and ConnectUPS is a trademark ofEaton Electrical Inc. Modbus is a registered trademark of Modicon. AS/400 is a registered trademark of InternationalBusiness Machines Corp.

ECopyright 1999–2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may bereproduced in any way without the express written approval of Eaton Corporation.

Page 3: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

Class B EMC StatementsFCC Part 15NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant topart 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference ina residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installedand used in accordance with the instructions, may cause harmful interference to radio communications. However,there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmfulinterference to radio or television reception, which can be determined by turning the equipment off and on, the useris encouraged to try to correct the interference by one or more of the following measures:

S Reorient or relocate the receiving antenna.

S Increase the separation between the equipment and the receiver.

S Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

S Consult the dealer or an experienced radio/TV technician for help.

ICES-003This Class B Interference Causing Equipment meets all requirements of the Canadian Interference CausingEquipment Regulations ICES-003.

Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur duCanada.

VCCI Notice

Page 4: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

Special SymbolsThe following are examples of symbols used on the UPS or accessories to alert you to importantinformation:

RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and theassociated warning should be observed.

CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual foradditional information, such as important operating and maintenanceinstructions.

RJ-45 RECEPTACLE - For 230V models only: this receptacle provides networkinterface connections. Do not plug telephone or telecommunications equipmentinto this receptacle.

This symbol indicates that you should not discard the UPS or the UPS batteriesin the trash. This product contains sealed, lead-acid batteries and must bedisposed of properly. For more information, contact your local recycling/reuse orhazardous waste center.

This symbol indicates that you should not discard waste electrical or electronicequipment (WEEE) in the trash. For proper disposal, contact your localrecycling/reuse or hazardous waste center.

Page 5: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com i

Table of Contents

1 Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Safety Warnings 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Installation 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Inspecting the Equipment 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Connecting the UPS Internal Battery 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Setup 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rack-Mount Setup 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Tower Setup 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installing the UPS 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Remote Emergency Power-off Installation 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Rear Panels 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 Operation 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Turning the UPS On 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Starting the UPS on Battery 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Turning the UPS Off 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Initiating the Self-Test 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operating Modes 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Normal Mode 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Battery Mode 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bypass Mode 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Standby Mode 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5 Configuration 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6 Additional UPS Features 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .X-Slot Cards 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Single-Port Card 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .USB Card 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Network Transient Protector 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Load Segments 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

TABLE OF CONTENTS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.comii

7 UPS Maintenance 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS and Battery Care 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Storing the UPS and Batteries 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .When to Replace Batteries 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Replacing Batteries 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

How to Replace Internal Batteries 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .How to Replace Extended Battery Modules 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Testing New Batteries 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Recycling the Used Battery or UPS 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 Specifications 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9 Troubleshooting 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Audible Alarms and UPS Conditions 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Silencing an Audible Alarm 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Service and Support 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10 Warranty 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Two-Year Limited Warranty (US and Canada) 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Ten-Year Pro-Rated Limited Warranty (US and Canada) 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Load Protection Guarantee (US and Canada) 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 7: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 1

Chapter 1 Introduction

The Powerware® 9125 uninterruptible power system (UPS) protectsyour sensitive electronic equipment from the most common powerproblems including power failures, power sags, power surges,brownouts, line noise, high voltage spikes, frequency variations,switching transients, and harmonic distortion.

Power outages can occur when you least expect it and powerquality can be erratic. These power problems have the potential tocorrupt critical data, destroy unsaved work sessions, and damagehardware — causing hours of lost productivity and expensive repairs.

With the Powerware 9125, you can safely eliminate the effects of powerdisturbances and guard the integrity of your equipment. Figure 1 showsthe Powerware 9125 UPS with an optional Extended Battery Module(EBM).

Figure 1. The Powerware 9125 UPS with Optional EBM

Providing outstanding performance and reliability, the Powerware 9125’sunique benefits include the following:

S Online UPS design with pure sine wave output. The UPS filters andregulates incoming AC power and provides consistent power to yourequipment without draining the battery.

S 2U rack height that conserves valuable rack space.

S Two-in-one form factor for using the UPS in a rack-mountconfiguration or as a standalone cabinet.

S ABM® technology that uses advanced battery management toincrease battery service life, optimize recharge time, and provide awarning before the end of useful battery life.

S Hours of extended runtime with up to four EBMs.

Page 8: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INTRODUCTION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com2

S Start-on-battery capability for powering up the UPS even if utilitypower is not available.

S Hot-swappable batteries that simplify maintenance by allowing you toreplace batteries safely without powering down the critical load.

S Emergency shutdown control through the remote emergencypower-off (REPO) port.

S Optional X-Slot® cards with enhanced communication capabilities forincreased power protection and control.

S Network transient protector that guards your networkcommunications equipment from surges. Low voltage models canalso protect modems, fax machines, or other telecommunicationsequipment.

S Advanced power management with the Software Suite CD forgraceful shutdowns and power monitoring.

S Sequential shutdown and load management through separatereceptacle groups, called load segments.

S Backed by worldwide agency approvals.

Page 9: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 3

Chapter 2 Safety Warnings

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS

This manual contains important instructions that you should follow during installation andmaintenance of the UPS and batteries. Please read all instructions before operating theequipment and save this manual for future reference.

DANGERThis UPS contains LETHAL VOLTAGES. All repairs and service should be performed byAUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTSinside the UPS.

WARNINGS This UPS contains its own energy source (batteries). The output receptacles may carry

live voltage even when the UPS is not connected to an AC supply.

S For 220–240V models, the output receptacles may remain electrically live. If the inputpower source in your application is wired line-to-neutral (as in most Europeanapplications), the voltage to the output receptacles is 0V. With line-to-line input wiring,the voltage to the output receptacles is 110–120V (measured from line-to-ground orline-to-neutral, depending on the UPS wiring).

S Do not remove or unplug the input cord when the UPS is turned on. This removes thesafety ground from the UPS and the equipment connected to the UPS.

S To reduce the risk of fire or electric shock, install this UPS in a temperature and humiditycontrolled, indoor environment, free of conductive contaminants. Ambient temperaturemust not exceed 40°C (104°F). Do not operate near water or excessive humidity (95%maximum).

S To comply with international standards and wiring regulations, the total equipmentconnected to the output of this UPS must not have an earth leakage current greater than1.5 milliamperes.

Page 10: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com4

CAUTIONS Batteries can present a risk of electrical shock or burn from high short-circuit current.

Observe proper precautions. Servicing should be performed by qualified servicepersonnel knowledgeable of batteries and required precautions. Keep unauthorizedpersonnel away from batteries.

S Proper disposal of batteries is required. Refer to your local codes for disposalrequirements.

S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.

Sikkerhedsanvisninger

VIGTIGE SIKKERHEDSANVISNINGERGEM DISSE ANVISNINGER

Denne manual indeholder vigtige instruktioner, som skal følges under installation ogvedligeholdelse af UPS’en og batterierne. Læs venligst alle instruktioner inden betjening afudstyret og gem denne manual mhp. fremtidige opslag.

FAREDenne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse børkun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kanrepareres af brugeren.

ADVARSEL!S Denne UPS indeholder sin egen energikilde (batterier). Udgangsstikkene kan endog være

strømførende, når UPS’en ikke er koblet til en vekselstrømsforsyning.

S På 220–240V-modeller kan udgangsstikkene være strømførende. Hvis ledningsføringentil indgangsstrømkilden på din enhed er fase-til-neutral (som på de fleste europæiskeenheder), er spændingen til udgangsstikkene 0V. Med en fase-til-faseindgangsledningsføring er spændingen til udgangsstikkene 110–120V (målt frafase-til-jord eller fase-til-neutral, afhængig af UPS-ledningsføringen).

S Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt.Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.

S Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit forledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød.Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller højfugtighed (maksimalt 95%).

S I overensstemmelse med internationale normer og bestemmelser for el-installation mådet udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride enjordafdelingsspænding på mere end 1,5 milliampere.

Page 11: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 5

ADVARSELS Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj

kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres afkvalificeret servicepersonale med kendskab til batterier og gældende forsigtighedsregler.Hold uautoriseret personale væk fra batterierne.

S Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler forbortskaffelsesprocedurer.

S Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere vedåben ild.

Belangrijke Veiligheidsinstructies

BELANGRIJKE VEILIGHEIDSINSTRUCTIESBEWAAR DEZE INSTRUCTIES

Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie enhet onderhoud van de UPS en de accu’s. Lees alle instructies voordat u de apparatuur inbedrijf neemt en bewaar deze handleiding als naslagwerk.

GEVAARDeze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties enonderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd.Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen wordenGEREPAREERD.

WAARSCHUWINGS Deze UPS bevat een eigen energiebron (batterijen). De uitgangscontactdoos kan onder

spanning staan, zelfs wanneer de UPS niet is aangesloten op de netspanning.

S Bij de modellen van 220–240V kan de uitgangscontactdoos onder spanning blijven staan.Als de bedrading van de ingangsspanningsbron in uw systeem loopt van fase naar aarde(zoals bij de meeste Europese systemen) dan bedraagt de spanning op deuitgangscontactdozen 0 V. Als de ingangsbedrading loopt van fase naar fase danbedraagt de spanning op de uitgangscontactdozen 110–120V (gemeten tussen fase enaarde of tussen fase en neutraal, afhankelijk van de UPS-bedrading).

S Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl deUPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geenaardebeveiliging meer hebben.

Page 12: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com6

S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in eengebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geengeleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C nietoverschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid(max. 95%).

S Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de geheleapparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom vanmeer dan 1,5 milliampère hebben.

OPGELETS Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden

veroorzaken door een grote kortsluitstroom. Neem de juiste voorzorgsmaatregelen inacht. Het onderhoud moet worden uitgevoerd door bevoegde onderhoudsmonteurs dieverstand hebben van accu’s en op de hoogte zijn van de vereiste voorzorgsmaatregelen.Houd onbevoegden uit de buurt van de accu’s.

S De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uwplaatselijke voorschriften.

S Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.

Page 13: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 7

Tarkeita Turvaohjeita

TÄRKEITÄ TURVAOHJEITA - SUOMISÄILYTÄ NÄMÄ OHJEET

Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS-virtalähteen ja akkujenasennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohjemyöhempää tarvetta varten.

VAARATämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot onjätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄNKÄYTTÄJÄN HUOLLETTAVIA OSIA.

VAROITUSS Tässä UPS-virtalähteessä on oma energianlähde (akut). Lähtövastakkeissa voi olla

jännite, vaikka UPS-virtalähdettä ei ole kytketty verkkovirtaan.

S 220–240V -malleissa lähtövastakkeissa voi säilyä jännite. Jos sovelluksen tulovirtalähdeon johdotettu linjasta neutraaliin (kuten useimmissa eurooppalaisissa sovelluksissa)lähtövastakkeiden jännite on 0 V. Linjasta linjaan –tulojohdotuksessa lähtövastakkeidenjännite on 110–120V (mitataan linjasta maahan tai linjasta neutraaliin, UPS-virtalähteenjohdotuksesta riippuen).

S Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaaturvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.

S Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtaviaepäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältäkosteita tiloja (95 % maksimi).

S Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteenulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA).

VAROS Akut voivat aiheuttaa sähköiskun tai palovammojen vaaran johtuen suuresta

oikosulkuvirrasta. Noudata kaikkia asianmukaisia varotoimia. Laitteen saa huoltaa vainammattitaitoinen huoltohenkilökunta, joka tuntee akut ja niihin liittyvät varotoimet. Äläpäästä valtuuttamatonta henkilöstöä lähelle akkuja.

S Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.

S Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.

Page 14: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com8

Consignes de sécurité

CONSIGNES DE SÉCURITÉ IMPORTANTESCONSERVER CES INSTRUCTIONS

Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de touteprocédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulterentièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuelafin de pouvoir vous y reporter ultérieurement.

DANGER!Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et deréparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.

AVERTISSEMENT!S Cette onduleur possède sa propre source d’alimentation (batteries). Il est possible que

les prises de sortie soient sous tension même lorsque l’onduleur n’est pas connectée àune alimentation CA.

S En ce qui concerne les modèles 220–240 V, il est possible que les prises de sortierestent sous tension. Si la source d’alimentation de votre application est câblée phase etneutre (comme dans la majorité des applications européennes), la tension vers les prisesde sortie est de 0 V. Avec un câblage d’entrée phase à phase, la tension vers les prisesde sortie est de 110–120 V (mesurée entre phase et terre ou phase et neutre suivant lecâblage de l’onduleur).

S Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine desupprimer la mise à la terre de l’onduleur et du matériel connecté.

S Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleuruniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où latempérature et l’humidité ambiantes sont contrôlées. La température ambiante ne doitpas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphèreexcessivement humide (95 % maximum).

S Afin d’être conforme aux normes et règlements internationaux de câblage, le courant defuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pasdépasser 1,5 mA.

Page 15: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 9

ATTENTION!S Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant

d’un courant de court-circuit haute intensité. Observez les précautions appropriées.L’entretien doit être réalisé par du personnel qualifié connaissant bien les batteries etles précautions nécessaires. N’autorisez aucun personnel non qualifié à manipuler lesbatteries.

S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlementsen vigueur dans votre localité.

S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faireexploser.

Sicherheitswarnungen

WICHTIGE SICHERHEITSANWEISUNGENAUFBEWAREN

Dieses Handbuch enthält wichtige Anweisungen, die Sie während der Installation undWartung des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterienbefolgen müssen. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit demGerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.

WARNUNGDie USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten solltennur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzerzu wartenden Komponenten.

ACHTUNGS Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene

Energiequelle (Batterien). Die Ausgangssteckdosen können Spannung führen, auch wenndas USV nicht an eine Wechselstromquelle angeschlossen ist.

S Bei Modellen mit 220–240 Volt können die Ausgangssteckverbinder stromführendbleiben. Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist(wie in den meisten europäischen Anlagen), beträgt die Spannung an denAusgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt dieSpannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zuMasse oder Leitung zu Masseleiter, abhängig von der USV-Verkabelung.

S Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist,weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenenGeräten entfernt wird.

Page 16: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com10

S Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mitkontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitendenSchmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)betreiben.

S Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an denAusgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom voninsgesamt 1,5 Milliampere nicht überschreiten.

VORSICHT!S Batterien können das Risiko eines elektrischen Schlags bergen oder durch hohen

Kurzschlussstrom in Brand geraten. Die richtigen Vorsichtsmaßnahmen beachten. DieWartung muss von qualifiziertem Wartungspersonal durchgeführt werden, das imUmgang mit Batterien geübt ist und über gute Kenntnisse der erforderlichenVorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten.

S Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichenBestimmungen zu beachten.

S Batterien niemals verbrennen, da sie explodieren können.

Avvisi di sicurezza

IMPORTANTI ISTRUZIONI DI SICUREZZACONSERVARE QUESTE ISTRUZIONI

Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e lamanutenzione dell’UPS e delle batterie. Leggere integralmente le istruzioni prima diutilizzare l’apparecchiatura e conservare il presente manuale per futuro riferimento.

PERICOLOLa TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazionidi riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DAPERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON visono PARTI RIPARABILI DALL’UTENTE.

Page 17: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 11

AVVERTENZAS L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita possono essere

sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA.

S Nei modelli da 220–240 V è possibile che le prese d’uscita rimangano sotto tensione. Sela fonte di alimentazione in entrata dell’installazione è costituita da un collegamentolinea-neutro (come accade nella maggior parte delle installazioni europee), la tensionedelle prese d’uscita è pari a 0 V. Con un cablaggio in entrata del tipo linea-linea, latensione sulle prese d’uscita è 110–120 V (con misurazione effettuata da linea a terra oda linea a neutro in base al cablaggio dell’UPS).

S Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di continuità èacceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza delgruppo statico di continuità e dell’apparecchiatura ad esso collegata.

S Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico dicontinuità in un ambiente interno a temperatura ed umidità controllata, privo di agenticontaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Nonutilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).

S Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tuttal’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avereuna corrente di dispersione di terra superiore a 1,5 milliampere.

ATTENZIONES Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a

un’elevata corrente di corto circuito. Osservare le dovute precauzioni. L’assistenza deveessere eseguita da personale qualificato esperto di batterie e delle necessarieprecauzioni. Tenere il personale non autorizzato lontano dalle batterie.

S Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fareriferimento alle disposizioni locali.

S Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte allefiamme.

Page 18: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com12

Viktig Sikkerhetsinformasion

VIKTIGE SIKKERHETSINSTRUKSJONERGJEM DISSE INSTRUKSJONENE

Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering ogvedlikehold av UPS-enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, oggjem håndboken til fremtidig referanse.

FARLIGDenne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kunutføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅNOEN AV DELENE i UPS’en.

FARLIGS UPS-enheten inneholder sin egen energikilde (batterier). Utgangsstikkene kan være

strømførende selv når UPS-enheten ikke er koblet til et strømuttak.

S Utgangsstikkene kan være strømførende for 220–240V modellene. Spenningen tilutgangsstikkene vil være 0 V dersom din enhets strømkilde er fase-til-nøytral (som på defleste europeiske enheter). Med ledningsført fase-til-fase inngang vil spenningen tilutgangsstikkene være 110–120V (målt fra fase-til-jord eller fase-til-nøytral, avhenging avUPS-ledningsføringen).

S Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at ikkesikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet med den.

S For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i etinnendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes inærheten av vann eller ved meget høy luftfuktighet (95% maks.).

S Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere totallekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonalestandarder og forkablingsbestemmelser.

Page 19: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 13

FORSIKTIGS Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm.

Treff passende forholdsregler. Service bør utføres av kvalifisert servicepersonale medkjennskap til batterier og nødvendige forholdsregler. Hold uautorisert personale borte frabatteriene.

S Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning avbatterier.

S Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.

Regulamentos de Segurança

INSTRUÇÕES DE SEGURANÇA IMPORTANTESGUARDE ESTAS INSTRUÇÕES

Este manual contém instruções importantes que devem ser seguidas durante a instalação emanutenção do no-break e das baterias. Leia todas as instruções antes de operar oequipamento e guarde este manual para consultá-lo futuramente.

CUIDADOA UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem serexecutados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não hánenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.

ADVERTÊNCIAS Este no-break possui sua própria fonte de energia (baterias). As tomadas de saída podem

estar energizadas mesmo que o no-break não esteja conectado a uma fonte de energiaelétrica.

S Nos modelos 220–240V, pode ser que as tomadas de saída permaneçam energizadas.Se a alimentação da sua aplicação for do tipo fase-neutro (como ocorre na maioria dasaplicações na Europa), a tensão das tomadas de saída é de 0 V. Com a alimentaçãofase-fase, a tensão das tomadas de saída é de 110–120V (medida como fase-terra oufase-neutro, dependendo da instalação elétrica do no-break).

S Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Istoremoverá o aterramento de segurança da UPS e do equipamento conectado.

Page 20: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com14

S Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambienteinterno com temperatura e umidade controladas e livres de contaminadores condutíveis.A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou emumidade excessiva (máx: 95%).

S Para estar de acordo com os padrões internacionais e os regulamentos de fiação, oequipamento total conectado à saída desta UPS não deve ter uma corrente de fuga àterra maior que 1,5 miliampères.

PERIGOS As baterias podem oferecer risco de choque elétrico ou queimadura, ocasionados por

alta tensão com possibilidade de curto-circuito. Tome as precauções adequadas. Amanutenção deve ser realizada por pessoal qualificado, com conhecimento sobrebaterias e ciente das precauções exigidas. Mantenha o pessoal não autorizado afastadodas baterias.

S Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do localpara maiores informações sobre os regulamentos de descarte de produtos.

S Nunca jogue as baterias no fogo, porque há risco de explosão.

Предупреждения по мерам безопасности

ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИСОХРАНИТЕ ЭТИ УКАЗАНИЯ

В данном руководстве содержатся важные инструкции по установке иобслуживанию источника бесперебойного питания (ИБП) и батарей. Передработой с оборудованием прочтите все инструкции. Сохраните данноеруководство для дальнейшего использования.

ОПАСНОВ данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Всеработы по ремонту и обслуживанию должны выполняться ТОЛЬКОУПОЛНОМОЧЕННЫМОБСЛУЖИВАЮЩИМПЕРСОНАЛОМ. ВнутриИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.

Page 21: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 15

ПРЕДУПРЕЖДЕНИЕS В данном ИБП установлены собственные источники энергии (батареи).

На выходных розетках может быть напряжение, даже если ИБП неподключен к сети переменного тока.

S На выходных розетках моделей с напряжением 220-240 В может бытьнапряжение. Если устройство рассчитано на тип подключения“фаза-нейтраль” (как большинство устройств, изготавливаемых в Европе),напряжение на выходных розетках равно 0 В. При типе подключения“фаза-фаза” напряжение на выходных розетках составляет 110-120 В (приизмерении “фаза-земля” или “фаза-нейтраль”, в зависимости отэлектрической схемы ИБП).

S Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки привключенном ИБП. При этом защитное заземление отключается от ИБП иот оборудования, подключенного к ИПБ.

S Для снижения опасности пожара или поражения электрическим токомустанавливайте ИБП в закрытом помещении с контролируемымитемпературой и влажностью, в котором отсутствуют проводящиезагрязняющие вещества. Температура окружающего воздуха не должнапревышать 40°С. Не эксплуатируйте устройство около воды или в местах сповышенной влажностью (макс. 95%).

S Для обеспечения соблюдения требований международных стандартов итребований к разводке электрических цепей, суммарная величина токаутечки на землю всего оборудования, подключенного к выходу ИБП, недолжна превышать 1,5 миллиампера.

ОСТОРОЖНОS Высокое напряжение, вызванное коротким замыканием в батарее, может

привести к поражению электрическим током или ожогу. Соблюдайтемеры предосторожности. Техническое обслуживание должноосуществляться квалифицированным персоналом по работе систочниками питания, знакомым с мерами предосторожности. Недопускайте к работе с батареями посторонних.

S Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь кместным нормативным актам за информацией о требованиях кутилизации.

S Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могутвзорваться под воздействием огня.

Page 22: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com16

Advertencias de Seguridad

INSTRUCCIONES DE SEGURIDAD IMPORTANTESGUARDE ESTAS INSTRUCCIONES

Este manual contiene instrucciones importantes que debe seguir durante la instalación y elmantenimiento del SIE y de las baterías. Por favor, lea todas las instrucciones antes deponer en funcionamiento el equipo y guarde este manual para referencia en el futuro.

PELIGROEste SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico debenser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hayNINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.

ADVERTENCIAS Este SIE contiene su propia fuente de energía (baterías). Los receptáculos de salida

pueden transportar voltaje activo aun cuando el SIE no esté conectado con una fuente deCA.

S Para los modelos 220–240V, es posible que los receptáculos de salida permanezcaneléctricamente activos. Si la fuente de energía de entrada de su aplicación estácableada de línea a neutro (como la mayoría de las aplicaciones europeas), el voltaje alos receptáculos de salida es 0V. Con cableado de entrada de línea a línea, el voltajehacia los receptáculos de salida es 110–120V (medido de línea a tierra o de línea aneutro, lo que dependerá del cableado del SIE).

S No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Estosuprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.

S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugarcubierto, con temperatura y humedad controladas, libre de contaminantes conductores.La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o conhumedad excesiva (95% máximo).

S Para cumplir con los estándares internacionales y las normas de instalación, la totalidadde los equipos conectados a la salida de este SIE no debe tener una intensidad depérdida a tierra superior a los 1,5 miliamperios.

Page 23: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 17

PRECAUCIÓNS Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por

corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado deservicio que conozca de baterías y esté al tanto de las precauciones requeridas debedarle servicio al equipo. Mantenga al personal no autorizado alejado de las baterías.

S Es necesario desechar las baterías de un modo adecuado. Consulte las normas localespara conocer los requisitos pertinentes.

S Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone ala llama.

Säkerhetsföreskrifter

VIKTIGA SÄKERHETSFÖRESKRIFTERSPARA DESSA FÖRESKRIFTER

Den här anvisningen innehåller viktiga instruktioner som du ska följa under installation ochunderhåll av UPS-enheten och batterierna. Läs alla instruktioner innan du använderutrustningen och spara den här anvisningen för framtida referens.

FARADenna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERADSERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar somANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.

VARNINGS Den här UPS-enheten innehåller sin egen energikälla (batterier). Uttagen kan vara

spänningsförande även då UPS-enheten inte är ansluten till spänningsnätet.

S På modellerna 220 – 240 V kan de utgående uttagen fortfarande vara strömförande. Omden ingående strömkällan i din applikation är kopplad ledare-till-nolla (det vanligaste iEuropa) är spänningen till de utgående uttagen 0 V. Är den ingående strömkällan koppladledare-till-ledare är spänningen i de utgående uttagen 110–120 V (uppmätt frånledare-till-jord eller ledare-till-nolla beroende på UPS:ens anslutning).

S Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningenfrån både UPS-enheten och den anslutna utrustningen.

Page 24: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SAFETY WARNINGS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com18

S Minska risken för brand eller elektriska stötar genom att installera denna UPS-enhetinomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledandeföroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inteutrustningen nära vatten eller vid hög luftfuktighet (max 95 %).

S För att överensstämma med internationell standard och installationsföreskrifter får inteden totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström somöverstiger 1,5 milliampere.

VIKTIGTS Batterierna kan innebära en risk för elektrisk stöt eller brännskada från kortsluten

starkström. Iakttag lämpliga försiktighetsåtgärder. Service ska utföras av utbildadservicepersonal med kunskap om batterierna och nödvändiga försiktighetsåtgärder. Hållej behörig personal borta från batterierna.

S Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.

S Använda batterier får aldrig brännas upp. De kan explodera.

Page 25: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 19

Chapter 3 Installation

This section explains:

S Equipment inspection

S UPS internal battery connection

S UPS setup and installation, including Extended Battery Modules(EBMs)

S Remote emergency power-off (REPO) installation

S UPS rear panels

Inspecting the Equipment

If any equipment has been damaged during shipment, keep the shippingcartons and packing materials for the carrier or place of purchase and filea claim for shipping damage. If you discover damage after acceptance,file a claim for concealed damage.

To file a claim for shipping damage or concealed damage: 1) File withthe carrier within 15 days of receipt of the equipment; 2) Send a copy ofthe damage claim within 15 days to your service representative.

NOTE Check the battery recharge date on the shipping carton label. If the date has expiredand the batteries were never recharged, do not use the UPS. Contact your servicerepresentative.

Page 26: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com20

Connecting the UPS Internal Battery

To ensure proper battery operation:

1. Verify that the UPS is off and unplugged.

2. Remove the UPS front cover (see Figure 2).

Figure 2. Removing the UPS Front Cover

3. Connect the internal battery connector (see Figure 3).

Figure 3. Connecting the Internal Battery Connector

4. Replace the UPS front cover (see Figure 4).

Figure 4. Replacing the UPS Front Cover

5. Continue to the following section, “UPS Setup.”

Page 27: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 21

UPS Setup

The Powerware 9125 UPS is designed for flexible configurations and canbe installed in a rack or as a standalone cabinet.

If you are installing the UPS in a rack, continue to the following section“Rack-Mount Setup;” otherwise, continue to “Tower Setup” onpage 22.

Rack-Mount Setup

The UPS can be installed in 19- or 23-inch racks and needs only 2U ofvaluable rack space.

CAUTIONThe UPS and EBM are heavy (see page 53). A minimum of two people are required to lift thecabinets into the rack.

NOTE Mounting rails are required for each UPS and EBM cabinet. If rails are not alreadyinstalled in your rack, contact your local distributor to order rail kits.

To install the UPS and optional EBMs in a rack:

1. Place the UPS on a flat, stable surface with the front of the UPSfacing toward you.

2. Attach the supplied mounting handles to the mounting brackets andsecure with the supplied screws (see Figure 5).

3. Align the mounting brackets with the screw holes on the sides ofthe UPS and secure with the supplied screws (see Figure 5).

4. If installing optional EBMs, repeat Steps 1 through 3 for eachcabinet.

MountingHandle

MountingBracket

Figure 5. Installing the Mounting Handles and Brackets

Page 28: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com22

NOTE The EBMs must be installed below the UPS as shown in Figure 6.

5. Slide the UPS and any optional EBMs into the rack.

6. Secure the cabinets to the rack according to the rail kit instructions.

7. Continue to “Installing the UPS” on page 25 to complete theinstallation.

UPS

OptionalEBMs

Figure 6. Rack-Mount UPS with EBMs

Tower Setup

The tower setup varies depending on the number of cabinets you areinstalling:

1. For one cabinet, the pedestals must be installed. Continue to Step 2.

For two or more cabinets, the joining brackets must be installed. Skipto Step 6.

2. Place the UPS cabinet horizontally so that the left end of the cabinetis accessible (see Figure 7).

3. Slide and align the UPS pedestals with the screw holes on the endof the UPS cabinet. Secure the pedestals with the screws providedin the accessory kit.

Figure 7. Installing the UPS Pedestals

Page 29: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 23

4. Carefully position the cabinet upright with the air vents at the top(see Figure 8).

5. Continue to “Installing the UPS” on page 25 to complete theinstallation.

Air Vents

Figure 8. UPS with Pedestals

6. Carefully position the cabinets upright with the air vents at the top(see Figure 9).

Air Vents

Figure 9. Tower UPS with EBMs

Page 30: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com24

7. Remove the adjacent corner screws from the rear panels as shownin Figure 10 to install the joining brackets. Discard the screws.

8. Align each joining bracket with the screw holes and secure with thescrews provided in the accessory kit.

9. If installing additional EBMs, repeat Steps 7 and 8 for each cabinet.

10. Continue to the following section, “Installing the UPS,” to completethe installation.

Joining Bracket

Joining Bracket

EBM UPS

Figure 10. Installing the Joining Brackets

Page 31: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 25

Installing the UPS

NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damagemay occur to your equipment and void your warranty.

Figure 11 shows a typical installation only. See “UPS Rear Panels” onpage 29 for the rear panel of each model.

To install the UPS and optional EBMs:

1. If installing an optional EBM, continue to Step 2; otherwise, skip toStep 3.

2. Plug the EBM cable(s) into the battery connector(s) as shown inFigure 11. Up to four EBMs may be connected to the UPS.

UPS BatteryConnector

Power Cord

EBM Cable

Output ReceptaclesCommunication Port

UPS

EBM

EBM

EBM Battery Connectors

Figure 11. Typical UPS Installation with Two EBMs

3. If you are installing power management software, connect yourcomputer to the UPS communication port using the suppliedcommunication cable.

4. Plug the equipment to be protected into the appropriate UPS outputreceptacles (see page 46 for more information on load segments).

NOTE DO NOT protect laser printers with the UPS because of the exceptionally high powerrequirements of the heating elements.

Page 32: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com26

5. If an emergency power-off (disconnect) switch is required by localcodes, see the following section, “Remote Emergency Power-offInstallation,” to install the REPO switch before powering on theUPS.

6. For 230V models only. Plug the detachable UPS power cord into theinput connector on the UPS rear panel.

7. Plug the UPS power cord into a power outlet.

All front panel indicators flash briefly and the UPS conducts aself-test. When the self-test is complete, theμ indicator flashes,indicating the UPS is in Standby mode with the equipment offline. Ifthe or indicator flashes, see page 59.

Site Wiring FaultIndicator

Battery ServiceIndicator

Figure 12. Fault Indicators

8. Press the On button.

Theμ indicator illuminates solid and the bar graph indicatorsdisplay the percentage of load being applied to the UPS. The UPS isnow in Normal mode and supplying power to your equipment.

To change the factory-set defaults, see “Configuration” on page 37.

NOTE The batteries charge to 80% capacity in approximately 2 hours. However, it isrecommended that the batteries charge for 36 hours after installation or long-term storage.

NOTE If you installed power management software and optional EBMs, ensure maximumbattery runtime by using the ERM configurator tool on the Software Suite CD and connectinga minimum load of 10% (15% recommended) to the UPS.

Page 33: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 27

Remote Emergency Power-off Installation

The Powerware 9125 includes a REPO port that allows power to beswitched off at the UPS output receptacles from a customer-suppliedswitch in a remote location.

The REPO feature shuts down the protected equipment immediatelyand does not follow the orderly shutdown procedure initiated by anypower management software.

Any devices that are operating on battery power are also shut downimmediately. When the REPO switch is reset, the equipment will notreturn to battery power until the UPS is manually restarted.

If the Off button is pressed after the REPO is activated, the UPSremains in Standby mode when restarted until the On button ispressed.

WARNINGThe REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must beseparated from any hazardous voltage circuits by reinforced insulation.

CAUTIONTo ensure the UPS stops supplying power to the load during any mode of operation, theinput power must be disconnected from the UPS when the emergency power-off function isactivated.

NOTE The REPO function activates when the REPO contacts close.

NOTE For Europe, the emergency switch requirements are detailed in Harmonizeddocument HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety,Chapter 46: Isolation and Switching.”

To install the REPO switch:

1. Verify that the UPS is off and unplugged.

2. Remove the REPO connector from the accessory kit.

3. Connect isolated, normally-open, dry contacts (rated to handle60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum)across the REPO device to Pin 1 and Pin 2 (see Figure 13).Use stranded, non-shielded wiring, size 0.75 mm2–0.5 mm2

(18–20 AWG).

Page 34: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com28

NOTE A separate contact must simultaneously cause UPS input AC power to be removed.

Pin 1 Pin 2

Figure 13. REPO Connector

4. Connect the REPO connector to the REPO port on the UPS rearpanel.

5. Verify that the externally-connected REPO switch is not activated toenable power to the UPS output receptacles.

6. Plug in the UPS and start the UPS by pressing the On button.

7. Activate the external REPO switch to test the REPO function.

8. De-activate the external REPO switch and restart the UPS.

Page 35: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 29

UPS Rear Panels

This section shows the rear panels of the Powerware 9125 models.

REPO Port

5-15 Receptacles

Battery Connector

Power Cordwith 5-15 Plug

Communication Port

Network Transient Protector

X-SlotCommunication Bay

Figure 14. 700–1500 VA, 120V Rear Panel

REPO Port

5-15 Receptacles

Battery Connector

Circuit Breakers

Power Cordwith 5-20 Plug

Network Transient Protector

Communication Port

X-SlotCommunication Bay

Figure 15. 2000 VA, 120V Rear Panel (with 5-15R)

Page 36: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

INSTALLATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com30

REPO Port

5-15 Receptacles

Battery Connector

Circuit Breakers

Power Cord with5-20 Plug

Network Transient Protector

Communication Port

X-SlotCommunication Bay

5-20 Receptacles

Figure 16. 2000 VA, 120V Rear Panel (with 5-20R)

Network Transient Protector

IEC-320Receptacles

Battery Connector

IEC-320 Input ConnectorCommunication Port

X-SlotCommunication Bay

REPO Port

Figure 17. 700–2000 VA, 230V Rear Panel

Page 37: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 31

Chapter 4 Operation

This section describes:

S Turning the UPS on and off

S Starting the UPS on battery

S Initiating the self-test

S Operating modes

Turning the UPS On

After the UPS is connected to a power outlet, it conducts a self-test andenters Standby mode.

To turn on the UPS, press the On button on the front panel. Theμindicator illuminates solid and the bar graph indicators display thepercentage of load being applied to the UPS.

Starting the UPS on Battery

To turn on the UPS without using utility power, press and hold theOn button for at least four seconds. The UPS starts up in Battery modeand supplies battery power to your equipment. When the UPS starts onbattery, it does not conduct a self-test to conserve battery power.

Page 38: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

OPERATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com32

Turning the UPS Off

NOTE Pressing the Off button while the UPS is in Battery mode causes the UPS to shutdown immediately.

To turn off the UPS:

1. Prepare your equipment for shutdown.

2. Press and hold the Off button for approximately three seconds.The UPS transfers to Standby mode (if utility power is available) andremoves power from your equipment.

3. Unplug the UPS; the UPS shuts down in five seconds. All frontpanel indicators flash briefly twice prior to shutdown.

If you do not unplug the UPS, it remains in Standby mode.

Initiating the Self-Test

NOTE The batteries must be fully charged and the UPS must not be in Battery mode toperform the self-test.

NOTE Load must be applied to the UPS to perform the battery test. Apply the followingload amounts according to the UPS rating: 50% load for 700 VA; 35% load for 1000 VA; 45%load for 1250 VA; 38% load for 1500 VA; or 25% load for 2000 VA.

Press and hold the button for three seconds to initiate the self-test.During the five-second test, the bar graph indicators cycle through twice.If the alarm beeps or a UPS alarm indicator stays on, see Table 10 onpage 58.

Page 39: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

OPERATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 33

Operating Modes

The Powerware 9125 front panel indicates the UPS status through theUPS indicators. Figure 18 shows the UPS front panel indicators andcontrols.

Flashing

Unlit

Lit

Indicator LegendTest/Alarm Reset Button

On ButtonOff Button

Bypass Mode Indicator

Battery Mode Indicator

Normal Mode Indicator

Bar Graph Indicators

Alarm Indicators (see page 57)

Figure 18. UPS Front Panel

Page 40: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

OPERATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com34

Normal Mode

During Normal mode, theμ indicator illuminates and the front paneldisplays the percentage of UPS load capacity being used by theprotected equipment (see Figure 19). The UPS monitors and charges thebatteries as needed and provides power protection to your equipment.

<10%

10–25%

26–50%

51–75%

76–100%

>100%

Figure 19. Load Level Indicators

When all of the bar graph indicators are illuminated and the indicatorflashes, power requirements exceed UPS capacity; see page 59 formore information.

Page 41: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

OPERATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 35

Battery Mode

When the UPS is operating during a power outage, the alarm beepsonce per second and the + --- indicator illuminates. The front paneldisplays the approximate percentage of battery capacity remaining (seeFigure 20).

>75%

>50%

>25%

Low Battery Warning

Shutdown Imminent

Figure 20. Battery Capacity Indicators

If battery capacity becomes low while in Battery mode, the indicatorstarts flashing and the alarm becomes continuous. This warning isapproximate, and the actual time to the Shutdown Imminent warningmay vary significantly.

NOTE Depending on the UPS load and number of Extended Battery Modules (EBMs), theLow Battery warning may occur before the batteries reach 25% capacity. See Table 9 onpage 56 for estimated runtimes.

When shutdown is imminent, the indicator flashes. Immediatelycomplete and save your work to prevent data loss and similar difficulties.

If utility power returns before UPS shutdown, the UPS transfers toNormal mode operation while the battery recharges.

If utility power returns after UPS shutdown, the UPS automaticallyrestarts.

Page 42: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

OPERATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com36

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers yourequipment to utility power. Battery mode is not available; however, theutility power continues to be passively filtered by the UPS. The

indicator illuminates. The UPS transfers to Bypass mode when:

S The UPS has an overtemperature condition.

S The UPS has an overload condition of 101 to 110% for 2 minutes.

S The UPS has an overload condition of 111 to 150% for 30 seconds.

S The UPS detects a fault in the battery or UPS electronics.

Standby Mode

When the UPS is turned off and remains plugged into a power outlet,the UPS is in Standby mode. Theμ indicator flashes and the bar graphindicators are off, indicating that power is not available to yourequipment. The battery recharges when necessary.

NOTE For 220–240V models, the output receptacles may remain electrically live (up to110–120V). Unplug the UPS to ensure power is not available to the output receptacles.

Page 43: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 37

Chapter 5 Configuration

When the UPS is in Configuration mode, the bar graph indicatorsrepresent the configuration options. Use the control buttons(On button and button) to modify the UPS configuration. Figure 21shows the LEDs and Table 1 explains the corresponding options.

NOTE The UPS can be configured while in Battery mode. If the UPS transfers to batterypower while in Configuration mode, the UPS remains in Configuration mode and indicatesBattery mode on the front panel after exiting Configuration mode.

CAUTIONDO NOT press the Off button while the UPS is in Configuration mode; pressing theOff button removes all power to your equipment immediately and the UPS entersStandby mode.

To reconfigure the UPS default settings:

1. Press and hold the On button and the button simultaneouslyfor approximately three seconds. The UPS transfers toConfiguration mode.

The LEDs flash briefly and then display the enabled options.

2. Press the On button to scroll through the options. Each time youpress the button, the UPS beeps. The LED for the selected optionindicates the current setting; flashing represents disabled options(see Figure 21 and Table 1).

Scrolling past the last LED returns to the first configuration option.

If you press the On button and nothing happens, the UPS is still inOperation mode. Repeat Step 1 to enter Configuration mode, andthen perform Step 2.

3. Press the button ONCE to select the Voltage option or to togglethe Site Wiring Fault Alarm or AC Input Failure Alarm on or off.

NOTE The UPS automatically exits Configuration mode after two minutes.

Page 44: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

CONFIGURATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com38

4. Press and hold the On button and the button simultaneouslyfor three seconds to exit Configuration mode at any time.

1Press and hold the On and Test/Alarm Resetbuttons simultaneously for three seconds totoggle between Configuration and Operationmodes.

& 4Press the Test/Alarm Resetbutton ONCE to select anoption.

3

Press the On button toscroll to the next option.

2

On ButtonTest/AlarmReset Button

Configuration Mode LEDs

Figure 21. Using Configuration Mode

Page 45: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

CONFIGURATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 39

Table 1. Configuration Mode LEDs and Options

Configuration ModeLEDs Option LED Status Explanation

120/230VNominal InputVoltage

On (default) Nominal input voltage is 120V for low voltage models and230V for high voltage models.All other nominal input voltages are disabled.

Flashing 120/230V is disabled; one of the other input voltage options isselected.

110/220VNominal InputVoltage

On Nominal input voltage is 110V for low voltage models 220Vfor high voltage models.All other nominal input voltages are disabled.

Flashing(default)

110/220V is disabled; one of the other input voltage options isselected.

127/240VNominal InputVoltage

On Nominal input voltage is 127V for low voltage models and240V for high voltage models.All other nominal input voltages are disabled.

Flashing(default)

127/240V is disabled; one of the other input voltage options isselected.

Site WiringFault Alarm

On (default) Alarm sounds when the polarity of the outlet is reversed orthe ground connection is missing; have a qualifiedelectrician repair the outlet wiring.

Flashing* Alarm DOES NOT sound when the polarity of the outlet isreversed or the ground connection is missing.* For 230V models, Site Wiring Fault is not available (flashingis the only status).

AC InputFailure

On (default) Alarm sounds when there is an AC input failure.Failure

Flashing Alarm DOES NOT sound when there is an AC input failure.

NOTE 208V nominal input voltage is available. Contact the Help Desk at one of the telephone numbers on page 60 forassistance.

Page 46: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

CONFIGURATION

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com40

Page 47: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 41

Chapter 6 Additional UPS Features

This section describes:

S X-Slot cards

S Network transient protector

S Load segments

X-Slot Cards

X-Slot cards allow the UPS to communicate in a variety of networkingenvironments and with different types of devices. The Powerware 9125is factory-installed with a Single-Port Card or USB Card, depending onthe customer order.

S ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilitiesas well as monitoring through a Web browser interface; connects to atwisted-pair Ethernet (10/100BaseT) network. It has a built-inswitching hub that allows three additional network devices to beconnected to the network without the requirement of additionalnetwork drops. In addition, a Powerware Environmental MonitoringProbe can be attached to obtain humidity, temperature, smoke alarm,and security information.

S Relay Interface Card - has isolated dry contact (Form-C) relay outputsfor UPS status: Utility failure, Low battery, UPS alarm/OK, or Onbypass.

S Modbus® Card - allows you to continuously and reliably monitor theUPSs in your Building Management System (BMS).

S Multi-Server Card - has six serial communication ports that cancommunicate simultaneously with other computers using PowerwareLanSafe® Power Management Software (provided on the SoftwareSuite CD).

S Single-Port Card - connects to the Powerware Expansion Chassis toenable multiple communication options or to a PC for powermanagement control.

S USB Card - connects to a USB port on your computer.

t

Page 48: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

ADDITIONAL UPS FEATURES

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com42

Relay Interface Card

Multi-Server Card

X-Slot Communication Bay(Single-Port Card shown)

USB Card

ConnectUPS-X Web/SNMP Card

Modbus Card

Figure 22. Optional X-Slot Cards

Single-Port Card

To establish communication between the UPS and a computer, connectyour computer to the UPS communication port using the suppliedcommunication cable.

When the communication cable is installed, power managementsoftware can exchange data with the UPS. The software polls the UPSfor detailed information on the status of the power environment. If apower emergency occurs, the software initiates the saving of all dataand an orderly shutdown of the equipment.

The cable pins are identified in Figure 23 and the pin functions aredescribed in Table 2.

3

8 79

1

6

245

Figure 23. Communication Port

Page 49: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

ADDITIONAL UPS FEATURES

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 43

Table 2. Communication Port Pin Assignment

Pin Number Signal Name Function Direction from the UPS

1 Low Batt Low Battery relay contact; 20 mA, 30 Vdc contact rating Out

2 TxD Transmit to external device Out

3 RxD Receive from external device In

4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In

5 GND Signal common (tied to chassis) —

6 DSR To external device (tied to Pin 4) Out

7 RTS PnP from external device (default) or On Bypass relaycontact (jumper-selectable)

In / Out

8 AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Out

9 Power Source +V (8 to 24 volts DC power) Out

The On-Bypass Relay Contact. You can enable the On-Bypass relay usingthe jumper on the Single-Port Card. The jumper default is disabled.

To enable the On-Bypass relay:

1. Remove the Single-Port Card on the UPS rear panel. Retain thescrews (see Figure 24).

Figure 24. Removing the Single-Port Card

2. Move the J3 jumper to the AS/400® position to enable theOn-Bypass relay as shown in Figure 25.

Page 50: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

ADDITIONAL UPS FEATURES

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com44

On-Bypass Relay Jumper(J3)

On-BypassDisabled

On-BypassEnabled

AS/400NORM

Figure 25. On-Bypass Relay Jumper

3. To prevent electrostatic discharge (ESD), place one hand on a metalsurface such as the UPS rear panel.

Align the Single-Port Card with the slot guides and slide the cardinto the slot until it is firmly seated.

4. Secure the Single-Port Card with the screws removed in Step 1.

USB Card

With this card, the UPS can communicate with a USB-compliantcomputer using Powerware LanSafe Power Management Software(v5.0.1 or higher).

To establish communication between the UPS and a computer:

1. Connect the USB cable to the USB port on your computer.

2. Install the Powerware LanSafe software and USB drivers accordingto the instructions provided with the Software Suite CD.

Page 51: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

ADDITIONAL UPS FEATURES

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 45

Network Transient Protector

The network transient protector, shown in Figure 26, is located on therear panel and has jacks labeled IN and OUT. This featureaccommodates a single RJ-45 (10BaseT) network connector.

Low voltage models can also accommodate an RJ-11 telephoneconnector that provides protection for modems, fax machines, or othertelecommunications equipment. As with most modem equipment, it isnot advisable to use this jack in digital PBX (Private Branch Exchange)environments.

NOTE DO NOT connect any telephone or fax/modem equipment to the 230V models; onlynetwork protection is available for 230V models.

1. Connect the network or telephone (low voltage models only) cableto the jack labeled IN.

2. Connect the input connector of the equipment you are protecting tothe jack labeled OUT.

IN OUT

OUTIN

NETWORK TRANSIENT PROTECTOR

Figure 26. Network Transient Protector

Page 52: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

ADDITIONAL UPS FEATURES

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com46

Load Segments

Load segments are sets of receptacles that can be controlled by powermanagement software, providing an orderly shutdown and startup ofyour equipment. For example, during a power outage, you can keep keypieces of equipment running while you turn off other equipment. Thisfeature allows you to save battery power. See your power managementsoftware manual for details (refer to the Software Suite CD orwww.powerware.com for the latest information).

NOTE If power management software is not used, the individual load segments cannot becontrolled.

Each UPS has two load segments as shown in Figure 27 and Figure 28.Figure 27 shows the load segments for all models except thePW9125 2000 20R model (shown in Figure 28).

Load Segment 2

Load Segment 1

Figure 27. UPS Load Segments (120V Model Shown)

Load Segment 1

Load Segment 2

Figure 28. UPS Load Segments for PW9125 2000 20R

Page 53: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 47

Chapter 7 UPS Maintenance

This section explains how to:

S Care for the UPS and batteries

S Replace the batteries

S Test new batteries

S Recycle used batteries or UPS

UPS and Battery Care

For the best preventive maintenance, keep the area around the UPSclean and dust-free. If the atmosphere is very dusty, clean the outside ofthe system with a vacuum cleaner.

For full battery life, keep the UPS at an ambient temperature of25°C (77°F).

NOTE If the UPS requires any type of transportation, verify that the UPS is unplugged andturned off and then disconnect the UPS internal battery connector using the steps in“Connecting the UPS Internal Battery” on page 20 in reverse order.

NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of servicelife varies, depending on the frequency of usage and ambient temperature. Batteries usedbeyond expected service life will often have severely reduced runtimes. Replace batteries atleast every 5 years to keep units running at peak efficiency.

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every12 months by plugging the UPS into a power outlet. The batteriescharge to 80% capacity in approximately 2 hours. However, it isrecommended that the batteries charge for 36 hours after long-termstorage.

Check the battery recharge date on the shipping carton label. If the datehas expired and the batteries were never recharged, do not use theUPS. Contact your service representative.

Page 54: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

UPS MAINTENANCE

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com48

When to Replace Batteries

When the indicator flashes, the batteries may need replacing.Conduct a self-test by pressing and holding the button for threeseconds. After the test is complete, the indicator should turn off (itmay take a few seconds to turn off). If the indicator continues toflash, contact your service representative to order new batteries.

Replacing Batteries

NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

With the hot-swappable battery feature, UPS batteries can be replacedeasily without turning the UPS off or disconnecting the load.

If you prefer to remove input power to change the batteries, see“Turning the UPS Off” on page 32.

Consider all warnings, cautions, and notes before replacing batteries.

WARNINGS Batteries can present a risk of electrical shock or burn from high short-circuit current. The

following precautions should be observed: 1) Remove watches, rings, or other metalobjects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top ofbatteries.

S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.Attempting to alter wiring can cause injury.

Page 55: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

UPS MAINTENANCE

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 49

How to Replace Internal Batteries

CAUTIONPull the battery out onto a flat, stable surface. The battery is unsupported when you pull itout of the UPS.

To replace the UPS internal batteries:

1. Remove the UPS front cover (see Figure 29).

NOTE DO NOT attempt to open the left side.

Figure 29. Removing the UPS Front Cover

2. Unscrew and set aside the battery retaining bracket (see Figure 30).

3. Disconnect the battery cable from the UPS battery connector andremove the battery cable from the wire clips.

Battery Retaining Bracket

Wire Clips

BatteryConnector

Figure 30. Accessing the UPS Internal Battery

Page 56: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

UPS MAINTENANCE

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com50

4. Pull the battery out onto a flat, stable surface (see Figure 31). See“Recycling the Used Battery or UPS” on page 52 for properdisposal.

Figure 31. Removing the Battery

5. Slide the new battery into the UPS.

6. Reconnect the battery cable and secure the battery cable in thewire clips.

7. Reinstall the battery retaining bracket and screws removed inStep 2.

8. Replace the UPS front cover.

How to Replace Extended Battery Modules

CAUTIONThe Extended Battery Module (EBM) is heavy (see page 53). A minimum of two people arerequired to lift the cabinets into the rack.

To replace the EBMs:

1. Unplug the EBM cable from the UPS.

If additional EBMs are installed, unplug the EBM cable from thebattery connector on each EBM.

2. If the EBM is in a tower configuration, remove the joining brackets.

3. If the EBM is in a rack, install the supplied mounting handles andbrackets on the new EBM.

Page 57: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

UPS MAINTENANCE

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 51

4. Replace the EBM. See “Recycling the Used Battery or UPS” onpage 52 for proper disposal.

5. Reinstall the joining brackets if removed in Step 2.

6. Plug the new EBM into the UPS as shown in Figure 32.

For additional EBMs, plug the EBM cable into the battery connectoron the adjacent EBM.

UPS BatteryConnector

Joining Brackets

EBM BatteryConnectors

EBM Cables

Figure 32. EBM Connections (120V Model Shown)

NOTE The battery connectors are designed to ensure proper connection with the correctEBM model (use EBM model PW9125 24 EBM with 700–1000 VA UPSs and EBM modelPW9125 48 EBM with 1250–2000 VA UPSs).

Page 58: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

UPS MAINTENANCE

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com52

Testing New Batteries

NOTE The batteries must be fully charged and the UPS must not be in Battery mode toperform the self-test.

NOTE For an accurate battery test, apply the following load amounts to the UPS:50% load for 700 VA; 35% load for 1000 VA; 45% load for 1250 VA; 38% load for 1500 VA; or25% load for 2000 VA.

Press and hold the button for three seconds to initiate a self-test.After the test is complete, the indicator should turn off (it may take afew seconds to turn off). If the indicator continues to flash, checkthe battery connections. Call your service representative if the problempersists.

Recycling the Used Battery or UPS

Contact your local recycling or hazardous waste center for informationon proper disposal of the used battery or UPS.

WARNINGS Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper

disposal of batteries is required. Refer to your local codes for disposal requirements.

S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to theskin and eyes. It may be toxic.

CAUTIONDo not discard the UPS or the UPS batteries in the trash. This product contains sealed,lead-acid batteries and must be disposed of properly. For more information, contact yourlocal recycling/reuse or hazardous waste center.

CAUTIONDo not discard waste electrical or electronic equipment (WEEE) in the trash. For properdisposal, contact your local recycling/reuse or hazardous waste center.

Page 59: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 53

Chapter 8 Specifications

This section provides the following specifications:

S Model list

S Weights and dimensions

S Electrical input and output

S Environmental and safety

S Battery

Table 3. Model List

120V Models 230V Models

UPS Models PW9125 700PW9125 1000PW9125 1250PW9125 1500PW9125 2000

PW9125 2000 20R

PW9125 700iPW9125 1000iPW9125 1250iPW9125 1500iPW9125 2000i

NOTE The model numbers shown are for gray units; model numbers for black units end with “BLK.”

Table 4. Weights and Dimensions

UPS Extended Battery Module (EBM)

Dimensions(WxDxH)

43.2 x 49.3 x 8.9 cm17.0” x 19.4” x 3.5” (2U)

43.2 x 49.3 x 8.9 cm17.0” x 19.4” x 3.5” (2U)

Weights 700–1000 VA: 15 kg (34 lb)1250–2000 VA: 23 kg (50 lb)

29.5 kg (65 lb)

Page 60: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SPECIFICATIONS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com54

Table 5. Electrical Input

120V Models 230V Models

Nominal Voltage 120V default; 110, 120, 127V selectable* 230V default; 220, 230, 240V selectable*

Voltage Range 80–144V for 110, 120, 127V nominal 160–288V for 220, 230, 240V nominal

Nominal Frequency 45–65 Hz, 50/60 Hz auto-sensing

Noise Filtering MOVs and line filter for normal and common mode noise

Connections 700–1500 VA: 6-ft, 5-15P power cord2000 VA: 6-ft, 5-20P power cord

10A, IEC 320-C14 input connector

* 208V nominal input voltage is available. Contact the Help Desk at one of the telephone numbers on page 60 forassistance.

Table 6. Electrical Output

120V Models 230V Models

Power Levels (Rated atNominal Inputs)

PW9125 700: 700 VA, 490WPW9125 1000: 1000 VA, 700WPW9125 1250: 1250 VA, 875WPW9125 1500: 1500 VA, 1050WPW9125 2000: 2000 VA, 1400W

PW9125 2000 20R: 2000 VA, 1400W

PW9125 700i: 700 VA, 490WPW9125 1000i: 1000 VA, 700WPW9125 1250i: 1250 VA, 875WPW9125 1500i: 1500 VA, 1050WPW9125 2000i: 2000 VA, 1400W

Regulation(Normal Mode)

Nominal output voltage ±3%

Regulation(Battery Mode)

Nominal output voltage ±3%

Voltage Waveform Normal mode: Sine wave; <5% THD with full PFC and nonlinear load

Output Receptacles (6) 5-15RPW9125 2000 20R only: (4) 5-20R, (2) 5-15R

(6) IEC-320

Page 61: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SPECIFICATIONS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 55

Table 7. Environmental and Safety

120V Models 230V Models

Operating Temperature 0°C to 40°C (32°F to 104°F)Optimal battery performance: 25°C (77°F)

Storage Temperature 0°C to 25°C (32°F to 77°F)

Transit Temperature -25°C to 55°C (-13°F to 131°F)

Relative Humidity 5–90% noncondensing

Operating Altitude Up to 3,000 meters above sea level

Transit Altitude Up to 10,000 meters above sea level

Heat Dissipation(Recharge Mode up to8 Hours)

700 VA: 472 BTU/hr1000 VA: 601 BTU/hr1250 VA: 879 BTU/hr1500 VA: 986 BTU/hr

2000 VA: 1201 BTU/hr

Audible Noise Less than 45 dBA Normal mode, typical loadLess than 50 dBA Battery mode

Surge Suppression ANSI C62.41 Category B (formerly IEEE 587)

Safety Conformance UL 1778, UL 497A;CSA C22.2, No. 107.1, 107.2;

NOM-019-SCFI

UL 1778, UL 497A;CSA C22.2, No. 107.1, 107.2;

EN 62040-1-1 and IEC 60950-1;NOM-019-SCFI

Agency Markings cULus, CSA, NOM cULus, CSA, CE, NOM, NEMKO

EMC (Class B) FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003, VCCI

Table 8. Battery

UPS Configuration 700–1000 VA: (2) 12V, 9 Ah internal batteries1250–2000 VA: (4) 12V, 9 Ah internal batteries

EBM Configuration PW9125 24 EBM: (8) 12V, 9 AhPW9125 48 EBM: (8) 12V, 9 Ah

Type Sealed, maintenance-free, valve-regulated, lead-acid

Charging Internal battery: approximately 2 hours to 80% usable capacityat nominal line voltage after full load discharge

External battery: no more than 10x discharge time to 90% usable capacityat nominal line voltage after full load discharge

Monitoring Advanced monitoring for earlier failure detection and warning

Page 62: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

SPECIFICATIONS

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com56

Table 9. Battery Runtimes (in Minutes)

700–1000 VA Models

Load UPS InternalBatteries +1 EBM +2 EBMs +3 EBMs +4 EBMs

200 VA/140W 37 271 546

400 VA/280W 19 142 278

700 VA/490W 9 72 156

850 VA/595W* 6 59 124

1000 VA/700W* 5 48 104

* Runtimes do not apply for 700 VA models.

1250–2000 VA Models

Load UPS InternalBatteries +1 EBM +2 EBMs +3 EBMs +4 EBMs

400 VA/280W 46 177 331 501 682

700 VA/490W 25 96 180 272 370

850 VA/595W 21 76 142 214 292

1000 VA/700W 16 61 115 174 237

1250 VA/875W 11 46 87 131 179

1500 VA/1050W** 8 37 70 106 144

1800 VA/1260W*** 6 30 57 85 116

2000 VA/1400W*** 5 26 49 74 100

** Runtimes do not apply for 1250 VA models.

*** Runtimes do not apply for 1250 VA and 1500 VA models.

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

Page 63: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 57

Chapter 9 Troubleshooting

This section explains:

S UPS alarms and conditions

S How to silence an alarm

S Service and support

Audible Alarms and UPS Conditions

The UPS has an audible alarm feature to alert you of potential powerproblems. Use Table 10 to determine and resolve the UPS alarms andconditions.

NOTE Some alarms, such as the Overtemperature and Overload alarms, must be cleared byshutting down and restarting the UPS (see page 59 for more information).

Flashing

Unlit

Lit

Indicator Legend

Self-Test

Test/AlarmReset Button

Battery ServiceSite Wiring Fault

Overtemperature

Overload

Figure 33. Alarm Indicators

Silencing an Audible Alarm

Before silencing an alarm, check the alarm condition and perform theapplicable action to resolve the condition (see Table 10).

To silence the alarm for an existing fault, press the button. If UPSstatus changes, the alarm beeps, overriding the previous alarm silencing.

Page 64: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

TROUBLESHOOTING

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com58

Table 10. Troubleshooting Guide

Alarm or Condition Possible Cause Action

The indicator is not on;the UPS does not start.μ The power cord is not

connected correctly.Check the power cord connections.

The wall outlet is faulty. Have a qualified electrician test and repair the outlet.

The remote emergencypower-off (REPO) switch isactive.

Reset the REPO switch and restart the UPS.

The indicator isflashing; power is notavailable at the UPS outputreceptacles.

μ The UPS is in Standbymode.

Press the On | button to supply power to the connectedequipment.

The UPS operates normally,but some or all of theprotected equipment is noton

The equipment is notconnected to the UPScorrectly.

Verify that the equipment is plugged into the UPSreceptacles.

on.The output receptaclecircuit breaker (2000 VAonly) is open.

Check the load. Disconnect faulty load equipment. Waitseveral minutes before resetting the UPS circuit breaker.

One of the load segmentshas been turned off throughthe power managementsoftware.

Reactivate the segment with the software.

Output circuit breaker trips(2000 VA only).

Load fault. Check the load. Disconnect faulty load equipment. Waitseveral minutes before resetting the UPS circuit breaker.

The UPS does not providethe expected backup time.

The battery needs chargingor service.

Plug the UPS into a power outlet for 36 hours to charge thebattery. After charging the battery, press and hold the

button for 3 seconds; then check the indicator.If the indicator is still flashing, see “ReplacingBatteries” on page 48.

Intermittent audible alarm

Battery The UPS is on battery (see“Battery Mode” on page 35for more information).

The UPS is powering the equipment with battery power.Check the bar graph indicators for available batterycapacity and prepare your equipment for shutdown.

Warning - Low Battery

Low Battery warning. This warning is approximate, and the actual time to theShutdown Imminent warning may vary significantly.Depending on the UPS load and number of ExtendedBattery Modules (EBMs), the Low Battery warning mayoccur before the batteries reach 25% capacity. SeeTable 9 on page 56 for estimated runtimes.

Page 65: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

TROUBLESHOOTING

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 59

ActionPossible CauseAlarm or Condition

Shutdown - Low Battery

Shutdown imminent. Prepare for a shutdown. Save your work and turn off yourequipment.

Bypass The UPS is in Bypass mode. The equipment is transferred to utility power; however,the utility power continues to be passively filtered by theUPS. Check for one of the following alarms:Overtemperature, Overload, or Battery Service.

Bypass Bypass is not available.Input voltage is not within±12% of nominal or inputfrequency is not within ±3%of nominal.

The UPS is receiving utility power that may be unstable orin brownout conditions. The UPS continues to supplypower to your equipment. If conditions worsen, the UPSmay switch to battery power.

Battery Service The battery may be fullydischarged.

Plug the UPS into a power outlet for 36 hours to charge thebattery. After charging the battery, press and hold the

button for 3 seconds; then check the indicator.If the indicator is still flashing, see “ReplacingBatteries” on page 48.

The battery is notconnected correctly.

Check the battery connections. Call your servicerepresentative if the problem persists.

Site Wiring Fault(120V models only)

Ground wire connectiondoes not exist or the lineand neutral wires arereversed in the wall outlet.

Have a qualified electrician correct the wiring.To disable this alarm, see “Configuration” on page 37.

OvertemperatureUPS internal temperature istoo high. The UPS transfersto Bypass mode, allowingthe UPS to cool.

Turn off and unplug the UPS. Clear vents and remove anyheat sources. Ensure the airflow around the UPS is notrestricted. Wait at least five minutes and restart the UPS.If the condition persists, contact your servicerepresentative.

OverloadContinuous audible alarm

Power requirementsexceed UPS capacity(101–110% for 2 minutes or111–150% for 30 seconds)or the load is defective.

Turn off and unplug the UPS. Remove some of theequipment from the UPS. Wait at least five seconds untilall LEDs are off and restart the UPS. You may need toobtain a larger capacity UPS.

Page 66: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

TROUBLESHOOTING

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com60

ActionPossible CauseAlarm or Condition

Self-TestThe self-test has notcompleted properly.

Verify that the proper amount of load is applied to the UPSbefore starting the self-test: 50% load for 700 VA; 35%load for 1000 VA; 45% load for 1250 VA; 38% load for1500 VA; or 25% load for 2000 VA.

UPS fault condition. Save your work and turn off your equipment. Turn off andunplug the UPS. Contact your service representative. Thealarm cannot be silenced.

Service and Support

If you have any questions or problems with the UPS, call your LocalDistributor or the Help Desk at one of the following telephone numbersand ask for a UPS technical representative.

United States: 1-800-356-5737 or 1-919-870-3149Canada: 1-800-461-9166 ext 260All other countries: Call your local service representative

Please have the following information ready when you call the HelpDesk:

S Model number

S Serial number

S Version number (if available)

S Date of failure or problem

S Symptoms of failure or problem

S Customer return address and contact information

If repair is required, you will be given a Returned Material Authorization(RMA) Number. This number must appear on the outside of the packageand on the Bill Of Lading (if applicable). Use the original packaging orrequest packaging from the Help Desk or distributor. Units damaged inshipment as a result of improper packaging are not covered underwarranty. A replacement or repair unit will be shipped, freight prepaid forall warrantied units.

NOTE For critical applications, immediate replacement may be available. Call the HelpDesk for the dealer or distributor nearest you.

Page 67: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 61

Chapter 10 Warranty

Two-Year Limited Warranty (US and Canada)

Powerware UPS Models: 3105, 3110, 3115, 9104, 9120, 9125, 9140, and FERRUPS® up to 3.1 kVAWARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a DelawareCorporation company (“Company”).

LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”)of any Powerware 3105, 3110, 3115, 9104, 9120, 9125, 9140, and FERRUPS up to 3.1 kVA Products (individuallyand collectively, the “Product”) purchased on or after June 1, 2004 and cannot be transferred. This Warranty applieseven in the event that the Product is initially sold by Company for resale to an End-User.

LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] inthe fifty (50) United States, the District of Columbia, and Canada is twenty-four (24) months from the date ofpurchase.

WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually andcollectively, the ”Warranted Items”) are free from defects in material and workmanship. If, in the opinion ofCompany, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s soleobligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor,as applicable), at the option of Company.

PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS: The Warranted Item will be repaired orreplaced at a Company site or such other location as determined by Company.

If the Warranted Item is to be replaced by Company, and the End-User supplies a credit card number or purchaseorder for the value of the replacement Product, Company will use commercially reasonable business efforts to ship(via standard ground shipment and at no cost to the End-User) the replacement Warranted Item to the End-Userwithin one (1) business day after Company receives notice of the warranty claim. In such case, the End-User mustreturn (at Company’s expense) the defective Warranted Item to Company in the same packaging as thereplacement Warranted Item received by the End-User or as otherwise instructed by Company. If Company doesnot receive the defective Warranted Item, Company will either charge the End-User’s credit card, or send theEnd-User an invoice (which the End-User agrees to pay), for the value of the replacement Product.

If the Warranted Item is to be replaced by Company, but the End-User is unwilling or unable to supply a credit cardnumber or purchase order for the value of the replacement Product, Company will use commercially reasonablebusiness efforts to ship (via standard ground shipment and at no cost to the End-User) the replacement WarrantedItem to the End-User within one (1) business day after Company receives the defective Product from the End-User.

In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges forreturn of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that arereplaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced byCompany shall become the property of Company.

Page 68: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

WARRANTY

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com62

WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damagescaused by: (a) failure to properly store the Product before installation, including the charge of batteries no later thanthe date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing byCompany personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) impropertesting, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Companypersonnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Productunder other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.

This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Itemsrepaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warrantysubject to all the terms thereof.

Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.

COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THEAPPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TOEND-USER.

COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOTCREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANTSOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTEDPURSUANT TO AN OPEN SOURCE LICENSE.

THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THEPRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHERWARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES INTHE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLELIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTYOBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDINGNEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.

LIMITATION OF LIABILITY: The remedies of the End-User set forth herein are exclusive and are the sole remediesfor any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than theProducts, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims ofcustomers of the End-User or any special, indirect, incidental or consequential damages whatsoever. The totalcumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liabilityis based.

Company shall not be responsible for failure to provide service or parts due to causes beyond Company’sreasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Productin a normal way; follow the Product’s user’s guide; and protect against further damage to the Product if there is acovered defect.

OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt byCompany of all payments due to it (including interest charges, if any). During such time as Company has notreceived payment of any amount due to it for the Product, in accordance with the contract terms under which theProduct is sold, Company shall have no obligation under this Warranty. Also during such time, the period of thisWarranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of anyoverdue or unpaid amounts.

Page 69: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

WARRANTY

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 63

COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services notexpressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspectionthat determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will beborne by the End-User.

OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outsideof the USA, call your local Powerware product sales or service representative, or call the Customer Reliability Centerin the USA at 919-870-3149. For comments or questions about this Warranty, write to the Customer QualityRepresentative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.

Ten-Year Pro-Rated Limited Warranty (US and Canada)

Powerware UPS Models: 5115, 5125, 5140, 9104, 9120, 9125, 9140, 9155, 9170+, and FERRUPSWARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a DelawareCorporation company (“Company”).

LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-User (the“End-User”) of any Powerware 5115, 5125, 5140, 9104, 9120, 9125, 9140, 9155, 9170+, and FERRUPS Products(individually and collectively, the “Product”) and cannot be transferred. This Warranty applies even in the event thatthe Product is initially sold by Company for resale to an End-User.

WHAT THIS WARRANTY COVERS: In addition to the standard Two-Year Limited Warranty covering the applicableProduct, the warrantor warrants that the Product will have a service life (defined below) of ten years from the dateof purchase (the “Ten-Year Service Life”) when used in accordance with the storage, handling, installation,operation and maintenance procedures prescribed in the Product’s user’s guide. “Service life” means the Product’sability to deliver at least 80% of its original rated backup time.

If Company finds, in its sole discretion, that any Product has not provided the Ten-Year Service Life, Company will,as its sole obligation and the End-User’s sole remedy for Company’s breach of this warranty, repair or replace theProduct, at its option, F.O.B. Company’s factory, for a charge, payable by the End-User to Company pro-rated on thefollowing basis:

The End-User will be allowed a credit against Company’s list price of equivalent equipment at the time of return ofthe Product to Company, in proportion to the percentage of Ten-Year Service Life remaining at the time of return ofthe Product to Company. In calculating the available credit, the remaining portion of the Ten-Year Service Life will berounded up or down to the nearest whole year. The End-User will assume responsibility to pay the balance of thelist price; and Company reserves the right to require payment prior to delivery of the repaired or replacementequipment.

For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:

Years 1-2 - Product repaired or replaced pursuant to terms of Limited Warranty

Years 3-10 - Unit Credit ($) = Current List Price × Years of Unexpired Life10 Years of Warranted Life

Page 70: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

WARRANTY

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com64

WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damagescaused by: (a) failure to properly store the Product before installation, including the charge of batteries no later thanthe date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing byCompany personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) impropertesting, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Companypersonnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Productunder other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.

This Warranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card withinthirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. AnyWarranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of theoriginal Warranty subject to all the terms thereof.

Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.

COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THEAPPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TOEND-USER.

COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOTCREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANTSOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTEDPURSUANT TO AN OPEN SOURCE LICENSE.

THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THEPRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHERWARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES INTHE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLELIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTYOBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDINGNEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.

LIMITATION OF LIABILITY: The remedies of the End-User set forth herein are exclusive and are the sole remediesfor any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than theProducts, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims ofcustomers of the End-User or any special, indirect, incidental or consequential damages whatsoever. The totalcumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liabilityis based.

Company shall not be responsible for failure to provide service or parts due to causes beyond Company’sreasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Productin a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to theProduct if there is a covered defect.

Page 71: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

WARRANTY

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com 65

OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt byCompany of all payments due to it (including interest charges, if any). During such time as Company has notreceived payment of any amount due to it for the Product, in accordance with the contract terms under which theProduct is sold, Company shall have no obligation under this Warranty. Also during such time, the period of thisWarranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of anyoverdue or unpaid amounts.

COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services notexpressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspectionthat determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will beborne by the End-User.

OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outsideof the USA, contact your local Powerware product sales or service representative, or call the Customer ReliabilityCenter in the USA at 919-870-3149. Company will not accept any Product for return, credit or exchange unlessexpressly authorized by Company in writing and delivered FOB Company factory. For comments or questions aboutthis Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina27616 USA.

Load Protection Guarantee (US and Canada)

Powerware UPS Models 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9140, 9150, 9155, 9170+, andFERRUPSGUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a DelawareCorporation company (“Company”).

LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the“End-User”) of any Powerware 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9140, 9150, 9155, 9170+, andFERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applieseven in the event that the Product is initially sold by Company for resale to an End-User.

WHAT THIS GUARANTY COVERS: For the lifetime of the Product, Guarantor promises to repair or replace, atGuarantor’s option, the equipment (valued up to the limits shown below*) that is damaged by an AC power linesurge, spike, or other transient when properly connected to Guarantor’s uninterruptible power system (“UPS”).Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the followingcircumstances arise:

1. The UPS is plugged into properly grounded and wired outlets, using no extension cords, adapters, other groundwires or other electrical connectors;

2. The installation of the UPS complies with all applicable electrical and safety codes described by the NationalElectric Code (NEC);

3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and

4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.

*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:

S $25,000 for Powerware UPS Models 3105, 3110, and 3115

S $150,000 for Powerware UPS Models 5110, 5115, and 5125

S $250,000 for Powerware UPS Models 9120, 9125, 9140, 9150, 9155, 9170+, and FERRUPS products

Page 72: Powerware 9125 Two-in-One UPS 700–2000 VA User’s …42u.com/pdf/powerware-9125-user-guide.pdf · EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514

WARRANTY

EATON Powerware® 9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com66

WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User’s equipment does notinclude reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damagescaused by: (a) failure to properly store the Product before installation, including the charge of batteries no later thanthe date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product notauthorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer orAgent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product notauthorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer orAgent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with theProduct’s labels or instructions.

This Guaranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card withinthirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.

Company shall not be responsible for any charges for testing, checking, removal or installation of any items.

LIMITATION OF LIABILITY: THE REMEDIES OF THE END-USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLEREMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISEPROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDINGNEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THEPRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OFCAPITAL, CLAIMS OF CUSTOMERS OF THE END-USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIALDAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS AREBASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OROTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE.

Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causesbeyond Company’s reasonable control.

END-USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End-User must use the Product ina normal way; follow the Product’s operation and maintenance manual; and protect against further damage to theProduct if there is a covered defect.

OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt byCompany of all payments due to it (including interest charges, if any). During such time as Company has notreceived payment of any amount due to it for the Product, in accordance with the contract terms under which theProduct is sold, Company shall have no obligation under this Guaranty.

COSTS NOT RELATED TO GUARANTY: The End-User shall be invoiced for, and shall pay for, all services notexpressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspectionthat determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will beborne by the End-User.

TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA,contact your local Powerware product sales or service representative, or call the Customer Reliability Center in theUSA at 919-870-3149. For comments or questions about this Load Protection Guaranty, write to the CustomerQuality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.