Power/Vac ® OEM Express SwitchgearMetalclad Switchgear4.16kV-250 MVA through13.8kV-1500 MVA

g

FULLY ASSEMBLEDMECHANICALLY

COMPLETE SWITCHGEARWITHOUT DEVICES

AND WIRE.

DEA-275

Page 2: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

POWER/VAC® OEM EXPRESS SWITCHGEAR

Designed with the OEM in mind, Power/Vac®

OEM Express is fully assembled mechanicallycomplete switchgear without devices andwire. This results in shorter cycles than fin-ished switchgear products, while allowing theOEM to add contributive value by mountingdevices and wiring the equipment. OEM Ex-press is the same robust, high quality design,

TABLE OF CONTENTSTABLE OF CONTENTSTABLE OF CONTENTSTABLE OF CONTENTSTABLE OF CONTENTS

GENERAL DESCRIPTIONGENERAL DESCRIPTIONGENERAL DESCRIPTIONGENERAL DESCRIPTIONGENERAL DESCRIPTION ........................................................................................................................................................................................................................................................................................................................................................................................................................................................11111

STSTSTSTSTANDARD DESIGN FEAANDARD DESIGN FEAANDARD DESIGN FEAANDARD DESIGN FEAANDARD DESIGN FEATURESTURESTURESTURESTURES ............................................................................................................................................................................................................................................................................................................................................................................................33333

VACUUM BREAKER DESIGNVACUUM BREAKER DESIGNVACUUM BREAKER DESIGNVACUUM BREAKER DESIGNVACUUM BREAKER DESIGN .....................................................................................................................................................................................................................................................................................................................................................................................................................44444

BREAKER FEABREAKER FEABREAKER FEABREAKER FEABREAKER FEATURESTURESTURESTURESTURES .................................................................................................................................................................................................................................................................................................................................................................................................................................................................................55555

RARARARARATINGS, WEIGHTS TINGS, WEIGHTS TINGS, WEIGHTS TINGS, WEIGHTS TINGS, WEIGHTS AND DIMENSIONSAND DIMENSIONSAND DIMENSIONSAND DIMENSIONSAND DIMENSIONS ................................................................................................................................................................................................................................................................................................................................77777

SECTION VIEWSSECTION VIEWSSECTION VIEWSSECTION VIEWSSECTION VIEWS...................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................88888

ROLLOUTSROLLOUTSROLLOUTSROLLOUTSROLLOUTS ...........................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................99999

AVAVAVAVAVAILABLE UNIT COMBINAAILABLE UNIT COMBINAAILABLE UNIT COMBINAAILABLE UNIT COMBINAAILABLE UNIT COMBINATIONSTIONSTIONSTIONSTIONS ...................................................................................................................................................................................................................................................................................................................................................................1010101010

CIRCUIT BREAKER CHARACTERISTICSCIRCUIT BREAKER CHARACTERISTICSCIRCUIT BREAKER CHARACTERISTICSCIRCUIT BREAKER CHARACTERISTICSCIRCUIT BREAKER CHARACTERISTICS ............................................................................................................................................................................................................................................................................................................ 1111111111

NON-STNON-STNON-STNON-STNON-STANDARD ANDARD ANDARD ANDARD ANDARD AND HIGH CLOSEAND HIGH CLOSEAND HIGH CLOSEAND HIGH CLOSEAND HIGH CLOSE

AND LAAND LAAND LAAND LAAND LATCH CAPTCH CAPTCH CAPTCH CAPTCH CAPABILITYABILITYABILITYABILITYABILITY CIRCUIT BREAKERS CIRCUIT BREAKERS CIRCUIT BREAKERS CIRCUIT BREAKERS CIRCUIT BREAKERS...........................................................................................................................................................................................................................................1212121212

g

which has made Power/Vac® switchgear andPower/Vac® breakers the most recognizedname in the industry for medium voltageswitchgear. A full range of ratings are avail-able from 5kV 250mva through 15kV1500mva. Both indoor and outdoor construc-tion is offered along with a wide variety ofstacking configurations.

1

Page 3: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

OEM EXPRESS SWITCHGEARPOWER/VAC®—QUALITY, EXPERIENCE & RELIABLITYTAILORED TO THE NEEDS OF THE OEM

In 1977 General Electric introduced POWER/VAC® and trans-formed the metalclad switchgear industry. Clean quiet, reliable anddurable, POWER/VAC® metalclad switchgear offered significant ad-vantages over air magnetic designs. Now many companies offervacuum switchgear, many of them look like POWER/VAC®, but notone can match POWER/VAC’s years of in-service experience.

More Than 40 Yearsof Interrupter Experience

GE pioneered experimental vacuum interrupters in the 1920’s.Refined it and introduced the world’s first vacuum interrupter distribu-tion breaker in the 1960’s. To date, this interrupter design has beenthe world leader in vacuum technology and has accumulated over 35years of reliable field service. It’s the heart of thousands of POWER/VAC® breakers in service with ratings from 4.16kV - 250 MVA through13.8kV - 1500 MVA at 1200, 2000, 3000, 3500, and 4000 amps (fancooled).

World-wide AcceptancePOWER/VAC® metalclad switchgear is in service throughout the

U.S. and in dozens of other countries. Many installations are sub-jected to harsh operating environments: salt air abroad offshore plat-forms miles out to sea, high altitudes in the mountains of Chile,excessive heat at fertilizer plants in Trinidad, humidity at petro-pro-cessing operations in Venezuela, wind and sand at power plants,public works and oil exploration installations in Saudi Arabia. It isonline in paper mill, steel mills, cement mills, petro-chemical facili-ties and in electric utility systems the world over - wherever a highvalue is placed on reliability, POWER/VAC® is the industry acceptedleader.

© 1996 GENERAL ELECTRIC COMPANY

POWER/VAC switchgear withstands tough seas and saltair aboard this natural gas platform.

POWER/VAC switchgear helps protect electric utilitysystems around the world.

2

Page 4: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

3

E. VOLE. VOLE. VOLE. VOLE. VOLTTTTTAGEAGEAGEAGEAGETRANSFORMERSTRANSFORMERSTRANSFORMERSTRANSFORMERSTRANSFORMERS meet allapplicable industry standards andare mounted in an easy-accessroll-out tray.

FFFFF. DR. DR. DR. DR. DRYYYYY TYPE CONTROL TYPE CONTROL TYPE CONTROL TYPE CONTROL TYPE CONTROLPOWER TRANSFORMERSPOWER TRANSFORMERSPOWER TRANSFORMERSPOWER TRANSFORMERSPOWER TRANSFORMERS havemolded epoxy resin insulation and aremounted in a draw out tray for easyaccess. Ratings run through 15kVA singlephase. When a higher rating or 3 CPT’s,are required, a key interlocked fused roll-out tray will be supplied with stationaryCPT’s mounted in the rear of the unit.

G. CABLE COMPARTMENT in abasic two-breaker vertical section hasample space for termination of up to two750 MCM cables per phase, includingstress cone makeup. When only onebreaker is required in a vertical section, theentire cable space is available for use. Intwo-high breaker equipment, a verticalsteel trough serves as a separation barrierfrom the other cable compartment. Thisduct is easily removed to facilitate initialinstallation of the “inside” cables. Whenthe vertical steel duct is in place, there isstill access to the “inside” terminations.The power cable compartment can bearranged to permit both sets of cables toexit below or above.

H. PORTH. PORTH. PORTH. PORTH. PORTABLE BREAKER LIFTABLE BREAKER LIFTABLE BREAKER LIFTABLE BREAKER LIFTABLE BREAKER LIFTtrucks allow handling a breaker or roll-outduring installation into a compartment, orduring removal for inspection or mainte-nance. Lifts for both indoor and outdoorequipment have interlocks on the liftingforks to lock the breaker in place duringtransporting.

OEM EXPRESS SWITCHGEAR OFFERS MANY SUPERIOROEM EXPRESS SWITCHGEAR OFFERS MANY SUPERIOROEM EXPRESS SWITCHGEAR OFFERS MANY SUPERIOROEM EXPRESS SWITCHGEAR OFFERS MANY SUPERIOROEM EXPRESS SWITCHGEAR OFFERS MANY SUPERIORDESIGN FEADESIGN FEADESIGN FEADESIGN FEADESIGN FEATURESTURESTURESTURESTURES

A. MAIN BUSCOMPARTMENT is completelyisolated by metal barriers. Bus barsare provided with high dielectricfluidized bed epoxy bus insulation andpass through track-resistant polyesterglass barriers between cubicles. Allmain bus is tin-plated for positivecontact and low resistance, and areinsulated with preformed boots (notshown in this photo). Porcelaininsulation to ground is optional.Silver plated copper bus is optional.

B. SECONDARYDISCONNECTS combine thepositive-contact reliability of a plugwith the automatic, self-aligningconvenience of sliding-type contacts.While in the test position, secondarycontacts are easily disengaged orrengaged by a linkage operated fromthe front of the circuit breaker.

C. CURRENTC. CURRENTC. CURRENTC. CURRENTC. CURRENTTRANSFORMERSTRANSFORMERSTRANSFORMERSTRANSFORMERSTRANSFORMERS are typicallylocated behind mechanically actuatedsafety shutter barrier that isolates theprimary disconnects as the breaker ismoved into the DISCONNECT position.Two single accuracy CT’s per phasecan be accomodated on both the lineand load sides of the breaker (as manyas12 CT’s per breaker). CT’s are frontaccessible after removal of the shuttersafety barrier.

D. AUXILIARY SWITCH (MOC)can be provided at the bottom of thebreaker compartment so thatadditional contacts can be actuated bythe operation of the breaker. Thebreaker will operate this switch whenit is in the “Test” or “Connect”position. POSITION SWITCH (TOC)can be provided at the bottom of thebreaker compartment so that it will beoperated by a bracket on the breakerframe when the breaker is in the“Connect” position. The positionswitch is used to indicate if thebreaker is connected or withdrawn.

Page 5: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

4

POWER/VPOWER/VPOWER/VPOWER/VPOWER/VACACACACAC® ® ® ® ® VVVVVACUUM BREAKERS DESIGNED FORACUUM BREAKERS DESIGNED FORACUUM BREAKERS DESIGNED FORACUUM BREAKERS DESIGNED FORACUUM BREAKERS DESIGNED FORQUALITY AND SAFETYQUALITY AND SAFETYQUALITY AND SAFETYQUALITY AND SAFETYQUALITY AND SAFETY

Standardization Means High QualityA high degree of standardization has been achieved with POWER/

VAC® breakers. All breakers are the same size regardless of voltage orinterrupting capability. Additionally, most parts of the frame, primaryconductors, disconnects and mechanisms are interchangeable through-out the breaker product line. This results in a higher quality productand reduces training time for operating and maintenance personnel.

Interlock System ProtectsOperating Personnel

For personnel safety, POWER/VAC® breakers are designed with anumber of mechanical and electrical interlocks. For example, breakercontacts must be open before the breaker can be moved to or from theCONNECT position. A positive mechanical stop is provided when thebreaker reaches the CONNECT or TEST/ DISCONNECT positions.Mechanical interference interlocks are provided to permit only theinsertion of properly rated breakers into any specific compartment.These and other necessary interlocks provide a comprehensive protec-tion system. Futhermore, springs automatically discharge when thebreaker is withdrawn from the CONNECT position and breakers cannotbe inserted in the closed position. Closed door drawout design alsocontributes an extra measure of operator protection.

1. Front Panel

2. Primary Disconnect 3. Contact Erosion Indicator

Page 6: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

5

Breaker FeaturesBreaker FeaturesBreaker FeaturesBreaker FeaturesBreaker Features1. FRONT P1. FRONT P1. FRONT P1. FRONT P1. FRONT PANEL:ANEL:ANEL:ANEL:ANEL:This 11-gauge steel front panel fits into a collar - frame in theequipment when the breaker is in the CONNECT position. Itprovides a metal barrier between the breaker compartment andthe secondary device compartment. Well marked and easy-to-read operating controls and indicators include TRIP button,CLOSE button, OPEN/CLOSE indicator, CHARGE/DISCHARGEindicator, OPERATION counter and provision for manual charg-ing the breaker.

2. PRIMAR2. PRIMAR2. PRIMAR2. PRIMAR2. PRIMARYYYYY DISCONNECT DISCONNECT DISCONNECT DISCONNECT DISCONNECT:::::The primary disconnect finger set is rugged and easy to inspect.Designed for optimum contact, built of silver-plated copper andtested for continuous and momentary currents. These discon-nects provide proper contact integrity throughout the life of the gearfor the critical primary disconnect function.

3. CONT3. CONT3. CONT3. CONT3. CONTACT EROSION INDICAACT EROSION INDICAACT EROSION INDICAACT EROSION INDICAACT EROSION INDICATTTTTOR:OR:OR:OR:OR:GE Vacuum interrupter contacts seldom wear out over the normal dutylife-span of a circuit breaker. Nevertheless, a contact erosion indicatoris provided for inspection convenience. It is visible when the breaker iswithdrawn from the compartment.

4. INTERRUPTER SUPPORT4. INTERRUPTER SUPPORT4. INTERRUPTER SUPPORT4. INTERRUPTER SUPPORT4. INTERRUPTER SUPPORT:::::A rugged, high strength, track-resistant polyester glass support assem-bly firmly positions and holds the interrupter and primary conductorswhile providing insulation to ground and between phases. This supportassembly can be removed quickly by disengaging six bolts. Only asimple alignment of contact wipe is required in the unlikely event that theinterrupter assembly needs to be replaced.

5. BREAKER MECHANISM:5. BREAKER MECHANISM:5. BREAKER MECHANISM:5. BREAKER MECHANISM:5. BREAKER MECHANISM:ML-17H for 1500, ML-18, and ML-18H mechanisms use spring-charged,stored energy design that is mechanically and electrically trip-free andcan be operated by dc control voltages of 48V, 125V, or 250V, or acvoltages of 120 VAC, and 240 VAC. High quality mechanism parts areprecision-tooled for operating consistency, reliability, maintenance easeand long life.

6. ROLL-IN OPTION:6. ROLL-IN OPTION:6. ROLL-IN OPTION:6. ROLL-IN OPTION:6. ROLL-IN OPTION:A roll-in breaker designed for use in the lower compartment of indoorswitchgear is available in all breaker ratings. The roll-in feature eliminatesthe need for a lift truck and reduces the required front aisle space. Uppercompartments may be used for devices or used as auxillary compart-ments above 1200A, 2000A, and 3000A breakers. The breaker used forthis option is the same as used for the two-high product, with the additionof an undercarriage.

4. Interrupter Support

5. Breaker Mechanism

6. Roll-in Option

Page 7: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

THE INSIDE STTHE INSIDE STTHE INSIDE STTHE INSIDE STTHE INSIDE STORORORORORYYYYYON ON ON ON ON ADDITIONALADDITIONALADDITIONALADDITIONALADDITIONAL OEM EXPRESS FEA OEM EXPRESS FEA OEM EXPRESS FEA OEM EXPRESS FEA OEM EXPRESS FEATURESTURESTURESTURESTURES

1. T1. T1. T1. T1. Two-High Breaker Stackingwo-High Breaker Stackingwo-High Breaker Stackingwo-High Breaker Stackingwo-High Breaker Stacking can save up to 50% in floor space for mostapplications, depending on the rating, and results in fewer shipping splits. Inaddition, cubicle dimensions are the same across all ratings so space require-ments are clearly defined at the outset. System planning and layout are thussimplified.

2. Breakers Roll Along Side-Rails Into Position2. Breakers Roll Along Side-Rails Into Position2. Breakers Roll Along Side-Rails Into Position2. Breakers Roll Along Side-Rails Into Position2. Breakers Roll Along Side-Rails Into Positionto assure proper alignment. Positive stops are provided in TEST/DISCON-NECT and CONNECT positions. Movement to the CONNECT position isaccomplished with a racking mechanism that can be manually, or (as an option)remote electrically operated from the front of the unit with the door closed.

3. Precision T3. Precision T3. Precision T3. Precision T3. Precision Toolingoolingoolingoolingooling brings uniform quality to breaker and equipment partsand facilitates troublefree field assembly and operation.

4. T4. T4. T4. T4. Transformer Roll-out Transformer Roll-out Transformer Roll-out Transformer Roll-out Transformer Roll-out Traysraysraysraysrays can be mounted as a combination of two trayseither in the top or bottom cubicles. The combination can be two sets of VT’s orone VT and one CPT up to 15 KVA in either the top or bottom section. Thetransformer primaries are connected with insulated bus and are automaticallygrounded when withdrawn.

5. A Rugged Steel Frame5. A Rugged Steel Frame5. A Rugged Steel Frame5. A Rugged Steel Frame5. A Rugged Steel Frame employs bolted reinforced gussets for addedstrength and dimensional integrity. Seismic-qualified versions are available.Grounded metal barriers isolate all high voltage compartments.

6. Easy Installation6. Easy Installation6. Easy Installation6. Easy Installation6. Easy Installation results because many foundations that are smooth andlevel don’t require embedded floor steel or grouting. To reduce installation time,equipment can be lifted into place without using skids.

7. Blank Front Hinged Doors 7. Blank Front Hinged Doors 7. Blank Front Hinged Doors 7. Blank Front Hinged Doors 7. Blank Front Hinged Doors are furnished as standard allowing ampledevice mounting space for complex configurations. Pre-punched fronthinged doors are available as an option. Open doors are securely heldwith positive stops so breakers can be inserted and withdrawn withoutdamaging control wire or protective devices.

8. Bolted Rear Covers 8. Bolted Rear Covers 8. Bolted Rear Covers 8. Bolted Rear Covers 8. Bolted Rear Covers are furnished as standard. Rear hinged coversare available as an option.

9. UL Recognized OEM Switchgear 9. UL Recognized OEM Switchgear 9. UL Recognized OEM Switchgear 9. UL Recognized OEM Switchgear 9. UL Recognized OEM Switchgear is available.

10. Device Panels 10. Device Panels 10. Device Panels 10. Device Panels 10. Device Panels are furnished for mounting fuse blocks and surfacemount devices in all breaker cubicles.

111111. T1. T1. T1. T1. Terminal Block Mounting Space erminal Block Mounting Space erminal Block Mounting Space erminal Block Mounting Space erminal Block Mounting Space is provided as standard in eachbreaker cubicle.

6

A FULL SELECTION OF ACCESORIESA FULL SELECTION OF ACCESORIESA FULL SELECTION OF ACCESORIESA FULL SELECTION OF ACCESORIESA FULL SELECTION OF ACCESORIESTo facilitate inspection, maintenance and test opera-tions, General Electric offers a full selection of devicesand accesories for POWER/VAC® metalcladswitchgear.

A. OPTIONAL GROUND ANDA. OPTIONAL GROUND ANDA. OPTIONAL GROUND ANDA. OPTIONAL GROUND ANDA. OPTIONAL GROUND ANDTEST DEVICES TEST DEVICES TEST DEVICES TEST DEVICES TEST DEVICES are manualllyor electrically operated andprovide facilities for ground-ing either the bus side or theoutgoing cable side of themetalclad unit, of for “phas-ing out” operating circuits.

B. B. B. B. B. TEST CABINETTEST CABINETTEST CABINETTEST CABINETTEST CABINET provides aconvenient means to close andtrip breakers for maintenance orinspection.

C. OPTIONAL REMOTE RACKINGC. OPTIONAL REMOTE RACKINGC. OPTIONAL REMOTE RACKINGC. OPTIONAL REMOTE RACKINGC. OPTIONAL REMOTE RACKINGDEVICEDEVICEDEVICEDEVICEDEVICE is portable and connects toa remote control panel via a 30 footcable. It is motorized and electri-cally racks the breaker betweenthe CONNECT and DISCONNECTpositions with the door closed.

D.D.D.D.D. RACKING HANDLERACKING HANDLERACKING HANDLERACKING HANDLERACKING HANDLEmanually operates the breaker rackingmechanism to move the breaker betweenthe CONNECT and TEST/DISCONNECTpositions.

Page 8: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

RATINGS, WEIGHTS & DIMENSIONS

(1) 111” for standard outdoor construction; 112” for protected and common aisle construction.(2) 109” for standard outdoor:; 181” for protected aisle; 272” for common aisle construction.(3) For common aisle construction, add 1500 pounds to weights of 2 indoor vertical sections.(4) 58” minimum front aisle space available for indoor.

Weights and Dimensions - Breakers and Equipment

Typical Section Dimensions - Indoor and Outdoor Equipment

Breakers Indoor equipment Outdoor Equipment Indoor & Outdoor

Breaker Vertical Auxiliary Breaker Auxiliary For Protected Required Section (less Vertical Vertical Vertical Aisle, Add to Clearance Breakers) Section Section (less Section Section

Breakers)

Breaker Current Breaker Height Depth Width Weight Width Weight Height Depth Width Weight Width Weight Depth Weight Roll-out Front RearType Rating Weights (3) (1) (2) Weight Aisle Aisle

(Amps) (VT- Min. Min.(CPT) (4)

1200 550VB-4.16 2000 650250 3000 780

3500 8504000 860

1200 5502000 650

VB-4.16 3000 780350 3500 850

4000 860

1200 5502000 650

VB-7.2 3000 780500 3500 850

4000 860

1200 550 95 94 36 3100 36 3100 111 109 36 3600 36 3600 75 1100 500 66 262000 650 OR OR

VB-13.8 3000 780 112 181500 3500 850 OR

4000 860 272

1200 5502000 650

VB-13.8 3000 780750 3500 850

4000 860

1200 5502000 650

VB-13.8 3000 7801000 3500 850

4000 860

1200 5502000 650

VB-13.8 3000 7801500 3500 850

4000 860

7

Page 9: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

Typical Equipment Section Views

Typical 2 Bkr. Feeder Unit. For cable Above Typical Incoming Unit With Main Breakers & CPT & VT Roll-outs in Same Unit

*Space for (4) single accuracy per phase, 2 in Upper Studs & 2 on Lower Studs. Rating Range: 150A - 4000A Accuracy Per ANSI C37.20 Table 6.Contact factory for hi-accuracy CT mounting requirements.

TTTTTypical Upper and Lower Unit Configurationypical Upper and Lower Unit Configurationypical Upper and Lower Unit Configurationypical Upper and Lower Unit Configurationypical Upper and Lower Unit ConfigurationData subject to change without notice.

(1) Typical Breaker Units - 5/15 kVUpper 1200A or 2000A Breaker Lower 1200A, 2000A or 300A BKR.

(2) Typical Auxiliary Units - 5/15 kVAlt. Lower: Fuses Only

BUS COMPARTMENT• Copper bus is standard.• Bus supports designed for 80,000A momentary.• All joints connected with 2 bolts and booted.• Bus support insulation system:

Non-tracking polyester glass (std. 5kV & 15kV)Porcelain inserts (optional)Fluidized bed epoxy bus insulation.

CABLE COMPARTMENT• Designed for up to 2-750 MCM/ per breaker; cables above or

below.• CT’s with greater than ANSI accuracy must be mounted in cable

compartment and may limit such cases to one breaker per verticalsection.

• Stress cone space of 21 inches is provided and use of performedstress cones, such as GE Termimatic (TM), is recommened.

Fuses for 3 CPT or 1 CPT > 15kVA CPT andsecondary breaker located in CableCompartment.

8

Space for FuseBlocks & Misc.

Surface MtdBkr Control Devices

Page 10: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

GE Medium Voltage Switchgear Layout & Sizing

ROLLOUTS

Devices Ratings Roll-out Unit A Compartment B Compartment

Lower Upper Lower Upper

3-VT’s (1) 5kV and 15kV -- Yes Yes Yes Yes

2-VT’s (1) 5kV and 15kV -- Yes Yes Yes Yes

1-CPT (1) 5/10/15/kVA -- No Yes Yes No

1-CPT (2) 25kVA and 37.5kVA -- No No No No

CPT Fuses (3) -- Fused Unit No No Yes No

(1) Fuses are an intregal part of the device.(2) CPT has to be installed in cable compartment. CPT fuses are installed in a key interlocked fused roll-out.(3) Must have a key interlock for CPT secondary breaker.

Notes:(A) Upper compartment roll-out connection can be as follows: Bus Line Line

Bus Bus Line

(B) Only one roll-out can be installed in an auxiliary tie bus compartment.

(C) Lower compartment roll-out connection can be as follows: Bus Bus LineBus Line Line

Data subject to change without notice.

9

See Note A

See Note C

Page 11: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

GE Medium Voltage Switchgear Layout & Sizing

AVAILABLE UNIT COMBINATIONS

1200ABreaker

1200ABreaker

1200ABreaker

2000ABreaker

Auxiliary Unit

3000ABreaker

Breaker or Bus

Entrance

Tie Bus1200-3000A

1200-2000ABreaker

AuxiliaryUnit

Auxiliary Unit

1200-2000ABreaker

Bus Entrance1200-3000A

Bus Entrance1200-3000A

(1)

Auxiliary Unit

Auxiliary Unit

AuxiliaryUnit

BusEntrance

1200-3000A

1200-3000ATie Breaker

Bus Entrance1200-3000A

1200-2000ABreaker

Note:(1) Auxiliary Unit:

a ) When used adjacent to a tie breaker for a tie bus transition section, only (1) bus connected rollout tray can be utilized.b ) When used to house rollout trays only, rules on page 9 apply.c ) Auxiliary unit above a 3000A breaker can house rollouts only. Tie transition bus in not available above a 3000A breaker.

Contact factory for 3500A & 4000A bus and breaker applications.

Data subject to change without notice.

(1)

(1)

1)

10

(1)

Page 12: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

GE Medium Voltage Switchgear Application Data

Table 3.1.1 POWER/VAC® Circuit Breaker Characteristics

Data subject to change without notice.

Notes Applying to Table 3.1.1

(1) Maximum voltage for which the breaker is designed and the upperlimit for operation.

(2) K is the ratio of rated maximum voltage to the lower limit of the rangeof operating voltage in which the required symmetrical and asymmetri-cal interrupting capabilities vary in inverse proportion to the operatingvoltage.

(3) To obtain the required symmetrical interrupting capability of a circuitbreaker at an operating voltage between 1/ K times rated maximum volt-age and rated maximum voltage, the following formula shall be used:

Required Symmetrical Interrupting Capability =Rated Short-circuit x (Rated Max. Voltage)

(Operating Voltage)

For operating voltages below 1/K times rated maximum voltage, therequired symmetrical interrupting capability of the circuit breaker shallbe equal to K times rated short-circuit current.

11

(4) With the limitation stated in 5.10 of ANSI - C37.04-1991, all values applyfor polyphase and line-to-line faults. For single phase-to-ground faults,the specific conditions stated in 5.10.2.3 of ANSI-C37.04-1991 apply.

(5) Current values in this column are not to be exceeded even for operatingvoltages below 1/K times rated maximum voltage. For voltages betweenrated maximum voltage and 1/ times rated maximum voltage, follow (3)above.

(6) NOTE: 1500 MVA not a listed rating according to ANSI C37.06 Table 2.1.

(7) NOTE: GE reserves the right to improve the design and/or modify thespecifications in this publication without notice.

*Fan cooled only.

Symmetrical Rating Basis ANSI C37.06 (1987)Identification Rated Values Related Required Capabilities

(6) & (7)Voltage Insulation Current Current Values

Rated Withstand Maximum 3 SecTest Voltage Symmetrical Short time

Interrupting CurrentCapability (5) Carrying

Capability

Normal Normal 3- Rated Rated Low Crest Continuous Short circuit Rated Rated Rated K times Related Short- Closing andrms phase Maximum Voltage Frequency Impulse rms Current rms current Interrupting Permissable Maximum circuit rms Current Latching

voltage Class rms Voltage Range rms Voltage Voltage Rating at 60 Rating (at Time Cycles) Tripping rms Voltage CapabilityCLass (kV) (MVA) (kV) (1) Factor K (kV) (kV) Hz (amperers) Rated Max Delay, Y Divided by rms Current

kV) (kA) (Seconds) K (kV) (kA) (kA) (kA)(3) (4)

4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 36 584.16 250 4.76 1.24 19 60 2000 29 5 2 3.85 36 36 584.16 250 4.76 1.24 19 60 3000 29 5 2 3.85 36 36 584.16 350 4.76 1.19 19 60 1200 41 5 2 4.0 49 49 784.16 350 4.76 1.19 19 60 2000 41 5 2 4.0 49 49 784.16 350 4.76 1.19 19 60 3000 41 5 2 4.0 49 49 784.16 350 4.76 1.19 19 60 3500 41 5 2 4.0 49 49 784.16 350 4.76 1.19 19 60 4000* 41 5 2 4.0 49 49 78

7.2 500 8.25 1.25 36 95 1200 33 5 2 6.6 41 41 667.2 500 8.25 1.25 36 95 2000 33 5 2 6.6 41 41 667.2 500 8.25 1.25 36 95 3000 33 5 2 6.6 41 41 667.2 500 8.25 1.25 36 95 3500 33 5 2 6.6 41 41 667.2 500 8.25 1.25 36 95 4000* 33 5 2 6.6 41 41 66

13.8 500 15 1.30 36 95 1200 33 5 2 6.6 41 41 3713.8 500 15 1.30 36 95 2000 18 5 2 11.5 23 23 3713.8 500 15 1.30 36 95 3000 18 5 2 11.5 23 23 3713.8 750 15 1.30 36 95 1200 28 5 2 11.5 23 23 5813.8 750 15 1.30 36 95 2000 28 5 2 11.5 36 36 5813.8 750 15 1.30 36 95 3000 28 5 2 11.5 36 36 5813.8 750 15 1.30 36 95 3500 28 5 2 11.5 36 36 5813.8 750 15 1.30 36 95 4000* 28 5 2 11.5 36 36 58

13.8 1000 15 1.30 36 95 1200 37 5 2 11.5 48 48 7713.8 1000 15 1.30 36 95 2000 37 5 2 11.5 48 48 7713.8 1000 15 1.30 36 95 3000 37 5 2 11.5 48 48 7713.8 1000 15 1.30 36 95 3500 37 5 2 11.5 48 48 77

13.8 (6) 1500 15 1.00 36 95 1200 63 5 2 15.0 63 63 10113.8 (6) 1500 15 1.00 36 95 2000 63 5 2 15.0 63 63 10113.8 (6) 1500 15 1.00 36 95 3000 63 5 2 15.0 63 63 10113.8 (6) 1500 15 1.00 36 95 3500 63 5 2 15.0 63 63 10113.8(6) 1500 15 1.00 36 95 4000* 63 5 2 15.0 63 63 101

Page 13: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

GE Medium Voltage Switchgear Layout & Sizing

Table 3.1.2 Non-Standard High Close and Latch Capability Circuit Breakers(these ratings exceed ANSI -C37.06)

Data subject to change without notice.

Identification Rated Values Related Required Capabilities(6) (7)

Voltage Insulation Current Current ValuesRated Withstand Maximum 3 Sec

Test Voltage Symmetrical Short timeInterrupting Current

Capability (5) CarryingCapability

Normal Normal Rated Rated Low Crest Continuous Short circuit Rated Rated Rated K times related Short- Closing andrms 3-phase Maximum Voltage Frequency Impulse rms Current rms Current Interrupting Permissable Maximum circuit rms Current Latching

Voltage Class rms Voltage Range rms Voltage Voltage Rating at 60 Rating (at Time (Cycles) Tripping rms Voltage CapabilityClass (MVA) (kV) (1) Factor K (kV) (kV) Hz amperes kV) (ka) Delay Y Divided by rms Current(kV) (2) (3) (4) (Seconds) K (kV0 (kA) (kA) (kA)

12002000

4.16 250 4.76 1.24 19 60 3000 29 5 2 3.85 36 36 7835004000*

120002000

7.2 500 8.25 1.25 36 95 3000 33 5 2 6.6 41 41 78350004000*

120002000

13.8 500 15 1.30 36 95 3000 18 5 2 11.5 23 23 5835004000*

12002000

13.8 750 15 1.360 36 95 3000 28 5 2 11.5 36 36 7735004000*

* Fan Cooled Only

Table 3.1.3 PowerVac® Power Circuit Breaker Characteristics*Ratings Basis on 50 Hertz per IEC

Insulation Level

Circuit Breaker Rated Voltage Power Impulse Rated Normal Rated Short Circuit Short-time Short Circuit Making

Type kV Frequency Withstand Current Amps Breaking Current Current kA Current kA peakkA rms sym. (1) (2) rms 3 sec.

3.6VBI-25 3.6 20 60 1250, 2000 25 25 633.6VBI-40 3.6 20 60 1250, 2000 40 40 1007.2VBI-25 7.2 20 60 1250, 2000 25 25 637.2VBI-40 7.2 20 60 1250, 2000 40 40 100

12.0VBI-25 12.0 28 75 1250, 1600, 2000 25 25 6312.0VBI-40 12.0 28 75 1250, 1600, 2000 40 40 10013.8VBI-25 13.8 36 95 1250, 2000 25 25 6313.8VBI-40 13.8 36 95 1250, 2000 40 40 10013.8VBI-63 15.0 36 95 1250, 2000 63 63 170

* Does not apply to Switchgear(1) Rated operating sequence (duty cycle) CO + 15 sec. + CO(2) Interrupting time 5 cycles at 50 Hz.

12

Page 14: Power/Vac OEM Express Switchgear · OEM EXPRESS SWITCHGEAR POWER/VAC®—QUALITY, EXPERIENCE & RELIABLITY TAILORED TO THE NEEDS OF THE OEM In 1977 General Electric introduced POWER/VAC

© 1998 General Electric Company

gFor further information, call your local GE sales office, or write:

GE Industrial SystemsGE Switchgear Operations510 E. Agency RoadWest Burlington, IA 52655

Outside U.S.A., write:GE Electrical Distribution & Control Export Operation41 Woodford AvenuePlainville, CT 06062, U.S.A.