  • WELCOME

    • This is a presentation for the E1-E2 Civil Technical

    Module for the Topic: Structural Design of Different

    Building Components.

    • Eligibility: Those officers of civil wing who have got the

    Upgradation from E1 to E2.

    • This presentation is last updated on 21-3-2011.

    • You can also visit the Digital library of BSNL to see this

    topic.

    For internal circulation of BSNL only

  • For internal circulation of BSNL only

    AGENDA

    Basic Codes for Design.

    General Design Consideration of IS: 456-2000.

    Steps for design of a multi-storied building.

    Calculation of horizontal loads on buildings.

    Vertical load analysis.

    Horizontal load analysis.

    Column Design

    Design of Various Structural Component

    Development Length

  • INTRODUCTION

    Analysis & design of building depends on type of building, its

    complexity, number of stories etc.

    Structural system is finalized after thorough Study of

    architectural drawings.

    Choice of an appropriate structural system is important for its

    economy and safety. There are two type of building

    systems:-

    (a) Load Bearing Masonry Buildings.

    (b) RCC Framed Buildings.

    Structural frame is finalized & sizes of structural members

    are conveyed to the concerned architect.

    For internal circulation of BSNL only

  • INTRODUCTION

    Load Bearing Masonry Buildings

    • Low rise buildings with small spans generally constructed as

    load bearing brick walls with RCC slab & beams.

    • Suitable for building up to four or less stories.

    • Adequate for vertical loads & also serves to resists

    horizontal loads like wind & earthquake by box action.

    • Provisions of IS: 4326 e.g. providing horizontal RCC Bands

    & vertical reinforcement in brick wall etc. need to be followed

    to ensure safety against earthquake

    • Design to be done as per BIS code IS:1905

    For internal circulation of BSNL only

  • INTRODUCTION

    RCC Framed Structures

    • RCC frames are provided in both principal directions

    and

    • Loads are transmitted to ground through vertical framing

    system i.e Beams, Columns and Foundations.

    • Effective in resisting both vertical & horizontal loads.

    • Brick walls are non load bearing filler walls only.

    • Suitable for multi-storied building as it is very effective

    in resisting horizontal loads due to earthquake / wind.

    For internal circulation of BSNL only

  • INTRODUCTION

    RCC Framed Structures

    • Before starting structural design of a RCC building, the

    following information/ data are required:

    (i) Set of architectural drawings;

    (ii) Soil Investigation report

    (iii) Location of the place or city in order to decide on

    wind and seismic loadings

    (iv) Data for lifts, water tank capacities on top, special

    roof features or loadings, etc.

    For internal circulation of BSNL only

  • BASIC CODES OF DESIGN

    Useful Codes/Hand Books For Structural Design of RCC

    Structures

    (i) IS 456 : 2000 – Plain and reinforced concrete – code of practice

    (ii) Loading Standards:

    IS 875 (Part 1-5) – Code of practice for design loads (other than

    earthquake) for buildings and structures

    Part 1 : Dead loads

    Part 2 : Imposed (live) loads

    Part 3 : Wind loads

    Part 4 : Snow loads

    Part 5 : Special loads and load combinations

    For internal circulation of BSNL only

  • BASIC CODES OF DESIGN

    Earthquake Resistant Design

    • IS 1893 : 2002 – Criteria for earthquake resistant design of

    structure.

    • IS 13920: 1993 – Ductile detailing of reinforced concrete

    structure subject to seismic forces – Provisions of IS 13920-

    1993 shall be adopted in all reinforced concrete structures

    located in seismic zone III, IV or V

    Design Handbooks (Bureau of Indian standards) -

    • SP 16 : 1980 – Design Aids to IS 456 : 1978 (Based on

    previous version of code but still useful)

    • SP 34 : 1987 – Handbooks on Reinforced Concrete Detailing

    For internal circulation of BSNL only

  • BASIS OF DESIGN

    Aim Of Design

    • To design structures with appropriate degree of safety to –

    • Perform satisfactorily during its intended life.

    • Sustain all loads/ deformations of normal construction & use

    • Have adequate durability & resistance to fire.

    Method of Design

    • Structure and structural elements to be normally designed by

    Limit State Method.

    • Working Stress Method may be used where Limit State

    Method can not be conveniently adopted

    For internal circulation of BSNL only

  • LOADS

    DESIGN LOAD –

    Design load to be taken in appropriate method of design is –

    • Characteristic load with appropriate partial safety factors for

    limit state design

    • Characteristic load in case of working stress method

    For internal circulation of BSNL only

  • LOAD COMBINATIONS

    BASIC LOAD CASES USED FOR ANALYSIS

    No. Load case Directions

    1 DL Downwards

    2 IL(Imposed/Live load) Downwards

    3 EXTP (+Torsion) +X; Clockwise torsion due to EQ

    4 EXTN (-Torsion) +X; Anti-Clockwise torsion due to EQ

    5 EZTP (+Torsion) +Z; Clockwise torsion due to EQ

    6 EZTN (-Torsion) +Z; Anti-Clockwise torsion due to EQ

    For internal circulation of BSNL only

  • LOAD COMBINATIONS

    LOAD COMBINATIONS

    • 1.5 (DL + IL)

    • 1.2 (DL + IL ± EL)

    • 1.5 (DL ± EL)

    • 0.9 DL ± 1.5 EL

    • EQ load must be considered for +X, -X, +Z and –Z directions.

    Moreover, accidental eccentricity can be such that it causes

    clockwise or anticlockwise moments.

    • Thus, ±EL above implies 8 cases, and in all, 25 cases must be

    considered. It is possible to reduce the load combinations to

    13 instead of 25 by not using negative torsion considering

    symmetry of the building. For internal circulation of BSNL only

  • Grade of Concrete

    Minimum Grade of Concrete

    For internal circulation of BSNL only

  • Steps of Design

    Steps for Design of Multi-Storeyed

    RCC Framed Buildings

    Step1: Study of architectural Drawings

    Step2: Finalization of Structural Configuration.

    Step3: Preliminary Sizes of Structural members.

    Step4: Load Calculation and

    Step5: Analysis for various load combinations.

    Step6: Design of various structural components for

    most critical load combination.

    For internal circulation of BSNL only

  • Preliminary Sizes

    Finalising Preliminary Sizes

    • Slab: Slab thickness is decided based on span/depth ratio.

    • Beam: Width of beam to be at least equal to width of wall

    (230 or 300 mm). Larger beam width is helpful in placement

    of reinforcement in one layer & for resisting shear & torsion.

    - Depth of beam generally taken as 1/12th (for Heavy Loads)

    to 1/15th (for Lighter Loads) of span.

    • Column: Size of column depends upon axial load &

    moments from both directions and is finalized after

    approximate calculations.

    For internal circulation of BSNL only

  • Loads

    Types of Loads –

    Vertical Loads –

    • Dead Load (Self Weight) – Dl – As per IS-875(part-1)

    • Imposed Load (Live Load) – LL Or IL – As per IS-875 (Part-2)

    • Snow Load

    Horizontal Loads –

    • Earthquake Load (Seismic) – EQX & EQZ (As per IS-1893)

    • Wind Load – WL –As Per IS-875 (Part-3)

    • Special Loads & Load Combinations

    For internal circulation of BSNL only

  • Dead Loads – Unit Wt of Bldg Materials (IS 875 Pt-1)

    For internal circulation of BSNL only

    MATERIAL

    UNIT WEIGHT

    kN/m3 kN/m2

    PLAIN CONCRETE 24

    REINFORCED CONCRETE 25

    BRICK MASONRY 19-20

    STONE MASONRY 21-27

    TIMBER 6-10

    CEMENT-PLASTER 21

    LIME -PLASTER 18

    STEEL 78.5

    AC SHEET -ROOFING 0.16

    GI SHEET -ROOFING 0.15

    MANGLORE TILES 0.65

    STEEL WORK -ROOFING 0.16-0.23

  • Live Loads on Floors of T.E. Bldgs

    For internal circulation of BSNL only

    TYPE OF FLOOR USAGE

    LIVE LOAD

    (kN/m2)

    SWITCH ROOM(NEW TECHNOLOGY) 6.0

    OMC ROOM,DDF ROOM,POWER PLANT,

    BATTERY ROOM

    6.0

    MDF ROOM 10.0

    WEATHER MAKER 12.0

    LIVE LOADS ON ROOFS

    ROOF WITH ACCESS 1.5

    ROOF WITHOUT ACCESS 0.75

  • Loads

    Procedure for Vertical load calculation on Columns–

    Step(i): Transfer slab floor load (both LL & DL) to beams

    using formulae for equivalent UDL as :-

    Equivalent UDL on short span beam = w B/4

    Equivalent UDL on long span beam = w B/4 x [2-(B/L)]

    where w is the total load on slab panel in KN/Sqm &

    L & B respectively are long span & short spans of slab

    panel.

    For internal circulation of BSNL only

  • Loads

    Procedure for Vertical load calculation on Columns–

    Step(ii): Add weight of wall (if any), self weight of beam etc.

    to obtain load on beam (in running meter). Calculate

    similarly for each beam

    Step(iii): Transfer loads from beams to columns.

    Step(iv):Repeat Step (i) to Step (iii) for each floor.

    Step(v): Add for each column for all floors to get total load on

    each column at footing level for entire building.

    For internal circulation of BSNL only

  • Loads

    Procedure for Horizontal (Seismic) Load Calculation–

    • Load Calculations for Seismic Load case is carried out as

    per IS:1893-2002 clause 7.5.3.

    • The Seismic Shear at various floor levels is calculated for

    the whole Building using the values from IS 1893-2002.

    • Design Seismic base shear is –

    Vb = Ah W

    Where W= Seismic weight as per clause 7.4.2 (Full dead load

    + appropriate percentage of imposed load of building as

    given in Table 8)

    For internal circulation of BSNL only

  • Procedure for Horizontal (Seismic) Load Calculation :

    Design Imposed Load for eq. Force Calculation

    Table 8 (IS 1893)

    Percentage of Imposed Load to be Considered

    in Seismic Weight Calculation (Clause 7.3.1 )

    Imposed Uniformity Percentage of

    Distributed Floor Load Imposed Loads

    ( kN/ m2 )

    (1) (2)

    Upto and including 3.0 25

    Above 3.0 50

    For internal circulation of BSNL only

    Load Calculation

  • Loads

    Procedure for Horizontal (Seismic) Load Calculation –

    Ah = Design Horizontal acceleration spectrum value (cl. 6.4.2)

    = (Z/2) (I/R) (Sa/g)

    Where Z = Zone factor as per table 2 of IS 1893

    I= Importance factor as per table 6 of IS-1893

    = 1.5 (If the bldg. is T.E. Bldg.)

    R = Response reduction factor as per table 7 of IS 1893

    = 3.0 for OMRF or 5.0 for SMRF

    (Sa/g) = Average response acceleration coefficient based on

    soil type & natural periods and damping of structure. (Refer

    Fig. 2 page 16 of IS 1893)

    For internal circulation of BSNL only

  • • Procedure for Horizontal (Seismic) Load Calculation :

    For calculating (Sa/g) value as above we have to calculate

    T i.e. Fundamental Natural Time Period (in Seconds)

    (Clause 7.6 of IS Code)

    • T = 0.075 h0.75 (For RC Frame building)

    where h = Height of building in Meter

    • In case of RCC building with brick in fills walls.

    T = 0.09 h / d ½ where h = height of building in meter

    & d = Base dimension of the building at plinth level in

    meter along the considered direction of lateral force.

    For internal circulation of BSNL only

    Load Calculation

  • Procedure for Horizontal (Seismic) Load Calculation :

    • Distribution of base shear (Clause 7.7 of IS 1893) –

    Distribution of total design base shear to different floor

    levels along height of building is done using formula –

    Fi = w i h i2 / ∑(i=1 to n) w i h i

    2 x Vb

    Where Fi = Design lateral force at floor i

    Wi = Seismic weight of floor i

    hi = height of floor in m from base.

    n = number of storyes in the building is equal to

    number of levels at which masses are located.

    Vb = Total Design base shear

    For internal circulation of BSNL only

    Load Calculation

  • ANALYSIS OF STRUCTURE

    VERTICAL LOAD ANALYSIS

    a) GENERAL:

    • It is presumed that all joints of the frame are monolithic.

    • To simplify analysis, three dimensional multistoried R.C.C.

    framed structure is considered as combination of planer

    frames in two directions.

    • It is assumed that each of these planer frames act

    independently of other frames.

    For internal circulation of BSNL only

  • ANALYSIS OF STRUCTURE

    Vertical Load Analysis

    • Procedure for Frame analysis for calculation of moments

    in Columns & beams:

    • Step(i): First, the load from slab is transferred to adjoining

    beams using formula given below:-

    • For computation of Bending Moments in beams, equivalent

    uniformly distributed load of beam is taken as

    Equivalent UDL on short beam of slab panel = w B/3.0

    Equivalent UDL on long beam of slab panel = w B/6 x [ 3-(B/L)2 ]

    where w is the total load on the slab panel in KN/Sqm &

    L & B are long span & short spans of slab respectively.

    For internal circulation of BSNL only

  • ANALYSIS OF STRUCTURE

    Vertical Load Analysis

    • Procedure for Frame analysis for calculation of

    moments in Columns & beams:

    Step(ii): Over this load, weight of wall, self weight of beam

    etc. are added to get load on beam (in running metre).

    Step(iii): The load (in running Metre) on each beam is

    calculated as in Step (i) & Step (ii).

    Step(iv): Step (i) to Step (iii) is repeated for each floor

    Step(v): Then these loads are used as u.d.l on a particular

    frame for analysis by moment distribution method.

    For internal circulation of BSNL only

  • ANALYSIS OF STRUCTURE

    METHOD OF ANALYSIS:

    • Analysis of large framed structures is too Cumbersome

    with classical methods of structure analysis such as –

    – Clapeyron’s theorem of three moments,

    – Castingiliano’s therefore of least work,

    – Poison’s method of virtual work etc.

    Therefore, simpler methods are mostly followed in 2-D

    manual analysis of structures. These are –

    • Hardy cross method of moment distribution.

    • Kani’s method of iteration.

    For internal circulation of BSNL only

  • ANALYSIS OF STRUCTURE

    Horizontal Load Analysis

    • Frame analysis for horizontal loads calculated in step 4

    may be carried out by using Approximate Methods:-

    (i) Cantilever method.

    (ii) Portal method.

    • Approximate methods are used for preliminary designs

    only.

    • For final design exact methods are used which are –

    (i) Slope deflection or matrix methods

    (ii) Factor method.

    For internal circulation of BSNL only

  • DESIGN OF RCC STRUCTURE

    Design of Various Structural Components –

    • After load calculation & analysis for vertical & horizontal

    loads, design & of various structural components e.g. –

    – Columns,

    – Foundations,

    – Beams,

    – Slabs & staircase etc

    are carried out as per various clauses of IS codes with

    help from charts & tables given in BIS handbooks.

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    26.4 Nominal Cover to Reinforcement

    • Nominal cover is the design depth of concrete cover to

    all steel reinforcements, including links.

    • It shall be not less than the diameter of the bar.

    • Minimum values for nominal cover of normal weight

    aggregate concrete which should be provided to all

    reinforcement, including links depending on the condition

    of exposure shall be as given in Table 16 of IS 456.

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    26.4 Nominal Cover to Reinforcement (Table 16 )

    Exposure Nominal Concrete Cover

    in mm not Less Than

    Mild 20

    Moderate 30

    Severe 45

    Very Severe 50

    Extreme 75

    • For longitudinal reinforcing bar in column nominal cover shall

    in any case not be less than 40 mm, or less than bar dia.

    • For footings minimum cover shall be 50 mm.

    For internal circulation of BSNL only

  • Design of Columns

    Design of Columns

    • After obtaining (i) Vertical load, (ii) Moments due to

    horizontal loads on either axis & (iii) Moments due to

    vertical loads on either axis, acting on each column, at all

    floor levels of the building,

    • Columns are designed by charts of SP-16(Design Aids).

    • Design of each column is carried out from the top of

    foundation to the roof, varying the amount of steel

    reinforcement for suitable groups for ease in design.

    Slenderness effects in each storey are also considered

    for each column group.

    For internal circulation of BSNL only

  • Design of Columns

    Column

    A compression member, the effective length > three times

    the least lateral dimension.

    Short and Slender Compression Members

    When both slenderness ratios lex/D and ley/b are

  • Design of Columns

    Design Of Columns – Important Considerations

    (ii) Unsupported Length –

    In beam-slab construction, it is the clear distance between the floor &

    under side of shallower beam framing into columns in each direction at

    next higher floor level.

    (iii) Slenderness limits for columns –

    The unsupported length between end restraints shall not exceed 60

    times the least lateral dimension of a column.

    (iv) Minimum Eccentricity – All columns shall be designed for

    emin ≥ l/500+ D/30 ≥ 20 mm

    Where l= Unsupported length of column in mm. D= Lateral dimension

    of column in the direction under consideration in mm.

    For internal circulation of BSNL only

  • Design of Columns

    Design Of Columns – Design Approach

    • The design of column is complex as it is subjected to axial

    loads & moments which may very independently.

    Column design requires –

    – Determination of the cross sectional dimension.

    – The area of longitudinal steel & its distribution.

    – Transverse steel.

    • The maximum axial load & moments acting along the length

    of column are considered for design of the column section.

    • The transverse reinforcement is provided to impart effective

    lateral support against buckling to every longitudinal bar.

    For internal circulation of BSNL only

  • Design of Columns

    Design Of Columns – Reinforcement Provisions as per

    IS:456-

    A. Longitudinal reinforcement

    • Area of longitudinal reinforcement shall be not less than

    0.8% nor more than 6% of cross sectional area of the

    column.

    • However maximum area of steel should not exceed 4% to

    avoid practical difficulties in placing & compacting concrete.

    • In pedestals, in which the longitudinal reinf. is not taken into

    account in strength calculations, nominal reinforcement

    should be not be less than 0.15% of cross sectional area.

    • Minimum dia of longitudinal bar should be 12 mm

    For internal circulation of BSNL only

  • Design of Columns

    Design Of Columns – Reinforcement Provisions as per

    IS:456

    A. Longitudinal reinforcement

    • Spacing between bars < 300mm along periphery of column

    • The minimum number of bars shall be four in rectangular

    columns & six in circular columns.

    B. Transverse reinforcement (STIRRUPS)

    • Diameter of lateral ties should not be less than 1/4th of dia of the

    largest longitudinal bar & in no case should be less than 6 mm.

    • Spacing of lateral ties should not > least of the following:-

    –Least lateral dimension of the column.

    –16 times the smallest diameter of longitudinal bars to be tied.

    –300 mm.For internal circulation of BSNL only

  • SLAB DESIGN

    TYPES OF SLABS

    Based on Ratio of long span to short span –

    • One way slab – Long span (ly)/Short span (lx ) > 2

    • Two way slab – Long span (ly)/Short span (lx ) < 2

    Based on Edge Conditions

    • Simply supported

    • Restrained – Edge Conditions of supporting edge

    • Cantilever

    For internal circulation of BSNL only

  • SLAB DESIGN

    • The design of floor slab is carried out as per –

    Clause 24.4 &

    Clause 37.1.2 & Annexure D of IS:456-2000 .

    The Bending moment coefficients are taken from

    Table- 26 or

    Table – 27 of BIS code

    • depending on support conditions

    • Bending moment is calculated & reinforcement

    steel is obtained from charts given in SP-16.

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Clause 22.2 Effective Span –

    For internal circulation of BSNL only

    S.

    No.

    Support condition Effective span

    1 Simply supported not built integrally

    with its supports

    Lesser of (i) clear

    span + effective

    depth of slab, &

    (ii) centre to

    centre of

    supports

    2 Continuous when the width of the

    support is < 1/12th of clear span

    Do

  • BIS 456 EXTRACT

    For internal circulation of BSNL only

    S.

    No.

    Support condition Effective span

    3 Continuous when the width of

    the support is > lesser of 1/12th

    of clear span or 600 mm

    (i) for end span with one end

    fixed and the other end

    continuous or for intermediate

    spans,

    (ii) for end span with one end

    free and the other end

    continuous,

    (iii) spans with roller or rocker

    bearings.

    (i) Clear span between the

    supports

    (ii) Lesser of (a) clear span +

    half the effective depth of slab,

    and (b) clear span + half the

    width of the discontinuous

    support

    (iii) The distance between

    centers of bearings

  • BIS 456 EXTRACT

    For internal circulation of BSNL only

    S.

    No.

    Support condition Effective span

    4 Cantilever slab at the end of

    a continuous slab

    Length up to the centre

    of support

    5 Cantilever span Length up to the face of

    the support + half the

    effective depth

    6 Frames Centre to centre

    distance

  • BIS 456 EXTRACT

    EFFECTIVE DEPTH Clause 23.0

    • Effective depth of beam or slab =

    distance between centroid

    of area of tension reinf.

    & maximum comp. fiber,

    • Excluding thickness of finishing material not placed

    monolithically with member and the thickness of any

    concrete provided to allow for wear.

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Clause 23.2 CONTROL OF DEFLECTION

    The deflection shall generally be limited to following:

    • Final deflection < span/250

    (Due to all loads & measured from as-cast level of

    supports of floors, roofs and all other horizontal

    members.)

    • Final deflection < span/350 or 20mm whichever

    is less

    (Including effects of temperature, creep & shrinkage

    occurring after erection of partitions & application of

    finishes.).

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Clause 23.2 CONTROL OF DEFLECTION

    • For beams, vertical deflection limits may

    generally be assumed to be satisfied provided

    that span/depth ratio are not greater than the

    value obtained as below –

    (a) Basic values of span/effective depth ratios for

    spans up to 10m:

    Cantilever 7

    Simply supported 20

    Continuous 26

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Clause 23.2 CONTROL OF DEFLECTION

    • For spans >10m, values in (a) may be multiplied by

    10/span in meters,

    Modification Factors are applied –

    • Based on area & type of steel for tension

    reinforcement (As per Fig. 4 of IS456)

    • Based on area of compression reinforcement (As per

    Fig. 5 of IS456)

    • For flanged beams (As per Fig. 6 of IS456)

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Clause 24.1 SLABS –Control of Deflection

    • The provisions of 23.2 for beams apply to slabs also.

    • For slabs spanning in two directions shorter of the two

    spans to be used for span/effective depth ratios.

    • For two-way slabs of shorter spans (≤3.5 m) with mild

    steel reinf., span/depth ratios given below may

    generally be assumed to satisfy vertical deflection limits

    for loading class up to 3 kN/m2.

    Simply supported slabs 35

    Continuous slabs 40

    For HYSD bars grade Fe 415 & Fe500, values given

    above to be multiplied by 0.8.

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    26.5.2 Requirement of Reinforcement – SLABS

    26.5.2.1 Minimum reinforcement

    • Mild steel reinf. in either direction in slabs ≥ 0.15 %

    of total cross sectional area.

    • For high strength deformed bars ≥ 0.12 percent of

    total (Fe415/Fe500 bars) cross sectional area.

    26.5.2.2 Maximum diameter

    • The dia of reinforcing bars < 1/8th of total thickness

    of slab

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    Requirement of Reinforcement – SLABS

    26.3.3 Maximum distance between bars

    The horizontal distance between parallel main

    reinforcement bars ≤ 3d or 300 mm

    The horizontal distance between parallel

    reinforcement bars provided against shrinkage

    and temperature ≤ 5d or 300 mm whichever is

    smaller.

    For internal circulation of BSNL only

  • SLAB DESIGN

    Steps for Design of Slabs –

    • Step 1: Selection of preliminary depth of slab

    • Step 2: Calculate design loads, bending moments

    • Step 3: Determination/checking of the effective and

    total depths of slabs

    • Step 4: Determination of areas of steel

    • Step 5: Selection of diameter & spacing of

    reinforcing bars

    For internal circulation of BSNL only

  • BIS 456 EXTRACT

    • Torsion reinforcement is provided at any corner

    where the slab is simply supported on both edges

    meeting at that corner.

    • It consist of top and bottom reinforcement, each with

    layers of bars placed parallel to sides of slab &

    extending from edges a minimum distance of one-

    fifth of the shorter span.

    • Area of reinf. in each of these four layers is three-

    quarters of the area required for maximum mid-span

    moment in slab

    For internal circulation of BSNL only

  • BEAM DESIGN

    26.5.1.1 Tension reinforcement

    a) Minimum reinforcement -

    As = 0.85

    bd fy

    where

    AS =minimum area of tension reinforcement

    b =breadth of beam or the breadth of the web

    d =effective depth of T-beam

    fy =characteristic strength of reinforcement in N/mm2 &

    b) Maximum reinforcement - The maximum area of

    tension reinforcement not to exceed 0.04 bD.

    For internal circulation of BSNL only

  • BEAM DESIGN

    • Compression reinforcement

    • The maximum area of compression reinforcement

    not to exceed 0.04 bD

    • Side face reinforcement

    •Where depth of web in a beam >750 mm, side face

    reinf is to be provided along the two faces. The total

    area of such reinf. should not < 0.1 percent of web area

    and shall be

    • distributed equally on two faces at a spacing not >

    300 mm or web thickness whichever is less.

    For internal circulation of BSNL only

  • BEAM DESIGN

    Minimum shear reinforcement (Clause 26.5.1.6)

    • Minimum shear reinforcement in the form of stirrups shall

    be provided such that:

    Asv = 0.4

    bsv 0.87fy

    Maximum spacing of shear reinforcement (Clause 26.5.1.5)

    • The maximum spacing of shear reinforcement measured

    along axis of member shall be < 0.75 d for vertical

    stirrups and d for inclined stirrups at 45 degrees.

    • In no case shall the spacing to be >300 mm.

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    • Foundations transfer loads from the building or individual

    columns to earth. Foundations must be designed to

    prevent –

    • Structural Failure

    • Shear failure of soil

    • Excessive settlement &

    • To minimize differential settlement

    • Depth of footing is determined from the consideration of –

    (a) Bending Moment

    (b) One way shear

    (c)Two way shear

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    • To determine area required for proper transfer of total

    load on the soil, the total load (the combination of dead,

    live and any other load without multiplying it with any load

    factor) need to be considered.

    Total Load including Self Weight of footing

    Plan Area of footing = -----------------------------------------------

    Allowable bearing capacity of soil

    Thickness of the edge of footing –

    The thickness at the edge shall not be less than 15 cm for

    footing on soils.

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    Bending Moment (Reference Clauses- 34.2.3.1 & 34.2.3.2)

    • The critical section for bending Moment is considered

    at the face of column, Pedestal or wall.

    Shear (Reference Clause 33.2.4.1)

    • The critical section for one way shear is at the vertical

    section located at a distance equal to the effective

    depth (d) from the face of the column, pedestal or wall

    of the footing in case of footings on soils.

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    For one way action

    For one way shear action, the nominal shear stress is

    calculated as follows:-

    Vu

    τv = -------

    b.d

    Where

    τv = Shear stress, Vu = Factored vertical shear force

    b = Breadth of critical section, d = Effective depth

    τv < τc ( τc = Design Shear Strength of concrete based on % of

    longitudinal tensile reinforcement refer Table 61 of SP-16)

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    For Two Way Action (Punching shear )

    Critical section for punching shear is at d/2 from the face of

    column or pedastal

    For two way shear action, the nominal shear stress is calculated

    in accordance with clause 31.6.2 of the code as follows:-

    Vu

    τv = ----------

    b0.d

    Where b0 = Periphery of the critical section

    For internal circulation of BSNL only

  • FOUNDATION DESIGN

    Design of Foundations – Important Considerations

    Development Length (Reference Clause 34.2.4.3)

    • The critical section for checking the development length in a

    footing shall be assumed at the same planes as those

    described for bending moment in clause 34.2.3 of code and

    also at all other vertical planes where abrupt changes of

    section occur.

    Reinforcement –

    Minimum % of steel in footing slab should be 0.12% &

    Maximum spacing should not be more than 3 times

    effective depth or 300mm which ever is less.

    For internal circulation of BSNL only

  • DETAILING

    • Reinforcing steel of same type and grade shall be

    used as main reinforcement in a structural member.

    • Simultaneous use of two different types or grades of

    steel for main and secondary reinforcement is

    permissible.

    • The calculated tension or compression in any bar at

    any section shall be developed on each side of the

    section by an appropriate development length or end

    anchorage or by a combination thereof.

    For internal circulation of BSNL only

  • Development Length

    Development Length of Bars

    Ld = υσst /4τbd,

    φ = nominal diameter of bar, τbd = design bond stress

    σst = stress in bar at the section considered at design load

    • Design bond stress in limit state method for plain bars in

    tension is given in clause 26.2.1.1

    • For deformed bars conforming to IS 1786 these values

    are to be increased by 60 %.

    • For bars in compression, the values of bond stress for

    bars in tension is to be increased by 25 percent

    For internal circulation of BSNL only

  • Development Length

    For internal circulation of BSNL only

  • For internal circulation of BSNL only