Note: these conditions given in the table are normal service conditions. The conditions going beyond these values are special service conditions. These service conditions can be modified according to the actual conditions of a project. Enclosure Dimensions KYN28A-24(Ⅱ) S/N Name Unit Value 1 Ambient air temperature Maximum temperature +40 Minimum temperature -15 Maximum daily temperature difference K 25 2 Altitude m ≤1000 3 Pollution level (equivalent to c) 4 Relative humidity Average daily relative humidity ≤95 Average monthly relative humidity ≤90 5 Seismic capacity (horizontal acceleration) g 0.2 Side View Width W (mm) Depth D (mm) Height H (mm) Front door panel thickness H1 (mm) Plain batten door Raise door 800 118002200 2400 35 55 1000 2400 Service Conditions Technical Parameters and Performance Requirements S/N Name Unit Value 1 Rated voltage kV 24 2 Rated frequency Hz 50 3 Rated current A ≤3150 4 Temperature rise test 1.1Ir 5 Rated power-frequency withstand voltage (1min) kV 65 6 Rated lightning impulse withstand voltage (peak) kV 125 7 Rated short-circuit breaking current kA 40 8 Rated short-circuit making current kA 100 9 withstand current and duration kA/s 40/4 10 Rated peak withstand current kA 100 11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2 12 Partial discharge Testing voltage kV 1.1×24 Single insulator pC ≤3 13 Degree of protection Enclosure IP4X Compartment IP2X 14 Creepage distance Ceramic material (to earth) mm ≥432 Organic material (to earth) ≥480 15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥180 16 Loss of service continuity category LSC2 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷 1) 20 Allowable internal arc duration s 1 Note: 1) if the rated current 3150A, air cooling should be adopted Front View KYN28A-24(Ⅱ) Metal-Enclosed Withdrawable Switchgear Add: 338 Jinhai Avenue, Wenzhou Economic& Technical Development Zone, Zhejiang Province Tel.: 0086-577-57572871 Fax: 0086- 577-57577212 E-mail[email protected] Websitewww.murge-electric.com Note: 1) Rated current 1250A FOCUS ON USER, JUST DO BETTER W L H IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specifications IEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches Application Standard

PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

Note: these conditions given in the table are normal service conditions. The conditions going beyond these values are specialservice conditions. These service conditions can be modified according to the actual conditions of a project.

Enclosure Dimensions

KYN28A-24(Ⅱ)

S/N Name Unit Value

1 Ambient air temperature

Maximum temperature℃

+40

Minimum temperature -15

Maximum daily temperature difference K 25

2 Altitude m ≤1000

3 Pollution level Ⅱ(equivalent to c)

4 Relative humidityAverage daily relative humidity

%≤95

Average monthly relative humidity ≤90

5 Seismic capacity (horizontal acceleration) g 0.2

Side View

Width W (mm) Depth D (mm)Height H

(mm)

Front door panel thickness H1

(mm)

Plain batten door Raise door

8001)

1800、22002400

35 551000 2400

Service Conditions

Technical Parameters and Performance Requirements

S/N Name Unit Value

1 Rated voltage kV 24

2 Rated frequency Hz 50

3 Rated current A ≤3150

4 Temperature rise test 1.1Ir

5 Rated power-frequency withstand voltage (1min) kV 65

6 Rated lightning impulse withstand voltage (peak) kV 125

7 Rated short-circuit breaking current kA 40

8 Rated short-circuit making current kA 100

9 withstand current and duration kA/s 40/4

10 Rated peak withstand current kA 100

11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2

12 Partial dischargeTesting voltage kV 1.1×24

Single insulator pC ≤3

13 Degree of protectionEnclosure IP4X

Compartment IP2X

14 Creepage distanceCeramic material (to earth)

mm≥432

Organic material (to earth) ≥480

15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥180

16 Loss of service continuity category LSC2

17 Minimum clearance from SMC partition (if any) to live conductor mm 45

18 SMC partition thickness mm ≥5

19 Cooling mode 自冷1)

20 Allowable internal arc duration s 1

Note: 1) if the rated current ≥3150A, air cooling should be adopted

Front View

KYN28A-24(Ⅱ)

Metal-Enclosed Withdrawable Switchgear

Add: 338 Jinhai Avenue, Wenzhou Economic&

Technical Development Zone, Zhejiang Province

Tel.: 0086-577-57572871 Fax: 0086- 577-57577212

E-mail:[email protected]

Website:www.murge-electric.com

Note: 1) Rated current ≤1250A

FOCUS ON USER, JUST DO BETTER

W L H

IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches

Application Standard

Page 2: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

The side plate employs inward double-bending technology.

Enclosure-top relief cover plate

One side is equipped hinges

One side is fixed with nylon screws

Reduce resistance in pressure relief

Realize quick relief to ensure safety

The secondary line is laid in the full-metal-protectedsecondary line trunking, which can effectively preventarcs burning the secondary line in case of failure inthe Enclosure. Signals can be correctly transmittedthrough the secondary line to the comprehensiveprotection controls system to realize fast fault-clearing, mitigating the damage inflicted by failure onelectric equipment and improving the stability ofelectric systems.

The contact box in the enclosure employs astructure with the back fixed, which can improvethe insulation coordination between the handcartand enclosure body.

The rear upper and lower doors are interlocked with an

interlock, which ensures that the rear upper door cannot

be opened when the rear lower door is closed; on the

contrary the rear lower door cannot be closed when the

rear upper door is opened.

The ground interlock, simpler in structure and more flexible

and reliable in operation, can deliver free switch of

interlocking functions whether equipped with a manual or

motorized earthing switch, without requiring changing any

part.

KYN28A-24(Ⅱ)

Simple and natural; Sleek and streamlined; Harmonious and aesthetic

In harmony with the distribution environment

Evident artistic bearing of industrial electrical Enclosures

Tech

nica

l inn

ovat

ion

neve

r end

s.Technical innovation never ends.

The time for power restoration can be shortened.

Separate replacement is realizable in case of failures.

The side has no protruded screws and relief holes.

The framework is connected with dimpled rivets.

Page 3: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

KYN28A-12(Ⅱ)

S/N Name Unit Value

1 Rated voltage kV 12

2 Rated frequency Hz 50

3 Rated current A ≤4000

4 Temperature rise test 1.1Ir

5 Rated power-frequency withstand voltage (1min) kV 42

6 Rated lightning impulse withstand voltage (peak) kV 75

7 Rated short-circuit breaking current kA 40

8 Rated short-circuit making current kA 100

9 Rated short-time withstand current and duration kA/s 40/4

10 Rated peak withstand current kA 100

11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2

12 Partial dischargeTesting voltage kV 1.1×12

Single insulator pC ≤3

13 Degree of protectionEnclosure IP4X

Compartment IP2X

14 Creepage distanceCeramic material (to earth)

mm≥216

Organic material (to earth) ≥240

15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥125

16 Loss of service continuity category LSC2

17 Minimum clearance from SMC partition (if any) to live conductor mm 30

18 SMC partition thickness mm ≥5

19 Cooling mode Self-cooling 1)

20 Allowable internal arc duration s 1

Width W (mm) Depth D (mm)Height H

(mm)

Front door panel thickness H1

(mm)

Plain batten door Raise door

400、500、6001)

1450、1610、17502240

35 55650、800、1000 2240

Note: these conditions given in the table are normal service conditions. The conditions going beyond these values arespecial service conditions. These service conditions can be modified according to the actual conditions of a project.

Note: 1) if the rated current ≥3150A, air cooling should be adopted

KYN28A-12(Ⅱ)

Note: 1) Busbar lifting Enclosure

Metal-Enclosed Withdrawable Switchgear

FOCUS ON USER, JUST DO BETTER

Front View Flat-top Side View Ladder Enclosure Side View

W L H L H

Enclosure Dimensions

Service Conditions

Technical Parameters and Performance Requirements

S/N Name Unit Value

1 Ambient air temperature

Maximum temperature℃

+40

Minimum temperature -15

Maximum daily temperature difference K 25

2 Altitude m ≤1000

3 Pollution level Ⅱ(equivalent to c)

4 HumidityAverage daily relative humidity

%≤95

Average monthly relative humidity ≤90

5 Seismic capacity (horizontal acceleration) g 0.2

Add: 338 Jinhai Avenue, Wenzhou Economic&

Technical Development Zone, Zhejiang Province

Tel.: 0086-577-57572871 Fax: 0086- 577-57577212

E-mail:[email protected]

Website:www.murge-electric.com IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches

Application Standard

Page 4: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

Enclosure-top relief cover plate

One side is equipped hinges

One side is fixed with nylon screws

Reduce resistance in pressure relief

Realize quick relief to ensure safety

The secondary line is laid in the full-metal-protectedsecondary line trunking, which can effectively preventarcs burning the secondary line in case of failure inthe enclosure. Signals can be correctly transmittedthrough the secondary line to the comprehensiveprotection controls system to realize fast fault-clearing, mitigating the damage inflicted by failureon electric equipment and improving the stability ofelectric systems.

KYN28A-12(Ⅱ)

Tech

nica

l inn

ovat

ion

neve

r end

s.

The ground interlock, simpler in structure and more

flexible and reliable in operation, can deliver free

switch of interlocking functions whether equipped

with a manual or motorized earthing switch, without

requiring changing any part.

The rear upper and lower doors are interlocked with an

interlock, which ensures that the rear upper door cannot be

opened when the rear lower door is closed; on the contrary the

rear lower door cannot be closed when the rear upper door is

opened.

The relief cover has a corrugated grille inside to preventarcs burning particles to spatter.

The side plate employs inward double-bending technology.

The framework is connected with dimpled rivets.

The side has no protruded screws and relief holes.

Separate replacement is realizable in case of failures.

The time for power restoration can be shortened.

Simple and natural; Sleek and streamlined; Harmonious and aesthetic

In harmony with the distribution environment

Evident artistic bearing of industrial electrical Enclosures

Technical innovation never ends.

Page 5: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

KYN61-40.5 (Ⅱ)

S/N Name Unit Value

1 Rated voltage kV 40.5

2 Rated frequency Hz 50

3 Rated current A ≤3150

4 Temperature rise test 1.1Ir

5 Rated power-frequency withstand voltage (1min) kV 95

6 Rated lightning impulse withstand voltage (peak) kV 185

7 Rated short-circuit breaking current kA 31.5

8 Rated short-circuit making current kA 80

9 short-time withstand current and duration kA/s 31.5/4

10 Rated peak withstand current kA 80

11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2

12 Partial dischargeTesting voltage kV 1.1×40.5

Single insulator pC ≤3

13 Degree of protectionEnclosure IP4X

Compartment IP2X

14 Creepage distanceCeramic material (to earth)

mm≥729

Organic material (to earth) ≥810

15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥300

16 Loss of service continuity category LSC2

17 Minimum clearance from SMC partition (if any) to live conductor mm 60

18 SMC partition thickness mm ≥5

19 Cooling mode Self-cooling1)

20 Allowable internal arc duration s 1

S/N Name Unit Value

1 Ambient air temperature

Maximum temperature℃

+40

Minimum temperature -15

Maximum daily temperature difference K 25

2 Altitude m ≤1000

3 Pollution level Ⅱ(equivalent to c)

4 Relative humidityAverage daily relative humidity

%≤95

Average monthly relative humidity ≤90

5 Seismic capacity (horizontal acceleration) g 0.2

Width W (mm) Depth D (mm)Height H

(mm)

Front door panel thickness H1 (mm)

Plain batten door Raise door

12001)

2800、30002600

35 551400 2600

Note: these conditions given in the table are normal service conditions. The conditions going beyond these values arespecial service conditions. These service conditions can be modified according to the actual conditions of a project.

Note: 1) if the rated current ≥3150A, air cooling should be adopted

KYN61-40.5 (Ⅱ)

前视图 侧视图Note: 1) Rated current ≤1250A

Metal-Clad Withdrawable Switchgear

FOCUS ON USER, JUST DO BETTER

W L H

Add: 338 Jinhai Avenue, Wenzhou Economic&

Technical Development Zone, Zhejiang Province

Tel.: 0086-577-57572871 Fax: 0086- 577-57577212

E-mail:[email protected]

Website:www.murge-electric.com

Enclosure Dimensions

Service Conditions

Technical Parameters and Performance Requirements

IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches

Application Standard

Page 6: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

The secondary line is laid in the full-metal-protected

secondary line trunking, which can effectively prevent arcs

burning the secondary line in case of failure in the

enclosure. Signals can be correctly transmitted through the

secondary line to the comprehensive protection controls

system to realize fast fault-clearing, mitigating the damage

inflicted by failure on electric equipment and improving

the stability of electric systems.

KYN61-40.5 (Ⅱ)

A new secondary interlock, which is adapted to a 510~610mm

hardcart travel, and whose 58-pin and 46-pin aviation plugs can

be basically universal to all mechanisms.

While remaining the same its original size

1400x2600x2800, it has its internal layout reasonably

adjusted, allowing its tie-Busbars to have an air

clearance ≥300mm other than the phase-to-phase

clearance.

The handcart base employs a track structure and makes

use of special welding fixture, delivering reinforcement

and steadiness.

An adaptive limit switch device,

which adapts to the fit clearances

in the front, rear, left and right

directions, with an application

range of ±5mm.

A new ground interlock featuring small operating force, long life,

great stability, and convenient and efficient assembly,

commissioning and maintenance.

While remaining the same its original size

1400x2600x2800, it has its internal layout reasonably

adjusted, allowing its copper Busbars in the Busbar

chamber to have a clearance ≥300mm other than the

phase-to-phase clearance.

Simple and natural; Sleek and streamlined; Harmonious and aesthetic

In harmony with the distribution environment

Evident artistic bearing of industrial electrical Enclosures

Tech

nica

l inn

ovat

ion

neve

r end

s.Technical innovation never ends.

Page 7: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

Width W (mm) Depth D (mm) Height H (mm)

600 800/1000 2200

800 800/1000 2200

1000 800/1000 2200

Name Unit Value

Ambient air temperature

Maximum temperature ℃ 40

Minimum temperature ℃ -5

Maximum daily temperature difference K 25

Altitude m ≤2000

Pollution level Ⅲ

HumidityAverage daily relative humidity40℃ % ≯50

In the case of a lower temperature, it is allowed to have a higher relative humidity (up to 90% when the ambient temperature is +20℃)

Seismic intensity Level 8

Name Unit Value

Rated operating voltageAC V ≯1000

DC V ≯1500

Rated insulation voltage V 1000AC

Frequency Hz 50-60

Rated impulse withstand current KV 8

Overvoltage category 级 Ⅲ

Rated current A ≯6300

Rated withstand current kA 100

Rated peak withstand current kA 220

Rated short-time withstand current (1s) kA 100

①Distribution busbar peak currentStandard kA 105

Improved kA 176

Degree of protectionEnclosure IP IP4X

Enclosure IP IP2X

Crash rating Enclosure IK IK10

Internal isolation mode 3a/3b/4b

Profile modulus mm 25

Drawer unit height

mm 150

mm 200

mm 300

mm 400

mm 500

mm 600

Incoming mode

Upper busbar

Lower cable

Side busbar

Outgoing modeRear upper cable

Rear lower cable

FOCUS ON USER, JUST DO BETTER

Add: 338 Jinhai Avenue, Wenzhou Economic&

Technical Development Zone, Zhejiang Province

Tel.: 0086-577-57572871 Fax: 0086- 577-57577212

E-mail:[email protected]

Website:www.murge-electric.com

Aikko Low-voltage Switchgear

Enclosure Dimensions

Service Conditions

Basic Technical Parameters and Performance Requirements

IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches

Application Standard

Page 8: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

Visual shape Industrial beauty

Visual shape Industrial beauty

Electric enclosures-though industrial products, need to meet human’s aesthetic needs. In the R&D of Aikko low-voltage switchgears, Murge’s artisans pay close attention to industrial design from details, interpreting beauty from product modelling to operation interfaces, from color matching to environment integration, and from industrial steadiness to atmosphere creation.

Aikko low-voltage switchgears

Geometrically simple modelling Industrial style blending gray and blue

Friendly operation interfaceErgonomic operation interface

Harmonious with the distribution environment

Compatible with hand pull, hand cranking and electric models, it can keep a highly unified panel style.

Functionally strong auxiliary contacts can meet any requirement for their functions and prevent misoperation.

Hand-pull and hand-cranking mechanisms

Basic structure

Interlock module, auxiliary contacts in operating and testing positions

Hand-pull mechanism

Module of hand cranking structure

Hand-cranking mechanism

Hand-pull and hand-cranking electric mechanisms

Basic structure

Electrically operated auxiliary contacts,

auxiliary contacts in operating and testing

positions

Hand-pull electric mechanism

Module of hand cranking structure

Hand-cranking electric mechanism

Double-bending, joined with rigid rivets, and equipped with positioning fixture

Primary and secondary plugs with a record of failure-free operation of millions of times

The T-shaped holes in the drawer bottom plate enhance the flexibility of mounting parts and components.

The backward bending of the drawer rear plate increases the clearances of electric equipment connecting busbars.

The drawer has secondary line binding holes in side to ensure reasonable and consistent wiring.

Safety is a permanent topic.

Humanity is the guide for exploration.

Aikko low-voltage switchgears work on the details with careful consideration, changing not a bit.

+ = + =

+ = + =

Visual splicing instructions A sliding mounting bracket

Brand-new invented Aikko sections Green manufacturing processes Easy-mounting connection mode

Drawable structure A change of reliability

Compatible mechanism module

This time, Murge works hard to make innovation.

The patent, Aikko sections, breaks more than the tradition,

and improve more than strength.

The innovation from within is a thorough transformation

Framed structure Tough strength

Enhance the strengthen, and increase the capability

Page 9: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

S/N Name Unit Value

1 rated voltage kV 12 24 36

2 rated current A 630 630 630

3 rated closed loop breaking current A 630 630 630

4 rated on load breaking current A 630 630 630

5 rated short time withstand current kA 16 16 16

6 rated peak withstand current kA 40 40 40

7 rated short-circuit making current kA 40 10 40

8

rated power frequency withstand voltage

kV 28 50 70

9 across the isolating distance kV 32 60 80

10

rated lightning withstand voltage

Phase-to-phase and phase-to-

earthkV 75 125 170

11 across the isolating distance kV 85 145 195

12 rated transfer current A 630 630 630

13 mechanical endurance ops M1 1000 M1 1000 M1 1000

14 electrical endurance ops E3(100) E3(100) E3(100)

15 pressure of SF6 gas(20℃) bar 0.5 0.5 0.5

16 yearly leakage rate ≤% 0.5 0.5 0.5

17 enclouse degree of protection IP3X IP3X IP3X

18 (IAC)internal arcing classification A-FL

16kA 1sA-FL

16kA 1sA-FL

16kA 1s

Tabulated Parameters

FOCUS ON USER, JUST DO BETTER

Add: 338 Jinhai Avenue, Wenzhou Economic&

Technical Development Zone, Zhejiang Province

Tel.: 0086-577-57572871 Fax: 0086- 577-57577212

E-mail:[email protected]

Website:www.murge-electric.com Gas Insulated Switchgears

FMG-SF6

Page 10: PowerPoint 演示文稿 · 17 Minimum clearance from SMC partition (if any) to live conductor mm 45 18 SMC partition thickness mm ≥5 19 Cooling mode 自冷1) 20 Allowable internal

The FMG is a SF6 gas insulated switch disconnector for medium voltage switchgear

within secondary distribution networks, rating up to 36kV. It features compact size

and the lightweight construction. The epoxy resin enclosure is tightly sealed and filled

with SF6 gas as insulation and arc-quenching medium, which can provide good

insulation and resistance to moisture and pollution area, realizing virtually free

maintenance.

SF6 Load Break SwitchLBS-12/24/36

No. Switchgear Type

Optional Configuration Enclosure Dimensions (WxDxH)mm

Breaker

Current instrum

ent transform

e

Transformer

Load switch

Disconnector

Earthing sw

itch

Fuse

Main busbar

Relay protection

12 24 36

1.Incoming/Outgoing LBS Panel ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265

2.Transformer Protection Panel ◎ ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265

3. Metering Panel ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265

4. CB Outgoing Panel ◎ ◎ ◎ ◎ ◎ ◎ 750×1070×1700 750×1070×1700 1000×1585×2265

5.CB Outgoing with Metering Panel ◎ ◎ ◎ ◎ ◎ ◎ ◎ 750×1070×1700 750×1070×1700 1000×1585×2265

Single Line Diagram

Enclosure configuration parameter

Outline dimension diagram

Incoming LBS Trafo protect. metering Cbog w/.meter Cb outgoing

1.1 Phase distance= 210 mm for 12kV or 24kV

1.2 Phase distance= 275 mm for 24kV

1.3 Load Break Switch for 36 kV (with different mechanism)