Note: these conditions given in the table are normal service conditions. The conditions going beyond these values are specialservice conditions. These service conditions can be modified according to the actual conditions of a project.
Enclosure Dimensions
KYN28A-24(Ⅱ)
S/N Name Unit Value
1 Ambient air temperature
Maximum temperature℃
+40
Minimum temperature -15
Maximum daily temperature difference K 25
2 Altitude m ≤1000
3 Pollution level Ⅱ(equivalent to c)
4 Relative humidityAverage daily relative humidity
%≤95
Average monthly relative humidity ≤90
5 Seismic capacity (horizontal acceleration) g 0.2
Side View
Width W (mm) Depth D (mm)Height H
(mm)
Front door panel thickness H1
(mm)
Plain batten door Raise door
8001)
1800、22002400
35 551000 2400
Service Conditions
Technical Parameters and Performance Requirements
S/N Name Unit Value
1 Rated voltage kV 24
2 Rated frequency Hz 50
3 Rated current A ≤3150
4 Temperature rise test 1.1Ir
5 Rated power-frequency withstand voltage (1min) kV 65
6 Rated lightning impulse withstand voltage (peak) kV 125
7 Rated short-circuit breaking current kA 40
8 Rated short-circuit making current kA 100
9 withstand current and duration kA/s 40/4
10 Rated peak withstand current kA 100
11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2
12 Partial dischargeTesting voltage kV 1.1×24
Single insulator pC ≤3
13 Degree of protectionEnclosure IP4X
Compartment IP2X
14 Creepage distanceCeramic material (to earth)
mm≥432
Organic material (to earth) ≥480
15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥180
16 Loss of service continuity category LSC2
17 Minimum clearance from SMC partition (if any) to live conductor mm 45
18 SMC partition thickness mm ≥5
19 Cooling mode 自冷1)
20 Allowable internal arc duration s 1
Note: 1) if the rated current ≥3150A, air cooling should be adopted
Front View
KYN28A-24(Ⅱ)
Metal-Enclosed Withdrawable Switchgear
Add: 338 Jinhai Avenue, Wenzhou Economic&
Technical Development Zone, Zhejiang Province
Tel.: 0086-577-57572871 Fax: 0086- 577-57577212
E-mail:[email protected]
Website:www.murge-electric.com
Note: 1) Rated current ≤1250A
FOCUS ON USER, JUST DO BETTER
W L H
IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches
Application Standard
The side plate employs inward double-bending technology.
Enclosure-top relief cover plate
One side is equipped hinges
One side is fixed with nylon screws
Reduce resistance in pressure relief
Realize quick relief to ensure safety
The secondary line is laid in the full-metal-protectedsecondary line trunking, which can effectively preventarcs burning the secondary line in case of failure inthe Enclosure. Signals can be correctly transmittedthrough the secondary line to the comprehensiveprotection controls system to realize fast fault-clearing, mitigating the damage inflicted by failure onelectric equipment and improving the stability ofelectric systems.
The contact box in the enclosure employs astructure with the back fixed, which can improvethe insulation coordination between the handcartand enclosure body.
The rear upper and lower doors are interlocked with an
interlock, which ensures that the rear upper door cannot
be opened when the rear lower door is closed; on the
contrary the rear lower door cannot be closed when the
rear upper door is opened.
The ground interlock, simpler in structure and more flexible
and reliable in operation, can deliver free switch of
interlocking functions whether equipped with a manual or
motorized earthing switch, without requiring changing any
part.
KYN28A-24(Ⅱ)
Simple and natural; Sleek and streamlined; Harmonious and aesthetic
In harmony with the distribution environment
Evident artistic bearing of industrial electrical Enclosures
Tech
nica
l inn
ovat
ion
neve
r end
s.Technical innovation never ends.
The time for power restoration can be shortened.
Separate replacement is realizable in case of failures.
The side has no protruded screws and relief holes.
The framework is connected with dimpled rivets.
KYN28A-12(Ⅱ)
S/N Name Unit Value
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A ≤4000
4 Temperature rise test 1.1Ir
5 Rated power-frequency withstand voltage (1min) kV 42
6 Rated lightning impulse withstand voltage (peak) kV 75
7 Rated short-circuit breaking current kA 40
8 Rated short-circuit making current kA 100
9 Rated short-time withstand current and duration kA/s 40/4
10 Rated peak withstand current kA 100
11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2
12 Partial dischargeTesting voltage kV 1.1×12
Single insulator pC ≤3
13 Degree of protectionEnclosure IP4X
Compartment IP2X
14 Creepage distanceCeramic material (to earth)
mm≥216
Organic material (to earth) ≥240
15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥125
16 Loss of service continuity category LSC2
17 Minimum clearance from SMC partition (if any) to live conductor mm 30
18 SMC partition thickness mm ≥5
19 Cooling mode Self-cooling 1)
20 Allowable internal arc duration s 1
Width W (mm) Depth D (mm)Height H
(mm)
Front door panel thickness H1
(mm)
Plain batten door Raise door
400、500、6001)
1450、1610、17502240
35 55650、800、1000 2240
Note: these conditions given in the table are normal service conditions. The conditions going beyond these values arespecial service conditions. These service conditions can be modified according to the actual conditions of a project.
Note: 1) if the rated current ≥3150A, air cooling should be adopted
KYN28A-12(Ⅱ)
Note: 1) Busbar lifting Enclosure
Metal-Enclosed Withdrawable Switchgear
FOCUS ON USER, JUST DO BETTER
Front View Flat-top Side View Ladder Enclosure Side View
W L H L H
Enclosure Dimensions
Service Conditions
Technical Parameters and Performance Requirements
S/N Name Unit Value
1 Ambient air temperature
Maximum temperature℃
+40
Minimum temperature -15
Maximum daily temperature difference K 25
2 Altitude m ≤1000
3 Pollution level Ⅱ(equivalent to c)
4 HumidityAverage daily relative humidity
%≤95
Average monthly relative humidity ≤90
5 Seismic capacity (horizontal acceleration) g 0.2
Add: 338 Jinhai Avenue, Wenzhou Economic&
Technical Development Zone, Zhejiang Province
Tel.: 0086-577-57572871 Fax: 0086- 577-57577212
E-mail:[email protected]
Website:www.murge-electric.com IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches
Application Standard
Enclosure-top relief cover plate
One side is equipped hinges
One side is fixed with nylon screws
Reduce resistance in pressure relief
Realize quick relief to ensure safety
The secondary line is laid in the full-metal-protectedsecondary line trunking, which can effectively preventarcs burning the secondary line in case of failure inthe enclosure. Signals can be correctly transmittedthrough the secondary line to the comprehensiveprotection controls system to realize fast fault-clearing, mitigating the damage inflicted by failureon electric equipment and improving the stability ofelectric systems.
KYN28A-12(Ⅱ)
Tech
nica
l inn
ovat
ion
neve
r end
s.
The ground interlock, simpler in structure and more
flexible and reliable in operation, can deliver free
switch of interlocking functions whether equipped
with a manual or motorized earthing switch, without
requiring changing any part.
The rear upper and lower doors are interlocked with an
interlock, which ensures that the rear upper door cannot be
opened when the rear lower door is closed; on the contrary the
rear lower door cannot be closed when the rear upper door is
opened.
The relief cover has a corrugated grille inside to preventarcs burning particles to spatter.
The side plate employs inward double-bending technology.
The framework is connected with dimpled rivets.
The side has no protruded screws and relief holes.
Separate replacement is realizable in case of failures.
The time for power restoration can be shortened.
Simple and natural; Sleek and streamlined; Harmonious and aesthetic
In harmony with the distribution environment
Evident artistic bearing of industrial electrical Enclosures
Technical innovation never ends.
KYN61-40.5 (Ⅱ)
S/N Name Unit Value
1 Rated voltage kV 40.5
2 Rated frequency Hz 50
3 Rated current A ≤3150
4 Temperature rise test 1.1Ir
5 Rated power-frequency withstand voltage (1min) kV 95
6 Rated lightning impulse withstand voltage (peak) kV 185
7 Rated short-circuit breaking current kA 31.5
8 Rated short-circuit making current kA 80
9 short-time withstand current and duration kA/s 31.5/4
10 Rated peak withstand current kA 80
11 Short-duration power frequency withstand voltage of auxiliary and control circuits kV 2
12 Partial dischargeTesting voltage kV 1.1×40.5
Single insulator pC ≤3
13 Degree of protectionEnclosure IP4X
Compartment IP2X
14 Creepage distanceCeramic material (to earth)
mm≥729
Organic material (to earth) ≥810
15 Phase-to-phase and phase-to-earth clearance (air insulation) mm ≥300
16 Loss of service continuity category LSC2
17 Minimum clearance from SMC partition (if any) to live conductor mm 60
18 SMC partition thickness mm ≥5
19 Cooling mode Self-cooling1)
20 Allowable internal arc duration s 1
S/N Name Unit Value
1 Ambient air temperature
Maximum temperature℃
+40
Minimum temperature -15
Maximum daily temperature difference K 25
2 Altitude m ≤1000
3 Pollution level Ⅱ(equivalent to c)
4 Relative humidityAverage daily relative humidity
%≤95
Average monthly relative humidity ≤90
5 Seismic capacity (horizontal acceleration) g 0.2
Width W (mm) Depth D (mm)Height H
(mm)
Front door panel thickness H1 (mm)
Plain batten door Raise door
12001)
2800、30002600
35 551400 2600
Note: these conditions given in the table are normal service conditions. The conditions going beyond these values arespecial service conditions. These service conditions can be modified according to the actual conditions of a project.
Note: 1) if the rated current ≥3150A, air cooling should be adopted
KYN61-40.5 (Ⅱ)
前视图 侧视图Note: 1) Rated current ≤1250A
Metal-Clad Withdrawable Switchgear
FOCUS ON USER, JUST DO BETTER
W L H
Add: 338 Jinhai Avenue, Wenzhou Economic&
Technical Development Zone, Zhejiang Province
Tel.: 0086-577-57572871 Fax: 0086- 577-57577212
E-mail:[email protected]
Website:www.murge-electric.com
Enclosure Dimensions
Service Conditions
Technical Parameters and Performance Requirements
IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches
Application Standard
The secondary line is laid in the full-metal-protected
secondary line trunking, which can effectively prevent arcs
burning the secondary line in case of failure in the
enclosure. Signals can be correctly transmitted through the
secondary line to the comprehensive protection controls
system to realize fast fault-clearing, mitigating the damage
inflicted by failure on electric equipment and improving
the stability of electric systems.
KYN61-40.5 (Ⅱ)
A new secondary interlock, which is adapted to a 510~610mm
hardcart travel, and whose 58-pin and 46-pin aviation plugs can
be basically universal to all mechanisms.
While remaining the same its original size
1400x2600x2800, it has its internal layout reasonably
adjusted, allowing its tie-Busbars to have an air
clearance ≥300mm other than the phase-to-phase
clearance.
The handcart base employs a track structure and makes
use of special welding fixture, delivering reinforcement
and steadiness.
An adaptive limit switch device,
which adapts to the fit clearances
in the front, rear, left and right
directions, with an application
range of ±5mm.
A new ground interlock featuring small operating force, long life,
great stability, and convenient and efficient assembly,
commissioning and maintenance.
While remaining the same its original size
1400x2600x2800, it has its internal layout reasonably
adjusted, allowing its copper Busbars in the Busbar
chamber to have a clearance ≥300mm other than the
phase-to-phase clearance.
Simple and natural; Sleek and streamlined; Harmonious and aesthetic
In harmony with the distribution environment
Evident artistic bearing of industrial electrical Enclosures
Tech
nica
l inn
ovat
ion
neve
r end
s.Technical innovation never ends.
Width W (mm) Depth D (mm) Height H (mm)
600 800/1000 2200
800 800/1000 2200
1000 800/1000 2200
Name Unit Value
Ambient air temperature
Maximum temperature ℃ 40
Minimum temperature ℃ -5
Maximum daily temperature difference K 25
Altitude m ≤2000
Pollution level Ⅲ
HumidityAverage daily relative humidity40℃ % ≯50
In the case of a lower temperature, it is allowed to have a higher relative humidity (up to 90% when the ambient temperature is +20℃)
Seismic intensity Level 8
Name Unit Value
Rated operating voltageAC V ≯1000
DC V ≯1500
Rated insulation voltage V 1000AC
Frequency Hz 50-60
Rated impulse withstand current KV 8
Overvoltage category 级 Ⅲ
Rated current A ≯6300
Rated withstand current kA 100
Rated peak withstand current kA 220
Rated short-time withstand current (1s) kA 100
①Distribution busbar peak currentStandard kA 105
Improved kA 176
Degree of protectionEnclosure IP IP4X
Enclosure IP IP2X
Crash rating Enclosure IK IK10
Internal isolation mode 3a/3b/4b
Profile modulus mm 25
Drawer unit height
mm 150
mm 200
mm 300
mm 400
mm 500
mm 600
Incoming mode
Upper busbar
Lower cable
Side busbar
Outgoing modeRear upper cable
Rear lower cable
FOCUS ON USER, JUST DO BETTER
Add: 338 Jinhai Avenue, Wenzhou Economic&
Technical Development Zone, Zhejiang Province
Tel.: 0086-577-57572871 Fax: 0086- 577-57577212
E-mail:[email protected]
Website:www.murge-electric.com
Aikko Low-voltage Switchgear
Enclosure Dimensions
Service Conditions
Basic Technical Parameters and Performance Requirements
IEC62271-200: 2011 High voltage switchgear and controlgear –Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV IEC62271-1-2007: High voltage switchgear and controlgear-Part 1: Common specificationsIEC20071-102: High voltage switchgear and controlgear –Part 102 : Alternating current disconnectors and earthing switches
Application Standard
Visual shape Industrial beauty
Visual shape Industrial beauty
Electric enclosures-though industrial products, need to meet human’s aesthetic needs. In the R&D of Aikko low-voltage switchgears, Murge’s artisans pay close attention to industrial design from details, interpreting beauty from product modelling to operation interfaces, from color matching to environment integration, and from industrial steadiness to atmosphere creation.
Aikko low-voltage switchgears
Geometrically simple modelling Industrial style blending gray and blue
Friendly operation interfaceErgonomic operation interface
Harmonious with the distribution environment
Compatible with hand pull, hand cranking and electric models, it can keep a highly unified panel style.
Functionally strong auxiliary contacts can meet any requirement for their functions and prevent misoperation.
Hand-pull and hand-cranking mechanisms
Basic structure
Interlock module, auxiliary contacts in operating and testing positions
Hand-pull mechanism
Module of hand cranking structure
Hand-cranking mechanism
Hand-pull and hand-cranking electric mechanisms
Basic structure
Electrically operated auxiliary contacts,
auxiliary contacts in operating and testing
positions
Hand-pull electric mechanism
Module of hand cranking structure
Hand-cranking electric mechanism
Double-bending, joined with rigid rivets, and equipped with positioning fixture
Primary and secondary plugs with a record of failure-free operation of millions of times
The T-shaped holes in the drawer bottom plate enhance the flexibility of mounting parts and components.
The backward bending of the drawer rear plate increases the clearances of electric equipment connecting busbars.
The drawer has secondary line binding holes in side to ensure reasonable and consistent wiring.
Safety is a permanent topic.
Humanity is the guide for exploration.
Aikko low-voltage switchgears work on the details with careful consideration, changing not a bit.
+ = + =
+ = + =
Visual splicing instructions A sliding mounting bracket
Brand-new invented Aikko sections Green manufacturing processes Easy-mounting connection mode
Drawable structure A change of reliability
Compatible mechanism module
This time, Murge works hard to make innovation.
The patent, Aikko sections, breaks more than the tradition,
and improve more than strength.
The innovation from within is a thorough transformation
Framed structure Tough strength
Enhance the strengthen, and increase the capability
S/N Name Unit Value
1 rated voltage kV 12 24 36
2 rated current A 630 630 630
3 rated closed loop breaking current A 630 630 630
4 rated on load breaking current A 630 630 630
5 rated short time withstand current kA 16 16 16
6 rated peak withstand current kA 40 40 40
7 rated short-circuit making current kA 40 10 40
8
rated power frequency withstand voltage
kV 28 50 70
9 across the isolating distance kV 32 60 80
10
rated lightning withstand voltage
Phase-to-phase and phase-to-
earthkV 75 125 170
11 across the isolating distance kV 85 145 195
12 rated transfer current A 630 630 630
13 mechanical endurance ops M1 1000 M1 1000 M1 1000
14 electrical endurance ops E3(100) E3(100) E3(100)
15 pressure of SF6 gas(20℃) bar 0.5 0.5 0.5
16 yearly leakage rate ≤% 0.5 0.5 0.5
17 enclouse degree of protection IP3X IP3X IP3X
18 (IAC)internal arcing classification A-FL
16kA 1sA-FL
16kA 1sA-FL
16kA 1s
Tabulated Parameters
FOCUS ON USER, JUST DO BETTER
Add: 338 Jinhai Avenue, Wenzhou Economic&
Technical Development Zone, Zhejiang Province
Tel.: 0086-577-57572871 Fax: 0086- 577-57577212
E-mail:[email protected]
Website:www.murge-electric.com Gas Insulated Switchgears
FMG-SF6
The FMG is a SF6 gas insulated switch disconnector for medium voltage switchgear
within secondary distribution networks, rating up to 36kV. It features compact size
and the lightweight construction. The epoxy resin enclosure is tightly sealed and filled
with SF6 gas as insulation and arc-quenching medium, which can provide good
insulation and resistance to moisture and pollution area, realizing virtually free
maintenance.
SF6 Load Break SwitchLBS-12/24/36
No. Switchgear Type
Optional Configuration Enclosure Dimensions (WxDxH)mm
Breaker
Current instrum
ent transform
e
Transformer
Load switch
Disconnector
Earthing sw
itch
Fuse
Main busbar
Relay protection
12 24 36
1.Incoming/Outgoing LBS Panel ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265
2.Transformer Protection Panel ◎ ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265
3. Metering Panel ◎ ◎ ◎ 375×1070×1700 500×1070×1700 750×1585×2265
4. CB Outgoing Panel ◎ ◎ ◎ ◎ ◎ ◎ 750×1070×1700 750×1070×1700 1000×1585×2265
5.CB Outgoing with Metering Panel ◎ ◎ ◎ ◎ ◎ ◎ ◎ 750×1070×1700 750×1070×1700 1000×1585×2265
Single Line Diagram
Enclosure configuration parameter
Outline dimension diagram
Incoming LBS Trafo protect. metering Cbog w/.meter Cb outgoing
1.1 Phase distance= 210 mm for 12kV or 24kV
1.2 Phase distance= 275 mm for 24kV
1.3 Load Break Switch for 36 kV (with different mechanism)