powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing powermanager 2 Starting and Stopping the Project 3 Configuration 4 KPI View 5 Basic Report 6 Advanced Report 7 Trends 8 System Administration and Optimization 9 Literature Index

powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

Page 1: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

powermanager

V3.3

Commissioning Manual

E50417-H1040-C612-A2

Preface

Open Source Software

Table of Contents

System Overview 1Installing powermanager 2Starting and Stopping the Project 3Configuration 4KPI View 5Basic Report 6Advanced Report 7Trends 8System Administration and Optimization 9Literature

Index

Page 2: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

iiNOTEFor your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of LiabilityThis document has been subjected to rigorous technicalreview before being published. It is revised at regular inter-vals, and any modifications and amendments are includedin the subsequent issues. The content of this document hasbeen compiled for information purposes only. AlthoughSiemens AG has made best efforts to keep the document asprecise and up-to-date as possible, Siemens AG shall notassume any liability for defects and damage which resultthrough use of the information contained herein.This content does not form part of a contract or of businessrelations; nor does it change these. All obligations ofSiemens AG are stated in the relevant contractual agree-ments.Siemens AG reserves the right to revise this document fromtime to time.Document version: E50417-H1040-C612-A2.01Edition: 04.2016Version of the product described: V3.3

CopyrightCopyright © Siemens AG 2016. All rights reserved.The disclosure, duplication, distribution and editing of thisdocument, or utilization and communication of the contentare not permitted, unless authorized in writing. All rights,including rights created by patent grant or registration of autility model or a design, are reserved.Registered TrademarksSENTRON® and SICAM® are products of Siemens AG. Anyunauthorized use is illegal. All other designations in thisdocument can be trademarks whose use by third parties fortheir own purposes can infringe the rights of the owner.

Page 3: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Preface

Purpose of the ManualThis manual covers the following topics:• Installation of the powermanager from the product DVD on a server PC.

• Basic functions of the powermanager:– Configuration– Reporting– Display of Trends– Display of KPIs

Target AudienceThis manual is mainly intended for customers who are involved in the configuration, operation, and parame-terization of powermanager.

ScopeThis manual is valid for powermanager.

Prerequisite KnowledgeYou must be familiar with the basic concepts of the following fields before you start using this manual:• Automation

• Electrical engineering

Other Standardspowermanager has been developed in compliance with ISO 9001:2008 standard.

Technical SupportIf you have any further questions regarding powermanager, do not hesitate to contact your local Siemensrepresentative.Assistance with queries regarding powermanager is also available on the following Internet site:powermanager support

Training CoursesFurther training material is available on the following Internet site:powermanager training material

Notes on SafetyThis manual is not a complete index of all safety measures required for operation of the equipment (module ordevice). However, it comprises important information that must be followed for personal safety, as well as toavoid material damage. Information is highlighted and illustrated as follows according to the degree ofdanger:

powermanager, , Commissioning Manual 3E50417-H1040-C612-A2, Edition 04.2016

Page 4: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

! WARNINGWARNING means that death or severe injury may result if the measures specified are not taken.

² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTIONCAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.

² Comply with all instructions, in order to avoid moderate or minor injuries.

iiNOTEImportant information about the product, product handling or a certain section of the documentationwhich must be given particular attention.

Qualified Electrical Engineering PersonnelOnly qualified electrical engineering personnel may commission and operate the equipment (module, device)described in this document. Qualified electrical engineering personnel in the sense of this manual are peoplewho can demonstrate technical qualifications as electrical technicians. These persons may commission,isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Proper UseThe equipment (device, module) may be used only for such applications as set out in the catalogs and thetechnical description, and only in combination with third-party equipment recommended and approved bySiemens.Problem-free and safe operation of the product depends on the following:• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenanceWhen electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If properaction is not taken, death, severe injury or property damage can result:• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting theequipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered duringtesting and commissioning.

Further Information on the ProductSiemens provides products and solutions with industrial security functions that support the secure operationof plants, solutions, machines, equipment and/or networks. They are important components in a holisticindustrial security concept. With this in mind, Siemens’ products and solutions undergo continuous develop-ment. Siemens recommends strongly that you regularly check for product updates.

Preface

4 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 5: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action(e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial securityconcept. Third-party products that may be in use should also be considered. For more information aboutindustrial security, visit http://www.siemens.com/industrialsecurity.To stay informed about product updates as they occur, sign up for a product-specific newsletter. For moreinformation, visit http://support.automation.siemens.com.

Preface

powermanager, , Commissioning Manual 5E50417-H1040-C612-A2, Edition 04.2016

Page 6: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

6 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 7: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The OpenSource Software used in the product and the license agreements concerning this software can be found in theReadme_OSS. These Open Source Software files are protected by copyright. Your compliance with thoselicense conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In theevent of conflicts between Siemens license conditions and the Open Source Software license conditions, theOpen Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source SoftwareLicense Conditions provide for it you can order the source code of the Open Source Software from yourSiemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 yearssince purchase of the Product. We are liable for the Product including the Open Source Software contained init pursuant to the license conditions applicable to the Product. Any liability for the Open Source Softwarebeyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defectsresulting from modifications to the Open Source Software by you or third parties is excluded. We do notprovide any technical support for the Product if it has been modified.

powermanager, , Commissioning Manual 7E50417-H1040-C612-A2, Edition 04.2016

Page 8: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

8 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 9: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Table of Contents

Preface..........................................................................................................................................................3

Open Source Software..................................................................................................................................7

1 System Overview........................................................................................................................................131.1 Overview.......................................................................................................................... 141.2 Supported Languages....................................................................................................... 16

2 Installing powermanager........................................................................................................................... 172.1 Installing Siemens Automation License Manager (ALM) V5.3............................................. 182.2 Installing powermanager.................................................................................................. 192.3 Transferring the License Keys............................................................................................ 202.4 Silent Installation.............................................................................................................. 21

3 Starting and Stopping the Project.............................................................................................................. 233.1 Overview.......................................................................................................................... 243.2 Starting the Project via Console......................................................................................... 253.3 Starting a Project via Project Administration.......................................................................273.4 Stopping the powermanager Project................................................................................. 28

4 Configuration............................................................................................................................................. 294.1 Configuring a Device.........................................................................................................304.2 Tabs in Standard View.......................................................................................................314.3 Overview.......................................................................................................................... 324.4 Dashboard........................................................................................................................ 334.5 Selected Values.................................................................................................................344.6 Power Quality................................................................................................................... 354.7 Harmonics........................................................................................................................ 364.8 Energy.............................................................................................................................. 374.9 Trend................................................................................................................................384.10 Operations .......................................................................................................................394.11 Web..................................................................................................................................414.12 Parameters....................................................................................................................... 424.13 Functions on the Tool Bar..................................................................................................434.14 Project Tree.......................................................................................................................444.14.1 Overview of Project Tree..............................................................................................444.14.2 Internal and Project-specific Object Names...................................................................444.14.3 Project Tree Components.............................................................................................444.15 Starting and Stopping Communication.............................................................................. 52

powermanager, , Commissioning Manual 9E50417-H1040-C612-A2, Edition 04.2016

Page 10: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

4.16 Devices............................................................................................................................. 534.16.1 Device Engineering for Power Monitoring Devices, E-counters, and Circuit Breakers......534.16.2 Generic Modbus Device............................................................................................... 574.16.2.1 Overview of Generic Modbus Device.......................................................................574.16.2.2 Device Engineering for Generic Modbus Device...................................................... 574.16.3 Virtual Counter............................................................................................................ 584.16.3.1 Overview of Virtual Counter................................................................................... 584.16.3.2 Device Engineering for Virtual Counter................................................................... 584.16.4 Calculation Value.........................................................................................................604.16.4.1 Overview of Calculation Value................................................................................ 604.16.4.2 Device Engineering for Calculation Value................................................................604.16.5 Load Monitoring..........................................................................................................614.16.5.1 Overview of Load Monitoring................................................................................. 614.16.5.2 Runtime View........................................................................................................ 624.16.5.3 Device Engineering for Load Monitoring................................................................. 674.16.5.4 Schedule................................................................................................................714.16.6 Manual Measuring Devices.......................................................................................... 734.16.6.1 Overview of Manual Measuring Devices..................................................................734.16.6.2 Runtime View........................................................................................................ 734.16.6.3 Device Engineering................................................................................................ 744.16.6.4 Overview............................................................................................................... 754.16.7 Average Value Devices.................................................................................................784.16.7.1 Overview............................................................................................................... 784.16.7.2 Average Value Configuration Tab........................................................................... 794.16.8 Converter Devices........................................................................................................804.16.8.1 Overview............................................................................................................... 804.16.8.2 Device Engineering for Converter Device................................................................ 804.17 Displaying Measured Values.............................................................................................. 864.18 Alert Classes......................................................................................................................874.19 Reaction Plans...................................................................................................................894.19.1 Overview of Reaction Plans.......................................................................................... 894.19.2 Opening and Closing Reaction Plans.............................................................................894.19.3 Configuring Reaction Plans.......................................................................................... 904.19.4 Selecting a Source....................................................................................................... 934.19.5 Deleting Devices..........................................................................................................964.20 Filter Administration......................................................................................................... 984.20.1 Overview of Filter Administration.................................................................................984.20.2 Using Filters................................................................................................................ 984.20.3 Managing Filters..........................................................................................................984.20.4 Configuring Filters..................................................................................................... 1014.21 Power Peak Analysis........................................................................................................ 1044.21.1 Overview of Power Peak Analysis............................................................................... 1044.21.2 Opening the Power Peaks Window.............................................................................1044.21.3 Creating a Report.......................................................................................................1054.21.4 Configuring Power Peaks........................................................................................... 1054.21.5 Saving the Power Peaks Configuration....................................................................... 1084.21.6 Calculating Power Peaks............................................................................................ 1094.21.7 Closing the Power Peak Window................................................................................ 109

5 KPI View....................................................................................................................................................111

Table of Contents

10 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 11: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

6 Basic Report.............................................................................................................................................. 1136.1 Report View.................................................................................................................... 1146.2 Tabs in Report View.........................................................................................................115

7 Advanced Report...................................................................................................................................... 1177.1 Overview of Reporting.................................................................................................... 1187.2 Prerequisites................................................................................................................... 1197.3 powermanager Report Window....................................................................................... 1207.3.1 Opening the powermanager Report Window..............................................................1207.3.2 Templates................................................................................................................. 1217.3.3 Reports......................................................................................................................1227.3.4 Quick Selection – Semiautomatic Report Creation...................................................... 1237.3.5 Schedule – Automatic Report Creation....................................................................... 1257.3.6 Closing the powermanager Report Window................................................................1277.4 Types of Reports............................................................................................................. 1287.4.1 Overview of Types of Reports.....................................................................................1287.4.2 Report Types............................................................................................................. 1287.4.3 Cost Center Report.....................................................................................................1297.4.4 Measuring Point Comparison..................................................................................... 1327.4.5 Measured Value Comparison......................................................................................1337.4.6 Duration Curve.......................................................................................................... 1357.4.7 Standard Report........................................................................................................ 1367.4.8 Energy Report............................................................................................................1377.5 Preparing the Cost Center Report.....................................................................................1387.5.1 Media........................................................................................................................1387.5.2 Tariff Sets.................................................................................................................. 1387.5.3 Cost Centers.............................................................................................................. 1427.6 Datapoints...................................................................................................................... 1457.6.1 Editing Datapoints in the Report Template................................................................. 1457.6.2 Inserting Datapoints in the Cost Center Report........................................................... 1467.6.3 Inserting Datapoints in the Energy Report and Other Report Types..............................1487.6.4 Device Types............................................................................................................. 1527.6.5 Filters........................................................................................................................152

8 Trends....................................................................................................................................................... 1538.1 Overview........................................................................................................................ 1548.2 Creating a Trend View..................................................................................................... 1558.3 Configuring Trend View.................................................................................................. 1568.4 Selecting a Datapoint...................................................................................................... 1588.5 Displaying the Trend View...............................................................................................160

9 System Administration and Optimization................................................................................................ 1619.1 Creating a New Project....................................................................................................1629.2 Adapting the Archive Size................................................................................................1669.3 Creating Users................................................................................................................ 1689.4 Performance Optimization...............................................................................................1739.5 Distributed Systems........................................................................................................ 176

Table of Contents

powermanager, , Commissioning Manual 11E50417-H1040-C612-A2, Edition 04.2016

Page 12: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

9.6 Mass Parameterization.................................................................................................... 1799.7 Measuring Period and Tariff Synchronization................................................................... 1829.7.1 Overview...................................................................................................................1829.7.2 Measuring Period Synchronization............................................................................. 1829.7.3 Tariff Synchronization................................................................................................185

Literature.................................................................................................................................................. 189

Index.........................................................................................................................................................191

Table of Contents

12 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 13: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

System Overview

1.1 Overview 141.2 Supported Languages 16

1

powermanager, , Commissioning Manual 13E50417-H1040-C612-A2, Edition 04.2016

Page 14: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OverviewApplication

powermanager is used to acquire, monitor, evaluate, represent, and archive energy data of the followingdevices:• PAC1500 E-counters

• PAC3100, PAC3200, PAC4200, PAC5100, PAC5200 Power Monitoring Devices

• 3WL, 3VA, and 3VL circuit breakers

• SICAM P85x devices

• Any Modbus TCP enabled measuring devices.powermanager has the following functions to perform the above tasks:• Tree view of the system (project tree)

• Measured value display with predefined user views

• Alarm management

• Reporting, integrated report engine with predefined report templates, like Energy analysis or Cost Centerreport and individual reports based on EXCEL.

• Load monitoring

• Reaction plans

• Power peak analysis

• Key Performance Indicators (KPI)

• Support for distributed systems

• Archiving system

• User management

Predefined Standardpowermanager is delivered with out-of-the-box standard projects. This enables immediate use of powerman-ager without system configuration.

Device Integrationpowermanager supports integration with the following products:• PAC1500 E-counters: This device has an integrated optical interface (IrDA). Using a Modbus RTU commu-

nication module, you can connect it to powermanager using the gateway functionality of the PAC4200.You can also use any Modbus gateway to establish the connection.

• PAC3100 Power Monitoring Device 1.0 or higher: Connect PAC3100 Power Monitoring device topowermanager using the gateway functionality of the PAC4200. You can also use any Modbus gatewayto establish the connection.

• PAC3200 Power Monitoring Device 2.0.x or higher: Connect PAC3200 Power Monitoring device topowermanager through the integral Ethernet interface using Modbus TCP.

• PAC4200 Power Monitoring Device 1.2 or higher: Connect the PAC4200 Power Monitoring device topowermanager through the integral Ethernet interface using Modbus TCP.

• PAC5100/PAC5200 multifunctional devices: Connect the PAC5100/PAC5200 multifunctional devices topowermanager via Ethernet interface.

• 3VL molded-case circuit breakers: Connect the 3VL molded-case circuit breakers to powermanager viathe gateway functionality of the PAC4200. You can use any other gateway to establish the connection.

1.1

System Overview1.1 Overview

14 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 15: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• 3WL air circuit breakers: Connect the 3WL air circuit breakers to powermanager via the gateway func-tionality of the PAC4200. You can use any other gateway to establish the connection.

• 3VA molded-case circuit breakers: Connect the 3VA molded-case circuit breakers to powermanager viaCOM800/COM100 gateway.

• P850/P855 multifunctional devices: Connect the P850/P855 multifunctional devices to powermanagervia Ethernet interface.

Other DevicesYou can connect any Modbus enabled measuring devices to powermanager through the Ethernet or gatewayusing the RS485 interface.

System Overview1.1 Overview

powermanager, , Commissioning Manual 15E50417-H1040-C612-A2, Edition 04.2016

Page 16: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Supported Languagespowermanager supports eight languages:• English

• German

• Spanish

• Portuguese

• French

• Italian

• Turkish

• Simplified ChineseWindows, dialogs, and designations of the measured variables included in the standard version are translatedto the local language. You can name all the created objects in the local language.

1.2

System Overview1.2 Supported Languages

16 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 17: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Installing powermanager

2.1 Installing Siemens Automation License Manager (ALM) V5.3 182.2 Installing powermanager 192.3 Transferring the License Keys 202.4 Silent Installation 21

2

powermanager, , Commissioning Manual 17E50417-H1040-C612-A2, Edition 04.2016

Page 18: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Installing Siemens Automation License Manager (ALM) V5.3ALM is installed during the installation of powermanager.

iiNOTEIf a lower version of ALM is found on the system during installation, it will be upgraded to the latestversion.

ALM manages the license keys for operating powermanager.You can operate powermanager based on the conditions of use of the installed license.

2.1

Installing powermanager2.1 Installing Siemens Automation License Manager (ALM) V5.3

18 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 19: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Installing powermanagerInstallation Prerequisites

Ensure that the following prerequisites are met before you start the powermanager installation.Minimum Hardware and Software RequirementsThe minimum hardware and software requirements for installing powermanager are available in readme.pdf.Microsoft ExcelEnsure that Microsoft Excel is installed on the system for viewing reports.The minimum required Microsoft Excel version is available in readme.pdf.Windows Group MembershipAll powermanager users must be members of the Microsoft Windows users group Power Users.Administration RightsYou must have administrators' rights on the system where the powermanager is installed.No Spaces in Path NameThere should not be any spaces in the path name.

Installation StepsTo install powermanager:² Close all active applications before you start powermanager installation.

² Insert the installation disk in the DVD.

² Open the DVD drive and double-click Setup.exe.The powermanager installation starts.

iiNOTEDuring installation, under the Scope of the Installation field, select Typical.

If the powermanager installation is successful, the following path is created in the Start menu: Start > AllPrograms > SENTRON > powermanager V3.3.

2.2

Installing powermanager2.2 Installing powermanager

powermanager, , Commissioning Manual 19E50417-H1040-C612-A2, Edition 04.2016

Page 20: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Transferring the License KeysThe license keys are included on the USB drive supplied with the installation disk. Additionally, you receivemultiple USB drives, each containing different license keys for optional or expansion packages.

Transferring the LicensesTo transfer the license key to the system where powermanager is installed.² Insert the USB drive in the USB port of the system.

² Click Start > All Programs > Siemens Automation > Automation License Manager.ALM opens.

² In the ALM window, click View > Management.

² Select and copy the required license keys from the USB drive.

² Paste the license key in the system.The required license keys become available on the powermanager system.

2.3

Installing powermanager2.3 Transferring the License Keys

20 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 21: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Silent InstallationSilent installation is an unattended installation via command prompt.If the previous version of powermanager is found on the system during installation of powermanager V3.3, itwill be upgraded to latest version automatically.To install powermanager via command prompt:² Insert the installation disk in the DVD-ROM.

² Execute the Setup.exe by using either of the following commands in command prompt:Setup.exe /is /L <lang ID>

- or -

² <Source>\Setup.exe -si /L <lang ID> INSTALLDIR=<Install Path>

where:Setup.exe /si is used to install the powermanager.Setup.exe /sf is to repair the powermanager.Setup.exe /sx is to uninstall the powermanager.L <lang ID> indicates the language ID that is passed as a command line argument for the language param-eter. The IDs for English and German language are 1033 and 1031 respectively.<Install Path> indicates the location at which powermanager will be installed on the local system.For example, Setup.exe /si /L 1031 INSTALLDIR=D:\Sentron\.Restart the system to complete the installation.If you want to avoid the restarting of the system, enter /noreboot as a command line argument. Restart thesystem manually to complete the installation.

iiNOTE

The command line argument si is case-sensitive.Uninstallation of powermanager V3.3 will remove all files including the installed service packs and patches.

2.4

Installing powermanager2.4 Silent Installation

powermanager, , Commissioning Manual 21E50417-H1040-C612-A2, Edition 04.2016

Page 22: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

22 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 23: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Starting and Stopping the Project

3.1 Overview 243.2 Starting the Project via Console 253.3 Starting a Project via Project Administration 273.4 Stopping the powermanager Project 28

3

powermanager, , Commissioning Manual 23E50417-H1040-C612-A2, Edition 04.2016

Page 24: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OverviewAdapting the Archive Size

By default, you can archive 100 devices in the powermanagerV3.3 project. To archive more devices orincrease the capacity of each device, adjust the archive size. For more information, see 9.2 Adapting theArchive Size.

3.1

Starting and Stopping the Project3.1 Overview

24 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 25: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Starting the Project via ConsoleTo start the powermanager V3.3 project:² Click Start > All Programs > SENTRON > powermanager V3.3 > Console to open the powermanager

console.The powermanager: Console window is opened.

[sc_Console, 3, en_US]

The powermanager: Console window lists the processes that powermanager uses.The St column indicates the status of each process.0 (Red) - Process is stopped.1 (Yellow) - Process started.

3.2

Starting and Stopping the Project3.2 Starting the Project via Console

powermanager, , Commissioning Manual 25E50417-H1040-C612-A2, Edition 04.2016

Page 26: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

2 (Green) - Process started and is currently running.² Select the powermanager project you want to start from the Project list box.

²Click to start the project.

After all the processes in the selected project is started, the project Log in window is displayed.

[sc_Basepanel_login, 3, en_US]

² Enter root in the User name field.Leave the Password field blank.Select the language from the Language list box.

² Click Login.The Base Panel window is displayed.

iiNOTEWhen powermanager is installed, the root user account has no password assigned to it. If required, assign apassword to the root user.The processes visible in the powermanager console are background processes. Opening or closing thepowermanager console has no effect on the state of the process. Data acquisition continues to run evenwhen the console is closed.

After starting the project, you can add devices in the project tree.

Starting and Stopping the Project3.2 Starting the Project via Console

26 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 27: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Starting a Project via Project AdministrationTo start the powermanager V3.3 project:² Click Start > All Programs > SENTRON > powermanager V3.3 > Project Administration.

The powermanager: Project Administration window opens.

²Click to start the project.

3.3

Starting and Stopping the Project3.3 Starting a Project via Project Administration

powermanager, , Commissioning Manual 27E50417-H1040-C612-A2, Edition 04.2016

Page 28: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Stopping the powermanager Project

iiNOTEStopping a project ends the current data collection cycle.Therefore, ensure that you save the collected data.

To stop a project:² Ensure that it is safe to stop the project.

² Click Start > All Programs > SENTRON > powermanager V3.3 > Console to open the powermanagerconsole.

²Click to stop the currently running project.The following confirmation dialog opens:

[sc_StopProjConf, 1, en_US]

Figure 3-1 Stop Project - Confirmation Dialog

² Click Yes.powermanager stops the project.The status color of all the processes changes from green to red.The status color of process monitor remains green.

iiNOTEThe processes visible in the powermanager console are background processes. Opening or closing theconsole window has no effect on the process state. Data acquisition continues to run when the console isclosed.

3.4

Starting and Stopping the Project3.4 Stopping the powermanager Project

28 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 29: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Configuration

4.1 Configuring a Device 304.2 Tabs in Standard View 314.3 Overview 324.4 Dashboard 334.5 Selected Values 344.6 Power Quality 354.7 Harmonics 364.8 Energy 374.9 Trend 384.10 Operations 394.11 Web 414.12 Parameters 424.13 Functions on the Tool Bar 434.14 Project Tree 444.15 Starting and Stopping Communication 524.16 Devices 534.17 Displaying Measured Values 864.18 Alert Classes 874.19 Reaction Plans 894.20 Filter Administration 984.21 Power Peak Analysis 104

4

powermanager, , Commissioning Manual 29E50417-H1040-C612-A2, Edition 04.2016

Page 30: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Configuring a DeviceTo configure a device in powermanager for the first time:² Map the structure of the plant to the project tree.

For more information, see 4.14.1 Overview of Project Tree.

² Create the device in the project tree.For more information, see 4.14.3 Project Tree Components.

² Configure the device.For more information, see 4.16 Devices.

² Start communication between powermanager and the device.For more information, see 4.15 Starting and Stopping Communication.

² Display the measured values.For more information, see 4.16 Devices.

4.1

Configuration4.1 Configuring a Device

30 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 31: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Tabs in Standard ViewThe Standard view contains the following tabs:• Dashboard

• Overview

• Selected values

• Power quality

• Harmonics

• Energy

• Trend

• Operations

• Web

• Parameters

4.2

Configuration4.2 Tabs in Standard View

powermanager, , Commissioning Manual 31E50417-H1040-C612-A2, Edition 04.2016

Page 32: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OverviewThe Overview tab is available for all devices except virtual devices. This tab displays the summary of differentdata point values measured by the devices.The color next to Alarm field displays the current status of the alarm. The color next to the Communicationfield shows the communication status between the device and powermanager.

[sc_overviewtab, 1, en_US]

Figure 4-1 Overview Tab

4.3

Configuration4.3 Overview

32 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 33: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

DashboardThe Dashboard tab displays the values of the data points, which are configured in the Dashboard configura-tion tab corresponding to the selected device.

[sc_Dashboard, 1, en_US]

4.4

Configuration4.4 Dashboard

powermanager, , Commissioning Manual 33E50417-H1040-C612-A2, Edition 04.2016

Page 34: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Selected ValuesThe selected values tab lists all preselected measured variables with description, current measured value, anddefined unit.You can preselect the measured values in the Display column of the Configuration tab in the Device Engi-neering view.

[sc_SelectedValues_tab, 2, en_US]

Figure 4-2 Selected Values Tab for PAC3200

The parameters for Selected values tab are set on the device or on the device type (inheritance). You cancreate filters in the system.If a measured value is highlighted in red, it indicates that the address is deactivated in the configuration.To add additional measured values:• Right-click a system, an area, or a device.

• Select Device engineering and click the device or device type.

• Select the measured values for the device or device type.

• Select Display.

• Click Save.

iiNOTEWhen selecting at area level or system level, select the device type from the shortcut menu.Area level: Inheritance of the list by all devices of the selected device type within the area.System level: Inheritance of the list by all devices of the selected device type within the station.

4.5

Configuration4.5 Selected Values

34 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 35: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Power QualityThe Power quality tab is available only for the PAC3200/4200/5100/5200 and P850/P855. This tab displaysactual, minimum, and maximum values of the power factor and frequency.This tab also displays the actual and maximum distortion in the voltage and current values.

[sc_powerqualitytab, 1, en_US]

4.6

Configuration4.6 Power Quality

powermanager, , Commissioning Manual 35E50417-H1040-C612-A2, Edition 04.2016

Page 36: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

HarmonicsThe values of the harmonics are displayed in a bar chart. This tab is only available for the PAC5200 andPAC4200 devices.

[sc_Harmonics_tab, 3, en_US]

Figure 4-3 Harmonics Tab for PAC4200

Select any one of the following values to display the data:• Voltage L-N: Harmonics voltage l-n (in %).

• Voltage L-L: Harmonics voltage l-l (in %).

• Current: Harmonics current I (in A).Select a harmonic to view the detailed values (including time stamp) of the harmonic. The bar chart shows theharmonic proportions related to the basic oscillation up to the 17th or 31st harmonic.By default, you see the instantaneous values of the harmonics. Click show maxima to view the maximumvalues of the harmonics.

4.7

Configuration4.7 Harmonics

36 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 37: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

EnergyThe Energy tab displays the energy consumption details. This tab enables you to compare the energyconsumption between two different time periods.To compare the energy consumption between two different time periods:² Select a Data point, from the drop-down list.

² Select an Interval, from the drop-down list.

² Select an Duration, from the drop-down list.

² Select the Compare option.

² Click Apply, to compare the energy consumption between two selected time periods.The comparision is displayed in the form of a graph.

4.8

Configuration4.8 Energy

powermanager, , Commissioning Manual 37E50417-H1040-C612-A2, Edition 04.2016

Page 38: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

TrendThe Trend tab is available for all devices.This tab is similar to the Trend window.The Trend tab displays Voltage, Current, Power, Power interval, Power factor, THD, and Custom. Thecustom graph is configured in the Trend configuration tab.For more information on trending in powermanager, see 8.1 Overview.

4.9

Configuration4.9 Trend

38 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 39: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OperationsThe Operations tab consists of three sections Digital output, Digital input, and Commands for measuringdevices. The State of the breaker is displayed for circuit breakers.

Operations Tab

[sc_SDO_tab, 2, en_US]

Figure 4-4 Switched Digital Outputs Tab for PAC4200

You can switch the digital outputs of the PAC3200 and PAC4200 devices on the Digital output section. Forthis purpose, configure the digital outputs as remote output in the device.A lamp icon indicates the switching state:Icon State

Signal of the digital output is high (1).Signal of the digital output is low (0).

4.10

Configuration4.10 Operations

powermanager, , Commissioning Manual 39E50417-H1040-C612-A2, Edition 04.2016

Page 40: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Use the button to the right of the lamp icon to switch on or off the digital output.

Digital InputThis section displays the digital input and its type of use.

CommandsThe commands section contains buttons that can be used to change device settings during runtime.The commands can only be transferred if password protection is switched off on the device.The following commands are available:PAC3100 • Acknowledge diagnostics

• Reset maxima• Reset minima• Reset counter

PAC3200 • Acknowledge diagnostics• Reset maxima• Reset minima• Reset counter

PAC4200 • Reset operating hours counter• Reset maxima• Reset minima• Reset counter• Reset event

3VL/3WL • Breaker ON• Breaker OFFIn addition to the circuit breakers, a symbol indicates the current status.

3VA • Reset min/max

Configuration4.10 Operations

40 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 41: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

WebThe Web tab is only visible for the PAC5100/PAC5200 and P850/P855 devices. This tab displays the web inter-face for the PAC5100/PAC5200 and P850/P855 device connected to powermanager.Use the COMTRADE viewer to view the saved fault records. The COMTRADE view is installed in the followinglocation:C:\Program Files (x86)\Siemens\Energy\ComtradeViewer\V4_54\For information on the individual tabs, see the PAC5100/PAC5200 and SICAM P850/P855 documentation.

4.11

Configuration4.11 Web

powermanager, , Commissioning Manual 41E50417-H1040-C612-A2, Edition 04.2016

Page 42: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

ParametersParameters tab displays the device information. This includes manufacturer, firmware version, module infor-mation, and so on.

[sc_DeviceData_tab, 2, en_US]

Figure 4-5 Parameters Tab

4.12

Configuration4.12 Parameters

42 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 43: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Functions on the Tool Bar

Standard view

In this view, devices can be created and configured. It also displays all the createddevices.

KPI view

In this view, the KPIs can be created and configured. It also displays all the createdKPIs.

Report view

In this view the report templates can be created and configured. Reports can becreated out of the configured templates. You can also view all the created reporttemplates and reports.

Variable trend

In this view, the variations in the values of a device over a specific time range canbe represented. A trend can contain any number of hierarchical areas for repre-senting curves, with scales and legends. Value-over-time and value-over-valuerepresentations are also possible.

Alert screen

In this view, the alerts and events are displayed in the form of a table. You can sortand filter alerts for display.

Online Help

Opens the powermanager Online Help.

The new icons can be added to the tool bar.To add new icons to the tool bar:• Right-click the tree root.

• Select System settings.The system settings section opens.

• Select the User interface tab.

• In the Language settings section, select the languages for which you want the icon to be enabled.

• In the Toolbar settings section, select the number of Additional toolbar buttons you want to add, fromthe drop-down list.

• Click Save.

will be added to the toolbar.

• Right-click , to assign a panel for the newly created icon.The Reference parametrization dialog opens.

• Select a panel from the Please select a panel section.

• Click OK.The panel is assigned to the selected panel.

iiNOTEExpert license is required to add additional tool bar buttons.

4.13

Configuration4.13 Functions on the Tool Bar

powermanager, , Commissioning Manual 43E50417-H1040-C612-A2, Edition 04.2016

Page 44: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Project Tree

Overview of Project Tree

A project tree maps the arrangement of devices based on areas and sectors.When the application is installed, the project tree contains the root System1 and the no area area.The project tree root branches to areas. Areas branch into sectors. Sectors branch into subsectors. Up to 6branching levels are possible. You can attach devices to sectors and subsectors.

[sc_ProjectTree_Overview, 2, en_US]

Figure 4-6 Project Tree Root (System1) with the "no area" Area

Internal and Project-specific Object Names

Each object in the project tree has an internal and a project-specific name.Internal Name• The first name given to the object is assigned as the internal name.

• The internal name is a system-wide unique identifier.

• The internal name must not contain any blanks or special characters.

• Internal name cannot be changed later.Project-specific Name• The project-specific name is displayed on the user interface.

• A project-specific name is not necessarily unique.

• A project-specific name can contain blanks and special characters.

• A project-specific name can be changed at any time.

• A project-specific name can be translated to multiple languages.

Assigning a Name when Creating Areas or DevicesYou assign the internal name when creating areas or devices. The system uses the internal name as theproject-specific name.Assign the project-specific name when you create the sector. The system generates the internal name.

Project Tree Components

Project Tree RootThe project tree root represents the complete system. When the application is installed, the root is calledSystem1.Right-click the project tree root to access the following cross-area functions:• Area Administration

• Filter Settings

• System Settings

• Driver Settings

• Mass Parameterization

4.14

4.14.1

4.14.2

4.14.3

Configuration4.14 Project Tree

44 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 45: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

AreasYou can divide the project tree root into different areas based on your requirements.

[sc_Areas, 2, en_US]

Figure 4-7 Areas in Project Tree

The "no area" AreaThe no area area accommodates devices that you cannot assign clearly to an area. A device created in theproject tree root is automatically moved to the no area area.Creating an AreaTo create an area:² Right-click on the project tree root.

² Click Create area.

² Assign a name to the new area. Ensure that there are no other projects having similar name.Assign the internal name when you create an area. The system assumes the internal name as the project-specific name for all languages. Then, you can change the automatically generated project-specific name.For more information, see 4.14.2 Internal and Project-specific Object Names.

² Click Create.

² Rename the area to its project-specific name.For more information on renaming an area, see Renaming an Object.

The new area is visible in the project tree.

SectorsAn area can be further subdivided into sectors.A sector can be further subdivided in other sectors. You can create up to five levels of sectors.

[sc_Sectors, 2, en_US]

Figure 4-8 Sectors and Subdivision of Sectors

Creating a SectorTo create a sector:² Right-click the area or sector in which you want to create the sector.

Configuration4.14 Project Tree

powermanager, , Commissioning Manual 45E50417-H1040-C612-A2, Edition 04.2016

Page 46: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click New Sector.A dialog opens asking for the project-specific name.

[sc_CreateSector, 2, en_US]

Figure 4-9 Assign a Project-specific Name

² Assign a project-specific name to the new sector.

Click to assign a project-specific name in multiple languages.

² Click OK.

iiNOTETo add project-specific names in other languages later, use the Rename option. For more information, seeRenaming an Object.

The sector is visible in the project tree.

DevicesYou can create devices in an area or sector.

Configuration4.14 Project Tree

46 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 47: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Devices, 2, en_US]

Figure 4-10 Devices Attached to Areas and Sectors

Creating a DeviceTo create a device:² Right-click the area or sector in which you want to create the device.

² Click create device.

² Click the device type.

[sc_CreateDevice, 4, en_US]

Figure 4-11 Selecting a Device Type

Configuration4.14 Project Tree

powermanager, , Commissioning Manual 47E50417-H1040-C612-A2, Edition 04.2016

Page 48: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Assign a name to the device.

² Click Create.Wait until powermanager creates the device.Creation of the new device takes some time depending on the device and the project size.

² Assign project-specific name to the device.To assign project-specific name to the device, use the Rename option. For more information, seeRenaming an Object.

The new device is now visible in the project tree and is recognized by the system.However, it is not yet configured. For information on how to configure a device, see 4.16 Devices.

Opening Device EngineeringAfter creating a device, powermanager immediately opens the device engineering view for subsequent config-uration.To open device engineering view if you closed it immediately after creating a device:² Right-click the device you want to configure.

² Click device engineering.The device engineering tabs are visible set against a blue background.For more information on configuration of the individual device types, see 4.16 Devices.

Copying/Moving ObjectsYou can move or copy sectors or devices within the project tree.Copied devices use the internal name of the original device. The name contains a numerically incrementalsuffix as a distinguishing feature.For example, <name>_1, <name>_2, and so on.When you copy or move a sector, all the devices and subsectors inside the sector are also copied or moved tothe new location.To copy/move an object:² Select the object that you want to copy/move.

iiNOTETo select multiple objects, press and hold CTRL key on your keyboard and select the objects that you wantto copy or paste.

² Using the left or right mouse button, drag the object to the location where you want to copy it.

² Release the mouse button.After you release the mouse button, you are asked whether you want to copy or move the object.

[sc_MoveCopy_Objects, 2, en_US]

Figure 4-12 Moving or Copying an Object

Configuration4.14 Project Tree

48 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 49: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Select whether you want to copy or move the object.Press ESC if you want to cancel the operation.

² Click Yes to confirm the action.

² Assign project-specific name to the device.To assign project-specific name to the device, use the Rename option. For more information, seeRenaming an Object.

Renaming an ObjectUse the Rename option to change the project-specific names of areas, sectors, or devices.You can also use this option to assign object names in multiple languages for localized user interfaces.

You can rename an object after:• Creation of a new area or a device

• Copying a sector or a deviceTo rename an object:² In the project tree, right-click the area, sector, or device that you want to rename.

² Click rename <object>.Here, <object> can be an area, a sector, or a device.

[sc_RenameObjects, 2, en_US]

Figure 4-13 Renaming an Object

² In the Text for every language window, change the object name for any language.

Configuration4.14 Project Tree

powermanager, , Commissioning Manual 49E50417-H1040-C612-A2, Edition 04.2016

Page 50: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_DeviceName, 1, en_US]

Figure 4-14 Text for every language Window

² Click OK.The updated object name is visible if the user interface is set to that language.

Deleting an ObjectYou can delete devices, complete sectors, or complete areas from the project tree.• For sectors, specify the action for the objects inside the sector.

You can either delete the subordinate objects, or transfer them to the upper level.

• If you delete an area, and do not delete the objects inside the area, then the objects are moved to the noarea area.

To delete an object:² In the project tree, right-click the area, sector, or device that you want to delete.

iiNOTETo select multiple objects for deletion:• Select multiple objects.

To select multiple objects, press and hold CTRL key on your keyboard and select the objects that youwant to delete.

• Right-click on any of the selected objects.

² Click delete <object>.Here, <object> can be an area, a sector, or a device.

Configuration4.14 Project Tree

50 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 51: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_DeleteObject, 2, en_US]

Figure 4-15 Deleting an Object

² If you are deleting an area or a sector, select the appropriate action for the subordinate objects from thedialog that opens.

[sc_DeleteObject_Confirmation, 2, en_US]

Figure 4-16 Deleting an Area or a Sector

Configuration4.14 Project Tree

powermanager, , Commissioning Manual 51E50417-H1040-C612-A2, Edition 04.2016

Page 52: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Starting and Stopping CommunicationYou must explicitly start or stop the communication of powermanager with the connected devices.You can start or stop an individual device, or all the devices of a sector, an area, or the entire system mappedin the project tree.The project tree shows the communication status. The device symbol that precedes the device name containsa red X or a green check.

[sc_StartStop_Communication, 2, en_US]

• Red X denotes that powermanager is not connected to the device.

• Green check denotes that powermanager is connected to the device.

Starting Communication with an Individual DeviceTo connect powermanager to an individual device:² In the project tree, right-click the device.

² In the context menu, click communication > start communication.Communication between the device and powermanager is started. The device symbol changes from red X to agreen check.

Stopping Communication with an Individual DeviceTo disconnect powermanager from an individual device:² In the project tree, right-click the device.

² Click communication > stop communication.Communication between the device and powermanager is stopped. The device symbol changes from a greencheck to red X.

Starting Communication with All DevicesTo connect powermanager to all the devices:² In the project tree, right-click a sector, an area, or the project tree root.

² Click Start communication for all devices.

Stopping Communication with All DevicesTo disconnect powermanager from all the devices:² In the project tree, right-click a sector, an area, or the project tree root.

² Click Stop communication for all devices.

4.15

Configuration4.15 Starting and Stopping Communication

52 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 53: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Devices

Device Engineering for Power Monitoring Devices, E-counters, and CircuitBreakers

Configuring a Devicepowermanager sets up a standard configuration for each new device. You only have to specify the IP address.The device engineering permits the following application-specific configuration settings:• Setting up a device as a gateway.

• Modification of the measured variable units.

• Modification of the measured variable names.

• Selection of the measured variables for display on the powermanager interface.

• Selection of the measured variables for archiving.

• Selection of the measured variables for alert triggering, with modification of the alert limits and assign-ment to alert classes.

• Modification of message texts.

4.16

4.16.1

Configuration4.16 Devices

powermanager, , Commissioning Manual 53E50417-H1040-C612-A2, Edition 04.2016

Page 54: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Communication & Units

[sc_CommunicationUnits_tab, 2, en_US]

Figure 4-17 Communication & Units Tab

The Communication & Units tab contains the following components:• IP address: The IP address of the device.

• Gateway communication: Select the gateway communication option to use the device as a gateway forconnecting subnetworked Modbus RTU devices.– Specify the IP address of the gateway in the IP address field.– Access point: The PAC4200 Power Monitoring Device or any standard gateway can be used as

gateway. For PAC4200, specify the slot into which the Expansion module PAC RS485 is plugged.– Unit address: Modbus address of the device in the Modbus RTU subnetwork.

Configuration4.16 Devices

54 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 55: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Units and factors: The powermanager standard records all measured variables in the base units.You can change the unit. Deactivate the Inherit area settings option box to edit the Unit and Divisorcolumns.For example, modify the active power unit from watts to kilowatts and set the relevant denominator to1000.

iiNOTEModification of the unit only affects the powermanager interface and not the archived values.The unit can be converted for reporting in the report template. For more information, see 7.6.1 EditingDatapoints in the Report Template.You can also convert the units using a virtual counter. For more information, see 4.16.3.1 Overview ofVirtual Counter.

Configuration

iiNOTEEnable communication between powermanager and the device to make the table entries fully visible onthe Configuration tab.For more information, see 4.15 Starting and Stopping Communication .

The Configuration tab defines the following attributes for all measured variables:• Group assignment

• Designation of the powermanager interface

• Display on the powermanager interface

• Archiving

• Alerts, triggering, limits, and alert classesTo adapt the standard configuration to your requirements:• Deselect the inherit area settings option to enable editing of the fields.

The grid of the table changes color to purple.

• Modify the values as required.

• Click Save to save the changes.

Configuration4.16 Devices

powermanager, , Commissioning Manual 55E50417-H1040-C612-A2, Edition 04.2016

Page 56: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Reducing_Addresses, 2, en_US]

Figure 4-18 Configuration Tab

The Configuration tab consists of the following columns:• group: powermanager arranges the measured variables in groups. The group column shows the assign-

ment.You can assign groups to measured variables from the Filter box in the groups tab of the Runtime view.

• element: Device name and description of the measured variable in the language that was selected whenlogging in.The description can be changed on the Extended configuration tab.

• display: Selection of the measured variables displayed on the Selected values tab.The restriction to Selected values is also effective in the display of all devices belonging to a sector, anarea, or the overall plant. Filters for the cross-device display setting do not deactivate the selection. Formore information on filters, see 4.20.1 Overview of Filter Administration.The selection does not modify the scope of display on the Groups tab.

• address: Measured variables that powermanager fetches from the device (polling).

• archive: Measured variables that powermanager archives.

• alert: The measured variables that are monitored for limit values.Deactivation of an alert resets user-specific modification of alert limits high alert and low alert to thepredefined standard.

• high alert: If the upper threshold is exceeded, a high alert is triggered.The change to the default value automatically activates the option in the alert column.

• low alert: The lower threshold. If the device parameters fall below this value, an alert is triggered.The change to the default value automatically activates the option in the alert column.

• Alert class: An alert can be assigned to an alert class.For more information on Alert class, see 4.18 Alert Classes.

• Unit: Unit of the measured variable as supplied by the device.The unit cannot be changed. You can find the subset of the units you can modify in the units and factorsarea of the Communication & Units tab.

Configuration4.16 Devices

56 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 57: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Extended ConfigurationOn the Extended configuration tab, you can modify the descriptions of the measured variables for theGerman powermanager user interface and all other languages offered by default. The table fields are open forediting.The reset to default values switch resets all changes to the delivery status of the powermanager standard.

Alert ConfigurationOn the Alert configuration tab, you can define message texts for the status of the digital inputs of the device.

Trend ConfigurationThe Trend configuration tab enables you to configure trend curves for generating trend graphs. This func-tionality is only available for PAC3200, PAC4200, PAC5100, PAC5200, P850, and P855 devices.You can add a maximum of nine trend curves for each device.The Trend Configuration tab is only visible if you access the Device Engineering view at the System level.The trend curves configured for a device type are applicable to all the devices of that device type. For example,if you add trend curves to PAC4200 device type, then those trend curves are visible for all the PAC4200devices added to the project.A new curve is visible under the Trend tab in the standard view of the device type.

Dashboard configurationThe Dashboard configuration tab enables you to configure gauge, trend, and bar chart configurations. Thisfunctionality is only available for PAC3200, PAC4200, PAC5100, PAC5200, P850, and P855 devices.The Dashboard Configuration tab is only visible if you access the Device Engineering view at the Systemlevel.

Generic Modbus Device

Overview of Generic Modbus DeviceWith the generic Modbus device, you can link any Modbus-enabled measuring devices to powermanager.You can view:• Up to 50 measured variables

• 10 status messages

• 5 power demand values

• 5 counter value

• 10 commands (write values)

• 10 digital outputsPower and energy values are displayed in groups.

Device Engineering for Generic Modbus Device

StipulationsThe following specifications are mandatory for device configuration:• Name of the measure value

• Transformation type

• Index

• Specification of the Modbus Function Code

• Specification of a factor with which the supplied measured value is multiplied

4.16.2

4.16.2.1

4.16.2.2

Configuration4.16 Devices

powermanager, , Commissioning Manual 57E50417-H1040-C612-A2, Edition 04.2016

Page 58: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Unit of the measure value

• Specification of a message for the status messages

Overflow LimitsYou can parameterize the overflow limits of the counters on the Counter Configuration tab.

Support of Free Interval LengthsThe values that are parameterized as power demand values in the generic Modbus device are restamped inthe system.

Setting the Endian Byte OrderYou can set the endian byte order for polling the data on the Communication & Units tab.Depending on whether the device transmits data in big endian order or little endian order, select the appro-priate option for data polling under Endian Byte Order on the Communication & Units tab.

Configuring Digital OutputsEach generic modbus device that you create contains provision to configure 10 command data points and 10digital outputs.You can configure these command datapoints and digital outputs from the Extended configu-ration tab in the Device engineering view.You can assign values to each command data points (write values) on the Write values tab in the standardview of Generic modbus device.Additionally, you can view and change the state of the digital outputs on the Operations tab in the standardview of Generic modbus device.

Virtual Counter

Overview of Virtual CounterA virtual counter records:• Active energy

• Reactive energy

• Counter units of the universal counterUsing virtual counter, you can:• Calculate demand values

You can add or subtract the demand values.

• Convert unitsYou can convert the unit of a counter value. For example, Wh to kWh.

• Make demand values from third-party devices available for report analysisVirtual counters are available for selection in powermanager reporting under the datapoint type pmVirt-Counter

Device Engineering for Virtual CounterOn the Counter configuration tab, assign an energy counter or a universal counter to the virtual counter.Define the unit and the corresponding conversion factor.

4.16.3

4.16.3.1

4.16.3.2

Configuration4.16 Devices

58 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 59: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_CounterConfig_tab, 2, en_US]

Figure 4-19 Counter Configuration Tab for Virtual Counter Device

Following components are visible on the Counter configuration tab of the device engineering view:• Unit

– Unit recorded by the universal counter of the connected device. For example, m3 for cubic meters.– Unit of the energy counter.

• FactorDefine a factor to convert units. For example, conversion from watt-hours to kilowatt hours with a factorof 0.001.

• VariableUniversal counter or energy counter

• OperatorOperators for adding or subtracting counters

To add a universal or energy counter to the Counter configuration tab:² Define the unit of the counter in the Unit field.

² Click .The VC input panel window opens.

² In the VC input panel window, define the factor in the Factor field.Select the universal or energy counter from the Variable drop-down list.

² Click OK.

² Click Save, to save the changes.

Configuration4.16 Devices

powermanager, , Commissioning Manual 59E50417-H1040-C612-A2, Edition 04.2016

Page 60: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

iiNOTEYou can add up to 10 counters per virtual counter.You can also add one virtual counter as an universal/energy counter for another virtual counter.

Calculation Value

Overview of Calculation ValueThe Calculation value object enables you to group and convert a maximum of 10 freely selected measuredvalues using a customized formula.

[sc_CalculationValue_tab, 2, en_US]

Figure 4-20 Calculation Value

iiNOTEDelete a device only if it is not used in any calculation unit.

Device Engineering for Calculation Value

Structure of the FormulaVariableSelect the measured values using the selection tree. Every selected measured value is assigned a variable iden-tifier p1, p2, and so on. Use the variables in the calculation formula.

4.16.4

4.16.4.1

4.16.4.2

Configuration4.16 Devices

60 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 61: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OperatorsThe mathematical operators +, -, *, and / are used for addition, subtraction, multiplication, and divisionrespectively.They are also used for the following Boolean functions:Notation 1 Notation 2 FunctionOR || ORAND && ANDXOR ^ EXCLUSIVE ORNOT | NOT

BracketsUse brackets for expressions.Formula in the Function BoxCreate the formula in the Function box.The Function box is case-sensitive.If a variable identifier used in the Function box does not correspond to any measured value, the value of thatidentifier is zero.Ensure that the formula is syntactically correct. The function is checked for validity before it is saved.ExamplesFollowing are some examples of syntactically correct formulas:• p1 + p2 + p3

• (p1 + p2) / 1000

• (p1 || p2) && p3

Load Monitoring

Overview of Load MonitoringElectricity supply contracts contain provisions to calculate the kilowatthour rate and the demand rate.The demand rate is calculated according to the maximum imported power.Therefore, avoid power peaks and distribute the power demand uniformly throughout the day.

MonitoringLoad monitoring enables you to:• Monitor the power demand values

• Respond to deviations from the planned target

Orientation VariablesLoad monitoring supplies two orientation variables for estimation of consumption behavior:• Correction power

• Forecast energy consumption

Correction PowerThe correction power is the power that is connected or disconnected to optimally use the energy volume avail-able for the current tariff interval. It informs you whether the energy imported in the tariff interval is withinthe limits of available energy and is used optimally.Forecast Energy ConsumptionLoad monitoring forecasts the expected energy consumption at the end of the tariff interval. The forecast isrecalculated for each calculation interval and becomes more precise after each calculation interval.Tariff Interval / Calculation Interval

4.16.5

4.16.5.1

Configuration4.16 Devices

powermanager, , Commissioning Manual 61E50417-H1040-C612-A2, Edition 04.2016

Page 62: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The tariff interval is subdivided into a number of calculation intervals that can be selected. The correctionpower and the consumption forecast are determined for each calculation interval.

ResponseLoad monitoring supports reactive measures with:• Switching bits

• Alerts

Switching BitsLoad monitoring sets the following switching bits:• Element No switch: The bit is set if the correction power is within the limit curve or the first or last calcu-

lation interval is calculated.

• Element switchOff: powermanager sets this bit if the load needs to be deactivated.

• Element switchOn: powermanager sets this bit if the load needs to be activated.The bits are triggered based on the defined limit curve.For more information on limit curves, see 4.16.5.3 Device Engineering for Load Monitoring.The switching state is queried in reaction plans.For more information on reaction plans, see 4.19.1 Overview of Reaction Plans.

Alerts and WarningsAn alert or a warning can be optionally configured for each switching bit. Configure it when defining the limitcurve.For more information on limit curves, see 4.16.5.3 Device Engineering for Load Monitoring.

Runtime ViewThe Runtime view for load monitoring shows the following tabs.

OverviewThe Overview tab shows the consumption development of the monitored datapoint in the current tariffinterval:• Actual energy consumption

• Forecast energy consumption

• Timing

• Correction valueThe values are shown as percentage values in a bar chart and as absolute numerical values.

4.16.5.2

Configuration4.16 Devices

62 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 63: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Overview_tab, 2, en_US]

Figure 4-21 Overview Tab

The bar chart contains the following components:• 100% mark: The 100 % mark identifies the energy setpoint.

• Consumption: The blue Consumption bar shows the actual percentage energy consumption in thecurrent tariff interval. The reference value is 100 % of the setpoint.The chart displays the consumption value up to a maximum of 125 %. If the consumption goes beyondthat threshold, then the color of the bar changes to red.

• Forecast: The Forecast bar shows the forecast of the consumption in the current tariff interval.The forecast is updated for each calculation interval.The chart displays the consumption value up to a maximum of 125 %. If the consumption goes beyondthat threshold, then color of the bar changes to red.

• Time: The yellow time bar shows the timing in the current tariff interval. The 100 % mark is the tariffinterval end time. The bar ends at the 100 % mark when the last calculation interval is reached.

• Correction value: The Correction value bar shows the positive or negative power correction value. Usethis value to adjust the actual power to its optimal value so that it corresponds to the setpoint.The red bar or the green bar denotes the correction value for the power. Both bars originate from the 100% mark.– Red bar: The red bar indicates negative correction value. It starts from the 100 % mark and moves to

the right of the mark.Switch off some power to bring the correction bar back to 100 % mark.

– Green bar: The green bar indicates positive correction value. It starts from the 100 % mark andmoves to the left of the mark.You can activate more power to bring the correction bar back to 100 % mark.

Invalid values are shown in magenta.

Configuration4.16 Devices

powermanager, , Commissioning Manual 63E50417-H1040-C612-A2, Edition 04.2016

Page 64: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The Interval BoxThe Interval box displays the calculation intervals.The first value specifies the last completed calculation interval. The second value shows the number of calcula-tion intervals into which the tariff interval is subdivided.The Consumption, Prognosis, and Correction boxes show the absolute numerical values corresponding to thebar charts for the same values.

Energy ProfileThe Energy profile tab displays the deviation between actual energy consumption and rated energyconsumption during the current tariff interval.

[sc_EnergyProfile_tab, 2, en_US]

Figure 4-22 Energy Profile Tab

The Energy profile tab contains the following information:• The X-axis denotes the time curve of the tariff interval.

• The Y-axis denotes the imported energy in kWh.

• The black trend line denotes the consumption setpoint. It is always linear.

Configuration4.16 Devices

64 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 65: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• The colored trend line shows the actual consumption.The trend line is either blue, red, or magenta.– If the actual consumption is below the setpoint, the trend line is blue. This condition indicates a

positive correction power in the current calculation interval. You can activate extra power withoutexceeding the setpoint.

– If the actual consumption is above the setpoint, the trend line is red. This condition indicates a nega-tive correction power in the current calculation interval. Switch off some power to bring theconsumption to the setpoint.

– If powermanager encounters an invalid value during the calculation interval, the trend line ismagenta.

Daily TrendThe Daily trend tab displays the power demand of the monitored load during the day.

[sc_DailyTrend_tab, 2, en_US]

Figure 4-23 Daily Trend Tab

The Daily trend tab displays the following information:• The X-axis shows the tariff intervals for a 24 hour time range.

• The Y-axis shows the power in kW.

• The orange horizontal axis shows the power setpoint.

• The blue column shows the actual output of one tariff interval.

• The red column shows the tariff interval with the highest power demand during the day.

• The magenta column shows the tariff intervals with invalid values.

Configuration4.16 Devices

powermanager, , Commissioning Manual 65E50417-H1040-C612-A2, Edition 04.2016

Page 66: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Previous Day TrendThe Previous day trend tab shows the power demand of the monitored loads during the previous day.The display corresponds to the daily trend.The previous day's trend is not displayed if no data is available for the previous day or if the calculation intervallength has changed with respect to the previous day.

EnvelopeThe Envelope tab shows:• Correction power values of the calculation intervals during the current tariff interval.

• Parameterized limit curve. The limit curve defines the threshold of the correction power. Switching is onlyrecommended if the actual power exceeds the limit curve. The purpose of limit definition is to smoothbrief power spikes, thus reducing the number of switching recommendations.

Superpositioning of the two curves results in the calculation intervals with the switching recommendation thattakes effect.

[sc_LimitCurve_tab, 3, en_US]

Figure 4-24 Envelope Tab

Limit curveThe limit curve shows the defined positive and negative limits within which no switching recommendation isgiven.The limit curve can be configured in device engineering view, on the Envelope tab.The Envelope tab displays the following information:• The X-axis shows the time curve of the tariff interval.

• The Y-axis shows the correction power in kW.

• The colored bars show the correction power of the calculation interval.– The green bars above the X-axis indicate positive correlation power in the calculation interval.– The red bars below the X-axis indicate negative correlation power in the calculation interval.

Configuration4.16 Devices

66 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 67: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Device Engineering for Load Monitoring

OverviewA load monitoring unit created in the project tree monitors one datapoint.Following configurations are necessary for the load monitoring unit to start monitoring:• Selection of the datapoint

• Definition of the tariff interval and of the calculation interval

• Definition of the setpoint, either constant or variable, during the day

• Definition of the limit curve

• Definition of the responseTo access the Configuration tab for a load monitoring device, right-click the device and click device engi-neering. Device engineering opens automatically when you create a configuration.After making the configuration changes, click the Apply button to confirm the changes.Any tariff interval running at this time is stopped and marked as invalid.

iiNOTEEnsure that you use only positive values for load monitoring. Using negative values results into displayproblems.

4.16.5.3

Configuration4.16 Devices

powermanager, , Commissioning Manual 67E50417-H1040-C612-A2, Edition 04.2016

Page 68: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Parameterization

[sc_Parameterization_tab, 3, en_US]

Figure 4-25 Parameterization Tab

Datapoint selectionThe Datapoint selection area enables you to select the data source that you want to monitor.Ensure that you provide the appropriate information in the following list boxes to select the data source thatyou want.

Configuration4.16 Devices

68 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 69: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Type: Select any one of the device types from the Type list box:– Calculation Value– Converter– 3VAETU8– Generic Modbus Device– PAC1500– PAC3100– PAC3200– PAC4200– PAC5100– PAC5200– P850– P855

• Device: The Device list box shows the devices created in the project tree of the device type selected inthe Type list box. Select any one of the devices.

• Element: The element is the data source that you want to monitor. From the Element list box, select themomentary power value of the device selected in the Device list box.

Click to select the data source directly from the project tree structure.Interval SettingsUse the Interval settings area to define the length of the tariff and calculation intervals.• Tariff interval: Define the tariff interval in minutes and seconds.

• Calculation interval: Define the calculation interval in minutes and seconds.While defining the tariff and calculation intervals, ensure that:• The tariff interval is integrally divisible by the calculation interval.

• 60 minutes are integrally divisible by the tariff interval.

• The tariff interval lasts a maximum of 60 minutes.SetpointAssign a constant or variable setpoint to the monitored data source.Set a schedule for a variable setpoint.• Guideline: Select Guideline to assign a constant setpoint to the monitored data source.

Selecting this option activates the Setpoint field.

• Setpoint: Define the momentary power in kW in the Setpoint field. The smallest calculated setpoint is 1kW.

• Timetable: Select Timetable to assign a variable setpoint to the monitored data source.The Edit button is activated after you select this option.Click Edit to prepare a schedule for a variable setpoint.For more information on creating schedules, see 4.16.5.4 Schedule.

Limit CurveThe limit curve defines the threshold of the correction power. Switching is only recommended if the actualpower exceeds the limit curve. The purpose of limit definition is to smooth brief power spikes, thus reducingthe number of switching recommendations.

Configuration4.16 Devices

powermanager, , Commissioning Manual 69E50417-H1040-C612-A2, Edition 04.2016

Page 70: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_LM_LimitCurve_tab, 1, en_US]

Figure 4-26 Limit Curve Tab

Setting the Positive and Negative Limit Correction PowerDefine the upper and lower envelopes for the positive and the negative thresholds of the correction power onthe Limit curve tab.Define the following fields:• Alarming

Select whether you want the limit curve to be defined according to power (in kW) or the percentage ofthe setpoint.

• Maximum correction valueThe maximum correction value determines the range of value of the correction power displayed in thediagram.Ensure that the limits of the interpolation points P1 to P4 do not exceed the maximum correction value.

• Envelope 1Define the threshold for the positive correction power in the Envelope 1 area.

• Envelope 2Define the threshold for the negative correction power in the Envelope 2 area.

• P1, t1 to P4, t4Define the interpolation points of the limit curve in these boxes under the Envelope 1 and Envelope 2areas.You can see the preview of the limit curve at the bottom of the Limit curve tab.

AlertingActivate the alerts in the Alerting area of the Limit curve tab.

Configuration4.16 Devices

70 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 71: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The internal switching bits of the system trigger the alerts sending. In turn, which switching bits the systemsets depends on the defined limit curve.There are four options available in the Alerting area:• no switch

Select this option to receive an alert/warning whenever the switchNo switching bit is set.You do not need to connect or disconnect the load.

• switch offSelect this option to receive an alert/warning whenever the switchOff switching bit is set.Disconnect the load.

• switch onSelect this option to receive an alert/warning whenever the switchOn switching bit is set.Load can be connected.

• soonSwitch off the load because the percentage threshold in the Limit % field is reached.The value in the Limit % field refers to the energy consumption setpoint in the tariff interval. 100 %corresponds to the setpoint.

Schedule

PurposeFor each tariff interval during a day, a schedule defines the rated power of the monitored datapoint. Thus, theplanned rated power varies in intervals and can increase or decrease at various times in a day.The system calculates the number of tariff intervals. The interval length in the schedule is prepared accord-ingly. For example, if a 15-minute tariff interval is configured, the schedule contains 96 intervals.A schedule applies to any selected calendar period. For all days without an assigned individual schedule, thesystem accesses a default schedule.The time difference between summer and winter time is not considered in the schedule. Configure thechangeover days separately.To create or edit schedules, explicitly activate an edit mode. This prevents inadvertent parameterization errors.

Path and File NameThe system subdivides consecutive calendar periods into days and creates a file in the following directory:<project_name>\data\EC_TimeTableThe format of the name assigned to the file is:<load_monitor_name>_YYYYMMDD.csvThe file containing the default schedule is named:<load_monitor_name>_default.csv

Opening the Edit Schedule WindowFor information on opening the Edit Schedule window, see Parameterization under Device Engineering inLoad Monitoring.

Edit Schedule WindowThe Edit schedule window enables you to create and edit timetables. You can define the schedules for aprolonged period and store them for each day.

4.16.5.4

Configuration4.16 Devices

powermanager, , Commissioning Manual 71E50417-H1040-C612-A2, Edition 04.2016

Page 72: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_EditSchedule, 1, en_US]

Figure 4-27 Edit Schedule Window

The schedule table has the following columns:• No.: The nth tariff interval in the course of the day. The system calculates and specifies the number of

tariff intervals.

• Time: Start time of the tariff interval.

• setpoint: Power setpoint on the monitored datapoint in the tariff interval.The Action area has the following boxes:• View file: This option is selected by default when you open the Edit Schedule window. It enables you to

view the current schedule in the table.Also, only the starting point of the schedule is activated in the Period area when you select this option.

• Save/edit file: Select this option to edit the schedule.Selecting this option activates both the starting point and ending point of the schedule in the Periodarea.Additionally, you can edit the setpoint in the Setpoint column of the schedule table.

Creating a ScheduleTo create a schedule:• Check whether an individual schedule exists for the target period.

The schedule table has the heading Default schedule when the default schedule is visible. The tabledoes not have a heading when an individual schedule is assigned to the currently selected day.

Configuration4.16 Devices

72 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 73: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Select Save/edit file.

• In the Period area, define the time range for which the schedule is valid.

• Set up the schedule in the table. Define the power setpoint of the monitored datapoint for each tariffinterval.Empty Setpoint cells in the table assume the value from the Setpoint cell above. If you want to apply aconstant setpoint through the entire day, define the setpoint only for the first interval at the start of theday.If the Setpoint cell of the first tariff interval at the start of the day is not filled, the value entered on theParameterization tab applies.

• Click Apply to confirm the changes.

Creating a Default ScheduleIf no default schedule exists, powermanager shows an error message when you open the Edit Schedulewindow.To create a default schedule:• Create a schedule in the Edit Schedule window.

For more information on creating a schedule, see Creating a Schedule above.

• After you create a schedule, go to <project_name>\data\EC_TimeTable.

• Select the new schedule file.The file name format for the new file is: <load_monitor_name>_YYYYMMDD.csv.The date YYYYMMDD in the file name corresponds to the date value in the dialog.

• Replace the date YYYYMMDD with default.Therefore, the new file name has the format: <load_monitor_name>_default.csv.

Creating a Blank TableClick New in the Edit table area to empty all the setpoints from the currently selected schedule. This action isonly possible in the display mode. To fill the blank table, switch to the edit mode.

Manual Measuring Devices

Overview of Manual Measuring DevicesSeveral electrical subsystems within non-residential buildings or small and medium industrial plants consist ofmeasuring devices, which are either not capable of or restricted from communicating with any externalsystems such as powermanager. The manual measuring device feature enables you to manually add data froman external device that cannot be integrated with powermanager.

Runtime ViewThe runtime view for manual measuring devices shows the following tabs.

Overview TabThe Overview tab displays the measured values entered for the selected devices. This tab shows a maximumof 50 previous values. In order to add new measured values for the device, switch to Input view. For moreinformation, see 4.16.6.4 Overview.

Energy TabThe Energy tab displays the energy consumption details. This tab enables you to compare the energyconsumption between 2 different time periods.

4.16.6

4.16.6.1

4.16.6.2

Configuration4.16 Devices

powermanager, , Commissioning Manual 73E50417-H1040-C612-A2, Edition 04.2016

Page 74: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_TrendTab, 3, en_US]

Figure 4-28 Energy Tab

For more information, see 4.8 Energy.

Device EngineeringAfter adding the device to powermanager, on the Unit+Overflow tab, define the following parameters:Unit: The measurement unit for the data entered for the device. You cannot change the unit after you savethe configuration.Overflow: The maximum acceptable measured value.

iiNOTEEnsure that the overflow value is greater than or equal to 0.The overflow value cannot be negative.

4.16.6.3

Configuration4.16 Devices

74 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 75: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_DeviceEngineering, 2, en_US]

Figure 4-29 Unit+Overflow Tab for Manual Measuring Device

ArchivingBy default, powermanager creates an archive of the measured values entered for a device. Each archive storesmeasured values upto 13 months. After the archive is full, it is closed and you cannot edit the archive.

ReportingYou can generate the Cost Center report and the Energy report for manual measuring devices.

OverviewThe Input view enables you to add measured values for the manual measuring devices.In the menu bar, click View > Input to switch to input mode.

iiNOTEIn the Input view, only the manual measuring devices are visible at the sector, area, and project tree rootlevel.The sector, area, and project tree root level display:• The list of manual measuring devices.

• The latest measured value entered for each device and the timestamp associated with the measuredvalue.

To enter a measured value for a device:

4.16.6.4

Configuration4.16 Devices

powermanager, , Commissioning Manual 75E50417-H1040-C612-A2, Edition 04.2016

Page 76: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click on the project tree root, an area, or a sector to view the list of available manual measuring devices.

- or -

Configuration4.16 Devices

76 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 77: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click the device to see the list of previous 50 measured values.

² At the sector, area, or project tree root level, double-click the device name in the table for which youwant to add the measured value.- or -

² Click on the right-side of the table.The Input panel window opens.

Configuration4.16 Devices

powermanager, , Commissioning Manual 77E50417-H1040-C612-A2, Edition 04.2016

Page 78: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_InputMeasuredValue, 2, en_US]

Figure 4-30 Input Panel Dialog

² In the Input measured value window, enter the following details:Date: The date on which the measured value was recorded.Hour: The hour of the day when the measured value was recorded.Minute: The quarter of the hour when the measured value was recorded.Value: The measured value of the device.

iiNOTE

• The date and time entered in the Input panel dialog must be between the date and time of creationof the device and the current date and time.

• If the overflow limit set for the device is 0, then ensure that the measured value that you enter ishigher than the measured value entered for the previous timestamps.

² Click OK. The measured value is added to the device.The updated time and value are now visible under <last time> and <last value> columns respectively.

iiNOTEAfter you add the measured value, the time and value entered is visible under <new time> and <newvalue> columns respectively.

² Click on the right-side of the table, to edit the input Value.The Input panel dialog opens.

Average Value Devices

OverviewThe average value device is a virtual device, which enables you to calculate the average value of any datapoint from a physical device or another average value device over a specific time period.After configuring an average value device, you can monitor, represent, and archive the average value calcu-lated by the device.

4.16.7

4.16.7.1

Configuration4.16 Devices

78 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 79: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The Device Engineering view enables you to define average value parameters for each device on theAverage value configuration tab. You can define up to 10 average value parameters for each device.For more information, see 4.16.7.2 Average Value Configuration Tab.

Average Value Configuration TabThe Average value configuration tab enables you to configure the Average value device.By default, there are 10 placeholders available to add the parameters for which you want to calculate theaverage value. The placeholders for average value parameters are named Average Value 1, Average Value 2,Average Value 3...Average Value 10.

[sc_AverageValue_Tab, 2, en_US]

Average Value Configuration TabTo add an average value parameter for an average value device:² Select a placeholder from the Average value configuration table.

² Click .The dpSelector window opens.

iiNOTE

To delete a parameter, select the parameter and click . The parameter is deleted and is replaced by therespective placeholder.For example, if you delete the third parameter, then it is replaced by the placeholder Average Value 3.

² In the dpSelector window, select the device for which you want to create the average value parameters.

² Click OK.

4.16.7.2

Configuration4.16 Devices

powermanager, , Commissioning Manual 79E50417-H1040-C612-A2, Edition 04.2016

Page 80: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² The average value parameter is added to the table.

² By default, the average value for a device is calculated for an interval of 15 minutes. However, you canset the interval between 1 min to 1440 minutes (24 hours).

² Under the Factor column, define a factor to calculate the average value for the defined unit.

² Under the Unit column, define the unit of the average value data point.

² Click Save, to save the configuration.

iiNOTEEnsure that the average value parameter fulfills the following conditions:• The selected data point must be available for the device.

• The selected data point must belong to a local system and not a distributed system.

• The selected data point type must be an integer, unsigned integer, or float value.

• The selected data point must not be an average value data point itself.

• Each combination of the data point and the calculation interval should be unique.Additionally, the selected data point must also be archived for powermanager to calculate the correctaverage value. If the data point is not archived, powermanager will still calculate the average value for thatdata point. However, if you restart the project, powermanager does not calculate the correct value for thedata point.

iiNOTEFor information on the Configuration and Extended Configuration tabs, see 4.16.1 Device Engineeringfor Power Monitoring Devices, E-counters, and Circuit Breakers.

Converter Devices

OverviewThe converter device is a virtual device, which enables you to convert the power values to correspondingenergy values and vice versa.After configuring a converter device, you can monitor, represent, and archive the power or energy valuescalculated by the device.The Device Engineering view enables you to select data points to convert for each device on the Converterconfiguration tab. You can define up to 10 converter data points for each device.For more information, see 4.16.8.2 Device Engineering for Converter Device.

Device Engineering for Converter DeviceThe device engineering view enables you to define power/energy parameters for each device on theConverter configuration tab. You can define up to 10 parameters for each device.By default, there are 10 placeholders available in each tab to add the power or energy parameters. The place-holders for energy parameters are named Energy Value 1, Energy Value 2, Energy Value 3...Energy Value10. The placeholders for power parameters are named Power Value 1, Power Value 2, Power Value3...Power Value 10.

Converting Energy to PowerTo add energy parameters to the Energy to Power tab:² Select a placeholder from the Energy to Power table.

4.16.8

4.16.8.1

4.16.8.2

Configuration4.16 Devices

80 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 81: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Energy2Power_Converter, 2, en_US]

Figure 4-31 Energy to Power Converter Tab

² Click .The Selection tree for energy values window opens. The Selection tree for energy values windowdisplays only the energy data points of all the devices.

Configuration4.16 Devices

powermanager, , Commissioning Manual 81E50417-H1040-C612-A2, Edition 04.2016

Page 82: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_EnergyDP_Input, 1, en_US]

Figure 4-32 Selection tree for energy values

iiNOTE

To delete a parameter, select the parameter and click . The parameter is deleted and is replaced by therespective placeholder.For example, if you delete the third parameter, then it is replaced by the placeholder Energy Value 3.

² In the Selection tree for energy values window, select the data points for which you want to create theaverage value parameters.

² Click OK.The converter parameter is added to the table.

² Under the Period (mins) column, select the time interval for which the energy data is collected. This datais then converted to power data.

Configuration4.16 Devices

82 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 83: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Under the Factor column, define a factor to convert units. For example, converting kW to kWh.

² Under the Unit column, define the unit of the converter data point.

² Select the show trend option from the Show trend column.This enables you to view the trend graph of the selected data points in the trends view.

² Click Save.

Converting Power to EnergyTo add power data points to the Power to Energy tab:² Select a placeholder from the Power to Energy table.

[sc_Power2Energy_Converter, 2, en_US]

Figure 4-33 Power to Energy Converter Tab

² Click .The Selection tree for power values window opens. The Selection tree for power values windowdisplays only the power data points of all the devices.

Configuration4.16 Devices

powermanager, , Commissioning Manual 83E50417-H1040-C612-A2, Edition 04.2016

Page 84: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_PowerDP_Input, 1, en_US]

Figure 4-34 Selection tree for power values

iiNOTE

To delete a parameter, select the parameter and click . The parameter is deleted and is replaced by therespective placeholder.For example, if you delete the third parameter, then it is replaced by the placeholder Power Value 3.

² In the Selection tree for power values window, select the data point for which you want to create theaverage value parameters.

² Click OK.The converter parameter is added to the table.

² Under the Factor column, define a factor to convert units. For example, converting kWh to kW.

² Under the Unit column, define the unit of the converter data point.

Configuration4.16 Devices

84 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 85: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Select the show trend option from the Show trend column.This enables you to view the trend graph of the selected data points in the trends view.

² Click Save.

iiNOTEEnsure that the converter parameter fulfills the following conditions:• The selected data point must be available for the device.

• The selected data point must not be a converter data point itself.

• Each data point selected for conversion must be unique.Additionally, the selected data point must also be archived for powermanager to correctly convert the datapoint. If the data point is not archived, powermanager will still convert that data point. However, if yourestart the project, powermanager does not calculate the correct conversion value for the device.

iiNOTEFor information on the Configuration and Extended Configuration tabs, see: 4.16.1 Device Engineeringfor Power Monitoring Devices, E-counters, and Circuit Breakers.

Configuration4.16 Devices

powermanager, , Commissioning Manual 85E50417-H1040-C612-A2, Edition 04.2016

Page 86: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Displaying Measured ValuesThe measured values of the configured devices can be displayed:• Per device

• Across all devices of a sector

• Across all devices of an area

• Across all devices of the plantYou can restrict the view by using previously defined filters or filters you have defined for the specific applica-tion.

Displaying Measured Values of a DeviceTo display the measured values of a device:² Ensure that the Standard view is activated.

If Standard view is not activated, click to activate the Standard view.

² Select a device in the project tree.The Selected values tab opens in the runtime area.

² Select a group from the filter field.

Displaying Measured Values of Several DevicesTo display the measured values of several devices:² Ensure that the Standard view is activated.

If Standard view is not activated, then click to activate the Standard view.

² In the project tree, select an area, a sector, or the project tree root.The Selected values tab opens in the runtime view.

The standard installation contains the No filter and Default filters. Define application-specific filters to restrictthe view.

4.17

Configuration4.17 Displaying Measured Values

86 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 87: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Alert ClassesAlerts are subdivided into alert classes. powermanager provides four predefined alert classes.

Assigning a Measured Value to an Alert ClassAssign alerts, high alert threshold, low alert threshold, and alert class to a measured value in the Configura-tion tab of the device engineering view.A measured value has only one alert-triggering upper threshold (High alert) and one alert-triggering lowerthreshold (Low alert). Only one alert is assigned to one alert class. The alert-triggering upper and lower thresh-olds of a measured value cannot be assigned to different alert classes.

[sc_AlertClasses, 1, en_US]

Figure 4-35 Alert Classes

Type of Alert ClassesThe following types of alert classes are available:

Table 4-1 Alert Classes

List box in deviceengineering

Alert class (DPE) Abbreviation Priority Color Type of acknowledgement

Warning notacknowledgeable

Warning does notrequire acknowl-edgement

WANQ 50 Yellow Cannot be acknowledged

Warning Warning requiresacknowledgement

WA 50 Yellow CAME or WENT requiresacknowledgement

Alert NQ Alert does notrequire acknowl-edgement

ANQ 60 Red Cannot be acknowledged

Alert Warning requiresacknowledgement

A 60 Red CAME or WENT requiresacknowledgement

[sc_Alarms, 2, en_US]

Figure 4-36 Base Panel's Alert Area

• The abbreviations are displayed in the first column of the alert area.

• The priority of the alert is displayed in the second column of the alert area.

• Cannot be acknowledged: The alert area can only be in the CAME or no alert state. The normal state isonly achieved by a value change. Acknowledgement is not possible.

4.18

Configuration4.18 Alert Classes

powermanager, , Commissioning Manual 87E50417-H1040-C612-A2, Edition 04.2016

Page 88: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• CAME or WENT required acknowledgement: Each alert range can be in one of the following states.– came/unacknowledged– came/acknowledged– went/unacknowledged– No alert

The normal state is only achieved by a value change and acknowledging the alert. However, foracknowledging the alert, acknowledge either the came alert in the came/unacknowledged state orthe went alert in the went/unacknowledged state.

Alert Coding

Table 4-2 Alert Coding

Color Cycle MeaningYellow Flashing rapidly Pending, unacknowledged warningYellow Flashing slowly No longer pending, unacknowledged warningYellow Uninterrupted Pending, acknowledged warningRed Flashing rapidly Pending, unacknowledged alertRed Flashing slowly No longer pending, unacknowledged alertRed Uninterrupted Pending, acknowledged alert

Configuration4.18 Alert Classes

88 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 89: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Reaction Plans

Overview of Reaction Plans

Automated Switching of Digital OutputsBased on the configuration of the reaction plans, powermanager switches the interfaced devices' digitaloutputs automatically. Automation requires configuration of the reaction plans.

Target, Function, and SourceA reaction plan consists of three parts:• Target

The target of a reaction plan is a digital output. On the device, configure the output as Remote output toenable switching.

• FunctionThe function denotes the type of triggering.The switching operation can be triggered as follows:– Digital input of a device– Alert of a measured value– Switching bit of load monitoring

• SourceAny datapoint element (DPE) that provides the selected function serves as the source.Together, the function and the source are the switching condition.

Assigning the Target and ConditionYou must prepare a separate reaction plan to switch a digital output automatically.A maximum of one condition can be assigned to one target. However, you can assign a single condition tomultiple targets.

ValidityThe system checks the validity of the source and target when a reaction plan is configured.The reaction plan is not checked during the runtime. Later changes in the system lead to incorrect parameteri-zation. When you reopen the configuration view for reaction plans, messages pointing out such arising param-eterization errors are displayed.

Opening and Closing Reaction Plans

Opening Reaction PlansTo open reaction plans:² Click View > Reaction Plan to open the reaction plans.

² In the project tree, click an area, a sector, or a device to view all the digital outputs in that object.Root: Displays digital outputs of all devices in the system.Area: Displays digital outputs of all devices in the selected area.Sector: Displays digital outputs of all devices in the selected sector.Device: Displays digital outputs of the selected device.

²

Click to return to the Standard view.

4.19

4.19.1

4.19.2

Configuration4.19 Reaction Plans

powermanager, , Commissioning Manual 89E50417-H1040-C612-A2, Edition 04.2016

Page 90: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Configuring Reaction Plans

The reaction plans are listed in tables in two tabs:Parameterize outputs tabThis tab shows:• Assignment of the target, function, and source

• Switching status of the sourceThe status of the source can be inverted with a switching command.

[sc_ParameterizeOutputs_tab, 2, en_US]

Figure 4-37 Parameterize Outputs

Switching outputs tabThis tab shows the switching status of the target.You can force the switching of the digital output using a switching command.

ScopeThe reaction plans table lists the existing digital outputs. Additionally, incorrectly parameterized, deactivated,or reaction plans that can still be configured are visible.The scope is limited to the level selected in the project tree. All digital outputs existing in the system are listedwhen the project tree root is selected.A digital output only appears once in the list. Therefore, you can assign only one condition to one output.

SortingWhen you open the reaction plans table, all the columns are automatically sorted in ascending order based onthe digital outputs, that is, the first two columns: output area.sector(s) and Output.Sorting is possible for all columns.

4.19.3

Configuration4.19 Reaction Plans

90 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 91: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Click the column header to sort the table in descending order. Click once again to sort the table in ascendingorder.

Active Reaction PlanA reaction plan is created and active in the runtime system when a function and a source are assigned to adigital output.The Function column provides the following functions:• Digital input

• Alert

• Load monitoringSelect a source whenever you select a function. The system opens a corresponding selection window. A func-tion can be reassigned at any time. The source for a selected function can be changed later.Select the No function function to deactivate an existing reaction plan.The columns for sources that are not assigned are blank.

Remote Output PrerequisiteThe Type of use column shows the type of use of the digital output that has been set on the device, eitherdirectly or with configuration software.Digital outputs can only be parameterized if they have been configured as a Remote output. The Functioncolumn only offers functions for selection if this prerequisite is met. Otherwise, the Function and Sourcecolumns are blank.

Nonexecutable ParameterizationA configured reaction plan becomes nonexecutable if the type of use of the digital output is modified later,either directly on the device or via the powerconfig configuration software. In this case, a different value isvisible in the table instead of the Remote output type of use.The system uses color coding to identify reaction plans that have become nonexecutable. The existing assign-ment of the target, function, and source is retained.Color Error class MeaningRed 1 The output is configured as Rotation. It cannot be switched.Yellow 2 An alert is selected as the source, but the associated alert handling is not activated.

The alert cannot arrive, and so the reaction plan is not executed.Gray 3 The address of the source or of the target is deactivated. In this case, the system

does not register the changes or the switching command is not forwarded to thedevice.

Switching commands are executed until the reaction plan is deleted. The "No function" function cancelsassignment of the source.The output remains in its last known state if communication with the source is interrupted. The output statuschanges accordingly as soon as communication with the source is established again and its status changes.The digital output remains in its last known state if communication with the digital output is interrupted. Theoutput status changes accordingly as soon as communication with the output is established again and thestatus of the source changes.

Behavior in Distributed SystemsIf the digital input of a remote device (non-local device in a distributed system) is linked to the digital outputof a local device in a reaction plan and the distributed system is no longer accessible the local device maintainsthe last output state internally.For example, if there is a communication disruption, the local device internally maintains the last output state.

Configuration4.19 Reaction Plans

powermanager, , Commissioning Manual 91E50417-H1040-C612-A2, Edition 04.2016

Page 92: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

iiNOTEIf the input state of the remote device changes during the communication disruption the local device doesnot recognize this status change.

Logical InversionIn the Inverted column, you can invert the switching state. Inverting the switching state also inverts theoutput status.

Columns in Parameterize Outputs TabThe columns of the Parameterize outputs tab are sorted according to Targets, Functions, and Sources.The Parameterize outputs tab has the following columns:• Digital output location and Digital output

These columns display the digital output of the device that is attached in the designated area and sectorof the project tree.

• Type of useThis column displays the configured type of use of the digital output. Configuration of a reaction planrequires the Remote output type of use.

• FunctionThis column is used to set the trigger for the switching operation of the digital output.You can set one of the following triggers:– Digital input of the device– Alert of a measured value– Switching bit of load monitoring

Click the table cell to open a list box. You can select the trigger types from this list.Click on a list entry to open the corresponding dialog for selection of the source.

• Source location and SourceThese columns display the datapoint element attached in the designated area and sector of the projecttree. This provides the selected function.Click a cell to open a selection window.

• Source stateThis column displays whether the source is switched on or off.

• InvertedYou can invert the switching state using this column.If this column is set to YES, then logical inversion is switched on.If this column is set to NO, then logical inversion is switched off.

Columns in Switch Outputs TabThe Switch outputs tab shows the switching status of the digital output. You can change the switching statususing a switching command.The Switch outputs tab has the following columns:• Digital output location and Digital output

These columns display the digital output of the device that is attached in the designated area and sectorof the project tree.

• StateThis column displays the switching state of the digital output.If the switching state is OFF, then the digital output is low.If the switching state is ON, then the digital output is high.

Configuration4.19 Reaction Plans

92 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 93: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Switching groupThis column displays the switch group.

• Type of useThis column displays the configured type of use of the digital output. Configuration of a reaction planrequires the Remote output type of use.

• SwitchThis column displays the command for switching the digital output.Change the command to OFF to switch the signal of the digital output to low.Change the command to ON to switch the signal of the digital output to high.Based on the change in the switching status in this column, the values in the Status columns areupdated.

Saving the ConfigurationClick Save, to save the configurations made in database.If the configuration contains errors a dialog appears with a warning.

Restoring the ConfigurationClick Reset, to restore the last save configuration in the tables.

Selecting a Source

Digital Input FunctionThe Digital input function forwards the status of the digital input to the digital output:• The digital output switches to the ON status if the digital input switches to the ON status.

• The digital output switches to the OFF status if the digital input switches to the OFF status.Digital inputs of all devices in the source system are offered as a binary input, regardless of their parameteriza-tion:• PAC4200: At least two digital inputs. Up to 10 digital inputs if 2 DI/DO modules are fitted.

• PAC3200: 1 digital input

• PAC3100: 2 digital inputs

• Generic Modbus device: 10 digital inputs

Selection Tree for Digital InputsUse a filtered view of the project tree to select the source. Click the Digital input value in the Functioncolumn to open the Selection tree for digital inputs window.

4.19.4

Configuration4.19 Reaction Plans

powermanager, , Commissioning Manual 93E50417-H1040-C612-A2, Edition 04.2016

Page 94: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_SelectionTree_BinaryInput, 2, en_US]

Figure 4-38 Selection Tree for Digital Inputs Window

Click OK to transfer the selected source to the reaction plans table and close the window.

Alert FunctionDepending on the alert triggered by a specific event, the Alert function switches the digital output.You can select the high and low limits of the analog values that have an alert configuration, regardless ofwhether the alert itself is activated.Alerts that are not activated are shown in gray in the list of reaction plans. They do not trigger a reaction plan.

Selection Tree for AlertsUse a filtered view of the project tree to select the source. Click the Alert value in the Function column to openthe Selection tree for alerts window.

Configuration4.19 Reaction Plans

94 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 95: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_SelectionTree_Alerts, 2, en_US]

Figure 4-39 Selection Tree for Alerts Window

Click OK to transfer the selected source to the reactions plan table and close the window.

Load Monitoring FunctionThe Load monitoring function switches the digital output depending on the switching recommendation of theassigned load monitor.The following switching bits represent the switching recommendation:• switchNo

The SwitchNo bit is set when the correction power is within the configured limit curve.

• switchOffThe switchOff bit is set when load has to be deactivated to avoid exceeding the setpoint in the tariffinterval and the correction power lies outside the limit curve.

Configuration4.19 Reaction Plans

powermanager, , Commissioning Manual 95E50417-H1040-C612-A2, Edition 04.2016

Page 96: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• switchOnThe switchOn bit is set when load is connected without exceeding the setpoint in the tariff interval andthe correction power lies within the limit curve.

Selection Tree for Load MonitoringUse a filtered view of the project tree to select the load monitoring function and switching bits. Click the Loadmonitoring value in the Function column to open the Selection tree for load monitoring window.

[sc_SelectionTree_LM, 2, en_US]

Figure 4-40 Selection Tree for Load Monitoring Window

Deleting Devices

Before deleting a device from the system, check whether any of its elements is used as a source or target in areaction plan.If an element is being used, then the system displays a message with instructions to resolve the issue.

4.19.5

Configuration4.19 Reaction Plans

96 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 97: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

You cannot delete the device until the corresponding reaction plans have been deleted.

Configuration4.19 Reaction Plans

powermanager, , Commissioning Manual 97E50417-H1040-C612-A2, Edition 04.2016

Page 98: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Filter Administration

Overview of Filter Administration

You can use filters to restrict the scope of the measured quantities, displayed in the base panel, to individualviews.Some examples of filtering are:• Filtering current values of all devices belonging to a specific sector

• Filtering voltage values supplied by all devices of the PAC4200 type

• Filtering total active power of all devices in the system with heating as part of their names

Using FiltersUser-defined filters are available at the area, sector, and project tree root level. The required filter can beselected from the filter list box in the base panel.

Filter Administration and ConfigurationUse filter administration to define new filters or to modify existing ones. Right-click the project tree root toview the filter configuration options.

Using Filters

To apply a user-defined filter:²

In the tool bar, click to open the Standard view of the base panel.

² In the project tree, select the level (root, area, or sector) to which you want to apply the filter.

² Select the required filter from the filter list box.The base panel shows the filtered datapoints of the selected project tree branch.The system remembers the assignment of the project tree branch and filter. Use No filter from the filter listbox to return to the unfiltered overall view.

iiNOTEIf the filter list box shows only the default and No filter filters, then it implies that no user-defined filtersare created.In this case, create a filter list.

Managing Filters

Opening Filter AdministrationRight-click the project tree root and then click Filter administration to open the filter administration view.

4.20

4.20.1

4.20.2

4.20.3

Configuration4.20 Filter Administration

98 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 99: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_FilterAdmin_Open, 3, en_US]

Figure 4-41 Selecting Filter Administration

Filter Administration View

[sc_FilterAdmin_View, 2, en_US]

Figure 4-42 Filter Administration View

Configuration4.20 Filter Administration

powermanager, , Commissioning Manual 99E50417-H1040-C612-A2, Edition 04.2016

Page 100: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Filter administration is split into the following three areas:• Basic Functions

The area at the top provides four basic functions:–

– Create a filter

– – Delete a filter

– – Save filter settings

– – Rename a filter

• Previous SettingsThe previous settings area shows the settings of the currently selected filter.

• Configuration ElementsThe Filter mode and Filter definition areas enable you to configure the filters.

Creating a New FilterTo create a filter:²

Click .

² Name the filter and click Accept.The filter name appears in the list box at the top of the filter administration view.

² Configure the filter in the configuration elements area.

²Click to save the filter.You can change the filter name later to adapt it to a different language.

Modifying an Existing FilterTo modify an existing filter:² Select the filter you want to edit from the list box at the top of the filter administration view.

² Change the filter configuration in the configuration elements area.

²Click to save the filter.

Deleting a Filter

² Select the filter you want to delete from the list box at the top of the filter administration view.

²Click to delete the selected filter.

The selected filter is deleted.

iiNOTEYou cannot delete the default filter.

Configuration4.20 Filter Administration

100 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 101: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Renaming a FilterTo rename a filter:² Select the filter you want to rename from the list box at the top of the filter administration view.

²Click to rename the selected filter.

² Enter the new name in the dialog.The dialog shows several languages for selection. Change the name in the required target language.

Configuring Filters

Types of DefinitionsFilter administration offers two methods of configuring filter settings:• Select selection criteria from predefined lists.

To do this, select the list option.

• Definition of text sequences that conduct a full text search.To do this, select the wildcard option.

AreasThe filter conditions can be applied to:• Area

Areas that are created in the project tree.

• Device typeDevice types.

• Device nameDevices that are created in the project tree.

• SectorsSectors that are created in the project tree.

• Measured valueAll retrievable measured values.

Five tabs denote the objects to which filter conditions are applied. Each tab represents one object.If you select the list option, the tabs provide area-specific lists for selection.A text sequence of the wildcard filter definition type is effective in the area in which it has been created.

Language DependenceIf you use the list option, the filter results are identical for all languages in the project. The system saves thecompiled filter based on the internal designation.Wildcards refer to the designations in the current language. When you use wildcards, the same filter indifferent languages return different results.

List Filter ModeAssigning Selection CriteriaTo adopt selection criteria for a filter, move the values from the available groups and available measure pointsboxes to the selected box.• Selecting a measured variable for the filter

Select a measured variable from the available measure points box and click to move it to theselected box.

4.20.4

Configuration4.20 Filter Administration

powermanager, , Commissioning Manual 101E50417-H1040-C612-A2, Edition 04.2016

Page 102: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Selecting all the measured variables for the filter

Click to move all the measured variables to the selected box.

• Removing a measured variable from the filter

Select a measured variable from the selected box and click to move it to the available measurepoints box.

• Removing all measured variables from the filter

Click to remove all measured variables from the selected box.

Wildcards Filter ModeThe wildcards mode allows you to define text sequences that filter the display as full text search criteria.The text sequences can contain wildcards.

[sc_Filter_WildcardsMode, 1, en_US]

Figure 4-43 Power Peak: Wild Card Filter Mode

Table 4-3 Wildcards

? Any character* One or several of any characters

Example:The text sequence PAC* entered in the advance selection of the Device tab limits displays only the devicesfrom the PAC series.

Configuration4.20 Filter Administration

102 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 103: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Empty FilterNo filter is active when the Pattern box is blank or contains the test sequence *.The configured filters are displayed immediately in the Previous settings area.

Configuration4.20 Filter Administration

powermanager, , Commissioning Manual 103E50417-H1040-C612-A2, Edition 04.2016

Page 104: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Power Peak Analysis

Overview of Power Peak Analysis

powermanager contains a report generator for determination of power peaks within a specified time range.You can evaluate the following values using the report generator:• Power demand values of the PAC device types. The time stamp of the power demand values is at the start

of the period.

• Parameterized power demand values of generic Modbus devices.ReportYou receive the result of analysis in the form of a tabular report in the csv file format. You can open, print, andedit the report file with Microsoft Excel.powermanager issues the report in the language that you set.

[sc_Powerpeak_Report, 1, en_US]

Figure 4-44 Power Peak Analysis Report

Opening the Power Peaks Window

To open the Power Peaks window:² In the menu bar click Tools > Power peak analysis.The Power Peaks window opens and displays the last saved configuration.

4.21

4.21.1

4.21.2

Configuration4.21 Power Peak Analysis

104 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 105: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Powerpeaks_Window, 2, en_US]

Figure 4-45 Power Peaks Window

Creating a Report

To create a report:² Open the Power Peaks window.

² Modify the configuration data to suit your requirements.

² In the Target Path field, specify the directory where you want to save the report.

² Click Create Report to start the report creation.Wait until the progress bar goes up to 100 % and then goes back to 0 %.Save the modified configuration if you wish to keep it.

Configuring Power Peaks

ScopeConfiguring power peak analysis comprises:• Selecting datapoints

• Defining the limit of the datapoint

• Narrowing down the query period

4.21.3

4.21.4

Configuration4.21 Power Peak Analysis

powermanager, , Commissioning Manual 105E50417-H1040-C612-A2, Edition 04.2016

Page 106: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Displaying power peaks in the report

• Report file name and path

Selecting DatapointsThe Measured values table lists the datapoints that are included in the analysis and are printed in the report.The Meas. Value Selection area under the Measured value table provides the following functions for editingthe table entries:• Including datapoints in the Measured value table.

• Deleting a datapoint from the Measured value table.

• Changing the limit of a datapoint or limits of all datapoints.

Including a Datapoint in the Measured Value TableTo include a datapoint in the Measured values table:²

Click to open the Value Selection dialog.

² In the Value Selection dialog, select the required datapoint from the selection tree.

²Click .

² Specify the threshold of the datapoint in the Limit field.Violation of the threshold is considered to be a power peak.

² Select Single Limit option.

²Click .

The datapoint with its assigned threshold is now visible in the Measured Value table.

Deleting a Datapoint from the Measured Value Table

iiNOTEThe system deletes the selected datapoint without prompting for confirmation.

To delete a datapoint from the Measured value table:² Select the datapoint that you want to delete.

²Click to delete the selected datapoint.

Deleting All Datapoints from the Measured Value Table

iiNOTEThe system deletes the selected datapoint without prompting for confirmation.

To delete all datapoints from the Measured value table:²

Click to delete all datapoints from the Measured value table.

Editing a Datapoint from the Measured Value TableTo edit a datapoint from the Measured value table:

Configuration4.21 Power Peak Analysis

106 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 107: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Select the datapoint that you want to edit.The data for the selected datapoint becomes visible in the Meas. Value Selection area.

² Make the required changes to the datapoint details.

² Select Single Limit option.

²Click to save the changes.

Editing Single/General Limit

Selecting the Single Limit or General Limit option changes the behavior of the button.² Select the Single Limit option to transfer the current values of the Measured value and Limit fields to the

Measured value table while retaining the existing entries in the table.- or -

² Select the General Limit option to transfer the current values of the Measured value and Limit fields tothe Measured value table and overwriting the thresholds of the existing entries with the new thresholdvalue.

iiNOTETo cancel this step, reedit all limits already parameterized.

Query PeriodThe Start time and End time fields in the Query parameters area narrow down the query period.A number of previously defined calendar periods are available for selection.

Open intervals:• Today

• This week

• This month

• This yearClosed intervals:

• Yesterday

• Last week

• Last month

• Last year

• Last 24 hours

• Last 3 daysAny periods:

• Any day

• Any periodA selected previously defined period can be modified to suit requirements.To define a query period:² Click Set query time.

² Select one of the previously defined periods in the dialog.- or -

² Define an individual period in the Start time and End time fields.

Configuration4.21 Power Peak Analysis

powermanager, , Commissioning Manual 107E50417-H1040-C612-A2, Edition 04.2016

Page 108: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

²Click to save the changes.

Displaying Power Peaks in the ReportTo display the power peaks in the report:² Select Show percentage deviation.

The system calculates and prints the percentage deviation of the power peak from the parameterizedlimit value.

² In the Number area, the All option is selected by default. Keep this option selected if you want to displayall the power peaks per measuring point in the report.- or -

² Select Input if you want to display a set number of power peaks per measuring point in the report.Specify the limit in the field beside the Input option.If the number of power peaks exceed the set value, then an annotation is inserted in the report.

Report Filename and PathFilenamepowermanager generates the power peak analysis report in the csv file format.The format of the file name is:Peak_Data_<YYYY>_<MM>_<DD>_<HH>_<MM>_<SS>.csvHere, <YYYY>, <MM>, and <DD> denote year, month, and date respectively. They indicate the date when thereport generation started.<HH>, <MM>, and <SS> denote the hour, minute, and second respectively. They indicate the time when thereport generation started.DirectoryTo select the directory where the report is saved:² Specify the directory in the Target path field.

By default, the Target path field contains the address of the last set directory.If you want to save the report to other directory, overwrite the path to suit your requirements.The lowermost directory must end with a directory delimiter. For example, ../data/ instead of ../data.

Default DirectoryIf the specified directory does not exist, powermanager saves the report in the default directory.The \data directory underneath the project directory is the default directory.The default directory is set by default when the application is installed.Any directory deviating from the default directory is stored on the client system and not throughout thesystem.

Saving the Power Peaks Configuration

iiNOTEUnsaved configuration changes are lost when you close the Power Peaks window.

² Click to save the power peaks configuration.

4.21.5

Configuration4.21 Power Peak Analysis

108 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 109: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Calculating Power Peaks

Scopepowermanager calculates power peaks based on archived data.A power peak consists of one or more periods. It begins with the end period of the first measured value thatexceeds the defined threshold and ends with the end period of the last measured value that exceeds thedefined threshold.To determine the end of the period, the period length at the time of the period start is determined and isadded to it. If several measured values exceed the limit in succession, the highest violation within the timerange is specified as the power peak. The end period of the value is always specified in the report as the timefor a measured value.

Percentage DeviationThe percentage deviation from the limit is calculated based on:((Value of the highest violation) – (Limit)) / (Limit) * 100The percentage deviation is rounded to integral percentages without decimal places.

Example of Percentage DeviationConsider a scenario where the defined limit is 2 kW and the query period is from:01.01.2010 10:00 to 01.01.2010 11:00

Table 4-4 Measured Values

Time stamp (period start) Time range [min] Value [W]01.01.2010 10:00 h 15 195701.01.2010 10:15 h 15 211001.01.2010 10:30 h 15 221501.01.2010 10:45 h 15 201301.01.2010 11:00 h 15 957

Based on the values in the preceding table, the following violations have occurred:01.01.2010 10:30 h to 01.01.2010 11:00 hValue: 2215 WTherefore, the percentage of deviation is:( 2215 W – 2000 W ) / ( 2000 W ) * 100 % = 11 %

Closing the Power Peak Window

To close the Power Peaks window:² Click to save the configuration changes.

²Click to close the Power Peaks window.

iiNOTEUnsaved configuration changes are lost when you close the Power Peaks window.

4.21.6

4.21.7

Configuration4.21 Power Peak Analysis

powermanager, , Commissioning Manual 109E50417-H1040-C612-A2, Edition 04.2016

Page 110: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

110 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 111: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

KPI View

In this view you can generate the Key Performance Indicators (KPI) of any building or industry. The viewconsists of a tree where you can add KPIs. KPIs can be calculated according to time ranges like day, week,month, and year. A cluster of KPIs is a group. Group1 is available by default. A maximum of 9 KPIs can becreated in a group.

5

powermanager, , Commissioning Manual 111E50417-H1040-C612-A2, Edition 04.2016

Page 112: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

112 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 113: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Basic Report

6.1 Report View 1146.2 Tabs in Report View 115

6

powermanager, , Commissioning Manual 113E50417-H1040-C612-A2, Edition 04.2016

Page 114: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Report ViewThe Report view is used to create, view, and configure reports and report templates. It consists of 4 tabs,Create report, View report, Template management, and Schedule.The reports created can be saved to an external server via a web client.

iiNOTEReport license is not required for working with Report view.

[sc_Report_View, 1, en_US]

6.1

Basic Report6.1 Report View

114 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 115: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Tabs in Report ViewCreate report

The Create report tab displays all the available report templates in the form of a template tree. Each reporttemplate can be configured to create a different report. Reports can be scheduled to be created in regularintervals of time.

View reportsThe View reports tab displays the type, file name, and the last modified time of all the created reports.

Template managementThe Template management tab displays the following types of report templates, which can be created:Types of Reports, which can be created:• Absolute energy

• Cost center allocation

• Energy analysis

• Load duration curve

• Load variance analysis

• Standard

• Total energy

SettingsThe Settings tab is used to configure the medium configuration, cost center configuration, and display theschedule of the reports to be generated.

6.2

Basic Report6.2 Tabs in Report View

powermanager, , Commissioning Manual 115E50417-H1040-C612-A2, Edition 04.2016

Page 116: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

116 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 117: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Advanced Report

7.1 Overview of Reporting 1187.2 Prerequisites 1197.3 powermanager Report Window 1207.4 Types of Reports 1287.5 Preparing the Cost Center Report 1387.6 Datapoints 145

7

powermanager, , Commissioning Manual 117E50417-H1040-C612-A2, Edition 04.2016

Page 118: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Overview of Reportingpowermanager enables you to generate reports based on the data from the process database.The powermanager reports generator uses predefined Microsoft Excel templates to display the reports. Thedata is displayed in Microsoft Excel as raw data.Report creation can be manual, semiautomatic, or fully automatic. Fully automatic reports creation is time-driven and does not require user intervention.

Getting StartedTo create new reports:• Determine the type of reports that are available in powermanager.

• Prepare the cost center report.– Create one or more media.– Create one or more tariff sets.– Create one or more cost centers.

• Create report templates.In the template, define the type of data that is logged in the report.

• Create the reports based on the defined template.Do the first-time report creation manually. You can make the report creation semiautomatic / fully auto-matic for subsequent reports.

7.1

Advanced Report7.1 Overview of Reporting

118 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 119: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

PrerequisitesEnsure that you meet the following prerequisites before starting with the reporting functionality of power-manager.

Setting Microsoft Excel Macro Security LevelTo configure the Microsoft Excel macro security level:• Open Microsoft Excel.

For Excel 2007, click > Excel Options.For Excel 2010/2013, click the File tab, and then click Options.The Excel Options window opens.

• In the Excel Options window, click Trust Center.The Trust Center page opens.

• On the Trust Center page, click Trust Center Settings....The Trust Center window opens.

• In the Trust Center window, click Macro Settings.

• On the Macro Settings page, select Enable all macros.

• Click OK to close the Trust Center window.

• Click OK to close the Excel Options window.

Permanently Running ServerEnsure that you have a server that runs permanently to ensure that automatic reports generation is possible.Install Microsoft Excel on the server.Open Microsoft Excel.

7.2

Advanced Report7.2 Prerequisites

powermanager, , Commissioning Manual 119E50417-H1040-C612-A2, Edition 04.2016

Page 120: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

powermanager Report Window

Opening the powermanager Report Window

To open the powermanager report window:² In the menu bar, click Tools > Report .Microsoft Excel opens in the powermanager Report window.

[sc_ReportWindow, 1, en_US]

Figure 7-1 powermanager Report Window

The powermanager report window consists of the following components:Component DescriptionTemplateNew Click New to create a report template.Open Click Open to open an existing template for editing.ReportsNew Click New to create a report based on an existing template.Open Click Open to open an existing report.

The default file name of the Microsoft Excel file in powermanager report window is Report.xls.To return to the Report.xls window when multiple windows are open:• Click the View tab, and click Switch Windows > Report.xls.

7.3

7.3.1

Advanced Report7.3 powermanager Report Window

120 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 121: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Templates

Overview of TemplatesThe predefined powermanager standard report templates are Excel templates. Enter the operating data inthese Excel templates to customize them according to your specifications.Define the following in the report template:• Datapoints

• Report type

• Unit in the report, which deviates from the unit of the queried datapoints

• Unit conversion

• The cost center for the cost center report and the mediumThe created report template in Excel is stored as an XLTM template.

Creating a New TemplateTo create a template:² Click New under Template area.

- or -

² Click the Add-Ins tab, and click Template > New.

² In the Report format window, select the report format.

² Click OK.The Report types window opens.

² Select one or more report types.For more information on report types, see 7.4.2 Report Types.

² Click OK.Excel opens the standard template of the selected report format.

² Add the required datapoints to the template. For more information on adding datapoints, see7.6.1 Editing Datapoints in the Report Template.

² Click to save the template.

- or -

²

For Microsoft Excel 2007, click , and click File > Save.For Microsoft Excel 2010/2013, click the File tab and then click Save.Ensure that you do not use the Save As option to save the template as this procedure saves the templateas an Excel table.

iiNOTEEnsure that the name of the template does not end with a number.

Editing an Existing TemplateTo edit an existing template:² Click Open under Template area.

- or -

7.3.2

Advanced Report7.3 powermanager Report Window

powermanager, , Commissioning Manual 121E50417-H1040-C612-A2, Edition 04.2016

Page 122: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click the Add-Ins tab, and click Template > Open.The Template option in the menu bar is available in all windows that you open from the report generatorwindow.The Select a file window opens.

² Select and open the template that you want to edit.

² In the Report format window, select the report format.

² Click OK.The Report types window opens.

² Select one or more report types.For more information on report types, see 7.4.2 Report Types.

² Click OK.Excel opens the standard template of the selected report format.

² Add the required datapoints to the template. For more information on adding datapoints, see7.6.1 Editing Datapoints in the Report Template.

² Click to save the template.

- or -

²

For Microsoft Excel 2007, click , and click File > Save.For Microsoft Excel 2010/2013, click the File tab and then click Save.Ensure that you do not use the Save As option to save the template as this procedure saves the templateas an Excel table.

iiNOTEEnsure that the name of the template does not end with a number.

Reports

This section describes manual initiation of report creation.Select the following to control report creation:• Report template

• Report type

• Creation periodBy default, the creation period is the period defined in the report type. You can individually overwrite both thestart time and the period.

Creating a ReportTo create a report:² Click New under Report area.

- or -

² Click the Add-Ins tab, and click Reports > New.

² In the dialog that opens, select the template for the report.

7.3.3

Advanced Report7.3 powermanager Report Window

122 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 123: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² In the Time period for the report window, specify the report type and time range for the report.Depending on the selected report type, the system assigns a default time range to the report.You can modify this time range to suit your requirements.

² Click OK.The report generator creates the report. The report opens in a new window in Excel.

²

For Microsoft Excel 2007, click , and click File > Save.For Microsoft Excel 2010/2013, click the File tab and then click Save.For more information on saving reports, see Saving Reports.

Saving ReportsThe powermanager standard storage system is uniform for all users.The default storage location for all the generated reports is:<Project_name>\data\xls_report\Report\When you save a report for the first time, the system creates a subdirectory under the preceding path. Thename of the subdirectory is the same as that of the report type.Subsequent save commands open the designated folder for the report.Additionally, you can save reports in any folders independent of the default storage path.The powermanager report generator names the reports based on the following format:• <template_name>\YYYYMMDD.xlsmHere, YYYY, MM, and DD stand for year, month, and day respectively. The date displayed is the generationdate of the report.

Opening an Existing ReportTo open an existing report:² Click Open under Report area.

- or -

² Click the Add-Ins tab, and click Reports > Open.The Select a file dialog opens.

² In the Select a file dialog, navigate to the relevant subdirectory and select the report that you want toopen.

² Click Open.

Quick Selection – Semiautomatic Report Creation

Use the quick selection feature to partially automate the report creation.Initiate the report generation.The system defines the template, report type, and report period.

Creating a Quick SelectionA quick selection saves the information on the template, report type, and report period for reuse.To create a quick selection:² Click the Add-Ins tab, and click Report > Quick Selection.

The Reports option in the menu bar is available in all windows that you open from the report generatorwindow.The Quick Selection window opens.

7.3.4

Advanced Report7.3 powermanager Report Window

powermanager, , Commissioning Manual 123E50417-H1040-C612-A2, Edition 04.2016

Page 124: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

²In the Quick Selection window, click .The Quick Selection dialog opens.

[sc_QuickSelection_Dialog, 1, en_US]

Figure 7-2 Quick Selection

² Enter the following information in the Quick Selection dialog:Label: Quick selection nameTemplate: Default template that is applied to the reports generated using this quick selectionReport Type: Default report type that is applied to the reports generated using this quick selectionIf the template does not contain the selected report type, the report generator sends the following errormessage: No report types defined in the template.In this case, include the report type in the template before creating the quick selection or select anotherreport type.Print: Select this option to send the report to the default printer selected assigned to the system. If youselect this option, the system does not prompt for confirmation.Save: Select this option to save the report without being prompted for confirmation.For more information on saving reports, see Saving Reports.Close: Select this option if you do not want to view the report after creation. The report is saved in theselected location.Time period: Under Time period, select Last period if you want to generate report for the previousmonth or previous day.Select Current period if you want to generate the report for the current month or current day.

² Click OK.The quick selection template is available for selection in the Quick selection field of the powermanager reportwindow.

Creating a Report Using Quick SelectionThe Quick Selection field in the home window of the report generator lists all available templates for quickselection.For more information on creating a new quick selection template, see Creating a Quick Selection in thepreceding section.To create a report using quick selection:² In the Quick Selection field, double-click the template you want to use.

- or -

Advanced Report7.3 powermanager Report Window

124 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 125: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Select a quick selection template and click Create report.The report generator creates the report without prompting for confirmation. Depending on the quick selectionsettings, the report is saved, printed, or displayed in the Excel window.

Schedule – Automatic Report Creation

You can automate report generation using the Schedule feature. An active schedule creates reports periodi-cally. For example, every morning, the daily report for the previous day, and so on.

Viewing the List of Active SchedulesClick the Add-Ins tab, and click Report > Schedule to view the list of active schedules in the Schedulewindow.

[sc_ScheduleWindow, 1, en_US]

Figure 7-3 Schedule Window

The lamp icon that precedes the schedule name indicates the status of the schedule:• Green lamp:

Schedule is active. Reports are created based on the time range given in the schedule.

• White lamp:Schedule is switched off.

• Red lamp:An error occurred during the report generation.

• Yellow lamp: The reports are not generated because the powermanager Report feature is not runningand these reports were skipped when powermanager Report feaure was last switched on.

Creating a Schedule

² Click the Add-Ins tab, and click Report > Schedule.The Schedule window opens.

²In the Quick Selection window, click .The Schedule dialog opens.

7.3.5

Advanced Report7.3 powermanager Report Window

powermanager, , Commissioning Manual 125E50417-H1040-C612-A2, Edition 04.2016

Page 126: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_ScheduleDialog, 2, en_US]

Figure 7-4 Schedule Dialog

Advanced Report7.3 powermanager Report Window

126 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 127: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Enter the following information in the Schedule dialog:Label: Schedule nameTemplate: Default template that is applied to the reports generated using the scheduleReport Type: Default report type that is applied to the reports generated using the scheduleIf the template does not contain the selected report type, the report generator sends the following errormessage: No report types defined in the template.In this case, include the report type in the template before creating the schedule or select another reporttype.Interval: Interval between each report generationFor example, select 1 month(s) to generate the report monthly.Next call: Date and time when the report generation starts at the end of each intervalActive: Select Active if you want start the schedule immediately after creation.Print: Select this option to send the report to the default printer selected assigned to the system. If youselect this option, the system does not prompt for confirmation.Save: Select this option to save the report without being prompted for confirmation.For more information on saving reports, see Saving Reports.HTML export: Select this option if you want to save the report in the HTML format.The HTML report is saved in the folder:C:\Siemens\SENTRON\powermanagerV3.3\data\xls_reportMailing list: Select this option if you want to email the report to a particular mailing list immediatelyafter the report creation.After you select this option, select the mailing list from the list box below.In the powermanager report window, click Report > Mailing list to create a mailing list.Time period: Under Time period, select Last period if you want to generate report for the previousmonth or previous day.Select Current period if you want to generate the report for the current month or current day.Specify the path to save the report.

² Click OK to close the Schedule dialog.The new schedule is listed in the Schedule window.

² Click OK to close the Schedule window.

Closing the powermanager Report Window

To close the powermanager report window:² Save and close all the open report windows except Report.xls.

² Close Report.xls.

iiNOTEIf you try to close Report.xls without closing all the other report windows, you get the following message:The project cannot be terminated as project files are still open!

7.3.6

Advanced Report7.3 powermanager Report Window

powermanager, , Commissioning Manual 127E50417-H1040-C612-A2, Edition 04.2016

Page 128: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Types of Reports

Overview of Types of Reports

This section contains the different type of reports that can be generated using powermanager.powermanager generates different report types with varying formats.Report FormatThe report format contains information about the measured variables that can be selected. For example,demand values or energy counters.It also contains definitions for the display format. For example, display report data as a characteristic curve orit recycles data.Report TypesThe report type determines the time interval and time range displayed on the report.Default report formats and report types are already defined in powermanager.

Report Types

Overview of Report TypesThe report type defines the interval and the period of the data export. For example, cumulation of the data in15-minute intervals throughout the day.

Report Types WindowThe Report types dialog appears after selection of the report format. It shows all report types that areassigned to the selected report format and allows narrowing down to certain types. This restriction is effectivewhen the report is created manually.

[sc_ReportTypes, 1, en_US]

Figure 7-5 Report Types Window

7.4

7.4.1

7.4.2

Advanced Report7.4 Types of Reports

128 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 129: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Existing report typesThe Existing report types box lists all the existing report types.

• Report types for this templateThe Report types for this template box lists all the report types that are used when creating a report.

• Use the < and > buttons to move individual report types from one box to another.

• Use the << and >> buttons to move all the available report types from one box to another.

• The Min color and Max color boxes define the color coding of the extreme values in the report. Click thebuttons to change the color.

Cost Center Report

Overview of Cost Center ReportThe cost center report represents consumption and the correlated costs per medium, grouped according tocost centers.

Report TemplateCost Center report is generated using the following report template:• CostTemplate.XLTMFor more information on templates, see 7.3.2 Templates.

Report TypesBy default, the Cost Center report contains the following report types:Name Interval Period Start of the PeriodDaily report Hour Day Previous day, 00:00:00 hMonthly report Day Month First day of the month, 00:00:00 h

Period and Start of the Period have default values. You can define the report period individually when youcreate a report.

OutputThe report contains three sheets:• Std

• Cost center report diagram

• Cost center report table

Std SheetThe Std sheet contains the raw data of the Cost Center report with values displayed for fixed intervals. Thissheet also displays the total value for all intervals.

7.4.3

Advanced Report7.4 Types of Reports

powermanager, , Commissioning Manual 129E50417-H1040-C612-A2, Edition 04.2016

Page 130: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_CostCenter_Report, 1, en_US]

Figure 7-6 Cost Center Report with Raw Data Displayed for Hourly Intervals During a Day

Cost Center Report Diagram SheetThe Cost Center Report Diagram sheet shows the media assigned to each Cost Center.It also shows the consumption and cost per medium in the selected time interval.

Advanced Report7.4 Types of Reports

130 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 131: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_CostCenter_Diagram, 1, en_US]

Figure 7-7 Cost Center Report Diagram

In the above figure, the top chart shows the consumption values for the media and the bottom chart showsthe cost per medium for the devices.For each cost center, a maximum of 10 media can be displayed according to the assignment of a maximum of10 tariff sets in the cost center definition.The columns for consumption and costs of a medium have the same color. Different media are color-coded.The legend explains the color assignments.

Advanced Report7.4 Types of Reports

powermanager, , Commissioning Manual 131E50417-H1040-C612-A2, Edition 04.2016

Page 132: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Cost Center Report Table SheetThe figure below shows the following values of the reporting period:• Overall consumption per medium and consumption per cost center.

• Total costs per medium and costs per cost center.

• Overall consumption per medium across all cost centers.

• Total costs per medium across all cost centers.

• Total costs per cost center.

• Total costs across all cost centers.

[sc_CostCenter_Sheet, 1, en_US]

Figure 7-8 Cost Center Report Table

iiNOTE

• An empty cell in the matrix indicates that no corresponding medium is assigned to the cost center.

• The total costs of a cost center result from the sum of the costs for each medium. The values of thecosts per medium are added up without checking the unit or the currency of the value.

Measuring Point Comparison

Overview of Measuring Point ComparisonThe measuring point comparison report shows the total consumption of different measuring points over aspecific period in a bar chart.

Report TemplateThe measuring point comparison report is generated using the following report template:• CompareValues.XLTM

Report TypesBy default, the measuring point comparison report contains the following report types:Name Interval Period Start of the PeriodComparison_15min_Day 15 minutes Day Previous day, 00:00:00 hComparison_15min_Month 15 minutes Month Current day of the previous month, 00:00:00 hComparison_Hours_Day Hour Day Previous day, 00:00:00 hComparison_Hours_Month Hour Month Current day of the previous month, 00:00:00 hComparison_Days_Month Day Month Current day of the previous month, 00:00:00 hComparison_Days_Year Day Year Current day of the previous year, 00:00:00 h

7.4.4

Advanced Report7.4 Types of Reports

132 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 133: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Period and Start of the Period have default values. You can define the report period individually when youcreate a report.The interval selected in the report type is irrelevant for the display in the diagram. It displays the total valuesover the period.The interval determines which data is used for the calculation.

OutputThe report contains two sheets:• Std

Raw data accumulated according to the report type

• Sum graph

Sum Graph Sheetpowermanager takes the unit for the vertical axis from the data point entered in column C of the reporttemplate. You can overwrite the unit when you define the report template.

[sc_MeasuringPointComparison, 1, en_US]

Figure 7-9 Measuring Point Comparison

Measured Value Comparison

Overview of Measured Value ComparisonThe Measured value comparison report shows the energy consumption per interval over the selected timerange.

7.4.5

Advanced Report7.4 Types of Reports

powermanager, , Commissioning Manual 133E50417-H1040-C612-A2, Edition 04.2016

Page 134: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

There are two types of comparisons done:• Comparison of the consumption values of several measuring points in the same time range.

• Comparison of the consumption values of the same data point.For example, comparison of one day with the previous day.

Up to 10 measuring points can be displayed in the diagram.

Report TemplateThe measuring value comparison report is generated using the following report template:• ComparisonValues.XLTM

Report TypesBy default, the measuring value comparison report contains the following report types:Name Interval Period Start of the PeriodComparison_15min_Day 15 minutes Day Previous day, 00:00:00 hComparison_15min_Month 15 minutes Month Current day of the previous month, 00:00:00 hComparison_Hours_Day Hour Day Previous day, 00:00:00 hComparison_Hours_Month Hour Month Current day of the previous month, 00:00:00 hComparison_Days_Month Day Month Current day of the previous month, 00:00:00 hComparison_Days_Year Day Year Current day of the previous year, 00:00:00 h

Period and Start of the Period have default values. You can define the report period individually when youcreate a report.

Offset for Period ComparisonThe time interval for data export can be varied based on the time ranges. The offset can be defined in theOffset box of the report template. The Insert measured value dialog contains a corresponding Offset box, inwhich you can insert the offset digit.Offset0 Period that is selected during report generation.1 One period later. For example, next day.2 ......

.

.

.-1 One period earlier. For example, previous day.-2 ......

.

.

.

Use offset to compare consumption values of the same device over several periods.For more information on setting offsets, see 7.6.3 Inserting Datapoints in the Energy Report and Other ReportTypes.

OutputThe report contains two sheets:• Std, raw data, values cumulated according to the report type

• Graph

Advanced Report7.4 Types of Reports

134 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 135: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Graph Sheet

[sc_MeasuredValueComparison, 1, en_US]

Figure 7-10 Measured Value Comparison, 15-minute Intervals During the Day

Duration Curve

Overview of Duration CurveThe duration curve indicates which power demand value is applied for how long in the selected period. Entriesare sorted in ascending order of the length of the selected period.

Report TemplateThe duration curve report is generated using the following report template:• ContinousLine.XLTM

Report TypesBy default, the duration curve report contains the following report types:Name Interval Period Start of the periodDaily duration curve (Daily_cl) Hour Day Previous day, 00:00:00 hMonthly duration curve(Monthly_cl)

Day Month First day of the previous month, 00:00:00 h

Yearly duration curve (Yearly_cl) Month Year First day of the current previous year's month,00:00:00

By default, the period and start of the period values are predefined. When creating the report, you can definethe report period individually.

7.4.6

Advanced Report7.4 Types of Reports

powermanager, , Commissioning Manual 135E50417-H1040-C612-A2, Edition 04.2016

Page 136: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OutputThe output contains two sheets:• Std, raw data, cumulated according to the report type

• Graphic

Graphic Sheet

[sc_DailyDurationCurve, 2, en_US]

Figure 7-11 Daily Duration Curve with Hourly Intervals

Standard Report

Overview of Standard ReportUse the standard report to query all raw data; both counted and general measured values.The standard installation contains no graphic display of data. Add the graphic display of data individually toMicrosoft Excel.

Report TemplateThe standard report is generated using the following report template:• StdTemplate.XLTM

Report TypesBy default, the standard report contains the following report types:Name Interval Period Start of the PeriodDaily report Hour Day Previous day, 00:00:00 h

7.4.7

Advanced Report7.4 Types of Reports

136 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 137: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Name Interval Period Start of the PeriodMonthly report Day Month First day of the month, 00:00:00 h

By default, the period and start of the period values are predefined. When creating the report, you can definethe report period individually.

Energy Report

Overview of Energy ReportUse the energy report to export the energy or power demand values.Energy report exports only the raw data without graphical processing.

Report TemplateThe energy report is generated using the following report template:• EnergyReport.XLTM

Report TypesBy default, the energy report contains the following report types:Name Interval Period Start of the PeriodDaily report Hour Day Previous day, 00:00:00 hMonthly report Day Month First day of the month, 00:00:00 h

By default, the period and start of the period values are predefined. When creating the report, you can definethe report period individually.

7.4.8

Advanced Report7.4 Types of Reports

powermanager, , Commissioning Manual 137E50417-H1040-C612-A2, Edition 04.2016

Page 138: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Preparing the Cost Center Report

Media

Overview of MediaMedia are used only in the cost center report. Create at least one medium in the system to create a tariff set, acost center, and the cost center report.powermanager uses the term medium for a material or energy type with an assigned unit. For example, elec-tricity measured in kWh or water consumption measured in m3.There are no restrictions on defining the medium. Therefore, non-metric units can also be defined.A medium that is used in a tariff set cannot be deleted.

iiNOTEYou can select the unit of the medium independently of the unit of the recorded measured variable. In thecost center report template, you can convert the unit of the datapoint to the unit of the medium. Forexample, m³ to kWh.

Creating a MediumTo create a medium:² Open the powermanager report window.

² Click the Add-Ins tab, and click Report > Configuration > Media.

² In the Password dialog, enter the password as erAdmin and click OK.The Medium window opens.

²In the Medium window, click .The Media dialog opens.

² In the Media dialog, enter the name and unit of the medium in the respective fields.

² Click OK.

Tariff Sets

Overview of Tariff SetsA tariff set is used to:• Assign one or several prices to a medium.

• Define which price is to apply on which days and at what time of the day.

• Specify the calendar period throughout which it is validUse tariff sets to define cost centers. You must have at least one tariff to create a cost center.PrerequisiteCreate at least one medium in the system to define a tariff set.For more information on creating a medium, see 7.5.1 Media.

Structure of a Tariff SetDivision into Subtariff SetsA tariff set contains up to 10 subtariff sets. Subtariff sets follow one another in chronological order. You canuse only one subtariff set at a time.Default Subtariff Set

7.5

7.5.1

7.5.2

Advanced Report7.5 Preparing the Cost Center Report

138 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 139: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

A tariff set contains at least one subtariff set. This subtariff set is named Default. You cannot delete thissubtariff set.powermanager applies the Default subtariff set to all the calendar periods, which are not covered by any othersubtariff sets.Additionally Defined Subtariff SetsYou can create new subtariff sets in addition to the Default subtariff set. You can delete the created subtariffsets if required. The validity period of the created subtariff sets cannot overlap. If the validity period of acreated subtariff set overlaps with the validity of the Default subtariff set, then the validity of the Defaultsubtariff set is overwritten.TariffsOne subtariff set contains up to 12 tariffs.You can assign hourly tariffs, tariffs for weekdays, Sundays, and holidays.• Ensure that the week from Monday to Sunday is occupied completely. Definition of holiday tariffs is

optional.

• You can distribute several tariffs over a day. The validity periods must not overlap and must cover thewhole day.

Creating a Tariff SetTo create a tariff set:² Open the powermanager report window.

² Click the Add-Ins tab, and click Report > Configuration > Tariff Sets.

² In the Password dialog, enter the password as erAdmin and click OK.The Tariff sets window opens.

[sc_TariffSets_Window, 1, en_US]

Figure 7-12 Tariff Sets Window

²In the Tariff sets window, click .The Tariff set Details window opens.

² Enter the tariff data in the Tariff set Details window.For the description of all the fields in the Tariff set Details window, see Tariff set Details Window.

² Click OK.

Advanced Report7.5 Preparing the Cost Center Report

powermanager, , Commissioning Manual 139E50417-H1040-C612-A2, Edition 04.2016

Page 140: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Tariff set Details WindowYou can define 12 tariffs per subtariff set. The tariffs are numbered from Tariff 1 through Tariff 12.

[sc_TariffSetsDetails_Window, 1, en_US]

Figure 7-13 Tariff Set Details

The Tariff sets Details window contains the following fields:• Name

Name of the tariff set.

• MediumMaterial or energy type with an assigned unit that is priced in the tariff.For more information, see 7.5.1 Media.

• CurrencyCurrency of cost recording.

Advanced Report7.5 Preparing the Cost Center Report

140 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 141: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Sub-tariff SetAll data within the Sub-tariff set area refers to the currently selected subtariff set.You can see the existing subtariff sets in the list box in this area.The Sub-tariff set area has the following components:– Copy

Click Copy to create a copy of the currently open subtariff set.– Edit

Click Edit to change the name of the subtariff set.– Delete

Click Delete to delete the subtariff set.powermanager does not prompt you for confirmation after you click Delete.

– Valid from, Valid toThe time range for which the subtariff set is valid.The system shows an error if the validity range of two subtariff sets overlap.The set the validity of the subtariff set to one day, set the validity from 00:00:00 h to 23:59:59 h.

• Times/CostsUnder the Times/Costs area, select a tariff to activate it.Specify the following information for each tariff that you select:– Specify the validity period for the tariff.

The validity period must be exact to the hour. If you select minutes and seconds along with thehour, then powermanager considers only the hour entry.By default, the validity period is set from 00:00:00 to 00:00:00, indicating a validity of a full day.

– Price for the consumption time.– The days of the weeks for which the tariff is applicable.

Select the Ho option if you want to apply the tariff to the holidays too.The system ensures that there are no time overlaps or errors. You receive an error message if thetotal daily period deviates from the 24-hour day or the defined weekdays do not result in a 7-dayweek.

• Holidays (Ho)You can list the public holidays in the Holidays box.For more information, see Defining Holidays in the following section.

Defining HolidaysTo define the holidays for the period that is recorded in the cost center report:² In the Holidays (Ho) area, click Add.

The Insert Date dialog opens.

² In the Insert Date dialog, enter the date of the holiday.

² Click OK.The specified date is added to the list of holidays.

Deleting a Tariff SetDelete a tariff set only if it is not assigned to a cost center.If you delete a tariff set that is assigned to some cost center, then the cost center configuration becomes erro-neous.To delete a tariff set:² Open the powermanager report window.

² Click the Add-Ins tab, and click Report > Configuration > Tariff Sets.

Advanced Report7.5 Preparing the Cost Center Report

powermanager, , Commissioning Manual 141E50417-H1040-C612-A2, Edition 04.2016

Page 142: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² In the Password dialog, enter the password as erAdmin and click OK.The Tariff sets window opens.

²In the Tariff sets window, select the tariff set that you want to delete and click .

² Click OK on the confirmation message.

Cost Centers

Overview of Cost CentersDefine a cost center to create the template of the standard cost center report.You need at least one tariff set to define a cost center.For more information on creating a tariff set, see 7.5.2 Tariff Sets.One cost center can be assigned up to 10 tariff sets.One cost center cannot be assigned multiple tariff sets containing the same medium. For example, you cannotassign two tariff sets with electricity medium.You can assign the same tariff set to multiple cost centers.A cost center is not bound to a specific template and is available for general use.

Creating a Cost CenterTo create a cost center:² Open the powermanager report window.

² Click the Add-Ins tab, and click Report > Configuration > Cost Centers.

² In the Password dialog, enter the password as erAdmin and click OK.The Cost Center window opens.

[sc_CostCenters_Window, 1, en_US]

Figure 7-14 Cost Center Window

²In the Cost Center window, click .The Cost Center dialog opens.If there are no tariff sets defined, then powermanager does not open the Cost Center dialog and showsan error message.

7.5.3

Advanced Report7.5 Preparing the Cost Center Report

142 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 143: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_CostCenterDialog, 1, en_US]

Figure 7-15 Cost Center Dialog

² Enter the following information in the Cost Center dialog:NameCost center nameEnsure that the cost center has a unique name.Tariff setYou can assign up to 10 tariff sets to one cost center.Select the tariff sets from the list box.

² Click OK.

Deleting a Cost Center

iiNOTEOnly delete a cost center if it is not used in a template.The delete command deletes the cost center immediately without prompting for confirmation. Templatesthat access the deleted cost center will no longer function.

To delete a cost center:² Open the powermanager report window.

² Click the Add-Ins tab, and click Report > Configuration > Cost Centers.

Advanced Report7.5 Preparing the Cost Center Report

powermanager, , Commissioning Manual 143E50417-H1040-C612-A2, Edition 04.2016

Page 144: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² In the Password dialog, enter the password as erAdmin and click OK.The Cost Center window opens.

² In the Cost Center window, select the cost center that you want to delete.

²Click to delete the selected cost center.

Advanced Report7.5 Preparing the Cost Center Report

144 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 145: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Datapoints

Editing Datapoints in the Report Template

OverviewThe procedure to add or edit a datapoint in a template is common for all templates:• Define the control data of a datapoint in Insert Measured Values window.

• The Insert Measured Values window makes the possible data available for selection in list fields.

• The report generator applies the data from the Insert Measured Values window to the Excel template.For more information on control data, see 7.6.2 Inserting Datapoints in the Cost Center Report and7.6.3 Inserting Datapoints in the Energy Report and Other Report Types.

Inserting Datapoints into a TemplateTo insert datapoints in a template:² Create the first datapoint in column C of the Excel template.

Mark any cell or any cell area in column C.Click the Add-Ins tab, and click Template > Insert DP.The Measured Value window opens.

² In the Measured Value window, enter the necessary information.For more information on Measured Value window, see 7.6.2 Inserting Datapoints in the Cost CenterReport and 7.6.3 Inserting Datapoints in the Energy Report and Other Report Types.

² Click OK.Excel applies the data from the Measure Value window to column C of the template.

² Enter datapoints description under the header row to improve readability.If you use Change DP, the boxes are automatically filled with the measuring point designation from thedatapoint name.

² Insert further datapoints in column D, E, and so on.

[sc_Comments.tiff, 1, en_US]

Editing a DatapointTo edit a datapoint:² Select the datapoint you want to edit.

² Click the Add-Ins tab, and click Template > Modify DP.The Measure Value window opens.

² In the Measure Value window, edit the required information.

² Click OK.Excel applies the updated data from the Measure Value window to the template.

7.6

7.6.1

Advanced Report7.6 Datapoints

powermanager, , Commissioning Manual 145E50417-H1040-C612-A2, Edition 04.2016

Page 146: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Deleting a DatapointTo delete a datapoint:² Select the datapoint you want to delete.

² Press DELETE on the keyboard.

Inserting Datapoints in the Cost Center Report

Insert Measured Value Window

[sc_InsertMeasureValue_Window, 1, en_US]

Figure 7-16 Insert Measured Value Window for Cost Center Report

7.6.2

Advanced Report7.6 Datapoints

146 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 147: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The Insert Measured Value window for Cost Center report contains the following fields:• Archive type

The Counter value is selected by default in the Archive Type list box. It limits the list of measured valuesto the consumption values.

• SystemIn a single system installation of powermanager, System1 is selected by default. You cannot change thisvalue.In a distributed system installation of powermanager, select any one of the distributed systems.

• Device TypeFrom the Device Type list box, select the device type of the device that supplies the data. This device isalso called the datapoint type (DPT).For more information on device types, see 7.6.4 Device Types.The Device List box at the bottom of the table lists the devices associated with the selected device type.

• Measured ValueFrom the Measured Value list box, select the measured value that the selected device supplies. Thismeasured value is also called the datapoint element (DPE).Its availability depends on the selected device type. The table in the following section lists the counters.

• Device name representationIn the Device name representation list box, select the name and additional information for the devicewhich appears in the Device list box.The Device name representation list box has the following options:– DP/Technical name

The device is listed under its internal device name. The name of the root precedes the device name.For example, System1:PAC4200_Anlage.

– AliasThe device is listed under its alias.Devices without assigned aliases do not appear in the list.

– Custom nameThe device is listed under its internal name.The name of the selected datapoint element and the suffix value are appended to the device name.For example, PAC4200_Anlage.counter.W_t1.value.

• FilterUse the filter feature to limit the number of devices in the Device list box to a subset.For more information on filters, see 7.6.5 Filters.

• Cost CenterFrom the Cost Center list box, select the cost center to which the counter demand values are assigned.

• MediumFrom the Medium list box, select the medium that is assigned to the cost center via the tariff set.If several media are assigned to the selected cost center, the list box offers the media for selection.

• Change unit in the reportThe Change unit in the report box shows the unit of the selected medium.

• Unit of the datapointThe Unit of the datapoint box shows the unit of the datapoint.

• DivisorThe Divisor box determines the conversion ratio for both the units. By default, the value in the Divisorbox is 1.ExampleTo convert from watt hours to kilowatt hours, enter the divisor value as 1000.

Advanced Report7.6 Datapoints

powermanager, , Commissioning Manual 147E50417-H1040-C612-A2, Edition 04.2016

Page 148: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Weighting (0-1)Proportional assignment of the counted consumption values for the selected cost center, expressed as adecimal factor.For example, the value 0.2 corresponds to a proportional share of 20%.

• Device listThe Device list box lists all devices created in the system that correspond to the selected device type andthe filter criterion. Select the desired device.

Energy Counters and Universal Counters

Table 7-1 Energy Counters and Universal Counters

Counter/device type GenericModbusDevice

PAC1500

PAC3100

PAC3200

PAC4200

PAC5100

PAC5200

VirtualCounter

P850 P855 3VA

counter.W_t1Active energy on-peaktariff

X X X X X X X X X

counter.W_t2Active energy off-peaktariff

X X

counter.Q_t1Reactive energy on-peaktariff

X X X X X

counter.Q_t2Reactive energy off-peaktariff

X X

counter.counterUniversal counter

X1 X X X

counter.counter_2Second universal counterof the PAC4200

X

counter.user_counter_1counter.user_counter_2 …counter.user_counter_1010 pulse counters of thePAC4200

X

Inserting Datapoints in the Energy Report and Other Report Types7.6.3

1 5 universal counters

Advanced Report7.6 Datapoints

148 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 149: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_InsertMeasuredValueWindow, 1, en_US]

Figure 7-17 Insert Measured Value Window

The Insert Measured Values window shows little variations for all the remaining report types.The Insert Measured Values window for measuring point comparison and measured value comparison reporttypes shows an additional button: Change unit in report.The Insert Measured Values window for the duration curve report type only allows you to select meanvalues.

Advanced Report7.6 Datapoints

powermanager, , Commissioning Manual 149E50417-H1040-C612-A2, Edition 04.2016

Page 150: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

The Insert Measured Values window has the following fields:• Archive type

Select one of the following options from the Archive type list box:– Counter

Select this option to limit the list of measured values to the consumption values.– HDB directly

Select this option to limit the list of measured values to the general measured values.Select the HDB directly option for the energy report to select power demand values.

• SystemIn a single system installation of powermanager, System1 is selected by default. You cannot change thisvalue.In a distributed system installation of powermanager, select any one of the distributed systems.

• Device TypeFrom the Device Type list box, select the device type of the device that supplies the data. This is alsocalled the datapoint type (DPT).For more information on device types, see 7.6.4 Device Types.The Device list box at the bottom of the table lists the devices associated with the selected device type.

• Measured ValueFrom the Measured Value list box, select the measured value that the selected device supplies. This isalso called the datapoint element (DPE).Its availability depends on the selected device type.The relevant datapoint elements for load profile are listed under value.04_powerPeriod.cumulated….The names and availability of the datapoint elements depend on the device type:– For PAC4200, add the act_period limitation to differentiate between current period and instanta-

neous period.For PAC4200, the current period indicates the last completed period.

– On the PAC3100 and PAC3200, select only the entries with the appended suffix _EM.For more information, refer to the following query under the Siemens Support Database, FAQ:“What must be observed to ensure that the time stamp and the power demand values of the devicesare correctly exported? ”Cumulated Power Values (power demand)Cumulated active power exportPAC4200: value.04_powerPeriod.cumulated_active_power_export_act_periodPAC3200, PAC3100: value.04_powerPeriod.cumulated_active_power_export_EMCumulated active power importPAC4200: value.04_powerPeriod.cumulated_active_power_import_act_periodPAC3200, PAC3100: value.04_powerPeriod.cumulated_active_power_import_EMCumulated apparent powerPAC4200: value.04_powerPeriod.cumulated_apparent_power_act_periodCumulated reactive power exportPAC4200: value.04_powerPeriod.cumulated_reactive_power_export_act_periodPAC3200, PAC3100: value.04_powerPeriod.cumulated_reactive_power_export_EMCumulated reactive power importPAC4200: value.04_powerPeriod.cumulated_reactive_power_import_act_periodPAC3200, PAC3100: value.04_powerPeriod.cumulated_reactive_power_import_EM

Advanced Report7.6 Datapoints

150 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 151: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Device name representationIn the Device name representation list box, select the name and additional information for the devicewhich appears in the Device list box.The Device name representation list box has the following options:– DP/Technical name

The device is listed under its internal device name. The name of the root precedes the device name.For example, System1:PAC4200_Anlage.

– AliasThe device is listed under its alias.Devices without assigned aliases do not appear in the list.

– Custom nameThe device is listed under its internal name.The name of the selected datapoint element and the suffix value are appended to the device name.For example, PAC4200_Anlage.counter.W_t1.value.

• DP functionThe DP function field has a predefined value.

• OffsetAdjust the value in the Offset box for the Measured value comparison report.For more information on using offset for Measured value comparison report, see 7.4.5 Measured ValueComparison.For other reports, do not change the predefined value 0.

• FilterUse the filter feature to limit the number of devices in the Device list box to a subset.For more information on filters, see 7.6.5 Filters.

• Automatic formattingSelect any one of the following options from the Automatic formatting list box to format the raw data inthe report output:– No formatting: Select this option if you do not want to format the exported data.– Only format: Select this option to assign values up to a fixed number of decimal places.– Format and unit: Select this option to assign values to a fixed number of decimal places. The unit of

the measured variable is also displayed.

[sc_DailyReport, 1, en_US]

• Min / max markerSelect this option to highlight the minimum and maximum values in the report.

Advanced Report7.6 Datapoints

powermanager, , Commissioning Manual 151E50417-H1040-C612-A2, Edition 04.2016

Page 152: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Statistical functionsYou can print the minimum value, maximum value, average of all values, or sum of all values in thefooters of the reports.The default report templates are prepared only for these four functions.

Device Types

Table 7-2 Device Types

Designation of Device Type Device TypepmDevPAC1500 PAC1500pmDevPAC3100 PAC1500pmDevPAC3200 PAC3200pmDevPAC4200 PAC4200pmDevPAC5100 PAC5100pmDevPAC5200 PAC5200pmMB MB devicepmVirtCounter Virtual counterpmDevP850 P850pmDevP855 P855pmDevManualMeasuringDevice Manual Measuring Device

Filters

Use filters to limit the number of devices in the Device list box in the Insert measured value window to asubset.

WildcardsThe filter feature uses the * and ? wildcards.• The character * searches for any number of contiguous characters within the device name.

• The character ? searches for exactly one of any characters within the device designation.The Device name representation box determines the component parts of the device designation.

Filter Examples

Table 7-3 Filter Examples

Filter Displayed Devices* Standard case. No filtering. All devices of the selected device type are listed.System1:PAC4200_A* All devices of System1 whose device names begin with the character string

System1:PAC4200_A. The devices are listed if the value DP is set in the Selectionbox. Only then is the character string System1 a filterable name component.

*_A All devices with _A as the last two characters of their name.*4200* All devices with 4200 at any point within the device name.*PAC?200* All devices with PAC and 200 in their names. There is precisely one character

between PAC and 200.*_? All devices with the name component _ in the penultimate position and precisely

one character in the last position.(Empty) No devices are displayed.

7.6.4

7.6.5

Advanced Report7.6 Datapoints

152 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 153: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Trends

8.1 Overview 1548.2 Creating a Trend View 1558.3 Configuring Trend View 1568.4 Selecting a Datapoint 1588.5 Displaying the Trend View 160

8

powermanager, , Commissioning Manual 153E50417-H1040-C612-A2, Edition 04.2016

Page 154: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

OverviewTrends allow you to represent the variations in the values of a device over a specific time range. A trend cancontain any number of hierarchically arranged areas for representing curves, with scales and legends. Value-over-time and value-over-value representations are both possible here.

8.1

Trends8.1 Overview

154 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 155: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Creating a Trend ViewTo create a trend view:²

Click in tool bar.An empty Trend window and the Select Trend View dialog open.

[sc_SelectTrendView_Dialog, 1, en_US]

Figure 8-1 Select Trend View Dialog

iiNOTEIf the Select Trend View dialog does not open, click Properties... in the Trend window to open the dialog.

² On the Select Trend View dialog, click New.

² Assign a name to the new trend and click OK.The new trend view is created and is visible in the Select trend configuration and time range list on theSelect Trend View dialog.

² Close the Select Trend View dialog and start the configuration of the new trend view.

8.2

Trends8.2 Creating a Trend View

powermanager, , Commissioning Manual 155E50417-H1040-C612-A2, Edition 04.2016

Page 156: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Configuring Trend ViewTo configure a trend view:²

Click in the tool bar.An empty Trend window and the Select Trend View dialog open.

[sc_SelectTrendView_Dialog, 1, en_US]

Figure 8-2 Select Trend View Dialog

² From the Select trend configuration and time range list on the Select Trend View dialog, select thetrend view that you want to edit.

² Click Edit.The Trend Configuration Editor window opens.In the Trend Configuration Editor window, select the datapoint and define the time range.For more information, see 8.4 Selecting a Datapoint.

² Click OK to close the Trend Configuration Editor window.

² In the Select Trend View window, select the time limitation from the Time Range list box.There are two types of time ranges available to complement the time ranges selected from the TrendConfiguration Editor:Open: The values for these time ranges come from the database. Additionally, new values are added tothese time ranges online.Closed: The values for these time ranges come exclusively from the database.

² Click View if the time range is closed.- or -

8.3

Trends8.3 Configuring Trend View

156 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 157: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click Forward if time range is open.In this scenario, define the Start time and End time for the time range.Click View.

The trend window shows the configured trend view.The trend retains all its configurations if it is used again.

iiNOTEThe trend view allows visual comparison of individual trends. You can add or remove datapoints from thetrend view to modify the results. For more information, see 8.4 Selecting a Datapoint.

Trends8.3 Configuring Trend View

powermanager, , Commissioning Manual 157E50417-H1040-C612-A2, Edition 04.2016

Page 158: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Selecting a DatapointSelecting a Datapoint Using Trend Configuration Editor Window

Select the datapoints for the trend view from the Trend Configuration Editor window.You can accommodate one or more datapoints in the view. Visual comparison of individual trends is thuspossible. A maximum of 16 datapoints can be represented in one trend.

[sc_TrendConfigEditor_Window, 2, en_US]

Figure 8-3 Trend Configuration Editor Window

To select datapoints for a trend view:² From the Selected Curve list box, select Undefined Curve.

- or -

8.4

Trends8.4 Selecting a Datapoint

158 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 159: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² If Undefined Curve entry is not available in the list box, click New to create an entry.

²Click to assign a datapoint to the curve.The dpSelector window opens.

² Select the datapoint in the dpSelector window, and click OK.The new datapoint name is displayed in the Select datapoint with datapoint selector and SelectedCurve field.You can further customize the trend view on the Scale and Style tabs on the Trend Configuration Editorwindow.

² Click OK.The datapoint is added to the trend view. The trend is displayed for the defined time range.

Trends8.4 Selecting a Datapoint

powermanager, , Commissioning Manual 159E50417-H1040-C612-A2, Edition 04.2016

Page 160: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Displaying the Trend ViewOpening a Trend View

Click from the tool bar to open the Trends window.

• If the Trends window was last closed using the button or the ALT + F4 command, it opens thelast closed trend view.

• If the Trends window was last closed using the Close button on the window, it opens an empty trendview along with the Select Trend View dialog.You can open a trend view from this dialog.

You can open an existing trend view.

Viewing the Trend Window

[sc_TrendView_Window, 1, en_US]

Figure 8-4 Trend View

• Click the graphic to open the Trend Ruler Values window.

• Use the scroll wheel to zoom in and out of the trend view.

• Click Legend to open the header area. The header area lists the datapoints, which enables displaying andhiding of the curves.

8.5

Trends8.5 Displaying the Trend View

160 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 161: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

System Administration and Optimization

9.1 Creating a New Project 1629.2 Adapting the Archive Size 1669.3 Creating Users 1689.4 Performance Optimization 1739.5 Distributed Systems 1769.6 Mass Parameterization 1799.7 Measuring Period and Tariff Synchronization 182

9

powermanager, , Commissioning Manual 161E50417-H1040-C612-A2, Edition 04.2016

Page 162: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Creating a New ProjectA new project can be created by using powermanager: Project Administrator.

iiNOTEThe name of the powermanager project must not contain any spaces.

Creating a New ProjectTo create a project:² Click Start > All Programs > SENTRON > powermanager V3.3 > Project Administration.

The powermanager: Project Administrator window opens.

[sc_ProjectAdmin_Window, 3, en_US]

² Click .The New project dialog opens.

Step 1: Project type settingsThere are two types of projects, which can be created:Server project: A server project contains all managers on the same machine.Client project: Client project is associated with a remote user interface. The remote project is connected toanother project on a server. The remote project is created and started on the client. On the client, a directorystructure and config file are automatically created (copied from the sever). In case of a configuration UI, onlyconfiguration and log files are created and where as for visualization UI, all parts are created except the data-base. Note: The changes in the configuration file are not copied to the server automatically. To access thepanels on the server, the project path has to be shared. The sever project can be selected in the New projectpanel (see figure below). Note: The non-executable projects cannot be selected. The project administrationpanel of the client allows you to view the status of the project (running, stopped, and so on).² Select a project type from the Selecting project type section.

9.1

System Administration and Optimization9.1 Creating a New Project

162 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 163: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_SelectProjType, 1, en_US]

² Click Next.Step 2: General settings² In the General settings section, enter a unique Project name.

² Click to, open the Choose a Folder dialog.In the Choose a Folder dialog, browse to the folder where you want to save the new project.

[sc_GeneralSettings, 1, en_US]

System Administration and Optimization9.1 Creating a New Project

powermanager, , Commissioning Manual 163E50417-H1040-C612-A2, Edition 04.2016

Page 164: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

² Click Next.Step 3: UI settingsThis step is only applicable if you have selected Client project in the Project type setting step.

[sc_ServerProj, 1, en_US]

² Click to browse to a location where a server project already exists.

² Select the Language of the project.

² Click Next.Step 4: Create projectThe Creating new project section displays the settings of the new project.

System Administration and Optimization9.1 Creating a New Project

164 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 165: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_CreatingNewProj, 1, en_US]

² Click Ok, to create the project.The Information dialog opens to confirm the creation of the project.

² Click Ok.The project is created and it is available for selection in the powermanager console.

System Administration and Optimization9.1 Creating a New Project

powermanager, , Commissioning Manual 165E50417-H1040-C612-A2, Edition 04.2016

Page 166: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Adapting the Archive SizeOptimum Archive Size

The optimum archive size depends on the number of devices in the project. Data loss can occur if archives aretoo small. Storage capacity is wasted if archives are too large.In the standard powermanager V3.3 installation, the archive is designed for 100 devices. When operatingmore than 500 devices, you must individually adapt the archive settings to your project. For more information,refer to the online help and the following query under the Siemens Support Database, FAQ: “What must beobserved to ensure that the time stamp and the power demand values of the devices are correctly exported? ”The archive_XXX.dpl files supplied in the standard installation are examples of a possible configuration.Adapt these files to your project.

Predefined Parameterization DataAdaptation is easy to perform with the help of the supplied predefined parameterization data.The following preconfigured parameterization data is available:• Up to 100 devices

• Up to 200 devices

• Up to 500 devices

• Up to 1000 devices

Changing the Archive ConfigurationTo change the archive configuration with the aid of the parameterization data included:• Open the powermanager base panel.

• In the menu bar, click Settings > System management.The System Management window opens.

• On the Database tab, click .The ASCII Manager window opens.

• Select the Import option in the ASCII Manager window.

• Give the following project path:<drive letter>\Siemens\SENTRON\powermanagerV3.3\PowermanagerLib\dplist\.Here, <drive letter> is the letter assigned to the drive where powermanager is installed.

• Open one of the following .dpl files based on your project size:– archive_normal.dpl for up to 20 devices (default setting)– archive_50.dpl for up to 50 devices– archive_100.dpl for up to 100 devices– archive_200.dpl for up to 200 devices– archive_500.dpl for up to 500 devices– archive_1000.dpl for up to 1000 devices

• In the ASCII Manager window, click Start.

• Enter the valid password and close the window.The new configuration is used after the next automatic archive change.

9.2

System Administration and Optimization9.2 Adapting the Archive Size

166 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 167: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Changing the Archive ImmediatelyTo change the archive immediately:• In the menu bar, click Settings > System management.

The System Management window opens.

• In the System Management window, click on the Database tab.The File Selection window opens.

• To change the archive, select an archive and click Activity.To change the archive database configuration, select an archive and click Configure.

• Restart the project.

System Administration and Optimization9.2 Adapting the Archive Size

powermanager, , Commissioning Manual 167E50417-H1040-C612-A2, Edition 04.2016

Page 168: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Creating UsersCreate a user account in the powermanager for each user of your projects.

iiNOTEDo not delete the standard root user account.

To create a user:• In the menu bar, click Settings > System management.

The System Management window opens.

• Open the Permission tab in the System Management window.

9.3

System Administration and Optimization9.3 Creating Users

168 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 169: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Click .The User Administration window opens.

[sc_UserAdmin_Window, 1, en_US]

Figure 9-1 User Administration Window

The User Administration table contains the following columns:– User name

powermanager login name– Groups

User groups to which a user is assignedEach user receives specific user rights through the group. Assign each user to at least one group.

– IDInternal identification number of the user account

– User languageLanguage of the powermanager user interfacepowermanager suggests the language when you log on.

System Administration and Optimization9.3 Creating Users

powermanager, , Commissioning Manual 169E50417-H1040-C612-A2, Edition 04.2016

Page 170: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• On the User Administration window, click Add User.The User Characteristics window opens.

[sc_UserCharacteristics_Window, 1, en_US]

Figure 9-2 User Characteristics Window

System Administration and Optimization9.3 Creating Users

170 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 171: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Enter following information in the User Characteristics window:– User name

Name of the user accountThe user uses this name to log on.

– Full NameFull name of the user

– DescriptionShort description of the user account

– LanguageLanguage of the powermanager user interfaceThe language is suggested to the user at logon.

– Group membershipAssign the user to at least one user group. You can also assign the user to multiple groups.The group assignment confers the group rights on the user. For more information on the rightsassigned to the users in different groups, see Authorization Levels and User Groups.

– PasswordClick Password to open the field for assigning password.Ensure that you assign a password for each user having administration rights. Else, the access topowermanager is unprotected.

• Click OK to confirm creation of the new schedule.The user account is created in powermanager. The account is listed in the User administration window.The user can log in with the assigned user name and password.

• Click Close to exit the User administration window.

Authorization Levels and User GroupsThe powermanager standard has the following predefined groups and levels:• 5 user groups

• 5 authorization levels

• assignment of user groups

• authorization levels

Table 9-1 Authorization Levels

Level Name in the dialog Scope of rights1 Visualize Allows only visualization2 Normal operator authorization Allows the opening of panels3 Extended operator authorization Allows the execution of commands, the setting of

substitute values, the setting of correction values, andthe modification of value range types

4 Administration Allows the use of GEDI and PARA5 Acknowledgement Allows the acknowledging of alerts

Table 9-2 Rights of the User Groups in the powermanager Standard

Group/Level Visualization Operator Authorization Administration Acknowledge-mentNormal Advanced

Root X X X X XPara X X X X XOperator all X X X X

System Administration and Optimization9.3 Creating Users

powermanager, , Commissioning Manual 171E50417-H1040-C612-A2, Edition 04.2016

Page 172: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Operator X X XGuest X

The group assignment confers the group rights on the user.

System Administration and Optimization9.3 Creating Users

172 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 173: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Performance OptimizationOverview

powermanager offers the following options to improve the performance of the system:• Smoothing supplied data

• Extending polling times

• Reducing active addresses

Smoothing Supplied DataSmoothing is used to reduce the amount of communication and the volume of data stored in the system.powermanager can smooth the data supplied by the devices in the driver before it is processed further in thecontrol system.Value-dependent Smoothing with Relative Threshold Valuepowermanager performs value-dependent smoothing with a relative threshold (specified in [%]).A value is only smoothed if the difference between value arriving in the driver and the last value transferred tothe Event Manager less than the relative threshold.No smoothing takes place if the difference between the consecutive values exceeds the relative thresholdvalue.Value RangeMeaningful threshold values lie in the range from 0% to 5%.Smoothing Supplied DataTo smooth the supplied data:• Right-click the project tree root.

• In the context menu, click System settings > Driver settings to view the driver settings.

9.4

System Administration and Optimization9.4 Performance Optimization

powermanager, , Commissioning Manual 173E50417-H1040-C612-A2, Edition 04.2016

Page 174: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• In the Driver settings view, enter the relative threshold percentage in the % field next to the changesmoothing button.The recommended relative threshold range is from 0 through 5 %.

[sc_DriverSettings, 3, en_US]

• Click change smoothing to start the smoothing process.

Extending Polling TimesDepending on the measured value type, measured values are read (polled) by the devices at different times.The communication load is reduced when the polling times are increased.To change the polling times:• Right-click the project tree root.

• In the context menu, click System settings > Driver settings to view the driver settings.

• Select the polling times from the list box next to [s].

• Click against each device to confirm the polling time for that device.

Reducing AddressesYou can reduce the number of active addresses to optimize the performance of powermanager. You canreduce the addresses for PAC3200 and PAC4200 devices using a semi-automated process. For PAC1500 andPAC3100, the scope of addresses is already reduced by default.To reduce the addresses:• Right-click the project tree root.

• From the context menu, click device engineering > PAC3200/PAC4200.

• Go to the Configuration tab.

• On the Configuration tab, deselect the Inherit default settings option.

System Administration and Optimization9.4 Performance Optimization

174 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 175: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• To reduce address of a device, under the Address column, deselect the checkbox corresponding to thedevice.

• Save the above configuration.ResultThe reduced scope of addresses affects:• Newly created devices

• Devices with the Inherit area settings option activatedRestoring the Original Address ConfigurationTo restore the original address configuration, activate the Inherit default settings option and save thechange.

System Administration and Optimization9.4 Performance Optimization

powermanager, , Commissioning Manual 175E50417-H1040-C612-A2, Edition 04.2016

Page 176: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Distributed SystemsOverview

Distributed systems enable connection of two or more autonomous powermanager systems via a commonnetwork. Each subsystem of a distributed system can be configured either as a single-station system or amulti-station system. Each system can process and display values and alerts of other systems.

LicensingThere must be a powermanager Distributed Systems license on every powermanager system that is oper-ated in a distributed system.

Interface to the SystemsCommunication of the parameterized subsystems takes place exclusively via the Distribution Manager. Enterthe parameterized subsystems in the powermanager Console before starting.

Permanent Network ConnectionA permanent network connection is required for mutual data access by the participating systems.

Creating New ProjectsFor information on how to create a project, see 9.1 Creating a New Project.

iiNOTECreation of a new project using a wizard is not recommended in the case of powermanager.

Parameterization of Distributed SystemsConfig FileEntry Possible values Description[general]distributed

1 or 0 Mandatory entry. This entry defines a distributed system. A distrib-uted system requires the distributed = 1 entry in the[general] section. This value can also be overwritten for indi-vidual Managers.[ctrl_1]distributed = 0In this case, the Control Manager with the number 1 cannot accessthe DPs of other systems (DP identification is not communicated tothis Manager).

[dist]distPort

Port number.The default value is4777.

Defines the port numbers used by the Dist Manager to acceptconnections from other systems. The default value is 4777. Do notdefine port numbers if your projects run on different computers.However, if your projects run on the same computer, define the portnumbers.

[dist]distPeer

– distPeer = "host1[:port1][$host2[:port2]]" system numberDefines the hosts and the system number to which the Dist Managerestablishes the connection as the "client" (the other system is the"server"). If the other system is redundant, powermanager separatesboth host names using $.

The following entries exist in the powermanager configuration file. The entries are examples and you mustadjust them accordingly.[general]

9.5

System Administration and Optimization9.5 Distributed Systems

176 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 177: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

distributed = 1[dist]#Establishing connection to Host1 with system number 1#distPeer = "Host1" 1#Establishing connection to Host2 with system number 2#distPeer = "Host2" 2#Establishing connection to Host3 with system number 3#distPeer = "Host3" 3#Establishing connection to Host4 with system number 4#distPeer = "Host4" 4System Names and System NumbersCorresponding to the distpeer entries in the configuration file, applicable system names and numbers areassigned to the project databases. A system name and a system number can only be used once within asystem network.The system name and number are assigned when creating a project in the project administration.The powermanager project have a predefined system name (System1) and system number (1). If you want toconnect multiple projects having the predefined system name and system number, change the system nameand system number of the individual projects.Use the following command to change the system name and number:

iiNOTEStop the project before you run the below command.

iiNOTEpowermanager saves the individual datapoints including the system name in the database. If the systemname is changed, it is recommended to reconfigure the datapoints in KPI, Reports (Basic and Advanced),and Custom panels.

WCCOAtoolSyncTypes –system <system_number> <system_name> -proj <project_name>Here, <system_number> is the new system number that is assigned to the project,<system_name> is the new system name that is assigned to the project,<project_name> is the name of the project.ExampleIf the system name is System2, the system number is 2, and the project name is powermanager, use thefollowing command:WCCOAtoolSyncTypes –system 2 System2 -proj powermanagerIf you want to run the distributed system as a single-user system again, then set the system number back to 1.Synchronous TimesSynchronize the times of the individual system if you want to run them in a distributed system.

Updating Archive StructureTo ensure that all the systems are able to read the updated report data, update the archive structure.To update the archive structure:• Open the powermanager base panel and open the Report window.

For information on how to open the Report window, see 7.3.1 Opening the powermanager ReportWindow.

• In the Report window, click Report > Configuration > Archive Structure.

• Enter the valid password.The default password is erAdmin.

System Administration and Optimization9.5 Distributed Systems

powermanager, , Commissioning Manual 177E50417-H1040-C612-A2, Edition 04.2016

Page 178: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Click OK.

• Click Yes on all subsequent dialogs.

System Administration and Optimization9.5 Distributed Systems

178 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 179: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Mass ParameterizationOverview

You can automate creation of new devices in the project tree. To do this, create a csv file in the project datadirectory.ExampleConsider that you want to create the following devices in an automated fashion:• Two PAC4200 devices with the names MyPAC4200_1 and MyPAC4200_2

• One PAC3100 device with the name MyPAC3100_1 via Slot1 of the gateway MyPAC4200_2

• One PAC3100 device with the name MyPAC3100_2 via the standard gatewayTo create the csv file:• The format of the command to create the above devices in automated fashion is:

DP name;DP type;area;sector;IP address;gateway;unit_address;frame;portHere,– DP name is the internal device name.– DP type is the device type.

Following device types are available in powermanager:– pmDev3VAETU5– pmDev3VAETU8– pmDev3VLCOM21– pmDev3WL (3WL)– pmDevPAC1500, pmDevPAC3100, pmDevPAC3200, pmDevPAC4200, pmDevPAC5100,

pmDevPAC5200– pmDevMB (generic Modbus device)– pmDevP850, pmDevP855 (SICAM P85x devices)– pmDevManualMeasuringDevice

– Area is the area name in the project tree.– Sector is the sector name in the project tree.

Only 1 sector level is supported.– IP address is the IP address of the system.– Gateway has a value range of TRUE or FALSE.

Following gateways can be defined:– Modbus-TCP: FALSE– Modbus-RTU: TRUE

– Unit_Address is the address of the unit in the subnetworked Modbus network.– Modbus-TCP: 0 (no relevance)– Modbus-RTU: 1 - 247

– Frame is defined as [tcp; rtu]

– Following ports are available:– Modbus-TCP: 502– Modbus-RTU – Slot1 : 17002 (7KM PAC4200, RS 485 bus is connected to slot "MOD1")– Modbus-RTU – Slot2 : 17003 (7KM PAC4200, RS 485 bus is connected to slot "MOD2")– Modbus-RTU – standard gateway: 502

9.6

System Administration and Optimization9.6 Mass Parameterization

powermanager, , Commissioning Manual 179E50417-H1040-C612-A2, Edition 04.2016

Page 180: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Therefore, for the above example, the following entries must be made in the csv file:MyPAC4200_1;pmDevPAC4200;area_4;sector_2;192.168.219.214;FALSE;0;tcp;502MyPAC4200_2;pmDevPAC4200;area_4;sector_2;192.168.219.215;FALSE;0;tcp;502MyPAC3100_1;pmDevPAC3100;area_4;sector_2;192.168.219.215;TRUE;1;rtu;17002MyPAC3100_2;pmDevPAC3100;area_4;sector_2;192.168.219.214;TRUE;1;rtu;502

iiNOTE

• Select tcp as a frame for a device you want to operate over the standard gateway.

• A predefined sample file PM_MassDataTmplte.csv is present in the data directory of the demoproject.

User InterfaceIn the menu bar, click Tools > Mass parameterization to access the mass parameterization display.

[sc_MassParameterization, 3, en_US]

Figure 9-3 Mass Parameterization View

The mass parameterization view contains the following components:• File

The File table in the left panel lists all the csv files that are created in the data directory of the currentproject.

System Administration and Optimization9.6 Mass Parameterization

180 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 181: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

• Read fileSelect a file from the file table and click read file to see the data of the file in the right panel.– If a device with an identical name and device type exists in the project tree, the device is highlighted

in Yellow.– If a device with an identical name and a different device type exists in the project tree, the device is

highlighted in Red.

• Import dataClick Import data to import the data of the selected file.

You can also overwrite existing devices or create areas that do not exist.

System Administration and Optimization9.6 Mass Parameterization

powermanager, , Commissioning Manual 181E50417-H1040-C612-A2, Edition 04.2016

Page 182: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Measuring Period and Tariff Synchronization

Overview

powermanager enables you to synchronize the power demand values and the tariffs of multiple devices usingthe digital input of a single device. You can only synchronize the PAC devices (PAC3100, PAC3200, andPAC4200).

iiNOTEIt is recommended that you enable synchronization when configuring the devices.

powermanager enables you to add offline device for synchronization. These devices are taken into considera-tion when they come online.

PrerequisitesEnsure that you meet the following prerequisites before enabling synchronization:• Ensure that all the devices that you want to synchronize have the Synchronization via Bus setting

enabled.

• Ensure that the synchronization interval for all the devices is 15 minutes.

Measuring Period Synchronization

To synchronize measuring period:² Right-click the system node from the tree.

² Select System settings.

² Select the Synchronization tab.The Measuring period dialog opens.

9.7

9.7.1

9.7.2

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

182 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 183: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_MeasuringPeriod_synchronization, 2, en_US]

Figure 9-4 Measuring Period Dialog

The Measuring period tab displays the following columns:Sync.: Select the checkbox in this column against the device for which you want to enable synchronization.Device: Devices added for synchronizationBus/DI/Clock/None: Synchronization type set for the deviceInterval Length: Synchronization interval. This must always be set at 15 minutes.² Select Synchronize measuring period with this digital input.

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

powermanager, , Commissioning Manual 183E50417-H1040-C612-A2, Edition 04.2016

Page 184: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

²Click to add devices for synchronization.The selection tree for digital inputs window opens.

[sc_DigitalInput, 2, en_US]

Figure 9-5 Selection Tree for Digital Input Window

² Select the digital inputs for devices that you want to synchronize.

² Click OK.The device is added to the synchronization table.

² To enable synchronization for a particular device, select the device using the checkbox under the Sync.column.

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

184 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 185: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

iiNOTE

To enable synchronization for all devices, click .

² Click to save the changes.

Tariff Synchronization

To synchronize tariff:² Right-click the project tree root.

² In the context menu, click System settings > Synchronization > Tariff.The Tariff tab opens.

9.7.3

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

powermanager, , Commissioning Manual 185E50417-H1040-C612-A2, Edition 04.2016

Page 186: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

[sc_Tariff_synchronization, 2, en_US]

Figure 9-6 Tariff Synchronization Tab

The tariff tab displays the following columns:Set tariff: Select the checkbox in this column against the device for which you want to enable synchroniza-tion.Device: The devices that you added for synchronization.² Select Set high/low tariff with this digital input.

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

186 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 187: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

²Click to add devices for synchronization.The selection tree for digital inputs window opens.

[sc_DigitalInput, 2, en_US]

Figure 9-7 Selection Tree for Digital Input Window

² Select the digital inputs for devices that you want to synchronize.

² Click OK.The device is added to the synchronization table.

² Under Tariff signal meaning, select the appropriate option.1-signal at digital input means high tariff: Select this option if you want to set the tariff to high.1-signal at digital input means low tariff: Select this option if you want to set the tariff to low.

² To enable synchronization for a particular device, select the device using the checkbox under the Sync.column.

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

powermanager, , Commissioning Manual 187E50417-H1040-C612-A2, Edition 04.2016

Page 188: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

iiNOTE

To enable synchronization for all devices, click .

² Click to save the changes.

System Administration and Optimization9.7 Measuring Period and Tariff Synchronization

188 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 189: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Literature

/1/ SIMATIC, Siemens Automation Manager, Manual

/2/ SIMATIC, Siemens Automation Manager, Online Help

/3/ powermanager, Help

/4/ Configuration manual, system manual, and device manuals for the PAC1500, PAC3100, PAC3200, PAC4200,PAC5100, PAC5200, 3VL, 3VA, 3WL, and P85x (P850 and P855) Power Monitoring Devices

/5/ Online support for powermanager: http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=en&objid=35384803&subtype=133000&caller=view

powermanager, , Commissioning Manual 189E50417-H1040-C612-A2, Edition 04.2016

Page 190: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

190 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016

Page 191: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

Index

A

AlertAlert Class 87, 87Alert Class Types 87

ArchiveAdapting the Archive Size 24, 166

Area 45Create 45No area 45

Authorization Levels 171

C

Configuration 30Console 28Cost Center 142

Create 142Delete 143

Cost Center Report 138Datapoints 146

Cumulated Power Values 150

D

Datapoint 145, 158Delete 146Edit 145, 145Insert 145

Delete Object 50Device 46

Configure 30Create 47

Device Engineering 53Device Integration 14

3VA 153VL 143WL 15P850/P855 15PAC1500 14PAC3100 14PAC3200 14PAC4200 14PAC5100/PAC5200 14

Device Type 147, 150Distributed Systems 176

E

Energy Counter 59Excel 118, 119, 119

Macro 119Extending Polling Times 174

F

Factor 55Filter 86, 86, 147, 151, 152Filter Administration 98Forecast Energy Consumption 61

I

Insert Measured Value 146, 148Installation

Automation License Manager 18powermanager 19Prerequisites 19

L

License Keys 20Load Monitoring 61

Alert 62, 70Correction Power 61Daily Trend 65Energy Profile 64Envelope 66Limit Curve 66, 69Orientation Variables 61Previous Day's Trend 66Response 62Schedule 71Switching Bits 62

powermanager, , Commissioning Manual 191E50417-H1040-C612-A2, Edition 04.2016

Page 192: powermanager Commissioning Manual - Siemens...powermanager V3.3 Commissioning Manual E50417-H1040-C612-A2 Preface Open Source Software Table of Contents System Overview 1 Installing

M

Medium 138Create 138

Microsoft Excel 19

P

Performance Optimization 173Polling Times 174Reducing Addresses 174Smoothing 173

Power Demand 150Power Peak Analysis 104Project

Stop 28Project Tree

Area 45Device 46Project Tree Root 44Sector 45

Q

Quick selection 123

R

Reaction Plans 89Source 93

Renaming Object 49Report 118

Create, Fully Automatic 125Create, Manual 122Create, Semiautomatic 123Open 123Save 123Schedule 123

Report Types 128Window 128

S

Schedule 71, 125Create 125Dialog 127View 125

Sector 45Create 45

Starting Communication 52Stopping Communication 52

T

Tariff Set 138Create 139Delete 141Holidays 141

Template 121Create 121Edit 121

Trend View 154Configure 156Create 155Display 160Open 160

Trends 154Datapoints 158

U

Unit 55User

Create Users 168User Administration 169

User Groups 171

V

Virtual Counter 58, 148

Index

192 powermanager, , Commissioning ManualE50417-H1040-C612-A2, Edition 04.2016