Power IT LV Capacitor Bank APC The ABB comprehensive solution for automatic power factor correction: APC standard, reinforced and de-tuned automatic capacitor banks

PowerIT LV Capacitor Bank APC

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PowerIT LV Capacitor Bank APC

PowerIT LV Capacitor Bank APC

The ABB comprehensive solution for automatic power factor correction:APC standard, reinforced and de-tuned automatic capacitor banks

Page 2: PowerIT LV Capacitor Bank APC

APCL and APCM: standard and reinforced ranges

Lifting lugs

Fans

Contactors

HRC Fuses

Busbar

RVC Controller

LVCS capacitors

Bottom cable entry

Plinth

APCM2 cubicle of 400kvar

The ABB comprehensive solution for automatic power factor correction

The APC is a powerful and compact automatic bank.

It is very easy to install and to operate.

It provides a high level of reliability and security.

APCL2 box of 125kvar

Fan

RVC Controller

Contactors

HRC Fuses

Protection against direct

contact

Ample space for wiring

LVCS Capacitors

Bottom cable entry

Page 3: PowerIT LV Capacitor Bank APC

APCR cubicle of 300kvar

Lifting lugs

Fans

Contactors

HRC Fuses

RVC Controller

Busbar

LVCS Capacitors modules

Reactors modules

Bottom cable entry

Plinth

Powerful and compactABB capacitors and a specially designed ventilation system allow the

APC to reach a maximum reactive power within a minimum volume.

Easy to select The APC exists in 5 versions: 2 types of boxes (APCL1 and APCL2)

and 3 types of cubicles (APCM1, APCM2 and APCR).

The APC offers a power range from 25 to 400kvar. Small power steps

and appropriate switching sequences allow an acute regulation.

Easy to installThe APC is a complete unit, factory tested and ready for connection.

Its commissioning may be completely automatic.

There is ample space for wiring.

The APCL box is equipped with wall mounting brackets.

The APCM and APCR cubicles are equipped with a plinth and lifting

lugs for easy handling.

Easy to useThe multiple automatic functions of the RVC and its user-friendly

interface make the APC very easy to operate.

3

APCR: de-tuned range - with reactors

Page 4: PowerIT LV Capacitor Bank APC

LVCS

The reliability of the APC is based on a set of ABB components specially designed for the reactive power compensation application.

The APC has an IP23D protection level (closed door) and is protected against direct and accidental contact (open door).

ABB Contactors

Contactors have been specially selected for their excellent endurance tests handling capability.

4

Reliable and safe

ABB capacitors

The dielectric of the capacitors windings is made of in-house metallized polypropylene film giving exceptional properties:

• high voltage withstand capability.

• excellent peak current handling capacity.

• high capacitance stability.

• long life even under high electrical stress.

• very low losses.

• exceptional self-healing properties.

LVCS capacitors

The LVCS protection system offers a reliable and safe protection. It is based on:

• the instant reaction of state of the art overpressure detection and disconnection devices.

• a double casing insulation protecting the windings from the environment and assuring a high capacitance stability over the whole capacitor service life.

The LVCS is suitable for maximum ambient temperature of +55°C (class D) and minimum of -25°C.

The LVCS reinforced range is rated at 474V.

Contactor-type terminals

Built-in safety discharge resistor (<50V in 1 min)

Dry type self-healing capacitor winding

Thermo-setting resin

Insulating enclosure

Overpressure sensitive disconnector

Page 5: PowerIT LV Capacitor Bank APC

5

ABB Reactors (for APCR execution)

The dry type resin embedded reactors are specially designed to suit the reactive power compensation application.

Their exceptional linearity and thermal stress resistance characteristics ensure a high reliability degree even in

case of temporary overvoltage.

Ventilation

Except for the APCL1 type, all APCs are equipped with a ventilation system specially selected for its long life duration. The APC ventilation system consists

of fans with temperature-dependent speed control and temperature probes which provide the fans with the necessary thermal data. These fans adapt their

speed to the actual cooling requirements of the APC. In case of temporary overheating, the APC is automatically disconnected.

RVC PF Controller

The RVC is insensitive to the presence of harmonics.

The RVC complies with EU directives for EMC for operation at 50Hz and bears the CE marking to this effect.

The RVC is suitable for hot environments thanks to its maximum ambient temperature of 70°C.

The RVC is fitted with an overvoltage and undervoltage protection.

RVC

LCD display with indication of:

• inductive/capacitive PF

• active outputs

• demand for switching on/off a capacitor step

• alarm conditions

• overtemperature condition

Keypad

Automatic setting of:

• phase shift

• C/k

• number of outputs

• type of switching sequence

Easy commissioning with automatic recognition of:

• special connections (single-phase, CT leads)

• number of outputs

• type of switching sequence

Automatic/manual mode

Environment friendly

The ISO 14001 certification guarantees our commitment to the environment.

Page 6: PowerIT LV Capacitor Bank APC

Wiring diagram

Main circuit-breaker.

Top cable entry (for APCM1, APCM2 and APCR only).

RVT controller (for APCM1, APCM2 and APCR only).

6

Options

While having all the functions of the RVC, the RVT also has

features including:

programmable protection thresholds (undervoltage,

overtemperature, excessive harmonic distortion, etc…).

The RVT protects your capacitor bank. It is recommended

for instal lation where overvoltage, resonance or

overtemperature is likely to happen.

full graphics display.

guided navigation and programming.

network information and bank monitoring (voltage,

current, harmonics spectrum, etc...)

RS-485 Modbus adapter allowing communication with a

monitoring system. All RVT parameters are remotely

accessible (including harmonic spectra and tables.)

multi-language support.

help button giving instant access to a description of all

RVT features and functionality.

printer connection.

input contacts for day/night cos ϕ and external alarm.

output contacts for alarm and fan relays.

RVT Modbus

C1 C12 capacitor steps

F1 main fuses or protective devices

F2 control fuses

F3 F14 capacitor step fuses

K1 K12 contactors

P1 PF controller

T1 power transformer

T2 12V DC power supply

CT current transformer

V1 regulated speed fan

* R1 R12 reactors (APCR only)

T1

F1

F3-F14

P1

C1-C12

K1-K12

V1

T2

F2

TI

LOADS

R1-R12 *

For a maximum protection of your capacitor bank against temporary deterioration ofyour network quality.

(for further information on the RVT controller, please refer to our specific documentation)

Page 7: PowerIT LV Capacitor Bank APC

Technical specifications

Nominal voltage and frequency: 230, 400V - 50Hz (standard range).240, 480V - 60Hz (standard range).400V - 50Hz (reinforced range rated at 474V).400, 415, 525, 690V - 50Hz (de-tuned capacitor bank)240, 380, 480, 600V - 60Hz (de-tuned capacitor bank)

Connection: Three phase.

Power factor setting: From 0.7 inductive to 0.7 capacitive.

Starting current setting (C/k):From 0.05A to 1A for the RVC controller.From 0.01A to 5A for the RVT controller (optional for the APCM1,APCM2 and APCR).

Operation:Automatic or manual setting of the controller with indication of : - the number of active outputs.

- the inductive or capacitive power factor.- alarm conditions.- overtemperature.- demand for switching on/off a capacitor step.

Losses:Dielectric losses: less than 0.2 Watt/kvar.Capacitor total losses: less than 0.5 Watt/kvar(discharge resistors included).Automatic bank total losses at 400V 50Hz:

- without reactors: less than 1.5 Watt/kvar (including accessories losses),

- with reactors: less than 5.5 Watt/kvar(including accessories losses).

Capacitors:Dry type self healing according to IEC 60831-1&2. Voltage test: 2.15 Un between terminals during 10 sec at rated

frequency (above IEC 60831-1&2).Acceptable overloads: - overvoltage tolerance:

10% max. intermittently.- overcurrent tolerance: 30% permanently.

Temperature range: -25°C / class D according to IEC 60831-1&2.

Reactors (APCR only):- Type : dry type resin embedded according to IEC 289, IEC 76- Maximal harmonic voltage distortion:

U3/U1 = 0.5 % U5/U1 = 6.0 %U7/U1 = 5.0 % U11/U1 = 3.5 %U13/U1 = 3.0 % (not exceeding a THDU of 8 %).

The automatic capacitor bank complies with IEC 60439.

Automatic capacitor bank tests:- Functional test.- Insulation test.

CE Marked.

Protection:IP23D (closed door).Protected against direct and accidental contact (open door).

Execution: Indoor.

Color: Beige RAL 7032.

Ambient temperature: -5°C/+40°C according to IEC 60439.

Ventilation:- Natural for the APCL1.- Forced for the APCL2, APCM1, APCM2 and APCR(temperature-dependent speed control fans).

Installation:Box: - Wall mounting (fixation brackets included).

- Bottom cable entry.Cubicle: - Floor fixation.

- Equipped with a plinth.- Lifting lugs provided.- Top or bottom cable entry.

Important notice: The installation of capacitors on networks disturbed by harmonicsmay require special precautions especially when there is a risk ofresonance.

7

Page 8: PowerIT LV Capacitor Bank APC

8

APCL1, APCL2, APCM1 and APCM2 Range

Standard range240V 60Hz - Clean networkType Power Regulation Recommended

(kvar) at 240V x*kvar main circuit-breakerAPCM1 75 6*12.5 T4N320FF

87.5 7*12.5 T5N630FF100 8*12.5 T5N630FF

APCM2 112.5 9*12.5 T5N630FF125 5*25 T5N630FF150 6*25 T5N630FF175 7*25 S6N800F 3P F200 8*25 S6N800F 3P F

Standard range480V 60Hz - Clean networkType Power Regulation Recommended

(kvar) at 480V x*kvar main circuit-breakerAPCM1 150 6*25 T4N320FF

175 7*25 T5N630FF200 8*25 T5N630FF

APCM2 225 9*25 T5N630FF250 5*50 T5N630FF300 6*50 T5N630FF350 7*50 S6N800F 3P F400 8*50 S6N800F 3P F

Higher ratings will be obtained by connecting several units in parallel.

Standard range230V 50Hz - Clean networkType Power Regulation Recommended

(kvar) at 230V x*kvar main circuit-breakerAPCL1 25 4*6.25 T1N160FFC

37.5 3*12.5 T1N160FFCAPCL2 50.0 4*12.5 T3N250FF

62.5 5*12.5 T4N320FFAPCM1 75 6*12.5 T4N320FF

87.5 7*12.5 T5N630FF100 8*12.5 T5N630FF

APCM2 112.5 9*12.5 T5N630FF125 5*25 T5N630FF150 6*25 T5N630FF175 7*25 S6N800F 3P F200 8*25 S6N800F 3P F

Standard range400V 50Hz - Clean networkType Power Regulation Recommended

(kvar) at 400V x*kvar main circuit-breakerAPCL1 25 2*12.5 T1N160FFC

37.5 3*12.5 T1N160FFC50 4*12.5 T1N160FFC

62.5 5*12.5 T1N160FFC75 3*25 T3N250FF

APCL2 87.5 7*12.5 T3N250FF100 4*25 T3N250FF125 5*25 T4N320FF

APCM1 150 6*25 T5N630FF175 7*25 T5N630FF200 8*25 T5N630FF

APCM2 225 9*25 T5N630FF250 5*50 T5N630FF300 6*50 S6N800F 3P F350 7*50 S6N800F 3P F400 8*50 S7S1250F 3P F

Reinforced range (capacitor rated at 474V)400V 50Hz - Slightly polluted networkType Power Regulation Recommended

(kvar) at 400V x*kvar main circuit-breakerAPCL1 20 2*10 T1N160FFC

30 3*10 T1N160FFC40 4*10 T1N160FFC50 5*10 T1N160FFC60 3*20 T1N160FFC

APCL2 70 7*10 T3N250FF80 4*20 T3N250FF

100 5*20 T3N250FFAPCM1 120 6*20 T4N320FF

140 7*20 T5N630FF160 8*20 T5N630FF

APCM2 180 9*20 T5N630FF200 5*40 T5N630FF240 6*40 T5N630FF280 7*40 S6N800F 3P F320 8*40 S6N800F 3P F

Page 9: PowerIT LV Capacitor Bank APC

9

De-tuned range400V 50Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 400V x*kvar main circuit-breaker5.67 - 7 - 12.5 100 4*25 T3N250FF

125 5*25 T4N320FF150 3*50 T5N630FF150 6*25 T5N630FF175 7*25 T5N630FF200 4*50 T5N630FF200 8*25 T5N630FF250 5*50 T5N630FF300 6*50 S6N800F 3P F

De-tuned range415V 50Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 415V x*kvar main circuit-breaker5.67 - 7 - 12.5 100 4*25 T3N250FF

125 5*25 T4N320FF150 3*50 T5N630FF150 6*25 T5N630FF175 7*25 T5N630FF200 4*50 T5N630FF200 8*25 T5N630FF250 5*50 T5N630FF300 6*50 S6N800F 3P F

De-tuned range525V 50Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 525V x*kvar main circuit-breaker5.67 - 7 - 12.5 100 4*25 T3N250FF5.67 - 7 - 12.5 125 5*25 T3N250FF5.67 - 7 150 3*50 T4N320FF5.67 - 7 - 12.5 150 6*25 T4N320FF5.67 - 7 175 7*25 T4N320FF5.67 - 7 200 4*50 T5N630FF5.67 - 7 200 8*25 T5N630FF5.67 - 7 250 5*50 T5N630FF5.67 - 7 300 6*50 T5N630FF

De-tuned range690V 50Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 690V x*kvar main circuit-breaker5.67 - 7 - 12.5 100 4*25 T1N160FFC

125 5*25 T3N250FF150 3*50 T3N250FF150 6*25 T3N250FF175 7*25 T3N250FF200 4*50 T4N320FF200 8*25 T4N320FF250 5*50 T5N630FF300 6*50 T5N630FF

APCR Range

De-tuned range240V 60Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 240V x*kvar main circuit-breaker6 - 7 - 12.5 100 4*25 T5N630FF

125 5*25 T5N630FF150 6*25 T5N630FF

De-tuned range380V 60Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 380V x*kvar main circuit-breaker6 - 7 - 12.5 100 4*25 T4N320FF

125 5*25 T4N320FF150 3*50 T5N630FF150 6*25 T5N630FF175 7*25 T5N630FF200 4*50 T5N630FF200 8*25 T5N630FF250 5*50 S6N800F 3P F300 6*50 S6N800F 3P F

De-tuned range480V 60Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 480V x*kvar main circuit-breaker6 - 7 - 12.5 100 4*25 T3N250FF

125 5*25 T3N250FF150 3*50 T4N320FF150 6*25 T4N320FF175 7*25 T5N630FF200 4*50 T5N630FF200 8*25 T5N630FF250 5*50 T5N630FF300 6*50 T5N630FF

De-tuned range600V 60Hz - Polluted network% Reactors Power Regulation Recommended

(kvar) at 600V x*kvar main circuit-breaker6 - 7 - 12.5 100 4*25 T1N160FFC

125 5*25 T3N250FF150 3*50 T3N250FF150 6*25 T3N250FF175 7*25 T4N320FF200 4*50 T4N320FF200 8*25 T4N320FF250 5*50 T5N630FF300 6*50 T5N630FF

Higher ratings will be obtained by connecting several units in parallel.

Page 10: PowerIT LV Capacitor Bank APC

APCL1 APCL2 APCM1

APCM2 APCR

550600

2000

1950

100

100

100

550

450

600

600

275(*)

275(*)

400

400

100

100

1900

1950

550 75

0

1300

1350

10

Dimensions

Overall dimensions

H (mm) W (mm) D (mm) Maximum weight

APCL1 550 450 275 26 kg

APCL2 750 550 275 42 kg

APCM1 1350 600 400 100 kg

APCM2 1950 600 400 175 kg

APCR 2000 600 550 500 kg

* thickness of the air grid (25 mm) not included

Page 11: PowerIT LV Capacitor Bank APC

Capacitor bank selection

Non linear loads total power (kVA)

Transformer rated power (kVA)

> 25 %15 to 25 %< 15 %

Standard range Reinforced range De-tuned range *

> 60 %

De-tuned range+

Harmonic filtering solution **

Thumb rule

* Please check that the de-tuned capacitor bank does not interfere with telecommunication frequency used by the utilities.

** Requires a technical audit. Please ask our LVNQ specialists for details.

Network study

Our LVNQ specialists will, on request, perform a harmonic study of your network in order to propose

you a reactive power compensation solution that prevents any risk of resonance, for maximum reliability.

11

Page 12: PowerIT LV Capacitor Bank APC

2GC

S30

1013

A00

40

The

Indu

stria

lITw

ordm

ark

and

all a

bove

-men

tione

d pr

oduc

t nam

es in

the

form

Pow

erIT

are

regi

ster

ed o

r pen

ding

trad

emar

ks o

f AB

B.

While all care has been taken to ensure that the information contained in this publication is correct, no

responsibility can be accepted for any inaccuracy. We reserve the right to alter or modify the information

contained herein at any time in the light of technical or other developments. Technical specifications are valid

under normal operating conditions only. We do not accept any responsibility for any misuse of the product and

cannot be held liable for indirect or consequential damages.

This product has been certified by ABB Group as IndustrialIT EnabledTM - Information Level. All product

information is supplied in interactive electronic format, based on ABB Aspect ObjectTM technology.

The IndustrialIT commitment from ABB ensures that every enterprise building block is equipped with the

integral tools necessary to install, operate, and maintain it efficiently throughout the product lifecycle.

www.abb.com/lowvoltage