Installation Instructions Original Instructions PowerFlex 750-Series Power Jumpers Catalog Numbers 20F, 20G, 21G Summary of Changes This publication contains new and updated information as indicated in the following table. PowerFlex® 750-Series drives contain protective MOVs (metal-oxide varistors) and Common Mode Capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the tables on page 3 . Topic Page Summary of Changes 1 Precautions 2 Power Jumper Configuration 2 Jumper Installation, Removal, and Storage 4 Jumper Locations and Settings 5 Topic Page Added voltage code B to the Jumper Locations and Settings table 5, 6 ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored. R/L1 S/L2 T/L3 PE-A1 PE-A PE-A2 DC+ DC– PE-B MOV and AC EMI Capacitor Phase to Ground Common Mode Capacitor to Ground Frames 8…10

PowerFlex 750-Series Power Jumpers Installation Instructions...PowerFlex 750-Series Power Jumpers Jumper Installation, Removal, and Storage Jumper screws (Frames 2…5), wires (Frames

  • Upload
    others

  • View
    19

  • Download
    0

Embed Size (px)

Citation preview

  • Installation Instructions

    Original Instructions

    PowerFlex 750-Series Power JumpersCatalog Numbers 20F, 20G, 21G

    Summary of ChangesThis publication contains new and updated information as indicated in the following table.

    PowerFlex® 750-Series drives contain protective MOVs (metal-oxide varistors) and Common Mode Capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the tables on page 3.

    Topic Page

    Summary of Changes 1

    Precautions 2

    Power Jumper Configuration 2

    Jumper Installation, Removal, and Storage 4

    Jumper Locations and Settings 5

    Topic Page

    Added voltage code B to the Jumper Locations and Settings table 5, 6

    ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored.

    R/L1S/L2T/L3

    PE-A1

    PE-A

    PE-A2

    DC+

    DC– PE-B

    MOV and AC EMI Capacitor Phase to Ground Common Mode Capacitor to Ground

    Frames 8…10

  • PowerFlex 750-Series Power Jumpers

    PrecautionsBefore proceeding, verify that all power to the drive has been removed.

    Qualified Personnel

    Personal Safety

    Product Safety

    Power Jumper Configuration

    ATTENTION: Allow only qualified personnel familiar with adjustable frequency AC drives and associated machinery to plan or implement the installation, start-up, and subsequent maintenance of the system. Failure to comply can result in personal injury and/or equipment damage.

    ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before removing/installing jumpers.

    Frames 1…7

    Measure the DC bus voltage at the following points (see the PowerFlex 750-Series AC Drive Installation Instructions, publication 750-IN001 for locations):

    • Measure the DC bus voltage at the power terminal block by measuring between the +DC and -DC terminals or between the +DC and -DC test point sockets if equipped.

    • Also measure between the +DC terminal or test point and the chassis, and between the -DC terminal or test point and the chassis. The voltage must be zero for all three measurements.

    Frames 8…10

    Measure the DC bus voltage at the DC+ and DC- TESTPOINT sockets on the front of the power module (see Installation Instructions for location).

    ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage can result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference an applicable ESD protection guide.

    ATTENTION: Risk of equipment damage exists. The drive power source type must be accurately determined. Jumpers PE-A, PE-A1, PE-A2, and PE-B must be configured for the power source type according to the recommendations shown in the following table.

    2 Rockwell Automation Publication 750-IN011F-EN-P - June 2017

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/750-in001_-en-p.pdf

  • PowerFlex 750-Series Power Jumpers

    To connect or disconnect these devices, refer to pages 5…7.

    In addition, on an ungrounded distribution system where the line-to-ground voltages on any phase could exceed 125% of the nominal line-to-line voltage, install an isolation transformer. See Wiring and Grounding Guidelines for PWM AC Drives, publication DRIVES-IN001, for more information on impedance grounded and ungrounded systems.

    Recommended Power Jumper Configurations – Frames 1…7

    Power Source TypeJumper PE-A (1) (2)

    (MOV / Input Filter Caps)

    (1) When MOVs are disconnected, the power system must have its own transient protection to maintain known and controlled voltages.(2) Frame 5…7 Common DC Input drives do not have the PE-A jumper.

    Jumper PE-B(DC Bus Common Mode Caps)

    Benefits of Correct Configuration on Power Source Type

    Non-solid Ground• AC fed ungrounded• Impedance grounded• B phase ground• DC fed from an active

    converter

    Disconnected Disconnected Helps avoid severe equipment damage when ground fault occurs.

    Solid Ground• AC fed solidly grounded• DC fed from passive rectifier,

    which has a solidly grounded AC source

    Connected Connected Reduced electrical noise, most stable operation, EMC compliance, reduced voltage stress on components and motor bearings.

    Recommended Power Jumper Configurations – Frames 8…10

    Power Source TypeJumper PE-A1 (1)

    (MOV)

    (1) When MOVs are disconnected, the power system must have its own transient protection to Achieve known and controlled voltages.

    Jumper PE-A2(Input Filter Caps)

    Jumper PE-B(DC Bus Common Mode Caps)

    Benefits of Correct Configuration on Power Source Type

    Non-solid Ground• AC fed ungrounded• Impedance grounded• B phase ground• DC fed from an active converter

    Disconnected Disconnected Disconnected Helps avoid severe equipment damage when ground fault occurs.

    Solid Ground• AC fed solidly grounded• DC fed from passive rectifier,

    which has a solidly grounded AC source

    Connected Connected Connected Reduced electrical noise, most stable operation, EMC compliance, reduced voltage stress on components and motor bearings.

    IMPORTANT Common mode capacitors are used to conform with the EMC Directives. Removing these devices can withdraw the associated directive.

    Rockwell Automation Publication 750-IN011F-EN-P - June 2017 3

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/drives-in001_-en-p.pdf

  • PowerFlex 750-Series Power Jumpers

    Jumper Installation, Removal, and StorageJumper screws (Frames 2…5), wires (Frames 1, 6 & 7), or plugs (Frames 8…10) are used to complete an electrical connection when installed/connected. When power jumper screws are not used, they are stored on the left interior chassis wall as shown.

    When installing a jumper screw or wire, note the recommended torque listed.

    Drive Identification

    The ‘Voltage Code’ and ‘Default Power Jumper Configuration’ are on the drive nameplate. Use this information to perform the proper procedure in the following tables.

    ATTENTION: Hazard of equipment damage exists if jumpers are not properly disconnected.

    For Frames 2…5, completely remove the jumper screw from the circuit board.

    Frames 1, 6 & 7, secure the disconnected jumper wire to the standoff provided.

    Frames 8…10 drive assemblies, secure the disconnected jumper plug in the socket that is provided and verify that all drive assemblies are identically configured.

    Recommended Torque Values

    Frames Recommended Torque Recommended Screwdriver/Socket

    1 Not Applicable Not Applicable

    2…5 1.36 N•m (12.0 lb•in) 0.14 N•m (1.2 lb•in) 6.4 mm (0.25 in.) flat or T15 Hexalobular

    6…7 1.36 N•m (12.0 lb•in) 7 mm socket or T20 Hexalobular

    Drive Power Jumpers

    Frame 4 Shown

    Jumper Screws Installed

    Jumper Screws Not Installed

    Jumper Screw Storage

    Cat No. 20G11 N D 011 AA0NNNNN

    UL Type 1 - only with Debris Hood and Conduit PlateUL Open Type/IP20 - without Debris Hood and Conduit Plate

    Specifications and Custom Catalog Numberrepresenting options installed at factory.See Nameplate 2 (Located behind HIM)for equivalent base catalog number and separate options

    Nameplate 1:

    Mfd. in 2009 on Jan. 19

    Series: A

    Input: 3 Phase, 47-63HzAC Voltage RangeAmps ND (HD)

    Power ND (HD)

    Output: 3 Phase, 0-400 HzAC Voltage RangeBase Frequency (default)Continuous Amps ND (HD)60Sec Ovld Amps ND (HD)3 Sec Ovld Amps ND (HD)

    0-40050 Hz

    342-440 432-528

    0-46060 Hz

    xxxxxxxxx

    xxxxxxxxx

    xxxxxxxxx

    xxxxxxxxx

    xxx xxx xxx xxx

    5.5 HP (4 HP) 7.5 HP (5 HP)

    N223

    Serial Number: xxxxxxxx

    Original Firmware: x.xxx

    TUV Rheinland

    Product Safety

    ..

    Production inspected

    W

    E CEN 61800-5-1

    Made in the U.S.A. Fac1C

    400V Class 480V Class

    II (2) G D

    Functional Safety

    Type approved

    Voltage Code Default Power Jumper Configuration

    4 Rockwell Automation Publication 750-IN011F-EN-P - June 2017

  • PowerFlex 750-Series Power Jumpers

    Jumper Locations and SettingsThe following pages show jumper locations and settings.

    Jumper Locations and Settings

    Frame

    Volta

    geCo

    de

    Factory Default Jumper SettingsPower Source Type

    Catalog Code ‘A’ Catalog Code ‘J’

    1 BCD

    PE-A jumper wire connected to ground.PE-B jumper wire insulated/disconnected from ground.

    PE-A jumper wire and PE-B jumper wire connected to ground.

    Solid Ground Connect the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) to ground.

    Non-Solid GroundInsulate the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) from ground.

    2 BCD

    PE-A InstalledPE-B Not Installed

    PE-A InstalledPE-B Installed

    Solid GroundInstall jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and ‘PE-B’ (CM Cap).See page 4 for recommended torque.

    Non-Solid GroundRemove both jumper screws.

    3 BCDE

    PE-A InstalledPE-B Not Installed

    PE-A InstalledPE-B Installed

    Solid Ground Install jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and ‘PE-B’ (CM Cap).See page 4 for recommended torque.

    Non-Solid GroundRemove both jumper screws.

    4 BCDE

    PE-A InstalledPE-B Not Installed

    PE-A InstalledPE-B Installed

    Solid Ground Install Jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and ‘PE-B’ (CM Cap).See page 4 for recommended torque.

    Non-Solid GroundRemove both jumper screws.

    PE-A

    PE-B

    InsulatedConnected

    Insulated

    Connected

    PE-B

    PE-A

    PE-B

    PE-A

    PE-B

    PE-A

    Rockwell Automation Publication 750-IN011F-EN-P - June 2017 5

  • PowerFlex 750-Series Power Jumpers

    5 BCDE

    PE-A InstalledPE-B Not Installed

    PE-A InstalledPE-B Installed

    Solid Ground Install jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and ‘PE-B’ (CM Cap).See page 4 for recommended torque.

    Non-Solid GroundRemove both jumper screws.

    6 BCDEF

    PE-A jumper wire connected to ground.PE-B jumper wire insulated/disconnected from ground.

    PE-A jumper wire and PE-B jumper wire connected to ground.

    Solid Ground Connect the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) to ground. See page 4 for recommended torque.

    Non-Solid GroundInsulate the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) from ground.

    7 BCDEF

    PE-A jumper wire connected to ground.PE-B jumper wire insulated/disconnected from ground.

    PE-A jumper wire and PE-B jumper wire connected to ground.

    Solid Ground Connect the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) to ground. See page 4 for recommended torque.

    Non-Solid GroundInsulate the MOV/Input Filter Cap jumper wire (PE-A) and the CM Cap jumper wire (PE-B) from ground.

    Jumper Locations and Settings (Continued)

    Frame

    Volta

    geCo

    deFactory Default Jumper Settings

    Power Source TypeCatalog Code ‘A’ Catalog Code ‘J’

    PE-B

    PE-A

    DC+PE-B

    PE-A

    E4

    Insulated Connected

    InsulatedConnected

    PE-B

    PE-A

    Insulated Connected

    InsulatedConnected

    6 Rockwell Automation Publication 750-IN011F-EN-P - June 2017

  • PowerFlex 750-Series Power Jumpers

    8…10 CDEF

    PE-A1 & PE-A2 connected to ground.PE-B jumper plug insulated/disconnected from ground.

    PE-A1, PE-A2, and PE-B connected to ground.

    Solid Ground Connect the MOV jumper wire (PE-A1), Input Filter Cap jumper plug (PE-A2), and the CM Cap jumper plug (PE-B) to ground. See page 4 for recommended torque.

    Non-Solid GroundInsulate/disconnect the MOV jumper wire (PE-A1), Input Filter Cap jumper plug (PE-A2), and the CM Cap jumper plug (PE-B) from ground.

    Jumper Locations and Settings (Continued)

    Frame

    Volta

    geCo

    deFactory Default Jumper Settings

    Power Source TypeCatalog Code ‘A’ Catalog Code ‘J’

    PE-A1

    PE-A2

    P3

    P2

    PE-A1

    Insulated (P2)

    Connected (P3)

    Insulated

    Connected

    Insulated (J4)

    Connected (J3)

    PE-A1 and GND positions on early production drives.

    1.86 N•m (16.0 lb•in)

    Insulated

    Connected

    Rockwell Automation Publication 750-IN011F-EN-P - June 2017 7

  • Rockwell Automation SupportUse the following resources to access support information.

    Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

    Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/

    Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page

    Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page

    Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page

    Product Compatibility and Download Center (PCDC)

    Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page

    Additional Resources

    These documents contain additional information concerning related products from Rockwell Automation.

    You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

    Resource Description

    PowerFlex 750-Series AC Drive Installation Instructions, 750-IN001. Provides the basic steps that are required to install a PowerFlex 750-Series AC drive.

    Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives,publication DRIVES-IN001.

    Provides basic information to properly wire, help protect, and ground pulse-width modulated (PWM) AC drives.

    Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control, publication SGI-1.1.

    Provides general guidelines for the application, installation, and maintenance of solid-state control.

    Product Certifications website, http://www.ab.com. Provides declarations of conformity, certificates, and other certification details.

    Allen-Bradley, PowerFlex, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

    Rockwell Automation maintains current product environmental information on its website athttp://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

    *PN-448244*PN-448244

    Publication 750-IN011F-EN-P - June 2017Supersedes Publication 750-IN011E-EN-P - February 2014 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.pagehttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/750-in001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/drives-in001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/rockwellautomation/certification/overview.pagehttp://www.rockwellautomation.com/literature/

    PowerFlex 750-Series Power Jumpers Installation InstructionsSummary of ChangesPrecautionsQualified PersonnelPersonal SafetyProduct Safety

    Power Jumper ConfigurationJumper Installation, Removal, and StorageDrive Identification

    Jumper Locations and SettingsAdditional Resources

    Back Cover

    Introduction_Category Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3 Primary, B2D5, D6Installation instructions15Post / External

    LMNANALaunch Materials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    ** Minimum order quantities on all JIT items are based on the publication length. **

    Publication lengthMinimum Order Quantity

    77 or more pages1 (no shrink wrap required)

    33 to 76 pages25

    3 to 32 pages50

    1 or 2 pages100

    Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170 gsm 2pp100# gloss cover, 100# gloss text

    A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color170gsm Silk – 120gsm Silk80# gloss cover, 80# gloss text

    A52 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Gray shading indicates Obsolete Print Catagories

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B31 color100gsm bond50# matte sheet text, self cover

    B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B52 color100gsm bond50# matte sheet text, self cover

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Gray shading indicates Obsolete Print Catagories

    Just In Time (JIT) or Off Set (OS)?

    Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the “Either” category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

    Black & White Printing

    Color Printing

    Color Printing

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Publication Number:750-IN011F-EN-PSample: 2030-SP001B-EN-P11” x 17”LOOSE -Loose LeafYESPre-sale / MarketingTOP

    Use Legacy Number:NOYES or NO8.5” x 11”PERFECT - Perfect BoundA1LEFT

    Legacy Number if applicable:Sample Legacy Number: 0160-5.338.375” x 10.875SADDLE - Saddle StitchA2RIGHTCORNER

    Publication Title:PowerFlex 750-Series Power JumpersSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25” x 11” (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Used in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25” x 10.875”STAPLED1 -1 positionA3

    Part Number:PN-448244If SAP Part Number, be sure to enter PN- before the number7.385” x 9” (RSI Std)STAPLED1B - bottom 1 positionA5

    (required) CategoryD5Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6” x 4”STAPLED2 - 2 positionsA6

    Paper Stock Color:White is assumed. For color options contact your vendor5.5” x 8.5” (half-size)THERMAL - Thermal bound (Tape bound)A7

    Ink Color:One color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75” x 7.75”THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count ofPublication:8Total page count including cover. Enter PAGE count, not SHEET count4.75” x 7” (slightly smaller half-size)A9

    (required) Finished Trim Size Width:8.5” x 11”This is sheet size, before folding4.25" x 5.50"Post Sale / Technical Communication

    Fold:NoneReview key below. Leave blank if folded for saddle stitching4” x 6”B1

    Finished Fold Size:This is size after folding is completed3” x 5”B2

    Binding/Stitching:SADDLE - Saddle StitchReview key below9” x 12” (Folder)B3None

    Stitching Location:SIDEBlank, Corner or SideA4 (8 ¼” x 11 ¾”) (210 x 297 mm)B4Half or V or Single Fold

    Drill Hole (Yes/No):NOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of ¼ inch from the inner page border.A5 (5.83” x 8.26”) (148 x 210 mm)B5C or Tri-Fold

    Number of Tabs Needed:5 tab in stock at RR Donnelley36” x 24” PosterCatalogsDbleParll

    Number of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24” x 36” PosterC1Sample

    Glue Location on Pad:Glue location on pads18” x 24” PosterC2Short (must specify dimensions between folds in Comments)

    (required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold

    (required) Cost Center:19134 - Power CIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

    Comments:D2Double Gate

    FoldsHalf, V, Single C or Tri

    Dble Parll

    Z or Accordian Microfold or French

    Double Gate

    Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

    Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

    Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

    Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3

    D4

    D5

    D6

    D7

    D8

    D9

    MBD000B0209.bin

    MBD000B020B.bin

    MBD000B020C.bin

    MBD000B020A.bin

    MBD000B0205.bin

    MBD000B0207.bin

    MBD000B0208.bin

    MBD000B0206.bin

    MBD000B0203.bin

    MBD000B0204.bin

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice