Upload
adewole-adeyemi-charles
View
214
Download
0
Embed Size (px)
Citation preview
7/31/2019 POWERAFRICA2012_adewole_ID25
1/8
IEEE PES PowerAfrica 2012 Conference and Exhibition
Johannesburg, South Africa, 9-13 July 2012
Fault Detection and Classification in a Distribution Network Integrated with
Distributed Generators
A.C. Adewole and R. TzonevaCentre for Substation Automation and Energy Management Systems
Cape Peninsula University of Technology, Cape Town, South Africa
Phone: +27 021-959-6459, Email: [email protected]
Abstract This paper develops a methodology for application indistribution network fault detection and classification. The
proposed methodology is based on wavelet energy spectrumentropy decomposition of disturbance waveforms to extractcharacteristic features by using level-4 db4 wavelet coefficients.Thus, few input features are required for the implementation.
Different simulation scenarios encompassing various fault types atseveral locations with different load angles, fault resistances, faultinception angles, and load switching are applied to the IEEE 34
Node Test Feeder. In particular, the effects of system changeswere investigated by integrating various Distributed Generators
(DGs) into the distribution feeder. Extensive studies, verification,and analysis made from the application of this technique validatethe approach. Comparison with statistical methods based onstandard deviation and mean absolute deviation has shown thatthe method based on log energy entropy is very reliable, accurate,and robust.
Index Terms Discrete wavelet transform, distribution network,fault detection and classification, wavelet energy spectrum.
1.INTRODUCTION
The recent restructuring in electric power utilities over the
last decade has brought about the need for efficientgeneration and transfer (transmission and distribution) ofelectric power to load centers. The mode of power evacuation
is usually via overhead lines. Overhead lines are subject to
the forces of nature and other uncontrollable factors, thus
liable to faults.
An essential aspect of Abnormal Event Management
(AEM) is fault detection and diagnosis. In the past, most
research and development in power system faults detection
and diagnosis focused on transmission systems, and it is notuntil recently with the introduction of stringent fault indices
by regulatory bodies that research on power system faults hasbegun on the unique aspects of distribution networks. The
application of algorithms designed for transmission networkswhen used for distribution lines are prone to errors because of
the non-homogeneity, presence of laterals/tap-offs, radial
operation, and load taps along distribution lines. Therefore,
there is the need for contingency plans to troubleshoot faults
and expedite service restoration in order to reduce downtime.
Many diagnostic methods have been developed andproposed, but a perfect, dependable, and secure method is
still the objective of continuous research. Methods based on
Wavelet Transform (WT) for fault diagnosis were proposed
by [1]-[6]. Reference [7] proposed a method for fault
detection and classification in transmission systems using
wavelet and fuzzy logic. Similarly, [5], [8], [10] suggested
techniques using WT and Artificial Neural Network (ANN)
for transmission line fault detection and classification.
Another technique based on WT and Support Vector Machine(SVM) was proposed by [11] for power system disturbance
classifier in transmission systems. Reference [12] presented a
methodology for the classification of Power Quality (PQ)
disturbances using Wavelet Packet Transform (WPT) andfuzzy k-nearest neighbor classifier. A method by [13] for PQ
disturbances was based on Discrete Wavelet Transform
(DWT) and wavelet network. Reference [14] also presented a
WT and rule based method for power quality classification in
a transmission network. A method based on Hubbard-
Stratonovich (HS) transform and radial basis function neuralnetwork was suggested by [15]. Reference [16] described a
method for fault detection and classification based on WT
decomposition of the transformed current values. The method
suggested the use of wavelet entropies for multi-agent fault
diagnosis in distribution networks.
Although, the method by [15] is fast because of the
reduction in the computational requirements, the use of level-1 coefficients may fail to provide the appropriate transientcharacteristics that truly represent the fault type/phase(s)
especially where there is mutual coupling between the
phases. Also, the technique described by [14] did not cover
the effect of noise disturbance on the model. The method
proposed by [16] made use of Clarks Transform to convert
the three phase current measurements to modal domain. The
disadvantage of this is the added computation that would be
required during implementation. In addition, the effects ofload angle, load switching, and capacitor switching were not
considered in the various literature reviewed.In this paper, wavelet energy spectrum entropy based on
log energy is employed to detect and classify faults in atypical distribution network. This is implemented by taking
into account the distinct nature of distribution networks and
network changes that are likely to occur. To validate the
proposed approach, extensive simulation studies are carried
out on the IEEE 34 Node Test Feeder Benchmark model at
different fault locations, fault resistances, fault inceptionangles, load angle variations, load and capacitor switching,
and network topology changes.
7/31/2019 POWERAFRICA2012_adewole_ID25
2/8
The rest of this paper is organized as follows: Section II
explains the principles of Wavelet Transform. Section III
describes the Power System Model. The implementation of
the fault detection and classification algorithm is outlined in
section IV. Section V provides the results and discussion ofthis approach. Section VI summarizes the conclusion.
II. WAVELET TRANSFORM ANALYSIS
A. Wavelet Transform
The classical Fourier Transform (FT) is a frequency
domain method. That is, it transforms a signal from time-
based to frequency-based one. Thus, time information is lost
and it is impossible to tell when an event took place. Short
Time (STFT) was introduced to correct the shortcoming of
the FT. However, a fixed time window is used. Many signalsrequire a more flexible approach where the window size can
be varied to determine the frequency or time more accurately.
A method such as WT capable of multiple resolutions in time
and frequency and with a flexible window size is thereby
required. The windowing in WT automatically uses short
time intervals for high frequency components and long time
intervals for low frequency components by using scale and
shift techniques.WT can be implemented using the Continuous Wavelet
Transform (CWT). The CWT of a signal )(tx is the integral of
the product between )(tx and the daughter-wavelets, which
are the time translated and scale expanded/compressed
versions of a function having finite energy, called mother-
wavelet.
The CWT of a signal )(tx is defined as [17], [18]:
dta
bttx
abaC
+
= )(
1),( (1)
where )(t is the mother wavelet, a is the scale factor, b is
the translation factor (position along the time axis), a2/1 is
the normalization value of )(,t
ba so that if )(t has a unit
length, then its scaled version )(,t
ba would also have a unit
length.
Another variant of WT is DWT. One area in which the
DWT has been particularly successful is transient analysis in
power systems [1], [2], [19]. This is because it acquires the
transient features and accurately analyzes them in both thetime and frequency contexts at different frequency bands with
different resolutions.
The mathematical expression for DWT is given by [17-20]:
=
km
m
m
knkfnmDWT
2
2)(
2
1),( (2)
where )(kf is a discrete signal,)(n is the mother wavelet
(window function), m and n are time scale parameters, k is
the number of coefficients, 2
m is the variable for scale, 2km
is the variable for shift, and 21m is the energy normalization
component to ensure the same scale as the mother wavelet.
In implementing Multi-Resolution Analysis (MRA) for
DWT, the scaling and wavelet functions are obtained from
[21], [22].
)22)( (
)2/(
,ntt
mm
nm
= (3)
)22)( (
)2/(
,ntt
mm
nm
= (4)
where )(, tnm is the scale function, and )(, tnm is the wavelet
function.
Wavelets are localized in both time (through translation)
and frequency (through dilation). The first scale covers a
broad frequency range at the high frequency end of the
spectrum and the higher scales cover the lower end of the
frequency spectrum. Signal decomposition starts by passing
the signal through a set of filters. Approximations are the
high-scale, low-frequency components of the signal producedby filtering with a low-pass filter with coefficient vector )(h
.The details are the low-scale, high-frequency components of
the signal produced by a high-pass filter with coefficient
vector )(g .
The filters are given by [22]:
)2(2)()( ntngt
n
= (5)
)2(2)()( ntnht
n= (6)
After each level of decomposition, the sampling frequency is
reduced by half. Then, the lowpass filter output
(approximation) is decomposed to produce the components ofthe next level. The original signal sequence )(kf can also be
represented by the sum of all components i.e the sum of all
the details and the approximation at the last level of
decomposition. For example, for two levels of
decomposition, the representation is:
)()()()()()(22111kcAkcDkcDkcAkcDkf ++=+=
)()()(1
kcAkcDkf l
l
jj
+==
(7)
where cDj
is the detail at scale j and cAl
is the approximation
at scalej, and l= 2.
B. Feature Extraction
Fault signals are known to contain transients and
harmonics. These high-frequency components carry essential
information that could be used to identify fault orabnormalities in power system network. The energy of
wavelet coefficient varies over different scales as per the
7/31/2019 POWERAFRICA2012_adewole_ID25
3/8
energy distribution in the signal. Wavelet energy is the sum
of the square of WT coefficients.
The wavelet energy of a signal at scale jand instant k is
given as [23]-[25]:
)(
2
kDjEjk=
(8)
At scale j , the instants = 1, 2, 3, ..., N
The log energy entropy of the signal at scale j is:
=k
jkEEj EW log(9)
Standard Deviation is a statistical measure of distribution
or spread in a data set and it is derived from the square root of
the variance in a data set. Mean Absolute Deviation (MAD)is the mean of the absolute deviations of the data set from the
mean of the data. It shows the statistical dispersion of a dataset.
The standard deviation of the signal at scale j , instants k is:
( )= =N
k
jkj jDN 1
221
)(1
1
(10)
Similarly, the Mean Absolute Deviation of a signal is givenas:
=
=N
k
jjkDN
MAD1
1 (11)
whereDjk is the detail coefficient at scale j , instant k , j is
the mean at scale j , and N is the number of instants.
III. POWER SYSTEM MODEL
A. Base Case IEEE 34 Node Test Benchmark Feeder
The distribution network used is the IEEE 34 Node Test
Feeder. It is a long feeder operated at 60Hz with unbalanced
loading and nominal voltage of 24.9 kV. Fig. 1 shows the
IEEE 34 Node Test Feeder.
Fig. 1. IEEE 34 Node Test Feeder.
Simulation of the power system was carried out using
DIgSILENT PowerFactory and the steady state load flow
results were validated with the results from IEEE 34 nodebenchmark system in [26]. The relative error of the node
phase voltages is shown in Table 1.
Table 1. Node Voltage Relative Error vs. [26]
Dynamic electromagnetic transient simulation of differentfault types involving Single Phase-to-ground (1 Ph.-g), two
Phase (2 Ph.), two phase-to-ground (2 Ph.-g), and three phase
(3 Ph.) faults were performed. These simulations were carried
out at different locations at an interval of 10% along the main
feeder, at 95% of the main feeder, and on the laterals. Faultresistances )(Rf of 0, 2.5, 5, 10, 20, and 100, and
fault inception angles (fa) of 0o, 30o, 45o, 60o, and 90o were
used in the simulations. The fault inception angle fa is thephase angle of phase A voltage at the fault inception time.
Simulations were done to discriminate between transients due
to switching conditions from load and capacitor switching.Load angle variations of 0o, 60o, 90o were also carried out.
The waveforms were generated with a sampling rate of 128
samples per cycle.
B. Modified IEEE 34 Node Test Benchmark Feeder
Three cases which involved the integration of Distributed
Generators (DGs) into the benchmark model were studied inthis paper. These include:
DG1 case study: maximum load + 20% of DG
installed at node 840
DG2 case study: maximum load + 20% of DG
installed at node 844
DG3 case study: maximum load + 10% of DGs
installed at node 840 and 844 respectively.
Distributed generation refers to the electric power
generation (usually between 5kW and 10MW) at theconsumption end of a distribution network. The generated
power is integrated to the distribution network at the
substation, feeder, or customer load levels [27]. DGs can be
implemented with wind turbine, hydro, PV, fuel cells, etc.
The integration of DGs into a distribution network often
causes protection coordination issues [28].
Case studies involving the integration of DGs into the IEEE
34 node test feeder were carried out to investigate the abilityof WT based log energy entropy to correctly detect and
classify faults even after DGs were integrated.
Relative Error
(%)
Phase A Phase B PHASE C
Minimum -5.2032 -1.5586 -0.2325
Maximum
Average
-0.0307
3.1509
1.2722
0.7719
2.3210
0.8746
7/31/2019 POWERAFRICA2012_adewole_ID25
4/8
The studies carried out in this paper did not assign any
specific energy source to the DG. Also, the parameters of the
synchronous generators were based on previous work carried
out by [28]. The connection of the generator to the grid was
via a 500kVA step-up transformer. The transformerimpedances were also set equal to the transformer at node
832 (XFM-1).However, the transformer winding was changed to delta-
star type based on the recommendations by [27] on optimal
transformer winding types for DGs. The placement and sizing
of the DGs were based on [28]-[31]. Thus, node 840 (along
the main line) and node 844 (one of the laterals) were used
with a 20% penetration level one at a time. Furthermore,another test case was simulated with smaller DGs co-located
in the network at nodes 840 and 844 respectively. A plot of
the voltage profile is given in Fig. 2. Similarly, a plot of the
short circuit currents at various nodes are shown in Fig. 3.
Nodes 836-1 refers to lateral 836-862, while Node 836-2
refers to lateral 836-840. The voltage profile plot shows the
impact of the integration of DG into the feeder. Also, there
was an increase in the short circuit current at various nodes inthe feeder.
Fig. 3. Voltage Profile of the various Case Studies
IV. ALGORITHM FOR FAULT DETECTION AND
CLASSIFICATION
A. Feature Extraction
Various simulations were carried out in DIgSILENT
PowerFactory. The waveform plots of the three phase andzero sequence currents were exported to MATLAB as ASCII
files. These files are decomposed into coefficients using db4
level-6.
Daubechies 4 (db4) is one of the most used wavelet in
power system disturbance analysis and it was chosen for this
research because of its orthogonality, compact support in the
time domain, and for its good performance in power system
studies as reported by [11], [12], [32], [33].
The lowpass filter )(g and highpass filter )(h of the db4
have four coefficients. These coefficients are:4830.0,8365.0,2241.0,1294.0
4321==== gggg
1294.0,2241.0,8365.0,4830.04321
==== hhhh
The particular level of decomposition to use is based on the
wavelet spectra. The log energy entropy, standard deviation,and mean absolute deviation at levels-1 to -6 were computed
using (9) - (11). Level-4 was chosen as the level of interest
for both fault detection and classification because the best
results for log energy entropy, standard deviation, and mean
absolute deviation were obtained at that level. Level-4
corresponds to the frequency range of 240Hz to 480Hz.
Fig. 4. Short Circuit Current for the various Case Studies
B. Design of Rule Based Detector and Classifier
The proposed algorithm in this paper is implemented with
software subroutines written in MATLAB. The fault
detection module is activated first and on detection of a faultcondition, the fault type and faulted phase(s) module is
triggered to perform the classification tasks. Each fault has its
characteristic feature or signature by which its faulted
phase(s) can be identified.
The fault detection module compares the computed level-4
entropy values with a predetermined threshold )(d for each
of the phases. The predetermined threshold )(d is carefully
800 810 820 830 840 850 860 870 880 8900.95
0.96
0.97
0.98
0.99
1
1.01Voltage Profile
Node
P
h.
Vab(p
.u)
DG Case 1
DG Case 2
DG Case 3
Base Case
1 2 3 4 5 6 7 8 9 100
100
200
300
400
500
600
700
800
900
1000
N-800
N-8
08
N-8
16
N-8
24
N-8
54
N-832
N-8
58
N-8
34
N-8
36-1
N-8
36-2
N = Node
Short Circuit Current for Case Studies
Nodes
MaxShortCircuitCurrent/(A)
Base Case
DG Case 1
DG Case 2
DG Case 3
7/31/2019 POWERAFRICA2012_adewole_ID25
5/8
chosen to ensure that the algorithm would be able to
accurately discriminate between faults and normal switching
events. In this particular case, da = 100, db = 100, and
dc= 100. Fault is detected when any of the computed
wavelet entropy values )(),(),( cWEEbWEEaWEE for the
three phases is greater than dp . ),,( CBAp . whereda ,
db , anddcare the entropy value thresholds for phase A, B,
and C respectively.
When fault is detected, the fault classification module is
triggered for fault type classification and faulted phase(s)
identification. The patterns observed through exhaustive
simulations were used to draw up the rules for the algorithm.
Fig. 5. is a flow chart for the implementation of this
algorithm.
The criteria for fault classification are:
R1: if )(aWEE > )(ca , & )(bWEE < )(cb & )(cWEE < )(cc
A-g FaultR2: if )(aWEE < )(ca , & )(bWEE > )(cb & )(cWEE < )(cc
B-g Fault
R3: if )(aWEE < )(ca , & )(bWEE < )(cb & )(cWEE > )(cc
C-g Fault
R4: if )(aWEE > )(ca , & )(bWEE > )(cb & )(cWEE < )(cc
AB Fault
R5: if )(aWEE < )(ca , & )(bWEE > )(cb & )(cWEE > )(cc
BC Fault
R6: if )(aWEE > )(ca , & )(bWEE < )(cb & )(cWEE > )(cc
CA Fault
R7: if )(aWEE > )(ca , & ( )(bWEE ) > )(cb & )(cWEE < )(cc
AB-g FaultR8: if )(aWEE < )(ca , & ( )(bWEE ) > )(cb & )(cWEE > )(cc
BC-g Fault
R9: if )(aWEE > )(ca , & )(bWEE < )(cb & )(cWEE > )(cc
CA-g Fault
R10: if )(aWEE > )(ca , & )(bWEE > )(cb & )(cWEE > )(cc
3Ph. Fault.
where )(),(),( cWEEbWEEaWEE are the computed level-4
log energy entropy values for phases A, B, and C. )(ca ,
)(cb , and)(cc are the fault classification thresholds for
phases A, B, C respectively and was set to 100.
2Ph. and 2Ph.-g faults were classified using the values of0IWEE . Line-to-ground faults exhibited higher zero sequence
entropy ( 0IWEE ), thus, this formed the basis for 2Ph. and
2Ph.-g classification.
Therefore, faults with values of 0IWEE > -250 will be
classified as 2 Ph.-g faults.
V. RESULTS AND DISCUSSIONS
A. Results
The proposed method was tested using several fault cases
comprising of various fault types, fault conditions, and
system parameters. In particular, the line segments at thebeginning and at the extreme end of the feeder were studied.
Initialization
Select the nextevent
3 Ph. Fault
Select level -4 detail coefficients
DWT level -6 decompositionusing db4 mother wavelet
PrintResult
No
Yes
Select 3Ph. & zerosequence currents
waveforms
dpWEEp >
WEE IWEE p 0, CBAp ,,Compute log energy entropy
Fault?
Single PhaseFault?
2 Ph. Phase Fault ?
2 Ph.-g Phase
Fault?
A-g, B-g, C-g
AB, BC, CA
AB-g, BC-g, CA-g
Yes
Fig. 5. Flowchart of the Proposed Algorithm
7/31/2019 POWERAFRICA2012_adewole_ID25
6/8
Fig. 6. Distribution Plot of 2Ph. Fault for DG1 Case Study
The effects of the following were considered: Faultresistance, fault distance, fault inception angle, and the
integration of DGs. Fig. 6. is a visualization of the
distribution or spread of 2 Ph. faults for 10% to 95% of the
main feeder, laterals 820-822, and 846-848 respectively for
DG1 case study using log energy entropy. This shows that the
fault types are quite distinguishable from one another. From
the results obtained through several simulation cases, the
faulted phase was seen to have the highest log energy
entropy. The text in bold signify the faulted phase(s).
Statistical methods have been reported to show good
performance in power system analysis [34-39]. The proposed
method based on wavelet log energy entropy is comparedwith that based on features from Standard Deviation and
Mean Absolute Deviation (MAD) of the WT decomposition.Tables 2-4 show some of the results obtained for log energy
entropy, standard deviation and mean absolute deviation
respectively.
Table 2. DG1 Case Study at 10% of the Main Feeder (Rf= 0 , f = 0o)
Method
No Fault
(0o) Load
Angle
No Fault
(60o) Load
Angle
No Fault
(90o) Load
Angle
Load
Switching
Capacitor
844
Switching
1 Ph.
A-g
2Ph.
A-B
2Ph.
A-B-g
3Ph.
)(aWEE 62.16 26.74 64.64 59.2 77.73 219.22 188.20 213.95 217.055
)(bWEE 9.76 53.38 12.03 8.42 32.71 36.65 126.39 159.20 165.31
)(cWEE
)0(IWEE
)(a)(b)(c)0(I
)(aMAD
)(bMAD
)(cMAD
)0(IMAD
47.94
-451.03
3.68
3.00
2.75
0.20
2.12
1.82
1.80
0.12
10.59
-414.94
3.42
2.87
3.12
0.23
2.08
1.87
1.77
0.14
42.45
-414.94
3.16
3.11
3.03
1.83
1.94
1.90
1.83
0.24
45.45
-474.87
3.67
2.99
2.75
0.20
2.12
1.82
2.57
0.13
38.67
-440.38
4.34
3.45
2.81
0.21
2.53
2.11
1.88
0.13
83.38
-136.23
25.86
6.54
5.87
6.83
13.55
3.52
3.17
3.62
38.16
-506.73
33.23
32.69
3.27
0.13
13.30
12.95
2.25
0.091
73.36
-132.63
27.21
51.15
11.57
20.69
13.54
19.51
5.44
8.91
229.449
-820.41
26.33
34.50
42.89
17.84
13.48
14.29
18.33
4.28
Table 3. B-C Fault at Line 846-848 (Rf= 2.5 , f=30o)
Case
Study)(aWEE )(bWEE )(cWEE )0(IWEE )(a )(b )(c )0(I )(aMAD )(bMAD )(cMAD )0(IMAD
Base
Case
19.94 154.22 170.03 -279.02 1.79 6.11 6.56 0.45 1.54 3.95 4.10 0.25
DG1 46.34 138.03 146.82 -282.16 3.52 4.85 5.16 0.13 2.17 4.88 5.48 1.93
DG2
DG3
61.89
20.01
137.41
165.35
122.88
127.53
-255.06
-282.67
3.52
3.84
4.63
4.66
4.72
4.56
0.11
0.09
2.51
2.73
3.105
3.09
2.99
2.87
0.07
0.06
Table 4. C-A-G Fault at Line 820-822 (Rf= 5 , f = 60o)
Case
Study )(aWEE )(bWEE )(cWEE )0(IWEE )(a )(b )(c )0(I )(aMAD )(bMAD )(cMAD )0(IMAD
Base
Case
188.90 21.41 194.09 -69.81 13.04 3.27 13.74 4.85 6.61 2.14 6.64 2.01
DG1 185.5 30.55 180.87 -82.18 9.76 4.11 8.86 4.24 5.46 3.00 5.04 1.78
DG2
DG3
136.9
144.4
22.69
12.99
159.07
154.47
-142.2
-165.48
9.56
8.91
4.01
2.73
8.93
9.35
3.92
0.18
5.22
4.63
2.39
1.88
4.92
5.04
1.40
0.09
B. Discussion
7/31/2019 POWERAFRICA2012_adewole_ID25
7/8
The algorithm was able to differentiate between fault events
and no fault conditions like load switching, capacitor
switching, and steady-state system operation when log energy
entropy, standard deviation, and mean absolute deviation
were used as inputs. Tables 2-4 show the results obtained atfault locations close to the upstream substation, a lateral, and
at a location 189,205 ft. away from the upstream substationrespectively. Table 2 present some of the values obtained for
fault detection at 10% of the main feeder (Line 806-808).
Tables 3 and 4 show the results for faults at various fault
inception angles and fault resistances. For all the methods
presented, the faulted phase is associated with values many
times greater than the healthy/unfaulted phase(s). For faultdetection and classification using log energy entropy, the
various fault types were quite distinguishable for all the case
studies. Furthermore, the thresholds used for the fault
detection and classification for the base case performed well
even for the DG cases without the need to review these
thresholds. Simulation plots and entropy results showed the
existence of mutual coupling in the phases especially for
faults in close proximity to the DG location. However, the
algorithm was able to accurately distinguish between the
healthy phase(s) and the faulted phase(s). Although, different
entropy values were obtained for different combination of
fault resistances and fault inception angles for the same
location, that did not affect the detection and classificationperformance since the results obtained per fault types were
apparently above the pre-defined thresholds.The values obtained for and MAD after the integration
of DGs were not completely useful for fault classification
because there were similarities between the values obtained
for faulted phase(s) in one location and the values for healthy
phase(s) at another location. Table 5 illustrates some of the
errors obtained when using and MAD. Entry 1 of Table 5was misclassified as no fault. Entry 2 was also misclassified
as A-B fault. Entries 3 and 4 were wrongly denoted as no
fault respectively. Also, the values of and MAD showed a
corresponding decrease in value for faults with high
resistances and for faults located far away from the
substation. This implies that and MAD are influenced by
fault resistance and fault location.
Table 5. Features Using Standard Deviation and Mean Absolute Deviation
CaseStudy
Location Fault
Type
Fault Parameters )(a )(b )(c )0(I )(aMAD )(bMAD )(cMAD )0(IMAD
DG1 Line 834-842 A-g Rf= 0, f= 0o 5.12 3.85 3.55 1.99 3.43 2.57 2.30 1.16
DG1 Line 834-842 B-g Rf= 0, f= 0o 9.25 10.25 4.05 4.39 5.31 4.53 2.30 1.97
Base Case Line 828-830 A-g Rf= 100, f= 0o 5.43 2.98 2.88 2.08 3.46 1.93 2.00 0.86
Base Case Line 834-842 A-g Rf= 100, f= 0o 5.35 3.39 3.35 2.67 3.34 2.17 2.21 1.02
VI. CONCLUSION
This paper proposes an accurate approach for fault
detection and classification of fault types and faulted phase(s)
in distribution networks. Various scenarios were simulatedusing DIgSILENT PowerFactory. DWT was implemented in
MATLAB to decompose the three phase and zero sequence
current waveforms using db4 level-4 detail coefficients. A
rule based method was used afterwards for fault detection and
classification tasks respectively. It was observed that the
proposed method based on wavelet log energy entropy
accurately detects and classify the fault type. Comparisons
with statistical feature extraction methods based on
computation of standard deviation and mean absolutedeviation of the WT decomposition show that the method
based on log energy entropy is very reliable, accurate, robust,
and is independent of system conditions/changes. That is, it
provided accurate results irrespective of load angle variation,
load and capacitor switching, and network topology changes.
It is also immune to varying fault location, fault resistance,
and fault inception angles. It has been shown to be suitable
for conventional distribution network as well as modified
network with DGs. As a result of its simplicity, accuracy andspeed of operation, it can be used to aid existing protection
equipment in fault diagnosis.
ACKNOWLEDGEMENT
This research work is funded by the South African
National Research Foundation (NRF) UID62364 Substation
Automation and Energy Management Systems.The authors
are grateful for the financial support.
REFERENCES
1 Z.G. Bo, A.T. Johns, and R.K. Aggarwal, R.K., A Novel Fault Locator basedon the Detection of Fault Generated High Frequency Transients.Developments in Power System Protection, IEE Conference Publication, No.
434. pp. 197-200. 25-27th Mar. 1997.
2 Z.Q. Bo, G. Weller, and M.A. Redfern, Accurate fault location technique fordistribution system using fault-generated high-frequency transient voltagesignals.IEE Proceedings of Generation, Transmission, and Distribution, Vol.
146, No. 1, pp. 73-79, Jan. 1999.
3 A.M. Gaouda, M.M.A. Salaina M.K. Sultan, and A.Y. Cliildiaoi, PowerQuality Detection and Classification using Wavelet-Multiresolution Signal
Decomposition. IEEE Transactions on Power Delivery, Vol. 14, No. 4, pp.1469-1476, Oct.1999.
7/31/2019 POWERAFRICA2012_adewole_ID25
8/8
4 A. Abur, and F.H. Magnago, Use of time delays between modalcomponents in wavelet based fault location Electrical Power and
Energy Systems,No. 22, pp. 397403, 2000.
5 K. Gayathri, N. Kumarappan, and C. Devi, An Apt method for FaultIdentification and Classification on EHV Lines using Discrete Wavelet
Transform. Power Engineering Conference IPEC, Singapore, pp. 217-
222, 3-6 Dec., 2007.
6 O.A.S. Youssef, Combined Fuzzy-Logic Wavelet-Based FaultClassification Technique for Power System Relaying.IEEE Transactions
on Power Delivery, Vol. 19, No. 2, pp. 582-589. 2004.
7 R.N. Mahanty, and P.B. Dutta Gupta, A fuzzy logic based faultclassification approach using current samples only. Electric Power
Systems Research, No. 77, pp. 501507, 2007.
8 K.M. Silva, B. A. Souza, and N.S.D. Brito, Fault Detection andClassification in Transmission Lines based on Wavelet Transform andANN.IEEE Transactions on Power Delivery, Vol. 21, No. 4, pp. 2058-
2063, 2006.
9 V.S. Kale, S.R. Bhide, P.P. Bedekar and G.V.K. Mohan, Detection andClassification of Faults on Parallel Transmission Lines using WaveletTransform and Neural Network. World Academy of Science, Engineering
and Technology, No. 46, pp. 927-931, 2008.
10 M. Geethanjali, M. and K. Sathiya Priya, Detection and Classification inTransmission Lines. International Conference on Control, Automation,
Communication and Energy Conservation, pp. 1-7, 4-6 June, 2009.11 S. Ekici, S. Yildirim, M. Poyraz, Energy and entropy-based feature
extraction for locating fault on transmission lines by using neural network
and wavelet packet decomposition, Expert Systems with Applications,No.34, pp. 29372944, 2008.
12 B.K. Panigrahi and V.R. Pandi, Optimal feature selection forclassification of power quality disturbances using wavelet packet-based
fuzzy k-nearest neighbor algorithm IET Generation, Transmission,Distribution, Vol. 3, Iss. 3, pp. 296306, 2009.
13 M.A.S. Masoum, S. Jamali, N. Ghaffarzadeh, Detection andclassification of power quality disturbances using discrete wavelet
transform and wavelet networks. IET Science, Measurement,
Technolology. Vol. 4, Iss. 4, pp. 193205, 2010.
14 H.K. Chuah, P. Nallagownden, and K.S. Rama Rao, Power QualityProblem Classification Based on Wavelet Transform and a Rule-Based
method. IEEE International Conference on Power and Energy (PECon2010), Kuala Lumpur, Malaysia, pp. 1-6, Nov 29 - Dec 1, 2010.
15 S.R. Samantaray, P.K. Dash, G. Panda, Fault classification and locationusing HS Transform and radial basis function neural network, Electric
Power Systems Research, No. 76, pp. 897905, 2006.
16 El-Zonkoly A.M. Fault Diagnosis in Distribution Networks withDistributed Generation, Smart Grid and Renewable Energy, pp. 1-11,
February 2011.
17 M. Vetterli and C. Herley. Wavelets and Filter Banks: Theory andDesign.IEEE Transactions on Signal Processing. Vol. 40, No. 9, pp.
2207-2232, Sep. 1992.
18 A. Borghetti, S. Corsi, C.A. Nucci, M. Paolone, L. Peretto, and R.Tinarelli, On the use of continuous-wavelet transform for fault location
in distribution power systems. Electrical Power and Energy Systems,
No. 28, pp. 608617, 2006.
19 A.S. Yilmaz, A. Subasi, M. Bayrak, V. M. Karsli, E. Ercelebi,
Application of lifting based wavelet transforms to characterize powerquality events. Energy Conversion and Management, No. 48, pp. 112
123, 2007.
20 S. Ekici, S. Yildirim,M. Poyraz, A transmission line fault locator basedon Elman recurrent networks. Applied Soft Computing, pp.341347,
2009.
21 S. Burrus, R.A. Gopinath, and H. Guo, Introduction to Wavelet andWavelet Transform: A Primer.Prentice-Hall, 1998.
22 J.C. Goswami, and A.K. Chan, Fundamental of Wavelets: Theory,Algorithms and Application.John Wiley & Sons, 1999.
23 H. Zhengyou, F. Ling, L. Sheng, and B. Zhiqian, Fault Detection andClassification in EHV Transmission Line Based on Wavelet Singular
Entropy. IEEE Transactions on Power Delivery, Vol. 25, No. 4, pp.2156-2163, 2010.
24 H. Zhengyou, H.E. Shibin, G. Xiaoqin, C., Jun, Z., Zhiqian, and Q.Qingquan, Study of a new method for power system transients
classification based on wavelet entropy and neural network. Electrical
Power and Energy Systems, Vol. 33, pp. 402410, 2011.
25 A.M. El-Zonkoly, Fault diagnosis in distribution networks withdistributed generation. Electric Power Systems Research Vol. 81, pp.
14821490, 2011.
26 IEEE Distribution System Analysis Subcommittee. Radial Test Feeders[Online]. Available:
http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.html .
27 P. Barker, R.W. de Mello, Determining the impact of distributedgeneration on power systems: part 1 Radial power systems. In Proc.
IEEE Power Eng. Soc. Summer Meeting, Vol. 1, pp. 16451658, 2000.
28 J.A. Silva, H.B. Funmilayo, and K.L. Butler-Purry, Impact of DistributedGeneration on the IEEE Node Radial Test Feeder with OvercurrentProtection.Proceedings of 39thNorth American Power Symposium. pp.
49-57, 2007.
29 R.C. Dugan and W.H. Kersting, Induction machine test case for the 34-bus test feeder-description. IEEE Power Engineering Society General
Meeting, pp. 1-4, 2006.30 S. Santoso, and Z. Zhou, Induction machine test case for the 34-bus test
feeder: a wind turbine time domain model. IEEE Power Engineering
Society General Meeting, pp. 1-4, 2006.
31 N. Samaan, T. McDermott, B. Zavadil, and J. Li, Induction machine testcase for the 34-bus test feeder-steady state and dynamic solutions.IEEE
Power Engineering Society General Meeting, pp. 1-5, 2006.
32 N. Perera, and A.D. Rajapakse, Power system transient classification forprotection relaying. 13th International Conference on Harmonics andQuality of Power, ICHQP, pp. 1 6, 2008.
33 F. B. Costa, B. A. Souza, and N. S. D. Brito, Real-time detection of fault-induced transients in transmission lines,IET Electronics Letters, pp. 753-
755, May 2010.
34 P.K. Dash, M.V. Chilukuri, B.K. Panigrahi, Power Quality Analysis and
Classification using a Generalized Phase Corrected Wavelet Transform.Power Electronnics, Machines and Drives, Conf Pub No. 487, pp.610-
615, 16-18 April, 2002.
35 P. K. Dash, B. K. Panigrahi, and G. Panda, Power Quality AnalysisUsing STransform.IEEE Transactions on Power Delivery, vol. 18, No.
2pp. 406-411, April 2003.
36 W. Kanitpanyacharoean, S. Premrudeepreechacharn. Power QualityProblem Classification using Wavelet Transformation and Artificial
neural Network IEEE PES Power Systems Conference and Exposition,
vol. 3, pp. 1496-1501. 2004.
37 G.G. Pozzebon, G.G. Pena, A.F.Q Goncalves, R.Q. Machado, NeuralClassification of Power Quality Disturbances: An Application of the
Wavelet Transform and Principal Component Analysis 9 th IEEE/IAS
International Conference on Industry Applications (INDUSCON), pp. 1-6.
2010.
38 C. Venkatesh, D.V.S.S Siva Sarma, M. Sydulu, Classification of voltagesag, swell and harmonics using S-transform based modular neuralnetwork 14thInternational Conference on Harmonics and Quality of
Power (ICHQP),pp. 1-7, 2010.
39 J. Christy X. Jeno Vedamani S. Karthikeyan , Wavelet Based Detectionof Power Quality Disturbance - A Case Study. Proceedings of 2011
International Conference on Signal Processing, Communication,
Computing and Networking Technologies (ICSCCN 2011) pp. 157-162,2011.
http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.htmlhttp://ieeexplore.ieee.org/search/searchresult.jsp?searchWithin=Authors:.QT.Perera,%20N..QT.&newsearch=partialPrefhttp://ieeexplore.ieee.org/search/searchresult.jsp?searchWithin=Authors:.QT.Rajapakse,%20A.D..QT.&newsearch=partialPrefhttp://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=4662486http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=4662486http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.htmlhttp://ieeexplore.ieee.org/search/searchresult.jsp?searchWithin=Authors:.QT.Perera,%20N..QT.&newsearch=partialPrefhttp://ieeexplore.ieee.org/search/searchresult.jsp?searchWithin=Authors:.QT.Rajapakse,%20A.D..QT.&newsearch=partialPrefhttp://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=4662486