POWER SYSTEM PROTECTION AND RECENT TRENDS

BYBY

J DAKSHINA MURTHYJ DAKSHINA MURTHY

SENIOR CONSULTANT, ESCISENIOR CONSULTANT, ESCI

&&

FORMER CHIEF ENGINEER,FORMER CHIEF ENGINEER,

AP TRANSCO, HYDERABADAP TRANSCO, HYDERABAD

Page 2: Power System Protection & Recent Trends by Jdm - Latest

Developments in Relay Technology

• Till 1980 Electromagnetic Relays

• 1980 – 1986 Static Relays

• 1986 – 1990 Microprocessor based relays

• 1990 Numerical relays

Page 3: Power System Protection & Recent Trends by Jdm - Latest

Solid State Relays

• Input quantities adjusted to levels suitable for Input quantities adjusted to levels suitable for electronic circuits.electronic circuits.

• Current signals converted to voltage signals.Current signals converted to voltage signals.

• Decision taken based on rectified DC quantities.Decision taken based on rectified DC quantities.

Page 4: Power System Protection & Recent Trends by Jdm - Latest

Solid State Relays:

• These are semiconductor devices composed of These are semiconductor devices composed of electronic components like resistors, diodes , electronic components like resistors, diodes , transistors etc. transistors etc.

• No moving parts No moving parts

• Lighter and smaller than electromagnetic relaysLighter and smaller than electromagnetic relays

Page 5: Power System Protection & Recent Trends by Jdm - Latest

Solid State Relays:

• Perform the same function as electromagnetic relays Perform the same function as electromagnetic relays except that they need less voltage to operate except that they need less voltage to operate

• Switching can be performed in very short times Switching can be performed in very short times

• Affected by transients, which, if present in the inputs, Affected by transients, which, if present in the inputs, may cause them to malfunctionmay cause them to malfunction

Page 6: Power System Protection & Recent Trends by Jdm - Latest

Solid State Relays:

• Reliable but electronic components may drift due to Reliable but electronic components may drift due to high ambient temperature and aginghigh ambient temperature and aging

• Energize trip circuits using electronic devices such as Energize trip circuits using electronic devices such as silicon control rectifiers. Hence no arcing during silicon control rectifiers. Hence no arcing during switching switching

• Switches in solid state relays have leakage currents Switches in solid state relays have leakage currents irrespective of the fact whether the switches are open irrespective of the fact whether the switches are open or closed or closed

Page 7: Power System Protection & Recent Trends by Jdm - Latest

Digital Relays

• Filtered signals converted to Square waves

• Evaluation is done based on Phase Angle Comparison

• Either discrete logics or Microprocessors are used

Page 8: Power System Protection & Recent Trends by Jdm - Latest

Digital Relays:

Power system protection has changed a lot since the Power system protection has changed a lot since the

evolution of microprocessorsevolution of microprocessors

Very large integration made it possible to put togetherVery large integration made it possible to put together

numerous components in a single chip numerous components in a single chip

Today, digital techniques are implemented to protect Today, digital techniques are implemented to protect all components of power systemall components of power system

Basically, digital techniques use the same logic that is Basically, digital techniques use the same logic that is used in electromechanical and solidused in electromechanical and solid state relays state relays

Page 9: Power System Protection & Recent Trends by Jdm - Latest

Digital Relays have many advantages over

electromechanical relays :

• Economical : : Major reason for the acceptance of Major reason for the acceptance of digital relays is that they present many features at digital relays is that they present many features at reasonable price.reasonable price.

• Fast operation : There are two reasons for their fast There are two reasons for their fast operation. One, digital relays barely use any operation. One, digital relays barely use any mechanical parts. Two, the use of high speed mechanical parts. Two, the use of high speed processors have made these relays very fast.processors have made these relays very fast.

Page 10: Power System Protection & Recent Trends by Jdm - Latest

• Self- Monitoring : Monitor themselves continuously, : Monitor themselves continuously, whereas electromechanical relays must be tested by whereas electromechanical relays must be tested by personnel at regular intervals. Self- Monitoring personnel at regular intervals. Self- Monitoring feature saves time as well as moneyfeature saves time as well as money

• Multiple Features : Relays, Meters, Control : Relays, Meters, Control Switches, Indicators and Communication devices can Switches, Indicators and Communication devices can be integrated into a single microprocessor based be integrated into a single microprocessor based protective relay. Substation / System schematics and protective relay. Substation / System schematics and wiring diagrams are easy to generate due to reduced wiring diagrams are easy to generate due to reduced number of devices and related wiringnumber of devices and related wiring

Page 11: Power System Protection & Recent Trends by Jdm - Latest

• Reduced Commissioning Time : Microprocessor based relays have metering features and remote capabilities which make commissioning simple and less time consuming

• Less Outage Time : Fast operation and fault location capability of microprocessor based relays for transmission line protection reduce the power outage time considerably. When relays, without a fault locator capability, detect a fault, crew spends a lot of time in finding the location of the fault by patrolling the line.

Page 12: Power System Protection & Recent Trends by Jdm - Latest

• Flexibility : Digital relays can be designed and built using general purpose hardware . A relay can be used to protect different power system components by loading different software programs

• Small Size : Digital relays are lighter in weight and need less space than the electromechanical and solid state relays. East to transport.

• Easy Replacement : Due to economical advantage,

digital relays, if fail it can be replaced in full. This saves time and labor needed for repairs

Page 13: Power System Protection & Recent Trends by Jdm - Latest

Numerical Relays :

• Signals are filtered using an Anti – aliasing filterSignals are filtered using an Anti – aliasing filter

• Sampled signals are converted to numerical values atSampled signals are converted to numerical values at

each sampling point each sampling point

• Calculations are carried out in real time using one or Calculations are carried out in real time using one or

several microprocessors several microprocessors

Page 14: Power System Protection & Recent Trends by Jdm - Latest

Numerical Relay

Structure of numerical relays:Structure of numerical relays:

A numerical relay consists of the following main A numerical relay consists of the following main subsystems:subsystems:

• MicroprocessorMicroprocessor

• Analog input systemAnalog input system

• Digital output system Digital output system

• Power supplyPower supply

Page 15: Power System Protection & Recent Trends by Jdm - Latest

Block Diagram of a Typical Numerical Relay

Page 16: Power System Protection & Recent Trends by Jdm - Latest

Numerical relays operate on sampled signals and Numerical relays operate on sampled signals and adopt digital computations. Sampling is the process adopt digital computations. Sampling is the process of converting analog input signals, such as current of converting analog input signals, such as current and voltage, into digital input signals. These analog and voltage, into digital input signals. These analog input signals, in case of electromechanical and static input signals, in case of electromechanical and static relays, are directly fed into the electromagnetic relays, are directly fed into the electromagnetic winding or electronic circuits. In order to protect the winding or electronic circuits. In order to protect the relay from large transients of the input signals a relay from large transients of the input signals a surge filter is used.surge filter is used.

Page 17: Power System Protection & Recent Trends by Jdm - Latest

An anti-aliasing filter is used to avoid possible errors An anti-aliasing filter is used to avoid possible errors in reconstructing input signal carried out after the in reconstructing input signal carried out after the A/D Sample / Hold section. Any signal having A/D Sample / Hold section. Any signal having harmonic components of order Nharmonic components of order N±1, 2N ±1, ….., x N ±1, 2N ±1, ….., x N ±1, where N is the number of samples per cycle, can ±1, where N is the number of samples per cycle, can exhibit aliasing. Perfectly, an anti-aliasing filter has exhibit aliasing. Perfectly, an anti-aliasing filter has to cut off all signal components above the Nyquist to cut off all signal components above the Nyquist rate of N/2. In practical, however, such a filter can rate of N/2. In practical, however, such a filter can not cut off all out of band frequencies, so the anti-not cut off all out of band frequencies, so the anti-aliasing filter cut off frequency is set at about N/3.aliasing filter cut off frequency is set at about N/3.

Page 18: Power System Protection & Recent Trends by Jdm - Latest

The A/D converts the sample values that represent the The A/D converts the sample values that represent the analog input signals into the digital input signals. analog input signals into the digital input signals. However, the conversion is not instantaneous, and for However, the conversion is not instantaneous, and for this reason, the A/D system typically includes a this reason, the A/D system typically includes a sample-and-hold circuit. The sample-and-hold circuit sample-and-hold circuit. The sample-and-hold circuit provides ideal sampling and holds the sample values provides ideal sampling and holds the sample values for quantization by the A/D converter.for quantization by the A/D converter.

The microprocessor containing the relay algorithm is The microprocessor containing the relay algorithm is the controller of the numerical relay. The the controller of the numerical relay. The microprocessor most often performs all control, microprocessor most often performs all control, computation, self-test and communication function. computation, self-test and communication function. The algorithm functions as a digital filter to extract The algorithm functions as a digital filter to extract the fundamental component of the input signal, based the fundamental component of the input signal, based on which the relay operation is carried out.on which the relay operation is carried out.

Page 19: Power System Protection & Recent Trends by Jdm - Latest

The signal from the digital filter is compared with the pre-The signal from the digital filter is compared with the pre-set threshold in the digital output system. The relay set threshold in the digital output system. The relay operation is decided based on this comparison.operation is decided based on this comparison.

Relay algorithmRelay algorithmThe algorithm is designed to remove as much as possible all The algorithm is designed to remove as much as possible all of unwanted components from the input signals such as of unwanted components from the input signals such as harmonic, DC, etc. Two common algorithms, the Discrete harmonic, DC, etc. Two common algorithms, the Discrete Fourier Transform (DFT) and the Root Mean Square (RMS) Fourier Transform (DFT) and the Root Mean Square (RMS) algorithm are generally used.algorithm are generally used.

Page 20: Power System Protection & Recent Trends by Jdm - Latest

The DFT can extract any frequency from the signal. Since The DFT can extract any frequency from the signal. Since the DFT is capable of rejecting everything except the the DFT is capable of rejecting everything except the frequency being measured, it has a good response to frequency being measured, it has a good response to transient overshoot.transient overshoot.

Root Mean Square (RMS)Root Mean Square (RMS)The Root Mean Square is a method of calculating the The Root Mean Square is a method of calculating the magnitude of a periodically varying quantity. It can be magnitude of a periodically varying quantity. It can be calculated for a series of discrete values or for a calculated for a series of discrete values or for a continuously varying function.continuously varying function.

Page 21: Power System Protection & Recent Trends by Jdm - Latest

Numerical Technique – Advantages

Analogue Technique Numerical Technique

• More complex hardwareMore complex hardware Simple hardware Simple hardware• Slowly DecreasingSlowly Decreasing Abruptly Decreasing Abruptly Decreasing

accuracy accuracy performance performance• Difficult to modifyDifficult to modify Simple to modify Simple to modify• Simple to verify Simple to verify Difficult to verify Difficult to verify • Data manipulationData manipulation Data manipulation Data manipulation

difficultdifficult simple simple• Data storage difficultData storage difficult Data storage simple Data storage simple• Self Supervision difficultSelf Supervision difficult Self Supervision simple Self Supervision simple

Page 22: Power System Protection & Recent Trends by Jdm - Latest

Numerical Technique – Advantages

• Less spaceLess space Better functionality Better functionality• Less wiring Less wiring Adaptive functions Adaptive functions• Less terminations Less terminations Better performance Better performance • Less componentsLess components Savings in civil works Savings in civil works• Less aging problemsLess aging problems Savings in erection, Savings in erection, • Self Supervision Self Supervision cabling and commissioning cabling and commissioning• Communication Communication Savings in maintenance Savings in maintenance • Greater flexibility Savings in cost/functionGreater flexibility Savings in cost/function

Page 23: Power System Protection & Recent Trends by Jdm - Latest

POWER TRANSFORMER PROTECTION

Page 24: Power System Protection & Recent Trends by Jdm - Latest

General ratings of Power transformers used.

1. 400/220 KV 315 MVA Auto Transformers

2. 220/132 KV 100MVA Auto Transformers

3. 220/33 KV 50 & 31.5MVA Transformers

4. 132/66 KV 40 & 27.5MVA Transformers

5. 132/33 KV 50, 31.5, 25, 16, 15 MVA Transformers

6. 132/11 KV 16, 15 & 7.5 MVA Transformers

7. 33/11 KV 8, 5, 3.15 MVA Transformers

Page 25: Power System Protection & Recent Trends by Jdm - Latest

• Most of the Power transformers of 132/11KV and above are of Star-Star vector grouping with the neutral solidly earthed. There are a few transformers with delta-star on HV side). The 33/11KV and

11KV/415V Transformers are of delta-star (delta on HV side).

Page 26: Power System Protection & Recent Trends by Jdm - Latest

The types of faults that the transformers are subjected to

are classified as :-

• Through Faults:- These are due to overload conditions

and external short circuits. Time graded O/C & E/F

relays are employed for external short circuit conditions.

Fuses are provided for Distribution transformers.

• Internal Faults:-

1) Electrical Faults : - Faults which cause immediate

serious damage such as phase to earth or phase to

Page 27: Power System Protection & Recent Trends by Jdm - Latest

phase faults, short circuits between turns of HV&LVphase faults, short circuits between turns of HV&LV

windings, etc.windings, etc.

2) 2) Incipient Faults: -- Which are initially minor faults, Which are initially minor faults,

causing slowly developing damage, such as a poorcausing slowly developing damage, such as a poor

electrical connection of conductors or breakdown ofelectrical connection of conductors or breakdown of

insulation, etc.insulation, etc.

Page 28: Power System Protection & Recent Trends by Jdm - Latest

Conservator AlarmAlarm

Trip

Transformer Transformer TankTank

Page 29: Power System Protection & Recent Trends by Jdm - Latest

The following relays are employed to protect the transformer against internal faults.

i) Buchholz relays

ii) Differential relays

iii) REF relays,

iv) Over fluxing relays

Page 30: Power System Protection & Recent Trends by Jdm - Latest

Buchholz Relays : -Whenever a fault in transformer develop slowly,Whenever a fault in transformer develop slowly,heat is produced locally, which begins toheat is produced locally, which begins todecompose solid or liquid insulated materialsdecompose solid or liquid insulated materialsand thus to produce inflammable gas and oiland thus to produce inflammable gas and oilflow. This phenomenon has been used in the gasflow. This phenomenon has been used in the gasprotection relay or popularly known as Buchholzprotection relay or popularly known as Buchholzrelay. This relay is applicable only to the so-calledrelay. This relay is applicable only to the so-calledconservator type transformer in which the transformerconservator type transformer in which the transformertank is completely filled with oil, and a pipe connectstank is completely filled with oil, and a pipe connectsthe transformer tank to an auxiliary tank or “Conservator” the transformer tank to an auxiliary tank or “Conservator” which acts as an expansion chamber. which acts as an expansion chamber.

Page 31: Power System Protection & Recent Trends by Jdm - Latest

Figure shown as Bucholz relay connected into the pipe leading to the conservator tank and arrange to detect gas produced in the

transformer tank. As the gas accumulates for a minor fault

the oil level falls and, with it a float `F' which operates a

mercury switch sounding an alarm. When a more serious

fault occurs within the transformer during which intense

heating takes place, an intense liberation of gases results.

These gases rush towards the conservator and create a rise in

pressure in the transformer tank due to which the oil is forced

through the connecting pipe to the conservator. The oil flow

develops a force on the lower float shown as "V" in the figure

and overtrips it causing it contacts to complete the trip circuit of

the transformer breaker. Operation of the upper float indicates

an incipient fault and that of the lower float a serious fault.

Page 32: Power System Protection & Recent Trends by Jdm - Latest
Page 33: Power System Protection & Recent Trends by Jdm - Latest

Buchholz relay Operation : Certain Precautions:

The Buchholz relay may become operative not only during faults within the transformer. For instance, when oil is added to a transformer, air may get in together with oil, accumulate under the relay cover and thus cause a false operation of the gas relay. For this reason when the 'Gas' alarm signal is energized, the operators must take a sample of the gas from the relay, for which purpose a special clock is provided. Gases due to faults always have colour and an odour and are inflammable.

Page 34: Power System Protection & Recent Trends by Jdm - Latest

The lower float may also falsely operate if the oil velocity in the connection pipe, though not due to internal faults, is sufficient to trip over the float. This can occur in the event of an external short circuit when over currents flowing through the windings overheat the copper and the oil and cause the oil to expand. If mal-operation of Buchholz relay due to overloads or external

short circuits is experienced, it may be necessary that

the lower float is adjusted for operation for still higher

velocities.

Page 35: Power System Protection & Recent Trends by Jdm - Latest

In installing these relays the following requirements

should be fulfilled.

a) The conductors connecting the contacts to the terminals on the cover must have paper insulation, as rubber insulation may be damaged by the oil.

b) The floats must be tested for air tightness, for example, by submerging them in hot oil to create a surplus pressure in them.

c) The relay cover and the connection pipe should have a slope of 1.5 to 3 percent and not have any protruding surface to ensure unrestricted passage of the gases into the conservator.

Page 36: Power System Protection & Recent Trends by Jdm - Latest
Page 37: Power System Protection & Recent Trends by Jdm - Latest

Differential Relays :-A Differential relay compares the currents on both sides of the transformer. As long as there is no fault within the protected equipment (Transformer), the current circulates between the two CTs and no current flows through the differential element. But for internal faults the sum of the CTs secondary currents will flow through

the differential relay making it to operate.

Two basic requirements that the differential relay connections are to be satisfied are :

a) It must not operate for load or external faults.

b) It must operate for internal faults.

Page 38: Power System Protection & Recent Trends by Jdm - Latest

As on-load tap change facilities are invariably provided in the grid transformers, any departure from the nominal tap position will result in spill currents in the relay circuits.

Further, the CTs are often of different types and have

dissimilar magnetization characteristics, again result-ing in spill current during heavy through fault

conditions.

To avoid unwanted relays operation under the above

two conditions, a "Percentage Bias" differential relay is used.

Page 39: Power System Protection & Recent Trends by Jdm - Latest
Page 40: Power System Protection & Recent Trends by Jdm - Latest

The operating characteristics of percentage bias differential relay is shown in the figure.

The current flowing through the operating coil of the relay should be nearly zero during normal operating conditions and when external short circuit occurs.

While setting the differential relay on a transformer, the (mismatch) current through differential element at normal tap and positive and negative extreme taps are to be computed. Differential element pickup setting and/or bias settings is adopted based on maximum percentage mismatch adding some safety margin.

Differential Current = | I1 -I2 | | I1-I2 |

Bias Setting = ------------

(I1+ I2) / 2

Page 41: Power System Protection & Recent Trends by Jdm - Latest

C T Ratios and connections for differential relay

1. A simple rule of thumb is that the CTs on any Wye (Star) winding of a Power transformer should be connected in delta and the CTs on any delta winding should be connected in Wye (Star).

2. a) If the CTs are to be connected in Star, the C.T Ratio will be In / lA where in is transformer full load current.

b) If the CTs are to be connected in Delta, the C.T Ratio will be In/0.5775 A.

Page 42: Power System Protection & Recent Trends by Jdm - Latest

Differential Relay Improvement

• Differential Relay has improved a lot with the Differential Relay has improved a lot with the introduction of numerical relay introduction of numerical relay

• Numerical relays use techniques such as harmonic Numerical relays use techniques such as harmonic

blocking, wave shape recognitionblocking, wave shape recognition

• In case of electromagnetic and static relays, in a In case of electromagnetic and static relays, in a

typical delta-wye power transformer, the current typical delta-wye power transformer, the current transformer would be connected as wye-delta. transformer would be connected as wye-delta.

Page 43: Power System Protection & Recent Trends by Jdm - Latest

• Another feature involves correction for current Another feature involves correction for current transformer ratios, which may require external transformer ratios, which may require external auxiliary current transformer.auxiliary current transformer.

• On the other hand, with the numerical relays, all On the other hand, with the numerical relays, all current transformers are connected in wye current transformers are connected in wye configuration and phase compensations are done in configuration and phase compensations are done in the relaythe relay

• The magnitude compensation in numerical relays is The magnitude compensation in numerical relays is also done in the relay also done in the relay

Page 44: Power System Protection & Recent Trends by Jdm - Latest
Page 45: Power System Protection & Recent Trends by Jdm - Latest
Page 46: Power System Protection & Recent Trends by Jdm - Latest
Page 47: Power System Protection & Recent Trends by Jdm - Latest

Restricted Earth Fault Protection (REF) : -

This relay is operative only for the internal faults of the transformer and thus fast operating time can be achieved.

1. An external fault on the star side will result in current flowing in the line CT of the affected phase and a balancing current in the neutral CT and current in the relay is zero and hence relay is stable. During an internal fault, the line current on the line CT gets reversed and hence relay operates.

Page 48: Power System Protection & Recent Trends by Jdm - Latest

2. The arrangement of residually connected CTs on the delta side of a transformer is only sensitive to earth faults on the delta side because zero sequence currents are blocked by the delta winding.

For external faults no current flows through REF unless a CT gets saturated. Hence minimum pickup current setting is adopted (10% or 20% In) on REF relay. Based on the through fault current, the stabilizing resistor is set such that the relay will not operate for external fault when a CT gets saturated. This relay operates only for internal earth faults, instantaneously.

Page 49: Power System Protection & Recent Trends by Jdm - Latest
Page 50: Power System Protection & Recent Trends by Jdm - Latest

Fault current for external fault If = 2500 A (assume)

C.T.Ratio (line and neutral) - 300/1 A

2500

Secondary fault current = ------ = 8. 33 A (Sec.)

300

RCT = C.T. Resistance

TL = Lead Resistance = 7.41 Ohms/Km (2.5 sq mmCu)

Voltage developed across CT (Saturated)

(Vk) = If (RCT + 2RL)

= 8.33(5 + 3)

= 66.64 Volts

Relay burden = l VA

Relay Operating

Current = 0.2 A (Set value)

Page 51: Power System Protection & Recent Trends by Jdm - Latest

Relay Operating VoltageVR =

Relay burden ------------------ Relay Operating current = 1/0.2 = 5 Volt Stabilizing Resistor SR = VK - VR ----------- ISet

= 66.64 - 5.0

---------------

0.2

= 308.2 Ohms

Set SR = 310 Ohms

If the calculated value of SR exceeds the existing range, the current settings can be raised accordingly and arrived at suitable SR value.

Page 52: Power System Protection & Recent Trends by Jdm - Latest
Page 53: Power System Protection & Recent Trends by Jdm - Latest

Overfluxing Protection:

1. Overfluxing condition in a transformer can occur during system over voltage and/or under frequency

conditions (V/F).

2. The Overfluxing condition does not call for high speedtripping. The tripping can be delayed depending on the

overflux withstand capability of the transformer.

3. Relays with definite time delay (nearly 30Sec.) and inversecharacteristic are being employed.

Page 54: Power System Protection & Recent Trends by Jdm - Latest

Other Protective devices employed

• Pressure Relief Value (PRV) Pressure Relief Value (PRV) • Winding TemperatureWinding Temperature• Oil Temperature Oil Temperature • OLTC BuchholzOLTC Buchholz

Page 55: Power System Protection & Recent Trends by Jdm - Latest

Transmission Line Protection

Page 56: Power System Protection & Recent Trends by Jdm - Latest

Distance Relays: -

Introduction:

• The impedance relays also called distance relays are The impedance relays also called distance relays are employed to provide protection to transmission lines employed to provide protection to transmission lines connected in a network as they are economic and connected in a network as they are economic and possess several technical advantages. They are possess several technical advantages. They are comparatively simple to apply, operate with extremely comparatively simple to apply, operate with extremely high speed, and both primary and backup protection high speed, and both primary and backup protection features are inherent in them. features are inherent in them.

Page 57: Power System Protection & Recent Trends by Jdm - Latest

Distance Relays: - (cont’d)

• Moreover, they can be easily modified to work as unit Moreover, they can be easily modified to work as unit schemes by coordinating them with power line carrier schemes by coordinating them with power line carrier facilities and are suitable for high speed reclosing. facilities and are suitable for high speed reclosing. The impedance relay is made to respond to the The impedance relay is made to respond to the impedance between the relay location and the point impedance between the relay location and the point where fault is incident. The impedance is proportional where fault is incident. The impedance is proportional to the distance to the fault, (hence the name 'distance to the distance to the fault, (hence the name 'distance relay') and is therefore independent of the fault relay') and is therefore independent of the fault current levels.current levels.

Page 58: Power System Protection & Recent Trends by Jdm - Latest

Distance Relaying Principle:

• A distance relay compares the currents and voltages at the relaying point with Current providing the operating torque and the voltage provides the restraining torque. In other words an impedance relay is a voltage restrained overcurrent relay.

• The equation at the balance point in a simple impedance relay is K1V2 = K2I2 or V/I = K3 where K1, K2 and K3 are constants. In other words, the relay is on the verge of operation at a constant value of V/I ratio, which may be expressed as an impedance

Page 59: Power System Protection & Recent Trends by Jdm - Latest

Since the operating characteristics of the relay depend Since the operating characteristics of the relay depend upon the ratio of voltage and current and the phase upon the ratio of voltage and current and the phase angle between them, their characteristics can be best angle between them, their characteristics can be best represented on an R-X diagram where both V/I ratio represented on an R-X diagram where both V/I ratio and the phase angle can be plotted in terms of an and the phase angle can be plotted in terms of an impedance R+jX. Further, the power system impedance R+jX. Further, the power system impedance like fault impedance, power swings, loads impedance like fault impedance, power swings, loads etc. can also be plotted on the same R-X diagram. etc. can also be plotted on the same R-X diagram. Therefore response of a particular relay during power Therefore response of a particular relay during power swing, faults and other system disturbances can easily swing, faults and other system disturbances can easily be assessed.be assessed.

Page 60: Power System Protection & Recent Trends by Jdm - Latest

Types of Distance Relays:(1) (1) Impedance relayImpedance relay

(2)(2) Reactance relayReactance relay

(3)(3) Mho relayMho relay

(4)(4) Modified impedance relayModified impedance relay

Impedance relay:• Characteristics of an impedance relay on R-X Characteristics of an impedance relay on R-X

diagram is shown in fig diagram is shown in fig • Operation of the impedance relay is independent of Operation of the impedance relay is independent of

the phase angle between V and I. The operating the phase angle between V and I. The operating characteristic is a circle with its center at the origin, characteristic is a circle with its center at the origin, and hence the relay is non-directional.and hence the relay is non-directional.

Page 61: Power System Protection & Recent Trends by Jdm - Latest
Page 62: Power System Protection & Recent Trends by Jdm - Latest

Characteristic of Directional Impedance Relay:

• Characteristic of a directional impedance relay in the Characteristic of a directional impedance relay in the complex R-X phase is shown in fig.complex R-X phase is shown in fig.

• The directional unit of the relay causes separation of The directional unit of the relay causes separation of the regions of the relay characteristic shown in the the regions of the relay characteristic shown in the figure by a line drawn perpendicular to the line figure by a line drawn perpendicular to the line impedance locus. The net result is that tripping will impedance locus. The net result is that tripping will occur only for points that are both within the circles occur only for points that are both within the circles and above the directional unit characteristic.and above the directional unit characteristic.

Page 63: Power System Protection & Recent Trends by Jdm - Latest
Page 64: Power System Protection & Recent Trends by Jdm - Latest

The Reactance-type Distance Relay:

• Reactance relay measures V/I Sin Reactance relay measures V/I Sin θθ (i.e. Z sin (i.e. Z sin θθ = X). = X). Whenever the reactance measured by the relay is less Whenever the reactance measured by the relay is less than the set value, the relay operates. The operating than the set value, the relay operates. The operating characteristic on R-X diagram is shown in fig characteristic on R-X diagram is shown in fig

• The resistance component of impedance has no effect The resistance component of impedance has no effect on the operation of reactance relay, the relay responds on the operation of reactance relay, the relay responds solely to reactance component of impedance. This solely to reactance component of impedance. This relay is inherently non-directional. The relay is most relay is inherently non-directional. The relay is most suitable to detect earth faults where the effect of arc suitable to detect earth faults where the effect of arc resistance is appreciable.resistance is appreciable.

Page 65: Power System Protection & Recent Trends by Jdm - Latest
Page 66: Power System Protection & Recent Trends by Jdm - Latest

Mho relay: This is a directional impedance relay, also known as This is a directional impedance relay, also known as

admittance relay. Its characteristic on R-X diagram is a admittance relay. Its characteristic on R-X diagram is a circle whose circumference passes through the origin as circle whose circumference passes through the origin as illustrated in figure showing that the relay is inherently illustrated in figure showing that the relay is inherently directional and it only operates for faults in the forward directional and it only operates for faults in the forward direction. direction.

Modified impedance relay:Also known as offset Mho relay whose characteristic encloses theAlso known as offset Mho relay whose characteristic encloses the

origin on R-X diagram as shown in figorigin on R-X diagram as shown in fig

This offset mho relay has three main applications: -This offset mho relay has three main applications: -

i)i) Busbar zone backup Busbar zone backup

ii)ii) Carrier starting unit in distance/carrier blocking schemes. Carrier starting unit in distance/carrier blocking schemes.

iii) Power Swing blocking.iii) Power Swing blocking.

Page 67: Power System Protection & Recent Trends by Jdm - Latest
Page 68: Power System Protection & Recent Trends by Jdm - Latest

Main Features in Distance Scheme

Distance schemes consist of the following major

components:-

i) Starters.

ii) Measuring units.

iii) Timers

iv) Auxiliary relays

Starters: -

The starting relay (or starter) initiates the distance

scheme in the event of a fault within the required

reach (more than zone-3).

Page 69: Power System Protection & Recent Trends by Jdm - Latest

Starters: -Starters: -

Other functions of the starter are: -Other functions of the starter are: -

a)a) Starting of timer relays for second and third zones.Starting of timer relays for second and third zones.

b)b) Starting of measuring elements.Starting of measuring elements.

The starters are generally of Mho or impedance type.The starters are generally of Mho or impedance type.

With Mho type starters: -

Measuring units for phase and earth faults can be eitherMeasuring units for phase and earth faults can be either

directional or non-directional as Mho starter isdirectional or non-directional as Mho starter is

inherently directional inherently directional

Page 70: Power System Protection & Recent Trends by Jdm - Latest

With impedance type starters: -

• Measuring units have to be directional as impedance starters are non – directional.

• The under impedance relay can be used in conjunction with the directional relay as starter which will then function similar to the Mho starter.

Measuring units: -• They are generally of a mho or reactance or a

combination of mho, reactance and resistance types.•

Page 71: Power System Protection & Recent Trends by Jdm - Latest

Phase Fault Units:-

These measuring units are fed with line to line These measuring units are fed with line to line voltages (such as Vab, Vbc) and difference between voltages (such as Vab, Vbc) and difference between line currents (Ia-Ib). They measure the positive line currents (Ia-Ib). They measure the positive sequence impedance from the relay location to the sequence impedance from the relay location to the fault point. Three such relays respond correctly to all fault point. Three such relays respond correctly to all possible single line to ground faults line to line faults, possible single line to ground faults line to line faults, double line to ground faults and 3-phase faults. They double line to ground faults and 3-phase faults. They however do not respond correctly to earth faults.however do not respond correctly to earth faults.

Page 72: Power System Protection & Recent Trends by Jdm - Latest

Earth Fault Units: -

• These measuring units utilize line to neutral voltage (Van, Vbn Vcn) and phase currents (Ia, Ib, Ic). In order to make these units measure the positive sequence impedance correctly, a zero sequence current compensation is to be provided which is obtained by:

• KN = (Z0-Z1)/ 3*Z1 (where Z1 = positive sequence impedance of line.

• Z0 = Zero sequence impedance of line)• In the current circuit (1+KN) Ia will be fed for the

above measurement.

Page 73: Power System Protection & Recent Trends by Jdm - Latest

Timers: -

• Timer relays when initiated by starters provide the Timer relays when initiated by starters provide the time lag required for zones. They also will be used time lag required for zones. They also will be used for zone extension purpose whenever required.for zone extension purpose whenever required.

Auxiliary relays: -

• Distance scheme comprises of several auxiliary Distance scheme comprises of several auxiliary relays, which perform functions such as flag relays, which perform functions such as flag indications, trippings, signaling, alarm etc.indications, trippings, signaling, alarm etc.

Page 74: Power System Protection & Recent Trends by Jdm - Latest

Additional Features in distance schemes: -

i) Power Swing blocking relay

ii) VT fuse failure relay.

iii) Switch onto fault relay

iv) Fault locator

v) Auto-reclosing scheme.

vi) Carrier communication scheme.

Page 75: Power System Protection & Recent Trends by Jdm - Latest

Power Swing blocking: -

• Distance relay which respond to balanced 3-phase Distance relay which respond to balanced 3-phase changes in the impedance will be affected by power changes in the impedance will be affected by power swings. These swings or oscillations occur following swings. These swings or oscillations occur following a system disturbance such as major load change or a a system disturbance such as major load change or a dip in voltage due to delayed fault clearance.dip in voltage due to delayed fault clearance.

• In case of fault, the transition from period of In case of fault, the transition from period of impedance locations (25 to 33% of starter impedance) impedance locations (25 to 33% of starter impedance) to fault impedance (starter impedance) is sudden to fault impedance (starter impedance) is sudden whereas during power swings. The PSB relays use whereas during power swings. The PSB relays use this difference to block the tripping during swings.this difference to block the tripping during swings.

Page 76: Power System Protection & Recent Trends by Jdm - Latest

VT fuse failure relay: -

The distance relays being voltage restraint O/C The distance relays being voltage restraint O/C relays, loss of voltage due to main PT fuse failure or relays, loss of voltage due to main PT fuse failure or inadvertent removal of fuse in one or more phases inadvertent removal of fuse in one or more phases will cause the relay operation. The fuse failure relay will cause the relay operation. The fuse failure relay will sense such condition by the presence of residual will sense such condition by the presence of residual voltage without residual current and blocks the relay.voltage without residual current and blocks the relay.

Page 77: Power System Protection & Recent Trends by Jdm - Latest

Switch onto fault: -

• When the line is switched on to a close by fault (say after line clear with earth switch closed), the voltage at the relaying point will be zero. Faults of this type will normally be cleared by backup zones.

• The voltage applied to the relay is low and this condition occurring simultaneously with the operation of starter will cause instantaneous trip by SOTF relay. This SOTF feature will be effective only for about 1-2 seconds after the line is charged. Faults occurring after this time will be measured in the normal way.

Page 78: Power System Protection & Recent Trends by Jdm - Latest

Fault locator: -

• It measures the distance between the relay location It measures the distance between the relay location and fault location in terms of Z in Ohms, or length in and fault location in terms of Z in Ohms, or length in KM or percentage of line length.KM or percentage of line length.

• This relay gets same inputs as the distance relay This relay gets same inputs as the distance relay (connected in series with one of the main relays). (connected in series with one of the main relays). The measurement is initiated by trip signal from The measurement is initiated by trip signal from distance relays.distance relays.

• The fault locator gives the exact location of the fault, The fault locator gives the exact location of the fault, thereby reducing the time of restoration.thereby reducing the time of restoration.

Page 79: Power System Protection & Recent Trends by Jdm - Latest

Factors affecting distance relay operation:-

i) Fault resistance.

ii) Infeed effect.

iii) Branching-off effect.

iv) Load encroachment.

Page 80: Power System Protection & Recent Trends by Jdm - Latest

Fault resistance:-

Fault resistance has two components:-Fault resistance has two components:-

a) Arc resistance.a) Arc resistance.

b) Ground resistance.b) Ground resistance.

In a fault between phases, only arc resistance is involved.In a fault between phases, only arc resistance is involved.

For a fault at F, the actual line impedance For a fault at F, the actual line impedance

= R + JX = ZL= R + JX = ZL

Due to the presence of fault resistance, the impedance Due to the presence of fault resistance, the impedance measured by the relaymeasured by the relay

= R + JX + RF = ZR (where ZR > ZL)= R + JX + RF = ZR (where ZR > ZL)

Page 81: Power System Protection & Recent Trends by Jdm - Latest

Fault arc resistance is given by Warrington's Fault arc resistance is given by Warrington's formula:formula:

Rarc = 8750 X l / I 1.4Rarc = 8750 X l / I 1.4

where where l = length of arc in ftl = length of arc in ft

I = fault current in AmpsI = fault current in Amps

Page 82: Power System Protection & Recent Trends by Jdm - Latest
Page 83: Power System Protection & Recent Trends by Jdm - Latest

• The arc resistance has little effect on accuracy of The arc resistance has little effect on accuracy of zone-1 unit as it operates instantaneously before the zone-1 unit as it operates instantaneously before the arc can stretch appreciably except in case of short arc can stretch appreciably except in case of short lines. Reactance relays are therefore used for short lines. Reactance relays are therefore used for short lines where the fault resistance may be comparable lines where the fault resistance may be comparable with that of the protected lines and also for ground with that of the protected lines and also for ground faults where the ground resistance is high.faults where the ground resistance is high.

• The arc resistance will have greater impact on The arc resistance will have greater impact on accuracy of backup zones (time delayed) as the arc accuracy of backup zones (time delayed) as the arc stretches appreciably.stretches appreciably.

Page 84: Power System Protection & Recent Trends by Jdm - Latest

Infeed effect:-

• The effect of intermediate current source between The effect of intermediate current source between relay location and fault point is termed as infeed relay location and fault point is termed as infeed effect. Consider the sketch indicated in fig ---effect. Consider the sketch indicated in fig ---

• A fault at F on the line BC is at a distance of Z1+Z2 A fault at F on the line BC is at a distance of Z1+Z2 for the relay at station A. But when current I2 flows for the relay at station A. But when current I2 flows from bus D, the impedance to the fault as seen by the from bus D, the impedance to the fault as seen by the relay at A is relay at A is

• Z1 + Z2 + Z2 x (I2/I1).Z1 + Z2 + Z2 x (I2/I1).• Thus the fault is seen by the relay as farther than what Thus the fault is seen by the relay as farther than what

it really is, i.e. it really is, i.e. distance relay under reaches due to the distance relay under reaches due to the infeed effect.infeed effect.

• The effect of infeed becomes more pronounced with The effect of infeed becomes more pronounced with more interconnections at station B.more interconnections at station B.

Page 85: Power System Protection & Recent Trends by Jdm - Latest
Page 86: Power System Protection & Recent Trends by Jdm - Latest

Branching-off effect: -

• Consider the sketch indicated in fig ---

• A fault at F is at the distance of Z1+Z2 for the relay at station A. But when current I1 gets distributed as I2 & I3 at station B, the impedance to fault seen by the relay at station A will be (Z1 + I3/I1 * Z2) which is less than (Z1+Z2).

• Then the fault is seen by the relay as nearer than what it really is i.e. distance relay overreaches due to branching-off effect. This overreaching tendency will cause the relay to loose its selectivity.

Page 87: Power System Protection & Recent Trends by Jdm - Latest

Load encroachment: -

• While protecting long lines the necessary reach While protecting long lines the necessary reach may be so large that the minimum service may be so large that the minimum service impedance (or load impedance) falls within the impedance (or load impedance) falls within the region of the starter. This would result in region of the starter. This would result in tripping without there being any fault. The two tripping without there being any fault. The two conditions i.e. operation at heavy load and short conditions i.e. operation at heavy load and short circuit differ by virtue of phase angle between circuit differ by virtue of phase angle between voltage and current. For the load impedance, voltage and current. For the load impedance, the phase angle will be within +30 to -30 Deg. the phase angle will be within +30 to -30 Deg. While during short circuits, the fault impedance While during short circuits, the fault impedance has a phase angle of 60 to 80 deg. (i.e. line has a phase angle of 60 to 80 deg. (i.e. line angle).angle).

Page 88: Power System Protection & Recent Trends by Jdm - Latest

• Load encroachment problem is more pronounced Load encroachment problem is more pronounced in case of under impedance starters and gets in case of under impedance starters and gets lessened in case of mho, elliptical, lens etc, type lessened in case of mho, elliptical, lens etc, type of starters. Relays with suitable characteristic on of starters. Relays with suitable characteristic on R-X diagram have to be carefully chosen to R-X diagram have to be carefully chosen to protect long and heavily loaded lines, and this protect long and heavily loaded lines, and this becomes easily possible with microprocessor becomes easily possible with microprocessor based numerical relays.based numerical relays.

Page 89: Power System Protection & Recent Trends by Jdm - Latest

Non-switched scheme vs switched scheme: -

• In an ideal Non-switched scheme, there will be 6 starters, 3 for phase faults and 3 for ground faults. There will be independent measuring units for both phase faults and earth fault for each phase, for all three zones, totaling to 18 units. This scheme is faster and more accurate but is costly.

Page 90: Power System Protection & Recent Trends by Jdm - Latest

• In the switched scheme, only one measuring unit will be used for all types of faults. This single measuring unit is switched to the correct fault loop impedance by switching-in the respective voltages and currents by the starter.

• The reach of the measuring element gets extended to zone-2 and zone-3 after the elapse of corresponding timings through zone extension process. Switched scheme is relatively slow in operation and has the risk of total scheme failure in the event of failure of the only one measuring unit available.

Page 91: Power System Protection & Recent Trends by Jdm - Latest

Zone extension schemes: -

• As a via media between non-switched and switched As a via media between non-switched and switched schemes, there are schemes with zone extension schemes, there are schemes with zone extension facility (such as EE make MM3V & MR3V relays). facility (such as EE make MM3V & MR3V relays). These schemes consists of 3 measuring units for These schemes consists of 3 measuring units for phase faults and 3 measuring units for earth faults phase faults and 3 measuring units for earth faults (apart from 3 starters).(apart from 3 starters).

• The reach of the measuring unit gets extended to The reach of the measuring unit gets extended to zone-2 and zone-3 after elapse of corresponding zone-2 and zone-3 after elapse of corresponding timings through a zone extension process.timings through a zone extension process.

Page 92: Power System Protection & Recent Trends by Jdm - Latest

Other Operating Characteristics:

• Earlier when electromagnetic relays were in use, the characteristics involving straight lines and /or circles on R-X diagram were only possible. With the advent of static relays, microprocessor based relays and presently of numerical relays, any desired/required-operating characteristic is possible giving wider choice for selection of relays. Infact there are relays, which can be programmed remotely.

Page 93: Power System Protection & Recent Trends by Jdm - Latest

Application of distance relays:

• Since the distance relays are fed from the secondaries of Since the distance relays are fed from the secondaries of line CTs and bus PTs/line CVTs, the line parameters are line CTs and bus PTs/line CVTs, the line parameters are to be converted into secondary values to set the relay as to be converted into secondary values to set the relay as per requirements.per requirements.

• Zsecy = Zpri/Impedance ratioZsecy = Zpri/Impedance ratio

(where Impedance ratio = P.T.Ratio/C.T.Ratio)(where Impedance ratio = P.T.Ratio/C.T.Ratio)

• Hence any changes in C.T .ratio has to be effected Hence any changes in C.T .ratio has to be effected along with revision of relay settings only.along with revision of relay settings only.

Page 94: Power System Protection & Recent Trends by Jdm - Latest

For the lines, the impedance in Ohms per KM is approximately as For the lines, the impedance in Ohms per KM is approximately as under:under:

----------------------------------------------------------------------------------------------------------------------------------------------------------------------

KVKV Z1 (= Z2 )Z1 (= Z2 ) Line AngleLine Angle

----------------------------------------------------------------------------------------------------------------------------------------------------------------------

132 KV132 KV 0.40.4 60 to 70 Deg.60 to 70 Deg.

220 KV220 KV 0.40.4 70 to 80 Deg.70 to 80 Deg.

400 KV400 KV 0.30.3 80 to 85 Deg.80 to 85 Deg.

--------------------------------------------------------------------------------------------------------------------------------------------------------------------

The line impedance is to be computed depending on line configurationThe line impedance is to be computed depending on line configuration

conductor size and clearness. The values in the table are only conductor size and clearness. The values in the table are only representative.representative.

A distance relay is stepped for either 3 zones or 4 zones to provide A distance relay is stepped for either 3 zones or 4 zones to provide protection.protection.

Page 95: Power System Protection & Recent Trends by Jdm - Latest
Page 96: Power System Protection & Recent Trends by Jdm - Latest

To ensure proper coordination between distance relays in power system, it is To ensure proper coordination between distance relays in power system, it is customary tocustomary to

choose relay ohmic setting as follows: -choose relay ohmic setting as follows: -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------S.No. ZonesS.No. Zones ReactanceReactance Time Time------------------------------------------------------------------------------------------------------------------------------------------------------------------------------1.1. Zone-1Zone-1 80% of ZL80% of ZL Instantaneous Instantaneous

(no intentional time (no intentional time delay).delay).

2.2. Zone-2Zone-2 100% of ZL + 40-50% 100% of ZL + 40-50% 0.3 to 0.4 seconds 0.3 to 0.4 secondsof ZSLof ZSL

3.3. Zone-3Zone-3 100% of ZL + 120% 100% of ZL + 120% 0.6 to 0.8 seconds 0.6 to 0.8 seconds

of ZSLof ZSL

4.4. Zone-4Zone-4 100% of ZL + 120%100% of ZL + 120% 0.9 to 1.5 seconds 0.9 to 1.5 secondsof ZLLof ZLL

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Page 97: Power System Protection & Recent Trends by Jdm - Latest

• where ZL = Positive sequence impedance of line to be where ZL = Positive sequence impedance of line to be protected.protected.

• ZSL = Positive sequence impedance of adjacent shortest ZSL = Positive sequence impedance of adjacent shortest line.line.

• ZLL = Positive sequence impedance of adjacent longest ZLL = Positive sequence impedance of adjacent longest line.line.

• Note:Note:

i)i) Where a three zone relay only is available, the zone 3 Where a three zone relay only is available, the zone 3 will be set to cover the adjacent longest line.will be set to cover the adjacent longest line.

jj)jj) The zonal timings will be carefully selected to properly The zonal timings will be carefully selected to properly grade with the relays on all the feeders emanating from grade with the relays on all the feeders emanating from the adjacent bus.the adjacent bus.

Page 98: Power System Protection & Recent Trends by Jdm - Latest

Norms of protection adopted for transmission lines in

A.P.System:-

i) 132 KV Lines: -• A switched type distance scheme supplemented by three

numbers directional O/L relays and 1 No. directional E/L relay.

ii)220 KV Lines: -• Two Distance Schemes: -

Main-I: - Non-switched scheme fed from bus PT.

Main-II: - A switched scheme fed from line CVT.

Page 99: Power System Protection & Recent Trends by Jdm - Latest

• A provision is generally made for the changeover of voltage supply for the distance schemes from the bus PT to line CVT and vice-versa.

• Each distance scheme is fed from independent CT secondary cores.

iii) 400 KV Lines:-• Two Distance Schemes:-

Main-I:- Non-switched or Numerical distance schemesMain-II:- Non-switched or Numerical distance schemes

Page 100: Power System Protection & Recent Trends by Jdm - Latest

Details of distance relays:-

1) Make: - GEC Alstom Ltd.

i) MM3V : - It is an electromagnetic type distance relay with:

3-mho measuring units for phase to phase faults.

3-mho measuring units for phase to earth faults.

3-mho starting units, each starter being associated with one phase and operating for all faults associated with that phase and one offset mho unit for power swing blocking.

Page 101: Power System Protection & Recent Trends by Jdm - Latest

R-X diagram is indicated

Setting range in ohms for Zone-1

--------------------------------------

0.834 to 30

1.335 to 48

1.668 to 60

Z2 = 1 to 3.5 times Z1

Z3 = 1 to 5 times Z1

---------------------------------------

Some of the schemes are provided with a Zone-4 timer to make the scheme works as a 4 zone relay, the starter itself being the 4th zone.

Page 102: Power System Protection & Recent Trends by Jdm - Latest
Page 103: Power System Protection & Recent Trends by Jdm - Latest

MR3V: -

• It is an electromagnetic relays with 3 mho units for phase faults, 3 reactance units for earth faults. 3 mho starters, each being associated with one phase for all types of faults and one offset mho unit for power swing blocking.

• Setting ranges same as in MM3V.

• R-X diagram for phase faults is same as that for MM3V relay and for earth faults it is indicated in figure

Page 104: Power System Protection & Recent Trends by Jdm - Latest
Page 105: Power System Protection & Recent Trends by Jdm - Latest

SHPM (Quadra mho): -

• It is a non-switched static scheme with 18 measuring mho units. The zone-3 measuring elements will act as starters, which have either mho or a lenticular characteristic. The operating characteristic on R-X diagram is indicated in figure

• The lenticular characteristics allows healthy overloads and hence prevents tripping on load encroachment.

• Setting range: - 0.2 to 240 Ohms.• It has built-in feature of continuous self monitoring (on

demand and periodic self testing).• All the additional features provided by relay can be enabled

or disabled with the help of switches provided for them.

Page 106: Power System Protection & Recent Trends by Jdm - Latest
Page 107: Power System Protection & Recent Trends by Jdm - Latest

PYTS: -• It is a static switched scheme with modular plug-in construction

(with built in test points).• It has 3 under impedance starters and a single mho measuring

unit. One U/I unit for power swing blocking. R-X diagram is indicated in figure

• Setting range: 0.05 to 40 Ohms, with starter having range of 20 to 70 Ohms.

• It has an uncompensated U/I starter, which has become a problem due to load encroachment for long lines.

• The V-I characteristic of the starter is indicated in above figure.• When the voltage is less than 65% rated, the starter operates at a

current greater than 0.25 In. With low voltages at some of the stations, this feature has caused relay to operate unnecessarily.

Page 108: Power System Protection & Recent Trends by Jdm - Latest
Page 109: Power System Protection & Recent Trends by Jdm - Latest
Page 110: Power System Protection & Recent Trends by Jdm - Latest
Page 111: Power System Protection & Recent Trends by Jdm - Latest
Page 112: Power System Protection & Recent Trends by Jdm - Latest
Page 113: Power System Protection & Recent Trends by Jdm - Latest
Page 114: Power System Protection & Recent Trends by Jdm - Latest
Page 115: Power System Protection & Recent Trends by Jdm - Latest
Page 116: Power System Protection & Recent Trends by Jdm - Latest
Page 117: Power System Protection & Recent Trends by Jdm - Latest

PD – 521: -

• It is a numerical protection relay with polygon It is a numerical protection relay with polygon characteristics.characteristics.

• It consists of four impedance zones with independent R It consists of four impedance zones with independent R and X values for each zoneand X values for each zone

• Zone – 4 can be utilized as a special zone for cabie Zone – 4 can be utilized as a special zone for cabie protection.protection.

• R – X diagram as indicated in figure.R – X diagram as indicated in figure.• Through MMI, one can enter and edit the settings (The Through MMI, one can enter and edit the settings (The

settings are password protected) settings are password protected) • Setting Range Setting Range :: 0.1 to 2000 Ohms.0.1 to 2000 Ohms.• Timers Timers :: 0 to 10 Secs.0 to 10 Secs.

Page 118: Power System Protection & Recent Trends by Jdm - Latest
Page 119: Power System Protection & Recent Trends by Jdm - Latest

MICOM DISTANCE RELAY (Alstom make):

MICOM P440 series is a distance scheme with

Advanced numerical technology. MICOM P441 and

P442 relays have five zones of phase fault protection and

five zones of earth fault protection.

a) Phase fault protection

Phase fault quadrilateral characteristics is shown in the

figure.

Zones 1,2 & 3 – directional forward zones, as used in

conventional three zone distance schemes. Note that

Zone-1 can be extended to Zone-1X when required in

Zone-1 extension scheme.

Page 120: Power System Protection & Recent Trends by Jdm - Latest

Zone P – Programmable. Selectable as aZone P – Programmable. Selectable as a

directional forward or reverse zone.directional forward or reverse zone.

Zone-4 – Directional reverse zone. Note thatZone-4 – Directional reverse zone. Note that

Zone-3 and Zone-4 can be set together to giveZone-3 and Zone-4 can be set together to give

effectively a forward zone with a reverse offset.effectively a forward zone with a reverse offset.

Page 121: Power System Protection & Recent Trends by Jdm - Latest
Page 122: Power System Protection & Recent Trends by Jdm - Latest

Earth Fault Protection:

• Earth fault quadrilateral characteristics is similar to the phase fault quadrilateral characteristics as shown below. Resistive reaches can be set independently for phase and earth fault protections.

• All earth fault elements are quadrilateral shaped, and are directionalised similar to the phase fault elements. The impedance reaches of earth fault elements use residual compensation of the corresponding phase fault reaches.

Page 123: Power System Protection & Recent Trends by Jdm - Latest
Page 124: Power System Protection & Recent Trends by Jdm - Latest

RELZ-100:

• It is a numerical relay with quadrilateral impedance units for phase and earth faults. Each measuring unit has individual and independent setting of the reach in resistive and reactive directions, as well as for the zero sequence compensation factor, KN. Entire Zone-3 reach (in forward direction) is available in reverse direction with a separate timer T3R. R-X diagram is as indicated

Page 125: Power System Protection & Recent Trends by Jdm - Latest

• Four groups of setting parameters are possible to suit Four groups of setting parameters are possible to suit different system conditions. Only one of the groups different system conditions. Only one of the groups will be in service by choice. It has continuous self will be in service by choice. It has continuous self monitoring and self testing feature and indicate the monitoring and self testing feature and indicate the same by extinguishing "Relay Available" LED on the same by extinguishing "Relay Available" LED on the relay. Through MMI, one can enter; edit the settings, relay. Through MMI, one can enter; edit the settings, read the mean service values of line voltage, current, read the mean service values of line voltage, current, real, reactive power and frequency. It stores data of real, reactive power and frequency. It stores data of latest 3 disturbances occurred. (The settings are not latest 3 disturbances occurred. (The settings are not password protected).password protected).

• Setting rage:Setting rage: 0.1 to 150 Ohms.0.1 to 150 Ohms.• Timers:Timers: 0 to 10 Secs.0 to 10 Secs.• It has a feature which does overload supervision and It has a feature which does overload supervision and

unsymmetrical load condition, which can be used for unsymmetrical load condition, which can be used for alarm or trip.alarm or trip.

Page 126: Power System Protection & Recent Trends by Jdm - Latest
Page 127: Power System Protection & Recent Trends by Jdm - Latest

Make: - Seimens Ltd.

7SA511 relay:

• It is a numerical protection scheme with 16 bit microprocessor. With three version of detectors.

i) Phase selective overcurrent fault detector.

ii) Voltage controlled (under-impedance) fault detector (with independent R & X reaches) and

iii) Polygonally shaped angle-dependent impedance fault detector.

• It has five zones (two of which can be used for communication schemes).

• R-X diagram is indicated below.

Page 128: Power System Protection & Recent Trends by Jdm - Latest

• Apart from common features, it provides Emergency Apart from common features, it provides Emergency overcurrent function, which comes into picture when main overcurrent function, which comes into picture when main distance scheme is blocked due to VT fuse failure conditions.distance scheme is blocked due to VT fuse failure conditions.

• It provides two user defined logic functions. It has continuous It provides two user defined logic functions. It has continuous self monitoring and self testing feature. It stores data of latest self monitoring and self testing feature. It stores data of latest three faults and measures values of load current, operating three faults and measures values of load current, operating voltage, power and frequency continuously.voltage, power and frequency continuously.

• Setting range:0.1 to 200 Ohms with 0.0 to 32 sec (in step of Setting range:0.1 to 200 Ohms with 0.0 to 32 sec (in step of 0.01 sec) timers.0.01 sec) timers.

• Four groups of settings are possible to suit different system Four groups of settings are possible to suit different system conditions. Only one of the groups will be in service by conditions. Only one of the groups will be in service by choice.choice.

Page 129: Power System Protection & Recent Trends by Jdm - Latest
Page 130: Power System Protection & Recent Trends by Jdm - Latest

SEL – 321: - • It is numerical relay with Four Mho zones for phase

faults with independent phase to phase overcurrent supervision.

• Four ground faults for Mho and Quadrilateral zones with independent phase and residual overcurrent supervision and zero sequence compensation.

• Two Quadrilateral zones for power swing blocking.• Load-encroachment characteristics.• Instantaneous, Definite time and IDMT overcurrent

characteristics.• Six (6) setting groups are available in the scheme.

Page 131: Power System Protection & Recent Trends by Jdm - Latest

Setting ranges:-

• For Mho zones : 0.25 to 320 Ohms (Secondary)

• For Quadrilateral Zones :• Reactance : 0.25 to 320 Ohms

(Secondary)• Resistance : 0.25 to 250 Ohms

(Secondary)• Timers : 0-2000 Cycles

Page 132: Power System Protection & Recent Trends by Jdm - Latest
Page 133: Power System Protection & Recent Trends by Jdm - Latest

BUS BAR PROTECTIONBUS BAR PROTECTION

Page 134: Power System Protection & Recent Trends by Jdm - Latest

Differential Protection for Bus bars:

Short-circuit on bus bars can have very serious Short-circuit on bus bars can have very serious consequences for the operation of the power system. consequences for the operation of the power system. The most widely used and acceptable type of protection The most widely used and acceptable type of protection for 35 – 200kV bus bars is high-speed differential for 35 – 200kV bus bars is high-speed differential protection. It is based on Kirchhoff’s current law that protection. It is based on Kirchhoff’s current law that requires the sum of all currents entering the bus to sum requires the sum of all currents entering the bus to sum to zero. Should an internal fault occur, however, the to zero. Should an internal fault occur, however, the sum currents measured at current transformer locations sum currents measured at current transformer locations will not be zero and tripping should occur. This type of will not be zero and tripping should occur. This type of bus protection for one phase is shown in the following bus protection for one phase is shown in the following Figure:Figure:

Page 135: Power System Protection & Recent Trends by Jdm - Latest

The current transformer secondaries are added together The current transformer secondaries are added together to give the sum of the currents in all four lines; and the to give the sum of the currents in all four lines; and the sum is sent to the differential relay. In case a fault sum is sent to the differential relay. In case a fault occurs that is external to the CT connections, say at the occurs that is external to the CT connections, say at the point 1 in the Figure, the total current flowing to that point 1 in the Figure, the total current flowing to that fault will be exactly equal to the total current entering fault will be exactly equal to the total current entering the bus on lines 2,3,4 and no current will flow to the the bus on lines 2,3,4 and no current will flow to the differential relay. However, if a fault occurs on the bus, differential relay. However, if a fault occurs on the bus, between phases or from phase to ground, the sum of the between phases or from phase to ground, the sum of the line currents will equal the total bus fault current and line currents will equal the total bus fault current and the relay will correctly measure this quantity.the relay will correctly measure this quantity.

Page 136: Power System Protection & Recent Trends by Jdm - Latest

Bus differential protectionBus differential protection

Page 137: Power System Protection & Recent Trends by Jdm - Latest

• High impedance circulating current schemeHigh impedance circulating current scheme

• Biased differential or low impedance Biased differential or low impedance circulating scheme.circulating scheme.

Page 138: Power System Protection & Recent Trends by Jdm - Latest

S. No. Details High impedance circulating current relay

Low impedance biased differential relay

1. Principle The currents entering and leaving the busbar are compared conti-nuously. It involves choosing of impedance high enough to stabilise the relay for heavy external faults.

It has differential and bias setting. The resultant bias is proportional to arithmetic sum of all currents, whereas the operating current is vector sum of all circuit currents.

2. CTs It requires all identical CT ratios

It can work with CTs of unequal ratios also.

3. Burden Imposes comparatively high burden on CTs. Auxiliary CTs reduce the performance of scheme

Imposes less burden on CTs. Auxiliary CTs have no effect on performance of scheme

Page 139: Power System Protection & Recent Trends by Jdm - Latest

S.No. Details High impedance circulating current relay

Low impedance biased differential relay

4. CT Saturation Operation of scheme even when CTs get saturated during internal faults

Operation of scheme even when CTs get saturated during internal faults.

5. Performance Highly sensitive for internal faults and completely stable for external faults

Highly sensitive for internal faults and completely for external faults

6. Relays in A.P System

GEC make CAG34, PBDCB

GEC make MBCZABB make RADSS

Page 140: Power System Protection & Recent Trends by Jdm - Latest
Page 141: Power System Protection & Recent Trends by Jdm - Latest

• For some high impedance schemes, only Voltage Setting ‘V’ will be set. (The calculations are similar to that of Restricted Earth Fault relay setting for the Transformer protection).

Low Impedance Busbar Scheme:-

• This relay operates on circulating current principle and differential current setting ( 20% In) is adopted on the relay. The bias setting is generally set by the relay manufacturer based on bus fault levels.

Page 142: Power System Protection & Recent Trends by Jdm - Latest

Busbar Protection

a) Check Feature: -• To prevent incorrect tripping due to damage to wiring To prevent incorrect tripping due to damage to wiring

and equipment from extraneous sources, check relay and equipment from extraneous sources, check relay is provided. This check relay is provided by is provided. This check relay is provided by duplication of primary protection using a second set duplication of primary protection using a second set of current transformers cores on all circuits other than of current transformers cores on all circuits other than bus section and bus couple units. The check system is bus section and bus couple units. The check system is arranged in a similar manner of the primary arranged in a similar manner of the primary protection, but forms one zone only covering the protection, but forms one zone only covering the whole of the busbars (in case of single sectionalized whole of the busbars (in case of single sectionalized busbar or both the buses (in case of double busbar busbar or both the buses (in case of double busbar arrangement).arrangement).

Page 143: Power System Protection & Recent Trends by Jdm - Latest

b) Supervision

• When a CT secondary winding or connections between CT and the relay circuit become open circuited, the relay may maloperate for load or through faults depending on the effective primary setting. This condition of an open circuit can be detected by using supervision (over voltage) relay, which is arranged to give alarm.

• The supervision must be time delayed to avoid a false alarm during genuine fault conditions, typically three seconds is adopted.

Page 144: Power System Protection & Recent Trends by Jdm - Latest

Numerical Busbar Protection Highly stable for external faults Highly stable for external faults Highly sensitive for internal faults Highly sensitive for internal faults Operating speed around 50 msecOperating speed around 50 msec Adaptability to the dynamically changing topology of the Adaptability to the dynamically changing topology of the

busbar busbar Centralized or distributed architectureCentralized or distributed architecture Support easy maintenance, operation and future expansion of Support easy maintenance, operation and future expansion of

the busbarthe busbar Can operate with different of CTsCan operate with different of CTs Fiber optic cable used for communication between central and Fiber optic cable used for communication between central and

peripheral units peripheral units Ensure high communication speedEnsure high communication speed

Page 145: Power System Protection & Recent Trends by Jdm - Latest

Numerical Busbar Protection(cont’d)Management Functions:In addition to the protection and control elements, numerical

busbar protection provides a wide range of measurement,

monitoring, post fault analysis and self-diagnostic features.

Circuit breaker control Trip circuit supervision(using PSL) Online measurements Plant status monitoring Four alternative setting groups Programmable scheme logic (PSL) Sequence of event recording (SOE)

Page 146: Power System Protection & Recent Trends by Jdm - Latest

Numerical Busbar Protection(cont’d)

Management Functions: Comprehensive disturbance recording (waveform capture) User configurable LEDs Local and remote communication ports Time synchronization Fully customizable menu texts Multilevel password protection Test facilities Power- up diagnostics and continuous self-monitoring of relay User friendly setting and analysis software

Page 147: Power System Protection & Recent Trends by Jdm - Latest

Examples of numerical busbar protectionExamples of numerical busbar protection::

MICOM P740 (Areva)MICOM P740 (Areva)REB 500 (ABB)REB 500 (ABB)

Page 148: Power System Protection & Recent Trends by Jdm - Latest

BREAKER FAILURE RELAY (LBB PROTECTION)

Main protective schemes provided for Main protective schemes provided for line/transformer /generator are required to operate and line/transformer /generator are required to operate and clear the fault immediately, isolating the faulty section clear the fault immediately, isolating the faulty section of the system. It is then important that the circuit of the system. It is then important that the circuit breaker operates correctly, clearing the fault quickly by breaker operates correctly, clearing the fault quickly by tripping.tripping.

However there is a risk that breaker may not trip (either However there is a risk that breaker may not trip (either due to mechanical sluggishness or due to inability to due to mechanical sluggishness or due to inability to interrupt heavy fault current). Then the fault gets interrupt heavy fault current). Then the fault gets cleared by backup relays at remote stations.cleared by backup relays at remote stations.

Page 149: Power System Protection & Recent Trends by Jdm - Latest

• Increasing power system complexity demands shorter Increasing power system complexity demands shorter fault clearing times. It is therefore necessary to fault clearing times. It is therefore necessary to provide breaker failure relay (also called “Local provide breaker failure relay (also called “Local breaker backup relay” or “Stuck breaker protection”). breaker backup relay” or “Stuck breaker protection”). This scheme will isolate the bus to which the stuck This scheme will isolate the bus to which the stuck breaker is connected, faster. It comprises of O/L & breaker is connected, faster. It comprises of O/L & E/L relays with a timer. The LBB relay is energized E/L relays with a timer. The LBB relay is energized by trip command of main protection schemes and by trip command of main protection schemes and thus initiate master trip relay of the busbar protection thus initiate master trip relay of the busbar protection scheme after elapsing of defined time. Then the entire scheme after elapsing of defined time. Then the entire breaker connected to the bus get tripped, thus breaker connected to the bus get tripped, thus isolating faulty element.isolating faulty element.

Page 150: Power System Protection & Recent Trends by Jdm - Latest
Page 151: Power System Protection & Recent Trends by Jdm - Latest

• In A.P System, ABB make RAICA, GEC make In A.P System, ABB make RAICA, GEC make CTIG39 type breaker failure relays are commonly CTIG39 type breaker failure relays are commonly used. The general practice is to set the current setting used. The general practice is to set the current setting = 20% of In and Time setting = 200 m .Sec. The = 20% of In and Time setting = 200 m .Sec. The schematic diagrams for the application of the LBB schematic diagrams for the application of the LBB relay (type CTIG) are indicated in the figure.relay (type CTIG) are indicated in the figure.

• Even if the busbar protection scheme is not available, Even if the busbar protection scheme is not available, the LBB scheme can be made use of by providing the LBB scheme can be made use of by providing special trip circuits and trip relays similar to that of special trip circuits and trip relays similar to that of bus protection trip circuits for each line. A schematic bus protection trip circuits for each line. A schematic for such application is indicated in figure for such application is indicated in figure

Page 152: Power System Protection & Recent Trends by Jdm - Latest