Air Circuit BreakersSeries 3SW68
1-1www.sassin.com
Power Distribution Electrics
Body 1
Front drawer base
Body 2
Shell
Terminal block
Busbar
Back drawer base
Arc chute
Auxiliary switch
Motor
Current Transformer
Contact system
Release
Operating mechanism
Intelligentauxiliary switch
Overview
Air Circuit BreakersSeries 3SW68
1-2 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Applications and functions
Incoming-feeder and outgoing-feeder function in distribution systems Switching and protecting large powers, motors, capacitors, generators, transformers, busbars and cables Overload protection Short-circuit protection with short delay Instantaneous short-circuit protection Used in building, industry, energy and infrastructure
Instruction of type code
Instruction of external structure
1. Terminal of secondary circuit
2. Drawer shelf
3.
4.
5. Switching-ON button
6. Indicator of energy-storage and energy-release
7. “Unlocking button” of the three positions (“separated”,
“test” and “connected”)
8. Safety padlock position
9. Cranking bar
10. Indicator of switching-on(I) and switching-off(O)
11.
12.
13. Release indicator and resetting button
Data label
Manual energy-storage and energy-release
Intelligent controller
Switching-OFF button
Breaking capacity: N; H ; S
Rated current (A)200, 400, 630, 800, 1000, 1250, 1600 (Frame A)1250, 1600, 2000, 2500 (Frame B)2000, 2500, 3200, 4000 (Frame C)4000, 5000, 6300 (Frame D)
Connection typeH: Horizontal terminal connectionV: Vertical terminal connection
Intelligent controller modelL: L typeM: M typeH: H type
Poles: 3: 3P; 4: 4P
Installation typeF: Fix typeD: Drawer type
FrameA: 3SW68-1600B: 3SW68-2500C: 3SW68-4000D: 3SW68-6300
Series code
N200HL3FAW68
12
987
10111213 4
3
56
Strength of former insulation materials.
Strength increased after adopting new insulation materials using nanotechnology.
Air Circuit BreakersSeries 3SW68
1-3www.sassin.com
Power Distribution Electrics
Low space requirements
3SW68 devices are very compact thus require very little space for installation. Frame A devices (up to 1600 A) fit into a 400 mm wide switchgear panel.Frame B,C,D devices (up to 6300 A) are the smallest of their kind and with their smallest construction width fits into a 800 mm wide switchgear panel.
3SW68-1600/1600 3SW8-2000/1600
60%
40%
100%
100%
80%
60%
40%
20%
0%
Communication
The use of modern communication-capable circuit breakers opens up completely new possibilities in terms of start-up, parameterization, diagnostics, maintenance and operation. This allows varieties of ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects.
Strength of new material
55%
160140120100
80604020
0
20%
60
58
56
54
52
50
48
46
44
Four-pole circuit breaker with a drawer as an example
Strength of former insulation materials.
Strength increased after adopting new insulation materials using nanotechnology.
Former materials New materials
Actual body size Reduction of body size
Example of comparation with 3SW8 in measurement
Modular design
Components like auxiliary releases, motorized operating mechanisms,electronic releases, current sensors, auxiliary circuit signaling switches, automatic reset devices, interlocks and engagement operating mechanisms can all be exchanged or retrofitted in the back ground, thus allowing the circuit breaker to be adapted to new, changing required.
Impact strength(Mpa)
Bending strength(KI/m²)
Features and benefits
Former materials New materials
Air Circuit BreakersSeries 3SW68
1-4 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Complete current range and high-breaking capacity
Icu (kA)
Ics (kA)
Icw(kA/1s)9080706050403020100
AC400V-N AC400V-H AC690V-N AC690V-H
Icu (kA)
Ics (kA)
Icw(kA/1s)160
140
120
100
80
60
40
20
0
Icu (kA)
Ics (kA)
Icw(kA/1s)120
100
80
60
40
20
0
Icu (kA)
Ics (kA)
Icw(kA/1s)70
60
50
40
30
20
10
0AC400V-N AC400V-H AC690V-N AC690V-H
3SW68-1600 Rated current In(A)
3SW68-2500 Rated current In(A)
3SW68-4000 Rated current In(A)
3SW68-6300 Rated current In(A)
3SW68-1600 Breaking capacity
3SW68-2500 Breaking capacity
3SW68-4000 Breaking capacity
3SW68-6300 Breaking capacity
200
400
630
800
1000
1250
1600
1000
1250
1600
2000
2500
2000
2500
3200
4000
4000
5000
6300
65 42 42
30 30 30
35 35 35
65 65 65
85 85 85
50 50 50
65 65 65
85 85 85
100 100 100
120 100 100
85 85 85
65 65 65
100 100 100
100 100 100
120 120 120
150 150 135
65 55 50
AC400V-N AC400V-H AC400V-S AC690V-N AC690V-H
AC400V-N AC400V-H AC400V-S AC690V-N AC690V-H
85 85 85
Air Circuit BreakersSeries 3SW68
1-5www.sassin.com
Power Distribution Electrics
D63003,4
N H S4000 5000 6300
50/60400,690
100012
100%In
100 120 15085 100 100
100 120 15085 100 100
220 264 330187 220 220
100 120 13585 100 100
25-3070
1000800
500010000
Technical specifications:
30° 30°
3SW68-1600IEC60947-2
CEA
16003,4
N H200 400 630 800 1000 1250 1600
50/60400,690
100012
100%In
65 6530 35
42 5530 35
143 14363 73
42 50- -
25-3070
65003000
1500030000
30° 30° 30° 30° 30° 30°
-5 to +40℃, max. 95 % humidity-40 to +75℃
2000
Fixed /DrawerWxHxD
248x351x297318x351x597248x351x297318x351x297254x320x194324x320x194254x320x194324x320x194
B25003,4
N H1250 1600 2000 2500
50/60400,690
100012
100%In
65 8550 65
65 8550 65
143 187105 143
65 85- -
25-3070
50002500
1250025000
C40003,4
N H S2000 2500 3200 4000
50/60400,690
100012
100%In
85 100 12065 85 85
85 100 10065 85 85
187 220 264143 1 65 165
85 100 10065 85 85
25-3070
20001500
1000020000
Fixed /DrawerWxHxD
347x450x390442x450x390347x450x390442x450x390
367x403x308.5462x403x308.5367x403x308.5462x403x308.5
Fixed /DrawerWxHxD
440x450x390556x450x390440x450x390556x450x390
460x403x308.5586x403x308.5460x403x308.5586x403x308.5
Fixed /DrawerWxHxD
769x487x390995x487x390769x487x390995x487x390785x407x290
1010x407x290785x407x290
1010x407x290
TypeStandardApprovalFrame typeRated frame current In (A)Number of polesClass of breaking capacityRated current In(A)
Rated frequency (Hz)Rated voltage, Ue (V) Rated insulating voltage Ui (V)Rated impulsed withstand voltage, Uimp(kV)N-pole rated current Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 400V O-CO (kA)(AC) 50-60 Hz 690V O-CO (kA) Rated operating short-circuit breaking capacity,Ics(AC) 50-60 Hz 400V O-CO-CO (kA)(AC) 50-60 Hz 690V O-CO-CO (kA) Rated short-circuit making capacity (peak),Icm(AC) 50-60 Hz 400V (kA)(AC) 50-60 Hz 690V (kA) Rated short-time withstand current for 1s Icw (kA)(AC) 50-60 Hz 400V (kA/s)(AC) 50-60 Hz 690V (kA/s) Making time msMax breaking time msElectrical life (times) in 400V in 690VMechanical life (times) without maintenance with maintenanceMounting position
Installation typeDismension (mm)Drawer,horizontal, 3P Drawer,horizontal, 4PDrawer,Vertical, 3PDrawer,Vertical, 4PFixed,horizontal, 3PFixed,horizontal, 4PFixed,Vertical, 3PFixed,Vertical, 4PAmbient temperatureStorage temperatureAltitude( Max)
3SW68-2500IEC60947-2
CEIEC60947-2
CEIEC60947-2
CE
3SW68-4000 3SW68-6300
Air Circuit BreakersSeries 3SW68
1-6 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Basic protection
Overload protection
Short-time delayed short-circuit protection
Instantaneous short-circuit protection
Ground fault protection
Neutral pole protection
Additional functions
MCR Function
Thermal memory
Contact loss indicator
Self-diagnostic function
Fault memory
Test function
Zone Selective Interlocking
Closing counting
Parameter display
Fault trip display
Load monitoring display
Current display
Achieve communication through device net
Time display
Measurement
Current measurement
Voltage measurement
Frequency measurement
Power measurements
Power factor measurement
Phase sequence detection
Imbalance function
Energy measurement
Harmonic measurement
Protection
Overvoltage protection
Undervoltage protection
Imbalance protection
Over frequency protection
Under-frequency protection
Phase sequence protection
Inverse power protection
Communication
Communication Interface
Achieve communication through MODBUS
Achieve communication through PROFIBUS
L
S
I
G
N
Intelligent controller model
3SW68-L
Function
3SW68-H 3SW68-M
Intelligent controller characteristics
Note: “ ” available “ ” selectable ” ” unavailable
Air Circuit BreakersSeries 3SW68
1-7www.sassin.com
Power Distribution Electrics
Intelligent controller model and panel description
Intelligent controller model type 3SW68-L Basic 3SW68-M Standard 3SW68-H Communication
Introduction of intelligent controller panel
L type Intelligent controller panel(3SW68-1600)
Note: Parameter setting IR <Isd <II
1. RESET Button It pops up when fault tripping or test tripping. The circuit breaker can be switched on only when the button is pressed down. Meanwhile, the fault indicator resets.2. Indication of rated current (In)3. MCU indicator It remains lit when the controller is under normal working.4. Over-voltage indicator It lights up when current reaches 1.15IR.5. Current bar indicator To display the real time current as the percentage of IR; 10% each step.6. Fault reason indicator To show the fault reason after tripping occurs. If power supply works normally, it will indicate the fault reason after fault tripping. Press RESET to quit. If power supply is lost, press FAULT CHECK key to show the reason of last tripping when power recovers.7. Current settings adjustor8. Time settings adjustor9. FAULT CHECK key Press the key to enter fault check status when the controller is under normal working.10. TEST key Press TEST key, the breaker trips immediately, but no fault recorded. Press RESET and CLEAR after test. 11. CLEAR key
1
2 3
45
6
789
10
11
Air Circuit BreakersSeries 3SW68
1-8 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
M type and H type Intelligent controller panel for (3SW68-1600)
Indication1. RESET button It pops up when fault tripping or test tripping. The circuit breaker can be switched on only when the button is pressed down. Meanwhile, the fault indicator resets.2. LCD display3. Fault and alarm RESET key4. FAULT/ALARM LED indicator The indicator is out when normal working; it flashes quickly when maintenance; it turns on in red when alarm.5. NORMAL LED indicator It flashes in green always when the controller is power on and under normal working.6. LED curve Red LED indicators are equipped in the curve. The corresponding indicator flashes to indicate the fault reason when fault tripping. The corresponding indicator remains lit to indicate the current setting when protection settings.7. Test port A 16-pin test port is available on the bottom of front panel for plug-in portable power supply or inspection unit.
Keyboard 8. Function key 1 – Measurement: For measuring (In password input interface, the LEFT key) Press to enter the measurement default menu to measure current “I”, voltage “U’, frequency “F”, power “P”, energy “E”, and harmonic “H”.9. Function key 2 – Settings: For system parameter settings (In password input interface, the RIGHT key) Press to enter the setting default menu to set “Clock settings”, “Meter settings”, “Test & Lock”, “Communication settings”, “I/O settings”.10. Function key 3 – Protections: For protection parameter settings Press to set the parameters of “Current protection”, “Load monitor”, “Voltage protection”, and “Other protections”. 11. Function key 4 – Information: For history record and maintenance Press to check “Current alarm”, “Operation times”, “Contact wear”, “Product information”, “Tripping record”, “Alarm record”, “Transposition record”.12. UP – To move up or change the parameters upwards13. DOWN – To move down or change the parameters downwards.14. Esc – To exit and return to previous menu or cancel the current setting selection.15. ENTER – To enter the next menu, select the current parameter, or save the updates.
ESC
IR
Is
IsdIg
Ii
3SW68Intelligent controller
Reset
Fault/Alarm
Normal
8 9 10 11
12 13 14 15
1
2
3
45
6
7
ESC
Air Circuit BreakersSeries 3SW68
1-9www.sassin.com
Power Distribution Electrics
L type Intelligent controller panel(3SW68-2500、4000、6300)
1. Mechanical RESET button It pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. Operation indicator It remains flashing when the controller is under normal working.4. IR% 40%~100% indicator: To display the real time current as the percentage of IR.5. Indication of rated current (In)6. Simulation test area 6.1.Query key: check the last fault record (Record is shown as: one of the four fault indicators, IR, Isd, Ii, and Ig, becomes lighting. Press Clear button to clear indication). 6.2.Test key: When press Test Key under normal working status of controller, the breaker, commanded by the controller, trips instantaneously. Meanwhile, Ii fault indicator lights up, but no fault recorded. 6.3.Check key: self-diagnosis of inner working, each light will automatically scan, and will show a menu in one minute. 6.4.Clear button: clear the fault indicator7. Protect characteristic parameter setting area 7.1. IR (time-lapse protection) original setting is IR = 1.0 I n, t R = 480s. 7.2. I sd (short delay protection) original setting is I sd = 8 IR t sd = 0.4s (NO, OFF means inverse switch status default setting is OFF). 7.3. I i (instantaneous protection) original setting Ii =10In. 7.4. I g (ground fault protection) original setting I g = 0.8 I ntg = 0.4s.8. Fault indicator: Lighting when fault occurs.
运行 通信 遥控 故障
Electronic Controller
3SW68 L-
I R% Load current
40 60 80 100
In= A 4000
0.6
1.00.9
0.50.40.30.2
0.80.7
1.0
0.70.60.50.4 1.0
0.950.9
0.850.8
OFF
OFF
0.6
0.80.75
0.50.40.30.2
0.70.65
OFF
10864
321.5
1215
432
1512108
OFF
6
1
90604530 480
360240180120
15
0.10.2
0.40.30.20.1
0.30.4
2I t OFFON @8IR
@1.5 IR
Isd
Ii
Ig
tR S
tsd s
tg s
In
In
In
IR
IR
2
4
6
8
3
5
7
1
Operation
Quary Test Check Clear
Air Circuit BreakersSeries 3SW68
1-10 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
M type Intelligent controller panel (3SW68-2500、4000、6300)
1. Mechanical RESET button It pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. Power indicator: It keeps flashing when power on.4. LCD display5. Indication of rated current (In)6. Simulation test area
6.1. ENTER key: To enter or confirm menu.
6.2. ESC key: To return to previous menu or exit menu
6.3. UP DOWN key: To scroll up or down the menu
7. Protection characteristic parameter setting area7.1. IR ( long-time delay protection) default setting IR=1.0In, t R = 480s7.2. I sd (short delay protection) default setting Isd=8IR , tsd = 0.4s (NO, OFF means inverse switch, original setting is OFF)7.3. I i (instantaneous protection) default setting I i = 10 I n7.4. I g (ground fault protection) default setting I g = 0.8 I n, tg = 0.4s8. Fault indicator: Lighting when fault occurs.
Electronic Controller
3SW68-M
In= A
0.6
1.00.9
0.50.40.30.2
0.80.7
1.0
0.70.60.50.4 1.0
0.950.9
0.850.8
OFF
OFF
0.6
0.80.75
0.50.40.30.2
0.70.65
OFF
10864
321.5
1215
432
1512108
OFF
6
1
90604530 480
360240180120
15
0.10.2
0.40.30.20.1
0.30.4
2I t OFFON @8IR
@1.5 IR
Isd
Ii
Ig
tR
tsd
tg
In
In
In
IR
IR
0.6
1.00.9
0.50.40.30.2
0.80.7
1.0
ESCESC
0.70.60.50.4 1.0
0.950.9
0.850.8
OFF
OFF
0.6
0.80.75
0.50.40.30.2
0.70.65
OFF
10864
321.5
1215
432
1512108
OFF
6
1
90604530 480
360240180120
15
0.10.2
0.40.30.20.1
0.30.4
2I t OFFON @8IR
@1.5 IR
Isd
Ii
Ig
tR S
tsd S
tg(S)
In
In
In
IR
IR
4000
2
4
6
8
3
5
7
1
ESCESC
Operation
Air Circuit BreakersSeries 3SW68
1-11www.sassin.com
Power Distribution Electrics
ESCESC
In= A
Electronic Controller
3SW68 H-
RESET
Warn/Alarm
Healthy
BUS
IR
Is
I sd
I i
I g
4000
2
3
4
1
5
6
7
8
H type Intelligent controller panel(3SW68-2500、4000、6300)
1 Mechanical RESET buttonIt pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. LCD display4. Indication of rated current (In)5. Software RESET button6. Status indicator area7. Characteristic curve and protection reason indicator8. Function key area
.
Air Circuit BreakersSeries 3SW68
1-12 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Intelligent controller protection characteristics
SW68-L and 68-M3 3SW
OFF (Set by user) Setting current adjustment range IR(A)
tR(S) at 7.2IR
tR(S) at 2IR
1.05IR
≤2h action
2h no action
0.4xIn 0.45 0.5 0.55 0.6 0.7 0.8 0.9 1.0xIn xIn xIn xIn xIn xIn xIn xIn
15 30 60 120 240 480 Note: 30,60,120,240 for 3SW68-L(1600)
8.4 16.9 33.7 67.5 135 270
0.65 1.3 2.6 5.2 10.4 20.8
60 Note: 30 min for 3SW68-L(1600)
When 1>8IR
When 1>8IR
Inverse characteristic (set by user) I²tsd(s)(according to requirements set by the user) I²tsd(s)
0.1 0.2 0.3 0.4
0.06 0.14 0.23 0.35
As per characteristic curves
OFF 1.5xIR 2xIR 2.5xIR 3xIR 4xIR 5xIR 6xIR 8xIR 10xIR 12xIR 20xIR
Note: (3,4,6,8,10,12,15)In for 3SW68-L(1600)
OFF 0.2xIn 0.3xIn 0.4xIn 0.5xIn 0.6xIn 0.7xIn 0.8xIn 0.9xIn 1.0xIn
(Note: (0.2~0.8)In for 3SW68-L(1600)
0.1 0.2 0.3 0.4
0.06 0.14 0.23 0.35
Inverse time characteristics
1.3 1.25IR( IR for generator protection))
tR(S) at 1.5IR
Thermal memory time setting(min)
Returnable time (s)
Earth fault settings ( ±10%)accuracy
Setting current adjustment range Ig(A)
Overload alarm setting (accuracy ±10%)
Overload alarm currentDelay time tm (s)
Inverse time characteristics
0.5tR
when Im>IR
Setting current adjustment range Isd(A)
Definite characteristic (set by user) tsd(s) (according to requirements set by the user) tsd(s)
Instantaneous short-circuit setting (accuracy of ±10%)
Setting current adjustment range Ii(A)
Definite time characteristics ( set by user) tg(s)
Returnable time (s)
Inverse time characteristics (set by user) I²tsd(s)
OFF 1.5xIR 2xIR 2.5xIR 3xIR 4xIR 5xIR 6xIR 8xIR 10xIR 12xIR 20xIR Note:(3~10)IR for 3SW68-L(1600)
Overload long-time delay settings (accuracy ±10% based on tR(s) at 1.5IR)
Short-circuit short-time delay settings (accuracy ±10% based on tR(s) at 1.5IR when I<8IR)
As per characteristic curves
Air Circuit BreakersSeries 3SW68
1-13www.sassin.com
Power Distribution Electrics
3SW68-H
Setting current adjustment range Isd (A) ±10% accuracy
Short circuit short definite time Isd(A)
Setting delay time tsd(s)±15% accuracy
1/10tR (tR(s)when 1.5IR as a benchmark)
0.1 0.2 0.3 0.4 0.06 0.14 0.23 0.35
Instantaneous short-circuit ISetting current adjustment range Ig(A)±10% accuracy
Ground protection type T WSetting current adjustment range Ig(A)±10% accuracySetting delay time tg(s) ±15% accuracy 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0.06 0.14 0.23 0.35 resetting ratio is 0.85
Current imbalancealarm/trip/off selectabe
alarm/trip/off selectabe
(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done.
(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done.
Required current protection
Setting range of value of start protection required(0.2~1)xInSetting range of protection action time required 15~1500s
Under voltage protection
Load monitoring (power based)
Over voltage protection
Alarm/trip selectable(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done; the return character will be lower than 0.9 setting value.
Made 1/mode 2/OFF selectableMeasurementFrequencyPower
Electric energy
Current DemandPower DemandHarmonic Self-test function
DI/DO FunctionZone selective interlocking featureTest function
40~65HzActive power: -32768kW~32768kWReactive power: -32768kar~32768karApparent power: 0kVA~65535kVAActive energy: 0~4294967295kWhReactive energy: 0~4294967295kWhApparent energy: 0~4294967295kWhCurrent real-time measurementsPower real-time measurementsCurrrent:3~31harmonicVoltage:3~31harmonicThe EEPROM fault, setting parameters lost, AD sampling error, RAM or ROM error, error messages and alarm signalsProvide digital input and output (AC250V 5A resistive or DC110V 0.5A resistive)Short circuit interlock and ground interlockTest release: Long-time delay, short-time delay ,instantaneous ,ground
ON/OFF selectable
1.05IR
1.30R(Generator protection 1.25IR)
Delay time
Inverse time characteristics
Thermal memory time setting
Setting current adjustment range Isd ±10% accuracy
8.4 16.9 33.8 67.5 135 2700.94 1.88 3.75 7.50 15 300.65 1.3 2.6 5.2 10.4 20.8
Instantaneous 10 20 30 45 60 120 180
Set by the user as needed, tR(s)when 1.5IR as a benchmark,10% accuracy)(0.4~1.0)xIn (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)
ON/OFF selectable(1.5~15)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)
ON/OFF selectable(1.5~15)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)
ON/OFF selectable(1.0~20)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)
ON/OFF selectable(0.2~1.0)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)
Setting current adjustment range IR(A)
15 30 60 120 240 480
Alarm/trip selectable(When the current imbalance is greater than 1.1 times the set value,the protection action will be done; the return character will be lower than 0.9 setting value.
Overload long-time delay settings
≤2h action2h no action
tR(S) at 7.2IR
tR(S) at 2IRtR(S) at 1.5IR
tR(S) at 6.0IR
Short-circuit short-time delay settings
Returnable time (s)
Returnable time (s)
Air Circuit BreakersSeries 3SW68
1-14 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Current protection characteristics for intelligent controller
Monitor and controlling setting(R)
setting(lc1)
setting(lc1)
2l tswitch off2l tinput
t
0 I
Short-circuit short-time delay definite time (I²t OFF)
Overload long-time delay current setting IROverload long-time delay time setting tR
Short- circuit short-time delay current setting Isd Short-circuit short-time delay inverse time (I²t ON) Short-circuit short-time delay time setting tsd nstantaneous setting IiShort-circuit i
Long delay, short delay, instantaneous protection features
I
t
Characteristics curve
Earth fault current setting Ig
Earth fault delay time setting tg
Earth fault protection features
t
I
Air Circuit BreakersSeries 3SW68
1-15www.sassin.com
Power Distribution Electrics
Protection characteristics of intelligent controller 3SW68-H
Characteristics curve of overload protection
00801 02 03 05 081 1 5 2 3 5 8 10
10000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
Ig earth fault protection current setting value tg fault protection time setting valueearth
0.4s0.3s0.2s0.1s
Ir4=0.2ln-1.01ln
t (s)
x ln
Earth fault protection characteristic curve
Isd
Ir3
Ir3
t (s)10000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.8 1 1.5 2 3 5 8 10 15 20
× IR
Ir1=0.4-1 X In
tL=15StL=30StL=60StL=120StL=240StL=480S
Ir2=1-15 x In
t
ts=0.3S
ts=0.2S
ts=0.1S
s=0.4S
kA30 60 90 100 120 150 200
Ir1: Overload long-delay setting Ir2: Short-circuit short-delay current settingIr3: Overload long-delay time settingTl: Instantaneous short-circuit current settingTs: Short-circuit short-delay time setting
Air Circuit BreakersSeries 3SW68
1-16 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Kinds of characteristic overview ( rate curve: C8)
Fast inverse time lag C8
trip
tim
e (s
ecs)
* Ir (setting value of long time delay)
standard inverse time lag C8 fast inverse time lag C8express inverse time lag C8 express inverse time lag(M) C8
high voltage fuse compatibility C8 2I t C1
0.01
0.1
1
10
100
1000
1 10
Express inverse time lag C8
* Ir (setting value of long time delay)
0.1
1
10
100
1000
1 10
* Ir (setting value of long time delay)
0.1
1
10
100
1000
10000
1 10
trip
tim
e (s
ecs)
trip
tim
e (s
ecs)
* Ir (setting value of long time delay)
0.1
1
10
100
1000
10000
1 10
trip
tim
e (s
ecs)
Standard inverse time lag C8
Air Circuit BreakersSeries 3SW68
1-17www.sassin.com
Power Distribution Electrics
The meaning of terminals
SB1
SB2SB3
S1~S7DW
XT
TA
FUFQ
QY
DT
M
SASAL
Q1~Q8Q9~Q14
Abbreviation MeaningClosing button (self-providedby user)Shunt button (self-provided byuser)Under-voltage button(self-provided by user)Indicator (self-provided by user)Circuit breaker
Secondary wiring circuit
Current mutual transformer
Fuse (self-provided by user)Shunt releaseUnder-voltage releaseUnder-voltage delay release with time delay Closed coil
Motor operating mechanism
Limit switch of motorContact for malfunction tripping indicatorAuxiliary contacts 4NO+4NCContacts for drawer 3-position indicator
Abbreviation Abbreviation Meaning Meaning
Connection diagram for the secondary circuit of the L-type intelligent controller
1 2 3 4
5 6 8 10 12 14 16 18 20 22 24 26
SB1 E
SB2 E
SB3 E
XT
DW
TA
AC220V/DC110-220V
DC24V
FU
M
SA
28
58 61 6446 49 52 5537 39 41 437 9 11 13 15 17 19 21 23 2527 29 31 33 35
30 32 34 36 38 40 42 44 45 47 48 50 51 53 54 56 57 59 60 62 63 65 66
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13Q14
DT F Q/QY
P
FU
L N PE
12 13 14 15 16 17 18 19
S5 S6 S7S2 S3 S4S1
PE N
SAL
FU
- +
Electronic controller Auxiliary contact for user
Fault indicator Storage indicator Closing indictor Tripping indicator
Control power supply
Breaker body
ST Power modules TV
Shuntrelease
Closingelectromagnet
Contracteletromanet
Under-voltagerelease Drawer three-position indication
Electronic controller
Maincircuit
#1, #2: Input terminal of auxiliary power supply; #1 is the positive pole.P: Protective ground terminal to connect the side plate of the breaker.#3, #4, #5: SDE malfunction tripping output contacts (#4 is the common terminal); contact capacity: AC380V 16A#13, #14, #19, #20, #21: #19 is the output common terminal; #20 is output contact No.1 (D01) for self-diagnosis function; #21 is output contact No.2 (D02) for malfunction tripping function; #13 is output contact No.3 (D03) for overload warning function; #14 is output contact No.4 (D04) for grounding alarm function.#25, #26: To connect external current transformer (For 3P+N only)Note:1)It is necessary to select power supply unit when DC control power is applied. Connect the DC control power to power supply unit, where the output contacts have already been connected before delivery.2)Normally it is not necessary to select power supply unit when AC control power is applied; just simply connect the power supply to the terminal #1 and #2. In case you require power supply unit, please make the connection according to the wiring diagram. The output contacts of the unit have already been connected before delivery.3)Drawer 3-position indicator is an optional device for users.4)The connections marked in the dotted lines are to be made by the users.5)The conditions that the controller outputs self-diagnosis signal:a.Controller internal temperature ≥80℃b.Chip works abnormallyc.Controller loses power6)Different power supplies can be connected when the control voltages of DT, F and Q/QY are not same.7)A pushbutton with normal open contact can be installed in series between the terminal #42 and power supply for manually controlling pre-storage.8)SB2 can be connected in parallel to relay contacts for remote tripping.9)Additional accessories need to be self-provided by users.
Air Circuit BreakersSeries 3SW68
1-18 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
1 2 5 6 7 8 9 10 13 15 16 29 30
3 4 17 18 19 20 21 22 23 24
12
25
A (+) B (-)
L1~L4
P1~P3
ZT100
DW
ZCT
A,B,C
N
A (+) B (-)
D01 D02
D03 OR DI2 D04 OR DI1
P 11 14
282726
DC24V
Un U1 U2 U3
Power input
Auxiliary contacts synchronous with the circuit breaker
Communication ground wire Communication
port
Add N-phase input in 3P + N
3SW68-1600 Intelligent controllerLinear signal coil
Power mutual inductor Add mutual inductor input in ground or leakage
Voltage measurement signal input
Center ground lug
Programmable input / Output contacts
To the power line side
Figure: input and output interfaces of 3SW68-1600 type M, H
Connection port of 3SW68-1600(type M、H)
1 2
6 8 10 12 14 16 18 20 22 24 26
SB1 E
SB2 E
SB3 E
XT
DW
TA
AC220V/DC110-220V
DC24V
FU
M
SA
28
58 61 6446 49 52 5537 39 41 4311 13 15 17 19 21 23 25 27 29 31 33 35
30 32 34 36 38 40 42 44 45 47 48 50 51 53 54 56 57 59 60 62 63 65 66
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13Q14
DT F Q/QY
P
FU
L N PE
12 13 14 15 16 17 18 19
S5 S6 S7S4S1
PE N
SAL
FU
- +
5 7 9
3 4
S3S2
Contract electromagnet
Under-voltagerelease Auxiliary contact for user Drawer 3-position indicator
Control power supply
Electronic controllerBreaker body
Main circuit Electronic controller Closing
electromagnet Shunt release
Fault indicator Storage instruction Closing instruction Tripping indication
ST Power modules TV
Note: Short 3 and 4 when no external currenttransformer needs to beconnected
Connection diagram for secondary circuit of the M , H-type intelligent controller
Qa Qb Qc Qd
Air Circuit BreakersSeries 3SW68
1-19www.sassin.com
Power Distribution Electrics
SB1SB2SB3
S1~S7DWXT
TAFUFQ
QYDT
MSA
SAL
Q1~Q8Q9~Q14
Meaning Abbreviation Meaning Meaning
TN
Qa , QbQc , Qd
Motor operating mechanism Limit switch of MotorContact for malfunction tripping indicatorContacts for closing indicatorContacts for tripping indicatorAuxiliary contacts 4NO+4NCContacts for drawer 3-position indicator
Current mutual transformerFuse (self-provided by user)Shunt releaseUnder-voltage releaseUnder-voltage delay release with time delay Closed coil
AbbreviationAbbreviationClosing button (self-provided by user)Shunt button (self-provided by user)Under-voltage button(self-provided by user)Indicator (self-provided by user)Circuit breakerSecondary wiring circuitResidual current transformer (can be supplied upon user’s request)
The meaning of terminalsPower supply input#1, #2: DC24V #1: positive pole #2: negative pole; P: Protective ground terminal to connect the side plate of the breaker.External current transformer inputTerminals #3, #4 are for external current transformer input.The terminals are to be connected to the output terminals of external current transformer ZT100 when the grounding method is type T.The terminals are to be connected to the output terminals of external rectangular current transformer ZCT1 when the grounding method is type W.Auxiliary contacts for malfunction trippingTerminals #5, #6, #7 are the contacts for malfunction tripping indicator. Contact capacity: AC380V 2A; DC250V 0.3AAuxiliary contacts synchronous with circuit breakerTerminals #8, #9, #10, #11, #12, #14 are two sets of auxiliary contacts synchronous with circuit breaker. Contact capacity: AC380V 1A; DC250V 0.15ACommunication output#15, #16: Communication interface output. The output methods of three communication protocols are the same. #15 and #16 are blank when with communication function.#13: Communication shielding groundProgrammable I/O interfaceTerminals #17~#24 are blank when signal unit is not selected. (DO: DC11V 0.5A, AC250V 5A; DI: DC11V~13V AC110V~250V)When the signal unit is type S1: (4DO mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)#21, #22: Programmable output contact No.3 (DO3)#23, #24: Programmable output contact No.4 (DO4)When the signal unit is type S2: (3DO+1DI mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)#21, #22: Programmable output contact No.3 (DO3)#23, #24: Programmable switching input No.1 (DI1)When the signal unit is type S3: (3DO+1DI mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)
#21, #22: Programmable switching input No.1 (DI1)#23, #24: Programmable switching input No.2 (DI2)Voltage signal inputTerminals #25~#28 are the input terminal of voltage signal. Please pay attention that the connection sequence must be right and they must be connected to the line side of the power supply. The terminals are blank if no additional functions are selected.Terminals #29~#30 are to be connected to signal input of neutral line with an external current transformer when grounding method is 3P+N.Note:1) It is necessary to select power supply unit when DC control power is applied. Connect the DC control power to power supply unit, where the output contacts have already been connected before delivery.2) Normally it is not necessary to select power supply unit when AC control power is applied; just simply connect the power supply to the terminal #1 and #2. In case you require power supply unit, please make the connection according to the wiring diagram. The output contacts of the unit have already been connected before delivery.3) Drawer 3-position indicator is an optional device for users.4) The connections marked in the dotted lines are to be made by the users.5) The conditions that the controller outputs self-diagnosis signal:a. Controller internal temperature ≥80℃b. Chip works abnormallyc. Controller loses power6) Different power supplies can be connected when the control voltages of DT, F and Q/QY are not same.7) A pushbutton with normal open contact can be installed in series between the terminal #42 and power supply for manually controlling pre-storage.8) SB2 can be connected in parallel to relay contacts for remote tripping.9) Additional accessories need to be self-provided by users.
Air Circuit BreakersSeries 3SW68
1-20 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Secondary circuit wiring diagram equipped with Intelligent controller (3SW68-2500、4000、6300)
Main circuit
Position indication
Control unitUnder
voltageElectric
switch onElectric
switch offElectric energy storage
Ready-for-close
Remote
resetAuxiliary sw
itch
ConnectionTest
Separation
Fault tripping
Switch on
Switch off
Ready-for-charging
Circuit breakerPow
er source
Draw-out base communication
module
Power module output
Six line program-mable extended output module
Ready-for-close
Auxiliary switch
Intelligent controller
Auxiliary open mode
Four groups convertible contactFour pieces of normally-open and four pieces of normally-closed contacts
Six-group convertible contactSix pieces of normally-open and six pieces of normally-closed contacts
picture 1Perm
utation and combination of external term
inal picture 2
Permutation and com
bination of internal terminal
picture 3
Air Circuit BreakersSeries 3SW68
1-21www.sassin.com
Power Distribution Electrics
Explanation of terminal block:1#、2#: Auxiliary power input 1# is“+” 2# is“-”if it is direct current3#、4#、5#、6#: A、B、C、N three-phase voltage input terminal are used for voltage indication (optional)7#、8#、9#:Fault trip indication signal output10#、11#、12#:Switch on indication signal output 13#、14#、15#:Switch off indication signal output16#、17#:Programmable output 1(optional)18#、19#:Programmable output 2(optional)20#、21#:ZS1 signal output,20# connects“+”,21# connects“-”(optional)22#、23#:ZS1signal output,22# connects“-”,23# connects“+”(optional)24#、25#、26#:Intelligent controller communication terminal,24# connects with SH Shielding layer, 25# connects A,26# connects B, but connects with the draw-out-base communication module input if there is a draw-out-base communication module,24# connects S',25# connects A',26# connects B'(optional)27#、28#:Added earth current or current leakage type transformer input(optional)29#、30#:External neutral current transformer input (optional)31#、32#、33#:Under voltage(or time delayed)release power input, 33# is empty terminal(optional)34#、35#、36#:Closing electromagnet power input,36# is empty terminal37#、38#、39#:Shunt release power input,39# is empty terminal40#、41#、42#:Energy storage electrically operated power input and energy storage ready signal output.43#、44#、45#:Open ready signal output(optional)46#、47#、48#: Remote reset power input, 48# is empty terminal (optional)49#、50#、51#:Programmable extended output,49# connects A,50# connects B, 51# is empty terminal(optional)52#、53#、54#:Empty terminal(Spare)55#~58#:Auxiliary switch for connecting terminal output
Explanation of symbol
Under-voltage button (Self-provided by user)Closing button (Self-provided by user)Shunt button (Self-provided by user) Remote reset button (Self-provided by user)Shunt releaseRemote control closed relay (Self-provided by user)Remote control trip relay (Self-provided by user)
SB1SB2SB3SB4
FJ1 J2
Under-voltage (or time delayed) releaseClosing electromagnetElectric motor operating mechanismElectric motor limit switchTerminal blockFuse
QX M SAXT Fu
Abbreviation Meaning Abbreviation Meaning
A1~A6: Three position signal output(optional)B1~B6: Empty terminal(Spare)T1~T4: Three position signal input(optional)S、A、B:Communication output(optional)
Illustration1.The corresponding circuit breakers in the diagram are switched off and no energy stored. The controller indicates no fault2.The dotted line part shall be connected by user, the picture is for reference only.3. 1#, 2# terminal power source must be prepared when the main loop current is 0.4 In. The DC24V、AC230VAC or 400V power can be connected depending on controller power type. The power then connects with DC 110VD and C220V after converted by power module.4. Q, X, F, M connects different control power sources depending on respective voltage specifications. Please note X, F are short-time duty components, the electrified time should not exceed 4 seconds.5.37# terminal directly connects power source (see the picture) (automatic pre-energy storage). It can also connect power source after serially connecting the normally open button (Manual pre-energy storage).6.The three position signal sampling from the draw-out base communication module should be processed by optical coupling isolation.7. The outdoor terminal which fixed on the drawing frame of breaker, wiring connection is according to picture 2; the terminal which fixed in internal breaker, wiring connection is according to picture 3.
Selection and ordering data
200 3P4P
400 3P4P
630 3P4P
800 3P4P
1000 3P4P
1250 3P4P
1600 3P4P
Number ofpoles Type code Order code Type code Order code
Fixed type Drawer type
L type controller
In(A)
Frame A3SW68-1600 Horizontal terminal connection
Vertical terminal connection200 3P
4P400 3P
4P630 3P
4P800 3P
4P1000 3P
4P1250 3P
4P1600 3P
4PHorizontal terminal connection
200
400
630
800
1000
1250
1600
3P4P3P4P3P4P3P4P3P4P3P4P3P4P
W68AF 3LH200NW68AF 4LH200NW68AF 3LH400NW68AF 4LH400NW68AF 3LH630NW68AF 4LH630NW68AF 3LH800NW68AF 4LH800NW68AF 3LH1000NW68AF 4LH1000NW68AF 3LH1250NW68AF 4LH1250NW68AF 3LH1600NW68AF 4LH1600N
2805728058280592806028061280622806328064280652806628067280682806928070
W68AD 3LH200NW68AD 4LH200NW68AD 3LH400NW68AD 4LH400NW68AD 3LH630NW68AD 4LH630NW68AD 3LH800NW68AD 4LH800NW68AD 3LH1000NW68AD 4LH1000NW68AD 3LH1250NW68AD 4LH1250NW68AD 3LH1600NW68AD 4LH1600N
2809928100281012810228103281042810528106281072810828109281102811128112
3W68AF 3LV200N4W68AF 4LV200N3W68AF 3LV400N4W68AF 4LV400N3W68AF 3LV630N4W68AF 4LV630N3W68AF 3LV800N4W68AF 4LV800N3W68AF 3LV1000N4W68AF 4LV1000N3W68AF 3LV1250N4W68AF 4LV1250N3W68AF 3LV1600N4W68AF 4LV1600N
2807128072280732807428075280762807728078280792808028081280822808328084
W68AD 3LV200NW68AD 4LV200NW68AD 3LV400NW68AD 4LV400NW68AD 3LV630NW68AD 4LV630NW68AD 3LV800NW68AD 4LV800NW68AD 3LV1000NW68AD 4LV1000NW68AD 3LV1250NW68AD 4LV1250NW68AD 3LV1600NW68AD 4LV1600N
2811328114281152811628117281182811928120281212812228123281242812528126
N type65kA
H type65kA W68AF 3LH200H
W68AF 4LH200HW68AF 3LH400HW68AF 4LH400HW68AF 3LH630HW68AF 4LH630HW68AF 3LH800HW68AF 4LH800HW68AF 3LH1000HW68AF 4LH1000HW68AF 3LH1250HW68AF 4LH1250HW68AF 3LH1600HW68AF 4LH1600H
W68AD 3LH200HW68AD 4LH200HW68AD 3LH400HW68AD 4LH400HW68AD 3LH630HW68AD 4LH630HW68AD 3LH800HW68AD 4LH800HW68AD 3LH1000HW68AD 4LH1000HW68AD 3LH1250HW68AD 4LH1250HW68AD 3LH1600HW68AD 4LH1600H
2814128142281432814428145281462814728148281492815028151281522815328154
2818328184281852818628187281882818928190281912819228193281942819528196
Rated current
Air Circuit BreakersSeries 3SW68
1-22 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
200
400
630
800
1000
1250
1600
Type code Order code Type code Order codeFixed type Drawer type
In(A)3P4P3P4P3P4P3P4P3P4P3P4P3P4P
Vertical terminal connection
200
400
630
800
1000
1250
1600
3P4P3P4P3P4P3P4P3P4P3P4P3P4P
M type controllerHorizontal terminal connection
H type65kA
W68AF 3LV200HW68AF 4LV200HW68AF 3LV400HW68AF 4LV400HW68AF 3LV630HW68AF 4LV630HW68AF 3LV800HW68AF 4LV800HW68AF 3LV1000HW68AF 4LV1000HW68AF 3LV1250HW68AF 4LV1250HW68AF 3LV1600HW68AF 4LV1600H
2815528156281572815828159281602816128162281632816428165281662816728168
W68AD 3LV200HW68AD 4LV200HW68AD 3LV400HW68AD 4LV400HW68AD 3LV630HW68AD 4LV630HW68AD 3LV800HW68AD 4LV800HW68AD 3LV1000HW68AD 4LV1000HW68AD 3LV1250HW68AD 4LV1250HW68AD 3LV1600HW68AD 4LV1600H
2819728198281992820028201282022820328204282052820628207282082820928210
N type65kA W68AF 3MH200N
W68AF 4MH200NW68AF 3MH400NW68AF 4MH400NW68AF 3MH630NW68AF 4MH630NW68AF 3MH800NW68AF 4MH800NW68AF 3MH1000NW68AF 4MH1000NW68AF 3MH1250NW68AF 4MH1250NW68AF 3MH1600NW68AF 4MH1600N
2822528226282272822828229282302823128232282332823428235282362823728238
W68AD 3MH200NW68AD 4MH200NW68AD 3MH400NW68AD 4MH400NW68AD 3MH630NW68AD 4MH630NW68AD 3MH800NW68AD 4MH800NW68AD 3MH1000NW68AD 4MH1000NW68AD 3MH1250NW68AD 4MH1250NW68AD 3MH1600NW68AD 4MH1600N
2826728268282692827028271282722827328274282752827628277282782827928280
Vertical terminal connection200 3P
4P400 3P
4P630 3P
4P800 3P
4P1000 3P
4P1250 3P
4P1600 3P
4P
W68AF 3MV200NW68AF 4MV200NW68AF 3MV400NW68AF 4MV400NW68AF 3MV630NW68AF 4MV630NW68AF 3MV800NW68AF 4MV800NW68AF 3MV1000NW68AF 4MV1000NW68AF 3MV1250NW68AF 4MV1250NW68AF 3MV1600NW68AF 4MV1600N
2823928240282412824228243282442824528246282472824828249282502825128252
W68AD 3MV200NW68AD 4MV200NW68AD 3MV400NW68AD 4MV400NW68AD 3MV630NW68AD 4MV630NW68AD 3MV800NW68AD 4MV800NW68AD 3MV1000NW68AD 4MV1000NW68AD 3MV1250NW68AD 4MV1250NW68AD 3MV1600NW68AD 4MV1600N
2828128282282832828428285282862828728288282892829028291282922829328294
Rated current Number ofpoles
L type controllerFrame A3SW68-1600
Air Circuit BreakersSeries 3SW68
1-23www.sassin.com
Power Distribution Electrics
200 3P4P
400 3P4P
630 3P4P
800 3P4P
1000 3P4P
1250 3P4P
1600 3P4P
Type code Order code Type code Order codeFixed type Drawer type
M type controller
In(A)
Frame A3SW68-1600 Horizontal terminal connection
Vertical terminal connection200 3P
4P400 3P
4P630 3P
4P800 3P
4P1000 3P
4P1250 3P
4P1600 3P
4P
H type65kA
W68AF 3MH200HW68AF 4MH200HW68AF 3MH400HW68AF 4MH400HW68AF 3MH630HW68AF 4MH630HW68AF 3MH800HW68AF 4MH800HW68AF 3MH1000HW68AF 4MH1000HW68AF 3MH1250HW68AF 4MH1250HW68AF 3MH1600HW68AF 4MH1600H
2830928310283112831228313283142831528316283172831828319283202832128322
W68AD 3MH200HW68AD 4MH200HW68AD 3MH400HW68AD 4MH400HW68AD 3MH630HW68AD 4MH630HW68AD 3MH800HW68AD 4MH800HW68AD 3MH1000HW68AD 4MH1000HW68AD 3MH1250HW68AD 4MH1250HW68AD 3MH1600HW68AD 4MH1600H
2835128352283532835428355283562835728358283592836028361283622836328364
W68AF 3MV200HW68AF 4MV200HW68AF 3MV400HW68AF 4MV400HW68AF 3MV630HW68AF 4MV630HW68AF 3MV800HW68AF 4MV800HW68AF 3MV1000HW68AF 4MV1000HW68AF 3MV1250HW68AF 4MV1250HW68AF 3MV1600HW68AF 4MV1600H
2832328324283252832628327283282832928330283312833228333283342833528336
W68AD 3MV200HW68AD 4MV200HW68AD 3MV400HW68AD 4MV400HW68AD 3MV630HW68AD 4MV630HW68AD 3MV800HW68AD 4MV800HW68AD 3MV1000HW68AD 4MV1000HW68AD 3MV1250HW68AD 4MV1250HW68AD 3MV1600HW68AD 4MV1600H
2836528366283672836828369283702837128372283732837428375283762837728378
200 3P4P
400 3P4P
630 3P4P
800 3P4P
1000 3P4P
1250 3P4P
1600 3P4P
H type controllerHorizontal terminal connectionN type
65kA W68AF 3HH200NW68AF 4HH200NW68AF 3HH400NW68AF 4HH400NW68AF 3HH630NW68AF 4HH630NW68AF 3HH800NW68AF 4HH800NW68AF 3HH1000NW68AF 4HH1000NW68AF 3HH1250NW68AF 4HH1250NW68AF 3HH1600NW68AF 4HH1600N
2839328394283952839628397283982839928400284012840228403284042840528406
W68AD 3HH200NW68AD 4HH200NW68AD 3HH400NW68AD 4HH400NW68AD 3HH630NW68AD 4HH630NW68AD 3HH800NW68AD 4HH800NW68AD 3HH1000NW68AD 4HH1000NW68AD 3HH1250NW68AD 4HH1250NW68AD 3HH1600NW68AD 4HH1600N
2843528436284372843828439284402844128442284432844428445284462844728448
Rated current Number ofpoles
Air Circuit BreakersSeries 3SW68
1-24 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Type code Order code Type code Order codeFixed type Drawer type
W68AF 3HV200NW68AF 4HV200NW68AF 3HV400NW68AF 4HV400NW68AF 3HV630NW68AF 4HV630NW68AF 3HV800NW68AF 4HV800NW68AF 3HV1000NW68AF 4HV1000NW68AF 3HV1250NW68AF 4HV1250NW68AF 3HV1600NW68AF 4HV1600N
2840728408284092841028411284122841328414284152841628417284182841928420
W68AD 3HV200NW68AD 4HV200NW68AD 3HV400NW68AD 4HV400NW68AD 3HV630NW68AD 4HV630NW68AD 3HV800NW68AD 4HV800NW68AD 3HV1000NW68AD 4HV1000NW68AD 3HV1250NW68AD 4HV1250NW68AD 3HV1600NW68AD 4HV1600N
2844928450284512845228453284542845528456284572845828459284602846128462
W68AF 3HH200HW68AF 4HH200HW68AF 3HH400HW68AF 4HH400HW68AF 3HH630HW68AF 4HH630HW68AF 3HH800HW68AF 4HH800HW68AF 3HH1000HW68AF 4HH1000HW68AF 3HH1250HW68AF 4HH1250HW68AF 3HH1600HW68AF 4HH1600H
2847728478284792848028481284822848328484284852848628487284882848928490
W68AD 3HH200HW68AD 4HH200HW68AD 3HH400HW68AD 4HH400HW68AD 3HH630HW68AD 4HH630HW68AD 3HH800HW68AD 4HH800HW68AD 3HH1000HW68AD 4HH1000HW68AD 3HH1250HW68AD 4HH1250HW68AD 3HH1600HW68AD 4HH1600H
2851928520285212852228523285242852528526285272852828529285302853128532
W68AF 3HV200HW68AF 4HV200HW68AF 3HV400HW68AF 4HV400HW68AF 3HV630HW68AF 4HV630HW68AF 3HV800HW68AF 4HV800HW68AF 3HV1000HW68AF 4HV1000HW68AF 3HV1250HW68AF 4HV1250HW68AF 3HV1600HW68AF 4HV1600H
2849128492284932849428495284962849728498284992850028501285022850328504
W68AD 3HV200HW68AD 4HV200HW68AD 3HV400HW68AD 4HV400HW68AD 3HV630HW68AD 4HV630HW68AD 3HV800HW68AD 4HV800HW68AD 3HV1000HW68AD 4HV1000HW68AD 3HV1250HW68AD 4HV1250HW68AD 3HV1600HW68AD 4HV1600H
2853328534285352853628537285382853928540285412854228543285442854528546
H type controllerFrame A3SW68-1600
200
400
630
800
1000
1250
1600
In(A)3P4P3P4P3P4P3P4P3P4P3P4P3P4P
Vertical terminal connection
200
400
630
800
1000
1250
1600
3P4P3P4P3P4P3P4P3P4P3P4P3P4P
Horizontal terminal connectionH type65kA
Vertical terminal connection200 3P
4P400 3P
4P630 3P
4P800 3P
4P1000 3P
4P1250 3P
4P1600 3P
4P
Rated current Number ofpoles
Air Circuit BreakersSeries 3SW68
1-25www.sassin.com
Power Distribution Electrics
L type controllerFrame B3SW68-2500
1250 3P4P
1600 3P4P
2000 3P4P
2500 3P4P
Type codeIn(A)
Horizontal terminal connection
Vertical terminal connection1250 3P
4P1600 3P
4P2000 3P
4P2500 3P
4P
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
Horizontal terminal connection
Vertical terminal connection1250 3P
4P1600 3P
4P2000 3P
4P2500 3P
4P
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
M type controllerHorizontal terminal connection
N type65kA
H type85kA
W68BF 3LH1250NW68BF 4LH1250NW68BF 3LH1600NW68BF 4LH1600NW68BF 3LH2000NW68BF 4LH2000NW68BF 3LH2500NW68BF 4LH2500N
W68BF 3LV1250NW68BF 4LV1250NW68BF 3LV1600NW68BF 4LV1600NW68BF 3LV2000NW68BF 4LV2000NW68BF 3LV2500NW68BF 4LV2500N
W68BF 3LH1250HW68BF 4LH1250HW68BF 3LH1600HW68BF 4LH1600HW68BF 3LH2000HW68BF 4LH2000HW68BF 3LH2500HW68BF 4LH2500H
W68BF 3LV1250HW68BF 4LV1250HW68BF 3LV1600HW68BF 4LV1600HW68BF 3LV2000HW68BF 4LV2000HW68BF 3LV2500HW68BF 4LV2500H
N type65kA W68BF 3MH1250N
W68BF 4MH1250NW68BF 3MH1600NW68BF 4MH1600NW68BF 3MH2000NW68BF 4MH2000NW68BF 3MH2500NW68BF 4MH2500N
Rated current Number ofpoles Order code Type code Order Code
Fixed type Drawer type
2856128562285632856428565285662856728568
W68BD 3LH1250NW68BD 4LH1250NW68BD 3LH1600NW68BD 4LH1600NW68BD 3LH2000NW68BD 4LH2000NW68BD 3LH2500NW68BD 4LH2500N
2857728578285792858028581285822858328584
2856928570285712857228573285742857528576
W68BD 3LV1250NW68BD 4LV1250NW68BD 3LV1600NW68BD 4LV1600NW68BD 3LV2000NW68BD 4LV2000NW68BD 3LV2500NW68BD 4LV2500N
2858528586285872858828589285902859128592
2859328594285952859628597285982859928600
W68BD 3LH1250HW68BD 4LH1250HW68BD 3LH1600HW68BD 4LH1600HW68BD 3LH2000HW68BD 4LH2000HW68BD 3LH2500HW68BD 4LH2500H
2860928610286112861228613286142861528616
2860128602286032860428605286062860728608
W68BD 3LV1250HW68BD 4LV1250HW68BD 3LV1600HW68BD 4LV1600HW68BD 3LV2000HW68BD 4LV2000HW68BD 3LV2500HW68BD 4LV2500H
1821418215182161821718218182191822018221
1822218223182241822518226182271822818229
W68BD 3MH1250NW68BD 4MH1250NW68BD 3MH1600NW68BD 4MH1600NW68BD 3MH2000NW68BD 4MH2000NW68BD 3MH2500NW68BD 4MH2500N
1823818239182401824118242182431824418245
Air Circuit BreakersSeries 3SW68
1-26 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
1250
1600
2000
2500
Type code Order code Type Code Order CodeFixed type Drawer type
In(A)3P4P3P4P3P4P3P4P
Frame B3SW68-2500
Mtype controllerVertical terminal connection
W68BF 3MV1250NW68BF 4MV1250NW68BF 3MV1600NW68BF 4MV1600NW68BF 3MV2000NW68BF 4MV2000NW68BF 3MV2500NW68BF 4MV2500N
1823018231182321823318234182351823618237
W68BD 3MV1250NW68BD 4MV1250NW68BD 3MV1600NW68BD 4MV1600NW68BD 3MV2000NW68BD 4MV2000NW68BD 3MV2500NW68BD 4MV2500N
1824618247182481824918250182511825218253
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
H type85kA W68BF 3MH1250H
W68BF 4MH1250HW68BF 3MH1600HW68BF 4MH1600HW68BF 3MH2000HW68BF 4MH2000HW68BF 3MH2500HW68BF 4MH2500H
1825418255182561825718258182591826018261
Horizontal terminal connectionW68BD 3MH1250HW68BD 4MH1250HW68BD 3MH1600HW68BD 4MH1600HW68BD 3MH2000HW68BD 4MH2000HW68BD 3MH2500HW68BD 4MH2500H
1827018271182721827318274182751827618277
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
Vertical terminal connectionW68BF 3MV1250HW68BF 4MV1250HW68BF 3MV1600HW68BF 4MV1600HW68BF 3MV2000HW68BF 4MV2000HW68BF 3MV2500HW68BF 4MV2500H
1826218263182641826518266182671826818269
W68BD 3MV1250HW68BD 4MV1250HW68BD 3MV1600HW68BD 4MV1600HW68BD 3MV2000HW68BD 4MV2000HW68BD 3MV2500HW68BD 4MV2500H
1827818279182801828118282182831828418285
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
H type controller
Vertical terminal connection1250
1600
2000
2500
3P4P3P4P3P4P3P4P
Horizontal terminal connectionN type65kA W68BF 3HH1250N
W68BF 4HH1250NW68BF 3HH1600NW68BF 4HH1600NW68BF 3HH2000NW68BF 4HH2000NW68BF 3HH2500NW68BF 4HH2500N
1828618287182881828918290182911829218293
W68BD 3HH1250NW68BD 4HH1250NW68BD 3HH1600NW68BD 4HH1600NW68BD 3HH2000NW68BD 4HH2000NW68BD 3HH2500NW68BD 4HH2500N
1830218303183041830518306183071830818309
W68BF 3HV1250NW68BF 4HV1250NW68BF 3HV1600NW68BF 4HV1600NW68BF 3HV2000NW68BF 4HV2000NW68BF 3HV2500NW68BF 4HV2500N
1829418295182961829718298182991830018301
W68BD 3HV1250NW68BD 4HV1250NW68BD 3HV1600NW68BD 4HV1600NW68BD 3HV2000NW68BD 4HV2000NW68BD 3HV2500NW68BD 4HV2500N
1831018311183121831318314183151831618317
N type65kA Rated current Number of
poles
Air Circuit BreakersSeries 3SW68
1-27www.sassin.com
Power Distribution Electrics
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
L type controllerHorizontal terminal connection
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
1250
1600
2000
2500
Type code Order code Type code Order codeFixed type Drawer type
In(A)3P4P3P4P3P4P3P4P
H type controller
1250
1600
2000
2500
3P4P3P4P3P4P3P4P
Horizontal terminal connectionH type85kA
W68BF 3HH1250HW68BF 4HH1250HW68BF 3HH1600HW68BF 4HH1600HW68BF 3HH2000HW68BF 4HH2000HW68BF 3HH2500HW68BF 4HH2500H
1831818319183201832118322183231832418325
W68BD 3HH1250HW68BD 4HH1250HW68BD 3HH1600HW68BD 4HH1600HW68BD 3HH2000HW68BD 4HH2000HW68BD 3HH2500HW68BD 4HH2500H
1833418335183361833718338183391834018341
W68BF 3HV1250HW68BF 4HV1250HW68BF 3HV1600HW68BF 4HV1600HW68BF 3HV2000HW68BF 4HV2000HW68BF 3HV2500HW68BF 4HV2500H
1832618327183281832918330183311833218333
W68BD 3HV1250HW68BD 4HV1250HW68BD 3HV1600HW68BD 4HV1600HW68BD 3HV2000HW68BD 4HV2000HW68BD 3HV2500HW68BD 4HV2500H
1834218343183441834518346183471834818349
Frame B3SW68-2500
N type85kA 18350
18351183521835318354183551835618357
W68CD 3LH2000NW68CD 4LH2000NW68CD 3LH2500NW68CD 4LH2500NW68CD 3LH3200NW68CD 4LH3200NW68CD 3LH4000NW68CD 4LH4000N
1836618367183681836918370183711837218373
1835818359183601836118362183631836418365
W68CD 3LV2000NW68CD 4LV2000NW68CD 3LV2500NW68CD 4LV2500NW68CD 3LV3200NW68CD 4LV3200NW68CD 3LV4000NW68CD 4LV4000N
1837418375183761837718378183791838018381
2000 3P4P
2500 3P4P
3200 3P4P
4000 3P4P
Horizontal terminal connectionH type100kA 18382
18383183841838518386183871838818389
W68CD 3LH2000HW68CD 4LH2000HW68CD 3LH2500HW68CD 4LH2500HW68CD 3LH3200HW68CD 4LH3200HW68CD 3LH4000HW68CD 4LH4000H
1839818399184001840118402184031840418405
W68CF 3LH2000NW68CF 4LH2000NW68CF 3LH2500NW68CF 4LH2500NW68CF 3LH3200NW68CF 4LH3200NW68CF 3LH4000NW68CF 4LH4000N
W68CF 3LV2000NW68CF 4LV2000NW68CF 3LV2500NW68CF 4LV2500NW68CF 3LV3200NW68CF 4LV3200NW68CF 3LV4000NW68CF 4LV4000N
W68CF 3LH2000HW68CF 4LH2000HW68CF 3LH2500HW68CF 4LH2500HW68CF 3LH3200HW68CF 4LH3200HW68CF 3LH4000HW68CF 4LH4000H
Rated current
Vertical terminal connection
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
Vertical terminal connection1839018391183921839318394183951839618397
W68CD 3LV2000HW68CD 4LV2000HW68CD 3LV2500HW68CD 4LV2500HW68CD 3LV3200HW68CD 4LV3200HW68CD 3LV4000HW68CD 4LV4000H
1840618407184081840918410184111841218413
W68CF 3LV2000HW68CF 4LV2000HW68CF 3LV2500HW68CF 4LV2500HW68CF 3LV3200HW68CF 4LV3200HW68CF 3LV4000HW68CF 4LV4000H
Frame C3SW68-4000
Number ofpoles
Air Circuit BreakersSeries 3SW68
1-28 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
L type controllerFrame C3SW68-4000
1842218423184241842518426184271842818429
W68CD 3LV2000SW68CD 4LV2000SW68CD 3LV2500SW68CD 4LV2500SW68CD 3LV3200SW68CD 4LV3200SW68CD 3LV4000SW68CD 4LV4000S
2000 3P4P
2500 3P4P
3200 3P4P
4000 3P4P
W68CF 3LH2000SW68CF 4LH2000SW68CF 3LH2500SW68CF 4LH2500SW68CF 3LH3200SW68CF 4LH3200SW68CF 3LH4000SW68CF 4LH4000S
1841418415184161841718418184191842018421
1843018431184321843318434184351843618437
W68CD 3LH2000SW68CD 4LH2000SW68CD 3LH2500SW68CD 4LH2500SW68CD 3LH3200SW68CD 4LH3200SW68CD 3LH4000SW68CD 4LH4000S
2000 3P4P
2500 3P4P
3200 3P4P
4000 3P4P
W68CF 3LV2000SW68CF 4LV2000SW68CF 3LV2500SW68CF 4LV2500SW68CF 3LV3200SW68CF 4LV3200SW68CF 3LV4000SW68CF 4LV4000S
1843818439184401844118442184431844418445
S type120kA
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
M type controllerHorizontal terminal connection
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
N type85kA W68CF 3MH2000N
W68CF 4MH2000NW68CF 3MH2500NW68CF 4MH2500NW68CF 3MH3200NW68CF 4MH3200NW68CF 3MH4000NW68CF 4MH4000N
1844618447184481844918450184511845218453
W68CD 3MH2000NW68CD 4MH2000NW68CD 3MH2500NW68CD 4MH2500NW68CD 3MH3200NW68CD 4MH3200NW68CD 3MH4000NW68CD 4MH4000N
1846218463184641846518466184671846818469
W68CF 3MV2000NW68CF 4MV2000NW68CF 3MV2500NW68CF 4MV2500NW68CF 3MV3200NW68CF 4MV3200NW68CF 3MV4000NW68CF 4MV4000N
1845418455184561845718458184591846018461
W68CD 3MV2000NW68CD 4MV2000NW68CD 3MV2500NW68CD 4MV2500NW68CD 3MV3200NW68CD 4MV3200NW68CD 3MV4000NW68CD 4MV4000N
1847018471184721847318474184751847618477
Vertical terminal connection
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
Horizontal terminal connection
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
H type100kA W68CF 3MH2000H
W68CF 4MH2000HW68CF 3MH2500HW68CF 4MH2500HW68CF 3MH3200HW68CF 4MH3200HW68CF 3MH4000HW68CF 4MH4000H
1847818479184801848118482184831848418485
W68CD 3MH2000HW68CD 4MH2000HW68CD 3MH2500HW68CD 4MH2500HW68CD 3MH3200HW68CD 4MH3200HW68CD 3MH4000HW68CD 4MH4000H
1849418495184961849718498184991850018501
W68CF 3MV2000HW68CF 4MV2000HW68CF 3MV2500HW68CF 4MV2500HW68CF 3MV3200HW68CF 4MV3200HW68CF 3MV4000HW68CF 4MV4000H
W68CD 3MV2000HW68CD 4MV2000HW68CD 3MV2500HW68CD 4MV2500HW68CD 3MV3200HW68CD 4MV3200HW68CD 3MV4000HW68CD 4MV4000H
1848618487184881848918490184911849218493
3206932070320713207232073320743207532076
Type code Order code Type code Order codeFixed type Drawer type
In(A)Rated current Number of
poles
Horizontal terminal connection
Air Circuit BreakersSeries 3SW68
1-29www.sassin.com
Power Distribution Electrics
Frame C3SW68-4000
M type controller
2000 3P4P
2500 3P4P
3200 3P4P
4000 3P4P
Type code Order code Type code Order codeFixed type Drawer type
In(A)
Horizontal terminal connectionS type120kA
W68CF 3MH2000SW68CF 4MH2000SW68CF 3MH2500SW68CF 4MH2500SW68CF 3MH3200SW68CF 4MH3200SW68CF 3MH4000SW68CF 4MH4000S
W68CD 3MH2000SW68CD 4MH2000SW68CD 3MH2500SW68CD 4MH2500SW68CD 3MH3200SW68CD 4MH3200SW68CD 3MH4000SW68CD 4MH4000S
3207732078320793208032081320823208332084
3209332094320953209632097320983209932100
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
W68CF 3MV2000SW68CF 4MV2000SW68CF 3MV2500SW68CF 4MV2500SW68CF 3MV3200SW68CF 4MV3200SW68CF 3MV4000SW68CF 4MV4000S
W68CD 3MV2000SW68CD 4MV2000SW68CD 3MV2500SW68CD 4MV2500SW68CD 3MV3200SW68CD 4MV3200SW68CD 3MV4000SW68CD 4MV4000S
3208532086320873208832089320903209132092
3210132102321033210432105321063210732108
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
H type controllerHorizontal terminal connectionN type
85kA W68CF 3HH2000NW68CF 4HH2000NW68CF 3HH2500NW68CF 4HH2500NW68CF 3HH3200NW68CF 4HH3200NW68CF 3HH4000NW68CF 4HH4000N
W68CD 3HH2000NW68CD 4HH2000NW68CD 3HH2500NW68CD 4HH2500NW68CD 3HH3200NW68CD 4HH3200NW68CD 3HH4000NW68CD 4HH4000N
3210932110321113211232113321143211532116
3212532126321273212832129321303213132132
Rated current
2000
2500
3200
4000
3P4P3P4P3P4P3P4P
Horizontal terminal connection
Vertical terminal connection
2000 3P4P
2500 3P4P
3200 3P4P
4000 3P4P
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
H type100kA
W68CF 3HV2000NW68CF 4HV2000NW68CF 3HV2500NW68CF 4HV2500NW68CF 3HV3200NW68CF 4HV3200NW68CF 3HV4000NW68CF 4HV4000N
W68CD 3HV2000NW68CD 4HV2000NW68CD 3HV2500NW68CD 4HV2500NW68CD 3HV3200NW68CD 4HV3200NW68CD 3HV4000NW68CD 4HV4000N
3211732118321193212032121321223212332124
3213332134321353213632137321383213932140
W68CF 3HH2000HW68CF 4HH2000HW68CF 3HH2500HW68CF 4HH2500HW68CF 3HH3200HW68CF 4HH3200HW68CF 3HH4000HW68CF 4HH4000H
W68CD 3HH2000HW68CD 4HH2000HW68CD 3HH2500HW68CD 4HH2500HW68CD 3HH3200HW68CD 4HH3200HW68CD 3HH4000HW68CD 4HH4000H
3214132142321433214432145321463214732148
3215732158321593216032161321623216332164
W68CF 3HV2000HW68CF 4HV2000HW68CF 3HV2500HW68CF 4HV2500HW68CF 3HV3200HW68CF 4HV3200HW68CF 3HV4000HW68CF 4HV4000H
W68CD 3HV2000HW68CD 4HV2000HW68CD 3HV2500HW68CD 4HV2500HW68CD 3HV3200HW68CD 4HV3200HW68CD 3HV4000HW68CD 4HV4000H
3214932150321513215232153321543215532156
3216532166321673216832169321703217132172
Number ofpoles
Air Circuit BreakersSeries 3SW68
1-30 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Frame C3SW68-4000
H type controllerHorizontal terminal connection
2000
2500
3200
4000
Type code Order code Type code Order codeFixed type Drawer type
In(A)3P4P3P4P3P4P3P4P
Vertical terminal connection2000 3P
4P2500 3P
4P3200 3P
4P4000 3P
4P
S type120kA
W68CF 3HH2000SW68CF 4HH2000SW68CF 3HH2500SW68CF 4HH2500SW68CF 3HH3200SW68CF 4HH3200SW68CF 3HH4000SW68CF 4HH4000S
W68CD 3HH2000SW68CD 4HH2000SW68CD 3HH2500SW68CD 4HH2500SW68CD 3HH3200SW68CD 4HH3200SW68CD 3HH4000SW68CD 4HH4000S
3217332174321753217632177321783217932180
3218932190321913219232193321943219532196
W68CF 3HV2000SW68CF 4HV2000SW68CF 3HV2500SW68CF 4HV2500SW68CF 3HV3200SW68CF 4HV3200SW68CF 3HV4000SW68CF 4HV4000S
W68CD 3HV2000SW68CD 4HV2000SW68CD 3HV2500SW68CD 4HV2500SW68CD 3HV3200SW68CD 4HV3200SW68CD 3HV4000SW68CD 4HV4000S
3218132182321833218432185321863218732188
3219732198321993220032201322023220332204
Rated current
4000
5000
6300
3P4P3P4P3P4P
Frame D3SW68-6300
L type ControllerHorizontal terminal connection
Vertical terminal connection4000 3P
4P5000 3P
4P6300 3P
4P
N type100kA W68DF 3LH4000N
W68DF 4LH4000NW68DF 3LH5000NW68DF 4LH5000NW68DF 3LH6300NW68DF 4LH6300N
W68DD 3LH4000NW68DD 4LH4000NW68DD 3LH5000NW68DD 4LH5000NW68DD 3LH6300NW68DD 4LH6300N
322053220632207322083220932210
322173221832219322203222132222
W68DF 3LV4000NW68DF 4LV4000NW68DF 3LV5000NW68DF 4LV5000NW68DF 3LV6300NW68DF 4LV6300N
W68DD 3LV4000NW68DD 4LV4000NW68DD 3LV5000NW68DD 4LV5000NW68DD 3LV6300NW68DD 4LV6300N
322113221232213322143221532216
322233222432225322263222732228
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
H type120kA W68DF 3LH4000H
W68DF 4LH4000HW68DF 3LH5000HW68DF 4LH5000HW68DF 3LH6300HW68DF 4LH6300H
W68DD 3LH4000HW68DD 4LH4000HW68DD 3LH5000HW68DD 4LH5000HW68DD 3LH6300HW68DD 4LH6300H
322293223032231322323223332234
322413224232243322443224532246
W68DF 3LV4000HW68DF 4LV4000HW68DF 3LV5000HW68DF 4LV5000HW68DF 3LV6300HW68DF 4LV6300H
W68DD 3LV4000HW68DD 4LV4000HW68DD 3LV5000HW68DD 4LV5000HW68DD 3LV6300HW68DD 4LV6300H
322353223632237322383223932240
322473224832249322503225132252
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connectionS type150kA W68DF 3LH4000S
W68DF 4LH4000SW68DF 3LH5000SW68DF 4LH5000SW68DF 3LH6300SW68DF 4LH6300S
W68DD 3LH4000SW68DD 4LH4000SW68DD 3LH5000SW68DD 4LH5000SW68DD 3LH6300SW68DD 4LH6300S
322533225432255322563225732258
322653226632267322683226932270
Vertical terminal connection
Number ofpoles
Air Circuit BreakersSeries 3SW68
1-31www.sassin.com
Power Distribution Electrics
Frame D3SW68-6300
L type ControllerS type150kA
4000 3P4P
5000 3P4P
6300 3P4P
Type code Order code Type code Order codeFixed type Drawer type
In(A)W68DF 3LV4000SW68DF 4LV4000SW68DF 3LV5000SW68DF 4LV5000SW68DF 3LV6300SW68DF 4LV6300S
W68DD 3LV4000SW68DD 4LV4000SW68DD 3LV5000SW68DD 4LV5000SW68DD 3LV6300SW68DD 4LV6300S
322593226032261322623226332264
322713227232273322743227532276
Rated current Vertical terminal connection
4000
5000
6300
3P4P3P4P3P4P
M type ControllerHorizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
N type100kA
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
H type120kA
W68DF 3LV4000HW68DF 4LV4000HW68DF 3LV5000HW68DF 4LV5000HW68DF 3LV6300HW68DF 4LV6300H
W68DD 3LV4000HW68DD 4LV4000HW68DD 3LV5000HW68DD 4LV5000HW68DD 3LV6300HW68DD 4LV6300H
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
S type150kA
W68DF 3MH4000NW68DF 4MH4000NW68DF 3MH5000NW68DF 4MH5000NW68DF 3MH6300NW68DF 4MH6300N
W68DD 3MH4000NW68DD 4MH4000NW68DD 3MH5000NW68DD 4MH5000NW68DD 3MH6300NW68DD 4MH6300N
322773227832279322803228132282
322893229032291322923229332294
W68DF 3MV4000NW68DF 4MV4000NW68DF 3MV5000NW68DF 4MV5000NW68DF 3MV6300NW68DF 4MV6300N
W68DD 3MV4000NW68DD 4MV4000NW68DD 3MV5000NW68DD 4MV5000NW68DD 3MV6300NW68DD 4MV6300N
322833228432285322863228732288
322953229632297322983229932300
W68DF 3MH4000HW68DF 4MH4000HW68DF 3MH5000HW68DF 4MH5000HW68DF 3MH6300HW68DF 4MH6300H
W68DD 3MH4000HW68DD 4MH4000HW68DD 3MH5000HW68DD 4MH5000HW68DD 3MH6300HW68DD 4MH6300H
323013230232303323043230532306
323133231432315323163231732318
323073230832309323103231132312
323193232032321323223232332324
W68DF 3MH4000SW68DF 4MH4000SW68DF 3MH5000SW68DF 4MH5000SW68DF 3MH6300SW68DF 4MH6300S
W68DD 3MH4000SW68DD 4MH4000SW68DD 3MH5000SW68DD 4MH5000SW68DD 3MH6300SW68DD 4MH6300S
323253232632327323283232932330
323373233832339323403234132342
W68DF 3MV4000SW68DF 4MV4000SW68DF 3MV5000SW68DF 4MV5000SW68DF 3MV6300SW68DF 4MV6300S
W68DD 3MV4000SW68DD 4MV4000SW68DD 3MV5000SW68DD 4MV5000SW68DD 3MV6300SW68DD 4MV6300S
323313233232333323343233532336
323433234432345323463234732348
Vertical terminal connection
Vertical terminal connection
Vertical terminal connection
Number ofpoles
Air Circuit BreakersSeries 3SW68
1-32 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
4000
5000
6300
Type code Order code Type code Order codeFixed type Drawer type
In(A)3P4P3P4P3P4P
Frame D3SW68-6300
H type controllerHorizontal terminal connection
Vertical terminal connection4000 3P
4P5000 3P
4P6300 3P
4P
N type100kA
W68DF 3HV4000NW68DF 4HV4000NW68DF 3HV5000NW68DF 4HV5000NW68DF 3HV6300NW68DF 4HV6300N
W68DD 3HV4000NW68DD 4HV4000NW68DD 3HV5000NW68DD 4HV5000NW68DD 3HV6300NW68DD 4HV6300N
323553235632357323583235932360
323673236832369323703237132372
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
H type120kA
4000
5000
6300
3P4P3P4P3P4P
Horizontal terminal connection
4000 3P4P
5000 3P4P
6300 3P4P
S type150kA W68DF 3HH4000S
W68DF 4HH4000SW68DF 3HH5000SW68DF 4HH5000SW68DF 3HH6300SW68DF 4HH6300S
W68DD 3HH4000SW68DD 4HH4000SW68DD 3HH5000SW68DD 4HH5000SW68DD 3HH6300SW68DD 4HH6300S
324093241032411324123241332414
W68DF 3HH4000NW68DF 4HH4000NW68DF 3HH5000NW68DF 4HH5000NW68DF 3HH6300NW68DF 4HH6300N
W68DD 3HH4000NW68DD 4HH4000NW68DD 3HH5000NW68DD 4HH5000NW68DD 3HH6300NW68DD 4HH6300N
323493235032351323523235332354
323613236232363323643236532366
W68DF 3HH4000HW68DF 4HH4000HW68DF 3HH5000HW68DF 4HH5000HW68DF 3HH6300HW68DF 4HH6300H
W68DD 3HH4000HW68DD 4HH4000HW68DD 3HH5000HW68DD 4HH5000HW68DD 3HH6300HW68DD 4HH6300H
323733237432375323763237732378
323853238632387323883238932390
W68DF 3HV4000HW68DF 4HV4000HW68DF 3HV5000HW68DF 4HV5000HW68DF 3HV6300HW68DF 4HV6300H
W68DD 3HV4000HW68DD 4HV4000HW68DD 3HV5000HW68DD 4HV5000HW68DD 3HV6300HW68DD 4HV6300H
323793238032381323823238332384
323913239232393323943239532396
W68DF 3HV4000SW68DF 4HV4000SW68DF 3HV5000SW68DF 4HV5000SW68DF 3HV6300SW68DF 4HV6300S
W68DD 3HV4000SW68DD 4HV4000SW68DD 3HV5000SW68DD 4HV5000SW68DD 3HV6300SW68DD 4HV6300S
324033240432405324063240732408
324153241632417324183241932420
323973239832399324003240132402
Rated current
Vertical terminal connection
Vertical terminal connection
Number ofpoles
Air Circuit BreakersSeries 3SW68
1-33www.sassin.com
Power Distribution Electrics
Air Circuit BreakersSeries 3SW68
1-34 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Electric operation mechanismIt is used for breaker motor for energy storage and automatic energy-restoringNormal standard configuring accessories are as below
Accessories
Rated voltage (V) Conventional thermal current Ith(A)
Rated control capacity
AC230415250
10830VA
DC 75W
Rated control power voltage Ue(v)Tripping voltage (V)Reliable switch-on voltage(V)Reliable switch-off voltage(V)Power consumptionDelay time of under-voltage delayed release (s)
AC400, AC230(0.35~0.7)Ue(0.85~1.1)Ue≤0.35Ue12VA0.5, 1, 2, 3
Rated control power voltage Us(v)Tripping voltage(V)Power consumptionStorage time (s)
AC400, AC230, DC220, DC110(0.85~1.1)Us80VA, 80W<5
Closing electromagnet After charging is finished, the closing electromagnet can break the circuit breaker by remote controlNormal configuring accessories
Rated control power source voltage Us(v)Tripping voltage(V)Closing time (ms)
AC400, AC230, DC220, DC110(0.85~1.1)Us<70
Rated control power source voltage Us(v)Tripping voltage (V)Break time (ms)
AC400, AC230, DC220, DC110(0.7~1.1)Us<30
Shunt releaseTo break the circuit breaker by remote controlNormally deployed accessories
Under-voltage releaseThe under-voltage release consists of release coil and control units.The under-voltage release works in two ways: instantaneous operation and delayed operation.Operational accessory
Note: If the delay time of under-voltage delayed release is above 3 second, it is the special specification
Auxiliary contactStandard configuration we provided to client is four convertible contacts. The six convertible contacts, four normally open, four normally closed contacts or six normally open, normally closed contacts are also available for special applications
Air Circuit BreakersSeries 3SW68
1-35www.sassin.com
Power Distribution Electrics
Outline and installation dimensions
74
Ø11 15
51
50 25
150
51
72
4xØ6.5
29795
297
276265230
35
364
353
8xØ3.5
317
352
70 70
a
4470 70
25Ø11
Installation dimensions of door Vertical terminal Horizontal terminal
Button of breaker
Centerof breaker
Centerof door
Vertical terminal Horizontal terminal248
351
145
282
74
Rated current a(mm)200-630A800-1000A1250-1600A
51015
3SW68-1600/3P Drawer type
Air Circuit BreakersSeries 3SW68
1-36 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
(3SW68-1600)4P Drawer type
70 70 70
a
70 70 7050
25
Ø11 15
35
276265230
35
317
352
7
364
353
8xØ3.5
Button of breaker
Centerof breaker
Centerof door
Installation dimensions of door Vertical terminal Horizontal terminal
Ø11 15
297
4xØ6.5
297
95 74
51
150
7251
50 25
150
318
351
74 215
352
Vertical terminal Horizontal terminal
Rated current a(mm)200-630A800-1000A1250-1600A
51015
Air Circuit BreakersSeries 3SW68
1-37www.sassin.com
Power Distribution Electrics
Rated current a(mm)200-630A800-1000A1250-1600A
51015
Installation dimensions of door Vertical terminal Horizontal terminal
Vertical terminal Horizontal terminal
70 70
50
25
Ø1115
70 70
a
276265230
8xØ3.5
Button of breaker
Centerof doorCenter
of breaker
330
319
283
320
237
254
Ø11 15
15
150
52
50100 90
194
194
16
R
52
60 52
150
4xØ7
(3SW68-1600)3P Fixed type
Air Circuit BreakersSeries 3SW68
1-38 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
Rated current a(mm)200-630A800-1000A1250-1600A
51015
Ø11 15
1515
050
5260 52
150
4xØ7100 90
194
194
52
320
324
Installation dimensions of door Vertical terminal Horizontal terminal
Vertical terminal Horizontal terminal
276265230
8xØ3.5
330
319
283
Centerof door
Centerof breaker
Button of breaker
35
70
a
70 70 70 70 7050
25
Ø11
15
(3SW68-1600)4P Fixed type
Air Circuit BreakersSeries 3SW68
1-39www.sassin.com
Power Distribution Electrics
3P N
3P N
304.
579
3P NOn the board before the next level of inlet and outletLevel on the outlet plate forward
On the board before the next vertical inlet and outlet
77 77
5-Φ11 5-Φ1138.5 38.5
25 25 25 25
30
25 13.552
90.5
1552 82
1552 82
25 13.552
102
Used as the center extended busbar of the horizontal, front board inlet and outlet wire combination of a 3-pole circuit breaker
Used as the extended busbar in the left or right of the horizontal, front board inlet and outlet wire combination of a 3-pole circuit breaker
Used as the extended busbar in the left or right of the horizontal, front board inlet and outlet wire combination of a 4-pole circuit breaker
Note: Use the busbar to connect the screws; Class M10 is of 8.8 torque: and 50 Nm should be used with the contact washer.
244.
5
3P N
3P N
5025 Φ11
1542
015
15.5
130
130
244.
5
Special wiring 3SW68-1600 (Darwer type)
Forward outlet plate
Forward under the outlet plate on the vertical
7738.5
25 25
30
8252
30
25 25
77
2552
13.5
38.55-Φ11
1552 82
25 13.552
15
5-Φ11
Used as the extended busbar center-left or right of the horizontal,front board inlet and outlet wire combination of a 4-pole circuit breaker, and also available as that of the vertical inlet and outlet wire combination of 3 or 4-pole circuit breaker
Extended busbar size of the breaker
Air Circuit BreakersSeries 3SW68
1-40 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
(3SW68-2500) Fixed type
Rated Current (In)
Mounting hole
4P 3P
420(P)325(P)
347(3P)367(3P)422(4P)462(4P)
403
4-Ø8
Mounting hole center
Vertical wiring
Horizontal wiring
A
N 3P
95 78.595 95
95 95 95 78.5
7030
1530
Φ10
1530
H
135
56.5
1250A 1600A 2000A 2500A 15mm 15mm 20mm 20mmFemale cable(H)
Vertical wiring
Mounting hole center
Chamber door
70 30
Φ10
30.5 170 98308.5
366
248
A
Horizontal wiring
Chamber door248
H
135
56.5
30.5 170308.5
98
366
A
Mounting hole center
Air Circuit BreakersSeries 3SW68
1-41www.sassin.com
Power Distribution Electrics
(3SW68-2500) Fixed type
4P 3P
70
Φ10
A
30
126
135
107.5 175 100380
455
Chamber door
135
56.5
H
A
107.5 175 100
390455
Mounting hole center
47 position
Chamber door
247(3P)347(3P)369(4P)442(4P)
4-Ø8
450
Mounting hole
3P
95
95
7030
1530
Φ10
A
N
95 95
95 95
1530
H42
Horizontal wiring
Mounting hole center
Vertical wiring
Horizontal wiring
Vertical wiring
Rated Current (In) Female cable(H)1250A 1600A 2000A 2500A 15mm 15mm 20mm 20mm
47 position
Air Circuit BreakersSeries 3SW68
1-42 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
3P
7030
1530
A
N
2000~2500A
3200~4000A
Ø13
126 126 126 94
136 141(3P)136(4P)
141(3P)136(4P)
79
10050Ø13
5025
2000~2500A
3200~4000A
126 126 126
126 126 126
94
94
3015
3010
5025
403
4P 3P544(4P)418(3P)
440(3P)460(3P)566(4P)586(4P)
248AA
3200~4000A 2000~2500A
30.5 170 98308.5366
40356
.513
530
1010 20
135
56.5
248AA3200~4000A 2000~2500A
30.5 170 98308.5366
56.5
135
Ø13
70 30
403
71.5
135
100
50
Ø13
(3SW68-4000) Fixed type
Horizontal wiring
Vertical wiring
Mounting hole center
Chamber door
Chamber door
Mounting hole center
Vertical wiring
Horizontal wiring Mounting hole center
4-Ø8Mounting hole
Air Circuit BreakersSeries 3SW68
1-43www.sassin.com
Power Distribution Electrics
(3SW68-4000) Darwer type
450
4P 3P
325(3P)440(3P)540(4P)566(4P)
57.5
63
2000~2500A 126 126 126 36.5(P)31(4P)
3015
126 126 126 36.5(P)31(4P)
5025
3200~4000A
3200~4000A
2000~2500A
136 141(3P)136(4P)
141(3P)136(4P)
21.5(3P)16(4P)100
50
5025
Ø13
Ø13
126 126 12636.5(P)31(4P)
3P
A
N
3015
Horizontal wiring
Horizontal wiring
Vertical wiring
107.5 175 100390455
126
135
70 30
Ø13
2000~2500AA
Vertical wiring Chamber door
Mounting hole center
47 position
2000~2500A
126
135
107.5 175 100390455
A
Chamber door
Mounting hole center
47 position
Mounting hole center 3200~4000A
126
135
10
30
492
10
141
135
100
50Ø13
492
A A3200~4000A
Horizontal wiring Vertical wiring
Air Circuit BreakersSeries 3SW68
1-44 www.sassin.com
Pow
er D
istr
ibut
ion
Elec
tric
s
4P 3P
4P 3P
225115
(2.5)
255
307.
5
Installation base of circuit breaker
Mounting hole centerline The center line of door openings
8-Ø5
260
100
286
Mounting hole centerline
Mounting hole centerline The center line of door openings
290
351
115240
(2.5)
8-Ø5
Mounting hole centerline
270
110
322
Door openings
Door openings
(3SW68-1600) Fixed type
(3SW68-1600) Darwer type
Installation base of circuit breaker
Air Circuit BreakersSeries 3SW68
1-45www.sassin.com
Power Distribution Electrics
(3SW68-4000)Fixed type
4P 3P
355 (42.5)220
13.5
285
8-Ø4
393
317
4P 3P
355 (42.5)162.5(3P)157(4P)
4518
281
393
19 7315
315
3
11-Ø4
44.5
(3SW68-4000)Darwere type
Mounting hole centerline The center line of door openings
Installation base of circuit breaker
Mounting hole centerline
Door openings
Door openings
Mounting hole centerline
Mounting hole centerline The center line of door openings
Installation base of circuit breaker