CONTENTS

1. POWER CABLES WITH THERMOPLASTIC INSULATION

2. CROSS-LINKED POLYETHYLENE (XLPE) INSULATED POWER CABLES

3. RUBBER INSULATED POWER CABLES

4. INSULATED ELECTRIC POWER CABLES AND FLEXIBLE CORDS

5. HALOGEN-FREE FLAME RETARDANT POWER CABLES AND CONDUCTORS

6. PAPER INSULATED METAL SHEATHED POWER CABLES

1. POWER CABLES WITH THERMOPLASTIC INSULATION

1.1. LOW VOLTAGE PVC INSULATED AND SHEATHED

POWER CABLES, 1 kV

1.2. LOW VOLTAGE AND MEDIUM VOLTAGE PVC INSULATED AND SHEATHED AND STEEL ARMOURED POWER CABLES, 1 AND 6 kV

1.3. MEDIUM VOLTAGE PVC INSULATED AND SHEATHED

POWER CABLES, 10 kV

1.4. CABLES FOR SPECIAL APPLICATION

1.1 LOW VOLTAGE PVC INSULATED AND SHEATHED POWER CABLES, 1 kV 1.1.1 PVC insulated and sheathed power cable, 1 kV

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up. Interstices filled with PVC threads and overlapped of PVC tapes. Filling of unvulcanized rubber for circular conductor cross-sections.

Sheath : Seamless tube of PVC compound in black colour.

Application : For power distribution in urban networks, industrial plants, thermo and hydropower stations.

Nominal voltage 1 kV

Number of cores Cross-section * Note **

- single-core 1,5 - 500 mm2 circular

- two-core 1,5 - 50 mm2 circular

- three-core 1,5 - 400 mm2 circular, sector

- 3 1/2 - core 25 - 400 mm2 circular, sector

- four-core 1,5 - 400 mm2 circular, sector

- 5-61 cores 1,5 and 2,5 mm2 circular

* 1,5 mm2 only for copper conductor. ** Sector shaped conductor for and over 35 mm2.

TYPE SPECIFICATION

PVC / PVC, AL / PVC / PVC

IEC 60502

PP00 , PP00-A JUS N.C5.220

PVC / PVC, AL / PVC / PVC

BS 6346

NYY , NAYY VDE 0276

VVG , AVVG , KVVG , AKVVG

GOST 16442 GOST 1508

1.1.2 PVC insulated and sheathed power cable with concentric conductor, 1 kV

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up. Interstices filled with PVC threads and overlapped of PVC tapes. Filling of unvulcanized rubber for circular conductor cross-sections.

Concentric conductor : Copper wire bandage with copper tape counter-spiral.

Sheath : Seamless tube of PVC compound in black colour.

Application : For low voltage power distribution in urban networks and places where electrical protection is required.

Nominal voltage 1 kV

Number of cores Cross-section Note

- single-core 1,5 - 300 mm2 circular

- two-core 1,5 - 50 mm2 circular

- three-core 1,5 - 300 mm2 circular, sector

- four-core 1,5 - 300 mm2 circular, sector

TYPE SPECIFICATION

PVC / PVC - S, AL / PVC / PVC - S

IEC 60502

PP40 , PP40-A JUS N.C5.220

PVC / PVC - S, AL / PVC / PVC - S

BS 6346

NYCY , NAYCY, NYCWY , NAYCWY

VDE 0276

KVVG∃ , AKVVG∃ GOST 1508

1.2 LOW VOLTAGE AND MEDIUM VOLTAGE PVC INSULATED AND SHEATHED

AND STEEL ARMOURED POWER CABLES, 1 AND 6 kV 1.2.1 PVC insulated and sheathed power cable armoured with steel tape 1 and 6 kV

TYPE SPECIFICATION

PVC / DTA / PVC , AL / PVC / DTA / PVC

IEC 60502

PP41 , PP41-A JUS N.C5.220

PVC / DTA / PVC , AL / PVC / DTA / PVC

BS 6346

NYBY , NAYBY, VDE 0271

VBbŠv , VVBG , AVBbŠv GOST 16442

KVBbŠv , AKVBbŠv GOST 1508

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up. Interstices filled with PVC threads and overlapped of PVC tapes. Filling of unvulcanized rubber for circular conductor cross-sections.

Mechanical protection : Armour of two steel tapes with two layers of impregnated paper beneath.

Sheath : Seamless tube of PVC compound in black colour.

Application : For power distribution in urban networks and industrial plants and places where mechanical damage may be expected.

Number of cores Cross-section Note

Nominal voltage 1 kV

- single-core 25 - 500 mm2 circular, DC voltage

- two-core 1,5 - 50 mm2 circular

- three-core 1,5 - 400 mm2 circular, sector

- 3 1/2 - core 25 - 400 mm2 circular, sector

- four-core 1,5 - 400 mm2 circular, sector

- 5 - 61 cores 1,5 ; 2,5 mm2 circular

Nominal voltage 6 kV

- three-core 16 - 300 mm2 circular

1.2.2 PVC insulated and sheathed power cable armoured with round steel wires, 1

and 6 kV

TYPE SPECIFICATION

PVC / SWA / PVC , AL / PVC / SWA / PVC

IEC 60502

PP44 , PP44-A JUS N.C5.220

PVC / SWA / PVC , AL / PVC / SWA / PVC

BS 6346

NYRGBY , NAYRGBY, VDE 0271

VPb[v , AVPb[v GOST 16442

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up. Interstices filled with PVC threads and overlapped of PVC tapes. Filling of unvulcanized rubber for circular conductor cross-sections.

Mechanical protection : Round steel galvanised wire armour.

Sheath : Seamless tube of PVC compound in black colour.

Application : For power distribution in urban networks and in places mechanical strains may be expected. Laying directly into ground, vertical mine shafts and hydro power plants.

Number of cores Cross-section Note

Nominal voltage 1 kV

- single-core 25 - 500 mm2 circular, DC voltage

- two-core 1,5 - 50 mm2 circular

- three-core 1,5 - 400 mm2 circular, sector

- 3 1/2 - core 25 - 400 mm2 circular, sector

- four-core 1,5 - 400 mm2 circular, sector

- 5 - 61cores 1,5 ; 2,5 mm2 circular

Nominal voltage 6 kV

- three-core 16 - 300 mm2 circular

1.2.3 PVC insulated and sheathed power cable armoured with flat steel wires, 1 and

6 kV

TYPE SPECIFICATION

PVC / SWA / PVC , AL / PVC / SWA / PVC

IEC 60502

PP45 , PP45-A JUS N.C5.220

PVC / SWA / PVC , AL / PVC / SWA / PVC

BS 6346

NYFGBY , NAYFGBY, VDE 0271

VPb[v , AVPb[v GOST 16442

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up. Interstices filled with PVC threads and overlapped of PVC tapes. Filling of unvulcanized rubber for circular conductor cross-sections.

Mechanical protection : Flat galvanised steel wire armour.

Sheath : Seamless tube of PVC compound in black colour.

Application : For power distribution in urban networks and mines where mechanical strains are expected. Laying directly into ground. Suitable for vertical laying.

Number of cores Cross-section Note

Nominal voltage 1 kV

- single-core 50 - 500 mm2 circular, DC voltage

- two-core 6 - 50 mm2 circular

- three-core 4 - 400 mm2 circular, sector

- 3 1/2 - core 25 - 400 mm2 circular, sector

- four-core 4 - 400 mm2 circular, sector

Nominal voltage 6 kV

- three-core 16 - 300 mm2 circular

1.3 MEDIUM VOLTAGE PVC INSULATED AND SHEATHED POWER CABLES, 10kV 1.3.1 PVC insulated and sheathed power cable with electrical protection over each

core, 10 kV

TYPE SPECIFICATION

PVC / PVC - S , AL / PVC / PVC - S

IEC 60502

PHP48 , PHP48-A JUS N.C5.220

NYSEY , NAYSEY, VDE 0271

Nominal voltage 10 kV

Number of cores Cross-section Note

- single-core 16 - 300 mm2 circular

- three-core 16 - 300 mm2 circular

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of high quality PVC compound with semiconductive layer under and over insulating.

Electrical protection : Copper tapes or wires wound hellically over insulation.

Cable core : Cores laid-up. Interstices filled suitable filling.

Sheath : Seamless tube of PVC compound in red colour.

Application : For connection of generators in power plants, for secondary circuits from transformers to distribution in steel

1.3.2 PVC insulated and sheathed power cable with electrical protection over each

core armoured with steel tape, 10 kV

TYPE SPECIFICATION

PVC / DTA / PVC - S , AL / PVC / DTA / PVC - S

IEC 60502

PHP81 , PHP81-A JUS N.C5.220

NYSEYBY , NAYSEYBY VDE 0271

Nominal voltage 10 kV

Number of cores Cross-section Note

- single-core 16 - 300 mm2 circular

- three-core 16 - 300 mm2 circular

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of high quality PVC compound with semiconductive layer under and over insulating.

Electrical protection : Copper tapes or wires wound hellically over insulation.

Cable core : Cores laid-up. Interstices filled suitable filling.

Mechanical protection : Armour of two steel tapes.

Sheath : Seamless tube of PVC compound in red colour.

Application : For high voltage distribution in urban networks, industrial plants where increased electrical and mechanical protection is required.

1.3.3 PVC insulated and sheathed power cable with electrical protection over each

core armoured with round steel wire, 10 kV

TYPE SPECIFICATION

PVC / SWA / PVC - S , AL / PVC / SWA / PVC - S

IEC 60502

PHP84 , PHP84-A JUS N.C5.220

NYSEYRGY , NAYSEYRGY VDE 0271

Nominal voltage 10 kV

Number of cores Cross-section Note

- single-core 16 - 300 mm2 circular

- three-core 16 - 300 mm2 circular

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of high quality PVC compound with semiconductive layer under and over insulating.

Electrical protection : Copper tapes or wires wound hellically over insulation.

Cable core : Cores laid-up. Interstices filled suitable filling.

Mechanical protection : Round galvanised steel wires armour.

Sheath : Seamless tube of PVC compound in red colour.

Application : For high voltage distribution in urban networks, industrial plants and mines. Laying directly into ground or ducts. Suitable for vertical installation.

1.3.4 PVC insulated and sheathed power cable with electrical protection over each

core armoured with flat steel wire, 10 kV

TYPE SPECIFICATION

PVC / SWA / PVC - S , AL / PVC / SWA / PVC - S

IEC 60502

PHP85 , PHP85-A JUS N.C5.220

NYSEYFGY , NAYSEYFGY VDE 0271

Nominal voltage 10 kV

Number of cores Cross-section Note

- single-core 16 - 300 mm2 circular

- three-core 16 - 300 mm2 circular

CONSTRUCTION :

Conductor : Wire or soft annealed stranded copper or aluminium.

Core : Conductor insulated with seamless layer of high quality PVC compound with semiconductive layer under and over insulating.

Electrical protection : Copper tapes or wires wound hellically over insulation.

Cable core : Cores laid-up. Interstices filled suitable filling.

Mechanical protection : Flat galvanised steel wires armour.

Sheath : Seamless tube of PVC compound in red colour.

Application : For high voltage distribution in urban networks, industrial plants where increased electrical and mechanical protection is required. Suitable for inclined and vertical installation.

1.4.1 PVC - insulated and PVC - sheathed flat cables for lifts and cranes

TYPE SPECIFICATION

DPP / U , DPP / U - Y JUS under consideration

HO7VVH6 - F VDE 0281 teil 404

Nominal voltage: 300 / 500 V for cross section 1 mm2

450 / 750 V for other cross sections

Number of cores Cross-section Note

- from 3 to 24 1; 1,5 ; 2,5 mm2 circular

- from 4 to 25 4 ; 5 mm2 circular

Number of cores 5 6 9 12 16 20 24

Arrangement of cores

2 + 3 2 x 3 3 x 3 3 x 4 4 x 4 5 x 4 6 x 4

CONSTRUCTION :

Conductor : Flexible stranded copper wire.

Core : Conductor insulated with seamless layer of PVC compound.

Cable core : Cores laid-up in parallel.

Sheath : PVC compound squirted over cores in grey colour.

Application : Cables applied to electric lifts and cranes are used for feeding of electric motors, as well as for control-signalling connections.

1.4.2 Oil-field cables

TYPE SPECIFICATION

KPBP, KPBK TU 16505.129-82

Nominal voltage 3,3 kV

Number of cores Cross-section Note

- three-core 6 - 50 mm2 circular

Cross-section

Thickness of insulation

Max.overall diameter

Mass Delivery lengths

Type of cable

(mm2) (mm) (mm) (kg/km) (m)

3 x10 3 29 898 1700

3 x 16 3 32 1125 1700

KPBK

3 x 25 3 35 1564 1700

3 x10 3 13.6 x 33.8 950 1700

3 x 16 3 15.0 x 37.4 1177 1700

KPBP

3 x 25 3 15.4 x 43.0 1615 1700

CONSTRUCTION :

Conductor : Wire soft annealed copper.

Core : Conductor insulated with seamless layer of PET high density.

Cable core :

KPBP :

- cores laid-up in parallel and wrapped suitable tape.

KPBK :

- cores laid-up and wrapped suitable tape.

Mechanical protection : Armour from shape galvanised steel tapes in form “Z” ( for KPBP ) and in form “S” (for KPBK).

Application: For feeding of electric energy motors in mine, for long and short run, trouble-free service as a power source for down hole oil well pumps.

2. CROSS-LINKED POLYETHYLENE (XLPE) INSULATED

POWER CABLES

2.1 LOW VOLTAGE XLPE INSULATED CABLES 1 kV

2.2 MEDIUM VOLTAGE XLPE INSULATED CABLES 6 - 35 kV 2.3 HIGH VOLTAGE XLPE INSULATED CABLES 60 - 150 kV

2.1 LOW VOLTAGE XLPE INSULATED CABLES 1 kV 2.1.1 XLPE insulated and PVC or PE oversheathed cables, 1 kV

CONSTRUCTION:

Conductor: circular, solid or stranded, soft annealed copper or aluminium, or stranded sector-shaped soft annealed copper or aluminium, or solid aluminium sector shaped Core: XLPE insulated conductor

Cable core: Laid-up cores. Interstices filled with suitable material. Thermoplastic tape wrapping or extruded layer of unvulcanized rubber compound

Oversheath: Black extruded PVC or PE compound

Application: For power distribution in city networks, industrial plants, steam and hydroelectric power stations

Nominal voltage 1 kV

Number of cores Conductor size* Note**

- single-core 1,5 - 500 mm2

- two-core 1,5 - 50 mm2

- three-core 1,5 - 400 mm2 round, sector

- four core with reduced neutral

25 - 400 mm2 round, sector

- four-core 1,5 - 400 mm2 round, sector

- five-core 1,5 - 35 mm2

- 7-61cores 1,5 and 2,5 mm2

* -Aluminium conductors for conductor size 25 mm² and greater -Aluminium conductors of sizes from 50 mm² up to 240 mm² may be solid, sector-shaped or circular ** Sector-shaped conductors for conductor size 35 mm² and greater

TYPE STANDARD

XP00 (-S), XE00 (-S) XP00-A (S, SJ), XE00-A (S, SJ)

JUS N.C5.230

XLPE/PVC (PE) Al-XLPE/PVC (PE)

IEC 60502-1

XLPE/PVC Al-XLPE/PVC

BS 5467

N2XY, N2X2Y NA2XY, NA2X2Y

VDE 0276-603

U1000 R2V U1000 AR2V

NFC 33-321

PvVG, APvVG GOST 16-442

2.1.2 Cables with XLPE insulation, double steel tape armour and PVC or PE

oversheath, 1 kV

CONSTRUCTION:

Conductor: Solid or stranded, soft annealed copper or aluminium

Core: XLPE insulated conductor

Cable core: Laid-up cores. Interstices filled with suitable material. Thermoplastic tape wrapping or extruded layer of unvulcanized rubber compound

Armour: The tape armour shall be applied helically in two layers

Oversheath: Black extruded PVC or PE.

Application: For power distribution in city networks and industrial plants, where greater mechanical stresses are expected.

Nominal voltage 1 kV

Number of cores Conductor size* Note**

- single-core 1,5 - 500 mm2 DC voltage

- two-core 1,5 - 50 mm2

- three-core 1,5 - 400 mm2 round, sector

- four core with reduced neutral

25 - 400 mm2 round, sector

- four-core 1,5 - 400 mm2 round, sector

- five-core 1,5 - 35 mm2

- 7-61cores 1,5 and 2,5 mm2

* Aluminium conductors for conductor size 25 mm² and greater ** Sector-shaped conductors for conductor size 35 mm² and greater

TYPE STANDARD

XP41 , XE41 XP41-A , XE41-A

JUS N.C5.230

XLPE/DTA/PVC

XLPE/DTA/PE

Al-XLPE/DTA/PVC

Al-XLPE/DTA/PE

IEC 60502-1

XLPE/DTA/PVC Al-XLPE/DTA/PVC

BS 5467

N2XBY, N2XB2Y NA2XBY, NA2XB2Y

VDE 0276-603 + IEC 60502

U1000 RVFV U1000 ARVFV

NFC 33-322

PvVBbG , APvVBbG GOST 16-442

2.1.3 Cables with XLPE insulation, round galvanized steel wire armour and PVC or

PE oversheath, 1 kV.

CONSTRUCTION:

Conductor: Solid or stranded, soft annealed copper or aluminium

Core: XLPE insulated conductor

Cable core: Laid-up cores. Interstices filled with suitable material. Thermoplastic tape wrapping or extruded layer of unvulcanized rubber compound.

Armour: Single layer of round galvanized steel wires, with or without steel counter-helix tape

Oversheath: Black extruded PVC or PE compound

Application: For power distribution in city networks, where great mechanical stresses are expected. Suitable for inclined routs or for vertical laying

Nominal voltage 1 kV

Number of cores Conductor size* Note **

- single-core 25 - 500 mm2 DC voltage

- two-core 1,5 - 50 mm2

- three-core 1,5 - 400 mm2 round, sector

- four core with reduced neutral

25 - 400 mm2 round, sector

- four-core 1,5 - 400 mm2 round, sector

* Aluminium conductors for conductor size 25 mm² and greater ** Sector-shaped conductors for conductor size 35 mm² and greater

TYPE STANDARD

XP44 , XP44-A

XE44 , XE44-A JUS N.C5.230

XLPE/SWA/PVC

XLPE/SWA/PE, Al-XLPE/SWA/PVC

Al-XLPE/SWA/PE

IEC 60502-1

XLPE/SWA/PVC, Al-XLPE/SWA/PVC

BS 5467

N2XRY , NA2XRY

N2XR2Y , NA2XR2Y VDE 0276-603

PvVKbG , APvVKbG GOST 16-442

2.1.4 Self-supporting aerial bundle of XLPE insulated conductors, 1 kV

TYPE STANDARD

X00-A

X00/0-A JUS N.C5.250

NFA2X VDE 0276-626

- NFC 33-209

Nominal voltage 1 kV

Number of cores Conductor size* Note

- two-core 16 and 25 mm2

- four-core 16 and 25 mm2 25 - 70 mm

2 *

-three-core, with neutral and street-lighting conductors

25 - 70 mm

2

25 - 150 mm2 **

* VDE ** NFC

CONSTRUCTION:

Phase-core: Black XLPE insulated aluminium stranded conductor

Neutral-core (messenger): Black XLPE insulated aluminium-steel or aluminium alloy stranded conductor

Lighting conductor: Black XLPE insulated aluminium stranded conductor

Bundle of insulated conductors: Laid-up cores, or cores laid-up around messenger

Application: In aerial low voltage distributive networks, for street-lighting, individual house connecting, illumination of sporting-places, public and other objects, as in industrial plants for supplying of low voltage consumers

2.2 MEDIUM VOLTAGE XLPE INSULATED CABLES 6 - 35 kV 2.2.1 Cables with XLPE insulation, screened and PVC or PE oversheathed, 6 - 35 kV

Number of cores Conductor size Note

Nominal voltage 6 and 10 kV

- single-core 16 - 500 mm2 6 and 10 kV

- three-core 16 - 300 mm2 6 and 10 kV

Nominal voltage 20 kV

- single-core 35 - 500 mm2

- three-core 35 - 300 mm2

Nominal voltage 35 kV

- single-core 50 - 500 mm2

- three-core 50 - 300 mm2

TYPE STANDARD

XHP 48 , XHE 48 XHP 48-A , XHE 48-A

JUS N.C5.230

XLPE/PVC , XLPE/PE

Al-XLPE/PVC, Al-XLPE/PE IEC 60502-2

XLPE/PVC

Al-XLPE/PVC BS 6622

N2XSY, N2XS2Y,

N2XSEY, N2XSE2Y

NA2XSY, NA2XS2Y

NA2XSEY, NA2XSE2Y

VDE 0276-620

CONSTRUCTION:

Conductor: stranded compacted, soft annealed copper or aluminium

Core: XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper wire screen, wires laid helically around the core, with copper counter-helix equalizing tape applied over

Cable core (for three-core cables): Screened cores laid-up. Interstices filled with suitable material. Thermoplastic tape wrapping.

Oversheath: Black extruded PVC or PE.

Application: For distributive and industrial power networks, medium voltage distributive plants, steam and hydroelectric power stations.

2.2.2 Cables with XLPE insulation, screened and PE oversheathed, including

barrier which prevents water penetration through metallic screen along the length of cable, 6 - 35 kV

TYPE STANDARD

XHE 49 XHE 49-A

JUS N.C5.230

XLPE/PE-wp

Al-XLPE/PE-wp IEC 60502-2

N2XS(F)2Y,

NA2XS(F)2Y VDE 0276-620

Number of cores Conductor size Note

Nominal voltage 6 and 10 kV

- single-core 16 - 500 mm2

Nominal voltage 20 kV

- single-core 35 - 500 mm2

Nominal voltage 35 kV

- single-core 50 - 500 mm2

CONSTRUCTION:

Conductor: stranded compacted, soft annealed copper or aluminium, water sealed (on request)

Core: XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper wire screen, wires laid helically around the core, with copper counter-helix equalizing tape applied over.

Protection against the water penetration: Longitudinal protection - swellable tapes applied under and over the metallic screen, with possibility of radial protection - aluminium-copolymer foil applied under the oversheath.

Oversheath: Black extruded PE compound

Application: In power distributive and industrial networks, medium voltage distributive plants, steam and hydroelectric power stations, where the cables are exposed to influence of wet and aggressive medium.

2.2.3 Three-core cables with XLPE insulated solid sector shaped conductors,

common copper screen and PVC or PE oversheath, 10 kV

TYPE STANDARD

XHP 47-ASJ , XHE 48-ASJ

XHE 47/49-ASJ

JUS N.C5.230 + HD 620

Al-XLPE/PVC,

Al-XLPE/PE wp IEC 60502-2

NA2XSEY, NA2XSE2Y

NA2XSE(F)2Y VDE 0276-620

CONSTRUCTION:

Conductor: Aluminium solid sector shaped

Core: XLPE insulated conductor, with semi-conducting layers applied under and over insulation

Cable core: Screened cores laid-up. Interstices filled with suitable material. Semi-conducting tape wrapping.

Common metallic screen: copper wire screen, wires laid helically around the cable core, with copper counter-helix equalizing tape applied over.

Protection against water penetration (optional): Swellable cords, swellable tapes applied under and over the copper screen.

Oversheath: Black extruded PVC or PE compound.

Application: In power distributive and industrial networks, medium voltage distribution plants, steam and hydroelectric power stations.

Nominal voltage 10 kV

Number of cores Conductor size Note

- three-core 50 - 240 mm2

2.2.4 Three-core cables with XLPE insulation, screened, double steel tape

armoured and PVC or PE oversheathed, 6 - 35 kV

CONSTRUCTION:

Conductor: stranded compacted, soft annealed copper or aluminium

Core: XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper tape helically applied over each insulated core (or copper wires with copper tape).

Cable core: Screened cores laid-up. Interstices filled with suitable material. Thermoplastic tape.

Separation sheath: Black extruded PVC or PE.

Armour: The tape armour shall be applied helically in two layers.

Oversheath: Black extruded PVC or PE.

Application: For medium voltage power distribution in industrial plants where greater mechanical stresses are expected.

Number of cores Conductor size Note

Nominal voltage 6 and 10 kV

- three-core 16 - 300 mm2

Nominal voltage 20 kV

- three-core 35 - 300 mm2

Nominal voltage 35 kV

- three-core 50 - 300 mm2

TYPE STANDARD

XHP 81 , XHE 81 XHP 81-A , XHE 81-A

JUS N.C5.230

XLPE/DTA/PVC

XLPE/DTA/PE

Al-XLPE/DTA/PVC,

Al-XLPE/DTA/PE

IEC 60502-2

N2XSEYBY,

NA2XSEYBY,

N2XSE2YB2Y,

NA2XSE2YB2Y

VDE 0276-620

2.2.5 Three-core cables with XLPE insulation, screened, round galvanized steel

wire armoured and PVC or PE oversheathed, 6 - 35 kV

CONSTRUCTION:

Conductor: stranded compacted, soft annealed copper or aluminium

Core: XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper tape helically applied over each insulated core(or copper wires with copper tape).

Cable core: Screened cores laid-up. Interstices filled with suitable material. Thermoplastic tape wrapping.

Separation sheath: Black extruded PVC or PE.

Armour: Single layer of round galvanized steel wires, with or without steel counter-helix tape.

Oversheath: Black extruded PVC or PE.

Application : For medium voltage power distribution in industrial plants where great mechanical stresses are expected. Suitable for vertical laying.

Number of cores Conductor size Note

Nominal voltage 6 and 10 kV

- three-core 16 - 300 mm2

Nominal voltage 20 kV

- three-core 35 - 300 mm2

Nominal voltage 35 kV

- three-core 50 - 300 mm2

TYPE STANDARD

XHP 84 , XHE 84 XHP 84-A , XHE 84-A

JUS N.C5.230

XLPE/SWA/PVC, XLPE/SWA/PE

Al-XLPE/SWA/PVC,

Al-XLPE/SWA/PE

IEC 60502-2

XLPE/SWA/PVC

Al-XLPE/SWA/PVC, BS 6622

N2XSEYRY,

NA2XSEYRY, VDE 0276-620

2.2.6 Three-core cables with XLPE insulation, screened, flat galvanized steel wire

armoured and PVC or PE oversheathed, 6 - 35 kV

CONSTRUCTION:

Conductor : stranded compacted, soft annealed copper or aluminium

Core : XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper tape helically applied over each insulated core(or copper wires with copper tape).

Cable core : Screened cores laid-up. Interstices filled with suitable material. Thermoplastic tape wrapping.

Separation sheath: Black extruded PVC or PE.

Armour: Single layer of flat galvanized steel wires, with steel counter-helix tape applied over

Oversheath : Black extruded PVC or PE.

Application : For medium voltage power distribution in industrial plants and mines where greater mechanical stresses are expected.

Number of cores Conductor size Note

Nominal voltage 6 and 10 kV

- three-core 16 - 300 mm2

Nominal voltage 20 kV

- three-core 35 - 300 mm2

Nominal voltage 35 kV

- three-core 50 - 300 mm2

TYPE STANDARD

XHP 85 , XHE 85 XHP 85-A , XHE 85-A

JUS N.C5.230

XLPE/FSWA/PVC, XLPE/FSWA/PE

Al-XLPE/FSWA/PVC,

Al-XLPE/FSWA/PE

IEC 60502-2

XLPE/FSWA/PVC

Al-XLPE/FSWA/PVC, BS 6622

N2XSEYFY, NA2XSEYFY,

VDE 0273 + IEC 60502

2.2.7 Self-supporting aerial bundle of XLPE insulated, screened, PVC or PE

oversheathed cables, 10 - 35 kV

TYPE STANDARD

XHP 48/0-A , XHE 48/0-A JUS N.C5.231

CONSTRUCTION :

Conductor : aluminium stranded compacted

Core : XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper wire screen, wires laid helically around the core, with copper counter-helix equalizing tape applied over.

Oversheath : Black extruded PVC or PE compound

Messenger: 50 mm² galvanized steel rope covered with black extruded PVC or PE compound.

Bundle of cables : Cores laid-up around the messenger

Application: For medium voltage power distribution where laying of cables in ground is difficult and where the applying of self-supporting aerial bundle of cables is more economical.

Number of cores Conductor size Note

Nominal voltage 10 kV

- three-core 25 - 150 mm2

Nominal voltage 20 kV

- three-core 35 - 150 mm2

Nominal voltage 35 kV

- three-core 50 - 150 mm2

2.2.8 Self-supporting aerial bundle of XLPE insulated, screened, PE oversheathed cables, with barrier which prevents water penetration through metallic screen along the length of cable, 10 - 35 kV

TYPE STANDARD

XHE 49/0-A JUS N.C5.231

Number of cores Conductor size Note

Nominal voltage 10 kV

- three-core 25 - 150 mm2

Nominal voltage 20 kV

- three-core 35 - 150 mm2

Nominal voltage 35 kV

- three-core 50 - 150 mm2

CONSTRUCTION :

Conductor : aluminium stranded compacted

Core : XLPE insulated conductor, with semi-conducting layers applied under and over the insulation

Metallic screen: copper wire screen, wires laid helically around the core, with copper counter-helix equalizing tape applied over.

Protection against the water penetration: Longitudinal protection - swellable tapes applied under and over the metallic screen, with possibility of radial protection - aluminium-copolymer foil applied under the oversheath.

Oversheath : Black extruded PVC or PE compound

Messenger: 50 mm² galvanized steel rope covered with black PE extruded compound.

Bundle of cables : Single-core cables laid-up around the messenger.

Application : For medium voltage power distribution where laying of cables in ground is difficult and where the applying of self-supporting aerial bundle of cables is more economical.

2. HIGH VOLTAGE CABLES WITH INSULATION OF CROSS-LINKED

POLYETYLENE 60 - 150 KV 2.3.1 High voltage cables with XLPE insulation, copper wire screened, PE oversheated, 60 -150 kV

CONSTRUCTION :

Conductor : stranded, soft annealed copper or aluminium

Core : XLPE insulated conductor, with semi-conducting layers under and over the insulation

Metallic screen: copper wire screen with copper contact tape

Outer sheath : Black extruded high density polyethylene.

Application : For bulk transsmision of electrical energy in big cities and big industry plants.

Conductor material Size Note

Nominal voltage 69 kV

- Copper 240 - 800 mm2

- Aluminium 240 - 1000 mm2

Nominal voltage 110 kV - 150 kV

- Copper 300 - 800 mm2

- Aluminium 300 - 1000 mm2

TYPE STANDARD

XLPE/PE

Al-XLPE/PE IEC 60840

2XS2Y

A2XS2Y IEC 60840

XHE 48 XHE 48-A

IEC 60840

2.3.2 High voltage cables with XLPE insulation, copper wire screened, with radial and longitudinal protection against water penetration, PE oversheated, 60 -150 kV

CONSTRUCTION :

Conductor : stranded, soft annealed copper or aluminium, water sealed.

Core : XLPE insulated conductor, with semi-conducting layers under and over the insulation

Metallic screen: copper wire screen with copper contact tape

Protection against the water penetration: Longitudinal protection - swellable tapes applied under and over the metallic screen,

Radial protection - aluminium-copolimer tape applied under the outer sheath.

Outer sheath : Black extruded high density polyethylene.

Application : For bulk transsmision of electrical energy in big cities and big industry plants. Suitable for wet locations.

Conductor material Size Note

Nominal voltage 69 kV

- Copper 240 - 800 mm2

- Aluminium 240 - 1000 mm2

Nominal voltage 110 kV - 150 kV

- Copper 300 - 800 mm2

- Aluminium 300 - 1000 mm2

TYPE STANDARD

XLPE/Al foil/PE

Al-XLPE/Al foil/PE IEC 60840

2XS(FL)2Y

A2XS(FL)2Y IEC 60840

XHE 49 XHE 49-A

IEC 60840

2.3.3 High voltage cables with XLPE insulation, lead sheathed, PE oversheated, 60 -150 kV

TYPE STANDARD

XLPE/LC/PE

Al-XLPE/LC/PE IEC 60840

2XSK2Y

A2XSK2Y IEC 60840

XHO 03 XHO 03-A

IEC 60840

CONSTRUCTION :

Conductor : stranded, soft annealed copper or aluminium, water sealed.

Core : XLPE insulated conductor, with semi-conducting layers under and over the insulation

Protection against the water penetration: Longitudinal protection - swellable tape under the outer sheath.

Metallic screen: lead sheath

Outer sheath : Black extruded high density polyethylene.

Application : For bulk transsmision of electrical energy in big cities and big industry plants. Suitable for wet and chemichal agersive locations.

Conductor material Size Note

Nominal voltage 69 kV

- Copper 240 - 800 mm2

- Aluminium 240 - 1000 mm2

Nominal voltage 110 kV - 150 kV

- Copper 300 - 800 mm2

- Aluminium 300 - 1000 mm2

2.3.4 High voltage precipitator cables with XLPE insulation, 40 - 111 kV

TYPE STANDARD

XLPE/PVC

Al-XLPE/PVC VDE 0146

2XSYEF A2XSYEF

VDE 0146

CONSTRUCTION :

Conductor : stranded, soft annealed copper or aluminium

Core : XLPE insulated conductor, with semi-conducting layers under and over the insulation

Metallic screen: copper wire screen with copper contact tape

Outer sheath : Black extruded PVC compound.

Application : For electrostatic filters in incineration plants, in the chemical and cement industries.

Nominal voltage 40 - 111 kV

Conductor material Size Note

- Copper 16 - 70 mm2

- Aluminium 16 - 70 mm2

3. RUBBER INSULATED POWER CABLES

3.1 FLEXIBLE RUBBER CABLES FOR PORTABLE POWER CONSUMERS

3.2 FLEXIBLE RUBBER CABLES FOR MINES WITH

00UNDERGROUND EXPLOITATION

3.3 HEAVY DUTY FLEXIBLE RUBBER CABLES FOR MINES WITH SURFACE EXPLOITATION

3.4 SHIPBOARD POWER AND TELECOMMUNITATION CABLES

INSULATED WITH HARD-GRADE EPR

3.5 ROUND AND FLAT RUBBER CABLES FOR CRANES, ELEVATORS, TRANSPORTERS AND IMMERSION WATER PUMPS

3.6 POWER CABLES FOR AIRPORT LIGHTING

3.7 VERY FLEXIBLE RUBBER CABLES FOR RAIL VEHICLES AND TROLLEY BUSES

3.8 FLEXIBLE RUBBER CABLES FOR ARC WELDING 3.9 FLAT ARMOURED CABLES FOR OIL-WELLS OF HIGHER

THERMAL CLASS (2300C)

3.1 FLEXIBLE RUBBER CABLES FOR PORTABLE POWER CONSUMERS 3.1.1 Flexible, natural or synthetic rubber insulated and natural rubber sheathed

cables

CONSTRUCTION : :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation: Elastomer based on natural or EPR - synthetic compound

Cabling: Two or more cabled cores with or without suitable filler

Sheath: Elastomer based on natural compound in black colour

Application: In dry and wet locations for connection portable power consumers such as washing machines, vacuum cleaners and other heating appliances exposed to medium mechanical stress.

Nominal voltage 300 / 500 V

Number of cores Cross section Note

2 0,75 - 10* mm2

3 - 5 0,75 - 6* mm2

* Cross section 4,6 and 10 mm2 are not in IEC 245 - 4 standard.

TYPE STANDARD

H05RR - F VDE 0282 HD 22.4 S3 BS 6500

245 IEC 53 IEC 245 - 4

KG , KG - HL TU 16.K73.05

GG / J , EpG / J JUS.N.C3.502

3.1.2 Natural rubber insulated and polychloroprene sheathed flexible cables

CONSTRUCTION :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation: Elastomer based on natural compound

Cabling: Two or more cabled cores with or without suitable filler

Sheath: Elastomer based on polychloroprene

Application: In dry and wet locations for connection portable power consumers such as washing machines, vacuum cleaners and other heating appliances exposed to medium mechanical stress. It is suitable for using in open air.

Nominal voltage 300 / 500 V

Number of cores Cross section Note

2 0,75 - 10* mm2

3 - 5 0,75 - 6* mm2

* Cross section 4,6 and 10 mm2 are not in IEC 245 - 4 standard.

TYPE STANDARD

H05RN - F VDE 0282 HD 22.4 S3 BS 6500

245 IEC 57 IEC 245 - 4

KGN TU 16.K73.05

GN / J JUS.N.C3.402

3.2 FLEXIBLE RUBBER CABLES FOR MINES WITH UNDERGROUND EXPLOITATION

3.2.1 Flexible mine power cables for mobile devices

CONSTRUCTION :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Cabling: For cables, two or more cabled cores

Inner sheath: Only in a some more-core cables of elastomer based on SBR or polycloroprene compound

Separator: Rubberised textile or nylon tape

Outer sheath: Elastomer based on polychloroprene compound

Application: For connection of heavy duty mobile equipement where medium mechanical stresses occur, in locations where there is no danger from explosion and in mines without methane. For industrial and agricultural workshop appliances.

Nominal voltage 450 / 750 V

Number of cores Cross section Note

1 1,5 - 500 mm2

2 and 5 1 - 25 mm2

3 and 4 1 - 300 mm2

7, 8, 10 , 12, 14, 18, 1,5 - 4 mm2

19, 24, 27, 30, 36, 37 1,5 and 2,5 mm2

TYPE STANDARD

H07RN - F VDE 0282 HD 22.4 S3 BS 6500

245 IEC 66 IEC 245 - 4

KPGSN TU 16.K73.05

GN 50, EpN 50 JUS.N.C5.350

3.2.2 Flexible mine power cables with metallic screen around each insulated

TIP STANDARD

NSSHÖU... + ... / 3E VDE 0250

EpN 53 JUS.N.C5.353

Nominal voltage 0,6 / 1 kV

Number of cores Cross section Note

2 - 18 1,5 - 4 mm2

2 - 7 6 - 95 mm2

2 - 4 120 - 185 mm2

CONSTRUCTION :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Separator: Under and over insulation rubberised nylon tape

Metallic screen: Tinned copper wires as a braid around each insulated core

Cabling: Two or more cabled core

Inner sheath: Elastomer based on ethylene-propylene ( EPR )

Separator: Rubberised nylon tape

Outer sheath: Elastomer based on polychloroprene

Application: In mines with underground exploitation for connecting to supply machines, equipment and apparatus, where danger of methane and of coal-dust explosion is present.

3.2.3 Flexible mine power cables with metallic concentric screen over inner sheath

TIP STANDARD

NSSHÖU ... con VDE 0250

EpN 55 JUS.N.C5.353

Nominal voltage 0,6 / 1 kV

Number of cores Cross section Note

2 - 18 1,5 - 4 mm2

2 - 7 6 - 95 mm2

2 - 4 120 - 185 mm2

CONSTRUCTION :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Separator: Over insulation, rubberised nylon tape

Cabling: Two or more cabled cores

Inner sheath: Elastomer based on ethylene-propylene ( EPR )

Separator: Rubberised nylon tape

Metallic screen: A concentric protective conductor in form of a tinned annealed copper wire braid or tinned copper wires heliclly applied over inner sheath

Separator: Rubberised nylon tape

Outer sheath: Elastomer based on polychloroprene

Application: In mines with underground exploitation for connecting to supply machines, equipment devices and apparatus, where danger of methane and of coal-dust explosion is present.

3.2.4 Very flexible mine power cables for supply drilling machines (rotary drills)

TYPE STANDARD

H07RN - F * VDE 0282 HD 22.4 S3 BS 6500

EpN 58 JUS.N.C5.358

∗ Cable type H07RN - F * is flexible of cable type H07RN - F because of a reduced cabled cores.

CONSTRUCTION :

Conductor: Finely - stranded annealed tinned copper (class 5)

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Cabling: The cores are cabled

Inner sheath: Elastomer based on ethylene-propylene (EPR)

Separator: Rubberised nylon tape

Outer sheath: Elastomer based on polychloroprene

Application: In mines with underground exploitation for supply drilling machines (rotary drills) in locations endangered by fire and where danger of methane and of coal-dust explosion is present.

Nominal voltage 450 / 750 kV

Number of cores Cross section Note

3 - 5 1.5 - 10 mm2

3.2.5 Special rubber mine power cables for supply of electric devices and lighting

TYPE STANDARD

NSSHCGÖU VDE 0250

EpN 60 JUS.N.C5.360

Nominal voltage 0.6 / 1 kV

Power cores Protective core*

Number of cores x cross section

Cross section Note

3 x 2.5 mm2 2.5 mm2

3 x 4 mm2 4 mm2

3 x 6 mm2 6 mm2

3 x 10 mm2 10 mm2

3 x 16 mm2 16 mm2

* Nominal cross section of protective conductor may be higher of values in table.

CONSTRUCTION :

Power cores:

Conductor: Finely - stranded annealed tinned copper (class 5)

Separator: Rubberised nylon tape

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Separator: Semi-conducting nylon tape

Protective core:

Conductor: Finely - stranded annealed tinned copper (class 5)

Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape

Cabling: Three power and one protective core are laid up together

Separator: Semi-conducting nylon tape

Outer sheath: Elastomer based on polychloroprene in yellow colour

Application: In mines with underground exploitation endangered by fire and where danger of methane and of coal-dust explosion is present, for supply machines, devices, apparatus, for secondary current circuits and for electrical lighting.

3.2.6 Special rubber mine power cables for supply of electrical devices and lighting

TYPE STANDARD

NSSHCGÖU VDE 0250

EpN 61 JUS.N.C5.360

Nominal voltage 0.6 / 1 kV

Power cores Protective cores* Note

Number of cores x cross section

Number of cores x cross section

3 x 25 - 3 x 150 mm2 3 x 10 / 3 mm2

* Nominal cross section of protective conductors may be higher of values in table

CONSTRUCTION :

Power cores:

Conductor: Finely - stranded annealed tinned copper (class 5)

Separator: Rubberised nylon tape

Insulation:Elastomer based on ethylene-propylene compound ( EPR )

Separator: Semi-conducting nylon tape

Protective cores:

Conductor: Finely - stranded annealed tinned copper (class 5)

Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape

Cabling: Three power and three protective cores in the interstices between power cores are laid up together

Inner sheath: Elastomer based on ethylene-propylene (EPR)

Separator: Rubberised nylon tape

Outer sheath: Elastomer based on polychloroprene in yellow colour

Application: In mines with underground exploitation endangered by fire and where danger of methane and of coal-dust explosion is present, for supply machines, devices, apparatus and for electrical lighting.

3.2.7 Special rubber mine power cables for supply of electrical devices and lighting

TYPE STANDARD

NSSHCGÖU... + ... ST VDE 0250

EpN 62 JUS.N.C5.360

Nominal voltage 0.6 / 1 kV

Power cores Command cores** Protective core*

Number of cores x cross section

Number of cores x cross section

Cross section

3 x 16 - 3 x 50 mm2 2 x 6 mm2 10 mm2

* Nominal cross section of protective conductors may be higher of values in table ** Nominal cross section of command (pilot) conductors may be also 4 or 10 mm2

CONSTRUCTION :

Power cores: Conductor: Finely - stranded annealed tinned copper (class 5) Separator: Rubberised nylon tape Insulation:Elastomer based on ethylene-propylene compound ( EPR ) Separator: Semi-conducting nylon tape Protective core: Conductor: Finely - stranded annealed tinned copper (class 5) Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape Command (pilot) cores: Conductor: Finely - stranded annealed tinned copper (class 5) Insulation:Elastomer based on ethylene-propylene compound ( EPR ) Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape Cabling: Three power, one protective and two command (pilot) cores are laid up together in such a manner that the command and the protective cores fill the interstices between the power cores Separator: Semi-conducting nylon tape Inner sheath: Elastomer based on (EPR) Separator: Rubberised nylon tape Outer sheath: Elastomer based on polychloroprene in yellow colour

Application: In mines with underground exploitation endangered by fire and where danger of methane and of coal-dust explosion is resent, for supply machines, devices, apparatus, electrical lighting and for auxiliary current circuits.

3.2.8 Special rubber mine power cables for supply of electrical devices and lighting

TIP STANDARD

NSSHCGÖU... kon + ... ST+ + ... ST + ... ÜL

VDE 0250

EpN 63 (EpN 63 - S) JUS.N.C5.360

Nominal voltage 0.6 / 1 kV

Power cores Command cores** Cont.ol core *

No x cross section No x cross section Cross section

Cross section of concentric conductor

3 x 25 - 3 x 150 2 x 6 mm2 10 mm2 10 mm2 * Nominal cross section of protective conductors may be higher of values in table ** Nominal cross section of command (pilot) conductors may be also 4 or 10 mm2

CONSTRUCTION :

Power cores: Conductor: Finely-stranded tinned copper (cl. 5) Separator: Rubberised nylon tape Insulation: Elastomer based EPR Separator: Semi-conducting nylon tape Control core: Conductor: Finely-stranded tinned copper (cl. 5) Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape Command (pilot) cores: Conductor: Finely-stranded tinned copper (cl. 5) Insulation:Elastomer based on EPR Semi-conducting layer: Extruded semi-conducting rubber or semi-conducting nylon tape Cabling: Three power, one control and two command (pilot) cores are laid up together in such a manner that the command (pilot cores) and control core fill up the interstices Separator: Semi-conducting nylon tape Inner sheath: Elastomer based on EPR Separator: Rubberised nylon tape Concentric protective conductor: In form of a tinned copper wire braid or helically applied (EpN 63) or double coating of combination of copper and steel wires (EpN 63 - S) Separator: Rubberised nylon tape Outer sheath: Elastomer based on polychloroprene in yellow colour

Application: In mines with underground exploitation endangered by fire and where danger of methane and of coal-dust explosion is present, for supply and directly connecting of portable machines, cutters, loaders and mine equipment, where the protection of the command (pilot) conductor is desired.

3.2.9 Special rubber mine power cables for supply portable transformers

TYPE STANDARD

NTSCGERLWÖU VDE 0250

EpN 64, EpN 65 JUS.N.C5.364

Nominal voltage 3.6 / 6 kV

Cross section Construction Note

16 mm2 3 x 16 / 10 / 6

25 mm2 3 x 25 / 10 / 6

35 mm2 3 x 35 / 16 / 6

50 mm2 3 x 50 / 25 / 6

70 mm2 3 x 70 / 35 / 6

95 mm2 3 x 95 / 50 / 6

CONSTRUCTION :

Power cores:

Conductor: Finely-stranded tinned copper (cl. 5)

Separator: Rubberised nylon tape

Insulation: Elastomer based EPR

Semi-conducting layer: Extruded semi-conducting rubber (EpN 65) or semi-conducting nylon tape (EpN 64)

Cabling: Power cores are laid up together

Inner sheath: Elastomer based on EPR (EpN 64) or of semi-conducting elastomer (EpN 65)

Separation sheath: Extruded insulated rubber or rubberised nylon tape with overhead

Concentric conductor: Annealed tinned copper wire braid

Separator: Semi-conducting nylon tape

Concentric command conductor: Annealed tinned copper wires concentrically applied around separation sheath

Separator: Rubberised nylon or textile tape

Outer sheath: Elastomer based on polychloroprene in red colour

Application: In dry and wet locations and in mines with underground exploitation. It is suitable for use as high-voltage power distribution cable in methane pits for connection of portable transformers and other applications.

3.3 HEAVY DUTY FLEXIBLE RUBBER CABLES FOR MINES WITH SURFACE EXPLOITATION

3.3.1 Heavy duty flexible mine power cable with concentric protective conductor

TYPE STANDARD

NHSSHCGÖU... con

NTSCWÖU

VDE 0250

Ep(H)N 74 JUS.N.C5.374

Nominal voltage (kV) Construction

3.6 / 6 3 x 10 / 10 do 3 x 185 / 95

6 / 10 3 x 10 / 10 do 3 x 185 / 95

8.7 / 15 3 x 16 / 16 do 3 x 185 / 95

12 / 20 3 x 16 / 16 do 3 x 185 / 95

14 / 25 3 x 25 / 16 do 3 x 185 / 95

18 / 30 3 x 25 / 16 do 3 x 150 / 70

20 / 35 3 x 35 / 16 do 3 x 120 / 70

CONSTRUCTION :

Power cores:

Conductor: Finely-stranded tinned copper (cl. 5) Separator: Semi-conducting nylon tape Semi-conducting layer: Extruded semi-conducting rubber Insulation: Elastomer based EPR Semi-conducting layer: Extruded semi-conducting rubber

Cabling: Three power cores are laid up together

Inner sheath: Elastomer based on natural rubber, SBR or ethylene propylene (EPR)

Separator: Rubberised nylon tape

Concentric protective conductor: Annealed tinned copper wires are helically applied over inner sheath

Separator: Rubberised nylon tape

Outer sheath: Elastomer based on polychloroprene in red colour

Application: In mines with surface exploitation may be installed in dry, humid and moist locations, in maste waters, air and similar, where there are high mechanical stresses. In quarries, shipyards and in industry for transmission of great amount of power, for supply heavy mobile machines, dredges, cranes and docks.

3.3.2 Flexible heavy duty mine power cable with protective conductor in interstices between the power cores

TIP STANDARD

NTSCGEWÖU VDE 0250

KŠVG TU 16.505.522

KŠVGT - 10 TU 16.705.101

Ep(H)N 78 JUS.N.C5.374

Nominal voltage (kV) Construction

3.6 / 6, 6 /10 3x10+3x6 do 3x185+3x 50

8.7 / 15, 12/20 3x16+3x10 do 3x185+3x 50

14 / 25 3x25+3x10 do 3x185+3x 35

18 / 30 3x25+3x10 do 3x150+3x 25

20 / 35 3x35+3x10 do 3x120+3x 16

CONSTRUCTION :

Power cores: Conductor: Finely-stranded tinned copper (cl. 5) Separator: Semi-conducting nylon tape Semi-conducting layer: Extruded semi-conducting rubber Insulation: Elastomer based EPR Semi-conducting layer: Extruded semi-conducting rubber Protective cores: Conductor: Finely-stranded tinned copper (cl. 5) Semi-conducting layer: Extruded semi-conducting rubber Cabling: Three power cores and three protective cores in interstices between the power cores are laid up together Separator: Semi-conducting nylon tape Inner sheath: Elastomer based on natural rubber, SBR or ethylene propylene (EPR) Separator: Rubberised nylon tape or reinforcement braid of textile or nylon threads Outer sheath: Elastomer based on polychloroprene in red colour

Application: In mines with surface exploitation may be installed in dry, humid and moist locations, in maste waters, air and similar, where there are high mechanical stresses. In quarries, shipyards and in industry for transmission of great amount of power, for supply heavy mobile machines, dredges, cranes and docks and where the cable may be forced to describe and S-bend.

3.3.3 Flexible heavy duty mine power cable with concentric screen around each power core, with two control and one command conductor

TYPE STANDARD

NTSCGEÖU VDE 0250

SHD - GC ICEA S 68-516

Ep(H)N 78/53 JUS.N.C5.374

Nominal voltage 3.6 / 6 do 12 / 20 kV

Type of cores Number of cores Cross section

Power cores 3 16 up to 185 mm2

Protective cores 2 6 up to 95 mm2

Command core 1 10 mm2

CONSTRUCTION :

Power cores: Conductor: Finely-stranded tinned copper (cl. 5) Separator: Semi-conducting nylon tape Semi-conducting layer: Extruded semi-conducting rubber Insulation: Elastomer based EPR Semi-conducting layer: Extruded semi-conducting rubber Protective cores: Conductor: Finely-stranded tinned copper (cl. 5) Semi-conducting layer: Extruded semi-conducting rubber Command core: Conductor: Finely-stranded tinned copper (cl. 5) Insulation: Elastomer based EPR Cabling: Three power cores, two protective (control) cores and one command core are laid up together (control cores and command core fill up the interstices between power screened cores) Separator: Semi-conducting nylon tape Inner sheath: Elastomer based on natural rubber SBR or ethylene propylene (EPR) Separator: Rubberised nylon tape or reinforcement braid of textile or nylon threads Outer sheath: Elastomer based on polychloroprene in red colour

Application: In mines with surface exploitation may be installed in dry, humid and moist locations, in maste waters, air and similar, where there are high mechanical stresses. In quarries, shipyards and in industry for transmission of great amount of power, for supply heavy mobile machines, dredges, cranes and docks and where the cable may be forced to describe and S-bend.

3.4 SHIPBOARD POWER AND TELECOMMUNITATION CABLES INSULATED WITH HARD-GRADE EPR ELASTOMER

3.4.1 Shipboard power cables without screen

Nominal voltage 0.6 / 1 kV

Number of cores Cross section Note

1 4 up to 300 mm2

2 1 up to 25 mm2

3 1 up to 120 mm2

4 1 up to 95 mm2

5 1 up to 2.5 mm2

7 to 24 1 and 1.5 mm2

TYPE STANDARD

MGG, MGH DIN 89160

KNR, - GOST 7866

CONSTRUCTION :

Conductor: Copper tinned annealed stranded

Insulation: Halogen-free, extruded compound of hard-grade ethylene-propylene elastomer (HEPR)

Cabling: Two or more cabled cores, only in more-core cables

Sheath: Vulcanised, flame retardant compound based on polycloroprene elastomer (type MGG), or halogen-free extruded thermoplastic compound based on olefin-copolymer (MGH)

Application: They are used for stationary on other floating objects, bat only in locations where there is no danger of radio or radar equipment interference. Since the cables are not electrically protected, these cables must only be installed below the top metallic deck and at those points at which the cables are separated from aerials, aerial lead-ins, wireless rooms, radio direction finders or other radio locating and receiving equipment.

3.4.2 Shipboard power cables, screened

TYPE STANDARD

MGCG, MGCH DIN 89158

KNR, - GOST 7866

Nominal voltage 0.6 / 1 kV

Number of cores Cross section Note

1 4 up to 300 mm2

2 1.5 up to 25 mm2

3 1 up to 120 mm2

4 1 up to 95 mm2

5 1 up to 2.5 mm2

7 to 24 1.5 mm2

CONSTRUCTION :

Conductor: Copper tinned annealed stranded

Insulation: Halogen-free, extruded compound of hard-grade ethylene-propylene elastomer (HEPR)

Cabling: Two or more cabled cores, only in more-core cables

Filler: Only in more-core cables of extruded elastomeric or thermoplastic compound

Separator: Polyester tape

Electrical screen: Metallic nonmagnetic material as a braid of copper annealed untinned wires

Separator: Polyester tape

Sheath: Vulcanised, flame retardant compound based on polycloroprene elastomer (type MGCG), or halogen-free extruded thermoplastic compound based on olefin-copolymer (MGCH)

Application: They are used for stationary installation on ships, boats and on other floating objects in all their rooms and on open decks, for the transmission of power, for signalling and for control. The electrical screen reduces interference with radio communication and electronic installations in the event of serious mechanical damage, it also protects persons from accidental electric shock.

3.4.3 Shipboard telecommunication cables, screened

Nominal voltage 250 V

Construction of cable Note

1 x 2 x 0.75 mm²

2 x 2 x 0.75 mm²

4 x 2 x 0.75 mm²

7 x 2 x 0.75 mm²

10 x 2 x 0.75 mm²

14 x 2 x 0.75 mm²

19 x 2 x 0.75 mm²

24 x 2 x 0.75 mm²

TYPE STANDARD

FMGCG, FMGCH DIN 89159

KNRT, GOST 7866

CONSTRUCTION :

Conductor: Copper tinned annealed stranded

Insulation: Halogen-free, extruded compound of hard-grade ethylene-propylene elastomer (HEPR)

Cabling core: Two cabled core in pair

Cabling pairs: Two or more cabled pairs

Filler: Only in more-core cables of extruded elastomeric or thermoplastic compound

Separator: Polyester tape

Electrical screen: Metallic nonmagnetic material as a braid of copper annealed untinned wires

Separator: Polyester tape

Sheath: Vulcanised, flame retardant compound based on polycloroprene elastomer (type FMGCG), or halogen-free extruded thermoplastic compound based on olefin-copolymer (FMGCH)

Application: They are used for stationary installation on ships, boats and on other floating objects in all their rooms and below decks and on the superstructure for measuring, control, command and alarm systems. The electrical screen reduces interference with radio communication and position-finding equipment.

3.5 ROUND AND FLAT RUBBER CABLES FOR CRANES, ELEVATORS, TRANSPORTERS AND IMMERSION WATER PUMPS

3.5.1 Round rubber cables for cranes, elevators and lifts

CONSTRUCTION :

Conductor: Finely-stranded annealed tinned or untinned copper (class 5 or 6)

Insulation: Elastomer based on EPR

Cabling: Two or more cabled cores

Separator: Polyester or rubberised nylon tape

Sheath: Elastomer based on polychloroprene in black colour

Application: In dry and damp rooms and outdoors, as well as in water. Not to be used for high speed lifts (exceeding 2.5 m/s) or in high buildings (exceeding 50 m).

Nominal voltage 300 / 500 V

Number cores Cross section Note

6, 12, 16, 19 1 up to 2.5 mm2

TYPE STANDARD

NFLGÖU VDE 0250

245 IEC 75 IEC 245 - 5

RDOH SEN 24 02 60

H05RN03 - F HD 359

DEpN JUS

3.5.2 Flat rubber cables for cranes, elevators, and transporters and for immersion water pumps

TYPE STANDARD

NGFLGÖU VDE 0250

EpN / U , DEpN / U JUS

Nominal voltage 300 / 500 V

Type EpN / U Type DEpN / U

No cores Cross section No cores Cross section

3 and 4 1.5 up to 25 mm2 4 1.5 up to 95 mm2

7 6 up to 25 mm2

8 and 12 1.5 and 2.5 mm2

CONSTRUCTION :

Conductor: Finely-stranded annealed tinned or untinned copper (class 5 or 6)

Insulation: Elastomer based on EPR

Sheath: Elastomer based on polychloroprene in black colour

Application: In dry and wet rooms and for cranes, elevators, transporters and other equipment as well as for immersion water pumps.

3.6 POWER CABLES FOR AIRPORT LIGHTING 3.6.1 Airport rubber high-voltage primary cable without electrical screen

TYPE STANDARD

SRN FAA L - 824

SEpN JUS

Nominal voltage 5000 ( 8000) V

No cores Cross section Note

6 mm2 1

8 AWG ( 8.36)

CONSTRUCTION :

Conductor: Copper stranded tinned conductor (class 2)

Insulation: Elastomer based on EPR

Sheath: Elastomer based on polychloroprene

Application: They are used for interconnect the isolating transformers in series and theirs supplied by a constant current regulator in high-voltage series primary circuits on airport starting-landing paths. This type of airport cable used in places, where thunder storms and thunder claps in proximity of the cables are not frequent and where is not a danger of their being attacked by rodents, termites and other deleterious insects.

3.6.2 Airport rubber high-voltage primary cable, screened

TYPE STANDARD SRC7N FAA L - 824 SEpN / Z JUS

Nominal voltage 5000 ( 8000) V

No cores Cross section Note

6 mm2 1

8 AWG ( 8.36)

CONSTRUCTION :

Conductor: Copper stranded tinned conductor (class 2)

Insulation: Elastomer based on EPR

Electrical screen: Tinned copper wires helically applied or copper tape with overhead

Sheath: Elastomer based on polychloroprene

Application: They are used for interconnect the isolating transformers in series and theirs supplied by a constant current regulator in high-voltage series primary circuits on airport starting-landing paths. This type of airport cable used in places, where thunder storms and thunder claps in proximity of the cables are frequent and where is not a danger of their being attacked by rodents, termites and other deleterious insects.

3.6.3 Airport rubber secondary low-voltage cable

TYPE STANDARD

SRN FAA L - 824

SEpN / FJ JUS

Nominal voltage 300 / 500 V

No cores Cross section Note

1 4 mm2 2

2.5 mm2 12AWG (3.31)

4 mm2

CONSTRUCTION :

Conductor: Finely-stranded copper annealed tinned (class 5)

Insulation: Elastomer based on EPR

Sheath: Elastomer based on polychloroprene

Application: These airport cables are used in secondary circuits for supply of airfeld low voltage lighting on the airport starting-landing paths.These cables are generally two-core, but they also can be others construction.

3.7 VERY FLEXIBLE RUBBER CABLES FOR RAIL VEHICLES AND TROLLEY BUSES

TYPE STANDARD

NSGAFÖU VDE 0250

ŽEpN / F, ŽEpN / FV JUS

CONSTRUCTION :

Conductor: Finely-stranded copper annealed tinned (class 5)

Insulation: Elastomer based on EPR

Sheath: Elastomer based on polychloroprene

Application: These cables are used for locomotives and railway coach, for electric traction engines, electric circuits for heating, for control, for steering and for lighting. These cables, are used for rail vehicles, trolley buses and other similar machines.

Nominal voltage 750, 1500, 3000 V

Type 750 V Type 1500 and 3000 V

No cores Cross section No cores Cross section

1 1.5 to 240 1 1.5 to 240

3.8 FLEXIBLE RUBBER CABLES FOR ARC WELDING

CONSTRUCTION :

Conductor: Very finely-stranded copper conductor

Separator: Crepe paper tape

Insul./sheath: Elastomer based on polychloroprene

Application: For connection arc welding units when ever flexible cable is required,

Nominal voltage 100 V

No cores Cross section Note 1 10 up to 120 mm2

TYPE STANDARD

NSLFFÖU VDE 0250

H01N2 - D

H01N2 - E VDE 0282 HD 22.6 S2

SO SEN 24 02 47

245 IEC 82 IEC 245 - 6

ARC WELDING BS 638

KOG - 1 TU 16.K73.03

ZN / S JUS N.C9.030

3.9 Flat armoured cables for Oil-wells of higher thermal class ( 2300C )

Nominal voltage 2.31 / 4 kV

Number of cores Cross-section Note

three-core 10 – 33.6 mm2 flat

Cross-section

Thickness of insulation

Thickness of lead sheath

Approx. overall diameter

Total mass ( approx. )

Delivery lengths

(mm2) (mm) (mm) (mm) (kg/km) (m)

3 x10 1.6 0.9 11.5 x 29.5 1500 2000

3 x 13.3 1.6 0.9 12.0 x 31.5 1830 2000

3 x 16 1.6 0.9 12.5 x 32.5 1970 2000

3 x 21.2 1.8 1.0 13.5 x 36.0 2300 1700

3 x 33.6 1.6 1.0 15.0 x 40.5 2890 1400

TYPE SPECIFICATION

KEPSBPT FKS 9.NK.01

CONSTRUCTION :

Conductor : Solid round wire of electrolytic annealed copper., class 1

Core : Conductor insulated with special elastomer bassed on EPDM compound of thermal class

Sheath : Extruded lead sheath, fatigue and corrosion resistant, which provides protection of insulation from oil, chemicals, gases and insulation decompression

Bedding : Suitable tape is helically wrapped with overlaps

Cable core : Cores laid-up in parallel and wrapped suitable tape with overlaps

Armour : Fully galvanised steel tape (on four sides) wrapped with overlaps in form “Q”-profile, which provides excellent mechanical and anti-corrosion protection..

Application: Flat power armoured cables for oil wells of higher thermal class with special rubber insulation based on EPDM compound are used in oil wells for installations of submersible power electric pumps..

4. INSULATED ELECTRIC POWER CABLES AND FLEXIBLE

CORDS

4.1 PVC INSULATED CABLES

4.2 RUBBER INSULATED CABLES

4.1 PVC INSULATED CABLES 4.1.1 PVC insulated single core cables

CONSTRUCTION OF TYPE ( P , P/M ) :

Conductor : Soft annealed solid (class 1) or stranded (class 2) copper conductor. Insulation : Extruded PVC . Standard colours : black, bright, blue, brown, green/yellow.

Application : For electric power wiring in dry premises for lasting laying in tubes over or under mortar as well as on insulators. Max. permissible temperature 70 oC.

CONSTRUCTION OF TYPE P/F :

Conductor : Soft annealed flexible cord conductor Insulation : Extruded PVC . Standard colours : black, bright, blue, brown, green/yellow.

Application : For electric power wiring in dry premises where special flexibility is required, for lasting laying in tubes over or under mortar as well as on insulators. Max.permissible temp. 70 oC.

Nominal voltage 450 / 750 V

Type No. of cores Cross-section Note

P 1 1,5 - 16 mm2

P/M 1 1,5 - 400 mm2

P/F 1 1,5 - 240 mm2

TYPE STANDARD

P JUS.N.C3.200

HO7V-U VDE 0281-3 NFC 32-201-3

BS 6004 PV-1 GOST 6323

P/M JUS N.C3.201

HO7V-R VDE 0281-3 NFC 32-201-3

BS 6004 PV-2 GOST 6323

P/F JUS N.C3.202

HO7V-K VDE 0281-3 NFC 32-201-3

BS 6004 PV-3 GOST 6323

4.1.2 PVC insulated and sheathed flat cords

CONSTRUCTION :

Conductor : Soft annealed solid copper conductor.

Core insulation : Extruded PVC

Sheath : Common PVC sheath.

Standard core colours according to JUS N.CO.010. Sheath mostly in black colour.

Application : For wiring in dry premises over or under mortar without special mechanical protection. Max. permissible temperature 70oC.

Nominal voltage 300 / 500 V

No. of cores Cross-section Note

2 - 3 1,5 - 4 mm2

TYPE STANDARD

PP/R JUS.N.C3.230

NYIFY VDE 0250 teil 201

4.1.3 PVC insulated and sheathed cables for fixed wiring

TYPE STANDARD

PP JUS.N.C3.220

NYM VDE 0250 teil 204

VVG GOST 16442

Nominal voltage 300 / 500 V

No. of cores Cross-section Note

2 - 5 1,5 - 35 mm2

CONSTRUCTION:

Conductor : Soft annealed solid (class 1) or stranded (class 2) copper conductor.

Core insulation : Extruded PVC.

Stranding : Cores laid-up together. Interstices filled with unvulcanized rubber.

Sheath : Seamless PVC tube over stranding cores.

Standard core colours according to JUS N.CO.010. Sheath mostly in grey colour.

Application : In dry and damp premises over or under mortar as well as outdoors. Max. permissible temperature 70oC.

4.1.4 PVC insulated and sheathed flat core cables

TYPE STANDARD

PP/U JUS.N.C3.235

PVC sh flat BS 6004

Nominal voltage 500 V

No. of cores Cross-section Note

2 - 3 1 - 6 mm2

CONSTRUCTION :

Conductor : Soft annealed solid copper conductor.

Insulation : Extruded PVC.

Sheath : Extruded PVC.

Standard core colours according to JUS N.CO.010. Sheath mostly in grey colour.

Application : In dry and damp premises for permanent laying on, over or under mortar or steel construction. Max. permissible temperature 70oC.

4.1.5 Light PVC insulated and sheathed flexible cables

CONSTRUCTION:

Conductor : Soft annealed flexible (class 5) copper conductor.

Core insulation : Extruded PVC.

Sheath : Extruded PVC.

Standard colours : According to JUS N. CO. 010.

Sheath mostly in black or white colour.

Application : For wiring small portable electric appliances operating under light conditions such as portable lamps, fans, refrigerators and other household appliances, where the cable cannot be in touch with surfaces at temperatures exceeding 85 °C. Max. permissible temperature 70oC.

Nominal voltage 300 / 300 V

No. of cores Cross-section Note

2 - 4 0,5 - 1 mm² PP/L

2 0,5 - 0,75 mm2 PP/L - U

TYPE STANDARD

PP/L JUS.N.C3.301

HO3VV-F VDE 0281 - 5

NFC 32-201 - 5 BS 6500

PVS GOST 7399

PP/L - U JUS.N.C3.301

HO3VVH2 - F VDE 0281 - 5

ŠVVP GOST 7399

4.1.6 Ordinary PVC insulated and sheathed flexible cables

CONSTRUCTION:

Conductor : Soft annealed flexible (class 5) copper conductor.

Core insulation : Extruded PVC.

Sheath : Extruded PVC.

Standard colours : According to JUS N. CO. 010.

Sheath mostly in grey, black or white colour.

Application : For wiring small portable electric appliances operating under heavy duty conditions such as washing machines, vacuum cleaners and thermal appliances where the cables cannot be in touch with surfaces at temperatures exceeding 85 °C. Max. permissible temperature 70oC.

Nominal voltage 300 / 500 V

No. of cores Cross-section Note

2 - 7 0,75 - 2,5 mm² PP / J

2 0,75 mm2 PP / J - U

TYPE STANDARD

PP/J JUS.N.C3.302

HO5VV-F VDE 0281 - 5

NFC 32-201 - 5 BS 6500

PVS GOST 7399

PP/J - U JUS.N.C3.302

HO5VVH2 - F VDE 0281 - 5

ŠVVP GOST 7399

4.2 RUBBER INSULATED CABLES 4.2.1 Flexible rubber conductors with textile braid for mobile devices 4.2.1.1 Flexible rubber conductors with textile braid

CONSTRUCTION:

Conductor : Finely stranded annealed tinned copper conductor

Insulation : Natural rubber compound

Cabling : Two or three cores are laid up together with suitable filler in the interstices between insulated cores

Braid : Textile cord

Application: For flexible connections in domestic premises, kitchens, offices and for supplying hand appliances which are subjected to heavy mechanical stresses.

No. of cores Cross-section Note

2 0.75-1.5 mm²

3 0.75-1.5 mm²

TYPE STANDARD

GT / J JUS N.C3.401

H03RT – F

VDE 0282

BS 6500

NF – C 32102

ŠRO GOST 7399

4.2.1.2 Flexible rubber insulated and rubber sheathed conductors with textile braid

over sheath

No. of cores Cross-section* Note

2 0.75-10 mm²

3-5 0.75-1.5 mm²

* Cross section 6 and 10 mm2 are not in IEC 245 - 4 standard.

TYPE STANDARD

GGT / J

EpGT / J JUS N.C3.502

H05RRT – F VDE 0282

CONSTRUCTION:

Conductor : Finely stranded annealed tinned copper conductor

Insulation : Natural rubber compound

Cabling : Two or three cores are laid up together with suitable filler in the interstices between insulated cores

Sheath: Natural rubber compound

Braid : Textile cord

Application: For flexible connections in domestic premises, kitchens, offices and for supplying hand appliances which are subjected to heavy mechanical stresses.

5. HALOGEN-FREE FLAME RETARDANT POWER CABLES AND CONDUCTORS

5.1 HALOGEN-FREE FLAME RETARDANT POWER CABLES AND CONDUCTORS FOR RATED VOLTAGES UP TO 1 kV

5.2 MEDIUM VOLTAGE HALOGEN-FREE FLAME RETARDANT POWER CABLES 10 - 35 kV

5.1 HALOGEN-FREE FLAME RETARDANT POWER CABLES AND CONDUCTORS FOR RATED VOLTAGES UP TO 1 kV

5.1.1 Halogen-free installation conductors, 300/500 V

TRADE MARK FKS-PLAMEX 1

TYPE STANDARD

NHMH VDE 0250-215

Nominal voltage 300/500 V

Number of cores Size Note

- 1-core 1,5 - 16 mm2

- 2-core 1,5 - 2,5 mm2

- 3-core 1,5 - 10 mm2

- 4-core 1,5 - 35 mm2

- 5-core 1,5 - 16 mm2

- 7-core 1,5 - 2,5 mm2

CONSTRUCTION :

Conductor : Solid or stranded, soft annealed copper

Core : Polypropylene insulated conductor

Cable core : Laid-up cores. Interstices filled with extruded halogen-free flame retardant compound.

Oversheath : Cream-white extruded halogen-free flame retardant compound.

Improved performance in the case of fire:

Reduced flame propagation: IEC 332-1; VDE 0472-804B

No corrosive combustion gases: IEC 754-2; VDE 0472-813

Low smoke density: IEC 1034; VDE 0472-816

Application : For fixed installation over, on, in and under plaster, in dry and moist wet rooms, in masonry and in concrete, mainly in buildings with safety requirements.

5.1.2 Halogen-free installation conductors with improved performance in the case of fire, 300/500 V

Nominal voltage 300/500 V

Number of cores Size Note

- 1-core 1,5 - 16 mm2

- 2-core 1,5 - 2,5 mm2

- 3-core 1,5 - 10 mm2

- 4-core 1,5 - 35 mm2

- 5-core 1,5 - 16 mm2

- 7-core 1,5 - 2,5 mm2

TRADE MARK FKS-PLAMEX 2

TYPE STANDARD

NHXMH DIN VDE 0250-214

CONSTRUCTION :

Conductor : Solid or stranded, soft annealed copper

Core : XLPE insulated conductor

Cable core : Laid-up cores. Interstices filled with extruded halogen-free flame retardant compound.

Oversheath : Grey extruded halogen-free flame retardant compound.

Improved performance in the case of fire:

Reduced flame propagation: IEC 332-3C; VDE 0472-804C

No corrosive combustion gases: IEC 754-2; VDE 0472-813

Low smoke density: IEC 1034; VDE 0472-816

Application : For fixed installation over, on, in and under plaster, in dry and moist wet rooms, in masonry and in concrete, mainly in buildings with a high concentration of people and/or valuable contents.

5.1.3 Halogen-free power cables with improved performance in the case of fire, 0.6/1 kV

Nominal voltage 1 kV

Number of cores Size Note *

- 1-core 1,5 - 300 mm2

- 2-core 1,5 - 25 mm2

- 3-core 1,5 - 240 mm2 round, sector

- 4-core,reduced neut. 35 - 240 mm2 round, sector

- 4-core 1,5 - 240 mm2 round, sector

- 5-core 1,5 - 25 mm2

- 7-61 cores 1,5 - 4 mm2

* Sector-shaped conductors for conductor size 35 mm² and greater

TRADE MARK FKS-PLAMEX 3

FKS-PLAMEX 3C

TYPE STANDARD

N2XH, N2XCH VDE 0276-604

CONSTRUCTION :

Conductor : Solid or stranded, soft annealed copper

Core : XLPE insulated conductor

Cable core : Laid-up cores. Interstices filled with extruded halogen-free flame retardant compound.

Concentric conductor: Copper wires with copper contact tape (with C designation)

Oversheath : Black extruded halogen-free flame retardant compound.

Improved performance in the case of fire:

Flame propagation: IEC 332-3C; VDE 0472-804C Corrosive combustion gases: IEC 754-2; VDE 0472-813 Low smoke density: IEC 1034; VDE 0472-816

Application: For installation indoors and outdoors; laying in the ground is not permitted. These cables are intended mainly for use in buildings and installations with increased safety requirements for people and valuable contents, e.g. hospitals, power plants, public buildings, underground rail systems etc. as a means of preventive fire protection.

5.1.4 Halogen-free power cables with improved performance in the case of fire for special applications, 0.6/1 kV

Nominal voltage 1 kV

Number of cores Size* Note

- 1-core 1,5 - 300 mm2

- 2-core 1,5 - 25 mm2

- 3-core 1,5 - 185 mm2

- 4-core,reduced neut. 35 - 185 mm2

- 4-core 1,5 - 240 mm2

- 5-core 1,5 - 25 mm2

- 7- 40 cores 1,5 -4 mm2

* With round conductors only, according to the standard

TRADE MARK FKS-PLAMEX 4

FKS-PLAMEX 4C

TYPE STANDARD

NHXHX, NHXCHX DIN VDE 0266

CONSTRUCTION :

Conductor : Solid or stranded, soft annealed copper

Core : Halogen-free cross-linked compound insulated conductor

Cable core : Laid-up cores. Interstices filled with extruded halogen-free flame retardant compound.

Concentric conductor: Copper wires with copper contact tape (with C designation)

Oversheath : Black extruded cross-linked halogen-free flame retardant compound.

Improved performance in the case of fire:

Reduced flame propagation: IEC 332-3C; VDE 0472-804C No corrosive combustion gases: IEC 754-2; VDE 0472-813 Low smoke density: IEC 1034; VDE 0472-816

Application: For use in the containment of nuclear power plants. Also may be used in buildings with increased safety requirements.

5.1.5 Halogen-free power cables with circuit integrity of cable in the case of fire, 0.6/1 kV

CONSTRUCTION :

Conductor : Solid or stranded, soft annealed copper

Core : Mica tape wrapped, halogen-free cross-linked compound insulated conductor

Cable core : Laid-up cores. Interstices filled with suitable halogen-free flame retardant material.

Concentric conductor: Copper wires with copper contact tape (with C designation) Separator : glass tape (optional)

Oversheath : Orange extruded cross-linked halogen-free flame retardant compound.

Improved performance in the case of fire:

Reduced flame propagation: IEC 332-3C; VDE 0472-804C No corrosive combustion gases: IEC 754-2; VDE 0472-813 Low smoke density: IEC 1034; VDE 0472-816 Circuit integrity of cable: IEC 331; VDE 0472-814

Application : For installation indoors and outdoors, laying in the ground is not permitted. They are suitable for power supplies to safety systems, e.g. in places where many people gather, schools, hospitals, etc.

Nominal voltage 1 kV

Number of cores Size* Note

- 1-core 1,5 - 300 mm2

- 2-core 1,5 - 25 mm2

- 3-core 1,5 - 185 mm2

- 4-core,reduced neut. 35 - 185 mm2

- 4-core 1,5 - 240 mm2

- 5-core 1,5 - 25 mm2

- 7- 30 cores 1,5 -4 mm2

* With round conductors only, according to the standard

TRADE MARK FKS-PLAMEX 5

FKS-PLAMEX 5C

TYPE STANDARD

NHXHX FE180 NHXCHX FE180

DIN VDE 0266

5.1.6 Halogen-free power cables with circuit integrity of cable installation in the case of fire, 0.6/1 kV

Nominal voltage 1 kV

Number of cores Size* Note

- 1-core 1,5 - 300 mm2

- 2-core 1,5 - 25 mm2

- 3-core 1,5 - 185 mm2

- 4-core, reduced neut. 35 - 185 mm2

- 4-core 1,5 - 240 mm2

- 5-core 1,5 - 25 mm2

- 7- 30 cores 1,5 -4 mm2

* With round conductors only, according to the standard

TRADE MARK FKS-PLAMEX 6

FKS-PLAMEX 6C

TYPE STANDARD

NHXHX FE180/E90 NHXCHX FE180/E90

DIN VDE 0266

CONSTRUCTION :

Conductor : Solid or stranded, annealed copper

Core : Mica tape wrapped, halogen-free cross-linked compound insulated conductor

Cable core : Laid-up cores. Interstices filled with suitable halogen-free flame retardant material.

Concentric conductor: Copper wires with copper contact tape (with C designation)

Separator : high-temperature resistant glass tape

Oversheath : Orange extruded cross-linked halogen-free flame retardant compound.

Improved performance in the case of fire:

Flame propagation: IEC 332-3C; VDE 0472-804C Corrosive combustion gases: IEC 754-2; VDE 0472-813 Low smoke density: IEC 1034; VDE 0472-816 Circuit integrity of cable: IEC 331; VDE 0472-814; 90 minutes: DIN 4102-12

Application : For installation indoors and outdoors, laying in the ground is not permitted. For power supplies to cable installation sections required for direct firefighting, e.g. water pressurisation systems, ventilation systems for safety staircases, smoke,heat extraction systems.

5.2 MEDIUM VOLTAGE HALOGEN-FREE FLAME RETARDANT POWER CABLES 10 - 35 kV

5.2.1 MV halogen-free power cables with improved performance in the case of fire, 10 - 35 kV

Number of cores Size Note

Nominal voltage 10 kV

- single-core 25 - 500 mm2

- three-core 25 - 300 mm2

Nominal voltage 20 kV

- single-core 35 - 500 mm2

- three-core 35 - 300 mm2

Nominal voltage 35 kV

- single-core 50 - 500 mm2

- three-core 50 - 300 mm2

TRADE MARK FKS-PLAMEX S

TYPE STANDARD

N2XSH

N2XSEH

HD 622 S1;

DIN VDE 0267

CONSTRUCTION :

Conductor : stranded, soft annealed copper

Core : XLPE insulated conductor, with semi-conducting layers under and over the insulation

Metallic screen: copper tape, or copper wire screen with copper contact tape

Cable core : Laid-up cores. Interstices filled with suitable halogen-free material.

Separator : Glass tape (optional)

Oversheath : Black extruded halogen-free flame retardant compound.

Improved performance in the case of fire: Reduced flame propagation: IEC 332-3C; VDE 0472-804C No corrosive combustion gases: IEC 754-2; VDE 0472-813

Low smoke density: IEC 1034; VDE 0472-816

Application : For power supplies in fossil fuel power plants and also for indoor installations in places with increased safety requirements.

6. PAPER INSULATED METAL SHEATHED POWER CABLES

6.1 LEAD SHEATHED POWER CABLES 1 kV 6.2 LEAD SHEATHED POWER CABLES 6 kV

6.3 LEAD SHEATHED POWER CABLES 10 kV

6.4 LEAD SHEATHED POWER CABLES 20 kV

6.5 LEAD SHEATHED POWER CABLES 35 kV

6.6 ALUMINIUM SHEATHED POWER CABLES 1,10,20 AND 35 kV

6.1 LEAD SHEATHED POWER CABLES FOR 1 kV 6.1.1 Paper insulated lead sheathed power cable steel tape armoured and anti-

corrosive protection ,1 kV

TYPE SPECIFICATION

PILC/DSTA/S

PILC/DSTA/S M.I.N.D BS 6480

PILC/DSTA/S

PILC/DSTA/S M.I.N.D IEC 55-2

IPO 13 , IPO 13-A

NPO 13 , NPO 13-A JUS N.C5.020

NKBA, NAKBA VDE 0255

SBU, ASBU GOST 18410-73

CONSTRUCTION:

Conductor : Wire or stranded cooper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated paper or impregnated jute with bitumen compound covers.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute with bitumen compound covers.

Application : For direct laying in ground in urban and industrial networks. Cable type NPO 13 is applied for vertical or inclined installations.

Nominal voltage 1 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

- four-core 3+1 16 - 400 mm2 circular, shaped

- four-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 25 mm²

6.1.2 Paper insulated lead sheathed power cable steel tape armoured and outer

PVC sheath,1 kV

TYPE SPECIFICATION

PILC / DSTA / PVC

PILC/ DSTA / PVC M.I.N.D BS 6480

PILC / DSTA / PVC

PILC / DSTA / PVC M.I.N.D IEC 55-2

IPO 14 , IPO 14-A

NPO 14, NPO 14-A JUS N.C5.020

NKBY , NAKBY VDE 0255

SBŠvU, ASBŠvU GOST 18410-73

CONSTRUCTION:

Conductor : Wire or stranded cooper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated paper or impregnated jute with bitumen compound covers.

Mechanical protection: Two steel tapes.

Outer protection: PVC sheath

Application : In urban and industrial networks for direct laying in ground at places where greater corrosion influence may be experienced (aggressive and wet soil and electric pulling effects). NPO 14 type is applied for vertical and inclined installations.

Nominal voltage 1 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

- four core 3+1 16 - 400 mm2 circular, shaped

- four-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 25 mm².

6.1.3 Paper insulated lead sheathed power cable armoured with round steel wire

and anti-corrosive protection, 1 kV

TYPE SPECIFICATION

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D BS 6480

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D

IEC 55-2

IPO 23, IPO 23-A

NPO 23 , NPO 23-A

JUS N.C5.020

NKRA , NAKRA VDE 0255

SKlU, ASKlU GOST 18410-73

CONSTRUCTION:

Conductor : Wire or stranded cooper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated jute. Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In urban and industrial networks for direct laying in ground at places where greater mechanical strains may be experienced. NPO 23 type is applied for vertical or inclined installations.

Nominal voltage 1 kV

Number of core Cross-section

- three-core 16 - 400 mm2

- four core(3+1) 16 - 400 mm2

- four-core 16 - 400 mm2

6.1.4 Paper insulated lead sheathed power cable armoured with round steel

galvanised wire and counter - spiral of steel galvanised tape and outer PVC sheath, 1 kV

TYPE SPECIFICATION

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D BS 6480

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D IEC 55-2

NPO 25 , NPO 25-A

IPO 25, IPO 25-A JUS N.C5.020

NKRGbY , NAKRGbY VDE 0255

CONSTRUCTION:

Conductor : Wire or stranded cooper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated jute.

Mechanical protection: Round steel galvanised wire and counter-spiral of steel galvanised tape.

Outer protection: PVC sheath.

Application : In mine and industrial plants at places where greater corrosion influence and mechanical damages may be experienced. NPO 25 type is applied for vertical or inclined installations .

Nominal voltage 1 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

- four core(3+1) 16 - 400 mm2

- four-core 16 - 400 mm2

6.2 LEAD SHEATHED POWER CABLES FOR RATED VOLTAGE 6 kV 6.2.1 Paper insulated lead and PVC sheathed power cable, 6 kV

TYPE SPECIFICATION

PILC/PVC ,

PILC/PVC M.I.N.D BS 6480

PILC/PVC ,

PILC/PVC M.I.N.D IEC 6055-2

NPO 04, NPO 04-A

IPO 04 ,IPO 04- A JUS N.C5.020

NKY, NAKY VDE 0255

SŠvU, ASŠvU

CSŠvU, CASŠvU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes

Cable core :Cores laid-up and wound with paper tape layer impregnated with normal and semi-hard compound.

Sheath : Seamless tube of lead and lead alloy.

Outer protection: PVC sheath

Application : In industrial plants. This type is not buried directly in ground. NPO 04 type is applied for inclined and vertical installations.

Nominal voltage 6 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.2.2 Paper insulated lead sheathed power cable armoured with round steel wire and anti-corrosive protection, 6 kV

TYPE SPECIFICATION

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D BS 6480

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D IEC 55-2

IPO 23, IPO 23-A

NPO 23 , NPO 23-A JUS N.C5.020

NKRA , NAKRA VDE 0255

SKlU, ASKlU

CSKlU,CASKlU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi hard compound.

Sheath : Seamless tube of lead and lead alloy.

Inner protection: Impregnated jute.

Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial and mine plants, at places where greater mechanical strains may be experienced. It is buried directly into ground. NPO 23 type is applied for inclined and vertical installations.

Nominal voltage 6 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.2.3 Paper insulated lead sheathed power cable armoured with round steel galvanised wire and counter - spiral of steel galvanised tape and outer PVC sheath, 6 kV

TYPE SPECIFICATION

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D BS 6480

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D IEC 55-2

NPO 25 , NPO 25-A

IPO 25, IPO 25-A JUS N.C5.020

NKRGbY , NAKRGbY, VDE 0255

CONSTRUCTION:

Conductor : Wire or stranded cooper or aluminium conductor.

Core : Conductor insulated with paper tapes.

Cable core : Cores laid-up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated jute.

Mechanical protection: Round steel galvanised wire and counter-spiral of steel galvanised tape.

Outer protection: PVC sheath.

Application : In industrial and mine plants, at places where greater effects of corrosion and mechanical strains have been experienced. NPO 25 type is applied for inclined or vertical installations.

Nominal voltage 6 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.3 LEAD SHEATHED POWER CABLES 10 kV 6.3.1 Paper insulated lead and PVC sheathed power cable, 10 kV

TYPE SPECIFICATIOND

PILC/PVC ,

PILC/PVC M.I.N.D BS 6480

PILC/PVC ,

PILC/PVC M.I.N.D IEC 6055-2

NPO 04, NPO 04-A

IPO 04 ,IPO 04- A JUS N.C5.020

NKY, NAKY VDE 0255

SŠvU, ASŠvU

CSŠvU, CASŠvU

GOST 18410-73

GOST 18409-73

CONSTRUCTION:

Conductor : Wire or stranded copper or aluminium conductor.

Core: Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi hard compound.

Sheath : Seamless lead or lead alloy tube.

Outer sheath: PVC sheath.

Application : In industrial plants and thermo and hydroelectric plants. It is laid in dry and wet rooms. It is not buried directly into ground. NPO 04 type is applied for inclined installations.

Nominal voltage 10 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.3.2 Paper insulated lead sheathed power cable steel tape armoured and bitumen-

enamel cover, 10 kV

TYPE SPECIFICATION

PILC/DSTA

PILC/DSTA M.I.N.D BS 6480

PILC/DSTA

PILC/DSTA M.I.N.D IEC 6055-2

IPO 11 , IPO 11-A

NPO 11 , NPO 11-A JUS N.C5.020

NKB, NAKB VDE 0255

CONSTRUCTION:

Conductor : Wire or stranded copper or aluminium conductor.

Core: Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated paper or jute with bitumen compound covers.

Mechanical protection: Two steel tapes

Outer protection: Bitumen-enamel cover.

Application : In industrial plants and sub-stations. It is not buried directly into ground. NPO 11 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 35 mm²

6.3.3 Paper insulated lead sheathed power cable steel tape armoured and anti-

corrosive protection, 10 kV

TYPE SPECIFICATION

PILC/DSTA /S

PILC/DSTA/S M.I.N.D BS 6480

PILC/DSTA/S

PILC/DSTA/S M.I.N.D IEC 6055-2

IPO 13 , IPO 13-A

NPO 13 , NPO 13-A JUS N.C5. 020

NKBA, NAKBA VDE 0255

SBU, ASBU

CSBU,CASBU

GOST 18410-73

GOST 18409-73

CONSTRUCTION:

Conductor : Wire or stranded copper or aluminium conductor.

Core: Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated paper or jute with bitumen compound covers.

Mechanical protection: Two steel tapes

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial networks for direct burial into ground. NPO 13 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 35 mm²

6.3.4 Paper insulated lead sheathed power cable with inner PVC sheath steel tape

armoured and anti-corrosive protection.10 kV

TYPE SPECIFICATION

PILC/PVC/DSTA /S

PILC/PVC/DSTA/S M.I.N.D BS 6480

PILC/PVC/DSTA/S

PILC/PVC/DSTA/S M.I.N.D IEC 55-2

IPOP 13 , IPOP 13-A

NPOP 13 , NPOP 13-A JUS N.C5.020

NKYBA, NAKYBA VDE 0255

CONSTRUCTION:

Conductor : Wire or stranded copper or aluminium conductor.

Core: Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube

Inner protection: Bitumen cover and PVC sheath.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute layer with bitumen compound interlayers.

Application : In urban networks and industrial plants, at places where greater corrosion,electric pulling and mechanical damages may be experienced. It is buried directly into ground and water. NPOP type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 35 mm²

6.3.5 Paper insulated lead sheathed power cable, steel tape armoured and outer

PVC sheath, 10 kV

TYPE SPECIFICATION

PILC /DSTA / PVC

PILC/ DSTA / PVC M.I.N.D BS 6480

PILC / DSTA / PVC

PILC / DSTA / PVC M.I.N.D IEC 55-2

IPO 14 , IPO 14-A

NPO 14, NPO 14-A JUS N.C5.020

NKBY , NAKBY VDE 0255

SBŠvU, ASBŠvU

CSBŠvU,CASBŠvU

GOST18410-73

GOST 18409-73

CONCTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core : Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated paper or jute with bitumen compound covers.

Mechanical protection: Two steel tapes

Outer protection: PVC sheath.

Application : In urban networks and industrial plants, at places where greater corrosion and mechanical damages may be experienced. It is buried directly into ground. NPO 14 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 35 mm²

6.3.6 Paper insulated lead sheathed power cable armoured with round steel wire

and anti-corrosive protection, 10 kV

TYPE SPECIFICATION

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D BS 6480

PILC/ SWA /S ,

PILC / SWA / S M.I.N.D IEC 55-2

IPO 23, IPO 23-A

NPO 23 , NPO 23-A JUS N.C5.020

NKRA , NAKRA VDE 0255

SKlU, ASKlU

CSKlU,CASKlU

GOST 18410-73

GOST 18409-73

CONCTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core : Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated jute.

Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial and mine plants, at places, where greater mechanical strains are experienced. It is applied for direct burial into ground, as well as for sub-water installations(sea, river).NPO 23 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.3.7 Paper insulated lead sheathed power cable armoured with round steel wire and outer PVC sheath, 10 kV

TYPE SPECIFICATION

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D BS 6480

PILC / SWA / PVC ,

PILC / SWA / PVC M.I.N.D IEC 55-2

NPO 25 , NPO 25-A

IPO 25, IPO 25-A JUS N.C5.020

NKRGbY , NAKRGbY, VDE 0255

CONCTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core : Paper tape insulated conductor.

Cable core :Cores laid up and wound with paper tape layer and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection: Impregnated jute.

Mechanical protection: Round steel galvanised wire and counter-spiral of steel galvanised tape.

Outer protection: PVC sheath.

Application : in industrial or mine plants, at places where greater influence of corrosion and mechanical strains may be experienced. It is applied for direct burial into ground , as well as for sub-water installations(sea, rivers).NPO 25 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.4 LEAD SHEATHED POWER CABLES 20 kV 1.4.1 Paper insulated lead and PVC sheathed screened power cable, 20 kV

TYPE SPECIFICATION

PILC/PVC screened,

PILC/PVC M.I.N.D screened BS 6480

PILC/PVC screened ,

PILC/PVC M.I.N.D screened IEC 6055-2

NPHO 04, NPHO 04-A

IPHO 04 ,IPHO 04- A JUS N.C5.020

NHKY, NAHKY VDE 0255

CONSTRUCTION:

Conductor : Stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes and screened .

Cable core :Cores laid-up and wound with cotton tapes reinforced with copper threads and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Outer protection: PVC sheath.

Application : In industrial plants and thermo and hydropower stations. It is laid in dry and wet rooms. It is not buried directly into ground. NPHO 04 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section

-single-core 25-400 mm2

- three-core 25 - 400 mm2

6.4.2 Paper insulated lead sheathed screened power cable, steel tape armoured and anti-corrosive protection, 20 kV

TYPE SPECIFICATION

PILC/DSTA /S screened PILC/DSTA/S M.I.N.D

screened BS 6480

PILC/DSTA/S screened PILC/DSTA/S M.I.N.D

screened IEC 55-2

IPHO 13 , IPHO 13-A NPHO 13 , NPHO 13-A

JUS N.C5.020

NHKBA, NAHKBA VDE 0255

CONSTRUCTION: Conductor: Stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes and screened.

Cable core : Cores laid-up and wound with cotton tapes reinforced with copper threads and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube. Inner protection : Impregnated paper or impregnated jute with bitumen compound covers. Mechanical protection : Two steel tapes. Outer protection : Impregnated jute with bitumen compounds covers.

Application : In urban and industrial networks for direct burial into ground. NPHO 13 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section Note **

- three-core 25 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 70 mm²

6.4.3 Paper insulated lead sheathed screened cable, steel tape armoured and outer PVC sheath, 20 kV

TYPE SPECIFICATION

PILC / DSTA / PVC screened

PILC/ DSTA / PVC screened M.I.N.D

BS 6480

PILC / DSTA / PVC screened

PILC / DSTA / PVC screened M.I.N.D

IEC 55-2

IPHO 14 , IPHO 14-A

NPHO 14, NPHO 14-A JUS N.C5.020

NHKBY , NAHKBY VDE 0255

CONSTRUCTION:

Conductor: Stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes and screened.

Cable core : Cores laid-up and wound with cotton tapes reinforced with copper threads and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection : Impregnated paper or impregnated jute with bitumen compound covers.

Mechanical protection : Two steel tapes.

Outer protection: PVC sheath

Application : In urban networks, industrial plants, thermo and hydropower plants, at places where greater influence or corrosion and mechanical damages my be experienced. It is buried directly into ground. NPHO 14 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section Note **

- three-core 25 - 400 mm2 circular, shaped

** Shaped conductors are cross-section greater or 70 mm²

6.4.4 Paper insulated lead sheathed screened cable armoured with round steel wire and anti-corrosive protection, 20 kV

TYPE SPECIFICATION

PILC/ SWA /S screened,

PILC / SWA / S M.I.N.D screened

BS 6480

PILC/ SWA /S screened

PILC / SWA / S M.I.N.D screened

IEC 55-2

IPHO 23, IPHO 23-A

NPHO 23 , NPHO 23-A JUS N.C5.020

NHKRA , NAHKRA VDE 0255

CONSTRUCTION:

Conductor: Stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes and screened.

Cable core : Cores laid-up and wound with cotton tapes reinforced with copper threads and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection : Impregnated jute

Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial and mine plants, at places where greater mechanical strains may be experienced. It is applied for direct burial into ground , as well as for sub-water installations(sea, rivers).NPHO 23 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section

- three-core 25 - 400 mm2

6.4.5 Paper insulated lead sheathed screened power cable armoured with steel wire and outer PVC sheath, 20 kV

TYPE SPECIFICATION

PILC / SWA / PVC screened,

PILC / SWA / PVC screened M.I.N.D

BS 6480

PILC / SWA / PVC screened

PILC / SWA / PVC screened M.I.N.D

IEC 55-2

NPHO 25 , NPHO 25-A

IPHO 25, IPHO 25-A JUS N.C5.020

NHKRGbY , NAHKRGbY, VDE 0255

CONSTRUCTION:

Conductor: Stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes and screened.

Cable core : Cores laid-up and wound with cotton tapes reinforced with copper threads and all impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube.

Inner protection : Impregnated jute .

Mechanical protection: Round steel galvanised wire and counter spiral of steel galvanised tape.

Outer protection : PVC sheath.

Application : In industrial and mine plants, at places where greater influence of corrosion and mechanical strains may be experienced. It is applied for direct burial into ground, as well as for sub-water installations ( sea, rivers). NPHO 25 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section

- three-core 25 - 400 mm2

6.4.6 Paper insulated separate lead sheathed power cable ,steel tape armoured and anti-corrosive protection, 20 kV

TYPE SPECIFICATION

PILC/DSTA /S (S.L)

PILC/DSTA/S (S.L) M.I.N.D BS 6480

PILC/DSTA/S (S.L)

PILC/DSTA/S (S.L) M.I.N.D IEC 55-2

IPZO 13 , IPZO 13-A

NPZO 13 , NPZO 13-A JUS N.C5.020

NEKBA, NAEKBA

NEKEBA, NAEKEBA VDE 0255

OSBU, AOSBU GOST 18410-73

CONSTRUCTION :

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath is protected with two impregnated paper tape or thermo- plastic tape and impregnated paper tape or impregnated paper tape and fibrous material with bitumen compound covers.

Cable core : Separate lead and protected cores laid-up and interestice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In urban and industrial networks for direct burial into ground .NPZO 13 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section Note

- three-core 25 - 400 mm2 circular

6.4.7 Paper insulated separate lead and PVC sheathed power cable, steel tape armoured and anti-corrosive protection , 20 kV

TYPE SPECIFICATION

PILC/PVC/DSTA /S (S.L)

PILC/PVC/DSTA/S (S.L) M.I.N.D

BS 6480

PILC/PVC/DSTA/S (S.L)

PILC/PVC/DSTA/S (S.L) M.I.N.D

IEC 55-2

IPZOP 13 , IPZOP 13-A

NPZOP 13 , NPZOP 13-A JUS N.C5.020

NEKYBA, NAEKYBA VDE 0255

CONSTRUCTION:

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath protected with bitumen compound and PVC sheath.

Cable core : Separate lead and protected cores laid-up, interstice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound covers.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute with compound covers.

Application : In urban and industrial networks for direct burial into ground, at places where greater corrosion of lead sheath-is experienced (aggressive ambient, one side pulling force, etc.) NPZOP 13 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section Note

- three-core 25 - 400 mm2 circular

6.4.8 Paper insulated separate lead sheathed power cable armoured with steel galvanised wire and anti-corrosive protection, 20 kV

TYPE SPECIFICATION

PILC/SWA /S (S.L)

PILC/SWA/S (S.L) M.I.N.D BS 6480

PILC/SWA/S (S.L)

PILC/SWA/S (S.L) M.I.N.D IEC 55-2

IPZO 23 , IPZO 23-A

NPZO 23 , NPZO 23-A JUS N.C5.020

NEKERA, NAEKERA

NEKRA, NAEKRA VDE 0255

OSKU, AOSKU GOST 18410-73

CONSTRUCTION:

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath is protected with two impregnated paper tape or thermo- plastic tape and impregnated paper tape or impregnated paper tape and fibrous material with bitumen compound covers.

Cable core : Separate lead and protected cores laid-up, interstice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound covers.

Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial and mine plants, at places where greater mechanical strains may be experienced. It is applied for direct burial into ground, as well as sub-water installations(sea, rivers).NPZO 23 type is applied for inclined or vertical installations.

Nominal voltage 20 kV

Number of cores Cross-section Note

- three-core 25 - 400 mm2 circular

6.5 LEAD SHEATHED POWER CABLES 35kV 6.5.1 Paper insulated lead and PVC sheathed screened power cable, 35 kV

TYPE SPECIFICATION

PILC/PVC screened,

PILC/PVC M.I.N.D screened BS 6480

PILC/PVC screened ,

PILC/PVC M.I.N.D screened IEC 55-2

NPHO 04, NPHO 04-A

IPHO 04 ,IPHO 04- A JUS N.C5.020

NHKY, NAHKY VDE 0255

CONSTRUCTION:

Conductor : Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard-compound.

Sheath : Seamless lead alloy tube.

Outer protection: PVC sheath.

Application : In industrial plants, thermo- and hydroelectric power plants. It is not buried directly into ground. NPHO 04 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section

-single-core 25-400 mm2

6.5.2 Paper insulated power cable with separate lead sheath, steel tape armoured

and anti corrosive protection, 35 kV

TYPE SPECIFICATION

PILC/DSTA /S (S.L)

PILC/DSTA/S (S.L) M.I.N.D BS 6480

PILC/DSTA/S (S.L)

PILC/DSTA/S (S.L) M.I.N.D IEC 55-2

IPZO 13 , IPZO 13-A

NPZO 13 , NPZO 13-A JUS N.C5.020

NEKBA, NAEKBA

NEKEBA, NAEKEBA VDE 0255

OSBU, AOSBU

COSBU, CAOSBU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath is protected with two impregnated paper tape or thermo- plastic tape and impregnated paper tape or impregnated paper tape and fibrous material with bitumen compound covers.

Cable core : Separate lead and protected cores laid-up and interestice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In urban and industrial networks for direct burial into ground. NPZO 13 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section

-three-core 25-400 mm2

6.5.3 Paper insulated power cable with separate lead and PVC sheaths, steel tape armoured and anti-corrosive protection, 35 kV

TYPE SPECIFICATION

PILC/PVC/DSTA /S (S.L)

PILC/PVC/DSTA/S (S.L) M.I.N.D

BS 6480

PILC/PVC/DSTA/S (S.L)

PILC/PVC/DSTA/S (S.L) M.I.N.D

IEC 55-2

IPZOP 13 , IPZOP 13-A

NPZOP 13 , NPZOP 13-A JUS N.C5.020

NEKYBA, NAEKYBA VDE 0255

CONSTRUCTION:

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath protected with bitumen compound and PVC sheath.

Cable core : Separate lead sheathed and protected cores laid-up, interstice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound covers.

Mechanical protection: Two steel tapes.

Outer protection: Impregnated jute with compound covers.

Application : In urban and industrial networks for direct burial in into ground, at places where greater corrosion of lead sheath may be experienced( aggressive soil, one-side pulling, etc.).NPZOP 13 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section

-three-core 25-400 mm2

6.5.4 Paper insulated power cable with separate lead sheaths armoured with galvanised steel wire and anti-corrosive protection, 35 kV

TYPE SPECIFICATION

PILC/SWA /S (S.L)

PILC/SWA/S (S.L) M.I.N.D BS 6480

PILC/SWA/S (S.L)

PILC/SWA/S (S.L) M.I.N.D IEC 55-2

IPZO 23 , IPZO 23-A

NPZO 23 , NPZO 23-A JUS N.C5.020

NEKERA, NAEKERA

NEKRA, NAEKRA VDE 0255

OSKU, AOSKU GOST 18410-73

CONSTRUCTION:

Conductor: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead or lead alloy tube separately for each core. Sheath is protected with two impregnated paper tape or thermo- plastic tape and impregnated paper tape or impregnated paper tape and fibrous material with bitumen compound covers.

Cable core : Separate lead and protected cores laid-up, interstice filled up with impregnated jute.

Inner protection: Impregnated jute with bitumen compound covers.

Mechanical protection: Round steel galvanised wire.

Outer protection: Impregnated jute with bitumen compound covers.

Application : In industrial and mine plants, at places where greater mechanical strains may be experienced. It is applied for direct burial into ground, as well as for sub-water laying( sea, rivers).NPZO 23 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section Note

- three-core 25 - 400 mm2 circular

6.5.5 Single-core paper insulated lead sheathed power cables armoured with special aluminium wire and outer PVC sheath, 35 kV

TYPE SPECIFICATION

PILC/AWA /PVC

PILC/AWA/PVC M.I.N.D BS 6480

PILC/AWA /PVC

PILC/AWA/PVC M.I.N.D IEC 55-2

IPHO 37 , IPHO 37-A

NPHO 37 , NPHO 37-A JUS N.C5.020

CONSTRUCTION:

Construction: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead alloy tube.

Inner protection: Thermoplastic tapes and impregnated jute with bitumen compound covers.

Mechanical protection: Aluminium alloy wire and counter-spiral of aluminium tape.

Outer protection: PVC sheath.

Application : For sub-water laying(sea,rivers). NPHO 37 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section Note

- single-core 25 - 400 mm2 circular

6.5.6 Paper insulated lead sheathed screened power cable armoured with special aluminium wire and anti-corrosive protection, 35 kV

TYPE SPECIFICATION

PILC/AWA /S

PILC/AWA/S M.I.N.D BS 6480

PILC/AWA /S

PILC/AWA/S M.I.N.D IEC 55-2

IPHO 36 , IPHO 36-A

NPHO 36 , NPHO 36-A

JUS N.C5.020

CONSTRUCTION:

Construction: Solid stranded copper or aluminium conductor.

Core : Conductor insulated with paper tapes, screened and impregnated with normal or semi-hard compound.

Sheath : Seamless lead alloy tube.

Inner protection: Thermoplastic tapes and impregnated jute with bitumen compound covers.

Mechanical protection: Aluminium alloy wire .

Outer protection: Two layers of impregnated jute with bitumen covers.

Application : For sub-water laying(sea, rivers). NPHO 36 type is applied for inclined or vertical installations.

Nominal voltage 35 kV

Number of cores Cross-section Note

- single-core 25 - 400 mm2 circular

6.6 ALUMINIUM SHEATHED POWER CABLES FOR 1,10,20 AND 35 kV 6.6.1 Paper insulated aluminium and PVC sheathed power cable, 1 kV

TYPE SPECIFICATION

NPA 04, NPA 04-A

IPA 04 ,IPA 04- A JUS N.C5.020

NPA 04, NPA 04-A

IPA 04 ,IPA 04- A IEC 55-2

NKLY, NAKLY VDE 0255

AŠvU, AAŠvU GOST 18410-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes.

Cable core :Cores laid-up and wound with a layer of paper tapes and all impregnated with normal or semi-hard compound.

Sheath : Seamless aluminium tube.

Outer protection : Bitumen compound covers and PVC sheath.

Application : In urban and industrial networks for direct burial into ground, cable trenches, at places where greater influence of vibrations may be expected. NPA 04 type is applied for inclined and vertical installations.

Nominal voltage 1 kV

Number of cores Cross-section

- three-core* 16 - 400 mm2

- four core cable(3+1) 16 - 400 mm2

*Aluminium sheath serves as the fourth core.

6.6.2 Paper insulated aluminium sheathed power cable, inner PVC sheath, steel, tape armoured and anti-corrosive protection, 1 kV

TYPE SPECIFICATION

IPAP 13 , IPAP 13-A

NPAP 13 , NPAP 13-A JUS N.C5.020

IPAP 13 , IPAP 13-A

NPAP 13 , NPAP 13-A IEC 55-2

NKLBA, NAKLBA VDE 0255

AABlU, AAB2lU GOST 18410-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes.

Cable core :Cores laid-up and wound with a layer of paper tapes and all impregnated with normal or semi-hard compound.

Sheath : Seamless aluminium tube.

Inner protection: Bitumen covers and PVC sheath.

Mechanical protection: Two steel tapes

Outer protection: Impregnated jute layers with interlayer of bitumen compound.

Application : In urban and industrial networks for direct burial into ground, at places where greater influence of corrosion, mechanical damages and vibration may be experienced. NPAP 13 type is applied for inclined or vertical installations.

Nominal voltage 1 kV

Number of cores Cross section Note **

- three-core 16 - 400 mm2 circular, shaped

*Aluminium sheath serves as the fourth core. ** Shaped conductors are cross-section greater or 25 mm²

6.6.3 Paper insulated aluminium and PVC sheathed power cable, 10 kV

TYPE SPECIFICATION

NPA 04, NPA 04-A

IPA 04 ,IPA 04- A JUS N.C5.020

NPA 04, NPA 04-A

IPA 04 ,IPA 04- A IEC 55-2

NKLY, NAKLY VDE 0255

AŠvU, AAŠvU

CSŠvU,CAAŠvU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes.

Cable core :Cores laid-up and wound with a layer of paper tapes and all impregnated with normal or semi-hard compound.

Sheath : Seamless aluminium tube.

Outer protection : Bitumen compound covers and PVC sheath.

Application : In urban networks, industrial plants, thermo-and hydroelectric plants, at places, where greater vibration effects may be expected ( bridges, etc.).It is buried directly into ground.

NPA 04 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section

- three-core 16 - 400 mm2

6.6.4 Paper insulated aluminium sheathed power cable with inner PVC sheath, steel tape armoured and anti-corrosive protection, 10 kV

TYPE SPECIFICATION

IPAP 13 , IPAP 13-A

NPAP 13 , NPAP 13-A JUS N.C5.020

IPAP 13 , IPAP 13-A

NPAP 13 , NPAP 13-A IEC 55-2

NKLBA, NAKLBA VDE 0255

AABlU, AAB2lU

CAABlU,CAAB2lU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes.

Cable core :Cores laid-up and wound with a layer of paper tapes and all impregnated with normal or semi-hard compound.

Sheath : Seamless aluminium tube.

Inner protection: Bitumen covers and PVC sheath.

Mechanical protection: Two steel tapes

Outer protection: Impregnated jute layers with interlayer of bitumen compound.

Application : In urban and industrial networks for direct burial into ground, at places where greater effects of corrosion, mechanical damages and vibration may be expected. NPAP 13 type is applied for inclined or vertical installations.

Nominal voltage 10 kV

Number of cores Cross-section Note **

- three-core 16 - 400 mm2 Circular, shaped

** Shaped conductors are cross-section greater or 35 mm²

6.6.5 Single core paper insulated power cable with aluminium and PVC sheath, 20 and 35 kV

TYPE SPECIFICATION

NPHA 04, NPHA 04-A

IPHA 04 ,IPHA 04- A JUS N.C5.020

NPHA 04, NPHA 04-A

IPHA 04 ,IPHA 04- A IEC 55-2

NHKY, NAHKY VDE 0255

AAŠvU

CAAŠvU

GOST 18410-73

GOST 18409-73

CONSTRUCTION :

Conductor : Wire or stranded copper or aluminium conductor.

Core: Conductor insulated with paper tapes, screened and impregnated with normal or semi- hard compound

Sheath : Seamless aluminium tube.

Outer protection : Bitumen compound covers and PVC sheath.

Application : In urban networks, industrial plants, thermo- and hydro power stations, at places where greater influence of vibrations may be experienced(bridges, etc.).It is laid directly into ground. NPHA 04 type is applied for inclined or vertical installations.

Nominal voltage 20 and 35kV

Number of cores Cross-section

-single-core 25-400 mm2

HOLDING

INDUSTRIJA KABLOVA a.d. JAGODINA - SERBIA

General manager:

phone: +381 35 / 221 102, 221 814 fax: +381 35 / 229 498

Marketing: phone: +381 35 / 221 002, 229 500

fax: +381 35 / 223 779

Internet: http://www.fks.co.yu

E-mail: [email protected]

[email protected] [email protected]

manufacturing program

products of steel, copper and aluminium - rolled steel and copper wire, - copper and aluminium conductors, cross- section up to 1000 mm

2,

- aluminium steel reinforced conductors, cross-section up to 1000 mm

2.

power cables - with impregnated paper insulation, nominal voltage up to 35 kV,

- with polyvinyl chloride PVC insulation, nominal voltage up to 11kV,

- with cross linked polyethylene insulation, nominal voltage up to 220 kV,

- with natural or synthetic rubber insulation, nominal voltage up to 35 kV.

insulated conductors and power cords

telecommunication cables - telephone cables with paper or thermoplastic insulation (filled and jelly filled),

- coaxial telephone cables, - cables for digital transmission (PCM signal) - combined signal-telecommunication cables for railway, - signal cables and cables for measuring-setting technique,

- RF, RG and CATV coaxial cables, , - optical cables.

microcables and conductors

cable accessories - cable joints and terminations for power cables with paper, PVC and cross linked polyethylene insulation,

- cable accessories for jointing and terminating on telecommunication cables with paper, thermoplastic insulation, coaxial and optical cables,

- heatshrinkable cable accessories for power and telecommunication cables,

- heatshrinkable foils, ducts and other products, - premoulded cable accessories for 10, 20 and 35 kV.

enamelled wire

connectors and terminals

electric cord sets and cable harnesses

integral parts from electro-insulating materials

industrial electronics

heating cables and heating systems

engineering

equipment