2
APGI, YADKIN DIV. PORTABLE HAND TOOLS INSPECTION PROCEDURES {Portable Hand Tools SHALL be tested Quarterly at a Minimum} ELECTRICAL TOOL TESTING VISUAL: A visual inspection of each tool’s enclosure & cord SHALL be performed. If damages are found that can be safely repaired, they are performed. If it is determined that the damages are irreparable, the tool is destroyed. GROUND CONTINUITY: Upon passage of the visual inspection, the tool SHALL be tested using a Fluke multi-meter to perform a ground conductor continuity test between the plug & the tool case. [Does NOT include “double insulated” tools.] Any tool failing this test is reviewed to determine if it is repairable, if not it is destroyed. POWER CONTINUITY: A Fluke multi-meter SHALL be utilized to perform a continuity test on the power conductors. The tool’s switch SHALL make and break continuity of the power wires. Any tool failing this test is reviewed to determine if is repairable, if not it is destroyed. POWER-TO-GROUND ISOLATION: A) 3-Wire plug: (Preferred Testing Method) A GFCI Receptacle SHALL be used to check power to ground isolation. Plug the tool into a “tested” GFCI receptacle. Operate the tool. If the tool DOES NOT trip the GFCI, the tool is “OK” to be used. {(Alternate Testing Method) A Fluke multi-meter SHALL be utilized to perform a power-to-ground isolation test. Insulation of a minimum of 2 Mega-Ohms between ground and both power wires (hot & neutral) will be required to pass this test.} Any tool failing this test All electrical cords SHALL be inspected prior to use for physical damage. Original: 98/12/03 Revised: 01/10/30 Reviewed: 03/11/19

Portable Hand Tools Inspection Procedure

Embed Size (px)

DESCRIPTION

Portable Hand Tools Inspection Procedure

Citation preview

YADKIN, INC

APGI, YADKIN DIV.

PORTABLE HAND TOOLS INSPECTION PROCEDURES

{Portable Hand Tools SHALL be tested Quarterly at a Minimum}

ELECTRICAL TOOL TESTING

VISUAL: A visual inspection of each tools enclosure & cord SHALL be performed. If damages are found that can be safely repaired, they are performed. If it is determined that the damages are irreparable, the tool is destroyed.GROUND CONTINUITY: Upon passage of the visual inspection, the tool SHALL be tested using a Fluke multi-meter to perform a ground conductor continuity test between the plug & the tool case. [Does NOT include double insulated tools.] Any tool failing this test is reviewed to determine if it is repairable, if not it is destroyed.

POWER CONTINUITY: A Fluke multi-meter SHALL be utilized to perform a continuity test on the power conductors. The tools switch SHALL make and break continuity of the power wires. Any tool failing this test is reviewed to determine if is repairable, if not it is destroyed.

POWER-TO-GROUND ISOLATION:A) 3-Wire plug: (Preferred Testing Method) A GFCI Receptacle SHALL be used to check power to ground isolation. Plug the tool into a tested GFCI receptacle. Operate the tool. If the tool DOES NOT trip the GFCI, the tool is OK to be used. {(Alternate Testing Method) A Fluke multi-meter SHALL be utilized to perform a power-to-ground isolation test. Insulation of a minimum of 2 Mega-Ohms between ground and both power wires (hot & neutral) will be required to pass this test.} Any tool failing this test is reviewed to determine if is repairable, if not it is destroyed.

B) 2-Wire plug (Double Insulated): A Fluke multi-meter SHALL be utilized to perform a power-to-ground isolation test. Insulation of a minimum of 2 Mega-Ohms between both power wires (hot & neutral) and the tools exposed metal parts will be required to pass this test. Any tool failing this test is reviewed to determine if is repairable, if not it is destroyed.

TAGGING: Tools passing the above tests are tagged indicating the next required testing date of the tool and issued for use. If a tool has NO tag or the date on the tag has been surpassed, the tool SHALL not be used until it has been successfully re-tested & then re-tagged.

Examples (Non-Inclusive) Hand Drill, Hand Band Saw, Hand Grinder, Hand Held Conduit Threader, Floor Standing Conduit Threader. Generally, any hand held power tool that must be in human contact to be operated.

All electrical cords SHALL be inspected prior to use for physical damage.

Original: 98/12/03

Revised: 01/10/30

Reviewed: 03/11/19