SPECIFICATION SHEETS FOR: Pompano Pet Lodge 930 Northwest 31 st Avenue Pompano Beach, FL 33069 JOB#: 000000-0015 3375 COMMERCE PARKWAY PHONE: (954) 791-1313 MIRAMAR, FL 33025 FAX: (954) 791-0688 LICENSE: EF#20001380 DATE: 8/26/16

Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

SPECIFICATION SHEETS FOR:

Pompano Pet Lodge 930 Northwest 31st Avenue Pompano Beach, FL 33069

JOB#: 000000-0015

3375 COMMERCE PARKWAY PHONE: (954) 791-1313 MIRAMAR, FL 33025 FAX: (954) 791-0688

LICENSE: EF#20001380

DATE: 8/26/16

Page 2: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

FireWarden-100-2(E)Intelligent Addressable FACP with Built-In Communciator

Addressable

DN-7101:A • A1-110

7101

cov.

jpg

GeneralThe Notifier FireWarden-100-2 (NFW2-100) is a combinationFACP (Fire Alarm Control Panel) and DACT (Digital AlarmCommunicator/Transmitter) all on one circuit board. This com-pact intelligent addressable control panel has an extensive listof powerful features.

The SLC (Signaling Line Circuit) of the FireWarden-100-2operates using a Rapid Group Polling communication protocoltechnology that polls multiple devices simultaneously for aquicker device response time.This patented technology allowsa fully-loaded panel with up to 198 devices to report an inci-dent and activate the notification circuits in under 10 seconds.With this improved polling, devices can be wired on standardtwisted, unshielded wire up to a distance of 10,000 feet. (Con-sult the wire table on page 3 for specific installation instruc-tions.)

The FireWarden-100-2’s quick-remove chassis protects theelectronics during construction. The backbox can be installedallowing field wiring to be pulled. When construction is com-pleted, the electronics can be quickly installed with just twobolts.

Available accessories include LED, graphic and LCD annunci-ators, and reverse polarity/city box transmitter.

The panel is programmed through the FACP’s keypad or via astandard PS-2 computer keyboard, which can be pluggeddirectly into the printed circuit board. This permits easy typingof address labels and other programming information.

NOTE: Unless otherwise specified, the terms FireWarden-100-2 isused in this document to refer to both the FireWarden-100-2 andthe FireWarden-100-2E FACPs (Fire Alarm Control Panels).

Features• Listed to UL standard 864, 9th edition.• On-board DACT.• Four Style Y (Class B) or two Class A (Style Z) NAC cir-

cuits.

• Selectable strobe synchronization for System Sensor,Wheelock, and Gentex devices.

• Remote Acknowledge, Silence, Reset and Drill via address-able monitor modules.

• Up to 32 annunciators or remote annunciators via EIA-485.

• EIA-232 printer/PC interface (variable baud rate) on maincircuit board.

• Integral 80-character LCD display with backlighting.• Real-time clock/calendar with automatic daylight savings

control.• Detector sensitivity test capability (NFPA 72 compliant).• History file with 1,000-event capacity.

• Maintenance alert warns when smoke detector dust accu-mulation is excessive.

• Automatic device type-code verification.• One person audible or silent walk test with walk-test log and

printout.• Point trouble identification.• Waterflow (nonsilenceable) selection per monitor point.

• System alarm verification selection per detector point.• PAS (Positive Alarm Sequence) and presignal delay per

point (NFPA 72 compliant).NOTE: Only detectors may participate in PAS.

SLC LOOP:• SLC can be configured for NFPA Style 4, 6, or 7 operation.• SLC supports up to 198 addressable devices per loop (99

detectors and 99 monitor, control, or relay modules).• SLC loop maximum length 10,000 ft. (3,000 m.).

See wire table on page 3.

NOTIFICATION APPLIANCE CIRCUITS (NACS):• Four onboard NACs with additional NAC capability using

output control modules (NC-100).

• Silence Inhibit and Auto Silence timer options.• Continuous, March Time, Temporal or California code for

main circuit board NACs with two-stage capability.• Selectable strobe synchronization per NAC.• 2.5 amps maximum per each NAC circuit.NOTE: Maximum or total 24VDC system power shared betweenall NAC circuits and auxiliary power outputs is 3.6 amps. (Systempower increases to 6.6 amps with optional XRM-24 transformer.)

PROGRAMMING AND SOFTWARE:• Autoprogram (learn mode) reduces installation time.• Custom English labels (per point) may be manually entered

or selected from an internal library file.• Two programmable Form-C relay outputs.• 99 software zones.

• Continuous fire protection during online programming at thefront panel.

DN-7101:A • 09/21/07 — Page 1 of 4

Page 3: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

• Program Check automatically catches common errors notlinked to any zone or input point.

User interface

LED INDICATORS• AC POWER (green)• FIRE ALARM (red)

• SUPERVISORY (yellow)• ALARM SILENCED (yellow)• SYSTEM TROUBLE (yellow)

• MAINTENANCE/PRESIGNAL (yellow)• DISABLED (yellow)• BATTERY FAULT (yellow)

• GROUND FAULT (yellow)

KEYPAD CONTROLS• ACKNOWLEDGE/STEP• ALARM SILENCE• DRILL

• SYSTEM RESET (lamp test)• 16-key alpha-numeric pad (similar to telephone keypad)• 4 cursor keys

• ENTER

Ordering OptionsNFW2-100(E): 198-point addressable Fire Alarm ControlPanel, one SLC loop. Includes 80-character LCD display, sin-gle printed circuit board mounted on chassis, and cabinet.

NFW2-100R: Same as NFW2-100, exept in a red backbox.

4XTM Reverse Polarity Transmitter Module: Providessupervised output for local energy municipal box transmitter,alarm, and trouble.

DP-9692B: Optional dress panel for FireWarden-100-2.

TR-CE-B: Trim Ring for semi-flush mounting.

BB-26: Battery backbox, holds up to two 26 AH batteries andCHG-75.

NFS-LBB: Battery box, houses two 55 AH batteries.

CHG-75: Battery charger for lead-acid batteries with a ratingof 25 to 75 AH.

CHG-120: Remote battery charging system for lead-acid bat-teries with a rating of 55 to 120 AH. Requires additional NFS-LBB for mounting.

NOTE: CHG-120 or CHG-75 required for batteries larger than18AH.

BAT Series: Batteries, see data sheet DN-6933.

XRM-24(E): Optional transformer. Increases system power to6.6 amps. Use XRM-24E with FireWarden-100-2E.

PRT/PK-CABLE: Cable printer/personal computer interfacecable.

PRN-6: UL listed compatible event printer. Uses tractor-fedpaper.

COMPATIBLE ANNUNCIATORSACM-8R: Relay module provides 8 Form-C 5.0 amp relays.

ACM Annunciator Series: LED-type fire annunciators capa-ble of providing up to 99 software zones of annunciation. Avail-able in increments of 16 or 32 points to meet a variety ofapplications.

LDM Graphic Series: Lamp Driver Module series for usewith custom graphic annunciators.

FDU-80 (Liquid Crystal Display) point annunciator: 80-character, backlit LCD-type fire annunciators capable ofdisplaying English-language text.

NOTE: For more information on Compatible Annunciators for usewith the FireWarden-100-2, see the following data sheets (docu-ment numbers) ACM-8R (DN-3558), ACS/ACM Series (DN-0524),LDM Series (DN-0551), FDU-80 (DN-6820).

COMPATIBLE ADDRESSABLE DEVICESAll feature a polling LED and rotary switches for addressing.

NI-100: Addressable low-profile ionization smoke detector.

NP-100: Addressable low-profile photoelectric smoke detector.

NP-100T: Addressable low-profile photoelectric smoke detec-tor with thermal sensor.

NH-100: Fast-response, low-profile heat detector.

NH-100R: Fast-response, low-profile heat detector with rate-of-rise option.

ND-100: Photoelectric low-flow duct smoke detector.

ND-100R: Photoelectric low-flow duct smoke detector withrelay option.

NMM-100: Addressable Monitor Module for one zone of nor-mally-open dry-contact initiating devices. Mounts in standard4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B(Class B) or Style D (Class A) IDC.

NDM-100: Dual Monitor Module. Same as NMM-100 except itprovides two Style B (Class B) only IDCs.

NMM-100P: Miniature version of NMM-100. Excludes LEDand Style D option. Connects with wire pigtails. May mount indevice backbox.

NZM-100: Similar to NMM-100, but may monitor up to 20 con-ventional two-wire detectors. Requires resettable 24 VDCpower. Consult factory for compatible smoke detectors.

NC-100: Addressable Control Module for one Style Y/Z(Class B/A) zone of supervised polarized Notification Appli-ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.Notification Appliance Circuit option requires external 24 VDCto power notification appliances.

NC-100R: Addressable relay module containing two isolatedsets of Form-C contacts, which operate as a DPDT switch.Mounts directly to a 4.0" (10.16 cm.) box, surface mount usingthe SMB500.

NOT-BG12LX: Addressable manual pull station with interfacemodule mounted inside.

N100-ISO: Fault Isolator Module.

SMB500: Used to mount all modules except the NMM-100P.

NZM-100-6Six-zone interface module. Mount one or twomodules in a BB-2F cabinet (optional). Mount up to six mod-ules on a CHS-6 chassis in a BB-6F.

NOTE: For more information on Compatible Addressable Devicesfor use with the FireWarden-100-2, see the following data sheets(document numbers): N100-ISO (DN-6994), NP-100/NP-100T(DN-6995), NI-100 (DN-6996), NH-100/NH-100R (DN-6997), ND-100/ND-100R (DN-7006), NMM-100/NMM-100P/NDM-100/NZM-100 (DN-6999), NC-100/NC-100R (DN-7000), NOT-BG12LX (DN-7001), and NZM-100-6 (DN-60150).

Page 2 of 4 — DN-7101:A • 09/21/07

Page 4: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Wiring RequirementsWhile shielded wire is not required, it is recommended that allSLC wiring be twisted-pair to minimize the effects of electricalinterference. Wire size should be no smaller than 18 AWG(0.78 mm²) and no larger than 12 AWG (3.1 mm²). The wiresize depends on the length of the SLC circuit. Use the tablebelow to determine the specific wiring requirements for theSLC.

SLC Wire Requirements

Distance in Feet (m) Wire Size Wire Type

Twisted-pair, unshielded 10,000 feet (3,048 m) 12 AWG (3.31 mm2)

Non-Plenum (FPLR):Genesis 4315, Belden 5020UL

Plenum (FPLP):Genesis 4515, Belden 6020UL

Twisted-pair, unshielded 8,000 feet (2,438 m) 14 AWG (2.08 mm2)

Non-Plenum (FPLR):Genesis 4313, Belden 5120UL

Plenum (FPLP):Genesis 4513, Belden 6120UL

Twisted-pair, unshielded 4,875 feet (1,486 m) 16 AWG (1.31 mm2)

Non-Plenum (FPLR):Genesis 4311, Belden 5220UL

Plenum (FPLP):Genesis 4511, Belden 6220UL

Twisted-pair, unshielded 3,225 feet (983 m) 18 AWG (0.821 mm2)

Non-Plenum (FPLR):Genesis 4306, Belden 5320UL

Plenum (FPLP):Genesis 4506, Belden 6320UL

FireWarden-100-2 Wire Requirements

DN-7101:A • 09/21/07 — Page 3 of 4

Page 5: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

SYSTEM SPECIFICATIONS

Page 4 of 4 — DN-7101:A • 09/21/07

System Capacity• Intelligent Signalling Line Circuits....................................... 1 • Addressable device capacity .......................................... 198

• Programmable software zones ......................................... 99• Annunciators .................................................................... 32

Electrical SpecificationsAC Power: FireWarden-100-2: 120 VAC, 60 Hz, 3.0 amps.FireWarden-100-2(E): 240 VAC, 50 Hz, 1.5 amps. Wire size:minimum 14 AWG (2.00 mm²) with 600 V insulation.

Battery: Two 12 V 18AH lead-acid batteries. Battery chargercapacity: 7 – 18 AH. FireWarden-100-2 cabinet holds maxi-mum of two 18 AH batteries.

Communication Loop: Supervised and power-limited.

Notification Appliance Circuits: Each terminal block pro-vides connections for two Style Y (Class B) or one Style Z(Class A) for a total of four Style Y (Class B) or two Style Z(Class A) NACs. Maximum signaling current per circuit: 2.5amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252UL listed) for Style Y (Class B) NAC. Refer to panel documen-tation and Notifier Device Compatibility Document for listedcompatible devices.

Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30VAC (resistive). Form-C relays.

Special Application Power (24 VDC Nominal): Jumperselectable (JP4) for conversion to resettable power output. Upto 0.5 amps total DC current available from each output.Power-limited.

Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal): Up to 0.5 amps for powering four-wire smoke detectors. Power-limited. Refer to Notifier DeviceCompatibility Document for listed compatible devices.

Remote Sync Output: Remote power supply synchronizationoutput. Nominal special application power: 24 VDC. Maximumcurrent: 40 mA. End-of-Line Resistor: 4.7K ohm. Output linkedto NAC 1 control. Supervised and power-limited.

Telephone Interface: Requires dedicated business tele-phone number with a minimum of 7 volts DC. Obtain dedicatedphone line directly from your local phone company. Do not useshared phone lines or PBX (digital) type phone line extensions.

Cabinet SpecificationsDoor: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x

16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring(TR-CE-B): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping SpecificationsWeight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.)high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.

Temperature and Humidity RangesThis system meets NFPA requirements for operation at 0 –49°C/32 – 120°F and at a relative humidity 93% ± 2% RH(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, theuseful life of the system's standby batteries and the electroniccomponents may be adversely affected by extreme tempera-ture ranges and humidity. Therefore, it is recommended thatthis system and its peripherals be installed in an environmentwith a normal room temperature of 15 – 27°C/60 – 80°F.

NFPA StandardsThe FireWarden-100-2 complies with the following NFPA 72Fire Alarm Systems requirements:

– LOCAL (Automatic, Manual, Waterflow and SprinklerSupervisory).

– AUXILIARY (Automatic, Manual and Waterflow) (requires4XTM).

– REMOTE STATION (Automatic, Manual and Waterflow)(Where a DACT is not accepted, the alarm, trouble andsupervisory relays may be connected to UL 864 listedtransmitters. For reverse polarity signaling of alarm andtrouble, 4XTM is required.)

– PROPRIETARY (Automatic, Manual and Waterflow).– CENTRAL STATION (Automatic, Manual and Waterflow,

and Sprinkler Supervised).– AUTO DETECTOR SELF TEST

Agency Listings and ApprovalsThe listings and approvals below apply to the basic FireWar-den-100-2 control panel. In some cases, certain modules maynot be listed by certain approval agencies, or listing may be inprocess. Consult factory for latest listing status.

• UL: S635• FM approved

• CSFM: 7165-0028:235• MEA: 120-06-E, Volume 2

FireWarden® and Notifier® are registered trademarks of HoneywellInternational Inc. Microsoft® and Windows® are registered trademarks of theMicrosoft Corporation.©2007 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Page 6: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-60772:A4 • 1/5/2015 — Page 1 of 8

NOTIFIER FirstCommandNFC-50/100(E)

Voice Evacuation & Emergency Communications System

DN-60772:A4

GeneralNotifier’s First Command NFC-50/100 and NFC-50/100E aremultipurpose emergency voice evacuation panels for fire appli-cations, mass notification applications, or both. The First Com-mand delivers 50 or 100 watts of audio power for distribution toup to eight speaker circuits (i.e. zones). The NFC-50/100(E)comes standard with a single speaker circuit and a built-in 50watt, 25V amplifier. A secondary 50 watt amplifier (NFC-BDA-25/70V) can be added for single speaker circuit backup or toincrease system capacity to two speaker circuits and an addi-tional 50 watts of audio power. An optional NFC-CE6 moduleadded to the NFC-50/100(E) will upgrade the system to a max-imum of eight speaker circuit outputs. All speaker output cir-cuits can be wired in either Style Y (Class B) or Style Z (ClassA) configuration. The NFC-50/100(E) has fourteen field pro-grammable messages (up to 60 seconds each), built-in fieldconfigurable pre- and post-announce tone generators and afully supervised Notification Appliance Circuit (NAC) with 2.0amps of synchronized NAC power. The NFC-50/100(E)includes three built-in Form-C relay contacts, (AC power, trou-ble and MNS active) a NAC follower and 500mA special appli-cation power. A built-in power supply delivers operationalpower and an onboard battery charger supports charging upto 26AH batteries (NFC cabinet holds up to 18AH batteries).

For fire protection applications, the NFC-50/100(E) is anadjunct (slave) to any UL listed FACP, providing reverse polar-ity or contact closure; can be used as a stand-alone unit fornon-fire applications. For seamless integration between fireand mass notification, the NFC-50/100(E) can be directly acti-vated via serial communication between the NFW2-100(Rev3), NFS-320 or NFS2-640. Activation of the NFC-50/100(E) viaother FACP's uses the eight on board Command Input Circuits(CMD's). Two of the eight CMD circuits (CMD 1 & CMD 2) canbe individually field programmed for activation by an FACPNotification Appliance Circuit reverse polarity and all eight canbe activated by a contact closure. In addition, the NFC-50/100(E) can be activated from a building's Private BranchExchange (PBX) with the integral night ring feature.

All NFC-50/100(E) programming is done by using a simple,built-in programming utility accessed from any laptop. Foradded flexibility, the NFC-50/100(E) supports both 25V and70V speaker output operation. By adding a 70V transformerconversion module (NFC-XRM-70V) or an additional 70 voltsecondary amplifier (NFC-BDA-25/70V) the system supports70 volt speaker devices.

The NFC-50/100(E) can expand in order to accommodatelarger or more complex installations. To add more control andincrease system capacity, any combination of up to eightexternal remote consoles (including the NFC-LOC, NFC-RPU,and NFC-RM) and up to eight distributed audio amplifiers(including the NFC-50DA(E), NFC-100DA(E) and NFC-125-DA(E) can be connected on the external data bus and audioriser data bus to create a fully integrated command center. Afully loaded system supports up to 1100 watts of total audiopower and up to 24 speaker circuit outputs.

TYPICAL APPLICATIONS

Features• UL Listed to UL 2572 Communication (Control Units Mass

Notification Systems) and UL 864 (emergency voice evacu-ation for fire).

• Modular design for system flexibility and easy expansion.

• Removable terminal blocks.

• 50 watts of 25V audio power (expandable to 100 watts)RMS.

• 2 amp Notification Appliance Circuit (NAC) output, syncgenerator, or follower for System Sensor, Wheelock or Gen-tex protocols.

• Optional 70Vtransformer available for the primary amplifier.(Note that speaker wiring continues to be supervised instandby, alarm and when background music is playing withthis optional transformer installed).

• Eight Command Input Circuits to activate messages 1 to 8:

– CMD1 and CMD2 are field selectable to be activated from12 or 24 VDC Notification Appliance Circuits (reversepolarity) or contact closures.

– CMD3-CMD8 are activated by contact closures.

• Speaker Circuits.

– Single Style Y (Class B) or Style Z (Class A) speaker Cir-cuit.

• Schools • Nursing Homes • Factories

• Theaters • Military facilities • Restaurants

• Auditoriums • Places of Worship • Office Buildings

Page 7: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 8 — DN-60772:A4 • 1/5/2015

– Two Style Y (Class B) or Style Z (Class A) speaker cir-cuits (with optional NFC-BDA-25/70V Audio Amplifierinstalled).

– Eight Style Y (Class B) or Style Z (Class A) speaker cir-cuits (with optional NFC-BDA-25/70V and NFC-CE6installed).

• 520Hz square wave tones available, which can beuploaded to the NFC-50/100 to meet NFPA Low Frequencyrequirements. (Refer to the Device Compatibility Document15378 for listed compatible speakers.)

• NFC-50/100(E) can be controlled by an FACP via the ANN/ACS (EIA-485) link of the NFW2-100 (Rev 3), and via theACS (EIA-485) link of the NFS-320 or NFS2-640. The NFS-320 or NFS2-640 must be firmware version 20.0 or higher.

• Integral supervised microphone.

• Microphone time-out feature which reverts back to pre-recorded message if emergency page exceeds the pro-grammed time.

• 14 recorded messages.

• Field-selectable message and custom message recordingcapability using the local microphone, a USB port, or anexternal audio input.

• External Audio Input can be used for background music.

• Up to 60 second message duration for all messages.

• Integral tone generators field selectable for multiple tonetypes.

• Powered by integral AC power supply or batteries duringAC fail.

• Programmable delay of immediate, 2 hours or 6 hoursreporting of AC Loss.

• Piezo sounder for local trouble.

• 100 event history log.

• Three Form-C relays:

– AC Power Loss Relay - TB1.

– System Trouble Relay - TB2.

– MNS Active - TB3.

• 500mA (0.5A) Special Application (auxiliary power) outputfor addressable modules when interfaced with compatibleaddressable FACPs and End-of-Line power supervisionrelays.

• System Status LEDs (refer to “Controls and Indicators” inproduct manual LS10001-001NF-E).

• Integral Dress Panel.

• Optional TR-CE-B semi-flush trim ring.

• Any combination of up to eight (8) external remote con-soles:

– Optional NFC-RM Remote Microphone (includes cabi-net). See DN-60778.

– Optional NFC-RPU Remote Page Unit (includes cabinet).See DN-60775.

– Optional NFC-LOC Local operator console (includes cab-inet). See DN-60777.

• Any combination of up to eight (8) distributed audio amplifi-ers:

– Optional NFC-50DA(E) distributed amplifier, 50 watts.See DN-60776.

– Optional NFC-125DA(E) distributed amplifier, 125 watts.See DN-60776.

– Optional NFC-50/100 distributed amplifier with backupcapability, 50/100 watts. See DN-60776.

Optional Internal Expansion ModulesNFC-CE6: Circuit Expander Module provides connections forup to six Style Z (Class A) or Style Y (Class B) speaker cir-cuits. Circuits are configured through the web-based program-ming utility.

NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding asecond speaker circuit increases the total NFC-50/100 poweroutput to 100 watts or can also be used as a backup amplifier.

NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding asecond speaker circuit increases the total NFC-50/100 poweroutput to 100 watts or can also be used as a backup amplifier.

NFC-XRM-70V: 70V Transformer Conversion Module. Con-verts the NFC-50/100(E) primary amplifier to a 70V output.This transformer mounts directly to the NFC-50/100(E) maincontrol board by two metal brackets.

Page 8: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-60772:A4 • 1/5/2015 — Page 3 of 8

Control and Indicators

PUSH BUTTON CONTROLS

LED Status Indicators (visible with door closed)

LED Indicators (visible with door and dress panel open)• Speaker Volume Control Fault (yellow).

• Option Card Fault (yellow).

• Amplifier Over Current Fault (yellow).

Product Line Information NFC-50/100: (Primary Operating Console) 50 Watt, 25V singlespeaker zone emergency voice evacuation system, integralmicrophone, built in tone generator and 14 recordable mes-sages.

NFC-50/100E: Export version (Primary Operating Console) 50Watt, 25V single speaker zone emergency voice evacuationsystem, integral microphone, built in tone generator and 14recordable messages. (240 VAC, 50Hz).

NFC-CE6: Speaker Circuit/Zone Expander Module.

NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding asecond speaker circuit increases the total NFC-50/100 poweroutput to 100 watts or can also be used as a backup amplifier.

NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding asecond speaker circuit increases the total NFC-50/100 poweroutput to 100 watts or can also be used as a backup amplifier.

NFC-XRM-70V: 70V Transformer Conversion Module. Con-verts the NFC-50/100(E) primary amplifier to a 70V output.This transformer mounts directly to the NFC-50/100(E) maincontrol board by two metal brackets.

NFC-LOC: Local Operator Console (Complete user interface),Please refer to the data sheet DN-60777 for more information.NFC-RPU: Remote Page Unit Hand held microphone, 14message buttons. Please refer to the data sheet DN-60775 formore information.NFC-RM: Remote Microphone only. Please refer to the datasheet DN-60778 for more information.NFC-50DA: Distributed (Remote) Audio Amplifier, 50 watts.Please refer to the data sheet DN-60776 for more information.NFC-50DAE: Export version. Distributed (Remote) AudioAmplifier, 50 watts. (240 VAC, 50Hz). Please refer to the datasheet DN-60776 for more information.

• All Call • Message Select 1-14

• MNS Control • Diagnostic Select

• System Control • Trouble Silence

• Speaker Select 1-24 • Console Lamp Test

Fire System Active (green)LOC/RPU/RM 1-8 Active (green)

MNS Control (green) Main Console Fault (yellow)

System Control (green) AC Power (green)

System in Use (green) Ground Fault (yellow)

Speaker Zone 1-24 Active (green)

Charger Fault (yellow)

Speaker Zone 1-24 Fault (yellow)

Battery Fault (yellow)

OK to Page (green) Data Bus Fault (yellow)

Microphone Trouble (yellow) NAC Fault (yellow)

Message 1-8 Active (red) NAC Active (green)

Message 1-8 Fault (yellow) System Trouble (yellow)

Remote Amplifier 1-8 Fault (yellow)

Audio Riser Fault (yellow)

LOC/RPU/RM 1-8 Fault (yellow)

Page 9: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 4 of 8 — DN-60772:A4 • 1/5/2015

horns/strobes

Speaker CircuitsTB20 & TB21

NAC CircuitTB19

Internal options

NFC-CE6 circuit expander

NFC-BDA25/70Voptional amplifier

NFC-FFT firefighter telephone

remoteconsoles

NFC-LOClocal operator console

NFC-RPUremote paging unit

NFC-RMremote microphone

TB4

TB12

TB22distributed audioexternal battery charger - J7

NFC-50DA 50W remote amplifier

NFC-125DA 125W remote amplifier CHG-120 charger

CHG-75 charger

NFC-50/100(E) FirstCommand (Possible Configurations)

NFC-50/100DA 50/100W remote

amplifier

Page 10: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-60772:A4 • 1/5/2015 — Page 5 of 8

NFC-125DA: Distributed (Remote) Audio Amplifier, 125 watts.Please refer to the data sheet DN-60776 for more information.NFC-125DAE: Export version. Distributed (Remote) AudioAmplifier, 125 watts. (240 VAC, 50Hz). Please refer to the datasheet DN-60776 for more information.NFC-50/100DA: Distributed (Remote) Audio Amplifier with backup, 50 watts/100 watts at 25Vrms or 70Vrms. Please refer to thedata sheet DN-60776 for more information.NFC-50/100DAE: Export version. Distributed (Remote) AudioAmplifier with back up, 50 watts/100 watts (240 VAC, 50Hz).Please refer to the data sheet DN-60776 for more information.NFC-BDA-BU: Expander card for ECC-50BDA remote amplifierfor 100 watt primary / 50 watt back up operation.Please refer tothe data sheet DN-60776 for more information.NFC-CE4: Distributed Audio Speaker Circuit/Zone expandermodule.

NFC-FFT: Fire Fighter Telephone System. Please refer to thedata sheet DN-60779 for more information.NFC-RTZM: Remote Telephone Zone Module. Allows forsecure access to the NFC via cell phone or remote telephonemeans; not UL listed.Please refer to the data sheet DN-60818for more information.N-FPJ: Remote Phone Jack.

FHS-F: Fire Fighters Remote Handset.

FHSC-R: Fire Fighters Handset Cabinet Recessed.

FHSC-S: Fire Fighters Handset Cabinet Surface Mount

TR-CE-B: Optional Trim Ring.

THUMBLTCH: Optional Thumb Latch. (Non UL-Listed).

CHG-75: 25 to 75 ampere-hours (AH) External Battery Charger.

CHG-120: 25-120 ampere-hours (AH) External Battery Charger.

ECC-MICROPHONE: Replacement Microphone only.

BAT-1270: Battery,12 volt,7.0 AH (Two required).

BAT-12120: Battery,12 volt,12.0 AH (Two required).

BAT-12180: Battery,12 volt, 18.0 AH (Two required).

BAT-12260: Battery, 12 volt, 26.0 AH (Two required).

BB-26: Battery cabinet mounts up to two 26 AH batteries.

Wiring RequirementsSee product manual, part number LS10001-001NF-E fordetailed wiring requirements.

Total System Capacity: (NFC-50/100(E) only) • Total Built-in Audio Power: 50 Watts.

• Total Expandable Audio Power: 100 Watts.

• Total Built-in Speaker Circuits: 2.

• Total Expandable Speaker Circuits: 8.

• Audio Message Max Time Duration: 60 seconds.

• External Audio Input: 1.

Total System Capacity: (Fully Loaded System) • Total Distributed Audio Power: 1100 Watts.

• Total Speaker Circuits Per System: 24.

• Total Remote Consoles Supported: 8.

• Total Distributed Audio Amplifiers Supported: 8.

Electrical Specifications

PRIMARY (AC) POWER (TB15)

NFC-50/100: 120 VAC, 60 Hz, 3.5 amps.

NFC-50/100E: 240 VAC, 50 Hz, 2.0 amps.

Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation.

SECONDARY POWER (BATTERY) CHARGING CIRCUIT (J7)

• Supports lead-acid batteries only.

• Float charge voltage at 27.3V

• Maximum charge current: 1.0 Amp

• Maximum battery charge capability: 2.8 Amps, 26AH (NFCcabinet holds max. 18AH battery).

• Minimum Battery size:12 Amp Hour.

AC LOSS RELAY CONTACT RATING (TB3)

• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).

FORM C - TROUBLE RELAY CONTACT RATING (TB2)

• 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).

MNS ACTIVE RELAY CONTACT RATING (TB1)

• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).

NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT RATING

(TB19)

• One (1) Style Y (Class B) or Style Z (Class A) circuit.

• Power-limited circuitry, (Class 2) supervised.

• Nominal operating voltage: 24 VDC.

• Maximum signaling current for special application power:2.0A.

• Maximum signaling current for regulated power: 200mA.

• Maximum wiring impedance: 1Ω.

• Current limit: fuse-less, electronic, power-limited.

• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) requiredfor Style Y (Class B) operation.

Refer to the Device Compatibility Document 15378 for listedcompatible devices.

NAC FOLLOWER OUTPUT REMOTE SYNC (TB18)

• Connections for FACP NAC synchronization trigger signal.

• Output terminals: pass-through to other system compo-nents.

• Trigger input voltage: 9 to 32 VDC, 24 VDC rated.

• Input current draw in Alarm condition: 10 mA at rated volt-age.

SPECIAL APPLICATION POWER (AUX. POWER) (TB17)

• 500 mA @ 24 VDC.

• Used for powering addressable modules and associatedEnd-of-Line power supervision relays.

Power-limited circuitry. Refer to the Device Compatibility Doc-ument 15378 for a list of compatible devices.

SPEAKER VOLUME CONTROL OVERRIDE (TB23)

• Style Y (Class B) or Style Z (Class A) circuit.

• Special application power.

• Power-limited circuitry, supervised.

• Nominal operating voltage: 24 VDC.

• Maximum signaling current: 0.25 amps.

• Current limit: fuse-less, electronic, power-limited.

• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252)required for Style Y (Class B) operation.

Page 11: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 6 of 8 — DN-60772:A4 • 1/5/2015

Speaker Circuits• Primary Speaker Circuit (TB20)

• Secondary Speaker Circuit (TB21) (with optional amplifieronly).

– Circuit can be wired Style Y (Class B) or Style Z (Class A).

– Power-limited circuitry.

– Normal Operating Voltage: 25 VRMS @ 2 amps max andmaximum Load Impedance of 12.5Ω (70V @ 700 mAmax. with maximum load Impedance of 100Ω operationpossible by plugging optional NFC-XRM-70V conversiontransformer into J12 of the main control board).

– Output Power: 50 watts (10 watts when backgroundmusic is employed).

– Frequency Range: 400Hz - 4,000Hz.

– Maximum total capacitance for each speaker circuit: 250uF.

– End-of-Line Resistor required for Style Y circuit: 15 KΩ, 1watt (P/N: ELR-15K).

Command Input Circuits (alarm polari-ties shown) CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Ter-minals 1(-) and 2(+) are output terminals which provide feedthrough of the NAC circuits to NAC devices down stream.

CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Ter-minals 1(-) and 2(+) are output terminals which provide feedthrough of the NAC circuits to NAC devices downstream.

CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

• Power-limited and supervised circuitry.

• Normal Operating Voltage Range: 10.5 VDC - 29 VDC;(Maximum Voltage: 29 VDC).

• NAC Reverse Polarity Current (requires End-of-Line Resis-tor from NAC): 1.6 mA maximum.

• Contact Closure Operation Current (requires 4.7KΩ, ½ wattEnd-of-Line Resistor P/N 27072): 6.6 mA maximum.

• Maximum Wiring Impedance CMD1 - CMD8 (Contact Clo-sure Operation): 200Ω.

NOTE: When the system is programmed for Mass Notification,CMD1and CMD2 will be programmed for Reverse Polarity only.See manual P/N LS10001-001NF-E for more details.

MAXIMUM INPUT IMPEDANCE:

• CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ.

• CMD1 - CMD8 (Contact Closure Operation): 4.75KΩ.

NIGHT RING INPUT - TB16, TERMINALS 1 (+) & 2 (-)

• Contact closure input.

• Isolated, non-supervised.

• Operation current: 3.8 mA, maximum.

• Maximum wiring impedance: 30KΩ.

• Minimum isolation withstand voltage: 1500 VRMS.

EXTERNAL OPERATOR INTERFACE POWER OUTPUT (TB24)

• Non-resettable power for external operator interface com-ponents.

• Power-limited circuitry, non-supervised.

• Nominal operating voltage: 24 VDC.

• Maximum output current: 0.80 amps.

• Current limit: fuse-less, electronic, power-limited circuit.

EXTERNAL DATA BUS (EIA-485) (TB12)

• Data connections for external operator interface components.

• Redundant transceiver circuitry for Class A operability.

• Power-limited circuitry, supervised.

• Maximum wiring impedance: 13.2Ω.

FACP DATA BUS (EIA-485) (TB13)

• Dedicated connection to FACP serial bus.

• Output terminals: pass-through to other system components.

• Isolated, supervised.

• Minimum isolation withstand voltage: 1500 VRMS.

• Maximum wiring impedance: 40Ω (ANN-BUS), 26Ω (ACS-BUS).

• External Audio Riser (TB22).

• Style Y (Class B) or Style Z (Class A) audio connections toexternal operator interface components.

• Power-limited circuitry, supervised.

• Audio signal level: 3.85 V, maximum.

• Frequency range: 400 Hz - 4 KHz RMS.

• Frequency range (NFC-50/125DA): 800Hz - 2KHz RMS.

EXTERNAL AUDIO INPUT (TB5)

• Input Impedance: 8.5KΩ nominal @1KHz.

• Input Voltage: 700 mV rms maximum.

• Input Current: 0.1 mA maximum @ 700 mV.

NOTE: Some laptops/personal computers only provide an audiooutput for headphones. It may be necessary to adjust the head-phone output level for proper recording of voice messages.

NFC-CE6 Circuit Expander Module Specifications• Power-limited circuitry.

• Up to six (6) circuits on the NFC-CE6 can be wired as StyleY (Class B) or Style Z (Class A).

• Normal Operating Voltage for Speaker Circuits: 25 V@ 2.0amps max. (Maximum Load Impedance of 12.5Ω).

• 70.0 V @ 700 mA max. with maximum Load Impedance of100Ω operation possible for the primary circuit by pluggingin an optional NFC-XRM-70V conversion transformer intoJ12 of the main control board. The same operation is possi-ble for the optional 50W amplifier by selecting the NFC-BDA-70V model.

• Speaker circuit wiring is supervised during standby, back-ground music, and alarm.

• Output Power: 50 watts total; Frequency Range: 400Hz -4,000Hz.

• Maximum total capacitance: 250 µF. (Note that the totalcapacitance for the speaker outputs must not exceed themaximum of 250 µF).

• End-of-Line Resistor required for Style Y (Class B) speakercircuit: 15 KΩ, 1 watt (P/N: ELR-15K)TB13 on the maincontrol board: ACS/ANN (EIA-485) electrically isolated linkto FACP provides programmed speaker control.

Page 12: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-60772:A4 • 1/5/2015 — Page 7 of 8

Cabinet SpecificationsBackbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x5.20"(13.23 cm) deep.

Door: 19.26” (48.92 cm) high x 16.82”(42.73 cm) wide x0.12”(0.30 cm) deep.

Trim Ring (TR-CE-B): 22.00” (55.88 cm) high x 19.65” (49.91cm) wide.

Shipping Specifications Base Unit Weight: 27.85 lbs (12.63 kg).

Temperature and Humidity rangesThis system meets NFPA requirements for operation at 0-49ºC/32-120º F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the usefullife of the system's standby batteries and the electronic com-ponents may be adversely affected by extreme temperatureranges and humidity. Therefore, it is recommended that thissystem and its peripherals be installed in an environment witha normal room temperature of 15-27º C/60-80º F.

Agency Listings and ApprovalsThe listings and approvals below apply to the basic NFC-50/100(E) control panel. In some cases, certain modules may notbe listed by certain approval agencies or listing may be in pro-cess. Consult factory for latest listing status.

• UL/ULC Listed S635.

• Compliant with UFC 4-021-01.

• CSFM: 6911-0028:0265.

• NYC Fire Dept.Certificate of Approval: #6163

Standards and Codes The NFC-50/100(E) complies with the following UL Standardsand with NFPA 72 Fire Alarm system requirements.

• UL 864.

• UL 2572.

Page 13: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 8 of 8 — DN-60772:A4 • 1/5/2015

Notifier® is a registered trademark of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

Page 14: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

dn-6927:a • 04/30/09 — Page 1 of 2

FCPS-24S6(C/E) & FCPS-24S8(C/E)6- & 8-Amp 24-VoltRemote Power Supplies

Power Supplies

dn-6927:a

GeneralThe FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) areremote power supplies with battery charger. The FCPS-24S6/-24S8 may be connected to any 12 or 24 volt fire alarm controlpanel (FACP) or may be used as stand-alone supplies. Pri-mary applications include notification appliance (bell) circuit(NAC) expansion (to support ADA requirements and NAC syn-chronization) or auxiliary power to support 24 volt systemaccessories. The FCPS-24S6/-24S8 provides regulated andfiltered 24 VDC power to four notification appliance circuitsconfigured as either four Class B (Style Y) or Class A (Style Z,with ZNAC-4 option module). Alternately, the four outputs maybe configured as all non-resettable, all resettable or two non-resettable and two resettable. The FCPS-24S6/-24S8 alsocontains a battery charger capable of charging up to 18 AHbatteries. FCPS-24S6C & FCPS-24S8C are ULC-listed.

NOTE: Unless otherwise specified, the terms FCPS-24S6 andFCPS-24S8 used in this document refers to the standard FCPS-24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, theFCPS-24S6E and FCPS-24S8E

Features• UL-Listed NAC synchronization using System Sensor,

Wheelock, or Gentex “Commander2” appliances.

• Operates as a “sync-follower” or as a “sync-generator”(default). See note on page 2.

• Contains two fully-isolated input/control circuits - triggeredfrom FACP NAC (NAC expander mode) or jumped perma-nently “ON” (stand-alone mode).

• Four Class B (Style Y) or four Class A (Style Z, withZNAC-4 module) NACs.

• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load out-put, with 3 amps maximum/circuit, in NAC expander mode(UL 864).

• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuousoutput in stand-alone mode (UL 1481).

• Compatible with coded inputs; signals passed through.

• Optional power-supervision relay (EOLR-1).• In stand-alone mode, output power circuits may be config-

ured as: resettable, (reset line from FACP required),non-resettable, or a mix of two and two.

• Fully regulated and filtered power output - optimal for pow-ering four-wire smoke detectors, annunciators, and othersystem peripherals requiring regulated/filtered power.

• Power-limiting technology meets UL power-limiting require-ments.

• Form-C normally-closed trouble relay.

• Fully supervised power supply, battery, and NACs.• Selectable earth fault detection.• AC trouble report selectable for immediate 2-hour delay.

• Works with virtually any UL 864 fire alarm control which uti-lizes an industry-standard reverse-polarity notification cir-cuit (including unfiltered and unregulated bell power).

• Requires input trigger voltage of 9 - 32 VDC.

• Self-contained in compact, locking cabinet - 15”H x 14.5”Wx 2.75”D (cm: 38.1H x 36.83W x 6.985D).

• Includes integral battery charger capable of charging up to18 AH batteries. Cabinet capable of housing 7.0 AH batter-ies.

• Battery charger may be disabled via DIP switch for applica-tions requiring larger batteries.

• Fixed, clamp-type terminal blocks accommodate up to 12AWG (3.1mm2) wire.

SpecificationsPrimary (AC) Power:

• FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum.• FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum.

• Wire Size: minimum #14 AWG (2.0mm2) with 600 V insula-tion.

Control Input Circuit:

• Trigger Input Voltage: 9 to 32 VDC.• Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9

- 16 V).Trouble Contact Rating: 5 A at 24 VDC.

Auxiliary Power Output: Specific application power 500 mAmaximum.

Output Circuits:

• +24 VDC filtered, regulated.• 3.0 A maximum for any one circuit.

• Total continuous current for all outputs (stand-alone mode):– FCPS-24S6: 4.0 A maximum.– FCPS-24S8: 6.0 A maximum.

• Total short-term current for all outputs (NAC expander mode):– FCPS-24S6: 6.0 A maximum.– FCPS-24S8: 8.0 A maximum.

Secondary Power (Battery) Charging Circuit:

• Supports lead-acid batteries only.• Float-charge voltage: 27.6 VDC.

6927pho1.jpg

Page 15: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 2 — dn-6927:a • 04/30/09

System Sensor® and NOTIFIER® are registered trademarks of HoneywellInternational Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

• Maximum current charge: 1.5 A.

• Maximum battery capacity: 18 AH.

ApplicationsExample 1: Expand notification appliance power an additional6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to fourClass B (Style Y) outputs or four Class A (Style Z) outputs(using ZNAC-4). For example, the FACP notification appliancecircuits will activate the FCPS when reverse-polarity activationoccurs. Trouble conditions on the FCPS are sensed by theFACP through the notification appliance circuit.

Example 2: Use the FCPS to expand auxiliary regulated 24-volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A(FCPS-24S8). Both resettable and non-resettable poweroptions are available. Resettable outputs are created by con-necting the resettable output from the FACP to one or both ofthe FCPS inputs.

Example 3: Use addressable control modules to activate theFCPS instead of activating it through the FACP notificationappliance circuits. This typically allows for mounting the FCPSat greater distances* away from the FACP while expandingsystem architecture in various applications.

For example, an addressable control module is used to acti-vate the FCPS, and an addressable monitor module is used tosense FCPS trouble conditions. Local auxiliary power outputfrom the FCPS provides power to the addressable controlmodule.

*NOTE: Addressable FACPs are capable of locating control andmonitor modules at distances of up to 12,500 feet (3,810 meters).

Sync Follower/Generator NoteIn some installations, it is necessary to synchronize the flashtiming of all strobes in the system for ADA compliance.Strobes accomplish this by monitoring very short timing pulseson the NAC power which are created by the FACP. Wheninstalled at the end of a NAC wire run, the FCPS-24S6/-24S8can track (i.e. “follow”) the strobe synchronization timingpulses on the existing NAC wire run. This maintains the overallsystem flash timing of the additional strobes attaches to theFCPS.

When the FCPS-24S6/-24S8 is configured (via DIP switch set-tings) as a “sync follower,” the FCPS’s NAC outputs track thestrobe synchronization pulses present at the FCPS’s syncinput terminal. The pulses originate from an upstream FACP orother power supply.

When the FCPS-24S6/-24S8 are configured (via DIP switchsettings) as a “sync generator,” the FCPS’s sync input termi-nals are not used. Rather, the FCPS is the originator of thestrobe synchronization pulses on the FCPS’s NAC outputs. In“sync generator” mode, the sync type (System Sensor, Whee-lock, or Gentex) is selectable via DIP switch settings.

Standards and CodesThe FCPS-24S6 and FCPS-24S8 comply with the followingstandards:

• NFPA 72 National Fire Alarm Code.• UL 864 Standard for Control Units for Fire Alarm Systems

(NAC expander mode).• UL 1481 Power Supplies for Fire Alarm Systems.

Agency Listings and ApprovalsThese listings and approvals apply to the modules specified inthis document. In some cases, certain modules or applicationsmay not be listed by certain approval agencies, or listing maybe in process. Consult factory for latest listing status.

• UL Listed: S635, S674

• ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C)• CSFM Approved: 7315-0028:225 • MEA: 299-02-E

• FM Approved

Ordering InformationFCPS-24S6: 6.0 A, 120 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

FCPS-24S6C: Same as above, ULC-listed.

FCPS-24S6R: Same as FCPS-24S6 with red enclosure.

FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

FCPS-24S8: 8.0 A, 120 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

FCPS-24S8C Same as above, ULC-listed.

FCPS-24S8R: Same as FCPS-24S8 with red enclosure.

FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

ZNAC-4: Class A (Style Y) NAC option module.

EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wiresmoke detector power.

BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BATSeries data sheet DN-6933).

PS-1270: Battery, 12-volt, 7.0 AH (two required, see PSSeries data sheet DN-1109)

Page 16: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

dn-7114:c • 5/22/09 — Page 1 of 2

N-ANN-8080-Character LCD Serial Annunciator

Annunciators

dn-7114:c • A1-65

7114

cov.

jpg

GeneralThe N-ANN-80 annunciator is a compact, backlit, 80-characterLCD fire annunciator that mimics the Fire Alarm Control Panel(FACP) display. It provides system status indicators for ACPower, Alarm, Trouble, Supervisory, and Alarm Silenced condi-tions. The N-ANN-80 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communicationformat. Connected devices are powered, via two additionalwires, by either the host FACP or a remote UL-listed, filteredpower supply. N-ANN-80 is black; for white order N-ANN-80-W.

The N-ANN-80 displays English-language text of system pointinformation including device type, zone, independent pointalarm, trouble or supervisory status, as well as any customalpha labels programmed into the control panel. It includes con-trol switches for remote control of critical system functions. (Akeyswitch prevents unauthorized operation of the controlswitches.)

Up to eight N-ANN-80s may be connected to the ANN-BUS ofeach FACP. Minimal programming is required, which saves timeduring system commissioning. The N-ANN-80 is compatiblewith NOTIFIER FACPs with an ANN-BUS, such as the NFW-50.

Features• Listed to UL Standard 864, 9th Edition.• Backlit 80-character LCD display (20 characters x 4 lines).• Mimics all display information from the host panel.• Control switches for System Acknowledge, Signal Silence,

Drill, and Reset.• Control switches can be independently enabled or disabled

at the FACP.• Keyswitch enables/disables control switches and mechani-

cally locks annunciator enclosure • Keyswitch can be enabled or disabled at the FACP.• Enclosure supervised for tamper.• System status LEDs for AC Power, Alarm, Trouble, Supervi-

sory, and Alarm Silence.• Local sounder can be enabled or disabled at the FACP.• N-ANN-80 connects to the ANN-BUS terminal on the FACP

and requires minimal panel programming.• Displays device type identifiers, individual point alarm, trou-

ble, supervisory, zone, and custom alpha labels.• Time-and date display field.• Surface mount directly to wall or to single, double, or 4"

square electrical box.• Semi-flush mount to single, double, or 4" square electrical

box. Use ANN-SB80KIT for angled view mounting.• Can be remotely located up to 6,000 feet (1,800 m) from the

panel.• Backlight turns off during AC loss to conserve battery power

but will turn back on if an alarm condition occurs.• May be powered by 24 VDC from the host FACP or by remote

power supply (requires 24 VDC).• Up to eight N-ANN-80s can be connected on the ANN-BUS.

Controls and Indicators• AC Power• Alarm

• Trouble• Supervisory• Alarm Silenced

Specifications• Operating voltage range: 18 VDC to 28 VDC.• Current consumption @ 24 VDC nominal (filtered and non-

resettable): 40 mA maximum.• Ambient temperature: 32°F to 120°F (0°C to 49°C).• Relative humidity: 93% ± 2% RH (noncondensing) at 32°C

± 2°C (90°F ± 3°F).• 5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375”

(3.49 cm.) deep.• For use indoors in a dry location.• All connections are power-limited and supervised.

Agency Listings and ApprovalsThe listings and approvals below apply to the N-ANN-80. Insome cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult factoryfor latest listing status.

• UL: S635• FM approved• CSFM: 7120-0028:240

• MEA: 442-06-E Vol. 2

The ANN-BUS

POWERING THE DEVICES ON THE ANN-BUS FROMAUXILIARY POWER SUPPLYThe ANN-BUS can be powered by an auxiliary power supplywhen the maximum number of ANN-BUS devices exceeds theANN-BUS power requirements. See the FACP manual for moreinformation.

Page 17: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 2 — dn-7114:c • 5/22/09

©2009 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

ANN-BUS DEVICE ADDRESSINGEach ANN-BUS device requires a unique address (ID Number)in order to communicate with the FACP. A maximum of 8 devicescan be connected to the FACP ANN-BUS communication circuit.See the FACP manual for more information.

WIRE REQUIREMENTS: COMMUNICATIONS CIRCUITThe N-ANN-80 connects to the FACP ANN-BUS communica-tions circuit. To determine the type of wire and the maximum wir-ing distance that can be used with FACP ANN-BUS accessorymodules, it is necessary to calculate the total worst case currentdraw for all modules on a single 4-conductor bus. The total worstcase current draw is calculated by adding the individual worstcase currents for each module.

NOTE: For total worst case current draw on a single ANN-BUSrefer to appropriate FACP manual.

After calculating the total worst case current draw, the followingtable specifies the maximum distance the modules can belocated from the FACP on a single wire run. The table ensures6.0 volts of line drop maximum. In general, the wire length is lim-ited by resistance, but for heavier wire gauges, capacitance isthe limiting factor.

These cases are marked in the chart with an asterisk (*). Maxi-mum length can never be more than 6,000 feet (1,800 m),regardless of gauge used. See table below.

WIRE REQUIREMENTS: POWER CIRCUIT• 14 to 18 AWG (0.75 - 2.08 mm2) wire for 24 VDC power cir-

cuit is acceptable.• All connections are power-limited and supervised.• A maximum of eight N-ANN-80 modules may be connected

to this circuit.

WIRING CONFIGURATIONThe following figure illustrates the wiring between the FACP andANN-BUS devices.

FACP Wiring to ANN-BUS Device

ORDERING OPTIONS:N-ANN-80: Black 80 character LCD Annunciator.

N-ANN-80-W: White, 80 character LCD Annunciator. ANN-SB80KIT-B: Black surface mount backbox with angledwedge.

ANN-SB80KIT-W: White surface mount backbox with angledwedge.

Communication Pair Wiring Distance: FACP to Last ANN-BUS ModuleTotal Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge

0.100 1,852 ft. 4,688 ft. * 6,000 ft. *6,000 ft.

0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.

0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.

0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.

0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.

0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft.

0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft.

0.800 231 ft. 586 ft. 933 ft. 1,476 ft.

0.900 206 ft. 521 ft. 829 ft. 1,312 ft.

1.000 (max.) 185 ft. 469 ft. 746 ft. 1,181 ft.

ANN-BUS and power wiring are supervised and power-limited.

ANN-BUS Device

NFW-50

Page 18: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-7001:D • 4/13/2012 — Page 1 of 2

NOT-BG12LXAddressable Manual Pull Station

Intelligent/Addressable Devices

DN-7001:D • A1-380

The NOT-BG12LXAddressable Manual Pull Station

6643

cov1

.jpg

GeneralThe Notifier NOT-BG12LX is a state-of-the-art, dual-action(i.e., requires two motions to activate the station) pull stationthat includes an addressable interface for FireWarden seriesintelligent control panels, and the NSP-25 panel. Because theNOT-BG12LX is addressable, the control panel can display theexact location of the activated manual station. This leads firepersonnel quickly to the location of the alarm.

Features• Maintenance personnel can open station for inspection and

address setting without causing an alarm condition.

• Built-in bicolor LED, which is visible through the handle ofthe station, flashes in normal operation and latches steadyred when in alarm.

• Handle latches in down position and the word “ACTIVATED”appears to clearly indicate the station has been operated.

• Captive screw terminals wire-ready for easy connection toSLC loop (accepts up to 12 AWG/3.25 mm² wire).

• Can be surface mounted (with SB-10 or SB-I/O) or semi-flush mounted. Semi-flush mount to a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box.

• Smooth dual-action design.• Meets ADAAG controls and operating mechanisms guide-

lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.maximum activation force.

• Highly visible.• Attractive shape and textured finish.

• Key reset.• Includes Braille text on station handle.• Optional trim ring (BG12TR).

• Meets UL 38, Standard for Manually Actuated SignalingBoxes.

ConstructionShell, door, and handle are molded of durable polycarbonatematerial with a textured finish.

Specifications• Shipping Weight: 9.6 oz. (272.15 g)• Normal operating voltage: 24 VDC.• Maximum SLC loop voltage: 28.0 VDC.

• Maximum SLC standby current: 375 μA.• Maximum SLC alarm current: 5 mA.• Temperature Range: 32°F to 120°F (0°C to 49°C)

• Relative Humidity: 10% to 93% (noncondensing)• For use indoors in a dry location

InstallationThe NOT-BG12LX will mount semi-flush into a single-gang,double-gang, or standard 4" (10.16 cm) square electrical outletbox, or will surface mount to the model SB-10 or SB-I/O sur-face backbox. If the NOT-BG12LX is being semi-flushmounted, then the optional trim ring (BG12TR) may be used.

The BG12TR is usually needed for semi-flush mounting with 4"(10.16 cm) or double-gang boxes (not with single-gang boxes).

OperationPushing in, then pulling down on the handle causes it to latchin the down/activated position. Once latched, the word “ACTI-VATED” (in bright yellow) appears at the top of the handle,while a portion of the handle protrudes from the bottom of thestation. To reset the station, simply unlock the station with thekey and pull the door open. This action resets the handle; clos-ing the door automatically resets the switch.

Each manual station, on command from the control panel,sends data to the panel representing the state of the manualswitch. Two rotary decimal switches allow address settings (1 – 99 on NFW2-100/NFW2-100C, 1 – 50 for NFW-50/NFW-50C).

Architectural/Engineering SpecificationsManual Fire Alarm Stations shall be non-coded, with a key-operated reset lock in order that they may be tested, and sodesigned that after actual Emergency Operation, they cannotbe restored to normal except by use of a key. An operated sta-tion shall automatically condition itself so as to be visuallydetected as activated. Manual stations shall be constructed ofred-colored polycarbonate material with clearly visible operat-ing instructions provided on the cover. The word FIRE shallappear on the front of the stations in white letters, 1.00 inches(2.54 cm) or larger. Stations shall be suitable for surfacemounting on matching backbox SB-10 or SB-I/O; or semi-flushmounting on a standard single-gang, double-gang, or4" (10.16 cm) square electrical box, and shall be installed

Page 19: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 2 — DN-7001:D • 4/13/2012

NOTIFIER® is a registered trademark of Honeywell International Inc.©2012 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

within the limits defined by the Americans with Disabilities Act(ADA) or per national/local requirements. Manual Stationsshall be Underwriters Laboratories listed.

Manual stations shall connect with two wires to one of the con-trol panel SLC loops. The manual station shall, on commandfrom the control panel, send data to the panel representing thestate of the manual switch. Manual stations shall provideaddress setting by use of rotary decimal switches.

Product Line InformationNOT-BG12LX: Dual-action addressable pull station. Includeskey locking feature. (Listed for Canadian and non-Canadianapplications.)

SB-10: Surface backbox; metal.

SB-I/O: Surface backbox; plastic.

BG12TR: Optional trim ring.

17021: Keys, set of two.

Agency Listings and ApprovalsIn some cases, certain modules or applications may not belisted by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status.

• UL/ULC Listed: S692 (listed for Canadian and non-Cana-dian applications).

• MEA: 67-02-E Vol. IV.

• CSFM: 7150-0028:0199. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;6,632,108.

Page 20: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

NP-100(A) SeriesAddressable Photoelectric Detectors

Addressable Devices

DN-6995:D • A1-320

GeneralThe NP-100(A), NP-100T(A) and NP-100R(A) addressable,low-profile plug-in photoelectric detectors use a state-of-the-artphotoelectric sensing chamber with communications to provideopen area protection and are used exclusively with NOTIFIER’sFireWarden Series (FireWarden-100-2 and FireWarden-50)and Spartan (NSP-25) Addressable Fire Alarm Control Panels(FACPs). The NP-100T(A) adds thermal sensors that will alarmat a fixed temperature of 135°F (57°C). Since these detectorsare addressable, they will help emergency personnel quicklylocate a fire during its early stages, potentially saving preciousrescue time while also reducing property damage. Two LEDs oneach sensor light to provide a local, visible sensor indication.Remote LED annunciator capability is available as an optionalaccessory, PN RA100Z(A). The NP-100R(A) is a remote testcapable detector for use with DNR(A)/DNRW duct smoke detec-tor housings.

Features

SLC LOOP

• Two-wire loop connection.• Unit uses base for wiring.

ADDRESSING

• Addressable by device.• Rotary, decimal addressing: 01 – 99 with FireWarden-100-2

and NSP-25, and 01 – 50 with FireWarden-50.

ARCHITECTURE

• Unique single-source, dual-chamber design to respondquickly and dependably to a broad range of fires.

• Sleek, low-profile design.• Integral communications and built-in type identification.• Built-in tamper-resistant feature.• Removable cover and insect-resistant screen for simple field

cleaning.

OPERATION

• Withstands air velocities up to 4,000 feet-per-minute (20 m/sec.) without triggering a false alarm.

• Factory preset at 1.5% nominal sensitivity for panel alarmthreshold level.

• Visible LED “blinks” when the unit is addressed (communicat-ing with the fire panel) and latches on in alarm.

MECHANICALS

• Sealed against back pressure.• Direct surface mounting or electrical box mounting.• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm)

octagonal box, or 4.0" (10.16 cm) square electrical box (usinga plaster ring — included).

OTHER SYSTEM FEATURES

• Fully coated circuit boards and superior RF/transient protec-tion.

• 94-V0 plastic flammability rating.• Low standby current.

OPTIONS

• Remote LED output connection, PN RA100Z(A).

ApplicationsUse photoelectric detectors in life-safety applications to providea broad range of fire-sensing capability, especially where smol-dering fires are anticipated. Ionization detectors are often betterthan photoelectric detectors at sensing fast, flaming fires.

ConstructionThese detectors are constructed of off-white fire resistant plas-tic. NP-100(A) series plug-in, low-profile smoke detectors aredesigned to commercial standards and offer an attractiveappearance.

InstallationNP-100(A) series plug-in detectors use a detachable mountingbase to simplify installation, service and maintenance.

Mount base (all base types) on an electrical backbox which is atleast 1.5" (3.81 cm) deep. For a chart of compatible junctionboxes, see DN-60054.

NOTE: Because of the inherent supervision provided by the SLCloop, end-of-line resistors are not required. Wiring “T-taps” orbranches are permitted for Style 4 (Class B) wiring. NP-100R(A)mounts in a DNR(A)/DNRW duct detector housing.

OperationEach NP-100(A) series detector uses one of 99 possibleaddresses on the FireWarden-100-2 and NSP-25, or one of 50possible addresses on the FireWarden-50 Signaling Line Circuit(SLC). It responds to regular polls from the system and reportsits type and status.

The addressable photoelectric sensor in the NP-100(A) serieshas a unique unipolar chamber that responds quickly and uni-formly to a broad range of smoke conditions. It can withstandwind gusts up to 4,000 feet-per-minute (20 m/sec.) withoutsending an alarm level signal. Because of its unipolar chamber,the NP-100(A) series is approximately two times more respon-sive than most photoelectric sensors. This makes it a more sta-ble detector.

NP-100(A) in B210LP(A) Base

2151

_225

1B_

CE

ILIN

G.p

ng

DN-6995:D • 2/11/2015 — Page 1 of 2

Page 21: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

NOTIFIER® and FireWarden® are registered trademarks of HoneywellInternational Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Detector Sensitivity TestEach detector can have its sensitivity tested (required per NFPA72, Chapter 14 on Inspection, Testing and Maintenance) wheninstalled/connected to a FireWarden-100-2 or FireWarden-50addressable fire alarm control panel. The results of the sensitiv-ity test can be printed off the FireWarden-100-2 or FireWarden-50 for record keeping.

SpecificationVoltage range: 15 – 32 VDC (peak).

Standby current: 300 µA @ 24 VDC.

LED current: 6.5 mA @ 24 VDC (latched “ON”).

Air velocity: 4,000 ft./min. (20 m/sec.) maximum.

Size: 2.1" (5.33 cm) high; base determines diameter.

– B210LP(A): 6.1" (15.5 cm) diameter.– B501(A): 4.1" (10.4 cm) diameter.– B200SR(A): 6.875" (17.46 cm) diameter. – B224RB(A): 6.2" (15.748 cm) diameter.

Weight: 3.6 oz. (102 g).

Operating temperature range: for NP-100(A): 0°C to 49°C(32°F to 120°F); for NP-100T(A): 0°C to 38°C (32°F to 100°F).NP-100R(A): installed in a DNR(A)/DNRW -20°C to 70°C (-4°Fto 158°F).

Temperature: 0°C – 49°C (32°F – 120°F).

Relative humidity: 10% – 93%, non-condensing.

ListingsListings and approvals below apply to the NP-100(A), NP-100T(A), and NP-100R(A) detectors. In some cases, certainmodules may not be listed by certain approval agencies, or list-ing may be in process. Consult factory for latest listing status.

• UL Listed: S1115.• ULC Listed: S1115.• CSFM: 7272-0028:0231.• MEA: 243-02-E Vol. 2.• Maryland State Fire Marshal: permit 2173.• FM approved.

Product Line InformationNOTE: “A” suffix indicates ULC Listed model.

NP-100: Addressable photoelectric detector; B210LP baseincluded.

NP-100A: Sames as NP-100 with ULC Listing; B210LPA baseincluded.

NP-100T: Same as NP-100 but with thermal element; B210LPbase included.

NP-100TA: Same as NP-100T with ULC Listing; B210LPA baseincluded.

NP-100R: Remote test capable addressable photoelectricdetector for use with a DNRA/DNRW duct detector housing;B210LP base included.

NP-100RA: Same as NP-100R with ULC Listing for use with aDNRA duct detector housing; B210LPA base included.

INTELLIGENT BASES

NOTE: “A” suffix indicates ULC Listed model.

NOTE: For details about intelligent bases and their mounting, seeDN-60054.

B210LP(A): Plug-in detector base (included); standard U.S.flanged low-profile mounting base.

B210LPBP: Bulk pack of B210LP; package contains 10.

B501(A): Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.

B200SR(A): Intelligent sounder base capable of producingsound output with ANSI Temporal 3 or continuous tone.Replaces B501BH series bases in retrofit applications.

B224RB(A): Plug-in System Sensor relay base. Screw termi-nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30VDC inductive.

B224BI(A): Plug-in System Sensor isolator detector base.Maximum 25 devices between isolator bases (see DN-6994).

ACCESSORIES

F110: Retrofit flange to convert B210LP(A) to match theB710LP(A) profile, or to convert older high-profile bases to low-profile.

F110BP: Bulk pack of F110; package contains 15.

F210: Replacement flange for B210LP(A) base.

RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to aU.S. single-gang electrical box. For use with B501(A) andB210LP(A) bases only.

SMB600: Surface mounting kit

M02-04-00:Test magnet.

M02-09-00: Test magnet with telescoping handle.

XR2B: Detector removal tool. Allows installation and/or removalof detector heads from bases in high ceiling applications.

XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m)sections.

T55-127-010: Detector removal tool without pole.

BCK-200B: Black detector covers for use with NP-100(A) only;box of 10.

WCK-200B: White detector covers for use with NP-100(A) only;box of 10.

Page 2 of 2 — DN-6995:D • 2/11/2015

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Page 22: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-6999:C • 10/06/2010 — Page 1 of 4

Monitor ModulesNMM-100(A), NMM-100P(A), NZM-100(A), and NDM-100(A) for FireWarden Series Panels

Intelligent Addressable Devices

DN-6999:C

GeneralFour different monitor modules are available for Notifier’s Fire-Warden Series intelligent control panels for a variety of appli-cations. Monitor modules supervise a circuit of dry-contactinput devices, such as conventional heat detectors and pullstations, or monitor and power a circuit of two-wire smokedetectors (NZM-100(A)).

NMM-100(A) is a standard-sized module (typically mounts to a4" [10.16 cm] square box) that supervises either a Style D(Class A) or Style B (Class B) circuit of dry-contact inputdevices.

NMM-100P(A) is a miniature monitor module a mere 1.3"(3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D thatsupervises a Style B (Class B) circuit of dry-contact inputdevices. Its compact design allows the NMM-100P(A) to bemounted in a single-gang box behind the device it monitors.

NZM-100(A) is a standard-sized module that monitors andsupervises compatible two-wire, 24 volt, smoke detectors on aStyle D (Class A) or Style B (Class B) circuit.

NDM-100(A) is a standard-sized dual monitor module thatmonitors and supervises two independent two-wire Style B(Class B) dry-contact initiating device circuits (IDCs) at twoseparate, consecutive addresses in intelligent, two-wire systems.

NMM-100(A) Monitor Module• Built-in type identification automatically identifies this device

as a monitor module to the control panel.• Powered directly by two-wire SLC loop. No additional power

required.• High noise (EMF/RFI) immunity.

• SEMS screws with clamping plates for ease of wiring.• Direct Decade entry of address: 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50. • LED flashes during normal operation and latches on steady

to indicate alarm.The NMM-100(A) Monitor Module is intended for use in intelli-gent, two-wire systems, where the individual address of eachmodule is selected using the built-in rotary switches. It pro-vides either a two-wire or four-wire fault-tolerant InitiatingDevice Circuit (IDC) for normally-open-contact fire alarm andsupervisory devices. The module has a panel-controlled LEDindicator.

NMM-100(A) APPLICATIONSUse to monitor a zone of four-wire smoke detectors, manualfire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm activation devices. May also be usedto monitor normally-open supervisory devices with specialsupervisory indication at the control panel. Monitored circuitmay be wired as an NFPA Style B (Class B) or Style D (ClassA) Initiating Device Circuit. A 47K ohm End-of-Line Resistor(provided) terminates the Style B circuit. No resistor isrequired for supervision of the Style D circuit.

NMM-100(A) OPERATIONEach NMM-100(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC). A flashing LEDindicates that the module is in communication with the controlpanel. The LED latches steady on alarm (subject to currentlimitations on the loop).

NMM-100(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Maximum current draw: 5.0 mA (LED on).

Average operating current: 350 μA (LED flashing), 1 com-munication every 5 seconds, 47k EOL.

Maximum IDC wiring resistance: 40 ohms.

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box.

NMM-100(A) (Type H)

6999

cov.

jpg

Page 23: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 4 — DN-6999:C • 10/06/2010

NMM-100P(A) Mini Monitor Module• Built-in type identification automatically identifies this device

as a monitor module to the panel.• Powered directly by two-wire SLC loop. No additional power

required.• High noise (EMF/RFI) immunity.• Tinned, stripped leads for ease of wiring.

• Direct Decade entry of address: 01 – 99 on FireWarden-100-2, 01 – 50 on FireWarden-50.

The NMM-100P(A) Mini Monitor Module can be installed in asingle-gang junction directly behind the monitored unit. Itssmall size and light weight allow it to be installed without rigidmounting. The NMM-100P(A) is intended for use in intelligent,two-wire systems where the individual address of each moduleis selected using rotary switches. It provides a two-wire initiat-ing device circuit for normally-open-contact fire alarm andsecurity devices. NMM-100P(A)

NMM-100P(A) APPLICATIONSUse to monitor a single device or a zone of four-wire smokedetectors, manual fire alarm pull stations, waterflow devices, orother normally-open dry-contact devices. May also be used tomonitor normally-open supervisory devices with special super-visory indication at the control panel. Monitored circuit/deviceis wired as an NFPA Style B (Class B) Initiating Device Circuit.A 47K ohm End-of-Line Resistor (provided) terminates the cir-cuit.

NMM-100P(A) OPERATIONEach NMM-100P(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC).

NMM-100P(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Average operating current: 350 μA, 1 communication every5 seconds, 47k EOL; 600 μA Max. (Communicating, IDCShorted).

Maximum IDC wiring resistance: 40 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 400 μA.

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x0.65" (1.651 cm) deep.

Wire length: 6" (15.24 cm) minimum.

NZM-100(A) Interface Module• Supports compatible two-wire smoke detectors.• Supervises IDC wiring and connection of external power

source.• High noise (EMF/RFI) immunity.

• SEMS screws with clamping plates for ease of wiring.• Direct Decade entry of address:, 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50.• LED flashes during normal operation.• LED latches steady to indicate alarm on command from

control panel.The NZM-100(A) Interface Module is intended for use in intelli-gent, addressable systems, where the individual address ofeach module is selected using built-in rotary switches. Thismodule allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (nor-mal, open, or alarm) of one full zone of conventional detectorsback to the control panel. All two-wire detectors being moni-tored must be UL compatible with the module.

NZM-100(A) APPLICATIONSUse the NZM-100(A) to monitor a zone of two-wire smokedetectors. The monitored circuit may be wired as an NFPAStyle B (Class B) or Style D (Class A) Initiating Device Circuit.A 3.9 K ohm End-of-Line Resistor (provided) terminates theend of the Style B or D (class B or A) circuit (maximum IDCloop resistance is 25 ohms). Install ELR across terminals 8and 9 for Style D application.

NZM-100(A) OPERATIONEach NZM-100(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC). A flashing LEDindicates that the module is in communication with the controlpanel. The LED latches steady on alarm (subject to currentlimitations on the loop).

NZM-100(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Maximum current draw: 5.1 mA (LED on).

Maximum IDC wiring resistance: 25 ohms.

Average operating current: 300 μA, 1 communication and 1LED flash every 5 seconds, 3.9k eol.

EOL resistance: 3.9K ohms.

External supply voltage (between Terminals T3 and T4):DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrmsmaximum. Current: 90 mA per module maximum.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box.

6720m101.w

mf

Page 24: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

DN-6999:C • 10/06/2010 — Page 3 of 4

NDM-100(A) Dual Monitor ModuleThe NDM-100(A) Dual Monitor Module is intended for use inintelligent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutiveaddresses. It is capable of monitoring normally open contact firealarm and supervisory devices. The module has a single panel-controlled LED.

NOTE: The NDM-100(A) provides two Style B (Class B) IDC cir-cuits ONLY. Style D (Class A) IDC circuits are NOT supported inany application.

NDM-100(A) SPECIFICATIONSNormal operating voltage range: 15 to 32 VDC.

Maximum current draw: 6.4 mA (LED on).

Average operating current: 750 μA (LED flashing).

Maximum IDC wiring resistance: 1,500 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 240 μA

EOL resistance: 47K ohms.

Maximum SLC Wiring resistance: 40 Ohms.

Temperature range: 32° to 120°F (0° to 49°C).

Humidity range: 10% to 93% (non-condensing).

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x2.125" (5.398 cm) deep.

NDM-100(A) AUTOMATIC ADDRESSINGThe NDM-100(A) automatically assigns itself to two address-able points, starting with the original address. For example, ifthe NDM-100(A) is set to address “26”, then it will automati-cally assign itself to addresses “26” and “27”.

NOTE: “Ones” addresses on the NDM-100(A) are 0, 2, 4, 6, or 8only. Terminals 6 and 7 use the first address, and terminals 8 and9 use the second address.

InstallationNMM-100(A), NZM-100(A), and NDM-100(A) modules mountdirectly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)deep, electrical box. They may also be mounted to theSMB500 surface-mount box. Mounting hardware and installa-tion instructions are provided with each module. All wiringmust conform to applicable local codes, ordinances, and regu-lations. These modules are intended for power-limited wiringonly.

The NMM-100P(A) module is intended to be wired andmounted without rigid connections inside a standard electricalbox. All wiring must conform to applicable local codes, ordi-nances, and regulations.

Agency Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac-tory for latest listing status.

• UL: S635• ULC: S635

• FM Approved • CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-

100); 7300-0028:0237 (NDM-100)

• MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100);227-03-E Vol. 3 (NDM-100)

Product Line InformationNOTE: “A” suffix indicates ULC-listed model.

NMM-100(A): Monitor module.

NMM-100P(A): Monitor module, miniature.

NZM-100(A): Monitor module, two-wire detectors.

NDM-100(A): Monitor module, dual, two independent Class Bcircuits.

SMB500: Optional surface-mount backbox.

NOTE: See installation instructions and refer to the SLC WiringManual, PN 52304.

! CAUTION: Avoid duplicating addresses on the system.

Page 25: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 4 of 4 — DN-6999:C • 10/06/2010

Notifier® and FireWarden® are registered trademarks and FireWatch™ is atrademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

Page 26: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

dn-7000:a2 • 06/17/10 — Page 1 of 2

NC-100(A)Control Module for FireWarden Series Panels

Addressable

dn-7000:a2 • A1-360

GeneralThe NC-100(A) Addressable Control Module provides NOTI-FIER’s FireWarden Series intelligent control panels a super-vised Class B (Style Y) of Class A (Style Z) circuit forNotification Appliances (horns, strobes, etc.). Addressabilityallows the NC-100(A) to be activated, either manually orthrough panel programming, on a select (zone or area of cov-erage) basis.

Features• Built-in type identification automatically identifies these

devices to the control panel.

• Internal circuitry powered directly by two-wire SLC loop.The NC-100(A) module requires power (for horns, strobes,etc.).

• Integral LED “blinks” when communicating, and turns onsteady when activated.

• High noise immunity (EMF/RFI).

• The NC-100(A) may be used to switch 24-volt NAC power.• Wide viewing angle of LED.• SEMS screws with clamping plates for wiring ease.

• Direct Decade entry of address: 01 – 99 with FireWarden-100-2(C), or 01-50 with the FireWarden-50(C).

ApplicationsThe NC-100(A) is used to switch 24 VDC audible/visual power.

Construction• The face plate is made of off-white heat-resistant plastic.• Controls include two rotary switches for direct-dial entry of

address setting.• The NC-100(A) is configured for a single Class B (Style Y)

or Class A (Style Z) Notification Appliance Circuit.

OperationEach NC-100(A) uses one of the module addresses on a SLCloop. It responds to regular polls from the control panel andreports its type and status, including the open/normal/shortstatus of its Notification Appliance Circuit (NAC). The LEDblinks with each poll received. On command, it activates itsinternal relay. The NC-100(A) supervises Class B (Style Y) orClass A (Style Z) notification or control circuits.

Upon code command from the panel, the NC-100(A) will dis-connect the supervision and connect the external power sup-ply in the proper polarity across the load device. Thedisconnection of the supervision provides a positive indicationto the panel that the control relay actually turned ON. Theexternal power supply is always relay-isolated from the com-munication loop so that a trouble condition on the externalpower supply will never interfere with the rest of the system.

Rotary switches set a unique address for each module. Theaddress may be set before or after mounting. The built-inTYPE CODE (not settable) will identify the module to the con-trol panel.

SpecificationsNormal operating voltage: 15 to 32 VDC.

Maximum SLC current draw: 6.5 mA (LED on).

Average operating current: 350 μA (LED flashing).

External supply voltage: maximum 80 volts (RMS or DC).

Drain on external supply: 2 mA maximum (using internalEOL relay).

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% non-condensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box.

Agency Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac-tory for latest listing status.

• FM approved• UL/ULC Listed: file S635.• CSFM approved: file 7300-0028:230.

• MEA approved: file 72-01-E Vol. 2.

NC-100(A)

7000

cov.

JPG

Page 27: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Page 2 of 2 — dn-7000:a2 • 06/17/10

NOTIFIER® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

Contact Ratings

Product Line InformationNC-100: Intelligent addressable control module.

NC-100(A): Intelligent addressable control module, ULC listedversion.

SMB500: Optional surface-mount backbox.

CB500: Optional control module barrier, required by UL forseparating power-limited and non-power-limited wiring in thesame junction box as NC-100(A).

NOTE: For installation instructions, see document I56-2592-001and refer to the SLC Wiring Manual, document 52304. The NC-100R(A) relay module, previously on this data sheet, is now onDN-60383.

Current Rating

Maximum Voltage

Load Description Application

3 A 30 VDC Resistive Non-Coded

2 A 30 VDC Resistive Coded

.9 A 110 VDC Resistive Non-Coded

.9 A 125 VDC Resistive Non-Coded

.5 A 30 VDCInductive(L/R=5ms)

Coded

1 A 30 VDCInductive(L/R=2ms)

Coded

.3 A 125 VACInductive(PF=0.35)

Non-Coded

1.5 A 25 VACInductive(PF=0.35) Non-Coded

.7 A 70.7 VACInductive(PF=0.35) Non-Coded

2 A 25 VACInductive(PF=0.35) Non-Coded

Page 28: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Features

• Plug-in design with minimal intrusion into the back box

• Tamper-resistant construction

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Field-selectable candela settings on wall units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Horn rated at 88+ dBA at 16 volts

• Rotary switch for horn tone and three volume selections

• Universal mounting plate for wall units

• Mounting plate shorting spring checks wiring continuity before device installation

• Electrically Compatible with legacy SpectrAlert devices

• Compatible with MDL3 sync module

• Listed for ceiling or wall mounting

The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement.

Like the entire SpectrAlert Advance product line, wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults.

To further simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed.

Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections.

Indoor Selectable-Output Horns, Strobes, andHorn Strobes forWall Applications

SpectrAlert® Advance audible visible notification products

are rich with features guaranteed to cut installation times

and maximize profits.

MEA452-05-E3023572

7125-1653:186 (indoor strobes)7125-1653:188 (horn strobes,

chime strobes)7135-1653:189 (horns, chimes)

S4011 (chimes, horn strobes, horns)S5512 (strobes)

Page 29: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

SpectrAlert Advance SpecificationsArchitect/Engineer SpecificationsGeneralSpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185.

StrobeThe strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Horn Strobe CombinationThe horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply.

Synchronization ModuleThe module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical/Electrical SpecificationsStandard Operating Temperature 32°F to 120°F (0°C to 49°C)Humidity Range 10 to 93% non-condensingStrobe Flash Rate 1 flash per secondNominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1

Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)Input Terminal Wire Gauge 12 to 18 AWGWall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D)

Notes:1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.

Page 30: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Horn and Horn Strobe Output (dBA)

Switch Position Sound Pattern dB

8–17.5 Volts

16–33Volts

24-Volt NominalReverberant Anechoic

DC FWR DC FWR DC FWR DC FWR1 Temporal High 78 78 84 84 88 88 99 982 Temporal Medium 75 75 80 80 86 86 96 963 Temporal Low 71 71 76 76 83 80 94 894 Non-Temporal High 82 82 88 88 93 92 100 1005 Non-Temporal Medium 78 78 85 85 90 90 98 986 Non-Temporal Low 73 74 81 81 88 84 96 927† Coded High 82 82 88 88 93 92 101 1018† Coded Medium 78 78 85 85 90 90 97 989† Coded Low 74 75 81 81 88 85 96 92

†Settings 7, 8, and 9 are not available on 2-wire horn strobes.

UL Max. Strobe Current Draw (mA RMS)

Candela8–17.5 Volts 16–33 VoltsDC FWR DC FWR

Standard Candela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)

DC Input8–17.5 Volts 16–33 Volts15 15/75 15 15/75 30 75 95 110 115

Temporal High 137 147 79 90 107 176 194 212 218Temporal Medium 132 144 69 80 97 157 182 201 210Temporal Low 132 143 66 77 93 154 179 198 207Non-Temporal High 141 152 91 100 116 176 201 221 229Non-Temporal Medium 133 145 75 85 102 163 187 207 216Non-Temporal Low 131 144 68 79 96 156 182 201 210FWR InputTemporal High 136 155 88 97 112 168 190 210 218Temporal Medium 129 152 78 88 103 160 184 202 206Temporal Low 129 151 76 86 101 160 184 194 201Non-Temporal High 142 161 103 112 126 181 203 221 229Non-Temporal Medium 134 155 85 95 110 166 189 208 216Non-Temporal Low 132 154 80 90 105 161 184 202 211

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)

DC Input16–33 Volts

FWR Input16–33 Volts

135 150 177 185 135 150 177 185Temporal High 245 259 290 297 Temporal High 215 231 258 265Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258Temporal Low 232 251 282 292 Temporal Low 207 221 248 256Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262

UL Max. Horn Current Draw (mA RMS)

Sound Pattern dB8–17.5 Volts 16–33 VoltsDC FWR DC FWR

Temporal High 57 55 69 75Temporal Medium 44 49 58 69Temporal Low 38 44 44 48Non-temporal High 57 56 69 75Non-temporal Medium 42 50 60 69Non-temporal Low 41 44 50 50Coded High 57 55 69 75Coded Medium 44 51 56 69Coded Low 40 46 52 50

UL Current Draw Data

Horn Tones and Sound Output Data

Page 31: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

www.systemsensor.com

©2014 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS10201 • 1/14

SpectrAlert Advance Dimensions

Model DescriptionWall Horn StrobesP2R 2-Wire Horn Strobe, Standard cd, RedP2R-P 2-Wire Horn Strobe, Standard cd, Red, PlainP2R-SP 2-Wire Horn Strobe, Standard cd, Red, “FUEGO”P2RH 2-Wire Horn Strobe, High cd, RedP2RH-P 2-Wire Horn Strobe, High cd, Red, PlainP2W 2-Wire Horn Strobe, Standard cd, WhiteP2W-P 2-Wire Horn Strobe, Standard cd, White, PlainP2WH 2-Wire Horn Strobe, High cd, WhiteP2WH-P 2-Wire Horn Strobe, High cd, White, PlainP4R 4-Wire Horn Strobe, Standard cd, RedP4R-P 4-Wire Horn Strobe, Standard cd, Red, PlainP4RH 4-Wire Horn Strobe, High cd, RedP4W 4-Wire Horn Strobe, Standard cd, WhiteWall StrobesSR Strobe, Standard cd, RedSR-P Strobe, Standard cd, Red, PlainSR-SP Strobe, Standard cd, Red, “FUEGO”

SpectrAlert Advance Ordering Information

Notes:All -P models have a plain housing (no “FIRE” marking on cover)All -SP models have “FUEGO” marking on cover“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.

4.7˝

5.6˝

6.8˝Dia.

2.5˝

2.5˝

Wall-mount horn strobes

Model DescriptionWall Strobes (cont.)SRH Strobe, High cd, RedSRH-P Strobe, High cd, Red, PlainSRH-SP Strobe, High cd, Red, “FUEGO”SW Strobe, Standard cd, WhiteSW-P Strobe, Standard cd, White, PlainSWH Strobe, High cd, WhiteSWH-P Strobe, High cd, White, PlainHornsHR Horn, RedHW Horn, WhiteAccessoriesTR-HS Trim Ring, Wall, RedSBBR Indoor Surface Mount Back Box, RedSBBW Indoor Surface Mount Back Box, White

louis.colosimo
Highlight
Page 32: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Indoor Selectable- Output Speaker Strobes and Dual Voltage Evacuation Speakers for WallApplicationsThe SpectrAlert® Advance selectable output speaker

strobes and dual-voltage evacuation speakers can reduce

ground faults and enable faster installation.

Features

• Plug-in design and protective cover reduce ground faults

• Universal mounting plate with an onboard shorting spring tests wiring continuity before installation

• No extension ring required

• Field selectable candela settings: Standard: 15, 15/75, 30, 75, 95, 110, 115 High: 135, 150, 177, 185

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts)

• SP speakers offer high fidelity sound output

• SPV speakers offer high volume sound output

• Compatible with System Sensor synchronization protocol

• Electrical compatibility with existing SpectrAlert products

• Tamper-resistant construction

• Listed for ceiling or wall mounting

The SpectrAlert Advance Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components.

These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 11 field-selectable candela settings for both wall and ceiling speaker strobes.

The low total harmonic distortion of the SP speaker offers high fidelity sound output while the SPV speaker offers high volume sound output for use in high ambient noise applications.

SpectrAlert Advance makes installation easy• Attach a universal mounting plate to a 4 × 4 × 21⁄8 inch back box .

Flush-mount applications do not require an extension ring.• Connect the notification appliance circuit or speaker wiring to the

terminals on the mounting plate.• Attach the speaker or speaker strobe to the mounting plate by

inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw.

10-08-E7320-1653:201S4048

Page 33: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

SpectrAlert Advance Speaker and Speaker Strobe SpecificationsArchitectural/Engineering Specifications

GeneralSpectrAlert Advance speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150,177, 185.

SpeakerThe speaker shall be a System Sensor SpectrAlert Advance model _______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches.

Speaker Strobe combinationThe speaker strobe shall be a System Sensor SpectrAlert Advance model __________ listed to UL1480 and UL 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Synchronization ModuleThe module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical Specifications

Operating Temperature 32°F to 120°F (0°C to 49°C)

Humidity Range 10 to 93% non-condensing

Dimensions, Wall-Mount Length Width Depth

SP Speaker 6 in, 152 mm 5 in, 127 mm 2.8 in, 71 mmSPV Speaker 6 in, 152 mm 5 in, 127 mm 2.9 in, 74 mmWith Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 3.4 in, 86 mmSPS Speaker/Strobe (including lens and speaker)

6 in, 152 mm 5.1 in, 127 mm 4.7 in, 119 mm

With Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 5.325 in, 135 mmElectrical/Operating Specifications

Nominal Voltage (speakers) 25 Volts or 70.7 Volts (nominal)

Maximum Supervisory Voltage (speakers) 50 VDCStrobe Flash Rate 1 flash per secondNominal Voltage (strobes) Regulated 12 VDC/

FWR or regulated 24 DC/FWR

Operating Voltage Range (includes fire alarm panels with built in sync)

8 to 17.5 V (12 V nominal) or 16 to 33V (24 V nominal)

Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33V (24 V nominal)

Frequency Range 400 to 4000 HzPower ¼, ½, 1, 2 watts

Page 34: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

UL Current Draw DataUL Max. Strobe Current Draw (mA RMS)

Candela

8 to 17.5 Volts 16 to 33 Volts

DC FWR DC FWR

StandardCandela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

Sound OutputUL Reverberant (dBA @ 10 ft.) 2W 1W ½ W ¼ WWall-Mount SP Series 86 83 80 77Wall-Mount SPV Series 90 87 84 81Wall-Mount SPS Series 85 82 79 76Wall-Mount SPSV Series 89 86 83 80

Dimensions

5.00˝.97˝ 1.84˝

5.98˝

5.00˝ 2.83˝1.84˝1.60˝

5.97˝

Wall-Mount SP Speaker Wall-Mount SPS Speaker Strobe

Page 35: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

www.systemsensor.com

©2015 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS11602 • 2/15

Ordering Information for SpectrAlert® Advance Speakers and Speaker StrobesWall MountWhite Red DescriptionSPW SPR Speaker onlySPWV SPRV Speaker only, High dBSPSW SPSR Speaker Strobe, Standard cdSPSW-P SPSR-P Plain Speaker Strobe, Standard cdSPSW-ALERT — Speaker Strobe, Standard cd, Amber LensSPSW-CLR-ALERT — Speaker Strobe, Standard cd, Clear LensSPSWH SPSRH Speaker Strobe, High cdSPSWH-P — Plain Speaker Strobe, High cdSPSWV SPSRV Speaker Strobe, Standard cd, High dBSPSWV-P SPSRV-P Plain Speaker Strobe, Standard cd, High dBAccessoriesWhite Red DescriptionRFPW RFP 7 in × 9.5 in Retrofit PlateSBBSPW SBBSPR Surface Mount Back Box for Speakers and Speaker StrobesTRW TR Wall Mount Trim Ring

Notes:All -P models have a plain housing (no “FIRE” marking on the cover)“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.

Surface Mounting

Wall-Mount Speaker Strobe with SBBSPR Surface Mount Back

louis.colosimo
Highlight
louis.colosimo
Highlight
Page 36: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Features

• Plug-in design with minimal intrusion into the back box

• Tamper-resistant construction

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Field-selectable candela settings on ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Horn rated at 88+ dBA at 16 volts

• Rotary switch for horn tone and three volume selections

• Universal mounting plate for ceiling units

• Mounting plate shorting spring feature checks wiring continuity before device installation

• Electrically Compatible with legacy SpectrAlert devices

• Compatible with MDL3 sync module

• Listed for ceiling or wall mounting

The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement.

Like the entire SpectrAlert Advance product line, ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults.

To further simplify installation, SpectrAlert Advance utilizes a universal mounting plate so you can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed.

Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections.

Indoor Selectable-Output Strobes and Horn Strobes for Ceiling Applications

SpectrAlert® Advance audible visible notification products

are rich with features guaranteed to cut installation times

and maximize profits.

MEA452-05-E3023572

7125-1653:0186 (indoor strobes)7125-1653:0188 (horn strobes,

chime strobes)7135-1653:0189 (horns, chimes)

S4011 (chimes, horn strobes, horns)S5512 (strobes)

Page 37: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS10101

SpectrAlert Advance SpecificationsArchitect/Engineer SpecificationsGeneralSpectrAlert Advance strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185.

StrobeThe strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Horn Strobe CombinationThe horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply.

Synchronization ModuleThe module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical/Electrical SpecificationsStandard Operating Temperature 32°F to 120°F (0°C to 49°C)Humidity Range 10 to 93% non-condensingStrobe Flash Rate 1 flash per secondNominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1

Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal)Input Terminal Wire Gauge 12 to 18 AWGCeiling-Mount Dimensions (including lens) 6.8" diameter × 2.5" high (173 mm diameter × 64 mm high)Ceiling-Mount Surface Mount Back Box Skirt Dimensions (SBBCR, SBBCW)

6.9" diameter x 3.4" high (175 mm diameter x 86 mm high)

Notes:1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.

Page 38: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS10101

Horn Strobe Output (dBA)

Switch Position Sound Pattern dB

8–17.5 Volts

16–33Volts

24-Volt NominalReverberant Anechoic

DC FWR DC FWR DC FWR DC FWR1 Temporal High 78 78 84 84 88 88 99 982 Temporal Medium 74 74 80 80 86 86 96 963 Temporal Low 71 73 76 76 83 80 94 894 Non-Temporal High 82 82 88 88 93 92 100 1005 Non-Temporal Medium 78 78 85 85 90 90 98 986 Non-Temporal Low 75 75 81 81 88 84 96 927† Coded High 82 82 88 88 93 92 101 1018† Coded Medium 78 78 85 85 90 90 97 989† Coded Low 75 75 81 81 88 85 96 92

†Settings 7, 8, and 9 are not available on 2-wire horn strobes.

UL Max. Strobe Current Draw (mA RMS)

Candela8–17.5 Volts 16–33 VoltsDC FWR DC FWR

Standard Candela Range 15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)

DC Input8–17.5 Volts 16–33 Volts15 15/75 15 15/75 30 75 95 110 115

Temporal High 137 147 79 90 107 176 194 212 218Temporal Medium 132 144 69 80 97 157 182 201 210Temporal Low 132 143 66 77 93 154 179 198 207Non-Temporal High 141 152 91 100 116 176 201 221 229Non-Temporal Medium 133 145 75 85 102 163 187 207 216Non-Temporal Low 131 144 68 79 96 156 182 201 210FWR InputTemporal High 136 155 88 97 112 168 190 210 218Temporal Medium 129 152 78 88 103 160 184 202 206Temporal Low 129 151 76 86 101 160 184 194 201Non-Temporal High 142 161 103 112 126 181 203 221 229Non-Temporal Medium 134 155 85 95 110 166 189 208 216Non-Temporal Low 132 154 80 90 105 161 184 202 211

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)

DC Input16–33 Volts

FWR Input16–33 Volts

135 150 177 185 135 150 177 185Temporal High 245 259 290 297 Temporal High 215 231 258 265Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258Temporal Low 232 251 282 292 Temporal Low 207 221 248 256Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262

UL Current Draw Data

Horn Strobe Tones and Sound Output Data

Page 39: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

©2015 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS10102 • 03/15

SpectrAlert Advance Dimensions

Model DescriptionCeiling Horn StrobesPC2R 2-Wire Horn Strobe, Standard cd, RedPC2R-P 2-Wire Horn Strobe, Standard cd, Red, Plain

(no “FIRE”) markingPC2RH 2-Wire Horn Strobe, High cd, RedPC2W 2-Wire Horn Strobe, Standard cd, WhitePC2W-P 2-Wire Horn Strobe, Standard cd, White, Plain

(no “FIRE”) markingPC2W-SP 2-Wire Horn Strobe, Standard cd, White, “Fuego”

markingPC2WH 2-Wire Horn Strobe, High cd, WhitePC2WH-P 2-Wire Horn Strobe, High cd, White, Plain

(no “FIRE”) markingPC2WH-SP 2-Wire Horn Strobe, High cd, White, “Fuego”PC4R 4-Wire Horn Strobe, Standard cd, RedPC4RH 4-Wire Horn Strobe, High cd, RedPC4W 4-Wire Horn Strobe, Standard cd, White

SpectrAlert Advance Ordering Information

Notes:All -P models have a plain housing (no “FIRE” marking on cover)All -SP models have “FUEGO” marking on cover “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.

4.7"

5.6"

6.8"Dia.

2.5"

2.5"

5.703"

1.85"4.8"

6.922"dia.

2.5"

Ceiling-mount horn strobes Ceiling back box surface mount back box

Model DescriptionCeiling StrobesSCR Strobe, Standard cd, RedSCRH Strobe, High cd, RedSCW Strobe, Standard cd, WhiteSCW-P Strobe, Standard cd, White, Plain (no “Fire”) markingSCWH Strobe, High cd, WhiteAccessoriesSBBCR Surface Mount Back Box, Ceiling, Red SBBCW Surface Mount Back Box, Ceiling, White

louis.colosimo
Highlight
louis.colosimo
Highlight
Page 40: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Indoor Selectable-Output Speaker Strobes and Dual Voltage Evacuation Speakers for Ceiling ApplicationsSpectrAlert® Advance selectable-output speaker strobes

and dual-voltage evacuation speakers can reduce ground

faults and enable faster installation.

Features

• Plug-in design and protective cover reduce ground faults

• Universal mounting plate with an onboard shorting spring tests wiring continuity before installation

• No extension ring required

• Field selectable candela settings: Standard: 15, 15/75, 30, 75, 95, 110, 115 High: 135, 150, 177, 185

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts)

• SP speakers offer high fidelity sound output

• SPV speakers offer high volume sound output

• Compatible with System Sensor synchronization protocol

• Electrical compatibility with existing SpectrAlert products

• Tamper-resistant construction

• Listed for ceiling or wall mounting

The SpectrAlert Advance Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components.

These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 11 field-selectable candela settings for both wall and ceiling speaker strobes.

The low total harmonic distortion of the SP speaker offers high fidelity sound output while the SPV speaker offers high volume sound output for use in high ambient noise applications.

SpectrAlert Advance makes installation easy• Attach a universal mounting plate to a 4 × 4 × 21⁄8 inch back box .

Flush-mount applications do not require an extension ring.• Connect the notification appliance circuit or speaker wiring to the

terminals on the mounting plate.• Attach the speaker or speaker strobe to the mounting plate by

inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw.

10-08-E7320-1653:201S4048

Page 41: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

SpectrAlert Advance Speaker and Speaker Strobe SpecificationsArchitectural/Engineering Specifications

GeneralSpectrAlert Advance speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150,177, 185.

SpeakerThe speaker shall be a System Sensor SpectrAlert Advance model _______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches.

Speaker Strobe combinationThe speaker strobe shall be a System Sensor SpectrAlert Advance model __________ listed to UL1480 and UL 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Synchronization ModuleThe module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical Specifications

Operating Temperature 32°F to 120°F (0°C to 49°C)Humidity Range 10 to 93% non-condensingDimensions, Ceiling-Mount

Diameter Depth

SPC Speaker 6.8 in, 173 mm 2.8 in, 71 mmSPCV Speaker 6.8 in, 173 mm 2.9 in, 74 mmWith Surface Mount Back Box 6.9 in, 175 mm 3.4 in, 86 mmSPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 71 mmSPSCV Speaker Strobe 6.8 in, 173 mm 2.9 in, 74 mmWith Surface Mount Back Box 6.9 in, 175 mm 5.325 in, 135 mmElectrical/Operating Specifications

Nominal Voltage (speakers) 25 Volts or 70.7 Volts (nominal)

Maximum Supervisory Voltage (speakers) 50 VDCStrobe Flash Rate 1 flash per secondNominal Voltage (strobes) Regulated 12 V DC/FWR or regulated 24 DC/FWROperating Voltage Range (includes fire alarm panels with built in sync)

8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)

Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)Frequency Range 400 to 4,000 HzPower ¼, ½, 1, 2 watts

Page 42: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

UL Current Draw DataUL Max. Strobe Current Draw (mA RMS)

Candela

8 to 17.5 Volts 16 to 33 Volts

DC FWR DC FWR

StandardCandela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

Sound OutputUL Reverberant (dBA @ 10 ft.) 2W 1W ½ W ¼ WCeiling-Mount SPC Series 86 83 80 77Ceiling-Mount SPCV Series 90 87 84 81Ceiling-Mount SPSC Series 85 82 79 76Ceiling-Mount SPSCV Series 89 86 83 80

Dimensions

6.81˝ .97˝ 1.96˝ 6.81˝ .97˝ 1.84˝

6.81˝ 1.60˝ 1.84˝2.83˝

Ceiling-Mount SPV Speaker Ceiling-Mount SP Speaker

Ceiling-Mount SPS Speaker Strobe

Page 43: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

www.systemsensor.com

©2015 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS11102 • 2/15

Ordering Information for SpectrAlert® Advance Speakers and Speaker StrobesCeiling MountWhite Red DescriptionSPCW SPCR Speaker onlySPCWV SPCRV Speaker only, High dBSPSCW SPSCR Speaker Strobe, Standard cdSPSCW-P — Plain Speaker Strobe, Standard cdSPSCWH SPSCRH Speaker Strobe, High cdSPSCWH-P — Plain Speaker Strobe, High cdSPSCWV SPSCRV Speaker Strobe, Standard cd, High dBSPSCWV-P — Plain Speaker Strobe, High Volume, Clear Lens, WhiteSPSCWVH SPSCRVH Speaker Strobe, High cd, High dBSPSCW-CLR-ALERT — Speaker Strobe, Standard cd, Clear Lens AccessoriesWhite Red DescriptionRFPW RFP 7 in × 9.5 in Retrofit PlateSBBCW SBBCR Surface Mount Back BoxTRCW TRC Ceiling Mount Trim Ring

Notes:All -P models have a plain housing (no “FIRE” marking on cover)“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.

Surface Mounting

Ceiling-Mount Speaker with SBBCR/SBBCW Surface Mount Back Box Skirt

louis.colosimo
Highlight
louis.colosimo
Highlight
Page 44: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Features

• Weatherproof per NEMA 4X, IP56

• Listed to UL 1638 (strobe) and UL 464 (horn)

• Compatible with System Sensor synchronization protocol and legacy SpectrAlert products

• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch for horn tone and three volume selections

• Horn rated at 88+ dBA at 16 volts

• Rated from –40°F to 151°F

• Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed

• Plug-in design with minimal intrusion into the back box

• Tamper-resistant construction

• Listed for ceiling or wall mounting

SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F.

Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements.

Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults.

Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and-out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box.

Outdoor Selectable-Output Horns, Strobes, andHorn Strobes for Wall Applications

SpectrAlert® Advance outdoor audible visible products

are rich with features that cut installation times and

maximize profits.

MEA452-05-E3023572

7300-1653:187 (outdoor strobes)7125-1653:188 (horn strobes,

chime strobes)7135-1653:189 (horns, chimes)

S4011 (chimes, horn strobes, horns)S3593 (outdoor and alert strobes)

Page 45: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS01201

SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe SpecificationsArchitect/Engineer SpecificationsGeneralSpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185.

StrobeThe strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments.

Horn Strobe CombinationThe horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments.

Physical/Electrical SpecificationsOperating Temperature –40°F to 151°F (–40°C to 66°C)Strobe Flash Rate 1 flash per secondNominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1

Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)Input Terminal Wire Gauge 12 to 18 AWGWall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)Wall-Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D)Notes:1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.

Page 46: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS01201

Horn and Horn Strobe Output (dBA)

Switch Position

Sound Pattern dB

8–17.5 Volts

16–33Volts

24-Volt NominalReverberant Anechoic

DC FWR DC FWR DC FWR DC FWR1 Temporal High 78 78 84 84 88 88 99 982 Temporal Medium 74 74 80 80 86 86 96 963 Temporal Low 71 73 76 76 83 80 94 894 Non-

TemporalHigh

82 82 88 88 93 92 100 100

5 Non-Temporal

Medium78 78 85 85 90 90 98 98

6 Non-Temporal

Low75 75 81 81 88 84 96 92

7† Coded High 82 82 88 88 93 92 101 1018† Coded Medium 78 78 85 85 90 90 97 989† Coded Low 75 75 81 81 88 85 96 92

†Settings 7, 8, and 9 are not available on 2-wire horn strobe.

UL Max. Strobe Current Draw (mA RMS)

Candela8–17.5 Volts 16–33 VoltsDC FWR DC FWR

Standard Candela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)

DC Input8–17.5 Volts 16–33 Volts15 15/75 15 15/75 30 75 95 110 115

Temporal High 137 147 79 90 107 176 194 212 218Temporal Medium 132 144 69 80 97 157 182 201 210Temporal Low 132 143 66 77 93 154 179 198 207Non-Temporal High 141 152 91 100 116 176 201 221 229Non-Temporal Medium 133 145 75 85 102 163 187 207 216Non-Temporal Low 131 144 68 79 96 156 182 201 210FWR InputTemporal High 136 155 88 97 112 168 190 210 218Temporal Medium 129 152 78 88 103 160 184 202 206Temporal Low 129 151 76 86 101 160 184 194 201Non-Temporal High 142 161 103 112 126 181 203 221 229Non-Temporal Medium 134 155 85 95 110 166 189 208 216Non-Temporal Low 132 154 80 90 105 161 184 202 211

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)

DC Input16–33 Volts

FWR Input16–33 Volts

135 150 177 185 135 150 177 185Temporal High 245 259 290 297 Temporal High 215 231 258 265Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258Temporal Low 232 251 282 292 Temporal Low 207 221 248 256Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262

UL Max. Horn Current Draw (mA RMS)

Sound Pattern dB8–17.5 Volts 16–33 VoltsDC FWR DC FWR

Temporal High 57 55 69 75Temporal Medium 44 49 58 69Temporal Low 38 44 44 48Non-Temporal High 57 56 69 75Non-Temporal Medium 42 50 60 69Non-Temporal Low 41 44 50 50Coded High 57 55 69 75Coded Medium 44 51 56 69Coded Low 40 46 52 50

UL Current Draw Data

Horn Tones and Sound Output DataCandela DeratingFor K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table.

Strobe Output (cd)Listed Candela Candela rating at –40°F15

Do not use below 32°F15/753075 4495 70110 110115 115135 135150 150177 177185 185

Page 47: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

©2012 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS01201 • 3/12

SpectrAlert Advance Diagrams

Model DescriptionWall Horn StrobesP2RK*† 2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)P2RHK*† 2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)P2WK*† 2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)P2WHK*† 2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)P4RK† 4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box)Wall StrobesSRK*† Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)SRHK*† Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)SWK*† Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)SWHK*† Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)HornsHRK† Horn, Red, Outdoor (includes plastic weatherproof back box)AccessoriesSA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box

SpectrAlert Advance Ordering Information

Notes:* Add “-P” to model number for plain housing (no “FIRE” marking on cover), e.g., P2RK-P.† Add “-R” to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW.“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced.

4.7˝

5.6˝

6.8˝Dia.

2.5˝

2.5˝

Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box

Wall-Mount Horn Strobe with Plastic Weatherproof Back Box

louis.colosimo
Highlight
Page 48: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Outdoor, Selectable- Output Speaker Strobes and Dual-Voltage Evacuation Speakers for WallApplicationsSpectrAlert® Advance outdoor, selectable-output speaker

strobes and dual-voltage evacuation speakers meet

virtually any outdoor application requirement.

Features

• Weatherproof per NEMA 4X, IP56

• Rated from -40°F to 151°F

• Plug-in design reduces ground faults

• Universal mounting plate with onboard shorting spring that tests wiring continuity before devices are installed

• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch for speaker voltage (25 and 70.7 Vrms) and power settings (1/4, 1/2, 1 and 2 watts)

• Compatible with System Sensor synchronization protocol and legacy SpectrAlert products

• Tamper-resistant construction

• Listed for ceiling or wall mounting

SpectrAlert Advance offers the broadest line of outdoor speakers and speaker strobes in the industry. From metal and plastic outdoor back boxes, to white and red plastic housings, to wall and ceiling mounting options, SpectrAlert Advance can meet virtually any application requirement.

Wall-mount outdoor speakers and speaker strobes can be used indoors or outdoors in wet or dry applications, and can provide reliable operation from −40°F to 151°F. These speakers provide a broad frequency response range, low harmonic distortion and maintain a high sound pressure level at all tap settings to provide accurate and intelligible broadcast of evacuation messages.

Like the entire SpectrAlert Advance line, wall-mount outdoor speakers and speaker strobes include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, speaker voltage and power settings, and automatic selection of 12- or 24-volt operation enable installers to easily adapt devices to meet requirements.

Next, these devices use a universal mounting plate with an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults.

Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and-out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box.10-08-E7320-1653:20175S0

Page 49: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS11301

SpectrAlert® Advance Outdoor Speaker and Speaker Strobe SpecificationsArchitectural/Engineering Specifications

GeneralSpectrAlert Advance outdoor speakers and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between –40°F and 151°F from a regulated DC, or full-wave rectified, unfiltered power supply.

SpeakerSpeaker shall be a System Sensor SpectrAlert Advance Model ______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. Speaker shall be listed to Underwriters Laboratories Standard S4048 for outdoor fire protective signaling systems. Speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature from –40°F to 150.8°F. Speaker shall have power taps and wattage settings that are selected by rotary switches. The speaker must be installed with its weatherproof back box in order to remain outdoor approved per UL listing S4048. The speaker shall be suitable for use in air handling spaces and wet environments.

Speaker Strobe CombinationThe speaker strobe shall be a System Sensor Model _____ listed to UL 1638 and UL 1480 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms and shall have a frequency range of 400 to 4,000 Hz. Speaker shall have power taps that are selected by rotary switch. The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12 or 24 volts. The strobe shall also feature selectable candela output, providing options for 15 or 15/75 candela when operating on 12 volts and 15, 15/75, 30, 75, 110, 115, 135, 150, 177 or 185 candela when operating on 24 volts. The strobe shall comply with the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The speaker strobe shall be suitable for use in wet environments.

Physical Specifications

Operating Temperature –40°F to 151°F (–40°C to 66°C)Dimensions, Wall-Mount

SPS Speaker Strobe 6.0˝ L × 5.0˝ W × 4.7˝ D (including lens and speaker)SP Speaker 6.0˝ L × 5.0˝ W × 2.9˝ D

Dimensions, Wall-Mount Weatherproof Back Box 6.5˝ L × 5.5˝ H × 2.9˝ DElectrical/Operating Specifications

Nominal Voltage (speakers) 25 V or 70.7 V (nominal)Maximum Supervisory Voltage (speakers) 50 VDCStrobe Flash Rate 1 flash per secondNominal Voltage (strobes) Regulated 12 VDC/FWR or regulated 24 DC/FWROperating Voltage Range (includes fire alarm panels with built in sync)

8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)

Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)Frequency Range 400 to 4,000 HzPower ¼, ½, 1, 2 watts

Page 50: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS11301

UL Current Draw DataUL Max. Strobe Current Draw (mA RMS)

Candela

8 to 17.5 Volts 16 to 33 Volts

DC FWR DC FWR

StandardCandela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

Sound OutputUL Reverberant (dBA @ 10 ft.) 2W 1W ½ W ¼ WOutdoor Speaker 90 87 84 81Outdoor Speaker/Strobe 89 86 83 80

Dimensions

Candela DeratingFor K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table.

Strobe Output (cd)

Listed CandelaCandela rating at –40°F

15Do not use below 32°F15/75

3075 4495 70110 110115 115135 135150 150177 177185 185

5.00˝.97˝ 1.84˝

5.98˝

5.00˝ 2.83˝1.84˝1.60˝

5.97˝

Wall-Mount Outdoor Speaker Wall-Mount Outdoor Speaker Strobe

Page 51: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495

©2012 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS11301 • 09/12

Ordering Information for SpectrAlert® Advance Outdoor Speakers and Speaker StrobesWall MountWhite Red DescriptionSPWK SPRK Outdoor Speaker (includes plastic weatherproof back box)SPWK-R SPRK-R Outdoor Speaker (does not include plastic weatherproof back box)SPSWK SPSRK Outdoor Speaker Strobe, Standard cd (includes plastic weatherproof back box)SPSWK-P SPSRK-P Plain Outdoor Speaker Strobe, Standard cd(includes plastic weatherproof back box)SPSWK-R SPSRK-R Outdoor Speaker Strobe, Standard cd(does not include weatherproof back box)SPSWK-CLR-ALERT — Outdoor Speaker Strobe, Standard cd, Clear Lens, ALERT Printed

(includes plastic weatherproof back box)— SPSRHK Outdoor Speaker Strobe, High cd (135,150,177,185) (includes plastic weatherproof back box)AccessoriesWhite Red DescriptionMWBBW MWBB Wall, Metal Weatherproof Back Box

Notes: All -P models have a plain housing (no “FIRE” marking on cover)“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units, both the device and back box must be replaced.

Surface Mounting

Wall-Mount Speaker Strobe with Plastic Weatherproof Back Box

Wall-Mount Speaker Strobe with Metal Weatherproof Back Box

Wall-Mount Speaker with Plastic Weatherproof Back Box

Wall-Mount Speaker with Metal Weatherproof Back Box

louis.colosimo
Highlight
louis.colosimo
Highlight
Page 52: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

Agency Listings

Outdoor, Selectable-Output Speaker Strobes and Dual-Voltage Evacuation Speakers for Ceiling ApplicationsSpectrAlert® Advance outdoor audible visible products

are rich with features that cut installation times and

maximize profits.

Features

• Weatherproof per NEMA 4X, IP56

• Rated from –40°F to 151°F

• Plug-in design reduces ground faults

• Universal mounting plate with onboard shorting spring that tests wiring continuity before devices are installed

• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch for speaker voltage (25 and 70.7 Vrms) and power settings (1/4, 1/2, 1 and 2 watts)

• Compatible with System Sensor synchronization protocol and legacy SpectrAlert products

• Tamper-resistant construction

• Listed for ceiling or wall mounting

SpectrAlert Advance offers the broadest line of outdoor speakers and speaker strobes in the industry. From metal and plastic outdoor back boxes, to white and red plastic housings, to wall and ceiling mounting options, SpectrAlert Advance can meet virtually any application requirement.

Ceiling-mount outdoor speakers and speaker strobes can be used indoors or outdoors in wet or dry applications, and can provide reliable operation from −40°F to 151°F. These speakers provide a broad frequency response range, low harmonic distortion and maintain a high sound pressure level at all tap settings to provide accurate and intelligible broadcast of evacuation messages.

Like the entire SpectrAlert Advance line, ceiling-mount outdoor speakers and speaker strobes include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, speaker voltage and power settings, and automatic selection of 12- or 24-volt operation enable installers to easily adapt devices to meet requirements.

Next, these devices use a universal mounting plate with an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults.

Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and-out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box.10-08-E7320-1653:20175S0

Page 53: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS00901

SpectrAlert® Advance Outdoor Speaker and Speaker Strobe SpecificationsArchitectural/Engineering Specifications

GeneralSpectrAlert Advance outdoor speakers and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between –40°F and 151°F from a regulated DC, or full-wave rectified, unfiltered power supply.

SpeakerSpeaker shall be a System Sensor SpectrAlert Advance Model ______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. Speaker shall be listed to Underwriters Laboratories Standard S4048 for outdoor fire protective signaling systems. Speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature from –40°F to 150.8°F. Speaker shall have power taps and wattage settings that are selected by rotary switches. The speaker must be installed with its weatherproof back box in order to remain outdoor approved per UL listing S4048. The speaker shall be suitable for use in air handling spaces and wet environments.

Speaker Strobe CombinationThe speaker strobe shall be a System Sensor Model _____ listed to UL 1638 and UL 1480 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms and shall have a frequency range of 400 to 4,000 Hz. Speaker shall have power taps that are selected by rotary switch. The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12 or 24 volts. The strobe shall also feature selectable candela output, providing options for 15 or 15/75 candela when operating on 12 volts and 15, 15/75, 30, 75, 110, 115, 135, 150, 177 or 185 candela when operating on 24 volts. The strobe shall comply with the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The speaker strobe shall be suitable for use in wet environments.

Physical Specifications

Operating Temperature –40°F to 151°F (–40°C to 66°C)Dimensions, Ceiling-Mount

SPS Speaker Strobe 6.8˝ Dia. × 4.7˝ D (including lens and speaker)SP Speaker 6.8˝ Dia. × 2.9˝ D

Dimensions, Ceiling-Mount Weatherproof Back Box

7.2˝ Dia. × 2.9˝ D

Electrical/Operating Specifications

Nominal Voltage (speakers) 25 V or 70.7 V (nominal)Maximum Supervisory Voltage (speakers) 50 VDCStrobe Flash Rate 1 flash per secondNominal Voltage (strobes) Regulated 12 VDC/FWR or regulated 24 DC/FWROperating Voltage Range (includes fire alarm panels with built in sync)

8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)

Operating Voltage with MDL Sync Module 9 to 17.5 V (12 V nominal) or 17 to 33 V (24 V nominal)Frequency Range 400 to 4,000 HzPower ¼, ½, 1, 2 watts

Page 54: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

AVDS00901

UL Current Draw DataUL Max. Strobe Current Draw (mA RMS)

Candela

8 to 17.5 Volts 16 to 33 Volts

DC FWR DC FWR

StandardCandela Range

15 123 128 66 7115/75 142 148 77 8130 NA NA 94 9675 NA NA 158 15395 NA NA 181 176110 NA NA 202 195115 NA NA 210 205

HighCandela Range

135 NA NA 228 207150 NA NA 246 220177 NA NA 281 251185 NA NA 286 258

Sound OutputUL Reverberant (dBA @ 10 ft.) 2W 1W ½ W ¼ WOutdoor Speaker 90 87 84 81Outdoor Speaker/Strobe 89 86 83 80

Dimensions

Candela DeratingFor K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table.

Strobe Output (cd)

Listed CandelaCandela rating at –40°F

15Do not use below 32°F15/75

3075 4495 70110 110115 115135 135150 150177 177185 185

7.19˝

7.14˝

.97˝ 2.83˝ 7.19˝

7.14˝

1.60˝2.83˝ 2.83˝

Ceiling-Mount Outdoor Speaker Ceiling-Mount Outdoor Speaker Strobe

Page 55: Pompano Pet Lodge - RedTeam Software · 2017. 1. 26. · FireWarden-100-2(E) Intelligent Addressable FACP with Built-In Communciator Addressable DN-7101:A • A1-110 7101cov.jpg General

3825 Ohio Avenue • St. Charles, IL 60174Phone: 800-SENSOR2 • Fax: 630-377-6495

©2012 System Sensor.Product specifications subject to change without notice. Visit systemsensor.com

for current product information, including the latest version of this data sheet.AVDS00901 • 03/12

Ordering Information for SpectrAlert® Advance Outdoor Speakers and Speaker StrobesCeiling MountWhite Red DescriptionSPCWK — Outdoor Speaker (includes plastic weatherproof back box)SPSCWK — Outdoor Speaker Strobe, Standard cd, (includes plastic weatherproof back box)SPSCWHK — Outdoor Speaker Strobe, High cd (includes plastic weatherproof back box)SPSCWHK-P — Outdoor Speaker Strobe, High cd, PLAIN; (includes plastic weatherproof back box)SPSCWK-CLR-ALERT

— Outdoor Speaker Strobe, Selectable Candela, Clear Lens, ALERT Printed; (includes plastic weatherproof back box)

AccessoriesWhite Red DescriptionMWBBCW — Ceiling, Metal Weatherproof Back Box

Notes:“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units, both the device and back box must be replaced.

Surface Mounting

Ceiling-Mount Speaker with Plastic Weatherproof Back Box

Ceiling-Mount Speaker with Metal Weatherproof Back Box

Ceiling-Mount Speaker Strobe with Plastic Weatherproof Back Box

Ceiling-Mount Speaker Strobe with Metal Weatherproof Back Box