Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Point List ManualDNP 3.0REF615
Document ID: 1MRS756711Issued: 04.03.2009
Revision: AProduct version: 2.0
© Copyright 2009 ABB. All rights reserved
CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.
TrademarksABB is a registered trademark of ABB Group. All other brand or product namesmentioned in this document may be trademarks or registered trademarks of theirrespective holders.
GuaranteePlease inquire about the terms of guarantee from your nearest ABB representative.
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation
DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirements arecomplied with. In particular, any risks in applications where a system failure and/orproduct failure would create a risk for harm to property or persons (including but notlimited to personal injuries or death) shall be the sole responsibility of the person orentity applying the equipment, and those so responsible are hereby requested to ensurethat all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from theuse of this manual or the application of the equipment.
ConformityThis product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Council Directive 2004/108/EC) and concerning electricalequipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of a test conducted by ABB in accordance withArticle 10 of the directive in agreement with the product standards EN 50263 and EN60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN60255-27 for the low voltage directive. The IED is designed in accordance with theinternational standards of the IEC 60255 series.
Table of contents
Section 1 Introduction.......................................................................3This manual........................................................................................3Intended audience..............................................................................3Protocol documentation......................................................................4
Product documentation set............................................................4Document revision history.............................................................5Related documentation..................................................................5
Document symbols and conventions..................................................6Safety indication symbols..............................................................6Document conventions..................................................................6Functions, codes and symbols......................................................7
Section 2 DNP 3.0 data mappings...................................................9Overview.............................................................................................9Point list for REF615 Ver. 2.0 FE01-06..............................................9
Section 3 DNP 3.0 protocol implementation...................................17DNP 3.0 device profile......................................................................17DNP 3.0 implementation table..........................................................19
Section 4 Glossary.........................................................................23
Table of contents
REF615 1Point List Manual
2
Section 1 Introduction
1.1 This manual
Point List Manual describes the outlook and properties of the data points specific tothe IED. The manual should be used in conjunction with the correspondingCommunication Protocol Manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integratorresponsible for pre-engineering and engineering for communication setup in asubstation from an IED perspective.
The system engineer or system integrator must have a basic knowledge ofcommunication in protection and control systems and thorough knowledge of thespecific communication protocol.
1MRS756711 A Section 1Introduction
REF615 3Point List Manual
1.3 Protocol documentation
1.3.1 Product documentation set
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocolmanual
Technical manual
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manualApplication manual
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
Engineering manualEngineering manual
Commissioning manualCommissioning manual
Communication protocolmanualCommunication protocolmanual
Technical manualTechnical manual
en07000220.vsd
IEC07000220 V1 EN
Engineering Manual contains instructions on how to engineer the IEDs. The manualprovides instructions on how to use the different tools for IED engineering. It alsoincludes instructions on how to handle the tool component available to readdisturbance files from the IEDs on the basis of the IEC 61850 definitions. It furtherintroduces the diagnostic tool components available for IEDs and the PCM600 tool.
Installation Manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in chronological order in which the IED should be installed.
Commissioning Manual contains instructions on how to commission the IED. Themanual can also be used as a reference during periodic testing. The manual providesprocedures for energizing and checking of external circuitry, setting andconfiguration as well as verifying settings and performing directional tests. Thechapters are organized in chronological order in which the IED should becommissioned.
Section 1 1MRS756711 AIntroduction
4 REF615Point List Manual
Operation Manual contains instructions on how to operate the IED during normalservice once it has been commissioned. The manual can be used to find out how tohandle disturbances or how to view calculated and measured network data todetermine the cause of a fault.
Service Manual contains instructions on how to service and maintain the IED. Themanual also provides procedures for de-energizing, de-commissioning and disposalof the IED.
Application Manual contains application descriptions and setting guidelines sortedper function. The manual can be used to find out when and for what purpose a typicalprotection function can be used. The manual can also be used when calculatingsettings.
Technical Manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.
Communication Protocol Manual describes a communication protocol supported bythe IED. The manual concentrates on vendor-specific implementations.
Point List Manual describes the outlook and properties of the data points specific tothe IED. The manual should be used in conjunction with the correspondingCommunication Protocol Manual.
All manuals are not available yet.
1.3.2 Document revision historyDocument revision/date Product version HistoryA/04.03.2009 2.0 First release
Download the latest revision of the document from the ABB web sitehttp://www.abb.com/substationautomation.
1.3.3 Related documentationName of the document Document IDDNP 3.0 Communication Protocol Manual 1MRS756709
1MRS756711 A Section 1Introduction
REF615 5Point List Manual
1.4 Document symbols and conventions
1.4.1 Safety indication symbolsThis publication includes icons that point out safety-related conditions or otherimportant information.
The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.
The warning icon indicates the presence of a hazard which couldresult in personal injury.
The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence ofa hazard which could result in corruption of software or damage toequipment or property.
The information icon alerts the reader to relevant facts and conditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood thatoperation of damaged equipment could, under certain operational conditions, resultin degraded process performance leading to personal injury or death. Therefore,comply fully with all warning and caution notices.
1.4.2 Document conventions• Abbreviations and acronyms in this manual are spelled out in Glossary. Glossary
also contains definitions of important terms.• Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:To navigate between the options, use and .
• HMI menu paths are presented in bold, for example:Select Main menu/Configuration/HMI.
• Menu names are shown in bold in WHMI, for example:Click Information in the WHMI menu structure.
Section 1 1MRS756711 AIntroduction
6 REF615Point List Manual
• LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font,for example:When the function starts, the START output is set to TRUE.
1.4.3 Functions, codes and symbolsAll available functions are listed in the table. All of these may not be applicable toall products.
Table 1: Functions included in standard configurations
Function IEC 61850 IEC 60617 IEC-ANSIThree-phase non-directionalovercurrent protection
PHLPTOC1 3I> 51P-1
PHHPTOC1 3I>> (1) 51P-2 (1)
PHHPTOC2 3I>> (2) 51P-2 (2)
PHIPTOC1 3I>>> 50P/51P
Three-phase directional overcurrent,low stage
DPHLPDOC1 3I> → (1) 67-1 (1)
DPHLPDOC2 3I> → (2) 67-1 (2)
Three-phase directional overcurrent,high stage
DPHHPDOC1 3I>> → 67-2
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Non-directional earth-fault protection EFLPTOC1 I0> (1) 51N-1 (1)
EFLPTOC2 I0> (2) 51N-1 (2)
EFHPTOC1 I0>> 51N-2
EFIPTOC1 I0>>> 50N/51N
Directional earth-fault protection DEFLPDEF1 I0> → (1) 67N-1 (1)
DEFLPDEF2 I0> → (2) 67N-1 (2)
DEFHPDEF1 I0>> → 67N-2
Transient/Intermittent earth-faultprotection
INTRPTEF1 I0> → IEF 67NIEF
Non-directional (cross-country) earthfault, using calculated I0
EFHPTOC1 I0>> 51N-2
Negative-sequence overcurrentprotection
NSPTOC1 I2> (1) 46 (1)
NSPTOC2 I2> (2) 46 (2)
Phase discontinuity PDNSPTOC1 I2/I1> 46PD
Table continues on next page
1MRS756711 A Section 1Introduction
REF615 7Point List Manual
Function IEC 61850 IEC 60617 IEC-ANSIResidual overvoltage protection ROVPTOV1 U0> (1) 59G (1)
ROVPTOV2 U0> (2) 59G (2)
ROVPTOV3 U0> (3) 59G (3)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
PHPTUV2 3U< (2) 27 (2)
PHPTUV3 3U< (3) 27 (3)
Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)
PHPTOV2 3U> (2) 59 (2)
PHPTOV3 3U> (3) 59 (3)
Positive-sequence undervoltage PSPTUV1 U1< 47U+
Negative-sequence overvoltage NSPTOV1 U2> 47O-
Three-phase inrush detector INRPHAR1 3I2f> 68
Three-phase thermal protection forfeeders, cables and distributiontransformers
T1PTTR1 3Ith>F 49F
Autoreclosure DARREC1 O → I 79
Circuit breaker failure protection CCBRBRF1 3I>/I0>BF 51BF/51NBF
Master Trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Fuse failure supervision SEQRFUF1 FUSEF 60
Disturbance recorder RDRE1 - -
Circuit breaker condition monitoring SSCBR1 CBCM CBCM
Three-phase current measurement CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement RESCMMXU1 I0 In
Residual voltage measurement RESVMMXU1 U0 Vn
Three-phase voltage measurement VMMXU1 3U 3U
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energymeasurement
PEMMXU1 P, E P, E
Section 1 1MRS756711 AIntroduction
8 REF615Point List Manual
Section 2 DNP 3.0 data mappings
2.1 Overview
This document describes the DNP 3.0 data points and structures available inREF615 Ver. 2.0. The data points are unmapped as a default. The point lists describea superset of all data available through the standard configurations A, B, C, D, E andF including the optional functionalities. The names of the standard configurations areFE01, FE02, FE03, FE04, FE05 and FE06 respectively.
2.2 Point list for REF615 Ver. 2.0 FE01-06
The point tables show all the available DNP 3.0 data points in this IED. The dataobjects in the point tables are listed in alphabetical order based on their objects'IEC61850 names. The DNP 3.0 points can be freely added, removed, reorganizedand reconfigured using PCM600.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and Class0 and Class 2 for analog inputs. Analog values are provided with default scalings.The scalings can be freely be modified by the user.
This list represents the superset of DNP 3.0 points. The actual set of available pointsis determined by IED's ordercode.
Table 2: Binary inputs
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DAName ValuesArc protection
ARCPTRC11.Op.general ARCSARC1, Operate, general 1 = OperateARCPTRC21.Op.general ARCSARC2, Operate, general 1 = OperateARCPTRC31.Op.general ARCSARC3, Operate, general 1 = OperateARCSARC11.FADet.stVal ARCSARC1, Fault arc detected, stVal 1 = Fault arc detectedARCSARC11.InRemFA.stVal ARCSARC1, Remote fault arc detected, stVal 1 = Fault arc detectedARCSARC21.FADet.stVal ARCSARC2, Fault arc detected, stVal 1 = Fault arc detectedARCSARC21.InRemFA.stVal ARCSARC2, Remote fault arc detected, stVal 1 = Fault arc detectedARCSARC31.FADet.stVal ARCSARC3, Fault arc detected, stVal 1 = Fault arc detectedARCSARC31.InRemFA.stVal ARCSARC3, Remote fault arc detected, stVal 1 = Fault arc detected
Circuit breaker related signals (CB pos is found in AI)CBCILO1.EnaCls.stVal CBXCBR1, ENA_CLOSE, stVal 1 = Close enabledCBCILO1.EnaOpn.stVal CBXCBR1, ENA_OPEN, stVal 1 = Open enabledCBCSWI1.Pos.stSeld CBXCBR1, Switch, general, stSeld 1 = CB control selectedCBXCBR1.BlkCls.stVal CBXCBR1, Block closing, stVal 1 = Close blockedCBXCBR1.BlkOpn.stVal CBXCBR1, Block opening, stVal 1 = Open blocked
Circuit breaker failure protection
Table continues on next page
1MRS756711 A Section 2DNP 3.0 data mappings
REF615 9Point List Manual
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DAName ValuesCCBRBRF1.InCBFlt.stVal CCBRBRF1, CB faulty and unable to trip, stVal 1 = CB faultyCCBRBRF1.InPosCls.stVal CCBRBRF1, CB in closed position, stVal 1 = CB closedCCBRBRF1.InStr.stVal CCBRBRF1, CBFP start command, stVal 1 = CBFP startCCBRBRF1.OpEx.general CCBRBRF1, Breaker failure trip (external trip), general 1 = Breaker failure tripCCBRBRF1.OpIn.general CCBRBRF1, Operate, re-trip (internal trip), general 1 = Operate, re-tripCCBRBRF1.Str.general CCBRBRF1, Start, timer running, general 1 = Start, timer running
Current circuit supervisionCCRDIF1.Alm.stVal CCRDIF1, Alarm, stVal 1 = AlarmCCRDIF1.Op.general CCRDIF1, Detection of current circuit failure, general 1 = Failure
Three-phase current limit supervisionCMMXU1.HiAlm.stVal CMMXU1, High alarm, stVal 1 = High alarmCMMXU1.HiWrn.stVal CMMXU1, High warning, stVal 1 = High warningCMMXU1.LoAlm.stVal CMMXU1, Low alarm, stVal 1 = Low alarmCMMXU1.LoWrn.stVal CMMXU1, Low warning, stVal 1 = Low warning
Autoreclosing signalsDARREC1.ActRec.stVal DARREC1, Active reclose status, stVal 1 = AR activeDARREC1.AROn.stVal DARREC1, AR switched on, stVal 1 = AR switched ONDARREC1.CBManCls.stVal DARREC1, CB manually closed, stVal 1 = CB manually closedDARREC1.FrqOpAlm.stVal DARREC1, Frequent operation counter alarm, stVal 1 = Freq. operation alarmDARREC1.InBlkThm.stVal DARREC1, Thermal block (status), stVal 1 = Thermal blockDARREC1.InInhRec.stVal DARREC1, Inhibit reclose (status), stVal 1 = Inhibit recloseDARREC1.LO.stVal DARREC1, Lockout status, stVal 1 = Lockout statusDARREC1.Op.general DARREC1, Operate (close command to XCBR), general 1 = Operate, close CBDARREC1.OpOpn.general DARREC1, Operate (open command to XCBR), general 1 = Operate, open CBDARREC1.PrgCutOut.stVal DARREC1, Cutout time in progress, stVal 1 = Cutout time in progressDARREC1.PrgDsr.stVal DARREC1, Discrimination time in progress, stVal 1 = Discr time in progressDARREC1.PrgRec.stVal DARREC1, In progress status, stVal 1 = AR in progressDARREC1.PrgRec1.stVal DARREC1, In progress 1st reclose, stVal 1 = 1st reclose in progressDARREC1.PrgRec2.stVal DARREC1, In progress 2nd reclose, stVal 1 = 2nd reclose in progressDARREC1.PrgRec3.stVal DARREC1, In progress 3rd reclose, stVal 1 = 3rd reclose in progressDARREC1.PrgRec4.stVal DARREC1, In progress 4th reclose, stVal 1 = 4th reclose in progressDARREC1.PrgRec5.stVal DARREC1, In progress 5th reclose, stVal 1 = 5th reclose in progressDARREC1.ProCrd.stVal DARREC1, Protection coordination, stVal 1 = Prot coordinationDARREC1.RclTmStr.stVal DARREC1, Reclaim time started, stVal 1 = Reclaim time startedDARREC1.RdyRec.stVal DARREC1, Ready reclose status, stVal 1 = Reclose readyDARREC1.SucRec.stVal DARREC1, Successful reclose status, stVal 1 = Successful recloseDARREC1.UnsCBCls.stVal DARREC1, Unsuccessful CB closing status, stVal 1 = Unsuccessful CB closingDARREC1.UnsRec.stVal DARREC1, Unsuccessful reclose status, stVal 1 = Unsuccessful recloseDARREC1.WtMstr.stVal DARREC1, Master signal to follower, stVal 1 = Master signal to follower
Directional earth-fault protectionDEFHPTOC1.Op.general DEFHPDEF1, Operate, general 1 = OperateDEFHPTOC1.Str.general DEFHPDEF1, Start, general 1 = StartDEFLPTOC1.Op.general DEFLPDEF1, Operate, general 1 = OperateDEFLPTOC1.Str.general DEFLPDEF1, Start, general 1 = StartDEFLPTOC2.Op.general DEFLPDEF2, Operate, general 1 = OperateDEFLPTOC2.Str.general DEFLPDEF2, Start, general 1 = StartDPHHPTOC1.Op.general DPHHPDOC1, Operate, general 1 = OperateDPHHPTOC1.Str.general DPHHPDOC1, Start, general 1 = Start
Directional overcurrent protectionDPHLPTOC1.Op.general DPHLPDOC1, Operate, general 1 = OperateDPHLPTOC1.Str.general DPHLPDOC1, Start, general 1 = StartDPHLPTOC2.Op.general DPHLPDOC2, Operate, general 1 = OperateDPHLPTOC2.Str.general DPHLPDOC2, Start, general 1 = Start
Table continues on next page
Section 2 1MRS756711 ADNP 3.0 data mappings
10 REF615Point List Manual
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DAName ValuesNon-directional earth-fault and sensitive earth-fault protection
EFHPTOC1.Op.general EFHPTOC1, Operate, general 1 = OperateEFHPTOC1.Str.general EFHPTOC1, Start, general 1 = StartEFIPTOC1.Op.general EFIPTOC1, Operate, general 1 = OperateEFIPTOC1.Str.general EFIPTOC1, Start, general 1 = StartEFLPTOC1.Op.general EFLPTOC1, Operate, general 1 = OperateEFLPTOC1.Str.general EFLPTOC1, Start, general 1 = StartEFLPTOC2.Op.general EFLPTOC2, Operate, general 1 = OperateEFLPTOC2.Str.general EFLPTOC2, Start, general 1 = Start
Three-phase inrush detectionINRPHAR1.Str.general INRPHAR1, Start, general 1 = Start, generalINRPHAR1.Str.phsA INRPHAR1, Start, phsA 1 = Start, phsAINRPHAR1.Str.phsB INRPHAR1, Start, phsB 1 = Start, phsBINRPHAR1.Str.phsC INRPHAR1, Start, phsC 1 = Start, phsC
Transient/intermittent earth-fault protectionINTRPTEF1.Op.general INTRPTEF1, Operate, general 1 = OperateINTRPTEF1.Str.general INTRPTEF1, Start, general 1 = Start
Alarm LED StatesLEDGGIO1.SPCSO1.stVal Alarm LEDs, LED 1, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO2.stVal Alarm LEDs, LED 2, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO3.stVal Alarm LEDs, LED 3, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO4.stVal Alarm LEDs, LED 4, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO5.stVal Alarm LEDs, LED 5, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO6.stVal Alarm LEDs, LED 6, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO7.stVal Alarm LEDs, LED 7, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO8.stVal Alarm LEDs, LED 8, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO9.stVal Alarm LEDs, LED 9, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO10.stVal Alarm LEDs, LED 10, stVal 1 = ON, 0 = OFFLEDGGIO1.SPCSO11.stVal Alarm LEDs, LED 11, stVal 1 = ON, 0 = OFF
Global conditioningLEDPTRC1.Op.general Global conditioning, Operate, general 1 = OperateLEDPTRC1.Str.general Global conditioning, Start, general 1 = Start
Local/remote (also present in IIN)LLN0.Loc.stVal Control LLN0, Local / remote, stVal 1 = LocalLLN0.Loc1.stVal Control LLN0, Local / off, stVal 1 = Off
Negative sequence overcurrent protectionNSPTOC1.Op.general NSPTOC1, Operate, general 1 = OperateNSPTOC1.Str.general NSPTOC1, Start, general 1 = StartNSPTOC2.Op.general NSPTOC2, Operate, general 1 = OperateNSPTOC2.Str.general NSPTOC2, Start, general 1 = Start
Negative sequence overvoltage protectionNSPTOV1.Op.general NSPTOV1, Operate, general 1 = OperateNSPTOV1.Str.general NSPTOV1, Start, general 1 = Start
Phase discontinuty protectionPDNSPTOC1.Op.general PDNSPTOC1, Operate, general 1 = OperatePDNSPTOC1.Str.general PDNSPTOC1, Start, general 1 = Start
Phase overcurrent protectionPHHPTOC1.Op.general PHHPTOC1, Operate, general 1 = OperatePHHPTOC1.Str.general PHHPTOC1, Start, general 1 = StartPHHPTOC2.Op.general PHHPTOC2, Operate, general 1 = OperatePHHPTOC2.Str.general PHHPTOC2, Start, general 1 = StartPHIPTOC1.Op.general PHIPTOC1, Operate, general 1 = OperatePHIPTOC1.Str.general PHIPTOC1, Start, general 1 = Start
Table continues on next page
1MRS756711 A Section 2DNP 3.0 data mappings
REF615 11Point List Manual
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DAName ValuesPHLPTOC1.Op.general PHLPTOC1, Operate, general 1 = OperatePHLPTOC1.Str.general PHLPTOC1, Start, general 1 = Start
Phase overvoltage protectionPHPTOV1.Op.general PHPTOV1, Operate, general 1 = OperatePHPTOV1.Str.general PHPTOV1, Start, general 1 = StartPHPTOV2.Op.general PHPTOV2, Operate, general 1 = OperatePHPTOV2.Str.general PHPTOV2, Start, general 1 = StartPHPTOV3.Op.general PHPTOV3, Operate, general 1 = OperatePHPTOV3.Str.general PHPTOV3, Start, general 1 = StartPHPTUV1.Op.general PHPTUV1, Operate, general 1 = OperatePHPTUV1.Str.general PHPTUV1, Start, general 1 = StartPHPTUV2.Op.general PHPTUV2, Operate, general 1 = OperatePHPTUV2.Str.general PHPTUV2, Start, general 1 = StartPHPTUV3.Op.general PHPTUV3, Operate, general 1 = OperatePHPTUV3.Str.general PHPTUV3, Start, general 1 = StartPSPTUV1.Op.general PSPTUV1, Operate, general 1 = OperatePSPTUV1.Str.general PSPTUV1, Start, general 1 = Start
Disturbance recorderRDRE1.RcdMade.stVal Disturbance recorder, recording made, stVal 1 = Recording made
Residual current limit supervisionRESCMMXU1.HiAlm.stVal RESCMMXU1, High alarm, stVal 1 = High alarmRESCMMXU1.HiWrn.stVal RESCMMXU1, High warning, stVal 1 = High warning
Residual voltage limit supervisionRESVMMXU1.HiAlm.stVal RESVMMXU1, High alarm, stVal 1 = High alarmRESVMMXU1.HiWrn.stVal RESVMMXU1, High warning, stVal 1 = High warning
Residual overvoltage protectionROVPTOV1.Op.general ROVPTOV1, Operate, general 1 = OperateROVPTOV1.Str.general ROVPTOV1, Start, general 1 = StartROVPTOV2.Op.general ROVPTOV2, Operate, general 1 = OperateROVPTOV2.Str.general ROVPTOV2, Start, general 1 = StartROVPTOV3.Op.general ROVPTOV3, Operate, general 1 = OperateROVPTOV3.Str.general ROVPTOV3, Start, general 1 = Start
Fuse failure protectionSEQRFUF1.Str.general SEQRFUF1, General start of function , general 1 = StartSEQRFUF1.Str3Ph.general SEQRFUF1, Three-phase start of function, general 1 = Start
Circuit breaker condition monitoringSSCBR1.APwrAlm.stVal SSCBR1, Accumulated currents power (Iyt), exceeded alarm limit, stVal 1 = Iyt alarm limitSSCBR1.APwrLO.stVal SSCBR1, Accumulated currents power (Iyt), exceeded lockout limit, stVal 1 = Iyt lockout limitSSCBR1.CBLifAlm.stVal SSCBR1, Remaining life of CB exceeded alarm limit, stVal 1 = Remaining life alarmSSCBR1.ClsAlm.stVal SSCBR1, CB close travel time exceeded set value, stVal 1 = Close travel time alarmSSCBR1.LonTmAlm.stVal SSCBR1, CB 'not operated for long time' alarm, stVal 1 = Not operated alarmSSCBR1.OpnAlm.stVal SSCBR1, CB open travel time exceeded set value, stVal 1 = Open travel time alarmSSCBR1.OpNumAlm.stVal SSCBR1, Number of CB operations exceeds alarm limit, stVal 1 = CB operations alarmSSCBR1.OpNumLO.stVal SSCBR1, Number of CB operations exceeds lockout limit, stVal 1 = CB operations lockoutSSCBR1.PresAlm.stVal SSCBR1, Pressure below alarm level, stVal 1 = Low pressure alarmSSCBR1.PresLO.stVal SSCBR1, Pressure below lockout level, stVal 1 = Low pressure lockoutSSCBR1.SprChaAlm.stVal SSCBR1, Spring charging time has crossed the set value, stVal 1 = Spring charge alarm
Thermal protectionT1PTTR1.AlmThm.general T1PTTR1, Thermal alarm, general 1 = AlarmT1PTTR1.Op.general T1PTTR1, Operate, general 1 = OperateT1PTTR1.Str.general T1PTTR1, Start, general 1 = Start
Trip circuit supervisionTCSSCBR1.CirAlm.stVal TCSSCBR1, Alarm, stVal 1 = Alarm
Table continues on next page
Section 2 1MRS756711 ADNP 3.0 data mappings
12 REF615Point List Manual
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DAName ValuesTCSSCBR2.CirAlm.stVal TCSSCBR2, Alarm, stVal 1 = Alarm
Global conditioningTRPPTRC1.Op.general TRPPTRC1, Operate input signal, general 1 = Operate, inputTRPPTRC1.Tr.general TRPPTRC1, General trip output signal, general 1 = Trip, outputTRPPTRC2.Op.general TRPPTRC2, Operate input signal, general 1 = Operate, inputTRPPTRC2.Tr.general TRPPTRC2, General trip output signal, general 1 = Trip, output
Three-phase voltage limit supervisionVMMXU1.HiAlm.stVal VMMXU1, High alarm, stVal 1 = High alarmVMMXU1.HiWrn.stVal VMMXU1, High warning, stVal 1 = High warningVMMXU1.LoAlm.stVal VMMXU1, Low alarm, stVal 1 = Low alarmVMMXU1.LoWrn.stVal VMMXU1, Low warning, stVal 1 = Low warning
Raw I/O signalsXAGGIO130.Ind1.stVal X130 (AIM), X130-Input 1, stVal 1 = ON, 0 = OFFXAGGIO130.Ind2.stVal X130 (AIM), X130-Input 2, stVal 1 = ON, 0 = OFFXAGGIO130.Ind3.stVal X130 (AIM), X130-Input 3, stVal 1 = ON, 0 = OFFXAGGIO130.Ind4.stVal X130 (AIM), X130-Input 4, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO1.stVal X100 (PSM), X100-Output 1, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO2.stVal X100 (PSM), X100-Output 2, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO3.stVal X100 (PSM), X100-Output 3, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO4.stVal X100 (PSM), X100-Output 4, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO5.stVal X100 (PSM), X100-Output 5, stVal 1 = ON, 0 = OFFXGGIO100.SPCSO6.stVal X100 (PSM), X100-Output 6, stVal 1 = ON, 0 = OFFXGGIO110.Ind1.stVal X110 (BIO), X110-Input 1, stVal 1 = ON, 0 = OFFXGGIO110.Ind2.stVal X110 (BIO), X110-Input 2, stVal 1 = ON, 0 = OFFXGGIO110.Ind3.stVal X110 (BIO), X110-Input 3, stVal 1 = ON, 0 = OFFXGGIO110.Ind4.stVal X110 (BIO), X110-Input 4, stVal 1 = ON, 0 = OFFXGGIO110.Ind5.stVal X110 (BIO), X110-Input 5, stVal 1 = ON, 0 = OFFXGGIO110.Ind6.stVal X110 (BIO), X110-Input 6, stVal 1 = ON, 0 = OFFXGGIO110.Ind7.stVal X110 (BIO), X110-Input 7, stVal 1 = ON, 0 = OFFXGGIO110.Ind8.stVal X110 (BIO), X110-Input 8, stVal 1 = ON, 0 = OFFXGGIO110.SPCSO1.stVal X110 (BIO), X110-Output 1, stVal 1 = ON, 0 = OFFXGGIO110.SPCSO2.stVal X110 (BIO), X110-Output 2, stVal 1 = ON, 0 = OFFXGGIO110.SPCSO3.stVal X110 (BIO), X110-Output 3, stVal 1 = ON, 0 = OFFXGGIO110.SPCSO4.stVal X110 (BIO), X110-Output 4, stVal 1 = ON, 0 = OFFXGGIO120.Ind1.stVal X120 (AIM), X120-Input 1, stVal 1 = ON, 0 = OFFXGGIO120.Ind2.stVal X120 (AIM), X120-Input 2, stVal 1 = ON, 0 = OFFXGGIO120.Ind3.stVal X120 (AIM), X120-Input 3, stVal 1 = ON, 0 = OFFXGGIO120.Ind4.stVal X120 (AIM), X120-Input 4, stVal 1 = ON, 0 = OFFXGGIO130.Ind1.stVal X130 (BIO), X130-Input 1, stVal 1 = ON, 0 = OFFXGGIO130.Ind2.stVal X130 (BIO), X130-Input 2, stVal 1 = ON, 0 = OFFXGGIO130.Ind3.stVal X130 (BIO), X130-Input 3, stVal 1 = ON, 0 = OFFXGGIO130.Ind4.stVal X130 (BIO), X130-Input 4, stVal 1 = ON, 0 = OFFXGGIO130.Ind5.stVal X130 (BIO), X130-Input 5, stVal 1 = ON, 0 = OFFXGGIO130.Ind6.stVal X130 (BIO), X130-Input 6, stVal 1 = ON, 0 = OFFXGGIO130.SPCSO1.stVal X130 (BIO), X130-Output 1, stVal 1 = ON, 0 = OFFXGGIO130.SPCSO2.stVal X130 (BIO), X130-Output 2, stVal 1 = ON, 0 = OFFXGGIO130.SPCSO3.stVal X130 (BIO), X130-Output 3, stVal 1 = ON, 0 = OFF
1MRS756711 A Section 2DNP 3.0 data mappings
REF615 13Point List Manual
Table 3: Binary outputs
IEC 61850 LN.DO.DA IEC 61850 LN Desc, DO Desc, DANameCircuit breaker control
CBCSWI1.Pos.Oper.ctlVal CBXCBR1, Switch, general, Oper.ctlValReset current max. demand values
CMSTA1.RecRs.Oper.ctlVal CMMXU1, CMMXU1 max.demands, Oper.ctlValAutoreclosing reset signals
DARREC1.RsCnt.Oper.ctlVal DARREC1, DARREC1 counters, Oper.ctlValDARREC1.RsRec.Oper.ctlVal DARREC1, DARREC1 reset, Oper.ctlVal
Clear Indications and LEDsLLN0.LEDRs1.Oper.ctlVal General, indications and LEDs, Oper.ctlValLLN0.LEDRs2.Oper.ctlVal General, alarm LEDs, Oper.ctlValLLN0.RecRs.Oper.ctlVal General, all data, Oper.ctlVal
Reset accumulated energy valuesPEMMXU1.SupDmdRs.Oper.ctlVal PEMMXU1, Reset of accumulated energy , Oper,ctlVal
Disturbance recorder, clear memory and trig recordingRDRE1.MemClr.Oper.ctlVal Disturbance recorder, disturbance records, Oper.ctlValRDRE1.RcdTrg.Oper.ctlVal Disturbance recorder, trig recording, Oper.ctlVal
Reset signals of circuit breaker condition monitoringSSCBR1.RsAccAPwr.Oper.ctlVal SSCBR1, Reset accumulation energy, Oper.ctlValSSCBR1.RsCBWear.Oper.ctlVal SSCBR1, Reset input for CB remaining life and operation counter, Oper.ctlValSSCBR1.RsSprChaTm.Oper.ctlVal SSCBR1, SSCBR1 spring charge time alarm reset, Oper.ctlValSSCBR1.RsTrvTm.Oper.ctlVal SSCBR1, SSCBR1 travel time alarm reset, Oper.ctlVal
Table 4: Analog inputs
IEC 61850 LN.DO.DA Description Value range ScalingFunction Arg1 Arg2 Arg3 Arg4
Circuit breaker, operation counter and 4-pole (2 bit) position valueCBCSWI1.OpCntRs.stVal Operation counter 0…65535 Ratio 0 65535 0 65535CBCSWI1.Pos.stVal CB switch 0…3 Ratio 0 3 0 3
Phase current measurements
CMMXU1.A.phsA.instCVal.mag.f Phase current A0.00…40.00[xIn] Ratio 0 40 0 4000
CMMXU1.A.phsB.instCVal.mag.f Phase current B0.00…40.00[xIn] Ratio 0 40 0 4000
CMMXU1.A.phsC.instCVal.mag.f Phase current C0.00…40.00[xIn] Ratio 0 40 0 4000
Phase currents demand values
CMSTA1.AvAmps1.mag.f Phase current A demand0.00…40.00[xIn] Ratio 0 40 0 4000
CMSTA1.AvAmps2.mag.f Phase current B demand0.00…40.00[xIn] Ratio 0 40 0 4000
CMSTA1.AvAmps3.mag.fPhase currents Cdemand
0.00…40.00[xIn] Ratio 0 40 0 4000
CMSTA1.MaxAmps1.mag.fMaximum demand forphase A
0.00…40.00[xIn] Ratio 0 40 0 4000
CMSTA1.MaxAmps2.mag.fMaximum demand forphase B
0.00…40.00[xIn] Ratio 0 40 0 4000
CMSTA1.MaxAmps3.mag.fMaximum demand forphase C
0.00…40.00[xIn] Ratio 0 40 0 4000
Sequence of current measurement values
CSMSQI1.SeqA.c1.instCVal.mag.fPositive SequenceCurrent
0.00…40.00[xIn] Ratio 0 40 0 4000
CSMSQI1.SeqA.c2.instCVal.mag.fNegative SequenceCurrent
0.00…40.00[xIn] Ratio 0 40 0 4000
Table continues on next page
Section 2 1MRS756711 ADNP 3.0 data mappings
14 REF615Point List Manual
IEC 61850 LN.DO.DA Description Value range ScalingFunction Arg1 Arg2 Arg3 Arg4
CSMSQI1.SeqA.c3.instCVal.mag.f Zero Sequence Current0.00…40.00[xIn] Ratio 0 40 0 4000
Autoreclosing values
DARREC1.AutoRecSt.stVal Autoreclosing status-2…4 (seedoc) Ratio -2 4 -2 4
DARREC1.FrqOpCnt.stValFrequent operationcounter 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCnt1.stValOperation counter (1stshot) 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCnt2.stValOperation counter (2ndshot) 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCnt3.stValOperation counter (3rdshot) 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCnt4.stValOperation counter (4thshot) 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCnt5.stValOperation counter (5thshot) 0…65535 Ratio 0 65535 0 65535
DARREC1.OpCntRs.stValResettable operationcounter (all shots) 0…65535 Ratio 0 65535 0 65535
DARREC1.ShotPntr.stVal Shot pointer value 0…65535 Ratio 0 65535 0 65535Disconnector 4-pole (2 bit) position values
DCSXSWI1.Pos.stValDisconnector switch 1position 0…3 Ratio 0 3 0 3
DCSXSWI2.Pos.stValDisconnector switch 2position 0…3 Ratio 0 3 0 3
DCSXSWI3.Pos.stValDisconnector switch 3position 0…3 Ratio 0 3 0 3
Earth switch 4-pole (2 bit) position valuesESSXSWI1.Pos.stVal Earth switch position 0…3 Ratio 0 3 0 3
Device temperature, system values and countersLPHD1.NumPwrUp.stVal Number of power ups 0…65535 Ratio 0 65535 0 65535
LPHD1.PhyHealth1.stVal Warning0…65535 (seedoc) Ratio 0 65535 0 65535
LPHD1.PhyHealth2.stVal Internal fault0…65535 (seedoc) Ratio 0 65535 0 65535
LPHD1.WacTrg.stValNumber of watchdogdevice resets detected 0…65535 Ratio 0 65535 0 65535
LPHD1.WrmStr.stVal Number of warm starts 0…65535 Ratio 0 65535 0 65535Power measurement and accumulated power values
PEMMTR1.DmdVArh.actVal Forward reactive energy0…999999999(see doc) Ratio 0 999999999 0 999999999
PEMMTR1.DmdWh.actVal Forward active energy0…999999999(see doc) Ratio 0 999999999 0 999999999
PEMMTR1.SupVArh.actVal Reverse reactive energy0…999999999(see doc) Ratio 0 999999999 0 999999999
PEMMTR1.SupWh.actVal Energy unit Mult0…999999999(see doc) Ratio 0 999999999 0 999999999
PEMMXU1.TotPF.instMag.fAverage power factor(Total PF) -1.00…1.00 Ratio -1 1 -100 100
PEMMXU1.TotW.instMag.fTotal active power (TotalP)
0…999999(see doc) Ratio 0 999999 0 999999
PEMMXU1.TotVA.instMag.fTotal apparent power(Total S)
0…999999(see doc) Ratio 0 999999 0 999999
PEMMXU1.TotVAr.instMag.fTotal reactive power(Total Q)
0…999999(see doc) Ratio 0 999999 0 999999
Disturbance recorder valuesRDRE1.FltNum.stVal Number of recordings 0…65535 Ratio 0 65535 0 65535RDRE1.MemUsed.stVal Rec. memory used 0…100 [%] Ratio 0 100 0 100
Residual current and voltage
Table continues on next page
1MRS756711 A Section 2DNP 3.0 data mappings
REF615 15Point List Manual
IEC 61850 LN.DO.DA Description Value range ScalingFunction Arg1 Arg2 Arg3 Arg4
RESCMMXU1.A.res.instCVal.mag. Residual current 0…40.00 [xIn] Ratio 0 40 0 4000RESVMMXU1.PhV.res.instCVal.mag.f Residual voltage 0…4.00 [xUn] Ratio 0 4 0 400
Circuit breaker condition monitoring values
SSCBR1.AccAPwrPhA.mag.fAccumulated currentspower (Iyt), phase A
0.00…1000000.00 Ratio 0 1000000 0 1000000
SSCBR1.AccAPwrPhB.mag.fAccumulated currentspower (Iyt), phase B
0.00…1000000.00 Ratio 0 1000000 0 1000000
SSCBR1.AccAPwrPhC.mag.fAccumulated currentspower (Iyt), phase C
0.00…1000000.00 Ratio 0 1000000 0 1000000
SSCBR1.InaTmdCnt.stValNumber of days CB hasbeen inactive 0…9999 Ratio 0 9999 0 9999
SSCBR1.RmnLifPhA.stValCB Remaining life phaseA -9999…9999 Ratio -9999 9999 -9999 9999
SSCBR1.RmnLifPhB.stValCB Remaining life phaseB -9999…9999 Ratio -9999 9999 -9999 9999
SSCBR1.RmnLifPhC.stValCB Remaining life phaseC -9999…9999 Ratio -9999 9999 -9999 9999
SSCBR1.TmmsCls.mag.fTravel time of the CBduring closing operation
0.00…60000[ms] Ratio 0 60000 0 60000
SSCBR1.TmmsOpn.mag.fTravel time of the CBduring opening operation
0.00…60000[ms] Ratio 0 60000 0 60000
SSCBR1.TmsSprCha.mag.fCharging time of the CBspring
0.00…99.99[s] Ratio 0 99.99 0 9999
Temperature protection values
T1PTTR1.TmmsOp.stValEstimated time tooperate
0…600000[ms] Ratio 0 600000 0 600
T1PTTR1.TmmsRecEna.stValEstimated time todeactivate BLK_CLOSE
0…600000[ms] Ratio 0 600000 0 600
T1PTTR1.Tmp.mag.fProtected objecttemperature
-100.0…9999.9[Celsius] Ratio -100 9999.9 -1000 99999
T1PTTR1.TmpRl.mag.f Relative temperature0.00…99.9[Celsius] Ratio 0 99.9 0 999
T1PTTR1.TmpUsed.mag.f
The ambienttemperature used in thecalculation
-99…999.99[Celcius] Ratio -99 999.99 -9900 99999
Voltage measurement phase to ground and phase to phase values
VMMXU1.PhV.phsA.cVal.mag.fPhase to ground voltageA 0…4.00 [xUn] Ratio 0 4 0 400
VMMXU1.PhV.phsB.cVal.mag.fPhase to ground voltageB 0…4.00 [xUn] Ratio 0 4 0 400
VMMXU1.PhV.phsC.cVal.mag.fPhase to ground voltageC 0…4.00 [xUn] Ratio 0 4 0 400
VMMXU1.PPV.phsAB.instCVal.mag.fPhase to phase voltageAB 0…4.00 [xUn] Ratio 0 4 0 400
VMMXU1.PPV.phsBC.instCVal.mag.fPhase to phase voltageBC 0…4.00 [xUn] Ratio 0 4 0 400
VMMXU1.PPV.phsCA.instCVal.mag.fPhase to phase voltageCA 0…4.00 [xUn] Ratio 0 4 0 400
Sequence of voltage measurement values
VSMSQI1.SeqV.c1.instCVal.mag.fPositive SequenceVoltage 0…4.00 [xUn] Ratio 0 4 0 400
VSMSQI1.SeqV.c2.instCVal.mag.fNegative SequenceVoltage 0…4.00 [xUn] Ratio 0 4 0 400
VSMSQI1.SeqV.c3.instCVal.mag.f Zero Sequence Voltage 0…4.00 [xUn] Ratio 0 4 0 400
Section 2 1MRS756711 ADNP 3.0 data mappings
16 REF615Point List Manual
Section 3 DNP 3.0 protocol implementation
3.1 DNP 3.0 device profile
The following table provides a device profile document in the standard format definedin the DNP 3.0 Subset Definitions Document. While it is referred to in the DNP 3.0Subset Definitions as a document, it is in fact a table, and only a component of a totalinteroperability guide. The table, in combination with the Implementation table andthe point list tables provides a complete configuration/interoperability guide forcommunicating with a device.
Table 5: Device profile document
DNP 3.0 device profile documentVendor name: ABB Oy
Device name: REF615
Highest DNP level supported: Device function:
For requests: Level 2+ ○ Master
For responses: Level 2+ ● Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is described in theattached table):For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28 (index) are supported.Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01.16-bit and 32-bit Analog Change Events with Time may be requested.
Maximum data link frame size (octets): Maximum application fragment size (octets):
Transmitted: 292 Transmitted: Configurable (256...2048)
Received: 292 Received: 2048
Maximum data link re-tries: Maximum application layer re-tries:
○ None ● None
○ Fixed ○ Configurable
● Configurable (0...65535)
Requires data link layer confirmation:
○ Never
○ Always
○ Sometimes
● Configurable as: Never, Only for multi-frame messages, or Always
Requires application layer confirmation:
○ Never
○ Always
○ When reporting event data (slave devices only)
○ When sending multi-fragment responses (slave devices only)
Table continues on next page
1MRS756711 A Section 3DNP 3.0 protocol implementation
REF615 17Point List Manual
DNP 3.0 device profile document ○ Sometimes
● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages."
Timeouts while waiting for:
Data linkconfirm:
○ None ○ Fixed at ____ ○ Variable ● Configurable
Complete appl.fragment:
● None ○ Fixed at ____ ○ Variable ○ Configurable
Applicationconfirm:
○ None ○ Fixed at ____ ○ Variable ● Configurable
Complete appl.response:
● None ○ Fixed at ____ ○ Variable ○ Configurable
Others: Select/Operate Arm Timeout, not configurable; fixed at 10s, regardless of select timeout in the HMI.Need time interval, configurableUnsolicited notification delay, configurableUnsolicited response retry delay, configurableUnsolicited offline Interval, configurable
Sends/Executes Control Operations:
WRITE binaryoutputs
● Never ○ Always ○ Sometimes ○ Configurable
SELECT/OPERATE
○ Never ○ Always ○ Sometimes ● Configurable
DIRECTOPERATE
○ Never ○ Always ○ Sometimes ● Configurable
DIRECTOPERATE -NO ACK
○ Never ○ Always ○ Sometimes ● Configurable
Count > 1(Count > 1 isaccepted butignored)
● Never ○ Always ○ Sometimes ○ Configurable
Pulse on ● Never ○ Always ○ Sometimes ○ Configurable
Pulse off ● Never ○ Always ○ Sometimes ○ Configurable
Latch on ○ Never ● Always ○ Sometimes ○ Configurable
Latch off ○ Never ● Always ○ Sometimes ○ Configurable
Queue ● Never ○ Always ○ Sometimes ○ Configurable
Clear queue ● Never ○ Always ○ Sometimes ○ Configurable
The circuit breaker control model is configurable for either direct or SBO mode in the circuit breaker settings. If the operation mode doesnot match the CROB, the returned CROB status is hardware error (4). All other control points may be controlled by either direct or SBOcontrols.
Reports binary input change events when no specific variationrequested:
Reports time-tagged binary input change events when no specificvariation requested:
○ Never ○ Never
○ Only when time-tagged ○ Binary input change with time
○ Only non-time-tagged ○ Binary input change with relative time
● Configurable to send one or the other ● Configurable
Table continues on next page
Section 3 1MRS756711 ADNP 3.0 protocol implementation
18 REF615Point List Manual
DNP 3.0 device profile documentSends unsolicited responses: Sends static data in unsolicited responses:
● Never ● Never
○ Configurable ○ When device restarts
○ Only certain objects ○ When status flags change
○ Sometimes (attach explanation)
○ ENABLE/DISABLE UNSOLICITEDfunction codes supported
No other options are permitted.
Default counter object/variation: Counters roll over at:
● No counters reported ● No counters reported
○ Configurable ○ Configurable (attach explanation)
○ Default objectDefault variation:
○ 16 bits
○ Point-by-point list attached ○ 32 bits
○ Other value: _______
○ Point-by-point list attached
Sends multi-fragment responses:
● Yes
○ No
○ Configurable
Sequential file transfer support:
Append file mode ○ Yes ● No
Custom status code strings ○ Yes ● No
Permissions field ○ Yes ● No
File events assigned to class ○ Yes ● No
File events send immediately ○ Yes ● No
Multiple blocks in a fragment ○ Yes ● No
Max number of files open 0
● = Selected,○ = Not selected
3.2 DNP 3.0 implementation table
The following table identifies which object variations, function codes, and qualifiersthe IED supports in both request messages and response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will beresponded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will beresponded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 arealways responded.
1MRS756711 A Section 3DNP 3.0 protocol implementation
REF615 19Point List Manual
Table 6: Implementation table
OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)Objectnumber
Variationnumber Description Function codes (dec) Qualifier codes (hex)
Function codes(dec)
Qualifier codes(hex)
1 0 Binaryinput – anyvariation
1 (read)22 (assign class)
00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
1 1 (default) 1) Binaryinput
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
1 2 Binaryinput with
status
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
2 0 Binaryinput
change –any
variation
1 (read) 06 (no range, or all)07, 08 (limited qty)
2 1 Binaryinput
changewithout
time
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
2 2 Binaryinput
changewith time
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
2 3 1) Binaryinput
changewith
relativetime
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
10 0 Binaryoutput
status –any
variation
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
10 1 Binaryoutput
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
12 1 Controlrelay
outputblock
3 (select)4 (operate)5 (direct op)6 (dir. op, noack)
17, 28 (index) 129 (response) echo of request
30 0 Analoginput - anyvariation
1 (read)22 (assign class)
00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
30 1 32-bitanaloginput
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
Table continues on next page
Section 3 1MRS756711 ADNP 3.0 protocol implementation
20 REF615Point List Manual
OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)30 2 (default) 1) 16-bit
analoginput
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
30 3 32-bitanaloginput
without flag
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
30 4 16-bitanaloginput
without flag
1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
32 0 Analogchange
event – anyvariation
1 (read) 06 (no range, or all)07, 08 (limited qty)
32 1 32-bitanalogchangeevent
withouttime
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
32 2 16-bitanalogchangeevent
withouttime
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
32 3 32-bitanalogchange
event withtime
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
32 4 (default) 1) 16-bitanalogchange
event withtime
1 (read) 06 (no range, or all)07, 08 (limited qty)
129 (response)130 (unsol. resp)
17, 28 (index)
50 0 Time anddate
50 1 (default) 1) Time anddate
1 (read) 00, 01 (start-stop)06 (no range, or all)07 (limited qty = 1l)08 (limited qty)
129 (response) 00, 01 (start-stop)17, 28 (index) 2)
2 (write) 07 (limited qty = 1l)
50 3 Time anddate lastrecorded
time
2 (write) 07 (limited qty)
51 1 Time anddate CTO
129 (response)130 (unsol. resp)
07 (limited qty)(qty = 1)
51 2 Unsynchronized timeand date
CTO
129 (response)130 (unsol. resp)
07 (limited qty)(qty = 1)
Table continues on next page
1MRS756711 A Section 3DNP 3.0 protocol implementation
REF615 21Point List Manual
OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)52 2 Time delay
fine 129 (response) 07 (limited qty)
(qty = 1)
60 0 Not defined
60 1 Class 0data
1 (read) 06 (no range, or all)
60 2 Class 1data
1 (read) 06 (no range, or all)
20 (enbl. unsol.)21 (dab. unsol.)22 (assign class)
07, 08 (limited qty)06 (no range, or all)
60 3 Class 2data
1 (read) 06 (no range, or all)07, 08 (limited qty)
20 (enbl. unsol.)21 (dab. unsol.)22 (assign class)
06 (no range, or all)
60 4 Class 3data
1 (read) 06 (no range, or all)07, 08 (limited qty)
20 (enbl. unsol.)21 (dab. unsol.)22 (assign class)
06 (no range, or all)
80 1 Internalindications
1 (read) 00, 01 (start-stop)
2 (write) 3) 00 (start-stop)index=7
No object (function code only) 13 (cold restart) 4)
No object (function code only) 14 (warm restart) 4)
No object (function code only) 23 (delay meas.)
No object (function code only) 24 (record currenttime)
1) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Default variations areconfigurable; however, default settings for the configuration parameters are indicated in the table above.
2) For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively.Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-eventobjects, qualifiers 17 or 28 are always responded.)
3) Writes of internal indications are only supported for index 7 (Restart IIN1-7)4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken.
Section 3 1MRS756711 ADNP 3.0 protocol implementation
22 REF615Point List Manual
Section 4 Glossary
AR AutoreclosureCB Circuit breakerCTO Common time of occurrence. The time and date CTO object is
an information object that represents the absolute time of day.DNP 3.0 A distributed network protocol originally developed by Westronic.
The DNP3 Users Group has the ownership of the protocol andassumes responsibility for its evolution.
DO Data objectEMC Electromagnetic compatibilityHMI Human-machine interfaceIEC International Electrotechnical CommissionIEC 61850 International standard for substation communication and
modelling.IED Intelligent Electronic DeviceLED Light-emitting diodeLN Logical nodePCM600 Protection and Control IED ManagerSBO Select-before-operateWHMI Web Human-Machine Interface
Section 4Glossary
REF615 23Point List Manual
24
25
1MR
S756
711
A©
Cop
yrig
ht 2
009
ABB.
All
right
s re
serv
ed.
ABB OyDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11Fax +358 10 22 41094www.abb.com/substationautomation