Flexible and effi cient measurement
The extension board PM-2 allows cost-effective measurement of relevant pow-
er values in low and medium voltage systems.
Various measured values such as frequency, power and phase displacement
angle are directly available for the evaluation of the utilization of the equip-
ment, the evaluation of the quality and stability of the voltage as well as the
identifi cation of anomalies in the distribution network.
As an extension board for the net-line FW-5, the PM-2 is inserted into the I/O
area of the RTU. setIT offers the specifi cation of the measurement parameters
and the selection of measured values from V6.000. The values are integrated
directly in the process data from where they can be monitored, sent and recor-
ded based on custom criteria.
Typical application areas
• Local substations
• Decentralised power plants
• Systems with decentralised power distribution
• Industrial systems
PM-2Power measurement
Brief profi le PM-2
Power measurement module for
recording relevant values in low and
medium voltage systems. Measuring
currents I1,I2,I3,IN. Voltage measure-
ment U1, U2, U3. Calculating Ieff/Ueff
TRMS, ULL, P, Q, S, W, f, power factor,
active and reactive power.
Flexible selection of capacity from 12
single-point commands, 6 single-
point information, 8 metered values
and 47 measured values. Integration
as an extension board in telecontrol
systems of type FW-5/FW-5-GATE
series5e.
Internal power supply and commu-
nication via system bus. Confi gu-
ration as an I/O card in setIT from
V6.000.
Dimensions: 22.5x105x115 mm
(WxHxD)
PM-2 Power measurement
FW-5-GATE-4GDSO-1 (command operation)PM-2 (measure)
PM-1
L3L2L1
PM-1
monitoroperate
Control centre
LTE
LTE
monitor
operate
monitor
PM-2 Power measurement
© S
AE IT-system
s Gm
bH &
Co. KG S
ubject to tech
nical m
odification. Errors an
d omission
s excepted. Produ
ct images m
ay contain
special features. S
tatus:M
ai 2020
SAE IT-systems GmbH & Co. KG
Im Gewerbegebiet Pesch 14
50767 Köln (Cologne, Germany)
Phone.: +49(0)221/59808-0
Fax: +49(0)221/59808-60
www.sae-it.de
Design Power measurement module for telecontrol and substation automation in micro-housing, Polyamide V0, IP20, DIN top-hat rail assembly
Networks Measurement of medium voltages with CT, VT LV measurement with CT, voltage directly, 4-phase system, 3-phase system, one-phase
Current measurement PM-2 4 currents I1, I2, I3 IN: 0 … 1 A /5 A, resolution 1 mA, TRMS load 10 mΩ, overload max. 60 A (1 s), errors ±0.2%, sampling frequency 4 kHz
Voltage measurement PM-2
4 voltages U1, U2, U3: 0 … 690 V AC, ULL calculated, resolution 30 mV load 1130 kΩ, errors ±0.2%, sampling frequency 4 kHz
Network variables Frequency, 45 ... 66 Hz, resolution 0.001 Hz P, Q, S, error ±0.5% Energy W, Wb errors ±0.5%
Data range 47 measured values i.a. I, U, ULL, P, S, Q, W, Wb, f, PF 12 Single-point information: Faults, power load direction, rotary field errors 8 Counter values for power measurement 3 Single commands for acknowledgment
Measurement accuracy according to DIN EN 61557-12:2008
Status indicators LED in front plate for voltage, load, rotary fields and system status
Supply Internal via TBUS 100 mA @ TBUS
Dialectic strength 6 kV rated surge voltage, CAT III (600 V) CAT IV (300 V)
Standards EMC: DIN EN 61000-6-2:2006, DIN EN 61000-6-4:2011 Isolation: DIN EN 60870-2-1:1997
Housing Micro housing, Polyamide V0, IP 20, dimensions 22.5×105×115 mm (W×H×D) DIN top-hat rail, DIN-EN 60715 TH35 Screw terminal MSTB, 0.2 to 2.5 mm2
Ambient temperature -20° C... +70° C
Relative humidity < 95%, without condensation
Technical data: PM-2