2
PLµS 32™ DISTRIBUTED CONTROL SYSTEM The DRS Consolidated Controls PLμS 32™ Distributed Control System provides a complete spectrum of functions for Class 1E and non 1E safety systems including loop control, logic, analog and sequential control, and data acquisition and management. DRS PLμS 32™ distributed control systems have logged over a million hours of safety critical plant operations above and beyond the 500,000,000 hours logged by prior Consolidated Controls systems. The highly modular PLμS 32™ architecture provides solutions ranging from single plant subsystem control to complete Balance of Plant (BOP) applications. PLμS 32™ is based upon a fault-tolerant architecture featuring PERFORM Net™ that provides redundancy for all data paths and a dedicated microprocessor for each control loop. The system can be configured to be highly distributed with I/O and control functions located in the field, or highly centralized with all I/O and control functions located in one area without degradation in performance. The PLμS 32™ system provides operator interfaces ranging from traditional push buttons, indicators, and auto/manual stations to a state of the art safety related Video Display Unit (VDU) providing select and confirm touch screen control for all plant operations. Designed for the most demanding seismic and environmental conditions and built with precise redundant and deterministic processing and communications, PLμS 32™ delivers demonstrated reliability suited for all critical control systems. HIGHLIGHTS • Designed to meet NRC and IEEE guidelines • Firmware designed to meet: IEEE 7-4.3.2 IEEE 730-1 IEEE 1012 IEEE 1028 US NRC Regulatory Guide 1.152 US NRC Regulatory Guide 1.168 US NRC Regulatory Guide 1.169 (as well as additional specifications) • Meets MIL-STD-461D and MIL-STD-462D, EMI/RFI requirements per EPRI TR-102323 • Seismically Qualified to: IEEE 344

PLμS 32™ Distributed Control System - drs-cci.com · PLµS 32™ DISTRIBUTED CONTROL SYSTEM TheDRSConsolidatedControlsPLμS32™Distributed ControlSystemprovidesacompletespectrumoffunctions

  • Upload
    vananh

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

PLµS 32™ DISTRIBUTED CONTROL SYSTEM

The DRS Consolidated Controls PLμS 32™ DistributedControl System provides a complete spectrum of functionsfor Class 1E and non 1E safety systems including loopcontrol, logic, analog and sequential control, and dataacquisition and management. DRS PLμS 32™ distributedcontrol systems have logged over a million hours of safetycritical plant operations above and beyond the 500,000,000hours logged by prior Consolidated Controls systems. Thehighly modular PLμS 32™ architecture provides solutionsranging from single plant subsystem control to completeBalance of Plant (BOP) applications.

PLμS 32™ is based upon a fault-tolerant architecturefeaturing PERFORM Net™ that provides redundancy for alldata paths and a dedicated microprocessor for each controlloop. The system can be configured to be highly distributedwith I/O and control functions located in the field, or highlycentralized with all I/O and control functions located in onearea without degradation in performance.

The PLμS 32™ system provides operator interfaces rangingfrom traditional push buttons, indicators, and auto/manualstations to a state of the art safety related Video Display Unit(VDU) providing select and confirm touch screen control for allplant operations. Designed for the most demanding seismicand environmental conditions and built with precise redundantand deterministic processing and communications, PLμS 32™delivers demonstrated reliability suited for all critical controlsystems.

HIGHLIGHTS• Designed to meet NRC and IEEE guidelines• Firmware designed to meet:

IEEE 7-4.3.2IEEE 730-1IEEE 1012IEEE 1028US NRC Regulatory Guide 1.152US NRC Regulatory Guide 1.168US NRC Regulatory Guide 1.169(as well as additional specifications)

• Meets MIL-STD-461D and MIL-STD-462D, EMI/RFIrequirements per EPRI TR-102323

• Seismically Qualified to: IEEE 344

OPERATING ENVIRONMENT

Temperature +50ºF to +122ºF

(+10ºC to +50ºC)

Relative humidity 10 to 90 percent

Seismic classification Category IEEE 344

Safety classification Class 1E

EMI/RFI classification MIL-STD 461D/462D per

EPRI TR-102323

Environmental classification Category IEEE 323

FIELD I/O

Digital inputs

Field switch readers +48 VDC

Relay monitors +24 VDC

Analog inputs 4 to 20 mA

1 to 5 V

Thermocouple (E, J, K, T)

RTD (100 Ohm, 200 Ohm)

0 to 2K Ohm

Digital outputs

Field drivers +48 VDC

Relay drivers +24 VDC

Analog outputs 4 to 20 mA

Custom I/O As required

DRS Consolidated Controls Inc.

21 South Street, Danbury, CT 06810 Tel. +1.203.798.3030 www.drs-cci.com

DRS CC V6 06/15/11

(ISO 9001: Certified Company)

PHYSICAL CHARACTERISTICS

Single cabinet 24 L x 90 H x 36 D inches

(60.9 L x 228.6 H x 91.4 D cm)

Termination with Logic 60 L x 90 H x 36 W inches

cabinet (152.4 L x 228.6 H x 91.4 D cm)

CORE FUNCTIONALITY

Microprocessor Motorola 32 bit MC68360

Memory (UV-EPROM) 32/128 kbytes

Memory (RAM) 128 kbytes

Status indicators Board edge LED indicators

Export of DRS ICAS, LLC products may be subject to U.S. Export Controls. U.S. Export licenses may be required.

Specifications subject to change without notice. Copyright © DRS ICAS, LLC 2011. All Rights Reserved.