Technical Document

Version 0.0

November, 2008

www.cermate.com

PLC Connection Guide

TN527D

Communication settings between MicroLogix DF1 and PanelMaster

◎Revision Record

Revision Date Content Owner

Page 2: PLC Connection Guide - cermate.com

TND527-E0

Page 2 of 10 www.cermate.com

Preface

This tech note introduces how to connect AB MicroLogix Series DF1 RS232 CPU Port

with PanelMaster HMI.

MicroLogix PLC

Channel 0 Channel 1

Page 3: PLC Connection Guide - cermate.com

TND527-E0

Page 3 of 10 www.cermate.com

(1) PLC Parameter Setting:

(a) Executing Rockwell Software --- RSLinx tool to link with PLC(via DF1 RS232)

Step1: Connect with the program cable to Channel 0 and execute the “RSLinx” tool.

Page 4: PLC Connection Guide - cermate.com

TND527-E0

Page 4 of 10 www.cermate.com

Step2: Executing the “Auto-Configure” function to link with Channel0 automatically.

Step3: Setting the communication format (Standard: 19200; 8, None, 1/ node address:0); Driver=DF1

Full Duplex及 Error Detection=CRC.

Page 5: PLC Connection Guide - cermate.com

TND527-E0

Page 5 of 10 www.cermate.com

(a) When you wish to link with MicroLogix PLC, please follow below steps to create the devices that

you want to link with.

Step1: Executing the RSLogix 500 software and choose correct CPU type. With “OFFLINE” situation,

move the mouse to the device and press right button of the mouse. Select the “New Window”

to set the device range.

Step2: Select the ”Propertise” option.

Page 6: PLC Connection Guide - cermate.com

TND527-E0

Page 6 of 10 www.cermate.com

Step3: Change the “Last” device name from B3:0 to B3:255.

Step4: When you press “OK” button to return Propertise window, you will see the range is created

from B3:0 to B3:255. Please remember to execute “Download…” function to write this range

setting to PLC.

Page 7: PLC Connection Guide - cermate.com

TND527-E0

Page 7 of 10 www.cermate.com

(b) Cable Diagram:

HMI Side PLC Side

COM1 9-PIN Male

PV-Series

Serial Port 9-PIN Female

(DF1 RS232)

RXD + 2 3 TXD

TXD - 3 2 RXD

GND 5 5 SG

RTS 7 7 CTS

CTS 8 8 RTS

HMI Side PLC Side

COM2 9-PIN Female

PV-Series

Serial Port 9-PIN Female

(DF1 RS232)

RXD + 2 3 TXD

TXD - 3 2 RXD

GND 5 5 SG

RTS 7 7 CTS

CTS 8 8 RTS

Page 8: PLC Connection Guide - cermate.com

TND527-E0

Page 8 of 10 www.cermate.com

(2) HMI Setting:

Select 【Direct Link [COM] 】&【Device/Server: Allen Bradley → MicroLogix 1000/1500】

Set the linking parameter same like PLC software setting.

Page 9: PLC Connection Guide - cermate.com

TND527-E0

Page 9 of 10 www.cermate.com

(3) PLC Address

Bit Devices:

Word Devices:

~Thank You~

Page 10: PLC Connection Guide - cermate.com

TND527-E0

Page 10 of 10 www.cermate.com

Technical Support Information

中國大陸 QQ專線 : 800014850 www.panelmaster.com.cn / www.cermate.com

資料下載專區 ftp:://mail.cermate.com + User name + Password (欲加入會員需要申請)

合作貼牌聯絡專線: China: 0910011916 / 86-13823788405 [email protected] Taiwan: 886-910011915 [email protected]

Worldwide: 886-910011914 [email protected]

Cermate Technologies (Shanghai) Inc. 屏通科技(上海)有限公司

Phone: +86-21-51758590~2 FAX : +86-21-51758589

E-mail: [email protected]

Shenzhen Cermate Technologies Inc. 屏通科技(深圳)有限公司

Phone: +86-755-83562179, FAX : +86-755-83562294

E-mail: [email protected]

Cermate Technologies Inc. (台湾) 屏通科技股份有限公司 7F-1, No. 168, Lien-Cheng Road, Chung-Ho City, Taipei, Taiwan 235 R.O.C.

Phone: 886-2-22437000 FAX : 886-2-22499933

E-mail: [email protected]