Plc a120 Aeg

Embed Size (px)

Citation preview

  • 7/22/2019 Plc a120 Aeg

    1/236

    A120

    DIN-Rail Mount Controller

    (Basic Document)

    User Manual

    A91M.12-271 629.27-0195

    Translation of the German DescriptionA91M.12-271 605.27-0794

  • 7/22/2019 Plc a120 Aeg

    2/23627ii

    Notes

    Application Note

    Caution The relevant regulations must be observed for control applications in-volving safety requirements.For reasons of safety and to ensure compliance with documented system data,repairs to components should be performed only by the manufacturer.

    Training

    AEG Schneider Automation offers suitable training that provides further informationconcerning the system (see addresses).

    Data, Illustrations, AlterationsData and illustrations are not binding. We reserve the right to alter our products in linewith our policy of continuous product development. If you have any suggestions for im-provements or amendments or have found errors in this publication, please notify us byusing the form on the last page of this publication.

    Addresses

    The addresses of our Regional Sales Offices, Training Centers, Service and Engineer-ing Sales Offices in Europe are given at the end of this publication.

    CopyrightAll rights reserved. No part of this document may be reproduced or transmitted in anyform or by any means, electronic or mechanical, including copying, processing or anyinformation storage, without permission in writing by the AEG Schneider Automation.

    You are not authorized to translate this document into any other language.

    TrademarksAll terms used in this user manual to denote AEG Schneider Automation products are

    trademarks of the AEG Schneider Automation.

    1995 AEG Schneider Automation

  • 7/22/2019 Plc a120 Aeg

    3/236

  • 7/22/2019 Plc a120 Aeg

    4/23627iv

    Objectives

    This is the basic document for the A120 and station Geadat 120. It describes the scopeof performance of the programmable controller and supplies the user with all the infor-mation to build up the system for standard applications and load the user logic. The fol-lowing are described:

    Configuration (number of I/O points, programming panels, operating panels)Hardware layoutLayout of power supplyI/O field wiringProcedure during the initial start-up

    Furthermore, references to the documentation are made in suitable places which con-sider special applications (e.g. system networking, process visualization, programming,etc.).

    Note For complete configuration the supplementary user manual Process Peripheralfor Micro, A120 and Gedat 120 is also required.

  • 7/22/2019 Plc a120 Aeg

    5/23627 v

    Arrangement of This Guide

    Chapter 1 General

    This chapter describes performance features and functionality of the A120 (program-ming, operating, networking). Emphasis is placed on the question What can beachieved using the A120 and where are the limits to its performance. Concrete instruc-tions regarding handling will not be specified here - chapter 3 deals with these instruc-tions thoroughly.

    The following points are handled in detail:

    Structure (layout limits, hardware modules)

    Networking possibilities with other programmable controllersConnectable printers, programming and operating panelsOverview of available software

    Chapter 2 Operating

    This chapter deals exclusively with the themes which are relevant to the operator of anA120 which runs on the process arranged according to operating and display elementsas well as simple maintenance work. It shows how to build an operator interface andsupplies references which are of importance when programming system/user-specific

    operating instructions and maintenance plans for the A120.

    Chapter 3 Configuration

    This chapter contains detailed configuration descriptions, hardware settings as well asstructural guidelines with advice regarding the system start-up.

    Chapter 4 Specifications

    All the technical data regarding the A120 according to VDI guideline 2880 Bl.1 is sum-marized in this chapter.

    Chapter 5 Earthing and EMC Measures

    This chapter gives basic information on earthing and EMC measures.

    Appendix A Module Descriptions, arranged alphabetically

  • 7/22/2019 Plc a120 Aeg

    6/236

  • 7/22/2019 Plc a120 Aeg

    7/23627 vii

    Software Dolog AKF A120 and A120, Dolog AKFSoftware-Kit Standard Function Blocks

    E-Nr. 424 271 521 Block LibraryA91M.12-703 265

    or

    Modsoft AKF MICROSoftware-KitE-Nr. 424 704 703

    or

    Dolog AKF A120 / A250 or Dolog ALD A250

    Software-Kit SoftwarepaketE-Nr. 424 275 182 E-Nr. 424 703 322

    and

    A120, Dolog AKFStandard Function BlocksBlock Library

    A91M.12-703 265

    and

    A250, Dolog AKF

    Standard Function BlocksVolume 1 (A to P)Block Library

    A91M.12-703 266

    and

    A250, Dolog AKFStandard Function BlocksVolume 2 (Q to Z)Block Library

    A91M.12-703 267

  • 7/22/2019 Plc a120 Aeg

    8/236

  • 7/22/2019 Plc a120 Aeg

    9/23627 Table of Contents ix

    Table of Contents

    Chapter 1 General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1 Introduction 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 How the Components Work together 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 The CPU: Purpose and Mode of Operation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.2 The Memory: Purpose and Allocation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.3 I/O Modules: Purpose and Types 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.4 Busses 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3 General Assembling 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 Types of Communication 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4.1 Overview 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4.2 Modnet 1/SFB Interfaces 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.4.2.1 Master in Modnet 1/SFB Interfaces 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4.2.2 Slaves in Modnet 1/SFB Interfaces 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.4.3 Modnet 1/F Networks 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5 Programming 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.1 Special Programming Language 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5.2 Program Generation 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5.3 Programming- and Peripheral Devices 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.3.1 Programming Devices 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5.3.2 Suitable Printers 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.6 Overview of the Available Software Kits 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.7 Software Revision Index 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8 Module Overview 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2 Operating 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1 Display Elements 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2 Switches 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.3 Design of an Operator Interface 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.1 Operating the A120 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.2 Operating the Geadat 120 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4 Changing the Battery (Maintenance) 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5 Switching the Supply Voltage on and off 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.5.1 Switching the System on and off by the User 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5.2 Switching the System on and off as a Result of a Power Failure 26. . . . . . . . . . . . . . . . .2.5.3 Checking Measures (Inspection) 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 3 Configuration 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 Overview 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2 Configuration of Hardware 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.1 Assembling and Determining the I/O Nodes 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.1.1 Linear Drop Layout 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.1.2 Stacked Drop Layout 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2.2 Total Current 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/22/2019 Plc a120 Aeg

    10/23627Table of Contentsx

    3.3 Layout of Power Supply 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.1 Planning and Structuring the Electric Circuits 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.2 Connection Diagram of the UB Supply (24 VDC for Modules and Sensors) 36. . . . . . . .3.3.3 Connection Diagram of the Working Voltage Supply (US = 24 VDC or L = 115 / 230

    VAC) 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4 Start-Up Characteristics 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5 Layout of an Operator Interface 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6 Installation 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.1 Top Hat Rail 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.2 Backplanes 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.2.1 Mounting Backplanes 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.2.2 Interlocking Backplanes 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.2.3 Mounting and Connecting Backplanes by Using the BXT 201 57. . . . . . . . . . . . . . . . . . . .

    3.6.3 Modules 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.4 Earthing the A120 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.4.1 Earthing the Top Hat Rail and Module 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.4.2 Earthing the Shielded Cables 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6.5 Dimension Drawing 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.6 Disassembly 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.7 Electrical Connection 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.7 Configuration of the SystemFieldBus Line 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.7.1 Transmission Rates (Baud Rates) of the SystemFieldBus Interface 66. . . . . . . . . . . . . . .3.7.2 SystemFieldBus Connection 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.7.3 Building the Cable 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.7.4 Modnet 1/SFB Discharge Measures 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.7.5 Surge Voltage Protection for SystemFieldBus Cable Outside Buildings 71. . . . . . . . . . . .

    3.8 Checklist for Initial Start-up and Test 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.8.1 Setting, Mounting 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.8.2 Creating and Transmitting Programs 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.9 Documenting and Archiving 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.9.1 Hardware Settings 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.9.2 User Program with Additional Information 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.9.3 Archiving 80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 4 Specifications 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.1 User Program 82. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2 Power Supply Interface 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3 Process Interfaces 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3.1 I/O Numbers 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3.2 Inputs 84. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3.3 Outputs 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4 Data Port 88. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4.1 Operating Port RS 232C 88. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4.2 Communication Port RS 485 (Modnet 1/SFB) 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4.3 Communications Port (RS 232C / Telecontrol Operation) 89. . . . . . . . . . . . . . . . . . . . . . . .4.4.4 I/O Bus 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.5 Processor 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6 Memory 91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6.1 Signal Memory ALU 200 ... 202L 91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6.2 Signal Memory ALU 204, ALU 205 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6.3 Memory for the User Program 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6.4 Back-up Battery (Attached to the I/O Bus) 93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7 Processing Times 93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/22/2019 Plc a120 Aeg

    11/23627 Table of Contents xi

    4.8 Physical Characteristics 94. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.8.1 Construction Data 94. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.8.2 Connection Mode (According to UL Standards) 94. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.8.3 Permissible Line Lengths 95. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.9 Standards, Classifications 95. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.10 Environmental Specifications 96. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.10.1 Climatic Conditions 96. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.10.2 Shock and Vibration 96. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.10.3 Electric Conditions 97. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 5 Earthing and EMC Measures 99. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.1 Earth Grounding and Earthing 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.1 Earth Grounding of All Inactive Metal Parts 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.2 Protective Earthing According to VDE 0100 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.3 Functional Earthing 102. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.4 Reference Conductor System 102. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1.5 Earthing Measures for Cabinet Mounting 104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2 EMC Measures 105. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.1 Measures Taken Regarding Installation and Wiring 105. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2.1.1 Inside a Cabinet 105. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.1.2 Outside Cabinets in Closed Buildings 108. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.1.3 Outside Buildings 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.2.2 Measures Taken Regarding the Power Supply 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.3 Measures Taken Against Direct Radiated Noise 110. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2.4 Measures Taken at Sources of Interference 111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.3 Interference Suppression 111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.4 Design of Peripheral Connections 112. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.4.1 Wiring at Actuators 112. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.4.2 Wiring of the Reference Conductor in an Insulated Layout 113. . . . . . . . . . . . . . . . . . . . . .

    5.5 Protection and Safety Interlocks 114. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix A Module Descriptions 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ALU 200 Central Processing Unit Module Description 117. . . . . . . . . . . . . . . . . . . . . . . . . .

    ALU 201, ALU 201L Central Processing Unit Module Description 127. . . . . . . . . . . . . . .ALU 202, ALU 202L Central Processing Unit Module Description 137. . . . . . . . . . . . . . .ALU 204, ALU 205 Central Processing Units Module Description 151. . . . . . . . . . . . . . . .AS-P120-000 Primary Power Supply Module Description 167. . . . . . . . . . . . . . . . . . . . . . .DCF 77E Receiver Module Description 173. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DNO 201, DNP 205, DNP 210 Power supply Module Description 179. . . . . . . . . . . . . . .DTA 200 to DTA 202 Backplanes Module Description 185. . . . . . . . . . . . . . . . . . . . . . . . . .KOS 202 Modnet 1-Coupler Module Description 191. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UEM 001, UEM 201 Long Distance Data Transmission Equipment 205. . . . . . . . . . . . . .

    Index 221. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/22/2019 Plc a120 Aeg

    12/236

  • 7/22/2019 Plc a120 Aeg

    13/236

  • 7/22/2019 Plc a120 Aeg

    14/23627General2

    1.1 Introduction

    Backplane

    Front Plate

    Modules

    Top Hat Rail

    Label

    Figure 1 Basic Unit

    The Modicon A120 is a DIN-rail mount controller with front connection for smaller tomiddle-sized automation tasks. According to your applicational needs you can chooseone of the three CPUs with different functionalities:

    ALU 200 ... 202L 4 to max. 12 log. instructions, for serial applications and as the telecontrol substationGaedat 120.

    ALU 204, 205 30 / 90 log. instructions, for applications which come close to the performance of A250.

    The A120 provides the following automation functions according to the scope of expan-sion:

    Controlling and computingClosed-loop controlMeasured-value processingSignalling and monitoringPositioningIndirect addressing (in connection with ALU 204 / ALU 205)Fuzzy-logic (in connection with ALU 204 / ALU 205)Sequence control system (in connection with ALU 204 / ALU 205)Diagnosis (in connection with ALU 204 / ALU 205)Visualizing (Viewstar, in connection with ALU 202 ... 205)Communication (in connection with ALU 202 ... 205 oder KOS)

    The backplane is mounted on a top hat rail. The modules are inserted in the backplane(see Figure 1).

  • 7/22/2019 Plc a120 Aeg

    15/23627 General 3

    Backplanes are available which have a 1/2 19 width. They are 3 height units, whereby1 height unit is HE = 44.45 mm high.

    Front panels are used to cover the front connections of the module which, however,permit the functional displays to be seen. The front panels can be marked with insert-able fill-in labels individually for the terminal assignment. When changing the module,the fill-in labels are retained.

  • 7/22/2019 Plc a120 Aeg

    16/23627General4

    1.2 How the Components Work together

    The mode of operation of the A120 (compare Figure 2) is determined by the combinedcoordination of:

    Controller (CPU)MemoriesI/O Modules

    Program MemoryRAM

    Basic SoftwareEPROM / (RAM)

    Signal MemoryRAM

    CPU I/OModulesPAB

    EPROM-Card

    EPROM-Programming Station

    RS232C

    Programming Panel

    Figure 2 Mode of Operation of the A120 (Diagramatic Presentation) when Using the ALU 201L

    1.2.1 The CPU: Purpose and Mode of Operation

    The CPU contains the processor of the A120. It executes the individul instructions of aprogram according to the regulations preset by the basic software. It organizes thereading of external data and signals into the signal memory, processes this data andcarries out calculations, queues continuous processing results in the signal memoryand realizes the output of the results.

    Moreover, the interfaces for the communication with other programmable controllers(only the ALU 202) and for the programming panel connection port are located in theprocessor.

  • 7/22/2019 Plc a120 Aeg

    17/23627 General 5

    1.2.2 The Memory: Purpose and Allocation

    The memory is subdivided into 3 parts:

    Program Memory (RAM or EPROM)Basic Software (EPROM or EPROM card)Signal Memory (RAM)

    The user program is located in the user program memory which effects the control se-quence. The is either loaded from the EPROM card, which was placed into the ALU(see Figure 2) or loaded directly from the programming panel into the RAM.

    The process picture (I/O bits, markers, counter and timers) is filed in the signalmemory. User programs always work with the data from the signal memory and not

    with the input and output signals themselves.

    1.2.3 I/O Modules: Purpose and Types

    All the modules which directly effect the process are I/O modules. The following belongto this group:

    Input/output modules for processing discrete signal states

    Input/output modules for the processing of analog signals

    Counter modules

    Textual modules for the process dependent text output e.g for fault signal logs

    Consoles for the parameter assignment of the time values/number values (time mod-ule / counter module)

    Empty modules for the fixing of lines, which are not required, or for the prewiring ofreserved slots

    1.2.4 Busses

    I/O modules are linked to the CPU via the parallel I/O bus (PAB1) which is located onthe back of the backplane. Contacting the modules using the bus is effected automati-cally when the module is clipped on.

  • 7/22/2019 Plc a120 Aeg

    18/23627General6

    1.3 General Assembling

    The A120 consists of a basic unit and up to 3 expansions (compare Figure 3) accord-ing to your application task.

    The basic unit consists of:

    A basic backplane DTA 200, CPU ALU 200 with integrated supply voltage moduleand up to 3 I/O modules

    or

    a basic backplane DTA 200, a CPU ALU 201L, backplane supply power DNO 201 orDNP 205 or DNP 210 and up to 2 I/O modules

    or

    A basic backplane DTA 200, a CPU ALU 202L or ALU 204 ALU 205, a backplanesupply power DNP 205 or DNP 210 and up to 2 I/O modules

    An expansion consists of:

    An expansion backplane DTA 201 with up to 5 I/O modulesor

    an expansion backplane DTA 202 with up to 2 I/O modules

    Table 5 (page 18) presents an overview of the modules available.

    Configuration Layout Limits ot the A120:

    Table 1 Configuration Limits of the A120

    Configuration I/O slots Discrete I/O

    Points (max.) *

    Basic backplane with ALU 201L ... 205 2 32

    Basic backplane with ALU 200 3 48

    Expansion backplane DTA 201 5 80

    Expansion backplane DTA 202 2 32

    A120 with 3 expansion backplanes

    DTA 201 and ALU 201L ... 205 (maximum configuration) 17 272**

    A120 with 3 expansion backplanes

    DTA 201 and ALU 200 (maximum configuration) 18 288**

    * The I/O modules with 16 I/O points are taken as a basis. If the modules are used with fewer I/O points

    (analog I/O, relay A, ...) the specified maximum value is reduced accordingly.

    ** The expansion which is based purely on a computed maximum numbervalue is not reached in practice by

    using special modules and analog I/O.

  • 7/22/2019 Plc a120 Aeg

    19/23627 General 7

    DTA 200 DTA 201

    DTA 200 DTA 201 DTA 201

    DTA 200 DTA 201 DTA 201 DTA 201

    DTA 200

    DTA 202

    DTA 202

    DTA 202DTA 200

    DTA 200 DTA 201

    DTA 200 DTA 201 DTA 201

    Figure 3 Examples for A120 Layout

  • 7/22/2019 Plc a120 Aeg

    20/23627General8

    1.4 Types of Communication

    1.4.1 Overview

    In the broadest sense of the word the term networking refers to the connection of twoor more intelligent modules (networking nodes) for data exchange purposes. Thetransmission path on which this data exchange is handled is designated as bus. Thedata which has to be transmitted (relaying a message) is coded and transmitted in theform of telegrammes. The type and way of coding (telegramme structure) and the typeof transmission (serial/parallel) is called the networking procedure.

    Telegrammes can basically only be sent on command. One node is specifically entitledto give commands on the bus. It is called master and can communicate with all theother nodes. The master is defined according to the networking procedure on a hard-ware basis or on a software basis. All the remaining networking nodes are calledslaves. They can only communicate with the master.

    A120A250A350A500

    ALU 202... 205

    ALU/BIK

    Modnet 1/SFB

    U120Z300 KOS 202with Modem

    PC-WT1

    Modnet 1/F

    SlaveMaster

    Substation (Slave)Controller (Master)

    Figure 4 Example of a Modnet 1/SFB Network and a Modnet 1/F Network (Diagram

    Note Modnet 1/SFB communication is only possible with the A120, if the basic unit isequipped with a CPU ALU 202L ... 205 .

    Different types of busses are used at the various levels of the hierarchy in a networkedautomation system which is based on changing transfer requirements (e.g. datathroughput, transmittal speed), but these are not absolute assignments:

    Field communication Modnet 1/SFBTelecontrol communication Modnet 1/F

  • 7/22/2019 Plc a120 Aeg

    21/23627 General 9

    1.4.2 Modnet 1/SFB Interfaces

    The Modnet 1/SFB is a serial data bus that establishes the connection between seve-ral networking nodes. It facilitates (DEA procedure) the operation of modules (discreteI/O, analog I/O as well as intelligent function modules).

    BIK modules serve as interface for the transmission and reception of data telegrams.They establish the data transfer between the CPU and the remote I/O.

    Another area of use for this bus is networking. In such an application it can be usedwhen configuring the data path between two programmable controllers that have to belinked together (1N procedure).

    Modicon A120 with ALU 204 or ALU 205 can communicate with other devices through

    a Modnet 1/SFB interface on Modnet 1/SFB as master or slave (refer to Figure 5). 1Nas well as DEA protocols can run across this bus. The interface used for this connecti-on is an RS 485 port which is located on the ALU.

    1.4.2.1 Master in Modnet 1/SFB InterfacesController with Modnet 1/SFB interface ALU 204 / ALU 205 in an A120

    Controller with Modnet 1/SFB interface ALU 151-1 / ... ALU 154 in an A250

    Modnet 1/SFB interface BIK 114, BIK 116 in an A250

    Modnet 1/SFB interface BIK 151 in an A350/A500

    Modnet 1/SFB interface BIK 812 in an A500

    A120 withDEA 201

    DEA = Slave

    A120 withALU 204or ALU 205

    ALU = Slave ALU = Slave

    A120 withALU 202

    ALU 204 or

    A120

    SystemFieldBus

    Programming Devices

    Viewstar 200 PC

    Slave

    Slave

    ALU 205 = Master

    Figure 5 Example of Network between A120 (Master) and Slaves

  • 7/22/2019 Plc a120 Aeg

    22/236

  • 7/22/2019 Plc a120 Aeg

    23/23627 General 11

    1.5 Programming

    1.5.1 Special Programming Language

    AKF12 or AKF125Structured programming is created off-line in Dolog AKF (acc. IEC 1131-3). In additionthere are a number of support and assistance programs for initial start-up. Chapter 1.8contains an overview.

    Instruction List (Anweisungsliste)Ladder Diagram (Kontaktplan)

    Function Block Diagram (Funktionsplan)

    A detailed programming description is included in the documentation of the softwarepackage.

    ALD25 with ALU 204 / ALU 205The software kit ALD comprises the same features as AKF125. Additionally the follo-wing features are provided:

    Sequence Control System (SCS)Diagnosis (Diag)

    The detailed description of the programming is avilable in the documentation belongingto the software kit.

  • 7/22/2019 Plc a120 Aeg

    24/23627General12

    1.5.2 Program Generation

    Programming with the A120 is done off-line. In off-line programming the program is ge-nerated on an IBM-compatible PC (refer to 1.5.3) and subsequently transferred to thePLC. In contrast to on-line programming this does not require communication betweenprogramming device and PLC during program generation which means that the pro-gramming task for the A120 can be carried out at a different location. It is, however, ne-cessary to work with programming software (AKF125 or ALD25) that must be orderedseparately.

    Program Structure

    The structuring of a program means creating transparent and clear, self-contained partsof the application program. These parts are called blocks.

    Technology-specific and repeatable sequences can be used a number of times as de-bugged subprograms within a plant or as technology blocks. Function blocks can becompiled into both general-purpose and application-specific program libraries. Standardfunction blocks for complex control, data-handling and operating functions, integratedinto the PC*, form the foundation for simply creating complex and application-specificsoftware blocks.

    The blocks are composed of networks, the latter representing the lowest level of thestructure. Then user programm is composed of operations, which are assigned with pa-rameters (called instruction in instruction list).

    Figure 7 shows an example of the different structures.

  • 7/22/2019 Plc a120 Aeg

    25/23627 General 13

    Netzwerk2

    Blockend

    CTU

    SV

    S

    R Q

    OB1

    PB11

    FB111

    PB33

    Network1 Network2 Network4 Network5

    Network3Network2Network1

    Network1 Network2 Network3

    Network2 Network3 Network4

    Network3

    PB1 &

    =1

    PB11 PB22

    Network5Network4

    PB33WEG_REFTNNRRDY

    AF

    SFB 26

    BAF

    FILTP1 AUS

    AF

    FB111

    P3P2

    FILTP1 AUS

    AF

    FB111

    P3P2

    Network1

    PB22

    Name:FILT

    Idt: P1 MW IIdt: P2 MW I

    Idt: P3 BIT I

    Idt: AUS MW OIdt: AF BIT O

    :***

    Blockend

    Blockend

    Blockend

    : A = P 3

    : = = A F

    :***

    Network4

    : LD =P1

    : A D D = P 2

    : = =AUS

    :***

    PUMPE

    EIN HTAF

    FB112

    RUECKAUS

    VI

    Figure 7 Example of the Different Structures

  • 7/22/2019 Plc a120 Aeg

    26/23627General14

    1.5.3 Programming- and Peripheral Devices

    1.5.3.1 Programming DevicesThe A210 is programmed with the programming devices of the Modicon product familyor with IBM-compatible PCs.

    P510 (as of device index .03)P610 as of device index .03)P610 CP810P820CP840CIBM-compatible PC

    Table 2 Suitable Programming Devices for the Software Packages

    Available Suitable Operating System

    Software P510 P610(C) P810 / P820C / P820C MS DOS OS/2

    AKF12 / AKF125 yes yes yes yes no

    ALD25 no yes yes no yes

    COMAKF yes yes yes yes no

    CPC125 / CLC12 / FLC12 yes yes yes yes no

    POS20S / TXT10S yes yes yes yes no

    VS110 / VS200 xx yes yes yes yes no

    VS210 no no yes no yes

    Software packages (refer to chapter 1.6, page 16) can be provided for programmingwork and to assist with initial start-up.

    The programming panel will be connected to the RS 232C port of the ALU.

    The programming station EPS 2000 serves for programming the EPROMs.

  • 7/22/2019 Plc a120 Aeg

    27/236

  • 7/22/2019 Plc a120 Aeg

    28/23627General16

    1.6 Overview of the Available Software Kits

    Table 3 provides an overview and a short performance description of the software kitsavailable for the A120. Further information is available from the software kits in the pro-gramming instructions enclosed.

    The software kits are delivered in a slip case. They contain the following:

    Software on 3 1/2-diskettesProgram documentation

    Table 3 Overview of Software Available for the A120

    Type Name Performance Characteristics Comments

    AKF12 Dolog AKF A120 Special programming language as per can only run on IBM-compatible PCs with hard diskIEC 1131-3 in instruction list, ladder

    diagram, function plan

    AKF125 Dolog AKF A120/A250 Special programming language as per can only run on IBM-compatible PCs with hard diskIEC 1131-3 in instruction list, ladder

    diagram, function plan

    MICRO AKF Modsoft AKF Micro Special programming language as per can only run on IBM-compatible PCs with hard diskIEC 1131-3 in instruction list, ladder

    diagram, function plan

    ALD25 AKF/ALD A250 Sequence control system can only run on PCs with OS-2 and hard disk

    COMAKF COM AKF Off-line networking configuration for Dolog AKF can only run on IBM-compatible PCs with hard disk

    CLC12 Loop CTRLA120AKF Function blocks for control technology can only run on IBM-compatible PCs with hard disk

    CPC125 Proces CTRLA120/A250 AKF Function blocks for control technology can only run on IBM-compatible PCs with hard disk

    FLC12 Fuzzy-CTRL A120 Function blocks for fuzzy logik can only run on IBM-compatible PCs with hard disk

    POS20S EXPERT POS 202 Start-up aid (operating, programming per can only run on IBM-compatible PCs with hard diskDIN 66025, monitoring, and archiving)

    TXT10S EXPERT TXT1x2/201 Start-up aid (operating, monitoring) can only run on IBM-compatible PCs with hard disk

    VS110 CONFIG Viewstar 100 Configuration software for Viewstar 100 can only run on IBM-compatible PCs with hard disk

    VS125 Process visual display software for A120 can only run on IBM-compatible PCs with hard disk

    VS 2xx see Catalog

    PROU120 PRO U120 Configuration, parameter assignment and can only run on IBM-compatible PCs with hard disk

    programming of the substation U120.

    PROUZ120 PRO UZ120 Configuration, parameter assignment and can only run on IBM-compatible PCs with hard disk

    programming of the controller substation UZ120.

    PROZ120 PRO Z120 Configuration, parameter assignment and can only run on IBM-compatible PCs with hard disk

    programming of the controller Z120.

  • 7/22/2019 Plc a120 Aeg

    29/23627 General 17

    1.7 Software Revision Index

    The Table 4 gives an overview of the updated software revision index.The following Modules can be programmed:

    CPUfor AKF12 or AKF125 ALU 200, ALU 201, ALU 202for AKF125 or ALD25 ALU 204, ALU 205

    Discrete I/O Modules DEO 216, DEP 208, DEP 209, DEP 210, DEP 211,DEP 214, DEP 216, DEP 218, DEP 220,DAO 216, DAP 204, DAP 208, DAP 209, DAP 210,DAP 212, DAP 216, DAP 218, DAP 220

    Analog I/O Modules ADU 204, ADU 205, ADU 206,ADU 210, ADU 214, ADU 216,DAU 202, DAU 208

    Special Modules FRQ 204, TXT 201, ZAE 201, ZAE 204

    Other Modules DNO 201, DNP 205, DNP 210,KOS 201, KOS 202, KOS 203, KOS 204,DAX 216, DEX 216, DXX 216

    Table 4 Software Revision Index

    Module / Kind of Software SW No.

    SW Product.

    ALU 200 Basic Software Loadable 702 996 1)

    ALU 201L Loadable 701 998 1)2)

    ALU 202L Loadable 701 998 1)6)

    MICROAKF Programming Software (German) 424 703 203 from Version 2.0

    MICROAKF Programming Software (English) 424 704 703 from Version 1.0

    AKF12 Programming Software (German) 424 247 197 from Version 6.0

    AKF12 EN Programming Software (English) 424 271 521 from Version 6.0

    AKF125 Programming Software (German) 424 275 181 from Version 5.0

    AKF125 EN Programming Software (English) 424 275 182 from Version 5.0

    ALD25 Programming Software (German) 424 277 797 from Version 5.0

    COMAKF Communicat. Software (German) 424 247 198 from Version 4.5

    1) can be asked under Online, PC-Status2) when ALU is already loaded with the basic software

  • 7/22/2019 Plc a120 Aeg

    30/23627General18

    1.8 Module Overview

    Table 5 Overview of the Available A120 Modules

    Module Function

    Mechanical Structure

    DTA 200 Basic Backplane, 5 Slots

    DTA 201 Expansion Backplane, 5 Slots

    DTA 202 Expansion Backplane, 2 Slots

    BXT 201 Bus Extension 500 mm (Stacked Drop Layout)

    NUL 200 Dummy Module in Order to Prewire Reserve Slots

    NUL 202 Dummy Module in Order to Support Supply Voltage Lines

    Primary Power Supply Devices

    AS-P120-000 115 ... 230 VAC / 24 VDC, 1 A

    CPUs, Networking and Supply

    ALU 200 CPU, 5.8 ms/1k Instructions

    ALU 201 CPU, 1.3 ms/1k Instructions, with Clock

    ALU 202 CPU, 1.3 ms/1k Instructions, with Clock and Modnet 1/SFB Interface

    ALU 204 Controller, 30 k Instructions with Clock, Battery and Modnet 1/SFB Interface,

    to be programmed with AKF 125 or ALD25.

    ALU 205 Controller, 90 k Instructions with Clock, Battery and Modnet 1/SFB Interface,

    to be programmed with AKF 125 or ALD25.

    DEA 201 Interface to System Field Bus

    DEA 202 Interface to Interbus

    KOS 202 Communication Processor for Modnet 1/F Networks, RS 232C Port,

    can be retrofitted with Modem UE 001

    KOS 203 3) Communication Processor for Modnet 1/F Interfaces, Flash Memory, RS 232C Port,

    can be retrofitted with Modem UE 001

    (see User Manual Geadat 120, Telecontrol Stations A91M.12--271 870)

    DNO 201 Supply Module 24 VDC,

  • 7/22/2019 Plc a120 Aeg

    31/236

  • 7/22/2019 Plc a120 Aeg

    32/23627General20

    Table 7 Cable

    Cable Function

    JE-LiYCY SystemFieldBus cable, by the meter

    VKX 104 Coaxial cable VTH 104 Color monitor, 19.75 ft (6 m) longVKX 114 Quadruple mini coaxial cable VIP 101VTH 104, 6.58 ft (2 m) long

    YDL 032 Cable P510/P610 PRT 294/PRT 295YDL 36.1 Cable PRI 29S (PRT 294/PRT 295) YDL 044YDL 040 System field bus cable, 15.8 (0.4 m) lang

    YDL 044 Adapter cable YDL 36.1 P510/P610YDL 050 Sensor cable for intelligent function modules, cable entry downward

    YDL 051 Sensor cable for intelligent function modules, cable entry upward

    YDL 052 Cable P-device (9-pin connector) A250YDL 053 Cable VIP 101 PRI 29S (PRT 294/PRT 295) , 9.88 ft (3 m) longYDL 054 Cable VIP 101 printer (current loop), 9.88 ft (3 m) longYDL 063 Cable TXT Pxxx (2.5 m) long

    YDL 064 Cable TXT printer (3 m)

    YDL 101 Cable VIP 101 RGB-Monitor, 8.23 ft (2.5 m) longYDL 102 Cable VIP 101 Standard keyboard PBT 102, 4.94 ft (1.5 m) longYDL 103 Cable VIP 101 membrane keyboard PBT 103, 9.88 ft (3 m) longYDL 104 Cable VIP 101 PRI 29S (PRT 294/PRT 295), printer (LS), 16.46 ft (5 m) longYDL 105 Cable VIP 101 programming device (P510/P610), 9.88 ft (3 m) longYDL 106 Cable connecting board on the YDL 108 membrane keyboard PBT 103, 19.75 ft (6 m)YDL 107 Cable VIP 101 MTP 001 for PRI 29S (PRT 294/PRT 295), printer (LS), 6.58 ft (2 m)YDL 108 Cable VIP 101 MTR for PBT 102, PBT 103, 6.58 ft (2 m) long

    Table 8 Accessories

    Device Function

    BBS 1 RS 485 connector

    CER 001 Cable earthing bar for 8 cables

    GND 001 Capacitive discharge terminal

    SIM 011 Slip-on simulator for 8 discrete inputs

  • 7/22/2019 Plc a120 Aeg

    33/23627 Operating 21

    Chapter 2Operating

    This chapter deals exclusively with the themes which are relevant to theoperator of an A120 which runs on the process arranged according tooperating elements and display elements as well as simple maintenancework. It shows how to build an operator interface and supplies refer-ences which are of importance during the programming of system and/oruser-specific operating instructions and maintenance plans for the A120.

  • 7/22/2019 Plc a120 Aeg

    34/23627Operating22

    2.1 Display Elements

    Most modules have LED displays at their disposal for diagosis purposes. There aregreen, yellow and red LEDs and they have the following basic meanings (deviationsare possible):

    Green LED The LED is on if the supply voltage, switching voltage or sensor power supply which isrequired by the corresponding module is available.

    Yellow LED The LED is on if a processor which is available on the module is operating. In I/O mod-ules, it signals an overload or a short circuit.

    Red LED In I/O modules the red LED signals a 1 signal to the corresponding inputs and out-

    puts. Otherwise, its meaning is specific to modules.

    You will find a list of display elements of each module together with the special mean-ings under chapter 2 of each module description.

    2.2 Switches

    The A120 does not have any switches which are exclusively specified for the operation.Correspondingly, no switches are accessible if the front panel is assembled.

    Details regarding the switches are provided for configuration and maintenance can beconsulted in the descriptions of the modules for the corresponding modules.

    Note The DIP switches on the ALU which are accessible after removing the front pan-el of the DTA 200 are configuration settings !

  • 7/22/2019 Plc a120 Aeg

    35/236

  • 7/22/2019 Plc a120 Aeg

    36/236

  • 7/22/2019 Plc a120 Aeg

    37/236

  • 7/22/2019 Plc a120 Aeg

    38/23627Operating26

    2.5 Switching the Supply Voltage on and off

    Switching the supply voltage on or interrupting the supply voltage occurs when:

    The system is switched on and off by the userThe switching on and off of the system as a result of a power failure

    In both cases, one must ensure that no dangerous processing conditions can arise dur-ing the voltage loss or in case of a voltage recovery. This is of special importance inthe event of a power failure, since the voltage recovery can be effected by the user atan indefinite period of time in contrast to the switching on and off of the system.

    2.5.1 Switching the System on and off by the User

    The programmable controller is switched on and off via the central power supply. Checkthat all the measures mentioned in point 2.5.3 have been guaranteed before switchingoff.

    2.5.2 Switching the System on and off as a Result of a Power Failure

    The hazard of a power failure is a permanent risk. Always ensure therefore that all themeasures mentioned in point 2.5.3 have been guaranteed.

    2.5.3 Checking Measures (Inspection)

    Always ensure that the back-up battery(ies) are intactEnsure that the CPU is equipped with at least one working battery so that programsand data are not lost in the event of a failure in the supply voltage. Used batteries musttherefore be replaced immediately. It is recommended to use two batteries in order toincrease the back-up time.

    Do not change DIP switch settingsThe start-up characteristics of the programmable controller is dependent on the prob-lem definition determined during configuration phase and set via the DIP switch on theCPU. The latter may therefore in principle not be changed (basic regulation). Excep-tions to this rule should be mentioned explicitly.

    Note The battery can be waived only if IL and KOS parameters are stored inEPROMs.

  • 7/22/2019 Plc a120 Aeg

    39/23627 Configuration 27

    Chapter 3Configuration

    This chapter contains detailed configuration descriptions, hardwaresettings as well as structuring guidelines with advice regarding systemstart-up.

  • 7/22/2019 Plc a120 Aeg

    40/23627Configuration28

    3.1 Overview

    For device layout you have to configure:

    Equipment and I/O node determination as well as total current at the I/O bus(see chapter 3.2.1, page 29)

    Power supply for supply voltage UB (see chapter 3.3, page 33; chapter 3.3.2,page 36 and chapter 5, page 99)

    Power supply for working voltage US (see chapter 3.3, page 33; chapter 3.3.3,page 45 and chapter 5, page 99)

    Cabling of the sensors (see chapter 3.3.2, page 36 and chapter 5.2, page 105)

    Cabling of the actuators (see chapter 3.3.3, page 45; chapter 5.2, page 105and chapter 5.4, page 112)

    Start-up characteristics (see chapter 3.4, page 51)

    User interface layout (see chapter 3.5, page 52)

    Mounting, earthing, interference suppression, lightning protection, EMC (see chapter3.6, page 53; chapter 5.1, page 100; chapter 5.2, page 105; chapter 5.3, page 111)

    Check list for initial start-up and testing (see chapter 3.8, page 73)

    Dokumenting and archiving (see chapter 3.9, page 76)

  • 7/22/2019 Plc a120 Aeg

    41/236

  • 7/22/2019 Plc a120 Aeg

    42/236

  • 7/22/2019 Plc a120 Aeg

    43/23627 Configuration 31

    3.2.2 Total Current

    Check, if the selected power supply ALU 200 or DNO 201 or DNP 2xx or DEA 20x issufficient for supply of all I/O bus nodes.Table 10 shows a list of all nodes with a maximum loading (current sink).

    A power balance is automatically created by PRO-x120 during configuration.

    In the same way the loading for the dimensioning of the 24 V power supply can be de-termined.

    Table 9 List of Current Sources

    Module Type of Isolation IUB (24V) IPAB (5V)Maximum Maximum

    Primary Secundary

    ALU 200 non-isolated 0.4 A 0.45 A

    DNO 201 non-isolated 0.4 A 0.7 A

    DNP 205 isolated 0.85 A 2 A

    DNP 210 isolated 1.5 A 3.5 A

    DEA 201 non-isolated 0.85 A 1.6 A

    DEA 202 non-isolated 0.85 A 1.6 A

  • 7/22/2019 Plc a120 Aeg

    44/236

  • 7/22/2019 Plc a120 Aeg

    45/23627 Configuration 33

    3.3 Layout of Power Supply

    As the 24 VDC power supply for the A120 modules, the sensors and the actuatorsthree phase bridges without smoothing are sufficient. Monitoring for phase failure isnecessary in this case due to the max. allowable ripple of 5%. For single phase rectifi-cation the 24 VDC should be buffered in such a way, that the specifications given inchapter 4.2, page 83 are satisfied (UB = 20 ... 30 V; max. 5 % ripple)

    At the entry of the fused supply voltage in the system an overload protection (suppres-sor diode) should be connected. See Figure 10.The suppressor diodes, e.g. surge voltage protection OVP 2480 should be wired asquadripoles and arranged with low impedance reference conductors near to the powersupply.

    Every derivation has to be protected by a fuse and should be wired using a suppressordiode if long lines are used, e.g. 1N5646A, AEG E-No. 424 152 500.The fuse was to beadapted to the remissible current loading of the used suppressor diode. The advantageof this arrangement lies in the selective switching off of a branch via the associatedfuse, even if there is a short circuit in the diode.In environments where the risk of being struck by lightning is high, additional lightningprotection arrangements have to be made.Please see: chapter 5.1.3 Functional Earthing and chapter 5.1.4 Reference ConductorSystem.

    F Automatic Circuit-BreakerF25 Power Safety Switch 10 A or 25 A (25 A only with OVP 2480)

    Fa. E-T-A Elektronische Apparate GmbH,D-8503 Altdorf / Nrnberg,

    Order No. 410-K-2-01-17001, 10 A for mounting on top hat railOrder No. 410-K-2-05-17004, 25 A for mounting on top hat rail

    N Power Supply 24 V, max. 25 AV1 Surge Voltage Protection

    OVP 001 (max. 10 A) AEG E-No. 424 244 894, orOVP 2480 (max. 25 A), AEG E-No. 424 247 033(Placed close to the supply module)

    ...

    M

    U

    F

    F25

    3

    24 V --

    F

    F

    24 V

    0 V

    V1

    2,5 mm 2 Cu

    N

    2,5 mm 2 Cu

    ...

    1 3

    2 4

    Figure 10 Principle Power Supply Layout

  • 7/22/2019 Plc a120 Aeg

    46/236

  • 7/22/2019 Plc a120 Aeg

    47/236

  • 7/22/2019 Plc a120 Aeg

    48/23627Configuration36

    3.3.2 Connection Diagram of the UB Supply (24 VDC for Modules andSensors)

    A common supply circuit with its own power supply should be planned for the supply ofthe modules and sensors (inputs).

    Note: The layout shown applies to the length of the supply voltage line. There is ap-prox. 5 m between the power supply and the A120.One should observe chapters 5.2 EMC Measures and 3.3 Structure of the PowerSupply.

    DNO

    201/

    DAP220

    ADU

    214

    ZAE

    201/

    FRQ/ZAE204

    DNP2xx

    ALU

    200

    1a 2 3

    DAP208

    DEP214/

    DEO

    216

    KOS

    2xx

    DAU

    202/

    4

    DAU

    208

    DAP212/

    DAP204/

    DEP217

    5

    ADU

    206/

    POS202

    DEP216

    ADU

    210

    Figure 13 Mounting Example for Connection Diagram of the UB Supply (24 VDC)

    DAP220

    ADU

    214

    DEA

    20x

    1b 2 3

    DAP208

    DEP214/

    DEO

    216

    DAU

    202/

    4

    DAU

    208

    DAP212/

    DAP204/

    DEP217

    5

    ADU

    206/

    ADU

    210

    DEP216

    Figure 14 Equipment example for remote A120 expansion (UB = 24 VDC)

  • 7/22/2019 Plc a120 Aeg

    49/23627 Configuration 37

    C1 Capacitive Discharge Terminal GND 001, AEG E-No. 424 244 899F Automatic Circuit-BreakerF1 Automatic Circuit-Breaker 10 AV1 Surge Suppression OVP 001, AEG E-No. 424 244 894Z1 Shield Connection, Enclosed in Scope of Delivery of Cable Grounding BarZ2 Grounding Clip, AEG E-No. 424 249 007Z3 Cable Grounding Bar CER 001, AEG E-No. 424 244 739

    to ADU, DAU, KOS, ZAE

    to ALU 202

    F1 V1 F Z1 C1 Z3Z2

    Figure 15 Layout of Installation Accessories

  • 7/22/2019 Plc a120 Aeg

    50/23627Configuration38

    F Automatic Circuit-Breaker or FuseF25 Power Safety Switch 10 A or 25 A, see Figure 10, page 33N1 Power Supply for 24 VDC, max. 25 AV1 Surge Voltage Protection, see Figure 10, page 33

    DAUADU,

    F

    F

    F1

    3

    24 V --

    F

    F

    24 V

    0 V

    V1

    1b 2 3

    DEA DEO,DEP

    2,5 mm 2 Cu

    N12,5 mm

    2

    Cu

    DAP

    4

    U1 (UB = 24 VDC)F

    M

    5

    FRQ,POS,

    1a

    ALU,DNO,DNP,KOS

    ZAE

    F

    Figure 16 Connection Overview of the UB Supply (24 VDC)

  • 7/22/2019 Plc a120 Aeg

    51/236

    1a

    27 Configuration 39

    We recommend to build the circuits according to the following detailed circuit diagrams:

    F1 1 A Fuse, Medium Time-LagF1.25 1.25 A Fuse, Medium Time-LagF2 2 A Fuse, Medium Time-Lag

    DNO 201

    M2

    M

    U1 (UB = 24 VDC)

    F2

    21

    20

    19

    18

    22

    ALU 200

    U

    M

    PE

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    KOSF1

    DNP 210

    21

    20

    19

    18

    22

    M2

    F1.25

    M2

    DNP 205

    21

    20

    19

    18

    22

    Figure 17 Detailed Connection for the Supply Modules

    Note: Suppressor diodes are built into the modules ALU 200, DNO 201, DNP 205,DNP 210, KOS 2xx which are dimensioned as EMC protection.

    Note: ALU 200 and DNO 201 / DNP 2xx cannot be connected simultaneously.

  • 7/22/2019 Plc a120 Aeg

    52/236

    1b

    27Configuration40

    M

    U1 (UB = 24 VDC)

    DEA 20x

    21

    20

    19

    18

    22

    M2

    1.25 A Fuse, Medium Time-Lag

    Figure 18 Detailed Connection for remote I/Os

  • 7/22/2019 Plc a120 Aeg

    53/236

    2

    27 Configuration 41

    F2 Automatic Circuit-Breaker max. 2 A for a maximum of 150 inputs resp. 80 relays

    For operating mode Hot Restart the following components should be provided additionally,if while switching of the system the voltage on the inputs drops earlier than the voltage on the ALU.(Reading of the 0 signal in the last program cycle):C2 Smoothing capacity, size depending on loadR1 Current limiting resistor 0.86 Ohm / 3 W, AEG No. 424 104 884

    V3 Isolating diode BYW 80/200, AEG No. 424 201 560

    DEP 216 /

    M2

    M1

    M1

    M

    U1 (UB = 24 VDC)

    F2 Inputs

    I9

    I16

    ............

    I1

    I8

    ............

    R1

    V3

    C2

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    I9

    I16

    ............

    I1

    I8

    ............

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    DEP 220DEO 216

    I9

    I16

    ............

    I1

    I8

    ............

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    DEP 217

    +

    --

    DEP 214 /

    Figure 19 Detailed Connection for Supply of the Discrete Is

    Note: The DEP 208 ... 211, DEP 215 and DEP 218 require no 24 VDC connection,see module discription.

    The noise immunity can be increased, if discharage capacitors are connected to the Uand M terminals of each module. For more information refer to page 62.

  • 7/22/2019 Plc a120 Aeg

    54/236

    3

    27Configuration42

    Us

    M2

    M2

    M1

    M

    U1 (UB = 24 VDC)

    F2

    F2

    Relay Coils

    Inputs

    I1

    I8

    ............

    R1

    V3

    C2

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    DAP 204/DAP 208 DAP 220

    +

    --

    I1

    I8

    ............

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    DAP 212

    Us

    Us

    Us

    Us

    Us

    M4

    (Us)

    (Us)

    Us

    Us

    (Us)

    (Us)

    Us

    M1

    F2 Automatic Circuit-Breaker max. 2 A for a maximum of 150 inputs resp. 80 relays

    For operating mode Hot Restart the following components should be provided additionally,if while switching of the system the voltage on the inputs drops earlier than the voltage on the ALU.(Reading of the 0 signal in the last program cycle):C2 Smoothing capacity, size depending on loadR1 Current limiting resistor 0.86 Ohm / 3 W, AEG No. 424 104 884

    V3 Isolating diode BYW 80/200, AEG No. 424 201 560

    Figure 20 Detailed Connection for Supply of the Discrete I/Os

    Note: The DAP 210 and DAP 218 require no 24 VDC connection, see module discrip-tion.

    Note: Suppressor diodes are built into the modules DAP ... which are dimensioned asEMC protection.

    The noise immunity can be increased, if discharage capacitors are connected to the Uand M terminals of each module. For more information refer to page 62.

  • 7/22/2019 Plc a120 Aeg

    55/236

  • 7/22/2019 Plc a120 Aeg

    56/236

    5

    27Configuration44

    F2 Automatic Circuit-Breaker max. 2A

    M

    U1 (UB = 24 VDC)

    F2

    M1 + M2

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    1213

    11

    22

    ZAE 201/ZAE 204

    M2

    F2

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    1213

    11

    22

    POS 202

    +

    --

    FRQ 204/

    Figure 22 Detailed Connection for Supply of the ZAE and POS

    For detailed data about the connection to the process peripherals please refer to theuser manual or the respective module description.

    Note: Suppressor diodes are built into the modules POS 202, ZAE 201 and ZAE 204which are dimensioned as EMC protection.

    Note: Module TXT 201 doesnt require a 24 VDC connection.

    The noise immunity can be increased, if discharage capacitors are connected to the Uand M terminals of each module. For more information refer to page 62.

    Please earth the shield according to Chap. 3.6.4.2 (page 63)

  • 7/22/2019 Plc a120 Aeg

    57/23627 Configuration 45

    3.3.3 Connection Diagram of the Working Voltage Supply (US = 24 VDCor L = 115 / 230 VAC)

    The working voltages are combined for several outputs (correspond to a group). Everygroup has to be separately protected with a fuse.Please ensure that no unpermissible surge voltages occur which are caused by switch-ing inductive consumers. The latter can lead to risk of or destruction of semi conductorsin the programmable controller.

    US = 24 VDCThe working voltage supply should be effected from a separated power supply. Otherpower supplies should be planned for switching currents which are >25 A.

    Auxiliary circuits can be operated in an grounded or ungrounded state according toVDE 0100 and VDE 0113. When operating in an ungrounded state, insert an insulationmonitoring appliance in order to send a message in the event of an insulation error oc-curring.

    L = 115 / 230 VACActuators supplied with 115 VAC or 230 VAC can be interconnected to the contacts ofthe modules DAP 204, DAP 208 and DAP 212, see Figure 27, Page 49.

    Note: It is only permissible to use one power supply for the whole system, if the sup-ply requirement, is

  • 7/22/2019 Plc a120 Aeg

    58/23627Configuration46

    F Automatic Circuit-Breaker or FuseF25 Power Safety Switch 10 A or 25 A, see Figure 10, page 33N2 Power Supply for 24 VDC, max. 25 AV1 Surge Voltage Protection OVP ..., see Figure 10, page 33

    ...

    M

    U2 (Us = 24 VDC)

    F

    F

    3

    24 V --

    F

    F

    24 V

    0 V

    V1

    6 7

    DAP 204DAP 208DAP 212

    DAO 216DAP 216

    . . . . . .

    2,5 mm 2 Cu

    N2

    2,5 mm 2 Cu

    ...

    . . . . . .

    . . . . . .. . . . . .

    ...

    ...

    8

    DAP 204

    DAP 220

    DAP 208

    L = 115 /

    N

    230 VAC

    DAP 217F25

    9

    DAP 212

    L = 115 /

    N

    DAP 210

    DAP 218

    (230 VAC)

    DAP 292DAP 292

    Figure 24 Connection Overview of the US Supply (24 VDC)

    We recommend to build the circuits according to the following detailed circuit diagrams:

    The connection diagrams give additionally information about the measures to be carried

    out depending on the supply voltage.

    FusingOvervoltage protectionProtection circuit with inductive load (RC-circuit) etc.

  • 7/22/2019 Plc a120 Aeg

    59/236

  • 7/22/2019 Plc a120 Aeg

    60/236

  • 7/22/2019 Plc a120 Aeg

    61/236

  • 7/22/2019 Plc a120 Aeg

    62/236

    9

    27Configuration50

    DAP 212,

    N

    UB

    UB

    R

    R

    R

    R

    Q1

    Q2

    Q3

    Q4

    M1

    M2

    L = 115 VAC

    F4 F4

    C

    C

    C

    C

    Q7

    Q6

    Q3

    Q2

    Q8

    Q5

    Q4

    Q1

    DAP 210

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    DAP 292

    .

    .

    .

    .

    Q16

    Q9

    Q8

    Q1

    DAP 218

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    5

    4

    3

    1

    2

    12

    13

    11

    22

    .

    .

    .

    .

    .

    .

    .

    .

    F4 Automatic Circuit-Breaker max. 4 AL Hot L1 / L2 / L3N Reference ConductorRC Sufficient RC Wiring (According to Manufactor Data),

    Absolutely Necessary for Inductive Actuator (Loads)

    The fuses for DAP 210 and DAP 218 are integrated in the module.

    Figure 28 Detailed Connection for L = 115 VAC

    The relay contacts of DAP 212 and DAP 294 can switch 230 VAC, too.

  • 7/22/2019 Plc a120 Aeg

    63/23627 Configuration 51

    3.4 Start-Up Characteristics

    Please configure a main switch that can be operated mechanically for switching sup-ply voltage on and off. You have to integrate supply of the A 120 and supply of thesensors and actuators.In case of danger for man and machine please configure an additional emergency-out-equipment according to chapter 5.5 (page 114).

    Determine the kind of start-up characteristics (cold restart / hot restart / manual start/ automatic start) by setting the DIP switches B0 and B1. For more details, see theresp. module description of the ALU.

    Please make sure that no dangerous process conditions arise during voltage failure or

    voltage recovery. Especially consider this during powerfail, because voltage recoverycan happen at an undefined moment in contrast to switching the system on and off.

    Note: At Geadat 120During normal telecontrol processing the dialog with substations is exclusively executedby the telecontrol master station. For operation on-site a PADT is used.

  • 7/22/2019 Plc a120 Aeg

    64/236

  • 7/22/2019 Plc a120 Aeg

    65/236

  • 7/22/2019 Plc a120 Aeg

    66/23627Configuration54

    ca. 920

    ca. 215ca. 125

    ca. 10

    80 65 150

    6HE=266,7

    125...130

    60,5

    for M4/M5

    M4

    Top Hat Rail Backplane

    Top Hat Rail for Automatic Circuit-Breaker

    Second Row

    Figure 30 Bore Holes for Top Hat Rail and Backplane at Rear Connection

    max. 450

    ca. 215ca. 125

    ca. 10

    80 65 150

    6HE

    =266,7

    125...130

    60,5

    for M4/M5

    Top Hat Rail Back-

    Top Hat Rail for Automatic Circuit-Breaker

    plane

    Second Row

    125

    Figure 31 Bore Holes for Top Hat Rail and Backplanes at 19 Rack Mount

    Note: The distance of 6 HE to the second row must be kept when the bus extensioncable BXT 201 is used.

  • 7/22/2019 Plc a120 Aeg

    67/23627 Configuration 55

    3.6.2 Backplanes

    3.6.2.1 Mounting BackplanesPlace the backplane DTA 200, DTA 201 and DTA 202 in the following order on the tophat rails:

    Step1 Pull down the two clips which are located at the bottom of the backplane.

    Step2 Place the clip on the rear of the backplane over the top of the top hat rail.Using a 15 mm top hat rail:Before rest the attached bracing elements A flush against the bore holes on the back ofthe backplane.

    Step3 Drop the backplane into place against the mounting surface.

    Step 4 In addition you can secure the DTA by using two screws (max. 4 mm ).Using a 7.5 mm top hat rail (acc. DIN-EN 50 022): ca. 20mm longUsing a 15 mm top hat rail: ca. 25 mm long.

    Step 5 Push the two clips up into position.

    3

    2

    A44

    11

    Figure 32 Installation the backplanes

  • 7/22/2019 Plc a120 Aeg

    68/236

  • 7/22/2019 Plc a120 Aeg

    69/23627 Configuration 57

    3.6.2.3 Mounting and Connecting Backplanes by Using the BXT 201If the backplanes are stacked on two top hat rails (stacked drop layout), they are con-

    nected by a BXT 201 bus extension cable.Using the BXT 201, you must not use the DTA 202 that is always the last backplane ina drop.For mounting proceed as follows:

    Step 1 Before mounting the last backplane, please remove bus ribbon cable (see Figure 35)

    DTA 200 DTA 201

    DTA 201BXT 201

    DTA 201

    Bus Ribbon Cable

    Figure 34 Stacked Drop Layout

    Figure 35 Remove Bus Ribbon Cable

  • 7/22/2019 Plc a120 Aeg

    70/23627Configuration58

    Step 2 Mount the cable cleat in level with the respective backplane and follow the sequence offigures. The cleat is used for:

    mounting the BXT 201marking the boundaries of the backplane

    Figure 36 Mounting of the Cable Cleat

    Step 3 Now connect the BXT 201 bus extension cable to the respective backplane (seeFigure 37).It is absolutely necessary to connect terminal A to the basic backplane line.

    min. 60

    max. 120

    6HE

    =266.7

    Figure 37 Mounting of the BXT 201 Bus Extension Cable

  • 7/22/2019 Plc a120 Aeg

    71/23627 Configuration 59

    Step 4 Attach the cable ends to the cable cleats according to Figure 38

    Figure 38 Cable Grip of the BXT 201 Bus Extension Cable

    3.6.3 Modules

    1.

    2.3.

    Figure 39 Installing ALU

  • 7/22/2019 Plc a120 Aeg

    72/23627Configuration60

    1.

    2.3.*

    * Provides contactingto the hat rail

    Figure 40 Installing of the remaining modules

    Figure 41 Complete assembly of the A120

  • 7/22/2019 Plc a120 Aeg

    73/236

  • 7/22/2019 Plc a120 Aeg

    74/23627Configuration62

    Improving EMC Immunity on ModulesTo improve EMC immunity on modules, it is recommended to discharge U and M con-

    nections capacitively as short as possible from the terminal to functional earth. For thisreason make use of the capacitive discharge terminal GND 001, see Figure 43.

    F Automatic Circuit-BreakerC1 Capacitive Discharge TerminalGND 001, AEG E-No. 424 244 899

    21

    20

    19

    18

    17

    16

    15

    14

    10

    9

    8

    7

    6

    54

    3

    1

    2

    12

    13

    11

    22

    M

    U = 24 VDC

    I/O Module

    C1

    2,5 mm Cu2

    F

    1 2 3 4 5 6 7 8

    9 10 11 12 13 14 15 16

    U

    M

    Figure 43 Improving EMC Immunity on Modules

    Note: In case of environment with high disturbance, it is recommended to increasethe capacity on C1 from 2.2 nF to 22 nF.

  • 7/22/2019 Plc a120 Aeg

    75/23627 Configuration 63

    3.6.4.2 Earthing the Shielded CablesThe following table gives an overview of cables corresponding to applicational needs.

    Type E-No. Characteristics Use

    LiYrdF(Cgv)Y 424 002 691 shielded, 3 x 0.14 mm2 DCF 77E to KOS

    JE-LiYCY 424 234 035 shielded, twisted pair, SystemFieldBus to ALU 202,

    2 x 2 x 0.5 mm2 Inputs, Outputs for ADU and DAU;

    Impuls Counter for ZAE 204;

    Impuls Counter for ZAE 201

    MIYLY(C)Y 424 036 301 shielded, 5 x 0.5 mm2 Output module to TXT 201

    MIYLY(C)Y 424 153 530 shielded, 8 x 0.75 mm2 Sensor and drives for POS 202

    LiYrdF(Cgv)Y 424 238 059 shielded, twisted pair, Group Connection to ZAE 204;

    5 x 2 x 0.5 mm2 Position Sensing for ZAE 201;

    Sensor and drives for POS 202

    LiYrdF(Cgv)Y 424 219 915 shielded, 10 x 0.14 mm2 Sensor for POS 202

    Please earth the shielded cables as follows:

    Lay the shielded cable via the Cable Earthing Bar CER 001

    Remove shield insulation from the cable at the height of the cable cleat

    Press the cable with the shield removed into the cable cleat (contact to top hat rail)

    Use cable clips to relief strain on cables (see Figure 44)

    Cable Earthing Bar CER 001, AEG E-No. 424 244 739

    Figure 44 Earthing the Shields of I/O Cable to ADU, DAU, KOS, ZAE

    In case of long shielded cables observe the instructions in chapter 5.2 EMV-mea-sures, page 105.

  • 7/22/2019 Plc a120 Aeg

    76/23627Configuration64

    3.6.5 Dimension Drawing

    213

    127

    7,5

    142 8

    64 125

    16

    SlotforMounting/Demounting

    Figure 45 Dimension Drawing A120

  • 7/22/2019 Plc a120 Aeg

    77/23627 Configuration 65

    3.6.6 Disassembly

    The disassembly should be carried out in the reverse order of the assembly (accordingto the user information enclosed).

    3.6.7 Electrical Connection

    Connect modules (with the exception of ALU 201 and ALU 202) according tochapter 3.3, page 33

  • 7/22/2019 Plc a120 Aeg

    78/23627Configuration66

    3.7 Configuration of the SystemFieldBus Line

    3.7.1 Transmission Rates (Baud Rates) of the SystemFieldBus Interface

    Data transfer occurs according to baud rate either in self-clocked-mode.To guarantee correct data transfer, the cable lengths listed in Table 11 must not be ex-ceeded.

    Table 11 Transmission Rate and Core Number Depending on Cable Length

    Baud Rate Max. Bus Length

    62,5K baud 1200 m

    375K baud 300 m

    Each field bus line from devices with several Modnet 1/SFB interfaces can be set toanother baud rate.The baud rate on ALU and DEA is set with a DIP switch (refer to Description of Modu-les) and must be uniform within a field bus line.

    3.7.2 SystemFieldBus Connection

    The bus cable that enables interactive networking of ALU / DEA (slave) to ALU (master)must be built by the user. To do this, the BBS 1 connector and the JE-LiYCY cable are in-dividually available. Ordering instructions for the bus cable (by the meter) and the BBS1connector can be found in Chapter 4 of the module description (ALU 202). For distancesof less than 0.5 m, the already assembled YDL 40 cable can be used.

    The cable is fed from DEA to DEA (bus networking) beginning at the master (ALU) withdouble assignment of the terminals.

  • 7/22/2019 Plc a120 Aeg

    79/23627 Configuration 67

    3.7.3 Building the Cable

    Step 1 Cut cable to desired length.

    Step 2 Prepare the cable ends as shown in Figure 46 (left).

    Drawn to Scale 1:1CF Cu-foil shieldCS Cable ShieldPV PVC Jacket

    30 + 5

    + 2 7 +1

    7.3

    12

    CS

    PVPV

    CS

    CF

    Figure 46 Preparation of the Cable for the Attachment of the RS 485 Connector

    Step 3 Turn the cable shield CS over the PVC sheath PV.

    Step 4 Wrap as shown in figure (right) the overlapping cable shield with the enclosed Cu-foilshield CF.

    Step 5 Use as shown in the Figure 47, to fasten both cables in the area of Cu-foil shield (en-sure permanent cable shield bonding).

    Step 6 Connect the individual cores according to their colors as per Figure 47.At 62.5 or 375K baud a connection to the ports 3 and 8 (two-wire port) is sufficient.

    Step 7 If only one cable is connected to BBS 1 (beginning of bus and end of bus), the termina-ting resistors marked A in Figure 47 are preserved.If two cables are connected (looped-through bus) the terminating resistors (diagonalcutters) are removed. Close the BBS1 connector (cover and screws in separate plasticbags).

    Step 8 Plug BBS1 onto ALU and DEA and tighten screw.

    Step 9 Execute the discharge measures of the shield according to Chapter 3.7.4, page 69.

  • 7/22/2019 Plc a120 Aeg

    80/23627Configuration68

    A Terminating resistors, 120 eachB TerminalsC Cable cleatD Cable

    GE (YE) yellow coreGN (GN) green coreBR (BN) brown coreWS (WH) white core

    A

    B

    C

    D

    CD

    Figure 47 Assignment of Terminals/Ports on the BBS1 Connector

  • 7/22/2019 Plc a120 Aeg

    81/23627 Configuration 69

    3.7.4 Modnet 1/SFB Discharge Measures

    In case the ALU 202 is used as slave on Modnet 1/SFB, prepare the bus cable asshown in chapter 3.7.3, page 67. The shielding on the system field bus (SFB) as node(slave) should not be grounded directly due to the transient currents.Therefore the ALU 202 should be grounded only via the capacitive discharge terminal.

    C1 Capacitive Discharge Terminal GND 001, AEG E-No. 424 244 899Z1 Shield Connection,Included in Scope of Delivery of Cable Grounding Bar CER 001Z2 Grounding Clip, AEG E-No. 424 249 007

    Figure 48 Discharge Measures of ALU 202 Shield as Modnet 1/SFB Node (Slave)

    Note: A longer SystemFieldBus Cable that has been installed but not yet connectedmust be statically discharged. Proceed as follows:

    first connect BBS 1 to superior station (BIK)discharge the backplane of the other BBS1 nodes via PE

  • 7/22/2019 Plc a120 Aeg

    82/236

  • 7/22/2019 Plc a120 Aeg

    83/23627 Configuration 71

    3.7.5 Surge Voltage Protection for SystemFieldBus Cable Outside Build-ings

    In order to protect the transmission appliances, e.g. Modnet 1/SFB, from networkedsurge voltage (lightning bolt) it is recommended to use a surge suppressor in the dis-tributor mains. The rated leakage current should thus be 5 kA at least, e.g. type ARE,Order No. 919 232 to be ordered from:

    Fa. Dehn und ShneMail Box92318 Neumarkt 1

    For the protection of one Modnet 1/SFB cable two lightning ductors ARE in each build-ing are required.

    88

    35517.5

    45

    90

    IN

    OUT

    3

    4

    OUT

    1

    2

    IN

    Figure 50 Circuit Diagram and Dimension Drawing of the Lightning Ductor ARE

  • 7/22/2019 Plc a120 Aeg

    84/23627Configuration72

    W1 Modnet 1/SFB-Connection Cable JE-LiYCY, AEG E-No. 424 234 035Z2 Grounding Clip, AEG E-No. 424 249 007

    ARE ARE ARE ARE

    Outdoors

    ye

    gn

    DIN-Top hat rail

    shield

    SFB-node

    6 mm 2

    Z2

    W1

    6 mm 2

    ye

    gn

    shield

    Building 1 Building 2

    Figure 51 Connection Plan of the Lightning Ductor ARE

    Please note the following items:

    Green and yellow cores may not be interchanged

    Dontt mistake IN and OUT side (IN = field side)

    Functional ground (potential equalizer rail) has to be installed

    The Lightning Ductors have to be installed next to functional ground so that thesurge current can be discharged at the shortest way to the building ground. The linehas to be as short as possible with a minimum of 6 mm2

    In one pair of lines of a SystemFieldBus maximum 10 lightning ductors can be con-

    nected in series, i.e. max. 5 field line sections are possible.

  • 7/22/2019 Plc a120 Aeg

    85/23627 Configuration 73

    3.8 Checklist for Initial Start-up and Test

    The following chapter contains information that is necessary or recommended for initialstart-up. This informatiom applies for operating mode cold restart when the ALU is in-stalled.Setting measures are not mentioned here but in the relevant module descriptions.

    Note The settings mentioned here can differ from later system operation settings.The settings have to be adapted to the respective applicational requirements (see rele-vant module description).

    3.8.1 Setting, Mounting

    Top Hat RailMount top hat rail according to chapter 3.6.1, page 53

    DTAMount and connect backplane according to chapter 3.6.2, page 55The screw must not be removed from the DTA 200 (as delivered)

    ALUDIP switch check (as delivered)

    B0 and B1 in OFF position (manual restart)B2 in OFF position (RAM operation for initial start-up)

    Install in slot 0 of the DTA 200 according to chapter 3.6.3, page 59

    KOS 202Replace firmware and parameter EPROM, if requiredEquip and set additional (RAM / EPROM)Define networking parameters by PRO--FWT softwarePlug-in transmission module (e.g. UEM 001)Connect DCF-77.5 receiver, if requiredSelection of 201 or 202 operationInstall modules in backplane according to chapter 3.2.1, page 29

    Mounting according to chapter 3.6.3, page 59

    DEA 201DIP switch check (as delivered)

    S0 in ON position andS1 in OFF position (375 kBit/s)S2 and S3 in OFF position (master defaults of the switch-off are effective)

    Install in slot 0 of the DTA 200 according to chapter 3.6.3, page 59

    DEA 202DIP switch check (as delivered)

    S0 in OFF position (with status and parameter)

    S1 in OFF position (DEA-control word active)S2 and S3 in OFF position (master defaults of the switch-off are effective)Install in slot 0 of the DTA 200 according to chapter 3.6.3, page 59

    DNO 201, DNP 205, DNP 210Install in slot 1 of the DTA 200 according to chapter 3.6.3, page 59 (no settings)

  • 7/22/2019 Plc a120 Aeg

    86/23627Configuration74

    DEP-, DAP-, DAU-, NUL-ModulesInsert I/O modules in backplane according to chapter 3.2.1, page 29

    Installation according to chapter 3.6.3 (no settings)

    ADU 204Check ON position at DIP switch B1 (suppression of 50 Hz noise, as delivered)Install I/O modules in backplane according to chapter 3.2.1, page 29Mounting according to chapter 3.6.3, page 59

    ADU 205Check ON position at DIP switch B1 (suppression of 50 Hz noise, as delivered)Check ON position at DIP switch B2 (input voltage, as delivered)Install I/O modules in backplane according to chapter 3.2.1, page 29Mounting according to chapter 3.6.3, page 59

    ADU 206, ADU 210, ADU 216Insert I/O modules in backplane according to chapter 3.2.1, page 29Installation according to chapter 3.6.3 (no settings)

    ADU 214Check ON position at DIP switch B1 (suppression of 50 Hz noise, as delivered)Check ON position at DIP switch B2 (fritting activ, as delivered)Install I/O modules in backplane according to chapter 3.2.1, page 29Mounting according to chapter 3.6.3, page 59

    FRQ 204see Benutzerhandbuch (user manual) document part number A91V.12-703 821

    POS 202see Benutzerhandbuch (user manual) document part number A91V.12-279 339

    ZAE 201see Benutzerhandbuch (user manual) document part number A91V.12-271 856

    ZAE 204see Benutzerhandbuch (user manual) document part number A91V.12-271 962

    MiscellaneousInstall power supply circuit and take measures against surge voltage according to

    chapter 3.3, page 33Connect modules (with the exception of ALU) according to chapter 3.3, page 33Enter system related data onto the imprint strips of the individual modules (severedge of typewriter)Insert filled fill-in labels of the individual modules into the front panel of the backplaneSwitch on the power supply. The green supply LED is on all the modules

    For later program generation and transmission proceed as described in chapter 3.8.2,page 75

    Caution Only disassemble I/O modules after switching off working voltage on

    the respective modules.

    Note The DIP switch settings are only relevant, if supply voltage is connectet.

  • 7/22/2019 Plc a120 Aeg

    87/23627 Configuration 75

    3.8.2 Creating and Transmitting Programs

    YDL 32 +DRI 29P /

    PRT 294

    PRT 295EPS 2000

    YDL 36.1 +DRI 29S

    YDL 32 +DRI 29P /

    YDL 36.1 +DRI 29S

    LPT1 (PRT)/

    YDL 52

    YDL 36.1 +YDL 44

    COM1

    Pxxx

    A120

    COM1/COM2

    Figure 52 Connecting Programming Panels and Printers to the A 120

    Dolog AKF12 for ALU 200 ... 202LCreate user programm in off-line mode (see Dolog AKF12-Software part Program-ming)Transfer program to programmable controller RAM.

    As the transmission routine is different for each ALU type, proceed as follows:ALU 200 continued on page 121ALU 201 continued on page 134ALU 202 continued on page 148

    Dolog AKF125 or ALD25 for ALU 204, ALU 205Create user programm in off-line mode (see Dolog AKF125-Software part Program-ming)

    Transfer program to programmable controller RAM.Continued on page 164

  • 7/22/2019 Plc a120 Aeg

    88/236

  • 7/22/2019 Plc a120 Aeg

    89/236

  • 7/22/2019 Plc a120 Aeg

    90/23627Configuration78

    Table 12 gives an overview of the settings (protective circuits) mentioned in the docu-mentation aids.

    Table 12 Settings that can be Documented

    Type of Settings Modules Jumpers / Comments*

    Slots

    Equipment DTA 200 0 ... 3 Type of Module, I/O Node

    DTA 201 4 ... 18 Type of Module, I/O Node

    DTA 202 4 ... 18 Type of Module, I/O Node

    Earthing System DTA 200 Z Earth Ground Connected /

    not Connected

    Node Addresses ALU 202L ... 205 A0 ... A7 Slave-Adresse

    Start-Up Characteristics ALU B0 Cold Restart / Hot Restart

    B1 Automatic Start / Manual Start

    Type of Memory ALU 200 B2 OFF / ON - Line Mode

    ALU 201L, ALU 202L B2 RAM- / EPROM-Mode

    Second Battery ALU 201L ... 205,

    KOS 20x Equipped / not Equipped

    Transmission Rate

    Modnet 1/SFB ALU 202L ... 205 B3 62.5 / 375 kBd

    DEA 201 S0, S1 62.5 / 375 kBd

    Modnet 1/F KOS 202 ------ 600 Bd,

    also 1200 Bd, if CCITT frequencygrid

    Modnet 1/SFB Termination ALU 202L ... 205 Terminating Aviable / not Available

    Resirtors

    Modnet 1/F UEM 001 Various jumpers

    Modnet 1/F Termination Terminators existing / removed

    Switsch-off Behaviour DEA 201, DEA 202 S2, S3 forced switch-off /

    Master defaults are effective /

    switch-off with data saving

    Status Processing DEA 202 S0 with / without status and parameter

    Control Word Processing DEA 202 S1 DEA control word active / inactive(BKF 101 / BKF 102)

    Noise Suppression ADU 204, ADU 205,

    ADU 214 B1 50 Hz / 60 Hz

    Type of Input ADU 205 B2 Current Input / Voltage Input

    Fritting Procedure ADU 214 B2 activ / no activ

    Identcode ADU 216 J1 ADU 216 / ADU 206

    Sensor Signal Level ZAE 201 B1 24 V / 5 V

    * For more information see resp. module description.

  • 7/22/2019 Plc a120 Aeg

    91/23627 Configuration 79

    3.9.2 User Program with Additional Information

    This documentation is stored on hard disk or diskette and can be displayed to a moni-tor or printed out.

    The following documents are availble:

    Overview (program structure)

    Program Listing (user program)

    Equipment List including determined parameters, as number of:

    Marker bits

    Marker bytesMarker wordsMarker double wordsTimerCounter

    Selection of the Measuring Range (for ADU 206, ADU 210, ADU 214, ADU 216)

    Cross Reference List

    Symbols and Comments (symbols and comments of hardware addressese.g. inputs, outputs, markes)

    Signal Allocation List (log of signals used in the program)

    Complete Documentation (output of all lists mentioned above)

    For detailed description see slipcase of diskettes Dolog AKF for A120.

  • 7/22/2019 Plc a120 Ae