Planning IMI international pressurization systems

  • Upload
    jack-bc

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

  • 7/29/2019 Planning IMI international pressurization systems

    1/20

    engineering ADVAnTAgePressurisation & Water Quality Balancing & Control Thermostatic Control

    Pa ad aat

    Selection o the most suitable products orpressure maintenance | degassing | water make-up

    Reliable pressurisation is the basic requirement or a gentle and trouble-ree operation o heating,

    solar and cooling water systems. Our planning and calculation basics support you in choosing the right

    products, their size and perormance.

  • 7/29/2019 Planning IMI international pressurization systems

    2/20

    2

    PNEUMATEX PlAnning AnD cAlculATion

  • 7/29/2019 Planning IMI international pressurization systems

    3/20

    3

    PNEUMATEX PlAnning AnD cAlculATion

    Tab f tts

    Page

    caats

    4 5 General equations

    Stat st

    6 Quick selection

    7 Equipment

    cmpss st

    8 Quick selection

    9 Equipment

    Tasf st

    10 Quick selection

    11 Equipment

    Aqapss st

    12 Aquapresso in potable hot water systems

    13 Aquapresso in pressure-boosting systems

    13 Aquapresso pressure losses

    Safty thy

    14 Devices or sealed heating systems

    gssay

    15 General terms

    15 Geometry

    16 17 Pressures

    17 Volumes

    18 Temperatures

    19 Capacities

  • 7/29/2019 Planning IMI international pressurization systems

    4/20

    4

    PNEUMATEX PlAnning AnD cAlculATion

    caat

    Pressure maintenance

    Heating systems TAZ 110 C ollowing EN 12828, solar systems ENV 12977-1

    ga qats

    VA Water capacity o the system VA = VA central heating + VA district heating pipe : System design

    VA = vA Q + VA district heating pipe vA Specic water capacity, table 2

    Q Installed heat capacity

    Ve Expansion volume Ve = e VA e Expansion coecient or tmax, table 1

    VV Water reserve VV 0,005 VA 3 litre

    P0 Miniumum pressure 2) P0 = HST/10 + pD + 0,3 bar pZ pD (TAZ), table 1

    pa Initial pressure pa P0 + 0,3 bar

    Stat

    D Pressure actor D = (pe + 1)/(pe P0)

    VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) D VN 80 litre with Statico + Vento

    VK Collector volume1)

    pe Final pressure pe PSV ASV ASV = 0,5 bar or PSV 5 bar4)

    ASV = 0,1 PSV or PSV > 5 bar4)

    cmpss

    VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) 1,1 VK Collector volume1)

    pe Final pressure pe = pa + 0,2 pe PSV ASV

    TecBox Q = (HST) : page 8

    Tasf

    VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) 1,1 VK Collector volume1)

    pe Final pressure pe = pa + 0,4 pe PSV ASV

    TecBox Q = (HST) : page 10

    itmdat vsss5)

    VN Nominal volume VN VA e + 1,1 VK 1) + 5 3) e or tR and tmin, table 1

    1) In solar systems to ENV12977-1: collector volume VK that can evaporate when not in operation; otherwise VK = 0.2) The ormula or the minimum pressure P0 applies to the installation o the pressure maintenance on the suction

    side o the circulation pump. In case o a pressure-side installation P0 is to be increased by the pump pressure p.3) Add 5 litre when a Vento is installed in the system.4) The saety valves must work within these limits.5) Necessary or: heating systems tR > 70 C, chilled water systems tmin < 5 C, not or Transero TV and TPV.

    Table 1: e expansion coecient and pD vapour pressure

    t ( TAZ, tmax, tr, tm) | c 34 28 24 10 0 40 50 60 70 80 90 100 105 110

    e | 0 % glycol * = 0 C 0 0,0074 0,0118 0,0168 0,0224 0,0287 0,0356 0,0432 0,0472 0,0514

    pD | bar 0,2 0,4

    e | 40 % glycol * = -24 C 0 0,0059 0,0239 0,0300 0,0364 0,0431 0,0502 0,0576 0,0653 0,0693 0,0734

    pD | bar 0,2

    e chilled water systems t < 5 C 0,0110 0,0086 0,0066 0,0014

    e heating systems tR > 70 C 0,0063 0,0132 0,0208 0,0248 0,0290

    Table 2: vA approx. water capacity ** o central heatings reerred to the installed heat capacity Q

    tmax | tr c 90 | 70 80 | 60 70 | 55 70 | 50 60 | 40 50 | 40 40 | 30

    Radiators vA litre/kW 14,0 16,5 20,1 20,6 27,9 36,6

    Flat radiators vA litre/kW 9,0 10,1 12,1 11,9 15,1 20,1

    Convectors vA litre/kW 6,5 7,0 8,4 7,9 9,6 13,4

    Air handlers vA litre/kW 5,8 6,1 7,2 6,6 7,6 10,8

    Floor heating vA litre/kW 9,2 10,3 11,8 11,9 14,7 18,0 26,8

    * Antirogen N ** Water capcity = heat generator + distribution net + heat emitters

    Our on line calculation programSelectP! is based on an advancedcalculation method and data base.Thereore results may deviate slightlyin marginal areas.

  • 7/29/2019 Planning IMI international pressurization systems

    5/20

    5

    PNEUMATEX PlAnning AnD cAlculATion

    Ps pss mata

    Air controlled Compresso or

    water controlled Transero

    minimize the pressure variations

    between pa and pe.

    Compresso 0,1 bar

    Transero 0,2 bar

    P0 Mmm pss

    Stat

    P0 is set as pre set

    pressure on the

    gas side.

    cmpss

    P0 and the switching

    points are calculatedby the BrainCube.

    : page 4

    Tasf

    P0 and the switching

    points are calculated

    by the BrainCube.

    : page 4

    pa ita pss

    Stat

    pa is the cold ll pressure

    which determines the

    water reserve:

    pa P0 + 0,3 bar;

    water make-up on:

    pa 0,2 bar.

    cmpss

    pa allen short o during

    cooling, then compressoron.

    pa = P0 + 0,3

    Tasf

    pa allen short o during

    cooling, then pump on.

    pa = P0 + 0,3

    p Fa pss

    Stat

    pe is reached ater

    heating up to tmax.

    pe = PSV ASV

    cmpss

    pe exceeded by heating

    up, then air-side solenoidvalve open.

    pe = pa + 0,2

    Tasf

    pe exceeded by heating

    up, then water-side

    solenoid valve open.

    pe = pa + 0,4

    Table 3: DNe standard values or expansion pipes with Statico and Compresso

    Length up to approx. 30 m Dn 20 25 32 40 50 65 80 100

    Heating TAZ 110 C | Solar Q | kW 1.000 1.700 3.000 3.900 6.000 11.000 15.000 23.000

    Cooling tmax 50 C Q | kW 1.600 2.700 4.800 6.300 9.600 18.100 24.600 36.800

    Table 4: DNe standard values or expansion pipes with Transero T_ *

    T_ 4.1 T_ 6.1 T_ 8.1 T_ 10.1 T_ 4.2 T_ 6.2 T_ 8.2 T_ 10.2 TPV...P

    Length up to approx. 10 m Dn 32 32 32 32 50 | 40 50 | 40 50 | 40 50 | 40 50

    HST | m all all all all < 20 | 20 < 25 | 25 < 35 | 35 < 50 | 50 all

    Length up to approx. 30 m Dn 32 40 | 32 40 | 32 40 | 32 50 | 40 50 | 40 50 | 40 50 | 40 65

    HST | m all < 25 | 25 < 30 | 30 < 45 | 45 < 25 | 25 < 35 | 35 < 48 | 48 < 65 | 65 all

    * 2 expansion pipes DNe or Transero TV, TPV due to degassing; 1 expansion pipe DNe or Transero T, TP

    Table 5: DNe standard values or expansion pipes with Transero TI

    TI ..0.2 TI ..1.2 TI ..2.2 TI ..3.2

    Length up to approx. 10 m Dn 50 65 80 100

    Length up to approx. 30 m Dn 65 80 100 125

    PSVP0

    HST/1

    0+pD

    pa pe

    0,

    3bar

    0,3bar

    opt

    imumpressurerange

    0,5b

    ar

    online calculating and planning with StP!

  • 7/29/2019 Planning IMI international pressurization systems

    6/20

    6

    PNEUMATEX PlAnning AnD cAlculATion

    Stat

    Selection

    Heating systems TAZ 110 C, without addition o antireeze

    Qk st PSV 2,5 bar PSV 3,0 bar PSV 3,0 bar

    TAZ 100 C P0 1,0 bar P0 1,0 bar P0 1,5 bar

    HST 7 m HST 7 m HST 12 m

    Radiators Flat radiators Radiators Flat radiators Radiators Flat radiators

    90|70 90|70 70|50 90|70 90|70 70|50 90|70 90|70 70|50

    Q|kW nma vm Vn| litre nma vm Vn| litre nma vm Vn| litre

    10 25 18 12 18 12 12 25 18 18

    15 35 18 18 25 18 18 35 25 25

    20 35 25 25 35 18 18 50 35 25

    25 50 35 35 35 25 25 50 35 35

    30 80 35 35 50 35 25 80 50 5040 80 50 50 80 35 35 80 80 50

    50 120 80 50 80 50 50 120 80 80

    60 120 80 80 80 80 50 120 80 80

    70 120 80 80 120 80 80 140 120 80

    80 140 120 80 120 80 80 180 120 120

    90 180 120 120 120 80 80 180 120 120

    100 180 120 120 140 120 80 200 140 120

    130 300 140 140 180 120 120 300 180 180

    150 300 180 180 200 140 120 300 200 180

    200 400 300 200 300 180 180 400 300 300

    250 500 300 300 400 300 200 500 400 300

    300 500 400 300 400 300 300 600 400 400400 800 500 400 600 400 300 800 500 500

    500 1000 600 500 800 500 400 1000 800 600

    600 1000 800 600 800 500 500 1500 800 800

    700 1500 800 800 1000 600 600 1500 1000 800

    800 1500 1000 800 1500 800 600 2000 1000 1000

    900 1500 1000 1000 1500 800 800 2000 1500 1000

    1000 2000 1500 1000 1500 1000 800 2000 1500 1500

    1500 3000 2000 1500 2000 1500 1500 3000 2000 2000

    Stat SD

    a hat systm

    p t appx. 100 kW

    P Pwater make-up as pressure

    maintenance monitoring device

    according to EN 1282

    Zpa ZuVlor the central

    separation o micro bubbles

    Zpa ZuMor the central

    separation o sludge,

    with magnetic action

    Zpa ZuTor automatic venting

    during illing and during draining

    Fth asss, pdt ad

    st dtas: Datasheet Pleno

    : Datasheet Zeparo ZU

    : Datasheet Accessories

    examp

    Q = 200 kW

    PSV = 3 bar

    HST = 7 m

    Radiators 90|70 C

    Selected:

    Statico SU 300.3

    P0 = 1 bar

    Reduce the actory-set pre set

    pressure rom 1,5 bar to 1 bar!

    Technical data:

    : Datasheet Statico

    System example may require changes to meet local legislation

    HB

    tmax

    tRDNe

    HST

    DSV...H

    ZUVL

    PSV

    Q

    p

    Statico SD

    DLV

    DH

    ZUT

    ZUM

    Pleno PI

    Water make-upconnection

    pNS

    H | TH

  • 7/29/2019 Planning IMI international pressurization systems

    7/20

    7

    PNEUMATEX PlAnning AnD cAlculATion

    Above 100 C the static height HST decreases in the quick selection table.

    TAZ = 105 C: HST 2 m

    TAZ = 110 C: HST 4 m

    P0 = (HST/10 + pD) + 0,3 bar pD: table 1, page 4

    Recommended: P0 1 bar

    pa P0 + 0,3 with cold, but vented system

    eqpmt

    Secured shut-o with draining or expansion vessels according to EN 12828,

    DLV 20 up to VN 800 litres, DN 40 or VN 1000 5000 litres by customer.

    According to table 3 on page 5.

    Water make-up as pressure maintenance monitoring device according to EN 12828.

    Conditions:

    PlenoPIwithoutpump:requiredfreshwaterpressure:pNS P0 + 1,5 | pNS 10 bar,

    Pleno PI 6 | PI 9 with pump: pa Statico (: page 4) within the working pressure range DPP o the Pleno.

    Degassing and central venting.

    Conditions:

    pe, pa Statico (: page 4) within the working pressure range DPP o the Vento,

    VA Vento VA water capacity o the system.

    Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining

    process. Separator or sludge and magnetite in each system in the main return to the heat generator. For

    micro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central

    degassing (e.g. Vento, Transero) is installed. The static height HB according to the table above the micro

    bubble separator must not be exceeded.

    tmax | C 90 80 70 60 50 40 30 20 10

    HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7

    nt f TAZ abv 100 c

    P st pss stt P0

    F pss, ita pss

    lk shd vav DlV

    : Datasheet Accessories

    expas pp

    P

    : Datasheet Pleno

    Vt

    : Datasheet Vento

    Zpa

    : Datasheet Zeparo ZU | ZI, ZE

    Stat Su

    a hat systm

    p t appx. 700 kW

    Vt VP...e or the central venting

    and degassing, with water make-up

    as pressure maintenance monitoring

    device according to EN 12828

    Zpa Zio...S optional or micro

    bubbles or sludge particles, in this

    case conigured as sludge separator

    Zpa ZuT or automatic venting

    during illing and during draining

    Fth asss, pdt ad

    st dtas

    : Datasheet Vento

    : Datasheet Zeparo ZU | ZI, ZE: Datasheet Accessories

    System example may require changes to meet local legislation

    tmax

    tR

    HSTDSV...DGH

    ET

    PSV

    Q

    p

    DH

    ZUT

    ZIO...S

    Vento VP...E

    Water make-up connection

    Statico SU

    DLVH | TH

    online calculating and planning with StP!

  • 7/29/2019 Planning IMI international pressurization systems

    8/20

    8

    PNEUMATEX PlAnning AnD cAlculATion

    cmpss

    Selection

    Heating systems TAZ 110 C, without addition o antireeze

    Qk st TBx Pmay vss

    TAZ 100 C 1 compressor 2 compressors * Radiators Flat radiators

    C 10.1 F CPV 10.1 C 20.1 C 10.2 C 20.2 90|70 70|50 90|70 70|50

    C 10.1

    Q | kW Stat hht HST | m ** nma vm Vn | litre

    300 46,1 33,6 81,4 46,1 81,4 200 200 200 200

    400 46,1 33,6 81,4 46,1 81,4 300 300 200 200

    500 46,1 33,6 81,4 46,1 81,4 300 300 200 200

    600 46,1 33,6 81,4 46,1 81,4 400 400 300 300

    700 46,1 33,6 81,4 46,1 81,4 500 500 300 300

    800 42,7 33,6 81,4 46,1 81,4 500 500 400 300900 37,7 33,6 81,4 46,1 81,4 600 600 400 400

    1000 33,6 33,6 81,4 46,1 81,4 600 600 400 400

    1100 30,2 30,2 81,4 46,1 81,4 800 800 500 400

    1200 27,4 27,4 79,2 46,1 81,4 800 800 500 500

    1300 24,9 24,9 73,2 46,1 81,4 800 800 500 500

    1400 22,7 22,7 67,9 46,1 81,4 1000 1000 600 500

    1500 20,8 20,8 63,3 46,1 81,4 1000 1000 600 600

    2000 13,8 13,8 46,7 34,0 81,4 1500 1500 800 800

    2500 9,1 9,1 36,2 26,4 73,9 1500 1500 1000 1000

    3000 5,4 28,7 21,0 61,4 2000 2000 1500 1500

    3500 23,1 17,1 52,1 3000 3000 1500 1500

    4000 18,6 14,0 45,0 3000 3000 2000 15004500 14,8 11,4 39,3 3000 3000 2000 2000

    5000 11,6 9,2 34,7 3000 3000 2000 2000

    5500 8,8 7,3 30,7 4000 4000 3000 2000

    6000 6,2 5,6 27,3 4000 4000 3000 3000

    6500 3,9 4,0 24,4 4000 4000 3000 3000

    7000 21,8 5000 5000 3000 3000

    8000 17,3 5000 5000 4000 3000

    9000 13,7 4000 4000

    10000 10,5 4000 4000

    cmpss c 10.1 F

    TBx wth 1 mpss th pmay vss, ps

    pss mata 0,1 ba

    wth P P wat mak-p

    or heating systems

    up to approx. 3 000 kW

    itmdat vss Du or return

    temperatures above 70 C

    Zpa Zio...S conigured as micro

    bubble separator in the low,

    as sludge separator in the return

    Zpa ZuT or automatic venting

    during illing and during draining

    Fth asss, pdt adst dtas

    : Datasheet Pleno

    : Datasheet Zeparo ZU | ZI, ZE

    : Datasheet Accessories

    * 50 % output per compressor,

    ull redundancy in the ramed

    area

    ** The value decreases with

    TAZ = 105 C by 2 m

    TAZ = 110 C by 4 m

    examp

    Q = 900 kW

    Radiators 90 | 70 C

    TAZ = 100 C

    HST = 35 m

    PSV = 5 bar

    Selected:

    TecBox C 10.1-6 F

    Primary vessel CU 600.6

    Setting o BrainCube:

    HST = 35 m

    TAZ = 100 C

    Check PSV: (: page 9)

    or TAZ = 100 CPSV: 35 / 10 + 1,3 = 4,8 < 5 o.k.

    Technical data:

    : Datasheet Compresso

    HB

    tmax

    tRDNe

    HSTDSV...DGH

    ZIO...S

    ET

    PSV

    Q

    pZUT

    Intermediatevessel DU

    DLV

    DLVDLV

    CompressoPrimary vessel CU

    CompressoTecBox C 10.1 F

    ZUT

    ZIO...S

    Pleno P

    Water make-up connection

    pNS

    min P0 + 1,7 bar,max. 10 bar

    System example may require changes to meet local legislation

  • 7/29/2019 Planning IMI international pressurization systems

    9/20

    9

    PNEUMATEX PlAnning AnD cAlculATion

    = TecBox + Primary vessel + Secondary vessel (optional)

    The nominal volume can be allocated to multiple vessels o the same size.

    C CPV

    Precision pressure maintenance 0,1 bar

    + illsae water make-up

    + vacusplit degassing

    or TAZ, HST and PSV in the Parameter menu o the BrainCube

    TAZ = 100 C TAZ = 105 C TAZ = 110 C

    PSV 0,1 HST + 1,3 PSV 0,1 HST + 1,5 PSV 0,1 HST + 1,7

    PSV (0,1 HST + 0,8) 1,11 PSV (0,1 HST + 1,0) 1,11 PSV (0,1 HST + 1,2) 1,11

    The BrainCube determines the switching points and the minimum pressure P0.

    eqpmt

    According to table 3 on page 5. With multiple vessels with prorata output per vessel.

    Included in the scope o delivery.

    Water make-up as pressure maintenance monitoring device according to EN 12828.

    Conditions:

    PlenoPwithoutpump,withoutcontrol(controlthroughBrainCubeCompresso):

    required resh water pressure: pNS P0 (BrainCube) + 1,9 bar | pNS 10 bar,

    PlenoPI6|PI9withpump,withcontrol:pa, pe Compresso (: page 4) within the working pressure

    range DPP o the Pleno.

    Degassing and central venting.

    Conditions:

    pe, pa Compresso (: page 4) within the working pressure range DPP o the Vento | CPV,

    VA Vento VA water capacity o the system.

    Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining

    process. Separator or sludge and magnetite in each system in the main return to the heat generator. For

    micro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central

    degassing (e.g. Vento, Compresso CPV) is installed. The static height HB according to the table above the

    micro bubble separator must not be exceeded.

    tmax | C 90 80 70 60 50 40 30 20 10

    HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7

    cmpss

    Sday vsss

    TBx qpmt

    Stt vas

    Check PSV: or PSV 5 bar

    or PSV > 5 bar

    expas pps

    lk shd vav DlV

    P

    integrated into the CPV

    : Datasheet Pleno

    Vt

    integrated into the CPV

    : Datasheet Vento

    Zpa

    : Datasheet Zeparo ZU | ZI, ZE

    cmpss c 10.2

    TBx wth 2 mpsss ft f xt t th pmay

    vss, ps pss

    mata 0,1 ba

    wth Vt VP...e dass

    ad wat mak-p

    or heating systems

    up to approx. 6 500 kW

    Zpa Zio...F or the central

    separation o sludge

    Zpa ZuT or automatic venting

    during illing and during draining

    Fth asss, pdt ad

    st dtas

    : Datasheet Vento

    : Datasheet Zeparo ZU | ZI, ZE

    : Datasheet Accessories

    C 10.1 F:

    on the primary vessel up to 800 litres

    C 10 | C 20 | CPV 10:

    foor standing

    System example may require changes to meet local legislation

    tmax

    tRDNe

    HSTDSV...DGH

    ET

    PSV

    Q

    p

    CompressoTecBox C 10.2

    DLV

    ZUT

    ZIO...F

    Vento VP...E

    Water make-up connection

    CompressoPrimary vessel CG

    CompressoSecondary vessel CG...E

    DLV

    online calculating and planning with StP!

  • 7/29/2019 Planning IMI international pressurization systems

    10/20

    10

    PNEUMATEX PlAnning AnD cAlculATion

    Tasf

    Selection

    Heating systems TAZ 110 C, without addition o antireeze

    Qk st TBx Pmay vss

    TAZ 100 C 1 pump 2 pumps * Radiators Flat radiators

    T_ T_ T_ T_ T_ T_ T_ T_ TPV 90|70 70|50 90|70 70|504.1 6.1 8.1 10.1 4.2 6.2 8.2 10.2 19.2 P

    Q | kW Stat hht HST | m ** nma vm Vn | litre

    300 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 200 200 200 200

    400 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 300 300 200 200

    500 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 300 300 200 200

    600 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 400 400 300 300

    700 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 500 500 300 300

    800 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 500 500 400 300900 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 600 600 400 400

    1000 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 600 600 400 400

    1100 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 400

    1200 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 500

    1300 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 500

    1400 28,4 38,2 55,9 74,7 28,4 38,2 55,9 75,5 134,1 1000 1000 600 500

    1500 28,4 38,2 55,7 73,8 28,4 38,2 55,9 75,5 134,1 1000 1000 600 600

    2000 28,4 38,2 51,2 68,6 28,4 38,2 55,9 75,5 134,1 1500 1500 800 600

    2500 24,9 35,9 46,0 62,5 28,4 38,2 55,9 75,5 134,1 1500 1500 1000 1000

    3000 20,6 31,4 40,0 55,6 28,4 38,2 55,6 73,6 134,1 2000 2000 1500 1500

    3500 15,7 26,2 33,3 47,8 28,4 38,2 53,5 71,2 134,1 3000 3000 1500 1500

    4000 10,2 20,2 25,8 39,1 28,4 38,2 51,2 68,5 134,1 3000 3000 2000 1500

    4500 13,6 17,6 29,5 26,8 37,9 48,6 65,6 134,1 3000 3000 2000 2000

    5000 19,0 24,9 35,9 45,9 62,5 134,1 3000 3000 2000 2000

    5500 22,9 33,8 43,0 59,2 133,5 4000 4000 3000 2000

    6000 20,6 31,4 39,9 55,8 124,4 4000 4000 3000 3000

    6500 18,3 28,9 36,6 52,1 114,6 4000 4000 3000 3000

    7000 15,7 26,2 33,1 48,2 104,1 5000 5000 3000 3000

    8000 10,2 20,2 25,6 39,8 80,8 5000 5000 4000 3000

    9000 13,6 17,3 30,7 4000 4000

    10000 20,7 4000 4000

    Tasf TPV .1

    TBx wth 1 pmp, ps

    pss mata 0,2 bawth dass ad wat mak-p

    or heating systems

    up to approx. 5 000 kW

    Zpa Zio...F or the central

    separation o sludge

    Zpa ZuT or automatic venting

    during illing and during draining

    Fth asss, pdt ad

    st dtas

    : Datasheet Zeparo ZU | ZI, ZE

    : Datasheet Accessories

    * 50% output per pump,

    ull redundancy in the

    ramed area

    ** The value decreases with

    TAZ = 105 C by 2 m

    TAZ = 110 C by 4 m

    examp

    Q = 1300 kW

    Flat radiators 90 | 70 C

    TAZ = 105 C

    HST = 30 m

    PSV = 5 bar

    Selected:

    TecBox TPV 6.1

    Primary vessel TU 500

    Setting o BrainCube:

    HST = 30 m

    TAZ = 105 C

    Check PSV: (: page 11)

    or TAZ = 105 C

    PSV: 30 / 10 + 1,7 = 4,7 < 5 o.k.

    Check HST:

    or TAZ = 105 C

    HST: 38,2 2 = 36,2 > 30

    Technical data:

    : Datasheet Transero

    System example may require changes to meet local legislation

    tmax

    tRDNe

    HSTDSV...DGH

    ET

    PSV

    Q

    TranseroTecBox TPV .1

    TranseroPrimary vessel TU

    ZUT

    ZIO...FWater make-up connectionDPNS min 2 bar, max. 10 bar

    500 mm

    Statico SD

    DLV

  • 7/29/2019 Planning IMI international pressurization systems

    11/20

    11

    PNEUMATEX PlAnning AnD cAlculATion

    Tasf TV .2

    TBx wth 2 pmps, ps

    pss mata 0,2 bawth dass ad

    P P f th wat mak-p

    or heating systems

    up to approx. 10 000 kW

    Zpa Zio...S or the central

    separation o sludge

    Zpa ZuT or automatic venting

    during illing and during draining

    Fth asss, pdt ad

    st dtas

    : Datasheet Pleno

    : Datasheet Zeparo ZU | ZI, ZE

    : Datasheet Accessories

    = TecBox + Primary vessel + Secondary vessel (optional)

    The nominal volume can be allocated to multiple vessels o the same size.

    T TP TV TPV TPV...P TI

    Precision pressure maintenance 0,2 bar *

    + illsae water make-up

    + oxystop degassing

    * 2 buer vessels or optimal pressure maintenance

    or TAZ, HST and PSV in the Parameter main menu o the BrainCube

    TAZ = 100 C TAZ = 105 C TAZ = 110 C

    PSV 0,1 HST + 1,5 PSV 0,1 HST + 1,7 PSV 0,1 HST + 1,9

    PSV (0,1 HST + 1,0) 1,11 PSV (0,1 HST + 1,2) 1,11 PSV (0,1 HST + 1,4) 1,11

    The BrainCube determines the switching points and the minimum pressure P0.

    eqpmt

    At least one Statico SD 35, requirement or TI selection. Setting on P0 o the BrainCube.

    Transero T_: table 4 | Transero TI: table 5 : page 5

    Included in the scope o delivery.

    Water make-up as pressure maintenance monitoring device according to EN 12828 in combination with

    Transero T or TV. The control is made through the BrainCube o the Transero TecBox.

    Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining

    process. Separator or sludge and magnetite in each system in the main return to the heat generator. Formicro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central

    degassing (e.g. Vento, Transero) is installed. The static height HB according to the table above the micro

    bubble separator must not be exceeded.

    tmax | C 90 80 70 60 50 40 30 20 10

    HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7

    Tasf

    Sday vsss

    TBx qpmt

    Stt vas

    Check PSV: or PSV 5 bar

    or PSV > 5 bar

    Bff vsss

    expas pps

    lk shd vav DlV

    P

    : Datasheet Pleno

    Zpa

    : Datasheet Zeparo ZU | ZI, ZE

    System example may require changes to meet local legislation

    tmax

    tR DNe

    HST

    DSV...DGH

    ET

    PSV

    Q

    TranseroTecBox TV .2

    ZUT

    ZIO...S

    Pleno P

    Water make-up connection

    TranseroPrimary vessel TG

    TranseroSecondary

    vessel TG...E

    DLV

    Statico SD

    500 mm

    online calculating and planning with StP!

  • 7/29/2019 Planning IMI international pressurization systems

    12/20

    12

    PNEUMATEX PlAnning AnD cAlculATion

    Aqapss

    Calculation, Selection

    Aqapss ptab ht wat systms

    Aquapresso save valuable drinking water in potable hot water systems. The expansion water is not lost anymore through the

    saety valve but is absorbed by the Aquapresso. The correct setting o the pre set pressure is o importance or a aultless and

    reliable operation.

    Qk st P0 4,0 bar | pa 4,3 bar P0 3,0 bar | pa 3,3 bar

    Heating-up ro m 10 C to 60 C PSV | bar 6 7 8 10 6 7 8 10

    VSP | litre nma vm Vn | litre nma vm Vn | litre

    50 8 8 8 8 8 8 8 8

    80 8 8 8 8 8 8 8 8

    100 12 8 8 8 8 8 8 8

    150 18 12 8 8 8 8 8 8

    180 18 12 12 8 8 8 8 8

    200 25 12 12 8 12 8 8 8

    250 25 18 12 12 12 12 8 8

    300 35 18 18 12 18 12 12 12

    400 50 25 25 18 18 18 12 18

    500 50 35 25 25 25 18 18 25

    600 80 50 35 25 35 25 18 25

    700 80 50 35 35 35 25 25 25

    800 80 50 50 35 35 35 25 25

    900 140 80 50 35 50 35 35 35

    1000 140 80 50 50 50 35 35 35

    Aqapss ADF

    wth fwfsh f fw-thh a dk wat hat systm

    Aqapss ADF

    can be low through rom

    the top or rom the bottom,

    with hydrowatch installation

    always rom the bottom

    (PSV + 0,5) (P0 + 1,3)

    (P0 + 1) (PSV P0 0,8)

    pR0,8

    Pre set pressure P0 = pa 0,3 bar

    Saety valve PSV =

    Initial pressure pa = pFL

    Nominal volume VN = VSp e

    The pre set pressure o the Aquapresso is set at least 0,3 bar below the initial

    pressure pa.

    The initial pressure corresponds to the fow pressure pFl. It should be kept at a con-

    stant level by means o the installation o a pressure reducer in the cold water line.

    The non-operative pressure pR in the drinking water network must not exceed 80 %

    o the response pressure saety valve.

    VSp is the nominal volume o the drinking water heater.

    e (60 C, : table 1, page 4)

    examp

    VSp = 200 litre

    pa = 3,3 barPSV = 10 bar

    Selected:

    Aquapresso ADF 8.10

    with ull low-through

    P0 = 3 bar

    Reduce the actory-set pre set

    pressure rom 4 bar to 3 bar!

    Technical data:

    : Datasheet Aquapresso

    V = Vmax VD

    V = Vmax> VD

    Aquapresso ADF

    Bypass open,remove handwheel

    System example may require changes to meet local legislation

    pR

    pR

    pa

    pa

    PSV

    PSV

    hydrowatch

    Aquapresso ADF

    hydrowatch

    VSp

    VSp

  • 7/29/2019 Planning IMI international pressurization systems

    13/20

    13

    PNEUMATEX PlAnning AnD cAlculATion

    Aqapss pss-bst systms

    Aquapresso in pressure-boosting systems stabilize the drinking water network and reduce the switching requency. They can

    be installed at the low pressure and high pressure sides o a pressureboosting system. The mains pressure side ist always to be

    coordinated with the water supply company.

    Aqapss pss sss

    Aqapss

    a pss-bst systm

    Aqapss AuF

    at the low side;

    low-through rom the

    top to the bottom

    Aqapss Au

    at the high pressure side;

    no low-through

    Aquapresso on the low side

    Calculation according to 1988 T5

    Vmax| m/h VN | litre VD Nominal fow

    7 300according to

    < 7 15 500Datasheet

    > 15 800

    Aquapresso or shock absorption

    This topic is very complex and complicated.

    We recommend to have the calculation done

    by a specialized engineering oce.

    AppvasAquapresso are designed or drink-ing water systems. As there are no

    uniorm European standards, pleaseobserve the drinking water approv-als or the individual countries withrespect to the selection. These aredecisive or the deployment o low-

    resh ully low-through or no low-

    through Aquapresso.

    Aqapss A...F wth bypassI the max. volumelow Vmax is larger

    than the nominal low VD or low-through Aquapresso A...F, then theAquapresso is to be installed with abypass. The bypass is to be dimen-sioned or the dierence water quan-

    tity with a lowspeed o 2 m/s.: System examples: Installation | Operation

    Aquapresso on the high pressure side

    VN calculation according to DIN 1988 T5

    or the restriction o the switching requency

    VN = 0,33 Vmax

    s Switching requency | 1/h Pump capacity | kW

    20 4,015 7,5

    10 > 7,5

    VN calculation by storage volume V between

    working pressure and turn-o pressure

    VN = V

    n Number o pumps | pE Working pressure |

    pA Turn-o pressure | Vmax Max. volumefow pump

    pA + 1(pA pE) s n

    (pE + 1) (pA + 1)(P0 + 1) (pA pE)

    System example may require changes to meet local legislation

    V = Vmax> VD

    Aquapresso AUF

    Bypass open,removehandwheel

    V = Vmax VD

    Vmax

    Aquapresso AUF

    VmaxVDP0 at least 0,5 bar below theminimum supply pressure

    V=VD

    pE | pApE | pA

    Aquapresso AU

    P0 = 0,9 working pressureof the peak load pump,

    at least 0,5 bar belowthe working pressure

    Vmax

    pE | pA

    0,00

    0,05

    0,10

    0,15

    0,20

    0,25

    0,30

    0,00 0,50 1,00 1,50 2,00

    V | m/h

    DP

    |bar

    0,00

    0,05

    0,10

    0,15

    0,20

    0,25

    0 5 10 15 20 25 30 35

    V | m/h

    DP

    |bar

    ADF 8 12 litre

    ADF 18 35 litre

    ADF 50 80 litre

    AUF 140 600 litre

    AGF 300 700 litre

    AGF 1000 1500 litre

    AGF 2000 5000 litre

    Aquapresso ADF Aquapresso AUF | AGF

    |

    |

    |

    |

    online calculating and planning with StP!

  • 7/29/2019 Planning IMI international pressurization systems

    14/20

    14

    PNEUMATEX PlAnning AnD cAlculATion

    Safty thy

    Devices or sealed heating systems

    according to EN 12828 with TAZ 110 C

    ga qmts

    Ti Thmmt, display range 20 % above TAZ

    TAZ Tmpat mt according to EN 60730-2-9

    Tc Tmpat t

    lAZ lw-wat ptt2) or roo top installations

    Pi Mamt, display range 50 % above PSV

    SV Safty vav, EN 4126 or vapour emissionPss mata, e.g. Statico, Compresso, Transero

    Pss mata mt dv4), e.g. Pleno

    Addta qmts f Q > 300 kW/hat at

    lAZ lw-wat ptt2)

    eT Bw tak5)

    PAZ Pss mt

    Addta qmts wth sw-at hat

    emy through thermal discharge protection

    or saety heat consumer, e.g. with solid uel boilers

    examp:

    Safty qpmt

    ad t en 12828

    directly heated system

    Q > 300 kW

    : Datasht

    Accessories

    Accessories

    Accessories

    Accessories

    AccessoriesStatico | Compresso | Transero

    Pleno

    Accessories

    Accessories

    hatddtywith oil, gas,electricity,solid uels

    hatddtyheat exchangerwith vapour orliquids

    1)

    3)

    6)

    1) Temperature controller sucient according to standard, but not recommended.2) Minimum pressure or fow limiters can be used as an alternative. For central roo units above 300 kW not

    additionally, 1 low-water protection is sucient.3) Dimensioning or water discharge with 1 litre/kWh possible i the primary temperature does not exceed the

    evaporation temperature with the saety valve opening pressure PSV.4) Automatic water make-up device (e.g. Pleno) or minimum pressure limiter.5) Substitution with additional TAZ and PAZ possible. EN 12828 does not contain constructive specications.

    We recommend to proceed according to the known state o the art o the countries, e.g. SWKI 93-1 inSwitzerland or DIN 4751-2 in Germany.

    6) Only i the vapour pressure pD at fow temperature tpr is bigger than saety valve opening pressure PSV.

    System example may require changes to meet local legislation

    SV

    Q

    Pss matae.g. Statico SU

    Water make-upconnection

    Pss matamt dv

    Degassing with built-in watermake-up, e.g. Vento VP...E

    eT

    pD (tpr)> PSV

  • 7/29/2019 Planning IMI international pressurization systems

    15/20

    15

    PNEUMATEX PlAnning AnD cAlculATion

    Name o the new Pneumatex controls in Compresso, Transero, Pleno and Vento.

    Name or Pneumatex compact control units consisting o hydraulic part and BrainCube control.

    airproo | silentrun | dynalex | oxystop | vacusplit | helistill | leakree | illsae | secuguard |

    lowresh

    Damt

    Characteristic diameter o the device.

    Hht (H, H1, H2, )

    Characteristic overall height o the device.

    istaat dmss (h, h1, h2, )Wdth

    Characteristic overall width o the device.

    Dpth

    Characteristic overall depth o the device.

    lth

    Characteristic overall length o the device or the ixture.

    isat thkss

    empty wht

    o the device at the time o delivery without the packaging.

    ct

    Characteristic dimension or the device connection.ct

    Characteristic dimension or the device connection or streaming in media.

    ct t

    Characteristic dimension or the device connection or streaming o media.

    ct vss

    Characteristic dimension or the device connection to the vessel.

    ct wat mak-p

    Characteristic dimension or the water make-up connection.

    ct dwat

    Characteristic dimension or evacuation, dewatering operations.

    Ma thad, a, ISO 7-1Fma thad, yda, ISO 7-1

    Fma tad, ma thad, yda, ISO 228

    nma damt

    Numeric size speciications or tube dimensions according to the pressure device directive.

    Paka t

    Standard packaging quantity in a box or pallet. For articles with the speciications o the VPE please

    coordinate order quantities smaller than the VPE with the sales oice. Items within a VPE always

    provide o a unctional separate packaging.

    Bacb

    TBx

    Qaty fats

    D

    H

    hB

    T

    l

    SD

    g

    S

    Se

    SA

    Sg

    SnS

    SW

    rrp

    g

    Dn

    VPe

    gssay

    Geometrie

    General terms

  • 7/29/2019 Planning IMI international pressurization systems

    16/20

    16

    PNEUMATEX PlAnning AnD cAlculATion

    Stat hht

    Water column between the highest point o the system and the connecting branch o the expan-

    sion vessel, or water-controlled pressure-maintaining systems with pump (Transero) reerred to

    the suction joint o the pump.

    Maxmm stat hht f th dpymt f bbb spaats

    It depends on the temperature conditions at the place o installation o the separator.

    Mmm pss

    Lower limit value or the pressure maintenance. It is mainly deined by the static height HST and the

    vapour pressure pD. I the value is allen short o the unction o the pressure maintenance cannot

    be ensured. For large systems and temperature limits above 100 C the pressure limiting devices

    are triggered.Statico, Aquapresso: Pre set pressure to be set at the gas side.

    Be careul with respect to Aquapresso in drinking water systems! I the drinking water pressure

    alls short o the pre set pressure this may lead to pressure blows and to an increased bubble wear

    (: Initial pressure pa).

    Transero, Compresso, Vento, Pleno: The minimum pressure P0 is calculated by the BrainCube

    control rom the static height HST and the vapour pressure pD (TAZ).

    Mmm qd qpmt pss

    e.g. NPSH requirement or pumps or boilers

    Vap pss

    According to EN 12828 the excess pressure towards the atmosphere to prevent evaporation.

    ita pssLower threshold or an optimum pressure maintenance. During the operation it must always be

    above the minimum pressure. We recommend at least 0,3 bar. For systems with minimum pres-

    sure limiters this value must be selected such that the triggering o the limiters is prevented in all

    operating modes. With respect to Pneumatex devices with BrainCube control the initial pressure is

    calculated internally by the control.

    Statico: Pressure with minimum system temperature ater eeding the water reserve. Water make-

    up devices in the sense o a pressure maintenance monitoring device according to EN 12828

    must be triggered i the value is allen short o. I the illing temperature is equal to the lowest

    system temperature the initial pressure corresponds to the illing pressure. e.g. heating systems:

    lowest system temperature ~ illing temperature ~ 10 C.

    Compresso, Transero: Pressure at which the pump or the compressor must be triggered.

    Aquapresso: Pressure o the drinking water network beore the Aquapresso. It must also always begreater than the pre set pressure at low conditions.

    Fa pss

    Upper threshold or an optimum pressure maintenance. It must be at least 0,5 bar below the saety

    valve response pressure. For systems with maximum pressure limiters it must be selected such that

    the triggering o the limiters is prevented in all operating modes.

    Statico: The highest pressure to be assumed ater the max. system temperature has been achieved.

    Compresso, Transero: The pressure at which the spill device must open at the latest.

    Aquapresso: The highest pressure to be assumed ater the absorption o the drinking water to be

    stored.

    rsps pss safty vav

    According to EN ISO 4126-0 the pressure at which the saety valve at the heat generator begins

    to open.

    HST

    HB

    P0

    pZ

    pD

    pa

    p

    PSV

    gssay

    Pressures

  • 7/29/2019 Planning IMI international pressurization systems

    17/20

    17

    PNEUMATEX PlAnning AnD cAlculATion

    cs pss ta

    Dierence between response pressure and closing pressure or saety valves | EN ISO 4126-1.

    op pss ta

    Dierence between response pressure and opening pressure or saety valves | EN ISO 4126-1.

    Maxmm admssb pss

    According to the pressure device directive the maximum pressure or which the pressure device

    has been dimensioned according to the manuacturers speciication.

    Maxmm admssb pss Swtzad

    Pressure up to which the expansion vessel does not require an approval according to the Swiss

    directive SWKI 93-1 (PS VN 3000 bar litre).

    Pss fat

    Ratio between the required nominal volume VN and the water absorption volume Ve + VV or ex-

    pansion vessels.

    Fsh wat pss

    Flow pressure o the resh water network, e.g. drinking water network, that is available beore the

    water make-up device.

    Wk pss a

    Pressure range or which a water make-up or degassing device has been designed. It must be ad-

    justed to the working pressure o the system.

    Pss ss wth ma fw

    Pressure loss reerred to the nominal low capacity o a device, e.g. Aquapresso or Zeparo.

    expas fft

    According to EN 12828 the actor or the calculation o the expansion volume rom the water

    capacity. In this case, reerred to the solidiication point.

    ova systm wat apaty

    According to EN 12828 the overall water capacity o the heating system that is involved in the

    volume expansion.

    Spf va systm wat apaty

    Overall water capacity o the heating system that is involved in the volume expansion, reerred to

    the installed heating surace output.

    nma vm

    According to the pressure device directive the entire internal volume o the pressure compartment

    o the expansion vessel.

    Wat apaty f whh a dv s atd

    Characteristic perormance parameter that describes up to which water capacity the device, e.g.

    Vento, can be used.

    Wat tt t pas

    For solar systems to ENV 12977-1 the collector volume which can phase change to steam has to

    be added to the connecting pipes volume.

    expas vm

    According to EN 12828 the volume expansion o the water capacity o the heating system be-

    tween the min. and max. system temperature.

    Wat sv

    According to EN 12828 the water quantity in the expansion vessel or the compensation o waterlosses caused by the system.

    ASV

    oSV

    PS

    PScH

    Df

    pnS

    DPP

    DPVD

    VA

    vA

    Vn

    VA

    VK

    V

    VV

    Volumes

    Pressures

    gssay

  • 7/29/2019 Planning IMI international pressurization systems

    18/20

    18

    PNEUMATEX PlAnning AnD cAlculATion

    Maxmm systm tmpat

    Maximum temperature or the calculation o the volume expansion. For heating systems the di-

    mensioned low temperature at which a heating system is to be operated with the lowest outside

    temperature to be assumed (standard outside temperature according to EN 12828). For cooling

    systems the max. temperature that is achieved due to the operation mode or standstill, or solar

    systems the temperature up to which an evaporation is to be avoided.

    lwst systm tmpat

    Lowest temperature or calculating expansion volumes. The lowest system temperature is equal

    to the reezing point. It is dependant on the percentage o antireeze additives. For water without

    additives tmin = 0.

    Pmay fw tmpatMaximum low temperature in primary circuit o heat exchangers (indirect ired).

    rt tmpat

    Return temperature o the heating system with the lowest outside temperature to be assumed

    (standard outside temperature according to EN 12828).

    Maxmm fw tmpat

    Maximum low temperature or which a device is equipped according to the normative and saety-

    related requirements. TV may be greater than TS i the device is installed at a place with t TS,

    e.g. in the system return.

    Safty tmpat mt | Safty tmpat t | Tmpat mt

    Saety device according to EN 12828 or the temperature protection o heat generators. I the

    set temperature limit is exceeded the heating is turned o. Limiters are locked, controllers auto-

    matically release the heat supply i the set temperature is allen short o. Setting value or systems

    according to EN 12828 110 C.

    Maxmm admssb tmpat

    According to the pressure device directive the maximum temperature or which the pressure de-

    vice or the ixture has been dimensioned according to the manuacturers speciication.

    Mmm admssb tmpat

    According to the pressure device directive the minimum temperature or which the pressure de-

    vice or the ixture has been dimensioned according to the manuacturers speciication.

    Maxmm admssb tmpat f wat mak p

    The highest admissible temperature or make up units as part o a pressurisation or degassing sys-

    tem. This only applies i TW < TS.

    Maxmm admssb ba tmpatMaximum admissible permanent temperature or the butyl bag.

    Mmm admssb ba tmpat

    Minimum admissible permanent temperature or the butyl bag.

    Maxmm admssb ambt tmpat

    Maximum ambient temperature or the installation o a device.

    tmax

    tm

    tp

    tr

    TV

    TAZ

    TS

    TSm

    TW

    TB

    TBm

    Tu

    gssay

    Temperatures

  • 7/29/2019 Planning IMI international pressurization systems

    19/20

    19

    PNEUMATEX PlAnning AnD cAlculATion

    gssay

    Hat apaty

    Blowing-o capacity o a saety valve reerred to the vapour emission according to the component

    inspection.

    Hat apaty

    Blow o capacity o a saety valve reerred to the vapour emission according to the component

    inspection.

    Hat apaty

    Blow o capacity o a saety valve or water low according to speciication, related the to heat

    output o the heat generator, 1 kW = 1 l/h.

    Fw at | nma fw

    Nominal throughput o a device, e.g. Aquapresso, Zeparo or nominal low rate o a compressor or

    pump.

    Maxmm fw

    Maximum throughput o a device, e.g. Zeparo.

    Fw paamt

    Throughput o a device with a dierential pressure o 1 bar.

    Wat mak-p apaty

    Nominal capacity o a water make-up device.

    Vta

    Nominal voltage or an electric device.

    et t

    Admissible current load or a device.

    et ad

    Load or an electric device.

    Sd pss v

    Sound pressure level dB(A) eective perceived.

    cd f ptt aast mst ad physa tat

    according to EN 60529.

    Q

    QPSV

    QPSVW

    VD

    VM

    KVS

    VnS

    u

    i

    PA

    SPl

    iP

    Capacities

  • 7/29/2019 Planning IMI international pressurization systems

    20/20

    DSXINEN021105

    The products, texts, photographs, graphics and diagrams in this brochure may be subject to alteration by TA Hydronics

    without prior notice or reasons being given. For the most up to date inormation about our products and specications,please visit www.tahydronics.com.

    Addta fmat

    Systm ds: :Datasheet Planning and calculation

    :Online calculation sotware SelectP!

    Sht ts | tms: :Datasheet Planning and calculation | Glossary