Upload
jack-bc
View
217
Download
0
Embed Size (px)
Citation preview
7/29/2019 Planning IMI international pressurization systems
1/20
engineering ADVAnTAgePressurisation & Water Quality Balancing & Control Thermostatic Control
Pa ad aat
Selection o the most suitable products orpressure maintenance | degassing | water make-up
Reliable pressurisation is the basic requirement or a gentle and trouble-ree operation o heating,
solar and cooling water systems. Our planning and calculation basics support you in choosing the right
products, their size and perormance.
7/29/2019 Planning IMI international pressurization systems
2/20
2
PNEUMATEX PlAnning AnD cAlculATion
7/29/2019 Planning IMI international pressurization systems
3/20
3
PNEUMATEX PlAnning AnD cAlculATion
Tab f tts
Page
caats
4 5 General equations
Stat st
6 Quick selection
7 Equipment
cmpss st
8 Quick selection
9 Equipment
Tasf st
10 Quick selection
11 Equipment
Aqapss st
12 Aquapresso in potable hot water systems
13 Aquapresso in pressure-boosting systems
13 Aquapresso pressure losses
Safty thy
14 Devices or sealed heating systems
gssay
15 General terms
15 Geometry
16 17 Pressures
17 Volumes
18 Temperatures
19 Capacities
7/29/2019 Planning IMI international pressurization systems
4/20
4
PNEUMATEX PlAnning AnD cAlculATion
caat
Pressure maintenance
Heating systems TAZ 110 C ollowing EN 12828, solar systems ENV 12977-1
ga qats
VA Water capacity o the system VA = VA central heating + VA district heating pipe : System design
VA = vA Q + VA district heating pipe vA Specic water capacity, table 2
Q Installed heat capacity
Ve Expansion volume Ve = e VA e Expansion coecient or tmax, table 1
VV Water reserve VV 0,005 VA 3 litre
P0 Miniumum pressure 2) P0 = HST/10 + pD + 0,3 bar pZ pD (TAZ), table 1
pa Initial pressure pa P0 + 0,3 bar
Stat
D Pressure actor D = (pe + 1)/(pe P0)
VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) D VN 80 litre with Statico + Vento
VK Collector volume1)
pe Final pressure pe PSV ASV ASV = 0,5 bar or PSV 5 bar4)
ASV = 0,1 PSV or PSV > 5 bar4)
cmpss
VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) 1,1 VK Collector volume1)
pe Final pressure pe = pa + 0,2 pe PSV ASV
TecBox Q = (HST) : page 8
Tasf
VN Nominal volume VN (Ve + VV + 1,1 VK 1) + 5 3) ) 1,1 VK Collector volume1)
pe Final pressure pe = pa + 0,4 pe PSV ASV
TecBox Q = (HST) : page 10
itmdat vsss5)
VN Nominal volume VN VA e + 1,1 VK 1) + 5 3) e or tR and tmin, table 1
1) In solar systems to ENV12977-1: collector volume VK that can evaporate when not in operation; otherwise VK = 0.2) The ormula or the minimum pressure P0 applies to the installation o the pressure maintenance on the suction
side o the circulation pump. In case o a pressure-side installation P0 is to be increased by the pump pressure p.3) Add 5 litre when a Vento is installed in the system.4) The saety valves must work within these limits.5) Necessary or: heating systems tR > 70 C, chilled water systems tmin < 5 C, not or Transero TV and TPV.
Table 1: e expansion coecient and pD vapour pressure
t ( TAZ, tmax, tr, tm) | c 34 28 24 10 0 40 50 60 70 80 90 100 105 110
e | 0 % glycol * = 0 C 0 0,0074 0,0118 0,0168 0,0224 0,0287 0,0356 0,0432 0,0472 0,0514
pD | bar 0,2 0,4
e | 40 % glycol * = -24 C 0 0,0059 0,0239 0,0300 0,0364 0,0431 0,0502 0,0576 0,0653 0,0693 0,0734
pD | bar 0,2
e chilled water systems t < 5 C 0,0110 0,0086 0,0066 0,0014
e heating systems tR > 70 C 0,0063 0,0132 0,0208 0,0248 0,0290
Table 2: vA approx. water capacity ** o central heatings reerred to the installed heat capacity Q
tmax | tr c 90 | 70 80 | 60 70 | 55 70 | 50 60 | 40 50 | 40 40 | 30
Radiators vA litre/kW 14,0 16,5 20,1 20,6 27,9 36,6
Flat radiators vA litre/kW 9,0 10,1 12,1 11,9 15,1 20,1
Convectors vA litre/kW 6,5 7,0 8,4 7,9 9,6 13,4
Air handlers vA litre/kW 5,8 6,1 7,2 6,6 7,6 10,8
Floor heating vA litre/kW 9,2 10,3 11,8 11,9 14,7 18,0 26,8
* Antirogen N ** Water capcity = heat generator + distribution net + heat emitters
Our on line calculation programSelectP! is based on an advancedcalculation method and data base.Thereore results may deviate slightlyin marginal areas.
7/29/2019 Planning IMI international pressurization systems
5/20
5
PNEUMATEX PlAnning AnD cAlculATion
Ps pss mata
Air controlled Compresso or
water controlled Transero
minimize the pressure variations
between pa and pe.
Compresso 0,1 bar
Transero 0,2 bar
P0 Mmm pss
Stat
P0 is set as pre set
pressure on the
gas side.
cmpss
P0 and the switching
points are calculatedby the BrainCube.
: page 4
Tasf
P0 and the switching
points are calculated
by the BrainCube.
: page 4
pa ita pss
Stat
pa is the cold ll pressure
which determines the
water reserve:
pa P0 + 0,3 bar;
water make-up on:
pa 0,2 bar.
cmpss
pa allen short o during
cooling, then compressoron.
pa = P0 + 0,3
Tasf
pa allen short o during
cooling, then pump on.
pa = P0 + 0,3
p Fa pss
Stat
pe is reached ater
heating up to tmax.
pe = PSV ASV
cmpss
pe exceeded by heating
up, then air-side solenoidvalve open.
pe = pa + 0,2
Tasf
pe exceeded by heating
up, then water-side
solenoid valve open.
pe = pa + 0,4
Table 3: DNe standard values or expansion pipes with Statico and Compresso
Length up to approx. 30 m Dn 20 25 32 40 50 65 80 100
Heating TAZ 110 C | Solar Q | kW 1.000 1.700 3.000 3.900 6.000 11.000 15.000 23.000
Cooling tmax 50 C Q | kW 1.600 2.700 4.800 6.300 9.600 18.100 24.600 36.800
Table 4: DNe standard values or expansion pipes with Transero T_ *
T_ 4.1 T_ 6.1 T_ 8.1 T_ 10.1 T_ 4.2 T_ 6.2 T_ 8.2 T_ 10.2 TPV...P
Length up to approx. 10 m Dn 32 32 32 32 50 | 40 50 | 40 50 | 40 50 | 40 50
HST | m all all all all < 20 | 20 < 25 | 25 < 35 | 35 < 50 | 50 all
Length up to approx. 30 m Dn 32 40 | 32 40 | 32 40 | 32 50 | 40 50 | 40 50 | 40 50 | 40 65
HST | m all < 25 | 25 < 30 | 30 < 45 | 45 < 25 | 25 < 35 | 35 < 48 | 48 < 65 | 65 all
* 2 expansion pipes DNe or Transero TV, TPV due to degassing; 1 expansion pipe DNe or Transero T, TP
Table 5: DNe standard values or expansion pipes with Transero TI
TI ..0.2 TI ..1.2 TI ..2.2 TI ..3.2
Length up to approx. 10 m Dn 50 65 80 100
Length up to approx. 30 m Dn 65 80 100 125
PSVP0
HST/1
0+pD
pa pe
0,
3bar
0,3bar
opt
imumpressurerange
0,5b
ar
online calculating and planning with StP!
7/29/2019 Planning IMI international pressurization systems
6/20
6
PNEUMATEX PlAnning AnD cAlculATion
Stat
Selection
Heating systems TAZ 110 C, without addition o antireeze
Qk st PSV 2,5 bar PSV 3,0 bar PSV 3,0 bar
TAZ 100 C P0 1,0 bar P0 1,0 bar P0 1,5 bar
HST 7 m HST 7 m HST 12 m
Radiators Flat radiators Radiators Flat radiators Radiators Flat radiators
90|70 90|70 70|50 90|70 90|70 70|50 90|70 90|70 70|50
Q|kW nma vm Vn| litre nma vm Vn| litre nma vm Vn| litre
10 25 18 12 18 12 12 25 18 18
15 35 18 18 25 18 18 35 25 25
20 35 25 25 35 18 18 50 35 25
25 50 35 35 35 25 25 50 35 35
30 80 35 35 50 35 25 80 50 5040 80 50 50 80 35 35 80 80 50
50 120 80 50 80 50 50 120 80 80
60 120 80 80 80 80 50 120 80 80
70 120 80 80 120 80 80 140 120 80
80 140 120 80 120 80 80 180 120 120
90 180 120 120 120 80 80 180 120 120
100 180 120 120 140 120 80 200 140 120
130 300 140 140 180 120 120 300 180 180
150 300 180 180 200 140 120 300 200 180
200 400 300 200 300 180 180 400 300 300
250 500 300 300 400 300 200 500 400 300
300 500 400 300 400 300 300 600 400 400400 800 500 400 600 400 300 800 500 500
500 1000 600 500 800 500 400 1000 800 600
600 1000 800 600 800 500 500 1500 800 800
700 1500 800 800 1000 600 600 1500 1000 800
800 1500 1000 800 1500 800 600 2000 1000 1000
900 1500 1000 1000 1500 800 800 2000 1500 1000
1000 2000 1500 1000 1500 1000 800 2000 1500 1500
1500 3000 2000 1500 2000 1500 1500 3000 2000 2000
Stat SD
a hat systm
p t appx. 100 kW
P Pwater make-up as pressure
maintenance monitoring device
according to EN 1282
Zpa ZuVlor the central
separation o micro bubbles
Zpa ZuMor the central
separation o sludge,
with magnetic action
Zpa ZuTor automatic venting
during illing and during draining
Fth asss, pdt ad
st dtas: Datasheet Pleno
: Datasheet Zeparo ZU
: Datasheet Accessories
examp
Q = 200 kW
PSV = 3 bar
HST = 7 m
Radiators 90|70 C
Selected:
Statico SU 300.3
P0 = 1 bar
Reduce the actory-set pre set
pressure rom 1,5 bar to 1 bar!
Technical data:
: Datasheet Statico
System example may require changes to meet local legislation
HB
tmax
tRDNe
HST
DSV...H
ZUVL
PSV
Q
p
Statico SD
DLV
DH
ZUT
ZUM
Pleno PI
Water make-upconnection
pNS
H | TH
7/29/2019 Planning IMI international pressurization systems
7/20
7
PNEUMATEX PlAnning AnD cAlculATion
Above 100 C the static height HST decreases in the quick selection table.
TAZ = 105 C: HST 2 m
TAZ = 110 C: HST 4 m
P0 = (HST/10 + pD) + 0,3 bar pD: table 1, page 4
Recommended: P0 1 bar
pa P0 + 0,3 with cold, but vented system
eqpmt
Secured shut-o with draining or expansion vessels according to EN 12828,
DLV 20 up to VN 800 litres, DN 40 or VN 1000 5000 litres by customer.
According to table 3 on page 5.
Water make-up as pressure maintenance monitoring device according to EN 12828.
Conditions:
PlenoPIwithoutpump:requiredfreshwaterpressure:pNS P0 + 1,5 | pNS 10 bar,
Pleno PI 6 | PI 9 with pump: pa Statico (: page 4) within the working pressure range DPP o the Pleno.
Degassing and central venting.
Conditions:
pe, pa Statico (: page 4) within the working pressure range DPP o the Vento,
VA Vento VA water capacity o the system.
Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining
process. Separator or sludge and magnetite in each system in the main return to the heat generator. For
micro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central
degassing (e.g. Vento, Transero) is installed. The static height HB according to the table above the micro
bubble separator must not be exceeded.
tmax | C 90 80 70 60 50 40 30 20 10
HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7
nt f TAZ abv 100 c
P st pss stt P0
F pss, ita pss
lk shd vav DlV
: Datasheet Accessories
expas pp
P
: Datasheet Pleno
Vt
: Datasheet Vento
Zpa
: Datasheet Zeparo ZU | ZI, ZE
Stat Su
a hat systm
p t appx. 700 kW
Vt VP...e or the central venting
and degassing, with water make-up
as pressure maintenance monitoring
device according to EN 12828
Zpa Zio...S optional or micro
bubbles or sludge particles, in this
case conigured as sludge separator
Zpa ZuT or automatic venting
during illing and during draining
Fth asss, pdt ad
st dtas
: Datasheet Vento
: Datasheet Zeparo ZU | ZI, ZE: Datasheet Accessories
System example may require changes to meet local legislation
tmax
tR
HSTDSV...DGH
ET
PSV
Q
p
DH
ZUT
ZIO...S
Vento VP...E
Water make-up connection
Statico SU
DLVH | TH
online calculating and planning with StP!
7/29/2019 Planning IMI international pressurization systems
8/20
8
PNEUMATEX PlAnning AnD cAlculATion
cmpss
Selection
Heating systems TAZ 110 C, without addition o antireeze
Qk st TBx Pmay vss
TAZ 100 C 1 compressor 2 compressors * Radiators Flat radiators
C 10.1 F CPV 10.1 C 20.1 C 10.2 C 20.2 90|70 70|50 90|70 70|50
C 10.1
Q | kW Stat hht HST | m ** nma vm Vn | litre
300 46,1 33,6 81,4 46,1 81,4 200 200 200 200
400 46,1 33,6 81,4 46,1 81,4 300 300 200 200
500 46,1 33,6 81,4 46,1 81,4 300 300 200 200
600 46,1 33,6 81,4 46,1 81,4 400 400 300 300
700 46,1 33,6 81,4 46,1 81,4 500 500 300 300
800 42,7 33,6 81,4 46,1 81,4 500 500 400 300900 37,7 33,6 81,4 46,1 81,4 600 600 400 400
1000 33,6 33,6 81,4 46,1 81,4 600 600 400 400
1100 30,2 30,2 81,4 46,1 81,4 800 800 500 400
1200 27,4 27,4 79,2 46,1 81,4 800 800 500 500
1300 24,9 24,9 73,2 46,1 81,4 800 800 500 500
1400 22,7 22,7 67,9 46,1 81,4 1000 1000 600 500
1500 20,8 20,8 63,3 46,1 81,4 1000 1000 600 600
2000 13,8 13,8 46,7 34,0 81,4 1500 1500 800 800
2500 9,1 9,1 36,2 26,4 73,9 1500 1500 1000 1000
3000 5,4 28,7 21,0 61,4 2000 2000 1500 1500
3500 23,1 17,1 52,1 3000 3000 1500 1500
4000 18,6 14,0 45,0 3000 3000 2000 15004500 14,8 11,4 39,3 3000 3000 2000 2000
5000 11,6 9,2 34,7 3000 3000 2000 2000
5500 8,8 7,3 30,7 4000 4000 3000 2000
6000 6,2 5,6 27,3 4000 4000 3000 3000
6500 3,9 4,0 24,4 4000 4000 3000 3000
7000 21,8 5000 5000 3000 3000
8000 17,3 5000 5000 4000 3000
9000 13,7 4000 4000
10000 10,5 4000 4000
cmpss c 10.1 F
TBx wth 1 mpss th pmay vss, ps
pss mata 0,1 ba
wth P P wat mak-p
or heating systems
up to approx. 3 000 kW
itmdat vss Du or return
temperatures above 70 C
Zpa Zio...S conigured as micro
bubble separator in the low,
as sludge separator in the return
Zpa ZuT or automatic venting
during illing and during draining
Fth asss, pdt adst dtas
: Datasheet Pleno
: Datasheet Zeparo ZU | ZI, ZE
: Datasheet Accessories
* 50 % output per compressor,
ull redundancy in the ramed
area
** The value decreases with
TAZ = 105 C by 2 m
TAZ = 110 C by 4 m
examp
Q = 900 kW
Radiators 90 | 70 C
TAZ = 100 C
HST = 35 m
PSV = 5 bar
Selected:
TecBox C 10.1-6 F
Primary vessel CU 600.6
Setting o BrainCube:
HST = 35 m
TAZ = 100 C
Check PSV: (: page 9)
or TAZ = 100 CPSV: 35 / 10 + 1,3 = 4,8 < 5 o.k.
Technical data:
: Datasheet Compresso
HB
tmax
tRDNe
HSTDSV...DGH
ZIO...S
ET
PSV
Q
pZUT
Intermediatevessel DU
DLV
DLVDLV
CompressoPrimary vessel CU
CompressoTecBox C 10.1 F
ZUT
ZIO...S
Pleno P
Water make-up connection
pNS
min P0 + 1,7 bar,max. 10 bar
System example may require changes to meet local legislation
7/29/2019 Planning IMI international pressurization systems
9/20
9
PNEUMATEX PlAnning AnD cAlculATion
= TecBox + Primary vessel + Secondary vessel (optional)
The nominal volume can be allocated to multiple vessels o the same size.
C CPV
Precision pressure maintenance 0,1 bar
+ illsae water make-up
+ vacusplit degassing
or TAZ, HST and PSV in the Parameter menu o the BrainCube
TAZ = 100 C TAZ = 105 C TAZ = 110 C
PSV 0,1 HST + 1,3 PSV 0,1 HST + 1,5 PSV 0,1 HST + 1,7
PSV (0,1 HST + 0,8) 1,11 PSV (0,1 HST + 1,0) 1,11 PSV (0,1 HST + 1,2) 1,11
The BrainCube determines the switching points and the minimum pressure P0.
eqpmt
According to table 3 on page 5. With multiple vessels with prorata output per vessel.
Included in the scope o delivery.
Water make-up as pressure maintenance monitoring device according to EN 12828.
Conditions:
PlenoPwithoutpump,withoutcontrol(controlthroughBrainCubeCompresso):
required resh water pressure: pNS P0 (BrainCube) + 1,9 bar | pNS 10 bar,
PlenoPI6|PI9withpump,withcontrol:pa, pe Compresso (: page 4) within the working pressure
range DPP o the Pleno.
Degassing and central venting.
Conditions:
pe, pa Compresso (: page 4) within the working pressure range DPP o the Vento | CPV,
VA Vento VA water capacity o the system.
Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining
process. Separator or sludge and magnetite in each system in the main return to the heat generator. For
micro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central
degassing (e.g. Vento, Compresso CPV) is installed. The static height HB according to the table above the
micro bubble separator must not be exceeded.
tmax | C 90 80 70 60 50 40 30 20 10
HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7
cmpss
Sday vsss
TBx qpmt
Stt vas
Check PSV: or PSV 5 bar
or PSV > 5 bar
expas pps
lk shd vav DlV
P
integrated into the CPV
: Datasheet Pleno
Vt
integrated into the CPV
: Datasheet Vento
Zpa
: Datasheet Zeparo ZU | ZI, ZE
cmpss c 10.2
TBx wth 2 mpsss ft f xt t th pmay
vss, ps pss
mata 0,1 ba
wth Vt VP...e dass
ad wat mak-p
or heating systems
up to approx. 6 500 kW
Zpa Zio...F or the central
separation o sludge
Zpa ZuT or automatic venting
during illing and during draining
Fth asss, pdt ad
st dtas
: Datasheet Vento
: Datasheet Zeparo ZU | ZI, ZE
: Datasheet Accessories
C 10.1 F:
on the primary vessel up to 800 litres
C 10 | C 20 | CPV 10:
foor standing
System example may require changes to meet local legislation
tmax
tRDNe
HSTDSV...DGH
ET
PSV
Q
p
CompressoTecBox C 10.2
DLV
ZUT
ZIO...F
Vento VP...E
Water make-up connection
CompressoPrimary vessel CG
CompressoSecondary vessel CG...E
DLV
online calculating and planning with StP!
7/29/2019 Planning IMI international pressurization systems
10/20
10
PNEUMATEX PlAnning AnD cAlculATion
Tasf
Selection
Heating systems TAZ 110 C, without addition o antireeze
Qk st TBx Pmay vss
TAZ 100 C 1 pump 2 pumps * Radiators Flat radiators
T_ T_ T_ T_ T_ T_ T_ T_ TPV 90|70 70|50 90|70 70|504.1 6.1 8.1 10.1 4.2 6.2 8.2 10.2 19.2 P
Q | kW Stat hht HST | m ** nma vm Vn | litre
300 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 200 200 200 200
400 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 300 300 200 200
500 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 300 300 200 200
600 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 400 400 300 300
700 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 500 500 300 300
800 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 500 500 400 300900 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 600 600 400 400
1000 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 600 600 400 400
1100 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 400
1200 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 500
1300 28,4 38,2 55,9 75,5 28,4 38,2 55,9 75,5 134,1 800 800 500 500
1400 28,4 38,2 55,9 74,7 28,4 38,2 55,9 75,5 134,1 1000 1000 600 500
1500 28,4 38,2 55,7 73,8 28,4 38,2 55,9 75,5 134,1 1000 1000 600 600
2000 28,4 38,2 51,2 68,6 28,4 38,2 55,9 75,5 134,1 1500 1500 800 600
2500 24,9 35,9 46,0 62,5 28,4 38,2 55,9 75,5 134,1 1500 1500 1000 1000
3000 20,6 31,4 40,0 55,6 28,4 38,2 55,6 73,6 134,1 2000 2000 1500 1500
3500 15,7 26,2 33,3 47,8 28,4 38,2 53,5 71,2 134,1 3000 3000 1500 1500
4000 10,2 20,2 25,8 39,1 28,4 38,2 51,2 68,5 134,1 3000 3000 2000 1500
4500 13,6 17,6 29,5 26,8 37,9 48,6 65,6 134,1 3000 3000 2000 2000
5000 19,0 24,9 35,9 45,9 62,5 134,1 3000 3000 2000 2000
5500 22,9 33,8 43,0 59,2 133,5 4000 4000 3000 2000
6000 20,6 31,4 39,9 55,8 124,4 4000 4000 3000 3000
6500 18,3 28,9 36,6 52,1 114,6 4000 4000 3000 3000
7000 15,7 26,2 33,1 48,2 104,1 5000 5000 3000 3000
8000 10,2 20,2 25,6 39,8 80,8 5000 5000 4000 3000
9000 13,6 17,3 30,7 4000 4000
10000 20,7 4000 4000
Tasf TPV .1
TBx wth 1 pmp, ps
pss mata 0,2 bawth dass ad wat mak-p
or heating systems
up to approx. 5 000 kW
Zpa Zio...F or the central
separation o sludge
Zpa ZuT or automatic venting
during illing and during draining
Fth asss, pdt ad
st dtas
: Datasheet Zeparo ZU | ZI, ZE
: Datasheet Accessories
* 50% output per pump,
ull redundancy in the
ramed area
** The value decreases with
TAZ = 105 C by 2 m
TAZ = 110 C by 4 m
examp
Q = 1300 kW
Flat radiators 90 | 70 C
TAZ = 105 C
HST = 30 m
PSV = 5 bar
Selected:
TecBox TPV 6.1
Primary vessel TU 500
Setting o BrainCube:
HST = 30 m
TAZ = 105 C
Check PSV: (: page 11)
or TAZ = 105 C
PSV: 30 / 10 + 1,7 = 4,7 < 5 o.k.
Check HST:
or TAZ = 105 C
HST: 38,2 2 = 36,2 > 30
Technical data:
: Datasheet Transero
System example may require changes to meet local legislation
tmax
tRDNe
HSTDSV...DGH
ET
PSV
Q
TranseroTecBox TPV .1
TranseroPrimary vessel TU
ZUT
ZIO...FWater make-up connectionDPNS min 2 bar, max. 10 bar
500 mm
Statico SD
DLV
7/29/2019 Planning IMI international pressurization systems
11/20
11
PNEUMATEX PlAnning AnD cAlculATion
Tasf TV .2
TBx wth 2 pmps, ps
pss mata 0,2 bawth dass ad
P P f th wat mak-p
or heating systems
up to approx. 10 000 kW
Zpa Zio...S or the central
separation o sludge
Zpa ZuT or automatic venting
during illing and during draining
Fth asss, pdt ad
st dtas
: Datasheet Pleno
: Datasheet Zeparo ZU | ZI, ZE
: Datasheet Accessories
= TecBox + Primary vessel + Secondary vessel (optional)
The nominal volume can be allocated to multiple vessels o the same size.
T TP TV TPV TPV...P TI
Precision pressure maintenance 0,2 bar *
+ illsae water make-up
+ oxystop degassing
* 2 buer vessels or optimal pressure maintenance
or TAZ, HST and PSV in the Parameter main menu o the BrainCube
TAZ = 100 C TAZ = 105 C TAZ = 110 C
PSV 0,1 HST + 1,5 PSV 0,1 HST + 1,7 PSV 0,1 HST + 1,9
PSV (0,1 HST + 1,0) 1,11 PSV (0,1 HST + 1,2) 1,11 PSV (0,1 HST + 1,4) 1,11
The BrainCube determines the switching points and the minimum pressure P0.
eqpmt
At least one Statico SD 35, requirement or TI selection. Setting on P0 o the BrainCube.
Transero T_: table 4 | Transero TI: table 5 : page 5
Included in the scope o delivery.
Water make-up as pressure maintenance monitoring device according to EN 12828 in combination with
Transero T or TV. The control is made through the BrainCube o the Transero TecBox.
Air vent Zeparo ZUT, ZUTX or ZUP at each high point or venting during the illing and during the draining
process. Separator or sludge and magnetite in each system in the main return to the heat generator. Formicro bubbles in the system low, i possible, beore the circulation pump. The condition is that no central
degassing (e.g. Vento, Transero) is installed. The static height HB according to the table above the micro
bubble separator must not be exceeded.
tmax | C 90 80 70 60 50 40 30 20 10
HB | mWs 15,0 13,4 11,7 10,0 8,4 6,7 5,0 3,3 1,7
Tasf
Sday vsss
TBx qpmt
Stt vas
Check PSV: or PSV 5 bar
or PSV > 5 bar
Bff vsss
expas pps
lk shd vav DlV
P
: Datasheet Pleno
Zpa
: Datasheet Zeparo ZU | ZI, ZE
System example may require changes to meet local legislation
tmax
tR DNe
HST
DSV...DGH
ET
PSV
Q
TranseroTecBox TV .2
ZUT
ZIO...S
Pleno P
Water make-up connection
TranseroPrimary vessel TG
TranseroSecondary
vessel TG...E
DLV
Statico SD
500 mm
online calculating and planning with StP!
7/29/2019 Planning IMI international pressurization systems
12/20
12
PNEUMATEX PlAnning AnD cAlculATion
Aqapss
Calculation, Selection
Aqapss ptab ht wat systms
Aquapresso save valuable drinking water in potable hot water systems. The expansion water is not lost anymore through the
saety valve but is absorbed by the Aquapresso. The correct setting o the pre set pressure is o importance or a aultless and
reliable operation.
Qk st P0 4,0 bar | pa 4,3 bar P0 3,0 bar | pa 3,3 bar
Heating-up ro m 10 C to 60 C PSV | bar 6 7 8 10 6 7 8 10
VSP | litre nma vm Vn | litre nma vm Vn | litre
50 8 8 8 8 8 8 8 8
80 8 8 8 8 8 8 8 8
100 12 8 8 8 8 8 8 8
150 18 12 8 8 8 8 8 8
180 18 12 12 8 8 8 8 8
200 25 12 12 8 12 8 8 8
250 25 18 12 12 12 12 8 8
300 35 18 18 12 18 12 12 12
400 50 25 25 18 18 18 12 18
500 50 35 25 25 25 18 18 25
600 80 50 35 25 35 25 18 25
700 80 50 35 35 35 25 25 25
800 80 50 50 35 35 35 25 25
900 140 80 50 35 50 35 35 35
1000 140 80 50 50 50 35 35 35
Aqapss ADF
wth fwfsh f fw-thh a dk wat hat systm
Aqapss ADF
can be low through rom
the top or rom the bottom,
with hydrowatch installation
always rom the bottom
(PSV + 0,5) (P0 + 1,3)
(P0 + 1) (PSV P0 0,8)
pR0,8
Pre set pressure P0 = pa 0,3 bar
Saety valve PSV =
Initial pressure pa = pFL
Nominal volume VN = VSp e
The pre set pressure o the Aquapresso is set at least 0,3 bar below the initial
pressure pa.
The initial pressure corresponds to the fow pressure pFl. It should be kept at a con-
stant level by means o the installation o a pressure reducer in the cold water line.
The non-operative pressure pR in the drinking water network must not exceed 80 %
o the response pressure saety valve.
VSp is the nominal volume o the drinking water heater.
e (60 C, : table 1, page 4)
examp
VSp = 200 litre
pa = 3,3 barPSV = 10 bar
Selected:
Aquapresso ADF 8.10
with ull low-through
P0 = 3 bar
Reduce the actory-set pre set
pressure rom 4 bar to 3 bar!
Technical data:
: Datasheet Aquapresso
V = Vmax VD
V = Vmax> VD
Aquapresso ADF
Bypass open,remove handwheel
System example may require changes to meet local legislation
pR
pR
pa
pa
PSV
PSV
hydrowatch
Aquapresso ADF
hydrowatch
VSp
VSp
7/29/2019 Planning IMI international pressurization systems
13/20
13
PNEUMATEX PlAnning AnD cAlculATion
Aqapss pss-bst systms
Aquapresso in pressure-boosting systems stabilize the drinking water network and reduce the switching requency. They can
be installed at the low pressure and high pressure sides o a pressureboosting system. The mains pressure side ist always to be
coordinated with the water supply company.
Aqapss pss sss
Aqapss
a pss-bst systm
Aqapss AuF
at the low side;
low-through rom the
top to the bottom
Aqapss Au
at the high pressure side;
no low-through
Aquapresso on the low side
Calculation according to 1988 T5
Vmax| m/h VN | litre VD Nominal fow
7 300according to
< 7 15 500Datasheet
> 15 800
Aquapresso or shock absorption
This topic is very complex and complicated.
We recommend to have the calculation done
by a specialized engineering oce.
AppvasAquapresso are designed or drink-ing water systems. As there are no
uniorm European standards, pleaseobserve the drinking water approv-als or the individual countries withrespect to the selection. These aredecisive or the deployment o low-
resh ully low-through or no low-
through Aquapresso.
Aqapss A...F wth bypassI the max. volumelow Vmax is larger
than the nominal low VD or low-through Aquapresso A...F, then theAquapresso is to be installed with abypass. The bypass is to be dimen-sioned or the dierence water quan-
tity with a lowspeed o 2 m/s.: System examples: Installation | Operation
Aquapresso on the high pressure side
VN calculation according to DIN 1988 T5
or the restriction o the switching requency
VN = 0,33 Vmax
s Switching requency | 1/h Pump capacity | kW
20 4,015 7,5
10 > 7,5
VN calculation by storage volume V between
working pressure and turn-o pressure
VN = V
n Number o pumps | pE Working pressure |
pA Turn-o pressure | Vmax Max. volumefow pump
pA + 1(pA pE) s n
(pE + 1) (pA + 1)(P0 + 1) (pA pE)
System example may require changes to meet local legislation
V = Vmax> VD
Aquapresso AUF
Bypass open,removehandwheel
V = Vmax VD
Vmax
Aquapresso AUF
VmaxVDP0 at least 0,5 bar below theminimum supply pressure
V=VD
pE | pApE | pA
Aquapresso AU
P0 = 0,9 working pressureof the peak load pump,
at least 0,5 bar belowthe working pressure
Vmax
pE | pA
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0,00 0,50 1,00 1,50 2,00
V | m/h
DP
|bar
0,00
0,05
0,10
0,15
0,20
0,25
0 5 10 15 20 25 30 35
V | m/h
DP
|bar
ADF 8 12 litre
ADF 18 35 litre
ADF 50 80 litre
AUF 140 600 litre
AGF 300 700 litre
AGF 1000 1500 litre
AGF 2000 5000 litre
Aquapresso ADF Aquapresso AUF | AGF
|
|
|
|
online calculating and planning with StP!
7/29/2019 Planning IMI international pressurization systems
14/20
14
PNEUMATEX PlAnning AnD cAlculATion
Safty thy
Devices or sealed heating systems
according to EN 12828 with TAZ 110 C
ga qmts
Ti Thmmt, display range 20 % above TAZ
TAZ Tmpat mt according to EN 60730-2-9
Tc Tmpat t
lAZ lw-wat ptt2) or roo top installations
Pi Mamt, display range 50 % above PSV
SV Safty vav, EN 4126 or vapour emissionPss mata, e.g. Statico, Compresso, Transero
Pss mata mt dv4), e.g. Pleno
Addta qmts f Q > 300 kW/hat at
lAZ lw-wat ptt2)
eT Bw tak5)
PAZ Pss mt
Addta qmts wth sw-at hat
emy through thermal discharge protection
or saety heat consumer, e.g. with solid uel boilers
examp:
Safty qpmt
ad t en 12828
directly heated system
Q > 300 kW
: Datasht
Accessories
Accessories
Accessories
Accessories
AccessoriesStatico | Compresso | Transero
Pleno
Accessories
Accessories
hatddtywith oil, gas,electricity,solid uels
hatddtyheat exchangerwith vapour orliquids
1)
3)
6)
1) Temperature controller sucient according to standard, but not recommended.2) Minimum pressure or fow limiters can be used as an alternative. For central roo units above 300 kW not
additionally, 1 low-water protection is sucient.3) Dimensioning or water discharge with 1 litre/kWh possible i the primary temperature does not exceed the
evaporation temperature with the saety valve opening pressure PSV.4) Automatic water make-up device (e.g. Pleno) or minimum pressure limiter.5) Substitution with additional TAZ and PAZ possible. EN 12828 does not contain constructive specications.
We recommend to proceed according to the known state o the art o the countries, e.g. SWKI 93-1 inSwitzerland or DIN 4751-2 in Germany.
6) Only i the vapour pressure pD at fow temperature tpr is bigger than saety valve opening pressure PSV.
System example may require changes to meet local legislation
SV
Q
Pss matae.g. Statico SU
Water make-upconnection
Pss matamt dv
Degassing with built-in watermake-up, e.g. Vento VP...E
eT
pD (tpr)> PSV
7/29/2019 Planning IMI international pressurization systems
15/20
15
PNEUMATEX PlAnning AnD cAlculATion
Name o the new Pneumatex controls in Compresso, Transero, Pleno and Vento.
Name or Pneumatex compact control units consisting o hydraulic part and BrainCube control.
airproo | silentrun | dynalex | oxystop | vacusplit | helistill | leakree | illsae | secuguard |
lowresh
Damt
Characteristic diameter o the device.
Hht (H, H1, H2, )
Characteristic overall height o the device.
istaat dmss (h, h1, h2, )Wdth
Characteristic overall width o the device.
Dpth
Characteristic overall depth o the device.
lth
Characteristic overall length o the device or the ixture.
isat thkss
empty wht
o the device at the time o delivery without the packaging.
ct
Characteristic dimension or the device connection.ct
Characteristic dimension or the device connection or streaming in media.
ct t
Characteristic dimension or the device connection or streaming o media.
ct vss
Characteristic dimension or the device connection to the vessel.
ct wat mak-p
Characteristic dimension or the water make-up connection.
ct dwat
Characteristic dimension or evacuation, dewatering operations.
Ma thad, a, ISO 7-1Fma thad, yda, ISO 7-1
Fma tad, ma thad, yda, ISO 228
nma damt
Numeric size speciications or tube dimensions according to the pressure device directive.
Paka t
Standard packaging quantity in a box or pallet. For articles with the speciications o the VPE please
coordinate order quantities smaller than the VPE with the sales oice. Items within a VPE always
provide o a unctional separate packaging.
Bacb
TBx
Qaty fats
D
H
hB
T
l
SD
g
S
Se
SA
Sg
SnS
SW
rrp
g
Dn
VPe
gssay
Geometrie
General terms
7/29/2019 Planning IMI international pressurization systems
16/20
16
PNEUMATEX PlAnning AnD cAlculATion
Stat hht
Water column between the highest point o the system and the connecting branch o the expan-
sion vessel, or water-controlled pressure-maintaining systems with pump (Transero) reerred to
the suction joint o the pump.
Maxmm stat hht f th dpymt f bbb spaats
It depends on the temperature conditions at the place o installation o the separator.
Mmm pss
Lower limit value or the pressure maintenance. It is mainly deined by the static height HST and the
vapour pressure pD. I the value is allen short o the unction o the pressure maintenance cannot
be ensured. For large systems and temperature limits above 100 C the pressure limiting devices
are triggered.Statico, Aquapresso: Pre set pressure to be set at the gas side.
Be careul with respect to Aquapresso in drinking water systems! I the drinking water pressure
alls short o the pre set pressure this may lead to pressure blows and to an increased bubble wear
(: Initial pressure pa).
Transero, Compresso, Vento, Pleno: The minimum pressure P0 is calculated by the BrainCube
control rom the static height HST and the vapour pressure pD (TAZ).
Mmm qd qpmt pss
e.g. NPSH requirement or pumps or boilers
Vap pss
According to EN 12828 the excess pressure towards the atmosphere to prevent evaporation.
ita pssLower threshold or an optimum pressure maintenance. During the operation it must always be
above the minimum pressure. We recommend at least 0,3 bar. For systems with minimum pres-
sure limiters this value must be selected such that the triggering o the limiters is prevented in all
operating modes. With respect to Pneumatex devices with BrainCube control the initial pressure is
calculated internally by the control.
Statico: Pressure with minimum system temperature ater eeding the water reserve. Water make-
up devices in the sense o a pressure maintenance monitoring device according to EN 12828
must be triggered i the value is allen short o. I the illing temperature is equal to the lowest
system temperature the initial pressure corresponds to the illing pressure. e.g. heating systems:
lowest system temperature ~ illing temperature ~ 10 C.
Compresso, Transero: Pressure at which the pump or the compressor must be triggered.
Aquapresso: Pressure o the drinking water network beore the Aquapresso. It must also always begreater than the pre set pressure at low conditions.
Fa pss
Upper threshold or an optimum pressure maintenance. It must be at least 0,5 bar below the saety
valve response pressure. For systems with maximum pressure limiters it must be selected such that
the triggering o the limiters is prevented in all operating modes.
Statico: The highest pressure to be assumed ater the max. system temperature has been achieved.
Compresso, Transero: The pressure at which the spill device must open at the latest.
Aquapresso: The highest pressure to be assumed ater the absorption o the drinking water to be
stored.
rsps pss safty vav
According to EN ISO 4126-0 the pressure at which the saety valve at the heat generator begins
to open.
HST
HB
P0
pZ
pD
pa
p
PSV
gssay
Pressures
7/29/2019 Planning IMI international pressurization systems
17/20
17
PNEUMATEX PlAnning AnD cAlculATion
cs pss ta
Dierence between response pressure and closing pressure or saety valves | EN ISO 4126-1.
op pss ta
Dierence between response pressure and opening pressure or saety valves | EN ISO 4126-1.
Maxmm admssb pss
According to the pressure device directive the maximum pressure or which the pressure device
has been dimensioned according to the manuacturers speciication.
Maxmm admssb pss Swtzad
Pressure up to which the expansion vessel does not require an approval according to the Swiss
directive SWKI 93-1 (PS VN 3000 bar litre).
Pss fat
Ratio between the required nominal volume VN and the water absorption volume Ve + VV or ex-
pansion vessels.
Fsh wat pss
Flow pressure o the resh water network, e.g. drinking water network, that is available beore the
water make-up device.
Wk pss a
Pressure range or which a water make-up or degassing device has been designed. It must be ad-
justed to the working pressure o the system.
Pss ss wth ma fw
Pressure loss reerred to the nominal low capacity o a device, e.g. Aquapresso or Zeparo.
expas fft
According to EN 12828 the actor or the calculation o the expansion volume rom the water
capacity. In this case, reerred to the solidiication point.
ova systm wat apaty
According to EN 12828 the overall water capacity o the heating system that is involved in the
volume expansion.
Spf va systm wat apaty
Overall water capacity o the heating system that is involved in the volume expansion, reerred to
the installed heating surace output.
nma vm
According to the pressure device directive the entire internal volume o the pressure compartment
o the expansion vessel.
Wat apaty f whh a dv s atd
Characteristic perormance parameter that describes up to which water capacity the device, e.g.
Vento, can be used.
Wat tt t pas
For solar systems to ENV 12977-1 the collector volume which can phase change to steam has to
be added to the connecting pipes volume.
expas vm
According to EN 12828 the volume expansion o the water capacity o the heating system be-
tween the min. and max. system temperature.
Wat sv
According to EN 12828 the water quantity in the expansion vessel or the compensation o waterlosses caused by the system.
ASV
oSV
PS
PScH
Df
pnS
DPP
DPVD
VA
vA
Vn
VA
VK
V
VV
Volumes
Pressures
gssay
7/29/2019 Planning IMI international pressurization systems
18/20
18
PNEUMATEX PlAnning AnD cAlculATion
Maxmm systm tmpat
Maximum temperature or the calculation o the volume expansion. For heating systems the di-
mensioned low temperature at which a heating system is to be operated with the lowest outside
temperature to be assumed (standard outside temperature according to EN 12828). For cooling
systems the max. temperature that is achieved due to the operation mode or standstill, or solar
systems the temperature up to which an evaporation is to be avoided.
lwst systm tmpat
Lowest temperature or calculating expansion volumes. The lowest system temperature is equal
to the reezing point. It is dependant on the percentage o antireeze additives. For water without
additives tmin = 0.
Pmay fw tmpatMaximum low temperature in primary circuit o heat exchangers (indirect ired).
rt tmpat
Return temperature o the heating system with the lowest outside temperature to be assumed
(standard outside temperature according to EN 12828).
Maxmm fw tmpat
Maximum low temperature or which a device is equipped according to the normative and saety-
related requirements. TV may be greater than TS i the device is installed at a place with t TS,
e.g. in the system return.
Safty tmpat mt | Safty tmpat t | Tmpat mt
Saety device according to EN 12828 or the temperature protection o heat generators. I the
set temperature limit is exceeded the heating is turned o. Limiters are locked, controllers auto-
matically release the heat supply i the set temperature is allen short o. Setting value or systems
according to EN 12828 110 C.
Maxmm admssb tmpat
According to the pressure device directive the maximum temperature or which the pressure de-
vice or the ixture has been dimensioned according to the manuacturers speciication.
Mmm admssb tmpat
According to the pressure device directive the minimum temperature or which the pressure de-
vice or the ixture has been dimensioned according to the manuacturers speciication.
Maxmm admssb tmpat f wat mak p
The highest admissible temperature or make up units as part o a pressurisation or degassing sys-
tem. This only applies i TW < TS.
Maxmm admssb ba tmpatMaximum admissible permanent temperature or the butyl bag.
Mmm admssb ba tmpat
Minimum admissible permanent temperature or the butyl bag.
Maxmm admssb ambt tmpat
Maximum ambient temperature or the installation o a device.
tmax
tm
tp
tr
TV
TAZ
TS
TSm
TW
TB
TBm
Tu
gssay
Temperatures
7/29/2019 Planning IMI international pressurization systems
19/20
19
PNEUMATEX PlAnning AnD cAlculATion
gssay
Hat apaty
Blowing-o capacity o a saety valve reerred to the vapour emission according to the component
inspection.
Hat apaty
Blow o capacity o a saety valve reerred to the vapour emission according to the component
inspection.
Hat apaty
Blow o capacity o a saety valve or water low according to speciication, related the to heat
output o the heat generator, 1 kW = 1 l/h.
Fw at | nma fw
Nominal throughput o a device, e.g. Aquapresso, Zeparo or nominal low rate o a compressor or
pump.
Maxmm fw
Maximum throughput o a device, e.g. Zeparo.
Fw paamt
Throughput o a device with a dierential pressure o 1 bar.
Wat mak-p apaty
Nominal capacity o a water make-up device.
Vta
Nominal voltage or an electric device.
et t
Admissible current load or a device.
et ad
Load or an electric device.
Sd pss v
Sound pressure level dB(A) eective perceived.
cd f ptt aast mst ad physa tat
according to EN 60529.
Q
QPSV
QPSVW
VD
VM
KVS
VnS
u
i
PA
SPl
iP
Capacities
7/29/2019 Planning IMI international pressurization systems
20/20
DSXINEN021105
The products, texts, photographs, graphics and diagrams in this brochure may be subject to alteration by TA Hydronics
without prior notice or reasons being given. For the most up to date inormation about our products and specications,please visit www.tahydronics.com.
Addta fmat
Systm ds: :Datasheet Planning and calculation
:Online calculation sotware SelectP!
Sht ts | tms: :Datasheet Planning and calculation | Glossary