Pg 13 PIPING Local codes or ordinances governing ammonia mains should be followed, in addition to the recommendations here. Recommended Material Because copper and copper-bearing materials are attacked by ammonia, they are not used in ammonia piping systems. Steel piping, fittings, and valves of the proper pressure rating are suitable for ammonia gas and liquid. Ammonia piping should conform to ASME Standard B31.5, and to IIAR Standard 2, which states the following: 1. Liquid lines 40 mm and smaller shall be not less than Schedule 80 carbon steel pipe. 2. Liquid lines 50 to 150 mm shall be not less than Schedule 40 carbon steel pipe. 3. Liquid lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe. 4. Vapor lines 150 mm and smaller shall be not less than Schedule 40 carbon steel pipe. 5. Vapor lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe. 6. Vapor lines 350 mm and larger shall be not less than Schedule 10 carbon steel pipe. 7. All threaded pipe shall be Schedule 80. 8. Carbon steel pipe shall be ASTM Standard A53 Grade A or B, Type E (electric resistance welded) or Type S (seamless); or ASTM Standard A106 (seamless), except where temperature-pressure criteria mandate a higher specification material. Standard A53 Type F is not permitted for ammonia piping. PIPING Códigos ou ordenações regem alimentação de amoníaco locais deverão ser seguidas, para além das recomendações aqui. Material recomendado Por causa de cobre e cobre-rolamento materiais são atacados por amoníaco, que não são usados em sistemas de tubagens de amoníaco. Tubos de aço, acessórios e válvulas do classificação adequada pressão são adequados para o gás amoníaco e líquido. Tubagem de amoníaco devem estar em conformidade com norma ASME B31.5, e mentiroso Padrão 2, que afirma o seguinte: 1. linhas de líquido e 40 mm menor não deve ser inferior a tubulação de aço carbono Agenda 80. 2. As linhas de líquidos de 50 a 150 mm, deve ser igual ou superior a tubulação Schedule 40 aço carbono. 3. linhas de líquido de 200 a 300 mm, deve ser igual ou superior a tubulação de aço carbono 20 Calendário. 4. linhas de vapor de 150 mm e menores deve ser inferior a tubulação Schedule 40 aço carbono. 5. linhas de vapor de 200 a 300 mm, deve ser igual ou superior a tubulação de aço carbono Agenda 20. 6. linhas de vapor 350 milímetros e maior devem ser inferior a tubulação Schedule 10 aço carbono. 7. Todos tubo com rosca será Agenda 80. 8. Tubulação de aço de carbono deve ser norma ASTM A53 grau A ou B, Tipo E (resistência elétrica soldadas) ou do tipo S (Seamless); ou norma ASTM A106 (seamless), exceto quando critérios temperatura-pressão mandato maior material de especificação. Padrão A53 Tipo F não é permitida para a tubulação de amônia.

Piping

Embed Size (px)

DESCRIPTION

piping sch

Citation preview

Pg 13

PIPINGLocal codes or ordinances governing ammonia mains should be followed, in addition to the recommendations here.

Recommended MaterialBecause copper and copper-bearing materials are attacked by ammonia, they are not used in ammonia piping systems.Steel piping, fittings, and valves of the proper pressure rating are suitable for ammonia gas and liquid.Ammonia piping should conform to ASME Standard B31.5, and to IIAR Standard 2, which states the following:

1. Liquid lines 40 mm and smaller shall be not less than Schedule 80 carbon steel pipe.2. Liquid lines 50 to 150 mm shall be not less than Schedule 40 carbon steel pipe.3. Liquid lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe.4. Vapor lines 150 mm and smaller shall be not less than Schedule 40 carbon steel pipe.5. Vapor lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe.6. Vapor lines 350 mm and larger shall be not less than Schedule 10 carbon steel pipe.7. All threaded pipe shall be Schedule 80.8. Carbon steel pipe shall be ASTM Standard A53 Grade A or B, Type E (electric resistance welded) or Type S (seamless); or ASTM Standard A106 (seamless), except where temperature-pressure criteria mandate a higherspecification material. Standard A53 Type F is not permitted for ammonia piping.

PIPINGCdigos ou ordenaes regem alimentao de amonaco locais devero ser seguidas, para alm das recomendaes aqui.

Material recomendadoPor causa de cobre e cobre-rolamento materiais so atacados por amonaco, que no so usados em sistemas de tubagens de amonaco.Tubos de ao, acessrios e vlvulas do classificao adequada presso so adequados para o gs amonaco e lquido.Tubagem de amonaco devem estar em conformidade com norma ASME B31.5, e mentiroso Padro 2, que afirma o seguinte:

1. linhas de lquido e 40 mm menor no deve ser inferior a tubulao de ao carbono Agenda 80.2. As linhas de lquidos de 50 a 150 mm, deve ser igual ou superior a tubulao Schedule 40 ao carbono.3. linhas de lquido de 200 a 300 mm, deve ser igual ou superior a tubulao de ao carbono 20 Calendrio.4. linhas de vapor de 150 mm e menores deve ser inferior a tubulao Schedule 40 ao carbono.5. linhas de vapor de 200 a 300 mm, deve ser igual ou superior a tubulao de ao carbono Agenda 20.6. linhas de vapor 350 milmetros e maior devem ser inferior a tubulao Schedule 10 ao carbono.7. Todos tubo com rosca ser Agenda 80.8. Tubulao de ao de carbono deve ser norma ASTM A53 grau A ou B, Tipo E (resistncia eltrica soldadas) ou do tipo S (Seamless); ou norma ASTM A106 (seamless), exceto quando critrios temperatura-presso mandato maiormaterial de especificao. Padro A53 Tipo F no permitida para a tubulao de amnia.