Upload
others
View
9
Download
0
Embed Size (px)
Citation preview
Pilot Protection ofTransmission Lines
Outline
•
•
•
•
•
•
Transmission line introduction
Typical protection schemes
Need for pilot aided schemes
Various pilot schemes
Redundancy considerations
Desirable attributes of pilotrelay
Transmission Lines
•A Vital Part of the PowerSystem:
• Provide path totransfer power between generation and load
• Operate at voltage levels from 69kV to765kV
• Deregulated markets, economic, environmental requirements have pushed utilities to operate transmission lines close to their limits.
Transmission Lines
•Classification of line length dependson:Source-to-line Impedance Ratio (SIR),and
Nominal voltage
•Length considerations:Short Lines: SIR >4
Medium Lines: 0.5 < SIR <4
Long Lines: SIR <0.5
Typical Protection SchemesShort Lines
• Current differential
• Phasecomparison
• Permissive Overreach Transfer Trip (POTT)
• Directional Comparison Blocking (DCB)
Typical Protection SchemesMedium Lines
• Phasecomparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Inverse time overcurrent
• Current Differential
Typical Protection SchemesLong Lines
• Phasecomparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Current Differential
Introduction
• Nonpilot protection using overcurrent and distance relays, containa fundamental difficulty :
It is not possible to instantaneously clear a fault from both ends of a transmission line if the fault is near one end of the line.
• Pilot protection is an adaptation of the principles of differential relaying that avoids the use of controlcable between terminals.
• The term ‘pilot’ refers to a communication channel between two or more ends of a transmission line to provide instantaneous clearing over 100% of the line.
• This form of protection is also known as‘teleprotection’.
BUS
BUS
Communication Channel
Local Relay Remote Relay
Need ForPilot Aided Schemes
Pilot Communications Channels
• Distance-based pilot schemes traditionally utilize simple on/off communications between relays, but can alsoutilize peer-to-peer communications and GOOSE messaging over digital channels
• Typical communications media include:• Pilot-wire (50Hz, 60Hz,AT)• Power line carrier• Microwave• Radio• Optic fiber (directly connected ormultiplexed channels)
Distance-based Pilot Protection
Pilot-Aided Distance-Based Schemes
DUTT –Direct Under-reaching Transfer Trip
PUTT –Permissive Under-reaching TransferTrip
POTT –Permissive Over-reaching TransferTrip
Hybrid POTT –Hybrid Permissive Over-reaching Transfer Trip
DCB –Directional ComparisonBlocking Scheme
DCUB–Directional Comparison Unblocking Scheme
Direct Underreaching Transfer Trip (DUTT)
•Requires only underreaching (RU) functions which overlap in reach (Zone1).
• Applied with FSKchannel
•GUARD frequency transmitted during normal conditions
•TRIP frequency when one RU function operates
•Scheme does not provide tripping for faults beyond RU reach if remote breaker is open or channel is inoperative.
• Dual pilot channels improve security
Bus
Line
Bus
Zone 1
Zone 1
DUTT Scheme
Permissive Underreaching Transfer Trip (PUTT)
•Requires both under (RU) and overreaching (RO) functions
• Identical to DUTT, withpilot tripping signal supervised by RO (Zone 2)
Permissive Overreaching Transfer Trip (POTT)
• Requires overreaching (RO) functions (Zone 2).
• Applied with FSKchannel:• GUARD frequency sent instand-by
• TRIP frequency when one RO function operates
• No trip for external faults if pilot channel is inoperative
• Time-delayed tripping can be provided
Bus
Line
Bus
Zone 1
Zone 2
Trip
L ine
B reakers
O R
t
R x
Tx
A N D
(Z1)
(Z1)
o
Zone 1
Zone 2
Zone 2
Zone 1
POTT Scheme
POTT Scheme
POTT –Permissive Over-reaching TransferTrip
End Zone
BUS
BUS
Communication Channel
Local Relay
ZONE 2 PKP
OR
Ground Dir OCFwd
Remote Relay
Remote Relay FWD IGND
OR
Ground Dir OCFwd
Local Relay –Z2
Local Relay FWD IGND
TRIP
Remote Relay –Z2
ZONE 2 PKP
POTT
Communication Channel
RX POTT TX
POTT Scheme
POTT TX 1
POTT TX 2
POTT TX 3
POTT TX 4 Multi Phase
Remote Relay
A to G
B to G
C to G
Local Relay
POTT RX 1
POTT RX 2
POTT RX 3
POTT RX 4
Com
municatio
ns
Chan
nel(s)
POTT Scheme
Local Relay Remote Relay
ZZONONEE22OROR
GNDGND DIDIRR OOCC
FWFWDD
GND DIR OC REVGNDGND DIDIRR OOCC REVREV
POTT
Communication
Channel
RX POTT TX
TSitmaretr ET
Eiximpierre
GND DIR OC FWD
POTT SchemeCur ent reversal example
TRIP
Local Relay
Open
Remote Relay
Remote FWD
IGND
POTT RX POTT TX
Remote – Z2
Communication
ChannelOPEN
POTT TX
Communication
Channel
POTT RX
TRIP
POTT SchemeEcho example
Hybrid POTT
• Intended for three-terminal lines and weak infeedconditions
• Echo feature adds security during weak infeedconditions
• Reverse-looking distance and oc elements used to identify external faults
Bus
Line
Bus
Zone 1
Zone 2
Zone 2
Zone 1 Zone 4
LocalRemote
W e a k
sys tem
Hybrid POTT
Directional Comparison Blocking (DCB)
•Requires overreaching (RO) tripping and blocking (B) functions
• ON/OFF pilot channel typically used (i.e., PLC)•Transmitter is keyed to ON state whenblocking function(s) operate
•Receipt of signal from remoteend blocks tripping relays
• Tripping function set with Zone 2 reach orgreater
•Blocking functions include Zone 3 reverse and low-set ground overcurrent elements
Bus
Line
Bus
Zone 1
Zone 2
Zone 2
Zone 1
LocalRemote
DCB Scheme
BU
S
BU
S
End Zone
Communication Channel
Directional Comparison Blocking (DCB)
Directional Comparison Blocking (DCB)Internal Faults
Local Relay GND DIR OC Fwd Remote Relay
Local Relay – Z2
SSttaarrtt
Zone 2 PKP
OR
FWD IGND
Dir Block RXNO
TRIP TimerTRIP
Expired
Local Relay Remote Relay
Remote Relay – Z4
Zone 4 PKP
OR
REV IGND
GND DIR OC Rev
DIR BLOCK TX
Local Relay – Z2
Zone 2 PKP
OR
Dir Block RX
Communication
Channel
FWD IGND
GND DIR OC Fwd
TRIP Timer
Start No TRIP
Directional Comparison Blocking (DCB)External Faults
Directional Comparison Unblocking (DCUB)
•Applied to Permissive Overreaching (POR) schemes to overcome the possibility of carrier signal attenuation or loss as a result of thefault
•Unblocking provided in the receiver when signalis lost:
• If signal is lost due to fault, at least one permissive RO functions will be pickedup
•Unblocking logic produces short-duration TRIP signal (150-300 ms). If RO function not picked up, channel lockout occurs until GUARD signal returns
Bus
Line
Bus
Trip
Line
Breakers
(Un-Block) Tx1
Forward
Forward
(Block) Tx2
Forward
t
oAND t
o
AND
AND
AND
Lockout
(Block) Rx2
(Un-Block) Rx1
DCUBScheme
BU
S
BU
S
End Zone
Communication Channel
Directional ComparisonUnblocking (DCUB)
Directional ComparisonUnblocking (DCUB)Normal conditions
Local Relay
NO Loss of Guard
NO Permission
Remote RelayNO Loss of Guard
NO Permission
GUARD1 TXGUARD1 RX
Communication
Channel
GUARD2 TX GUARD2 RX
FSK Carrier FSK Carrier
Load Current
Directional ComparisonUnblocking (DCUB)Normal conditions, channel failure
GUARD1 TX
Communication
Channel
GUARD2 TX
FSK Carrier FSK Carrier
GNUOARRXD2 RX
SSttaarrtedted
SSttaarrtedted
Load Current
Loss of Channel
NGUOARRXD1RX
Block DCUB
until Guard OK
Local Relay
Loss of Guard
Block Timer Expired
Block DCUB
until Guard OK
Remote RelayLoss of Guard
Block TimerExpired
Directional ComparisonUnblocking (DCUB)Internal fault, healLthocyalcRhelaanyn–eZl2
Local Relay
Zone 2 PKP
Remote Relay
ZONE 2 PKP
Communication
Channel
GUTARRIDP11TX
TRIP
FSK Carrier
TRIP Z1FSK Carrier
Loss of Guard
Permission
TGRUIAP1RDR1XRX
GTRUIAP2RDT2XTX
Remote Relay – Z2
GTRUIAP2RDR2XRX
Directional ComparisonUnblocking (DCUB)Internal fault, chanLnoceallfRaelialuyr–eZ2
Local Relay
Zone 2 PKP
Loss of Guard
Block Timer Started
Remote Relay
ZONE 2 PKP
Loss of Guard
Communication
Channel
GNOUARRXD1RX GUTARRIDP11TX
TRIP
FSK Carrier
TRIP Z1FSK Carrier
GTRUIAP2RDT2XTX
Remote Relay – Z2
GNUOARRXD2 RX
Loss of Channel
StartedStarted
Duration Timer Expired
Redundancy Considerations
• Redundant protection systems increase dependability of the system:
• Multiple sets of protection using same protectionprinciple and multiple pilot channels overcome individual element failure, or
• Multiple sets of protection using different protection principles and multiple channels protects against failure of one of the protection methods.
• Security can be improved using “voting” schemes (i.e.,2-out-of-3), potentially at expense ofdependability.
• Redundancy of instrument transformers, battery systems,trip coil circuits, etc. also need tobe considered.
BU
S
BU
S
End Zone
Communication Channel 1
Communication Channel 2
Loss of Channel 2
AND Channels:
POTT Less Reliable
DCB Less Secure
OR Channels:
POTT More Reliable
DCB More Secure
More Channel Security More Channel Dependability
Redundant Communications
Redundant Pilot Schemes
Pilot Relay Desirable Attributes
• Integrated functions:• weak infeed• echo• line pick-up (SOTF)
• Basic protection elements used to keythe communication:• distance elements• fast and sensitive ground (zero and negative sequence) directional IOCs with current, voltage, and/or dual polarization