PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

Embed Size (px)

Citation preview

Page 1: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 1

April 2003

ICC

PILC Replacement: Getting the Lead Out

Spring ICC

Cincinnati, OH

April 30, 2003 ?

Page 2: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 2

April 2003

ICC

PILC IS GREAT!

• Low Profile

• High Fault Current Capability on Shield

• High Degree of Water Blocking

…So why shouldn’t you use it?

Page 3: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 3

April 2003

ICC

Why the Move Away From PILC?

• Fatigue Cracks in the Lead

• Oil Migration on Slopes

• EPA Rulings on Lead (#1 Hazardous Material)

• Comparative Expense

• Diminishing Installation Expertise

Page 4: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 4

April 2003

ICC

Replacement Challenges

• Small Duct Diameters

• Duct Conditions

• Cable Operating Temperature

• Fault Current Capability of Shield

Page 5: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 5

April 2003

ICC

How to Fit Extruded Dielectric Cables Into Existing Ducts

(Without Real Design Changes)

• Reduce the cable clearance to the duct wall. (Generally recommended minimum is 1/2”)

• Reduce the thickness of the extruded jacket. (Some utilities accept a .025” thick jacket over 750 kcmil Cu 25kV Cable)

• Extrude over compact sector conductors.

Page 6: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 6

April 2003

ICC

But These Options May Not Always Work

• Duct clearance should not be reduced to less than 1/2.”– Ducts are no longer in good condition.

– Cable may be damaged during pulling.

• Jacket thickness should not be reduced excessively.– Thin jackets may tear rather easily.

– The benefits of the jacket are then lost.

• Difficult to extrude over compact sector.– Rotation of conductor can cause problems.

– Costly process.

– Splicing and terminating may be a problem.

Page 7: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 7

April 2003

ICC

Primary Objectives

• Utilize a DRY Cable Design

• Keep a Low Profile

• Match Shield to Fault Current Requirement

• Match Ruggedness of Cable to Duct System

• Specify an Easy-to-Install Cable

Page 8: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 8

April 2003

ICC

Utilize a DRY Cable Design

• Consider the Sheath Material– Lead Over Extruded Dielectric– Corrugated and Welded Bronze– Sealed Corrugated and Folded Copper Tape

• Use Strand Filling in the Conductor

• Use Other Water Swellable Components

Page 9: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 9

April 2003

ICC

Keep a Low Profile

• Several Methods to Reduce the Cable Diameter– Compact the Conductor– Reduce the Thickness of Extruded Components

(Even the Insulation!)

– Use Flat Strap Concentric Neutrals

Page 10: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 10

April 2003

ICC

Match Shield to Fault Current

• Although lead sheath carries a high fault current, new cable may not need to carry the equivalent rating of the lead sheath.

• Determine fault requirements to optimize metallic sheath.

• Over designing the shield will result in increased I2R losses. ($$$)

Page 11: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 11

April 2003

ICC

Match Ruggedness of Cable

• What is the Condition of Your Ducts?

• A Thin Wall Jacket May Be Used If It’s Tough Enough– Consider Toughness and Heat Stability– LLDPE, HDPE, Polypropylene

• Determine Amount of Clearance Required – Can it Be Reduced to Less Than ½”?

Page 12: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 12

April 2003

ICC

Specify Easy-to-install Cable

• Round Conductors vs. Sector Conductor

• Flexibility is Key

• Connectability to existing system

• Consider Pulling Length

Page 13: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 13

April 2003

ICC

Design Higher Stress Cables

• A common design practice for HV power cables is to design the cable with a high maximum stress (e.g. EPR 240kV Class @ 10kV/mm)

• In MV cables, the design operating at the highest voltage stress is the 35kV #1/0 AWG Conductor (4 kV/mm).

• If the same insulation is used, why NOT design MV cable to a higher stress?

Page 14: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 14

April 2003

ICC

Electric Stress Variations Within Cable Insulation

Conductor

Conductor Shield

Insulation

Insulation Shield

Metallic Shield

Electric Stress DistributionWithin The Insulation

Page 15: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 15

April 2003

ICC

April 2003

S@DS@Dxx = = 2.0 x E2.0 x E

DDxx x LN x LN DD dd

Where:

S@Dx = Stress at diameter “Dx” , volts/mil E = Voltage across insulation, volts Dx = Diameter of interest, mils D = Diameter over insulation, mils d = Diameter over conductor shield, mils

Calculation of Voltage Stress in Cables

Page 16: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 16

April 2003

ICC

Reducing the Insulation Thickness Is The Last Step

• Compact Conductor

• Use a Flat Strap Neutral

• Reduce the Jacket Thickness

• Reduce Thickness of the Conductor and Insulation Shields

• Reduce Clearance to Duct

• THEN Reduce the Insulation Thickness

Page 17: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 17

April 2003

ICC

750 KCM2.95 INCH OD

3/C 750 KCM3.50 INCH OD

175 MILS EPR140 MILS JKT

3-1/C 750 KCM3.65 INCH OD

175 MILS EPR 80 MILS JKT

PILC

CABLE DESIGN SELECTIONStandard Designs - 15 KV

Page 18: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 18

April 2003

ICC

3/C 750 KCM2.95 INCH OD

PILC

3/C 750 KCM3.10 INCH OD

125 MILS EPR120 MILS JKT

140 MILS EPR110 MILS JKT

3-1/C 750 KCM3.10 INCH OD

125 MILS EPR50 MILS JKT

CABLE DESIGN SELECTIONReduced Wall Designs - 15 KV

Page 19: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 19

April 2003

ICC

Testing the Design

• Testing should show that the proposed design will stand up to the rigors on the installation and operation.

• Electrical and Mechanical Tests• Testing should be at or above proposed

operational limits. – (AEIC CG11-02 recommends same test level as used on the 100%

insulation level.)

Page 20: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 20

April 2003

ICC

Electrical Testing

• AC Breakdown Study• Ionization Factor• AEIC Qualification

(As Applicable)

• Accelerated Water Treeing Testing (AWTT)

• Accelerated Cable Life Testing (ACLT)

Page 21: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 21

April 2003

ICC

Mechanical Testing

• Should replicate the actual installation conditions, or be more severe

• May include such factors as:– Reverse Bends– High Sidewall Pressure– Small Minimum Bending Radii– Several Cycles of Pulls

• Electrical Testing Should Follow with No Significant Reduction in Electrical Properties

Page 22: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 22

April 2003

ICC

Page 23: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 23

April 2003

ICC

Reduced Insulation Wall Summary

• In Use for Over Ten Years

• Tested with Accessories

• A Definite Design Alternative for Tight Duct Situations

Page 24: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 24

April 2003

ICC

Accessories

• In general, premolded accessories may not pass corona tests when installed on reduced insulation thickness cables.

• Cold-shrink and heat-shrink accessories should pass electrical tests.– Trifurcating splices are available.

• Electrical Stress on Reduced Insulation Wall Cables Must Be Controlled at Both Conductor Shield and Insulation Shield Interfaces.

Page 25: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 25

April 2003

ICC

Accessories

• Joint size should allow installation in existing smaller manholes.

• Cold-shrink terminations can be used to replace potheads.

• Compression connectors can be used to shape sector conductors.

• Should be qualified to IEEE Std. 404.

Page 26: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 26

April 2003

ICC

Summary & Conclusions

• Overall cable design is more important than any individual component.

• Complete redesign not always necessary.• Several types of shields are available.• High temperature jackets should be considered.• Reduced Insulation Wall Is a Viable Option

Page 27: PILC Replacement Page 1 April 2003 ICC PILC Replacement: Getting the Lead Out Spring ICC Cincinnati, OH April 30, 2003 ?

PILC Replacement

Page 27

April 2003

ICC

Summary & Conclusions• Properly designed PILC replacement cables have

been found to be both electrically and mechanically suitable for installation and operation on utility network systems.

• Whatever the design chosen:– There should be no significant change in the electrical

and physical properties when comparing the reduced wall samples to the full wall samples.

– There should be no significant change in the electrical and physical properties after severe mechanical conditioning.