SINGLE LINE DESCRIPTION DOUBLE LINE
D D
SPLIT BRANCH TAKE-OFF WITH SQUAREELBOW & SPLITTER DAMPER
SPLIT BRANCH TAKE-OFF WITH RADIUSELBOW & SPLITTER DAMPER
POSITIVE PRESSURE RISER,TYPICALLY SUPPLY
NEGATIVE PRESSURE RISER, TYPICALLYRETURN, EXHAUST OR OUTSIDE AIR
F/S COMBINATION FIRE & SMOKE DAMPER F/S
FIRE DAMPER
MOTOR OPERATED DAMPER (MOD)
MANUAL VOLUME DAMPER, SINGLE BLADEDAMPER (SBD) FOR ROUND OR <10" TALL,OPPOSED BLADE DAMPER (OBD) >10" TALL
BACKDRAFT DAMPERBDD BDD
SMOKE DAMPER
SMOKE DETECTOR
DUCT SIZE: FIRST NUMBER IS PLAN WIDTH,SECOND NUMBER IS DEPTH.
24x3624x36
DUCTWORK LEGEND
SDSD
PRESSURE REDUCING VALVE
SHOCK ABSORBER
STRAINER W/ BLOW-OFF VALVE
SAFETY RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE W/ PIG TAIL & COCK
THERMOMETER
PRESSURE - TEMP. TAP
AIR VENT
PIPE ANCHOR
FLEXIBLE CONNECTOR
PIPE EXPANSION JOINT
PIPE UNION
DOUBLE CHECK BACKFLOW PREVENTER
PUMP & EQUIPMENT CONNECTOR
TEMPERATURE CONTROL VALVE (2-WAY)
DRAIN VALVE W/ HOSE END
PLUG VALVE IN RISER
FLOW BALANCING VALVE
GATE OR GLOBE VALVE IN RISER
FLOW CONTROL VALVE
BALL VALVE
PLUG OR BALANCING VALVE
CHECK VALVE
GLOBE VALVE
BUTTERFLY VALVE
VENTURI/FLOW INDICATOR
TEMPERATURE CONTROL VALVE (3-WAY)
SOLENOID VALVE
90° ELBOW UP
TEE UP
TEE DOWN
SHUT OFF (BALL, GATE, BUTTERFLY)
PIPING SYMBOLS90° ELBOW DN
S
FLOW SWITCH
HOSE BIBB
WALL HYDRANT
TEMPERATURE CONTROLLER OR SENSOR
STEAM TRAP TEST CHAMBER
STEAM TRAP:FT-FLOAT & THERMOSTATICTD-THERMODYNAMICIB-INVERTED BUCKETTS-THERMOSTATICBP-BALANCED PRESSURE
EQUIPMENT ABBREVIATIONSAIR HANDLING UNITAHU
AIR SEPARATORAS
BOILER (HOT WATER)B
BASE BOARDBB
BUFFER TANKBT
CONSTANT VOLUME BOXCV
DISHWASHER EXHAUST FANDEF
ELECTRIC BASEBOARD HEATEREBH
FURNACEF
FAN COILFC
FAN POWERED BOXFP
GLYCOL FEEDERGF
HUMIDIFIER
HC HEATING COIL
HP HEAT PUMP
HX HEAT EXCHANGER
KITCHEN EXHAUST FANKEF
MAKE-UP AIR UNITMAU
MOTOR CONTROL CENTERMCC
MIXING VALVEMV
PUMP P
RETURN (OR RELIEF) AIR FANRF
RADIANT ZONERZ
SNOWMELT AREASA
SUMP BASINSB
SUPPLY FANSF
STORAGE TANKST
THERMOSTATIC MIXING VALVETMV
UNIT HEATERUH
VARIABLE VOLUME BOXVV
WATER HEATERWH
H
CHILLERCH
COOLING COILCC
CIRC PUMPCP
CABINET UNIT HEATERCUH
COOLING TOWERCT
DUCT COILDC
ELECTRIC WATER HEATEREWH
EVAPORATIVE COOLING UNITECU
ENERGY RECOVERY UNITERU
EXHAUST FANEF
EXPANSION TANKET
VARIABLE VOLUME BOX W/ REHEATVR
TYPE OF AIR DEVICERE: GRD SCHEDULE.
AIR DEVICE DESIGNATION KEY
#CAEXHOSARAXFR
SIZE (INCHES) OR MINIMUMFREE AREA REQUIRED INSQUARE FEET.
NOTE:FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN ISNECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE.
INDICATES AIRINLET DEVICE.
======
AIR QUANTITY (CFM)COMBUSTION AIREXHAUSTOUTSIDE AIRRETURNTRANSFER
BXFR12x6
A15012x6
PLAN ABBREVIATIONS
ABOVE FINISHED FLOOR
AIR ADMITTANCE VALVE
ABOVE FINISHED GRADE
AUTOMATIC
BUILDING CONTROL SYSTEM
BACK DRAFT DAMPER
BUILDING
AAV
AFF
AFG
AUTO
BCS
BDD
BLDG
BETWEEN
COMMON (OR CLOSED)
COMBUSTION AIR
CONTROLS CONTRACTOR
CONTINUATION DESIGN BUILD
B/N
C
CA
CC
CDBBC
CUBIC FEET PER MINUTE (AIR FLOW RATE)
CAST IN PLACE
CEILING (OR COOLING)
CONCRETE
CONDENSATE
CONNECT (OR CONNECTION)
CONTRACTOR
CFM
CIP
CLG
CONC
COND
CONN
CONTR'R
CLEANOUT TO GRADECOTG
DOMESTIC HOT WATER RECIRC
EXISTING
DWR
(E)
EXHAUST AIREA
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING WATER TEMPERATURE
EAT
EC
EXH EXHAUST
EWT
GENERAL CONTRACTOR
GROUND HEAT EXCHANGER
GC
GHX
GALLONS PER MINUTE (WATER FLOW RATE)GPM
HORSEPOWER
HOT WATER
IN LIEU OF
HP
HW
ILO
KILOWATTSKW
LEAVING AIR TEMPERATURE
LINEAR FOOT
LEAVING WATER TEMPERATURE
LAT
LF
LWT
MECHANICAL CONTRACTORMC
MANUFACTURER
MOTOR OPERATED DAMPER
NEW
MFG
MOD
(N)
NORMALLY CLOSEDNC
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NORMALLY OPEN
NEC
NIC
NO
OUTSIDE AIROA
OPPOSED BLADE VOLUME DAMPER
ON CENTER
OBD
OC
OUTSIDE AIROSA
RETURN AIR
REQUIRED
RA
REQ'D
REQUIREMENTSREQ'MTS
SUPPLY AIR
SQUARE FOOT (FEET)
SA
SF
STATIC PRESSURESP
STAINLESS STEEL
THROW-AWAY (TRANSFER AIR)
TYPICAL
SS
TA
TYP
UNLESS NOTED OTHERWISEUNO
WALL CLEANOUTWCO
WITH REGARD TO
WATER COOLED
TRANSFER
WRT
W/C
XFR
DIAMETERØ
BY CONTRACTOR
COLD WATERCW
HOT WATER RECIRCHWC
ABOVEABV
BELOW FINISHED GRADEBFG
DOMESTIC WATER
DOMESTIC HOT WATER
DW
DHW
DOWNDN
DOMESTIC HOT WATER RECIRCDHR
COMBINATION FIRE/SMOKE DAMPER
FURNISHED BY OWNER
FSD
FBO
FLOOR CLEANOUTFCO
FOR CONTINUATIONFCT
FD FIRE DAMPER
REFER TO:RE:
WITHW/
CLEANOUTCO
FUTURE(F)
FREE AREAFA
FFI FOR FURTHER INFORMATION
WITHOUTW/O
VENT THRU ROOFVTR
NOTES1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ONTHIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, INPART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES ANDNOTATION CONVENTIONS OCCURRING IN THISDRAWING SET ARE NECESSARILY DEFINED ON THESELEGENDS. CONSULT THE ENGINEER IN THE EVENTSYMBOLOGY OR NOTATION INTERPRETATION ISREQUIRED.
PLAN SYMBOLSCONTROL PANEL/RADIANT MANIFOLD
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DIAGRAM CONTINUATION REFERENCE
PLUMBING/HVAC RISER
POINT OF NEW CONNECTION
DUCT STATIC PRESSURE SENSOR
ROOM PRESSURE SENSOR
EMERGENCY POWER OFF SWITCH
ACCESS PANEL
SNOWMELT MANIFOLD
SECTION CUT LETTER/SHEET SHOWN ON
POINT OF DISCONNECTION
-
SP
CO2
EPO
P
CO
--
-P
THERMOSTAT
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
T
S
H
H B
W H
TC
FS
ROOF DRAIN
FLOOR DRAIN
FLOOR SINK
HORIZONTAL CLEANOUT
VERTICAL CLEANOUT
DECK/ROOF DRAIN ABOVE
PIPING DESIGNATIONS
SNOWMELT SUPPLY
SNOWMELT RETURN
HEATING WATER SUPPLY (HIGH TEMP)
HEATING WATER RETURN (HIGH TEMP)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER RETURN
HIGH PRESSURE STEAM
HIGH PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE RETURN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
FLOOR COOLING SUPPLY
FLOOR COOLING RETURN
HEATING WATER SUPPLY (LOW TEMP)
HEATING WATER RETURN (LOW TEMP)
SOLAR HEATING WATER SUPPLY
SOLAR HEATING WATER RETURN
GROUND LOOP SUPPLY
GROUND LOOP RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
GLYCOL FEED
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
PUMPED CONDENSATE
GEOTHERMAL (OR GROUND) LOOP SUPPLY
GEOTHERMAL (OR GROUND) LOOP RETURN
CLOSED CONDENSER SUPPLY
CLOSED CONDENSER RETURN
CONDENSER SUPPLY
PLUMBING PIPING
CR
CS
CCR
CCS
GLR
GLS
CHR
CHS
GLR
GLS
GF
HWR
HWS
HWR(LT)
HWS(LT)
HWR(HT)
HWS(HT)
FCR
FCS
SHWR
SHWS
SMS
SMR
PC
MPR
MPS
LPS
LPR
HPR
HPS
RS
RL
STEAM & CONDENSATE PIPING
HYDRONIC PIPING90° ELBOW DOWN (ROUND DUCT ONLY)
ROUND 90° ELBOW UP (ROUND DUCT ONLY)
OFFSET TO CHANGE ELEVATION(AT 30° WHEN POSSIBLE)
D = DROP R = RISE
ROUND RADIUS ELBOW
90° STRAIGHT TEE
90° CONICAL TEE
45° BRANCH
45° CONICAL TEE
SIZE OR SHAPE TRANSITION
ROUND FLEXIBLE DUCT
90° ELBOW DN (NEGATIVE PRESSURE)
90° ELBOW DN (POSITIVE PRESSURE)
90° ELBOW UP (NEGATIVE PRESSURE)
90° ELBOW UP (POSITIVE PRESSURE)
90° RADIUS ELBOW
90° RADIUS ELBOW W/TURNING VANES
SQUARE DUCT SPLIT
ROUND DUCT SPLIT
SUMP PUMPSP
MECHANICAL SYSTEMS LEGEND
ABOVE SEA LEVEL
PROJECT ALTITUDE5,292'
' 'ISSUE LOG KEY:
#
DA
TE
ISSUE LOG
MECHANICAL SHEET INDEX
TITLE
MECHANICAL COVER SHEETM0-01
100%
DD
02.2
2.20
18ISSUED AS PART OF A SET' ' NOT PART OF SET' ' ISSUED FOR INFORMATION ONLY*
√√√
√
√
MECHANICAL DEMOLITION PLANM-1-01
MECHANICAL DETAILSM-5-01MECHANICAL SCHEDULESM-6-01
MECHANICAL PLANM-1-02
√√MECHANICAL ROOM ENLARGED PLANM-1-03
95%
CD'
s
04.3
0.20
18
√√√
√√√
√MECHANICAL CONTROLSM-7-01 √
100%
CD'
s
√√√
√√√
√
05.2
5.20
18
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
MECHANICALCOVER SHEET
M0-01
74"x 34"(E)
80"x 32"(E)
80"x
32"
(E)
74"x
34"
(E)
26"x20"(E)
22"x20"(E)
34"x10"(E)
34"x
10"
(E)
18"x
10"
(E)
F/S
26"x 20"(E)
26"x 20"(E)
26"x20"(E)
14"x 14"(E)
12"Ø
(E)
F/S
F/S
22"x20"(E)
16"x14"(E)
8"Ø(E
)10
"x8"
(E)
T
14"x 12"(E)
8"Ø(E
)
10"Ø
(E)
T
26"x20"(E)
26"x 20"(E)8"x 8"(E)
F/S
14"x14"(E)
12"x12"(E)
14"Ø
(E)
8"x8"(
E)
12"x10" (E)
10"Ø
(E)
T
T
22"x14"(E)12"x10"(E)
16"x
10"(
E)
T
18"x18"(E)
18"x16"(E)
16"x14"(E)
16"Ø(E)
T
T
10"Ø(E)
12"Ø(E)
10"x10"(E)
18"x16"(E)
16"x10"(E)
T
T
14"x12"(E)
38"x10"(E)
38"x10"(E)
F/S
F/S
F/S
F/S
8"x8"(
E)
F/S
F/S
F/S
F/S
F/S
F/S
F/S
14"x14"(E)
18"x16"(E)
14"x12"(E)
16"x14"(E)
MVDMVD
MVD
MVD
F/S
F/S
F/S
32"x
14"(
E)
T
16"Ø
(E)
8"x8"(E)F/S
F/S
F/S
12"x12"(E)
16"x
16"(
E)
F/S
F/S
F/S
F/S
T
24"x20"(E)
16"Ø(E)
20"x
20"(
E)
12"x12"(E)12"x12"(E)
24"x
22"(
E)
24"x
24"(
E)
26"x24"(E)
50"x
22"(
E)
24"x22"(E) 20"x20"(E) 18"x18"(E)
34"x
22"(
E)
14"x12"(E)
10"x
10"(
E)
10"x10"(E)12"x10"(E)16"x14"(E)
14"x12"(E)
12"x12"(E)
6"x6"(E)
10"x10"(E)
F/S
16"x
14"(
E)
12"x12"(E) 16"x14"(E)8"x6"(E)
10"x
10"(
E)
T
TT
T
TT
F/S
14"x14"(E)
16"x
16"(
E)
12"x10"(E)
T
18"x16"(E)
TT
T
T
T
T
T
T
T
T T
12"x
12"(
E)
8"x8
"(E
)
16"x14"(E)24"x10"(E) 20"x18"(E)28"x8"(E)
26"x12"(E)
26"x14"(E)
30"x8"(E)
12"x12"(E)
55"x20"(E)
8"Ø (E) 10"Ø (E)
10"Ø (E)8"Ø (E)
10"Ø (E)
10"Ø
(E)
8"Ø (E)
TT
111
1
1
1
1
1
1
1
1
1
1 11 1 1
1
1 1
1
1
1
1
1
1
1
1
1
1
14"x14"(E) 18"x8"(E) 12"x12"(E)
22
22
T4
55
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
MECHANICALDEMOLITION PLAN
M1-01Scale:
1 MECHANICAL DEMOLITION PLAN1/8"=1'-0"
FLAG NOTES:#
1. EXISTING TERMINAL UNIT TO REMAIN. REMOVECONTROLS INCLUDING ACTUATORS, WIRING, TUBING,AND THE ASSOCIATED THERMOSTAT.
2. REMOVE GRILLES IN THE ROOM AS SHOWN. REMOVEASSOCIATED FLEX. NOTE NECK SIZE OF EXISTINGGRILLE FOR REPLACEMENT.
3. REMOVE LOW PRESSURE DUCT BACK TO REHEATCOIL.
4. CAREFULLY REMOVE THERMOSTAT FROM WALL ANDRETAIN FOR RE-USE OR SALVAGE TO OWNER.REMOVE ANY AND ALL PNEUMATIC TUBING BACK TOMAIN LINE AND CAP. REMOVE ANY WIRINGASSOCIATED WITH THE THERMOSTAT.
5. CAREFULLY REMOVE SUPPLY GRILLE FROM CEILINGAND KEEP FOR RE-INSTALLATION IN THE NEW CEILING.
1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTEAND VENT PIPING MAY BE ROUTED IN SPACE THAT ISNOT REPRESENTED, BUT IS TO REMAIN. OTHERSYSTEMS MAY EXIST WITHIN THE SPACE THAT ARENOT REPRESENTED ON THESE DRAWINGS;MODIFICATIONS TO THESE SYSTEMS ARE NOTANTICIPATED.
2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.
3. PROVIDE PRELIMINARY TESTING OF EXISTINGHYDRONIC SYSTEMS. MEASURE CURRENT FLUIDFLOW RATE THROUGH ALL EXISTING COILS, RADIANT,AND SNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OF MEASUREDVALUES TO ENGINEER FOR REVIEW ANDCONFIRMATION OF SYSTEM DESIGN ASSUMPTIONSPRIOR TO DEMOLITION.
4. PROVIDE PRELIMINARY TESTING OF EXISTING HVACDUCTWORK SYSTEMS. MEASURE CURRENT AIRFLOW RATES AT ALL EXISTING SUPPLY, RETURN, ANDEXHAUST REGISTERS. MEASURE TOTAL AIR FLOWSAT MAIN DUCT BRANCHES AND ALL FAN SYSTEMS.SUBMIT REPORT OF MEASURED VALUES TOENGINEER FOR REVIEW AND CONFIRMATION OFSYSTEM DESIGN ASSUMPTIONS PRIOR TODEMOLITION.
5. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INTHE CEILING OF THE SPACE BELOW.
6. REMOVE ALL MECHANICAL ITEMS INDICATED.
7. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.
8. SEAL ALL OPEN DUCTS DURING CONSTRUCTION TOMITIGATE DUST AND DEBRIS FROM SYSTEM. CAPDUCTWORK IN LOCATIONS THAT ARE NOT BEINGRECONNECTED.
9. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.
10. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.
11. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.
12. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.
13. ALL EXISTING COMBINATION FIRE/SMOKE DAMPERSDEPICTED ON THIS SHEET SHALL BE REMOVED.
DEMOLITION NOTES:
Scale:
2 RADIOLOGY CORRIDOR FLOOR PLAN1/8"=1'-0"
AHU-2 (E)1
EXISTINGMECH./ELEC
AHU-1 (E)1
OAF-1 (E)2
60"x28" (E)
60"x
28" (
E)
80"x
32" (
E)
MVD
MVD
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
MECHANICAL ROOMENLARGED PLAN
M1-03
Scale:
1 MECHANICAL ROOM ENLARGED PLAN1/4"=1'-0"
FLAG NOTES:#
1. ALL EXISTING PNEUMATIC CONTROLS SHALL BECAREFULLY REMOVED. THE HYDRONIC VALVES SHALLBE REPLACED. DAMPER ACTUATORS SHALL FIELDVERIFY THE LOCATION SIZE AND TYPE OF ALLHYDRONIC CONTROL VALVES AND ACTUATORS FORREPLACEMENT AS A PART OF THE DIRECT DIGITALCONTROLS UPGRADE. VERIFY EXISTING DAMPERACTUATORS AND REPLACE WITH NEW.
2. APPROXIMATE LOCATION FOR EXISTING OUTSIDE AIRFAN.
1. RE: _/M_ SERIES FOR MECHANICAL DIAGRAMS.
2. COORDINATE ROUTING OF CONDENSATE DRAINLINES WITH ARCHITECT PRIOR TO INSTALLATION.
3. CEILING COORDINATION OF ALL MEP SYSTEMS(LIGHTING, DUCTWORK, DIFFUSERS, ELECTRICAL,FIRE PROTECTION, ETC.) MUST BE COMPLETED BYTHE CONTRACTOR PRIOR TO THE START OF ANYINSTALLATIONS.
4. DO NOT ROUTE DUCTWORK OVER ELECTRICALROOMS OR ELECTRICAL PANELS; MAINTAIN N.E.C.CLEARANCES. COORDINATE ROUTINGS WITH DIV. 16CONTRACTOR.
5. CONTRACTOR TO MAINTAIN 8'-6" CLEAR HEAD HEIGHTIN GARAGE AND INFORM THE ENGINEER ANDARCHITECT OF ANY AREAS THAT MAY NOT MEET 8'-6"PRIOR TO INSTALLATION, MINIMUM 8'-2" CLEAR HEADHEIGHT MUST BE MAINTAINED IN ACCESSIBLE VANAREAS.
6. PROVIDE FLEXIBLE DUCT AND PIPE CONNECTIONS TOALL MOTORIZED EQUIPMENT.
7. VERIFY ALL EQUIPMENT ACCESS PANELS WITHMANUFACTURER AND ARCHITECT.
8. ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.
9. PROTECT PIPING ROUTED ALONG COLUMNS, WALLS,ETC. FROM DAMAGE AS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.
10. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATEFIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.
11. THE SPACE ABOVE CEILING IS BEING UTILIZED AS ARETURN AIR PLENUM. ALL RETURN GRILLES SHALL BEPROVIDED WITH SOUND BOOTS AND A DIRECT PATHTO THE AIR HANDLING SYSTEM RETURN DUCT, OPENTO PLENUM. WHERE FULL HEIGHT WALLS AREINSTALLED AND THE RETURN AIR PATH ISCOMPROMISED, THE SOUND BOOT SHALL EXTENDTHROUGH THE WALL OR TRANSFER AIR DUCTSSHALL BE PROVIDED. OTHERWISE, PROVIDE Z- OR U-DUCT TRANSFER THROUGH WALL. TRANSFER DUCTSAND SOUND BOOTS SHALL BE LINED SHEET METAL.NON-METAL DUCT NOT PERMITTED.
12. T-STATS AND CO2 SENSORS SHALL BE LOCATEDNEAR THE LIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT & ELECTRICALENGINEER TO MATCH HEIGHT AND LOCATION.
13. ALL DUCTWORK SHALL BE ROUTED AS HIGH ASPOSSIBLE IN THE CEILING SPACE. UTILIZE JOISTSPACE WHEN POSSIBLE, ESPECIALLY WHERECROSSING OTHER DUCTS, PIPES, AND ELECTRICAL.
14. ACCESS PANELS SHALL BE 24x24, U.N.O. LOCATIONSSHOWN ARE APPROXIMATE, EXACT LOCATIONSSHALL BE COORDINATED WITH THE ARCHITECTSDRAWINGS AND WITH THE LOCATIONS OF THEEQUIPMENT OR APPARATUS THAT THEY SERVE.
15. SEAL ALL DUCT PENETRATIONS OF ACOUSTICPARTITIONS.
HVAC NOTES:
EXTERIOR DUCTINSULATION.
INSULATED ACOUSTICFLEX DUCT. 5'-0"MAXIMUM LENGTH
INTERNALLY LINED SUPPLYDUCT, OR AS NOTED INSPECIFICATIONS.
CONICAL SPIN-IN FITTING WITHMANUAL VOLUME DAMPER.
SHEET METALSTRAP.
S.S. WORM DRIVECLAMP.
SQUARE TO ROUND ADAPTERAS REQUIRED.
SHEET METALSHIELD.
SUPPORT AS REQUIREDFOR MIN RADIUSSPECIFIED.
MINIMUM ℄ RADIUS > 1.5 xFLEX DUCT DIAMETER.
CEILING DIFFUSER
NO SCALE
TYPICAL DIFFUSER CONNECTION DIAGRAM OFF DIAGRAM45° DUCT TAKE-
45°
NO SCALE
DAMPER IF H<8"
TAKE-OFF.AROUND ENTIRESEAL AIRTIGHT
OPPOSED BLADEDAMPER IF H>=8"
SINGLE BLADE
6" MINIMUM.1/4 OF "W" OR
ENDBEARING
W
H
GRILLE CONNECTION DIAGRAMEXHAUST/DUCTED RETURN
NO SCALE
FLEX DUCT CONNECTION FORLAY-IN CEILING, SHEET METALCONNECTION OVER HARD CEILING
SHEET METAL PLENUM(NO INSULATION). MATCHGRILLE NECK. HEIGHT 4"HIGHER THANCONNECTION.
WORM DRIVE S.S.CLAMP.
CEILING DIFFUSER.
FIRE DAMPER AND FIRE/SMOKE
NO LINING REQ'D.
SOLID METAL STUDNO LINING WITH
FRAMING.
THE WALL.EQUAL TO THAT ONMATERIAL OF RATINGWITH FIRE RESISTIVEOPENING TO BE LINED
CONCRETE OR MASONRY
METAL STUD
NO SCALE
WOOD STUD
WALLSLEEVE.
MAX. DIMENSIONS ASSOCIATED WITH THE TESTCONNECTION. ALL U.L. LISTED DAMPERS ALSO HAVESLEEVE THICKNESS IS CONTINGENT ON TYPE OFTO TERMINATE AT SLEEVES OR DAMPER FRAMES.BY U.L. STANDARD 555 ALL DUCTS ARE REQUIRED
LINKAGE ASSEMBLY OUT OF
THIS DIAGRAM IS NOT INTENDED TO
AND FIRE/SMOKE DAMPER INSTALLATION.COVER ALL CASES OF FIRE DAMPER
HOWEVER SLEEVE THICKNESS MUST ALSO NOT BELESS THAN DUCT GAGE OR THAT SPECIFICALLYAUTHORIZED BY A RECOGNIZED AUTHORITY.
SLEEVE
SHEET METAL DUCT.
DAMPER FRAME.
BREAKAWAY DUCTCONNECTION.
RECESSED DAMPER AND
RECOMMENDED MIN. SLEEVE THICKNESS
CONNECTION
CONNECTION
CONNECTION
85" UP
55"-84"
31"-54"
RATING.
18
20
22
FIRE RESISTIVE MATERIAL.
BREAKAWAY
CONNECTIONTYPE OFSLEEVE.
ANGLE.
13"-30"
RECTANGULARIN DIA. ORDUCT DIM.
12" DN
24
GAGE
26
.036"
.047"
.030"
.024"
.018"
UNCOATED STEELTHICKNESS
MIN. SLEEVECOATEDSTEEL
WALL.
RETAINING ANGLE.
CLOSURE DETAIL.
AIRSTREAM.
PROVIDE ACCESS PANELS ASREQUIRED.
1.1.
2.
NOTES:
DAMPER ASSEMBLY DIAGRAM
ROOF EXHAUST FAN DIAGRAMNO SCALE ( FLAT ROOF )
EXHAUST FAN.
BIRD SCREEN.
PRE-FAB CURB WITH11
2" INSULATION.
ROOFING.
BACKDRAFT DAMPER.
ANCHOR FAN TO CURB.
RUN FLASHING UPUNDER FAN BASE.
FLASHING AND COUNTERFLASHING.
NOTE:COORDINATE ROOF PENETRATIONS WITHROOFING MANUFACTURER.
TERMINAL UNIT DIAGRAM
HWR
HWS
NO SCALE
NOTE:PIPING COMPONENTS MAY BE INCLUDEDIN COMBINATION VALVE PACKAGED BYAUTOMATIC FLOW CONTROL VALVEMANUFACTURER.
NEW SWIVELUNION.
NEW BALLVALVE, TYP.
NEW PRESSURE ANDTEMP. TAP, TYP.
NEW 2-WAYCONTROL VALVE
W/ AUTOMATICFLOW CONTROL
PROVIDE MANUAL AIRVENT IF NOT PRESENT
NEW CONTROLS WITH24V DAMPERACTUATOR
NEWY-STRAINER
EXISTING TERMINALUNIT
EXISTING EXISTINGDUCT DUCT
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
MECHANICALDIAGRAMS
M5-01
GRILLE, REGISTER, DIFFUSER & LOUVER
SYMBOL TYPE PATTERN FINISH MANUFACTURER*& MODEL # ACCESSORIES REMARKS
SUPPLY 4-WAY WHITE KRUEGER PRISM LAY- IN CEILING 24x24
SUPPLY 4-WAY WHITE KRUEGER PRISM HARD CEILING 24x24
RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 LAY-IN CEILING 24x24
RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 LAY-IN CEILING 24x12
RETURN/ EXHAUST EGG CRATE WHITE KRUEGER EGC5 HARD CEILING 12x12
RETURN/EXHAUST EGG CRATE WHITE KRUEGER EGC5 HARD CEILING 24x24
EXHAUST SIDE WALL WHITE KRUEGER 1500 OBDSEE PLANS FOR SIZES
15° DEFLECTION 7/32" BARSw/ 1/2" BAR SPACING
MANUFACTURERS:GRD PRICE, TITUS
LOUVER GREENHECK, L&D, RUSKIN
GENERAL NOTES:A:
B:
A
B
C
D
E
F
G
GRILL ANDDIFFUSERNECK SIZESCHEDULE
CFM ROUND NECKSIZE
90-130 6
131-220 8
201-330 10
331-440 12
441-540 14
541-650 15
EXHAUST FAN SCHEDULE
MARK SERVICE TYPE
FAN MOTORSOUND DATA
MANUFACTURER*& MODEL #
WEIGHT(LBS.) ACCESSORIES REMARKS
CFM
ESP
BHP HP VOLT/PHASE
IN WC 63 Hz 125 Hz 250 Hz 5000 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
EF-1 LOCKERS DOWNBLAST 100 0.35 0.02 1/4 115/1 76 76 72 66 57 56 52 46 GREENHECK G-097-VG 150 24" ROOF CURB -
EF-2 TRIAGE UTILITY SET 350 0.5 0.09 1 / 4 115 / 1 77 78 70 68 64 59 51 42 GREENHECK SWD-7-VG 150ECM MOTOR
CONTROL DIAL FORBALANCING
MANUFACTURERS: * COOK, GREENHECK
GENERAL NOTES:A:B:C:
AHU-2 TERMINAL BOX SCHEDULE
MARK LOCATION/TYPE
INLET DIA.(IN.)
MAX.COOLING
CFM
MIN.COOLING
CFM
MAX.HEATING
CFM
MAX PD (IN.W.C.)
DISCH. N.C.@ 1.0" S.P.
RADIATEDN.C. @ 1.0"
S.P.
HEATING COILMANUFACTURER* &
MODEL # ACCESSORIES REMARKSE.A.T.DB (°F)
L.A.T.DB (°F)
SENSIBLEMBH
E.W.T.(°F)
L.W.T.(°F) GPM PIPE SIZE
MAX.WATER P.D.
(FT.)
NUMBEROF ROWS
TU-18 EXAMROOMS 12 370 370 370 0.35 24 24 55 95 13.2 180 140 1.3 3/4 5 2 EXISTING -
TU-19 NURSE 8 900 900 900 0.35 24 24 55 95 32.1 180 140 3.2 3/4 5 2 EXISTING -
TU-20 TREATMENT 16 900 900 900 0.35 24 24 55 95 32.1 180 160 3.2 3/4 5 2 EXISTING -
TU-21 X-RAY 14 1410 1410 1410 0.35 24 24 55 95 50.3 180 160 5.0 1 5 2 EXISTING -
TU-22 CORRIDOR 8 620 620 620 0.35 24 24 55 95 22.0 180 160 2.2 3/4 5 2 EXISTNG
TU-23 STORAGE 6 615 615 615 0.35 24 24 55 95 22.0 180 160 2.2 3/4 5 2 EXISTNG
TU-24 PSYCH 6 125 125 125 0.35 24 24 55 95 4.5 180 160 0.5 3/4 5 2 EXISTNG
TU-25 TRAUMA 10 1160 1160 1160 0.35 24 24 55 95 41.4 180 160 4.1 1 5 2 EXISTNG
TU-26 TRAUMA 10 1160 1160 1160 0.35 24 24 55 95 41.4 180 160 4.1 1 5 2 EXISTNG
TU-27 ELEV EQUIP 8 415 415 415 0.35 24 24 55 95 14.8 180 160 1.5 3/4 5 2 EXISTNG
TU-28 ELEV LOBBY 8 275 275 275 0.35 24 24 55 95 9.9 180 160 0.9 3/4 5 2 EXISTNG
TU-29 MULTIPATIENT 8 800 800 800 0.35 24 24 55 95 28.6 180 160 2.8 3/4 5 2 EXISTNG
TU-30 WAITING 12 1300 1300 1300 0.35 24 24 55 95 46.4 180 160 4.6 1 5 2 EXISTNG
MANUFACTURERS: * ENVIROTEC, KRUEGER, TITUS
GENERAL NOTES:A: PROVIDE 120V/24V TRANSFORMER FOR NEW DDC CONTROLSB:
AHU-1 TERMINAL BOX SCHEDULE
MARK LOCATION/TYPE
INLET DIA.(IN.)
MAX.COOLING
CFM
MIN.COOLING
CFM
MAX.HEATING
CFM
MAX PD (IN.W.C.)
DISCH. N.C.@ 1.0" S.P.
RADIATEDN.C. @ 1.0"
S.P.
HEATING COILMANUFACTURER* &
MODEL # ACCESSORIES REMARKSE.A.T.DB (°F)
L.A.T.DB (°F)
SENSIBLEMBH
E.W.T.(°F)
L.W.T.(°F) GPM PIPE SIZE
MAX.WATER P.D.
(FT.)
NUMBEROF ROWS
TU-1 RESTROOM/CORRIDOR 12 1200 600 600 0.35 24 24 55 95 37.5 180 140 2.1 3/4 5 2 EXISTING -
TU-2 VESTIBULE 8 420 420 420 0.35 24 24 55 95 15.1 180 140 1.5 3/4 5 2 EXISTING -
TU-3 WAITING 16 1150 1150 1150 0.35 24 24 55 95 41.0 180 160 4.1 1 5 2 EXISTING -
TU-4 WAITING 14 750 750 750 0.35 24 24 55 95 26.8 180 160 2.7 3/4 5 2 EXISTING -
TU-5 TRIAGE 8 275 275 275 0.35 24 24 55 95 9.9 180 160 1.0 3/4 5 2 EXISTNG
TU-6 FAST TRACK 6 250 250 250 0.35 24 24 55 95 9.0 180 160 0.9 3/4 5 2 EXISTNG
TU-7 FAST TRACK 6 370 370 370 0.35 24 24 55 95 13.2 180 160 1.3 3/4 5 2 EXISTNG
TU-8 FAST TRACK 10 1000 1000 1000 0.35 24 24 55 95 35.7 180 160 3.6 1 5 2 EXISTNG
TU-9 EXAMROOMS 10 1060 1060 1060 0.35 24 24 55 95 37.8 180 160 3.8 1 5 2 EXISTNG
TU-10 SOILEDUTILITY 8 350 350 350 0.35 24 24 55 95 12.5 180 160 1.3 3/4 5 2 EXISTNG
TU-11 EXAMROOMS 8 480 480 480 0.35 24 24 55 95 17.2 180 160 1.7 v 5 2 EXISTNG
TU-12 EXAMROOMS 8 480 480 480 0.35 24 24 55 95 17.2 180 160 1.7 1 5 2 EXISTNG
TU-13 NOURISH 12 650 650 650 0.35 24 24 55 95 23.2 180 160 2.3 3/4 5 2 EXISTNG
TU-14 NURSE 10 1045 1045 1045 0.35 24 24 55 95 37.3 180 160 3.7 1 5 2 EXISTNG
TU-15 EXAMROOMS 6 170 170 170 0.35 24 24 55 95 6.1 180 160 0.6 3/4 5 2 EXISTNG
TU-16 EXAMROOMS 8 410 410 410 0.35 24 24 55 95 14.7 180 160 1.5 3/4 5 2 EXISTNG
TU-17 ISOLATION 8 500 500 500 0.35 24 24 55 95 17.9 1.8 3/4 5 2 EXISTNG
MANUFACTURERS: * ENVIROTEC, KRUEGER, TITUS
GENERAL NOTES:A: PROVIDE 120V/24V TRANSFORMER FOR NEW DDC CONTROLSB:
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
MECHANICALSCHEDULES
M6-01
PRESSURE REDUCING VALVE
SHOCK ABSORBER
STRAINER W/ BLOW-OFF VALVE
SAFETY RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE W/ PIG TAIL & COCK
THERMOMETER
PRESSURE - TEMP. TAP
AIR VENT
PIPE ANCHOR
FLEXIBLE CONNECTOR
PIPE EXPANSION JOINT
PIPE UNION
DOUBLE CHECK BACKFLOW PREVENTER
PUMP & EQUIPMENT CONNECTOR
TEMPERATURE CONTROL VALVE (2-WAY)
DRAIN VALVE W/ HOSE END
PLUG VALVE IN RISER
FLOW BALANCING VALVE
GATE OR GLOBE VALVE IN RISER
FLOW CONTROL VALVE
BALL VALVE
PLUG OR BALANCING VALVE
CHECK VALVE
GLOBE VALVE
BUTTERFLY VALVE
VENTURI/FLOW INDICATOR
TEMPERATURE CONTROL VALVE (3-WAY)
SOLENOID VALVE
90° ELBOW UP
TEE UP
TEE DOWN
SHUT OFF (BALL, GATE, BUTTERFLY)
PIPING SYMBOLS90° ELBOW DN
S
DUCT/PIPE RISER DESIGNATION KEY
CHDWHWGW VPRSTS2
FLOW SWITCH
HOSE BIBB
WALL HYDRANT
TEMPERATURE CONTROLLER OR SENSOR
STEAM TRAP TEST CHAMBER
STEAM TRAP:FT-FLOAT & THERMOSTATICTD-THERMODYNAMICIB-INVERTED BUCKETTS-THERMOSTATICBP-BALANCED PRESSURE
BAR SINKBS 1/2" 1/2" 1-1/2"1-1/2"
FIXTURE CONNECTION SCHEDULEHW CW WASTE VENT
NOTES:
1. SIZES SHOWN ARE MINIMUM PIPE SIZES TO A SINGLE FIXTURE. LARGERSIZES MAY BE INDICATED ON PLANS WHERE REQUIRED.
2. MINIMUM DOMESTIC PIPE SIZE TO (2) OR MORE FIXTURES IS 3/4".
3. RE: MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR INDIRECT WASTESIZES.
4. WASTE AND VENT SIZES SHOWN ABOVE APPLY TO INDIVIDUAL VENTING ONLY.WHERE ALLOWED, INDIVIDUAL VENT CONNECTIONS MAY BE OMITTED ORSIZES MAY VARY WHEN CIRCUIT VENTS, COMMON VENTS, WASTE STACKVENTS, WET VENTS, OR COMBINATION DRAIN AND VENT SYSTEMS ARE USED.PRIOR APPROVAL FROM THE ENGINEER IS REQUIRED TO USE THESEALTERNATIVE VENTING METHODS.
5. PROVIDE TRAP GUARD FOR ALL FLOOR DRAINS AND FLOOR SINKS NOTLOCATED IN FOOD SERVICE AREAS.
6. MINIMUM SIZE FOR WASTE AND VENT PIPING BENEATH SLAB IS 2".
7. ALL FIXTURES LISTED ARE NOT NECESSARILY USED ON THIS PROJECT.
8. REFER TO APPLIANCE SCHEDULES (BY OTHERS) FOR ADDITIONAL PLUMBINGFIXTURE CONNECTIONS SUCH AS INST-HOTS, COFFEE MAKERS, ANDGARBAGE DISPOSALS.
9. PROVIDE ICE MAKER BOX ROUGH IN W/ 1/2"CW CONNECTION FOR ALLREFRIGERATOR LOCATIONS.
ABBREV.
CS CLOTHES WASHER ROUGH-IN 1/2" 1/2" 2" 1-1/2"
DRINKING FOUNTAIN / E.W.C.DF - 1/2" 1-1/2" 1-1/2"
DISH MACHINE ROUGH-INDM 3/4" 3/4" 2" 1-1/2"
DW DISHWASHER ROUGH-IN -1/2" 2" 1-1/2"
FD FLOOR DRAIN - - 2" 1-1/2"
FS FLOOR SINK - - 3" 2"
HOSE BIBHB - - -3/4"
HAND SINKHS 1-1/2" 1-1/2"1/2" 1/2"
KITCHEN SINK W/ OR W/O DISPOSERKS 1/2" 1/2" 2" 1-1/2"
LAVATORYLAV 1/2" 1-1/2" 1-1/2"1/2"
MOP SERVICE BASINMSB 3/4" 3" 2"3/4"
SHOWER / BATHTUBSH 3/4" 3/4" 2" 1-1/2"
SERVICE SINKSS 3" 2"1/2" 1/2"
TROUGH DRAINTD - - 3" 2"
URINAL (BLOWOUT)UR 1" 2" 1-1/2"-
URINAL (WASHDOWN)UR
UR URINAL (WATERLESS)
3/4" 2" 1-1/2"
- 2" 1-1/2"
-
-
WATER CLOSET (FLUSH VALVE)WC
WATER CLOSET (FLUSH TANK)WCT
- 1" 4" 2"
- 1/2" 4" 2"
WS 3/4"3/4" 2" 1-1/2"WORK SINK
EQUIPMENT ABBREVIATIONSAIR HANDLING UNITAHU
AIR SEPARATORAS
BOILER (HOT WATER)B
BASE BOARDBB
BUFFER TANKBT
CONSTANT VOLUME BOXCV
DISHWASHER EXHAUST FANDEF
ELECTRIC BASEBOARD HEATEREBH
FURNACEF
FAN COILFC
FAN POWERED BOXFP
GLYCOL FEEDERGF
HUMIDIFIER
HC HEATING COIL
HP HEAT PUMP
HX HEAT EXCHANGER
KITCHEN EXHAUST FANKEF
MAKE-UP AIR UNITMAU
MOTOR CONTROL CENTERMCC
MIXING VALVEMV
PUMP P
RETURN (OR RELIEF) AIR FANRF
RADIANT ZONERZ
SNOWMELT AREASA
SUMP BASINSB
SUPPLY FANSF
STORAGE TANKST
THERMOSTATIC MIXING VALVETMV
UNIT HEATERUH
VARIABLE VOLUME BOXVV
WATER HEATERWH
H
CHILLERCH
COOLING COILCC
CIRC PUMPCP
CABINET UNIT HEATERCUH
COOLING TOWERCT
DUCT COILDC
ELECTRIC WATER HEATEREWH
EVAPORATIVE COOLING UNITECU
ENERGY RECOVERY UNITERU
EXHAUST FANEF
EXPANSION TANKET
VARIABLE VOLUME BOX W/ REHEATVR
TYPE OF AIR DEVICERE: GRD SCHEDULE.
AIR DEVICE DESIGNATION KEY
#CAEXHOSARAXFR
SIZE (INCHES) OR MINIMUMFREE AREA REQUIRED INSQUARE FEET.
NOTE:FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN ISNECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE.
INDICATES AIRINLET DEVICE.
======
AIR QUANTITY (CFM)COMBUSTION AIREXHAUSTOUTSIDE AIRRETURNTRANSFER
BXFR12x6
A15012x6
REFERENCE SAMPLE
FFI = FOR FURTHER INFORMATIONFCT = FOR CONTINUATION
RE: B/M400 FFI
REFER TO:
DRAWING NUMBER ORDIAGRAM LETTER
SHEET NUMBER
PLAN ABBREVIATIONS
ABOVE FINISHED FLOOR
AIR ADMITTANCE VALVE
ABOVE FINISHED GRADE
AUTOMATIC
BUILDING CONTROL SYSTEM
BACK DRAFT DAMPER
BUILDING
AAV
AFF
AFG
AUTO
BCS
BDD
BLDG
BETWEEN
COMMON (OR CLOSED)
COMBUSTION AIR
CONTROLS CONTRACTOR
CONTINUATION DESIGN BUILD
B/N
C
CA
CC
CDBBC
CUBIC FEET PER MINUTE (AIR FLOW RATE)
CAST IN PLACE
CEILING (OR COOLING)
CONCRETE
CONDENSATE
CONNECT (OR CONNECTION)
CONTRACTOR
CFM
CIP
CLG
CONC
COND
CONN
CONTR'R
CLEANOUT TO GRADECOTG
DOMESTIC HOT WATER RECIRC
EXISTING
DWR
(E)
EXHAUST AIREA
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING WATER TEMPERATURE
EAT
EC
EXH EXHAUST
EWT
GENERAL CONTRACTOR
GROUND HEAT EXCHANGER
GC
GHX
GALLONS PER MINUTE (WATER FLOW RATE)GPM
HORSEPOWER
HOT WATER
IN LIEU OF
HP
HW
ILO
KILOWATTSKW
LEAVING AIR TEMPERATURE
LINEAR FOOT
LEAVING WATER TEMPERATURE
LAT
LF
LWT
MECHANICAL CONTRACTORMC
MANUFACTURER
MOTOR OPERATED DAMPER
NEW
MFG
MOD
(N)
NORMALLY CLOSEDNC
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NORMALLY OPEN
NEC
NIC
NO
OUTSIDE AIROA
OPPOSED BLADE VOLUME DAMPER
ON CENTER
OBD
OC
OUTSIDE AIROSA
RETURN AIR
REQUIRED
RA
REQ'D
REQUIREMENTSREQ'MTS
SUPPLY AIR
SQUARE FOOT (FEET)
SA
SF
STATIC PRESSURESP
STAINLESS STEEL
THROW-AWAY (TRANSFER AIR)
TYPICAL
SS
TA
TYP
UNLESS NOTED OTHERWISEUNO
WALL CLEANOUTWCO
WITH REGARD TO
WATER COOLED
TRANSFER
WRT
W/C
XFR
DIAMETERØ
BY CONTRACTOR
COLD WATERCW
HOT WATER RECIRCHWC
ABOVEABV
BELOW FINISHED GRADEBFG
DOMESTIC WATER
DOMESTIC HOT WATER
DW
DHW
DOWNDN
DOMESTIC HOT WATER RECIRCDHR
COMBINATION FIRE/SMOKE DAMPER
FURNISHED BY OWNER
FSD
FBO
FLOOR CLEANOUTFCO
FOR CONTINUATIONFCT
FD FIRE DAMPER
REFER TO:RE:
WITHW/
CLEANOUTCO
FUTURE(F)
FREE AREAFA
FFI FOR FURTHER INFORMATION
WITHOUTW/O
VENT THRU ROOFVTR
NOTES1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ONTHIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, INPART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES ANDNOTATION CONVENTIONS OCCURRING IN THISDRAWING SET ARE NECESSARILY DEFINED ON THESELEGENDS. CONSULT THE ENGINEER IN THE EVENTSYMBOLOGY OR NOTATION INTERPRETATION ISREQUIRED.
EAOARASA
RISER NUMBER
--------
----
CHILLED WATERDOMESTIC WATERHEATING WATERGASWASTE AND/OR VENTPIPING RISER (MISC TYPES)STORM DRAINSECONDARY STORM DRAIN
EXHAUST AIROUTSIDE AIRRETURN AIRSUPPLY AIR
AIR SIDE:
PIPING SIDE:
PLAN SYMBOLSCONTROL PANEL/RADIANT MANIFOLD
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DIAGRAM CONTINUATION REFERENCE
PLUMBING/HVAC RISER
POINT OF NEW CONNECTION
DUCT STATIC PRESSURE SENSOR
ROOM PRESSURE SENSOR
EMERGENCY POWER OFF SWITCH
ACCESS PANEL
SNOWMELT MANIFOLD
SECTION CUT LETTER/SHEET SHOWN ON
POINT OF DISCONNECTION
-
SP
CO2
EPO
P
CO
--
-P
THERMOSTAT
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
T
S
H
H B
W H
TC
FS
ROOF DRAIN
FLOOR DRAIN
FLOOR SINK
HORIZONTAL CLEANOUT
VERTICAL CLEANOUT
DECK/ROOF DRAIN ABOVE
PIPING DESIGNATIONS
SNOWMELT SUPPLY
SNOWMELT RETURN
HEATING WATER SUPPLY (HIGH TEMP)
HEATING WATER RETURN (HIGH TEMP)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER RETURN
NATURAL GAS
MEDIUM PRESSURE GAS
HIGH PRESSURE STEAM
HIGH PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE RETURN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DOMESTIC WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. SHOWN)
DHW RECIRCULATION
FIRE LINE
PRESSURIZED WASTE
PLUMBING VENT PIPE
WASTE PIPE
ACID WASTE PIPE
STORM DRAIN PIPE
STORM DRAIN OVERFLOW
COMPRESSED AIR PIPE
GREASE WASTE PIPE
ACID VENT PIPE
LIQUID PROPANE GAS
SECONDARY DRAIN
SAND AND OIL WASTE
FLOOR COOLING SUPPLY
FLOOR COOLING RETURN
PROPANE GAS
HEATING WATER SUPPLY (LOW TEMP)
HEATING WATER RETURN (LOW TEMP)
SOLAR HEATING WATER SUPPLY
SOLAR HEATING WATER RETURN
GROUND LOOP SUPPLY
GROUND LOOP RETURN
GROUND WATER SUPPLY
GROUND WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
DRAIN PIPE
FUEL OIL SUPPLY
FUEL OIL RETURN
GLYCOL FEED
GREASE VENT
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
FUEL OIL VENT
FUEL OIL FILL
PUMPED CONDENSATE
GEOTHERMAL (OR GROUND) LOOP SUPPLY
GEOTHERMAL (OR GROUND) LOOP RETURN
CLOSED CONDENSER SUPPLY
CLOSED CONDENSER RETURN
PROPANE DRAIN
CONDENSER SUPPLY
PLUMBING PIPING
NON-SOFTENED DOMESTIC WATER
CR
CS
CCR
CCS
GLR
GLS
CHR
CHS
GLR
GLS
GF
HWR
HWS
HWR(LT)
HWS(LT)
HWR(HT)
HWS(HT)
FCR
FCS
SHWR
SHWS
SMS
SMR
PC
MPR
MPS
LPS
LPR
HPR
HPS
PD
D
PG
LPG
MG
G
RS
RL
FOF
FOV
FOR
FOS
GWR
GWS
CW
HW
HWC
NS
140° HW
GV
SO
SD
ST
GW
AW
AV
V
W
PW
ST(OF)
F
CA
SOLID DRAIN PIPEDS
STEAM & CONDENSATE PIPING
HYDRONIC PIPING
SUMP PUMPSP
PR203
PLUMBING SYSTEMS LEGEND
ABOVE SEA LEVEL
PROJECT ALTITUDE5,292'
' 'ISSUE LOG KEY:
#
DA
TE
ISSUE LOG
PLUMBING SHEET INDEX
TITLE
PLUMBING COVER SHEETP0-01
100%
DD
02.2
2.20
18ISSUED AS PART OF A SET' ' NOT PART OF SET' ' ISSUED FOR INFORMATION ONLY*
√√
√
√
√
√
PLUMBING SPECIFICATION NOTES SHEETP0-02
PLUMBING DEMOLITION PLANPD1-01
PLUMBING PLANP1-01
PLUMBING DIAGRAMS SHEETP5-01
√PLUMBING MEDICAL GAS DEMOLITION PLANPD1-02
√PLUMBING SCHEDULESP6-01
√PLUMBING MEDICAL GAS PLANP1-02
1. NOT ALL REQUIRED CLEANOUTS ARE NECESSARILY SHOWN ON THESE PLANS. PROVIDE CLEANOUTS ON WASTE,VENT AND STORM PIPING AS REQUIRED BY CODE AND FOR REASONABLE MAINTENANCE BASED ON ACTUAL FIELDINSTALLATION. COORDINATE LOCATIONS WITH ARCHITECT/ENGINEER.
2. COORDINATE ROUTING OF CONDENSATE DRAIN LINES WITH ARCHITECT PRIOR TO INSTALLATION.
3. PIPING ON EXTERIOR WALLS OR PRE-CAST CONCRETE WALLS TO BE ROUTED IN FRAMED WALL ON INTERIOR SIDEOF INSULATION.
4. INSTALL THERMOSTATIC MIXING VALVES, ASSE 1070 LISTED, AT EACH PUBLIC HANDWASHING LAVATORY/SINK.SIZE TO MATCH HW PIPE SIZE.
5. TERMINATE PLUMBING VENTS NOT LESS THAN 12" ABOVE ROOF.
6. DO NOT ROUTE PIPING OVER ELECTRICAL ROOMS OR ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH DIV. 16 CONTRACTOR.
7. CONTRACTOR TO MAINTAIN 8'-6" CLEAR HEAD HEIGHT IN GARAGE AND INFORM THE ENGINEER AND ARCHITECT OFANY AREAS THAT MAY NOT MEET 8'-6" PRIOR TO INSTALLATION, MINIMUM 8'-2" CLEAR HEAD HEIGHT MUST BEMAINTAINED IN ACCESSIBLE VEHICLE AREAS.
8. PROVIDE FLEXIBLE PIPE CONNECTIONS TO ALL MOTORIZED EQUIPMENT.
9. ROUTE DOMESTIC HOT WATER RECIRC TO WITHIN 10 FEET OF ALL HOT WATER FIXTURES. CONNECT WITHIN 3FEET OF 0.5 GPM AND LOWER FAUCETS.
10. VERIFY ALL EQUIPMENT ACCESS PANELS WITH MANUFACTURER AND ARCHITECT.
11. PROTECT PIPING ROUTED ALONG COLUMNS, WALLS, ETC. FROM DAMAGE AS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.
12. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATE FIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.
13. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESSPANELS IN HARD-LID CEILINGS.
14. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN THE CEILING SPACE. UTILIZE JOIST SPACE WHENPOSSIBLE, ESPECIALLY WHERE CROSSING OTHER PIPES, DUCTS, AND ELECTRICAL.
15. ACCESS PANELS SHALL BE 24x24, U.N.O. LOCATIONS SHOWN ARE APPROXIMATE, EXACT LOCATIONS SHALL BECOORDINATED WITH THE ARCHITECTS DRAWINGS AND WITH THE LOCATIONS OF THE EQUIPMENT OR APPARATUSTHAT THEY SERVE.
16. SEAL ALL PIPING PENETRATIONS THROUGH ACOUSTIC PARTITIONS.
17. EXPOSED SOIL OR WASTE PIPING SHALL NOT BE INSTALLED ABOVE ANY WORKING, STORAGE, OR EATINGSURFACES IN FOOD SERVICE ESTABLISHMENTS.
GENERAL NOTES:
√ENLARGED PLUMBING PLANP4-01
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGCOVER SHEET
P0-01
GENERAL SPECIFICATIONS:
1. CONTROLS SYSTEM COMPONENTS SHALL BE COMPATIBLE WITH EXISTING BUILDING AUTOMATION SYSTEM (AUTOMATED LOGIC). CONTROLS SHALL BEFIELD INSTALLED. CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING AND INSTALLING ALL DEVICES REQUIRED FOR A FULLY FUNCTIONALCONTROL SYSTEM FOR THIS PROJECT, REGARDLESS OF VOLTAGE. IF THE CONTRACTOR CANNOT SELF PERFORM WORK REQUIRING LINE VOLTAGE THENTHE CONTRACTOR SHALL COORDINATE WITH AND COMPENSATE THE ELECTRICAL CONTRACTOR AS REQUIRED. CONTROLS CONTRACTOR SHALLCOORDINATE WITH EQUIPMENT SUPPLIERS TO ENSURE THAT ALL DEVICES ARE COMPATIBLE WITH THE EXISTING CONTROLS SYSTEM AND EXISTINGMECHANICAL EQUIPMENT. CONTROLS CONTRACTOR SHALL PROVIDE READ-ONLY ACCESS TO THE BAS VIA THE INTERNET FOR A PERIOD OF ONE YEAR TOASSIST WITH TROUBLESHOOTING ANY ISSUES RELATED TO THE HVAC SYSTEM IN THE AREA OF THIS PROJECT.
2. CONTROLS CONTRACTOR SHALL ALSO HAVE IN HIS BID AS A LINE ITEM FOR THE POTENTIAL NEED FOR THE TIME AND RESOURCES REQUIRED TO ASSISTTHE COMMISSIONING AGENT IN THE COMMISSIONING OF THE MECHANICAL AND ELECTRICAL SYSTEMS ASSOCIATED WITH THE TENANT FINISH WORKUTILIZING A WEB BASED COMMISSIONING PROCESS. WORK SHALL INCLUDE BUT NOT LIMITED TO: ATTENDING COMMISSIONING SCOPE MEETING,PERFORMING AND DOCUMENTING PRE-FUNCTIONAL CHECK LISTS, PROVIDING ASSISTANCE IN THE FUNCTIONAL TESTING OF EQUIPMENT AND PROVIDINGTOOLS REQUIRED TO PERFORM FUNCTIONAL TESTING.
3. ALL CONTROL WIRING TO BE INSTALLED IN PLENUM RATED CONDUIT.
4. NO NETWORKED CONTROL POINTS ARE ALLOWED. ALL SENSORS TO BE HARDWIRED DIRECTLY TO CONTROLLING MODULE.
CONTROLS SYSTEM NOTES
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS.
2. ALL SUBCONTRACTORS SHALL BE LICENSED, EXPERIENCED, AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE CONSTRUCTION INDUSTRYAND SHALL PERFORM IN A RESPONSIBLE MANNER WITH ESTABLISHED CONSTRUCTION SEQUENCE, SHALL RECOGNIZE THE PRIORITY OF THE CONSTRUCTIONDOCUMENTS, AND SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN THE CONSTRUCTION DOCUMENTS ARE UNCLEAR OR INCONSISTENT.
3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME CONTRACTOR OF DISCREPANCIES OR CONFLICTS IN THE CONSTRUCTION DOCUMENTS FOUNDDURING BIDDING AND/OR PRIOR TO PERFORMING THE WORK.
4. EXAMINATION OF BIDDING DOCUMENTS.
A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN (7) DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALLMAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORSTHEREIN WHICH HE MAY DISCOVER (REFER TO ARCHITECTURAL REQUIREMENTS). THE ARCHITECT WILL ISSUE ANY INTERPRETATION OR CORRECTION AS ANADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS ORCORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM ORWRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN THEIR BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTERAWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO THEIR FAILURE TO MAKE THEWRITTEN REQUESTS AS DESCRIBED ABOVE.
B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIRRESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGHCOMPREHENSION OF THE FULL INTENT AND SCOPE OF THE CONSTRUCTION CONTRACT DRAWINGS AND SPECIFICATIONS.
5. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE LISTEDEQUIPMENT SHALL BE ALLOWED IN THE BASE BID.
A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED ARECONSIDERED GENERAL EQUIVALENTS ONLY.
B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS: WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERALEQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL ANDOTHER WORK.
1) PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND PROPERLYFITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF DESIGN.
2) PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF DESIGN PLUS ANY SPECIFIED OPTIONS.
3) BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT, FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR SUBSTITUTIONSDO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE DESIGN.
6. INASMUCH AS DESIGN FOR REMODEL AND/OR REHABILITATION REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, ANDBECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THEENGINEER CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES HEREIN ENCOMPASS ALL CONTINGENCIES.FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR UNSEEN CONDITIONS.
7. THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE HINDERED BY THISWORK. ACCOUNT FOR ALL ADDITIONAL COSTS WHICH MAY BE INCURRED DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, FURNITURE,EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN AREA MAY BE ACCESSIBLE WHEN COMPILING HIS BID.
8. BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR DUCTWORK REMAINING TO BE CONNECTED TO NEW OR EXISTING SYSTEMS. PROVIDE DUCTWORK,PIPING, CONTROLS, DIFFUSERS, ETC., AS REQUIRED TO RESTORE CONTINUITY OF SYSTEMS, OR TO MAKE NEW WORK MEET EXISTING CONDITIONS, WHETHERINDICATED OR NOT.
9. SUBCONTRACTOR SHALL VERIFY EXISTENCE AND LOCATION OF ALL UTILITY SERVICES AND COORDINATE AS REQUIRED BY THEIR RESPECTIVE AREA OF THECONSTRUCTION, NOTIFYING THE PRIME CONTRACTOR OF VARIATIONS OR CONFLICTS.
10. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS, MATERIALS AND/OR EQUIPMENT SHALL BE IDENTIFIED BY THE SUBCONTRACTOR WITHSUFFICIENT TIME TO ALLOW SELECTION, PURCHASE, AND DELIVERY TO MAINTAIN CONSTRUCTION SCHEDULE.
11. PROVIDE MECHANICAL DEMOLITION AS REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED.VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. EXISTING FIXTURES, MECHANICAL EQUIPMENT, ETC., BEING REMOVED SHALL BE RETURNEDTO THE OWNER. DISPOSE OF ALL REMOVED PIPING, DUCTWORK, ETC. UNLESS NOTED OTHERWISE. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARESHOWN HATCHED, UNLESS OTHERWISE NOTED.
12. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND UTILITIES, PIPING, AND RACEWAY SYSTEMS IN CEILING SPACES ABOVE AND BELOW SPACE.
13. ALL DUCTWORK, DIFFUSERS, PIPING, FIXTURES, AND EQUIPMENT SHOWN IN LIGHT DASHED LINE WEIGHT IS EXISTING, NEW INDICATED BY HEAVIER LINE WEIGHT,EXCEPT WHERE NOTED. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED.
14. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE STRUCTURE, BEAMS, AND COLUMNS, AND EXISTING EQUIPMENT.
15. ALL EXISTING SUPPORT RODS AND STRAPS NOW SUPPORTING DUCTS, PIPES, AIR TUBING, ELECTRICAL CONDUIT, ETC. THAT ARE REMOVED TO ALLOW ROOM FORINSTALLATION OF NEW EQUIPMENT SHALL BE RELOCATED AND REINSTALLED, OR REPLACED IF DAMAGED.
16. ALL “CAPPED” SANITARY AND VENT LINES SHALL BE RECONNECTED OR RE-ROUTED AS NECESSARY TO PREVENT “DEAD-ENDS” IN THE PIPING. ALL PIPING SHALLDRAIN TO ACTIVE SANITARY WASTE LINES AND ALL BRANCHES WITH TRAPS SHALL BE ADEQUATELY VENTED.
17. CAP ALL DEMOLISHED AND ABANDONED DUCT TAKE-OFFS AT TRUNK DUCT.
18. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT, OWNER, AND ENGINEER.
19. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS/HER WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE SAFETY FEATURESAS REQUIRED BY LOCAL, STATE, OR NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF MODIFICATION OF HIS/HER WORK ISREQUIRED FOR COMPLIANCE.
20. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE ADOPTED NEW MEXICOSTATE CODES INCLUDING THE INTERNATIONAL BUILDING CODE, UNIFORM MECHANICAL AND PLUMBING CODES, FIRE AND ELECTRICAL CODES, MOST CURRENTNFPA, THE 2010 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES, ALL LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'SINSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS EXISTS, THE MOST STRINGENT REQUIREMENT SHALL APPLY.
21. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF COMPLETION.
22. WARRANTY THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP. THE WARRANTY SHALL BE FOR A PERIOD OF ONE YEAR AFTER OWNER'SACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
23. SUBMIT RECORD DOCUMENTS TO ARCHITECT. DOCUMENTS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC.
24. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER.
25. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE DEFECTIVE,CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO ADDITIONAL COST TO OWNER.
26. ALL MATERIALS AND/OR EQUIPMENT SHALL BE HANDLED AND INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
27. SUBMIT ALL MECHANICAL DIVISION SHOP DRAWING AND PRODUCT DATA AT ONE TIME. SUBMITTAL SHALL BE BOUND AND INDEXED IN A NEAT AND ORDERLYMANNER. PARTIAL SUBMITTALS WILL BE REJECTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, FIXTURES, INSULATION, DIFFUSERS,PUMPS, PIPING, VALVES, CONTROLS, AND FIRE PROTECTION.
28. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS,EQUIPMENT, OR INSTALLATION METHODS.
29. PROVIDE NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS, SAWCUTTING AND PATCHING, CONCRETE/PAVING, ETC., AS REQUIRED. PATCH TO MATCHEXISTING FLOOR LEVEL.
30. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE ORFUNCTION.
31. TEMPORARY HEAT SHALL BE FURNISHED BY THE GENERAL CONTRACTOR. USE OF THE PERMANENT HEATING SYSTEM WILL NOT BE ALLOWED.
32. COORDINATE ALL PENETRATIONS OF THE FLOOR SLAB PRIOR TO COMMENCING WORK. UTILIZE X-RAY AND VISUAL INVESTIGATION OF EXISTING CONDITIONS ASREQUIRED PRIOR TO DRILLING OR CUTTING. COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE WORK. ALL CONTRACTORS ARE INDIVIDUALLYRESPONSIBLE FOR ALL PENETRATIONS REQUIRED BY THEIR DIVISIONS.
33. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THEPASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ACCEPTABLEMATERIALS INCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE,METAL CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP-25 CAULK AND FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, ANDELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF PENETRATION ENCOUNTERED.
34. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE ARCHITECTURALDRAWINGS. IN THE ABSENCE OF ANY OTHER REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS IN BUILT-UP ROOFS, TALL CONE WITHEPDM BOOT FOR PIPE AND CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BEWATERTIGHT.
35. ALL FLOOR DRAINS CONNECTED TO THE SEWER SYSTEM SHALL BE EQUIPPED WITH TRAP PRIMERS OR TRAP GUARDS. PROVIDE TRAP PRIMERS WITH BACKFLOWPREVENTERS AND CONNECT TO THE NEAREST COLD WATER PIPING ADJACENT TO A FLUSHING FIXTURE. PROVIDE ELECTRONIC TRAP PRIMERS FOR ANY AREASWHERE THE NEAREST ADJACENT FLUSHING FIXTURES ARE NOT WITHIN A REASONABLE DISTANCE OR STRUCTURAL OBSTRUCTIONS PREVENT GRAVITY SLOPING OFTRAP PRIMER LINES. ADDED COST OF ELECTRIC POWER FOR ELECTRONIC TRAP PRIMERS SHALL BE BORNE BY PLUMBING CONTRACTOR. INSTALL ALL TRAPPRIMER VALVES AND ASSOCIATED SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
36. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING PENETRATIONS AND AIR DEVICE LOCATIONS.
37. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, ELECTRICAL, LANDSCAPING, AND INTERIOR DESIGN DRAWINGS PRIOR TOINSTALLATION.
38. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE.
39. MOUNT ALL STATS AT 48” A.F.F. IN “ACCESSIBLE” AREAS, 4'6” A.F.F. IN OTHER AREAS, UNLESS NOTED OTHERWISE (REFER TO ARCHITECTURAL). COORDINATELOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS (COORDINATE WITH ARCHITECH ANDOWNER). NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTAT INSTALLATION.
40. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN ACCORDANCE WITH NEBBOR AABC GUIDELINES FOR PROPORTIONAL BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW PRIOR TO BALANCING.MEASUREMENTS SHALL INCLUDE ALL MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC PRESSURE AT INLET AND OUTLET OF ALLPACKAGED EQUIPMENT, FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM
OUTSIDE AIR, AND 100% (ECONOMIZER) OUTSIDE AIR; VELOCITY DISTRIBUTION ACROSS THE FACE OF FILTERS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOWMEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE DROP, ANDPRESSURE DROP AT ALL COILS.
A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO ADJUST FAN SPEED.
B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE ROOM AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN BY ADIFFERENTIAL OF SUPPLY AND EXHAUST/RETURN OR BY NOTE, ADJUST SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST/RETURN TO PROVIDE THEINDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN 90%, INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. SUBMITTAL OFBALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT EXPLANATION IS CAUSE FOR REJECTION OF REPORT.
C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL BE RETAINEDBY THE OWNER, ARCHITECT, AND ENGINEER.
41. DUCTWORK:
A. FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASSINSULATION, HIGH-STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN REINFORCED “RIP STOP” ALUMINUM LAMINATE INTERIOR CORE, UL LISTED ANDLABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POS. 6”, NEC. 4”. FLEXMASTER TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINEEQUIVALENCE.
B. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS CLOTH, 10” W.C. RATED.
C. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5 GORE ELBOWS. “SNAP-LOCK”, LONGITUDINAL SEAM DUCT, OR ADJUSTABLE FITTINGS AREACCEPTABLE ON INDIVIDUAL GRILLE/DIFFUSER RUNOUTS ONLY.
D. INSULATION:
1) EXTERNALLY WRAP ALL RECTANGULAR AND ROUND SUPPLY AIR DUCTS WITH FLEXIBLE GLASS FIBER, ANSI/ASTM C612; 0.002 INCH FOIL SCRIM FACING.
E. DUCTWORK: G60 GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; CONSTRUCTED TO THE LATEST EDITION OF SMACNA “HVAC DUCT CONSTRUCTIONSTANDARDS”; +/- 1” W.C. PRESSURE CLASSIFICATION, SEAL CLASS “C”; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, STRAPS, ETC.
F. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH UNITED MCGILL “UNI-GRIP” UL LISTED, WATER BASED, NON-HARDENING, ELASTIC SEALANTOR EQUIVALENT. TAPE NOT ALLOWED.
42. PROVIDE ¼” GALVANIZED MESH SCREEN ON ALL COMBUSTION AIR DUCTS OR OPENINGS, AND ALL OPEN END RETURN AND EXHAUST DUCTS.
43. ALL DUCTWORK DIMENSIONS ARE FREE AREA DIMENSIONS.
44. DUCTWORK NOTES:
A. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE.
B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH.
1) WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT ELBOWS WITH SINGLE WIDTH (NON-AIRFOIL) TURNING VANES.
2) FOR DUCT DEPTHS OF 36” OR LESS, PROVIDE MANUFACTURED SINGLE WIDTH (NON-AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE WITHSMACNA DUCT CONSTRUCTION STANDARDS FOR “STANDARD SPACING”. USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36”. USE NOTRAILING EDGES.
C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED SIX FEET IN LENGTH.
D. RETURN AIR PLENUM: OTHER HVAC SYSTEMS IN THE PROJECT AREA USE THE SPACE ABOVE THE CEILING ON EACH FLOOR AS A RETURN AIR PLENUM.CONFORM TO THE REQUIREMENTS OF NFPA AND LOCAL CODE REQUIREMENTS FOR ALL MATERIAL INSTALLED IN THE RETURN AIR PLENUM.
E. PROVIDE A COMPLETE DUCTED RETURN AIR PATH BETWEEN ALL NEW AND MODIFIED RETURN AIR DEVICES (GRILLES ETC.) AND THEIR RESPECTIVE HVAC UNIT.
F. ALL BRANCH DUCTS TO DIFFUSERS/GRILLES TO BE PROVIDED WITH A BALANCING DAMPER.
45. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR CLAMPS. NO PIPE TAPE OR STRAPPING ALLOWED. ALL HANGERS SHALL BE SIZED FOR OD OFINSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET METAL SHIELDS FOR PIPING 1-1/2” AND LESS. PROVIDE CALCIUM SILICATE INSULATION INSERTSFOR ALL INSULATED PIPING 2” AND LARGER. MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE COPPER LINES FROM HANGERS WITH VIBRASORB OREQUIVALENT, COPPER COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT ACCEPTABLE.
46. NEW HOT AND COLD WATER BRANCHES TO BE ROUTED FROM NEAREST HOT WATER AND COLD WATER OF LINE SIZE EQUAL TO OR GREATER THAN NEWBRANCH--TYPICAL. EXISTING HOT AND COLD WATER BRANCHES TO BE REMOVED MUST BE CAPPED BACK AT MAINS, NO DEAD LEGS ALLOWED
47. PROVIDE LINE SIZE ISOLATION VALVES ON ALL BRANCH PIPING TO INDIVIDUAL ROOMS.
48. REFER TO PLUMBING FIXTURE CONNECTIONS SCHEDULE FOR PIPE SIZES TO INDIVIDUAL PLUMBING FIXTURES, UNLESS NOTED OTHERWISE.
49. PROVIDE SHOCK ARRESTERS AT ALL DOMESTIC HOT AND COLD WATER BRANCHES SERVING FIXTURES AND EQUIPMENT WITH QUICK CLOSING VALVES. SUCHFIXTURES AND EQUIPMENT INCLUDES FLUSH VALVE WATER CLOSETS, DISHWASHERS, ICE MACHINES, AND CLOTHES WASHERS. SHOCK ARRESTERS SHALL BECONSTRUCTED WITH A PISTON IN A SEALED COPPER TUBE CHAMBER, AND APPROVED FOR INSTALLATION WITHIN WALLS WITHOUT ACCESS PANELS. SIOUX CHIEFOR EQUIVALENT. BELLOWS TYPE NOT ACCEPTABLE.
50. DOMESTIC HOT AND COLD PIPING INSIDE BUILDING--BURIED LINES, TYPE “K” SOFT ANNEALED COPPER WATER TUBE, SINGLE LENGTH TO AVOIDFITTINGS, (WROUGHT COPPER FITTINGS WHERE UNAVOIDABLE) AND 1100°F SOLDER. NON-BURIED LINES, TYPE “L” HARD COPPER WATER TUBE, WROUGHT COPPERFITTINGS AND NO LEAD 95-5 SOLDER.
51. COPPER PIPE VALVES AND SPECIALTIES
A. GATE VALVES - BRONZE, CLASS 125, 200 LB. W.O.G.B. BALL VALVES - BRONZE, CLASS 125, 600 LB. W.O.G.C. CHECK VALVES - BRONZE, CLASS 125, 200 LB. W.O.G.D. BALANCING VALVES - 125 PSI W.P. FOR 250 DEGREE FARENHEIGHT SERVICE TIGHT SHUTOFF, TOUR AND ANDERSON STA, ARMSTRONG CBV, GERAND, OR
FLOWSET, BELL AND GOSSETT CIRCUIT SETTER.E. DIRECT UNIONS: FURNISH AND INSTALL A DIELECTRIC UNION AT EACH CONNECTION BETWEEN DISSIMILAR METALS.
52. MATERIALS; SOIL, WASTE, AND VENT PIPING (INSIDE BUILDING)
A. LINES ABOVE/BELOW GROUND--STANDARD WEIGHT, C.I. EPOXY COATED SOIL PIPE, AND FITTINGS. HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO HUBWITH 4-BAND HEAVY DUTY CLAMPS. UP THROUGH 2-1/2” MAY BE STANDARD WEIGHT, GALVANIZED STEEL PIPE WITH BLACK, W.I. DRAIN FITTINGS, OR DWVCOPPER TUBE WITH DWV FITTINGS AND 95-5 NO LEAD SOLDER.
53. PROVIDE EXPANSION JOINTS OR LOOPS ON ALL CHILLED WATER PIPING RUNS IN EXCESS OF 50 FEET AND IN ACCORDANCE WITH THE MANUFACTURER'SRECOMMENDATIONS.
54. GRADE AND VALVE ALL CHILLED WATER PIPING WITH 3/4” HOSE END VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM. VENT ALL HIGH POINTS INEQUIPMENT ROOMS AS NECESSARY WITH AUTOMATIC AIR VENTS PIPED TO CONVENIENT DRAIN. ALL HIGH POINTS IN SYSTEM OUTSIDE OF EQUIPMENT ROOMSWITH COMBINATION AUTOMATIC/MANUAL AIR VENTS AS REQUIRED TO RELIEVE AIR IN THE SYSTEM.
55. GAS PIPING: SCHEDULE 40 BLACK STEEL PIPE, 150 LB. MALLEABLE IRON SCREWED FITTINGS ON ABOVE GROUND PIPE, WELDED FITTINGS WITH ALL PIPING COATEDAND WRAPPED ON BURIED PIPE.
56. GAS VALVES: NON-LUBRICATED BALL STYLE VALVE WITH RESILIENT SEATS, AND ADJUSTABLE GLAND PACKING NUT, AGA AND UL LISTED FOR NATURAL GASSERVICE.
57. PROVIDE PLASTIC GROMMETS ON ALL HEATING WATER PIPING PASSING THROUGH WOOD JOISTS AND STUDS.
58. MATERIALS; HYDRONIC PIPING
A. ABOVE GRADE, UP THROUGH 2-1/2”: SCHEDULE 40 STEEL PIPE WITH MALLEABLE IRON THREADED FITTINGS, OR TYPE “L” COPPER TUBE WITH WROUGHTCOPPER FITTINGS AND 95-5 NO LEAD SOLDER.
B. ABOVE GRADE, 3” AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST IRON OR STEEL WELDING FITTINGS.
C. BELOW GRADE, UP THROUGH 1-1/4”: TYPE “K” SOFT ANNEALED COPPER TUBE, SINGLE LENGTH TO AVOID FITTINGS, (WROUGHT COPPER FITTINGS WHEREUNAVOIDABLE) AND 1100 DEGREE FARENHEIGHT SOLDER INSULATE WITH 1” THICK CLOSED CELL ELASTOMERIC INSULATION. ALL BURIED PIPE SHALL BESURROUNDED WITH 4” OF CLEAN SAND.
D. BELOW GRADE, 1-1/2” AND LARGER: JACKETED, PRE-INSULATED PIPING, WITH FLUID CARRIER PIPE EQUAL TO ABOVESPECIFICATION. ROVANCO, RICWELL/PERMA-PIPE OR EQUIVALENT.
59. DRAIN PAN PIPING--NOT BURIED--TYPE “M” COPPER, WROUGHT COPPER FITTINGS, AND 95-5 SOLDER; BURIED--TYPE L” COPPER WROUGHT COPPERFITTINGS, AND 95-5 SOLDER. ALL BURIED PIPE SHALL BE SURROUNDED WITH 4” OF CLEAN SAND.
60. INSULATE ALL CONDENSATE PIPING, CHILLED WATER, DOMESTIC WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RECIRCULATION, AND STORM ANDOVERFLOW PIPING WITH U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP-ON, PIPE INSULATION. INSULATE FITTINGS WITH GLASS FIBER BLANKETINSULATION AND PREMOLDED P.V.C. COVERS. ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 ORLESS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” MASTIC ONCOLD PIPING. ALL RAW EDGES OF INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC.
A. INSULATION THICKNESS BELOW BASED ON INSULATION CONDUCTIVITY VALUE NOT EXCEEDING 0.27 BTU*IN/(HR*FT^2*°F):
1) CHILLED WATER, HEATING WATER - ALL PIPE SIZES, 1.” THICK. - . RUNOUTS WITHIN 4 FEET OF TERMINAL AND 1” PIPE DIAMETER OR LESS - 1/2” THICK.
2) DOMESTIC HOT WATER (DHW) AND DOMESTIC HOT WATER RECIRCULATION: ALL PIPE SIZES - 1” THICK; NON-RECIRCULATED DHW RUNOUTS WITHIN 8 FEETOF FIXTURES - 1/2” THICK.
3) DOMESTIC COLD WATER AND CONDENSATE: ALL PIPE SIZES - 1/2” THICK.
4) HORIZONTAL STORM AND OVERFLOW PIPING: ALL SIZES - 1” THICK.
61. EQUIPMENT LABELS: LABEL ALL PIPING AND EQUIPMENT. PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE TAPE BANDINGON EACH END OF LABEL/FLOW ARROW. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH STANDARD CHAIN OR S-HOOKS.PROVIDE ENGRAVED PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT.
62. MEDICAL GAS SYSTEMS
A. REGULATORY REQUIREMENTS:
1) CONFORM TO NFPA 99.
B. SUBMITTALS:
1) PRIOR TO START OF WORK, THE CONTRACTOR'S MEDICAL GAS CERTIFIER SHALL REVIEW AND PROVIDE COMMENT TO ENGINEERS DESIGN TO INSUREFINAL COMPLIANCE.
2) SUBMIT MANUFACTURER'S PRODUCT DATA ON THE FOLLOWING:
a. MEDICAL GAS TUBING.b. STATION OUTLETS.c. MEDICAL GAS RAIL SYSTEMS.d. BRAZER CERTIFICATIONS.
C. PIPING MATERIALS
1) PIPING: COPPER, TYPE “L” OR MEDICAL QUALITY TYPE ACR, HARD TEMPER, CLEANED, CAPPED AND LABELED FOR OXYGEN SERVICE.
2) FITTINGS: WROUGHT COPPER, SOLDER JOINT, LONG RADIUS, CLEANED, CAPPED AND LABELED FOR OXYGEN SERVICE.
D. STATION OUTLETS:
1) OUTLETS TO BE GAS SPECIFIC AND ACCEPT ONLY SPECIFIC CONNECTIONS COMPATIBLE SPECIFIED. OUTLETS SHALL BE UL LISTED, CSA APPROVED AND MEET NFPA 99 STANDARD.
E. WASHING:
1) ON-SITE WASHING OF PIPE AND FITTINGS SHALL BE LIMITED TO RE-CLEANING SURFACES IN THE IMMEDIATE VICINITY OF JOINTS WHICH HAVE BECOME CONTAMINATED PRIOR TO JOINING.
F. JOINING:
1) ALL WORK SHALL BE PERFORMED BY BRAZERS CERTIFIED IN ACCORDANCE WITH AWS B2.2.
2) USE SILVER BRAZING ALLOY ANSI/AWS A5.8.
3) USE NO FLUX.
4) MAINTAIN A FLOW OF DRY OIL-FREE NITROGEN IN TUBING WHILE BRAZING TO PREVENT INTERNAL CORROSION.
5) JOINTS SHALL BE BRAZED WITHIN ONE HOUR OF BEING CLEANED. USE ONLY PLASTIC CAPS ON OD OF PIPE WHEN STOPPING WORK. DO NOT USE TAPE.
G. TESTS BY CONTRACTOR:
1) PERFORM THE INITIAL LEAK TEST, BLOWDOWN TEST, PRESSURE TEST, PIPING PURGE, AND CROSS CONNECTION TEST AS SPECIFIED IN NFPA 99. ISOLATEANY EQUIPMENT NOT RATED FOR THE TEST PRESSURE.
H. CERTIFICATION:
1) THE MEDICAL GAS SYSTEM SHALL BE TESTED BY A FACTORY TRAINED SERVICE REPRESENTATIVE OF THE MEDICAL GAS EQUIPMENT MANUFACTURERAFTER INSTALLATION OF THE SYSTEM HAS BEEN COMPLETED. THE REPRESENTATIVE SHALL PERFORM THE FOLLOWING SYSTEM VERIFICATION TESTS INACCORDANCE WITH NFPA 99: CROSS CONNECTION TEST, FLOW TEST, PIPING PURGE TEST, PIPING, PURITY TEST, AND CONCENTRATION TEST. APPROVEDMEDICAL GAS CERTIFICATION CONTRACTORS ARE SOUTHWEST MEDICAL GAS OR HEALTH CHOICE ENTERPRISES.
2) AT THE CONCLUSION OF TESTING, THE CERTIFIER SHALL PRESENT A TEMPORARY CERTIFICATE TO THE OWNER OR THE APPROPRIATE RESPONSIBLEPARTY, ANY ABNORMALITIES SHALL BE NOTED. IN ADDITION, IF REPAIR TO ANY PIECE OF MEDICAL GAS EQUIPMENT IS NECESSARY, PERFORM THIS REPAIRIN A REASONABLE TIME PERIOD. THE W
63. FIRE PROTECTION DESIGN/BUILD REQUIREMENTS:
A. PROVIDE MODIFICATIONS AND EXPANSION TO THE EXISTING AUTOMATIC SPRINKLER SYSTEM SERVING EXISTING BUILDING. COMPLETE DRAWINGS,SPECIFICATIONS, AND DETAILS SHALL BE SUBMITTED BY THE FIRE SPRINKLER DESIGN-BUILD CONTRACTOR.
B. THE FIRE SPRINKLER CONTRACTOR SHALL SERVE AS THE ENGINEER OF RECORD FOR ALL WORK PERFORMED UNDER THIS DIVISION. IF REQUIRED BY THEAUTHORITY HAVING JURISDICTION, (A.H.J.) SUBMIT COMPLETE FIRE SPRINKLER SYSTEM SHOP DRAWINGS AND HYDRAULIC CALCULATIONS, GENERATED BYCONTRACTOR. SHOP DRAWINGS SHALL BE A MINIMUM 1/8” SCALE, AND SHALL SHOW DEVICE AND APPLIANCE LOCATIONS, BUILDING BACKGROUNDINFORMATION, ROOM OCCUPANCY DESCRIPTIONS, DOOR SWINGS, FIRE RATINGS AND FIRE PROTECTION SYSTEM LAYOUT AND DETAILS. SHOP DRAWINGS ANDHYDRAULIC CALCULATIONS SHALL BE SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF NEW MEXICO. SUBMIT SHOP DRAWINGS ANDHYDRAULIC CALCULATIONS TO THE BUILDING AND FIRE DEPARTMENTS AND OBTAIN THEIR APPROVAL BEFORE SUBMISSION TO THE ARCHITECT.
C. WHERE REQUIRED BY THE A.H.J., ALL NEW SPRINKLER HEADS SHOULD HAVE THE CONNECTING MAIN AND BRANCH PIPE SIZES SHOWN.
1) SHOW THE CONNECTING MAIN AND BRANCH PIPE SIZES FOR ALL NEW, RELOCATED AND EXISTING SPRINKLER HEADS.
2) CONFORM TO LIGHT HAZARD OCCUPANCY REQUIREMENTS OF NFPA 13.
3) PROVIDE FLOW TEST INDICATING STATIC AND RESIDUAL PRESSURED DEVELOPED UNDER FIRE FLOW CONDITIONS AS REQUIRED BY A.H.J.
D. EXTEND THE EXISTING SPRINKLER SYSTEM, RELOCATE EXISTING AND ADD NEW SPRINKLER HEADS IN ACCORDANCE WITH NFPA 13, ALL APPLICABLE CODESAND ORDINANCES AND PROJECT REQUIREMENTS TO COMPLETE THE WORK.
E. SYSTEM SHALL BE INSTALLED COMPLETE AND OPERATIONAL, INCLUDING WATER FLOW INDICATOR, CONNECTIONS TO EXISTING ALARM, DRAIN PIPING,IDENTIFICATION SIGNS, ETC.
F. WORK SHALL BE PERFORMED BY A QUALIFIED FIRE SPRINKLER INSTALLER WITH A MINIMUM OF FIVE (5) YEARS EXPERIENCE IN SIMILAR INSTALLATIONS.
G. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO AND DURING INSTALLATION.
H. PROVIDE AN EXTRA STOCK OF SIX (6) SPRINKLER HEADS, THREE (3) OF EACH TYPE, AND A SPRINKLER WRENCH. SPRINKLER HEADS SHALL MATCH EXISTING INADJACENT AREAS.
64. COMBINATION FIRE AND SMOKE DAMPERS:
A. UNITS SHALL BE LABELED ACCORDING TO UL 555S. COMBINATION FIRE AND SMOKE DAMPERS SHALL BE LABELED ACCORDING TO UL 555 FOR 1-1/2HOUR RATING.
B. FUSIBLE LINKS SHALL BE REPLACEABLE AND 212 DEG F RATED.
C. FRAME AND BLADES SHALL BE AT LEAST 0.064-INCH THICK GALVANIZED SHEET STEEL, MOUNTING SLEEVE SHALL BE AT LEAST 0.052-INCH THICKGALVANIZED SHEET STEEL.
D. ELECTRICAL CONNECTION: 115V, SINGLE PHASE, 60 HZ.
A. BOOKS OF OPERATING AND MAINTENANCE INSTRUCTIONS SHALL BE PERSONALLY DELIVERED TO THE OWNER'S AUTHORIZED REPRESENTATIVE AND THEOWNER INSTRUCTED AS TO THEIR USE AND THE EQUIPMENT INVOLVED. (PROVIDE TWO BOOKS FOR EACH BUILDING). ALSO, INSTRUCT THE OWNER'SPERSONNEL ON EACH VALVE.
B. THE BOOK SHALL CONTAIN, BUT NOT BE LIMITED TO, THE FOLLOWING GENERAL ITEMS:1. SPARE PARTS LISTS FOR EACH PIECE OF EQUIPMENT.2. OPERATING MANUALS FOR EACH PIECE OF EQUIPMENT AND CONTROL.3. LUBRICATION CHARTS SHOWING TYPE OF LUBRICANT AND APPLICATION METHODS AND FREQUENCIES.4. FILTER CLEANING OR REPLACEMENT SCHEDULE. (ON CONTRACTOR'S LETTERHEAD STATIONARY).5. PREVENTIVE MAINTENANCE SCHEDULE FOR CHECKING ALL ITEMS SUCH AS BELT DRIVE, SAFETY CONTROLS AND OIL AND REFRIGERANT CHARGES.
CLEANING SCHEDULE OF ALL STRAINERS, TRAPS, COILS, TUBES, TOWER PANS, SPRAYS, ETC. (ON CONTRACTOR'S LETTERHEAD STATIONARY).6. NORMAL OPERATING INSTRUCTIONS INCLUDING A SEQUENCE OF OPERATION FOR EACH SYSTEM. (ON CONTRACTOR'S LETTERHEAD STATIONARY).7. INSTRUCTIONS AS TO PROCEDURE TO BE FOLLOWED FOR ANY EMERGENCY SITUATION, SUCH AS ALARMS OR SAFETY ITEMS BEING TRIPPED. (ON
CONTRACTOR'S LETTERHEAD STATIONARY).8. INSTRUCTIONS ON WHO TO CALL FOR SERVICE DURING GUARANTEE PERIOD. (ON CONTRACTOR'S LETTERHEAD STATIONARY).9. RECORD OF EQUIPMENT INSTALLED (COPY OF EACH SHOP DRAWING AS SET FORTH UNDER "SHOP DRAWING" PARAGRAPH).10. ALL WARRANTIES PROVIDED BY MANUFACTURERS ON THEIR EQUIPMENT THAT RUN LONGER THAN THE ONE YEAR GUARANTEE BY THE CONTRACTOR.
C. BOOKS SHALL BE ARRANGED IN SEQUENCE TO MATCH THE EQUIPMENT SCHEDULES INCLUDED IN THE SPECIFICATIONS.
D. PROVIDE RECORD DRAWINGS
E. APPROVAL WILL NOT BE GIVEN FOR FINAL PAYMENT UNTIL THE TESTS, BALANCING AND OPERATING INSTRUCTION PORTIONS HAVE BEEN COMPLETED.
OPERATION AND MAINTENANCE INSTRUCTIONS
1. ALL REFRIGERATION, BOILERS, AND PACKAGED EQUIPMENT SHALL BE STARTED BY THE MANUFACTURER OR UNDERTHE MANUFACTURER'S SUPERVISION. START-UP DATA SHALL BE RECORDED IN LOGS. COPIES OF START-UP LOGSSHALL BE FORWARDED TO MECHANICAL ENGINEER AND INCLUDED IN OPERATION AND MAINTENANCE
EQUIPMENT START-UP
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGSPECIFICATIONNOTES SHEET
P0-02
1"
2-1/2"
4"
(E) 6"SD
6"6"
4" 1-1/
2"
1"2"
2"
(E) 4"V
4"
2"2"
4"
4"
7
7 (E) 1
-1/2
"HW
(E) 2
"CW
(E) 2
"HW
(E) 2
-1/2
"CW
7 7
7
TYP.
(E) 2
"W
(E) 4"W
7
1(E) 4"VTR
6
6
6
6
7
TYP.
7
TYP.
7
7
7
7
7
(E) 1"HW(E) 2-1/2"CW
(E) 2"HW(E) 2-1/2"CW
(E) 4"W
7 7
7
7 77
7
7
7
TYP.
7TYP.
(E) CO
(E) 2"HW(E) 3"CW
(E) 2
"HW
(E) 3
"CW
(E) FS
(E) 4"W
(E) FS
(E) 4"W
(E) 6
"W(E
) 6"W
(E) 3"W
(E) 4
"WBELOW GRADE
ROUTED INCEILING SPACE
(E) 4
"W
(E) 3
/4"C
W(E
) 3/4
"HW
1
(E) 1
-1/4
"HW
(E) 3
/4"H
W
(E) 3
/4"C
W(E
) 3"W
(E) 4"W
(E) 1"HW(E) 2-1/2"CW
6
11
2
41
1
3
3
5
(E) 6"SD
(E) 4"SD
(E) 4
"SD
(E) 2"V
(E) 6
"SD
(E) 6"SD
(E) 6"SD
(E) 6
"SD
(E) 6
"SD
(E) 6
"SD
(E) 6
"SD
(E) 1
"HW
C(E
) 2-1
/2"C
W(E
) 3"C
W
(E) 3"CW
1
4
10
(E) 2" V
(E) 2
" V
.
8
8
9
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGDEMOLITION PLAN
PD1-01Scale:
1 PLUMBING DEMOLITION PLAN1/8"=1'-0"
NOTES:
FLAG NOTES:#
1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTE,VENT AND MEDICAL GAS PIPING MAY BE ROUTED INSPACE THAT IS NOT REPRESENTED, BUT IS TOREMAIN. OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ON THESEDRAWINGS; MODIFICATIONS TO THESE SYSTEMS ARENOT ANTICIPATED.
2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.
3. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INBELOW GRADE. THERE IS CURRENTLY AN EXISTINGROOF DRAIN SYSTEM LOCATED IN THE CEILINGSPACE ABOVE.
4. REMOVE ALL PLUMBING IFIXTURES INDICATED.
5. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.
6. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.
7. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.
8. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.
9. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.
10. COORDINATE WITH OWNER FOR DISPOSAL ORRE-USE REQUIREMENTS OF PLUMBING FIXTURES TOBE REMOVED.
1. REMOVE EXISTING SINK COMPLETE. REMOVEEXISTING WASTE PIPING DOWN TO BELOW GRADEAND SEAL AND CAP. REMOVE EXISTING HW/CW ANDVENT LINES BACK TO NEAREST ACTIVE MAIN. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATIONOF ALL PIPING.
2. REMOVE EXISTING WALL HUNG DRINKING FOUNTAINCOMPLETE. REMOVE EXISTING WASTE PIPING DOWNTO BELOW GRADE AND SEAL AND CAP. REMOVEEXISTING CW AND VENT LINES BACK TO NEARESTACTIVE MAIN AND CAP. REMOVE EXISTING SUPPORTSYSTEM. FIELD VERIFY EXISTING CONDITIONS ANDEXACT LOCATION OF ALL PIPING.
3. REMOVE EXISTING FLOOR DRAIN COMPLETE.REMOVE EXISTING WASTE PIPING DOWN TO BELOWGRADE AND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE ASSOCIATED TRAP PRIMER DEVICE ANDASSOCIATED SUPPLY PIPING. REMOVE CW FROMTRAP PRIMER BACK TO ACTIVE AMIN AND CAP. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATIONOF ALL PIPING.
4. REMOVE EXISTING WATER CLOSET COMPLETE.REMOVE EXISTING WASTE PIPING DOWN TO BELOWGRADE AND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE EXISTING CW SUPPLY COMPLETE BACK TONEAREST ACTIVE MAIN. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION OF ALL PIPING.
5. REMOVE EXISTING URINAL COMPLETE. REMOVEEXISTING WASTE PIPING DOWN TO BELOW GRADEAND SEAL AND CAP. REMOVE EXISTING VENTCOMPLETE BACK TO EXISTING ACTIVE MAIN AND CAP.REMOVE EXISTING CW SUPPLY COMPLETE BACK TONEAREST ACTIVE MAIN. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION OF ALL PIPING.
6. EXISTING STORM PIPING FROM ROOF ABOVE TOREMAIN. STORM PIPING TO REMAIN ACTIVE DURINGCONSTRUCTION. PROTECT PIPING DURINGCONSTRUCTION AND COORDINATE EXISTINGLOCATION WITH OTHER DISCIPLINES.
7. EXISTING PLUMBING FIXTURES TO REMAIN. PROTECTPLUMBING FIXTURE DURING CONSTRUCTION.
8. REMOVE EXISTING MEDICAL GAS STATIONCOMPLETE. REMOVE ALL ASSOCIATED A,V,O2 PIPINGCOMPLETE BACK TO NEAREST ACTIVE MAIN INCEILING SPACE AND CAP. FIELD VERIFY EXISTINGCONDITIONS AND EXACT LOCATION.
9. EXISTING MEDICAL GAS VALVE BOX TO REMAIN.FIELD VERIFY EXISTING CONDITIONS AND EXACTLOCATION.
10. REMOVE EXISTING HOSE BIBB HYDRANT ANDASSOCIATED CW SUPPLY LINE COMPLETE. FIELDVERIFY EXISTING CONDITIONS AND EXACT LOCATION.
11. EXISTING STORM DRAINAGE FROM CEILING SPACEDOWN TO BELOW GRADE IS TO REMAIN. EXISTINGSTORM DRAINAGE PIPING BELOW GRADE TOEXTERIOR IS REMAIN, BUT IS NOT SHOWN. TAKEPRECAUTION TO AVOID DAMAGING DURINGCONSTRUCTION. FIELD VERIFY EXISTING CONDITIONSAND EXACT LOCATION.
Scale:
2 RADIOLOGY CORRIDOR DEMOLITION PLAN1/8"=1'-0"
2"3/4"3/4"
(E)V(E)A
(E)O2(E)DPSS
(E)V(E)A
(E)O2
(E)DPSS2"
3/4"3/4"
(E)V
(E)A
(E)O
2
3/4"
1/2"
1/2"
(E)V
(E)A
(E)O
2
(E)V
(E)A
(E)O
2
3/4"
3/4"
1/2"
1/2"
(E)V(E)A
(E)O2
(E)DPSS2"
3/4"3/4"
(E)D
PS
S
(E)V
(E)A
(E)O
2
2"3/4"
3/4"
1
2
34
5
4
5
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGMEDICAL GASDEMOLITION PLAN
PD1-02Scale:
1 PLUMBING MEDICAL GAS DEMOLITION PLAN1/8"=1'-0"
NOTES:
FLAG NOTES:#
1. ADDITIONAL STORM, HYDRONIC, DOMESTIC, WASTE,VENT AND MEDICAL GAS PIPING MAY BE ROUTED INSPACE THAT IS NOT REPRESENTED, BUT IS TOREMAIN. OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ON THESEDRAWINGS; MODIFICATIONS TO THESE SYSTEMS ARENOT ANTICIPATED.
2. FIELD VERIFY ALL COMPONENTS PRIOR TODEMOLITION. THE INFORMATION ON THIS SHEET WASOBTAINED, IN PART, FROM HISTORIC DESIGNDRAWINGS. ONLY PORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATION DURINGDESIGN PROCESS.
3. (E) WASTE SYSTEM SERVING SPACE IS LOCATED INBELOW GRADE. THERE IS CURRENTLY AN EXISTINGROOF DRAIN SYSTEM LOCATED IN THE CEILINGSPACE ABOVE.
4. REMOVE ALL PLUMBING IFIXTURES INDICATED.
5. TEMPORARILY SEAL OR CAP PIPING TO BE RE-USEDFOR LATER CONNECTION.
6. REMOVE ALL DEMOLISHED COLD WATER, HOT WATERAND HOT WATER RECIRCULATION PIPING BACK TOBRANCH FROM MAIN TO ELIMINATE ALL DEAD ENDS INDOMESTIC WATER PIPING.
7. NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATION REPRESENTED INTHE DOCUMENTS VERSUS WHAT IS FOUND IN THEFIELD.
8. COORDINATE PATCHING AND REPAIRS OF WALLS,CEILINGS AND FLOORS WITH ARCHITECT.
9. PATCH STRUCTURAL OPENINGS IN FLOORS, WALLSAND ROOFS THAT WERE PREVIOUSLY OCCUPIED BYSYSTEMS AND EQUIPMENT DEMOLISHED UNDER THISCONTRACT IN ACCORDANCE WITH STRUCTURALENGINEER'S REQUIREMENTS.
10. COORDINATE WITH OWNER FOR DISPOSAL ORRE-USE REQUIREMENTS OF PLUMBING FIXTURES TOBE REMOVED.
1. REMOVE MEDICAL GAS STATION COMPLETE.FIELD VERIFY EXACT LOCATION.
2. REMOVE MEDICAL VALVE BOX COMPLETE. FIELDVERIFY EXACT LOCATION.
3. REMOVE AND CAP O2 TO VALVE. FIELD VERIFYEXACT LOCATION AND CONDITIONS.
4. REMOVE AND CAP A TO VALVE. FIELD VERIFYEXACT LOCATION AND CONDITIONS.
5. REMOVE AND CAP VAC BACK TO NEARESTACTIVE MAIN. FIELD VERIFY EXACT LOCATIONAND CONDITIONS.
4"
(E) 6"SD
6"6"
4"
4"
(E) 1
-1/2
"HW
(E) 2
"CW
(E) 2
"HW
(E) 2
-1/2
"CW
(E) 2
"W
(E) 4"W
(E) 4"VTR
(E) 1"HW
(E) 2"HW(E) 2-1/2"CW
(E) 4"W
(E) CO
(E) 2"HW(E) 3"CW
(E) 2
"HW
(E) 3
"CW
(E) FS
(E) 4"W
(E) FS
(E) 4"W
(E) 6
"W(E
) 6"W
(E) 3"W
(E) 4
"WBELOW GRADE
ROUTED INCEILING SPACE
(E) 4
"W
(E) 3
/4"C
W(E
) 3/4
"HW
(E) 1
-1/4
"HW
(E) 3
"W
(E) 4"W
(E) 1"HW
(E) 6"SD
(E) 4"SD
(E) 4
"SD
(E) 6
"SD
(E) 6"SD
(E) 6"SD
(E) 6
"SD
(E) 6
"SD
(E) 6
"SD
(E) 6
"SD
(E) 1
"HW
C(E
) 2-1
/2"C
W(E
) 3"C
W
(E) 3"CW
1 & 2P4-01
P6
P16
P17
P19
P6
P5
P5
P5
2" W
4" W
4" W
P7 P7
P7
P8
P10
3/4"
HW
3/4"
CW
3/4" H
W
3/4"
HW
3/4"
HW
1-1/
2" C
W
2-1/2" CW
21
5
4
3
5
7
1
1
1
5
P11
P14
2" W
2" W
3" W
2" W
P11
P6
(E)4" VTR
3" V
3" V
2" V
2" V
2" V
2" V
1-1/2" V
2" V
2" V 3" V
1-1/
2" C
W
3/4" HWC
(E)2-1/2"CW
3/4"
HW
3/4"
CW
3/4"
HW
3/4"
CW
P18
3/4" HW/CW
3/4"HW/CW
3/4"
CW
P6
2" V
ELEV.
MED.GAS
STAIRX1-SX
STAIR1067
EXTERIOR COURTYARD - NO PUBLIC ACCESS
TELE.
OFFICE1031
EXAM1032
EXAM1033
EXAM1034
EXAM1036
EXAM1037
EXAM1038
EXAM1039
EXAM1041
CORRIDOR1029
TRIAGE/ASSESMENT
1019
RECEPTION/ASSESMENT
1018
SECURITY1018A
WAITING1013
WHEELCHAIRSTORAGE
1002
QUIETWAITING
1011
ENTRYVESTIBULE
1001
WOMEN1008
MEN1009
HSKP1004
VENDING1007
CORRIDOR1005
CORRIDOR1161
CONSULT1024
MULTI-PATIENTEXAM/HOLDING
1026
PATIENT/SPECIMENTOILET
1022
CORRIDOR1021
CORRIDOR1020
FAST TRACK1023
MEDICATION/SUPPLY
1014
NUTRITION1016
FAST TRACK1023B
FAST TRACK1023C
FAST TRACK1023A
FAST TRACK1023D
FAST TRACK1023E
FAST TRACK1023F
FAST TRACK1023G
TREATMENT1078
CONTROL1082
TREATMENT1081
ALCOVE1076
CLEAN SUPPLY/EQUIPMENT
1074
TREATMENT1077
PATIENTTOILET
1079
X-RAY1083
COMM.1084
CORRIDOR1028
ELEC.1085
ALCOVE1088A
ALCOVE1088BALCOVE
1088C
CORRIDOR1087
MEDICATION1093
NOURISHMENT1094
PYXIS1098
STAFFTOILET
1097
PATIENTTOILET
1098
SOILEDUTILITY
1099NURSESTATION
1092
CORRIDOR1091
CRASH CART1111
CORRIDOR1109
ALCOVE1108
EXAM1101
EXAM1106
OBEXAM1102
OBEXAM1107
PATIENTTLT./SHWR
1103
PATIENTTOILET11034
CORRIDOR1027
EXAM1042
EXAM1043
EXAM1044
ISOLATION1046
ANTE1048FIRE
1047
NURSESTATION
1073CORRIDOR1072
EXAM1049
EXAM1051
WHEELCHAIRSTORAGE
1052
VESTIBULE1053
DECONSHOWER
1054
EMSCLOSET
1056
PSYCH.1057
TRAUMA1058
TRAUMA1059
CORRIDOR1071
HSKP1061
ELEV.EQUIP.
1068
ELEV.LOBBY
1064
ALCOVE1062
RESULTSWAITING
1117
OFFICE1123
STAFFLOCKERS
1124
OFFICE1123 STAFF
LOUNGE1152
OFFICE1112
OFFICE1113
TLT./SHOWER1114
CORRIDOR1134
CORRIDOR1127
(E) 4"W
WCO
(E) 2" V
(E) 2
" V
WCOWCO
3/4" HW/CW2" V
5
(E) 1
-1/2
"HW
(E) 1
-1/2
"HW
(E) CW
5
WCO
WCO
WCO
WCO
WCO
WCO
WCOWCO
WCO
WCO
WCO
2" W
3" W
WHA
1/2" CW
1/2"HW
8
2
12
11
5
11
2
2
8
8
9
6
P11
P17
1-1/4" CW
12
1
P10
13
P11
2" W
14
P13
3/4" CW
1
TOILET
PASSAGEWAYX1XX
BEDSTORAGE
X1XX
EXAM #1X1XX
OFFICEX1XX
XRAYREADING
X1XX
PHYSICIAN'SREADING RM.
X1XX
CORRIDOR
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGPLAN
P1-01
Scale:
1 PLUMBING PLAN1/8"=1'-0"
NOTES:
1. CONNECT NEW CW TO EXISTING CW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS AND EXACT LOCATION. SIZEPER PLAN.
2. CONNECT NEW CW/HW TO EXISTING CW/HW OFSAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS EXACT LOCATION. SIZE PER PLAN.
3. CONNECT NEW HWC TO EXISTING HWC OF SAMESIZE OR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.
4. CIRCUIT SETTER BALANCING VALVE. SET TO (1.5GPM) ADJUSTABLE. PROVIDE WITH ISOLATION BALLVALVE BEFORE AND AFTER CIRCUIT SETTER VALVE.
5. CONNECT NEW WASTE LINE TO EXISTING WASTEOF SAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS, EXISTING INVERT AND EXACTLOCATION. SIZE PER PLAN.
6. ROUTE 1/2" HW/CW DOWN IN WALL AND CAP FORFUTURE CONNECTION. PROVIDE STUB-OUT FORFUTURE LAVATORY.
7. ROUGH-IN 2" WASTE AND 1-1/2" VENT IN WALL FORFUTURE SINK CONNECTION.
8. CONNECT NEW VENT TO EXISTING VENT OF SAMESIZE OR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.
9. EXISTING STORM DRAIN LEADER DOWN TO BELOWGRADE TO REMAIN. FIELD VERIFY EXACT LOCATION.FURR-OUT AROUND EXISTING PIPING AS REQUIRED.PROVIDE ACCESS FOR STORM CLEAN-OUT.PROTECT EXISTING PIPING DURING DEMOLITIONAND CONSTRUCTION.
10. CONNECT NEW HW TO EXISTING HW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.
11. CONNECT NEW CW TO EXISTING CW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS EXACT LOCATION. SIZE PERPLAN.
12. CONNECT NEW VENT TO EXISTING 4" VTR. FIELDVERIFY EXISTING CONDITIONS AND EXACTLOCATION.
13. 3/4" HW/CW DOWN IN WALL. ROUTE 1/2" HW/CW TOCOUNTER SINK. EXTEND 1/2" HW/CW TO WATERDISPENSERS BY OTHERS AND CONNECT PERMANUFACTURERS REQUIREMENTS WITH QUARTERTURN ANGLE STOPS. EXTEND 1/2" CW TO ICEMAKER BOX. ROUTE DRAIN FROM ICE MACHINE TOCOUNTER SINK TAIL PIECE AND TERMINATEINDIRECTLY ABOVE TRAP.
14. INSTALL FLOOR DRAIN FLUSH WITH FLOORDEPRESSION FOR WHEEL CHAIR SCALE.COORDINATE EXACT LOCATION WITH WHEEL CHAIRSCALE MANUFACTURERS INSTALLATIONREQUIREMENTS.
FLAG NOTES:#
1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.
2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.
3. REFER TO P0-01 FOR THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZES TOINDIVIDUAL FIXTURES.
4. THE RENOVATION IS TO BE EXECUTED IN PHASES.REFER TO ARCHITECTURAL PLANS FOR PROJECTPHASING.
Scale:
2 RADIOLOGY CORRIDOR FLOOR PLAN1/8"=1'-0"
1. EXISTING WET AND DRY FIRE PROTECTION SYSTEMIN AREA INDICATED SHALL BE MODIFIED TOPROVIDE COVERAGE FOR THE REDESIGNEDEXISTING SPACE. MODIFY AS REQUIRED ORPROVIDE NEW SPRINKLER HEAD LAYOUT FORCOMPLETE COVERAGE OF THE RENOVATED AREA.MODIFY PIPING OR REPOSITION EXISTING FIRESPRINKLER HEADS AS REQUIRED.
FIRE PROTECTION NOTESX
2"3/4"3/4"
(E)V(E)A
(E)O2(E)DPSS
(E)V(E)A
(E)O2
(E)DPSS2"
3/4"3/4"
(E)V(E)A
(E)O2
(E)DPSS2"
3/4"3/4"
(E)D
PS
S
(E)V
(E)A
(E)O
2
2"3/4"
3/4"
1/2" O21/2" A
1" VAC
1/2"
O2
1/2"
A1"
VA
C
MVB-1
1/2"
O2
1/2"
A1"
VA
C
MGS-1
MGS-1
MGS-1
1
MGS-1
MGS-2
1/2" O21/2" A
1" VAC
1/2" O21/2" A
1" VAC
1/2" O21/2" A1" VAC1/2" O2
1/2" A1" VAC
MGS-2
MGS-2
MGS-2MGS-2
2"3/4"3/4"
(E)V(E)A
(E)O2
2
1
LPA-1
MVB-2
1/2"
O2
1/2"
A1"
VA
C
1/2" O21/2" A
1" VAC
MGS-1
MGS-1
3
3
3 3
3
3
3
3
3
3
3
1/2"
MGS-13
1"
MGS-1
3
MGS-1
3
LPA-2
ELEV.
MED.GAS
STAIRX1-SX
STAIR1067
EXTERIOR COURTYARD - NO PUBLIC ACCESS
TELE.
OFFICE1031
EXAM1032
EXAM1033
EXAM1034
EXAM1036
EXAM1037
EXAM1038
EXAM1039
EXAM1041
CORRIDOR1029
TRIAGE/ASSESMENT
1019
RECEPTION/ASSESMENT
1018
SECURITY1018A
WAITING1013
WHEELCHAIRSTORAGE
1002
QUIETWAITING
1011
ENTRYVESTIBULE
1001
WOMEN1008
MEN1009
HSKP1004
VENDING1007
CORRIDOR1005
CORRIDOR1161
CONSULT1024
MULTI-PATIENTEXAM/HOLDING
1026
PATIENT/SPECIMENTOILET
1022
CORRIDOR1021
CORRIDOR1020
FAST TRACK1023
MEDICATION/SUPPLY
1014
NUTRITION1016
FAST TRACK1023B
FAST TRACK1023C
FAST TRACK1023A
FAST TRACK1023D
FAST TRACK1023E
FAST TRACK1023F
FAST TRACK1023G
TREATMENT1078
CONTROL1082
TREATMENT1081
ALCOVE1076
CLEAN SUPPLY/EQUIPMENT
1074
TREATMENT1077
PATIENTTOILET
1079
X-RAY1083
COMM.1084
CORRIDOR1028
ELEC.1085
ALCOVE1088A
ALCOVE1088B
ALCOVE1088C
CORRIDOR1087
MEDICATION1093
NOURISHMENT1094
PYXIS1098
STAFFTOILET
1097
PATIENTTOILET
1098
SOILEDUTILITY
1099NURSESTATION
1092
CORRIDOR1091
CRASH CART1111
CORRIDOR1109
ALCOVE1108
EXAM1101
EXAM1106
OBEXAM1102
OBEXAM1107
PATIENTTLT./SHWR
1103
PATIENTTOILET11034
CORRIDOR1027
EXAM1042
EXAM1043
EXAM1044
ISOLATION1046
ANTE1048FIRE
1047
NURSESTATION
1073
CORRIDOR1072
EXAM1049
EXAM1051
WHEELCHAIRSTORAGE
1052
VESTIBULE1053
DECONSHOWER
1054
EMSCLOSET
1056
PSYCH.1057
TRAUMA1058
TRAUMA1059
CORRIDOR1071
HSKP1061
ELEV.EQUIP.
1068
ELEV.LOBBY
1064
ALCOVE1062
RESULTSWAITING
1117
OFFICE1123
STAFFLOCKERS
1124
OFFICE1123 STAFF
LOUNGE1152
OFFICE1112
OFFICE1113
TLT./SHOWER1114
CORRIDOR1134
CORRIDOR1127
1/2" O21/2" A1" VAC
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGMEDICAL GAS PLAN
P1-02Scale:
1 PLUMBING MEDICAL GAS PLAN1/8"=1'-0"
NOTES:
1. CONNECT O2, A, AND VAC TO EXISTING. FIELDVERIFY EXACT LOCATIONS AND EXISTINGCONDITIONS.
2. 1/2" O2, 1/2" A AND 1" VAC TO MBV-2 FROMEXISTING. FIELD VERIFY EXACT LOCATIONS ANDEXISTING CONDITIONS.
3. CONNECT 1/2" A, 1/2" O2 AND 1" VAC TO MGS-1.FIELD VERIFY EXACT LOCATIONS.
FLAG NOTES:#
1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.
2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.
3. REFER TO SHEET P6-01 FOR MEDICAL GASSCHEDULES.
4. THE RENOVATION IS TO BE EXECUTED IN PHASES.REFER TO ARCHITECTURAL PLANS FOR PROJECTPHASING.
A. PIPING LAYOUT IS DIAGRAMMATIC ONLY. SIZESSHOWN ARE NOMINAL INSIDE DIAMETER. ALLRECESSED PIPING SHALL BE SEAMLESS COOPERTUBING TYPE K SOFT TAMPER ASTM DESIGNATIONNO. B-88 FOR ASSEMBLY WITH L COPPER TUBINGSHALL BE USED. EXPOSED PIPING TO BE SAMEEXCEPT HARD TAMPER. THE USE OF FITTINGS ISMANDATORY. TUBING BENDERS AND MACHINESWHICH DRAW FITTINGS FROM THE TUBING NOTACCEPTABLE.
B. ENSURE THAT THE MEDICAL GAS AND VACUUMLINES ARE ELECTRICALLY GROUNDED AT SEVERALPOINTS.
C. ISOLATE PIPING FROM STUDS, HANGERS, ETC.,WHERE THERE ARE ABERRATIONS OR WHEREDISSIMILAR MATAL'S COME IN CONTACT WITH EACHOTHER.
D. COORDINATE ALL OTHER TRADES TO INSTALLMEDICAL GAS PIPING WITHOUT CONFLICT.
E. P.C. SHALL HAVE MEDICAL GASES AND ALLASSOCIATED EQUIPMENT CERTIFIED BY ANORGANIZATION AUTHORIZED TO CERTIFY MEDICALGASES.
F. PROVIDE AND INSTALL ALL MEDICAL GASES TOCOMPLY WITH THE REQUIREMENTS OF NFPA 99,NFPA 50 AND LOCAL BUILDING CODES.
G. MARK ALL MEDICAL GAS LINES WITH COLOR CODEMARKERS THAT COMPLY WITH NFPAREQUIREMENTS.
H. CONTRACTOR SHALL PROVIDE A MOCK-UP OF O2,VAC, AIR & SLIDE LAYOUT PRIOR TO INSTALLATIONOF ALL MEDICAL GAS STATION FOR APPROVAL.LOCATE SLIDE NEXT TO VAC.
I. ALL PRESSURE SENSORS SHALL BE WIRED TOLOCAL AREA ALARM PANEL.
J. ALL NEW MEDICAL GAS EQUIPMENT (VALVE BOXES,OUTLETS, AND ALARMS SHALL MATCH CURRENTSJRMC FACILITY GUIDELINES STANDARDS ANDCURRENT EXISTING SYSTEM REQUIREMENTS.
MED GAS NOTES:
(E) 1" HW
2-1/2" CW
3/4"
HW
2" C
W2"
CW
3/4" CW
1
1
1
1/2" CW
1-1/2" CW
1-1/2" CW
3/4" CW
3/4" CW
2-1/2" CW
1-1/2" CW
WHA
WHA
(E) 6"SD
(E) 4" W
4" W
2" W
4" W
4" W
4" W
4" W
3" V
2" V
2" V
2" V
2" V2" V
3/4" CW
3
2" V
WCO
WCOWCO
WCO
WCO
WCO SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ENLARGED PLUMBINGWASTEA VENT AND WATER ENLARGEMENT PLANS
P4-01Scale:
1 ENLARGED PLUMBING WATER PLAN1/4"=1'-0"
NOTES:
1. CONNECT NEW HW TO EXISTING HW OF SAME SIZEOR LARGER IN CEILING SPACE. FIELD VERIFYEXISTING CONDITIONS AND EXACT POINT OFCONNECTION.
2. WATER HAMMER ARRESTOR. PROVIDE IN ACCESSPANEL. COORDINATE LOCATION WITH WALLFINISHES AND ACCESSORIES.
3. CONNECT NEW WASTE LINE TO EXISTING WASTEOF SAME SIZE OR LARGER. FIELD VERIFY EXISTINGCONDITIONS, EXISTING INVERT AND EXACTLOCATION.
FLAG NOTES:#
1. REFER TO P0-01 FOR PLUMBING GENERAL NOTES.
2. REFER TO P5-01 FOR PLUMBING DIAGRAMS.
3. REFER TO P0-01 FOR THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZES TOINDIVIDUAL FIXTURES.
4. REFER TO ARCHITECTURAL DRAWINGS FOR PHASINGREQUIREMENTS.
Scale:
2 ENLARGED WASTE AND VENT PLAN1/4"=1'-0"
P1aP1P1
P3 P3
P3 P3
P4P1a
P1
P2
P9
WCO
P1aP1P1
P3 P3
P3 P3
P4P1a
P1
P2
P9
P11
P11
PIPE THRU ROOF DIAGRAMNO SCALE
6" M
IN.
24 GA. GALV. ROOF JACK W/6" FLANGE BY M.C., SET INPLASTIC CEMENT BY G.C.
PIPE BY M.C.
24 GA. GALV. STORM COLLARBY M.C., CLAMP IN PLACE &CAULK WEATHERTIGHT.
PIPE SLEEVE & CAULKING BYM.C.
SOLDERED LAP SEAM
2 LAYERS OF FELT BY G.C.
FINISHED ROOF FELTS BYG.C.
2" MIN.
NOTE:COOR'D ROOF PENETRATIONAND SEALING WITH ROOFMANUFACTURER ANDINSTALLING CONTRACTOR.
CLEANOUT DIAGRAMS
FLOOR CLEANOUT (FCO)
NO SCALE
SLOPE DN @ 1/4"/L.F.
CLEANOUT TO GRADE (COTG)
WASTE LINE
FINISHED GRADE
6"
ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSURE WITH ANCHOR FLANGE,HEAVY DUTY TOP, AND VANDAL PROOF FASTENERS, ZURN, Z-1400-HD-KBRASSCLEANOUT PLUG W/COUNTER SUNK HEAD.
ADJUSTABLE CLEANOUTAND ACCESS COVER ZURNZB-1400. TOP OF COVER TOBE FLUSH W/ TOP OF FLOOR.
16" CONC. PAD TROWELSMOOTH & EDGE.
1/8 C.I. BEND
BALANCE OF PIPING SAMEAS CLEANOUT TO GRADE.
FLOOR LINE
1/8 C.I. BEND
C.I. WASTE LINE.LGTH TO SUIT.
1/8 BEND IF CLEANOUTOCCURS AT END OF LINE.
PROVIDE FOLLOWING OPTIONS AS APPROPRIATECARPET MARKER - FOR CARPETED AREAS.SQUARE TOP - FOR CERAMIC TILE ORSIMILAR SQUARE PATTERN FLOOR.FLASHING CLAMP - FOR ABOVE GRADEWATER PROOFED AREAS.
DESIGNER NOTE:1. COORDINATE C.O.T.G.
WITH CIVIL ENGINEER.
WALL CLEANOUTDIAGRAMNO SCALE
1'-0
"
MAY EXTEND AS AWASTE OR VENT.
CHROME WALLCOVERAND SCREW.
PLUGGED TEE WITHCLEANOUT.
WALL.
FLOOR LINE.
1/8 C.I. BEND.
BALANCE OF PIPINGSAME AS CLEANOUTTO GRADE.
WASTE LINE
SLOPE DN @ 1/4"/L.F.
TWO-WAY CLEANOUT TO GRADE DIAGRAMSNO SCALE
6"
FINISHED GRADE
ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSUREWITH ANCHOR FLANGE, HEAVY DUTY TOP, AND VANDALPROOF FASTENERS, ZURN, Z-1400-HD-KBRASS CLEANOUTPLUG W/COUNTER SUNK HEAD.
24" X1 6"Ø CONC. PAD TROWELSMOOTH & EDGE.
C.I. WASTE LINE.LGTH TO SUIT.
1/8 C.I. BEND
DESIGNER NOTE:1. COORDINATE C.O.T.G. WITH
CIVIL ENGINEER.
WATER HAMMER ARRESTOR DIAGRAM (WHA) NO SCALE
CW/HW TO FIXTURE, TYP.
PD1 SIZING:SIZE FIXTURE UNITS
AA 1-4A 4-11B 12-32C 33-60
CW/HW BRANCH TO FIXTURES
WATER HAMMER ARRESTORON END OF BRANCH.
DIAGRAM & ISOMETRICDRINKING FOUNTAIN MOUNTING
NO SCALE
& TRIMPLATE.MANUFACTURER'S WALL HANGER
WALL.
S.S. PLATE.
CONCEAL WALLDAMAGE WITH
AGAINST WALL.P-TRAPS FLAT
34"
REPLACE (E) SINGLE INLET
FITTING.WITH (N) DOUBLE INLET
ISOMETRIC
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGDIAGRAMS
P5-01
PLUMBING FIXTURE SCHEDULE
SYMBOL TYPE A.D.A. FINISH MANUFACTURER* &MODEL #
FAUCET TRIM MFR.* &MODEL # INSTALLATION ACCESSORIES REMARKS POWER
FLOOR MOUNTEDWATER CLOSET NO VITREOUS CHINA AMERICAN STANDARD
MADERA 2234.128SLOAN ROYAL
111-1.28 FLOOR MOUNTED
AMERICAN STANDARDOPEN-FRONT SEAT:
5901.100T W/ EVERCLEANSURFACE. PROVIDE WITH
WATER HAMMER ARRESTORW/ ISOLATION VALVE IN
ACCESS PANEL. COORDINATELOCATION OF WHA WITH WALL
FINISHES AND TOILETACCESSORIES.
1.28 GPF NO
FLOOR MOUNTEDWATER CLOSET YES VITREOUS CHINA AMERICAN STANDARD
MADERA 3461.128SLOAN ROYAL
111-1.28 FLOOR MOUNTED
AMERICAN STANDARDOPEN-FRONT SEAT:
5901.100T W/ EVERCLEANSURFACE. PROVIDE WITH
WATER HAMMER ARRESTORW/ ISOLATION VALVE IN
ACCESS PANEL. COORDINATELOCATION OF WHA WITH WALL
FINISHES AND TOILETACCESSORIES.
1.28 GPF NO
URINAL YES VITREOUS CHINA AMERICAN STANDARDWASHBROOK 6590.501
SLOAN ROYAL186-0.5
WALL MOUNTED WITHCONCEALED ARM SUPPORT
CARRIER
COORDINATE INSTALLATIONHEIGHT WITH
ARCHITECTURAL. PROVIDEWITH DRAIN STRAINER.
.05 GPF NO
COUNTER MOUNTLAVATORY YES VITREOUS CHINA AMERICAN STANDARD
RONDALYN 0491.019
AMERICAN STANDARDMONTERRREY WITH GRID
STRAINER 5502.175COUNTER MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, 1/4 TURN
ANGLE STOPS AND SUPPLIES.
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOT WATER SUPPLY. PROVIDEWCO.
NO
WALL HUNGLAVATORY YES VITREOUS CHINA AMERICAN STANDARD
LUCERNE 0355.012
AMERICAN STANDARDMONTERRREY WITH GRID
STRAINER 5502.175WALL MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, FLOOR
MOUNTED CONCEALED ARMWALL CARRIER, 1/4 TURN
ANGLE STOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOW WATER SUPPLY. PROVIDEWCO.
NO
DRINKING FOUNTAIN YES STAINLESS STEEL ELKAYLZSVR8 - - WALL MOUNT
PROVIDE FLOOR MOUNTEDCONSEALED ARM CARRIER, 1/4 TURN
ANGLE STOPS, P-TRAP AND FLEXCONNECTION PROVIDE ELECTRICALCONNECTION. COORDINATE OUTLET
LOCATION WITH ELECTRICAL.PROVIDE WCO.
YES115V/60Hz, 5 AMPS, 370 WATTS
SINGLECOMPARTMENTCOUNTER SINK
YES STAINLESS STEEL ELKAYLRAD172055
AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED
1.5 GPM OUTLET AERATOR,PROVIDE WITH 17 G.A. P-TRAP,
TRUBRO UNDER-SINKPROTECTION, 1/4 TURN
ANGLE STOPS AND SUPPLIES,PROVIDE WITH ASSE 1071
LISTED POINT OF USETHERMOSTATIC MIXING
VALVE.
PROVIDE WITH PLASTER TRAP BYZURN IF REQUIRED IN PROCEDURE
ROOMS, REFER TO FLOOR PLAN FORLOCATION. PROVIDE WITH A REARCENTERED DRAIN. PROVIDE WCO.
NO
HAND SINK YES VITREOUS CHINA AMERICAN STANDARDLUCERNE 0355.012
AMERICAN STANDARDMONTERRREY WITH GRID
STRAINER 5502.175WALL MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, FLOOR
MOUNTED CONCEALED ARMWALL CARRIER, 1/4 TURN
ANGLE STOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOW WATER SUPPLY. PROVIDEWCO.
NO
EXAM SINK YES STAINLESS STEEL ELKAYLRAD222255
AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, 1/4 TURN
ANGLE STOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOW WATER SUPPLY. PROVIDEWCO.
NO
SINGLECOMPARTMENT
BREAKROOM SINKYES STAINLESS STEEL ELKAY
LRADQ221955AMERICAN STANDARDMONTERREY 7500.175 COUNTER MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, 1/4 TURN
ANGLE STOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOW WATER SUPPLY. PROVIDEWCO.
NO
MOP SINK - PRECAST TERRAZZO FIAT TSB100
SERVICE SINK FAUCET WITHVACUUM BREAKER AND PAIL HOOK
BY FIATMODEL: 830-AA
SERVICE SINK FAUCET WITHVACUUM BREAKER AND PAIL
HOOK BY FIATMODEL: 830-AA
PROVIDE WITH HOSE ANDBRACKET(832AA), BUMPERGAURDS(1239BB), AND SS
WALL GAURDS(MSG)
PROVIDE WITH MOP HANGER NO
NO
FLOOR DRAIN - CAST IRON ZURN Z415 - - PROVIDE WITH SURE SEALTRAP GUARD - NO
FLOOR SINK - CAST IRON ZURN Z1902 - - PROVIDE WITH SURE SEALTRAP GUARD
PROVIDE PRO-VENT TRAP GUARD,DOME STRAINER, HALF GRATE ONCONDENSATE RECEPTORS, FULL
GRATE ON REMAINDER
NO
HOSE BIBBFREEZELESS
TRENCH DRAINSYSTEM YES
STAINLESS STEELGRATE - POLY
TRENCH
NDS TRENCH DRAIN SYSTEM: 2TRENCHES, 5 GRATES, AND 1
CATCH BASIN- -
PROVIDE WITH 2X(DS-224) ENDCAPS. CATCH BASIN SHALL
HAVE #1242 - 3" OUTLET. EACHTRENCH DRAIN SHALL BE
PROVIDED WITH TWO - 2FT SSADA GRATES. CATCH BASIN
SHALL BE PROVIDED WITH 1 -2FT SS ADA GRATE. TOTAL OF
5 GRATES IN ALL. GRATESHALL BE STAINLESS STEEL
PERFORATED MODEL - DS-226
TRENCH DRAIN GRATE SHALL BENON-REMOVABLE/VANDAL PROOF.PROVIDE WITH VANDAL RESISTANT
SCREWS AND TOOL (DS-650-VR).(INSTALL FOR A COMPLETE TRENCHDRAIN SYSTEM. TOTAL LENGTH OF
10 FT.PROVIDE 2X(DS-091) 4 FTSLOPED TRENCH DRAINS WITH 1 -
2FT - DS-340 CENTER CATCH BASINWITH BOTTOM 3" OUTLET.
NO
LIGATURE RESISTANTWATER CLOSET YES
304 STAINLESS STEELWITH WHITE POWDER
COAT EXTERIORFINISH
WHITEHALL MODEL"WH2142-ADA-W-EGE10
PROVIDE WHITEHALL LIGATURERESISTANT FLUSH VALVE AND
ACCESS PANEL MODEL:WH2898-ADA
FLOOR WASTE OUTLET.ATTACH FIXTURE TO WALL
PROVIDE WITH LIGATURERESISTANT SEAT COVER.
COLOR WHITE.(WH-LRSC-WHITE). PROVIDE
WITH WATER HAMMERARRESTOR .
1.28 GPF NO
LIGATURE RESISTANTADA WALL HUNG
LAVATORYYES SOLID SURFACE
POLYMER RESIN WHITEHALL MODEL: WH3775
WHITE HALL MODEL: WH3373LAIR-CONTROL, SINGLE TEMP,
METERING CONICAL SPRAYHEAD& PUSHBUTTONS. PROVIDE WITH
ASSE 1070 COMPLIANTTEMPERATURE-PRESSUREBALANCING MIXING VALVE.WHITEHALL MODEL: MXTP
WALL MOUNTED
PROVIDE WITH 17 GA. P-TRAP,CONCEALED ARM WALL
CARRIER, 1/4 TURN ANGLESTOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH ASSE 1070
TEMPERATURE LIMITING DEVICE .PROVIDE WCO.
NO
SINGLE TEMP HOSESUPPLY BOX WITHVACUUM BREAKER
NO STAINLESS STEEL ACORN MODEL: 8104PROVIDE WITH -SSLF (STAINLESS
STEEL LEAD FREE OPTION) WALL MOUNTED
PROVIDE WITH ACORNCONTROLS LEAD FREETHERMOSTATIC MIXING
VALVE. ASSE 1017 COMPLIANT.ACORN MODEL:MV-17-2.
PROVIDE WITH LOCKABLEACCESS PANEL. PROVIDE
WITH T&S BRASS SPRAYERMODEL: PG-35AV-CH01.
VALVE SHALL BE A REPLACEABLECARTRIDGE TYPE WITH
VANDAL-RESISTANT LOCKSHIELDBONNET, REMOVABLE LOOSE KEY
WHEEL HANDLE AND SCREWDRIVEROPERATED STOP.
NO
EXAM SINK YES STAINLESS STEEL ELKAYLRAD222255
WHITE HALL MODEL: WH3373LAIR-CONTROL, SINGLE TEMP,
METERING CONICAL SPRAYHEAD& PUSHBUTTONS. PROVIDE WITH
ASSE 1070 COMPLIANTTEMPERATURE-PRESSUREBALANCING MIXING VALVE.WHITEHALL MODEL: MXTP
COUNTER MOUNTED
PROVIDE WITH 17 GA. P-TRAP,TRUBRO ADA UNDER-SINK
TRAP AND SUPPLYPROTECTION, 1/4 TURN
ANGLE STOPS AND SUPPLIES
PROVIDE WITH 0.5 GPM AERATOR.PROVIDE WITH WALL CLEANOUT.
PROVIDE WITH ASSE 1070TEMPERATURE LIMITING DEVICE
FOR HOW WATER SUPPLY. PROVIDEWCO.
NO
MANUFACTURERS:FIXTURE: AMERICAN STANDARD, KHOLER
FAUCET: DELTA, AMERICAN STANDARD, T&S, CHICAGO
DRAIN: ZURN, J.R. SMITH, WATTS
GENERAL NOTES:A: REFER TO FLOOR PLANS FOR FIXTURE LOCATIONS.B: ALL FIXTURES SHALL BE APPROVED BY OWNER.
P1
P1a
P2
P3
P3a
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
P14
P16
P17
P18
P19
MEDICAL GAS OUTLETALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY " BEACONMEDAEZ MEDICAL" AND SHALL MATCH EXISTING SJRMC FACILITY REQUIREMENTS.
GAS SERVICE STOCK NUMBER (WALL) REMARKS
SERVICE OUTLET:THE ROUGH-IN ASSEMBLY SHALL BE OF MODULAR DESIGN AND INCLUDE GAS-SPECIFIC 16-GAUGE STEELMOUNTING PLATE DESIGNED TO PERMIT ON-SITE GANGING OF MULTIPLE OUTLETS, IN ANY ORDER, ON 5"CENTERLINE SPACING. A MACHINED BRASS OUTLET BLOCK SHALL BE PERMANENTLY ATTACHED TO THEMOUNTING BRACKET TO PERMIT THE 1/2" OD (3/8" NOMINAL) TYPE-K COPPER INLET TUBE SWIVEL 360° FORATTACHMENT TO THE PIPING SYSTEM. THE LATCH-VALVE ASSEMBLY SHALL INCLUDE A SINGLE COMPRESSIONSEAL PRIMARY VALVE, BE GAS SPECIFIC FOR THE LABELED SERVICE, AND ACCEPT ONLY CORRESPONDINGGEOMETRICALLY SHAPED HOSE AND APPARATUS ADAPTERS. A DIE CAST, LIGHT GRAY, EPOXY POWDER COATEDTRIM PLATE SHALL BE PROVIDED TO TRIM EACH WALL OUTLET AND TO FILL THE SPACE BETWEEN ADJACENTOUTLETS. THE TRIM PLATE SHALL ALLOW LATCH VALVES TO BE INDIVIDUALLY REMOVED FOR SERVICING.
*MANUFACTURED ACCORDING TO ALL APPLICABLE NFPA AND CGA STANDARDS.*REMOVABLE COVER PLATES PROVIDE EASY ACCESS FOR PERIODIC INSPECTION OR MAINTENANCE.*LISTED BY UNDERWRITERS LABORATORIES, INC.
*NOTE: OUTLET CONNECTION TYPE SHALL BE VERIFIED AND COORDINATED WITH OWNER FOR REQUIREDCONNECTION TYPE REQUIEMENTS PRIOR TO SUBMITTAL AND ORDERING.
O2 6-121020 BEACON MADAEZ QUICK CONNECT WALL OUTLETSVAC 6-121023 BEACON MADAEZ QUICK CONNECT WALL OUTLETS
SLIDE 6-121020
MEDICAL VALVE BOX SCHEDULE
TYPE(RECESSED)
TYPE OF GAS AND SIZE
REMARKSO2
MVB-1
N20 VAC N2O EVAC N
ALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY" BEACON MEDAEZ MEDICAL"
STOCKNUMBER
SHUT-OFF VALVES*BE FULL-PORT, BALL VALVES*BE THREE-PIECE CONSTRUCTION FOR EASY INSTALLATION AND MAINTENANCE*HAVE TEFLON SEALS FOR LONG-LASTING, SMOOTH, EASY OPERATION*BE DESIGNED FOR WORKING PRESSURES OF 400 PSI OR 29" VACUUM*HAVE BLOW-OUT PROOF STEM*BE CLEANED FOR OXYGEN SERVICE*BE AVAILABLE IN 1/2" THROUGH 4" DIAMETER SIZES WITH TYPE K COPPER TUBING EXTENSIONS BRAZED TO FLANGES*HAVE A CORROSION-RESISTANT BRONZE BODY*REQUIRE ONLY ONE QUARTER OF A TURN TO COMPLETELY OPEN OR CLOSE
VALVES BOXESVALVE BOXES WILL:*INCLUDE A 1-1/2" LINE PRESSURE MONITORING GAUGE*BE AVAILABLE TO ACCOMMODATE ONE TO FOUR VALVES OF VARIOUS SIZES*BE LABELED FOR GAS IDENTIFICATION*BE ENCLOSED WITH A TRANSPARENT WINDOW DISPLAYING THE FOLLOWING CAUTION PERNFPA 99 (1990) AND CSA Z-305.1-M1984, "CAUTION: MEDICAL GAS SHUT-OFF VALVES. DO NOTCLOSE EXCEPT IN EMERGENCY."
REFERTO MFG. 1/2" 1"
A
1/2"
A 6-121022 BEACON MADAEZ QUICK CONNECT WALL OUTLETS
MEDICAL GAS STATION SCHEDULEMANUFACTURED BY "BEACON MEDAEZ MEDICAL"
STATIONGAS SERVICES & NO. OF OUTLETS REMARKS
O2
MGS-1
N20 VAC N2 EVAC SLIDE
WALL MOUNTED
NOTE: ALL GAS OUTLETS SHALL MATCH EXISTING MANUFACTURER TYPE. GAS OUTLET SHALL BEAS MANUFACTURED BY "BEACON MEDAEZ MEDICAL" UNLESS OUTLET TYPE IS NOT AVAILABLE.
MEDICAL GAS ABBREVIATIONS SCHEDULEMANUFACTURED BY "BEACON MEDAEZ MEDICAL"
MGO MEDICAL GAS OUTLET
MGS MEDICAL GAS STATION
MVB MEDICAL VALVE BOX
LPA LINE PRESSURE ALARM
O2 OXYGEN
N2O NITROUS OXIDE
V VACUUM
EV EVAC
A MEDICAL AIR
N NITROGEN
MAS MASTER ALARM STATION
1 1 11
A
EXISTING OUTLET CONNECTION TYPE AND MANUFACTURER SHALL BE VERIFIED ANDCOORDINATED WITH SJRMC FOR REQUIRED CONNECTION TYPE REQUIREMENTSPRIOR TO SUBMITTAL AND ORDERING.
MEDICAL GAS LINE PRESSURE ALARM PANEL
MARKTYPE OF GAS SERVICE
REMARKSO2
LPA-1
N20 VAC N2O EVAC N
ALL EQUIPMENT USED IN THIS SCHEDULE SHALL BE AS MANUFACTURED BY" BEACON MEDAEZ MEDICAL"
STOCKNUMBER
THE AREA PANEL SHALL CONSIST OF A POWER MODULE, DIGITAL MODULE, AND SENSORMODULE. THE POWER MODULE SHALL BE CAPABLE OF SUPPORTING UP TO EIGHT DIGITALMODULES AND CONVERTING 115/120 VAC TO LOW VOLTAGE DC. THIS MODULE SHALL CONTAINA FUSE TO PROTECT THE SYSTEM FROM VOLTAGE AND AMPERAGE SURGES AND A YELLOWPOWER ON INDICATOR THAT ILLUMINATES WHEN ELECTRICAL POWER IS AVAILABLE. DIGITALSHALL BE USED AS EITHER A MASTER ALARM OR AREA ALARM AND INCORPORATE A DIGITALLIQUID CRYSTAL DISPLAY (LCD) THAT CONTINUOUSLY INDICATES THE PRESSURE OR VACUUMIN THE SEGMENT OF THE PIPING SYSTEM BEING MONITORED. SENSOR MODULE SHALLCONTAIN A TRANSDUCER CAPABLE OF PROVIDING CALIBRATED SIGNALS TO THE DIGITALMODULE. SENSOR MODULES SHALL BE GAS SPECIFIC AND CAPABLE OF MOUNTING DIRECTLYIN THE MEDICAL GAS PIPELINE OR IN STANDARD WALL CONSTRUCTION.
*INCLUDES DRY CONTACT RELAYS (NO/MC) FOR CONNECTION OF REMOTE ALARMS.*COMPLETELY FACTORY ASSEMBLED AND PREWIRED.*LED INDICATOR LIGHTS PROVIDE FULL VISIBILITY WITH EXTENDED SERVICE LIFE.
REFERTO MFG. X X
A
X
LPA-2 REFERTO MFG. X X X
NEAR RECEPTION 1018
MVB-2 REFERTO MFG. 1/2" 1" 1/2"
CORRIDOR 1020 NEARTRIAGE 1019CORRIDOR 1071 NEARNURSE STATION 1073
NEAR NURSE STATION 1073
MGS-2 1 1 11ALL MGS-2STATIONS/OUTLETS SHALL BETAMPER PROOF/VANDALRESISTANT
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
PLUMBINGSCHEDULES
P6-01
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
ISOLATED GROUND DUPLEX RECEPTACLE
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERC
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
PULL BOX
PUSH BUTTON
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
METER
THERMOSTAT
ATS AUTOMATIC TRANSFER SWITCH
ONE-LINE DIAGRAM SYMBOLS
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
DISCONNECT SWITCH
FUSE
CIRCUIT BREAKER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
METER
SURGE SUPPRESSION DEVICE
VOLT-METER
SELECTOR SWITCH
GROUND
GF GROUND FAULT PROTECTION
AMP-METER
ST SHUNT TRIP
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COLD WATER GROUND CONNECTION
BUILDING STEEL GROUND CONNECTION
TIMER SWITCH
MULTI-OUTLET PLUG STRIP
TIME CLOCK
PHOTO-CELL
SWITCH
THERMAL OVERLOAD SWITCH
VARIABLE SPEED SWITCH
KEY SWITCH
LIGHTING FIXTURE SYMBOLSRECESSED LIGHTING FIXTURE
WALL MOUNTED LIGHT
WALL MOUNTED UP-LIGHT
PENDANT MOUNTED LIGHT
SURFACE MOUNTED LIGHT
DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE
MONO-POINT LIGHTING FIXTURE
RECESSED STEP LIGHT
FLUORESCENT STRIP LIGHT
WALL MOUNTED LINEAR FLUORESCENT LIGHT
RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER
FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT
WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
EMERGENCY LIGHTS
CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
LIGHTING CONTROL SYMBOLS
EXTERIOR POLE MOUNTED LIGHT
EXTERIOR POST (BOLLARD) MOUNTED LIGHT
DAYLIGHT PHOTO SENSORDL
KEY SWITCH
LV
VARIABLE SPEED SWITCH
DIMMER
THREE-WAY DIMMER
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR/SWITCH
THERMAL OVERLOAD SWITCH
OCCUPANCY SENSOR - WALL MOUNTED
OCCUPANCY SENSOR - CORRIDOR CEILING MOUNTED
S
S3
ST
SO
D3
D
SV
SK
SJS4
SKSV
ST
S
PC
TC
TS
A
V
SS
M
T
C
T
PB
CB
N
--
J
J
J
ABBREVIATIONSPOWER SYMBOLSSINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
NOTE:ALL SYMBOLS SHOWN ON LEGEND ARENOT NECESSARILY USED.
ELECTRICAL SYSTEMS LEGEND
OS
OS OCCUPANCY SENSOR - CEILING MOUNTED
OS
NOTES:· LIGHT LINEWEIGHT INDICATES EXISTING.
· HATCHED AREAS INDICATE DEMOLITION.
· 'C' ADJACENT TO A DEVICE INDICATESMOUNTING ABOVE COUNTERTOP.
AFC
AFF
AFG
AHJ
- ABOVE FINISHED CEILING
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AUTHORITY HAVING JURISDICTION
AL - ALUMINUM
AWG - AMERICAN WIRE GAUGE
BFG
BMS
BAS - BUILDING AUTOMATION SYSTEM
- BELOW FINISH GRADE
- BUILDING MANAGEMENT SYSTEM
C
CATV
CCTV
- CONDUIT
- COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM
- CLOSED CIRCUIT TELEVISION
CKT - CIRCUIT
CT - CURRENT TRANSFORMER
DISP - GARBAGE DISPOSAL
DW - DISHWASHER
(E) - EXISTING
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
GFI
FA
FACP
GRD
GC
- FIRE ALARM
- FIRE ALARM CONTROL PANEL
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND
IAW IN ACCORDANCE WITH-
IC
IDF
IG
IR
LAN
- INTERMEDIATE CROSS-CONNECT
- INTERMEDIATE DISTRIBUTION FRAME
- ISOLATED GROUND
- INFRARED
- LOCAL AREA NETWORK
NIC
MDF
(N)
MAIN DISTRIBUTION FRAME-
NEW-
NOT IN CONTRACT-
NL NIGHT LIGHT-
NTS NOT TO SCALE-
OC
PA
ON CENTER-
PUBLIC ADDRESS-
REF REFRIGERATOR-
TVSS
TTB TELECOMMUNICATIONS TERMINAL BOARD-
TRANSIENT VOLTAGE SURGE SUPPRESSOR-
TVTB TELEVISION TERMINAL BOARD-
UG
UNO
W
V
UNDERGROUND-
UNLESS NOTED OTHERWISE-
VOLT-
WATT-
WP
XP
WAN
WLAN
WAP
WIDE AREA NETWORK-
WIRELESS ACCESS POINT-
WIRELESS LOCAL AREA NETWORK-
WEATHERPROOF-
EXPLOSIONPROOF-
+18"DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS)MOUNTING HEIGHT TO CENTERLINE OF-
C
LOUDSPEAKER BAR - LEFT/CENTER/RIGHT
LOUDSPEAKER BAR - STEREO
LOUDSPEAKER - POWERED SUBWOOFER
LOUDSPEAKER BAR - CENTER CHANNEL
FIRE ALARM SYMBOLSFIRE ALARM CONTROL PANEL
REMOTE ANNUNCIATOR PANEL
SMOKE DETECTOR
HEAT DETECTOR
COMBO SMOKE/HEAT DETECTOR
FIRE ALARM HORN
FIRE ALARM STROBE
FIRE ALARM COMBO HORN/STROBE
FIRE ALARM PULL STATION
F FIRE ALARM SPEAKER
S FIRE ALARM COMBO SPEAKER/STROBE
FIREMAN'S PHONE JACK
DUCT DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
FIRE/SMOKE DAMPERFSD
FT
FF
F
F
H
H
ANN
FACP
H
SMOKE DETECTOR SOUND BARRIERSB
COSMOKE DETECTOR W/ CARBON MONOXIDE
BDT
BDR
BEAM TYPE SMOKE DETECTOR TRANSMITTER
BEAM TYPE SMOKE DETECTOR RECEIVER
INDIVIDUAL ADDRESSABLE MODULE
MONITORED RELAY
POST-INDICATOR VALVE
CARBON MONOXIDE DETECTOR
PIV
MR
IAM
CO
FIRE ALARM CHIME
FIRE ALARM CHIME/STOBE
REMOTE TESTER SWITCHRTS
CTR
LR
LCR
S
TELEVISION OUTLET - FLOORBOX
AUDIOVISUAL OUTLET - CEILING MOUNTED
AUDIOVISUAL OUTLET - WALL MOUNTED
AUDIOVISUAL OUTLET - FLOORBOX
AV
AV
TELEVISON OUTLET - CEILING MOUNTED
TELEVISION OUTLET - WALL MOUNTED
LOUDSPEAKER - CEILING MOUNTED
LOUDSPEAKER - WALL MOUNTED
MICROPHONE OUTLET - FLOORBOX
MICROPHONE OUTLET - WALL MOUNTED
AUDIOVISUAL SYMBOLS
SPEAKER ZONE HOMERUN
VIDEO PROJECTOR
TV
AV
PROJECTION SCREEN, TELEVISION, OR OTHER DISPLAY EQPT
SPK LOUDSPEAKER OUTLET
M
INTERACTIVE (ELECTRONIC) WHITEBOARD
S
S
TV
TV
M
LOW TEMPERATURE SENSORLT
GENERAL NOTES:1. THESE DRAWINGS ACCOMPANY THE CONSTRUCTION DOCUMENT
SPECIFICATIONS..
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURALDRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.
3. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE ASINDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTSREQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS.
4. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVEDBY OWNER - IN WRITING. WORK WHICH COULD RESULT IN ANACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BEPERFORMED WITH THE OWNER'S MAINTENANCE PERSONNELADVISED OF SUCH WORK.
5. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURINGCONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLEGENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAINCONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLEEQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL.
6. REVIEW ARCHITECTURAL, MECHANICAL AND OTHER DRAWINGSPRIOR TO BID.
7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THESATISFACTION OF THE ARCHITECT.
8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THELATEST EDITIONS OF LOCAL, STATE OF NEW MEXICO, AND NATIONALCODES AND ORDINANCES.
9. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
10. PROVIDE WITH SHOP DRAWING SUBMITTAL, ¼” SCALE LAYOUTDRAWINGS OF ROOMS WITH ELECTRICAL SWITCHBOARDS ANDTRANSFORMERS. LAYOUTS SHALL SHOW LOCATIONS OF, AND SHALLBE COORDINATED WITH MECHANICAL EQUIPMENT. ALL EQUIPMENTSHALL BE DRAWN TO SCALE.
11. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FORMATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS AREASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, ORINSTALLATION METHODS.
12. FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT AREREMAINING TO BE RECONNECTED TO NEW OR EXISTINGSWITHBOARDS/PANELBOARDS. PROVIDE SWITCHES, RECEPTACLES,CONDUIT, WIRE, ETC. AS REQUIRED, TO RESTORE CONTINUITY OFCIRCUIT(S).
13. EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOREXISTING BUILDINGS ARE TO BE NOTED “FOR GUIDANCE ONLY”. THEELECTRICAL CONTRACTOR TO FIELD CHECK ALL EXISTINGCONDITIONS PRIOR TO BIDDING AND TO INCLUDE IN HIS BID ANALLOWANCE FOR REMOVAL AND/OR RELOCATION OF EXISTINGCONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT ASINDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE ANDADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHERWORK AS REQUIRED.
14. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TOMECHANICAL AND ELECTRICAL DEMOLITION DRAWINGS FORLOCATION AND EXTENT OF DEMOLITION REQUIRED. CONTRACTORSHALL VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORKINVOLVED. PROVIDE LABOR AND MATERIALS REQUIRED TO MAINTAINAND/OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS.
15. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTINGUNUSED CONDUIT, WIRE, CABLE, J-BOXES, RECEPTACLES, SWITCHES,LIGHTS, FIRE ALARMS DEVICES, ETC. COMPLETE WITH ASSOCIATEDCIRCUITING TO SOURCE. WHERE IT IS NOT FEASIBLE TO REMOVETHE ABOVE, OUTLET SHALL BE ABANDONED, WIRE REMOVED, ANDBLANK COVER PLATES PROVIDED.
16. ALL (E) EQUIPMENT BEING REMOVED SHALL BE DISCARDED INACCORDANCE WITH APPLICABLE EPA REQUIREMENTS.
17. EXISTING ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BERETURNED TO THE OWNER, EXCEPT FOR THOSE ITEMS BEINGRELOCATED.
18. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BYOTHERS PRIOR TO ROUGH-IN.
19. REVIEW MECHANICAL DRAWINGS AND PROVIDE LIGHTS, SWITCHES,RECEPTACLES, TELECOM OUTLETS, EQUIPMENT CONNECTIONS, ETC.AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS.
20. INSTALL ALL MATERIALS IN ACCORDANCE WITH THEMANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BEBROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TOINSTALLATION.
21. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITHMANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, ANDINSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOPROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENTACTUALLY SUPPLIED.
22. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENTWHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDEDUNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDEDUNDER THIS SECTION.
23. WHERE THE RE-USE OF EXISTING CONDUITS, WIRES, DEVICES, ETC, ISPERMISSIBLE, MAKE CERTAIN THAT THE WIRING FOR SAME ISCONTINUOUS FROM OUTLET TO OUTLET AND THAT SUCH CIRCUIT ORSYSTEMS SHALL PASS THROUGH NO OUTLET OR JUNCTION BOXESWHICH MAY BE RENDERED INACCESSIBLE BY THE STRUCTURALCHANGES TO BE MADE TO THE BUILDING. EXISTING CONDUITS, WIRE,DEVICES. WHICH ARE NOT INDICATED FOR REUSE SHALL BECOMETHE PROPERTY OF THIS CONTRACTOR HOWEVER LIGHTINGFIXTURES, PANEL FUSED SWITCHES, CIRCUIT BREAKERS, FIRE ALARMEQUIPMENT, WIRE, ETC. SHALL BECOME THE PROPERTY OF THEOWNER.
24. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED ORLABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY.
25. WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20AMPERES FOR LIGHT SWITCHES, AND 20 AMPERES FOR DUPLEXRECEPTACLES. THE COLOR OF THE DEVICES AND COVER PLATESSHALL BE AS DIRECTED BY ARCHITECT.
26. ALL WIRING SHALL BE INSTALLED IN LISTED METALLICRACEWAYS. EMT FITTINGS SHALL BE MALLEABLE IRON ORSTEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE. MINIMUMCONDUIT SIZE IS ¾”. FOLLOW NEC FOR MAXIMUM NUMBER OFCONDUCTORS PER CONDUIT. CONDUIT SHALL BE OF SUFFICIENTSIZE AND CONDUCTOR QUANTITY SHALL BE LIMITED TO ELIMINATETHE NEED TO DE-RATE CONDUCTORS. METAL CLAD CABLE IS NOTPERMITTED.
27. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERALUSE. WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRESHALL BE COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZESINDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREECELSIUS AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FORHIGHER AMBIENT INSTALLATIONS.
28. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTINGAND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT.
29. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES ANDNUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALLBE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS.
30. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHERVIBRATING EQUIPMENT SHALL BE SEAL TITE FLEX AND APPROVEDFITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICESTO DUCTWORK OR MECHANICAL EQUIPMENT.
31. FOR LOW VOLTAGE WIRING ROUTED IN CONDUIT , PROVIDE PULLBOXES WHERE THE ROUTE IS LONGER THAN 100 FEET, OR HAS MORETHAN TWO (2) 90 DEGREE BENDS.
32. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTSSHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKECORRECTIONS NECESSARY AT NO COST TO OWNER.
33. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALSAND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FORA PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTSSHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
34. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FORCONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES,MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE.
35. MAINTAIN A CURRENT SET OF AS-BUILT RECORD DRAWINGS WHICHSHALL BE AVAILABLE FOR REVIEW DURING ENGINEER'S SITEOBSERVATIONS. UPON COMPLETION, PROVIDE RECORD DRAWINGSTO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS,CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC.
36. FOR 120V BRANCH CIRCUITS THAT EXCEED 75' IN LENGTH AND 277VBRANCH CIRCUITS THAT EXCEED 175' IN LENGTH INCREASE TO NEXTWIRE SIZE. (12 AWG GOES TO 10 AWG).
37. THIS RENOVATION PROJECT IS TO BE EXECUTED IN MULTIPLEPHASES. SEE ARCHITECTURAL PLANS FOR PROJECT PHASING.
FIRE ALARM BELLB
NO SCALETYPICAL DEVICE ALIGNMENT
EQ EQ
6"MIN.
℄
℄
℄
DOOR WINDOW
EQ EQ
℄
LIGHTINGCONTROL ℄
℄
OFFSET COMMUNICATIONSDEVICES FROM POWERDEVICES TO EITHEROPPOSITE SIDE OF STUD BAY,OR ADJACENT STUD BAY.
NOTES:1. IF ALIGNMENT OF DEVICES INDICATED HERE IS IN CONFLICT
WITH ADA REQUIREMENTS DUE TO INSTALLATION DETAIL, ADADIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALLSUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONSSHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.
EQ
BACKSPLASH
ABOVECOUNTERDEVICE
RECEPTACLE
COUNTERTOP
EQ
FINISHED FLOOR
FINISHED CEILING
6"MIN.
20"MAX.
ALIGN DEVICES (OUTLETS,CONTROLS, ETC.)VERTICALLY. DO NOTVERTICALLY ALIGN POWERAND COMMUNICATIONSDEVICES SIMULTANEOUSLY.
NORMAL CALL DOME LIGHT - WALL MOUNT
NURSECALL SYMBOLS
Z
J
NC
NCTC
T
B
D
P
Z
2
1
NORMAL CALL DOME LIGHT - SINGLE LED - WALL MOUNT
NURSE CALL ZONE LIGHT - WALL MOUNT
NORMAL CALL DOME LIGHT - CEILING MOUNT
NORMAL CALL DOME LIGHT - SINGLE LED - CEILING MOUNT
NURSE CALL ZONE LIGHT - CEILING MOUNT
DOMELESS CONTROLLER - ABOVE MOUNT
NURSE CALL MASTER STATION
NURSE CALL TERMINAL CABINET
CODEBLUE EMERGENCY STATION
TOILET EMERGENCY STATION w/ PULL CORD
STAFF EMERGENCY STATION
SINGLE PATIENT STATION
DOUBLE PATIENT STATION
STAFF PRESENCE PAD
STAFF STATION
DUTY STATION
PATIENT BED HANDHELD CONTROL
SE
CB
SS
'*' ISSUED FOR INFORMATION ONLY' ' NOT PART OF SET' ' ISSUED AS PART OF A SETISSUE LOG KEY:
#
DA
TE
ISSUE LOG
ELECTRICAL SHEET INDEX
TITLE
ELECTRICAL COVER SHEETE0-01
02.2
2.20
1810
0% D
D
ELECTRONIC SAFETY & SECURITY SYMBOLS
L
CEILING MOUNTED CAMERA
WALL MOUNTED CAMERA
MAGNETIC DOOR CONTACT SWITCH
ADA ACCESS CONTROL MAIN PANELADA
CR CARD READER
S ELECTRIC LOCK - STRIKE
LM ELECTRIC LOCK - MAGNETIC
LR ELECTRIC LATCH / ROD RETRACTOR
SM MAGNETIC DOOR CONTACT SWITCH
PANIC BUTTONP
INTRUSION MOTION SENSOR
SECURITY KEYPAD
MON CCTV MONITOR
ACCESS CONTROL MAIN PANELACP
EXIT PANIC/CRASH BAR SENSORREX
SECURITY CENTRAL PROCESSING UNITCPU
SECURITY/ACCESS CONTROL WORKSTATIONWS
K
I
MULTI-OUTLET WIREWAY
VOICE/DATA SYMBOLS
COMBO VOICE/DATA OUTLET (1 DATA, 1 VOICE UNO)
(1) VOICE WALL OUTLET
(1) DATA WALL OUTLET
(1) VOICE FLOOR OUTLET
(1) DATA FLOOR OUTLET
COMBO VOICE/DATA FLOOR OUTLET
VOICE/DATA/FIBER OUTLETOF
POINT OF SALE (POS) OUTLETPOS
AUTOMATED TELLER MACHINE (ATM) STATIONATM
PUBLIC PAYPHONE OUTLETPP
ELEVATOR PHONE OUTLETE
POWER/TELECOM POLE
WIRELESS LAN (WI-FI) ACCESS POINT OUTLET (2 CABLES)
FAX/COPIER OUTLET
EMERGENCY SERVICES PHONE OUTLETEM
F
C
EC - ELECTRICAL CONTRACTOR
MC MECHANICAL CONTRACTOR-
PC PLUMBING CONTRACTOR-
ELECTRICAL LIGHTING PLANE1-01
ELECTRICAL POWER PLANE1-02
ELECTRICAL SPECIAL SYSTEMS PLANE1-03
ELECTRICAL DIAGRAMSE5-01
ELECTRICAL ONE-LINE DIAGRAM AND SCHEDULESE0-02
MECHANICAL EQUIPMENT WIRING AND CONNECTIONS
ITEM FURNISHEDUNDER
SET IN PLACE ORMTD. UNDER
WIRED /CONNECTED
UNDER
1. EQUIPMENT MOTORS AND THERMAL OVERLOADS, RESISTANCEHEATERS MD MD ED
2. VFDs, MOTOR CONTROLLERS; MAGNETIC STARTERS, REDUCEDVOLTAGE STARTERS AND OVERLOAD RELAYS MD ED(a) ED
3.DISCONNECT SWITCHES (FUSED OR NON-FUSED), HP RATEDSWITCHES, THERMAL OVERLOAD SWITCHES AND FUSES, ANDMANUAL OPERATING SWITCHES
ED(a) ED(a) ED
4.
PUSHBUTTON STATIONS, PILOT LIGHTS, MULTI-SPEEDSWITCHES, FLOAT SWITCHES, THERMOSTATS, CONTROLRELAYS, TIMECLOCKS, CONTROL TRANSFORMERS, CONTROLPANELS, MOTOR VALVES, DAMPER ACTUATORS, SOLENOIDVALVES, EP AND PE SWITCHES AND INTERLOCKS
MD MD MD(b)
5. 120 VOLT POWER FOR BAS PANELS, FIRE PROTECTION ANDBOILER CONTROLS ED ED ED
6. FIRE/SMOKE DAMPERS AND ELEVATOR VENT DAMPERS MD MD ED(c)
MD = MECHANICAL DIVISIONED = ELECTRICAL DIVISION
NOTES:
( a ) IF FURNISHED AS PART OF FACTORY-WIRED EQUIPMENT, THEN WIRING AND CONNECTIONS ONLY BY ED
( b ) IF ANY OF THESE DEVICES CARRY THE FULL LOAD CURRENT TO ANY MOTOR THEY SHALL BE CONNECTED BY ED. CONTROLDEVICES CARRYING FULL LOAD CURRENT FURNISHED BY MD AND WIRED BY ED SHALL BE LOCATED AT THE DEVICE BEINGCONTROLLED, UNLESS SHOWN ON DRAWINGS OR MUTUAL AGREEMENT IS MADE BETWEEN THE CONTRACTORS WITH NOCHANGE IN THE CONTRACT PRICE.
( c ) WIRING FROM ALARM CONTACTS TO ALARM SYSTEM BY ED; ALL CONTROL FUNCTION WIRING BY MD. DUCT DETECTORSFURNISHED BY ED, SET IN PLACE BY MD
GENERAL NOTE: THE ABOVE LIST DOES NOT ATTEMPT TO INCLUDE ALL COMPONENTS. ALL ITEMS NECESSARY FOR A COMPLETESYSTEM SHALL BE INCLUDED IN THE BASE CONTRACT.
04.3
0.20
1895
% C
D
E1-04
ELECTRICAL DEMOLITION PLAN
05.2
5.20
18PE
RMIT
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALCOVER SHEET
E0-01
SCALE:1 PARTIAL ELECTRICAL ONE-LINE DIAGRAMNTS
PANELDPDA
PANELDPAE
FIRST FLOOR
PANELDPC
PANELDPN
PANELDPM
SWITCHBOARDEQUIPMENTBRANCH(NORTH)
BASEMENT
UPPER LEVEL
SWITCHBOARDCRITICALBRANCH
SWITCHBOARDEQUIPMENTBRANCH(SOUTH)
SWITCHBOARDNORMALPOWER
SWITCHBOARDLIFE SAFETYBRANCH
T
PANELLSL
PANELLSP
PANELNL
PANELCL
T
PANELNP
PANELNP1
T
PANELCP
T
PANELNP2
T
PANELME
PANEL: CP (EXISTING)2-SECTION
VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225
LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:
NO.LOAD
TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER
TYPE LOAD DESCRIPTIONLOAD
NO.A B C POLE TRIP A B C TRIP POLE A B C
1 1200 L EXAM LIGHTS 1 20 + 20 1 E TIME CLOCK 200 23 400 M ER DOOR ENTRY 1 20 + 20 1 L HELI DECK LIGHTS 1200 45 360 R RECEP SECURITY 1 20 + 20 1 L HELI DECK LIGHTS 1200 67 1440 R RECEP EXAM 14-15 1 20 + 20 1 R RECEP EXAM 8-9 1440 89 1440 R RECEP EXAM 12-13 1 20 + 20 1 R RECEP EXAM 6-7 1440 1011 1440 R RECEP EXAM 10-11 1 20 + 20 1 R RECEP EXAM 4-5 1440 1213 180 R RECEP NOURISHMENT 1 20 + 20 1 R RECEP MEDICATION 180 1415 540 R RECEP ALCOVE 1108 1 20 + 20 1 R RECEP MEDICATION 180 1617 720 R RECEP EXAM 1 1 20 + 20 1 R RECEP MEDICATION 180 1819 720 R RECEP EXAM 2 1 20 + 20 1 R RECEP N NURSE STA 540 2021 900 R RECEP OB EXAM 1 1 20 + 20 1 R RECEP N NURSE STA 360 2223 900 R RECEP OB EXAM 2 1 20 + 20 1 R RECEP N NURSE STA 1080 2425 400 E ISOLATION RM MONITOR 1 20 + 20 1 R RECEP RM 1048 ANTE 180 2627 1080 R WIRE MOLD NURSE STA 1 20 + 20 1 R RECEP EXAM 16-17 1440 2829 540 R RECEP S NURSE STA 1 20 + 20 1 R RECEP PHYSH RM 540 3031 360 R RECEP S NURSE STA 1 20 + 20 1 R RECEP TRAUMA 1 1080 3233 1080 R RECEP S NURSE STA 1 20 + 20 1 R RECEP TRAUMA 1 1080 3435 1080 R RECEP TRAUMA 2 1 20 + 20 1 M AUTO DOOR ENTRY 800 3637 1080 R RECEP TRAUMA 2 1 20 + 20 1 R RECEP RECEPTION 720 3839 360 R WP RECEP 1 20 + 20 1 R RECEP TRIAGE 720 4041 360 R RECEP PYXIS EQUIP 1 20 + 20 1 R RECEP TRIAGE 360 4243 360 R IT CLOSET SOUTH 1 20 + 20 1 R OUTSIDE ED #4 360 4445 360 R IT CLOSET SOUTH 1 20 + 20 1 R RECEP RECEPTION 720 4647 180 R HALLWAY EXIT 1 20 + 20 1 M DOOR AMB ENTRY 800 4849 720 R RECEP FAST TRACK 1 20 + 20 1 R RECEP FAST TRACK 720 5051 720 R RECEP FAST TRACK 1 20 + 20 1 E PNUMATIC TUBE NS 600 5253 180 R RECEP PATIENT MNTR 1 20 + 20 1 R RECEP ALCOVE 1062 180 5455 720 R RECEP MIDLAND/QA 1 20 + 20 1 R RECEP ALCOVE 1076 180 5657 360 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP ASSESS 720 5859 360 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP MULTI-PAT CP 360 6061 540 R RECEP RESULTS WAIT 1 20 + 20 1 R FAST TRACK 2 BED RM 1080 6263 560 R RECEP SUPPLY EQUIP 1 20 + 20 1 R RECEP TREATMENT 540 6465 540 R RECEP SUPPLY EQUIP 1 20 + 20 1 R RECEP TREATMENT 540 6667 1200 E
250V OUTLET X-RAY 2 15 + 20 1 R RECEP TREATMENT 540 6869 1200 E + 20 1 E DOOR POWER 1000 7071 540 R FAST TRK COMPS 1 20 + 20 1 E DOOR POWER 800 7273 900 R FAST TRK PRINTER 1 20 + SPACE 7475 SPACE + SPACE 7677 SPACE + SPACE 7879 SPACE + SPACE 8081 2400 E
FILM PROCESSOR 2 30 + SPACE 8283 2400 E + SPACE 84
LOAD TYPE PANEL TOTAL FEED THRUTOTAL
SUBFEEDTOTAL
FEEDERSUBTOTAL DEMAND FEEDER TOTAL
GENERAL NOTES:A. CRITICAL BRANCH POWER
(L) LIGHTING 3600 3600 125% 4500 B. SQUARE D NQOD
(R) RECEPTACLES 40520 40520 NEC 220 25260 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE
(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.
(M) MOTORS (ALL) 2000 2000 100% 2000 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.
(E) EQUIPMENT 10200 10200 100% 10200 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1) PROVIDE NEW 20A CB IN SPACE 72.
PANEL TOTAL (KVA): 42.0 (2)
(3)
PANEL TOTAL (A): 117 (4)
(5)
PANEL: NP (EXISTING)2-SECTION
VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225
LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:
NO.LOAD
TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER
TYPE LOAD DESCRIPTIONLOAD
NO.A B C POLE TRIP A B C TRIP POLE A B C
1 1080 R EXAM 14, 15 1 20 + 20 1 R CATV 360 23 900 R EXAM 12, 13 1 20 + 20 1 R RECEP EXAM 8, 9 900 45 1080 R EXAM 10, 11 1 20 + 20 1 R RECEP EXAM 6, 7 900 67 500 A NOURISH REFRG 1 20 + 20 1 R RECEP EXAM 4, 5 900 89 500 A NOURISH REFRG 1 20 + 20 1 R RESTROOM RECEPS 540 1011 720 R RECEP MEDICATION 1 20 + 20 1 R RECEP SOILED UTILITY 1080 1213 900 R RECEP ALCOVE 1088 1 20 + 20 1 SPARE 1415 1080 R RECEP OB EXAM 1 1 20 + 20 1 R RECEP EXAM 1 720 1617 1080 R RECEP OB EXAM 2 1 20 + 20 1 R RECEP EXAM 2 720 1819 1080 R EXAM 16, 17 1 20 + 20 1 M EXHAUST FANS EF-1 696 2021 400 A RECEP STAFF LOUNGE 1 20 + 20 1 M EXHAUST FANS EF-2 696 2223 1000 A RECEP STAFF LOUNGE 1 20 + 20 1 SPARE 2425 800 A RECEP STAFF LOUNGE 1 20 + 20 1 SPARE 2627 900 R RECEP PHYSH RM 1 20 + 20 1 SPARE 2829 720 R RECEP TRAUMA 1 1 20 + 20 1 R RECEP DARK RM/CNTRL 720 3031 720 R RECEP TRAUMA 1 1 20 + 20 1 R RECEP TRAUMA 2 900 3233 240 R ELEV PIT RECEP & LT 1 20 + 20 1 R RECEP TRAUMA 2 900 3435 270 L ELEV EQUIP RM LIGHTS 1 20 + 20 1 R RECEP J/C ELEV LOBBY 1260 3637 9500
PANEL NP1 3 100+ 20 1 R BLANKET WARMER 1500 38
39 10840 + 20 1 A ICE-MACHINE 1340 4041 10140 + 20 1 A U.C. REFRIG, CONV. 580 4243 1250 E HAND DRYER 1 20 + 20 1 M PNUMATIC TUBE 1176 4445 1250 E HAND DRYER 1 20 + 20 1 A HOT/COLD WATER 1500 4647 1250 E HAND DRYER 1 20 + 20 1 SPARE 4849 SPARE 1 20 + 20 1 SPARE 5051 1200 R VENDING MACHINE 1 20 + 20 1 SPARE 5253 1200 R VENDING MACHINE 1 20 + 20 1 SPARE 5455 900 R RECEP RM #3 1 20 + 20 1 R WIRE MOLD EQUIP STR 900 5657 540 R RECEP SECURITY 1 20 + 20 1 R WIRE MOLD EQUIP STR 1080 5859 360 R RECEP WAITING 1 20 + 20 1 R BLK TRAUMA 1080 6061 720 R BATHROOM SLEEP 1 20 + 20 1 R RED ED OPEN 720 6263 1260 R RECEP SLEEP 1 20 + 20 1 R RECEP TRIAGE/TRACK 1080 6465 1000 E VACUUM TUBE 1 20 + 20 1 R RECEP STAFF LOUNGE 720 6667 1000 E RESPITORY EQUIP CLT 1 20 + 20 1 R NORTH HALL TV 360 6869 600 E IT SPLIT UNIT 1 20 + 20 1 R CENTER HALL TV 360 7071 360 R RECEP TVS TRACK 1 20 + 20 1 R SOUTH HALL TV 360 7273 1080 R RECEP RR/TELE/QUIET 1 20 + 20 1 R RECEP TREATMENT 900 7475 900 R RECEP SUPPLY/EQUIP 1 20 + 20 1 R RECEP TREATMENT 1260 7677 720 R POWER STRIP HALLWAY 1 20 + 20 1 R RECEP TREATMENT 1260 7879 720 R POWER STRIP HALLWAY 1 20 + 20 1 SPARE 8081 720 R RECEP EQUIP STORAGE 1 20 + SPACE 8283 SPARE 1 20 + 20 1 R HOUSE KP, DRINK FTN 720 84
LOAD TYPE PANEL TOTAL FEED THRUTOTAL
SUBFEEDTOTAL
FEEDERSUBTOTAL DEMAND FEEDER TOTAL
GENERAL NOTES:A. NORMAL BRANCH POWER
(L) LIGHTING 270 1280 1550 125% 1938 B. SQUARE D NQOD
(R) RECEPTACLES 43380 14184 57564 NEC 220 33782 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE
(LM) LARGEST MOTOR 0 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.
(M) MOTORS (ALL) 2568 11076 13644 100% 13644 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.
(E) EQUIPMENT 6350 2500 8850 100% 8850 SPECIFIC NOTES:(A) APPLIANCES 6620 0 6620 3 5958 (1) PROVIDE GFCI CIRCUIT BREAKER IN SPACE 84
PANEL TOTAL (KVA): 64.2 (2)
(3)
PANEL TOTAL (A): 178 (4)
(5)
PANEL: NP1 (EXISTING)VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 225
LOCATION: ELEC CLOSET MAIN: MLOMOUNTING: SURFACE MINIMUM AIC:
NO.LOAD
TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER
TYPE LOAD DESCRIPTIONLOAD
NO.A B C POLE TRIP A B C TRIP POLE A B C
1 SPACE + SPACE 23 SPACE + SPACE 45 SPACE + SPACE 67 480 L X-RAY LIGHTS 1 20 + 20 1 X-RAY RECEP'S 720 89 SPACE + 20 1 X-RAY RECEP'S 720 1011 SPACE + SPACE 1213 SPACE + SPACE 1415 3300 M
AIR CURTAINAMB. ENTRY 3 40
+ SPACE 1617 3300 M + SPACE 1819 3300 M + 20 2 SPARE
2021 1000 E X-RAY (TIED TO 23) 1 20 + 2223 1000 E X-RAY 1 20 + 20 1 R CHART ROOM 900 2425 500 E ER DOORS 1 20 + 20 1 R CHART ROOM 900 2627 864 R GARDEN FOUNTAIN 1 20 + 20 1 R CHART ROOM 900 2829 800 L GARDEN LIGHTS 1 20 + 20 1 R CHART ROOM 900 3031 900 R RECEP CONSULT 1 20 + 20 1 R CHART ROOM 900 3233 720 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP VERTICAL 1080 3435 540 R RECEP MULTI-PATIENT 1 20 + 20 1 R RECEP VERTICAL 1260 3637 720 R RECEP REC/SCL/DOOR 1 20 + 20 1 R RECEP VERTICAL 1080 3839 1176 M ER HALLWAY EXHAUST 1 20 + 20 1 R RECEP VERTICAL 1080 4041 360 R ED TV MONITOR 1 20 + 20 1 R RECEP OFFICE/VERT 1080 42
LOAD TYPE PANEL TOTAL FEED THRUTOTAL
SUBFEEDTOTAL
FEEDERSUBTOTAL DEMAND FEEDER TOTAL
GENERAL NOTES:A. NORMAL BRANCH POWER
(L) LIGHTING 1280 1280 125% 1600 B. SQUARE D NQOD
(R) RECEPTACLES 14184 14184 NEC 220 12092 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE
(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.
(M) MOTORS (ALL) 11076 11076 100% 11076 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.
(E) EQUIPMENT 2500 2500 100% 2500 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 27.3 (2)
100A UPSTREAM BREAKER (3)
PANEL TOTAL (A): 76 (4)
(5)
WIRING SCHEDULE - COPPERAMPS
(2WG) (3WG) (4WG)
1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND
20 (2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C (4#12 & 1#12 G) 3/4"C
30 (2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C (4#10 & 1#10 G) 3/4"C
CONDUCTOR SIZES ARE BASED ON 60° TERMINATIONS LESS THAN 100A AND 75° TERMINATIONS GREATER THAN 100A
CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).
NOTE:ALL ITEMS ARE EXISTING TO REMAIN.ONE-LINE DIAGRAM SHOWN FORREFERENCE ONLY.
LUMINAIRE SCHEDULETYPE DESCRIPTION MOUNTING RECESS
DEPTHLED INPUT
WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFICNOTESLUMENS TEMP
R12x4 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 4000 3500 34 277 MARK WHSPR 2X4 4000LM 35K 90CRI
MIN10 MVOLT SWC
R22x2 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 3300 3500 30 277 MARK WHSPR 2X2 3300LM 35K 90CRI
MIN10 MVOLT SWC
R3 2x4 RECESSED FLANGED TROFFER, MINIMUM SECURITYCONFINEMENT GRADE, LED, 0-10V DIMMING RECESSED 3" 5500 3500 50 277 NEWSTAR 37M24-GJ-L2351-BB-27-DB
R4 2x2 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING RECESSED 4-1/2" 2000 3500 18 277 MARK WHSPR 2X2 2000LM 35K 90CRI
MIN10 MVOLT SWC
R5 4" DIA LED DOWNLIGHT, HAZE ALZAK CONE, WHITE TRIMRING, FLOOD DISTRIBUTION RECESSED 6" 1000 3500 16 277 JUNO IC4AL 10LM 35K 90CRI FL
MVOLT ZT 42L HZWH
R6 6" DIA LED DOWNLIGHT RETROFIT TRIM, WHITEREFLECTOR AND TRIM RING RECESSED 4-1/2" 1500 3500 20 277 JUNO JCLR6S 15LM 35K 90CRI
MVOLT ZT WWH
R7 2x4 RECESSED LED TROFFER, WHITE ALUMINUM FRAME,10% 0-10V DIMMING RECESSED 4-1/2" 3000 3500 25 277 MARK WHSPR 2X4 3000LM 35K 90CRI
MIN10 MVOLT SWC
R8 2x4 RECESSED FLANGED LED TROFFER, WHITEALUMINUM FRAME, 10% 0-10V DIMMING, 90+ CRI RECESSED 4-1/2" 4000 3500 34 277 MARK WHSPR 2X4 4000LM 35K 90CRI
MIN10 MVOLT SWC 3
W1 4' LINEAR LED VANITY, 1.5" SQUARE PROFILE DIFFUSER,WHITE
WALLSURFACE 888 3500 16 277 VODE 707-Z2-4/0-48-CM-AE-120-
0-Z-LO-35-S6-0-WH-0 2
S1 4' LED UTILITY STRIP WITH LENS SURFACE 3000 3500 25 277 LITHONIA ZL1N L48 SMR 3000LM FST MVOLT 35K 80CRI WH
S224" UNDER CABINET LED FIXTURE, HIGH-IMPACT ACRYLICLENS, ANTI-MICROBIAL WHITE SURFACE 1220 3500 12 277 SPECTRA HUC523-MVOLT-LED35-S1
LX12-AM
X1 EXIT SIGN, SINGLE FACE, WHITE THERMOPLASTIC BODY,GREEN LETTERS SURFACE N/A LED GREEN 2 277 LITHONIA LQM S W 3 G 120/277 1
X2 EXIT SIGN, DOUBLE FACE, WHITE THERMOPLASTIC BODY,GREEN LETTERS SURFACE N/A LED GREEN 2 277 LITHONIA LQM S W 3 G 120/277 1
GENERAL NOTES:A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT
QUOTE PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS ANDSPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES CONNECTED TO BATTERY INVERTER SYSTEM (SHOWN BY HATCH IN/OVER SYMBOL).C. ALL LEDS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:(1) INCLUDE EXIT DIRECTION ARROWS AS INDICATED ON PLAN.(2) INSTALL ABOVE MIRROR(S). COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS.(3) PROVIDE WITH MUD IN FLANGE.(4)
SCOPE OF WORKINCLUDES BRANCHCIRCUITS IN THESEPANELS ONLY.
TRANSFORMER75kVA 480/277V,208/120Y SEC
TRANSFORMER75kVA 480/277V,208/120Y SEC
DISCONNECTSWITCH 400A,225A FUSE
DISCONNECTSWITCH 200A,200A FUSE
SCOPE OF WORKINCLUDES BRANCHCIRCUITS IN THESEPANELS ONLY.
TRANSFORMER30kVA 480/277V,208/120Y SEC
PANEL: ME (EXISTING)VOLTAGE: 120/208V, 3PH, 4WMINIMUM BUS: 100
LOCATION: 2ND FLOOR MAIN: 100/3 CBMOUNTING: SURFACE MINIMUM AIC:
NO.LOAD
TYPE LOAD DESCRIPTIONBREAKER BUS BREAKER
TYPE LOAD DESCRIPTIONLOAD
NO.A B C POLE TRIP A B C TRIP POLE A B C
1 800 E FOAM RM HEATER EX 1 20 + 20 1 M N. BOILER FAN 696 23 800 E HEATER MECH RM 1 20 + 20 1 E BOILER CTL POWER 400 45 696 M EX-FAN NW MECH RM 1 20 + 20 1 M S. BOILER FAN 696 67 1200 E IT RACK UPS 1 20 + 20 1 M ELEV PIT PUMP 696 89 400 E WIND SOCK 1 20 + 20 1 M BOILER ROOM EX FAN 696 1011 400 E HVAC CONTROL PANEL 1 20 + 20 1 E TU WEST UNITS 950 1213 696 M CIRC PUMPS AHU 1 20 + 20 1 R RECEP FOPR AIR DRY 1080 1415 400 E C/P ON AHU 1 20 + 20 1 M EF6 696 1617 200 L ELEV CAB LIGHTS 1 20 + 20 1 ELEVATOR SHUNT TRIP 1819 400 E HVAC CONTROLS 1 20 + 20 1 M EF-3 696 2021 1200 E
CTL AIR COMP 3 15+ 20 1 E TU EAST UNITS 550 22
23 1200 E +30 3
MHANGER DOOR
2400 2425 1200 E + M 2400 2627
SPARE 2 40 + M 2400 2829 + SPACE 30
LOAD TYPE PANEL TOTAL FEED THRUTOTAL
SUBFEEDTOTAL
FEEDERSUBTOTAL DEMAND FEEDER TOTAL
GENERAL NOTES:A. EQUIPMENT BRANCH POWER
(L) LIGHTING 200 200 125% 250 B. SQUARE D NQOD
(R) RECEPTACLES 1080 1080 NEC 220 1080 C. NEW CIRCUITS SHOWN IN BOLD, USE EXISTING SPARE
(LM) LARGEST MOTOR 0 0 25% 0 OR CIRCUIT THAT IS NO LONGER IN USE.
(M) MOTORS (ALL) 12768 12768 100% 12768 D. EXISTING CIRCUITS NO LONGER USED RENAME 'SPARE'.
(E) EQUIPMENT 9900 9900 100% 9900 SPECIFIC NOTES:(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 24.0 (2)
(3)
PANEL TOTAL (A): 67 (4)
(5)
MECHANICAL EQUIPMENT SCHEDULE
MARK DESCRIPTION VOLT /PHASE HP WATTS FLA MCA MOCP STARTER DISCONNECT/
FUSE SIZE FEEDER CIRCUIT SPECIFIC NOTES
EF-1 EXHAUST FAN 120/1 1/4 SNAP SWITCH 30A(2WG) NP-20 1
EF-2 EXHAUST FAN 120/1 1/4 SNAP SWITCH 20A(2WG) NP-22 1
TU TERMINAL UNIT (EXISTING) 120/1 50 SNAP SWITCH 20A(2WG) SEE SHEET E1-03 2
GENERAL NOTES:A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.
SPECIFIC NOTES:(1) ON ROOF.(2) MULITPLE UNITS WITH SAME DESIGNATION. CONNECT CPT'S PROVIDED BY MC AT EXISTING UNIT.(3)(4)
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALONE-LINE DIAGRAMAND SCHEDULES
E0-02
2
SCOPE OF WORK
1SCOPE OF WORK
CP
NP
NP1
TTB(E)
1SCOPE OF WORK
JJ 2
3
3
3 4
1
5
1SCOPE OF WORK
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALDEMOLITION PLAN
E1-01
Scale:
1 ELECTRICAL DEMOLITION PLAN1/8"=1'-0"
A. THE ENGINEER HAS UNDERTAKEN NO FIELDVERIFICATION OF EXISTING DEVICES. ALL DEVICESSHOWN ARE FROM RECORD DRAWINGS. CONTRACTORSHALL FIELD VERIFY ALL EXISTING DEVICES THATPERTAIN TO THIS PROJECT.
B. FOR ALL ITEMS TO BE DEMOLISHED, REMOVE CIRCUITBACK TO POINT OF CONNECTION. MAKE BRANCHCIRCUIT WITH REMAINING DEVICES CONTINUOUS.
C. ELECTRICAL CONTRACTOR SHALL REMOVE ALLDEMOLISHED ITEMS FROM SITE UNLESS OWNERWISHES TO RETAIN. ITEMS REMOVED FROM SITESHALL BE DISPOSED OF IN A LEGAL MANNER.
D. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.
NOTES:
1. UNLESS NOTED OTHERWISE, REMOVE ALL EXISTINGELECTRICAL AND SPECIAL SYSTEM DEVICES IN AREAOF WORK AND REMOVE ALL EXISTING LIGHTINGFIXTURES AND LIGHTING CONTROLS IN AREA OFWORK. REMOVE ALL ASSOCIATED CONDUIT ANDCONDUCTORS SERVICING DEVICES, LIGHTING ANDMECHANICAL EQUIPMENT BEING REMOVED.
2. DISCONNECT DOOR MOTOR POWER FROM CRITICALBRANCH CIRCUIT.
3. MAINTAIN EXISTING CRITICAL BRANCH LIGHTINGHOMERUN FOR REUSE WITH NEW LIGHTING.
4. MAINTAIN EXISTING LIFE SAFETY BRANCH LIGHTINGHOMERUN FOR REUSE WITH NEW LIGHTING.
5. REROUTE EXISTING HOMERUN (CL-6 PER EXISTINGDRAWINGS) AFTER DEMOLITION OF UP-STREAMLIGHTING.
FLAG NOTES:#
Scale:
2 ELECTRICAL DEMOLITION PLAN1/8"=1'-0"
1
TYPICAL IN ENTRYVESTIBULE EXCEPTLIFE SAFETY
DDD
D
D
D D
DD
OS
OS
D
SS
D
SO
S
D
LSL
2
R1R1
R1 R1
R1
R1
R1
R1
R3 R3
R1 R1 R1 R2 R1 R1
D
R4 R4 R4 R4
R4
R4 R4
R4
R4
R4
R4
R4R4
R4
R2
R2
R2R2
R4 R4 R4
R4 R4
R4
R4R4R4
R4 R4 R4
R4R4R4
R4
R4
R4
R4
R4
R4
R4
R4
R4
R4
R1
R1
R1 R1
W1
W1
S1
X2
X1
X1
X1
X1
X1
X1
R4
R4
R6
R6
R6
R6
R6
R6
R6
R6
R5
R5
R5
R5
R5
R5
R5
R5
R5
R5 R5R5
R5
R5
R5
R5
R5
R5 R5 R5
R5
R5 R5
R5 R5
R5
R5
R5
R5
R5
R5
R5R5
R5
R5R5
R5
R5
R5
R5
R5R5R5
R4
R5
R5
SO
D
3
3
3
3
3
3
CL
(E)
6
R5 R5 R5
5
R5
5
R5
R4
5
5
4
7
S
D
ELEV.
MED.GAS
STAIRX1-SX
STAIR1067
EXTERIOR COURTYARD - NO PUBLIC ACCESS
OFFICE1031
EXAM1032
EXAM1033
EXAM1034
EXAM1036
EXAM1037
EXAM1038
EXAM1039
EXAM1041
CORRIDOR1029
TRIAGE/ASSESMENT
1019
RECEPTION/ASSESMENT
1018
SECURITY1018A
WAITING1013
WHEELCHAIRSTORAGE
1002
QUIETWAITING
1011
ENTRYVESTIBULE
1001
WOMEN1008
MEN1009
HSKP1004
VENDING1007
CORRIDOR1005
CORRIDOR1161
CONSULT1024
MULTI-PATIENTEXAM/HOLDING
1026
PATIENT/SPECIMENTOILET
1022
CORRIDOR1021
CORRIDOR1020
FAST TRACK1023
MEDICATION/SUPPLY
1014
NUTRITION1016
FAST TRACK1023B
FAST TRACK1023C
FAST TRACK1023A
FAST TRACK1023D
FAST TRACK1023E
FAST TRACK1023F
FAST TRACK1023G
TREATMENT1078
CONTROL1082
TREATMENT1081
ALCOVE1076
CLEAN SUPPLY/EQUIPMENT
1074
TREATMENT1077
PATIENTTOILET
1079
X-RAY1083
COMM.1084
CORRIDOR1028
ELEC.1085
ALCOVE1088A
ALCOVE1088B
ALCOVE1088C
CORRIDOR1087
MEDICATION1093
NOURISHMENT1094
PYXIS1098
STAFFTOILET
1097
PATIENTTOILET
1098
SOILEDUTILITY
1099NURSESTATION
1092
CORRIDOR1091
CRASH CART1111
CORRIDOR1109
ALCOVE1108
EXAM1101
EXAM1106
OBEXAM1102
OBEXAM1107
PATIENTTLT./SHWR
1103
PATIENTTOILET11034
CORRIDOR1027
EXAM1042
EXAM1043
EXAM1044
ISOLATION1046
ANTE1048FIRE
1047
NURSESTATION
1073
CORRIDOR1072
EXAM1049
EXAM1051
WHEELCHAIRSTORAGE
1052
VESTIBULE1053
DECONSHOWER
1054
EMSCLOSET
1056
PSYCH.1057
TRAUMA1058
TRAUMA1059
CORRIDOR1071
HSKP1061
ELEV.EQUIP.
1068
ELEV.LOBBY1064
ALCOVE1062
RESULTSWAITING
1117
OFFICE1123
STAFFLOCKERS
1124
OFFICE1123
STAFFLOUNGE
1152
OFFICE1112
OFFICE1113
TLT./SHOWER1114
CORRIDOR1134
CORRIDOR1127
R3 R3
R3 R3
D
D
D
D
R8
R8
R5
8
R5
R5
R4 R4
R4 R4 R4 R4
R4R4R4R4
R4 R4 R4 R4
(E)9
9
R4 R4
R4R4
R4 R4
R1
R1
R1
R1R1
R1
R2
R2
R2
R2
R2
R2
S
SS S
S
S2 S2
S2
S2
S2S2
S
S2
S2
S2
S
S2
S2
S2
R5
R55
5'
X1
4
5
TOILET
PASSAGEWAYX1XX
BEDSTORAGE
X1XX
EXAM #1X1XX
XRAYREADING
X1XX
PHYSICIAN'SREADING RM.
X1XX
CORRIDOR
R7R7
R7SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALLIGHTING PLAN
E1-02
A. ALL DIMMER SWITCHES SHALL BE LUTRON DIVA#DVSTV OR EQUIVALENT UNLESS NOTED OTHERWISE.
B. ALL CEILING MOUNTED OCCUPANCY SENSORS SHALLBE PASSIVE INFRARED WATT STOPPER #C1-305 OREQUIVALENT.
C. ALL WALL MOUNTED OCCUPANCY SENSORS SHALL BEDUAL TECHNOLOGY WATT-STOPPER #DSW-301 OREQUIVALENT.
D. THE LOWER CASE LETTERS NEXT TO LIGHT FIXTURESINDICATE WHICH LIGHTING CONTROL DEVICE (MANUALAND AUTOMATIC) CONTROLS LIGHT FIXTURES.
E. PROVIDE STAINLESS STEEL COVER PLATES ON ALLSWITCHES.
F. CONNECT EXIT SIGNS TO LIFE SAFETY LIGHTINGCIRCUIT.
G. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.
NOTES:
1. INSTALL IN CUTOUTS FROM EXISTING FIXTURES.CONNECT TO EXISTING CIRCUITING AND CONTROLS.
2. APPROXIMATE LOCATION OF LIFE SAFETY ANDCRITICAL BRANCH (480V) PANELS IN THE ELEC/MECHROOM ON SECOND FLOOR.
3. REPLACE LAMPS IN EXISTING INDIRECT/DIRECTCYLINDER LIGHT FIXTURE WITH COMPATIBLE LED60W EQUIVALENT RETROFIT LAMP.
4. CONNECT TO EXISTING CORRIDOR LIFE SAFETYLIGHTING CIRCUIT AND CONTROLS.
5. CONNECT TO EXISTING CORRIDOR NORMALLIGHTING CIRCUIT AND CONTROLS.
6. CONNECT TO EXISTING CRITICAL BRANCH LIGHTINGCIRCUIT (CL-5 PER EXISTING DRAWINGS).
7. HOMERUN TO SPARE 20/1 CIRCUIT BREAKER INCIRCUIT BRANCH PANEL CL IN MECH/ELEC ROOM ON2ND FLOOR.
8. CONNECT LIGHTING ON NORMAL BRANCH POWER TOEXISTING HOMERUN (NL-6 PRE-EXISTING DRAWINGS)AND CONTROLS.
9. CONNECT TO EXISTING CRITICAL BRANCH LIGHTINGCIRCUIT (CL-2 PER EXISTING DRAWINGS) ANDCONTROLS.
FLAG NOTES:#
Scale:
1 ELECTRICAL LIGHTING PLAN1/8"=1'-0"
Scale:
2 ELECTRICAL LIGHTING PLAN1/8"=1'-0"
JJ
CP
NP
NP1
TTB(E)
3 3
CP-66+42"
CP-68+42"
+42"
C
C
C
C
C
C
2
C
C
C
+78"
+42"
LSL
4
CP-65+42"
5 TYPICAL THISROOM
(E)(E)
(E)
(E)
(E) (E)(E)
6
CP-64+42"
CP
-63
CP
-63
CP
-65
CP-66
CP-68
CP-55
CP-55
NP-78 NP-78
NP-78
NP-76
NP
-78
NP
-76
NP-76
NP-76
NP-74
NP-75
NP-75
NP-75
NP-75
NP-74
NP-74
C
CP-51CP-49
CP-41
CP-41
NP-73
CP-49
CP-50
CP-42
CP-42CP-46
CP-46
CP-58
CP-58
CP-57 CP-57
CP-59 CP-59
CP-61
CP-64
NP-21
NP-66
NP-23
NP-25
NP-66
NP-66
NP-84
NP-51
NP-53NP-84
NP-84
NP-73
NP-73
NP-73
NP-73
NP-59
NP1-31
NP1-31
NP1-31
NP1-31
NP1-31
NP1-33
NP1-33NP1-33
NP1-33
NP1-35
NP1-35NP1-35
CP-60
NP1-37
NP1-37
NP1-37
NP1-37
NP1-34
NP1-34
NP1-34
NP1-34
NP1-36
NP1-36
NP1-36
NP1-36NP1-38NP1-38
NP1-40
NP1-40
NP1-40
NP1-40
NP1-42NP1-42
NP-64
NP-64
NP-64
ELEV.
MED.GAS
STAIRX1-SX
STAIR1067
EXTERIOR COURTYARD - NO PUBLIC ACCESS
OFFICE1031
EXAM1032
EXAM1033
EXAM1034
EXAM1036
EXAM1037
EXAM1038
EXAM1039
EXAM1041
CORRIDOR1029
TRIAGE/ASSESMENT
1019
RECEPTION/ASSESMENT
1018
SECURITY1018A
WAITING1013
WHEELCHAIRSTORAGE
1002
QUIETWAITING
1011
ENTRYVESTIBULE
1001
WOMEN1008
MEN1009
HSKP1004
VENDING1007
CORRIDOR1005
CORRIDOR1161
CONSULT1024
MULTI-PATIENTEXAM/HOLDING
1026
PATIENT/SPECIMENTOILET
1022
CORRIDOR1021
CORRIDOR1020
FAST TRACK1023
MEDICATION/SUPPLY
1014
NUTRITION1016
FAST TRACK1023B
FAST TRACK1023C
FAST TRACK1023A
FAST TRACK1023D FAST TRACK
1023EFAST TRACK
1023F
FAST TRACK1023G
TREATMENT1078
CONTROL1082
TREATMENT1081
ALCOVE1076
CLEAN SUPPLY/EQUIPMENT
1074
TREATMENT1077
PATIENTTOILET
1079
X-RAY1083
COMM.1084
CORRIDOR1028
ELEC.1085
ALCOVE1088A
ALCOVE1088B
ALCOVE1088C
CORRIDOR1087
MEDICATION1093
NOURISHMENT1094
PYXIS1098
STAFFTOILET
1097
PATIENTTOILET
1098
SOILEDUTILITY
1099NURSESTATION
1092
CORRIDOR1091
CRASH CART1111
CORRIDOR1109
ALCOVE1108
EXAM1101
EXAM1106
OBEXAM1102
OBEXAM1107
PATIENTTLT./SHWR
1103
PATIENTTOILET11034
CORRIDOR1027
EXAM1042
EXAM1043
EXAM1044
ISOLATION1046
ANTE1048FIRE
1047
NURSESTATION
1073
CORRIDOR1072
EXAM1049
EXAM1051
WHEELCHAIRSTORAGE
1052
VESTIBULE1053
DECONSHOWER
1054
EMSCLOSET
1056
PSYCH.1057
TRAUMA1058
TRAUMA1059
CORRIDOR1071
HSKP1061
ELEV.EQUIP.
1068
ELEV.LOBBY1064
ALCOVE1062
RESULTSWAITING
1117
OFFICE1123
STAFFLOCKERS
1124
OFFICE1123 STAFF
LOUNGE1152
OFFICE1112
OFFICE1113
TLT./SHOWER1114
CORRIDOR1134
CORRIDOR1127
+30"
NP1-40+86"
NP-64+86"
NP-78+86"
NP-76+86"
NP-74+86"
NP-75+86"
NP-59
+78"
+78"
+78"
+78"NP-73
NP1-36+86"
NP1-38+86"
NP1-42+86"
C
C
NP-46NP-40
NP-40
NP-42NP-38
10
CP-71
CP-71
LSPJNP-45
9
8
J
9
NP-43
J
9
NP-41
LSP-11 LSP-11
TU14
S
T
T T
T
T
T
T
T
T
T
T
T
TU18
S
TU19
S
TU17
S
TU06
S
TU06
S
TU06
S
TU03
S
TU07
S
TU16
S
TU19
S
TU18
S
TU02
STU10
S TU10
S
TU19
ST
TU21
S TU17
S
TU17
STU15
S
TU19
S
TU24
S
TU05
STU22
S
TU08
S
TU16
S
TU16
S
TU24
S
TU06
S
TU22
S
EF1
S
EF2
S
(ON ROOF)
(ON ROOF)
J
1
CP-70
+30"+30"
NP1-34+86"
+30"
+30"
+30"
+30"NP1-36
NP1-42+30"+30"
+30"NP1-38+30"
+30"
NP1-38+30"
+30"
+30" +30"
+86"
+30"
+30"
CP-50
+30"
+30"
+30"
NP-64+30"
+30"
+30"
+30"+30"
C
+60"
CNP-66
C
+42"
+42"
+42"
NP1-42
ME
4
ME-12
ME-12
ME-12
ME-12
ME-12
ME-12
ME-12ME-12
ME-12
ME-12
ME-12
ME-12
ME-12 ME-12 ME-12 ME-12 ME-12
ME-12ME-12
ME-22
ME-22
ME-22
ME-22 ME-22
ME-22
ME-22
ME-22ME-22
ME-22
ME-22
8
8
8
8 8
8
CP-51
CP-71
NP-71+86"
CP-73
JCP-70
JCP-70
1
JCP-70
1
J CP-70
1
JCP-63
1
J
11
ME-19
J CP-72
1
JCP-72
1
JCP-72
JCP-72
1
1
7
TOILET
PASSAGEWAYX1XX
BEDSTORAGE
X1XX
EXAM #1X1XX
XRAYREADING
X1XX
PHYSICIAN'SREADING RM.
X1XX
CORRIDOR
J
J
1
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALPOWER PLAN
E1-03
A. ALL DEVICES, WIRING, ETC. IN PATIENT CARE AREASSHALL COMPLY WITH ARTICLE NEC-517. PROVIDE REDRECEPTACLE OUTLETS FOR EMERGENCY BRANCHCIRCUITS.
B. VERIFY EXACT LOCATION AND HEIGHT OF ALL DEVICESWITH ARCHITECT PRIOR TO ROUGH-IN.
C. THE NUMBER NEXT TO ELECTRICAL DEVICESINDICATES BRANCH CIRCUIT.
D. NEW RECEPTACLES IN WAITING AREAS, CORRIDORS,AND OFFICES SHALL BE TAMPER- RESISTANT.
E. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.
NOTES:
1. CONNECT DOOR POWER SUPPLY (120V).
2. COORDINATE RECEPTACLE LOCATION WITHDRINKING FOUNTAIN SHOP DRAWINGS. PROVIDEGFCI CIRCUIT BREAKER IN PANEL NP.
3. CONNECT EXISTING ENTRY DOOR MOTOR POWER TOLIFE SAFETY BRANCH, CIRCUIT VACATED DURINGDEMOLITION.
4. APPROXIMATE LOCATION OF LIFE SAFETY ANDEQUIPMENT BRANCH PANELS IN THE MECH/ELECROOM ON SECOND FLOOR.
5. HOSPITAL GRADE TAMPER PROOF RECEPTACLE.
6. REPLACE (E) RECEPTACLE WITH GFCI TYPE.DOWNSTREAM GFI PROTECTION IS NOT REQUIRED.
7. CONNECT TO NEAREST RECEPTACLE CIRCUIT ONNORMAL POWER BRANCH. VERIFY TOTAL NUMBEROF RECEPTACLES ON CIRCUIT IS LESS THAN (8).
8. VERIFY LOCATION OF COMPUTER STATION WITHARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN.
9. CONNECT RECESSED HAND DRYER PERMANUFACTURER'S DIRECTION.
10. INSTALL RECEPTACLE FOR UNDER COUNTERREFRIGERATOR BELOW SINK. GROMMET CASEWORKFOR CORD PASS-THRU.
11. PROVIDE DEDICATED 120V CIRCUIT FROMEQUIPMENT BRANCH PANEL 'ME' FOR HVACCONTROL PANEL. COORDINATE LOCATION WITHCONTROLS CONTRACTOR.
FLAG NOTES:#
Scale:
1 ELECTRICAL POWER PLAN1/8"=1'-0"
Scale:
2 ELECTRICAL POWER PLAN1/8"=1'-0"
D
SED
SE
SE
SE
T
SE
SE
SE
SE
SE
SE SE SE
CR
CR
CR
CR
CR
CR
CR
CR
CR
1
CR
360°
360°
J
4
2
360°
360°
3
3
ELEV.
MED.GAS
STAIRX1-SX
STAIR1067
EXTERIOR COURTYARD - NO PUBLIC ACCESS
TELE.
OFFICE1031
EXAM1032
EXAM1033
EXAM1034
EXAM1036
EXAM1037
EXAM1038
EXAM1039
EXAM1041
CORRIDOR1029
TRIAGE/ASSESMENT
1019
RECEPTION/ASSESMENT
1018
SECURITY1018A
WAITING1013
WHEELCHAIRSTORAGE
1002
QUIETWAITING
1011
ENTRYVESTIBULE
1001
WOMEN1008
MEN1009
HSKP1004
VENDING1007
CORRIDOR1005
CORRIDOR1161
CONSULT1024
MULTI-PATIENTEXAM/HOLDING
1026
PATIENT/SPECIMENTOILET
1022
CORRIDOR1021
CORRIDOR1020
FAST TRACK1023
MEDICATION/SUPPLY
1014
NUTRITION1016
FAST TRACK1023B
FAST TRACK1023C
FAST TRACK1023A
FAST TRACK1023D
FAST TRACK1023E
FAST TRACK1023F
FAST TRACK1023G
TREATMENT1078
CONTROL1082
TREATMENT1081
ALCOVE1076
CLEAN SUPPLY/EQUIPMENT
1074
TREATMENT1077
PATIENTTOILET
1079
X-RAY1083
COMM.1084
CORRIDOR1028
ELEC.1085
ALCOVE1088A
ALCOVE1088B
ALCOVE1088C
CORRIDOR1087
MEDICATION1093
NOURISHMENT1094
PYXIS1098
STAFFTOILET
1097
PATIENTTOILET
1098
SOILEDUTILITY
1099NURSESTATION
1092
CORRIDOR1091
CRASH CART1111
CORRIDOR1109
ALCOVE1108
EXAM1101
EXAM1106
OBEXAM1102
OBEXAM1107
PATIENTTLT./SHWR
1103
PATIENTTOILET11034
CORRIDOR1027
EXAM1042
EXAM1043
EXAM1044
ISOLATION1046
ANTE1048FIRE
1047
NURSESTATION
1073
CORRIDOR1072
EXAM1049
EXAM1051
WHEELCHAIRSTORAGE
1052
VESTIBULE1053
DECONSHOWER
1054
EMSCLOSET
1056
PSYCH.1057
TRAUMA1058
TRAUMA1059
CORRIDOR1071
HSKP1061
ELEV.EQUIP.
1068
ELEV.LOBBY1064
ALCOVE1062
RESULTSWAITING
1117
OFFICE1123
STAFFLOCKERS
1124
OFFICE1123 STAFF
LOUNGE1152
OFFICE1112
OFFICE1113
TLT./SHOWER1114
CORRIDOR1134
CORRIDOR1127
CR
+30"
TV+86"
TV+86"
TV+86"
TV+86"
TV+86"
TV+86"TV
+86"
TV
+86"
TV+86"
TV+86"
TV+86"
TV
+78"
TV+78"
TV+78"
TV+78"
5
CR
TV+78"
+30"
+30"
+30"+30"
J4
CR
+36"
+36"
+36"+36"+36"
+36"
+36"
+30"
+30"
+30"+30"+30"
+30"
+30"
5
5
5 5 5
5
SM
LS
SM
LS
SM
LS
SM
LS
SM
LS
LM
LS
LM
LS
W
SM
LS
SM
LS
S
S
S
S
S
S
S
S
S
S
S
S
3
TV
TV
+86"
+86"
S
6
FAC
P
7
EXISTING TTB
EXISTING RACK
+84"
+84"
+84"
+84"
+84" +84"
+84"
8
8
8
ELEC.X1XXTOILET
X1XXX1XX
TOILET
PASSAGEWAYX1XX
BEDSTORAGE
X1XX
EXAM #1X1XX
XRAYREADING
X1XX
PHYSICIAN'SREADING RM.
X1XX
SECURITYX1XX
EXISTINGELEVATOR 4
X-EL4
CORRIDORJ
J
4
CR
SM
LSS
CR
SM
LS
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALSPECIAL SYSTEMSPLAN
E1-04
A. VERIFY EXACT LOCATION AND HEIGHT OF ALL DEVICESWITH ARCHITECT PRIOR TO ROUGH-IN.
B. ALL DEVICES, WIRING, ETC. IN PATIENT CARE AREASSHALL COMPLY WITH NEC ARTICLE 517.
C. VOICE/DATA, CATV, ACCESS CONTROL, AND CCTVDEVICES, CABLING, TERMINATIONS, ANDCONNECTIONS SHALL BE BY THE OWNER'S ON-CALLCONTRACTOR(S) AND SHALL CONFORM WITH LOCALSTANDARDS. ELECTRICAL CONTRACTOR SHALLPROVIDE AND INSTALL ALL OUTLET BOXES ANDPATHWAYS.
D. VOICE/DATA, CATV, SECURITY, AND CCTV SHALL BEROUTED VIA CONDUIT FROM OUTLET BOX TO ABOVEACCESSIBLE CEILING. CABLE SHALL BE ROUTED VIAJ-HOOKS, ARLINGTON LOOPS, OR SIMILAR CABLEMANAGEMENT SPACED NO GREATER THAN 5'-0"ABOVE ACCESSIBLE CEILINGS FROM OUTLET CONDUITTO TELECOM ROOM. E.C. SHALL PROVIDECOMMUNICATIONS PATHWAYS; COORDINATE ROUTINGWITH OWNER'S IT CONTRACTOR.
E. CONNECT NEW FIRE ALARM DEVICES TO EXISTINGSYSTEM.
F. CONNECT NEW SPEAKERS TO EXISTINGINTERCOM/PAGING SYSTEM.
G. NEW NURSE CALL SYSTEM DEVICES AND CABLINGSHALL BE BY THE OWNER'S ON-CALL CONTRACTOR(S).THE NEW DEVICES SHALL BE CONNECTED TO THEEXISTING NURSE CALL SYSTEM.
H. THIS RENOVATION PROJECT IS TO BE EXECUTED INMULTIPLE PHASES. SEE ARCHITECTURAL PLANS FORPROJECT PHASING.
NOTES:
1. PUSH BUTTON FOR REMOTE BUZZ-IN OF DOOR.
2. INSTALL ON MULLION.
3. REPLACE EXISTING CAMERAS WITH NEW.
4. MOTORIZED DOOR TO OPERATE UPON CARDREADER.
5. VERIFY LOCATION AT COMPUTER STATION WITHARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN.
6. VOICE/DATA, CATV, AND CCTV CABLING RUN BACKTO THIS ROOM. OWNER'S ON-CALL CONTRACTORSHALL PROVIDE ADDITIONAL EQUIPMENT ASNECESSARY TO ACCOMMODATE NEW DEVICES.
7. EXISTING FIRE ALARM CABINET AND POWERSUPPLIES.
8. CONNECT MAGNETIC HOLD OPENS TO FIRE ALARMSYSTEM TO RELEASE UPON ALARM.
FLAG NOTES:#
Scale:
1 ELECTRICAL SPECIAL SYSTEMS PLAN1/8"=1'-0"
Scale:
2 ELECTRICAL SPECIAL SYSTEMS PLAN1/8"=1'-0"
18"
64"
78"
90"
48"
ELECTRICAL DEVICES
96"
WALL-MOUNTOC
DLVS
CBC
TSTC
120"MAX.
TOP OF DEVICE
9'-0"+ CEILING
8'-0" CEILING
TOP OF CABINET
TOP OF CABINET
TOP OF DEVICE
CL OF DEVICE
18"
TOP OF DEVICE
48"
MINIMUM, TOP OF DEVICE
BOTTOM OF DEVICE
TOP OF CABINET
TOP OF CABINET90"
6"MIN.
96"
NOTES:1. IF MOUNTING HEIGHT OF DEVICES INDICATED HERE IS IN
CONFLICT WITH ADA REQUIREMENTS DUE TO INSTALLATIONDETAIL, ADA DIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALLSUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONSSHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.
TYPICAL DEVICE MOUNTING HEIGHTS
I
I
CR
FINISHED FLOOR
48"
84"
FINISHED CEILING
90"
78"
64"
24"
NO SCALE
I
WALL-MTDCABINET
CPUAPSACP
KCVCTCK
MAVTV
SANN
FACP
SH
SH
F
80"MIN.
96"MAX.
120"MAX.
CL OF DEVICE
CL OF DEVICE
TOP OF DEVICE
TOP OF CABINET
8'-0" CEILING
9'-0"+ CEILING
CL OF DEVICE
LOW VOLTAGE DEVICES FIRE ALARM DEVICES
B
A
T568B STANDARD8-POSITION / 8-CONDUCTOR DEVICE WIRING DIAGRAM
1
1
PAIR 2
PAIR 2
4
5
1
2
PIN
MODULAR CONNECTOR PINOUTS
8764 532
72 3 54 6
PAIR 1PAIR 3
PAIR 3PAIR 1
8
PAIR 4
PAIR 4
2
3
4
1
PAIR COLOR CODE
2
3
4
1
3
6
7
8
BLUE
WHITE/BLUE
WHITE/ORANGE
ORANGE
WHITE/GREEN
GREEN
WHITE/BROWN
BROWN
NO SCALE
OUTLET PATHWAY DIAGRAM - DRYWALL PARTITIONNO SCALE
OUTLET ASSEMBLY.
CONDUIT STUBBED ABOVEACCESSIBLE CEILING.
6" RADIUS MINIMUMCONDUIT SWEEP.
FINISHED FLOOR.
WALL SURFACE (GYP BD).
ACCESSIBLE CEILING.
PROVIDE INSULATED BUSHINGON END OF CONDUIT.
ADHERE TO ONE OF THE FOLLOWINGMETHODS FOR ROUTING CONDUIT FROMOUTLET:
1. STUB INTO SPACE ABOVEACCESSIBLE CEILING;
2. ROUTE TO NEAREST ARLINGTONLOOP PATHWAY;
3. ROUTE TO SERVING IDF/MDF.
CCOMMUNICATIONS OUTLET BOX DIAGRAM
THREADED NIPPLE WITHPROTECTIVE BUSHING.
COMMUNICATIONS CABLING.
CONDUIT PATHWAY,UP ORDOWN FROM OUTLET BOX.
SINGLE DEVICE MUD-RING.
ELECTRICAL OUTLET BOX;4-11/16" x 4-11/16" x 2-1/2".TYPICAL UNO.
NO SCALE
D
NOTES:1. PROVIDE LEVEL 1 ADMINISTRATION
PER ANSI/TIA/EIA-606.
2. PROVIDE LABEL ON FRONT OFFACEPLATE.
3. PROVIDE VOICE AND DATA PORTSAS INDICATED ON THE PLANS.PROVIDE ONLY ONE DATA PORT IFNOT INDICATED ON PLANS.
4PR CAT5E UTP CABLE(WHITE JACKET).
MODULAR COMMUNICATIONSFACEPLATE, BEIGE COLOR.
MODULAR CAT5E CONNECTOR(IVORY). TERMINATE T568B.
1"C.
MODULAR CAT5ECONNECTOR(DARK RED).TERMINATET568B.
4PR CAT5E UTP CABLE(BLUE JACKET).
VOICE/DATA OUTLET DIAGRAMNO SCALE
BLANK PORTFILLER. COLORTO MATCHFACEPLATE.
6"x6"x4" JUNCTION BOX, ABOVECEILING.
CARD READER, ONUNSECURED SIDE OFDOOR. 4"x4" OUTLET BOXWITH SINGLE-GANGMUDRING.
ELECTRIFIED LOCKSET IN DOOR,-OR- ELECTRONIC LATCHRETRACTION MECHANISM. SEEDOOR HARDWARE SCHEDULE.
DOOR POSITION SWITCH,IN DOOR FRAME.
1"C
.
3/4"
C.
1"C
.
STUB CONDUIT IN ACCESSIBLECEILING SPACE. ROUTE CABLING TOCONTROL PANELS VIA ARLINGTONLOOP PATHWAYS.
DOOR POWER SUPPLY, ABOVECEILING.
3/4"C.
120V
3/4"
C.
ELECTRIC POWERTRANSFER.
NOTE:ON ELECTRIC SLIDING DOORS, OMIT THEPOWER TRANSFER SWITCH AND TAKE ANINPUT FROM ACCESS CONTROL PANEL TOTRIGGER DOOR OPERATION.
EELECTRONIC ACCESS DOOR CONTROLNO SCALE
SAN JUAN REGIONALMEDICAL CENTER
Emergency Department Renovation
Mail: Phone:
48 C.R. 25O/ STE. 3/ DURANGOPhysical: 1235 THOROUGHBRED RD./ DURANGO, CO./ 81303 (970) 385-6774
RMKM ARCHITECTURE, P.C.
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛comProject No. 9659.00 Copyright 2016
ELECTRICALDIAGRAMS
E5-01