Performance. Safety. Solutions.

FRC GOVERNORSTHE MOST INNOVATIVE FEATURES IN THE INDUSTRY

Traditional PRO Governor

Latest Technology

Perfect Field

Replacement for

FIRE

COMMANDER

pressure

governor

• It monitors both the pump discharge and intake discharge pressures and

maintains a steady pump discharge pressure within system capabilities by

controlling the engine speed or holds a selected engine RPM.

• It operates in one of two modes, pressure or RPM

PRESSURE MODE

In pressure mode the governor maintains a constant pump discharge pressure. The

discharge pressure is monitored and compared to the Operator’s selected pressure

setting, the engine RPM is varied to keep the discharge pressure at the selected setting.

RPM MODE

In RPM mode the governor maintains a constant engine RPM.

FRC GOVERNORS

What is the purpose of a Governor?

Engine Control Methods:

• J1939 or ISO CAN Bus

– Most current production diesel engines

• Analog Signal (0.6 – 4.5V max)

– Used on most engines prior to CAN Bus

datalink control capability

– Used to control most engines, except

Caterpillar

• Pulse Width Modulated (PWM) Signal

– Used to control Caterpillar engines prior to

May 2008

FRC GOVERNORS

How does a Governor or Throttle control the Engine?

FRC GOVERNORS

What does a Governor kit consist of?

Panel Mount

Control Module

Cable

Harnesses

Pressure

Transducers

(1)

Discharge(1)

Intake

FRC GOVERNORSTHE MOST INNOVATIVE FEATURES IN THE INDUSTRY

ADJUSTMENT FEATURES

Quick Response

Control Knoballows faster and more

reliable pressure and

RPM adjustments

Traditional Push

Button Controlfor pressure and RPM

adjustment

Separate Pressure & RPM Buttonswith LED indicators

for the ease of selecting either mode of operation

Throttle-Ready LED is on when the required

interlock conditions are met and the governor

begins pump operations

Digital MasterPressure Display

for pump discharge and intake

Bi-coloredLED bar graphs

provides operator with clear

visual engine status

GREEN - normal

RED - fault / warning

2 Line Digital Message Displayclearly shows the pressure and RPM settings

during normal operations, as well as warning

alarms and stored data program features

Built-inDay/Night Sensoradjusts the brightness of

the LED displays to ensure

clear day/night viewing

Check Engine & Stop Engine LEDsrepeat engine warnings from the cab

An additional bi-color LED bar graph

specific for transmission temperature

Electronic Throttles

Dynamic Throttle

• No mechanical pieces

• Throttle speed =

operator’s request speed

• Bi-directional

• Button increments

become larger the longer

it is pressed

Electronic Throttles

PRESSURE

GOVERNOR

ENGINE

INFO

3 Model Type

Model Discharge Intake

PBA200 300 PSI N/A

PBA300 600 PSI N/A

PBA400 600 PSI 600 PSI

Features Knob Control Features Push Button Control

COMPLETE PRESSURE GOVERNOR,

ENGINE MONITORING AND MASTER PRESSURE DISPLAY

MASTER

PRESSURE

DISPLAY

PRESSURE

GOVERNOR

ENGINE

INFO

MASTER

PRESSURE

DISPLAY

PRESSURE

GOVERNOR

ENGINE

INFO

Only 1587 Data Bus capable

MASTER

PRESSURE

DISPLAY

PRESSURE

GOVERNORENGINE

INFO

FRC GOVERNORSPROVIDE SAFER PUMP OPERATION

• Constantly monitors discharge

pressure and make corrections

if required.

• Limits RPM increases when

conditions arise that fall outside

of normal operating parameters.

• Message display always alerts

operator to what the governor is

doing and what type of problem

it is encountering if one exists

FRC GOVERNORSPROVIDE SAFER PUMP OPERATION

Running Away From Water

● If pressure drops and an

increase in RPM does not bring the

pressure back up, the governor

recognizes this as a running away

from water condition.

● When this condition occurs the

governor switches to the RPM

LIMIT MODE, LOW WATER CYCLE

or NO SUPPLY WATER, alerts the

operator and controls the engine

RPM accordingly.

Running Away From Waterpressure is above 45 PSI but lower than expected at that RPM

RPM LIMIT MODE

● If the discharge pressure stays above

45 PSI, the governor behaves like a

manual throttle and the operator can

raise or lower the engine RPM.

● If the RPM is manually lowered to a

point where the pump is not running

away from water and pressure is stable,

the RPM limit mode is canceled.

● When the pressure comes back to the

selected pressure setting, the RPM limit

mode is canceled and the governor

switches to normal operation.

RPM LIMIT MODESystem Monitors Both Pressure & RPM – Calculating the Pumps Output Characteristics it Limits RPM if Pressure is Not Sufficient

Running Away From Waterpressure is between 15 and 45 PSI

LOW WATER CYCLEEngine Limitedto 1100 RPM

LOW WATER CYCLE

● If the discharge pressure is between

15 and 45 PSI, the engine is set at 1100

RPM.

● If the pressure does not rise above 45

PSI in 7 seconds, the governor sets the

engine RPM at idle.

● The governor repeats the low water

cycle as long as the discharge pressure

is between 15 and 45 PSI.

● When the pressure rises above 45

PSI the governor resumes normal

operation.

Running Away From Waterpressure is lower than 15 PSI

NO SUPPLY WATER

● If the discharge pressure is below 15

PSI, the engine RPM is set at idle and

the message display flashes NO

WATER.

● If, within 3 minutes, the discharge

pressure rises above 15 PSI the

governor enters the low water cycle.

● If the discharge pressure does not

rise above 15 PSI within 3 minutes, the

governor switches to idle mode and

cancels the pressure setting.

NO WATER MODEEngine Goes to IDLE

FRC GOVERNORS

Resources

FRC GOVERNORS

Resources

FRC GOVERNORS

Resources

FRC GOVERNORS

Pressure Transducers

FRC GOVERNORS

Calibration codes

FRC GOVERNORSFRC Governors Provide Flexibility with Over 50 Programmable Options

FRC GOVERNORS

Codes

Press and hold Silence for 5 sec to = “----”

Wait till P101 appears

FRC GOVERNORS

Codes

Compatible with the following Engines:

• Cummins IS

• Detroit Diesel

• Navistar / International

• Caterpillar

• Ford 6.7L – 2011 & Newer

• Mack

• Scania

• Mercedes – Domestic & Int’l

• Isuzu

• John Deere

• FAW

• MAN

• Iveco

FRC GOVERNORS

FRC GOVERNORSSoftware Update

Update Software with USB

Simple 4 step process to update

1 software for all governors for all FRC brand Governors

• PumpBoss

• InControl

• Total Control

• Pro-T

FRC GOVERNORS

SAE J1939 CAN bus for 2016 Engines

The baud (data) rate has been increased from 250 kbit/s to 500 kbit/s

FRC Governors/Throttle/Instruments

Have been updated to 500 kbit/s

All FRC Governor have a Auto detect fusion for

backward compatibility

FRC GOVERNORS

• Date over 1939 Bus

• Engine RPM

• Engine Temperature

• Oil Pressure

• Transmission Temperature

• Battery Voltage

• Engine Warning

• Stop Engine

• Engine Hours

• No Terminating Resistor in governors circuit

• 1939 CAN bus ( OEM provided)

• FRC Data –Link

• FRC provide external Terminators

• Required for a remote governor

FRC GOVERNORS

Built-in Diagnostics – Error Codes

FRC GOVERNORSError codes

Something is missing and unit will not operate

• Pressure Sensor

• Missing voltage (5 VDC)

• Missing single (0.5- 4.5 VDC)

• Causes

• Broking Wire or Wires

• Damaged Sensor (burst/ water hammer)

• Missing RPM (1939 CAN bus data)

• Broking Wire

• Missing or too many TR

• Data conflict with other devices

• Remote unit issues

• Missing 1939 CAN Bus

• Missing connection to master unit

• Missing TR

• Engine doesn’t respond to governor request after ECM SW update

• Confirm all required remote throttle setting are set

FRC GOVERNORS

Built-in Diagnostics – Fault Codes

FRC GOVERNORS

Fault codes

Singles are present but not normal

• Pressure sensor issues

• Ground return broken (single voltage is floating)

• Missed wired sensor (Ground is missing)

• 5V referrers to high

• Wires shorted

• Sensor damaged

• Engine Not Responding

• ECM not Configured for remote

• Minimum Discharge pressure not seen by the governor

• 1939 data intermitted