Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
PERFORMANCE MEASUREMENTS OF RAIL CURVE
LUBRICANTS
by
Lance Jon Wilson
Bachelor of Engineering (Mechanical)
Masters of Engineering Science
Queensland University of Technology, Australia
Thesis submitted for the degree of
Doctor of Philosophy
School of Engineering Systems Queensland University of Technology
2006
KEYWORDS
Rail Curve, Lubricant Performance, Elastohydrodynamic lubrication,
Rheology, Absorbed energy, Lubricating Grease, Rail/Wheel interface.
ABSTRACT
Wear of railroad rolling stock and rails costs millions of dollars annually in all
rail systems throughout the world. The rail industry has attempted to address
flange wear using rail curve lubricants and presently use a variety of lubricants
and lubricant applicators. The choice of lubricant and applicator is currently
based on considerations that do not address the wear problem directly.
This research quantified rail curve lubricant performance through laboratory
simulation. The effects of lubricants in the wheel/rail contact were
investigated. Rail curve lubricant performance was measured with a laboratory
rail/wheel simulator for the purpose of optimising the choice of lubricant.
New methods for measurement of rail curve lubricant performance have
been presented. These performance measurements are total absorbed energy,
the energy absorbed in the lubricant film instead of being utilised for wear
processes; total distance slid, the sliding distance or accumulated strain
achieved prior to development of a set tractive force limit; half life of
lubricant, the time taken for a lubricant to lose half of its sliding performance;
and apparent viscosity, a measure of the lubricity presented with respect to
accumulated strain.
The rail/wheel simulator used in this research consists of two dissimilar
wheels (disks) rotating in contact with one another simulating a conformal
gauge corner contact. The first wheel, a simulated rail, is driven by an electric
motor which then drives the second wheel, a simulated railroad wheel,
through the contact. Hydraulic braking on the railroad wheel is used to
simulate the rolling/sliding conditions.
The variables of the simulated contact that are controlled with this equipment
are normal force, input wheel speed, slip ratio between samples, sample
geometries and material properties, and lubricant types.
Rail curve lubricants were laboratory tested to define their properties using
the ASTM and other appropriate standards. The performance differences
measured using ASTM standards based tests were susceptible to repeatability
problems and did not represent the contact as accurately as the rail/wheel
simulator. This laboratory simulator was used to gather data in lubricated and
unlubricated conditions for the purpose of providing lubricant performance
measurements. These measurements were presented and the tested lubricants
were ranked conclusively using three industrially relevant performance
criteria.
Total sliding distance and total absorbed energy measurements of the rail
curve lubricants displayed clear differences in lubricant performance for both
of these criteria. Total sliding distance is equivalent to the number of axles in
the field situation, while total absorbed energy is the energy unavailable for
wear processes of rails and wheels. Lubricants designed using these
measurements will increase lubricant performance with respect to these
performance criteria which in turn will reduce wear to both rails and wheels.
Measurement of the apparent viscosity of rail curve lubricants, using the
rail/wheel simulator, displayed changes in rheological characteristics with
respect to accumulated strain. Apparent viscosity is a measure of the shear
stress transmitted from the wheels to the rails. Designing a rail curve lubricant
after analysing measurements taken from the rail/wheel simulator will assist in
identifying lubricant properties to reduce the wear producing shear stresses
generated in a rail wheel contact.
Decay of lubricant performance was measured for three different rail curve
lubricants under simulated conditions. The research found appreciable and
quantifiable differences between lubricants. Industrial application of the
findings will improve positioning of lubrication systems, improve choice of
lubricants and predict effective lubrication distance from the lubricant
application point.
Using the new methods of lubricant performance measurement developed in
this thesis, the objective of this research, to quantify rail curve lubricant
performance through laboratory simulation, has been achieved.
TABLE OF CONTENTS
Table of Contents................................................................................................................. i List of figures ....................................................................................................................... v List of tables ......................................................................................................................... x Statement of orginal authorship .....................................................................................xii Acknowledgments............................................................................................................xiii Nomenclature ...................................................................................................................xiv Chapter 1...............................................................................................................................1
Introduction .................................................................................................................. 1 1.1 Background.................................................................................................................... 1 1.2 Objective of Research.................................................................................................. 4 1.3 Summary and Thesis Outline ..................................................................................... 6 Chapter 2...............................................................................................................................7
Literature Review ......................................................................................................... 7 2.1 Rail/Wheel Wear Testing............................................................................................ 7 2.2 Rail/Wheel Wear Processes........................................................................................ 9
2.2.1 Rail/Wheel Wear: Surface initiated rolling contact fatigue.......................10 2.2.2 Rail/Wheel Wear Particles..............................................................................11
2.3 Rail Lubricant Characteristics...................................................................................12 2.4 Lubrication Regimes ..................................................................................................15 2.5 Rail Curve Lubricant Types Under Investigation.................................................16 2.6 Rail Curve Lubricating Grease Specifications .......................................................18 2.7 Rail Lubrication Research .........................................................................................19
2.7.1 Surface initiated rolling contact fatigue with lubrication...........................26 2.8 Lubricant Application Research...............................................................................28
2.8.1 Lubricant transport prediction/modelling ..................................................31 2.8.2 Summary ............................................................................................................36
2.9 Rail/Wheel Simulator - Description of equipment..............................................37 2.10 Lubricant Properties Testing..................................................................................39
2.10.1 ASTM D 1092 Standard Test Method for Measuring Apparent Viscosity of Lubricating Greases.............................................................................40 2.10.2 ASTM D 2596 Standard Test Method for Measurement of Extreme-Pressure Properties of Lubricating Grease ..........................................41 2.10.3 ASTM D 2266 Standard Test Method for Wear Preventive Characteristics of Lubricating Grease ....................................................................42 2.10.4 Rheometer Test ..............................................................................................43
2.11 Summary ....................................................................................................................45 Chapter 3.............................................................................................................................47
Theoretical calculations: Contact Mechanics of In-service and Rail Simulator conditions and lubricant film thickness...............................................47
3.1 Introduction.................................................................................................................47 3.2 Contact Mechanics Background ..............................................................................47
3.2.1 Wheel/rail contact models – A survey.........................................................49
ii
3.3 Geometry and Material Property Equations..........................................................52 3.4 Contact Mechanics Method......................................................................................54
3.4.1 Rectangular Contact Equations .....................................................................55 3.4.2 Elliptical Contact Equations...........................................................................56 3.4.3 Micro-slip/Creep Prediction ..........................................................................59
3.5 Conformal Rail/Wheel Contact...............................................................................62 3.6 Stress Distributions for In-service Conditions......................................................69 3.7 Stress Distributions for Simulator Conditions ......................................................75
3.7.1 Two Dimensional Line Contact Stress Distributions................................82 3.8 Elastohydrodynamic Film Thickness Calculation ................................................86
3.8.1 Shear rate of lubricant film .............................................................................88 3.8.2 Lubricant apparent viscosity calculation ......................................................92
3.9 Summary.......................................................................................................................95 Chapter 4.............................................................................................................................97
Commissioning and testing protocol of the rail/wheel interaction simulator ......................................................................................................................97
4.1 Introduction.................................................................................................................97 4.2 Equipment Modifications .........................................................................................98
4.2.1 Heat Dissipation ...............................................................................................98 4.2.2 Tread Loading Mechanism...........................................................................100 4.2.3 Data Acquisition .............................................................................................104 4.2.4 Tractive Force Application System.............................................................104 4.2.5 Slip/Creep Measurement ..............................................................................106
4.3 Testing equipment – construction/commissioning ...........................................106 4.3.1 Pre-Commissioning Testing Observations................................................106 4.3.2 Commissioning Testing Observations .......................................................107
4.4 Lubricated Testing Protocol ...................................................................................114 4.4.1 Preparation of the rail/wheel samples........................................................114 4.4.2 Material Properties .........................................................................................114 4.4.3 Test Sample Surface Roughness Results....................................................117 4.4.4 Testing Procedure ..........................................................................................117
4.5 Method of Measurements .......................................................................................118 4.5.1 Rotational Speed Measurement ...................................................................119 4.5.2 Output Torque Transducer ..........................................................................120 4.5.3 Input Torque ...................................................................................................120 4.5.4 Temperatures...................................................................................................122 4.5.5 Slip Calculation ...............................................................................................123 4.5.6 Torque Measurement for Tractive Force (Shearing Force) ...................124 4.5.7 Rail Flange Contact Conditions...................................................................127 4.5.8 Normal Load ...................................................................................................129
4.6 Measurement Errors ................................................................................................131 4.6.1 Thermal Expansion of Test Samples..........................................................131 4.6.2 Energy dissipation methods .........................................................................133 4.6.3 Slip From Lubrication Measurements (Zero slip predictions)...............135
4.7 Lubricant Performance Measures Error Analysis ..............................................137 4.8 Summary.....................................................................................................................149
iii
Chapter 5...........................................................................................................................152 Performance Measurement of Rail Curve Lubricants.......................................152
5.1 Introduction...............................................................................................................152 5.2 Testing Variables.......................................................................................................152 5.3 Unlubricated System Steady State Values ............................................................153
5.3.1 Lubricant Film Decay Half-Life Prediction ..............................................155 5.4 Input Data Variability ..............................................................................................156
5.4.1 Tread Load Temperature Dependence......................................................159 5.5 Rail/Wheel Simulator Results ................................................................................160
5.5.1 Group 1 Lubricant Performance Results (Tread Load = 9.5 kN, Braking Torque = 15 N.m, Rolling Speed = 20 km/hr)..................................161 5.5.2 Group 2 Lubricant Performance Results (Tread Load = 9.5 kN, Braking Torque = 15 N.m, Rolling Speed = 10 km/hr)..................................171 5.5.3 Group 3 Lubricant Performance Results (Tread Load = 9.5 kN, Braking Torque = 30 N.m, Rolling Speed = 20 km/hr)..................................180 5.5.4 Group 4 Lubricant Performance (Tread Load = 12.5 kN, Braking Torque = 15 N.m, Rolling Speed = 20 km/hr) .................................................189 5.5.5 Comparison and Discussion of All Groups..............................................197 5.5.6 Lubricant Performance Summary ...............................................................202 5.5.7 Apparent Viscosity Profiles ..........................................................................205
5.6 Experimental Observations ....................................................................................209 5.6.1 Temperature Profiles .....................................................................................209 5.6.2 Observed Lubricant Properties ...................................................................210 5.6.3 Lubricant Film Failure...................................................................................212 5.6.4 Braking Torque Setting .................................................................................212
5.7 Standards Based Lubricant Testing Results.........................................................213 5.7.1 Rheometry Method........................................................................................214 5.7.2 Rheometer Test Discussion and Results....................................................215 5.7.3 Experimental Rheometry Observations ....................................................216 5.7.4 ASTM D1092 Grease Pumpability .............................................................217 5.7.5 ASTM D2596 and ASTM D2266 Four Ball Tests ..................................217
5.8 Summary.....................................................................................................................221 Chapter 6...........................................................................................................................224
Discussion, future work and Conclusions...........................................................224 6.1 Introduction...............................................................................................................224 6.2 Discussion..................................................................................................................224 6.3 Future Work ..............................................................................................................227 6.4 Conclusions................................................................................................................229 References.........................................................................................................................233 Bibliography .....................................................................................................................238 APPENDIX A ................................................................................................................262 A. Seizure Wear ......................................................................................................262 B. Melt Wear ...........................................................................................................263 C. Oxidational wear ...............................................................................................265 D. Mild-oxidational wear.......................................................................................265 E. Severe-oxidational wear ...................................................................................268
iv
F. Plasticity dominated wear ................................................................................270 APPENDIX B.................................................................................................................271 A. Validation of Software for Rectangular Contact.........................................271 B. Validation of software for Elliptical Contact...............................................273 Appendix C – Technical Drawings..............................................................................277
v
LIST OF FIGURES
Number Page FIGURE 1 – TWIN DISK TEST APPARATUS FROM THE WORK OF DETERS AND PROKSCH
(2005)............................................................................................................................ 8 FIGURE 2 – (A) BALL ON DISK WEAR TEST APPARATUS, SPECIFIED LOADING REGIME AND (B)
TYPICAL WEAR SCAR OF THE WORK OF LEE AND POLYCARPOU (2005). ...................... 9 FIGURE 3 - STEEL PIN-ON-DISK WEAR MAP COMBINING RESULTS FROM MULTIPLE AUTHORS
BY LIM AND ASHBY (1986)......................................................................................... 10 FIGURE 4 - WEAR MAP SHOWING DEFINED WEAR MODES FOR BRITISH STANDARD RAIL
STEELS IN AN AMSLER WEAR TEST DEVICE (LEWIS AND OLOFSSON 2004).............. 12 FIGURE 5 – SEPARATION DISTANCES BETWEEN CONTACTING SURFACES FOR (A)
HYDRODYNAMIC LUBRICATION (HL)AND ELASTOHYDRODYNAMIC LUBRICATION, (B) MIXED-MODE LUBRICATION, AND (C) BOUNDARY LUBRICATION. .............................. 16
FIGURE 6 - WAYSIDE LUBRICATION DEVICE (PHOTO COURTESY OF QUEENSLAND RAIL). .. 28 FIGURE 7 – VOGEL ON-BOARD LUBRICATION DEVICE MOUNTED TO DISPLAY COMPONENTS
OF SYSTEM................................................................................................................... 29 FIGURE 8 - HI-RAIL LUBRICATION VEHICLE (PHOTO COURTESY OF QUEENSLAND RAIL). ... 29 FIGURE 9 - LUBRICANT APPLICATION BY HI-RAIL VEHICLE (PHOTO COURTESY OF
QUEENSLAND RAIL).................................................................................................... 30 FIGURE 10 - WAYSIDE LUBRICATOR LOCATION PLAN (FRANK 1981). ................................. 32 FIGURE 11 - RANGE OF LUBRICATION (FRANK 1981)........................................................... 33 FIGURE 12 - RAIL TRIBOMETER (PHOTO COURTESY OF QUEENSLAND RAIL)....................... 34 FIGURE 13 – RAIL/WHEEL SIMULATOR POST MODIFICATIONS BY THE AUTHOR. .................. 38 FIGURE 14 LOADING DIAGRAM FOR WEAR INVESTIGATION OF MARICH AND MUTTON(1989)
..................................................................................................................................... 39 FIGURE 15 – SCHEMATIC DRAWING OF ASTM D 1092 TEST DEVICE(ASTM 1999)............ 40 FIGURE 16 – SCHEMATIC DIAGRAM OF FOUR BALL TEST DEVICE SUITABLE FOR ASTM D
2266 AND ASTM D 2596 (ASTM 1991; ASTM 1997). ............................................ 42 FIGURE 17 – (LEFT) LUBRICANT FILM PRIOR TO ROLLING (~1MM THICKNESS). (RIGHT)
LUBRICANT FILM FOLLOWING ROLLING (~1µM)......................................................... 44 FIGURE 18- REFERENCE GEOMETRY USED FOR CONTACT MECHANICS CALCULATIONS
(ESDU 1984). ............................................................................................................. 52 FIGURE 19 - CONTACT DIMENSIONS, ELLIPSE RATIO, AND APPROACH COEFFICIENTS(ESDU
1995). .......................................................................................................................... 58 FIGURE 20 – CREEP PREDICTION FOR SIMULATOR WHEN CONTACT PATCH IS ASSUMED TO
HAVE NO REGIONS OF SLIP........................................................................................... 61 FIGURE 21 - CREEP PREDICTION FOR SIMULATOR WHEN CONTACT PATCH HAS REGIONS OF
SLIP.............................................................................................................................. 61 FIGURE 22 – WHEEL/RAIL CONTACT PROFILE(SATO 2005) (NOMENCLATURE FOR RADII IN
THIS FIGURE IS NOT USED)........................................................................................... 63 FIGURE 23 – WHEEL PROFILE FOR A CONED WHEEL (SATO 2005). ...................................... 64 FIGURE 24 – ROLLING RADIUS USED FOR CALCULATION OF LINE CONTACT WIDTH USING
WHEEL PROFILE FROM SATO (2005)............................................................................ 65 FIGURE 25 – CONTACT WIDTH PROFILE FOR CONSTANT NORMAL FORCE USING A VARIABLE
ROLLING RADIUS PROFILE. NOTE SCALE OF AXES DIFFERENT. ................................... 65 FIGURE 26 – MAXIMUM PRESSURE FOR CONSTANT TREAD LOAD ACROSS CONTACT AND
VARIABLE CONTACT RADIUS....................................................................................... 66 FIGURE 27- CONTACT WIDTH FOR CONSTANT TREAD LOAD AND CONSTANT MAXIMUM
PRESSURE ACROSS CONTACT FOR VARIABLE CONTACT RADIUS. ................................ 67
vi
FIGURE 28 – CONTACT PATCH DIMENSIONS FOR LINE AND ELLIPTICAL CONTACT FROM SAME NORMAL LOAD, 150,000 N.......................................................................................... 68
FIGURE 29 – STRESS DISTRIBUTION FOR TREAD CONTACT USING GEOMETRY OF SATO (2005) WITH A NORMAL LOAD OF 150 KN AND NO FRICTION FORCE. .................................... 71
FIGURE 30 - STRESS DISTRIBUTION FOR TREAD CONTACT USING GEOMETRY OF SATO (2005) WITH A NORMAL LOAD OF 150 KN AND FRICTION FORCE OF 0.185 TIMES THE NORMAL FORCE. ......................................................................................................................... 72
FIGURE 31 - STRESS DISTRIBUTION FOR TREAD CONTACT USING GEOMETRY OF SATO (2005) WITH A NORMAL LOAD OF 150 KN AND FRICTION FORCE OF 0.37 TIMES THE NORMAL FORCE. ......................................................................................................................... 72
FIGURE 32 – STRESS DISTRIBUTION FOR GAUGE CORNER CONTACT USING GEOMETRY OF SATO (2005) WITH A NORMAL LOAD OF 150 KN AND NO FRICTION FORCE. ............... 73
FIGURE 33 – STRESS DISTRIBUTION FOR GAUGE CORNER CONTACT USING GEOMETRY OF SATO (2005) WITH A NORMAL LOAD OF 150 KN AND FRICTION FORCE OF 0.185 TIMES THE NORMAL FORCE. ................................................................................................... 74
FIGURE 34 – STRESS DISTRIBUTION FOR GAUGE CORNER CONTACT USING GEOMETRY OF SATO (1994) WITH A NORMAL LOAD OF 150 KN AND FRICTION FORCE OF 0.37 TIMES THE NORMAL FORCE. ................................................................................................... 75
FIGURE 35 - STRESS DISTRIBUTION FOR A HEAVY HAUL CARRIAGE WITH A 27.5 TONNE AXLE LOAD TRAVELLING AT 42KM/HR INTO A 300M RADIUS CORNER USING THE RAIL PROFILE FROM SATO(2005) WITH A SUPER-ELEVATION OF 100MM AND RAIL GAUGE WIDTH OF 1067MM...................................................................................................... 77
FIGURE 36 – STRESS DISTRIBUTION FOR A SIMULATOR WITHOUT BRAKING TORQUE APPLIED...................................................................................................................................... 78
FIGURE 37 - STRESS DISTRIBUTION FOR A SIMULATOR WITH BRAKING TORQUE 15 N.M APPLIED. ...................................................................................................................... 79
FIGURE 38 - STRESS DISTRIBUTION FOR A SIMULATOR WITH BRAKING TORQUE 65 N.M APPLIED. ...................................................................................................................... 80
FIGURE 39 - STRESS DISTRIBUTION FOR A SIMULATOR TREAD LOAD OF 12.5 KN WITHOUT BRAKING TORQUE APPLIED. ........................................................................................ 80
FIGURE 40 - STRESS DISTRIBUTION FOR A SIMULATOR TREAD LOAD OF 12.5 KN WITH BRAKING TORQUE 15 N.M APPLIED............................................................................. 81
FIGURE 41 - STRESS DISTRIBUTION FOR A SIMULATOR TREAD LOAD OF 12.5 KN WITH BRAKING TORQUE 65 N.M APPLIED............................................................................. 82
FIGURE 42 – CONTACT STRESS MAGNITUDES FOR STRESS COMPONENTS USING CONDITIONS OF TREAD LOADING AT 9.5KN, 41.3MM CONTACT LENGTH........................................ 84
FIGURE 43 - CONTACT STRESS MAGNITUDES FOR STRESS COMPONENTS USING CONDITIONS OF TREAD LOADING AT 9.5KN, 20 MM CONTACT LENGTH. ......................................... 85
FIGURE 44 –CONTACT STRESS MAGNITUDES FOR STRESS COMPONENTS USING CONDITIONS OF TREAD LOADING AT 9.5KN, DYNAMOMETER TORQUE 15N.M, AND 41.3 MM CONTACT LENGTH. ...................................................................................................... 86
FIGURE 45 – ONE DIMENSIONAL SHEAR................................................................................ 89 FIGURE 46 – SHEAR RATE PREDICTION FOR AN EHL FILM UNDER THE RANGE OF
CONDITIONS FOR THE SIMULATOR. ............................................................................. 90 FIGURE 47 – SHEAR RATE PREDICTION FOR AN EHL FILM UNDER THE RANGE OF
CONDITIONS FOR IN-SERVICE CONDITIONS.................................................................. 91 FIGURE 48- SCHEMATIC DIAGRAM OF THE RAIL/WHEEL SIMULATOR................................... 97 FIGURE 49 – TREAD LOADING MECHANISM SHOWING ORIGINAL SCREW FORCE APPLICATOR.
................................................................................................................................... 100 FIGURE 50 – SIMPLIFIED WHEEL SAMPLE HOLDER ASSEMBLY. THE LARGE FLAT SECTION AT
THE LEFT IS THE SLIDER WHICH MOVES IN THE CHANNEL. AT THE LEFT END OF THE DEVICE THE CONTACT SURFACES CAN BE OBSERVED. .............................................. 102
FIGURE 51 – HYDRAULIC DYNAMOMETER SYSTEM............................................................ 105
vii
FIGURE 52 – RAIL SAMPLE WITH OXIDATIVE AND FATIGUE WEAR (A). WHEEL SAMPLE WITH OXIDISED MATERIAL REMOVED TO HIGHLIGHT PLASTIC DEFORMATION (B). ........... 107
FIGURE 53 – RAIL SAMPLE MOUNTED IN MACHINING JIG FOLLOWING INITIAL LATHE CUT, WITH PITTING AT THE OUTER EDGE OF THE RAIL SAMPLE(A). WHEEL SAMPLE WITH HARDENED MATERIAL, THE SMOOTHER RING, AT THE OUTER EDGE OF THE SAMPLE (B).............................................................................................................................. 108
FIGURE 54(A,B,C,D) – WEAR DEVELOPMENT OF RUNNING SURFACES ON WHEEL AND RAIL SAMPLES (LEFT TO RIGHT, TOP TO BOTTOM)............................................................. 109
FIGURE 55 – WEAR DEVELOPMENT OF RUNNING SURFACE FOLLOWING REPEATED LUBRICATED TESTS (A-C) WEAR PARTICLES AND EXCESS LUBRICANT (D). ............. 111
FIGURE 56 – GREASE APPLICATION PATTERN (A) AND SUBSEQUENT LUBRICANT FILM FAILURE OF RUNNING SURFACES (B). ........................................................................ 112
FIGURE 57 – (A)WEAR PARTICLES COLLECTED FROM LUBRICANT, TWO DISTINCT PARTICLE SIZES ARE ATTACHED TO THE MAGNETIC SAMPLE COLLECTOR (8MM DIAMETER). (B) DEMAGNETISED WEAR PARTICLES AT HIGHER MAGNIFICATION. ............................. 113
FIGURE 58 – (A) LUBRICANT FILM FAILURE ON RIGHT OF SAMPLE (B) LUBRICANT FILM FAILURE ON LEFT OF SAMPLE. MATERIAL REMOVED FROM THE SURFACE OF THE RAIL SAMPLE DESTROYS LUBRICANT FILM OVER A NOMINAL CONTACT WIDTH DEPENDING ON THE SIZE OF THE WEAR PARTICLES. ..................................................................... 114
FIGURE 59 – VARIABLE FREQUENCY DRIVE DISPLAY TORQUE VERSUS ANALOGUE OUTPUT CIRCUIT TO DATA ACQUISITION SYSTEM. NOTE: ALL VALUES FOR CALIBRATION NOT PLOTTED. ................................................................................................................... 121
FIGURE 60 – DIAGRAM OF TWIN-DISK ARRANGEMENT WITH NOMENCLATURE. ................ 124 FIGURE 61 – TORQUE COMPONENT DIAGRAM FOR OUTPUT SHAFT. ................................... 126 FIGURE 62 - MAXIMUM FLANGE SLIDING VELOCITY FOR A TYPICAL COMMUTER TRAIN
WHEEL DIAMETER (600MM). ..................................................................................... 128 FIGURE 63 - MAXIMUM FLANGE SLIDING VELOCITY FOR A TYPICAL HEAVY HAUL TRAIN
WHEEL DIAMETER (860MM). ..................................................................................... 129 FIGURE 64 – REFERENCE LOAD CELL CALIBRATION CURVE OR OUTPUT STRAIN VERSUS
INPUT LOAD AS APPLIED BY CALIBRATED MATERIALS TESTING DEVICE. ................. 130 FIGURE 65 – NORMAL VERSUS REFERENCE LOAD CELLS CALIBRATION CURVE. ............... 130 FIGURE 66 - POWER VERSUS TIME GRAPHS FOR WARM-UP PRIOR TO TESTING. DATA
PRESENTED HAS NOT BEEN PRE-PROCESSED. ............................................................ 134 FIGURE 67 – SLIP VERSUS TIME FOR THE TWO DEFINED WARM-UP PERIODS OF ZERO AND SET
BRAKING FORCES. ..................................................................................................... 136 FIGURE 68 – TEST SAMPLE TEMPERATURES AND SLIP VERSUS TIME FOR GROUP 1
LUBRICANT A TEST 1................................................................................................ 141 FIGURE 69 – EXPONENTIAL DECAY CURVE FITTED TO POWER LOSS DATA FOR GROUP 1
CONDITIONS............................................................................................................... 154 FIGURE 70 – EXPONENTIAL DECAY CURVE FITTED TO SLIP DATA FOR GROUP 1 CONDITIONS.
................................................................................................................................... 155 FIGURE 71 – BOX AND WHISKER PLOT OF NORMAL FORCE FOR EACH OF THE TESTS IN GROUP
1. ............................................................................................................................... 157 FIGURE 72 – BOX AND WHISKER PLOT OF INPUT ROLLING VELOCITY FOR EACH OF THE TESTS
IN GROUP 1................................................................................................................ 158 FIGURE 73 – BOX AND WHISKER PLOT OF BRAKING TORQUE UNDER FULLY DEVELOPED
CONDITIONS FOR EACH OF THE TESTS IN GROUP 1.................................................... 158 FIGURE 74 - NORMAL FORCE AND BULK SAMPLE TEMPERATURE VERSUS TIME FOR GROUP 1
TEST 1 LUBRICANT A................................................................................................ 159 FIGURE 75 - CUMULATIVE ABSORBED ENERGY OF LUBRICANT FILM VERSUS TIME FOR
GROUP 1. ................................................................................................................... 161 FIGURE 76 – POWER ABSORPTION RATES FOR EACH LUBRICANT IN GROUP 1 TESTS. NOTE
DIFFERENT TIME SCALES FOR EACH LUBRICANT....................................................... 162 FIGURE 77 - CUMULATIVE ABSORBED ENERGY VERSUS TIME FOR LUBRICANT C. ............ 163
viii
FIGURE 78 – TOTAL ENERGY ABSORBED PRIOR TO SET TRACTIVE FORCE LIMIT FOR GROUP 1.................................................................................................................................... 164
FIGURE 79 – OUTPUT TORQUE PROFILES FOR GROUP 1. ..................................................... 165 FIGURE 80 – SLIDING DISTANCE OF LUBRICANT PRIOR TO SET TRACTIVE FORCE LIMIT FOR
GROUP 1. ................................................................................................................... 166 FIGURE 81 – SLIDING VELOCITY PROFILE FOR GROUP 1..................................................... 167 FIGURE 82 – (TOP) HALF LIFE PREDICTION FOR GROUP 1 USING ( ) bxf x ae c−= + .
(BOTTOM) VALUE OF PREDICTED MINIMUM SLIP ‘C’. ............................................... 168 FIGURE 83 – REGRESSION PLOTS FOR LUBRICANT A TEST 2 GROUP 1 IN THE REGION < 5%
SLIP. ........................................................................................................................... 169 FIGURE 84 - HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 1 TESTING USING
( ) bxf x ae−= . ....................................................................................................... 170 FIGURE 85 – APPARENT VISCOSITY FOR GROUP 1. ............................................................. 171 FIGURE 86 - SLIP PROFILES FOR GROUP 2 AFTER SET CUT OFF LIMIT OF SLIP ACHIEVED.
LUBRICANT B TESTS 2 AND 3 HAD LIMITS OF 8% AND 7% RESPECTIVELY. ............. 172 FIGURE 87 - CUMULATIVE ABSORBED ENERGY VERSUS TIME FOR GROUP 2. ENERGY IS
CALCULATED FROM THE DIFFERENCE BETWEEN INPUT AND OUTPUT ENERGY. NOTE THE DIFFERENT SCALES ON VERTICAL AND HORIZONTAL AXES. .............................. 173
FIGURE 88 – TOTAL ENERGY ABSORBED PRIOR TO SET TRACTIVE FORCE LIMIT FOR GROUP 2.................................................................................................................................... 174
FIGURE 89 – POWER ABSORPTION RATES FOR EACH LUBRICANT IN GROUP 2 TESTS. NOTE THE DIFFERENT SCALES ON THE HORIZONTAL AXIS. ................................................. 175
FIGURE 90 – SLIDING DISTANCE OF LUBRICANT PRIOR TO SET TRACTIVE FORCE LIMIT FOR GROUP 2. ................................................................................................................... 176
FIGURE 91 – SLIDING VELOCITY PROFILES FOR GROUP 2. NOTE THE DIFFERENT SCALES ON THE HORIZONTAL AXIS. ............................................................................................. 177
FIGURE 92 – (TOP) HALF LIFE PREDICTION FOR GROUP 2 USING ( ) bxf x ae c−= + . (BOTTOM) VALUE OF PREDICTED MINIMUM SLIP ‘C’ OR OFFSET COEFFICIENT......... 178
FIGURE 93 - HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 2 TESTING USING
( ) bxf x ae−= . ....................................................................................................... 179 FIGURE 94 - APPARENT VISCOSITY FOR GROUP 2............................................................... 180 FIGURE 95 - CUMULATIVE ABSORBED ENERGY VERSUS TIME FOR GROUP 3. ENERGY IS
CALCULATED FROM THE DIFFERENCE BETWEEN INPUT AND OUTPUT ENERGY. NOTE THE DIFFERENT SCALES ON VERTICAL AND HORIZONTAL AXES. .............................. 181
FIGURE 96 – TOTAL ENERGY ABSORBED PRIOR TO SET SLIP LIMIT FOR GROUP 3. ............. 182 FIGURE 97 – POWER ABSORPTION RATES FOR EACH LUBRICANT IN GROUP 3 TESTS. NOTE
THE DIFFERENT SCALES ON THE HORIZONTAL AXIS. ................................................. 183 FIGURE 98 – SLIDING DISTANCE OF LUBRICANT PRIOR TO SET TRACTIVE FORCE LIMIT FOR
GROUP 3. ................................................................................................................... 184 FIGURE 99 – SLIDING VELOCITY PROFILE FOR GROUP 3. NOTE THE DIFFERENT SCALES ON
THE HORIZONTAL AXIS. ............................................................................................. 185 FIGURE 100 – OUTPUT TORQUE SIGNAL FOR LUBRICANT A IN GROUP 3. .......................... 186 FIGURE 101 – (TOP) HALF LIFE PREDICTION FOR GROUP 3 USING ( ) bxf x ae c−= + .
(BOTTOM) VALUE OF PREDICTED MINIMUM SLIP ‘C’. ............................................... 187 FIGURE 102 - HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 3 TESTING USING
( ) bxf x ae−= . ....................................................................................................... 188 FIGURE 103 – APPARENT VISCOSITY FOR GROUP 3. ........................................................... 189
ix
FIGURE 104 - CUMULATIVE ABSORBED ENERGY VERSUS TIME FOR GROUP 4. ENERGY IS CALCULATED FROM THE DIFFERENCE BETWEEN INPUT AND OUTPUT ENERGY NOTE THE DIFFERENT SCALES ON VERTICAL AND HORIZONTAL AXES. .............................. 190
FIGURE 105 – TOTAL ENERGY ABSORBED PRIOR TO SET TRACTIVE FORCE LIMIT FOR GROUP 4. ............................................................................................................................... 191
FIGURE 106 – POWER ABSORPTION RATES FOR EACH LUBRICANT IN GROUP 4 TESTS. NOTE THE DIFFERENT SCALES ON THE HORIZONTAL AXIS. ................................................. 192
FIGURE 107 – SLIDING DISTANCE OF LUBRICANT PRIOR TO SET TRACTIVE FORCE LIMIT FOR GROUP 4. ................................................................................................................... 193
FIGURE 108 – SLIDING VELOCITY PROFILE FOR GROUP 4. NOTE THE DIFFERENT SCALES ON VERTICAL AND HORIZONTAL AXES. .......................................................................... 194
FIGURE 109 – (TOP) HALF LIFE PREDICTION FOR GROUP 4 USING ( ) bxf x ae c−= + . (BOTTOM) VALUE OF PREDICTED MINIMUM SLIP ‘C’. ............................................... 195
FIGURE 110 - HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 4 TESTING USING
( ) bxf x ae−= ........................................................................................................ 196 FIGURE 111 – APPARENT VISCOSITY FOR GROUP 4. ........................................................... 197 FIGURE 112 – TOTAL ABSORBED ENERGY FOR GROUPS OF TESTS. NOTE THE DIFFERENT
SCALES ON THE VERTICAL AXIS................................................................................ 198 FIGURE 113 – TOTAL SLIDING DISTANCE PRIOR TO SET TRACTIVE FORCE LIMIT. NOTE THE
DIFFERENT SCALES ON THE VERTICAL AXIS. ............................................................ 199 FIGURE 114 – HALF LIFE VALUES SUMMARY NOTE THE DIFFERENT SCALES ON THE
VERTICAL AXIS. ........................................................................................................ 201 FIGURE 115 – APPARENT VISCOSITY VERSUS TIME FOR GROUP 1. NOTE THE DIFFERENT
SCALES ON THE HORIZONTAL AXIS. .......................................................................... 205 FIGURE 116 - APPARENT VISCOSITY VERSUS TIME FOR GROUP 2. NOTE THE DIFFERENT
SCALES ON THE HORIZONTAL AXIS. .......................................................................... 207 FIGURE 117 - APPARENT VISCOSITY VERSUS TIME FOR GROUP 3. NOTE THE DIFFERENT
SCALES ON THE HORIZONTAL AXIS. .......................................................................... 208 FIGURE 118 - APPARENT VISCOSITY VERSUS TIME FOR GROUP 4. NOTE THE DIFFERENT
SCALES ON THE HORIZONTAL AXIS. .......................................................................... 209 FIGURE 119 – ARES RHEOMETER USED FOR RHEOLOGY TESTING. ................................... 213 FIGURE 120 – CONE AND PLATE ARRANGEMENT FOR RHEOMETER TESTING. .................... 214 FIGURE 121 – APPARENT VISCOSITY VERSUS SHEAR RATE USING A FLAT PLATE
RHEOMETER............................................................................................................... 215 FIGURE 122 – ASTM D1092 GREASE PUMPABILITY RESULTS. ......................................... 217 FIGURE 123 - ASTM D2596 FOUR BALL WEAR TEST RESULTS. ........................................ 218 FIGURE 124 – ASTM D2596 WELD LOAD RESULTS........................................................... 219 FIGURE 125 – ASTM D2266 SCAR DIAMETER RESULTS. ................................................... 220 FIGURE 126 – TWO CROSSED CYLINDERS CALCULATION EXAMPLE(ESDU 1995). ........... 273
x
LIST OF TABLES
TABLE 1 LUBRICATION EFFECTIVE DISTANCE (MARICH ET AL. 2001A). 36 TABLE 2 – INPUT PARAMETERS FOR CONTACT STRESS PREDICTIONS USING THE PROFILES OF
SATO (2005) 70 TABLE 3 – TEST PARAMETERS USED FOR CONTACT MECHANICS CALCULATIONS 77 TABLE 4 - MANUFACTURER SPECIFIED VISCOSITY VALUES FOR TESTED LUBRICANTS. 87 TABLE 5 – PREDICTED MINIMUM LUBRICANT FILM THICKNESSES FOR TESTED LUBRICANTS.
88 TABLE 6 – THEORETICAL RESULTS FOR INPUTS TO EHL CALCULATIONS. 95 TABLE 7 - MATERIAL PROPERTIES OF TEST SAMPLES (MARICH AND MUTTON 1989). 115 TABLE 8 – MECHANICAL PROPERTIES OF SIMILAR HIGH CARBON STEEL ALLOYS
(AUTOMATION CREATIONS 2005B; AUTOMATION CREATIONS 2005A). 115 TABLE 9- MEASURED HARDNESS RESULTS FOR RAIL AND WHEEL SAMPLES WITH MINIMAL
LOADING CYCLES. 116 TABLE 10 – RAIL SAMPLE HARDNESS RANGE IN HB (BRINELL 3000 KGF STD). 116 TABLE 11 - WHEEL SAMPLE HARDNESS RANGE IN HB (BRINELL 3000 KGF STD). 116 TABLE 12 – ROUGHNESS MEASUREMENTS TAKEN FROM WHEEL AND RAIL SAMPLES AFTER
MACHINING AND AT THE COMPLETION OF ALL LUBRICATED TESTING. 117 TABLE 13 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF SURFACE VELOCITIES
FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 139
TABLE 14 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF SURFACE VELOCITIES FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 139
TABLE 15 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF SLIP RATIO FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 140
TABLE 16 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF SURFACE VELOCITIES FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 142
TABLE 17 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF INPUT AND OUTPUT POWER FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 142
TABLE 18 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF DISTANCE ROLLED FOR GROUP 1 TEST PARAMETERS. SUBSCRIPTS REFER TO INPUT AND OUTPUT SHAFTS. 143
TABLE 19 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF DISTANCE SLID AND POWER ABSORBED FOR GROUP 1 LUBRICANT A TEST 1 RESULTS. 145
TABLE 20 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF DISTANCE SLID AND POWER ABSORBED FOR GROUP 1 LUBRICANT A TEST 1 RESULTS. 147
TABLE 21 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF SURFACE VELOCITIES FOR GROUP 1 TEST PARAMETERS. 148
TABLE 22 - VALUES FOR EXPERIMENTAL ERROR CALCULATION OF APPARENT VISCOSITY, SHEAR STRESS AND SHEAR RATEFOR GROUP 1 TEST PARAMETERS. 149
TABLE 23 – TESTING VARIABLE VALUES. 152 TABLE 24 – EXTRAPOLATED MINIMUM VALUES FROM EXPERIMENTAL DATA. 155 TABLE 25 – HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 1 TESTING USING
( ) bxf x ae−= . 169 TABLE 26 – HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 1 TESTING USING
( ) bxf x ae−= . 179
xi
TABLE 27 – HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 1 TESTING USING
( ) bxf x ae−= . 188 TABLE 28 – HALF LIFE VALUES FOR EACH LUBRICANT IN GROUP 1 TESTING USING
( ) bxf x ae−= . 196 TABLE 29 – LUBRICANT PERFORMANCE SUMMARY. 202 TABLE 30 – RELATIVE LUBRICANT PERFORMANCE SUMMARY. 203 TABLE 31 – QUALITATIVE PERFORMANCE OF LUBRICANTS. 204 TABLE 32 – EXAMPLE VALUES FOR NEEDLE ROLLER IN BEARING RACE (2003). 271 TABLE 33 – COMPARISON OF RESULTS BETWEEN CALCULATION METHODS. 271 TABLE 34 – EXAMPLE VALUES FOR TWIN-DISK FATIGUE TESTING DEVICE WITH IDENTICAL
STEEL SAMPLES (ESDU 1995). 272 TABLE 35 – COMPARISON OF RESULTS BETWEEN CALCULATION METHODS OF CONTACT
STRESSES FOR TWIN DISK FATIGUE TESTING MACHINE (VALUES IN PARENTHESES CALCULATED WITHOUT FRICTION/TRACTION FORCE). 272
TABLE 36 – EXAMPLE VALUES FOR CROSSED CYLINDERS OF DIFFERING MATERIALS (2003). 273
TABLE 37 – COMPARISON OF RESULTS BETWEEN CALCULATION METHODS. 274 TABLE 38 – COMPARISON OF RESULTS BETWEEN CALCULATION METHODS OF ESDU AND
AUTHOR’S FOR PRINCIPAL AXIS ANGLE OF 90 DEGREES. 274 TABLE 39 – ELLIPTICAL CONTACT EXAMPLE FOR TWO TOROIDS IN CONTACT (2003). 275 TABLE 40 - COMPARISON OF RESULTS BETWEEN CALCULATION METHODS OF BORESI AND
SCHMIDT (1985) AND AUTHOR’S. 275
xii
STATEMENT OF ORGINAL AUTHORSHIP
The work contained in this thesis has not been previously submitted for a
degree or diploma at any other higher education institution. To the best of my
knowledge and belief, the thesis contains no material previously published or
written by another person except where due reference is made.
Signature: _______________________________
Lance Jon Wilson
Date:____________________________________
xiii
ACKNOWLEDGMENTS
The author wishes to thank all the technical staff of the School of Mechanical
Manufacturing and Medical Engineering. Special thanks to Wayne Moore,
Mark Hayne, Terry Beach, David McIntosh, David Allen, Alf Small, Glen
Turner and Jonathan James. I would also like thank Queensland Rail who has
supported this project both financially and with expert opinion.
Thanks go to CIEAM and the AMM group at QUT for financial support.
Special thanks to the supervisors of this project, Doug Hargreaves, Richard
Clegg and John Powell.
Thank you to my friends and family who have supported me throughout this
project.
To Patrick, the most determined man on the planet, thanks for giving me the
“Harden up and dry your eyes” at the most opportune moment and reigniting
my interest in research.
To Cameron thanks for helping me out with the quantitative analysis, and for
the editing services.
To Fiona my life partner, special thanks for all the support.
xiv
NOMENCLATURE
a = Major ellipse semi axis or contact half width
cA = Contact area
cA∂ = Error in contact area
ya = Acceleration in the ‘y’ direction
,A B = Geometry parameters
b = Minor ellipse semi axis or contact half width
ob = Gauge width
D = Distance rolled
D∂ = Error in distance rolled
iD = Distance rolled of input shaft
iD∂ = Error in distance rolled of input shaft
oD = Distance rolled of output shaft
oD∂ = Error in distance rolled of output shaft
sD = Distance slid
sD∂ = Error in distance slid
xv
TD = Total distance slid
TD∂ = Error in total distance slid
e = Proportion of total value
E = Young’s modulus
'E = Effective modulus
E = Absorbed energy
E∂ = Error in absorbed energy
sE = Sliding energy
sE∂ = Error in sliding energy
TE = Total Absorbed energy
TE∂ = Error in absorbed energy
( )E m = Complete elliptical integral of the second kind
( )f x = Function of x
F = Friction force
BTF = Force from shearing lubricant
FF = Flange force
g = acceleration due to gravity
xvi
ah = Super-elevation of rail
minh% = Minimum film thickness
K = Contact width equation constant
ik = Material constant, i denotes body number
( )K m = Complete elliptical integral of the first kind
L = Length of rectangular contact
lΔ = Change in length
0l = Original length
Tm = Mass of train carriage
n = Number of measurements
( ) ( ) ( ), , , , , ,p p y p x y p x y z = Pressure or pressure at location
P = Normal force
fP = Power absorbed by friction in simulator
maxP = Maximum power
iP = Power of input shaft
iP∂ = Error in power of input shaft
0p = Maximum pressure
xvii
oP = Power of output shaft
oP∂ = Error in power of output shaft
sP = Power absorbed by lubricant
sP∂ = Error in power absorbed by lubricant
xQ = Tractive force in direction of rolling
r = Rolling radius
r∂ = Error in rolling radius
R = Effective contact radius
cR = Curve radius
DR = Curvature difference
iiR = Radius of curvature, first i denotes body number and second i axis
number
ir = Rolling radius of input shaft
ir∂ = Error in rolling radius of input shaft
or = Rolling radius of output shaft
or∂ = Error in rolling radius of output shaft
xR = Effective radius in ‘x’ direction
xviii
yR = Effective radius in ‘y’ direction
t = Sample time
T = Torque
T∂ = Error in torque
BFT = Bearing friction torque
CT = Transmitted torque through contact patch
tt = Thickness
TT = Torque transducer torque
TΔ = Change in temperature
iT = Torque of input shaft
iT∂ = Error in torque of input shaft
oT = Torque of output shaft
oT∂ = Error in torque of output shaft
maxT = Maximum torque
u% = Mean surface velocity
v = Surface velocity
v∂ = Error in surface velocity
xix
iv = Surface velocity of input shaft
iv∂ = Error in surface velocity of input shaft
ov = Surface velocity of output shaft
ov∂ = Error in surface velocity of output shaft
,s su v = Sliding velocity
sv∂ = Error in sliding velocity
Tv = Train velocity
VΔ = Change in volume
HV = Volume when heated
0V = Original volume
W = Dimensionless load parameter
w = Rotational Speed
w∂ = Error in rotational speed
iw = Rotational Speed of input shaft
iw∂ = Error in rotational speed of input shaft
ow = Rotational Speed of output shaft
ow∂ = Error in rotational speed of output shaft
xx
zw = Load per unit width
x = Distance slid
y = Lubricant film thickness
lα = Linear thermal expansion coefficient
μ = Coefficient of friction
ξ = Experimental slip ratio
PVξ = Pressure viscosity coefficient
ξ∂ = Error in experimental slip ratio
xξ = Slip ratio in the direction of rolling
Vα = Volume thermal expansion coefficient
φ = Diameter
δ = Normal approach of bodies
yσ = Yield stress
yτ = Shear yield stress
USσ = Ultimate tensile strength
USτ = Ultimate shear yield strength
xxi
σ = Poisson’s ratio
xσ , yσ , zσ = Stresses in principal directions
η = Apparent viscosity
η∂ = Error in apparent viscosity
τ = Shear stress
τ∂ = Error in shear stress
xyτ , yzτ , zxτ = Shear stresses in principal directions
eτ = Effective shear stress, square root of second invariant of deviator tensor
γ = Shear strain
γ& = Shear strain rate
γ∂ & = Error in shear strain rate
β = Ellipse semi-axes ratio
0η = Absolute viscosity
Subscripts i = Subscript denoting input shaft
o = Subscript denoting output shaft
, ,x y z = Subscript denoting direction
1, 2 = Subscripts denoting body number
C h a p t e r 1
INTRODUCTION
1.1 Background
Wear of railroad rolling stock and rails costs millions of dollars each year in all
rail systems throughout the world. Excessive levels of noise are generated at
the rail/wheel interface in conjunction with wear, which is unacceptable in an
environmentally responsible rail network. It is commonly accepted that wear
and noise can be reduced through the use of lubrication at the rail/wheel
interface (Scott et al. 1998).
Wear of rail rolling stock is generally divided into two main areas, flange wear
and tread wear. These areas of wear are related to the contact points at the
rail/wheel interface. This thesis focuses on rail curve lubrication, with specific
emphasis on lubrication in the gauge corner (the location where the external
corner of the rail and the internal corner of the wheel contact). The reasons
for targeting the flange area is that flange wear has a significantly higher
maintenance cost and that increased flange contact increases energy
consumption (Reiff 1986; O'Rourke et al. 1989).
In industry, attempts have been made to address flange wear using lubricants.
There are presently a large number of lubricants and lubricant applicators
used on existing rail networks. The choice of lubricant and applicator is
currently based on considerations that do not address the problem of wear
directly. This is reflected by a lack of fundamental knowledge in the
performance of rail curve lubricants.
In the work of Clayton et al. (1988; 1989) lubricants were investigated in both
track and laboratory conditions. The field testing was designed to measure the
four features that Clayton et al. proposed are important for flange lubrication:
mobility (lubricant transport from the application point); durability (number
2
of axles to dry conditions); lubricity (reduction of friction); and contamination
(migration of the lubricant to the rail tread). Aspects of lubricity and durability
were investigated in the laboratory using a twin disk Amsler device. The
results of the field testing yielded a low correlation between field and
laboratory. In addition to this low correlation it was found the lubrication
conditions in the two tests were different. Furthermore Clayton et al. (1989)
questioned the statistical variation in performance between the lubricants. In
summary Clayton et al. (1989) states “At the present time, no laboratory test
would appear to be able to be used with confidence to evaluate the in-service
performance of wheel/rail lubricants.” The rail/wheel simulator developed in
the current thesis was designed and tested to achieve confidence in laboratory
testing of rail curve lubricants.
Witte and Kumar (~1986) and Kumar et al. (1991) designed a new test and
apparatus for design of rail lubricants in response to an industry need for a
standard test. Their focus, in terms of lubricant properties, was on lubricant
mobility, durability and lubricity. Their work ignored the effects of lubricant
migration that was investigated in the work of Clayton et al. (1988; 1989).
Witte and Kumar's (~1986) new device focused on simulating the stress and
creep properties, which is in contrast to work of Clayton et al. (1988; 1989)
that utilised a standard laboratory wear test device.
The results of Witte and Kumar's (~1986) concluded that the new test
correlated with a larger wheel/rail simulator, but quantitative correlation with
field data was not performed as in the work of Clayton et al. (1989).
Qualitative comparison between the laboratory and field data yielded some
correlation but the results were inconclusive. In summary the results of this
work provided a methodology for the analysis of lubricants with respect to
the parameters relevant to the wheel/rail system.
3
This thesis will address the lack of fundamental knowledge in the
determination of lubricant performance in gauge corner contact, focussing on
the equipment and the methodology employed in testing performance.
The rail industry requires a method for predicting the in-service performance
of a flange lubricant from a laboratory environment. Clear identification of
the in-service conditions of the rail over a range of conditions is required to
achieve such a method. A replica can then be made within a laboratory
environment where conditions can be varied and the effect of the lubricant
on the rail/wheel contact directly quantified.
It is the author's opinion from discussion with rail industry professionals and
from the broad rail industry literature that an effective lubricant for the flange
contact must possess the following characteristics:
• It must be highly adhesive to pearlitic steel;
• It must be able to maintain a protective film despite high velocity
rolling contact;
• When the lubricant is struck by the opposite contact surface the
lubricant must spread across this surface and not be expelled from the
contact into an undesirable location (ground, top of rail, rail vehicle
body);
• The lubricant must have the ability to be spread from the initial
application point down the rail and around the wheel;
• The lubricant must have a predictable decay in coefficient of friction
or lubricant effectiveness as a catastrophic lubricant film failure
translates to maximum wear. If wear is considered an energy based
process (Huq and Celis 2002) then as the coefficient of friction
increases there is a corresponding increase in the wear energy.
4
• For the purposes of inspection of lubricator functionality by
maintenance personnel the lubricant could exhibit an observable
colour.
• The lubricant must have a high resistance to sliding and sliding wear
processes.
Anecdotally the most significant issue in rail curve lubrication is the
application of the lubricant. European railways disable their wayside
lubricators during the winter months and use snow as the flange lubricant
(Waara 2001). The reasons behind this are twofold, primarily the lubricant
applicators do not function in the cold and cannot be maintained whilst
buried beneath the snow, and the other reason is that the snow itself appears
to provide adequate lubrication. Wear measurements carried out during
winter and summer in Sweden confirmed that snow is an effective lubricant
(Nilsson 2002). This form of lubrication is unsuitable in a warm environment.
In a warm environment without frozen winters, such as the Australian
Queensland Rail network, an effective lubricant must be applied.
With the desired properties of rail/wheel lubrication identified, a suitable
method for quantifying the effect on the rail/wheel system to variations in
lubrication properties is required.
1.2 Objective of Research
The objective of this research is to quantify rail curve lubricant performance
through laboratory simulation. The steps to achieve the objective of this
thesis were:
Measure the properties of the lubricants currently in use.
The lubricants have been laboratory tested to define the properties using the
ASTM and other appropriate standards.
5
Calculate and predict the contact mechanics at the wheel and rail gauge face.
A literature survey identified the methodologies employed to measure and
predict the rail/wheel contact conditions. Upon review, a suitable method was
selected and used to analyse the laboratory simulation devices.
Identify the wear mechanisms at the wheel and rail gauge face.
The wear mechanisms were identified using the parameters of the contact and
comparison with the body of literature. Wear particles were gathered and
inspected to assist in verifying the wear mechanism identified. Microscopic
inspection of the surfaces was carried out.
Quantify the effect of lubrication on the wear mechanisms arising from sliding and transmitted forces.
The laboratory simulator was used to gather data in lubricated and
unlubricated conditions for the purpose of providing lubricant performance
measurements.
Identify the tribological parameters required to minimise wear without introducing competing wear mechanisms.
Analysis of the results from the lubricant testing and laboratory simulators
determined trends between them. These trends indicated the lubricant
properties' effects on the system.
In addition to these steps, new methods for rail curve lubricant performance
measurement will be presented. These measurements include total absorbed
energy, the energy absorbed in the lubricant film instead of being utilised for
wear processes; total distance slid, the sliding distance or accumulated strain
achieved prior to development of a set tractive force limit; half life of
lubricant, the time taken for a lubricant to lose half of its sliding performance;
and apparent viscosity, a measure of the lubricity presented with respect to
accumulated strain.
6
Lubrication can be optimised for industry to effect a reduction in flange wear
so that maintenance resources are minimised and the rail/wheel life
maximized. The method used to achieve this will quantify rail curve lubricant
performance through laboratory simulation
1.3 Summary and Thesis Outline
Chapter 2 will explore the issues surrounding rail/wheel lubrication to
provide an overview of the area. Chapter 3 will then present the contact
mechanics relevant to this thesis with examples of in-service and simulated
conditions. This chapter highlights the similarities and differences of
simulator and 'real world' conditions to gain an insight into the experimental
methodology of Chapter 4. The rail/wheel simulator used in this work was
formerly a device used for rail/wheel materials investigations. Chapter 4
details the modifications to the simulator to analyse lubricant performance, as
well as the method, measurements and their associated errors. Chapter 5
presents all the experimental results from standards-based lubricant testing
and results from the simulated rail conditions with discussion on industrial
relevance and experimental findings. Finally, Chapter 6 summarises the
findings of the research, presents the conclusions and discusses directions of
future work.
7
C h a p t e r 2
LITERATURE REVIEW
2.1 Rail/Wheel Wear Testing
Rail/wheel wear testing is of interest to this research as these devices are
designed to replicate the wear conditions of a rail/wheel contact. Testing of
rail and wheel materials has been and is carried out to optimise the costs
associated with the wear of these materials by researchers and commercial
interests (Marich and Mutton 1989; Lee and Polycarpou 2005). Tests are
usually carried out with scaled models as, in most cases, the feasibility of
constructing a full size system is impractical and the costs prohibitive. In the
smaller testing apparatus two main types of apparatus are popular, twin disk
testing (see Figure 1), and pin on disk testing. A variant of the pin on disk
testing, ball on flat is shown in Figure 2.
The scientific and engineering communities have investigated the validity of
laboratory simulation when compared to specific real world engineering
problems. Marich and Mutton (1989) and Witte and Kumar (~1986), have
attempted to model the rail/wheel interface with limited success. Tribological
simulations are particularly complex to simulate because small changes in
conditions can produce extreme changes in results.
Perfect simulation of wear system is achieved when all of the tribological
conditions are exactly the same as the engineering system being investigated.
This is difficult to achieve, as parameters such as chemical environment,
weather conditions and variations in machine output or load cannot be
simulated in a laboratory environment. A full scale test facility of a rail/wheel
simulator located in Pueblo USA (Hannafious 1995) is a good example of a
thorough simulation, however this facility still suffers from the inability to
control weather conditions.
8
Figure 1 – Twin disk test apparatus from the work of Deters and Proksch (2005).
The author postulates that simulation of the rail/wheel interface, with
particular emphasis on tribology, should therefore:
Identify the required tribological parameters such as geometry (scaled models), contact area, load, sliding speed, material temperature, lubrication (application rate, application area) and chemical environment.
Identify parameters which affect wear modes. In the case of a lubricated flange contact, lubricant application rate significantly affects the wear rate.
Consider the physical size or scale of the simulation. The magnitude of the variation as a result of scale is unknown and must be verified experimentally.
Consider time as a scale factor. In a rail system wear takes several years.
Compare experimental results with the 'real' situation.
9
Swedish researchers Jendel and Nilsson (Jendel 1999; Nilsson 2002) have
begun to address these simulation problems by measuring sections of their
rail network in order to empirically predict the wear rates and investigate
lubricant performance.
Figure 2 – (a) Ball on disk wear test apparatus, specified loading regime and (b) typical wear scar of the work of Lee and Polycarpou (2005).
2.2 Rail/Wheel Wear Processes
Rails and wheels are exposed to a wide range of conditions and wear modes
or processes which lubrication is used to minimise. In order to simulate the
rail/wheel interface a simulator is required to be capable of these processes. A
suitable method of representing the conditions under which each of these
wear processes can occur was presented by Lim and Ashby (1986). They
plotted the results of wear testing and wear models in a non-dimensional
format as shown in Figure 3.
Lim and Ashby (1986) summarise wear modes into four main classifications,
seizure, melt wear, oxidation-dominated wear and plasticity dominated wear.
It is possible for all of the wear process types to occur is a rail/wheel system.
A detailed description of the wear processes, including mathematical models,
is included in Sections A through F in the Appendix A.
10
Figure 3 - Steel pin-on-disk wear map combining results from multiple authors by Lim and Ashby (1986).
2.2.1 Rail/Wheel Wear: Surface initiated rolling contact fatigue
Rail industry infrastructure experiences rolling contact fatigue as a material
failure in rails and wheels due to repeated loading. Two main types of fatigue
cracks occur, surface initiated cracks and subsurface cracks. Surface cracks are
initiated when the surface material reaches its plasticity (strain) limit: further
loading past this point results in cracking. Ratchetting is the process of
accumulated plastic strain from repeated loading. The repeated loading must
be a combination of normal and tractive forces, as the compressive stress
alone is not responsible for the plastic strain. Surface forces, such as traction
11
and creep forces, plastically deform the bulk material. The combination of
stresses and strains gives rise to hardening of materials and residual stresses, at
which point, if the further loading exceeds the material capabilities, will lead
to fatigue failure.
Rolling contact fatigue cracks propagate differently in the mating rail and
wheel faces. Wheels have cracks which penetrate into the material and branch
once the cracks reach a nominal depth. This branching then commonly
proceeds in a circumferential direction until further cracks are reached, then a
piece of the material may detach from the surface. The same process occurs
in rails but the crack can proceed in a direction perpendicular to the contact
and cause a rail break. A driving factor for crack propagation is the friction
associated with the crack faces, which is important when considering the
environment where rolling contact fatigue cracks develop.
2.2.2 Rail/Wheel Wear Particles
Wear particles from rails and wheels are grouped according to wear modes.
The tread contact primarily experiences rolling and micro-slip, whereas closer
to the flange sliding becomes more dominant because of the conical wheel
profile. The rolling and micro-slip region at the tread contact experiences
chemical (oxidative) and fretting wear processes which progress to plastic
deformation wear processes as the proportion of sliding increases (Bolton and
Clayton 1984; Olofsson and Telliskivi 2003). The wear debris from
rolling/sliding processes in the work of Bolton and Clayton (1984) is divided
into three classes. Type I wear is characterised by thin small oxidised wear
particles. Type II wear is characterised by a range of wear particle sizes with
the ability to form agglomerated particles. Type III wear is characterised by
high wear rates, large particle size and extremely rough surface texture.
Later work by Lewis and Dwyer-Joyce (2004) also define three modes of wear
using a wear mapping technique (see Figure 4). The definition of each mode
is based on wear particles, surface appearance, and wear rate. Each work
12
defines the wear modes with a different terminology but the metallurgical
analysis is consistent between them.
Deters and Proksch (2005) also reported similar findings with respect to wear
particles and hypothesised similar wear processes.
Figure 4 - Wear map showing defined wear modes for British Standard rail steels in an Amsler Wear Test Device (Lewis and Olofsson 2004).
2.3 Rail Lubricant Characteristics
Railway systems use a wide variety of lubricants to combat the effects of wear
in the flange contact. These lubricants are usually of three main types, oil,
grease and water. Railway systems often use a combination of lubricants.
Some European rail systems use grease wayside lubricators for six months of
the year and rely on snow (water) for the remaining months (Waara 2001). In
Australia grease wayside lubricators are most widely used, with on-board
lubricators beginning to be used as well. It is still not clear as to what
parameters make a ‘good’ lubricant.
The parameters of amount and location are generally agreed upon to ensure
best practice for lubrication. If the lubricant is not applied correctly it can be
13
spread to the tread of the wheel causing a dangerous loss of traction. Likewise
if the lubricant is applied in the correct location but is in excess, lubricant can
migrate to the tread contact area, again dangerous. Therefore right amount,
right location, is the focus for industry.
Lubricant manufacturers specify the benefits of rail curve lubrication in their
advertising material. They include:
reduction of friction and wear;
reduction or fuel/energy consumption
reduction of noise
reduction of maintenance of rolling stock and rail infrastructure
The lubricant properties they describe as beneficial are:
low toxicity
water resistant
wide temperature operating range
high adhesion to rail and wheel surfaces
good pumpability and compatibility with lubricant applicators
Recent studies by Hannafious (1995) showed benefits of rail lubrication to be
reduced fuel consumption, reduced wheel wear and reduced rail wear. The
lubricant applicators in these studies were of three general types, wayside,
onboard and high rail. The lubricators each had a preferred lubricant type:
wayside and high rail applicators used grease and onboard lubricators used
liquids sprayed onto the contacting surfaces. In addition to the benefits of
lubrication there are a number of negative issues:
Loss of traction from spread to TOR (top of rail)
Environmental damage from used lubricants
Locomotive fires from excess build up of lubricant
14
Increased creep forces resulting in rail roll-over and derailment.
Lubrication is generally applied for two reasons, both based on economics.
Firstly lubrication reduces rolling friction and energy lost to friction, a
reduction in the running costs of a rail network. Secondly reduced wear
provides a reduction in maintenance of rail infrastructure and rolling stock.
Research has focused on the first reason due to the relative ease of measuring
performance (Kumar et al. 1991). Unfortunately the research of Kumar et
al.(1991) has yet to provide any conclusive results as to which lubricant is the
best.
In Australia and USA grease is widely used as oil is considered unsuitable
(International Heavy Haul Association 2001). This paradigm arises from a
number of reasons. The fact that grease will stay adhered to a surface is an
important one as lubricant waste is an environmental and safety issue. Grease
also tends to be more resistant to environmental effects such as temperature
and rain. It is also far easier to add solid lubricants to grease; suspension of
graphite or molybdenum disulfide is difficult to achieve in oil.
Assuming that grease will be the optimum lubricant, parameters that improve
performance need to be targeted. Temperature stability is important, as well
as apparent viscosity. It is of little value if a grease has excellent temperature
stability and a viscosity which prevents it from being pumped. In situation
where flange temperatures may exceed 250°C in the rail/wheel system,
suitable soaps to suspend in grease are limited. Metal soaps are currently used
in lubricating greases to achieve temperature stability. Calcium soap greases
are considered to be suitable for lower temperature conditions, as above 87°C
stability is lost. Calcium greases also have excellent hydrophobic properties
(Polishuk 1998). Lithium soap greases, such as those in use in the Queensland
Rail network, have far higher temperature stability but lack the same
hydrophobic properties as calcium soap greases.
15
The next ingredient, solid lubricant, is responsible for the high load carrying
capacity of grease. Two main types are used, graphite and molybdenum
disulfide. Queensland Rail specify that graphite must be used and in a
minimum concentration. Each solid lubricant displays similar tribological
performance, the differences being impurity concentrations and hydrophobic
behaviour. There are other types of solid lubricants, but not in wide use in rail
curve lubrication.
2.4 Lubrication Regimes
Rail contacts experience a wide range of lubrication regimes in the field and
following is a concise summary of these regimes. Fluid film lubrication is
commonly divided into regimes according to lubricating film thickness
(Hamrock 1994). By listing the regimes, in order, from the largest separation
between bodies to the smallest, gives hydrodynamic lubrication,
elastohydrodynamic lubrication, mixed lubrication and boundary lubrication.
The type of lubrication condition is determined by the load carrying capacity
of the lubricant film. In hydrodynamic lubrication the full load can be
supported by the hydrodynamic forces within the lubricant film.
Elastohydrodynamic lubrication (EHL) is characterised by pressures which
cause local elastic deformation of the surfaces separated by the lubricant film.
EHL is the last regime in which the lubricant film still separates the bodies.
Under mixed-mode lubrication, the lubricant film cannot maintain the
hydrodynamic forces needed to separate the bodies and so partial asperity
contact occurs between the opposing surfaces. Boundary lubrication is the
final regime where surface asperities are supporting the load fully. The rail
curve lubricants under investigation are typically in the EHL lubricating
regime and this will be assumed throughout the thesis.
16
Figure 5 – Separation distances between contacting surfaces for (a) hydrodynamic lubrication (HL)and elastohydrodynamic lubrication, (b) mixed-mode lubrication, and (c) boundary lubrication.
2.5 Rail Curve Lubricant Types Under Investigation
Currently there are two main types of lubricant used on the Queensland Rail
network, Aluminium and Lithium based lubricating greases. These greases will
be measured for performance using standards based tests and the rail/wheel
simulator for the thesis objective, to quantify rail curve lubricant performance.
17
Polishuk (1998) states that aluminium complex greases commonly have the
following properties.
High dropping point
High temperature stability
Excellent water resistance
Low water emulsibility
Good reversibility
Ease of pumpability
Excellent work stability
Reduced oil bleed potential
Good oxidation resistance
Polishuk (1998) also presents that historically aluminium soaps are considered
a polymer. The polymeric property is that upon heating the soap becomes
liquefied and subsequent cooling reforms the structure.
Polishuk (1998) presents the advantageous characteristics of lithium greases
as:
High temperature stability
Water insoluble
Hydrophobic
Good low temperature pumpability
Long shelf life
There are other types of lubricant available, calcium based and
environmentally adapted, but they are not in wide use in the Queensland Rail
network.
18
2.6 Rail Curve Lubricating Grease Specifications
Lubricants are designed to meet the specifications of a tribological system. In
the case of rail/wheel lubrication this system lacks definition. Rolling element
bearings, for example, have well defined specifications. Therefore in a system
where specifications are broad, lubricant manufacturers are not able to target
specific features of rail/wheel contact.
Rail companies specify properties of the lubricant which may or may not be
directly relevant to the wear processes encountered at the interface. These
properties are: specific soap type; solid lubricants; suitability for specific grease
applicators.
The soap type, as previously discussed, is chosen for two main reasons,
temperature stability and water resistance. In an indirect way these properties
reduce wear. Temperature stability allows for pumping of the grease and
keeps the grease in the correct area. Water resistance allows the grease to stay
in the flange contact zone despite adverse weather conditions. In Queensland
different greases are used in regions of adverse weather because of the
empirical data and 'gut feel' of the track maintainers.
The solid lubricant components of the lubricating grease are specified as they
are known to have good wear characteristics, but the question remains
whether they are effective in the rail/wheel system. The amount (percentage)
of solid lubricant does not have a significant effect on the wear rate (Waara
2001). Conversely too little solid lubricant does not reduce wear to the
minimum attainable.
In order to reduce the costs associated with track maintenance, lubricants
must be compatible with existing lubrication systems. The detrimental effect
of this philosophy is that new lubricants which cannot be used with existing
infrastructure tend not be used. Rail wear can take many years to achieve a
reduction in rail head area that can be measured with accuracy. This
19
corresponds to lengthy trial periods in which experimental control is very
difficult, if not impossible to achieve.
It is interesting to note that lubricant manufacturers lack a consistent
approach to flange and gauge face lubrication. The outcomes from this
research will enable manufacturers to develop optimised lubricants.
2.7 Rail Lubrication Research
The current research issues in flange/gauge face lubrication are:
Lubricant transport prediction/modelling
Lubricator efficiency is measured by determining the distance of lubrication from the application point. In the body of literature, modelling of the lubricant transport process is deficient/absent (Frank 1981).
Wayside lubricator positioning
There has been work in this area to determine algorithms for placement. The research of Thelen and Lovette (1996) proposes that through direct measurement of lubricator effectiveness more efficient placement can be achieved.
Lubricators/Lubricator application methods
Lubricators have progressed through a series of iterations from mechanical through hydraulic to electronic devices. The lubricant applicator methodology has changed to remedy the negative aspects of wayside lubricators specifically to ensure increased device reliability.
Lubricant technology and performance measurement
Lubricants are a commercial product and the research in their development is therefore not available for review. Performance measurements of rail curve lubricants require further research (Clayton et al. 1988; Kumar et al. 1991; Mulvihill et al. 1994; Waara 2001)
Rail/wheel contact is an extremely complicated interface to simulate.
Geometric and physical considerations change rapidly in actual contacts, thus
there are a vast number of variables to consider. Drawing comparisons
20
between field and laboratory is difficult and direct comparisons have not been
made from scaled simulation results (Kumar et al. 1991; Waara 2001; Witte
and Kumar ~1986). Full scale test facilities are yet to publish significant
conclusions on optimal lubricant and lubrication strategies. Field trials using
in-service equipment are nearly impossible to manage due to the shear
number of variables that require recording, from the weather to axle loading.
Another difficulty in all of the testing types is the length of time involved in
gathering data for wear rates.
American researchers have attempted to overcome the simulation difficulties
with a full scale test facility. The track, named FAST (Facility for Accelerated
Service Testing) is yet to produce definitive research results in rail/wheel
tribology. Another full scale test facility exists in Sweden and is used by
Chalmers University, but there have been no publications relating to lubricant
performance at the time of writing. The value of testing using full scale
facilities will come with the sheer volume of results, to be analysed once the
rail/wheel interface is better understood.
Laboratory simulation is considered a useful tool in other tribological systems
and development of such a tool is important. The review of laboratory
lubricant testing devices is limited due to the paucity of recent publications.
There are four groups (Clayton et al. 1988; Kumar et al. 1991; Mulvihill et al.
1994; Waara 2001) that have published in the area of rail lubrication, the most
current work being that of Waara (2001). The recent work of Waara in
Sweden has focussed on the correlation between laboratory and field
lubrication. The field testing of rail curve lubricants, which Waara started in
1997, has investigated the influence of mineral oil based greases, such as the
ones tested in this thesis, environmentally adapted greases and the influence
of solid lubricant additives to these greases. Waara’s laboratory testing used a
Plint and Partner High Frequency Apparatus with a “cylinder on flat”
arrangement. The cylinder is applied to the flat with a force, then slid in an
oscillating motion. This apparatus is in direct contrast to the three other
21
groups of researchers, all of whom used a different variant of a twin disk
apparatus.
The research of Waara (2001) using the cylinder on flat device has similarities
and differences between field and laboratory:
The cylinder sliding forwards and backwards matches the gauge face contact as trains travel in both directions. The exception in the field is heavy haul lines that have trains travelling loaded in one direction and unloaded in the other, creating a primarily unidirectional loading situation.
The cylinder sliding backwards and forwards is different to the field in that it does not incorporate the rolling component of the field contact.
The section of the cylinder that is sliding (the contact patch) remains in a constant state of stress allowing no time for stress relaxation to occur. The field situation is a cyclic loading one, a single point on the wheel is compressed once per revolution. Without cyclic loading the fatigue component of the wear processes is minimised.
The shape and stress distribution of the contact is similar to the field but the area of contact is much smaller. As the contact area decreases for simulators, the effect of surface roughness increases. In this situation the wear processes may change from the field wear processes.
The spread of lubricant is achieved by sliding the cylinder across the flat whereas the field process is primarily a rolling motion. The spread of lubricant by sliding is desirable when it is considered that the process is more damaging to the lubricant and forces more lubricant from the contact. However, spreading the lubricant by sliding does not reflect the rolling and sliding that occurs in the field.
The final important difference between field and laboratory is the shearing rate across the flat block. The shearing rate is variable from stopped to full velocity at the centre across the flat block. The lubricant film thickness will be affected by the different shear rate and entrainment velocity. In contrast, the field situation has a train velocity, and consequently the shear rate of lubricant, which is constant through the curve.
22
The limitations in shear rate and sliding in the laboratory apparatus of Waara
(2001) led to choosing a twin disk device for the work in this thesis. The twin
disk devices appear more suitable with respect to the criteria for simulation
discussed in this chapter.
The twin disk devices have their limitations with simulating field conditions as
well. Similar to the cylinder on flat device, the contact area is small.
Compared to field conditions the stress conditions can be replicated quite
accurately using a twin disk device. The most important similarity for twin
disk devices to field conditions is the rolling/sliding contact. Slide to roll ratio
or slip percentage in these devices is fixed for a particular test and geometry.
The test device enables any slide to roll ratio to be set for examination. Some
devices have no method for adjustment during a test, whereas others do
(Tyfour et al. 1995; Beynon et al. 1996; Fletcher and Beynon 2000). This style
of laboratory apparatus is commonly used for rail steel wear investigations
under unlubricated conditions.
An important difference to the field conditions is the uni-directional loading
of the samples and lubricant. As previously mentioned, trains are a
bidirectional load system. In twin disk devices the disks can be rotated
backwards by installing the metal test samples backwards. In the research of
Kumar et al. (1991) and Clayton et al. (1988) the testing did not include
bidirectional examinations. In works published on unlubricated wear testing
of rail steels there is also no mention of this practice being employed (Clayton
1995; Huq and Celis 2002; Olofsson and Telliskivi 2003).
Twin disk devices typically have the limitation of a variable shearing force,
which is measured and presented as a friction force. When a train travels
through the corner there is a constant lateral force from the balance between
centrifugal and gravitational forces. This lateral force is proportional to the
shearing force on the gauge corner and is designed to be within a range to
prevent trail derailments. Therefore, to test for a rail curve it is suitable to
23
control this shearing force. The rail/wheel simulator used in this thesis is
capable of controlling the shearing force applied to the test sample.
The spread of lubricant in twin disk devices is achieved by rolling and sliding.
The direction the lubricant can escape in the device is the direction
perpendicular to rolling. The spread of lubricant in the device is similar to
field conditions due to the rectangular contact of a twin disk test device,
which has the maximum pressure in a line in the axis of rolling. Thus the
lubricant is forced forwards and to the outer edge of the contact. To more
closely match the lubricant spread, the metal test samples can be machined to
a barrel shape to generate the contact patch shape of the field conditions.
Kumar et al. (1991) changed the test sample geometry in this way, however in
the field, the elliptical contact moves up and down the gauge face, not in a
single line as in the twin disk situation.
Mulvihill et al. (1994) investigated rail/wheel lubrication with a twin disk
machine. Their work identified the following requirements for a scale
rail/wheel simulator:
Mimic the stress and creep experienced at the contact.
Generate two dimensional creep for the flow of lubricant from the contact.
Measure lubricant performance continuously throughout testing.
Accurately control lubricant application.
Results from their experiments indicated that the relationship between
lubricating grease ingredients and performance was not clearly defined.
Varying amounts of extreme pressure additives and solid lubricants had an
unpredictable effect on the test outcome. The definitive conclusion from the
experiments is that lubricants reduce power consumption and increase wear
life of the components.
24
Clayton et al. (1989) identified a need for a “simple inexpensive laboratory test
method” for the performance characterisation of rail curve lubricants.
Following his earlier research (Clayton et al. 1989), Clayton (1996) reviewed
the tribological issues in rail wheel contact. In this review, Clayton (1996)
identified a need for a laboratory test device that can measure lubricant
performance under a starved lubricant film. The work presented later in this
thesis represents a method of predicting the decay or half life of the starved
lubricant film to address this deficit in rail curve lubricant research.
The twin disk device of Clayton et al. (1989) was commissioned to replicate
the wear processes of an unlubricated five degree curve (approximately 350m
radius (Frank 1981)) and measured wear reduction and retention of
lubrication. Their test aimed to screen potential lubricant candidates for full
field trials. Nine lubricants were investigated using the commissioned
conditions.
Clayton et al. (1989) identified large variability in newly machined rollers and
excluded the data from analysis without providing explanation as to the cause
of the increased wear. Experimentally the author has found that with newly
machined samples there is a process of strain hardening which lowers the
wear rate. Probably the source of increased wear in the work of Clayton et al
(1989) was the lower material strength during the development of strain
hardening in the newly machined samples. . Clayton et al. (1989) also found
experimentally, that increased or decreased applied lubricant did not increase
test variability. This finding would suggest that there is a limit to the lubricant
that can be maintained in the system and any excess does not improve
performance.
Clayton et al. (1989) measured the lubricant performance as the number of
revolutions to lubricant film failure and the wear rate. The number of
revolutions is representative of the number of axles or strain history and was
defined as retentivity. The retentivity measurement, the revolutions prior to
25
the measured friction force to reaching 50% of the normal force, in the work
of Clayton et al. (1989) had large variability ( ± 45%). The variability between
tests was larger than the range of presented results for comparison between
lubricants. The paper did not make clear if the variability was from the
accuracy and resolution of measurements of the device or the test method
itself. Under fully lubricated conditions the wear rate was reduced by 1400
times as compared to the unlubricated case.
In addition Clayton et al. (1989) found that as the rate of friction force
increased, there was a corresponding reduction in retentivity performance,
which was also found in the experimental testing in this thesis. The final
phase of the tests of Clayton et al. (1989), the phase in which the lubricant film
is failing, was observed to be more consistent with the results from field
testing, with respect to the observed lubricant film and friction force
development. Performance measurement of a similar phase in the rail/wheel
simulator testing from this thesis will present the decay in lubricant film.
Clayton et al. (1989) proposed that research was required to determine the
lubricant film thickness and the decay of this thickness. This research
shortfall has been advanced by this thesis with the presentation of a
performance criterion to address the issue of film decay, namely half life.
Kumar et al. (1991) stresses that three test parameters are vital to the success
of laboratory simulation: contact stress; creep or slip; and lubricant quantity.
Emphasising lubricant quantity as an important test parameter indicates that
the volume of lubricant was not sufficient to the point of excess in any of
their testing. This implication is contrary to the work of Clayton et al. (1989).
Therefore to remove this parameter as a source of test variability, sufficient
lubricant volume is imperative.
Kumar et al. (1991) used input power from the driving motor as the measure
of lubricant performance and stated that power measurements were difficult
because the change in power was small in magnitude. The author believes that
26
the measurement resolution of the equipment was inadequate for the
objectives of Kumar’s research.
From the four groups of researchers that have published work on rail/wheel
lubrication in the last twenty years, the current research builds upon the
foundations of their research, refines the method for testing lubricant
properties, and poses more accurate methods that exploit the gaps identified
in the body of rail/wheel lubrication research.
2.7.1 Surface initiated rolling contact fatigue with lubrication
In addition to the wear research presented in the previous section, research
into rolling contact fatigue under lubricated conditions has been carried out.
This research is of importance due to the influence of lubrication of surface
fatigue crack propagation. Surface cracks on rails and wheels are exposed to
environmental conditions which can reduce crack face friction and
consequently increase crack propagation. Lubrication of the crack faces can
be provided by water in the environment or added as part of the maintenance
effort in gauge face lubrication. The negative effects of lubrication on fatigue
crack propagation has been divided into three hypotheses by Bower (1988):
1) Crack face friction is reduced with the introduction of lubrication, which increases the forces responsible for crack propagation.
2) Hydraulic forces from the compression of the crack containing trapped lubricant increasing the Mode I stress intensity.
3) Hydraulic forces from the compression of the crack containing trapped lubricant preventing the re-bonding of the crack surfaces.
Ekberg and Kabo (2005b) summarised the experimental findings of
lubricated rolling contact fatigue testing, and reported that: lubrication is
essential for surface cracks to propagate, and rate of crack propagation is
27
driven by the lubricant viscosity. Ekberg and Kabo (2005b) highlight the
important aspects of rolling contact fatigue in a rail environment:
The rolling contact provides a moving and rotating stress field.
Cracks begin as a Mode I failure and as the length increases change to a mixed Modes II and III.
Despite the primary mode of fatigue failure being Mode I, typically the failures do not conform to the Paris Law of fatigue life which predicts that primarily compressive loading will not result in a fatigue failure.
Rail and wheel contact experience very diverse loading regimes which make failure prediction difficult.
Surface fatigue cracks are typically not encountered in tunnels (Ishida and Abe
1996; Kondo et al. 1996), which give credence to the hypothesis that water
promotes crack propagation. Seasonal variations in recorded rail degradation
were found by Kalousek et al. (1996) which pointed to water being the main
contributing factor.
Franklin et al. (2005) investigated lubricated rolling contact fatigue using water
as the lubricant (at a rate of 2 drops per second). Previous research (Clayton
and Su 1996) has identified that water lubricated contacts fail faster than those
lubricated with grease or oil (including biodegradable materials). Water is the
most commonly encountered lubricant in a rail system and yet leads to the
largest reduction in fatigue life of rail materials. Tractive forces from driven
or braked surfaces promote the growth of surface fatigue cracks, which was
found experimentally by Ishida and Abe (1996). Despite the increased surface
fatigue crack propagation rates from lubrication, Ekberg and Kabo (2005a)
also detailed the positive influences of lubrication. The positive influences are
reduction of friction (locomotive power), reduction in wear rates and
reduction in noise. The reduction of friction is of importance to surface
fatigue crack initiation as the tractive force is a contributing factor.
28
2.8 Lubricant Application Research
It is important to consider the lubricant application system for the purpose of
improving simulation conditions. Railroads have three main methods for
applying lubricant to the gauge corner (Kumar et al. 1991):
Wayside lubricators, see Figure 6.
On-board lubricators, see Figure 7.
High rail lubricators, see Figure 8 and Figure 9.
Figure 6 - Wayside lubrication device (photo courtesy of Queensland Rail).
29
Figure 7 – Vogel on-board lubrication device mounted to display components of system.
Figure 8 - Hi-rail lubrication vehicle (photo courtesy of Queensland Rail).
30
Figure 9 - Lubricant application by hi-rail vehicle (photo courtesy of Queensland Rail).
The lubricant types investigated in this research are applicable to wayside
lubricators. Research into wayside (trackside) lubrication has primarily focused
on evaluating the effectiveness of lubrication on the cost incurring aspects of
rail infrastructure and rolling stock. Marich et al. (2001a) and Thelen and
Lovette (1996) investigated the rail system and the effect of lubrication on this
system. Their research focuses on the reduction of wear and energy
consumption (tractive effort) associated with the flange/gauge face contact.
Commercial research into wayside lubricators has been slow due to the low
demand of new systems. New systems are implemented following a major
breakthrough, or existing system maintenance costs exceed the cost of
replacement systems. These new systems are often developed commercially
and the results unpublished.
Research by Marich et al. (2000; 2001b) measured efficiency of lubrication
strategies in the Hunter Valley in Australia by obtaining the friction
coefficients at the head of the rail. The projects modified the system
31
parameters of lubricator location with respect to direction, loading and
whether on hi-rail and low-rail or both. Details of precise location are not
provided by Marich et al. (2000; 2001b) . There is also no indication that an
analytical algorithm was used in the determination of lubricator location.
The work of Marich et al. (2000; 2001b) identified an issue of contact pressure
between gauge face and flange where it decreased the efficiency of the
lubricator system. High flange forces forced the lubricant from the contact
zone either wasting the lubricant into the ballast material or onto the running
surface of the rail. Large compressive forces, such as those described in the
work of Marich et al. (2000; 2001b), were found to have a similar effect on the
response of lubricants in the rail/wheel simulator. The problem of lubricator
location with respect to a set level of flange force or shearing force could be
investigated to provide a design which enhances lubricant transport.
2.8.1 Lubricant transport prediction/modelling
The body of knowledge in rail/wheel lubrication provides general principles
of lubrication, not specific lubrication regimes. General principles prevent
accurate simulation of industry practice, an important simulation parameter.
These lubrication regimes are generally developed from field experience and
measurement. The extensive number of variables in a lubrication system and
their interactions are not well defined in the literature. Despite this dearth,
‘rules of thumb’ exist which provide guidance for suitable lubricant
application strategies.
Frank (1981) suggested that the lubrication device be placed at the point on
the curve where wear from flange contact is observed, as Figure 10 illustrates.
This location is easily measured and can therefore be located by track
personnel. The implication is that only after wear occurs can the location for
lubrication can be determined. Predicting the location for lubricators prior to
wear is the desired outcome. Measuring retentivity performance of a lubricant,
as measured with the rail/wheel simulator in this thesis, may allow for
32
placement based of effective lubricating distance rather than the point of
wear.
Figure 10 - Wayside lubricator location plan (Frank 1981).
Optimal lubricant spread may not occur using Frank's placement method
(1981) as the contact pressures may be sufficient to force the lubricant from
the desired location. Conversely if the contact pressure is inadequate excessive
amounts of lubricant can be transported by the wheel to locations other than
the rail gauge face (fling off).
The actuation system has a direct bearing on lubricant waste in the case of
excess applied lubricant. If the flange is not in contact with each passing axle
the system will continue to pump lubricant to the application point to form
large pools of lubricant. These large pools will be forced from the contact to
be thrown from the wheel or spread to the tread contact with only a small
proportion being used at the desired application point.
33
Figure 11 - Range of lubrication (Frank 1981).
Frank also proposed that the length of the lubricator delivery system be equal
to that of the wheel's circumference. This length ensures that the entire
flange receives lubricant. In the event that wheel contact is not maintained
over the length of the lubricator, excess lubricant (puddles) can again occur.
34
The proposed application methodology of Frank (1981) was employed in the
lubricated testing of the rail/wheel simulator.
Figure 11 is taken from the work of Frank (1981) and details the work that
they carried out to determine the effective range of lubricators. The
downstream lubricated distance can be seen to be related to the curve radius.
This curve radius dictates the speed at which a train can negotiate a corner
and also has a direct effect on the contact conditions at the flange. The
relationship in this table is empirical and considers the variable of curve radius
only. Maintaining a set flange force and corresponding lubricant shear force
could be used to generate further tables such as those presented by Frank
(1981). The experimental testing in this thesis measured lubricant
performance by setting a maximum shearing force and setting a simulated
flange force. These set points could be correlated against field data, using the
method Frank (1981) in the future.
Figure 12 - Rail tribometer (photo courtesy of Queensland Rail).
35
In the work of Marich et al. (2001a), lubricator position was determined
through the use of a tribometer, see Figure 12. Measurements of gauge face
friction were recorded following the application of lubricant to the rail.
Marich et al. (2001a), with respect to wayside lubricator location, concluded
that:
The ideal position for the wayside lubricator is at the same location as that presented by Frank (1981), at the onset of wear on the gauge face. Marich also proposed that this location is only applicable to curves of radius 400m-600m.
Lubricators placed in curves of radius 600m-1000m provide excellent lubrication where flanging occurs. The flanging forces in these curves are generally less than tighter curves ensuring more efficient use of the applied lubricant.
Lubricators should not be placed on curves of 300m or less. The reasons for this is flanging forces are high and force the lubricant from the contact zone. Carry distance for the lubricant is this case is short.
These conclusions do not address the issues that are associated with these
tight radius curves, that wear is usually more significant. In the case of tight
radius curves industry practice is to place the lubricators prior to the curve in
a position where flange contact forces are at a suitable level.
Marich et al. (2001a) has also developed guidelines to determine effective
lubrication distances (range) based on track structure and loading conditions.
These results are in Table 1 but minimal details of track conditions makes
application of these findings difficult.
The work of Thelen and Lovette (1996) identified a lack of mathematical
modelling of the lubrication transport mechanism. Thelen and Lovette, as
with other authors, defines the system as one in which the parameters are too
numerous parameters to model. Their work also tested the hypothesis that
lubrication effectiveness decreases exponentially with distance. Other authors
have suggested a similar model and Thelen and Lovette concluded with field
36
testing results that this was the case. Thelen et al. (1996) and Marich et al.
(2001a) propose that location of lubricators is best determined through
measurement of performance.
Range Sleeper Type Grade Traffic 8km-10km Wooden Moderate Normal 6km-7km Concrete Moderate Passenger and unloaded freight
trains 5km-6km Concrete Moderate Passenger and loaded freight
trains 3km-4.5km Concrete Severe Normal
Table 1 Lubrication effective distance (Marich et al. 2001a).
2.8.2 Summary
Existing methods of wayside lubrication used by the rail industry perform
adequately. In the case of systems where empirical methods use locally
gathered data the lubrication can be effective, if not the optimal for that
system. The research issue in this case is the poor applicability to other
systems. In order to address this problem new research in wayside lubrication
needs to address mathematical prediction of lubrication performance.
Specifically there are three areas in which there is a deficiency.
Lubrication transport prediction/modelling is currently at the stage of
collating field data and compiling tables of lubricator performance for curves
of a particular dimension. This data could be expanded to include type and
speed of rail traffic, providing wider applicability of the tables. Further
research into the physical system of lubricant transport on rail and wheels
needs to be carried out to move away from the empirical methods currently
employed.
Mathematical prediction of lubricant transport will assist in developing
models for wayside lubricator positioning, the next area of deficiency.
Currently the empirical positioning system of locating a lubricator is effective
but with knowledge of the transport mechanism could be optimised.
37
Further to the research into lubricants and their transport mechanisms,
lubricators require investigation to ensure that the methods that they employ
optimise the lubrication system. The current systems perform adequately but
too little is known about the system to optimise the design of the lubricant
application. The work into improving the reliability of the lubricators has
advanced the efficiency but this efficiency is not quantified. The additional
work required is optimization of the rail curve lubricant.
2.9 Rail/Wheel Simulator - Description of equipment
Having identified the issues in the field situation in the previous sections a
brief description of the rail/wheel simulator used in this thesis will be
presented. The rail/wheel simulator developed and used for this research
originated from the BHP Melbourne Research Laboratories in Australia. This
machine was purpose built by the laboratories to investigate wear of
rail/wheel couples (Marich and Mutton 1989). BHP Billiton is a major
supplier of materials to the rail industry and conducts their own heavy haul
rail operations.
In its original form the rail/wheel simulator was used to test wear rates of
rail/wheel couples. These couples consisted of different grades of rails and
wheels, from those currently in use to laboratory prepared samples. The
prepared samples had a range of hardness, chemical compositions and heat
treatments. Results from the wear machine were used to compare materials
varying in both strength and hardness. Wear rates were also measured for
continuously lubricated conditions, which is where the importance of this
equipment lies for the current thesis.
The wear test machine has two load parameters:
Tread Load to simulate the axle load of the system. In the centre rear of the photograph in Figure 13, the tread load pneumatic ram can be seen.
38
Flange Load for the simulation of curvature (flange contact). In the front right of the photograph in Figure 13, the flange load pneumatic ram can be seen.
Figure 13 – Rail/wheel simulator post modifications by the author.
These loads are depicted in Figure 14 from Marich and Mutton (1989). This
arrangement is suitable for imitating a range of loading conditions, such as
those experienced in the field.
Slip percentage is important in determining the velocity profile across a given
contact area. The slip percentage of the samples used in the work of Marich
and Mutton (1989) was approximately 20%, compared to a maximum value
of approximately 5% from a real rail/wheel system.
The simulated system of Marich and Mutton (1989) and modified rail/wheel
simulator used in this thesis is flexible to allow the use of a variety of wheel
and rail profiles. These profiles can be taken from new design drawings or
profiles of worn rolling stock and then be machined into the blank samples.
39
In addition to the physical geometry there is the contact geometry which can
be adjusted. In Figure 14, Angle of attack, or axis perpendicular to the page,
can be selected to give lateral slip and approach angle for the flange contact.
Figure 14 Loading Diagram for wear investigation of Marich and Mutton(1989)
2.10 Lubricant Properties Testing
Simulating a tribological system tends to have limited applicability for
commercial lubricant testing. Typically standards based tests are used to
characterise the lubricants. Lubricating grease is difficult to characterise and as
such there is a limited number of testing standards applicable. The tests
selected for this research are detailed, followed by an overview of the
rheology tests performed.
40
2.10.1 ASTM D 1092 Standard Test Method for Measuring Apparent
Viscosity of Lubricating Greases
Lubricating greases respond in a different way to most lubricants and as such
require modified viscosity testing. This test is used to produce a chart of the
apparent viscosity at a variety of shear rates.
Figure 15 – Schematic drawing of ASTM D 1092 test device(ASTM 1999).
The standard summarises the test method as:
The sample is forced through a capillary by means of a floating piston
actuated by the hydraulic system. From the predetermined flow rate and
the force developed in the system, the apparent viscosity is calculated by
means of Poiseuille’s equation. A series of eight capillaries and two pump
speeds are used to determine the apparent viscosity at sixteen shear rates.
The results are expressed as a log-log plot of apparent viscosity versus
shear rate.(ASTM 1999)
41
This test was used for two primary reasons. Pumping of grease is an
important component of rail lubricating systems. If the grease never reaches
its intended application point then its effectiveness is zero. In addition the
way in which lubricant is spread from the application point is a shearing
process and this test measures shearing performance over a range of shear
rates.
The limitation of ASTM D1092 with respect to this research is the original
purpose of the test is to predict pumping characteristics for grease in
pipelines, for example on a dragline boom. This is one characteristic in
optimising a rail curve lubricant, but not directly related to the performance in
the contact. To make this test suitable for rail application would require
varying the temperature and creating a map of apparent viscosity to ensure
good lubricant application practices.
2.10.2 ASTM D 2596 Standard Test Method for Measurement of
Extreme-Pressure Properties of Lubricating Grease
The standard summarises the test method as:
The tester is operated with one steel ball under load rotating against three
steel balls held stationary in the form of a cradle. The rotating speed is
1770 rpm. Lubricating greases are brought to 27 °C (80 °F) and then
subjected to a series of tests of 10-s duration at increasing loads until
welding occurs. (ASTM 1997)
Typically this test is used to rank lubricants qualitatively rather than quantify
performance. This test method is limited in its general application from the
low precision of the test results and the high inter-sample variability. In the
case of testing rail curve lubricants, only sliding occurs, whereas rolling is a
significant component in a rail/wheel contact. Despite the limitations this is a
42
suitable test method from the perspective that the contact pressure
characteristics are comparable to a gauge corner contact.
Figure 16 – Schematic diagram of four ball test device suitable for ASTM D 2266 and ASTM D 2596 (ASTM 1991; ASTM 1997).
2.10.3 ASTM D 2266 Standard Test Method for Wear Preventive
Characteristics of Lubricating Grease
The standard summarises the test method as:
A steel ball is rotated under load against three stationary steel balls
having grease-lubricated surfaces. The diameters of the wear scars on the
stationary balls are measured after completion of the test. (ASTM 1991)
This method was chosen for the same reasons as ASTM D 2596.
43
2.10.4 Rheometer Test
The context of rheometric testing is the prediction of the shear characteristics
of the test lubricants. In the case of lubricating greases the strain history of
the lubricant directly affects the structural properties (Nolan ~2000). Another
method of considering the structural changes with respect to shear history, is
the effect that energy absorbed or transmitted through a lubricating grease
affects the structural properties.
The ability to predict the energy capacity of a grease preceding full failure
using a relatively quick method, such as rheometry, is another tool for
lubricant designers.
There are two main components to a grease and as such two main effects.
The oil component behaves as liquid and the soap component as a solid. In
the short lifespan of rail curve grease it is assumed that the change in oil
properties is insignificant. Therefore the shearing of the solid soap is the main
factor in performance degradation.
In the case of the rail simulator three regions of distinctly different shearing
conditions may be considered. The initial region is when the lubricant film is
developing, see Figure 17. Prior to rolling, an excess of lubricant is applied to
the rail sample, the larger of the two, then the wheel sample is pressed against
the rail sample with the test load. The rail sample is then rotated which rotates
the wheel sample. The lubricant film in this process begins at approximately
1mm and rapidly decreases to approximately 1µm. This reduction is three
orders of magnitude and introduces significant accumulated strain.
Experimentally, observed in the work of the thesis, the majority of the applied
lubricant is expelled from between the cylinders. To predict the strain history
of the lubricant remaining in the contact, the initial and final volumes of
lubricant are considered. Initially with a 1mm thick surface we have 30g of
lubricant, following rotation this becomes 30mg and 1µm thickness.
44
Figure 17 – (Left) Lubricant film prior to rolling (~1mm thickness). (Right) Lubricant film following rolling (~1µm).
To apply this information in a practical sense the final mass, 30mg, is the
minimum lubricant application for each revolution if we assume total
lubricant degradation with each revolution. Now it was observed that the
lubricant does not degrade in a single revolution but with accumulated strain.
Experimentally this is observed by an increase in tractive coefficient.
Therefore a decision must be made regarding limits of tractive coefficient
which in this thesis was set by limiting the dynamometer to the required test
parameter.
There are competing factors in reaching a set value; consumable lubricant
costs, lubricant infrastructure and maintenance, wheel and rail wear
(replacement and maintenance), locomotive tractive power, and energy. If a
correlation between in-service performance or parameters can be reached
with rheological testing the advantages would be extremely valuable.
45
2.11 Summary
For the purpose of identifying issues in rail curve lubrication to ensure
optimal simulation and performance measurements of rail curve lubricants,
this chapter has explored the following areas:
The process and limitations of simulated tribological testing focusing on issues specific to rail/wheel simulators were discussed.
Mathematical models for wear processes used to identify the parameters that are required to be targeted with lubrication strategies were presented.
Solid mechanics models have been discussed to introduce contact mechanics of in-service and rail simulators.
Issues regarding lubricating the rail/wheel interface have been discussed with specific reference to the lack of specifications required for this interface.
Existing standard lubricant tests considered suitable for rail/wheel interfaces have been discussed and their limitations highlighted..
The following major points have been identified:
There has been some success with simulated lubrication testing (Clayton et al. 1988; Marich and Mutton 1989; Kumar et al. 1991; Mulvihill et al. 1994; Waara 2001)
A definitive choice of lubricant has not been found.
Measurement of lubricant performance has been focussed on wear (Clayton et al. 1988; Marich and Mutton 1989; Kumar et al. 1991; Mulvihill et al. 1994; Waara 2001).
Lubricant manufacturers do not have a consistent approach to rail curve lubrication.
Limited laboratory simulation has been performed on rail curve lubricants.
Primarily two types of laboratory simulators were used to investigate rail curve lubricants, reciprocating cylinder on flat
46
and twin disk. The majority of research has been carried out with twin disk devices.
The choice of simulator type used in this research is based on the advantages of the twin disk devices when compared to the cylinder on flat devices.
Shear force control is typically lacking in twin disk devices which have fixed slide to roll ratios. Shear force control was implemented in the twin disk device used in this thesis to overcome this limitation in investigating rail curve lubricant performance.
Clayton (1988) identified a need to measure lubricant performance throughout simulated testing, specifically targeting the end of the lubricant film's life. This has been achieved in this thesis and a model for the lubricant film decay presented. The decay is given as the lubricant performance measurement, half life.
The overall conclusion from this cross-section of literature is that a shortfall
in the knowledge surrounding lubrication of the gauge corner interface
existed. The proposed methodology to reduce this gap in knowledge was to
develop a scaled simulator to investigate the lubricants under simulated field
conditions. There was an examination of the contact mechanics of the in-
service and simulated wheel contact conditions. The simulator was then used
to test three rail curve lubricants currently employed by Queensland Rail for
comparison with the discussed standards based tests and the findings
discussed. Finally recommendations for further work and the conclusions
from the current work were presented.
47
C h a p t e r 3
THEORETICAL CALCULATIONS: CONTACT MECHANICS OF IN-SERVICE AND RAIL SIMULATOR CONDITIONS AND
LUBRICANT FILM THICKNESS
3.1 Introduction
Waara (2001), Kumar et al. (1991), and Clayton et al. (1989) all highlight the
need for accurate representation of the stress conditions in a rail/wheel
simulator. From this conclusion it is necessary to have the ability to calculate
the stress distributions for both the field and laboratory simulator using
contact mechanics.
The aim of this chapter is to provide the theoretical background to the
contact between wheel and rail and to demonstrate the use of software
developed to predict the contact dimensions and stresses. This chapter is
divided into presentation of the equations for elliptical and rectangular
contacts, comparison of software with published results, and examples of
typical stress distributions for in-service and simulator conditions.
3.2 Contact Mechanics Background
Tribology in essence is a combination of physics, chemistry and engineering.
The ratios of each part differ depending upon the problem and their
interaction with each other. Tribological processes must be studied using the
scientific disciplines simultaneously. A primary consideration in these
processes is mechanics of solids, specifically contact mechanics and fracture
mechanics. The contact mechanics is a description of the stress and strain
state of the bodies in contact.
In this project there are two general regimes of contact encountered. The
first, rolling contact, relates to the stresses and forces experienced by the tread
of the wheel. Second is the rolling/sliding regime experienced by the flange
and by the tread, only under adverse conditions. It is important to consider
48
both regimes as there may be stress field interactions between the two but the
area of interest in this thesis is the flange contact.
Studies of contact mechanics began with Hertz (1882), and remains the basis
for much of the current work in contact mechanics. Hertz's work focused on
Newton’s optical interference rings and the possible influence of elasticity.
Extensions of this theory include bearing design, real contact areas and rolling
and sliding contacts.
Hertz's theory however is based on a number of assumptions, which limits its
application to sliding contacts. These assumptions are:
the contact bodies are perfect materials, homogeneous, elastic and isotropic.
the strains are small.
smooth and non-conforming surfaces.
time changes do not affect geometry.
friction is negligible.
Both rails and wheels may not be assumed to be perfect materials, as they may
have work hardened contact surfaces which may also have been heat treated.
High stresses are experienced in this contact, which may negate the small
strain assumption. Both rail and wheel can suffer from geometric and
mechanical inhomogeneity. Finally friction is an important part of the contact
as the interface experiences both lateral and longitudinal creep.
The model used for the contact analysis in this thesis is the methods
proposed by the Engineering Sciences Data Unit (ESDU). Their work is an
extension to the work of Hertz and incorporates methods for minimising the
effects of the Hertz model assumptions. Their work also includes a method
for calculation of the stress tensor at any point in a body under contact. The
difficulty with using the methods of the ESDU is that the equations used for
solving the stress components are not suitable for use with a computer. The
49
method involves the use of graphs to estimate the equation parameters.
Historically, these parameters were used due to the necessity to calculate
values which are mathematically intensive.
In order to improve the accuracy of the contact mechanics analysis, software
to analyse rectangular and elliptical contacts was developed by the author,
using the methods of the ESDU as a basis. The software improves the
accuracy of results by calculating the equation parameters directly. These
parameters are for elliptical integrals and multiple simultaneous equations.
This software has been validated against other published contact mechanics
results (Hamrock 1994; Boresi and Schmidt 2003) and proven to be a valid
method with a greater accuracy and resolution than the ESDU method.
3.2.1 Wheel/rail contact models – A survey
The results of the development of wheel/rail models are used in a number of
areas with railway engineering, in particular the dynamics of the vehicles. This
information is used in the design of rail vehicles and rail infrastructure. This
project is looking for the stress and force behaviour of the wheel flange
contact (rail gauge face). In addition to force and stress, long term
performance of the rail materials can also be predicted from these models
(Bruni et al. 2000).
The most accurate but computationally intensive models have been
developed by Kalker (1990). The models then range in complexity and
computational intensity depending on the application. The models examined
in relation to this thesis had to focus on two main areas when dealing with a
wheel rail contact: the geometric system and the elasto-frictional system.
The geometric system must be able to encompass the rapid changes
experienced at the wheel/rail interface. These changes arise from the conicity
of the wheels and the changes of curvature of the head of the rail. There is
also the case in curving rail vehicles where three points of contact per axle
50
exist simultaneously, two normal and one tangential. The three point contact
is the geometrical situation where flange wear is encountered.
The elasto-frictional system must be able to predict the forces at the
rail/wheel interface whilst predicting the contact patch areas. From this a
prediction can be made of the stresses and creep experienced at the interface.
It is important that the geometrical contact model is able to take into account
multiple contacts that can occur in tight curves, where both the tread and
flange may be in contact with the rail. 'Lookup' tables can be used to lessen
the computational effort, but they are inferior to models that calculate the
geometry at each time step (Bruni et al. 2000). Increasing the model
complexity by predicting the geometry with respect to time is advantageous in
modelling the existing track, thereby allowing for better models through
verification. To further complicate the system, two dimensional descriptions
are only applicable for tangent track and long radius curves. Current interest
on wear in the literature is generally focused on short radius curves (Jendel
1999; Nilsson 2002). While outside the scope of this thesis, in future work,
three dimensional models could be considered to increase the accuracy of
geometric description.
Using the geometric description/model of Kalker (1990), the forces at the
rail/wheel interface, normal and tangential, can be calculated. The model uses
an elastic half space approximation for the contact patches, which, for most
cases, is sufficiently accurate. Elastic half space models are flawed when
applied to worn wheels and rails that have conformal profiles, as the
assumption of small contact patch compared to the rest of the body is invalid.
In these cases more intensive analysis must be carried out to formulate the
stresses.
Splitting the normal and tangential force calculations simplifies the system.
There is interaction between the forces but this is considered negligible.
Currently, the most rigorous method is by Kalker (1990), who describes a
51
non-linear method with a discretisation of the contact patch. This contact
patch calculated from the geometric model is used to determine the
deformation of the surfaces by an iterative method. This method is
advantageous in that the solution is the most rigorous, as previously
mentioned, but comes at a high computational cost.
The problem of modelling the forces at the rail/wheel interface is addressed
in other solutions by simplifying the situation. Kik and Piotrowski (1996)
proposed using an elliptical contact patch and an estimated deformation
distance/depth of the materials. This depth is chosen by the modeller and is
generally verified or calculated with the Kalker method. Another solution
from Bruni et al. (2000) and Pascal (1993) uses multi-elliptical Hertzian
contacts, which suffers from the inaccuracies previously mentioned.
Tangential problem solutions also use Kalker (1990) as the basis upon which
they are judged. Hertzian contact solutions use the creep values from the
normal solution to provide the tangential solutions. Other methods (Shen et
al. 1983) have an iterative solution of high computational intensity. Heuristic
models are also widely used and can give valid solutions (Kik and Piotrowski
1996).
In general, rail/wheel modelling is concerned with the dynamics of the
vehicle. This focus has been extended to include rail/wheel contacts but this
tends to be specifically focused on the tread contacts rather than the flange.
This is an area where the models can be extended to give a further
understanding of the interface. It is outside this thesis to develop a new model
for rail/wheel force interactions, but it does use a combination of Hertz
(1882), Johnson (1985) and the methods of the ESDU literature on contact
mechanics (ESDU 1984; ESDU 1994; ESDU 1995) to analyse the complex
rail/wheel interface system.
52
3.3 Geometry and Material Property Equations
The notation convention where applicable is the same as that used in the
ESDU methods (ESDU 1984; ESDU 1994; ESDU 1995). The geometry
labelling and orthogonal axes system is shown in Figure 18
Figure 18- Reference geometry used for contact mechanics calculations (ESDU 1984).
The material properties for each body were calculated with Equations (3.1)
and (3.2)
( )21
ikEσ
π−
= (3.1)
( )1 2
2'Ek k
π=+
(3.2)
ik = material constant, i denotes body number
53
σ = Poisson’s ratio
E = Young’s modulus
'E = Effective modulus
The geometric properties for each body were calculated with Equations (3.3)
and (3.4)
11 21 12 22
1 1 1 1 1R R R R R
⎛ ⎞ ⎛ ⎞= + + +⎜ ⎟ ⎜ ⎟⎝ ⎠ ⎝ ⎠
(3.3)
12 22
11 21
1 1 12
1 1 12
AR R
BR R
⎛ ⎞= +⎜ ⎟
⎝ ⎠⎛ ⎞
= +⎜ ⎟⎝ ⎠
(3.4)
R = Effective contact radius
iiR = Radius of curvature, first i denotes body number and second i
axis number
,A B = Geometry parameters
In the case where the principal axes of the contacting bodies are not aligned
the following equations for geometry, must be used.
54
12 2 2
11 12 21 22
11 12 21 22
11 12 21 22
2 2
11 12 21 22
11 12 21 22
11 12
1 1 1 11 1 1 1 14 1 1 1 12 cos 2
1 1 1 11 1 1 1 14 1 12
R R R RA
R R R R
R R R R
R R R RB
R R R R
R R
ω
⎡ ⎤⎡ ⎤⎛ ⎞ ⎛ ⎞⎢ ⎥⎢ ⎥− + −⎜ ⎟ ⎜ ⎟⎢ ⎥⎢ ⎥⎝ ⎠ ⎝ ⎠⎢ ⎥= + + + − ⎢ ⎥⎢ ⎥⎛ ⎞⎛ ⎞⎢ ⎥+ − −⎢ ⎥⎜ ⎟⎜ ⎟⎢ ⎥⎝ ⎠⎝ ⎠⎣ ⎦⎢ ⎥⎣ ⎦
⎛ ⎞ ⎛ ⎞− + −⎜ ⎟ ⎜ ⎟
⎝ ⎠ ⎝ ⎠= + + + +⎛ ⎞
+ −⎜ ⎟⎝ ⎠
12
21 22
1 1 cos 2R R
ω
⎡ ⎤⎡ ⎤⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥⎛ ⎞⎢ ⎥−⎢ ⎥⎜ ⎟⎢ ⎥⎝ ⎠⎣ ⎦⎢ ⎥⎣ ⎦
(3.5)
121
21 1 1
y
x
x y
D
RA
RB
R R R
B ARA B
=
=
= +
−=+
(3.6)
DR = Curvature difference
xR = Effective radius in ‘x’ direction
yR = Effective radius in ‘y’ direction
3.4 Contact Mechanics Method
The theoretical predictions for stresses arising from and in the contact area
are calculated using a combination of mathematical methods. The collection
of methods is based on work carried out by the Tribology section of the
Engineering Sciences Data Unit (1994). Additions and modifications to this
method were required as a result of the inability to directly apply the
equations to computerized calculation. Mathematical methods for calculating
the necessary elliptical integrals have been incorporated into this research to
improve the accuracy of results. Previously, computational methods for
55
elliptical integrals were time consuming and tables were used in the ESDU
method.
3.4.1 Rectangular Contact Equations
The rectangular contact is approximated by a contact ellipse with an infinite
dimension in the major axis.
The contact width is calculated by
( )1
211 21
1 211 21
4 R RPb k kL R R
⎡ ⎤⎡ ⎤⎛ ⎞= +⎢ ⎥⎢ ⎥⎜ ⎟ +⎝ ⎠ ⎣ ⎦⎣ ⎦ (3.7)
b = Minor ellipse semi axis or contact half width
P = Normal force
L = Length of rectangular contact
The distance of surface deformation at the centre of the contact is given by
Equation (3.8).
11 211 1
4 41 12 ln 2 ln2 2
R RP Pk kL b L b
δ ⎡ ⎤ ⎡ ⎤⎛ ⎞ ⎛ ⎞⎛ ⎞ ⎛ ⎞= − + −⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟⎢ ⎥ ⎢ ⎥⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠⎣ ⎦ ⎣ ⎦ (3.8)
δ = Normal approach of bodies
The pressure distribution across the rectangular contact is given by
( )1
2 2
0 21 yp y pb
⎡ ⎤= −⎢ ⎥
⎣ ⎦ (3.9)
( ) ( ) ( ), , , , , ,p p y p x y p x y z = Pressure or pressure at location
0p = Maximum pressure
The maximum direct stress 0( )p is given by
56
02Pp
L bπ⎛ ⎞= ⎜ ⎟⎝ ⎠
(3.10)
3.4.2 Elliptical Contact Equations
The contact dimensions are calculated using the methods of Hamrock (1995)
and the ESDU (1995).
ba
β = (3.11)
( )1
2 36'
E m PRb
Eβ
π⎛ ⎞
= ⎜ ⎟⎝ ⎠
(3.12)
( )1
36'
E m PRa
Eπβ⎛ ⎞
= ⎜ ⎟⎝ ⎠
(3.13)
( ) ( )
12 3
92 '
PK mE m R E
δπβ
⎡ ⎤⎛ ⎞= ⎢ ⎥⎜ ⎟⎝ ⎠⎢ ⎥⎣ ⎦
(3.14)
a = Major ellipse semi axis or contact half width
β = Ellipse semi-axes ratio
( )E m = Complete elliptical integral of the second kind
( )K m = Complete elliptical integral of the first kind
The method proposed by ESDU (1994) is
( )
13
aC W AaA B B
−⎛ ⎞= ⎜ ⎟+ ⎝ ⎠
(3.15)
57
( )
13
bC W AbA B B
⎛ ⎞= ⎜ ⎟+ ⎝ ⎠ (3.16)
W = Dimensionless load parameter
Where the coefficients are given by
( )1 13 3
2
2a
E m ACBπβ
⎡ ⎤ ⎛ ⎞= ⎢ ⎥ ⎜ ⎟⎝ ⎠⎣ ⎦
(3.17)
( )1 13 32
b
E m ACB
βπ
−⎡ ⎤ ⎛ ⎞= ⎢ ⎥ ⎜ ⎟
⎝ ⎠⎣ ⎦ (3.18)
The values of each coefficient are given in a series of graphs, see Figure 19.
The graphs do not allow for an accurate prediction of the coefficients and a
method for calculating the parameters for solution was developed by the
author. The method of solving these is a transcendental solution and the
author uses the methodology of Hamrock (1994). The new method was
verified against the ESDU, Hamrock (1994) and published elliptical integral
tables (Byrd and Friedman 1971).
Common to both equations is Equation (3.19).
( )( )1
321 2
34
W P k k A Bπ⎡ ⎤= + +⎢ ⎥⎣ ⎦ (3.19)
The distance of surface deformation at the centre of the contact is given by
Equation (3.20).
( )
12 3C W AA B B
δδ ⎛ ⎞= ⎜ ⎟+ ⎝ ⎠ (3.20)
58
Figure 19 - Contact dimensions, ellipse ratio, and approach coefficients(ESDU 1995).
59
Where the coefficient is given by Equation (3.21).
( ) ( )
1 132 34 AC K mE m Bδ
βπ
−⎡ ⎤ ⎛ ⎞= ⎢ ⎥ ⎜ ⎟⎝ ⎠⎣ ⎦
(3.21)
The pressure distribution across an elliptical contact is given by Equation
(3.22).
( )1
2 2 2
0 2 2, 1 x yp x y pa b
⎡ ⎤= − −⎢ ⎥
⎣ ⎦ (3.22)
Where the maximum stress is given by Equation (3.23).
03
2Ppabπ
= (3.23)
3.4.3 Micro-slip/Creep Prediction
In the lubricated testing a key measurement is the slip, but this slip is
composed of the micro-slip component calculated in this section and the slip
component due to lubrication. It is therefore imperative to predict the micro-
slip component to isolate the effect of lubrication on the rail/wheel contact.
Rolling contact of elastic bodies produces deformation on the surface of both
contacting bodies and subsequently creep or slip between these bodies. Free
rolling is defined as rolling in which there is no tractive force. In the case of
the simulator and field conditions there is always a tractive force applied, and
in all practical (real) rolling applications this force will exist. Tractive rolling
therefore has a strain component associated with the tractive force. This
tractive force can be a nominated value or defined as a proportion of the
normal force. Calculations of friction or traction coefficient will be based on
Amonton’s Law of Friction.
60
In the work of Johnson (1882) two methods, equations (3.24) and (3.25) are
given for predicting the creep of a line contact interface.
when 2
xx x
bQ Q PRP
ξ μ= << (3.24)
1
2
1 1 xx
QbR Pμξ
μ
⎧ ⎫⎛ ⎞⎪ ⎪= − − −⎨ ⎬⎜ ⎟⎝ ⎠⎪ ⎪⎩ ⎭
(3.25)
xξ = Slip ratio in the direction of rolling
xQ = Tractive force in direction of rolling
The first method, Equation (3.24), gives the limit of creep as the proportion
of slip across the contact surface approaches zero. The second method
Equation (3.25) is used for contacts where the ratio of tractive force to
friction force limit is such that the contact has a stick-slip interface.
Measurement of slip in laboratory simulated conditions requires a prediction
of the minimum slip. This minimum slip is used to check the values of the
input measurements and as an offset amount for the prediction of the decay
in slip of a lubricated contact.
Figure 20 shows the minimum values of creep using the first method, over
the range of shearing force the laboratory simulator is capable of producing.
In the case of maximum tractive force the value of creep is 0.06%.
Figure 21 displays the values of creep that will be used for all calculations that
involve slip. This graph is generated using the second method, Equation
(3.25), and it is assumed that the ratio of shearing force to maximum capable
tractive force is significant.
61
0 200 400 600 800 1000 1200 14000
1
2
3
4
5
6x 10
-4
Shear Force Qx (N)
ξ x
Normal Force 9500 NNormal Force 12500 N
Figure 20 – Creep prediction for simulator when contact patch is assumed to have no regions of slip.
0 200 400 600 800 1000 1200 14000
1
2
3
4
5
6
7
8x 10
-4
ξ x
Shear Force Qx (N)
Normal Force 9500 NNormal Force 12500 N
Figure 21 - Creep prediction for simulator when contact patch has regions of slip.
62
3.5 Conformal Rail/Wheel Contact
Rail/wheel contact in the gauge corner can be classified as a conformal
contact. While the contact mechanics of Hertz (1882) is not directly
applicable to conformal profiles, the rail/wheel profile is conformal in one
plane only, which can be seen in Figure 22. It is reasonable then to suggest
that rail/wheel contact can be approximated as a line contact with variable
contacting radii. The purpose of this comparison is to highlight the similarities
of the simulator, which has a line contact, and the field.
The following assumptions are made in order to apply Hertz contact
mechanics to rail/wheel contact.
The load per unit length is constant over the entire contact.
The approach or deformation is constant.
The material properties are constant over the entire surface.
Load will not vary depending on the angle between the normal
contact vector and the load vector.
Deformation or approach is not influenced by the ratio of contact
radii which is changing.
Locations of higher wear will not have a different strain accumulation
to those of lower wear and corresponding changes in material
properties.
Using the assumptions and modifying the rectangular contact width equation
gives Equation (3.26).
1
211 21
11 21
R Rb KR R
⎡ ⎤⎛ ⎞= ⎢ ⎥⎜ ⎟+⎝ ⎠⎣ ⎦
(3.26)
63
K = Contact width equation constant
This formula allows exploration of the theory that the conformal contact may
be approximated as a line contact with variable rolling radius.
Figure 22 – Wheel/rail contact profile(Sato 2005) (Nomenclature for radii in this figure is not used).
The contact radius can be calculated by considering that a conformal rail
wheel contact is approximated as a cylinder on a plate and the plate has an
infinite radius in the direction of rolling. The contact radius may be taken as
the wheel radius giving Equation (3.27).
11 22
22
11
1 1 1
1 1 0
R R R
RR R
= +
= =∞
∴ =
(3.27)
The original equation for line contact cannot be used now as the infinity term
overwhelms the equation. Rearranging the work of Hamrock (1994) gives an
Equation (3.28) for contact width.
64
12
12
8'
8'
Pb RL E R
PKL E
Kb RR
b K R
π
π
⎛ ⎞= ⎜ ⎟× × ×⎝ ⎠
=× ×
⎛ ⎞= ⎜ ⎟⎝ ⎠
= ×
(3.28)
Equation (3.28) states that the change in contact width is proportional to the
square root of the change in rolling radius. The rolling radius, shown in Figure
24, is a discontinuous function of two parts; a linear equation for the tread
and a circular equation for the gauge corner taken from the profile in Figure
23. The radius function was constructed by plotting the rolling radius versus
the surface position. The start point of the radius function will be the central
axis of the matching rail head profile and the end point will be where the
external 12mm radius joins the internal 14 mm radius. Both locations can be
seen in Figure 23. This forms a total contact length of approximately 30mm.
Figure 24 displays the position of contact along the tread, defined as surface
position versus the rolling radius with the zero point as the centre of the
tread.
Figure 23 – Wheel profile for a coned wheel (Sato 2005).
65
0 0.005 0.01 0.015 0.02 0.025 0.03 0.0350.43
0.432
0.434
0.436
0.438
0.44
0.442
Surface Position (m)
Rol
ling
Rad
ius
(m)
Figure 24 – Rolling radius used for calculation of line contact width using wheel profile from Sato (2005).
0 0.005 0.01 0.015 0.02 0.025 0.03 0.0353.47
3.475
3.48
3.485
3.49
3.495
3.5
3.505
3.51
3.515x 10
-3
Surface Position (m)
Con
tact
Wid
th "
b" (m
)
Constant Normal Force
Figure 25 – Contact width profile for constant normal force using a variable rolling radius profile. Note scale of axes different.
66
Using the modified equation for contact width and substituting values of
radius from Figure 24, with an axle load of 30 000 N gives a constant K value
of 2.8045E-5m and a contact profile given in Figure 25. The change in
contact width is small, 40 μ m, indicating that the hypothesis is plausible.
Investigating the change in contact pressure as a result of the radius profile
function in Figure 26 it can be seen that the pressure drops as the rolling
radius increases with a constant load. The assumption of constant load across
the surface, used in this plot, will become invalid as more of the curved gauge
corner is in contact. The contact forces will not be normal to the surface at
these locations and will invalidate the assumptions.
0 0.005 0.01 0.015 0.02 0.025 0.03 0.0359.06
9.08
9.1
9.12
9.14
9.16
9.18x 108
Surface Position (m)
Max
imum
Con
tact
Pre
ssur
e (P
a)
Figure 26 – Maximum pressure for constant tread load across contact and variable contact radius.
67
Changing the assumption of constant tread load (force) across the surface to a
constant maximum pressure across the surface and repeating the analysis, it is
necessary to develop a maximum pressure equation that is independent of
contact width, presented in Equation (3.29).
1
2
0 2Pkp
LRπ⎡ ⎤= ⎢ ⎥⎣ ⎦
(3.29)
Rearranging Equation (3.29) to determine the load distribution across the
surface due to the constant contact pressure gives Equation (3.30).
2
0p RLPkπ= (3.30)
Using this distribution of normal load and substituting into the contact width
Equation (3.28) gives the dashed line in Figure 27.
0 0.005 0.01 0.015 0.02 0.025 0.03 0.0353.46
3.47
3.48
3.49
3.5
3.51
3.52
3.53
3.54
3.55x 10-3
Surface Position (m)
Con
tact
Wid
th "
b" (m
)
Constant Normal ForceConstant Maximum Pressure
Figure 27- Contact width for constant tread load and constant maximum pressure across contact for variable contact radius.
68
The contact pressure used in Figure 27 for the constant maximum pressure
line is the mean pressure of the constant load situation. It can be seen that
there is a small difference in contact profile between the two situations. Figure
27 highlights these small differences by magnification of the contact width
axis (‘y’ axis), without which the change in contact width would appear to be
negligible (approximately 1%). Calculating the change in area between a
normal line contact of rolling radius, set to the mean value of the variable
radius profile (0.4314m) and the two special cases presented in Figure 27 gives
a difference of 0.12%.
-20 -15 -10 -5 0 5 10 15 20-15
-10
-5
0
5
10
15
x (mm)
y (m
m)
Figure 28 – Contact patch dimensions for line and elliptical contact from same normal load, 150,000 N.
Comparing the results of an elliptical contact at the rail head to three other
conditions, line contact, line contact with variable radius and constant load,
and line contact with variable radius and constant maximum pressure shows
that all conformal profiles have a maximum contact pressure of
approximately 0.9 GPa compared to an elliptical contact pressure of 1.5 GPa.
69
To achieve the same maximum pressure in the line contact as in the elliptical
contact requires an increase of wheel force from 150 kN to 440 kN. The
width of the line contact allows the stresses to be dissipated over a
significantly larger contact area which can be observed in Figure 28. In
summary conformal rail profiles offer a significant reduction in contact
pressure.
An important observation from this analysis is conformal wheel/rail contacts
can be approximated by a line contact of constant radius. Approximations in
terms of contact geometry and loading condition taken for the simulator to
mimic a gauge corner contact are proved valid.
3.6 Stress Distributions for In-service Conditions
The stress distributions for field conditions for rail/wheel contact are
presented for two reasons. Firstly to compare and contrast the gauge corner
and tread contacts and secondly to compare these distributions with the
rail/wheel simulator.
The plots of stress in this section will be for geometry taken from the work of
Sato (2005). Three different tractive forces will be used to generate the stress
distributions, zero tractive force, 50% of the limiting tractive force and the
full limiting tractive force. The tractive forces will be based on the maximum
coefficient of friction taken from the work of Lee and Polycarpou (2005).
Their work experimentally determined the friction coefficient to be 0.37 for a
maximum Hertzian pressure of 1.3 GPa and pearlitic rail steel.
Using the input parameters of Table 2, the stress tensor and the effective
maximum shear stress, eτ , shown in Equation (3.31), will be presented.
Maximum effective shear stress is presented in addition to the stress tensor
components, as fatigue failure has been shown to occur at the point of
maximum equivalent shear stress (ESDU 1984; Fletcher and Beynon 2000).
70
( ) ( ) ( )2 2 2
2 2 2
6x y y z z x
e xy yz zx
σ σ σ σ σ στ τ τ τ
− + − + −= + + + (3.31)
In the first case of zero tractive force, the stress distribution for a point
directly beneath the contact is shown in Figure 29. The maximum effective
shear stress, 390 MPa, is located beneath the surface at a depth of 3.9 mm.
The depth of maximum shear stress is the location where shelling fatigue
failures can occur and in this case a 3.9 mm thick section would be lost when
the material had reached its fatigue limit. It should be noted that there are no
shear stress components except the effective shear stress in figure 25 as a
result of the fact that there are no tractive forces. The effective shear stress
arises from the combination of all stress components.
PARAMETER VALUE UNITS Normal Force, P 150 kN
Coefficient of traction 0, 0.185, 0.37 Young’s modulus 207 GPa
Poisson’s ratio 0.3 Body 1 – Tread Contact
Maximum radius ∞ m Minimum radius 0.6 m
Body 2 - Tread Contact Maximum radius ∞ m Minimum radius 0.43 m
Body 1 – Gauge Corner Contact Maximum radius ∞ m Minimum radius 0.014 m
Body 2 - Gauge Corner Contact Maximum radius 0.43 m Minimum radius 0.012 m
Table 2 – Input parameters for contact stress predictions using the profiles of Sato (2005)
Applying a tractive force of 0.185 times the normal force increases the
maximum effective shear stress to 395 MPa and reduces the depth to 3.7 mm,
see Figure 30. Note that the tractive force introduces shear stresses that were
not evident in the case of zero applied tractive force. The maximum effect of
71
these stresses is at the surface of the materials in contact. The relatively minor
change in effective shear stress, 5 MPa, is due to minor increase of stress
penetration into the bodies, practically this translates to continued
accumulated damage from rolling contact beneath the surface and increased
stresses at the surface.
-1200 -1000 -800 -600 -400 -200 0 200 4000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τE
Figure 29 – Stress distribution for tread contact using geometry of Sato (2005) with a normal load of 150 kN and no friction force.
As the maximum effective shear stress moves close to the surface the greater
the likelihood of increased wear from the limited capacity of rail and wheel
steel to withstand the level of shear stress in Figure 30.
For full tractive force, Figure 31, the maximum effective shear stress, 423
MPa, occurs at the surface. In the event of sliding under these conditions the
effective shear stress would have the greatest damaging effects as there is no
material in which to contain the steel, to disperse the stress, under the applied
shear stress.
72
-1200 -1000 -800 -600 -400 -200 0 200 4000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 30 - Stress distribution for tread contact using geometry of Sato (2005) with a normal load of 150 kN and friction force of 0.185 times the normal force.
-1200 -1000 -800 -600 -400 -200 0 200 400 6000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 31 - Stress distribution for tread contact using geometry of Sato (2005) with a normal load of 150 kN and friction force of 0.37 times the normal force.
73
The worst or largest loading case is one in which a normal load of 150kN is
transmitted through the gauge corner will now be discussed. The contact in
this example is analogous to a toroid in an infinitely long round groove (or a
ball bearing in a race), where the force is transmitted through the axis of the
toroid as compared to the previous tread contact which is the same as two
crossed cylinders. The maximum contact pressure in this situation is much
larger than the more common tread contact situation, 2.3 GPa as compared
to 1.1 GPa.
Figure 32 shows the stress distribution for the gauge corner case of zero
tractive force, achievable only in a pure rolling case. The location of
maximum effective shear stress, 811 MPa, where fatigue failure is prevalent, is
below the surface at 2.2 mm and exceeds the shear yield stress, 330 MPa
(Table 8), for this material.
-2500 -2000 -1500 -1000 -500 0 500 10000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τE
Figure 32 – Stress distribution for gauge corner contact using geometry of Sato (2005) with a normal load of 150 kN and no friction force.
74
Figure 33 shows the contact case with a friction coefficient equivalent to half
the maximum value determined by Lee and Polycarpou (2005). Shear stress
components are becoming significant and the maximum effective shear stress,
830 MPa, is 0.2mm closer to the surface at 2mm depth
-2500 -2000 -1500 -1000 -500 0 500 10000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 33 – Stress distribution for gauge corner contact using geometry of Sato (2005) with a normal load of 150 kN and friction force of 0.185 times the normal force.
Figure 34 shows the contact case using the friction coefficient of 0.37
determined by Lee and Polycarpou (2005). Two shear stress components are
reaching the yield shear stress of 330 MPa, see Table 8, and the maximum
effective shear stress, 935 MPa, is at the surface.
In all cases of gauge corner contact as compared to tread contact the
increased state of stress would result in more wear. These stress distributions
provide a plausible explanation for the increased wear rates experienced by
the gauge corner in the field.
75
-2500 -2000 -1500 -1000 -500 0 500 10000
5
10
15
20
25
30
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 34 – Stress distribution for gauge corner contact using geometry of Sato (1994) with a normal load of 150 kN and friction force of 0.37 times the normal force.
3.7 Stress Distributions for Simulator Conditions
The purpose of the contact mechanics analysis for this project is to calculate
and visualise the stress distributions for contacting bodies. Presented in this
section is a typical stress distribution for a gauge corner, rather than the
maximum stress conditions presented in the previous section, in comparison
with the stress distributions for the rail/wheel simulator.
The stress distribution used for comparison, see Figure 35, is for a heavy haul
carriage with a 27.5 tonne axle load travelling at 42km/hr into a 300m radius
corner using the rail profile from Sato (2005) with a super-elevation of
100mm and rail gauge width of 1067mm.
The force used for the stress analysis was calculated using Equation (3.32)
from Waara (2001).
76
F T yF m a= (3.32)
FF = Flange force
ya = Acceleration in the ‘y’ direction
Tm = Mass of train carriage
The acceleration in the 'y' plane, perpendicular to the gravity acceleration
vector, is the balance between the centrifugal acceleration and the acceleration
from the super-elevation of the rail given by Equation(3.33)
2
2aT
yC o
ghvaR b
= − (3.33)
Tv = Train velocity
cR = Curve radius
g = acceleration due to gravity
ah = Super-elevation of rail
ob = Gauge width
Exploration of the stress distributions for all the different conditions tested in
the rail wheel simulator will now be presented. The simulator stress
distributions are for a line contact, representative of a conformal gauge corner
contact as in Section 3.5 using set values for the four groups of tests.
Groups 1 to 3 were tested at 9.5 kN and Group 4 tested at 12.5 kN normal
force levels. The plots will show the stress distributions for the static load and
the stress distributions for the set tractive torques in Table 3. The following
plots display the similarities in shape of stress distributions between in-service
and rail simulator conditions.
77
-600 -500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τE
Figure 35 - Stress distribution for a heavy haul carriage with a 27.5 tonne axle load travelling at 42km/hr into a 300m radius corner using the rail profile from Sato(2005) with a super-elevation of 100mm and rail gauge width of 1067mm
The 9.5 kN normal force case is plotted following Table 3 using the input
parameters from this table.
INPUT PARAMETER VALUE (UNITS) Rail Diameter 296.22 mm Wheel Diameter 97.21 mm Tread Load 9.5 kN Braking Torques 0, 15, 65 N.m Contact Length 41.3 mm
Table 3 – Test parameters used for contact mechanics calculations
78
-500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τE
Figure 36 – Stress distribution for a simulator without braking torque applied.
In the first case of no applied tractive force, see Figure 36 for the stress
distribution. The maximum effective shear stress, 153.5 MPa, is located
beneath the surface at a depth of 0.224 mm. Applying a braking torque of 15
Nm, which equates to 0.03 times the normal force, increases the effective
shear stress to 153.6 MPa and reduces the depth to 0.216 mm, see Figure 37.
The full tractive force, in Figure 38 moves the maximum effective shear
stress, 154.3 MPa, to 0.208 mm beneath the surface. It can be observed from
these results that the simulator is designed to measure low tractive forces such
as those experienced in a lubricated gauge corner contact.
79
-500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 37 - Stress distribution for a simulator with braking torque 15 N.m applied.
There is little difference between the stress distributions of the braked and un-
braked situations in the case of the simulator. This is due to a relatively small
maximum tractive force.
Consider now the maximum braking force condition which gives a ratio or
shearing force to normal force of 0.14 in Figure 38. The components of shear
stress can be observed to have increased in magnitude from the near zero
values in Figure 37 but are still insignificant when compared to the stresses
arising from the normal force. In all the situations plotted in this section the
position of maximum effective shear stress is below the surface. This
condition of shear stress will fatigue the underlying material and give a
shelling failure on the surface.
80
-500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 38 - Stress distribution for a simulator with braking torque 65 N.m applied.
-600 -500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τE
Figure 39 - Stress distribution for a simulator tread load of 12.5 kN without braking torque applied.
81
The tests carried out at the higher tread load of 12.5 kN have the same shape
stress distribution patterns as the lower tread load. However the shear stresses
contribute less to the stress tensor as the magnitude of the tractive forces are
equal but the proportion as compared to the increased normal force is
reduced. The ratios of shearing force to normal force for each of the braking
torque conditions given in Table 3 are 0.025 and 0.11.
In the first case of no applied tractive force, see Figure 39, the maximum
effective shear stress, 176.1 MPa, is located beneath the surface at a depth of
0.256 mm. Applying a braking torque of 15 Nm, which equates to 0.025 times
the normal force, increases the effective shear stress to 176.2 MPa and
reduces the depth to 0.248 mm, see Figure 40. The full tractive force, in
Figure 41, moves the maximum effective shear stress, 176.6 MPa, to 0.24 mm
beneath the surface.
-600 -500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 40 - Stress distribution for a simulator tread load of 12.5 kN with braking torque 15 N.m applied.
82
It is possible to observe in Figure 35 and Figure 39 that the stresses are similar
in magnitude at the surface. Into the body, of the heavy haul conditions, the
stress field extends further into the body as compared to the simulator.
However, the surface is the location of importance to this research as this is
the location of the lubricant film and observing the good correlation, indicates
it is appropriate to use this rail/wheel simulator.
-600 -500 -400 -300 -200 -100 0 100 2000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Stress (MPa)
Dep
th (m
m)
σX
σY
σZ
τXY
τYZ
τZX
τE
Figure 41 - Stress distribution for a simulator tread load of 12.5 kN with braking torque 65 N.m applied.
3.7.1 Two Dimensional Line Contact Stress Distributions
In the previous section the line plots of stress give an indication to the stress
state of the contacting bodies directly beneath the contact. In this section a
two dimensional slice is taken through the bodies to visualise the stresses
within the body. The effective shear stress plot is of particular interest as it
presents the region of maximum shear stress, providing an explanation for the
fatigued steel wear flakes that were encountered in the experimental testing.
83
The theoretical plots of contact stress that are presented within this section
are calculated using the assumption that the real contact width and measured
contact width are the same. This assumption becomes more valid as the real
contact area approaches the apparent contact area. The contact surfaces
develop, with loading history, to reduce the contact stress below the yield
stress for both rail and wheel samples, increasing the real contact area to
approach that of the apparent contact area. Figure 42 shows the theoretical
stress distribution for tread loading conditions for the simulator using a two
dimensional line contact. It can be seen that the most significant stress is the
compressive stress in the direction of the tread load (fz), and is in the yield
strength range of 380-580 MPa. Maximum effective shear stress for this
contact is subsurface at ~0.2mm, but is below the predicted shear yield
strength of 200-300 MPa (see Table 8).
Figure 43 shows the contact stress conditions for the same loading conditions
as Figure 42 with a reduction in contact length of fifty percent (20mm). The
compressive stresses, fz, for this case is in the range of plastic yielding. The
area of real contact for a newly machined sample may be lower than this case,
therefore the surface may plastically deform to reduce the surface pressure.
The previous contact stress predictions in this section do not include the
influence of surface traction forces. Figure 44 shows the contact stress
conditions for the same loading conditions as Figure 42 with an additional
braking torque of 15N.m applied. The addition of a surface traction force
varies the shear stresses. The maximum effective shear stress and the
position of maximum effective shear stress are not altered significantly by the
addition of the surface traction force. This can be observed by comparing the
effective shear stress plots between Figure 42 and Figure 44.
84
-252 -224-196 -168-140 -112-84.6
-28.9 -
fx Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-250-200
-150-100
-50
-410-365 -319-274 -229-184 -139-93.8-48.6 -48.6
fy Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-400
-300
-200
-100
-429-382-334
-286-238
-191-191
-143 -143
-95.4-95.4-47.7 -47
fz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-400
-300-200
-100
-60
-40
-20
0
4060
-80
80-40-100
100
-20
qyz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-100
0
100
173
47.3
77.792.8
108 123
138
108
154
qe Effective Shear Stress Component
y (mm)
z (m
m)
-0.6 -0.4 -0.2 0 0.2 0.4 0.6
0.2
0.4
0.6
50
100
150
Contact Pressure =477.0319MPa, Half width =0.30698mm,Coefficient of Friction=0, Poisson Ratio=0.3
Figure 42 – Contact stress magnitudes for stress components using conditions of tread loading at 9.5kN, 41.3mm contact length.
85
-359-319-279 -240-200 -161-121
81.3 81.3
-41.7 -4
fx Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
0.8
-300
-200
-100
-579 -516-452-388 -325-261 -198-134-70.4 -70.4
fy Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
0.8
-600
-400
-200
-617-548-480 -411-343
-274-274
-206 -206-137 -137
-68.5 -6
fz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
0.8
-600
-400
-200-500
50100-100
-50150 -150
qyz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
0.8
-100
0
100
25.2 46.968.6 90.3112
134155
177
199221
qe Effective Shear Stress Component
y (mm)
z (m
m)
-0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8
0.2
0.4
0.6
0.8
50
100
150
200
Contact Pressure =685.4999MPa, Half width =0.44113mm,Coefficient of Friction=0, Poisson Ratio=0.3
Figure 43 - Contact stress magnitudes for stress components using conditions of tread loading at 9.5kN, 20 mm contact length.
86
-252-223-195-167
-139-111
-82.9
-54.8 -54.8-26.7 -26.7
fx Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-200
-100
0
-410-364-318-271-225-179-133
-87.3-41.2
-41.2 -41
fy Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-400
-300
-200
-100
0
-429-382
-334-286
-238
-191 -191-143 -143-95.4 -95.4-47.7 -47.7
fz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-400
-200
0
-60-40-20
0204060
-8080 -100 -40100-20
-120
qyz Stress Component
y (mm)
z (m
m)
-0.5 0 0.5
0.2
0.4
0.6
-100
0
100
15.4 30.8
46.261
76.9
92.3108
123
138 154
qe Effective Shear Stress Component
y (mm)
z (m
m)
-0.6 -0.4 -0.2 0 0.2 0.4 0.6
0.2
0.4
0.6
50
100
150
Contact Pressure =477.0319MPa, Half width =0.30698mm,Coefficient of Friction=0.032485,Poisson Ratio=0.3
Figure 44 –Contact stress magnitudes for stress components using conditions of tread loading at 9.5kN, dynamometer torque 15N.m, and 41.3 mm contact length.
3.8 Elastohydrodynamic Film Thickness Calculation
The next theoretical calculation for the rail wheel simulator is the lubricant
film thickness. The lubricant film thickness will be used to predict the
apparent viscosity and shear rate of the lubricant films during testing.
Taking the assumption that the contact has a fully developed lubricant film,
by using the known parameters of oil in grease, a lubricant film thickness can
be predicted. A contact condition of pure rolling between two cylinders as
presented in ESDU85027 will now be discussed.
87
The contact conditions that will be used are those of the simulated testing in
Table 3. It will be assumed that the lubricant film thickness is only a function
of the oil, not the solid lubricants or soap.
Lubricant manufacturers do not supply detailed information regarding the
contents of lubricating grease and as a result some assumptions need to be
made regarding the contents. It was not possible to extract the oil from the
soap matrix without contaminating the oil, so direct measurement of the
properties of the lubricant constituents was not possible. Therefore, the
missing values were taken as a high viscosity index light machine oil and were
obtained from ESDU85027 for use within the simulation. The lubricants and
their properties are presented in Table 13.
Lubricant Type Kinematic Viscosity of Base Oil @ 40˚C cSt
Density kg/m3
Lubricant A 150 900 Lubricant B 100 900 Lubricant C 179 947
Table 4 - Manufacturer specified viscosity values for tested lubricants.
The method proposed by Hamrock (1997) is presented in Equation (3.34):
0.128 0.694 0.5680min 1.714( ) ( ) ( ')
' 'z
PVuwh E
E R E Rη ξ−=%% (3.34)
minh% = Minimum film thickness
zw = Load per unit width
u% = Mean surface velocity
PVξ = Pressure viscosity coefficient
0η = Absolute viscosity
88
Inspecting Equation (3.34) the minimum film thickness can be calculated if it
is assumed that the following variables are constant:
entrainment velocity
normal force
temperature
viscosity
pressure viscosity index
The minimum film thickness values that were calculated using software from
ESDU 85027 are presented in Table 5 and will be used later for analysis of
lubricant performance.
Test Conditions and Minimum Film Thickness Lubricant Type Normal Force: 9.5
kN Velocity: 6 m/s
Normal Force: 9.5 kN Velocity: 3 m/s
Normal Force: 12.5 kN Velocity: 6 m/s
Lubricant A 3.55 x 10-6 m 2.24 x 10-6 m 3.55 x 10-6 m Lubricant B 2.71 x 10-6 m 1.71 x 10-6 m 2.71 x 10-6 m Lubricant C 4.14 x 10-6 m 2.6 x 10-6 m 4.13 x 10-6 m
Table 5 – Predicted minimum lubricant film thicknesses for tested lubricants.
3.8.1 Shear rate of lubricant film
Using the predicted lubricant film thickness the shear rate of the lubricant
films can be determined. The lubrication model assumed for in-service and
rail simulator contacts is elastohydrodynamic lubrication (EHL). The rolling
velocity entrains the lubricant into the contact forming an EHL film,
assuming that conditions are of sufficient lubrication. The sliding velocity
component, of the rolling/sliding conditions, shears the lubricant, which
degrades the performance of the lubricating grease. Therefore there are two
effects coming into play, development of an EHL film, and degradation of
the EHL film by shear.
89
The lubricant film of a greased surface may be thicker than that predicted by
the EHL theory due to the soap content of the lubricating grease. Assuming
that the film thickness is modelled by an EHL conjunction, it is possible to
calculate the predicted shear rates.
Body 1
Body 2
Sliding Velocity
x
Figure 45 – One dimensional shear.
In Figure 45 Body 1 is moving with a constant velocity with respect to Body
2. This relative velocity gives rise to a shearing effect in the region between
the bodies that is filled with lubricating grease. The equations of shear for
these boundary conditions are presented in Equation (3.35).
Note: Small angle theory tan
xy
xy
γ
γ γ
=
= = (3.35)
γ = Shear strain
x = distance slid
y = Lubricant film thickness
90
s
s
xt y tx ut
uy
γ
γ•
∂ ∂=∂ ∂∂ =∂
=
(3.36)
γ& = Shear strain rate
,s su v = Sliding velocity
Figure 46 – Shear rate prediction for an EHL film under the range of conditions for the simulator.
Using Equation (3.36) the strain rate can now be predicted for the simulator
across the typical range of parameters, see Figure 46. In the case of the
simulator, the rolling velocity is fixed for a given test but the sliding velocity is
91
constantly changing. It is a similar situation the for the lubricant film thickness
in that the film thickness is greatest at time zero and decays over time.
The in-service conditions are now considered using EHL theory. The
theoretical shear rate and sliding velocity are reduced by an order of
magnitude for the in-service conditions of the rail/wheel interface compared
to the theoretical simulator conditions. This variation in the shear rate is a
consequence of the difference in sliding speeds experienced by each of the
contacts. Typically for in-service conditions slip will not exceed 5% compared
to simulator conditions of up to 100% slip as a result of controlling the
maximum shearing force.
Figure 47 – Shear rate prediction for an EHL film under the range of conditions for in-service conditions.
Comparing these shear rates in Figure 47 to the results from the pumpability
testing in Section 5.7.4 shows that there is a difference in shear rate of three
orders of magnitude. This difference will not allow for prediction of the
92
apparent viscosity from the pumpability tests unless some assumptions
concerning the rheology of the greases are made. The comparisons between
the simulator viscosity results and the ASTM tests and rheometer results will
be discussed later in Section 5.7
3.8.2 Lubricant apparent viscosity calculation
If the lubricant film thickness and flange gap can be identified, the shear rate
and therefore the viscosity of the lubricant can be determined. The real film
thickness is difficult to measure for both the rail system and the simulator.
The value of the film thickness must therefore be estimated using EHL
theory presented in Section 3.8. In the simulated system, the shear stress can
be predicted from the measured braking torque of the system by assuming the
contact patch dimensions and by assuming that the contact patch dimensions
will remain constant with respect to time. The contact patch dimensions will
remain constant if the normal force remains constant, and is independent in
variations in the lateral force (braking torque). The nominal load of the
simulator possesses slight fluctuations about a mean value. These slight
fluctuations allow the assumption of constant normal force and contact patch
dimensions to be made. The mean nominal load value is used in the
calculations of shear stress within the lubricant film.
To predict the apparent viscosity of the lubricants from the simulator, the
shear stress and shear strain must be calculated.
BT
c
FA
τ = (3.37)
BTF = Force from shearing lubricant
cA = Contact area
τ = Shear stress
93
The shear stress predicted by Equation (3.37) is commonly used for solid
bodies, that is, the lubricant film between the bodies in Figure 45 is
considered to be a solid. If the lubricant film is considered to be a liquid then
the relationship for viscosity, Equation (3.38), is used.
τ η γ•
= (3.38)
η = Apparent viscosity
Considering these relationships and the measurements from the simulator, a
prediction of the apparent viscosity of the lubricating grease can be made.
If the applied shear stress from the braking torque of the simulator is below
that which the lubricant can support, then the lubricant film will remain as a
solid and transmit the input torque. This effect was observed experimentally.
This effect is seen as the slip approaches zero despite an observable lubricant
film. During the progression of the simulation test, the lubricity of the
lubricant decreases with accumulated strain. Alternatively, presenting this with
respect to apparent viscosity, the viscosity increases with accumulated damage
from shear strain.
Preceding the point of limiting shear stress, the lubricant film behaves as a
fluid allowing slip to occur. Therefore at some point the yield shear stress of
the lubricant becomes larger than the applied shear stress and traction is
obtained. Predicting the point of traction with the use of rheological testing
would be fast and relatively inexpensive, if there was a correlation, and if it
was relevant as a performance criterion.
The simulator may assist in predicting the development of this yield stress
with respect to accumulated strain. The problem with this method is the
unknown film thickness and its development with time. Assuming that
lubricant film thickness is that of an EHL contact for the base oil of the
94
lubricant, plots of the stress versus strain rate curves for each lubricating
grease can be constructed.
The apparent viscosity is now investigated using Equation (3.39) by equating
Equation (3.37) and Equation (3.38).
BT
C S
F yA v
τ η γ
η
•= ×
= × (3.39)
In this equation there are four variables, two mathematically predicted and
two measured. The calculated shear stress is generated from the transmitted
torque by the lubricant, or the shearing of the lubricant applies a torque to the
output shaft. This shearing force can be calculated from the measured output
torque divided by the output radial vector. The contact area is predicted from
the contact mechanics calculations and is assumed to be constant for each
test. Sliding velocity is measured as the difference in rolling speeds between
input and output shafts. Film thickness is predicted from an EHL calculation
of the base oil of the lubricating grease. This parameter is assumed to be
constant during each test. From these values it can be seen that viscosity is a
function of time, or as previously mentioned, accumulated strain.
There are issues with predicting the value of film thickness. Film thickness
will change with time as the temperature of the lubricant increases, the effect
of which is to lower viscosity. In addition the soap matrix decaying with
accumulated strain will also decrease the film thickness. The contact velocity
for the EHL calculation is assumed to be constant, as the input velocity is
fixed for the duration of each test. However the velocity can vary during
testing. Lubricant manufacturers supply kinematic viscosity results in their
lubricant specification details which then requires an estimation of the oil
density to predict the dynamic viscosity required for an EHL film thickness
95
calculation. A nominal value was chosen from tables of physical constants or
the manufacturer specification if available.
Additional example conditions are given for the lubricant films to determine
the appropriate average stress range in Table 6.
Parameter Value Theoretical maximum braking torque 65 N.m Experimental maximum braking torque 62 N.m Experimental contact radius 50 mm Theoretical maximum tractive force 1300 N Theoretical contact area at 12.5 kN 28.8 mm2 Theoretical tractive shear stress at 12.5 kN normal load
45 MPa
Table 6 – Theoretical results for inputs to EHL calculations.
All the required parameters have been presented to calculate film thickness,
shear rate, and apparent viscosity for the simulator, including their limitations.
3.9 Summary
The following major points have been identified:
Software was developed and validated based on the methods of the ESDU to calculate the stresses in bodies in contact.
Under simulated conditions with the maximum tractive force the value of creep is 0.06%.
Conformal rail profiles can be approximated by a line contact, similar to that used in the simulated rail curve lubricant testing.
The maximum contact pressure in gauge corner contact is much larger than the more common tread contact situation, 2.3 GPa as compared to 1.1 GPa.
The tested simulator conditions match the stress distribution for a heavy haul carriage with a 27.5 tonne axle load travelling at 42km/hr into a 300m radius corner using the rail profile from Sato (2005) with a super-elevation of 100mm and rail gauge width of 1067mm.
96
Lubricant film thickness is calculated using elastohydrodynamic film theory for the calculation of shear strain. Shear strain is then used in conjunction with shear stress to predict the apparent viscosity of the rail curve lubricants.
This chapter presented the theoretical background of contact mechanics
specifically between wheel and rail to develop an understanding of the stress
conditions. Stress distributions for typical in-service and simulator conditions
were presented to demonstrate the similarities between the two conditions.
These highlighted the effects of geometry and changes in shear force on the
stress distributions and the reasons for increased wear in the gauge corner.
The model for apparent viscosity calculation using the rail/wheel simulator
was then detailed. These theoretical calculations form the basis of the next
chapter on the experimental method applied to the simulator and inputs for
the data analysis in Chapter 5.
97
C h a p t e r 4
COMMISSIONING AND TESTING PROTOCOL OF THE RAIL/WHEEL INTERACTION SIMULATOR
4.1 Introduction
This chapter details the rail/wheel simulator, see Figure 48, with specific
reference to the current work.
Hydraulic Dynamometer
Wheel Sample
M
Rail Sample
Torque Transducer
AC Motor
Normal ForceLoad Cell
Shaft Encoders
Heat Exchanger
Pneumatic Ram(Normal Force)
Support Bearings
Figure 48- Schematic diagram of the rail/wheel simulator.
The first section on equipment modifications broadly outlines the deficiencies
for lubrication research in the simulator and the steps taken to address them.
The experimental method and procedure follows. Details of the measurement
system and errors associated with each of the components and calculated
values of this system complete this chapter.
98
4.2 Equipment Modifications
The rail/wheel simulator was originally configured for rail/wheel wear
investigation. Unfortunately the maintenance and design information for the
simulator was unavailable which led to a full disassembly of the rail/wheel
simulator. This disassembly served two purposes, to overhaul all of the
components of the simulator that were worn as a result of previous use and
to understand the design of the system. Communication with the previous
researchers also highlighted some design deficiencies of the equipment that
were then rectified for the purposes of this research project. Significant
modifications were then proposed when considering heat dissipation, the
tread load mechanism and the data acquisition system to carry out the
objective of quantifying rail curve lubricant performance through laboratory
simulation.
4.2.1 Heat Dissipation
The primary concern with the operation of the rail/wheel simulator in the
previous research was the dissipation of heat generated during testing. A full
description of the issues concerning the heat dissipation was not provided
with the simulator. The simulator also arrived without the hydraulic
dynamometer and with the remnants of the heat exchanger for the hydraulic
oil disassembled. The previous heat exchanging system consisted of a coiled
copper tube of 12mm internal diameter wound in a continuous loop in the
main oil storage tanks. During a preliminary investigation into the heat load it
was determined that the input power from the variable frequency drive is
converted to heat, with minor losses to noise and vibration. Given this
information it was believed that the heat exchanger was required to have a 22
kW minimum capacity. A new heat exchanger was therefore required as the
existing heat exchanger possessed a capacity (approximately 2 kW capacity)
smaller than 22 kW.
The original heat transfer system, a copper pipe coil placed in the hydraulic oil
reservoirs with water input, was used as the basis for the new design. The
99
simplicity of the original design led to consideration of retrofitting the existing
pipe with extra length to increase the surface area. However, the length of
pipe required for the surface area to remove the heat load (approximately 100
m) would not physically fit into the existing oil storage reservoir. The increase
in pipe friction was also an issue for the increase in pipe length.
Existing decommissioned heat exchangers were disassembled and their heat
transfer characteristics determined using convection heat transfer equations
(name plate data for the heat exchangers was not available). The heat
exchangers that were investigated included a water-oil single pass shell and
tube heat exchanger and a water-oil plate heat exchanger. Two problems
were encountered when investigating the single pass shell and tube heat
exchanger. The first was that six of the units were necessary to achieve the
required energy dissipation. The second was that the back pressure of the oil
through each shell and tube heat exchanger would apply an undesirable
braking load to the system.
The analysis of the water-oil plate heat exchanger was carried out using the
methods of Holman (1997). This type was selected due its high surface area to
volume ratio, compact design and low fluid resistance. These advantages are
essential when considering the overall heat transfer coefficient of oil-water
compared to water-water is at least an order of magnitude smaller.
The plate heat exchanger used was originally selected for a 1 MW milk-water
application. In an oil-water application this capacity is reduced to 100 kW,
which is greater than the required 22 kW. With the plate exchanger installed
and at full heat load, the outlet water of the heat exchanger is imperceptibly
hotter than at the inlet when operating at full capacity. The hydraulic
dynamometer is sensitive to variations in the oil temperature. It is therefore
important to maintain a moderate and constant oil temperature. In this case
the oil temperature is limited to between 40˚C to 45˚C to reduce the friction
forces in bearings lubricated with the hydraulic oil.
100
4.2.2 Tread Loading Mechanism
The original tread and flange loading mechanisms utilised a mechanical screw
to apply the load, see Figure 49. A rubber cylinder was located between the
end of the screw and the load application point (within the encasing indicated
in red). The measured tread load in this configuration varied widely as a result
of vibrations. In addition, the applied load would change with temperature
and creep due to the viscoelastic properties of the rubber.
Figure 49 – Tread loading mechanism showing original screw force applicator.
The screw load applicator relied on displacement to provide a force. For a
constant force the screw load applicator required a fixed displacement.
Therefore, as wearing of the samples occurred the force transmitted between
the samples would reduce. The screw load applicator therefore did not
maintain a constant load throughout the duration of the wear tests in the
work of Marich and Mutton (1989). These considerations led to a redesign of
the tread loading mechanism.
101
A pneumatic system for tread loading was designed to replace the existing
mechanical system. The advantages of the pneumatic system is that it reduces
the amplitude of loading oscillations (dynamic loading) and reduce load
variations by eliminating factors such as the rubber cylinder and the influence
of wear that were present within the original system. A high capacity
pneumatic source supplying a single pressure control valve which supplies a
pneumatic actuator was used.
Pneumatic pressure control devices typically do not sense downstream
pressure variations. In practice this means that if the load experienced by the
pneumatic ram increases, there is a corresponding increase in the pressure of
the cylinder and piping to the outlet side of the pressure control valve. This
increase in pressure cannot be dissipated through the pressure control valve
but must be bled off through another mechanism, in this case a controlled
system bleed. The bleed is tuned to provide the minimum amplitude of load
oscillation.
The effects of this modification have been twofold. The variation of load with
time has been measured with the new configuration and found to be
negligible whereas previously this was a serious concern. Previously constant
changes to the mechanical system were required to hold the load within ten
percent of target load limits. Outcomes of increasing load stability and system
control have been achieved with this modification.
The wheel sample head has three bearing surfaces upon which friction acts.
This friction modifies the load experienced at the contact between rail and
wheel samples. Two of the surfaces are equipped with Teflon bearing pads
which are then lubricated with oil to provide as low a friction component as
possible. The third surface originally was a steel-steel contact and is now a
lubricated brass-steel contact. The contact surfaces are depicted in Figure 50.
102
Figure 50 – Simplified wheel sample holder assembly. The large flat section at the left is the slider which moves in the channel. At the left end of the device the contact surfaces can be observed.
In its original configuration the wheel sample head could rotate about its
vertical axis in the running channel and apply pressure at the corners of the
guide block. The pressure in the corners would increase from an increase in
wheel head temperature from thermal expansion as the test progressed. The
effect of this was to reduce the sensed/measured load while applying an
increasing tread load to the rail and wheel samples. In the previous research
this may have gone undetected as the problem was only detected by using a
measured extraction force which was not possible in the configuration used
by Marich and Mutton (1989). Mechanical advantage in the mechanical screw
loading system may have masked the appearance of this phenomenon.
Identification of the steel on steel bearing surface also highlighted the need
for improved load alignment. It was initially believed that the contact width of
the samples would minimise loading alignment issues. Investigation into this
matter showed that alignment issues existed as plastic deformation and
103
associated wear accumulated on one end of the test samples during a
commissioning test discussed further in Section 4.3. Rectification of the
alignment was carried out through guide rail adjustments.
The primary concern for alignment was that the loading force was not central
to the test samples, but offset to one side by approximately 10 mm. This
offset may have provided a torque about the vertical axis, and may have
applied a variable force across the test sample contact surfaces. This variable
force can only occur if the wheel sample holder is not sufficiently restrained.
The guide rails on the simulator frame now restrain the wheel sample holder
in the vertical and lateral directions. Experimentally there was no evidence of
a variable tread force across the contact surface.
The force to move the wheel sample holder can be a component of the
measured applied force from the pneumatic ram under static conditions, a
source of error in this measurement. The friction force remains after moving
the wheel sample holder into position. During testing the vibrations through
the contact patch into the wheel sample holder caused a reduction in the
friction force, such that it approached zero and the measured normal force is
the applied normal force. The friction force arose from the two normal
forces, the force of gravity from the mass of the sample holder and the force
from the applied braking torque. A variation of the force will cause a
corresponding variation in the friction force to move the wheel sample
holder. In addition as the wheel sample holder expands within the alignment
rail channel, from an increase in temperature, the friction force may increase.
A maximum friction force of less than 500N was required. It was therefore
necessary to know the tolerance of the alignment rails as this is the only
adjustment available to reduce the friction force in moving the wheel sample
holder.
Experimental measurement of the tolerances of the alignment rails was
carried out by measuring the force required to move the sample head in both
104
directions and the tolerance gap set to an acceptable friction force of 300N.
Verification, under a range of operating temperatures, that the friction force
was less than 500N under test conditions was carried out and found to be less
than the threshold value of 500N (approximately 350N).
4.2.3 Data Acquisition
In the process of checking the tread loading system, deficiencies in the data
feedback system became apparent. High frequency and resolution data were
acquired from the original load cell electronics to find the source of the issues.
Harmonic noise was found. The load cells were sensitive to electronic noise
from the 50 Hz single phase supply power and magnetic or electronic noise
from the variable frequency drive.
The entire loading measurement system was checked with respect to the
mechanical and electronic components. The load cells were a custom design
of a membrane type installed between the loading mechanism and the wheel
sample holder. These were physically inspected for damage to the strain
gauges and calibrated. There were no mechanical issues. The strain gauge
amplifiers were checked and found to be faulty. Upon replacement the noise
issues were still apparent. Two changes were made, addition of a 50 Hz filter
to the electronics and installation of an earthing circuit. Verification by repeat
data collection showed elimination of the power supply noise at 50 Hz and
reduction to barely detectable levels of the variable frequency drive noise.
Mechanical vibration of the entire simulator was now the dominant
component of signal noise.
4.2.4 Tractive Force Application System
In the work of Marich and Mutton (1989) it is not clear as to the purpose or
settings of their hydraulic braking system. It is not mentioned in the published
work but is apparent in the photographs of the simulator. The braking system
had been removed prior to its relocation so reverse engineering was
impossible.
105
Safety Relief Valve
Main Tank
Pressure Relief Valve Ball Valve
MWheel SampleDriving Input
Torque Transducer
Hydraulic Pump
Pressure Transducer Heat Exchanger
Figure 51 – Hydraulic dynamometer system.
A design study was carried out and a hydraulic dynamometer system installed.
The dynamometer system controlled braking torque only, contrary to other
twin-disk systems which measure friction force (Marich and Mutton 1989;
Markov 1995; Tyfour et al. 1995; Olofsson and Telliskivi 2003). The
controlled braking torque creates high slip conditions at the beginning of
lubricated tests. It is unlikely that in-service conditions would ever achieve this
level of slip except under extreme circumstances.
The hydraulic system design was vital due to the change in sample shape from
the work of Marich and Mutton (1989). Previously the wheel samples had a
flange upon which a load was applied. The slip in the work of Marich and
106
Mutton (1989) was purely related to geometry, and was variable across the
flange surface from root of the flange to the tip. The testing in this thesis used
a twin-disk design, with slip controlled by the dynamometer. Contact patch
dimensions and loads are easily measured and calculated with this sample
geometry. Future work will investigate changing the wheel profile to
investigate elliptical contacts.
4.2.5 Slip/Creep Measurement
The rotational speed measurement system for slip calculation has been totally
redesigned to increase the resolution of speed and slip measurements of the
rail and wheel samples. Previously the speed of shaft rotation was measured
with a proximity probe and notched wheel outputting to a digital display. This
method lacks the resolution and accuracy required to measure slip.
Inductance proximity probes are sensitive to changes in speed and distance to
inductive material (notch on wheel). To address the issues with the original
inductance probes shaft encoders were installed. The encoders have a
resolution of 5400 encoder counts per revolution to gather high resolution
data for the shaft position and speed. This modification increased the
accuracy of slip/creep measurement by two orders of magnitude and is
unique to twin disk rail curve lubricant devices.
4.3 Testing equipment – construction/commissioning
The commissioning testing results are presented to provide the background
for the testing methodology in the following sections.
4.3.1 Pre-Commissioning Testing Observations
The commissioning testing used recycled test samples, which had been used
in the work of Marich and Mutton (1989). Following use of the recycled test
samples, with a variety of testing protocols used to determine the capabilities
of the simulator, the samples displayed wear characteristics comparable to
that encountered in service (Marich and Mutton 1989). Two distinct wear
processes were observed, oxidative and fatigue wear. Oxidative wear can be
107
observed in Figure 52(a) as the darker section of the contact surface. The
fatigue wear was observed by the surface changing to an appearance matching
ratchetting fatigue wear and vibration and noise emanating from the contact.
This ratchetting is shown in Figure 52(b).
(a)
(b)
Figure 52 – Rail sample with oxidative and fatigue wear (a). Wheel sample with oxidised material removed to highlight plastic deformation (b).
4.3.2 Commissioning Testing Observations
Commissioning testing was carried out to develop the lubricated test methods
employed in this thesis. The wheel and rail samples used in commissioning
tests were recycled from the testing of Marich and Mutton (1989) and the rail
geometry changed to a flat twin-disk configuration. The samples were
prepared by machining the surfaces of both samples to flat, removing any
work hardened material. The samples were placed in the simulator and
prepared by applying loads which exceeded the yield stress of the wheel and
rail steels.
During the ‘run-in’ period a narrow ring of worn material was observed on
both wheel and rail samples, see Figure 53. An investigation was carried out
to determine the cause of this wear patch, which was only a small fraction of
the total width of the contact. Initially the contact zone was investigated with
methylene blue to ascertain whether the samples were indeed contacting
108
across the full width. The methylene blue test indicated that full contact was
achieved despite the obviously worn ring.
The samples were measured in-situ for trueness using dial indicators
(resolution ±0.01mm) and were found to be in the range below the resolution
of the measuring equipment. The loading mechanism on the wheel sample
holder was then investigated for alignment problems and no skew, to cause
the wear at the outer edge of the sample, could be found.
The samples were then removed to quantify the change in surface profile
from the ‘run-in’ period and for machining to re-prepare the surfaces. Surface
preparation was achieved by machining in a lathe using machining jigs which
have an axial run-out of less than 0.01mm. Measurements of surface profile
taken in the lathe did not have the resolution necessary to quantify the worn
section.
(a)
(b)
Figure 53 – Rail sample mounted in machining jig following initial lathe cut, with pitting at the outer edge of the rail sample(a). Wheel sample with hardened material, the smoother ring, at the outer edge of the sample (b).
During machining of the rail sample, material was observed to be plucked
from the surface, where the corresponding pits can be seen in Figure 53(a).
These pits could not be observed prior to the machining process, only a ring
of different surface texture. It was also noticed that the material hardness was
109
fairly constant across the surface. Conversely for the wheel sample the
material hardness was significantly higher at the worn region. Sparks from the
lathe cutting tool were observed during machining of the wheel sample which
is indicative of high hardness material.
Further investigation into the literature (Tyfour et al. 1995; Lewis and Dwyer-
Joyce 2004) gave indication that the phenomena observed was characteristic
of this type of contact. Sample preparation or pre-conditioning was resumed
with a freshly prepared pair of samples for investigation of lubricated contact.
(a)
(b)
(c)
(d)
Figure 54(a,b,c,d) – Wear development of running surfaces on wheel and rail samples (left to right, top to bottom).
There were three main phases observed during the lubricated testing:
lubricant spread and sample acceleration; gross sliding; and traction
development. In the first phase the lubricant is forced to the outer edges of
the samples where it is flung from the surface and the surfaces are observed
110
to have a consistent coverage of lubricant, Figure 54(a). The end of this phase,
when the samples are reaching the set velocity, marks the beginning of the
second phase: the wheel sample (output shaft) slowing down and gross sliding
of both surfaces occurs. This gross sliding continues until the lubricant film
breaks down and metal to metal contact occurs, Figure 54(b). This metal
contact can be seen in Figure 54(c) at the outer right edge of the samples.
The wear rings develop at a randomly different location with each test run,
but always on the newly machined material. The newly machined material was
measured and found to be softer than the worn rings. This surface
development is similar to the shake-down process experienced by new rails.
Figure 55 shows the development of the surface from two wide bands in (a)
to approximately fifty percent coverage in (b) and (c). The wear material that
was not transferred to the other surface collected at the outlet of the rolling
contact as shown in Figure 55(d).
Wear particles collected after testing consisted of two main particle sizes,
large flat flakes (> 1 mm) and small flakes (< 1 mm). The large flakes appear
to be from the initial breakdown of the lubricant film. Material removed
from the samples during this phase was seen to leave the contact zone which
can be observed clearly in Figure 56(b) by the ring of 'shiny' steel. The small
particles cannot be seen to form as testing progresses and can only be
observed in the collected excess lubricant.
The lubricant application method depicted in Figure 56(a), not the method
used in the later lubricated testing, does not spread a consistent thickness
layer over both samples, but does apply a reasonably uniform amount of
lubricant to the central region of the rail sample. The lubricant is spread by
the action of the samples rolling together where the excess lubricant is
forced from the contact patch forward and to the outer edges of the wheel
sample.
111
(a) (b)
(c)
(d)
Figure 55 – Wear development of running surface following repeated lubricated tests (a-c) Wear particles and excess lubricant (d).
Little excess lubricant collected at the edges of the rail sample using this
application method. There are two reasons for this, firstly the rail sample has a
much larger radius than the wheel sample, and therefore a larger centrifugal
force is generated, causing the lubricant to leave the rail sample, which has
been observed. Secondly the wheel sample is of a much smaller diameter and
therefore the volume of lubricant which can be supported through the
contact region is significantly less than the rail sample, forcing the excess
lubricant to the outer edges. The point at which the surplus lubricant collects
can be seen in Figure 55(d).
112
(a)
(b)
Figure 56 – Grease application pattern (a) and subsequent lubricant film failure of running surfaces (b).
The measurements of the rolling diameter of the rail and wheel samples
stabilised following an initial period of change. The period of change is typical
of pearlitic steels as the material strain hardens through repeated plastic strain
(Fletcher and Beynon 2000). Initially the freshly machined surfaces of the rail
and wheel samples would experience plastic deformation to increase the ‘real’
contact area. Then the strain will accumulate to a point where either the
material hardness or surface yield strength are above that of the contact
pressure. If the material cannot achieve the amount of strain hardening to
increase the material strength above the applied stress then the material will
reach the ductility limit and fail.
A wear characteristic similar to ratchetting was observed on the rail sample as
the contact surface has a pocked appearance. Ratchetting in rails appears as
small flakes of material being removed from the samples by the tractive force
after sufficient plastic deformation has taken place.
113
(a)
(b)
Figure 57 – (a)Wear particles collected from lubricant, two distinct particle sizes are attached to the magnetic sample collector (8mm diameter). (b) Demagnetised wear particles at higher magnification.
Changing the braking torque (applied shear force) generated new contact
surfaces by removing material from the rail and wheel samples that was at its
ductility limit, see Figure 57. In the work of Tyfour et al. (1995) steady state
wear conditions developed after a number of loading cycles. This behaviour
was also exhibited by the simulated system. Upon increase of surface traction
the cumulative strain distribution changed and greater material removal rates
were observed. The lubricant film would be completely destroyed in a ring
pattern as the large metal flakes left the surface, see Figure 58. Steady state
conditions were reached when the rings of new (shiny) material stop
appearing during the lubricated testing. In the commissioning tests preceding
the lubricated testing, surface traction was kept constant and steady state
conditions were reached.
114
(a)
(b)
Figure 58 – (a) Lubricant film failure on right of sample (b) Lubricant film failure on left of sample. Material removed from the surface of the rail sample destroys lubricant film over a nominal contact width depending on the size of the wear particles.
4.4 Lubricated Testing Protocol
The primary objective of the testing protocol was to determine the
performance properties of rail curve lubricants using the rail/wheel simulator
in line with the overall objective of the thesis.
4.4.1 Preparation of the rail/wheel samples
Following selection of a suitable material couple, the rail/wheel samples were
machined to the required profile. Following this the samples were installed in
the machine and the machine parameters set. The rail/wheel samples were
machined at the beginning of the lubricated testing and no further machining
was carried out on these samples. Test samples were never removed from the
test equipment to ensure alignments issues were constant throughout testing.
4.4.2 Material Properties
The chemical constituents and material properties for the rail and wheel
samples are detailed in Table 7 and Table 8.
115
Chemical Composition Brinell Hardness (HRC)
Material Type
C Mn Si Cr Mo Wheel samples 0.72 0.80 0.32 0.31 0.045 320-385
(34.2- 41.7) Rail samples 0.72 0.80 0.32 0.31 0.045 257-272
(25.3- 27.7) Table 7 - Material properties of test samples (Marich and Mutton 1989).
Material Brinell Hardness (HRC)
Shear Yield Strength (MPa)
Ultimate Shear Strength (MPa)
Tensile Yield Strength (MPa)
Ultimate Tensile Strength (MPa)
AISI 1080(Automation Creations 2005a)
293 (30.7) 330 536 585 965
AISI 1070(Automation Creations 2005a; Automation Creations 2005b)
212 (16.9) 217 390 385 703
Table 8 – Mechanical properties of similar high carbon steel alloys (Automation Creations 2005b; Automation Creations 2005a).
The shear properties presented in Table 8 were calculated using the work of
Guduru et el (1989), Equation (4.1) and Equation (4.2):
1.77y yσ τ= (4.1)
yσ = Yield stress
yτ = Shear yield stress
1.8US USσ τ= (4.2)
116
USσ = Ultimate tensile strength
USτ = Ultimate shear yield strength
The shear strength was predicted as this value was not available.
MIN MAX MEAN STD. DEV. Rail Surface (HB) 246 280 259 12 Wheel Surface (HB) 311 362 325 19 Rail Bulk Material (HB) 241 249 245 4 Wheel Bulk Material (HB) 287 307 295 11
Table 9- Measured hardness results for rail and wheel samples with minimal loading cycles.
NEWLY MACHINED TEST 1 TEST 2 TEST 3 TEST 4
Range 241-249 238-275 257-285 249-289 248-288 Mean 245 255 267 263 254 Std Dev. 4 17 11 16 31
Table 10 – Rail Sample Hardness Range in HB (Brinell 3000 kgf Std).
NEWLY MACHINED
TEST 1 TEST 2 TEST 3 TEST 4
Range 287-307 324-371 310-384 324-347 320-360 Mean 295 345 336 335 343
Std Dev. 11 20 31 9 17 Table 11 - Wheel Sample Hardness Range in HB (Brinell 3000 kgf Std).
Comparing the hardness values between those measured, in Table 9, and the
work of Marich and Mutton (1989), Table 7, shows similar values. Comparing
the experimental values to the quoted values in Table 8 it can be seen that the
rail alloys are harder than the 1070 steel but similar to the 1080 steel.
Hardness testing was carried out on the rail and wheel samples following each
of the lubricated tests to measure the hardness development from repeated
117
cycling. Table 10 and Table 11 show that after initial loading subsequent
loading does not increase the measurable surface hardness.
4.4.3 Test Sample Surface Roughness Results
Roughness testing was carried out after machining of the wheel and rail
samples and at the completion of all lubricated testing, the results contained
in Table 12. The measured surface roughness achieved post-machining was
less than the specified machining tolerance of 1.6 µm and less than the
predicted EHL film thickness.
Average roughness value range for newly machined surface. (Ra)
Average roughness value range at completion of all testing. (Ra)
1.08-1.22 µm 4.7-5.8 µm Table 12 – Roughness measurements taken from wheel and rail samples after machining and at the completion of all lubricated testing.
Roughness at the completion of all testing was more than the minimum film
thickness calculated for the assumed EHL conditions. The film thickness
calculations were conservative and based on lubricating oil component of the
lubricating grease. Experimentally it was found that during the lubricated tests
the surfaces did not experience metal on metal contact except at the lubricant
film failure point, not from initial contact as the film thickness calculations
would suggest. The lubricant film failures which were observed as rings of
removed lubricant film would probably have resulted from localised
roughness exceeding the lubricant film thickness.
4.4.4 Testing Procedure
Clean both samples in situ, initially with white spirit or similar, then finally with hexane to ensure any residue is removed.
Measure diameter of rail sample three times using pi tape (resolution ± 0.01mm).
Measure diameter of wheel sample three times using external micrometer (range 75-100mm, resolution ± 0.01mm).
118
Measure ambient temperature with infrared thermometer on surface of constant emissivity (Temperature range: -50 to + 500 degrees C, Accuracy: +/-2% of reading or +/-2 deg C) .
Position wheel sample holder to place rail and wheel samples in contact at specified tread load.
Start variable frequency drive and accelerate to test speed at a rate of 0.1 Hz per second.
After approximately five minutes a tractive force is applied by way of the hydraulic dynamometer. This force is set by adjusting the pressure in the hydraulic system and is measured at the wheel holder by the torque transducer.
The system is then shut down and lubricant is applied to the running surface of the rail sample.
Start variable frequency drive and accelerate to test speed (e.g. 20 Hz) at a rate of 0.1 Hz per second. Sixty seconds after start-up the dynamometer is activated at the set pressure.
Ensure wheel sample is rotating to prevent damage.
Measure data until set point is reached, the set point for each test was a time following development of full traction conditions.
Monitor slip conditions with HP5315A Universal Counter in frequency ratio mode.
Measure temperature of test samples with infra-red thermometer.
4.5 Method of Measurements
The method of measurements is presented here in order to aid understanding
of the test equipment and presented results in Chapter 5. A short summary of
each of the measurements is presented in this section followed by more
details of each particular measurement and its calibration.
The tread loads are measured indirectly, as it is not possible to measure at the
contact point during a test, but in the same axis as the direction of loading.
The pneumatic loading rams apply force to a diaphragm load cell placed
between the sample holder and the ram, see Figure 48. The load cells are then
119
calibrated in situ by placing a reference load cell at the loading point for a
direct measurement of the contact force.
Rotational speeds of both samples are measured with high precision shaft
encoders. The rotational speeds are also used to determine the slip ratio
between the samples, the sliding velocity of the flange contact, and the linear
velocity of samples.
In the work of Marich and Mutton (1989) the rotational speeds were
measured using notched wheels with a very low resolution for measuring
shaft position and speed. The modified method used in this thesis allows for a
more accurate prediction of the contact mechanics of the interface. The
limiting factor with the new method of slip calculation, as determined by error
analysis present in Section 4.7, is the resolution of the sample diameter
measurements.
The measurements of the sample diameters have been taken with a contact
measurement device. Higher resolution devices were considered but the
samples will experience thermal expansion effects of magnitude larger than
the resolution of the measuring equipment. The thermal effects have been
predicted from sample bulk temperatures and are presented in Section 4.6.1.
A further limitation in the slip prediction is the wear of samples in the tread
contact area. Sample geometry was measured to provide a suitable prediction
of the rate of diameter change. This change in diameter corresponds to a
change in slip and output ratio of the system and a variance in the sliding
speed of the contact. Experimentally it was found that a change in diameter
following testing could not be measured. Additionally testing was always
ceased prior to full lubricant film failure.
4.5.1 Rotational Speed Measurement
Rotation was measured using 5400 pulse per revolution incremental shaft
encoders. The encoders were physically connected to the input and output
120
shafts by timing belts which eliminates error from belt slip. This mounting
arrangement only allows an absolute error of one pulse in the total of pulses
over the sample period. Another method of interpreting this is the system has
a rotational resolution of 0.00116 radians/pulse (0.067 degrees/pulse).
The resolution of speed and slip measurements is dictated by the sampling
period. Therefore to increase resolution and accuracy, a suitable sampling rate
must be selected from the rotational speed of the slower shaft. The specified
minimum sampling rate was 1 Hz which correlates with a 16bit resolution
(0.0015 %) on the slower input shaft, and three times this resolution on the
faster output shaft.
4.5.2 Output Torque Transducer
A HBM T30FN industrial torque transducer was used to measure the output
torque. It is mounted between the end of the shafts holding the wheel sample
and the hydraulic dynamometer. It is specified to have a maximum torque of
2000 N.m and rotational speed limit of 10,000 RPM. The accuracy and
resolution of the transducer and associated electronics prior to data
acquisition was not specified by the manufacturer but the error bounds were
taken as ± 0.1 N.m.
Calibration of the transducer was carried out by a torque arm rigidly mounted
to the output shafts and restraining the dynamometer side of the torque
transducer. The results of the calibration and resulting regression were used to
verify that the transducer had not been damaged and the calibration correct as
the units are sold pre-calibrated.
4.5.3 Input Torque
Input torque was measured as an output from the variable frequency drive. It
is internally calculated by the variable frequency drive using the magnetic flux
density. The details of this calculation were unavailable from the
manufacturer.
121
The method used to calibrate this output was to apply known loads to the AC
motor, record the displayed value from the variable frequency drive and
acquire the analogue output data. This method relies on the AC motor having
the same characteristics as its name plate specifies. The preliminary data
gathered can be seen in Figure 59. Additional data was gathered across the
load range to verify the preliminary calibration but is not presented in Figure
59.
Further testing was carried out and was found to match the regression line
calculated from the preliminary data. The regression line coefficients are used
to adjust the output signal to torque input. The error associated with this data
was given by the manufacturers as ±5.0%.
Display % Torque vs DAQ Measured Torque
y = 67.414xR2 = 0.911
0
1000
2000
3000
4000
5000
6000
7000
0 20 40 60 80 100
% Torque
Inpu
t Tor
que
(mV)
Series1
Linear (Series1)
Figure 59 – Variable frequency drive display torque versus analogue output circuit to data acquisition system. NOTE: All values for calibration not plotted.
The variable frequency drive output was then converted to Nm using the
name plate specification of the electric motor of 22 kW at 975 RPM.
122
Input PowerInput Torque
Input Rotational Velocity= (4.3)
Substituting the values into equation (4.3) to determine the torque at 100%,
gives Equation (4.4) and the result.
22000 215Nm102.1018
ININ
IN
PTω
= = = (4.4)
The regression equation from Figure 59 is then applied at 100% input torque
to find the mV output value, then the calculated maximum input torque is
used to find the conversion between mV output and input torque giving
equation (4.5) for the analogue output signal of the variable frequency drive
(input torque).
1 mV 0.031962 Nm= (4.5)
4.5.4 Temperatures
All recorded temperatures were taken with an infra-red thermometer of fixed
emissivity (0.95). The resolution of this device is given as 0.1ºC, range of -50
ºC to 500 ºC, and accuracy of ±2%. The thermometer is calibrated at the
factory and was checked against reference thermometers and found to be
within the specified accuracy and resolution quoted.
The ambient temperature was taken from a surface of constant emissivity
close to the simulator. Bulk sample temperatures were taken through a
viewing port in the safety enclosure at a point in the centre of the track and
just prior to entry of the contact. In all cases a laser sighting system was used
to measure the same location. During testing it was observed that temperature
measurements taken while samples were stationary were reduced by
approximately 5 degrees as compared to those taken when the samples were
rotating.
123
4.5.5 Slip Calculation
The measurement of longitudinal slip is an approximation which takes into
account a number of factors, which are discussed further in Section 0 and
summarised here. The rolling diameters of the wheel and rail were taken using
contact measuring devices which have a level of precision below that required
for a high precision calculation of slip/creep (> 0.01% slip). The method used
in this thesis also cannot account for the worn rings and surface texture which
is necessary for measuring the ‘real’ diameters. Another source of error,
thermal expansion, is a factor which is difficult to account for as the thermal
profile and heat transfer system is highly variable. Thicknesses of the
remaining lubricants influenced the value of rolling diameters and therefore
the slip ratio as well.
The sampling of the rolling speeds through the encoders was taken at a 1Hz
rate. The reasoning for this is to maximise the precision of the rotational
speed ratio, close to 16bit precision (0.0015 %). The measurement point was
not taken at the same location on the rail rolling diameter, because there were
a number of rotations between each sample point; so the sampling point was
at a random location on both the rail and wheel samples.
This ‘slow’ sample rate averaged the rotational speeds during the period. The
other channels of data that were acquired stored only a single non-averaged
data value. Finding harmonic signal noise from stick slip phenomena in the
rotational speed data below a frequency of 2 Hz was impossible.
The slip ratio is calculated by Equation (4.6).
1 o ox
i i
w rw r
ξ⎛ ⎞
= −⎜ ⎟⎝ ⎠
(4.6)
iw = Rotational Speed of input shaft
ow = Rotational Speed of output shaft
124
ir = Rolling radius of input shaft
or = Rolling radius of output shaft
wIn
put
wO
utpu
t
R Input
ROutput
Figure 60 – Diagram of twin-disk arrangement with nomenclature.
At the conclusion of all testing in this research a lubricant film was present
and as such the subsequent wear rate was assumed to be negligible. The
values of radius for this research were therefore assumed to be constant
during each test.
4.5.6 Torque Measurement for Tractive Force (Shearing Force)
Tractive force in the simulator system is generated by applying a braking
torque to the output shaft. Power is transmitted from the input shaft through
the contact, then measured and controlled by the output shaft. The contact
can be a lubricant film or direct surface contact.
The output power of the shaft is limited by the transmissive characteristics of
this contact. In the case of a lubricant with zero viscosity and a film thickness
greater than the combined surface roughness, the output power would
125
approach zero. Similarly, if the surfaces of each sample could be polished
such that the coefficient of friction approached zero the output power would
also approach zero. Real systems have neither of these characteristics.
Tractive power is of interest because this power is a rolling resistance or
power loss. The level of tractive power absorbed by the lubricant before film
failure is a measure of performance of the test lubricant. The more power
absorbed by the lubricant, the less power absorbed in wear processes and
other associated losses. Quantifying power and absorbed energy may allow
for prediction of lubricant life in varying conditions.
The magnitude of the maximum tractive force and torque can be predicted
from the power characteristics of the AC motor using Equation (4.7).
x
Wheel
maximummaximum
TQr
PTω
=
= (4.7)
T = Torque
maxT = Maximum torque
maxP = Maximum power
Substituting values:22,000 65N.m
3 975 260
65N.m 1300N0.050m
maximum
x
T
Q
π= =
×⎛ ⎞×⎜ ⎟⎝ ⎠
= =
(4.8)
This maximum force and torque is a constant value for the system as these
values are directly related to the current limits in the motor and variable
126
frequency drive. These values, though, do not take into consideration any
losses.
Figure 61 – Torque component diagram for output shaft.
Losses occur in the output shaft. The total torque measured by the torque
transducer, shown in Figure 61, is the sum of the bearing friction torque and
the tractive contact torque. If we take the hypothesis that bearing friction is
negligible compared to the tractive torque then the tractive torque is equal to
the measured torque. Mathematically, torque is formulated using the Equation
(4.9).
T C BFT T T= − (4.9)
BFT = Bearing friction torque
CT = Transmitted torque through contact patch
TT = Torque transducer torque
127
The hypothesis is null if bearing friction torque is greater than 5% of
measured torque. The worst conditions of maximum tread load and
minimum braking torque are calculated using Equation (4.10).
T
o
F PTe Pr
μ
μ
=
× = × (4.10)
F = Friction force
e = Proportion of total value
Substituting values into the equation gives a coefficient of friction of 0.001.
This value is typical for the needle rollers used in the wheel head assembly
(Bailey and Association of Iron and Steel Engineers. 1996). Therefore at the
selected level of 5% of the measured torque the hypothesis is valid and
bearing friction can be ignored. Extrapolating from this hypothesis, it is then
reasonable to assume that the torque or shearing force experienced by the
contact patch is that of the measured torque.
4.5.7 Rail Flange Contact Conditions
The in-service flange contact is a highly variable contact as its location on the
wheel is variable. Its size can vary according to rail profile and/or wheel
profile from a point contact to a full conformal contact.
When the case of a two point contact for a wheel is considered, there is one
point on the tread surface and another point on the flange surface. The
contact ellipse on the tread is a rolling/sliding contact, with a dominant rolling
mode. The contact ellipse on the flange is a rolling/sliding contact with a
larger sliding component caused by the difference in the rolling radius to the
tread contact.
128
0 10 20 30 40 50 60 70 80 90 1000
0.5
1
1.5
2
2.5
Rolling Velocity (km/hr)
Slid
ing
Vel
ocity
(m/s
)Rolling Velocity Vs Maximum Flange Sliding Velocity
Wheel Diameter = 600mmFlange Height = 25mm
Figure 62 - Maximum flange sliding velocity for a typical commuter train wheel diameter (600mm).
Figure 62 and Figure 63 show the relationship of maximum theoretical flange
velocity versus rolling velocity for a commuter train wheel and heavy haul
wheel respectively. These charts are presented to allow comparison between
field and simulated conditions. The figures are calculated with Equation (4.11)
using geometry of typical rolling stock used in the Queensland Rail network.
Wheel rotational velocity (rad/s)
Rolling Tread
Sliding Tread Flange
Sliding
v r
v r r
v r
ωω ωω
ω
=
= −
=
=
(4.11)
129
0 10 20 30 40 50 60 70 80 90 1000
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
Rolling Velocity (km/hr)
Slid
ing
Vel
ocity
(m/s
)
Rolling Velocity Vs Maximum Flange Sliding VelocityWheel Diameter = 860mm
Flange Height = 25mm
Figure 63 - Maximum flange sliding velocity for a typical heavy haul train wheel diameter (860mm).
4.5.8 Normal Load
The normal load was measured with a diaphragm load cell. The diaphragm is
located between the pneumatic ram and the sample holder and is only capable
of measuring compression force. Two factors affect the accuracy and
resolution of the measurements from the load cell. Firstly some proportion of
force is lost or gained due to friction between sample holder and simulator
frame as previously discussed in Section 4.2.2, and secondly the non-linearity
of the load cell introduces an error as the calibration assumes a linear
response.
Measurement of the linearity of the load cell was carried out using a reference
load cell attached to a load cell amplifier of known characteristics (Yokogawa
oscilloscope). The reference load cell was verified against a calibrated
130
Hounsfield materials testing device prior to testing and its calibration results
are shown in Figure 64.
Reference Load Cell Calibration Curve
y = 0.0951xR2 = 0.9996
0
200
400
600
800
1000
1200
0 2000 4000 6000 8000 10000 12000
Load (N)
mV
Figure 64 – Reference load cell calibration curve or output strain versus input load as applied by calibrated materials testing device.
y = 1.0644x + 67.696R2 = 0.9954
0
200
400
600
800
1000
1200
0 200 400 600 800 1000 1200
Reference Cell (mV)
Nor
mal
Loa
d D
iaph
ragm
(mV)
Figure 65 – Normal versus Reference load cells calibration curve.
The result of the calibration testing, for the load cell, is shown in Figure 65. It
can be seen in both calibration figures that the regression correlation statistics
131
are high. Also of note is the offset voltage (67.7 mV) in the diaphragm load
cell, whereas the reference load cell does not have such an effect, 0 mV was
equal to 0 N.
4.6 Measurement Errors
The relative errors in each of the measurements have been discussed in the
previous section. This section will discuss the method used for error
propagation and the assumptions used in calculating results.
4.6.1 Thermal Expansion of Test Samples
The rail and wheel samples increase and decrease in size with respect to
temperature arising from frictional energy absorbed by the system. Predicting
the effect of thermal expansion on rolling diameter is important in order to
make an accurate prediction of slip/creep.
If a rail sample is considered as a thin hollow cylinder which is then unrolled
to a single length, it is possible to use the linear thermal expansion Equation
(4.12).
0
11 m/m C
l
l
l Tl
α
α μ
Δ = Δ
= ° (4.12)
lΔ = Change in length
0l = Original length
lα = Linear thermal expansion coefficient
Substituting experimental values gives Equation (4.13):
132
0.44mm @ 400.44 0.14mm
300mm 0.14mm0.05%
l T C
φπ
φφ φ
Δ = Δ = °
Δ = =
= ±= ±
(4.13)
TΔ = Change in temperature
φ = Diameter
Checking the linear thermal expansion assumption using the volume thermal
expansion with Equation (4.14) may provide a more rigorous value for the
change in sample diameter.
0
333 m/m C
V
V l
V
V TV
α
α αα μ
Δ = Δ
= ×= °
(4.14)
VΔ = Change in volume
0V = Original volume
Vα = Volume thermal expansion coefficient
The rail sample remains approximated as a cylinder and the volume is
calculated using Equation (4.15).
( )2 20 o i tr r tV π π= − (4.15)
tt = Thickness
Assuming that all the thermal expansion is in the radial direction, the worst
case, and the internal radius is constant, Equation (4.16), for heated volume
can be used.
133
( )( )2 2H o o iV r r r tπ π= + Δ − (4.16)
HV = Volume when heated
Rearranging and solving for the increase in radius for experimental conditions
gives Equation (4.17):
( )2 2
0.04mm2
300 0.08mm0.03%
o o o
o
o
V t r r r
rr
π
φ φφφ φ
Δ = Δ + Δ
Δ == ± Δ= ±= ±
(4.17)
The volume expansion method gives a slightly lower value of error, therefore
the linear expansion solution will be used in this thesis to predict the error.
4.6.2 Energy dissipation methods
Lubricant performance is measured in Chapter 5 as the power absorbed by
the lubricant film. The power measurement, dissipated power, is the
measured difference between the input and output power and subtracting any
extra power losses with the remaining power assigned to the effects of the
lubricant film. Power is dissipated in the simulator system by a number of
processes. The power dissipation of interest is that related to wear processes,
which is energy dissipated through sliding (frictional energy).
The sources of energy loss in the system are:
Frictional sliding at the contact interface
Friction in rolling bearings of sample holders
Noise from system
Electrical losses in variable frequency drive
Electrical losses in AC motor
134
Mechanical losses in AC motor
Thermal losses
Wear of rail/wheel test samples
In order to estimate the frictional sliding, some assumptions must be made
about the manner in which the remaining losses affect the system. All losses
associated with the input system will be assumed to be constant for a given
speed during the lubricated testing. The mechanical losses are considered to
be the most significant for this part of the system as they are directly related
to the rotational velocity, which for the input is fixed for any given test.
0 200 400 6002000
2500
3000
3500
4000Input Power vs Time
Time (s)
Pow
er (W
)
0 200 400 600-500
0
500
1000
1500
2000
2500Output Power vs Time
Time (s)
Pow
er (W
)
0 200 400 6000.05
0.1
0.15
0.2
0.25Slip % vs Time
Time (s)
Slip
(%)
0 200 400 600
1500
2000
2500
Power Dissipated vs Time
Time (s)
Pow
er (W
)
Figure 66 - Power versus Time graphs for warm-up prior to testing. Data presented has not been pre-processed.
The output shaft rotational velocity is variable throughout the test. Any
power loss that is dependent on velocity will also be variable. The friction
coefficient for the fully lubricated needle roller bearings is predicted to be at
least an order of magnitude smaller than the fully lubricated testing surface.
135
Therefore the bearing frictional power loss is assumed to be a negligible and
in constant proportion to the sliding frictional energy.
In Figure 66(left upper) the input power can be seen to reduce with respect to
time in sections of the curve with (Time > 180 s) and without braking torque
(Time < 180 s). The same can be observed for the output power, Figure
66(right upper) but is more difficult to observe from the signal noise. Slip
percentage in Figure 66(left lower) displays the same decay effect as the power
measurements. It can also be observed that with the application of tractive
force there is a corresponding increase of measured slip (Time > 180 s), in
accordance the theoretical calculations of Section 0.
Figure 66(right lower) is the most important chart and display the power
absorbed by the system in processes not attributable to a lubricant film, as in
the presented test none was applied. The power absorbed by the system is not
influenced by the application of an increased braking torque (shearing force)
but decays with time to a minimum value. This minimum value was
subtracted from the measured power losses in the lubricated testing to leave
the remaining power as that absorbed by the lubricant film.
The decay effect, observed in Figure 66, is used to predict the final values of
slip and power in the presentation of test results and will be discussed further
in Section 0.
4.6.3 Slip From Lubrication Measurements (Zero slip predictions)
The measured slip in the lubricated testing is composed of two components,
the micro-slip from the contact conditions, and the slip from the applied
lubricant. Isolating the slip due to lubrication requires removal of the micro-
slip component, which the method presented in this section has achieved.
Preceding each group of lubricated tests, there was a period of warm-up to
establish consistent operating conditions. This warm-up is divided into two
distinct periods, the first with no applied braking torque and the second with
136
the set braking torque. The braking torque for the lubricated tests was set
during the warm-up period and fixed for all the following tests in a particular
group to ensure consistency.
0 50 100 150 200 250 3000
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Time (s)
Slip
(%)
Slip Vs TimeNormal Force: 5 kN
Braking Force: 0.28 kN
No Applied TorqueBraking Torque Applied
Figure 67 – Slip versus time for the two defined warm-up periods of zero and set braking forces.
In Figure 67 each of the warm-up periods is plotted separately rather than
consecutively, as occurs in the experiment. It can be observed from the graph
that there is decay in slip to some nominal level with each of the applied
torques.
In the work of Johnson (1985) the micro-slip or creep, as seen experimentally
in Figure 67, is presented as an effect of material elasticity in tractive rolling
contact. This type of unlubricated slip/creep is the result of surface strains
caused by the normal and tangential forces on the contact and is predicted by
Johnson (1985) in equation (4.18).
137
12{1 (1 ) }x
xQa
R Pμξ
μ−= − − (4.18)
Johnson also defines the limits of micro-slip to be Equation (4.19):
1 and 1x xR Qa P
ξμ μ
< < (4.19)
In the case of the simulator, the variable frequency drive and braking system
are incapable of achieving the required tractive force to exceed the upper
micro-slip limit in Equation (4.19). Using Johnson's method the observable
slip percentage is predicted for the warm-up loading conditions in Figure 67
and calculated to be 0.017%. The calculated value is at the resolution limit of
measurable slip.
The importance of this value is not in its absolute value but in applying a
suitable equation to predict the stabilised value of slip in the lubricated testing.
The value of predicted minimum slip is subtracted from the measured values
in the presentation of results for the lubricated testing in Chapter 5.
4.7 Lubricant Performance Measures Error Analysis
The magnitudes of errors in each measurement are presented here for the
purpose of checking recorded experimental variability against measurement
errors. These values will be used to interpret the validity of the experimental
method and the presented data in Chapter 5. Equation (4.20) will be used to
calculate the errors from all results calculated from measured values
138
( )1
2 2 2
, ,....
....
Result Predicted error
, ,... Input parameters, ,... Errors in input parameters
R f A B
R RR A AA A
RR
A BA B
=
⎡ ⎤⎛ ∂ ⎞ ⎛ ∂ ⎞⎛ ⎞ ⎛ ⎞Δ = ∂ + ∂ +⎢ ⎥⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟∂ ∂⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠⎢ ⎥⎣ ⎦=
Δ ==
∂ ∂ =
(4.20)
Calculation of the estimated total error for each of the lubricant performance
criteria is important to ensure that the error does not overwhelm the
measurement.
The rotational speed and the estimated error are calculated using Equation
(4.21). The maximum error in the count measurement is 1 count and the
sample frequency error (5.0E-8 Hz) is assumed to be negligible.
25400
2 0.00116 radians/sec
5400
counts
wsample frequency
w
π
π
⎛ ⎞⎜ ⎟⎝ ⎠=
∂ = =
(4.21)
w = Rotational Speed
w∂ = Error in rotational speed
The surface velocity and the estimated error are calculated using Equation
(4.22).
2 2
v wr
v vv w rw r
=
⎛ ∂ ⎞ ⎛ ∂ ⎞⎛ ⎞ ⎛ ⎞∂ = ∂ + ∂⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟∂ ∂⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠
(4.22)
v = Surface velocity
139
v∂ = Error in surface velocity
r = Rolling radius
r∂ = Error in rolling radius
Using the values in Table 13 and Equation (4.22) the error in surface velocity
was calculated for the rail and wheel test pieces and presented in Table 14.
Variable Value Variable Error Value iw 39.813 rad/s
iw∂ 0.001 rad/s
ow 120.851 rad/sow∂ 0.001 rad/s
ir 148.10 mm ir∂ 0.005 mm
or 48.605 mm or∂ 0.005 mm
Table 13 - Values for experimental error calculation of surface velocities for Group 1 test parameters. Subscripts refer to input and output shafts.
Measurement error in surface velocity is small compared to the variation in
velocity experienced by a wheel in the field.
Variable Value Variable Error Value iv 5.8963 m/s
iv∂ 0.0003 m/s
ov 5.8739 m/sov∂ 0.0006 m/s
Sv 5.8963 m/sSv∂ 0.0007 m/s
Table 14 - Values for experimental error calculation of surface velocities for Group 1 test parameters. Subscripts refer to input and output shafts.
Sliding velocity is the difference between the input and output velocities and
is given by Equation (4.23) and the error presented in Table 14.
( ) ( )2 2
s i o
s i o
v v v
v v v
= −
∂ = ∂ + ∂ (4.23)
140
,s su v = Sliding velocity
sv∂ = Error in sliding velocity
The slip ratio and the estimated error are calculated using Equation (4.24).
12 2 2 2 2
2 2
1
; ; ;
o o
i i
o i o io i o i
o o o o o o
o i i i i i o i i i i i
w rw r
w w r rw w r r
r w r w w rw w r w w r r w r r w r
ξ
ξ ξ ξ ξξ
ξ ξ ξ ξ
⎛ ⎞= −⎜ ⎟⎝ ⎠
⎡ ⎤⎛ ⎞ ⎛ ⎞ ⎛ ⎞ ⎛ ⎞⎛ ⎞ ⎛ ⎞ ⎛ ⎞ ⎛ ⎞∂ ∂ ∂ ∂⎢ ⎥Δ = ∂ + ∂ + ∂ + ∂⎜ ⎟ ⎜ ⎟ ⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟ ⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟ ⎜ ⎟ ⎜ ⎟∂ ∂ ∂ ∂⎢ ⎥⎝ ⎠ ⎝ ⎠ ⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠ ⎝ ⎠ ⎝ ⎠⎣ ⎦∂ ∂ ∂ ∂= − = = − =∂ ∂ ∂ ∂
(4.24)
Variable Value Variable Error Value iw 39.813 rad/s
iw∂ 0.001 rad/s
ow 120.851 rad/sow∂ 0.001 rad/s
ir 148.10 mm ir∂ 0.005 mm
or 48.605 mm or∂ 0.005 mm
Table 15 - Values for experimental error calculation of slip ratio for Group 1 test parameters. Subscripts refer to input and output shafts.
Using Equation (4.24) and the values of variables in Table 13 the
experimental error in slip ratio is predicted to be 1.11E-4 or presented as slip
percentage 0.011%. This value is small compared to the experimentally
recorded slip ratio, and gives confidence to the prediction of slip and to the
measurement of sliding speeds and distances.
Using the error prediction of 0.05% in diameter, from the thermal expansion
calculations, in addition to the measurement error presented in Table 15 the
drift or error in slip ratio with respect to temperature can be calculated. The
predicted experimental error becomes larger at 0.065%. In the high slip part
of each test the frictional energy from sliding is converted to heat, which
expands the test pieces (see Figure 68 for time less than 600 seconds). Energy
141
lost to convection, from the test pieces in the testing region of high slip, is less
than the energy from friction absorbed by the test pieces. Subsequently the
temperatures of the test pieces rise. In the region of lower slip the
temperature of the wheel sample begins to approach that of the rail sample
from the convection coefficient increasing as a result of the increasing rolling
speed. As the surface velocities approach one another the convection
coefficients approach one another and the temperatures of both samples
approaches the temperatures of the unlubricated test.
0 100 200 300 400 500 600 700 800 900 10000
10
20
30
40
50
60
70
80
90
100
Time (s)
Tem
pera
ture
(o C)
0 100 200 300 400 500 600 700 800 900 10000
10
20
30
40
50
60
70
80
90
100
Slip
(%)
Slip %
Wheel TemperatureRail Temperature
Figure 68 – Test sample temperatures and Slip versus time for Group 1 Lubricant A Test 1.
If the temperatures of the test pieces in the lubricated testing match that of
the unlubricated testing then the predicted slip will have the error from the
thermal expansion of the samples removed. Therefore at the high slip region
where the error in slip measurement is greatest the absolute error is small in
proportion to the measured value. Also at the low slip region where the
142
measured value of slip is small the error from thermal expansion is also small
approaching that of a constant temperature test.
The next step in the measurements is determination of the errors in the input
and output power results using Equation (4.25) and Table 16.
2 2
Power Torque w
Power PowerPower Torque wTorque w
= ×
⎛ ⎞⎛ ⎞∂ ⎛ ∂ ⎞⎛ ⎞∂ = ∂ + ∂⎜ ⎟⎜ ⎟ ⎜ ⎟⎜ ⎟∂ ∂⎝ ⎠⎝ ⎠⎝ ⎠⎝ ⎠
(4.25)
Variable Value Variable Error Value
iT 88.8 N.miT∂ 0.1 N.m
oT 14.8 N.moT∂ 0.1 N.m
Table 16 - Values for experimental error calculation of surface velocities for Group 1 test parameters. Subscripts refer to input and output shafts.
The errors for power in Table 17 show that the smaller diameter and lower
torque of the output shaft increase the magnitude of the error as compared to
the input power. It is however less that 1% of the measured value of output
power and correspondingly the power values for both input and output can
be assumed valid.
Variable Value Variable Error Value iP 3535 W
iP∂ 4 W (0.1%)
oP 1788 W oP∂ 12 W (0.7%)
Table 17 - Values for experimental error calculation of input and output power for Group 1 test parameters. Subscripts refer to input and output shafts.
The distance travelled by each sample is calculated using Equation (4.26) but
for the purposes of error calculation the sample time term is assumed to have
143
no error as in the rolling velocity calculations. Removing the sample time term
(constant for all tests as 1 second) gives Equation (4.22) with distance
travelled equal to the magnitude of the velocity term, with the same level of
error presented in Table 18.
D wrt= (4.26)
D = Distance rolled
D∂ = Error in distance rolled
Variable Value Variable Error Value
iD 5.8963 miD∂ 0.0003 m
oD 5.8739 moD∂ 0.0006 m
Table 18 - Values for experimental error calculation of distance rolled for Group 1 test parameters. Subscripts refer to input and output shafts.
Using all of the calculated parameters for the input and output shafts the
effects of the lubricant film can be isolated. Prior to testing the simulator was
used under unlubricated conditions to gather baseline data. The baseline data
was then removed from the lubricated testing to give only the results assigned
to the lubricant. Any errors in the prediction of the baseline values to be
subtracted from the lubricated testing results were constant for all lubricants
in a particular group.
An issue for lubricant performance measurement error analysis is that the
baseline data between groups is not consistent from the different test
parameters and can limit test group comparisons. Investigation of this
parameter yielded no conclusive results as to the errors in baseline data
between groups, but the baseline data applied to each of the nine tests in a
group were checked for inconsistencies and none were found. Therefore
comparisons between test groups are assumed to be valid.
144
The lubricant film performance criteria of distance slid is calculated using
Equation (4.27) and the values from Table 18
( ) ( )2 2
s i o
s i o
D D D
D D D
= −
∂ = ∂ + ∂ (4.27)
iD = Distance rolled of input shaft
iD∂ = Error in distance rolled of input shaft
oD = Distance rolled of output shaft
oD∂ = Error in distance rolled of output shaft
sD = Distance slid
sD∂ = Error in distance slid
Power absorbed by the lubricant film is calculated similarly to the distance
slid. The difference in power between the input and output shafts minus the
power absorbed by friction in the simulator is defined as power absorbed.
The power absorbed by friction is a constant, calculated from the
unlubricated data, and will not be included in the error analysis.
( ) ( )2 2
s i o f
s i o
P P P P
P P P
= − −
∂ = ∂ + ∂ (4.28)
iP = Power of input shaft
iP∂ = Error in power of input shaft
oP = Power of output shaft
oP∂ = Error in power of output shaft
145
sP = Power absorbed by lubricant
sP∂ = Error in power absorbed by lubricant
fP = Power absorbed by friction in simulator
The values of error in the results of distance slid and power absorbed due the
lubricant film are small and presented in Table 19.
Variable Value Variable Error Value SD 5.8963 m
SD∂ 0.0007 m
SP 600 W SP∂ 13 W (2.1%)
Table 19 - Values for experimental error calculation of distance slid and power absorbed for Group 1 Lubricant A Test 1 results.
Energy at each time step is calculated using Equation (4.29) with the
measurement error taken as the same error as for power. This is valid as the
error in the time variable is negligible.
E Power t= × (4.29)
E = Absorbed energy
E∂ = Error in absorbed energy
The cumulative measurement errors will be calculated using Equation (4.30)
146
( )
( )
1
2
measured value sum of measured value
error in measured value
n
f x x
ff n xx
f x nxf xx
=
⎛ ∂ ⎞⎛ ⎞∂ = ∂⎜ ⎟⎜ ⎟∂⎝ ⎠⎝ ⎠
∂ = ∂=
=∂ =
∑
(4.30)
The two cumulative lubricant performance criteria of total absorbed energy
and total slid distance are calculated using Equation (4.31) and Equation
(4.32) .
1
2
n
T s
TT s
s
T s
E E
EE n EE
E E n
=
⎛ ⎞⎛ ⎞∂∂ = ∂⎜ ⎟⎜ ⎟⎜ ⎟∂⎝ ⎠⎝ ⎠
∂ = ∂
∑
(4.31)
sE = Sliding energy
sE∂ = Error in sliding energy
TE = Total Absorbed energy
TE∂ = Error in absorbed energy
n = Number of measurements
1
2
n
T s
TT s
s
T s
D D
DD n DD
D D n
=
⎛ ⎞⎛ ⎞∂∂ = ∂⎜ ⎟⎜ ⎟⎜ ⎟∂⎝ ⎠⎝ ⎠
∂ = ∂
∑
(4.32)
147
sD = Distance slid
sD∂ = Error in distance slid
TD = Total distance slid
TD∂ = Error in total distance slid
It is important to note that the errors for the cumulative lubricant
performance criteria are affected by the number of summed values. The larger
the number of values the smaller the relative error, but the larger the absolute
error. Therefore the errors presented in Table 20 are the maximum for all
Group 1 tests.
Variable Value Variable Error Value TD 2850 m
TD∂ 0.02 m
TE 37740 JTE∂ 330 J (0.9%)
Table 20 - Values for experimental error calculation of distance slid and power absorbed for Group 1 Lubricant A Test 1 results.
Apparent viscosity, as discussed in Section 0, is the relationship between shear
stress and shear rate, see Equation (4.33).
τηγ
=&
(4.33)
Shear stress is defined in Equation (4.34) using the measured shear force and
the predicted contact area and the error defined in Equation (4.35). Shear
strain is the ratio between sliding speed and lubricant film thickness given
with its equation for error in Equation (4.36) Predicted contact area and
lubricant film thickness, CA and y , are calculated values and will be assumed
to have no error. The errors presented in this section are for measured values
only.
148
oBT
C o C
TFA r A
τ = = (4.34)
2 2
2 2
2
1
o oo o
oo o
o C o C
T rT r
TT rr A r A
τ ττ
τ
⎛ ⎞ ⎛ ⎞⎛ ⎞ ⎛ ⎞∂ ∂∂ = ∂ + ∂⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟∂ ∂⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠
⎛ ⎞ ⎛ ⎞⎛ ⎞ ⎛ ⎞∂ = ∂ + ∂⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟⎜ ⎟ ⎜ ⎟⎝ ⎠ ⎝ ⎠⎝ ⎠ ⎝ ⎠
(4.35)
S
S
vy
v
γ
γ
=
∂ = ∂
&
&
(4.36)
Variable Value Variable Error Value oT 14.8 N.m
oT∂ 0.1 N.m
or 48.605 mm or∂ 0.005 mm
CA 2.54 E-5 m^2CA∂ 0 m^2
Sv 5.8963 m/s Sv∂ 0.0007 m/s
Table 21 - Values for experimental error calculation of surface velocities for Group 1 test parameters.
The magnitudes of measurement error in shear stress, shear strain and
apparent viscosity are small, see Table 22. It is important to note that these
values are only the measurement errors and do not take into consideration the
errors involved in predicting the contact area and lubricant film thickness. Of
these two parameters lubricant film thickness is of most concern as its
magnitude has the greatest influence on the calculation of shear stress and
subsequently apparent viscosity.
Assigning an error to the film thickness of 1 μ m (approximately 30% of the
film thickness), increases the predicted error in apparent viscosity from 0.005
Pa.s to 2 Pa.s. The absolute measurement of apparent viscosity then has an
error of 30% associated with it. This high level of error is not representative
149
however as can be observed in Table 22. The measured values are high
resolution with low associated errors. It is beyond the scope of this thesis to
investigate lubricating grease film thickness, but it is important to be aware of
the issues involved in predicting apparent viscosity
Variable Value Variable Error Value τ 12.009 MPa τ∂ 0.008 MPa γ& 1.66 E6 1/s γ∂ & 0.0007 1/s η 7.23 Pa.s η∂ 0.005 Pa.s
Table 22 - Values for experimental error calculation of apparent viscosity, shear stress and shear ratefor Group 1 test parameters.
The values of error in this section are not absolute for all tests. The errors
presented are calculated for a specific test in Group 1 but are typical for all
the Groups.
4.8 Summary
Details of the modifications to the experimental device have been presented,
highlighting the need for modifications and improvements to achieve the
objective to quantify rail curve lubricant performance through laboratory
simulation. Temperature of the rail/wheel simulator can be regulated with the
installation of the plate heat exchanger to improve simulation conditions.
Loading of the test samples has been modified with pneumatic rams to
improve simulation by applying a more constant force. Data acquisition has
been modified and improved across all measurements especially in the area of
slip measurement. High resolution slip measurements were attainable using
the newly installed shaft encoders for measuring lubricant film decay. Tractive
force control was achieved through the installation of a hydraulic
dynamometer.
Investigations of the performance capabilities of the rail/wheel simulator
prior to the lubricant analysis were presented detailing the wear characteristics
of newly machined samples. The wear encountered was found to match that
150
of in-service conditions. Additional issues with the wheel sample holder were
found and rectified which improved the simulation capability of the
rail/wheel simulator.
The commissioning results were then used to develop a suitable testing
protocol for investigation of rail curve lubricant performance. Presented in
the testing protocol section were the material properties of the rail and wheel
test samples for inspection of the chemical compositions and presentation of
the strength characteristics for interpreting the contact mechanics results of
Chapter 3.
Methods for the measurement of the variables of interest were then
presented. Rotational speed was measured with shaft encoders for the
purpose of measuring rolling velocity, sliding velocity and slip ratio. Output
torque was measured with a torque transducer in the hydraulic dynamometer
system for calculating output power, shear force, shear stress and power
absorbed by a lubricant film. The variable frequency drive on the input shaft
was used to measure input torque, for calculating input power and power
absorbed by a lubricant film. Temperatures of the rail and wheel samples
were measured during testing using a hand held infra red thermometer.
Normal load, important for calculating the stress distribution of the contact
between rail and wheel samples, was measured using a calibrated force
transducer.
Experimental methods and procedures have been outlined prior to the
presentation of the limitations in these measurements. Thermal expansion of
the rail and wheel samples was explored with reference to the changes in
measured slip conditions. The findings were that during the periods of
maximum thermal expansion the relative magnitude of the error in diameter
measurement is small and at test completion where the magnitude of slip is
small, the error was also small. Next the limitation in the measurement of
output torque due to frictional losses was calculated and found to be
151
negligible. The effects of lubrication were then isolated from the measured
values of absorbed power and slip by measuring and calculating the
unlubricated system responses across all tested parameters.
The final part of Chapter 4 presents the measurement errors to highlight the
improvements made to the rail/wheel simulator when comparing to standard
twin disk simulators. The levels of measurement error calculated for all
lubricant performance criteria give confidence to the lubricant performance
results. The next chapter will present the results from the discussed method
including standards based lubricant testing results.
152
C h a p t e r 5
PERFORMANCE MEASUREMENT OF RAIL CURVE LUBRICANTS
5.1 Introduction
The current chapter presents the results of lubricant testing with the focus on
the thesis objective; to quantify rail curve lubricant performance through
laboratory simulation
The first part of the chapter will outline the lubricant performance
measurement method using the Group 1 data set. The remainder of the
chapter discusses the results of the lubricant testing and the relevance to the
optimisation of rail/wheel lubrication.
5.2 Testing Variables
The experimental results were taken from four tests (sets of parameters),
referred to as groups. The first group, Group 1, was taken as a reference then
each of the input variables of normal force, braking torque and rolling speed
changed individually. Each group investigates the effect of a single input
variable change and is detailed in Table 23. In addition to the three input
parameters the stress from the normal force and the shearing force are
presented.
Group Number
Normal Force (N)
Compressive Stress (MPa)
Braking Torque (N.m)
Shearing Stress (MPa)
Rolling Speed (m/s)
1 9500 480 15 12 6 2 9500 480 15 12 3 3 9500 480 30 24 6 4 12500 550 15 12 6
Table 23 – Testing variable values.
In each group three different rail curve lubricants were tested. Lubricants A
and B were lithium complex greases with mineral oil and solid lubricants.
153
Lubricant C was an aluminium complex grease with mineral oil and solid
lubricants.
5.3 Unlubricated System Steady State Values
In order to isolate the effect of lubrication on the system, steady state values
for the recorded data need to be predicted or measured. The parameters of
interest are the power absorbed by the system as discussed in Section 4.6.2
and the minimum attainable slip. Subtracting the values of system power and
minimum slip, predicted from unlubricated conditions, from the
measurements under lubricated conditions gives only the measurement
attributable to the lubricant film. Prior to the prediction of the equilibrium
values all data was filtered through a five point moving average filter. The
filter was applied to identify linear trends in the collected data. The level of
filtering was selected to minimise data corruption from the filter and to
maximise the appearance of performance trends.
Power losses not directly attributable to the lubricant film are estimated. The
process for this estimation was to plot the power loss curve for unlubricated
test conditions, with the same testing variables as the lubricated tests. Decay
in the measurements of power and slip were assumed to have an exponential
function. Regression was carried out on the data using Equation (5.1) to find
the steady state power loss:
( )( ) Power loss
Time Steady state power lossAmplitude of the exponential
Exponential coefficient
bxf x ae c
f xxcab
−= +
=====
(5.1)
The steady state power loss was then subtracted from the total power loss
measured in lubricated testing to give the losses associated with the lubricant
film in the contact. Figure 69 shows the exponential regression fitted to the
154
non-lubricated Group 1 conditions. Minimum power loss values for all
groups are presented in Table 24. The residuals of the regression analysis were
tested with a Lilliefors normality test at a 5% significance level and found to
be normally distributed.
0 50 100 150 200 250 300-100
-50
0
50
100
Time (Seconds)
Pow
er (W
atts
)
Residuals
0 50 100 150 200 250 3001850
1900
1950
2000
2050
2100
2150
Time (Seconds)
Pow
er (W
atts
)
Data and Fits
Absorbed PowerExponential Decay
Residuals of Exponential Decay
Figure 69 – Exponential decay curve fitted to power loss data for Group 1 conditions.
A similar process was applied to the slip data to determine the minimum
attainable slip. The value for minimum attainable slip was theoretically
calculated using the method of Johnson (1985) but experimentally the
minimum attainable slip was found to differ from this value. The results of
this test for Group 1 conditions are shown in Figure 70. The values used in
lubricant performance analysis in each group are detailed in Table 24. The
residuals of the regression analysis of slip in Figure 70 were tested with a
Lilliefors normality test at a 5% significance level and found to be normally
distributed. In addition, a harmonic can be observed in the residuals with a
long period and amplitude of 2.5% of the signal. The source of the harmonic
is as yet unidentified.
155
0 50 100 150 200 250 300-2
-1
0
1
2
3x 10-3
Time (Seconds)
Slip
(%)
Residuals
0 50 100 150 200 250 3000.15
0.155
0.16
0.165
0.17
Time (Seconds)
Slip
(%)
Data and Fits
SlipExponential Decay
Exponential Decay
Figure 70 – Exponential decay curve fitted to slip data for Group 1 conditions.
The large difference in minimum slip values for Group 2 and 4 when
compared to Group 1 and 3, as observed from the error analysis in Section
4.7, is from the measurement of sample diameters.
Group Number Minimum power loss (Watts) Minimum slip (%) 1 1466 0.15 2 836 0.02 3 1734 0.15 4 1667 0.03
Table 24 – Extrapolated minimum values from experimental data.
5.3.1 Lubricant Film Decay Half-Life Prediction
The performance decay of lubricants is of interest for two purposes, first to
predict reapplication rates and second to predict the lubricated distance from
a lubricant application point. In this thesis the decay will be measured from
the slip measurement, following the system reaching the set shear stress value.
156
The x axis data (time) was normalised using the mean and standard deviation
to improve the accuracy of regression analysis results using Equation (5.2).
( )ˆ
ˆ normalised values values mean of standard deviation of
x xx
xxx x
x
σ
σ
−=
====
%
%
(5.2)
Regression was carried out on the slip data using Equation (5.3).
( )( ) Variable of interest
Time Amplitude of the exponential Exponential coefficient Minimum value of variable of interest
bxf x ae c
f xxabc
−= +
=====
(5.3)
The time for slip performance to degrade by 50% or half life was then
calculated with Equation (5.4) (Giancoli 1988).
( )ln 2
half lifebσλ
λ
=
= (5.4)
5.4 Input Data Variability
The three input parameters were analysed for discrepancies between tests
within a group to ensure consistent input parameters. The normal load, input
rolling velocity and fully developed braking torque for Group 1 are presented
in Figure 71, Figure 72 and Figure 73 respectively.
The box and whisker plots have lines for lower quartile, median and upper
quartile values. The whisker lines are 1.5 times the inter-quartile range with
any values outside the whiskers marked with a cross as an outlier.
157
9200 9300 9400 9500 9600 9700 9800 9900 10000
Lubricant A Test 1
Lubricant A Test 2
Lubricant A Test 3
Lubricant B Test 1
Lubricant B Test 2
Lubricant B Test 3
Lubricant C Test 1
Lubricant C Test 2
Lubricant C Test 3
Normal Force (N)
Figure 71 – Box and whisker plot of normal force for each of the tests in Group 1.
The normal force in Figure 71 has a high variability which is the results of two
noise components, dynamic loading and thermal expansion effects, which is
discussed later in section 5.4.1. Dynamic loading is accounted for in the
calculations of lubricant performance by using the measured value rather than
the nominal value.
In Figure 72 for rolling velocity, the tests for Lubricant C highlighted the
difficulty in speed control from the variable frequency drive by the large
number of outliers in Test 2 and 3. The longer test times of Lubricant A and
B allowed the speed controller to more closely track the changing loading
conditions experienced. In practical terms the variability in velocity is less than
0.1km/hr (0.02m/s) and was considered to be negligible.
Variability in the output torque in Figure 73 is the result of the lubricant film
continuing to decay as the lubricated test progressed.
158
5.85 5.86 5.87 5.88 5.89 5.9
Lubricant A Test 1
Lubricant A Test 2
Lubricant A Test 3
Lubricant B Test 1
Lubricant B Test 2
Lubricant B Test 3
Lubricant C Test 1
Lubricant C Test 2
Lubricant C Test 3
Rolling Speed (m/s)
Figure 72 – Box and whisker plot of input rolling velocity for each of the tests in Group 1.
12 12.5 13 13.5 14 14.5 15 15.5 16
Lubricant A Test 1
Lubricant A Test 2
Lubricant A Test 3
Lubricant B Test 1
Lubricant B Test 2
Lubricant B Test 3
Lubricant C Test 1
Lubricant C Test 2
Lubricant C Test 3
Output Torque (N.m)
Figure 73 – Box and whisker plot of braking torque under fully developed conditions for each of the tests in Group 1.
159
5.4.1 Tread Load Temperature Dependence
The tread load data was tested with a Lilliefors normality test and found not
to be normally distributed, even at a 20% significance level. The cause of this
non-normal load distribution is most likely the effect of frictional heat
absorption. The wheel and rail samples expand with temperature which
applies a larger load. The wheel sample holder appears to not move in
proportion with the thermal expansion. The friction forces in the normal
loading pneumatic ram and the contact surfaces of the wheel sample holder
may prevent the load from reducing back to the set value.
0 100 200 300 400 500 600 700 800 900 100020
40
60
80
Tem
pera
ture
(° C)
Time (secs)0 100 200 300 400 500 600 700 800 900 1000
9600
9800
Nor
mal
Loa
d (N
)
WheelRail
Normal Force
Figure 74 - Normal force and bulk sample temperature versus time for Group 1 Test 1 Lubricant A.
Figure 74 shows the temperature and normal load curves for a single test
sample in which the dependence of normal load on sample temperature is
observed by the matching curves. In the tests where full traction force was
reached quickly, it was impossible to gather enough temperature
measurements to verify this hypothesis. However, monitoring of the
160
temperatures showed the same trends, and inspecting the gathered tread
loading data post test, verified the findings of temperature versus tread load
interaction.
The slight (~2%) increase in normal force during testing was taken into
consideration during results analysis by using each normal force data point
separately, rather than a mean value.
5.5 Rail/Wheel Simulator Results
The results for each group are divided into two sections. The division is
created by separating all results above and below the in-service slip limit of
5% also approximately the point at which the nominated shear force is
reached. The readings above this limiting slip value are conditions unlikely to
be experienced in a rail/wheel situation but give a better understanding of the
lubricants’ capabilities, under extreme sliding and energy absorption
conditions. Results below the limiting slip value are applicable to rail/wheel
contacts where the tractive force is fixed. Slip will decrease to a minimum
value, a point at which there is no lubricating effect, and the time taken to
reach this point is of great importance. Predicting a half life for a lubricant
under set conditions aids in determining location of lubricator and/or
lubrication rates.
Note: In all plots the markers on the lines, circle, dot or cross, do not indicate
the number of results taken in a test. They are only plotted to identify the
different lines on each plot. All data points are spaced at 1 second intervals as
specified in the error analysis, Section 4.7. The time scales on all graphs must
be observed as there are differences between each of the lubricants depending
on the length of test time.
161
5.5.1 Group 1 Lubricant Performance Results (Tread Load = 9.5 kN,
Braking Torque = 15 N.m, Rolling Speed = 20 km/hr)
0 100 200 300 400 500 600 700 800 900 10000
0.5
1
1.5
2
2.5
3
3.5
4x 105
Time (s)
Cum
ulat
ive
Abs
orbe
d E
nerg
y (J
)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 75 - Cumulative absorbed energy of lubricant film versus time for Group 1.
Lubricant B had a higher rate of energy absorption than either Lubricant A or
C in the time preceding 300 seconds. In Figure 76 the power absorbed by the
lubricant film is more easily observed. Lubricant A can be observed to be
constant in the middle part of the test, between 100 and 500 seconds, whereas
Lubricant B steadily declines from its maximum. The time in which Lubricant
C is absorbing power is an order of magnitude smaller than the other
lubricants.
162
0 100 200 300 400 500 600 700 800 900 10000
200
400
600
800
Times (s)
Abs
orbe
d P
ower
(Wat
ts)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 100 200 300 400 500 600 700 800 9000
200
400
600
800
Times (s)
Abs
orbe
d P
ower
(Wat
ts)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 70 80 90 1000
200
400
600
800
Times (s)
Abs
orbe
d P
ower
(Wat
ts)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 76 – Power absorption rates for each lubricant in Group 1 tests. Note different time scales for each lubricant.
Lubricant C cannot be observed on Figure 75 as the amount of energy
dissipation is negligible. Plotting Lubricant C separately in Figure 77 shows
the minimal energy absorption as compared to Lubricants A and B. In
addition one of the tests for Lubricant C shows two times the total energy
absorption of the other two tests in this group. Assuming power absorbed by
lubricant is power that is not used in wear processes, ranks the lubricants in
terms of performance, as A with the best performance then B, then C as the
worst performer.
163
0 10 20 30 40 50 60 70 80 90 1000
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5x 104
Time (s)
Cum
ulat
ive
Abs
obed
Ene
rgy
(J)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 77 - Cumulative absorbed energy versus time for Lubricant C.
Plotting the total absorbed energy for each of the tests shows a clear
difference in performance between each of the lubricants (see Figure 78).
Lubricant A absorbed more energy than the two other lubricants, before the
set tractive force was achieved, which is the desired effect of the lubricant.
164
Lubricant A Lubricant B Lubricant C0
0.5
1
1.5
2
2.5
3
3.5
4x 105
Tota
l Abs
orbe
d E
nerg
y (J
)
Figure 78 – Total energy absorbed prior to set tractive force limit for Group 1.
The sliding distance over which a lubricant is considered effective was also
under investigation. Effective lubricant performance was defined, for the
purpose of this thesis, as the point at which the transmitted torque from input
to output reaches the defined value, in this group set to 15 N.m. Noise on the
torque signal made identification of this point in the recorded data difficult,
see Figure 79, and as such the point at which slip reached 5 % was taken as
the cut-off value.
The results on distance give an estimation of lubricant performance for a fully
lubricated case under extreme sliding conditions. Normal load and input
rolling speed were relatively constant over the test. The only parameter that
changed during the test was the transmitted tractive force through the
lubricant film. The closest in-service conditions to match the test conditions
are of a lubricated curve with a functioning lubricator which is suddenly
turned off.
165
0 100 200 300 400 500 600 700 800 900 10000
5
10
15
20
Time (s)
Out
put T
orqu
e (N
.m)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 100 200 300 400 500 600 700 800 9000
5
10
15
20
Time (s)
Out
put T
orqu
e (N
.m)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 70 80 90 1000
5
10
15
20
Time (s)
Out
put T
orqu
e (N
.m)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 79 – Output torque profiles for Group 1.
The trend in the previous absorbed energy results can again be seen in Figure
80 for total sliding distance, with the lubricants performing in the same rank
order A,B,C. Lubricant A has at least twice the performance of Lubricant B
which has twice the performance of Lubricant C.
The total sliding distance is a measure of the strain history that the lubricant
can withstand prior to development of the set tractive force. The set tractive
force can also be thought of as a shear stress limit. Sliding distance is
calculated as the difference between the rolled distance of the rail sample and
wheel sample which has been mathematically presented in Section 4.7.
166
Lubricant A Lubricant B Lubricant C0
500
1000
1500
2000
2500
3000
Dis
tanc
e (m
)
Figure 80 – Sliding distance of lubricant prior to set tractive force limit for Group 1.
The sliding velocity profiles over the test are given in Figure 81. Lubricant B
has a sliding velocity profile that steadily reduces over the course of the test.
Damage from sliding/shearing accumulated in this lubricant appears to
constantly degrade the performance. In comparison, Lubricant A reaches a
steady value of sliding velocity and remains at this value for a period then fails
in a manner similar to Lubricant C, except for the extreme differences in
lubricant life between Lubricants A and C.
Upon reaching the critical accumulated damage history in Lubricant C, there
was a definite point at which the lubricant film was observed to fail and reach
the full tractive load. This point was heard during testing, as the output shaft
rapidly increased in rotational velocity and was observed in Figure 81 as a
reduction in sliding velocity. The length of time for this transition, see Figure
81, is approximately 10 seconds for Lubricant C. Lubricant A and B did not
display this effect.
167
0 100 200 300 400 500 600 700 800 900 10000
2
4
6
8
Time (s)
Vel
ocity
(m/s
) Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 100 200 300 400 500 600 700 800 9000
2
4
6
8
Time (s)
Vel
ocity
(m/s
) Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 70 80 90 1000
2
4
6
8
Time (s)
Vel
ocity
(m/s
)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 81 – Sliding velocity profile for Group 1.
The data in the in-service conditions section of the tests, the portion where
the set shear stress had been reached, was analysed to find the expected half
life of the remaining lubricant using the method in Section 5.3.1.
168
Lubricant A Lubricant B Lubricant C0
200
400
600H
alf L
ife (s
)
Lubricant A Lubricant B Lubricant C0
2
4
6
Min
imum
Slip
(%)
Figure 82 – (top) Half life prediction for
Group 1 using ( ) bxf x ae c−= + .
(bottom) Value of predicted minimum slip ‘c’.
Predicting the half life was highly dependent on the coefficient ‘c’ in the
exponential curve fit, which has the expected value of zero but the regression
analysis did not agree, see Figure 82 (bottom).
Inspecting the example in Figure 83, the fit of the equation with the
displacement coefficient ‘c’ has a better fit. This cannot exist in practice, as
the lubricant film will fully degrade and zero slip conditions will be reached.
While mathematically this equation is a better fit (R2=0.9545 versus
R2=0.9814), the equation without ‘c’ was used to reflect the expected
outcome. Presentation of half-life lubricant performance in the summary,
Section 5.5.5 will use the equation without the offset coefficient.
169
0 10 20 30 40 50 60 70 80 90 100
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
5
Time (s)
Slip
(%)
Slipy=a*e (̂-bx)y=a*e (̂-bx)+c
Figure 83 – Regression plots for Lubricant A Test 2 Group 1 in the region < 5% slip.
HALF LIFE (S) Lubricant Type Mean Standard Deviation
A 274.51 144.37 B 983.9 592.77 C 87.75 8.5956
Table 25 – Half life values for each lubricant
in Group 1 testing using ( ) bxf x ae−= .
Lubricant C had a small but predictable half life, seen by the small standard
deviation, which may be the result of testing into the region of slip below 1%.
The other lubricant tests ceased prior to the reduction in slip reached by
Lubricant C. Lubricant B clearly had the longest half life but predictability of
total film failure would be problematic with the large standard deviation.
Next, in terms of performance, Lubricant A had large variability and longer
life than Lubricant C.
170
Lubricant A Lubricant B Lubricant C0
200
400
600
800
1000
1200
1400
1600
1800
Hal
f Life
(s)
Figure 84 - Half life values for each lubricant
in Group 1 testing using ( ) bxf x ae−= .
Figure 85 shows the apparent viscosity profiles for Group 1, calculated using
the method presented in Section 4.7. All lubricants in Figure 85 have a high
degree of linearity for apparent viscosity, especially Lubricant C. Lubricants A
and B have some extraneous results deviating from the linear behaviour
which can be attributed to the tests not yet having reached the set shear force
level. The source of the deviation from linearity is that the apparent viscosity
is continuing to change with accumulated strain, indicating that the shear life
of the lubricant has not been reached. Lubricant C is the exception in Figure
85 where it had reached its shear life. The development of apparent viscosity
with accumulated shear will be discussed further in Section 5.5.5
171
104
105
106
107
100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 85 – Apparent viscosity for Group 1. 5.5.2 Group 2 Lubricant Performance Results (Tread Load = 9.5 kN,
Braking Torque = 15 N.m, Rolling Speed = 10 km/hr)
The data for Lubricant B required a change in the cut off point between high
slip and the set traction force regions from 5% slip to 8% and 7% slip for
Tests 2 and 3 respectively due to the slip data not reaching the set cut off
level, which can be observed in Figure 86. This reduces the total absorbed
energy and slid distance by a small amount.
172
0 50 100 150 200 250 300 350 4000
1
2
3
4
5
6
7
8
9
Time (s)
Slip
(%)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 86 - Slip profiles for Group 2 after set cut off limit of slip achieved. Lubricant B Tests 2 and 3 had limits of 8% and 7% respectively.
173
0 500 1000 1500 20000
1
2
3x 105
Time (s)
Abs
orbe
d E
nerg
y (J
)
0 100 200 300 400 500 6000
2
4
6x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
0 20 40 60 80 100 120 140 1600
1
2
3x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 87 - Cumulative absorbed energy versus time for Group 2. Energy is calculated from the difference between input and output energy. Note the different scales on vertical and horizontal axes.
The cumulative absorbed energy profiles, see Figure 87, for Lubricants B and
C are consistent across each test whereas Lubricant A had a test which was
not consistent with the other two. Experimental observations of the tests for
Lubricant A highlighted the development of a wear ring from a section of
wear debris leaving the contact. The rank order for lubricant performance was
the same as Group 1, Lubricant A then B then C.
174
Lubricant A Lubricant B Lubricant C0
0.5
1
1.5
2
2.5x 105
Tota
l Abs
orbe
d E
nerg
y (J
)
Figure 88 – Total energy absorbed prior to set tractive force limit for Group 2.
The total absorbed energy or energy capacity of the lubricants in Figure 88
does not show the same magnitude of difference of performance between
lubricants as the Group 1 tests, but the same performance trend is present.
Halving the input rolling speed has decreased the energy capacity of
Lubricants A and B, with Lubricant C remaining approximately the same. The
speed reduction has also increased the variability of performance of Lubricant
A.
175
0 500 1000 1500 2000
0
100
200
300
Time (s)
Abo
sorb
ed P
ower
(W)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 100 200 300 400 500 600
0
100
200
300
Time (s)
Abo
sorb
ed P
ower
(W)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 50 100 150
0
100
200
300
Time (s)
Abo
sorb
ed P
ower
(W)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 89 – Power absorption rates for each lubricant in Group 2 tests. Note the different scales on the horizontal axis.
The power absorption rates for Group 2 are shown in Figure 89. Lubricant C
has an increasing power profile until lubricant failure, which may indicate
increased lubricant performance with increased temperature. Conversely
Lubricant B has the opposite profile with a steady reduction in absorbed
power over the test. Lubricant A, excluding Test 1 (the profile of absorbed
power at 250W at the beginning of the test time), has a similar absorbed
power profile to Lubricant C, except for the large period of minimal power
absorption in the first half of the test. The maximum power absorption rate
for each lubricant is similar. This rate is limited by the input power which is
also limited.
176
Lubricant A Lubricant B Lubricant C0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Dis
tanc
e (m
)
Figure 90 – Sliding distance of lubricant prior to set tractive force limit for Group 2.
The total sliding distance for Group 2 is presented in Figure 90. Lubricant B
is capable of sliding for half the distance at half the input rolling speed when
compared to Group 1 results. This indicates that the time to failure for
Lubricant B may be related to the lubricant film being forced from the
contact at a similar rate despite the rolling speed, a rheology effect. Lubricant
A had the opposite result with an increase in total sliding distance when
compared to Group 1 results, except Test 1 which had a similar magnitude to
the results of Group 1. Performance of Lubricant C remained similar to
Group 1 testing. Ranking of the lubricants changed with Lubricant C slightly
outperforming Lubricant B to give the order A, C, then B. The difference in
sliding distance performance of Lubricant B and C may not be significant.
177
0 500 1000 1500 20000
1
2
3
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 100 200 300 400 500 6000
1
2
3
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 20 40 60 80 100 120 140 1600
1
2
3
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 91 – Sliding velocity profiles for Group 2. Note the different scales on the horizontal axis.
Sliding velocity profiles for Group 2 are presented in Figure 91, where
Lubricants A and C have definite points of lubricant failure as previously
observed in Group 1. The exception is Lubricant A Test 1. The deceleration
is smaller than the other two tests. Lubricant C also had a grossly different
test with an almost immediate failure. Lubricant B had a similar profile to the
Group 1 tests with a steady decay observed.
178
Lubricant A Lubricant B Lubricant C0
50
100
150H
alf L
ife (s
)
Lubricant A Lubricant B Lubricant C0
2
4
6
8
Min
imum
Slip
(%)
Figure 92 – (top) Half life prediction for
Group 2 using ( ) bxf x ae c−= + .
(bottom) Value of predicted minimum slip ‘c’ or offset coefficient.
The slip profiles shown in Figure 86 highlight the differences in test
completion conditions. These conditions have a direct influence on the offset
coefficient in Figure 92 (bottom) which theoretically should be zero. Higher
measured slip at test completion gave a higher predicted offset coefficient,
which indicates a deficiency in the chosen regression model. The predicted
half lives, without an offset coefficient, shown in Figure 93, are different to
those shown in Figure 92 because of the different test completion conditions
between lubricants.
The half lives in Figure 92 for all lubricants are similar. In Figure 93 the half
life for Lubricant B dramatically increases and is much larger than Lubricants
A and C. The exception is Lubricant A Test 1 in which the half life is
179
approximately ten times larger than the other two samples. Ignoring this
sample as an outlier, the performance ranking is Lubricant B, C then A.
Considering all readings the performance ranking is Lubricant B, A then C,
which is the same as Group 1 and is presented in Table 26.
HALF LIFE (S) Lubricant Type Mean Standard Deviation
A 502.98 665.56 B 916.42 393.7 C 205.99 50.282
Table 26 – Half life values for each lubricant
in Group 1 testing using ( ) bxf x ae−= .
Lubricant A Lubricant B Lubricant C0
200
400
600
800
1000
1200
1400
Hal
f Life
(s)
Figure 93 - Half life values for each lubricant
in Group 2 testing using ( ) bxf x ae−= .
180
104 105 106100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
104 105 106100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
104 105 106100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 94 - Apparent viscosity for Group 2.
All lubricants in Figure 94 have a high degree of linearity, especially Lubricant
C, similar to Group 1. Lubricants A and B have the same apparent viscosity
development when compared to Group 1 for the reasons presented in
Section 5.5.1.
5.5.3 Group 3 Lubricant Performance Results (Tread Load = 9.5 kN,
Braking Torque = 30 N.m, Rolling Speed = 20 km/hr)
Group 3 investigated the increase of tractive force limit, or increased applied
shear stress to the lubricants. Compared to Group 1, the performance
indicators should be higher as the limiting shear stress was higher, however
this was not the case. The change in limiting shear stress caused further ‘shake
181
down’ or plastic deformation and removal of material, large wear particles,
which influenced the duration of tests in Group 3.
0 50 100 150 200 250 3000
1
2
3
4x 105
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 20 40 60 80 1000
5
10
15x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 700
5
10x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 95 - Cumulative absorbed energy versus time for Group 3. Energy is calculated from the difference between input and output energy. Note the different scales on vertical and horizontal axes.
The inter-test variability seen in Figure 95 and Figure 96 is high for Lubricant
A, and consistent with previous groups for Lubricants B and C. The
magnitude of energy absorbed by Lubricant A is smaller than Group 1 but
slightly larger than Group 2, which may indicate a limit to the shear force
capability of this lubricant. Approximately twice the absorbed energy,
compared to Group 1, was recorded for Lubricant C. This finding is in line
with the hypothesis that doubling the limiting shearing force increases the
measured performance. Lubricant B absorbed approximately half the energy,
as in Group 1, in direct contradiction to the hypothesis of increased capacity
182
with increased shear force limit. The capabilities of Lubricant B are
significantly reduced with increased shear stress. The performance of
lubricants was the same order as Group 1, A, B then C, however the
difference in performance between Lubricants B and C is small.
Lubricant A Lubricant B Lubricant C0
0.5
1
1.5
2
2.5
3
3.5
4x 10
5
Tota
l Abs
orbe
d E
nerg
y (J
)
Figure 96 – Total energy absorbed prior to set slip limit for Group 3.
183
0 50 100 150 200 250 3000
500
1000
1500
2000
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 20 40 60 80 1000
500
1000
1500
2000
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 700
500
1000
1500
2000
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 97 – Power absorption rates for each lubricant in Group 3 tests. Note the different scales on the horizontal axis.
Power absorption rates for Group 2 are shown in Figure 97. Total test times
for Lubricant C are similar around 60 seconds, where Lubricants A and B
have highly variable test times. The rate of decay of power, at the end of each
test, was consistent for each lubricant despite the differences in time at which
this occurred.
184
Lubricant A Lubricant B Lubricant C0
100
200
300
400
500
600
700
800
900D
ista
nce
(m)
Figure 98 – Sliding distance of lubricant prior to set tractive force limit for Group 3.
The same trend of small appreciable differences in performance between
Lubricants B and C can be seen in Figure 98 for total sliding distance. Their
performance is similar to that shown in Group 2 and is still markedly smaller
than Lubricant A. Ranking of the lubricants has changed to A, C then B, with
the mean value of Lubricant C, 2% higher than the mean value for Lubricant
B. The difference in performance may not be significant.
185
0 50 100 150 200 250 3000
2
4
6
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 20 40 60 80 1000
2
4
6
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 10 20 30 40 50 60 700
2
4
6
Time (s)
Slid
ing
Spe
ed (m
/s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 99 – Sliding velocity profile for Group 3. Note the different scales on the horizontal axis.
Lubricants B and C have similarly shaped velocity profiles, see Figure 99,
which confirm the previous result of similar sliding distance performance.
Lubricant A has a velocity profile which is not consistent across tests and has
a harmonic pattern in it. The source of this harmonic is unclear as the
dominant contributor to the value of sliding velocity is braking torque, shown
in Figure 100. The hydraulic system has a much larger dominant frequency,
>1Hz, where this noise has a frequency of 0.05 Hz and is probably not the
source.
186
50 100 150 200 25018
20
22
24
26
28
30
Time (s)
Out
put T
orqu
e (N
.m)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Figure 100 – Output torque signal for Lubricant A in Group 3.
187
Lubricant A Lubricant B Lubricant C0
50
100
150
200
Hal
f Life
(s)
Lubricant A Lubricant B Lubricant C0
0.5
1
1.5
Min
imum
Slip
(%)
Figure 101 – (top) Half life prediction for
Group 3 using ( ) bxf x ae c−= + .
(bottom) Value of predicted minimum slip ‘c’.
Lubricant B Test 2 has been excluded from the half life prediction plot in
Figure 101 as the raw data was noisy and appeared to be an outlier. The noise
influenced the half life prediction and an unreasonable value was calculated.
The offset coefficient predictions, Figure 101 (bottom), are smaller than
Group 1 and 2 results, and more consistent between tests. The magnitudes
are still greater than zero. In addition the half life performance ranking is the
reverse of the power performance rankings, Lubricant C, B, then A. Half lives
for Lubricants A and B are reduced when compared to Groups 1 and 2,
which may be expected, for these groups had a smaller limiting shear stress
than Group 3 and therefore less damaging conditions for the lubricant film.
Lubricant C however had a longer half life than its results from Group 1 and
188
the expected result of a shorter half life when compared to the Group 2
results. A summary of half life values is given in Table 27 and graphically
presented in Figure 102.
HALF LIFE (S) Lubricant Type Mean Standard Deviation
A 75.523 33.981 B 102.5 9.1104 C 157.24 75.278
Table 27 – Half life values for each lubricant
in Group 1 testing using ( ) bxf x ae−= .
Lubricant A Lubricant B Lubricant C0
50
100
150
200
250
Hal
f Life
(s)
Figure 102 - Half life values for each lubricant
in Group 3 testing using ( ) bxf x ae−= .
189
104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 103 – Apparent viscosity for Group 3.
All lubricants in Figure 103 have a high degree of linearity, especially
Lubricant C, similar to Groups 1 and 2. Lubricants A and B have some
extraneous results deviating from the linear behaviour that are larger than
previously observed in Groups 1 and 2. The increase in tractive force has
increased the variability in apparent viscosity for Lubricant A and B.
5.5.4 Group 4 Lubricant Performance (Tread Load = 12.5 kN, Braking
Torque = 15 N.m, Rolling Speed = 20 km/hr)
The final group, with an increased normal force, was expected to have
reduced performance when compared to Groups 1 and 2. Group 4
investigated whether increased compressive stress was more damaging to
lubricant films than the increased shear stress of Group 3.
190
0 50 100 150 200 250 300 350 4000
0.5
1
1.5
2x 105
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 10 20 30 40 50 60 700
1
2
3
4x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 50 100 150 200 2500
2
4
6x 104
Time (s)
Abs
orbe
d E
nerg
y (J
)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 104 - Cumulative absorbed energy versus time for Group 4. Energy is calculated from the difference between input and output energy Note the different scales on vertical and horizontal axes.
Lubricants A and B experienced a large reduction in performance and test
duration, seen in Figure 104, compared to Group 1, 2 and 3. Again Lubricant
C displayed a different trend by performing similarly to its results for Groups
1 and 2 but reduced performance when compared to Group 3. This lubricant
appears to be unaffected by the increased normal force for this performance
criterion.
191
Lubricant A Lubricant B Lubricant C0
2
4
6
8
10
12
14
16x 104
Tota
l Abs
orbe
d E
nerg
y (J
)
Figure 105 – Total energy absorbed prior to set tractive force limit for Group 4.
In Figure 105 for total absorbed energy Lubricant A remains the best
performer followed by Lubricant C then Lubricant B. The difference in
performance between lubricants has reduced, and the difference between
Lubricants B and C is not clear with this performance criterion.
192
0 50 100 150 200 250 300 350 4000
200
400
600
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 10 20 30 40 50 60 700
200
400
600
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 50 100 150 200 2500
200
400
600
Time (s)
Abs
orbe
d P
ower
(W)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 106 – Power absorption rates for each lubricant in Group 4 tests. Note the different scales on the horizontal axis.
Power absorption rates for Lubricants A and B are higher than Lubricant C
and have a distinct point at which the absorbed power reduces rapidly, seen in
Figure 106. Lubricant C has a continuous decay in power over the course of
the test.
193
Lubricant A Lubricant B Lubricant C0
200
400
600
800
1000
1200
Dis
tanc
e (m
)
Figure 107 – Sliding distance of lubricant prior to set tractive force limit for Group 4.
The absorbed power performance criterion does not highlight the poor
performance of Lubricant C when considering total slid distance in Figure
107. Experimentally Lubricant C did not have a period of gross sliding and
was considered to have failed from start-up. The performance rankings from
Figure 107 are clear, Lubricant A , B then C.
194
0 50 100 150 200 250 300 350 4000
2
4
6
Time (s)
Sld
ing
Spe
ed (m
/s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
0 10 20 30 40 50 60 700
2
4
6
Time (s)
Sld
ing
Spe
ed (m
/s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
0 50 100 150 200 2500
0.01
0.02
0.03
Time (s)
Sld
ing
Spe
ed (m
/s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 108 – Sliding velocity profile for Group 4. Note the different scales on vertical and horizontal axes.
It is important to note that the sliding speed recorded for Lubricant C, see
Figure 108, is approaching zero (0.02 m/s) whereas the other lubricants have
periods of sliding, before a definite reduction in velocity.
195
Lubricant A Lubricant B Lubricant C0
100
200
300
400
Hal
f Life
(s)
Lubricant A Lubricant B Lubricant C0
0.2
0.4
0.6
0.8
Min
imum
Slip
(%)
Figure 109 – (top) Half life prediction for
Group 4 using ( ) bxf x ae c−= + .
(bottom) Value of predicted minimum slip ‘c’.
Small offset coefficients of slip were calculated for Group 4, see Figure 109,
similar in magnitude to Group 3 but smaller than Groups 1 and 2. Lubricant
B performed best, then Lubricants C and A respectively. Differences between
A and C, using the exponential with offset regression formula, are difficult to
observe in Figure 109.
Considering an exponential decay to zero the performance rankings are
reordered, Lubricant C, B then A with details in Table 28 and Figure 110. The
difference between Lubricant B and C is small and there is a high variability in
the mean value of performance for C, but not for Lubricant B. Lubricant C
half life will be affected by the low slip measured during testing and may skew
the results.
196
HALF LIFE (S) Lubricant Type Mean Standard Deviation
A 148.76 16.151 B 353.22 50.317 C 393.14 226.16
Table 28 – Half life values for each lubricant
in Group 1 testing using ( ) bxf x ae−= .
Lubricant A Lubricant B Lubricant C0
100
200
300
400
500
600
Hal
f Life
(s)
Figure 110 - Half life values for each lubricant
in Group 4 testing using ( ) bxf x ae−= .
197
103 104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
103 104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
103 104 105 106 107100
102
104
Strain Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 111 – Apparent viscosity for Group 4.
Apparent viscosity results for Group 4 in Figure 111 show Lubricant C to
have a high degree of linearity, similar to Groups 1, 2 and 3 but is over a
much smaller range of strain rate corresponding to the small range in sliding
velocity. Lubricants A and B have some extraneous results deviating from the
linear behaviour previously observed in Groups 1 and 2, the increase in
normal force has increased the variability in apparent viscosity.
5.5.5 Comparison and Discussion of All Groups
The different phenomena observed between each set of conditions for a
lubricant, with respect to energy absorbed, can be more readily observed in
Figure 112. Lubricant A has reduced absorbed energy performance for all
changes in test parameters from Group 1. Reducing rolling speed reduced
198
the absorbed energy capacity by half, with the most plausible explanation
being the lubricant film cannot sustain the compressive force at the reduced
entrainment velocity. Lubricant B showed an even greater reduction in energy
capacity at the reduced rolling velocity whereas Lubricant C reduced
marginally.
Group 1 Group 2 Group 3 Group 40
1
2
3
4x 105 Lubricant A
Tota
l Abs
orbe
d E
nerg
y (J
)
Group 1 Group 2 Group 3 Group 40
1
2
3x 105 Lubricant B
Tota
l Abs
orbe
d E
nerg
y (J
)
Group 1 Group 2 Group 3 Group 40
5
10x 104 Lubricant C
Tota
l Abs
orbe
d E
nerg
y (J
)
Figure 112 – Total absorbed energy for groups of tests. Note the different scales on the vertical axis.
The increasing level of shearing force of Group 3 allowed Lubricant C to
absorb a greater amount of energy prior to development of full tractive force.
This absorption indicates a higher apparent viscosity than either Lubricants A
or B which will be discussed further in Section 5.5.7. The reduction in
absorbed energy capacity for Lubricant A from increased shear force in
199
Group 3 was not as drastic as the reduction of performance from reducing
rolling velocity in Group 2. A similar reduction in absorbed energy
performance was observed in the Lubricant B results when compared to
Group 1 and 3.
Group 1 Group 2 Group 3 Group 40
2000
4000
6000Lubricant A
Dis
tanc
e (m
)
Group 1 Group 2 Group 3 Group 40
200
400
600
800Lubricant B
Dis
tanc
e (m
)
Group 1 Group 2 Group 3 Group 40
100
200
300
400Lubricant C
Dis
tanc
e (m
)
Figure 113 – Total sliding distance prior to set tractive force limit. Note the different scales on the vertical axis.
Group 4 tests increased the normal load by 30% and reduced the absorbed
energy performance of Lubricants A and B more than the other parameter
changes, indicating a relationship between normal force and energy capacity.
In contrast Lubricant C did not appear to be affected by changes in test
parameters except the increase of limiting shear stress in Group 3. The
difference of soap between Lubricants A and B, lithium based, and Lubricant
200
C, aluminium based, is a likely source of differences in performance despite
similar additives and base oils.
Sliding distance performance for the lubricants does not have the same
characteristics as the energy absorbed results, see Figure 113. Lubricant A
sliding distance performance increases with a reduction in rolling velocity in
Group 2, in contrast to Lubricant B which loses about 75% of the sliding
distance performance when compared to results from Group 1. Lubricants A
and B also have reduced sliding distance performance with the increased
tractive force limits in Group 3. Lubricant C however has a high variability
and it is difficult to differentiate between Groups 1 through 3. Group 4 is the
exception. The increased tread load reduced the sliding distance performance
to negligible values for Lubricant C. Lubricants A and B also performed at a
reduced level of sliding distance performance with the application of greater
normal load but still had a definite period of sliding in which tractive force is
being absorbed by the lubricant rather than the contacting bodies in wear
processes.
201
Group 1 Group 2 Group 3 Group 40
500
1000
1500Lubricant A
Hal
f Life
(s)
Group 1 Group 2 Group 3 Group 40
1000
2000
3000Lubricant B
Hal
f Life
(s)
Group 1 Group 2 Group 3 Group 40
200
400
600Lubricant C
Hal
f Life
(s)
Figure 114 – Half life values summary Note the different scales on the vertical axis.
The performance values for half life in Figure 114 do not have the same
trends as the previous two summaries of absorbed energy and sliding
distance. The data has wide inter-group ranges, making observations difficult
to present with certainty.
Lubricants A and B have reduced half life performance with increased normal
load in Group 4 and increased shearing force in Group 3. Half life appears to
be unaffected by rolling speed for Lubricants A and B. Lubricant C is
observed to have increased performance with changes to the input parameters
of reduced rolling speed, increased shearing force and increased normal load
compared to those of Group 1. The increases of shear force and normal load
202
appear to improve the performance of Lubricant C, contrary to expected
outcomes.
5.5.6 Lubricant Performance Summary
Lubricant Type Group No. Performance Criteria A B C
Total energy absorbed (J) 324440 215320 28564 Total sliding distance (m) 2379 749 216 1 Half life of lubricant (s) 275 984 88 Total energy absorbed (J) 143200 36786 18094 Total sliding distance (m) 3597 224 246 2 Half life of lubricant (s) 503 916 206 Total energy absorbed (J) 202800 83200 75560 Total sliding distance (m) 574 184 187 3 Half life of lubricant (s) 76 782 157 Total energy absorbed (J) 78857 22298 28929 Total sliding distance (m) 614 123 3 4 Half life of lubricant (s) 149 353 393 Average Total energy absorbed (J) 106283 89401 37786 Average Total sliding distance (m) 1791 319 162 ALL Average Half life of lubricant (s) 250 758 211
Table 29 – Lubricant performance summary.
The overall performance of each lubricant was calculated by comparing the
mean values of each performance criteria, the absolute values presented in
Table 29, and assigning the best performing lubricant 100% and assigning
fractions to the other lubricants.
The purpose in presenting in this format is to compare lubricant performance
quantitatively while removing the absolute magnitudes of the values, which
have yet to be correlated with field data. The results of this analysis are in
Table 30. In addition to the group data is an overall performance ranking, the
‘ALL’ rows, which is calculated by taking the mean of the results of a
particular performance criterion from the 4 groups.
203
Lubricant Type Group No. Performance Criteria A B C
Total energy absorbed 100% 66% 9% Total sliding distance 100% 31% 9% 1 Half life of lubricant 28% 100% 9% Total energy absorbed 100% 26% 13% Total sliding distance 100% 6% 7% 2 Half life of lubricant 55% 100% 22% Total energy absorbed 100% 41% 37% Total sliding distance 100% 32% 33% 3 Half life of lubricant 10% 100% 20% Total energy absorbed 100% 28% 37% Total sliding distance 100% 20% 0% 4 Half life of lubricant 38% 90% 100% Total energy absorbed 100% 84% 36% Total sliding distance 100% 18% 9% ALL Half life of lubricant 33% 100% 28%
Table 30 – Relative lubricant performance summary.
Alternatively, taking a qualitative analysis approach to the results from the
groups and assigning each lubricant a numeric rank according to
performance, lower being better, give the ranks given in Table 31. The inter-
group performance values in Table 31 were calculated by taking the mean of
the ranks for a particular lubricant.
If each performance criterion has equal weight or importance, then the
lubricants have the performance order A, B then C. The tabled results do not
take into account the quantitatively large or small differences between
lubricants, which for some tests are extreme. Taking each performance
criterion separately the ranking of lubricant performance was not conclusive.
Lubricant A is the best performer under all test conditions for total energy
absorbed and total sliding distance. Total absorbed energy is a representation
of the stress history whereas sliding distance is a representation of strain
history, both are clearly important and Lubricant A is the best performer.
204
Lubricant Type Group No. Performance Criteria A B C
Total energy absorbed 1 2 3 Total sliding distance 1 2 3 1 Half life of lubricant 2 1 3
Inter-group performance 1.33 1.67 3.00 Total energy absorbed 1 2 3 Total sliding distance 1 3 2 2 Half life of lubricant 2 1 3
Inter-group performance 1.33 2.00 2.67 Total energy absorbed 1 2 3 Total sliding distance 1 3 2 3 Half life of lubricant 3 2 1
Inter-group performance 1.67 2.33 2.00 Total energy absorbed 1 3 2 Total sliding distance 1 2 3 4 Half life of lubricant 3 2 1
Inter-group performance 1.67 2.33 2.00 Total energy absorbed 1.00 2.25 2.75 Total sliding distance 1.00 2.50 2.50 ALL Half life of lubricant 2.50 1.50 2.00
Total Performance Rank 1.50 2.08 2.42 Table 31 – Qualitative performance of lubricants.
Strain life, calculated from total sliding distance, is similar between Lubricants
B and C, indicating that the strain history limits between lubricants is also
similar. Lubricant A has best strain history limit or sliding distance under all
conditions. Stress absorption capacity, from total absorbed energy, has the
same performance rankings as strain life with the exception of a slight
performance advantage to Lubricant B. Lubricant C only outperforms
Lubricant B in total absorbed energy when the normal force is increased.
Half life of the lubricants is a performance criterion that does not display clear
differences under all conditions. Lubricant B is the overall best performer in
this category, but it can be observed that an increase in normal load or
shearing force reduces the half life and Lubricant C becomes the best
205
performer. Lubricant A also loses half life performance with increased normal
load or shearing force similar to Lubricant B.
5.5.7 Apparent Viscosity Profiles
0 200 400 600 800 1000 1200100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 200 400 600 800 1000 1200100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 100 200 300 400 500 600100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 115 – Apparent viscosity versus time for Group 1. Note the different scales on the horizontal axis.
Accumulated strain causes structural changes in the lubricants, represented by
increasing values of apparent viscosity (Kuhn 1995; Kuhn and Balan 1997;
Yonggang and Jie 1998). Two parts of the apparent viscosity profile are
important in terms of lubricant performance. Firstly the length of time or
amount of accumulated strain for which a lubricant remains at a reduced
viscosity and secondly the plateau viscosity. The first part of reduced viscosity
minimises the transmission of force and stress between the two contacting
206
bodies, thereby reducing the wear and fatigue processes. The second part of
the apparent viscosity profile is the proportion of the input shear force
imparted to the output contact. Lowering the value of shear force reduces the
wear producing shear stress experienced by the contacting bodies. Therefore
the optimum characteristics of apparent viscosity are extended accumulated
strain life, presented in the apparent viscosity profiles as test time, and
minimal plateau viscosity at test completion.
Plotting apparent viscosity versus time for the lubricated testing in Group 1 to
4 displays the characteristic of increasing viscosity with strain history, which is
represented in this case as time elapsed. In Figure 115 to Figure 118
Lubricants A, B and C appear to have a limiting shear stress value, seen by the
profiles becoming ‘horizontal’ with the progression of time.
Lubricant C consistently has the highest finishing apparent viscosity across all
groups of tests followed by Lubricant A then Lubricant B. Inter-test
variability for Lubricant A is high when compared to Lubricants B and C
which appear to have predictable apparent viscosity profiles. The exceptions
to the predictable apparent viscosity profiles are periods in which the
apparent viscosity reduces, seen for Lubricant B in Group 1 and Lubricant C
in Group 2. The exceptions may be explained by extraneous lubricant
entering the contact area. The extraneous lubricant occurs from two
phenomena, lubricant flung from the outer edge of the samples where it has
been pushed, and lubricant falling from the safety guard where it may collect
from the centrifugally flung excess lubricant from the samples at the
beginning of the test.
207
0 500 1000 1500 2000 2500100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 100 200 300 400 500 600 700 800100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 100 200 300 400 500 600100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 116 - Apparent viscosity versus time for Group 2. Note the different scales on the horizontal axis.
208
0 100 200 300 400 500100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 100 200 300 400 500 600100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 50 100 150 200 250 300 350100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 117 - Apparent viscosity versus time for Group 3. Note the different scales on the horizontal axis.
209
0 100 200 300 400 500 600 700100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 100 200 300 400 500 600100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
0 50 100 150 200 250100
102
104
Time (s)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant A Test 1Lubricant A Test 2Lubricant A Test 3
Lubricant B Test 1Lubricant B Test 2Lubricant B Test 3
Lubricant C Test 1Lubricant C Test 2Lubricant C Test 3
Figure 118 - Apparent viscosity versus time for Group 4. Note the different scales on the horizontal axis.
5.6 Experimental Observations
5.6.1 Temperature Profiles
In the low speed testing, the lubricant films maintained integrity for far longer
than at high speed testing. The bulk temperature of the samples was lower
than the high speed testing under the same loading conditions. Frictional
energy is halved in the low speed case if we consider sliding velocity alone.
During the tests, the sliding velocity is not constant which does not allow for
comparison between high and low speed frictional energy heating.
It can be observed that the sample temperatures continue to rise during the
low speed testing whereas the temperature drops at the end of the test for the
210
high speed case. A plausible explanation for this phenomenon is the air
velocity across the samples in the high speed case gives a much larger
convection heat transfer coefficient. The testing may also be short enough
that the bulk of the heat energy is not transmitted into the simulator body
which is a significant thermal mass.
Thermal energy is added to the system through the hydraulic dynamometer
where the braking energy is converted into thermal energy. In addition to its
use in the dynamometer, oil is used to lubricate and cool the bearings of both
sample holders. The hydraulic oil for lubricating bearings in the sample
holders experiences a large increase in temperature through the testing
process and is returned to the main reservoir, whereas oil for the
dynamometer experiences a small increase in temperature and is returned to
the reservoir via the heat exchanger. Volume flow for the dynamometer is
two orders of magnitude larger than the lubricating system, which maintains
the reservoir temperature, ~30˚, but this does little to reduce the simulator
body temperature during a long test.
5.6.2 Observed Lubricant Properties
Separation of oil from the grease phase was observed in all lubricant samples.
Lubricant C had the largest volume of oil with similar handling conditions for
each of the lubricants. Lubricant samples were taken from minimum 20kg
containers and stored in 1 kg packages until used. All testing, except rheology
testing, was carried out using the single sample container. A backup set of
containers was stored for the duration of the project and the backup
container of Lubricant C displayed the same characteristics as the used
sample.
Separate tests were carried out to investigate the variable consistency of
Lubricant C. The absolute values of these tests were not recorded as the test
protocol differed from the main testing. Time for lubricant film development
and slip percentage with respect to time were recorded and compared.
211
Despite the oil bleed there was no easily discernable performance difference,
using the simulator, between an application of ‘oily’ grease or the consistent
grease.
The results would indicate that the oil, the main lubrication component, is still
reaching the target area whether oil bleed is present or not. In the case of a
gauge corner oil bleed would precipitate the oil from the contact zone down
the gauge face onto the rail web and not provide any lubricating effect.
The order in which each lubricant was applied during a battery of tests was
random, which meant that the temperature of the rail and wheel samples were
variable at the time of lubricant application. Lubricant B was observed to
spread much more readily onto a hot metal sample. Lubricants A and C did
not display this effect.
Application of larger braking torque in Group 3 introduced an effect where
the lubricant film would regain effectiveness as the temperature decreased.
Temperature of the test samples increased as frictional energy was absorbed
into the bodies. The system has a heat energy balance between input and
output. At the start of testing, with high sliding speed, input energy is greater
than output energy and the samples increase in temperature. As sliding speed
decreases and output shaft rotational velocity increases the output energy
from convection heat transfer becomes larger than the frictional input energy
and subsequently the samples decrease in temperature. This reduction in
temperature coincided with the regeneration of lubricant effectiveness.
It is postulated that due to the higher temperatures experienced during the
Group 3 tests, temperature reactive components of the lubricant become
active, which previously could not be observed. All lubricants displayed this
behaviour during testing. Additionally this phenomenon was explored by
allowing the samples to cool post test then testing without cleaning. The
lubricant performed as before with a reduction in performance. Practically
this translates to a situation where a train passes, there is a delay, and then
212
another train passes. It was not determined what temperature must be
achieved to get the most benefit from the temperature reactive lubricant
components.
Increasing the tread load from 9.5 kN to 12.5 kN resulted in no gross sliding
for Lubricant C. The lubricant appeared unable to adhere to the surfaces, with
this larger normal force. The lubricant film is visible and detectable by a larger
slip value than the unlubricated case, but is allowing for a full transmission of
the input power. Practically, this represents probable protection of the
surfaces from wear but high tractive power losses and full transmission of
forces related to fatigue. This high tractive power may be advantageous where
lubricant migration to the tread and traction loss is an issue, as this lubricant
acts as a friction modifier rather than a lubricant.
5.6.3 Lubricant Film Failure
Lubricant film failure was observed during testing when material was
removed from either contact surface. Newly machined rail/wheel samples
tested with lubricant and applied braking torque had a high rate of material
removal. Subsequent tests had progressively lower material removal rates as
surface hardness increased. Plastic deformation of both surfaces, accumulated
during testing, increased the wear resistance of the surfaces.
Upon application of a larger braking torque, high material removal rates were
observed again. Narrow bands (< 5 mm width) of contact surface were
observed without lubricant film following material removal. It is hypothesised
that the removed material reached its ductility limit with the increase in
shearing stress, causing material failure.
5.6.4 Braking Torque Setting
Braking torque was set by adjusting a hydraulic pressure relief valve to a
nominal value. This value was set using an inline oil pressure transducer
which was not accurately calibrated against the output torque transducer
signal. The nominal line pressure was adjusted during the warm-up and
213
monitored during testing to maintain a constant set point. The set point
would move with changes in lubricant temperature and flow rate. Minimising
output signal noise was achieved by maintaining oil temperature and setting
the valve position under maximum expected flow and not adjusting during
testing. The torque quoted in the testing results is an approximate value but
the experimental values of torque presented and used in the calculation of
results are the measured values.
5.7 Standards Based Lubricant Testing Results
Figure 119 – ARES Rheometer used for rheology testing.
The following sections will present and discuss the results obtained from the
standards based testing. The exception to this is the tests performed with the
214
rheometer (see Figure 119), which are not standards based, but use the test
device manufacturer's recommendations for testing (Yonggang and Jie 1998;
Nolan ~2000). This method is detailed in the following section.
5.7.1 Rheometry Method
Clean interface surfaces with solvents as per ASTM standard method. Refer to Figure 120 to observe surfaces and test piece arrangement.
Install top and bottom plates, zero gap and normal force.
Move top plate to furthest position and apply lubricant to bottom plate. Lubricant is applied using a spatula, the bulk of the product located in the centre of the plate.
Lower top plate to set gap. Ensure excess lubricant is observed around circumference of plates.
Perform selected test.
Move top plate to furthest position and clean lubricant from top and bottom plates as specified by ASTM standard method.
Figure 120 – Cone and plate arrangement for rheometer testing.
215
5.7.2 Rheometer Test Discussion and Results
The rheometer tests were quick to perform, which, if a correlation between
performance and rheological properties could be determined, would make
this a suitable test. However there is not a clear measured difference that
matches the trends seen in the simulator testing. This form of test does not
reach the shear rates experienced in a simulated or real rail wheel contact.
In the low shear rate region of Figure 121 Lubricant B has a higher viscosity
than Lubricant A and Lubricant C, conversely at the higher shear rate
Lubricant B and C swap positions. Lubricant B is therefore shear thinning at a
greater rate than Lubricants A and C. The decreased shear thinning of
Lubricant C at the higher shear rates may explain the observed behaviour of
short times to achieve tractive force in the simulator testing.
10-2 10-1 100 101 102 103100
101
102
103
104
Shear Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant ALubricant BLubricant C
Figure 121 – Apparent Viscosity versus Shear Rate using a flat plate rheometer.
216
5.7.3 Experimental Rheometry Observations
Lubricant was expelled from the surfaces using the cone and plate setup as
the strain accumulated. Moving the testing surfaces apart showed a reduction
in lubricant surface area. This ‘climbing’ effect was explained in the operating
manual of the rheometer and is often experienced by substances with elastic
properties.
The calibrated gap between cone and plate, 55µm, was difficult to reach. The
grease appeared to resist the applied normal movement similar to
compressing a viscoelastic solid. This compression applies a radial strain
history to the samples.
In the case of the parallel plates, lowering the top plate would introduce a
normal force on the plate as the lubricant was expelled. The magnitude of this
force was different for each grease tested. The magnitude of this force was
less than that experienced during the cone and plate rheometer testing. Plate
gap for the parallel plate testing was 1000µm.
Preliminary testing with the parallel plates used varying amounts of lubricant.
Tests with lubricant volume approximately equal to the nominal gap volume
had lubricant roll up at the outer edge which decreased the contact surface
area. The roll up would begin at a location where slightly more lubricant had
flowed out. Tests with a full ring of excess lubricant did not display this
property and maintained a full contact area for the test duration.
All of the greases tested displayed thixotropic effects. The aluminium
complex based grease structure appeared to reform its structure. This
reversible structure effect was observed following an applied strain. In
contrast the lithium complex greases displayed high strain history dependent
behaviour.
217
5.7.4 ASTM D1092 Grease Pumpability
The results of this capillary rheology test, Figure 122, do not highlight any
great difference between lubricants. The consistency NLGI rating for these
lubricants is the same, which this test confirmed. This test may be important
for the implementation of lubrication systems in designing the pumping and
plumbing of lubricants but no wear performance criteria are discernable.
100 101 102 103 10410
0
101
102
103
Shear Rate (s-1)
App
aren
t Vis
cosi
ty (P
a.s)
Lubricant ALubricant BLubricant C
Figure 122 – ASTM D1092 Grease Pumpability results.
5.7.5 ASTM D2596 and ASTM D2266 Four Ball Tests
The lubricants under investigation were tested using ASTM D2596 and
ASTM D2266, the four ball tests of wear and extreme pressure properties.
The purpose of this testing was to determine the performance characteristics
of the lubricants, measured by standard lubricant testing, which indicates the
extreme pressure and wear characteristics. Lubricant A achieved marginally
better results in both the extreme pressure and wear testing. Figure 123 shows
Lubricant A to have a consistently smaller scar diameter over the load range.
218
Lubricant B had a smaller scar diameter than Lubricant C, except at the 200
kgf point, but the weld point is lower.
0 50 100 150 200 250 300 350 4000
0.5
1
1.5
2
2.5
3
Load (kgf)
Sca
r Dia
met
er (m
m)
Lubricant ALubricant BLubricant C
Figure 123 - ASTM D2596 Four ball wear test results.
219
Lubricant A Lubricant B Lubricant C0
50
100
150
200
250
300
350
400
450
500
550
Wel
d Lo
ad (k
gf)
Figure 124 – ASTM D2596 Weld load results.
Weld point results in Figure 124 identify Lubricants A and C as the best
performers. Lubricant B is two load steps below the others, and is probably a
result of the smaller solid lubricant volume in this lubricant type.
220
Lubricant A Lubricant B Lubricant C0
0.2
0.4
0.6
0.8
1
1.2
1.4S
car D
iam
eter
(mm
)
Figure 125 – ASTM D2266 Scar diameter results.
Figure 125 displays a similar trend in performance, as the simulated testing,
with Lubricant A having the smallest scar diameter in the wear testing and
Lubricant C the largest. The differences in performance may not be
significant and are not conclusive.
The quicker development of set tractive force in the simulated tests for
Lubricant C is related to transfer of input force to output force. The output
surface then experiences this force and accumulates wear damage. In the case
of ASTM D2266 there is no limit to the tractive force. The higher viscosity of
Lubricant C transfers a greater force, damaging the surfaces at a greater rate
than either Lubricants A and B, seen by the larger wear scar results. Design of
a rheology test to explore the high end of shear rates could assist in predicting
the energy transfer available for wear processes.
221
5.8 Summary
Prior to the presentation of the lubricant performance tests in this chapter the
input variables and corresponding stress values were presented for each of the
four test groups. The test groups were structured to investigate the effect of
changing a single input parameter on the lubricant performance of the three
rail curve lubricants tested.
The method used to isolate the effect of lubrication from the total system
effects was presented, detailing the values of micro-slip and absorbed power
that are used in the analysis of lubricant performance. In addition the same
method for predicting the steady state values of unlubricated absorbed power
and micro-slip is used to predict the decay in lubricant performance,
measured as a half-life. The half-life was defined as the time for sliding
performance (slip) to reduce by 50%.
Results of the half-life performance of the rail curve lubricants may not
provide an accurate measurement of the wear performance but assuming that
the presence of lubricant reduces wear, the best performance would arise
from the longest half-life.
The input parameters were measured for all groups of tests and the results of
the first test were presented to display the variability in the input parameters
of normal load, rolling velocity and limiting braking torque. Rolling velocity
had a low variability of approximately 0.1 km/hr. Normal load had a higher
variability resulting from thermal effects but was reasonably consistent
between tests. Braking torque variability arose from the continuing decay in
lubricant performance but was reasonable consistent between tests. Variability
in all input parameters was larger than the predicted experimental error in the
measurements of the input parameters.
Each group of tests were presented to define and identify the differences in
performance between rail curve lubricants. Results for each lubricant were
then collated to measure changes in performance with changes to input
222
parameters. Lubricant A outperformed Lubricant B and C under all test
conditions for total absorbed energy and total sliding distance, both
performance criteria important for rail and wheel wear reduction. Lubricant B
outperformed Lubricant A and C for half-life, except for Group 3 in which
Lubricant C was the best performer. Considering all performance criteria,
with equal weights for each, ranks the lubricants with Lubricant A first then
Lubricant B then Lubricant C.
Apparent viscosity versus time profiles were presented in this chapter to
display the decay in apparent viscosity with accumulated strain damage.
Lubricant A and C had similarly shaped apparent viscosity profiles, with
Lubricant C having a reduced accumulated strain capacity when compared to
Lubricant A. Lubricant B was observed to have a slower rate of decay of
lubricity than Lubricant A and C and had lower apparent viscosity at test
completion.
In addition to the measured results some experimental observations were
made. Different temperature profiles were measured for each lubricant, which
was the result of differing amounts of frictional energy being absorbed into
the rail and wheel samples. Rolling speed also affected the heat transfer
characteristics of the system, reduced rolling velocity decreased the heat
transfer coefficient and increased sample temperatures were observed.
Lubricant film failure was observed when fatigued material, wear particles,
became loose from the rail or wheel samples. The film failure was observed
by a removed ring of lubricating film. The development of these rings
influenced the test results by reducing the performance indicators.
Shear force control issues were presented. The shear force or braking torque
applied by the hydraulic dynamometer was influenced by viscosity changes in
the hydraulic oil. Temperature control of the hydraulic oil was employed to
control viscosity and was identified as an important control issue.
223
Temperature control was achieved with the newly designed and installed heat
exchanger.
Lubricating grease has a limited number of applicable standards based tests.
Results of the applicable tests, ASTM D1092, ASTM D2266, and ASTM
D2596 were presented. Lubricant performance differences between the rail
curve lubricants could be observed, but concerns with the resolution of
measurements and repeatability and reproducibility of the tests reduced the
level of confidence in the results. Wear performance in the standards based
tests matched the wear related performance criteria of absorbed energy and
sliding distance in the rail/wheel simulator testing with Lubricant A
performing better than Lubricant B which performed better than Lubricant
C. Rheology testing using ASTM D1092 and an Aries rheometer displayed
similar results to the apparent viscosity results from the rail/wheel simulator.
Simulated and standards based lubrication tests have been completed and
their results presented and discussed. The simulated results had a practical
outcome of the selection of a lubricating grease which is most suitable when
using three separate performance criteria. Standards based tests agreed with
this assessment but the confidence in measurements was low from poor
repeatability of results. Across all tests the limitations and practical
observations have been discussed with further recommendations in the
following chapter.
224
C h a p t e r 6
DISCUSSION, FUTURE WORK AND CONCLUSIONS
6.1 Introduction
Chapter 2 explored the issues surrounding rail/wheel lubrication and
provided an overview of methodologies for rail/wheel lubrication for in
service and simulated conditions. Chapter 3 presented a contact mechanics
method to present stress distributions for examples of in-service and
simulated conditions. These results highlight the similarities and differences
between the simulated and 'real world' conditions to gain an insight behind
the experimental methodology in Chapter 4. Chapter 4 details the
modifications to the simulator, formerly a device used for rail/wheel materials
investigations, to analyse a simulated lubricated gauge corner contact. Chapter
4 also included the method, measurements and measurement errors
associated with the experimental procedure. Chapter 5 presented all of the
experimental results from standards-based lubricant testing and compared
them to the results obtained from the simulated rail conditions. Finally, this
current chapter summarises the findings of the research, presents the
conclusions and discusses the possible directions of future work.
6.2 Discussion
The objective of this thesis was to quantify rail curve lubricant performance.
Theoretical and experimental methodologies were developed for use with a
rail/wheel simulator. The rail/wheel simulator that was acquired for this
research was modified and improved to measure slip accurately on a larger
than typical twin disk device which has the capacity to use a number of
sample shapes for the purpose of investigating different contact patches. The
effect of lubrication was investigated with high resolution slip measurements,
not previously possible in the work of Marich and Mutton (1989).
225
The work in this thesis has highlighted the performance difference under
simulated conditions between lubricants designed for the rail industry and has
demonstrated the requirement for more specific parameters to be targeted by
lubricant manufacturers. This research has also highlighted the need for
lubricant suppliers and customers to identify performance requirements and
the methods of achieving them with lubricant ingredients with a more
transparent information sharing process.
Standard lubricant tests, such as those from ASTM provide inadequate
information for rolling stock and rail infrastructure managers to make
informed decisions as to which lubricant to use. The standards based testing
present results which may not be relevant to rail curve lubrication, whereas
the rail/wheel simulator gives results for performance criteria that are relevant
to rail curve lubrication. Performing a group of tests such as those presented
in this research can highlight advantages and deficiencies in a range of contact
conditions that standards based testing cannot achieve.
Possible improvements to current rail lubricant tests include the specification
of strain history at a particular strain rate from a standard twin disk test device
such as an Amsler machine. This value of strain history could be calculated
from a survey of the rail network using the common length of curves in
combination with rail profiles to give a representative slip value. The
specification of absorbed energy could be substituted for strain history or
made an additional criterion.
The twin disk tests would require specified input parameters of compressive
stress to match the loading regime of the rail network, rolling speed to match
typical cornering speed, and temperature to match the expected
environmental conditions. Using this type of laboratory simulator it would be
possible and useful to perform the tests at a range of strain rates or slip to
characterise the lubricant for most conditions experienced in the gauge
226
corner. The work presented in this thesis tested across a range of slip
conditions but the focus was on investigating limiting shear stress conditions.
Another suitable parameter to be included in lubricant specifications is
apparent viscosity. Limits of this value at nominated shear rates could reduce
the shear force transmission between contact surfaces. Fatigue related wear,
which is dependent upon shear stress, could be reduced using this method.
Tractive effort and fuel consumption may also be reduced through the
specification of apparent viscosity. Savings through lubrication have already
been identified (Clayton 1996) and increased savings may be possible using
the apparent viscosity testing method.
The predictions of half life are sensitive to the errors in the final value of slip.
These errors are dependent upon the temperature of test pieces, which is
dependent upon the number of samples taken after the set traction force is
reached. In the calculations of half life the offset coefficient is representative
of the thermal expansion error. Therefore to reduce the offset coefficient,
sufficient samples after the frictional power has reduced below the convective
power losses must be allowed for the test piece temperatures to stabilise as
near to unlubricated conditions as possible.
Observing that the decay in measured slip is the result of two processes, decay
of lubricant film and decay of sample temperature, the prediction of half life
could be improved by modelling each of these processes. Taking each of
these components as having an exponential decay gives Equation (6.1)
measured slip ratio, , , regression coefficients
bt dtae ce
a b c d
ξξ
− −= +=
= (6.1)
Using this model to perform a regression analysis of the slip gives a higher
correlation coefficient than the single exponential problem. A difficulty with
using this model is that there is no method of differentiating between the
227
effects of thermal expansion and lubricant film decay. The error analysis for
thermal expansion of the test pieces shows that the component of slip from
thermal expansion becomes small, rapidly leaving only the lubricant film
decay component.
Relating the half life predictions to the field is somewhat difficult. The
simulator test failure criteria is the reaching of a set tractive force, whereas the
field lubricant film failure criteria is that there is no lubricant remaining on the
rail. Considering the magnitude of wear in each case, for the simulator the
wear is negligible as the lubricant film still exists, for the field, wear is
considerable as the protective film has been totally removed. Simulator test
conditions therefore are not representative of the field situation in this aspect
but do represent the desired level of lubrication from an industry view point.
The slip calculation/measurement taken by the simulator is not affected by
film thickness which allows for the estimation of film thickness as the
magnitude of the value of film thickness will always reach zero despite
calibration or measurement errors. Film thickness is not required to be
specified but sliding distance is required. For a lubricant manufacturer, the
higher the film thickness there is a correspondingly smaller shear rate.
6.3 Future Work
Further work is required to set a final slip value that must be reached to
improve comparisons between lubricants. Modelling the half-life of a rail
curve lubricant could be improved by setting a final slip value to end the test,
which would result in eliminating the offset coefficient in the regression
equation. A dual exponential term equation was explored to account for the
two effects of lubricant film decay and thermal changes. The statistical
difference between the two regression models was small but observable.
However, the dual exponential model was unsuitable for predicting the time
to lubricant failure.
228
The rail/wheel simulator cannot control shearing force and shear strain rate
simultaneously. This research focussed on testing to a maximum shearing
force, in this case a set braking torque, for the duration of testing to monitor
the slip under varying loading conditions. A control system monitoring the
inputs to shearing force would be required, controlling the hydraulic
dynamometer and pneumatic ram, in order to achieve simultaneous control of
the shearing force and the shear strain rate.
A design for slip control was proposed and installed to the dynamometer
system to simultaneously control shear force and shear strain. In place of
controlling pressure alone, a dual control, flow and pressure system was
installed. The flow control has the effect of limiting the maximum slip
conditions experienced during the test. This modification was completed for
the purposes of future research and is yet to be fully validated.
Wider simulation could be achieved with different contact patch shapes. This
could be investigated further to model more closely the lubrication transport
mechanisms. Of particular interest is decreasing the contact width to increase
the maximum contact pressure, and change the contact shape using curved
surface samples. At this point the simulator is incapable of generating
pressures that are as high as the maximum in-service contact pressures
presented in Section 0. Modification of the simulator to allow assessment of
lubricant performance with in-service contact pressures approaching the
maximum attainable values would be a valuable improvement to the
rail/wheel simulator.
Wear of the samples was not measured as full lubricant film was maintained
throughout testing. Detecting wear by changes in profile geometry is
impossible for tests of limited duration therefore a mass loss method is
required. It was determined that a mass comparator was required to measure
at the specified resolution as conventional weighing devices are three orders
of magnitude of precision deficient. Due to the limitations in obtaining the
229
use of a commercial mass comparator, a novel inexpensive design was carried
out. The design, and results when carried out, will be published as work
ancillary to this project.
6.4 Conclusions
The objective of this research was to quantify rail curve lubricant performance
through laboratory simulation. The steps to achieve the objective of this
thesis were:
Quantified the performance of the typical rail curve lubricants using standard tests.
The lubricants have been laboratory tested to define the properties using the
ASTM and other appropriate standards. The lubricants were laboratory tested
to define the properties using the ASTM and other appropriate standards.
Information was gathered from both literature and field personnel as to the
performance properties of the lubricants. The results were inconclusive from
the standards based tests as to which lubricant was the best performer. The
performance differences measured were susceptible to repeatability problems
and did not represent the in-service conditions as accurately as the rail/wheel
simulator.
Quantified the contact mechanics of field and simulated conditions.
A literature survey was carried out to identify the methodologies employed to
measure and predict the rail/wheel contact. Upon review, a suitable method
for predicting the contact conditions was selected and used to analyse the
laboratory simulation device and representative in-service conditions. The
method was computerised and the software validated. The software will be
useful for all contact mechanics analysis especially for further rail curve
lubrication research.
Identified the wear mechanisms at the wheel and rail gauge face for the purpose of matching the simulator to field conditions.
230
The primary focus of this project was on optimisation of the lubrication in a
rail gauge corner contact and as such this objective was not explored in great
depth. The wear mechanisms were predicted using the parameters of the
contact and comparison with the body of literature. Wear particles were
gathered and inspected to assist in verifying the wear mechanism or
mechanisms identified and the simulator was confirmed as having the same
wear characteristics as the field. This work has demonstrated that the
simulator is capable of exploring wear mechanisms and generates wear typical
of rail/wheel contacts.
Quantified the effect of lubrication.
The laboratory simulator was used to gather data in lubricated and
unlubricated conditions for the purpose of providing lubricant performance
measurements. Analysis of the results from the lubricant testing and
laboratory simulators was carried out to determine trends between them.
These trends indicate performance differences between lubricants. The results
for the lubricants presented here also show that a single value for ranking a
lubricants performance is yet to be achieved, but using a number of criteria a
lubricant can be ranked quantitatively. Using the lubricant performance
measurements the tested lubricants were ranked conclusively with three
innovative industrially relevant performance criteria.
The outcome for the use of this thesis is to provide a method of quantitatively
ranking wheel/rail flange lubricants. However, to achieve performance
ranking with industrial relevance, correlation with field data must be carried
out. Despite the lack of correlation in this thesis the performance criteria
presented are relevant to field conditions. Accuracy of the contact stresses in
the rail/wheel simulator give credence to the results of lubricant performance
presented.
The unique contributions to rail curve lubricant research include the
development of a prediction model of lubricant half life under simulated
231
conditions. Lubricant half life represents the decay of lubricant performance
under a set shear stress level. Half life prediction is a relevant performance
criterion and research output for industry. Following correlation with field
results, the half life performance criterion will allow for improved lubricant
design and better placement of lubricators and the associated benefits of
improving the lubrication system.
Another significant contribution unique to the body of rail curve lubricant
research is the measurement of apparent viscosity of lubricating grease using a
twin-disk simulator. Measurement of the rheological development of a rail
curve lubricant using the rail/wheel simulator will assist in the design of
lubricants to achieve the performance requirements of the rail industry.
Rheological development is directly related to the tractive effort and
fuel/energy consumption of the locomotive, which is of great interest to the
rail industry.
The lubricating capacity of rail curve lubricants was defined and measured in
this thesis as total absorbed energy and total sliding distance. Total absorbed
energy is important to the rail industry for the purpose of reducing the
frictional energy and wear from flange contact. Increased energy capacity
translates to less energy available for wear processes. Total sliding distance is
important to the rail industry for the purpose of obtaining maximum
lubricating capacity from each lubrication system. Greater measured total
sliding distance translates to improved lubricant performance by increasing
the lubricating capacity of the rail curve lubricant. Applying total absorbed
energy and total sliding distance performance criteria to rail curve lubricant
specifications will improve the outcomes for the rail industry.
To summarise, new methods for rail curve lubricant performance
measurement have been presented. These performance measurements are
total absorbed energy, the energy absorbed in the lubricant film instead of
being utilised for wear processes; total distance slid, the sliding distance or
232
accumulated strain achieved prior to development of a set tractive force limit;
half life of lubricant, the time taken for a lubricant to lose half of its sliding
performance; and apparent viscosity, a measure of the lubricity presented with
respect to accumulated strain. Using the new method of lubricant
performance measurement the objective of this research to quantify rail curve
lubricant performance through laboratory simulation has been achieved.
233
REFERENCES
ASTM, I. (1991). ASTM D 2266-91 Standard Test Method for Wear Preventive Characteristics of Lubricating Grease.
ASTM, I. (1997). ASTM D 2596-97 Standard Test Method for Measurement of Extreme-Pressure Properties of Lubricating Grease (Four-Ball Method). ASTM International.
ASTM, I. (1999). ASTM D 1092-99 Standard Test Method for Measuring Apparent Viscosity of Lubricating Greases. ASTM International.
Automation Creations, I. (2005a). AISI 1070 Steel, hot rolled, 19-32 mm (0.75-1.25 in) round. http://www.matweb.com/search/SpecificMaterial.asp?bassnum=M1070B
Automation Creations, I. (2005b). AISI 1080 Steel, as rolled. http://www.matweb.com/search/SpecificMaterial.asp?bassnum=M1080G
Bailey, C.A., Association of Iron and Steel Engineers. (1996). The lubrication engineers manual. 2nd ed. Pittsburgh, Pa., Association of Iron and Steel Engineers.
Beynon, J.H., Kapoor, A., Tyfour, W.R. (1996). Deterioration of rolling contact fatigue life of pearlitic rail steel due to dry-wet rolling-sliding line contact. Wear 197(1-2): 255-65.
Bolton, P.J., Clayton, P. (1984). Rolling--sliding wear damage in rail and tyre steels. Wear 93(2): 145.
Boresi, A.P., Schmidt, R.J. (2003). Advanced mechanics of materials. 6th ed. ed. New York, John Wiley & Sons.
Bowden, F.P., Tabor, D. (2001). The friction and lubrication of solids. Oxford
New York, Clarendon Press Oxford University Press. Bower, A.F. (1988). The Influence Of Crack Face Friction And Trapped
Fluid On Surface Initiated Rolling-Contact Fatigue Cracks. Journal Of Tribology-Transactions Of The Asme 110(4): 704-11.
Bruni, S., Collina, A., Diana, G. (2000). Wheel-rail Contact Models For The Simulation of Rail Vehicle Dynamics - A Survey. AIMETA International Tribology Conference, L'Aquila, Italy.
Byrd, P.F., Friedman, M.D. (1971). Handbook of elliptic integrals for engineers and scientists. 2d ed., rev. ed. Berlin; New York, Springer-Verlag.
Clayton, P. (1995). Predicting the wear of rails on curves from laboratory data. Wear 181-183(1): 11.
234
Clayton, P. (1996). Tribological aspects of wheel-rail contact: A review of recent experimental research. Wear 191(1-2): 170-83.
Clayton, P., Danks, D., Steele, R. (1988). Laboratory Assessment of Lubricants for Wheel/Rail Applications. Lubrication Engineering 45(8): 501-6.
Clayton, P., Reiff, R., Steele, R. (1989). Wheel/Rail Lubricant Performance: In-Track and Laboratory Test Comparisons. The Fourth International Heavy Haul Conference, Brisbane, Queensland, Australia.
Clayton, P., Su, X. (1996). Surface initiated fatigue of pearlitic and bainitic steels under water lubricated rolling/sliding contact. Wear 200(1-2): 63-73.
Deters, L., Proksch, M. (2005). Friction and wear testing of rail and wheel material. Wear 258(7-8): 981-91.
Ekberg, A., Kabo, E. (2005a). Fatigue of railway wheels and rails under rolling contact and thermal loading--an overview. Wear
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1288-300. Ekberg, A., Kabo, E. (2005b). Fatigue of railway wheels and rails under
rolling contact and thermal loading-an overview. Wear 258(7-8): 1288-300.
ESDU (1984). Contact Phenomena II: Stress Fields and Failure Criteria in Concentrated Elastic Contact Under Combine Normal and Tangential Loading. Item No. 84017. ESDU International.
ESDU (1994). Contact Phenomena III: Calculation of Individual Stress Components in Concentrated Elastic Contacts Under Combine Normal and Tangential Loading. Item No. 85007. ESDU International, London.
ESDU (1995). Contact Phenomena. I: Stresses Deflections and Contact Dimensions for Normally-loaded Unlubricated Elastic Components. Item No. 78035. ESDU International.
Fletcher, D.I., Beynon, J.H. (2000). The effect of contact load reduction on the fatigue life of pearlitic rail steel in lubricated rolling-sliding contact. Fat Frac Eng Mat Struct 23(8): 639-50.
Frank, E.E. (1981). Locations of Lubricators. First Rail and Wheel Symposium, Memphis TN, USA.
Franklin, F.J., Weeda, G.J., Kapoor, A., Hiensch, E.J.M. (2005). Rolling contact fatigue and wear behaviour of the InfraStar 2-material rail. Wear 258(7-8): 1048-54.
Giancoli, D.C. (1988). Physics For Scientists and Engineers With Modern Physics. Prentice-Hall International.
Hamrock, B.J. (1994). Fundamentals of Fluid Film Lubrication. McGraw Hill Book Co.
Hannafious, J.H. (1995). Results of rail wear test at FAST, Volume 1: FAST/HAL test summaries. AAR Research Review.
235
Hertz, H. (1882). On The Contact of Elastic Solids. J. reine und angewandte Mathematik 92: 156-71.
Holman, J.P. (1997). Heat transfer. 8th ed. ed. New York, McGraw-Hill Companies.
Huq, M.Z., Celis, J.-P. (2002). Expressing wear rate in sliding contacts based on dissipated energy. Wear 252(5-6): 375-83.
International Heavy Haul Association (2001). Guidelines to Best Practices for Heavy Haul Railway Operations: Wheel and Rail Interface Issues. International Heavy Haul Association.
Ishida, M., Abe, N. (1996). Experimental study on rolling contact fatigue from the aspect of residual stress. Wear 191(1-2): 65.
Jendel, T. (1999). Prediction of Wheel and Rail Wear - A Pilot Study. TRITA - FKT Report 1999:03. Railway Technology, Department of Vehicle Engineering, Royal Institute of Technology, Stockholm. 50
Johnson, K.L. (1985). Contact mechanics. Cambridge [Cambridgeshire]; New York, Cambridge University Press.
Kalker, J.J. (1990). Three-dimensional elastic bodies in rolling contact. Dordrecht, Netherlands, Kluwer Academic.
Kalousek, J., Magel, E., Strasser, J., Caldwell, W.N., Kanevsky, G., Blevins, B. (1996). Tribological interrelationship of seasonal fluctuations of freight car wheel wear, contact fatigue shelling and composition brakeshoe consumption. Wear 191(1-2): 210.
Kik, W., Piotrowski, J. (1996). A fast approximate method to calculate normal load at contact between wheel and rail and creep forces during rolling. 2nd Mini-conference on Contact Mechanics and Wear of Rail-Wheel Systems.
Kondo, K., Yoroizaka, K., Sato, Y. (1996). Cause, increase, diagnosis, countermeasures and elimination of Shinkansen shelling. Wear 191(1-2): 199.
Kuhn, E. (1995). Description of the energy level of tribologically stressed greases. Wear 188(1-2): 138.
Kuhn, E., Balan, C. (1997). Experimental procedure for the evaluation of the friction energy of lubricating greases. Wear 209(1-2): 237-40.
Kumar, S., McDuff, P.J., Witte, A.C., McInerney, D.G. (1991). Development of a Laboratory Test for Rail Lubricants. NLGI 58th Annual Meeting, Phoenix, Arizona, USA.
Lee, K.M., Polycarpou, A.A. (2005). Wear of conventional pearlitic and improved bainitic rail steels. Wear 259(1-6): 391.
Lewis, R., Dwyer-Joyce, R.S. (2004). Wear mechanisms and transitions in railway wheel steels. Proceedings of the Institution of Mechanical Engineers, Part J: Journal of Engineering Tribology 218(6): 467-78.
Lewis, R., Olofsson, U. (2004). Mapping rail wear regimes and transitions. Wear 257(7-8): 721.
236
Lim, S.C., Ashby, M.F. (1986). Wear-Mechanism Maps. CUED/C-mat./TR.123. Cambridge University Engineering Department, Cambridge. 88
Marich, S., Kerr, M., Fogarty, R. (2001a). Optimising Trackside Lubrication for the Wheel/Rail System. RTA Conference.
Marich, S., Mackie, S., Fogarty, R. (2000). The Optimisation of Rail/Wheel Lubrication Practice in the Hunter Valley. RTSA Technical Conference CORE, Adelaide.
Marich, S., Mackie, S., Hill, I. (2001b). The Management of Wheel/Rail Interaction in the High Axle Load Coal Lines of the Hunter Valley. Heavy Haul Conference, Brisbane.
Marich, S., Mutton, P.J. (1989). An Investigation of Severe Wear Under Rolling/Sliding Contact Conditions Existing in Heavy Haul Railways. 7th International Wheelset Conference, Vienna.
Markov, D. (1995). Laboratory tests for wear of rail and wheel steels. Wear 181-183(Part 2): 678-86.
Mulvihill, M.A., Witte, A.C., Kumar, S. (1994). A New Approach to Wheel/Rail Lubrication. NLGI 61st Annual Meeting, Rancho Mirage, California, USA, NLGI (National Lubricating Grease Institute).
Nilsson, R. (2002). Rail Wear Development - Measurements and Evaluation. TRITA - FKT Report 2002:22. Railway Technology, Department of Vehicle Engineering, Royal Institute of Technology, Stockholm. 52
Nolan, S.J. (~2000). The Use of a Controlled Stress Rheometer to Evaluate the Rheological Properties of Grease. 0213. National Lubricating Grease Institute.
O'Rourke, M.D., Johnston, G., Ruvidini, A., Hagaman, B. (1989). Australian Road-Rail Lubrication Tests. The Fourth International Heavy Haul Railway Conference, Brisbane, Queensland, Australia.
Olofsson, U., Telliskivi, T. (2003). Wear, plastic deformation and friction of two rail steels--a full-scale test and a laboratory study. Wear 254(1-2): 80-93.
Pascal, J.P. (1993). About multi-hertzian contact hypothesis and equivalent conicity in the case of S1002 and UIC analytical wheel/rail profiles. Vehicle System Dynamics 22: 57-8.
Polishuk, A.T. (1998). A Brief History or Lubricating Greases. Llewellyn &McKane, Inc.
Quinn, T.F.J. (1991). Physical analysis for tribology. Cambridge; New York, Cambridge University Press.
Reiff, R. (1986). Rail/Wheel Lubrication Studies at FAST. Journal of the American Society of Lubrication Engineers 42(6): 340-9.
Sato, Y. (2005). Historical study on designing Japanese rail profiles. Wear 258(7-8): 1064-70.
237
Scott, W., Mercer, T., Donelan, J. (1998). Laboratory Evaluation of Rail/Wheel Lubricants/Friction Modifiers. Austrib '98 - Tribology at Work, Brisbane, Queensland Australia, The Institution of Engineers Australia.
Shen, Z.Y., Hedrick, J.K., Elkins, J.A. (1983). A comparison of alternative creep force models for rail vehicle dynamic analysis. 16th IA VSD Symp, Cambridge MA.
Thelen, G., Lovette, M. (1996). A parametric study of the lubrication transport mechanism at the rail-wheel interface. Wear 191(1-2): 113-20.
Tyfour, W.R., Beynon, J.H., Kapoor, A. (1995). The steady state wear behaviour of pearlitic rail steel under dry rolling-sliding contact conditions. Wear 180(1-2): 79-89.
Waara, P. (2001). Lubricant influence on flange wear in sharp railroad curves. Industrial Lubrication and Tribology 52(4): 161-8.
Witte, A.C., Kumar, S. (~1986). Design and Laboratory Testing of Rail Lubricants.
Yonggang, M., Jie, Z. (1998). A rheological model for lithium lubricating grease. Tribology International 31(10): 619-25.
238
BIBLIOGRAPHY
Adachi, K., Hutchings, I.M. (2003). Wear-mode mapping for the micro-scale
abrasion test. Wear 255(1-6): 23-9.
Afferrante, L., Ciavarella, M., Demelio, G. (2004). A re-examination of rolling
contact fatigue experiments by Clayton and Su with suggestions for
surface durability calculations. Wear 256(3-4): 329-34.
Ahlstroem, J., Karlsson, B. (2005). Fatigue behaviour of rail steel - a
comparison between strain and stress controlled loading. Wear 258(7-
8): 1187-93.
Ahlstrom, J., Karlsson, B. (2005). Fatigue behaviour of rail steel--a
comparison between strain and stress controlled loading. Wear 258(7-
8): 1187-93.
Akama, M., Mori, T. (2002). Boundary element analysis of surface initiated
rolling contact fatigue cracks in wheel/rail contact systems. Wear
253(1-2): 35-41.
Allen, P.D. (2000). The critical speed of a railway vehicle on a roller rig.
Proceedings of the Institution of Mechanical Engineers 215(2): 55.
Allwood, J., Ciftci, H. (2005). An incremental solution method for rough
contact problems. Wear 258(11-12): 1601-15.
Alwahdi, F., Franklin, F.J., Kapoor, A. (2005). The effect of partial slip on the
wear rate of rails. Wear 258(7-8): 1031-7.
ASTM, I. (1991). ASTM D 2266-91 Standard Test Method for Wear
Preventive Charateristics of Lubricating Grease.
239
ASTM, I. (1997). ASTM D 2596-97 Standard Test Method for Measurement
of Extreme-Pressure Properties of Lubricating Grease (Four-Ball
Method). ASTM International.
ASTM, I. (1999). ASTM D 1092-99 Standard Test Method for Measuring
Apparent Viscosity of Lubricating Greases. ASTM International.
Atzori, B., Meneghetti, G., Susmel, L. (2005). Material fatigue properties for
assessing mechanical components weakened by notches and defects.
Fatigue & Fracture of Engineering Materials and Structures 28(1-2): 83-97.
Automation Creations, I. (2005a). AISI 1070 Steel, hot rolled, 19-32 mm
(0.75-1.25 in) round.
http://www.matweb.com/search/SpecificMaterial.asp?bassnum=M1070B
Automation Creations, I. (2005b). AISI 1080 Steel, as rolled.
http://www.matweb.com/search/SpecificMaterial.asp?bassnum=M1080G
Bailey, C.A., Association of Iron and Steel Engineers. (1996). The lubrication
engineers manual. 2nd ed. Pittsburgh, Pa., Association of Iron and
Steel Engineers.
Bailey, W.J., Weir, I.S. (1998). Investigation of methods for direct rheological
model parameter estimation. Journal of Petroleum Science and Engineering
21(1-2): 1-13.
Ben Cheikh Larbi, A., Cherif, A., Tarres, M.A. (2005). Improvement of the
adhesive wear resistance of steel by nitriding quantified by the energy
dissipated in friction. Wear 258(5-6): 712-8.
Bernasconi, A., Davoli, P., Filippini, M., Foletti, S. (2005). An integrated
approach to rolling contact sub-surface fatigue assessment of railway
wheels. Wear
240
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 973-80.
Bernasconi, A., Filippini, M., Foletti, S., Vaudo, D. (2006). Multiaxial fatigue
of a railway wheel steel under non-proportional loading. International
Journal of Fatigue 28(5-6): 663-72.
Beynon, J.H., Kapoor, A., Tyfour, W.R. (1996). Deterioration of rolling
contact fatigue life of pearlitic rail steel due to dry-wet rolling-sliding
line contact. Wear 197(1-2): 255-65.
Blau, P.J. (1989). Friction and wear transitions of materials: break-in, run-in,
wear-in. Park Ridge, N.J., U.S.A, Noyes Publications.
Bogdanski, S. (2005). Liquid-solid interaction at opening in rolling contact
fatigue cracks. Wear
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1273-9.
Bogdanski, S., Brown, M.W. (2002). Modelling the three-dimensional
behaviour of shallow rolling contact fatigue cracks in rails. Wear
253(1-2): 17-25.
Bogdanski, S., Lewicki, P., Szymaniak, M. (2005). Experimental and
theoretical investigation of the phenomenon of filling the RCF crack
with liquid. Wear
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1280-7.
Bogdanski, S., Stupnicki, J., Brown, M.W., Cannon, D.F. (1999). A two
dimensional analysis of mixed-mode rolling contact fatigue crack
growth in rails. ESIS Publication 25(Multiaxial Fatigue and Fracture):
235-48.
241
Bolton, P.J., Clayton, P. (1984). Rolling--sliding wear damage in rail and tyre
steels. Wear 93(2): 145.
Boresi, A.P., Schmidt, R.J. (2003). Advanced mechanics of materials. 6th ed. ed.
New York, John Wiley & Sons.
Bowden, F.P., Tabor, D. (2001). The friction and lubrication of solids.
Oxford
New York, Clarendon Press
Oxford University Press.
Bower, A.F. (1988). The Influence Of Crack Face Friction And Trapped
Fluid On Surface Initiated Rolling-Contact Fatigue Cracks. Journal Of
Tribology-Transactions Of The Asme 110(4): 704-11.
Bruni, S., Collina, A., Diana, G. (2000). Wheel-rail Contact Models For The
Simulation of Rail Vehicle Dynamics - A Survey. AIMETA
International Tribology Conference, L'Aquila, Italy.
Bruzelius, K., Mba, D. (2004). An initial investigation on the potential
applicability of Acoustic Emission to rail track fault detection. NDT
and E International 37(7): 507-16.
Byrd, P.F., Friedman, M.D. (1971). Handbook of elliptic integrals for
engineers and scientists. 2d ed., rev. ed. Berlin; New York, Springer-
Verlag.
Chang, L.C. (2005). The rolling/sliding wear performance of high silicon
carbide-free bainitic steels. Wear 258(5-6): 730-43.
242
Chen, H., Ishida, M., Nakahara, T. (2005). Analysis of adhesion under wet
conditions for three-dimensional contact considering surface
roughness. Wear 258(7-8): 1209-16.
Chen, Y.-t., Liu, D.-y., Fang, H.-s., Bai, B.-z. (2000). Rolling contact fatigue of
rail steel. Gangtie Yanjiu Xuebao 12(5): 50-3.
Chevalier, L., Cloupet, S., Soize, C. (2005). Probabilistic model for random
uncertainties in steady state rolling contact. Wear 258(10): 1543-54.
Clayton, P. (1995). Predicting the wear of rails on curves from laboratory data.
Wear 181-183(1): 11.
Clayton, P. (1996). Tribological aspects of wheel-rail contact: A review of
recent experimental research. Wear 191(1-2): 170-83.
Clayton, P., Danks, D., Steele, R. (1988). Laboratory Assessment of
Lubricants for Wheel/Rail Applications. Lubrication Engineering 45(8):
501-6.
Clayton, P., Jin, N. (1996). Unlubricated sliding and rolling/sliding wear
behavior of continuously cooled, low/medium carbon bainitic steels.
Wear 200(1-2): 74-82.
Clayton, P., Reiff, R., Steele, R. (1989). Wheel/Rail Lubricant Performance:
In-Track and Laboratory Test Comparisons. The Fourth International
Heavy Haul Conference, Brisbane, Queensland, Australia.
Clayton, P., Su, X. (1996). Surface initiated fatigue of pearlitic and bainitic
steels under water lubricated rolling/sliding contact. Wear 200(1-2):
63-73.
Committee., A.I.H. (1992.). ASM handbook. Volume 18. Friction, lubrication
and wear technology. (Materials Park, Ohio), ASM International.
243
Decuzzi, P., Demelio, G. (2002). The effect of material properties on the
thermoelastic stability of sliding systems. Wear 252(3-4): 311-21.
Degaspari, J. (2001). Silencing the screech of wheel on rail. Engineering World.
11.
Denis, J., Briant, J., Hipeaux, J.-C., Institut Français du Pétrole Publications.
(2000). Lubricant properties analysis & testing. Paris, Editions
Technip.
Descartes, S., Desrayaud, C., Niccolini, E., Berthier, Y. (2005). Presence and
role of the third body in a wheel-rail contact. Wear 258(7-8): 1081-90.
Deters, L., Proksch, M. (2005). Friction and wear testing of rail and wheel
material. Wear 258(7-8): 981-91.
Donzella, G., Faccoli, M., Ghidini, A., Mazzu, A., Roberti, R. (2005). The
competitive role of wear and RCF in a rail steel. Engineering Fracture
Mechanics 72(2): 287.
Doquet, V., Pommier, S. (2004). Fatigue crack growth under non-
proportional mixed-mode loading in ferritic-pearlitic steel. Fatigue &
Fracture of Engineering Materials & Structures 27(11): 1051-60.
Duart, J.M., Pero-Sanz, J.A., Verdeja, J.I. (2005). Rails for high-speed trains.
Fatigue behavior. Revista de Metalurgia (Madrid, Spain) 41(1): 66-72.
Eden, H.C., Garnham, J.E., Davis, C.L. (2005). Influential microstructural
changes on rolling contact fatigue crack initiation in pearlitic rail
steels. Materials Science and Technology 21(6): 623-9.
Ekberg, A., Kabo, E. (2005). Fatigue of railway wheels and rails under rolling
contact and thermal loading--an overview. Wear Contact Mechanics and
Wear of Rail/Wheel Systems 258(7-8): 1288-300.
244
Enblom, R., Berg, M. (2005). Simulation of railway wheel profile development
due to wear--influence of disc braking and contact environment. Wear
258(7-8): 1055-63.
Epp, C.J. (1992). Wheel-Rail Lubrication and Alternative Technologies. NInth
International Rail Track Conference, Perth, Australia.
Epp, C.J., O'Rourke, M.D. (1989). Wheel/Rail Profiling and Lubrication.
Fourth International Heavy Haul Railway Conference, Brisbane, Australia.
Ertz, M. (2002). Creep Force Laws for Wheel/Rail Contact with
Temperature-Dependent Coefficient of Friction.
ESDU (1984). Contact Phenomena II: Stress Fields and Failure Criteria in
Concentrated Elastic Contact Under Combine Normal and
Tangential Loading. Item No. 84017. ESDU International.
ESDU (1994). Contact Phenomena III: Calculation of Individual Stess
Components in Concentrated Elastic Contacts Under Combine
Normal and Tangential Loadin. Item No. 85007. ESDU International,
London.
ESDU (1995). Contact Phenomena. I: Stresses Deflections and Contact
Dimensions for Normally-loaded Unlubricated Elastic Components.
Item No. 78035. ESDU International.
Esteban Fernandez, J., del Rocio Fernandez, M., Vijande Diaz, R., Tucho
Navarro, R. (2003). Abrasive wear analysis using factorial experiment
design. Wear 255(1-6): 38-43.
Fletcher, D.I., Beynon, J.H. (2000). The effect of contact load reduction on
the fatigue life of pearlitic rail steel in lubricated rolling-sliding contact.
Fat Frac Eng Mat Struct 23(8): 639-50.
245
Fletcher, D.I., Franklin, F.J., Kapoor, A. (2003). Image analysis to reveal crack
development using a computer simulation of wear and rolling contact
fatigue. Fatigue & Fracture of Engineering Materials and Structures 26(10):
957-67.
Frank, E.E. (1981). Locations of Lubricators. First Rail and Wheel Symposium,
Memphis TN, USA.
Franklin, F.J., Chung, T., Kapoor, A. (2003). Ratcheting and fatigue-led wear
in rail-wheel contact. Fat Frac Eng Mat Struct 26(10): 949-55.
Franklin, F.J., Weeda, G.-J., Kapoor, A., Hiensch, E.J.M. (2005a). Rolling
contact fatigue and wear behaviour of the infrastar two-material rail.
Wear Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1048-
54.
Franklin, F.J., Weeda, G.J., Kapoor, A., Hiensch, E.J.M. (2005b). Rolling
contact fatigue and wear behaviour of the InfraStar 2-material rail.
Wear 258(7-8): 1048-54.
Fridberg, A.M. (2005). Theory of friction and oscillation of two elastic bodies
in contact and its application to differential rotation of railw ay wheel
treads. Wear 258(7-8): 1091-9.
Galtier, A., Bettembourg, J.P., Perrin, J.L., Joeller, A., Coppola, T.,
Notargiacomo, S., Grijalvo, J. (2004). Contact fatigue of rails under
severe conditions. IRSID,Maizieres-les-Metz,Germany. 1-367
Gates, J.D., Gore, G.J. (1995). Wear of Metals: Philosophies and Practicalities.
Materials Forum 19: 53-89.
Giancoli, D.C. (1988). Physics For Scientists and Engineers With Modern
Physics. Prentice-Hall International.
246
Gladwell, G.M.L. (1980). Contact problems in the classical theory of elasticity.
Alphen aan den Rijn, The Netherlands, Sijthoff & Noordhoff.
Gomez, I., Vadillo, E.G. (2003). A linear model to explain short pitch
corrugation on rails. Wear 255(7-12): 1127-42.
Goryacheva, I.G. (1998). Contact mechanics in tribology. Dordrecht Boston
London, Kluwer Academic Publishers.
Goryacheva, I.G., Goryachev, A.P., Sadegi, F. (1995). Contact of elastic
bodies with thin visco-elastic coatings under conditions of rolling or
sliding friction. Journal of Applied Mathematics and Mechanics 59(4): 607-
14.
Grassie, S., Nilsson, P., Bjurstrom, K., Frick, A., Hansson, L.G. (2002).
Alleviation of rolling contact fatigue on Sweden's heavy haul railway.
Wear 253(1-2): 42-53.
Grassie, S.L. (1991). Mechanics and fatigue in wheel/rail contact: proceedings
of the Third International Conference on Contact Mechanics and
Wear of Rail/Wheel Systems, Cambridge, U.K. July 22-26, 1990.
Amsterdam New York, Elsevier.
Grassie, S.L. (2005). Rolling contact fatigue on the British railway system:
treatment. Wear
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1310-8.
Grassie, S.L., Elkins, J.A. (2005). Tractive effort, curving and surface damage
of rails: Part 1. Forces exerted on the rails. Wear 258(7-8): 1235-44.
Grohmann, H.-D., Schoech, W. (2002). Contact geometry and surface fatigue
- minimizing the risk of headcheck formation. Wear 253(1-2): 54-9.
247
Guduru, R.K., Darling, K.A., Kishore, R., Scattergood, R.O., Koch, C.C.,
Murty, K.L. (2005). Evaluation of mechanical properties using shear-
punch testing. Materials Science and Engineering A 395(1-2): 307-14.
Guicciardi, S., Melandri, C., Lucchini, F., de Portu, G. (2002). On data
dispersion in pin-on-disk wear tests. Wear 252(11-12): 1001-6.
Gunsel, S., Korcek, S., Smeeth, M., Spikes, H.A. (1999). Elastohydrodynamic
friction and film forming properties of lubricant base oils. Tribology
Transactions 42(3): 559-69.
Hamrock, B.J. (1994). Fundamentals of Fluid Film Lubrication. McGraw Hill
Book Co.
Hancock, H. (1958). Elliptic integrals. New York, Dover.
Hannafious, J.H. (1995). Results of rail wear test at FAST, Volume 1:
FAST/HAL test summaries. AAR Research Review.
Hansen, J., Calvert, J. (2003). Eddy current testing: a solution to detecting
rolling contact fatigue in rail. Proceedings - Corrosion & Prevention: Paper
54/1-Paper /9.
Hertz, H. (1882). On The Contact of Elastic Solids. J. reine und angewandte
Mathematik 92: 156-71.
Hiensch, M., Larsson, P.-O., Nilsson, O., Levy, D., Kapoor, A., Franklin, F.,
Nielsen, J., Ringsberg, J.W., Josefson, B.L. (2005). Two-material rail
development: field test results regarding rolling contact fatigue and
squeal noise behaviour. Wear 258(7-8): 964-72.
Hiraoka, N. (2005). A study on mild-to-severe wear transition due to
inconformity of wear-induced shape. Wear 258(10): 1531-5.
248
Holman, J.P. (1997). Heat transfer. 8th ed. ed. New York, McGraw-Hill
Companies.
Hong, H.-S. (2002). The role of atmospheres and lubricants in the oxidational
wear of metals. Tribology International 35(11): 725-9.
Hooke, C.J., Liao, P., Rao, M., Kukureka, S.N., Chen, Y.K. (1996). The
friction and wear of polymers in non-conformal contacts. Wear 200(1-
2): 83-94.
Hou, K., Kalousek, J., Magel, E. (1997). Rheological model of solid layer in
rolling contact. Wear 211(1): 134-40.
Huq, M.Z., Celis, J.-P. (2002). Expressing wear rate in sliding contacts based
on dissipated energy. Wear 252(5-6): 375-83.
Huq, M.Z., Celis, J.P. (1997). Reproducibility of friction and wear results in
ball-on-disc unidirectional sliding tests of TiN-alumina pairings. Wear
212(2): 151-9.
Huq, M.Z., Celis, J.P. (1999). Fretting wear of multilayered (Ti,Al)N/TiN
coatings in air of different relative humidity. Wear 225-229(1): 53-64.
International Heavy Haul Association (2001). Guidlines to Best Practices for
Heavy Haul Railway Operations: Wheel and Rail Interface Issues.
International Heavy Haul Association.
Ishida, M., Abe, N. (1996). Experimental study on rolling contact fatigue from
the aspect of residual stress. Wear 191(1-2): 65.
Iwnicki, S. (2003). Simulation of wheel-rail contact forces. Fatigue &
Fracture of Engineering Materials and Structures 26(10): 887-900.
Iyer. [Personal Communication, Solidworks Instructions].
249
Jendel, T. (1999). Prediction of Wheel and Rail Wear - A Pilot Study. TRITA
- FKT Report 1999:03. Railway Technology, Department of Vehicle
Engineering, Royal Institute of Technology, Stockholm. 50
Jiang, J., Stott, F.H., Stack, M.M. (2004). A generic model for dry sliding wear
of metals at elevated temperatures. Wear 256(9-10): 973-85.
Jin, X., Wu, P., Wen, Z. (2002). Effects of structure elastic deformations of
wheelset and track on creep forces of wheel/rail in rolling contact.
Wear 253(1-2): 247-56.
Johnson, K.L. (1985). Contact mechanics. Cambridge [Cambridgeshire]; New
York, Cambridge University Press.
Judge, T. (2000a). Lubrication optimizes wheel-rail interface.
http://www.rtands.com/feb00/lubricational.html. Railway Track and
Structures.
Judge, T. (2000b). Rail lubrication gaining momentum. RT and S: Railway
Track and Structures 99(2): 23-4.
Kabo, E., Ekberg, A. (2005). Material defects in rolling contact fatigue of
railway wheels--the influence of defect size. Wear Contact Mechanics and
Wear of Rail/Wheel Systems 258(7-8): 1194-200.
Kalker, J.J. (1990). Three-dimensional elastic bodies in rolling contact.
Dordrecht, Netherlands, Kluwer Academic.
Kalousek, J. (2005). Wheel/rail damage and its relationship to track curvature.
Wear 258(7-8): 1330-5.
Kalousek, J., Magel, E., Strasser, J., Caldwell, W.N., Kanevsky, G., Blevins, B.
(1996). Tribological interrelationship of seasonal fluctuations of
250
freight car wheel wear, contact fatigue shelling and composition
brakeshoe consumption. Wear 191(1-2): 210.
Kato, H. (2003). Severe-mild wear transition by supply of oxide particles on
sliding surface. Wear 255(1-6): 426-9.
Kenderian, S., Boro Djordjevic, B., Green Jr., R.E. (2002). Laser based and air
coupled ultrasound as noncontact and remote techniques for testing
of railroad tracks. Materials Evaluation 60(1): 65-70.
Kik, W., Piotrowski, J. (1996). A fast approximate method to calculate normal
load at contact between wheel and rail and creep forces during rolling.
2nd Mini-conference on Contact Mechanics and Wear of Rail-Wheel Systems.
Kim, C.-S., Kim, J.-K., Kim, D.-S. (2002). Evaluation of fatigue strength and
life in rail steel under variable amplitude load. JSME International
Journal, Series A: Solid Mechanics and Material Engineering 45(4): 495-503.
Kim, J.-K., Kim, C.-S. (2002). Fatigue crack growth behavior of rail steel
under mode I and mixed mode loadings. Materials Science &
Engineering, A: Structural Materials: Properties, Microstructure and Processing
A338(1-2): 191-201.
Kondo, K., Yoroizaka, K., Sato, Y. (1996). Cause, increase, diagnosis,
countermeasures and elimination of Shinkansen shelling. Wear 191(1-
2): 199.
Kuhlmann-Wilsdorf, D. (1996). What role for contact spots and dislocations
in friction and wear? Wear 200(1-2): 8-29.
Kuhn, E. (1995). Description of the energy level of tribologically stressed
greases. Wear 188(1-2): 138.
251
Kuhn, E., Balan, C. (1997). Experimental procedure for the evaluation of the
friction energy of lubricating greases. Wear 209(1-2): 237-40.
Kumar, S., McDuff, P.J., Witte, A.C., McInerney, D.G. (1991). Development
of a Laboratory Test for Rail Lubricants. NLGI 58th Annual Meeting,
Phoenix, Arizona, USA.
Lee, K.M., Polycarpou, A.A. (2005). Wear of conventional pearlitic and
improved bainitic rail steels. Wear 259(1-6): 391.
Lewis, R., Dwyer-Joyce, R.S. (2004). Wear mechanisms and transitions in
railway wheel steels. Proceedings of the Institution of Mechanical Engineers,
Part J: Journal of Engineering Tribology 218(6): 467-78.
Lewis, R., Olofsson, U. (2004). Mapping rail wear regimes and transitions.
Wear 257(7-8): 721.
Lim, S.C. (1998). Recent developments in wear-mechanism maps. Tribology
International 31(1-3): 87-97.
Lim, S.C. (2002). The relevance of wear-mechanism maps to mild-oxidational
wear. Tribology International 35(11): 717-23.
Lim, S.C., Ashby, M.F. (1986). Wear-Mechanism Maps. CUED/C-
mat./TR.123. Cambridge University Engineering Department,
Cambridge. 88
Ling, F.F., Bryant, M.D., Doelling, K.L. (2002). On irreversible
thermodynamics for wear prediction. Wear 253(11-12): 1165-72.
Liu, Q.Y., Jin, X.S., Zhou, Z.R. (2005). An investigation of friction
characteristic of steels under rolling-sliding condition. Wear 259(1-6):
439.
252
Liu, Q.Y., Zhang, B., Zhou, Z.R. (2003). An experimental study of rail
corrugation. Wear 255(7-12): 1121-6.
Liu, Z.X., Gu, H.C. (2002). Fatigue failure of rail wheels and mechanical
behavior of wheel steels. Materials Performance 41(1): 58-61.
Lu, X., Cotter, J., Eadie, D.T. (2005). Laboratory study of the tribological
properties of friction modifier thin films for friction control at the
wheel/rail interface. 259(7-12): 1262.
Lundberg, J., Hoglund, E. (2000). A new method for determining the
mechanical stability of lubricating greases. Tribology International 33(3-
4): 217-23.
Magel, E. (1999). Optimizing wheel, rail profiles.
http://www.rtands.com/jul99/optimizing.html. Simmons-Boardman
Publishing Corp.
Magel, E., Kalousek, J., Caldwell, R. (2005). A numerical simulation of wheel
wear. Wear 258(7-8): 1245-54.
Magel, E., Roney, M., Kalousek, J., Sroba, P. (2003). The blending of theory
and practice in modern rail grinding. Fatigue & Fracture of Engineering
Materials and Structures 26(10): 921-9.
Malcolm, B., Raymond, M., Christoph, B., Richard, H., et al. (2005).
Predicting the Occurrence and Effects of Defects in Castings. JOM
57(5): 29.
Marich, S., Kerr, M., Fogarty, R. (2001a). Optimising Trackside Lubrication
for the Wheel/Rail System. RTA Conference.
253
Marich, S., Mackie, S., Fogarty, R. (2000). The Optimisation of Rail/Wheel
Lubrication Practice in the Hunter Valley. RTSA Technical Conference
CORE, Adelaide.
Marich, S., Mackie, S., Hill, I. (2001b). The Management of Wheel/Rail
Interaction in the High Axle Load Coal Lines of the Hunter Valley.
Heavy Haul Conference, Brisbane.
Marich, S., Mutton, P.J. (1989). An Investigation of Severe Wear Under
Rolling/Sliding Contact Conditions Existing in Heavy Haul Railways.
7th International Wheelset Conference, Vienna.
Markov, D. (1995). Laboratory tests for wear of rail and wheel steels. Wear
181-183(Part 2): 678-86.
Markov, D.P. (2001). Tribofatigue of wheel-rail steels. Trenie i Iznos 22(4): 400-
9.
Matsumoto, A., Sato, Y., Nakata, M., Tanimoto, M., Qi, K. (1996). Wheel-rail
contact mechanics at full scale on the test stand. Wear 191(1-2): 101-6.
Matsumoto, A., Sato, Y., Ohno, H., Tomeoka, M., Matsumoto, K., Ogino, T.,
Tanimoto, M., Oka, Y., Okano, M. (2005). Improvement of bogie
curving performance by using friction modifier to rail/wheel
interface: Verification by full-scale rolling stand test. Wear 258(7-8):
1201-8.
Matsumoto, A., Sato, Y., Ono, H., Wang, Y., Yamamoto, M., Tanimoto, M.,
Oka, Y. (2002). Creep force characteristics between rail and wheel on
scaled model. Wear 253(1-2): 199-203.
Matveevsky, R.M. (1965). Trans. ASTM 87: 754.
254
Meehan, P.A., Daniel, W.J.T., Campey, T. (2005). Prediction of the growth of
wear-type rail corrugation. Wear 258(7-8): 1001-13.
Melley, R., Wissner, P. (1997). The Real Costs of Lubrication. AGM-CIM
99th.
Milne-Thomson, L.M. (1950). Jacobian elliptic function tables: a guide to
practical computation with elliptic functions and integrals together
with tables of sn u, cn u, dn u, z(u). New York, Dover.
Mohrbacher, H., Celis, J.-P., Roos, J.R. (1995). Tribology International 28(5): 269.
Mulvihill, M.A., Witte, A.C., Kumar, S. (1994). A New Approach to
Wheel/Rail Lubrication. NLGI 61st Annual Meeting, Rancho Mirage,
California, USA, NLGI (National Lubricating Grease Institute).
Murry, C.R. (1985). Wheel Diameter Requirements for Canefield Railways.
1985 Conference of the Australian Society of Sugar Cane Technologists,
Bundaberg, Queensland, Australia, Watson Ferguson and Company.
Niccolini, E., Berthier, Y. (2005). Wheel-rail adhesion: laboratory study of
"natural" third body role on locomotives wheels and rails. Wear 258(7-
8): 1172-8.
Nilsson, R. (2002). Rail Wear Development - Measurements and Evaluation.
TRITA - FKT Report 2002:22. Railway Technology, Department of
Vehicle Engineering, Royal Institute of Technology, Stockholm. 52
Nolan, S.J. (~2000). The Use of a Controlled Stress Rheometer to Evaluate
the Rheological Properties of Grease. 0213. National Lubricating
Grease Institute.
255
O'Rourke, M.D., Johnston, G., Ruvidini, A., Hagaman, B. (1989). Australian
Road-Rail Lubrication Tests. The Fourth International Heavy Haul
Railway Conference, Brisbane, Queensland, Australia.
Oila, A., Bull, S.J. (2005). Assessment of the factors influencing micropitting
in rolling/sliding contacts. Wear 258(10): 1510-24.
Olofsson, U., Telliskivi, T. (2003). Wear, plastic deformation and friction of
two rail steels--a full-scale test and a laboratory study. Wear 254(1-2):
80-93.
Pascal, J.P. (1993). About multi-hertzian contact hypothesis and equivalent
conicity in the case of S1002 and UIC analytical wheel/rail profiles.
Vehicle System Dynamics 22: 57-8.
Plint, M.A. (1995). Proceeding of the XI NCIT.
Polach, O. (2005). Creep forces in simulations of traction vehicles running on
adhesion limit. Wear 258(7-8): 992-1000.
Polishuk, A.T. (1998). A Brief History or Lubricating Greases. Llewellyn
&McKane, Inc.
Quinn, T. (2002a). Special Issue on 'Wear in oxidative environments'. Tribology
International 35(11): 689.
Quinn, T.F.J. (1991). Physical analysis for tribology. Cambridge; New York,
Cambridge University Press.
Quinn, T.F.J. (2002b). The oxidational wear of low alloy steels. Tribology
International 35(11): 691-715.
Ravikiran, A., Lim, S.C. (1999). A better approach to wear-rate representation
in non-conformal contacts. Wear 225-229(2): 1309-14.
256
Reiff, R. (1986). Rail/Wheel Lubrication Studies at FAST. Journal of the
American Society of Lubrication Engineers 42(6): 340-9.
Riahi, A.R., Alpas, A.T. (2003). Wear map for grey cast iron. Wear 255(1-6):
401-9.
Ringsberg, J.W. (2005). Shear mode growth of short surface-breaking RCF
cracks. Wear
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 955-63.
RINGSBERG, J.W., BERGKVIST, A. (2003). On propagation of short
rolling contact fatigue cracks. Fatigue & Fracture of Engineering Materials
and Structures 26(10): 969-83.
Ringsberg, J.W., Franklin, F.J., Josefson, B.L., Kapoor, A., Nielsen, J.C.O.
(2005a). Fatigue evaluation of surface coated railway rails using
shakedown theory, finite element calculations, and lab and field trials.
International Journal of Fatigue 27(6): 680-94.
Ringsberg, J.W., Skyttebol, A., Josefson, B.L. (2005b). Investigation of the
rolling contact fatigue resistance of laser cladded twin-disc specimens:
FE simulation of laser cladding, grinding and a twin-disc test.
International Journal of Fatigue 27(6): 702-14.
Roussel, N., Le Roy, R., Coussot, P. (2004). Thixotropy modelling at local and
macroscopic scales. Journal of Non-Newtonian Fluid Mechanics 117(2-3):
85-95.
Sato, Y. (2005). Historical study on designing Japanese rail profiles. Wear
258(7-8): 1064-70.
Satoh, Y., Iwafuchi, K. (2005). Crystal orientation analysis of running surface
of rail damaged by rolling contact. Wear 258(7-8): 1126-34.
257
Sawley, K., Kristan, J. (2003). Development of bainitic rail steels with
potential resistance to rolling contact fatigue. Fatigue & Fracture of
Engineering Materials & Structures 26(10): 1019-29.
Sawley, K., Wu, H. (2005). The formation of hollow-worn wheels and their
effect on wheel/rail interaction. Wear 258(7-8): 1179-86.
Scherge, M., Shakhvorostov, D., Pohlmann, K. (2003). Fundamental wear
mechanism of metals. Wear 255(1-6): 395-400.
Scott, W., Mercer, T., Donelan, J. (1998). Laboratory Evaluation of
Rail/Wheel Lubricants/Friction Modifiers. Austrib '98 - Tribology at
Work, Brisbane, Queensland Australia, The Institution of Engineers
Australia.
Shen, Z.Y., Hedrick, J.K., Elkins, J.A. (1983). A comparison of alternative
creep force models for rail vehicle dynamic analysis. 16th IA VSD
Symp, Cambridge MA.
Shevtsov, I.Y., Markine, V.L., Esveld, C. (2005). Optimal design of wheel
profile for railway vehicles. Wear 258(7-8): 1022-30.
Shur, E.A., Bychkova, N.Y., Trushevsky, S.M. (2005). Physical metallurgy
aspects of rolling contact fatigue of rail steels. Wear 258(7-8): 1165-71.
Simanek, D. (1996). Error Analysis (Non-Calculus).
http://www.lhup.edu/~dsimanek/errors.htm. Lock Haven University.
Sladkowski, A., Sitarz, M. (2005). Analysis of wheel-rail interaction using FE
software. Wear 258(7-8): 1217-23.
Smith, R., Mulliah, D., Kenny, S.D., McGee, E., Richter, A., Gruner, M.
(2005). Stick slip and wear on metal surfaces. Wear 259(1-6): 459.
258
Stack, M.M., Chi, K. (2003). Mapping sliding wear of steels in aqueous
conditions. Wear 255(1-6): 456-65.
Tapp, C. (2005). Mechanical properties of rail steel after cyclic deformation.
Fortschritt-Berichte VDI, Reihe 5: Grund- und Werkstoffe/Kunststoffe 719: i-
vii,1-116.
Thelen, G., Lovette, M. (1996). A parametric study of the lubrication
transport mechanism at the rail-wheel interface. Wear 191(1-2): 113-
20.
Thomas E. Karis, R.-N.K.M.S.J. (2003). Harmonic analysis in grease rheology.
Journal of Applied Polymer Science 90(2): 334-43.
Timoshenko, S. (1951). Theory of elasticity. 2d ed. New York, McGraw-Hill.
Tomeoka, M., Kabe, N., Tanimoto, M., Miyauchi, E., Nakata, M. Friction
control between wheel and rail by means of on-board lubrication.
Wear In Press, Uncorrected Proof.
Tyagi, R., Nath, S.K., Ray, S. (2003). Modelling of dry sliding oxidation-
modified wear in two phase materials. Wear 255(1-6): 327-32.
Tyfour, W.R., Beynon, J.H., Kapoor, A. (1995). The steady state wear
behaviour of pearlitic rail steel under dry rolling-sliding contact
conditions. Wear 180(1-2): 79-89.
Ueda, M., Matsushita, K., Onodera, N., Yamamoto, T. (2005a). High carbon
steel rails with excellent resistance to surface scratching and internal
fatigue damaging. Application: JP
JP, (Nippon Steel Corp., Japan). 19 pp.
259
Ueda, M., Matsushita, K., Onodera, N., Yamamoto, T. (2005b). Pearlitic rails
with with resistance to surface scratching and internal fatigue
damaging and method for their manufacture. Application: JP
JP, (Nippon Steel Corp., Japan). 20 pp.
Ueda, S., Uchino, K. (2003). Pearlitic steel rails with high resistance to wear
and inner fatigue damage. Application: JP
JP, (Nippon Steel Corp., Japan). 11 pp.
Van, K.D., Maitournam, M.H. (2002). On some recent trends in modelling of
contact fatigue and wear in rail. Wear 253(1-2): 219-27.
Viafara, C.C., Castro, M.I., Velez, J.M., Toro, A. (2005). Unlubricated sliding
wear of pearlitic and bainitic steels. Wear 259(1-6): 405.
Waara, P. (2001). Lubricant influence on flange wear in sharp railroad curves.
Industrial Lubrication and Tribology 52(4): 161-8.
Waara, P., Hannu, J., Norrby, T., Byheden, A. (2001). Additive influence on
wear and friction performance of environmentally adapted lubricants.
Tribology International 34(8): 547-56.
Walther, F., Eifler, D. (2003). Evaluation of the fatigue behavior of wheel
steels on the base of strain, temperature and resistance measurements.
Zeitschrift fuer Metallkunde 94(5): 505-10.
Walther, F., Eifler, D. (2004). Fatigue behaviour of railway wheels at different
temperatures: Interrelation of the microstructure and the fatigue
behaviour of railway wheels at ambient and elevated temperatures.
Materialpruefung 46(4): 158-62.
260
Wang, F., Zhou, D., Shi, H.J., Mesmacque, G. (1999). Numerical analysis of
rail rolling contact fatigue. Fatigue '99, Proceedings of the International
Fatigue Congress, 7th, Beijing, China, June 8-12, 1999 4: 2591-6.
Wang, L., Pyzalla, A., Stadlbauer, W., Werner, E.A. (2003). Microstructure
features on rolling surfaces of railway rails subjected to heavy loading.
Materials Science and Engineering A 359(1-2): 31-43.
Wellman, R.G., Nicholls, J.R. (2004). High temperature erosion-oxidation
mechanisms, maps and models. Wear 256(9-10): 907-17.
Witte, A.C., Kumar, S. (~1986). Design and Laboratory Testing of Rail
Lubricants.
Wu, T.X., Thompson, D.J. (2005). An investigation into rail corrugation due
to micro-slip under multiple wheel/rail interactions. Wear 258(7-8):
1115-25.
Yang, S.H., Kong, H., Yoon, E.-S., Kim, D.E. (2003). A wear map of bearing
steel lubricated by silver films. Wear 255(7-12): 883-92.
Yonggang, M., Jie, Z. (1998). A rheological model for lithium lubricating
grease. Tribology International 31(10): 619-25.
Yousif, A.E. (1983). The tribological characteristics of lubricating greases in
heavily loaded contacts. 85(3): 273.
Yuan, C.Q., Peng, Z., Zhou, X.C., Yan, X.P. (2005). The surface roughness
evolutions of wear particles and wear components under lubricated
rolling wear condition. Wear 259(1-6): 512.
Zakharov, S.M., Goryacheva, I.G. (2005). Rolling contact fatigue defects in
freight car wheels. Wear
261
Contact Mechanics and Wear of Rail/Wheel Systems 258(7-8): 1142-7.
Zakharov, S.M., Zharov, I.A. (2005). Criteria of bogie performance and
wheel/rail wear prediction based on wayside measurements. Wear
258(7-8): 1135-41.
Zerbst, U., Madler, K., Hintze, H. (2005). Fracture mechanics in railway
applications--an overview. Engineering Fracture Mechanics 72(2): 163.
262
APPENDIX A
A. Seizure Wear
Lim and Ashby (1986) defines seizure wear as the catastrophic shear of
junctions formed at the interface. This wear is also referred to as adhesive
wear. Bowden and Tabor (Bowden and Tabor 2001) investigated the metallic
junctions which form at interfaces and later Tabor investigated the effects of
shear on these metallic junctions. Bowden and Tabor's (2001) work is the
basis for the seizure wear model.
The model is constructed by defining the asperity pressure
r
F HA
= (1.2)
Where
F = Normal force on sliding interface (N)
rA = Real area of contact (m2) (small compared to nominal contact area)
H = Hardness of sliding surface (N/m2)
This then is developed to include the shear stress ( / rs F Aμ= ) due to
friction.
2
2 2t
r
F s HA
α⎛ ⎞
+ =⎜ ⎟⎝ ⎠
(1.3)
tα is an experimentally determined coefficient with a typical value of 12.
Seizure occurs, according to this model, when the real area of contact ( rA )
263
equals the nominal area of contact ( nA ). Therefore substituting the shear
force and contact area, then rearranging into the dimensionless form gives
equation
( )1
2 21rt
F HA
=+α μ
(1.4)
( ) 12 2
1
1 ot
HFH
=+α μ
(1.5)
In the case of unlubricated sliding for steel the coefficient of friction can be
given by Equation (1.6). This relationship has been developed from the
literature by Lim and Ashby (1986).
100.88 0.13log ( )vμ = − % (1.6)
Lim and Ashby (1986) proposes that the ratio of hardness can be set to unity,
simplifying the model. This is explained by the two mechanisms, temperature
related hardness and velocity related strain rate. Hardness decreases with
increasing temperature but the increasing temperature arises from increasing
surface velocity. The increase in surface velocity increases the strain rate
changing the material response which increases the measured hardness.
B. Melt Wear
High sliding speeds and pressure can develop high surface temperatures
which can exceed the melting point of the materials. The melting material
then behaves as a lubricant in the hydrodynamic regime. The viscous energy
developed in the liquid material is then dissipated to the surfaces increasing
the temperature of the surrounding material and subsequently increasing the
volume of molten material. Melt wear can be identified by the molten material
leaving the contact area.
264
Lim and Ashby(1986) presented the following equations to predict melt wear.
Equation (1.7) describes frictional heat energy.
mm
n
Vq K T L
Aα = − ∇ + (1.7)
Where
α = heat distribution coefficient
q = power input per unit area
mK = thermal conductivity of metal
T∇ = temperature gradient
L = latent heat of fusion per unit volume
mV = volumetric rate of molten material production
Frictional heat energy, qα , is equal to the sum of the heat conducted away
and the latent heat absorbed by the molten material. Next we define the
frictional energy and the temperature gradient and include them in Equation
(1.7) to give Equation (1.8).
( )m m o m
n b n
K T T VFv LA l A
αμ −= + (1.8)
Further, the molten material is assumed to be totally lost and gives the normalised wear rate of the following equation.
m
n
VW
vA= (1.9)
Rearranging the previous equations give Equation 2.9 for melt wear in non-dimensional terms.
265
*
*
1( ) [ 1]( )
m o o
m o
T T H TW FvL v T TT
αμ−= −
−% (1.10)
This equation has constants which are approximated with developed
equations. Similar to the previous model these equations or constants need to
be modified to suit rail/wheel steels and lubricated sliding conditions.
Equations (1.7) to (1.10) need to be modified prior to their application to
rail/wheel steels and lubricated sliding conditions by varying the values of the
constants within the equations.
C. Oxidational wear
Wear particles from sliding systems can take the form of molten metal, metal
particles and metal oxide particles. Oxide particles form when the critical flash
temperature corresponding to the oxidation activation energy is reached in an
oxidative environment. Lim and Ashby (1986) found that flash temperature is
predominantly affected by sliding speed therefore indicating that oxidation
rate is a function of velocity. Load was not found to have a significant effect
on flash temperature (Lim and Ashby 1986).
The process of oxidation wear is divided into two categories according to the
severity of oxidation. Mild oxidation, which refers to sliding speeds below 1
m/s and surfaces that have thin patchy oxidised films and severe oxidation,
which occurs at higher sliding speeds and is signified by continuous and
thicker oxidised films.
It is important to remember that the names of the wear regimes do not refer
to their wear rates but rather to the extent of oxidation. Wear rates for severe
oxidation are commonly lower than those for mild oxidation.
D. Mild-oxidational wear
Quinn (1991) proposes that flash heating at the contacting asperities causes
oxidation at the surface of these asperities. Once the oxide film has reached a
266
critical thickness this becomes detached as a wear particle and the process of
oxide formation begins again.
The model which Quinn proposes (developed and iterated over ~30years) is
based on a parabolic kinetic equation. Iron and steel tested experimentally fits
this parabolic equation but it is not suitable for all material types (Lim and
Ashby 1986).
2pm k tΔ = (1.11)
mΔ = Mass of oxygen used per unit area
pk = Parabolic rate constant
exp[ ]op o
Qk A
RT= − (1.12)
oA = Arrhenius constant
oQ = Activation energy
R = Gas constant
T = Absolute temperature
The model assumes that at a critical thickness the oxidised material will
become a wear particle. This gives the next equation in which the oxide
proportions are used to calculate the oxides. In a sliding, steel on steel contact
different oxides can form. Lim proposes that the average composition is
3 4Fe O which gives the proportion of 1 mol of Fe to 2/3 of 2O . Oxides will
add mass to the surface with the following equation.
267
2
2 ( / )3 Fe Fe O Fem V M MρΔ = Δ (1.13)
FeVΔ = volume of iron
Feρ = density of iron
2OM = molecular weight of oxygen
FeM = molecular weight of iron
Substituting the thickness of oxides, Z is equal to FeVΔ , into equation (1.14).
2
2 2
32
p
Fe
O Fe
Z C k t
MCM ρ
=
⎛ ⎞= ⎜ ⎟⎜ ⎟⎝ ⎠
(1.14)
Using equation (1.14) the time for a critical thickness to form is equated.
2
2 exp[ / ]c
co o f
tC A Q RT
Z=−
(1.15)
In this model, wear is taken to be the removal of this oxide volume. Wear is
the volume, the product of rA and cZ , lost in a specified time. Therefore
wear rate is the ratio of rA and cZ to the distance slid, cvt giving the equation
(1.16).
2
exp[ ]r o o
c f
A C A QW
vZ RT= − (1.16)
The equation proposed by Lim and Ashby (1986) differs from the equation
presented by Quinn (1991) in that the former removes a fraction which
268
relates to Quinn’s use of the Archard's Law and Hertzian contact in the
model. The value of this term approaches unity and is therefore ignored.
Finally the mathematical model is presented in the normalised variables in
equation (1.17).
2
expo o o
c f
c A r Q FWz a RT v
⎡ ⎤⎛ ⎞= −⎢ ⎥⎜ ⎟
⎢ ⎥⎝ ⎠ ⎣ ⎦
β (1.17)
In this model there are two parameters, the Arrhenius activation constant and
the activation energy for oxidation, which need to be calibrated to the system.
Static measurements of these parameters do not provide a good correlation
with experimental wear data, because the mechanical loading changes the
system and therefore changes the constants. Lim proposes to keep the
activation energy constant, the same as that measured in static laboratory
testing. Thus the Arrhenius activation constant refers to how the oxides grew
and in this case the growth is promoted by mechanical deformation.
Martensite forms under these conditions which changes the material
properties at the interface. Measured wear data shows a reduction in wear rate
following the formation of martensite. The reduction is explained by the
increase in hardness of this phase. Prediction of this phase transition is not
modelled by these equations, but can be, by changing the hardness values
chosen. This model tries to encompass a transition portion of the wear map
and as such, has a large variability in parameters. There is still more work to
be done to develop a more robust model.
E. Severe-oxidational wear
Severe-oxidational wear is encountered in a system of high sliding speed
where extensive oxides are formed. The oxides form a protective layer where
they plastically deform, melt and solidify. Lim devised a new model for this
type of wear. The assumptions made are:
269
Contacts are hot enough to melt.
The molten oxides spread heat in a uniform manner.
The material which is not oxidised maintains the bulk temperature.
Molten oxides will be lost to some degree.
The heat input to the surface is dissipated in two ways, the first by conduction
and the second by melting material.
( )
( )ox
ox m b rox m
f n
K T T AL V q
l Aα −
= − (1.18)
oxL = latent heat of oxide
mV = Rate of molten material production
fl = Equivalent heat flow length
oxK = Thermal conductivity of oxide
oxmT = Oxide melting point
Using the relationship of input energy equals the frictional energy of the
interface and defining the normalised wear rate as /m mW f V v=% gives the
model equation (1.19).
1
2 12( ) ( ) [ ( ) 1]
( )
oxox m b o
m oxox ox m b
K T T aHFN FW f vL a v NK T T
αμ−= −
−% (1.19)
mf = Fraction of material lost
270
In this model the only adjustable parameter is the fraction of material lost
which Lim proposes is ~0.01. In the course of wear measurements within this
regime this parameter has been suitably adjusted.
F. Plasticity dominated wear
Plasticity dominated wear is encountered at low sliding speeds and as the
name suggests plastic deformation occurs at the surface. Shear forces can
deform, cut and or plough asperities from the surface. There is also
delamination in this wear mode where sub-surface cracks grow from the
cyclic loading until a wear particle is formed and removed.
Archard’s law is presented here as the overriding equation. This equation has
one adjustable parameter Ak which experimentally has been seen to change
over a number of orders of magnitude.
AW k F= (1.20)
*
2 o vA
A
fk
fγ
= (1.21)
The Archard wear constant, Ak is the relationship of the volume fraction of
inclusions in the materials vf , the rate of plastic strain, oγ , and the area
fraction of voids, *Af . These parameters are all variable and require calibration
against suitable wear data. This model is widely used but it lacks the depth to
accurately model a variety of systems without modification of the constant.
Despite this disadvantage until a more suitable model arises this one will be
used.
271
APPENDIX B
A. Validation of Software for Rectangular Contact
The rectangular contact method of the ESDU, used as the basis for the
computer method to calculate the values for a rectangular contact, is
compared against published results from Hamrock (2003) and Boresi and
Schmidt (Hamrock 1994). This process is carried out to show the variation in
methodologies and the applicability of the method selected for this
investigation.
PARAMETER VALUE UNITS Load, P 1000 N/m
Body 1 composition Silicon nitride steel Young’s modulus 314 GPa
Poisson’s ratio 0.26 Body 2 composition Stainless steel
Young’s modulus 193 GPa Poisson’s ratio 0.3
Body 1 – Radius 1 0.02 M Body 2 – Radius 1 0.1 M
Table 32 – Example values for needle roller in bearing race (2003).
PARAMETER HAMROCK RESULT
CURRENT METHOD
DIFFERENCE %
Major semi-axis (µm) 15.6 15.6 0 Normal approach (µm)
0.0405 0.0404 0.25
Maximum normal pressure (MPa)
40.68 40.71 0.07
Table 33 – Comparison of results between calculation methods.
The example of twin disk fatigue testing machine is now presented. The
results of the rectangular contact method presented by the ESDU are
compared to the results obtained from Boresi and Schmidt (2003). Two
272
testing machines are considered for this example, one without friction and
one with friction (μ=0.1).
PARAMETER VALUE UNITS Load, P 24100/0.02 N/m
Body composition Steel Young’s modulus 200 GPa
Poisson’s ratio 0.29 Body 1 – Radius 1 0.04 M Body 2 – Radius 1 0.04 M
Table 34 – Example values for twin-disk fatigue testing device with identical steel samples (ESDU 1995).
PARAMETER BORESI AND SCHMIDT RESULT
CURRENT METHOD
DIFFERENCE %
Major semi-axis (µm) 530.1 530.1 0 Normal approach (µm)
Not given 31.7 N.A.
Maximum normal pressure (MPa)
1447 1447 0
Maximum tensile stress with friction (MPa)
322 321.2 0.27
Maximum compressive stress with friction (MPa)
1635 (1445) 1616.5(1446.7) 1.13(0.11)
Maximum shear stress with friction (MPa)
449 (433) 442(434.5) 1.56(0.35)
Maximum octahedral shear stress with friction (MPa)
369 (361) 389(383) 5.14(5.74)
Table 35 – Comparison of results between calculation methods of contact stresses for twin disk fatigue testing machine (Values in parentheses calculated without friction/traction force).
273
Both methods present similar results and the errors between the methods do
not exceed 5.74%, showing that the two methods produce comparable
results.
B. Validation of software for Elliptical Contact
The ESDU method (ESDU 1995) gives examples to illustrate the calculation
procedure for elliptical contacts. These examples will be used to verify the
Contact Software against the graphical method presented by the ESDU. The
first example is of two crossed cylinders as shown in Figure 126.
Figure 126 – Two crossed cylinders calculation example(ESDU 1995).
The input parameters are given in Table 36.
PARAMETER VALUE UNITS Load, P 1250 N
Body 1 composition Mild steel Young’s modulus 207 GPa
Poisson’s ratio 0.3 Body 2 composition Brass
Young’s modulus 101 GPa Poisson’s ratio 0.35
Body 1 – Radius 1 ∞ M Body 1 – Radius 2 0.025 M Body 2 – Radius 1 ∞ M Body 2 – Radius 2 0.075 M
Angle between axes 40 Degree Table 36 – Example values for crossed cylinders of differing materials (2003).
274
The results from ESDU and from the author’s calculation method for the
example in Table 36 are presented in Table 37.
PARAMETER ESDU RESULT
CURRENT METHOD
DIFFERENCE %
Major semi-axis (mm) 1.896 1.90432 0.44 Minor semi-axis (mm) 0.404 0.4028415 0.29 Normal approach (mm)
0.01195 0.01214 1.59
Maximum normal pressure (MPa)
780 778 0.25
Table 37 – Comparison of results between calculation methods.
Further comparison between the ESDU and the author’s results are presented
in Table 38. The contact angle between the two cylinders presented in Figure
126 has been altered from 40 to 90 degrees for this analysis.
PARAMETER ESDU RESULT
CURRENT METHOD
DIFFERENCE %
Major semi-axis (mm) 1.142 1.14697 0.43 Minor semi-axis (mm) 0.551 0.55356 0.46 Normal approach (mm)
0.01494 0.01490 0.27
Maximum normal pressure (MPa)
940 940 0
Table 38 – Comparison of results between calculation methods of ESDU and author’s for principal axis angle of 90 degrees.
There is a limitation to the resolution of the interpretation of the graphs used
in the ESDU method. The error involved in reading values from the graphs
provided within the ESDU method could potentially become quite high as
there are often multiple graphs associated with any one calculation. It should
be noted that the solutions presented here from the ESDU graphical method
were included within the ESDU documentation and were not calculated by
the Author. In absolute terms the error between the ESDU graphical method
and the Contact Software is less than one percent.
275
Further validation of the Contact Software for an elliptical contact was carried
out via a comparison results presented by Boresi and Schmidt (2003). This
example is of two steel toroids in contact with an angle between the principal
axes.
PARAMETER VALUE UNITS Load, P 4500 N
Body composition Mild steel Young’s modulus 200 GPa
Poisson’s ratio 0.29 Body 1 – Radius 1 0.06 M Body 1 – Radius 2 0.13 M Body 2 – Radius 1 0.08 M Body 2 – Radius 2 0.2 M
Angle between axes 60 Degree Table 39 – Elliptical contact example for two toroids in contact (2003).
PARAMETER BORESI AND SCHMIDT RESULT
SOFTWARE METHOD
DIFFERENCE %
Major semi-axis (µm)
Not given 1309 NA
Minor semi-axis (µm)
965 1000 3.6
Normal approach (µm)
29 27 6.9
Maximum compressive stress (MPa)
1586 1642 3.5
Maximum shear stress (MPa)
529 525 0.8
Maximum octahedral shear stress (MPa)
485 482 0.6
Depth of maximum shear stresses (mm)
0.51 0.55 7.8
Table 40 - Comparison of results between calculation methods of Boresi and Schmidt (1985) and author’s.
276
The results in Table 40 show a larger difference in results between calculation
methods than in the previous examples presented in Table 37 and Table 8.
The larger than expected errors between these two methods is a consequence
of the fact that Boresi and Schmidt (2003) present their results in terms of
stresses of interest rather than as a stress tensor. Approximation coefficients
are used by Boresi and Schmidt (2003) to transform the single maximum
stress value into the stress parameters. Calculation of the stress parameters
from the principal stresses obtained from the contact software was then
required to compare results between the Contact Software and the results
presented by Boresi and Schmidt (2003).
277
APPENDIX C – TECHNICAL DRAWINGS
278
279